| Plan Review Notes For Project E16030025 |
| Project Number |
E16030025 |
|
| Review Stop |
ENG-A |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-23 13:00:33 | PASSED WITH PROVISOS: THE GREENE SCHOOL | | | | | | #1 PLANS APPROVED AS-NOTED; | | | 4" DIAMETER FOR FIRELINE SHALL BE OF DUCTILE IRON | | | MATERIAL | | | UG FIRELINE PERMIT IS REQUIRED THRU CONSTRUCTION | | | SERVICES. | | | SUBMIT CITY'S APPROVE MATERIAL LIST. | | | SUBMIT STORM ELEMENTS AND STRUCTURES THAT WILL BE USED | | | ON CITY ROW. | | | | | | #2 PLAN IS APPROVED "AT-RISK" - SITE PLAN IS IN | | | PROGRESS. | | | | | | #3 NPDES REQUIREMENTS WILL APPLY. | | | | | | #4 ROW PERMIT IS REQUIRED FOR WORK IN BISCAYNE BLVD. | | | AND ALLEYWAY. | | | | | | IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF | | | WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD | | | FREE." | | | FOR MORE INFORMATION REFER TO THE LINK BELOW: | | | HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI | | | CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL | | | | | | MANUEL JULIAN GONZALEZ | | | ENGINEERING PROJECT COORDINATOR | | | PUBLIC WORKS DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | | | | | | | |
| |