| Notes |
| Date |
Text |
| 2011-06-28 12:13:48 | 06/28/2011 | | | | | | PLEASE SUBMIT THE FOLLOWING: | | | | | | #1 REVISE SUMMARY OF CONSTRUCTION TO INCLUDE: | | | A. ESTIMATED # OF DAYS STORMWATER VENUE WILL BE OUT OF | | | SERVICE. (# OF DAYS IT WILL BE BY-PASSED) | | | B. STORM CALCULATION SUPPORTING CFS. | | | C. AT WHAT POINT WILL THE STORM WILL BE BY-PASSED | | | | | | #2 BY-PASS SCHEMATIC DRAWING SHOWING | | | A. BY-PASS PUMP LOCATION | | | LOCATION AND PIPING. | | | B. FLOW DIRECTIONS | | | C. PUMP SPECS | | | | | | #3 IDENTIFY FPL ELECTRICAL CROSSING PROPOSED STORM. | | | DUCT BANK? FLEX CABLE? | | | | | | #4 REVISE CONSTRUCTION COST ESTIMATE: | | | A. ANY SHORING? | | | B. ADD WATER SERVICE RELOCATION | | | C. ADD LINE STOP FOR WATERMAIN | | | D. REMOVE AS-BUILTS AND REMOVE DENSITIES/TESTING | | | (THESE ITEMS ARE ALREADY FACTORED AS A PERCENTAGE IN | | | THE SUBTOTALS SECTION.) | | | PLEASE RESEND NEW COST ESTIMATE. | | | | | | #5 MOT AND ROW COMMENTS WHERE EMAILED 06/28/2011 | | | PLEASE REVIEW AND RESEND. | | | | | | MANUEL JULIAN GONZALEZ | | | ENGINEERING PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 644-7301 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | | | | | | | | | | | | | | | | |
| |