Plan Review Details - Project Z23060038
Plan Review Stops For Project Z23060038
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 07-11-2023 Cont ID  
Sent By swelter Date 07-11-2023 Time 16:11 Rev Time 0.00
Received By llouie Date 07-11-2023 Time 16:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 07-13-2023 Cont ID  
Sent By rbrown Date 07-13-2023 Time 10:06 Rev Time 0.00
Received By rbrown Date 07-13-2023 Time 10:06 Sent To  
Notes
2023-07-13 10:09:05DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. ANY PART OF AN ACCESSIBLE ROUTE WITH A SLOPE GREATER
 THAN 1:20 SHALL BE CONSIDERED A RAMP AND SHALL COMPLY
 WITH SECTION 405 OF FLORIDA ACCESSIBILITY CODE.
  
 3. DEP, US ARMY CORPS OF ENGINEERS, APPROVAL WILL BE
 REQUIRED PRIOR TO BUILDING PERMIT ISSUANCE.
  
 4. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, BACKFLOW PREVENTERS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status P Date 07-12-2023 Cont ID  
Sent By lquinone Date 07-12-2023 Time 09:19 Rev Time 0.00
Received By lquinone Date 07-12-2023 Time 09:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 07-07-2023 Cont ID  
Sent By pleduc Date 07-07-2023 Time   Rev Time 0.00
Received By pleduc Date 07-07-2023 Time 15:47 Sent To  
Notes
2023-07-07 15:51:13FIRE HAS NO OBJECTIONS TO THE PROPOSED AND APPROVES.
  
 FIRE'S APPROVAL OF THIS SUBMITTED PROJECT MAY NOT
 CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 1) SUBMITTED PLANS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 303
  
 1.1.1 THIS STANDARD ALSO APPLIES TO SUPPORT FACILITIES
 AND STRUCTURES USED FOR CONSTRUCTION, REPAIR, STORAGE,
 HAULING AND
 LAUNCHING, OR FUELING OF VESSELS IF FIRE ON A PIER
 WOULD POSE AN IMMEDIATE THREAT TO THESE FACILITIES, OR
 IF A FIRE AT A REFERENCED
 FACILITY WOULD POSE AN IMMEDIATE THREAT TO A DOCKING
 FACILITY.
  
 1.1.2 THIS STANDARD APPLIES TO MARINAS AND FACILITIES
 SERVICING
 SMALL RECREATIONAL AND COMMERCIAL CRAFT, YACHTS, AND
 OTHER
 CRAFT OF NOT MORE THAN 300 GROSS TONS.
  
  
 2) THE FIRE DEPARTMENT SHALL BE PROVIDED WITH ACCESS TO
 THE PROPOSED.
  
 PER NFPA 303
 4.2.2 FIRE DEPARTMENT ACCESS.
 4.2.2.1 THE FIRE DEPARTMENT SHALL HAVE ACCESS TO
 FENCED, GATED, OR LOCKED GROUNDS OR PIERS.
 4.2.2.2 APPROPRIATE MEANS OF ACCESS SUCH AS KEYS,
 CARDKEYS, OR COMBINATIONS SHALL BE
 PROVIDED TO THE FIRE DEPARTMENT OR SHALL BE PERMITTED
 TO BE SECURED IN A LOCK BOX ON THE
 PREMISES ACCESSIBLE TO THE FIRE DEPARTMENT
  
  
 3) FIRE EXTINGUISHERS SHALL BE PROVIDED PER NFPA
 6.2 PORTABLE FIRE EXTINGUISHERS.
 6.2.1 PLACEMENT.
 6.2.1.1 PLACEMENT OF PORTABLE FIRE EXTINGUISHERS SHALL
 BE IN ACCORDANCE WITH CHAPTER 5 OF
 NFPA 10, STANDARD FOR PORTABLE FIRE EXTINGUISHERS,
 UNLESS OTHERWISE PERMITTED BY 6.2.1.1.1, 6.2.1.1.2,
 OR 6.2.1.1.3
 6.2.1.1.1 PLACEMENT OF PORTABLE FIRE EXTINGUISHERS ON
 PIERS
 AND ALONG BULKHEADS WHERE VESSELS ARE MOORED OR ARE
 PERMIT TED TO BE MOORED SHALL MEET THE FOLLOWING
 CRITERIA:
 (1) EXTINGUISHERS LISTED FOR CLASS A, CLASS B, AND
 CLASS C FIRES
 SHALL BE INSTALLED AT THE PIER/LAND INTERSECTION ON A
 PIER
 THAT EXCEEDS 25 FT (7.62 M) IN LENGTH.
 (2) ADDITIONAL FIRE EXTINGUISHERS SHALL BE PLACED SUCH
 THAT THE
 MAXIMUM TRAVEL DISTANCE TO AN EXTINGUISHER DOES NOT
 EXCEED 75 FT (22.86 M)
  
