Plan Review Notes
Plan Review Notes For Project E12090016
Project Number E12090016
Review Stop ENG-M
Sequence Number 1
Notes
Date Text
2013-04-25 15:19:46PLAN COMMENTS:
  
 STATUS IS FAILED.
  
 #1 PLANS DO NOT SHOW STRAIGHT PIPE DISTANCE BEFORE AND
 AFTER METER.
  
 #2 2" FM CONNECTION IS UNACCEPTABLE WITH SO MANY
 FITTINGS. DIRECT TAPP WOULD BE ACCEPTABLE. FORD 202BS
 DOUBLE BAND BRASS SADDLE.
  
 #3 PROVIDE APPROVED MATERIAL LIST WITH METER BOX
 COATING INTERNAL AND EXTERNAL FOR SEWER COATINGS (USE
 MANHOLE COATING SECTION TO SELECT.)
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 #4 PROVIDE DIMENSIONS AND DISTANCES FROM EXISTING
 STRUCTURE TO PROPOSED STRUCTURE.
  
 #5 METER INSTALL RECOMMENDATIONS MUST MEET
 SPECIFICATION. PROVIDE CROSS SECTION OF 2" METER
 INSTALL SHOWING HORIZONTAL PLACEMENT.
 IT MUST BE INSTALLED IN A MANNER WHERE OPTIMUM METER
 ACCURAZY AND PERFORMANCE IS ACHIEVED. IT IS RECOMMENDED
 TO CONTACT METER SUPPLIER TO ASSIST IN THIS
 INSTALLATION TO ACHIEVE OPTIMUM PERFORMANCE. CONTACT
 CITY METER SHOP FOR METER TECHNICAL SUPPORT CONTACT
 INFORMATION (561) -822-1200.
  