Plan Review Notes
Plan Review Notes For Project E16100001
Project Number E16100001
Review Stop ENG-A
Sequence Number 4
Notes
Date Text
2018-01-24 13:23:03CANOPY HOTEL, E16100001
 ADDRESS: 704-718 S. DIXIE HWY
 STATUS: FAILED
  
 COMMENTS (PLEASE RESPOND TO COMMENTS IN WRITING):
 1. SHOW PROFILE FOR PROPOSED WATER MAIN SHOULD INCLUDE
 VERTICAL CLEARANCES BETWEEN WATER AND OTHER UTILITIES;
  
 2. REPLACE EXISTING 8-INCH DIAMETER (NOT 10-INCH
 DIAMETER AS SHOWN IN THE PLANS) SANITARY SEWER MAIN
 FROM MANHOLE TO MANHOLE TO A 12-INCH DIAMETER SDR-26
 SANITARY SEWER. THE CURRENT CONDITION OF THE EXISTING
 PIPE IS AT HALF CAPACITY AND MAY NOT WITHSTAND THE
 PROPOSED DEMAND;
  
 3. CCTV/DVD MUST BE PROVIDED BY DEVELOPER OF VIDEO OF
 SEWER MAIN TRINITY PL. TO BETTER ASSESS THE CONDITION
 OF THE EXISTING SYSTEM. WE SHOW INCONSISTENCY ON THE
 DIAMETER SIZE AND MATERIALS TYPE IN OUR AS-BUILTS AND
 FEEL THE DEVELOPER SHOULD VERIFY. OUR RECORDS INDICATE
 ASSET NUMBERS FOR THESE SEWER ELEMENTS DESCRIBED FROM
 WEST TO EAST: ASSET# SSMH6551, ASSET# SEWER LINE 07703,
 ASSET# SSMH0374. CHARLES PHOENIX, OF CITY O&M GROUP CAN
 BE CONTACTED TO COORDINATE THE ACCESS TO SANITARY
 SYSTEM. PLEASE ALLOW 48 HOUR NOTICE TO
 [email protected]. SUBMIT CD TO ENGINEERING SERVICES
 DEPARTMENT;
  
 4. NEED TO SHOW THE VERTICAL CLEARANCE AT ALL UTILITY
 CROSSINGS THERE ARE MISSING CONFLICT INFORMATION WHERE
 SERVICES ENTER THE SITE;
  
 5. WATER VALVE BOXES SHOULD NOT LAND WITHIN THE CURB
 RAMPS;
  
 6. WILL THE PROXIMITY AND HORIZONTAL DISTANCE BETWEEN
 THE PROPOSED AND EXISTING WATER MAIN BE A PROBLEM
 DURING CONSTRUCTION? CITY OF WPB PUBLIC UTILITIES
 DEPARTMENT WOULD LIKE A BRIEF SUMMARY RESPONSE OF MEANS
 AND METHOD FOR THIS INSTALLATION;
  
 7. PLEASE ADD STANDARD DETAIL WS-6. CITY'S STANDARD
 DETAILS (IN PDF FILE FORMAT) CAN BE DOWNLOADED FROM THE
 FOLLOWING SITE: HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-
 PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 8. DEDICATED FIRELINE SERVING 700 S DIXIE DOES NOT
 SHOWN ON PLANS. PLEASE SHOW CONNECTION TO THE PROPOSED
 WM;
  
 SOFIA QUINONES-BENEJAM, EI
 PROJECT ENGINEER
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 P: 561.494.1040 EXT: 1108
 C: 561.459.6518
 F: 561.494.1116
 EMAIL: [email protected]
  