  
 4) A STANDPIPE SYSTEM IS REQUIRED PER NFPA 303
 6.4* FIRE STANDPIPE SYSTEMS.
 6.4.1 CLASS I STANDPIPE SYSTEMS SHALL BE PROVIDED FOR
 PIERS, BULKHEADS, AND BUILDINGS WHERE THE HOSE LAY
 DISTANCE FROM THE
 FIRE APPARATUS EXCEEDS 150 FT (45 M).
  
 5) A FIRE HYDRANT COULD NOT BE IDENTIFIED AND IF
 APPLICABLE SHALL BE REQUIRED.
  
 A HYDRANT WOULD BE REQUIRED FOR THE FDC STANDPIPE
 SYSTEM AND BE WITHIN 100' OF EACH OTHER PER NFPA 14
 6.6 HYDRANTS AND WATER SUPPLIES. HYDRANTS AND WATER
 SUPPLIES FOR FIRE PROTECTION IN MARINAS AND BOATYARDS
 SHALL BE PROVIDED IN
 ACCORDANCE WITH NFPA 13, STANDARD FOR THE INSTALLATION
 OF SPRINKLER SYSTEMS; NFPA 14, STANDARD FOR THE
 INSTALLATION OF STANDPIPE AND HOSE
 SYSTEMS; AND NFPA 24, STANDARD FOR THE INSTALLATION OF
 PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES
  
 6) ANY ELECTRICAL WORK OR ELECTRICAL SERVICE SHALL
 COMPLY WITH THE REQUIREMENT OF NFPA 70 AND NFPA 303
  
 5.1 NATIONAL ELECTRICAL CODE. THE REQUIREMENTS SET
 FORTH HEREIN SUPPLEMENT AND RELATE THE REQUIREMENTS OF
 NFPA 70,
 NATIONAL ELECTRICAL CODE, TO THE SPECIFIC CONDITIONS
 AND COMBINATIONS OF CONDITIONS FOUND IN MARINAS AND
 BOATYARDS AND SHALL
 BE FOLLOWED IN ADDITION TO ANY REQUIREMENTS FOUND IN
 NFPA 70, INCLUDING, BUT NOT LIMITED TO, ARTICLE 555.
  
 5.2 LISTED OR LABELED. ALL ELECTRICAL MATERIALS,
 DEVICES, APPLIANCES, FITTINGS, AND OTHER EQUIPMENT
 SHALL BE LISTED OR LABELED
 BY A QUALIFIED TESTING AGENCY AND SHALL BE INSTALLED
 AND CONNECTED IN ACCORDANCE WITH LISTING REQUIREMENTS
 AND/OR MANUFACTURERS INSTRUCTIONS.
  
 5.3 ELECTRICAL DATUM PLANE.
  
 5.3.1 A BENCH MARK INDICATING THE ELECTRICAL DATUM
 PLANE (SEE3.3.7) OF THE LAND AREA SHALL BE PERMANENTLY
 LOCATED ON SHORE
 IN THE MARINA OR BOATYARD.
  
 5.3.2 ELECTRICAL SERVICES SHALL BE DISCONNECTED FROM
 THE POWER SOURCE WHEN THE WATER LEVEL REACHES THE BENCH
 MARK FOR THE
 ELECTRICAL DATUM PLANE.
  
 5.3.3 ALL ELECTRICAL CONNECTIONS SHALL BE LOCATED AT
 LEAST 12 IN. (305 MM) ABOVE THE DECK OF A FLOATING
 PIER.
 5.3.4 ALL ELECTRICAL CONNECTIONS SHALL BE LOCATED AT
 LEAST 12 IN. (305 MM) ABOVE THE DECK OF A FIXED PIER
 BUT NOT BELOW THE
 ELECTRICAL DATUM PLANE. (SEE 5.12.1 FOR RECEPTACLE
 LOCATIONS.)
  
