Plan Review Details - Project Z23040020
Plan Review Stops For Project Z23040020
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 07-13-2023 Cont ID  
Sent By swelter Date 07-13-2023 Time 09:33 Rev Time 0.00
Received By swelter Date 07-13-2023 Time 09:34 Sent To  
Notes
2023-07-13 09:34:41PROJECT IS EXEMPT FROM PUBLIC ART REQUIRMENT DUE TO THE
 FOLLOWING:
 THE LEGACY @ 45TH STREET AS PROPOSED IS A 100%
 AFFORDABLE HOUSING RENTAL DEVELOPMENT.
 THE CITY HAS MADE A CONDITIONAL COMMITMENT TO AWARD
 FEDERAL FUNDING TO THE PROJECT TO BENEFIT HOUSEHOLDS AT
 OR BELOW 80% AMI.
  
 FURTHER QUESTIONS CONTACT SYBILLE WELTER
 [email protected] OR 561.822.1521

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 07-12-2023 Cont ID  
Sent By rbrown Date 07-12-2023 Time 20:09 Rev Time 0.00
Received By rbrown Date 07-12-2023 Time 20:09 Sent To  
Notes
2023-07-12 20:12:01DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS
 SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT
 REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH
 COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963,
 OR BY EMAIL: [email protected]
  
 3. ELECTRIC VEHICLE CHARGING STATION. IF ELECTRIC
 VEHICLE (EV) CHARGING STATIONS ARE PROVIDED AT LEAST 1
 IN 25 MUST COMPLY WITH ACCESSIBLE PARKING SPACE
 REQUIREMENTS.
  
 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 5. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, BACKFLOW PREVENTERS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 6. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND
 CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF
 CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL
 NEIGHBORING PROPERTIES. THE CONTRACTOR SHALL SUBMIT A
 CONSTRUCTION PARKING PLAN TO THE ENGINEERING SERVICES
 DEPARTMENT.
  
 7. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 8. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION
 OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING,
 CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT
 (561) 805 6659, OR BY EMAIL: [email protected]
  
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 05-10-2023 Cont ID  
Sent By rbrown Date 05-10-2023 Time 20:47 Rev Time 0.00
Received By rbrown Date 05-10-2023 Time 20:47 Sent To  
Notes
2023-05-10 20:51:28DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 AS OF 5/10/23, INSUFFICIENT PLANS HAVE BEEN SUBMITTED
 FOR A MEANINGFUL REVIEW. NO ARCHITECTURAL PLANS HAVE
 BEEN SUBMITTED. THE SITE PLAN DOES NOT MAKE IT CLEARS
 AS TO WHAT IS THE FRONT WHAT IS THE REAR OF THE
 BUILDINGS. ARE THE WHEELCHAIR ACCESSIBLE RAMPS ONLY
 GOING TO THE REAR OF THE BUILDINGS? NEED MORE PLANS AND
 INFORMATION IN ORDER TO COMPLETE A REVIEW.
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status F Date 07-07-2023 Cont ID  
Sent By lquinone Date 07-07-2023 Time 14:29 Rev Time 0.00
Received By lquinone Date 07-07-2023 Time 14:29 Sent To  
Notes
2023-07-07 14:30:31 
 1. SHOW AND LABEL ANY EXISTING OR PROPOSED WATER
 SERVICES AND WATER METERS, ALONG WITH WHAT IS HAPPENING
 TO THEM- WATER MAIN INFORMATION IS NOT SHOWN ON SP-010
 2. SHOW EXISTING AND PROPOSED DEDICATED UTILITY
 EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO
 PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO
 STRUCTURES WITHIN THE EASEMENT- EASEMENTS CAN???T BE
 FOUND ON PLANS
 3. PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION
 OF WATER METER AND BACKFLOW PREVENTION.
 4. PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER
 AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD
 DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS. PLEASE
 INCLUDE FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES INCLUDING PIPE SIZE AND
 MATERIAL LOCATED IN THE RIGHT-OF-WAY.
 5. SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY
 TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT
 APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING
 PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM
 AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE
 PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER.
 6. PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER ALONG
 ENTIRE PROJECT FRONTAGE (CONDITION OF SITE PLAN
 APPROVAL)
 7. ADD NOTE TO PLANS SPECIFYING CITY???S DOWNSTREAM
 LIFT STATION NUMBER.
  
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 05-01-2023 Cont ID  
Sent By lquinone Date 05-01-2023 Time 13:52 Rev Time 0.00
Received By lquinone Date 05-01-2023 Time 13:51 Sent To  
Notes
2023-05-01 13:52:20Z23040020 ??? SUBMITTAL COMMENTS ??? 1ST REVIEW
  
 COMMENTS FROM LINDA M. QUINONES-CINTRON, PROJECT
 COORDINATOR, ENGINEERING SERVICES AT 561-494-1085
 [email protected]
 GENERAL:
 O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (Z-XXXXXXXX).
 O THE CITY OF WEST PALM BEACH HAS A NUMBER OF
 REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY
 AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND
 WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE
 DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK
 BELOW:
 A. HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WP
 B_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FUL
 L-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97
 B1960045731D3658206F27451722716EF
 B. THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE
 FOUND HERE:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
 C. ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM
 BEACH, FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08,
 ADOPTED SEPT. 22, 2008. (SUPPLEMENT NO. 18)
 CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL,
 SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER
 SERVICE FACILITIES OF THE CITY.
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
 O AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, REFER TO THE LINK BELOW:
 A. HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PU
 BLICATIONS/BACKFLOW-CROSS-CONNECTION- CONTROL-MANUAL
 O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1079 FOR FURTHER
 ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION
 ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD
 SURVEY, POT-HOLING, SOFT DIGS ETC.
 O PROVIDE EXISTING AND PROPOSED PERVIOUS AND IMPERVIOUS
 DATA.
  
 BACKFLOW ASSEMBLY AND METERS:
 O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER
 SERVICES AND WATER METERS, ALONG WITH WHAT IS HAPPENING
 TO THEM.
 O SHOW EXISTING AND PROPOSED DEDICATED UTILITY
 EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO
 PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO
 STRUCTURES WITHIN EASEMENT.
 O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION
 OF WATER METER AND BACKFLOW
 PREVENTION.
 O BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY
 OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER
 METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO
 PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE
 INSTALLED ABOVE-GROUND ONLY.
 O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE
 NOTE USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA.
  
 WATER/WASTEWATER PLAN:
 O PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND
 DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND
 SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH
 PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE
 AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS,
 BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO
 BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS,
 DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS,
 ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT
 ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF
 SANITARY SEWER LINES.
 O GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR
 SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW.
 O DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW FOR ALL
 SANITARY AND STORM SEWERS.
 O SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL.
 O PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED
 UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC,
 ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION
 FACILITIES INCLUDING PIPE SIZE AND MATERIAL LOCATED IN
 THE RIGHT-OF-WAY.
 O PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER
 AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD
 DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS. PLEASE
 INCLUDE FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES INCLUDING PIPE SIZE AND
 MATERIAL LOCATED IN THE RIGHT-OF-WAY.
 O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY
 TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT
 APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING
 AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE,
 MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS
 SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008
 FOR WATER.
 O PROVIDE FIRE FLOW TEST DATA.
 O PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND
 STORMWATER INFRASTRUCTURE ALONG ENTIRE PROJECT FRONTAGE
 (CONDITION OF SITE PLAN APPROVAL).
 O CUT AND CAP UTILITIES NOT IN USE AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 ROW.
 O WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL
 BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY
 PROPOSED LENGTH IN FEET.
 O CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY
 SEWER ARE REQUIRED.
 O PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE
 JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET.
 O ADD NOTE TO PLANS SPECIFYING CITY???S DOWNSTREAM LIFT
 STATION NUMBER.
 O PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR
 PROPOSED SANITARY LATERALS.
 O LABEL WATER LINES AS PRIVATE WHERE APPLICABLE.
 O PLEASE SHOW AND LABEL EXISTING AND PROPOSED GREASE
 TRAPS (IF ANY).
 O PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN
 OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER.
  
 FORMAL ENGINEERING REVIEW:
 O FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES
 NOI REQUIREMENTS WILL BE ENFORCED.
 - AN NOI IS REQUIRED FOR PROJECTS THAT:
 - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS
 THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF
 DEVELOPMENT OR SALE;
 - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE
 STATE OR TO SURFACE WATERS OF THE STATE THROUGH A
 MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4).
 - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF
 CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION
 THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL
 SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT
 OF THE 10-2 CERTIFICATION.
 O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE
 EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS.
 O FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF
 WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS.
 O FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING
 APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT
 SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING
 SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED
 LEAD-FREE DESIGN.
 O FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES
 ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY
 LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT
 PARCELS.
 O FOR FORMAL ENGINEERING SUBMITTAL, IF WATER LINES ARE
 BEING REPLACED IN ROW, SHOW ADJACENT PARCEL ADDRESSES.
 O FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO PROVIDE
 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF
 PROPOSED TRENCH IN CITY MAINTAINED ROADWAY AREAS PER
 CITY OF WPB STANDARD DETAIL GC-8.
 O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE
 CALCULATIONS OF PERVIOUS AND IMPERVIOUS AREAS FOR
 PROPOSED IMPROVED AREAS.
  
 QUESTIONS AND COORDINATION CONTACTS:
 O MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR WITH
 CITY OF WPB PUBLIC UTILITIES, REGARDING PLACEMENT OF
 BACKFLOW DEVICES AND WATER METERS. CONTACT HIM AT
 561-822-2262 OR [email protected]
 O COMMENTS FROM MIKE TECHNOW, PUB. UTILITIES ENGINEER,
 [email protected], 561-494-1047:
 O COMMENTS FROM RICKY ELIZONDO, PUB. UTILITIES PLANS
 EXAMINER, [email protected] , 561-494-1101:
 O COMMENTS FROM TRACY WARD, SR. STORMWATER ENGINEER,
 ENG. SERVICES DEPT. AT 561-494-1120 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 06-06-2023 Cont ID  
Sent By pleduc Date 06-06-2023 Time 09:42 Rev Time 0.00
Received By pleduc Date 06-06-2023 Time 09:42 Sent To  
Notes
2023-06-06 09:43:412ND REVIEW RESPONSE
  
 AFTER A REVIEW OF THE PPRC RESPONSE PACKET FOR THIS
 PROJECT, THE PREVIOUSLY SUBMITTED FIRE PREVENTION
 BUREAU COMMENTS APPEAR TO HAVE BEEN ADDRESSED.
  
 HOWEVER, THE BUREAU'S APPROVAL OF THIS SUBMITTED
 PROJECT DOES NOT CONSTITUTE ITS FINAL REVIEW OR
 APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE DEPARTMENT
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 05-05-2023 Cont ID  
Sent By pleduc Date 05-05-2023 Time   Rev Time 0.00
Received By pleduc Date 05-05-2023 Time 12:11 Sent To  
Notes
2023-05-05 12:16:53THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE DEPARTMENT.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT. THE FOLLOWING COMMENTS ARE INTENDED
 TO PROVIDE GUIDANCE FOR BUILDING PLAN SUBMITTAL.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING(S) SHALL COMPLY
 WITH THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION
 CODE, INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE
 CODES.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE PER THE FLORIDA FIRE PREVENTION CODE.
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED, AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 THE PROPOSED LOCATION OF THE FIRE HYDRANT AND FDC SHALL
 BE WITHIN 100' OF EACH OTHER AND CLOSELY COORDINATED
 WITH THE BUREAU OF FIRE PREVENTION.
  
 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM,
 ENSURE THEY COMPLY WITH THE REQUIREMENTS OF F.A.C. 61G
 AND SUBMITTED WITH THE MASTER PERMIT.
  
 9A. THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE
 LOCATIONS SHALL MEET AND BE INSTALLED PER THE
 REQUIREMENTS OF NFPA 24 AND SHALL BE COORDINATED WITH
 THE OFFICE OF FIRE MARSHAL, THE CITY'S ENGINEERS
 OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S PLANNING
 AND ZONING OFFICE.
  
 10. COMPLETE LIFE SAFETY PLANS FOR THE OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, EXIT SEPARATION DISTANCES, COMMON PATHS OF
 TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, EMERGENCY
 LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE
 EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES
 AND EQUIPMENT.
  
 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE
 SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY
 DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS.
  
 12. AREAS OF REFUGE SHALL BE PROVIDED AS REQUIRED PER
 THE FLORIDA BUILDING CODE AND NFPA 101, CH 7, MEANS OF
 EGRESS.
  
 12A. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7
 KEYWAY SYSTEM 6 OR MORE STORIES PER F.A.C.
  
 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTER???S
 EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA
 B44, SAFETY CODE FOR ELEVATORS.
  
 ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET
 MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN
 AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE
 IN THE HORIZONTAL POSITION.
  
 13. TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEMS.
  
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
  
 CONTACT WILL NEED TO BE MADE TO MARK FILLA, PALM BEACH
 COUNTY PUBLIC SAFETY RADIO SYSTEMS MANAGER,
 [email protected], 561-233-0837; AS OUR RADIOS OPERATE
 ON THEIR SYSTEM FOR DETAILED RADIO FREQUENCY AND
 INSTALLATION INSTRUCTIONS.
  
 14. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
 15. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 06-26-2023 Cont ID  
Sent By kdefranc Date 06-26-2023 Time 12:07 Rev Time 0.00
Received By kdefranc Date 06-26-2023 Time 12:05 Sent To  
Notes
2023-06-26 12:06:41FROM: KEVIE DEFRANC, SENIOR PLANNER 561-822-1449
 PROJECT: LEGACY AT 45TH STREET Z23040020
 JUNE 26, 2023
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PER SECTION 94-442(B)(1), PROVIDE
 LANDSCAPE PLANS SIGNED AND SEALED BY A REGISTERED
 LANDSCAPE ARCHITECT.
  
 2. SATISFIED. PROVIDE BOTH PHYSICAL HARDCOPIES AND
 ELECTRONIC COPIES OF THE LANDSCAPE PLANS.
  
 3. SATISFIED. PROVIDE A SEPARATE TREE DISPOSITION PLAN
 BASED ON A TREE SURVEY. INCLUDE EXISTING PALM AND
 CANOPY TREES IN THE RIGHT-OF-WAY AND ON ADJACENT
 PROPERTIES WITHIN 10 FEET OF THE PROPERTY LINE.
  
 4. SATISFIED. PER SECTION 94-443(D)(1), PROVIDE THE
 PROPOSED LANDSCAPE BUFFER WIDTH DIMENSIONS ON THE
 LANDSCAPE PLAN (SHEET NO. LP-1).
  
 5. SATISFIED. PROVIDE THE EXISTING AND PROPOSED
 EASEMENTS ON THE LANDSCAPE PLAN (SHEET NO. LP-1).
  
 6. NOT SATISFIED. PER SECTION 94-442(C)(2)(B), PROVIDE
 THE OPEN SPACE AREA CALCULATIONS (REQUIRED AND
 PROPOSED) ON THE LANDSCAPE PLAN (SHEET NO. LP-1).
  
 6/26/23 IN ACCORDANCE WITH SECTION 94-174(B)(6), THE
 MINIMUM REQUIRED OPEN SPACE AREA FOR PROPERTIES WITHIN
 THE INDUSTRIAL ZONING DISTRICT IS 40 PERCENT. UPDATE
 THE CALCULATIONS, ACCORDINGLY.
  
 7. PARTIALLY SATISFIED. PER SECTION 94-442(C)(2)(B),
 PROVIDE THE LANDSCAPE AREA CALCULATIONS (REQUIRED AND
 PROPOSED) ON THE LANDSCAPE PLAN (SHEET NO. LP-1).
  
 6/26/23 PROVIDE LENGTH OF EACH BUFFER IN CALCULATIONS.
  
 8. SATISFIED. PER SECTIONS 94-442(C)(2)(B) AND
 94-443(D), REVISE THE LANDSCAPE PLAN (SHEET NO. LP-1),
 ACCORDINGLY, AND PROVIDE THE TREES CALCULATIONS
 (REQUIRED AND PROPOSED) ON THE LANDSCAPE PLAN (SHEET
 NO. LP-1).
  
 9. SATISFIED. PER SECTION 94-442(C)(2)(B), AT LEAST ONE
 SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE FEET OF
 REQUIRED OPEN SPACE OR PORTION THEREOF. THEREFORE,
 PROVIDE THE SHRUBS CALCULATIONS (REQUIRED AND PROPOSED)
 ON THE LANDSCAPE PLAN (SHEET NO. LP-1).
  
 10. SATISFIED. PER SECTION 94-442(C)(2)(B), GRASS AREAS
 SHALL NOT EXCEED 60 PERCENT OF THE REQUIRED LANDSCAPE
 AREA. THEREFORE, PROVIDE THE GRASS AREAS CALCULATIONS
 (REQUIRED AND PROPOSED) ON THE LANDSCAPE PLAN (SHEET
 NO. LP-1).
  
 11. SATISFIED. PER SECTIONS 94-443(C)(3) AND (4),
 PROVIDE AN EXHIBIT SHOWING THE PARKING AREA SURFACE
 CALCULATIONS, PARKING SPACE AREAS AND LANDSCAPE AREAS.
 PROVIDE THE CALCULATIONS AND SHOW THE ACTUAL PROPOSED
 INTERIOR LANDSCAPE SQUARE FOOTAGE.
  
 12. NOT SATISFIED. PER SECTION 94-443(C)(3)(A), EACH
 ROW OF PARKING SPACES SHALL BE TERMINATED BY LANDSCAPED
 ISLANDS OF NOT LESS THAN EIGHT FEET IN WIDTH AND NOT
 LESS THAN THE LENGTH OF THE ADJACENT PARKING STALL.
 EACH LANDSCAPED ISLAND SHALL HAVE A MINIMUM RADIUS OF
 TWO AND ONE-HALF FEET AT ITS END SO AS TO ALLOW CAR
 MANEUVERING. EACH LANDSCAPED ISLAND SHALL CONTAIN AT
 LEAST ONE SHADE OR FLOWERING TREE PER ROW OF PARKING.
 THEREFORE, REVISE THE LANDSCAPE PLAN (SHEET NO. LP-1),
 ACCORDINGLY, AND PROVIDE THE DIMENSIONS OF THE PROPOSED
 TERMINAL LANDSCAPE ISLANDS. IDENTIFY/INDICATE THE
 REQUESTED VARIANCE RELATING TO THE TERMINAL LANDSCAPE
 ISLANDS ON THE LANDSCAPE PLAN (SHEET NO. LP-1), IF THIS
 IS STILL THE CASE AFTER THE REVISIONS.
  
 6/26/23 IT HAS BEEN IDENTIFIED THAT REQUIRED TERMINAL
 ISLANDS ARE MISSING. A CANOPY TREE IS REQUIRED FOR ALL
 ISLANDS.
  
 13. NOT SATISFIED. PROVIDE LOCATIONS AND SCREENING FOR
 ALL SPECIAL UTILITY STRUCTURES AND ABOVE GROUND
 APPURTENANCES ON THE LANDSCAPE PLAN (SHEET NO. LP-1).
  
 6/26/23 SHOW AND CALL OUT ABOVE GROUND EQUIPMENT.
  
 14. SATISFIED. PROVIDE THE DELINEATION OF IRRIGATION
 COVERAGE, SENSORS AND HIGH, MEDIUM AND LOW ZONES OF
 WATER USAGE. INCLUDE A STATEMENT THAT ALL LANDSCAPE
 AREAS, EXCLUDING THOSE AREAS WITH NATIVE NONINVASIVE
 PLANTS, WILL BE PROVIDED WITH PERMANENT AUTOMATIC
 IRRIGATION, INCLUDING ADJACENT RIGHTS???OF???WAY.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 05-09-2023 Cont ID  
Sent By kdefranc Date 05-09-2023 Time 14:48 Rev Time 0.00
Received By kdefranc Date 05-09-2023 Time 14:46 Sent To  
Notes
2023-05-09 14:47:51FROM: KEVIE DEFRANC, SENIOR PLANNER 561-822-1449
 PROJECT: LEGACY AT 45TH STREET Z23040020
 MAY 9, 2023
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PER SECTION 94-442(B)(1), PROVIDE LANDSCAPE PLANS
 SIGNED AND SEALED BY A REGISTERED LANDSCAPE ARCHITECT.
  
 2. PROVIDE BOTH PHYSICAL HARDCOPIES AND ELECTRONIC
 COPIES OF THE LANDSCAPE PLANS.
  
 3. PROVIDE A SEPARATE TREE DISPOSITION PLAN BASED ON A
 TREE SURVEY. INCLUDE EXISTING PALM AND CANOPY TREES IN
 THE RIGHT-OF-WAY AND ON ADJACENT PROPERTIES WITHIN 10
 FEET OF THE PROPERTY LINE.
  
 4. PER SECTION 94-443(D)(1), PROVIDE THE PROPOSED
 LANDSCAPE BUFFER WIDTH DIMENSIONS ON THE LANDSCAPE PLAN
 (SHEET NO. LP-1).
  
 5. PROVIDE THE EXISTING AND PROPOSED EASEMENTS ON THE
 LANDSCAPE PLAN (SHEET NO. LP-1).
  
 6. PER SECTION 94-442(C)(2)(B), PROVIDE THE OPEN SPACE
 AREA CALCULATIONS (REQUIRED AND PROPOSED) ON THE
 LANDSCAPE PLAN (SHEET NO. LP-1).
  
