| Plan Review Notes For Project E11110017 |
| Project Number |
E11110017 |
|
| Review Stop |
ENG-A |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-12-21 14:00:07 | PLEASE RESPOND TO COMMENTS IN WRITING: | | | | | | #1 CONCERNS AS TO SLOPE AND STORM WATER DETENTION ALONG | | | WEST SIDE OF PROPERTY. | | | (CROSS LLOPES FROM PATH TO CITY ROW ARE EXCESSIVE AS TO | | | SUPPLY ANY TYPE OF WATER DETENTION.) | | | | | | #2 IN REFERENCE TO COMMENT #1 THE SECTION C-C AT SHEET | | | C6 OF 13 DOS NOT INCLUDE THE STEPS UP TO F.F.E. | | | PLEASE REVISE TO SHOW ELEVATION. PLEASE ALSO SHOW THE | | | FENCELINE ON THE SECTION WITH FENCE HEIGHT. | | | INCLUDE TYPE OF FENCE MATERIAL. | | | | | | #3 DOMESTICE WATER METER AND BACKFLOW MUST BE BACK AT | | | 6" DIP WM. | | | THE WATER SERVICE WILL REQUIRE A PALM BEACH COUNTY | | | HEALTH DEPARTMENT PERMIT SINCE IT EXTENDS OVER 100' | | | (L.F.) | | | | | | #4 DRIVEWAY ENTRANCE/EXIT WILL REQUIRE STRIPING | | | MODIFICATION AT N. TAMARIND AVE. | | | (THIS INCLUDE STRIPING TO AVOID EXITING VEHICLES | | | DRIVING NORTH INTO THE CURBED ISLAND FEATURE. ) | | | | | | MANUEL JULIAN GONZALEZ | | | ENGINEERING PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 644-7301 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | | | | | | | |
| |