Notes
Date Text
2015-07-09 08:59:30EXFILTRATION TRENCH - CALCULATIONS USE DIFFERENT WIDTH
 AND WEIR HEIGHT THAN SHOWN ON PLANS. REQUESTED ENGINEER
 TO SUBMIT UPDATED CALCULATIONS.
  
 KELLY
2015-06-08 16:05:15#1 PLEASE NOTE ON EACH SHEET PLANE OF REFERENCE (DATUM)
 FOR ELEVATIONS SEC. 78-9. - CITY DATUM OR PLANE OF
 REFERENCE.
  
 #2 FERN STREET SHALL BE RESTORED (MILL AND RESURFACE 2-
 1 INCH LIFTS) THE FULL WEST BOUND TRAVEL LANE (FROM
 CENTERLINE OF ROAD) TO ACHIEVE ELEVATION AND CONSISTENT
 PAVEMENT PATTERN. SHOW EXTENTS OF THESE LIMITS WITH A
 SHADE PATTERN. REF.: CITY OF WPB STANDARD TRENCH
 RESTORATION DETAIL. ADDITIONAL SPOT ELEVATIONS WILL BE
 REQUIRED ALONG FERN TO DETECT PROPER SLOPE.
  
 #3 OVERHEAD CABLES FOR STREET LIGHTS ARE TO BE PLACED
 UNDERGROUND IN CONDUITS. 3 PROPOSED LIGHT LOCATIONS
 ALONG YOUR FRONTAGE WILL BE REQUIRED. FEED TO LIGHTS
 MUST ALSO BE COORDINATED BY CONTRACTOR/DEVELOPER TO
 PROVIDE ELECTRIC FEED. A SEPARATE PLAN SHOWING THE
 CONFIGURATION AND LIGHT POLE SPECS WILL BE REQUIRED TO
 PERMIT THRU CONSTRUCTION SERVICES DEPARTMENT. CITY'S
 "ACORN" DESIGN MUST SUBMITTED. CONTACT PLANNING AND
 ZONING FOR TYPE.
  
 #4 SHEET C-05 - NOTE "SAW-CUT" WHERE PROPOSED DRIVEWAY
 APRON CONNECTS TO SOUTH DIXIE HIGHWAY. EXISTING SPOT
 ELEVATIONS WILL BE REQUIRED WHERE DRIVEWAY APRON MEETS
 PAVEMENT.
  
 #5 SHEET C-05 - NOTE INSTALLATION OF BLUE RPM WHERE
 HYDRANT IS LOCATED.
  
 #6 SHEET C-05 - PRIOR TO ANY CONSTRUCTION IN THE PUBLIC
 RIGHT-OF-WAY, THE CONTRACTOR/DEVELOPER SHALL NOTIFY AND
 MEET WITH THE CITY'S LANDSCAPE PLANNER AND PROJECT
 MANAGER FOR FERN STREET IMPROVEMENTS TO COORDINATE
 SIDEWALK PLANTERS AND ROADWAY STANDARDS. THIS IS ALSO
 APPLICABLE FOR THE ALLEY WAY RESTORATION WHICH WILL
 REQUIRE MILLING AND RESURFACE WITH A MINIMUM OF SN#
 3.06 .NOTE ON PLANS THAT MINIMUM 3 CORE SAMPLES MUST BE
 OBTAINED ALONG THE CENTER OF THE ALLEY.
  
 #7 SHEET C-5 MUST REFLECT PROPOSED ROW PLANTER
 CONFIGURATION ALONG FERN ST.
  
 #8 SHEET C-05 NOTE STORM STRUCTURE SIZE AND TYPE ON
 SOUTH DIXIE WHERE OUTFALL IS PROPOSED . EXISTING
 STRUCTURE MAY NOT BE SUITABLE TO HANDLE THE PROPOSED
 PIPE TO BE CONNECTED AT SUCH ANGLE.
  
 #9 METER AREA MUST IDENTIFY AS A UTILITY EASEMENT.
 EASEMENT MUST INCLUDE DOMESTIC METER BOX AND FIRELINE
 CONTROL GATE VALVE.
  
 #10 NOTE ON SHEET C-05 THE TYPE "F" CURB TO BE
 INSTALLED AND VALLEY CURB AT APRONS.
  
 #11 NOTE ON SHEET C-12 PROVIDE PARKING SPACING
 DIMENSIONS TO THE PARALLEL PARKING ALONG FERN ST.
  
 #12 METER AREA APPEARS TO BE TOO SMALL FOR A 4'X6'
 VAULT, METER CAN BE PLACED ABOVE GROUND. PROVIDE AN
 ENLARGED VIEW OF THIS AREA, IT IS IMPORTANT TO SHOW AND
 CALL OUT ALL VALVES.
  
 #13 NOTE ON SHEET C-9 WATERMAIN PORTION SERVING YOUR
 PROPERTY FOR FIRE SERVICE SHALL BE NOTED AS (PRIVATE).
 IT SHOULD BE DOUBLE VALVED FOR PRESSURE TESTING AND
 SAMPLING.
  
 #14 SHEET C-9 CALL OUT WATERMAIN OUT ON FERN, THE NOTE
 CALLS OUT "CAS". EX 12" CAST WM. TAPPING AREA SHALL
 SHOW 50' MILL AND RESURFACE 50' IN EITHER DIRECTION.
 SHOW AREA SHADED.
  
 #15 SHEET C-9 CALL OUT FOOTAGE OF PIPE TO BE RESTRAINT
 FOR EACH PIPE CONNECTION. THIS WILL ASSIST SURVEYOR TO
 DISPLAY THIS INFORMATION ON THE AS-BUILT PLAN.
  
 #16 OTHER COMMENTS MAY BE COMING AS TO DRAINAGE AND
 DRAINAGE CALCULATIONS BY KELLY CRANFORD, P,E,
  
 #17 PROVIDE BASIC LAYOUT OF THE METER AREA, RPZ AND
 DCDA LOCATION. THE MINIMUM AREA APPEARS TO BE 10'X14',
 THE AREA YOUR PLAN SHOWS IS 10'X10'.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  
  
  
  Print


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved