2012-06-14 14:52:37COMMENTS:
 1. THE UTILITIES NEED TO BE RECONFIGURED TO A MASTER
 METER DESIGN. (PUBLIC UTILITIES WILL NOT PERMIT PUBLIC
 UTILITIES UNDER PRIVATE ROADS.)
 2. INSTALL VALVE ON WATER MAIN EXTENSION IN
 RIGHT-OF-WAY AT PROPERTY LINE.
 3. METER WILL NEED TO BE INSTALLED PAST THE PROPERTY
 LINE IN AN EASEMENT.
 4. REVISE PLAN DETAIL SHEETS TO REFLECT MASTER METER
 CONSTRUCTION.
 5. REVISE FDOT UTILITY PERMIT FORMS FOR MY SIGNATURE.
 (BRIAN R. MOREE, CONSTRUCTION MANAGER)
 6. DRAINAGE PIPE BETWEEN C-26 AND C-27 STRUCTURES
 DEPICT AN INVERT ELEVATION ABOVE 16.00, BUT THE PLAN
 NOTE STATES THE INVERT SHALL BE 16.00>
 7. CATCH BASIN BETWEEN C-43 AND C-44 DOES NOT INCLUDE
 INFORMATION.
  
 PLEASE RESPOND TO COMMENTS IN WRITING TO MR. BRIAN
 MOREE. ANY QUESTIONS CAN BE DIRECTED TO HIS E-MAIL OR
 PHONE.
  