| 2013-06-11 09:31:33 | PLEASE RESPOND TO COMMENTS IN WRITING. |
| | |
| | 1. RIM ELEVATION (20.65) OF STORM MANHOLE IS LOWER THAN |
| | THE GRATE ELEVATION (21.48) OF ALL OF THE STORM INLETS. |
| | 2. ELIMINATE THE CURB OPENING AROUND CATCH BASIN CB-1. |
| | DRIVEWAYS CAN PROVIDE FLOOD RELIEF IF THERE IS A STORM |
| | EVENT THAT WOULD EXCEED THE CAPACITY OF THE |
| | EXFILTRATION SYSTEM. |
| | 3. TIE ROOF DRAINAGE DIRECTLY INTO THE DRAINAGE |
| | STRUCTURES, IF POSSIBLE. |
| | 4. STORM SEWER PRECAST MANHOLE DETAIL (SHEET C-7) - USE |
| | CWPB'S DETAIL ST-3 FOR MANHOLE FRAME AND COVER INSTEAD |
| | OF CALLING OUT TOWN OF JUPITER'S. |
| | 5. PARKING SPACE #14 APPEARS TO BLOCK PARKING SPACE #8. |
| | 6. ONE-WAY SIGNS ON PARKER AVENUE AND SOUTHERN BLVD |
| | CANNOT GO IN THE LEVEL (UNRAISED) MEDIANS. |
| | 7. ZOO SIGN WILL NEED TO BE RELOCATED IN THE PARKER |
| | AVE. RIGHT-OF-WAY. |
| | 8. ADD CENTER LINE STRIPING IN THE PARKING LOT AT SOUTH |
| | DRIVEWAY. |
| | |
| | WITH REGARDS, |
| | TRACY L. WARD, P.E. |
| | SENIOR STORMWATER ENGINEER |
| | CITY OF WEST PALM BEACH |
| | ENGINEERING AND PUBLIC WORKS DEPARTMENT |
| | 401 CLEMATIS ST., 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | PHONE: 561-494-1120 |
| | FAX: 561-494-1116 |
| | CELL 561-351-0510 |
| | [email protected] |
| 2013-06-10 14:36:08 | PLEASE RESPOND TO COMMENTS IN WRITING: |
| | |
| | #1 DUMPSTER DETAIL MISSING. |
| | |
| | #2 SHEET C-3 REMOVE PAVER HATCH AT FDOT DRIVEWAY APRON. |
| | IT'S CONFUSING. |
| | |
| | #3 SHEET C-3 FDOT PERMIT REQUIRED FOR DRIVEWAY APPROACH |
| | AND ADA RAMP IN FDOT ROW. |
| | |
| | #4 SHEET C-3 CALL OUT 6" THICK CONCRETE DRIVEWAY |
| | APPROACH (3000PSI) AT PARKER AVENUE. |
| | |
| | #5 DUMPSTER PICK-UP MUST BE SPELLED OUT ON PLANS. WHO |
| | WILL ROLL OUT DUMPSTER AND WHERE WILL IT BE PLACED FOR |
| | PICK-UP. |
| | |
| | #6 SHEET C-2 DIMENSION ALL ADA RAMPS WIDTHS. |
| | |
| | #7 STATE ON PLANS NGVD 29 DATUM (ELEVATIONS). |
| | |
| | #8 MOVE DOMESTIC WATER TAP SO THAT WATER METER IS |
| | INSIDE 10' U.E. (TYPE K COPPER) |
| | |
| | #9 FIRE HYDRANT PIPE SHALL BE 6" DIP @ 36" DEEP. |
| | |
| | #10 SUBMIT A FDOT UTILITY APPLICATION PERMIT ALONG WITH |
| | 2 SETS OF REVISED PLANS. |
| | |
| | MANUEL JULIAN GONZALEZ |
| | ENGINEERING PROJECT COORDINATOR |
| | ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1085 |
| | FAX: (561) 494-1116 |
| | MOBILE: (561) 644-7301 |
| | EMAIL: [email protected] |
| | WWW.WPB.ORG/ENGINEERING |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| |
Print |