2013-05-28 12:09:32COMMENTS:
 #1 UPDATE PLAN SHOWING THE CONNECTION TO SEWER AT
 MALVERNE RD. AS AGREED.
 #2 UPDATE DRAINAGE PLAN TO REFLECT CHANGES AS PER
 DICUSSION WITH FDOT AND CITY OF WPB. NO NEW STRUCTURES
 REQUIRED.
 #3 A PERMIT FOR DRIVEWAY(S) OFF SOUTHERN BLVD WILL BE
 REQUIRED FROM FDOT.
 #4 DRIVEWAY OFF MALVERNE WILL REQUIRE A CONCRETE APRON
 AS PER CITY OF WPB STANDARD.
 #5 NO ROOF OVER CITY PICK?UP DUMPSTER AREA. NO FLOOR
 DRAINS WILL BE ALLOWED IN OPEN DUSMPER AREAS,
 #5 FIRELINE TIE?IN WILL REQUIRE A SIZE ON SIZE TEE, NOT
 A DIRECT TAP. NOTE ON PLAN "6"X6" CUT?IN TEE"