| Date |
Text |
| 2013-02-01 10:56:11 | RESPOND TO COMMENTS IN WRIRTTING: |
| | |
| | PLANS REFLECT A NEW TAP FOR DOMETIC WATER. (TAP WILL |
| | NOT BE APPROVED AT THE SPECIFIED LOCATION DUE TO THE WM |
| | THAT IT IS CONNECTED TO WILL BE PLACED OUT OF SERVICE |
| | IN NEAR FUTURE.) REVISE SHOWING TAP OFF 6" WATERMAIN |
| | LEG FEEDING THE BUILDING NOW (BEFORE FIRELINE CONTROL |
| | VALVE). (A SKETCH HAS BEEN SENT VIA EMAIL 02/01/2013 |
| | SHOWING AVAILABILITY OF SERVICE OPTIONS) |
| | |
| | ON THAT SAME NOTE: FOR PROPOSED FIRELINE PLEASE LOOK |
| | INTO THE OPTION OF CONNECTING TO EXISTING 6" WATERMAIN |
| | LEG. THIS MAIN WOULD REQUIRED A 6" RW GATE VALVE TO BE |
| | ABLE TO SHUT OFF AND TURN 90 DEGREES TO GRASSED AREA ON |
| | THE WEST SIDE OF BUILDING WHERE DCDA CAN BE PLACED. YOU |
| | DCDA IS PRIVATE SO THE CITY WILL NOT REQUIRE EASEMENT. |
| | FOR METER SERVICE THE CITY WILL REQUIRED AN 5' EASEMENT |
| | COVERING THE SERVICE UNDER SIDEWALK ALL THE WAY TO THE |
| | METER (IT SHOULD COVER THE METER AREA). THE EASMENT |
| | DOCUMENT CAN BE EMAIL TO YOU IF REQUEST IS MADE TO |
| | VINCENT NOEL (561) 494-1096. |
| | A LEGAL AND SKETCH WILL HAVE TO BE PRESENTED AT OWNERS |
| | EXPENSE. |
| | |
| | CONTRACTOR MUST ALSO PROVIDE FDC LOCATION ON PLANS AND |
| | IT MUST BE WITHIN 150 LINEAR FEET AWAY FROM NEAREST |
| | CITY FIRE HYDRANT. |
| | |
| | MANUEL JULIAN GONZALEZ |
| | ENGINEERING PROJECT COORDINATOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1085 |
| | FAX: (561) 494-1116 |
| | MOBILE: (561) 644-7301 |
| | EMAIL: [email protected] |
| | WWW.WPB.ORG/ENGINEERING |
| | |
| | |
| | |
| | |
| |
Print |