Plan Review Details - Project Z23060037
Plan Review Stops For Project Z23060037
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 07-13-2023 Cont ID  
Sent By rbrown Date 07-13-2023 Time 10:27 Rev Time 0.00
Received By rbrown Date 07-13-2023 Time 10:27 Sent To  
Notes
2023-07-13 10:28:56DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. ELECTRIC VEHICLE CHARGING STATION. IF ELECTRIC
 VEHICLE (EV) CHARGING STATIONS ARE PROVIDED AT LEAST 1
 IN 25 MUST COMPLY WITH ACCESSIBLE PARKING SPACE
 REQUIREMENTS.
  
 3. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, BACKFLOW PREVENTERS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 4. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND
 CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF
 CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL
 NEIGHBORING PROPERTIES. THE CONTRACTOR SHALL SUBMIT A
 CONSTRUCTION PARKING PLAN TO THE ENGINEERING SERVICES
 DEPARTMENT.
  
 5. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status P Date 07-12-2023 Cont ID  
Sent By lquinone Date 07-12-2023 Time 10:00 Rev Time 0.00
Received By lquinone Date 07-12-2023 Time 10:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 07-07-2023 Cont ID  
Sent By pleduc Date 07-07-2023 Time   Rev Time 0.00
Received By pleduc Date 07-07-2023 Time 16:05 Sent To  
Notes
2023-07-07 16:06:01FIRE HAS NO OBJECTIONS TO THE PROPOSED AND APPROVES.
  
 FIRE'S APPROVAL OF THIS SUBMITTED PROJECT MAY NOT
 CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 IF APPLICABLE, FIRE SHALL REVIEW ALL SUBMITTED PROJECT
 PLANS AT THE APPLICABLE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE FIRE CODES AND
 STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop PU-CS PUBLIC UTILITIES CUSTOMER SRVC
Rev No 1 Status F Date 07-13-2023 Cont ID  
Sent By mhurley Date 07-13-2023 Time 11:32 Rev Time 0.00
Received By mhurley Date   Time   Sent To  
Notes
2023-07-13 11:31:59PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -BACKFLOW ASSEMBLY CALLED OUT FOR RELOCATION MUST BE
 REPLACED AS IT IS NOT LEAD FREE COMPLIANT. ALSO
 INDICATE RP TYPE, LEAD FREE, AND SIZE.
 -EXISTING METER AT WESTERN METER BOX IS 1 INCH SIZE.
 ACCOUNT HOLDER IS PALM BEACH COUNTY AND ADDRESS 901
 EVERNIA ST. #I IN UTILITY BILLING SYSTEM.
 -THERE IS NO EXISTING METER IN THE EASTERN METER BOX.
 -EASTERN BACKFLOW ASSEMBLY NEEDS TO BE LABELED AS RP
 TYPE AND LEAD FREE. PIPING UPSTREAM BACKFLOW ASSEMBLY
 CANNOT BE PVC. ALSO OLD PIPING MAY NEED TO BE REMOVED
 AND REPLACED UNDER SIDEWALK.
 RESPECTFULLY,
 MARK HURLEY [email protected]

Review Stop PW PUBLIC WORKS
Rev No 1 Status P Date 07-12-2023 Cont ID  
Sent By   Date 07-12-2023 Time   Rev Time 0.00
Received By   Date 07-12-2023 Time   Sent To  
Notes
2023-07-12 09:48:38CONDITIONS OF APPROVAL:
 1- SHOULD THE TEMPORARY PARKING BE UTILIZED FOR STORAGE
 OF ANY SANITATION GARBAGE CONTAINERS, THE
 STORAGE/STAGING LOCATION OF THE CONTAINER(S) SHALL BE
 REVIWED AND APPROVED BY DEPARTMENT OF PUBLIC WORKS.
 2- ALL THE PARKING STALL PAINTING SHALL COMPLY WITH THE
 CITY`S MUNICIPAL CODE SECTION 94-485 AND FLORIDA
 STATUES [553.5041 F.S.].
 3- ALL STRIPING AND SIGNAGE SHALL COMPLY WITH THE
 LATEST CITY OF WEST PALM BEACH STANDARD DETAILS AND
 MEET THE M.U.T.C.D. LATEST EDITION.
 4. ALL PAVEMENT MARKING , SIGNING AND SIDEWALK DAMAGED
 DURING CONSTRUCTION SHALL BE RESTORED.
  
  
 DEPT. OF PUBLIC WORKS
 MATT HEJAZI
 [email protected]
 561-822-2045
  

Review Stop STORM STORMWATER
Rev No 1 Status F Date 07-13-2023 Cont ID  
Sent By tward Date 07-13-2023 Time 08:19 Rev Time 0.00
Received By tward Date 07-13-2023 Time 08:20 Sent To  
Notes
2023-07-13 08:19:46THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL. ONLY THE PLANS FOR THE PARKING LOT
 BETWEEN THE ALLEY AND EVERNIA ST. WAS REVIEWED.
  
 1. THE INVERT ELEVATION OF THE BLEEDER WILL ESTABLISH
 THE MAXIMUM VALUE FOR H2 IN THE EXFILTRATION TRENCH
 EQUATION.
  
 2. REMOVE THE PARKING SPACE NUMBERING FROM ALL PLAN
 SHEETS EXCEPT THE SITE PLAN.
  
 3. PGD PLAN SHOWS EXISTING 15-INCH RCP SOUTH OF THE
 CONTROL STRUCTURE. CONTROL STRUCTURE DETAIL SHOWS
 18-INCH RCP.
  
 4. REVIEW LABEL FOR THE INVERTED DEBRIS BAFFLE SHOWN ON
 THE PLAN VIEW OF THE CONTROL STRUCTURE DETAIL. IT LISTS
 TOP AND BOTTOM AS BEING CLOSED. SECTION A-A LISTS THE
 TOP AS BEING OPEN.
  
 5. PARKING LOT SECTION ON SHEET C-06 CALLS OUT ONE LIFT
 OF 1-INCH FC9.5 ASPHALT AND 6-INCH LIMEROCK BASE.
 STANDARD ASPHALT PAVEMENT DETAIL ON SHEET C-07 CALLS
 OUT TWO LIFTS OF 1-INCH SP9.5 ASPHALT AND 8 INCH
 LIMEROCK BASE.
  
 6. PROVIDE A PRB DETAIL.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP
 CRITERIA. STORMWATER CALCULATIONS WILL BE REVIEWED WITH
 THE ENGINEERING PERMIT SUBMITTAL.
  
 2. PROVIDE COPY OF SFWMD ERP AND FDEP NPDES
 CONSTRUCTION PERMIT BEFORE START OF CONSTRUCTION.
  
 3. PROVIDE EROSION AND SEDIMENT CONTROL PLAN WITH THE
 ENGINEERING PERMIT SUBMITTAL.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 07-11-2023 Cont ID  
Sent By vnoel Date 07-11-2023 Time 07:14 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2023-07-11 07:29:541. PROPOSED RESTRIPING OF NORTHERN LOT SHOULD NOT
 INCLUDE ALLEY.
 2. SHOW EXISTING CURB CUT IN VICINITY OF PROPOSED
 ENTRANCE OFF EVERNIA.
 3. SHEET C-09 REFERS TO SHEET C-09 FOR DETAIL OF
 METER/BACKFLOW RELOCATION.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 07-17-2023 Cont ID  
Sent By   Date 07-17-2023 Time   Rev Time 0.00
Received By   Date 07-17-2023 Time   Sent To  
Notes
2023-07-17 20:31:441) UNLESS AN ALLEY ABANDONMENT APPLICATION HAS BEEN
 SUBMITTED, PUBLIC ACCESS AND USAGE MUST BE MAINTAINED.
 THUS, NO FACILITIES COULD BE BUILT UPON THE ALLEY NOR
 PARKING ALLOWED THROUGHOUT. PLEASE REVISE THE SITE
 PLANS ACCORDINGLY
 2) RELOCATE THE PARKING STALLS AND EXTEND THE INTERNAL
 LANDSCAPE HIGHLAND FRONTING THE DRIVEWAY ON EVERNIA;
 SUCH REVISION WOULD IMPROVE INTERNAL CIRCULATION AND
 SAFETY BY REDUCING THE NUMBER OF VEHICULAR CONFLICT
 POINTS. MOREOVER, SUCH CONFIGURATION WOULD ALLOW BETTER
 PLACEMENT OF THE INTERNAL STOP LOCATION JUST EAST OF
 THE DRIVEWAY
 3) PLEASE REDUCE THE SIZE OF THE CONTOUR LINES FOR LOT
 DESIGNATION AND PROPERTY LINES, AS THEY ARE OCCLUDING
 SEVERAL REVIEW ITEMS
 4) SHEET C-10. PLEASE REMOVE UTILITY LINES-RELATED
 ITEMS/LAYER. SHOWCASE EXISTING AND PROPOSED PAVEMENT
 MARKINGS ALONG EVERNIA AND DATURA, INCLUSIVE OF TRAVEL
 LANES, ON-STREET PARKING, AND ALL TRANSPORTATION
 FEATURES ON THE OPPOSITE SIDE OF THE ROAD FRONTING THE
 PROPOSED DEVELOPMENT (I.E. CURB CUTS, PAVEMENT
 MARKINGS, SIDEWALK). PROVIDE PROPER LABELING AND
 DIMENSIONING FOR EACH ELEMENT
 5) PROVIDE DETAILS OF DRIVEWAY APRON AND SIDEWALK
 TRANSITION. PLEASE PROVIDE DOCUMENT NAME OR SHEET
 NUMBER CONTAINING SUCH INFORMATION
 6) PROVIDE THE NUMBER OF METERED STALLS THAT ARE BEING
 REMOVED OR RELOCATED, IF ANY
 7) IS VALET SERVICE PROPOSED OR PLANNED? IF SO, PROVIDE
 A THOROUGH OPERATIONAL ANALYSIS
 8) ARE THERE ANY BUS STOPS BEING IMPACTED?
 9) IS THE PROPOSED DEVELOPMENT IMPACTING AN EXISTING
 BICYCLE FACILITY?
 10) PROVIDE A CONSTRUCTION MANAGEMENT PLAN. PLEASE
 REFER TO CITY CODE 86-246 FOR DETAILS.
 11) ARE THERE ANY GATES PROPOSED? IF SO, CLEARLY
 SHOWCASE THE REQUIRED 20 FEET SETBACK DISTANCE FROM THE
 BACK OF THE SIDEWALK
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 07-13-2023 Cont ID  
Sent By ckimmerl Date 07-13-2023 Time 11:59 Rev Time 0.00
Received By ckimmerl Date 07-13-2023 Time 11:54 Sent To  
Notes
2023-07-13 11:59:001. CITY STAFF TO PROVIDE APPLICANT WITH PARAMETERS OR A
 CONDITION SPECIFYING WHAT HAPPENS TO THE SITE OR IS
 FURTHER REQUIRED AFTER THE 24 MONTH TEMPORARY WINDOW
 EXPIRES. STAFF TO WORK WITH APPLICANT AND TO PROVIDE
 DETAILS ON HOW AN EXTENSION IS GRANTED/APPROVED, AND
 WHAT CONDTIONS THE SITE/LOT WILL BE SUBJECT TO POST-24
 MONTHS.
  
 2. WHILE NOT IN SCOPE OF WORK, THE CONNECTING NORTHERN
 PARKING LOT AND SPACES UTILIZE THE EXISTING ALLEY.
 CANNOT HAVE SPACES OCCUPYING THE ALLEYWAY.
  
 3. JUSTIFICATION STATEMENT MENTIONS REVISION AND
 REMOVAL OF ALL INSTALLED IMPROVEMENTS AFTER THE
 TEMPORARY PARKING LOT EXPIRES, PLEASE PROVIDE A SET OF
 PLANS OR EXPLAIN IN DETAIL WHAT WILL HAPPEN TO THE SITE
 POST-TEMPORARY PARKING LOT.
  
  
 CHRIS KIMMERLY, AICP