Plan Review Notes
Plan Review Notes For Project E11100001
Project Number E11100001
Review Stop ENG-A
Sequence Number 1
Notes
Date Text
2011-11-21 08:19:18TEMPORARY CONSTRUCTION VILLAGE COMMENTS: ESD PERMIT #
 E11100001
  
 #1 PLAN SHOW USING PVC MATERIAL ON THE CITY SIDE, CITY
 ONLY ACCEPTS DIP (DUCTILE IRON PIPE), SHEET 700-CO-017
  
 #2 PLAN LACKS THE PROPERTY LINE AROUND THE ENTIRE SITE.
 THIS IS IMPORTANT TO SHOW ON SHEETS WHERE BMP'S AND
 NPDES ELEMENTS ARE USED TO CONTROL CONSTRUCTION
 ACTIVITY.
  
 #3 PLEASE PROVIDE USAGE INFORMATION FOR WATER AND
 SEWER. GPM, ETC. SPECIFY USING NEPTUNE PROTECTUS IIIS
 FIRE SERVICE METER. SHEET 700-CO-017
 METER VAULT AND BACKFLOW SHOULD BE ORIENTED - RUNNING
 NORTH AND SOUTH SAME AS BACKFLOW.
 NOTE: (6" FIRE PER AWWA 900 - 2,000 (HEAD LOSS 12 PSI)
 (CAN FEED FIRE HYDRANTS ON-SITE AND POTABLE WATER)
 AWWA SAYS 1600 GPM (6PSI LOSS NEPTUNE) = 6? NEPTUNE
 PROTECTUS IIIS FIRE SERVICE METER (HIGH PERFORMANCE)
  
 #4 SHOW A 20' UTILITY EASEMENT OVER THE WATER MAIN
 COVERING FROM THE POINT IT ENTERS PROPERTY UP TO AND
 INCLUDING THE THE 4'X6' METER VAULT.
 (BACKFLOW IS PRIVATE, THERE FORE DO NOT INCLUDE INSIDE
 THIS EASEMENT.) SHEET 700-CO-017
  
 #5 SHOW VERTICAL CLEARANCE OR SEPARATION BETWEEN
 PROPOSED WATER AND EXISTING 4" FM. SHEET 700-CO-017
  
 #6 4" FM SHOULD BE CALLED OUT AS "EXIST. 4" FM"
  
 #7 VERIFY LOCATION FOR EXISTING 4" FM, PLANS SHOWS IT
 BEING INSIDE OF YOUR PROPERTY. IF THIS IS TRUE THEN
 PROVIDE LAYOUT OF FM ACROSS YOUR PROPERTY AND SUPPLY
 EASEMENT INFORMATION.
  
 #8 WATER AND SEWER WILL NEED TO BE SUBMITTED TO PBC
 HEALTH DEPARTMENT.
  
 #9 COST ESTIMATE SHOULD BE REVISED TO INCLUDE ELEMENTS
 THAT WILL REMAIN FOR THE PERMANENT PHASE. PLEASE
 REVISE.
  
 #10 OBTAIN ROW PERMIT FOR WORK WITHIN JOG RD. JOG RD IS
 A PALM BEACH COUNTY ROADWAY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE FEEL FREE TO CONTACT
 MY OFFICE. THANK YOU!
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  Print


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved