Plan Review Notes
Plan Review Notes For Project E17020056
Project Number E17020056
Review Stop ENG-A
Sequence Number 1
Notes
Date Text
2017-04-25 16:14:38FOLLOWING ARE THE COMMENTS ON THE "FIRE LINE
 IMPROVEMENTS PLAN" - (SHEET 2 OF 3):
  
 1. ALL PROPOSED FIRE DEPARTMENT CONNECTIONS (FDC) SHALL
 BE WITHIN 150 FEET OF A FIRE HYDRANT AND SHALL BE
 WITHIN AN EASEMENT WITHIN THE PROPERTY. PLAN DOES SHOW
 AN EXISTING FIRE HYDRANT ACROSS THE STREET (N. DIXIE
 HWY.) AND AT A GREATER DISTANCE. PLEASE CONTACT THE
 OFFICE OF THE CITY'S FIRE MARSHALL TO OBTAIN APPROVAL
 OF YOUR PLAN (SIGNED AND STAMPED BY FIRE MARSHALL) AND
 THEN SUBMIT TWO COPIES OF THESE PLANS TO THE
 ENGINEERING DEPARTMENT. IN THE EVENT A NEW FIRE HYDRANT
 IS PROPOSED TO BE INSTALLED NEAR THE FDC, SHOW THAT IN
 THE REVISED PLANS DURING RESUBMITTAL;
  
 2. EXISTING 4-INCH DIP WATER CONNECTION TO THE SITE
 SHALL NEED TO BE TESTED AND RETRAINED BACK TO THE
 VALVE;
  
 3. PARKING LOT REPAVING SHALL BE PERMITTED SEPARATELY
 THROUGH CITY'S DEVELOPMENT SERVICES DEPARTMENT. PLEASE
 CONTACT DEVELOPMENT SERVICES DEPARTMENT AT:
 561-805-6700;
  