| Plan Review Notes For Project E14050008 |
| Project Number |
E14050008 |
|
| Review Stop |
ENG-D |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-07-01 13:41:35 | EMAILED TO CONSULTANT (BRIAN ARNOLD WITH WGI) ON | | | 7/1/2014 | | | | | | I HAD JUST A FEW MINOR COMMENTS. | | | | | | THE EXFILTRATION TRENCH DETAIL ON SHEET C-18 NOTES THAT | | | DIMENSIONS VARY FOR TRENCH DEPTH AND WIDTH. DIMENSIONS | | | NOT SPECIFIED ELSEWHERE IN PLANS. PLEASE ADD THE | | | DIMENSIONS TO THE DETAIL. | | | THE PLAN SHEET (C-4) AND DETAIL CALL OUT FLAP GATE FOR | | | CB-21 (C-8). A DETAIL FOR BACKFLOW VALVE INCLUDED ON | | | DETAIL SHEET (C-8). IS THE FLAP GATE INTENDED TO BE THE | | | BACKFLOW VALVE? | | | WITH THE SHOWN POTABLE WATER CONNECTION CONFIGURATION, | | | AN EASEMENT WILL BE REQUIRED AROUND CONTROL VALVE AND | | | METER. PLEASE ALSO SHOW THE BACKFLOW PREVENTER ON | | | EXISTING IRRIGATION LINE. (C-5) | | | PLEASE ADD A RETAINING WALL DETAIL. | | | THE COMPACTOR GATES OPENING INTO ALLEY IS A SAFETY | | | HAZARD. PLEASE ADJUST THE DESIGN SO THAT THE GATES WILL | | | NOT INADVERTENTLY SWING OPEN OBSTRUCT AND COME INTO | | | CONTACT WITH TRAFFIC UTILIZING THE ALLEY. | | | THE SUBMITTED CONSTRUCTION ESTIMATE NOT SIGNED AND | | | SEALED. I NEED TO CLARIFY SOMETHING WITH MY SUPERVISOR | | | WHEN HE RETURNS TO WORK NEXT WEEK, SO PLEASE WAIT UNTIL | | | RESUBMITTED. |
| |