| Plan Review Notes For Project E13040008 |
| Project Number |
E13040008 |
|
| Review Stop |
ENG-A |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-05-02 09:39:20 | 05-02-2013 | | | E13040008 854 CONNISTON (PROPOSED FIRE HYDRANT AND | | | PRIVATE FIRE LINE) (AKA THE UNIVERSAL CHURCH) | | | | | | YOU MAY MOVE THAT FIRE HYDRANT CLOSER TO THE TAP FOR | | | THE DCDA TO AVOID SUCH A LARGE AREA OF ROAD | | | RESTORATION. | | | ON SHEET C-1 YOU CALL OUT 1" OF ASPHALT. THAT MUST BE | | | 2" MIN. | | | GENERAL NOTE TO RE-STRIPE (THERMOPLASTIC) | | | 16"X6" MUST BE TAPPING VALVE AND SLEEVE. | | | CALL OUT 4" FIRELINE PIPE AS 4" DIP. | | | SEWER LINE GOING FROM MANHOLE EAST INTO THE PROPERTY | | | DOES NOT EXIST. | | | | | | MISSING ON PLANS: | | | ROAD RESTORATION DETAIL | | | SIDEWALK / CURB DETAILS ARE MISSING. | | | SIDEWALK NOTES. | | | PLEASE REVIEW OUR DETAILS TO SEE IF ANY MORE DETAILS | | | MAY NEED TO BE INCLUDED. | | | HTTP://WPB.ORG/ENGINEERING/ENGINEERING-SERVICES/ENGINEE | | | RING-STANDARDS/ | | | | | | | | | |
| |