2016-09-14 16:01:38FOLLOWING ARE THE COMMENTS ON WATER AND SEWER PLAN
 (SHEET C-8):
 1. PROPOSED SANITARY MANHOLE MH-1 IS PLACED ON THE
 PROPERTY LINE. MOVE IT ON SITE I.E. WITHIN THE PROPERTY
 LINE (REFER TO #1 COMMENT ON THE ATTACHED MARKED-UP
 SHEET).
 2. PLAN SHOWS TWO (2) 90? BENDS THOSE ARE PROPOSED FOR
 A NEW 8IN. WATER MAIN TO CONNECT TO AN EXISTING 8IN. WM
 STUB TO AVOID A STORM DRAIN MANHOLE (REFER TO THE AREA
 NEAR THE 1-1/2IN. WATER METER WITH 1-1/2IN. BACKFLOW
 PREVENTER ASSEMBLY, REFER TO #2 ON THE ATTACHED
 MARKED-UP PLAN).). THE CITY WILL NOT ACCEPT FITTINGS
 FOR WATER MAIN WHILE INSIDE THE RIGHT-OF-WAY (UP THE
 GROVE LANE). USE 2IN. POLY OR COPPER FROM THE 8IN. STUB
 OUT (REFER TO CITY?S STANDARD DETAIL WS-1, ISSUED IN
 2016). ALSO SHOW VERTICAL CONFLICT ELEVATIONS WITH THE
 STORM DRAIN WHILE CROSSING.
 3. UTILITY EASEMENT WILL BE REQUIRED FOR THE PROPOSED
 WATER METER ONSITE (REFER TO THE SKETCH LABELED #10 ON
 THE ATTACHED MARKED-UP PLAN).
 4. REMOVE THE 8IN. PVC SANITARY PIPE STUB/PLUG IT FROM
 INSIDE THE EXISTING MANHOLE LOCATED ON UP THE GROVE
 LANE (REFER TO #3 ON THE ATTACHED MARKED-UP PLAN).
 PLACE A NOTE ON THE PLAN: ?REHABILITATE MANHOLE PER
 CITY STANDARD?.
 5. 2IN. AND 4IN. PVC CONDUITS ARE SHOWN CROSSING THE
 2-IN. AND 6IN. WATERLINES. FROM THE CIVIL PLANS IT IS
 NOT CLEAR WHERE ARE THEY GOING. PLEASE SHOW CONFLICT
 WITH THE EXISTING 15IN. STORM DRAINS (ON UP THE GROVE
 LANE) IF THEY ARE CROSSING OVER INSIDE THE STREET
 RIGHT-OF-WAY (REFER TO #4 ON THE ATTACHED MARKED-UP
 PLAN). A PRIVATE UTILITY EASEMENT WILL BE REQUIRED IF
 CONDUITS GO OUT ON THE CITY RIGHT-OF-WAY.
 6. EXISTING DRIVEWAYS APRON/ENTRANCE TO THE EXISTING
 ROCK AREA SHALL BE REMOVED (REFER TO #5 ON THE ATTACHED
 MARKED-UP PLAN). PUT A LABEL ON THE PLAN NOTING:
 ?DRIVEWAY APPROACH SHALL BE REMOVED AND RESTORE WITH
 GRASS?
 7. LABEL SIZE AND MATERIAL FOR THE EXISTING WATERLINE
 THAT IS CONNECTING THE EXISTING 6IN. DDCV AND THE
 1-1/2IN. IRRIGATION METER TO THE EXISTING 10IN. DIP WM
 TO THE SOUTH (REFER TO #6 ON THE ATTACHED MARKED-UP
 PLAN).
 8. PLEASE NOTE THAT: AS OF DECEMBER 20, 2015 THE CITY
 OF WEST PALM BEACH CROSS-CONNECTION CONTROL MANUAL HAS
 BEEN REVISED, MAKING KNOWN THAT IN.ALL BACKFLOW DEVICES
 MUST BE LEAD FREE.IN. FOR MORE INFORMATION REFER TO THE
 LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
 9. NEAREST FIRE DEPARTMENT CONNECTION (FDC) DISTANCE TO
 FIRE HYDRANT SHALL BE A MAXIMUM OF 150 LINEAR FEET.
 CONSULT MEP AND FIRE CODE TO VERIFY (REFER TO #8 ON THE
 ATTACHED MARKED-UP PLAN).
 10. PLEASE USE THE CITY'S LATEST DETAILS FOR THE
 FOLLOWING STANDARD DETAILS: WS-1; WS-5; P-3.
  
  
  