 7. PER SECTION 94-442(C)(2)(B), PROVIDE THE LANDSCAPE
 AREA CALCULATIONS (REQUIRED AND PROPOSED) ON THE
 LANDSCAPE PLAN (SHEET NO. LP-1).
  
 8. PER SECTIONS 94-442(C)(2)(B) AND 94-443(D), REVISE
 THE LANDSCAPE PLAN (SHEET NO. LP-1), ACCORDINGLY, AND
 PROVIDE THE TREES CALCULATIONS (REQUIRED AND PROPOSED)
 ON THE LANDSCAPE PLAN (SHEET NO. LP-1).
  
 9. PER SECTION 94-442(C)(2)(B), AT LEAST ONE SHRUB
 SHALL BE PLANTED FOR EACH 500 SQUARE FEET OF REQUIRED
 OPEN SPACE OR PORTION THEREOF. THEREFORE, PROVIDE THE
 SHRUBS CALCULATIONS (REQUIRED AND PROPOSED) ON THE
 LANDSCAPE PLAN (SHEET NO. LP-1).
  
 10. PER SECTION 94-442(C)(2)(B), GRASS AREAS SHALL NOT
 EXCEED 60 PERCENT OF THE REQUIRED LANDSCAPE AREA.
 THEREFORE, PROVIDE THE GRASS AREAS CALCULATIONS
 (REQUIRED AND PROPOSED) ON THE LANDSCAPE PLAN (SHEET
 NO. LP-1).
  
 11. PER SECTIONS 94-443(C)(3) AND (4), PROVIDE AN
 EXHIBIT SHOWING THE PARKING AREA SURFACE CALCULATIONS,
 PARKING SPACE AREAS AND LANDSCAPE AREAS. PROVIDE THE
 CALCULATIONS AND SHOW THE ACTUAL PROPOSED INTERIOR
 LANDSCAPE SQUARE FOOTAGE.
  
 12. PER SECTION 94-443(C)(3)(A), EACH ROW OF PARKING
 SPACES SHALL BE TERMINATED BY LANDSCAPED ISLANDS OF NOT
 LESS THAN EIGHT FEET IN WIDTH AND NOT LESS THAN THE
 LENGTH OF THE ADJACENT PARKING STALL. EACH LANDSCAPED
 ISLAND SHALL HAVE A MINIMUM RADIUS OF TWO AND ONE-HALF
 FEET AT ITS END SO AS TO ALLOW CAR MANEUVERING. EACH
 LANDSCAPED ISLAND SHALL CONTAIN AT LEAST ONE SHADE OR
 FLOWERING TREE PER ROW OF PARKING. THEREFORE, REVISE
 THE LANDSCAPE PLAN (SHEET NO. LP-1), ACCORDINGLY, AND
 PROVIDE THE DIMENSIONS OF THE PROPOSED TERMINAL
 LANDSCAPE ISLANDS. IDENTIFY/INDICATE THE REQUESTED
 VARIANCE RELATING TO THE TERMINAL LANDSCAPE ISLANDS ON
 THE LANDSCAPE PLAN (SHEET NO. LP-1), IF THIS IS STILL
 THE CASE AFTER THE REVISIONS.
  
 13. PROVIDE LOCATIONS AND SCREENING FOR ALL SPECIAL
 UTILITY STRUCTURES AND ABOVE GROUND APPURTENANCES ON
 THE LANDSCAPE PLAN (SHEET NO. LP-1).
  
