| 2013-05-13 11:16:01 | COMMENTS TO EOR [email protected] |
| | PLEASE RESPOND TO ALL COMMENTS IN WRITING. THANK YOU! |
| | |
| | #1 PROVIDE VERTICLE CLEARANCES BETWEEN WATER, SEWER AND |
| | STORM. |
| | |
| | #2 PROVIDE ON PLAN VIEW THE LAYOUT FOR MASTER METER. |
| | METER MUST BE JUST INSIDE SITE AND MUST BE SHOWN IN A |
| | PROPOSED UTILITY EASEMENT. |
| | |
| | #3 PROVIDE A COPY OF THE APPROVED SITE PLAN. (YOU MAY |
| | PDF VIA EMAIL TO [email protected] |
| | |
| | #4 THE ISO CALCULATIONS AND WATERCAD MODEL DOES NOT |
| | REFLECT THE PRESSURE LOSS THRU THE METER, RPPA OR THE |
| | DCDA. CLARIFY IF THIS HAS BEEN ACCOUNTED FOR. |
| | |
| | #5 PROVIDE 2 (4" RIGID CONDUITS AT NEW DRIVEWAY AT |
| | LAMBERTON DRIVE AND EXECUTIVE CENTER DRIVE.) |
| | |
| | #6 PROVIDE SPOT ELEVATIONS ON PAVING AN D GRADING PLAN. |
| | PEDESTRIANS FROM PARKING UNTO BUILDINGS MAY BE WALK ON |
| | RAMPS THAT MAY NEED HAND RAILS. |
| | |
| | #7 LAMBERTON DRIVE STRIPING AND SIGNING MUST BE |
| | THERMOPLASTIC. IT MUST ALSO BE SUPPLIED WITH TRUNCATED |
| | DOMES. |
| | |
| | #8 REMOVE FIRE/DOMESTIC METER DETAIL ON SHEET C630. AND |
| | REMOVE THE GREASE/WATER SEPARATOR OFF SHEET C651. |
| | |
| | #9 PAVERS ON EXECUTIVE CENTER DRIVE AND CONGRESS AVE |
| | MUST HAVE A HOLDHARMLESS AGREEMENT WITH THE CITY FOR |
| | MAINTENANCE RESPONSABILITY. |
| | VINCENT NOEL CITY OF WPB PROPERTY |
| | |
| | #10 SEWER MANHOLES ARE PRIVATE AS THEY SERVE THE HOTEL |
| | PROPERTY, THERE IS AN EASEMENT THAT IS PRIVATE, PLEASE |
| | CONFIRM OWNERSHIP OF RIGHTS AS YOUR PLANS SHOW |
| | MIDIFYING SOME OF THE STRUCTURES. IF MANHOLES ARE |
| | MODIFIED THE CITY WOULD SUGGEST REHABILITATING THE |
| | LININGS SO THAT INFILTRATION OF WATER IS KEPT TO A |
| | MINIMUM. ALSO THE LIDS SHOULD BE CHECKED FOR PROPER |
| | SEAL AS TO KEEP RAIN WATER FROM ENTERING SEWER SYSTEM. |
| | |
| | #11 LANDSCAPING ALONG THE 10' UTILITY EASEMENT WILL |
| | HAVE TO CLEAR ANY UTILITIES IN PLACE INCLUDING CITY OF |
| | WPB IRRIGATION. ANY WORK ON EXECUTIVE CENTER DRIVE WILL |
| | REQUIRE THE CONTRACTOR TO OBTAIN A ROW PERMIT. SAME FOR |
| | CONGRESS AVE WITH PALM BEACH COUNTY ROW. |
| | |
| | #12 PROVIDE TRAFFIC DOCUMENTATION ON INTERSECTION OF |
| | EXECUTIVE CENTER DRIVE AND LAMBERTON DRIVE, |
| | |
| | PLEASE SEE STORMWATER COMMENTS: |
| | 1. REFERENCED FEMA FIRM PANEL AND FLOOD ZONE NOTED ON |
| | SHEET C300 AND OTHERS (AND IN DRAINAGE CALCS.) IS |
| | INCORRECT. |
| | 2. THE EXISTING CONDITIONS PLAN SHOWS WHAT APPEARS TO |
| | BE A 32' WIDE EASEMENT OVER THE SANITARY SEWER SYSTEM. |
| | IF THIS IS AN EASEMENT, PLEASE HAVE THE DEVELOPER |
| | PROVIDE A COPY OF THE EASEMENT DOCUMENT(S) TO SEE |
| | WHO/WHAT THE EASEMENT IS FOR AND IF THERE ARE ANY |
| | RESTRICTIONS. BUILDINGS 12 AND 17 ENCROACH INTO THE |
| | "EASEMENT". |
| | 3. SHEET C301 - HOW DOES RETENTION AREA SOUTH OF |
| | BUILDING 9 DRAIN? WHAT AREA(S) DRAIN TO THIS RETENTION |
| | AREA? |
| | 4. IRRIGATION SHEETS NOT LABELED OR NUMBERED. |
| | 5. LANDSCAPE PLANS MISSING A PLANT SCHEDULE. |
| | 6. MANY PROPOSED TREES PROPOSED NEAR OR ON TOP OF |
| | WATER/SEWER/STORM PIPES. I'VE HIGHLIGHTED MOST OF THE |
| | CONFLICTS WITH THESE UTILITY LINES ON SHEET L1.10. |
| | 7. NO TREES OR WALLS ARE TO BE PLACED WITHIN THE 10' |
| | UTILITY EASEMENT ALONG EXECUTIVE CENTER DRIVE. |
| | 8. WALL AT NE CORNER OF BUILDING 6 MAY BE IN CONFLICT |
| | WITH DCDA AND/OR BACKFLOW PREVENTER. |
| | 9. CONSIDER DIRECTIONAL ARROWS AT OUTBOUND TURN LANES |
| | OF LAMBERTON DRIVE. |
| | 10. ICPR MODEL DIFFICULT TO REVIEW. MODEL SCHEMATIC |
| | (WITH NODES/LINKS LABELED) ON TOP OF THE SITE PLAN |
| | WOULD BE HELPFUL. |
| | 11. DRAINAGE CALCULATIONS - PROVIDE SUPPORT FOR A/D |
| | SOILS USED IN CURVE NUMBER CALCULATION. |
| | 12. ENGINEER TO PROVIDE COPY OF EXISTING SFWMD ERP |
| | PEMIT(S). |
| | |
| | WITH REGARDS, |
| | TRACY L. WARD, P.E. |
| | SENIOR STORMWATER ENGINEER |
| | CITY OF WEST PALM BEACH |
| | ENGINEERING AND PUBLIC WORKS DEPARTMENT |
| | 401 CLEMATIS ST., 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | PHONE: 561-494-1120 |
| | FAX: 561-494-1116 |
| | CELL 561-351-0510 |
| | [email protected] |
| | |
| |