2017-01-26 14:57:16PROJECT NAME: CITY OF WEST PALM BEACH FIRE STATION #4 -
 1718 PARKER AVENUE (RELATED PERMIT #16051078)
  
 DATE: DECEMBER 30, 2016
  
 AFTER A REVIEWING THE PLANS DATED 9/1/2016 FOLLOWING
 ARE OUR COMMENTS:
  
 1. REVISE THE ?AUTO-CALC CERTIFIED COST ESTIMATE? TO
 SHOW IN THE SPREADSHEET THE ITEMS SEPARATED FOR ONSITE
 AND FOR WITHIN THE CITY?S RIGHT-OF-WAY. THIS WILL
 DERIVE THE ACCURATE ?SITE DEVELOPMENT REVIEW FEES? AND
 ?CONSTRUCTION ADMIN. FEES?;
 2. PROPOSED DUMPSTER SHOWN TO BE ON AN EXISTING WATER
 MAIN. PLEASE MOVE IT OUT OF THE WAY SO THAT FOUNDATION
 WORK FOR THE DUMPSTER PAD AND ENCLOSURE WALLS DOES NOT
 DAMAGE IT DURING CONSTRUCTION;
 3. SHOW GATE VALVE AT THE PROPERTY LINE BEFORE THE
 WATER MATER FOR THE 6? WATER LINE. ALSO SHOW AN
 ?ISOLATION VALVE? BEFORE THE ?DOUBLE DETECTOR CHECK
 VALVE/ASSEMBLY?;
 4. REVISE CLEANOUT LOCATIONS FOR THE SANITARY SERVICES;
 5. INCLUDE LATEST VERSION OF THE CITY?S STANDARD
 DETAILS IN THE PLANS;
  
 MOSTAQUE KHAN, P.E.
 LAND DEVELOPMENT ENGINEER