 14. PROVIDE THE DELINEATION OF IRRIGATION COVERAGE,
 SENSORS AND HIGH, MEDIUM AND LOW ZONES OF WATER USAGE.
 INCLUDE A STATEMENT THAT ALL LANDSCAPE AREAS, EXCLUDING
 THOSE AREAS WITH NATIVE NONINVASIVE PLANTS, WILL BE
 PROVIDED WITH PERMANENT AUTOMATIC IRRIGATION, INCLUDING
 ADJACENT RIGHTS???OF???WAY.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PU PUBLIC UTILITIES
Rev No 2 Status F Date 06-23-2023 Cont ID  
Sent By relizond Date 06-23-2023 Time 15:20 Rev Time 0.00
Received By relizond Date 06-23-2023 Time 15:20 Sent To  
Notes
2023-06-23 15:19:39-PLEASE PROVIDE CIVIL DRAWINGS MENTIONED IN SITE PLAN
 SHEET
 -PROVIDE CCTV OF ALL EXISTING SANITARY SEWER MAIN
 FRONTING PROJECT LIMITS BEFORE AND AFTER CONSTRUCTION.
 -PROVIDE SOFTDIG INFORMATION AT PROPOSED POINT OF
 CONNECTION
 -REFER TO THE CITY???S STANDARD DETAILS FOR PLACEMENT
 OF DDCA AND CITY???S POINT OF SERVICE (POS) WHICH
 REQUIRES A SECOND VALVE AT R/W
 -SET UP ALL PLAN SHEETS TO PRINT TO SCALE ON 11X17
 -SHOW ALL EXISTING WATER SERVICES/METER BOXES/VALVES
 VAULTS, AND SANITARY SEWER LATERALS WITHIN PROJECT
 LIMITS.
 -ALL EXISTING VALVES AND MANHOLES NEED TO BE LEGIBLE
 -SHOW EXISTING VALVES AND APPURTENANCES AND CORRECT
 ALIGNMENT OF EXISTING CITY-MAINTAINED UTILITIES
 -LABEL ALL UTILITIES TO BE MAINTAINED ON-SITE BY OWNER
 ENTITY AS ???PRIVATE???, AS APPLICABLE
 -ALL PROPOSED UTILITY EASEMENTS AND PLACEMENT OF
 DOMESTIC WATER METER/BACKFLOW PREVENTER ASSEMBLY NOT IN
 COMPLIANCE WITH APPLICABLE CITY???S STANDARD DETAILS
 WILL REQUIRE WATER DISTRIBUTION???S APPROVAL. PROVIDE 5
 FOOT RADIAL CLEARANCE IN ALL DIRECTIONS.
 -ALL PROPOSED UTILITY EASEMENTS AND PLACEMENT OF
 CLEANOUT NOT IN COMPLIANCE WITH APPLICABLE CITY???S
 STANDARD DETAILS WILL REQUIRE SANITARY COLLECTIONS
 APPROVAL. PROVIDE 5 FOOT RADIAL CLEARANCE IN ALL
 DIRECTIONS.
 -PROVIDE PROFILES FOR ALL CONNECTIONS TO EXISTING
 CITY-MAINTAINED UTILITIES FROM THE POINT OF CONNECTION
 TO THE POINT OF SERVICE.
 -ON PROFILE VIEW, SHOW ALL EXISTING AND PROPOSED
 UTILITIES (CITY-MAINTAINED AND DRY UTILITIES), CALL OUT
 UTILITY TYPE, DIMENSIONS, PIPE MATERIAL, AND VERTICAL
 CLEARANCE OD TO OD AT EACH UTILITY CROSSING.
 -PROVIDE DIMENSIONS BETWEEN PROPOSED UTILITIES TO
 ENSURE PROPER HORIZONTAL CLEARANCE
 --SINGLE WATER TAPS SERVING DOMESTIC, FIRE LINE,
 IRRIGATION, AND FIRE HYDRANT PRESENTS ISSUES FOR FUTURE
 MAINTENANCE/REPAIRS/REPLACEMENTS ETC. AS SHUTDOWN WILL
 DISRUPT SERVICE
 -SHOW ALL UTILITY CROSSINGS WITH HORIZONTAL AND
 VERTICAL SEPARATION, AS WELL AS SPECIFYING THE UTILITY
 TYPE, SIZE, AND MATERIAL.
 -PROVIDE LOS CALCULATIONS, AS WELL AS CHANGE IN DEMAND
 BETWEEN EXISTING CONDITIONS AND PROPOSED CONDITIONS.
 -PROVIDE PROJECT FACT SHEET
 -EXISTING WATER AND SEWER SERVICES CURRENTLY SERVING
 THE PROPERTY, IF NOT USED, NEED TO BE CUT AND CAP AT
 MAIN. REMOVAL IS REQUIRED IF LARGER THAN 2??? IN
 DIAMETER, OR AS REQUIRED BY THE RIGHT-OF-WAY???S
 GOVERNING AGENCY.
 -INCLUDE LEGEND, DATUM CONVERSION, AND NORTH ARROW ON
 PLANS
 -PROPOSED SEWER LATERALS LARGER THAN 6??? WILL REQUIRE
 CONNECTION A MANHOLE, WITH A CLEANOUT OF THE SAME SIZE
 INSTALLED AS THE CITY???S POS.
 -ADD NOTE TO PLANS SPECIFYING THE LIFT STATION THAT THE
 PROJECT IS UPSTREAM FROM.
 -PROVIDE A BLOW-UP DETAIL FOR ALL CONNECTION POINTS TO
 CITY-MAINTAINED UTILITIES.

