Plan Review Notes
Plan Review Notes For Project E10070002
Project Number E10070002
Review Stop ENG-A
Sequence Number 1
Notes
Date Text
2010-07-07 13:22:03COMMENTS:
  
 #1 EXISTING AND PROPOSED BUILDINGS WHICH HAVE PLUMBING
 DRAIN OUTLETS AT AN ELEVATION 12" OR LESS ABOVE THE
 GROUND SURFACE OF THE NEXT UPSTREAM MANHOLE, WHERE THE
 ELEVATION OF ANY FLOOR IS AT OR BELOW THE INVERT OF THE
 ADJACENT CITY SANITARY SEWER MAIN OR IS LESS THAN 12"
 ABOVE THE GROUND SURFACE OF THE NEXT UPSTREAM MANHOLE,
 OR WHERE A CONDITION EXISTS WHERE A PLUG IN THE CITY
 SANITARY SEWER MAIN WILL CAUSE THE HYDRAULIC GRADIENT
 TO RISE ABOVE THE LOWEST FLOOR LEVEL.
 YOUR FFE 19.00 AND YOUR PROPOSED MANHOLE IS 18.30
 SHOULD HAVE 12" CLERANCE MIN.
  
 #2 PROVIDE FFE AND CALL OUT EACH BUILDING ON SHEET C-3.
  
 #3 PROVIDE DIAMETER OF PROPOSED MANHOLE (4'DIA MIN)
 WITH 24" ACCESS OR REFERENCE MANHOLE DETAIL ON C-5.
  
 #4 LABEL CONDUIT COMING FROM SMALL BUILDING TO LARGE
 BUILDING (33' LONG)
  
 #5 PROVIDE FIRE HYDRANT OUT ON HAVERHILL ROAD TO SERVE
 FDC; FDC PLACEMENT SHOULD BE CLOSER TO ENTRANCE OF
 BUILDING WHERE FIRE DEPARTMENT COULD HAVE EASIER
 ACCESS.
  
 #6 PROVIDE WIDTH AND HEIGHT OF ENTRANCE COVERED AREA.
 IT MUST CLEAR EMERGENCY VEHICLES.
  
 #7 PROVIDE A COPY OF THE APPROVED SITE PLAN.
  
 #8 NEW FIRELINE WILL SERVE TWO BUILDINGS? BACKFLOW
 PROTECTION FOR EACH WILL BE REQUIRED. FIRE DEPT WILL
 HAVE TO OK THIS.
  
 #9 DOMESTIC WATER WILL SERVE SMALL BUILDING AND LARGE
 BUILDING? FOR LARGE BUILDING PROVIDE PUMP INFORMATION.
 IS THE BUILDING MULTI-STORY? REFLECT THAT ON SHEET C-3
 PROVIDE PEAK GPM, ALSO ANY PUMP INFORMATION.
  
 #10 IS FRED GLADSTONE DRIVE A PRIVATE ROAD?
  
 #11 IS LORING DRIVE A PRIVATE ROAD?
  
 #12 ALL SEWER LINES MUST BE COLOR CODED "GREEN" AT
 EVERY 10' OR "GREEN" STRIPING OR FULL GREEN COLOR PIPE
 ACCEPTABLE. (STORM WATER AND CONDUITS REMAIN WHITE).
 PROVIDE NOTE ON PLANS.
  
 #13 GREASE SEPARATOR IS NOT SHOWN ON PLAN. YOU SHOW
 DETAIL ON C-5.
  
 #14 A LINE IS SHOWN RUNNING PARALLEL TO FRED GLADSTONE
 DRIVE; IT LOOKS LIKE IT'S GOING TO THE ROW OF HAVERHILL
 ROAD FROM A LIFT STATION ON-SITE. IDENTIFY?
  
 DRAIN EASEMENTS ?
 DUMPSTERS ?
 80' UTIL EASEMENT ?
  
  
  
  Print


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved