Plan Review Details - Project Z23060022
Plan Review Stops For Project Z23060022
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 07-11-2023 Cont ID  
Sent By swelter Date 07-11-2023 Time 16:25 Rev Time 0.00
Received By swelter Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 07-12-2023 Cont ID  
Sent By rbrown Date 07-12-2023 Time 21:25 Rev Time 0.00
Received By rbrown Date 07-12-2023 Time 21:25 Sent To  
Notes
2023-07-12 21:28:56DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. ACCESSIBLE ROUTE. THE SITE PLAN DOES NOT SHOW A
 WHEELCHAIR ACCESSIBLE ROUTE FROM THE SIDEWALK TO THE
 BUUILDING ENTRANCE. WHEN SUBMITTED FOR PERMIT, THE
 PLANS SHALL SHOW AT LEAST ONE ACCESSIBLE ROUTE,
 COMPLYING WITH SECTIONS 206.2 AND 402.2 OF FLORIDA
 ACCESSIBILITY CODE, FROM THE PUBLIC RIGHT-OF-WAY TO ALL
 ACCESSIBLE BUILDING OR FACILITY ENTRANCES.
  
 3. ELECTRIC VEHICLE CHARGING STATION. IF ELECTRIC
 VEHICLE (EV) CHARGING STATIONS ARE PROVIDED AT LEAST 1
 IN 25 MUST COMPLY WITH ACCESSIBLE PARKING SPACE
 REQUIREMENTS.
  
 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 5. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND
 OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT,
 COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF
 OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED.
  
 6. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, BACKFLOW PREVENTERS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 7. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND
 CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF
 CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL
 NEIGHBORING PROPERTIES. THE CONTRACTOR SHALL SUBMIT A
 CONSTRUCTION PARKING PLAN TO THE ENGINEERING SERVICES
 DEPARTMENT.
  
 8. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 9. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION
 OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING,
 CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT
 (561) 805 6659, OR BY EMAIL: [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 07-12-2023 Cont ID  
Sent By lquinone Date 07-12-2023 Time 11:09 Rev Time 0.00
Received By lquinone Date 07-12-2023 Time 11:08 Sent To  
Notes
2023-07-12 11:09:30Z23060022 ??? SUBMITTAL PPRC COMMENTS ??? 1ST REVIEW
  
 COMMENTS FROM LINDA M. QUINONES- CINTRON, PROJECT
 COORDINATOR, ENGINEERING SERVICES AT [email protected]
 GENERAL:
 O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (Z-XXXXXXXX).
 O THE CITY OF WEST PALM BEACH HAS A NUMBER OF
 REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY
 AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND
 WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE
 DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK
 BELOW:
 A. HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WP
 B_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FUL
 L-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97
 B1960045731D3658206F27451722716EF
 B. THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE
 FOUND HERE:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
 C. ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM
 BEACH, FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08,
 ADOPTED SEPT. 22, 2008. (SUPPLEMENT NO. 18)
 CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL,
 SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER
 SERVICE FACILITIES OF THE CITY.
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
 O AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, REFER TO THE LINK BELOW:
 A. HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PU
 BLICATIONS/BACKFLOW-CROSS-CONNECTION- CONTROL-MANUAL
 O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1079 FOR FURTHER
 ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION
 ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD
 SURVEY, POT-HOLING, SOFT DIGS ETC.
 O PROVIDE EXISTING AND PROPOSED PERVIOUS AND IMPERVIOUS
 DATA.
  
 BACKFLOW ASSEMBLY AND METERS:
 O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER
 SERVICES AND WATER METERS, ALONG WITH WHAT IS HAPPENING
 TO THEM.
 O SHOW EXISTING AND PROPOSED DEDICATED UTILITY
 EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO
 PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO
 STRUCTURES WITHIN EASEMENT.
 O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION
 OF WATER METER AND BACKFLOW
 PREVENTION.
 O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE
 NOTE USC APPROVED).
  
 WATER/WASTEWATER PLAN:
 O PROVIDE VERTICAL DATUM AND DATUM CONVERSION
 INFORMATION (NAVD 1988 AND NGVD 1929).
 O PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE
 STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC.
 O PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND
 DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND
 SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH
 PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE
 AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS,
 BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO
 BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS,
 DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS,
 ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT
 ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF
 SANITARY SEWER LINES.
 O GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR
 SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW.
 O DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN
 VIEW FOR ALL SANITARY AND STORM SEWERS.
 O PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED
 UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC,
 ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION
 FACILITIES INCLUDING PIPE SIZE AND MATERIAL LOCATED IN
 THE RIGHT-OF-WAY.
 O PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER
 AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD
 DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS. PLEASE
 INCLUDE FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES INCLUDING PIPE SIZE AND
 MATERIAL LOCATED IN THE RIGHT-OF-WAY.
 O PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER ALONG
 ENTIRE PROJECT FRONTAGE (CONDITION OF SITE PLAN
 APPROVAL).
 O CUT AND CAP UTILITIES NOT IN USE AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 ROW.
 O WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL
 BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY
 PROPOSED LENGTH IN FEET.
 O CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY
 SEWER ARE REQUIRED.
 O PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE
 JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET.
 O ADD NOTE TO PLANS SPECIFYING CITY???S DOWNSTREAM LIFT
 STATION NUMBER.
 O PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR
 PROPOSED SANITARY LATERALS.
 O LABEL WATER LINES AS PRIVATE WHERE APPLICABLE.
 O PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN
 OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER.
  
 FORMAL ENGINEERING REVIEW:
 O FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES
 NOI REQUIREMENTS WILL BE ENFORCED.
 - AN NOI IS REQUIRED FOR PROJECTS THAT:
 - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS
 THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF
 DEVELOPMENT OR SALE;
 - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE
 STATE OR TO SURFACE WATERS OF THE STATE THROUGH A
 MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4).
 - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF
 CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION
 THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL
 SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT
 OF THE 10-2 CERTIFICATION.
 O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE
 EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS.
 O FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF
 WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS.
 O FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING
 APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT
 SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING
 SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED
 LEAD-FREE DESIGN.
 O FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES
 ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY
 LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT
 PARCELS.
 O FOR FORMAL ENGINEERING SUBMITTAL, IF WATER LINES ARE
 BEING REPLACED IN ROW, SHOW ADJACENT PARCEL ADDRESSES.
 O FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO PROVIDE
 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF
 PROPOSED TRENCH IN CITY MAINTAINED ROADWAY AREAS PER
 CITY OF WPB STANDARD DETAIL GC-8.
 O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE
 CALCULATIONS OF PERVIOUS AND IMPERVIOUS AREAS FOR
 PROPOSED IMPROVED AREAS.
  
 QUESTIONS AND COORDINATION CONTACTS:
 O MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR WITH
 CITY OF WPB PUBLIC UTILITIES, REGARDING PLACEMENT OF
 BACKFLOW DEVICES AND WATER METERS. CONTACT HIM AT
 561-822-2262 OR [email protected]
 O RICKY ELIZONDO, PROJECT ENGINEER, PUBLIC UTILITIES
 DEPARTMENT AT 561-494-1101 OR [email protected]
 O TRACY WARD, SR. STORMWATER ENGINEER, ENGINEERING
 SERVICES DEPT. AT 561-494-1120 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 07-07-2023 Cont ID  
Sent By pleduc Date 07-07-2023 Time   Rev Time 0.00
Received By pleduc Date 07-07-2023 Time 14:07 Sent To  
Notes
2023-07-07 14:09:37THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE DEPARTMENT.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT. THE FOLLOWING COMMENTS ARE INTENDED
 TO PROVIDE GUIDANCE FOR BUILDING PLAN SUBMITTAL.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING(S) SHALL COMPLY
 WITH THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION
 CODE, INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE
 CODES.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE PER THE FLORIDA FIRE PREVENTION CODE.
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED, AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 THE PROPOSED LOCATION OF THE FIRE HYDRANT AND FDC SHALL
 BE WITHIN 100' OF EACH OTHER AND CLOSELY COORDINATED
 WITH THE BUREAU OF FIRE PREVENTION.
  
 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE.
  
 FOR ANY LIFE SAFETY ENGINEERED SYSTEM, I.E FIRE
 SPRINKLER AND FIRE ALARM, ENSURE THEY COMPLY WITH THE
 REQUIREMENTS OF F.A.C. 61G AND SUBMITTED WITH THE
 MASTER PERMIT.
  
 9A. THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE
 LOCATIONS SHALL MEET AND BE INSTALLED PER THE
 REQUIREMENTS OF NFPA 24 AND SHALL BE COORDINATED WITH
 THE OFFICE OF FIRE MARSHAL, THE CITY'S ENGINEERS
 OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S PLANNING
 AND ZONING OFFICE.
  
 10. COMPLETE LIFE SAFETY PLANS FOR THE OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, EXIT SEPARATION DISTANCES, COMMON PATHS OF
 TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, EMERGENCY
 LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE
 EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES
 AND EQUIPMENT.
  
 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE
 SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY
 DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS.
  
 12. AREAS OF REFUGE SHALL BE PROVIDED AS REQUIRED PER
 THE FLORIDA BUILDING CODE AND NFPA 101, CH 7, MEANS OF
 EGRESS.
  
 12A. ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE
 FIGHTER???S EMERGENCY OPERATIONS REQUIREMENTS OF ASME
 A17.1/CSA B44, SAFETY CODE FOR ELEVATORS.
  
 ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET
 MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN
 AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE
 IN THE HORIZONTAL POSITION.
  
 13. TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEMS.
  
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
  
 PENDING FIRE DEPARTMENT PORTABLE RADIO TESTING RESULTS
 AND FOUND UNACCEPTABLE, CONTACT WILL NEED TO BE MADE TO
 KEN DECKER, PALM BEACH COUNTY PUBLIC SAFETY RADIO
 SYSTEMS MANAGER, [email protected], 561-233-0837; FOR
 HIS TESTING, AS OUR RADIOS OPERATE ON THEIR SYSTEM FOR
 DETAILED RADIO FREQUENCY AND INSTALLATION INSTRUCTIONS.
  
 14. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
 15. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status F Date 07-13-2023 Cont ID  
Sent By relizond Date 07-13-2023 Time 12:05 Rev Time 0.00
Received By relizond Date 07-13-2023 Time 12:01 Sent To  
Notes
2023-07-13 12:05:39-DENOTE SIZE AND MATERIAL OF EXISTING UTILITIES
 -UNUSED LATERALS/SERVICES WILL REQUIRE REMOVAL UP TO
 MAIN
 -HARD TO DIFFERENTIATE MAINS AND SERVICES
 -SHOW ALL EXISTING AND PROPOSED VALVES AND
 APPURTENANCES
 -ENSURE 5 FOOT RADIAL CLEARANCE FOR BOTH METER BOX AND
 CLEANOUT
 -SHOW ALL EXISTING DRY UTILITIES
 -CCTV REQUIRED IN ORDER TO CONFIRM LOCATIONS OF
 EXISITNG LATERALS
 -EXHIBIT ALL UTILITY CROSSINGS BETWEN PROPOSED AND
 EXISTING UTILITIES
 -DENOTE THE DOWNSTREAM LIFT STATION THAT SERVES THE
 PROJECT AREA
 -INCLUDE LEGEND AND DATUM CONVERSION
 -PROVIDE DEMAND CALCULATIONS TO DETERMINE SUFFICIENT
 FLOW SERVED BY EXISTING PIPES
  

Review Stop PU-CS PUBLIC UTILITIES CUSTOMER SRVC
Rev No 1 Status F Date 07-06-2023 Cont ID  
Sent By mhurley Date 07-06-2023 Time 11:47 Rev Time 0.00
Received By mhurley Date   Time   Sent To  
Notes
2023-07-06 11:46:56PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -JUSTIFICATION STATEMENT SAYS THAT THE PROPERTY IS ON
 THE NORTH SIDE OF ALPHA ST., BUT PLANS SEEM TO SHOW IT
 ON THE SOUTH SIDE.
 -1.5 INCH WATER METER HAS 2 INCH WATER SERVICE PIPING
 BETWEEN MAIN AND METER PER STANDARD DETAILS AND AML.
 -SPECIFICALLY ADD SIZE OF BACKFLOW ASSEMBLY ON THE
 LABEL.
 -VERIFY IF THE NEW BUILDING WILL HAVE FIRE SPRINKLERS.
 IF SO, WILL NEED SEPARATE DEDICATED FIRELINE WATER
 SERVICE WITH DETECTOR BACKFLOW ASSEMBLY.
 -SHOW UTILITIES FROM ENGINEERING PLAN ON LANDSCAPING
 PLAN. ENSURE THAT THERE IS SUFFICIENT DISTANCE BETWEEN
 PLANTS AND UTILITIES.
 RESPECTFULLY,
 MARK HURLEY [email protected]

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 07-06-2023 Cont ID  
Sent By jbjoseph Date 07-06-2023 Time 12:22 Rev Time 0.00
Received By jbjoseph Date 07-06-2023 Time 12:24 Sent To  
Notes
2023-07-06 12:23:50PLEASE PROVIDE THE FOLLOWING:
 1. LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID
 WASTE VOLUME PRODUCED ALONG WITH THE SIZE, TYPE AND
 QUANTITY OF THE CONTAINER (I.E. DUMPSTER/COMPACTOR)
 THAT WILL BE FOR THE SANITATION SERVICE.
  
 2. DUMPSTER ENCLOSURE DETAILS FOR SANITATION SERVICE
 (I.E. SOLID WASTE CONTAINER(S) TYPE, COLLECTION
 LOCATION, ETC.). FOR A FREESTANDING SITE DUMPSTER
 ENCLOSURE. THE ENCLOSURE SHALL COMPLY WITH THE LATEST
 REVISION OF CITY OF WEST PALM BEACH GENERAL
 CONSTRUCTION GARBAGE ENCLOSURE STANDARD. GC-7
  
 BRUCELY A. JOSEPH
 PUBLIC WORKS PROGRAM MANAGER
 [email protected]
 561-494-1141

Review Stop STORM STORMWATER
Rev No 1 Status F Date 07-13-2023 Cont ID  
Sent By tward Date 07-13-2023 Time 07:41 Rev Time 0.00
Received By tward Date 07-13-2023 Time 07:42 Sent To  
Notes
2023-07-13 07:41:51THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. THE CITY'S OFFICIAL VERTICAL DATUM PER CITY CODE
 SECTION 78-9 IS NGVD1929. THE NAVD1988 VERTICAL DATUM
 MAY BE USED IF THE CONVERSION EQUATION BETWEEN NAVD1988
 AND NGVD1929 IS PROVIDED. LIST THE CONVERSION EQUATION
 TO NGVD1929 ON THE SURVEY AND EVERY PLAN SHEET WITH
 ELEVATION INFORMATION.
  
 2. MOVE THE CONSTRUCTION ENTRANCE OUT OF THE RIGHT OF
 WAY.
  
 3. CONSTRUCT TYPE D CURB ALONG THE EDGE OF PAVEMENT
 ALONG THE FRONTAGE TO THE WEST DRIVEWAY OF 1320 ALPHA
 ST.
  
 4. SECTION A-A (SHEET 3 OF 5) CREATE A SWALE ALONG THE
 BACK OF SIDEWALK/RIGHT OF WAY TO PREVENT RUNOFF FROM
 FLOWING DIRECTLY OVER THE SIDEWALK.
  
 5. SECTION D-D (SHEET 3 OF 5) CREATE A SWALE ALONG THE
 PROPERTY LINE TO PREVENT RUNOFF FROM FLOWING DIRECTLY
 ONTO THE ADJACENT PROPERTY.
  
 5. CAN THE PROPOSED BUILDING BE MOVED NORTHWARD TO
 PROVIDE MOVE GREEN SPACE (RETENTION AREA) FOR
 STORMWATER RUNOFF? THE SITE APPEARS TO SLOPE FROM NORTH
 TO SOUTH. PER THE FLORIDA BUILDING CODE, RUNOFF IS NOT
 TO FLOW ONTO ADJACENT PROPERTIES.
  
 6. LABEL EXISTING UTILITIES (DIAMETER/MATERIAL) IN THE
 RIGHT OF WAY.
  
 7. SHOW MILL AND RESURFACING LIMITS FOR THE PAVEMENT
 CUTS IN THE RIGHT OF WAY.
  
 8. SHOW UTILITIES ON THE LANDSCAPE PLANS.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP
 CRITERIA. STORMWATER CALCULATIONS WILL BE REVIEWED WITH
 THE ENGINEERING PERMIT SUBMITTAL.
  
 2. PROVIDE COPY OF SFWMD ERP AND FDEP NPDES
 CONSTRUCTION PERMIT BEFORE START OF CONSTRUCTION.
  
 3. PROVIDE EROSION AND SEDIMENT CONTROL PLAN WITH THE
 ENGINEERING PERMIT SUBMITTAL.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 07-10-2023 Cont ID  
Sent By vnoel Date 07-10-2023 Time 07:06 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2023-07-10 09:31:111. ADD CONVERSION TO NGVD-29 TO SURVEY AND ENG. PLANS.
 2. NEED TO RELEASE EXISTING UNITY OF TITLE AND APPLY
 FOR UNITY OVER ENTIRE PARCEL. BOTH APPLICATIONS ARE
 MADE THRU ENGINEERING.
 3. NEED LETTER FROM HCD CONFIRMING IT IS AN APPROVED
 AFFORDABLE/WORKFORCE HOUSING PROJECT.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 07-13-2023 Cont ID  
Sent By   Date 07-13-2023 Time   Rev Time  
Received By   Date 07-13-2023 Time   Sent To  
Notes
2023-07-13 05:40:28TRAFFIC COMMENTS
 1) PROVIDE COUNTY TPS LETTER, ONCE AVAILABLE
 2) THE PARKING WAIVER REQUEST WOULD REQUIRE PROPER
 TRANSPORTATION DEMAND MANAGEMENT (TDM) MEASURES. PLEASE
 PROVIDE DETAILS OF PERTINENT AND EFFECTIVE TDMS
  
 SITE COMMENTS
 3) PROVIDE A TRANSPORTATION SPECIFIC SITE PLAN FOR THE
 GROUND FLOOR. SHOWCASING TRANSPORTATION RELATED
 FEATURES (E.G. ROADWAY WIDTHS, DRIVING AISLES, PARKING
 STALLS, SIDEWALK, CURB, GUTTER, DRIVEWAY, GATES,
 CROSSWALKS, VISIBILITY TRIANGLE, CORNER & DRIVEWAY
 SEPARATION DISTANCES, SLOPES, ETC.) PROPERLY LABELED
 AND DIMENSIONED
 4) IN THE TRANSPORTATION SITE PLAN, PLEASE SHOWCASE
 BASIC CURB DETAILS (E.G. DRIVEWAY, CURB CUTS, PAVEMENT
 MARKINGS, PARKING STALLS, ETC.) ON THE OPPOSITE SIDE OF
 THE ROADS SURROUNDING THE PROPOSED DEVELOPMENT
 5) PROVIDE A SIGNAGE AND PAVEMENT MARKING PLAN.
 INCLUSIVE OF ALL FEATURES WITHIN THE PROPOSED
 DEVELOPMENT AND ALONG ALL ROADS FRONTING THE SITE. SUCH
 PLAN CAN BE INSERTED IN THE TRANSPORTATION SPECIFIC ONE
 6) PROVIDE AUTOTURN ANALYSIS FOR GARBAGE TRUCK AND/OR
 SERVICE VEHICLES DRIVING IN AND OUT OF THE PROPOSED
 DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES AND WHEEL
 PATHS CLEARLY DISTINCT AND DEFINED IN DIFFERENT COLORS.
 PROVIDE THE ANALYSIS IN A SEPARATE SHEET. PLEASE
 PROVIDE DOCUMENT NAME AND SHEET NUMBER
 7) PARKING STALLS LOCATED AT THE END OF EACH ROW DO NOT
 SEEM TO PROVIDE PRACTICAL MANEUVERING. PLEASE PROVIDE
 AUTOTURN FOR EACH OF SUCH STALLS TO PROVE THEIR
 FEASIBILITY
 8) PROVIDE A CONSTRUCTION MANAGEMENT PLAN. PLEASE REFER
 TO CITY CODE 86-246 FOR DETAILS.
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 06-28-2023 Cont ID  
Sent By eschneid Date 06-28-2023 Time 12:13 Rev Time 6.00
Received By eschneid Date 06-28-2023 Time 12:13 Sent To  
Notes
2023-06-28 12:13:59CASE NO. FSPR 23-08
 VITA NOVA EXPANSION
 1330 ALPHA STREET
  
 - CONTACT ERIC SCHNEIDER @ 561-822-1446,
 [email protected]
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF TWO
 (2) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - AT SUCH TIME THAT THE PPRC COMMENTS HAVE BEEN
 RESUBMITTED AND BEEN SUFFICIENTLY ADDRESSED THE CASE
 WILL BE SCHEDULED FOR THE NEXT AVAILABLE CITY
 COMMISSION MEETING.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THE PPRC MEETING (BY SEPTEMBER 13,
 2023), THE PLANNING DIVISION MAY NOTIFY THE APPLICANT
 THAT THE CASE IS CONSIDERED WITHDRAWN. ANY FURTHER
 ACTION SHALL REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($300).
  
 - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 1) THIS APPLICATION IS A SPECIAL SITE PLAN REVIEW FOR
 AN AFFORDABLE HOUSING PROJECT IN ACCORDANCE WITH
 RESOLUTION NUMBER 306-22, WHICH REQUIRES CITY
 COMMISSION APPROVAL AND IS PROCESSED AS A FORMAL SITE
 PLAN REVIEW. THE PAYMENT SUBMITTED WITH THE APPLICATION
 WAS ONLY FOR AN INFORMAL SITE PLAN REVIEW. YOU ARE
 REQUIRED TO PAY AND ADDITIONAL $716 TO COVER THE
 DIFFERENCE IN THE SITE PLAN FEES ($500) AND THE
 ADVERTISING FEE FOR CITY COMMISSION ($216).
  
 2) PLEASE CLARIFY WHY THE DEED LISTS VITA NOVA OF
 RENAISSANCE VILLAGE, YET THE APPLICATION AND SUNBIZ
 SHOW IT AS VITA NOVA VILLAGE.
  
 3) THANK YOU FOR PROVIDING THE CONCURRENCY STATEMENT
 THAT THE APPLICATION COMPLIES WITH THE PBC TPS
 REQUIREMENTS; HOWEVER, THE CITY STILL REQUIRES THAT YOU
 PROVIDE A TPS LETTER FROM PALM BEACH COUNTY
 ENGINEERING.
  
 4) THE LETTERS OF NO OBJECTION FOR FPL, FPU, AT&T AND
 COMCAST ARE REQUIRED.
  
 5) THE JUSTIFICATION LETTER STATES THAT A UNITY OF
 TITLE WILL BE PROVIDED TO JOIN ALL THREE PROPERTIES IN
 ORDER TO UTILIZE THE FULL 0.77 ACRES FOR THE NUMBER OF
 UNITS PERMITTED UNDER RES. NO. 306-22. VINCE NOEL WILL
 DETERMINE IF THIS IS MAY BE DONE AS A UNITY OF TITLE OR
 IF A PLAT IS REQUIRED.
  
 6) CLARIFY WHY JUSTIFICATION STATEMENT LISTS 1316 ALPHA
 STREET AS HAVING FIVE UNITS, WHILE THE CITY HAS IT
 LISTED AS SIX UNITS. IF THERE ARE SIX UNITS, THEN THE
 JUSTIFICATION STATEMENT, DATA TABLES AND WAIVERS NEED
 TO BE UPDATED ACCORDINGLY.
  
 7) THE JUSTIFICATION STATEMENT MENTIONS THAT THERE ARE
 ON-SITE SUPPORT SERVICES. PLEASE LIST AND DESCRIBE WHAT
 THESE ON-SITE SERVICES ENTAIL. THIS MAY AFFECT THE USE
 CLASSIFICATION OF THE PROPERTY.
  
 8) THE ADDED UNITS PERMITTED BY RES. NO. 306-22 DO NOT
 REQUIRE A WAIVER TO THE SITE ACREAGE. PLEASE REMOVE
 THIS AS A WAIVER REQUEST FROM THE PLANS.
  
 9) RES. NO. 306-22 REQUIRES STREET-LEVEL
 THREE-DIMENSIONAL RENDERINGS FOR THE PROPOSED
 DEVELOPMENT AND ALL BUILDINGS ON ADJACENT SITES, PUBLIC
 SPACES AND STREETS TO ILLUSTRATE HOW THE NEW BUILDING
 RELATES TO THE SURROUNDING AREA. THE PROVIDED
 THREE-DIMENSIONAL RENDERINGS ONLY SHOW PROPOSED
 BUILDING AND NOT THE BUILDINGS ON ADJACENT SITES,
 PUBLIC SPACES AND STREETS SURROUNDING THE PROPOSED
 BUILDING.
  
 10) THE PROJECT IS REQUESTING A PARKING WAIVER TO
 PROVIDE NO PARKING SPACES FOR THE NEW UNITS (OVERALL
 50% PARKING REDUCTION). THE JUSTIFICATION STATEMENT
 LISTS REASONS TO SUPPORT THE WAIVER AS THE CURRENT
 PARKING LOT IS VACANT ON A DAY-TO-DAY BASIS AND THAT
 VITA NOVA VILLAGE ASSISTS RESIDENTS WITH TRANSPORTATION
 NEEDS, YET NO DATA WAS PROVIDED ON THE PARKING USE AND
 NO INFORMATION ON WHAT FORM THE TRANSPORTATION
 ASSISTANCE TAKES. ADDITIONALLY, THIS SITE IS LOCATED
 WITHIN A RESIDENTIAL AREA AND NOT IN CLOSE PROXIMITY TO
 MAJOR EMPLOYERS OR TRANSIT LINES. PLEASE PROVIDE BETTER
 JUSTIFICATION FOR THE PARKING WAIVER.
  
 11) BICYCLE PARKING IS REQUIRED AT A RATIO OF ONE SPACE
 FOR EVERY 20 AUTOMOBILE PARKING SPACES, OR FRACTION
 THEREOF, REQUIRED FOR THE USE. A TOTAL OF THREE BICYCLE
 PARKING SPACES ARE REQUIRED. THIS EQUATES TO TWO
 BICYCLE RACKS. THE TWO BICYCLE RACKS THAT ARE SHOWN
 ADJACENT TO THE NEW BUILDING DO NOT MATCH THE BICYCLE
 RACK DETAIL, NOR SO THEY SHOW ADEQUATE SPACE ADJACENT
 TO THE BUILDING OR ALONG THE WALKWAY TO THE BACK OF THE
 BUILDING. IT APPEARS THAT THE RACKS ARE ORIENTED THE
 WRONG WAY ON THE PLAN. SINCE IT DOES NOT APPEAR THAT
 THERE ARE ANY BICYCLE RACKS CURRENTLY ON THE SITE,
 STAFF SUGGESTS PUTTING ONE RACK AT THE NEW BUILDING AND
 INSTALLING THE OTHER RACK ADJACENT TO ONE OF THE
 EXISTING BUILDINGS TO PROVIDE CONVENIENT BICYCLE
 PARKING FOR MORE RESIDENTS.
  
 12) IS THERE AN OPPORTUNITY TO REORIENT THE WINDOWS ON
 AT LEAST ONE OF THE FLOORS TO FACING ALPHA STREET
 INSTEAD OF THE INTERIOR/NEIGHBORING LOT? THIS WOULD
 BREAK UP THE BLANK WALL ALONG ALPHA STREET.
  
 13) THE SITE PLAN DOES NOT MATCH THE CIVIL AND
 LANDSCAPE PLANS ON THE EAST AND WEST SIDES OF THE NEW
 BUILDING. ALL PLANS MUST BE CONSISTENT AND CODE
 COMPLIANT.
  
 14) THE SQUARE FOOTAGE OF THE PROPOSED BUILDING LISTED
 ON THE SITE PLAN DOES NOT MATCH THE SQUARE FOOTAGE
 LISTED ON THE ARCHITECTURAL PLAN. ALL PLANS MUST BE
 CONSISTENT AND CODE COMPLIANT.
  
 15) THE GRAVITY WALL AND GUIDERAIL EXCEED THE
 FENCE/WALL HEIGHT ALLOWANCE OF SIX (6) FEET WITHIN THE
 11.5-FOOT REAR SETBACK.
  
 16) THE GUIDERAIL MUST BE A DECORATIVE FENCE. PROVIDE A
 DETAIL SHOWING THE GUIDERAIL.
  
 17) THE BUILDING CROSS-SECTION SHOWS THE TOP OF THE
 SLAB AND THE GRADE SET AT THE SAME HEIGHT, YET THE
 CIVIL CROSS-SECTIONS SHOW THE FINISHED FLOOR AT LEAST
 ONE (1) FOOT LOWER THAN THE FINISHED FLOOR. THE
 ARCHITECTURAL CROSS-SECTION SHALL ACCURATELY DEPICT THE
 SITE CONDITIONS. NOTE: THIS MAY AFFECT THE HEIGHT OF
 THE STRUCTURE, SINCE IT IS MEASURED FROM THE FINISHED
 GRADE, NOT THE FINISHED FLOOR.
  
 18) WHILE DIMENSIONS WERE NOT PROVIDED, THE SIGN SHOWN
 ON THE FRONT OF THE BUILDING APPEARS LARGER THAN
 PERMITTED BY THE SIGN CODE.
  
 LANDSCAPE
  
 19) THE LANDSCAPE PLAN FAILS TO PROVIDE THE DISPOSITION
 OF WHAT IS LISTED AS TREE 34 ON THE SURVEY.
  
 20) PROVIDE HOW THE TREES PROPOSED TO REMAIN ON THE
 SITE WILL BE PROTECTED DURING CONSTRUCTION. NOTE: THE
 PALM TO BE RETAINED AT THE SOUTHWEST CORNER OF THE
 BUILDING APPEARS TO BE VERY CLOSE TO THE FOUNDATION AS
 WELL AS IN A LOCATION WHERE THE GRADE WILL BE CHANGED.
  
 21) THE CITY BASES ITS TREE MITIGATION ON THE CANOPY
 SIZE NOT DBH. PLEASE PROVIDE THE MITIGATION TABLE IN
 THIS FORMAT. PLEASE NOTE THAT SINCE THE OVERALL SITE IS
 DEFICIENT IN LANDSCAPE, THE MITIGATION SHALL OCCUR
 ON-SITE TO BRING THE SITE CLOSER TO CODE CONFORMITY AND
 NOT VIA PAYMENT INTO THE MITIGATION FUND. AN APPROVED
 TREE ALTERATION PERMIT IS REQUIRED PRIOR TO THE REMOVAL
 OF ANY TREES.
  
 22) THE LANDSCAPE PLAN SHALL SHOW THE PROPOSED WATER
 SERVICE, THE SANITARY LINE AND THE EXFILTRATION
 TRENCH/DRAINAGE LINES. THESE FEATURES SHALL NOT DISTURB
 THE EXISTING TREE ROOT SYSTEMS OR THE GROWTH POTENTIAL
 OF THE PROPOSED TREES.
  
 23) PROVIDE A SECTION DRAWING, TO SCALE, OF THE
 SOUTHERN PROPERTY LINE SHOWING HOW THE PROPOSED
 LANDSCAPE WILL BE INSTALLED IN RELATIONSHIP TO THE
 EXFILTRATION TRENCH, SWALE, FENCE AND GRAVITY WALL. THE
 VERTICAL AND HORIZONTAL SCALE SHALL BE THE SAME.
  
 24) PROVIDE THE SQUARE FOOTAGE OF THE FOOTPRINT OF THE
 BUILDING. STAFF IS UNABLE TO VERIFY THE 2,760 SQUARE
 FEET OF OPEN SPACE LISTED ON THE LANDSCAPE PLAN DATA
 TABLE. THE STAFF CALCULATION IS 3,463 SQUARE FEET OF
 OPEN SPACE. THIS DIFFERENCE AFFECTS THE REQUIRED AMOUNT
 OF LANDSCAPE.
  
 25) PROVIDE THE LINEAR FEET AROUND THE NEW BUILDING SO
 THAT STAFF CAN VERIFY THE AMOUNT OF FOUNDATION PLANTING
 THAT IS REQUIRED.
  
 26) WHILE THE PLAN IS TO JOIN THE DEVELOPMENT SITE INTO
 ONE LARGER PARCEL TO ALLOW MORE UNITS TO BE
 CONSTRUCTED, THE LANDSCAPE IS REQUIRED IF THIS IS A
 STAND-ALONE SITE. THIS INCLUDES THE EASTERN BUFFER
 LANDSCAPE AND THE 12 TREES REQUIRED BY THE NUMBER OF
 UNITS. IF THESE TREES CANNOT BE PLACED ON THE
 DEVELOPMENT SITE, THEY SHALL BE SPREAD ACROSS THE
 LARGER SITE TO ADDRESS THE EXISTING LANDSCAPE
 DEFICIENCIES.
  
 27) PROVIDE THE TOTAL SQUARE FOOTAGE OF THE LANDSCAPED
 AREA ON THE DEVELOPMENT SITE AND THE SQUARE FOOTAGE
 THAT WILL BE SODDED SO THAT STAFF CAN VERIFY THAT THE
 SODDED AREA IS LESS THAN 50% OF THE TOTAL LANDSCAPE
 AREA. NOTE: THE AMOUNT OF OPEN SPACE IS NOT TO BE USED
 FOR THIS CALCULATION SINCE OPEN SPACE ALSO INCLUDES
 AREAS THAT ARE NOT LANDSCAPED.
  
 28) THE PLANS SHOW OAK TREES WITHIN THE ALPHA STREET
 LANDSCAPE BUFFER. THERE ARE OVERHEAD LINES AT THIS
 LOCATION, WHICH DOES NOT SEEM TO COMPLY WITH THE FPL
 RIGHT TREE RIGHT PLACE STANDARD.
  
 29) THE LANDSCAPE CODE REQUIRES THAT AT LEAST ONE TREE
 SHALL BE PLANTED IN A REQUIRED BUFFER STRIP FOR EACH 30
 LINEAR FEET OR PORTION THEREOF. REQUIRED STREET TREES
 MAY BE CLUSTERED OR PLANTED IRREGULARLY AS DEEMED
 APPROPRIATE. CLUSTERING OF ALL REQUIRED TREES SHALL BE
 SUBJECT TO CITY APPROVAL. THE PLANS SHOW THE CLUSTERING
 OF TREES ALONG THE WESTERN PROPERTY LINE, WITH A GAP OF
 80 FEET BETWEEN TWO OF THE ORANGE GEIGER TREES. STAFF
 DOES NOT SUPPORT THE LARGE GAP AT THIS LOCATION. THE
 PROPOSED BUILDING, LOCATED FIVE (5) FEET FROM THE
 WESTERN PROPERTY LINE, WILL BE 40 FEET ABOVE THE GRADE
 OF THE NEIGHBORING ONE-STORY RESIDENTIAL STRUCTURE.
 THIS MASS NEEDS TO BE BROKEN UP BY LANDSCAPE SCREENING
 SINCE WITHOUT ADEQUATE SCREENING, THE PROPOSED BUILDING
 IS NOT IN CHARACTER WITH THE ADJACENT USE.
  
  
  

  Print