 5.9 ELECTRICAL INSTALLATION.
  
 5.9.1 WIRING ELECTRICAL EQUIPMENT AND MATERIALS
 INSTALLED ON PIERS, WHARVES, DOCKS, OR SIMILAR
 LOCATIONS, AND WIRING METHODS
 SHALL SPECIFICALLY CONFORM TO THE REQUIREMENTS OF
 ARTICLE 555 AND ANY OTHER APPLICABLE REQUIREMENTS OF
 NFPA 70, NATIONAL
 ELECTRICAL CODE.
  
 7) FIRE SHALL REVIEW ALL SUBMITTED PROJECT PLANS AT THE
 APPLICABLE TIME AND IN ACCORDANCE WITH THE REQUIREMENTS
 OF ALL APPLICABLE FIRE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PU-CS PUBLIC UTILITIES CUSTOMER SRVC
Rev No 1 Status F Date 07-13-2023 Cont ID  
Sent By mhurley Date 07-13-2023 Time 07:59 Rev Time 0.00
Received By mhurley Date   Time   Sent To  
Notes
2023-07-13 07:59:44PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -JUSTIFICATION SAID DOCK WILL HAVE POTABLE WATER. WHERE
 WILL THAT WATER COME FROM?
 -WILL DOCK HAVE FIRELINE WATER? IF SO, WHERE WILL THAT
 WATER COME FROM?
 RESPECTFULLY,
 MARK HURLEY [email protected]

Review Stop PW PUBLIC WORKS
Rev No 1 Status P Date 07-06-2023 Cont ID  
Sent By jbjoseph Date 07-06-2023 Time 13:30 Rev Time 0.00
Received By jbjoseph Date 07-06-2023 Time 13:30 Sent To  
Notes
2023-07-06 13:30:50NO COMMENTS.

Review Stop STORM STORMWATER
Rev No 1 Status P Date 07-13-2023 Cont ID  
Sent By tward Date 07-13-2023 Time 08:14 Rev Time 0.00
Received By tward Date 07-13-2023 Time 08:15 Sent To  
Notes
2023-07-13 08:15:37HOW WILL ADA ACCESS FROM THE SIDEWALK TO THE RAMP BE
 PROVIDED?
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 07-10-2023 Cont ID  
Sent By vnoel Date 07-10-2023 Time 13:29 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2023-07-10 13:30:571. SHOW CONNECTION TO EXISTING BICYCLE PATH.
 2. NEED TO REVIEW THE EXISTING BICYCLE AND BULKHEAD
 EASEMENTS.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 07-13-2023 Cont ID  
Sent By   Date 07-13-2023 Time   Rev Time  
Received By   Date 07-13-2023 Time   Sent To  
Notes
2023-07-13 06:15:291) PLEASE PROVIDE AND SHOWCASE THE PEDESTRIAN
 CONNECTION BETWEEN THE EXISTING WALKWAY AND THE DOCK
 RAMP
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 05-24-2024 Cont ID  
Sent By llouie Date 05-24-2024 Time   Rev Time 0.00
Received By llouie Date 05-24-2024 Time   Sent To  
Notes
2024-05-24 16:01:29REFERENCE: RESOLUTION NO. 266-23

Review Stop Z ZONING
Rev No 1 Status F Date 07-07-2023 Cont ID  
Sent By llouie Date 07-07-2023 Time   Rev Time  
Received By llouie Date 07-07-2023 Time   Sent To  
Notes
2023-07-07 08:49:34GENERAL COMMENTS:
  
 1. PROVIDE LETTERS FROM THE FOLLOWING PUBLIC UTILITIES
 CONFIRMING THAT THE PROPOSED PROJECT DOES NOT ENCROACH
 INTO THEIR EASEMENTS OR OTHERWISE INTERFERE WITH THE
 PROVISION OF THEIR SERVICES: AT&T, FPU.
  
 2. HOW WIDE IS THE RAMP? NO DIMENSION PROVIDED. PLEASE
 DIMENSION OUT THE RAMP IN THE SITE PLAN.
  
 3. ENGINEERING SERVICES DEPARTMENT TO PROVIDE COMMENTS
 ON THE ADA RAMP LOCATION.
  
  
 INSTRUCTIONS FOR RESUBMITTAL:
  
 * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FOUR
 (4) PAPER COPIES AND AN ELECTRONIC COPY OF ALL PLANS
 AND DOCUMENTS.
  
 * CHANGES ON THE RESUBMITTED PLANS MAY RESULT IN
 ADDITIONAL COMMENTS.
  
 * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE.
  
 * CONTACT LINDA LOUIE @ 561.822.1458 OR [email protected]
 IF THERE ARE ANY QUESTIONS.
  