2015-04-20 22:38:35PLEASE RESPOND TO COMMENTS IN WRITING:
  
 1. THE PEAK STAGES IN THE MODEL OCCUR AND THE END OF
 THE MODEL RUN (HOUR 72 AND 24). PLEASE EXTEND THE MODEL
 DURATION PAST THE END OF THE STORM EVENT TO SHOW THE
 PEAK STAGES DO NOT CONTINUE TO INCREASE.
  
 2. PLEASE INCLUDE A BASIN MAP.
  
 3. THE MODEL ASSUMES A DCIA OF 0% FOR ALL OF THE NODES,
 BUT SEVERAL OF THE BASIN AREAS HAVE INLETS WITHIN PAVED
 AREAS. PLEASE ADJUST THE DCIA TO REFLECT THE DESIGN.
  
 4. DO THE AREAS USED IN THE STAGE-STORAGE CALCULATIONS
 INCLUDE THE BUILDING AREAS?
  
 5. PLEASE SUBMIT THE CURVE NUMBER CALCULATIONS.
  
 6. PLEASE SUBMIT A MASS BALANCE REPORT FOR THE ICPR
 MODEL.
  
 7. PLEASE INDICATE WHICH NODE THE RATING CURVE IS
 ASSIGNED.
  
 8. PLEASE INDICATE THE SOURCE OF THE TAILWATER
 ELEVATIONS USED IN THE MODEL.
  
 9. THE RAINTANKS WERE MODELED AS STAGE AREA NODES WHILE
 ONLY A FINITE AMOUNT OF STORAGE IS PROVIDED IN THE
 TANKS. PLEASE REVISE THE MODEL TO REFLECT THE STORED
 VOLUME RATHER THAN MODELING THEM SIMILARLY TO OPEN
 PONDS.
  
 10. PLEASE SUBMIT HYDRAULIC GRADE LINE CALCULATIONS FOR
 THE PROPOSED ROADWAYS.
  