Plan Review Notes For Project E14050008
Project Number E14050008
Review Stop ENG-D
Sequence Number 2
Notes
Date Text
2014-07-01 13:41:35EMAILED TO CONSULTANT (BRIAN ARNOLD WITH WGI) ON
 7/1/2014
  
 I HAD JUST A FEW MINOR COMMENTS.
  
 THE EXFILTRATION TRENCH DETAIL ON SHEET C-18 NOTES THAT
 DIMENSIONS VARY FOR TRENCH DEPTH AND WIDTH. DIMENSIONS
 NOT SPECIFIED ELSEWHERE IN PLANS. PLEASE ADD THE
 DIMENSIONS TO THE DETAIL.
 THE PLAN SHEET (C-4) AND DETAIL CALL OUT FLAP GATE FOR
 CB-21 (C-8). A DETAIL FOR BACKFLOW VALVE INCLUDED ON
 DETAIL SHEET (C-8). IS THE FLAP GATE INTENDED TO BE THE
 BACKFLOW VALVE?
 WITH THE SHOWN POTABLE WATER CONNECTION CONFIGURATION,
 AN EASEMENT WILL BE REQUIRED AROUND CONTROL VALVE AND
 METER. PLEASE ALSO SHOW THE BACKFLOW PREVENTER ON
 EXISTING IRRIGATION LINE. (C-5)
 PLEASE ADD A RETAINING WALL DETAIL.
 THE COMPACTOR GATES OPENING INTO ALLEY IS A SAFETY
 HAZARD. PLEASE ADJUST THE DESIGN SO THAT THE GATES WILL
 NOT INADVERTENTLY SWING OPEN OBSTRUCT AND COME INTO
 CONTACT WITH TRAFFIC UTILIZING THE ALLEY.
 THE SUBMITTED CONSTRUCTION ESTIMATE NOT SIGNED AND
 SEALED. I NEED TO CLARIFY SOMETHING WITH MY SUPERVISOR
 WHEN HE RETURNS TO WORK NEXT WEEK, SO PLEASE WAIT UNTIL
 RESUBMITTED.