Plan Review Notes
Plan Review Notes For Project E11020022
Project Number E11020022
Review Stop ENG-A
Sequence Number 1
Notes
Date Text
2011-03-11 08:10:12PASSED WITH PROVISO
  
 #1 ADA TRUNCATED DOMES REQUIRED IN DETERIORATED
 CONCRETE CROSSING AREAS
 (INCLUDE ROW OF 7TH STREET
  
 #2 REPLACE OR REPLANT TREES IN PLANTERS THAT HAVE DIED
 (7TH STREET)
  
 #3 DUMPSTER AREA MUST MEET MINIMUM SCREENING
 REQUIREMENTS.
  
 #4 CONSTRUCTION CAUSING DAMAGE TO ALLEYWAYS WILL
 TRIGGER ASPHALT OVERLAY.
  
 #5 ANY WATER SERVICES FOUND OFF ALLEYWAY MUST BE CAPPED
 BACK AT MAIN.
  
 #6 PRIVATE HYDRANT MUST HAVE THE CLEARANCE REQUIRED TO
 OPERATE (7.5' RADIUS AT NOZZLES AND 4.5' FROM BACK)
  
 **************************************
  
 MANUEL JULIAN GONZALEZ
 CSD ENGINEERING REVIEW
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
 ****************************************
 COST ESTIMATE WILL BE ADJUSTED DEDUCTING
 MAINTENANCE OF TRAFFIC (6%) &
 CLEARING AND GRUBBING (4%)
  
  