| 2017-04-25 16:14:38 | FOLLOWING ARE THE COMMENTS ON THE "FIRE LINE | | | IMPROVEMENTS PLAN" - (SHEET 2 OF 3): | | | | | | 1. ALL PROPOSED FIRE DEPARTMENT CONNECTIONS (FDC) SHALL | | | BE WITHIN 150 FEET OF A FIRE HYDRANT AND SHALL BE | | | WITHIN AN EASEMENT WITHIN THE PROPERTY. PLAN DOES SHOW | | | AN EXISTING FIRE HYDRANT ACROSS THE STREET (N. DIXIE | | | HWY.) AND AT A GREATER DISTANCE. PLEASE CONTACT THE | | | OFFICE OF THE CITY'S FIRE MARSHALL TO OBTAIN APPROVAL | | | OF YOUR PLAN (SIGNED AND STAMPED BY FIRE MARSHALL) AND | | | THEN SUBMIT TWO COPIES OF THESE PLANS TO THE | | | ENGINEERING DEPARTMENT. IN THE EVENT A NEW FIRE HYDRANT | | | IS PROPOSED TO BE INSTALLED NEAR THE FDC, SHOW THAT IN | | | THE REVISED PLANS DURING RESUBMITTAL; | | | | | | 2. EXISTING 4-INCH DIP WATER CONNECTION TO THE SITE | | | SHALL NEED TO BE TESTED AND RETRAINED BACK TO THE | | | VALVE; | | | | | | 3. PARKING LOT REPAVING SHALL BE PERMITTED SEPARATELY | | | THROUGH CITY'S DEVELOPMENT SERVICES DEPARTMENT. PLEASE | | | CONTACT DEVELOPMENT SERVICES DEPARTMENT AT: | | | 561-805-6700; | | | |
| |