2014-03-10 11:06:33PASSED WITH PROVISO:
  
 #1 STAINLESS STEEL TAPPING SLEEVE IS NOT ALLOWED SINCE
 TAPPED LINE ONLY TWICE THE DIAMETER OF THE PROPOSED 4"
 PIPE.
 PLEASE USE A DUCTILE IRON SLEEVE. ON PAGE 19 OF 54 OF
 THE CITY'S APPROVED MATERIAL LIST YOU MAY FIND
 ACCEPTABLE PRODUCTS.
  
 #2 PLEASE SUBMIT AML PAGE 19 VIA EMAIL TO
 [email protected]
  
 #3 PLANS ARE BEING APPROVED "AS-NOTED"
  