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status F Date 05-11-2023 Cont ID  
Sent By relizond Date 05-11-2023 Time 10:35 Rev Time 0.00
Received By relizond Date 05-11-2023 Time 10:33 Sent To  
Notes
2023-05-11 10:34:50-NO WATER/SEWER SHEET PROVIDED TO REVIEW UTILITY
 SERVICE FED TO THE PROPOSED BUILDINGS.

Review Stop PU-CS PUBLIC UTILITIES CUSTOMER SRVC
Rev No 2 Status F Date 06-15-2023 Cont ID  
Sent By mhurley Date 06-15-2023 Time 08:21 Rev Time 0.00
Received By mhurley Date   Time   Sent To  
Notes
2023-06-15 08:20:56PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -SP-010 DOES NOT SHOW ANY WATER MAIN INFORMATION. NEED
 TO VERIFY WATER MAIN IS SUFFICIENT FOR WATER SERVICES.
 -THERE ARE NOTES ON SP-010 REFERRING TO CIVIL PLANS FOR
 EXACT LOCATIONS OF WATER SERVICE CONNECTIONS, BUT
 CANNOT FIND SHEET WITH THAT INFORMATION. PLEASE ADD
 ADDITIONAL SHEET WITHIN CIVIL ENGINEERING PLAN SET
 SHOWING THAT INFORMATION IN DETAIL.
 -ADD GRAPHIC SCALE TO SP-010
 -IRRIGATION METER IS SHOWN DOWNSTREAM OF DOMESTIC
 METER. CITY CANNOT PROVIDE METERS IN SERIES. THAT WOULD
 HAVE TO BE A PRIVATE SUB METER. PLEASE REVISE CALLOUT
 LABEL TO REFLECT THAT.
 -CALLOUT DUCTILE IRON PIPE (DIP) UPSTREAM OF DCDA.
 -FIRELINE WATER SERVICE IS 8 INCH AND WOULD GET BILLED
 FOR 8 INCH. DCDA SIZE SHOULD MATCH FIRELINE SIZE. NOT
 SURE IF THE 4 INCH SIZE WAS TYPO. THAT SIZE IS TOO
 SMALL FOR DOWNSTREAM FIRE HYDRANTS AS WELL (MINIMUM 6
 INCH).
 -VERIFY PRIVATE FIRE SYSTEM WILL NOT HAVE ANY ADDED
 CHEMICALS OR AUXILIARY WATER SUPPLY SUCH AS A WELL.
 -CANNOT FIND WATER AND SEWER DEMAND CALCULATIONS ON
 ENGINEERING WATER PLAN.
 -PARALLEL/DUAL DOMESTIC BACKFLOW ASSEMBLIES ARE
 RECOMMENDED AT 4 INCH WATER METER TO MINIMIZE WATER
 OUTAGES DURING BACKFLOW TESTING AND MAINTENANCE.
 -DOMESTIC WATER SERVICE, WATER METER, AND BACKFLOW
 ASSEMBLY NEAR NORTH SIDE OF PROPERTY IS NOT SHOWN ON
 LANDSCAPING PLAN. PLEASE ADD AND ENSURE NO LOCATION
 CONFLICTS BETWEEN PLANTS AND UTILITIES.
 -SURVEY IS NOT SIGNED, SEALED, AND DATED.
 -SURVEY DID NOT MENTION ANY EASEMENTS. WAS THERE A
 SEARCH TO VERIFY IF THERE ARE ANY EXISTING EASEMENTS AT
 THE PROPERTY? NEED TO VERIFY IF THERE ARE ANY EASEMENTS
 IF HAVE NOT ALREADY AS CAN AFFECT BACKFLOW ASSEMBLY
 LOCATION.
 -WATER METER IS SHOWN ON PRIVATE PROPERTY, BUT DO NOT
 SEE UTILITY EASEMENT.
 RESPECTFULLY,
 MARK HURLEY [email protected]

Review Stop PU-CS PUBLIC UTILITIES CUSTOMER SRVC
Rev No 1 Status F Date 05-05-2023 Cont ID  
Sent By mhurley Date 05-05-2023 Time 13:06 Rev Time 0.00
Received By mhurley Date   Time   Sent To  
Notes
2023-05-05 13:06:39PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -ON SITE PLAN S-1, ARE THE BUILDINGS EXISTING OR
 PROPOSED?
 -IN RESUBMITTAL PACKAGE, ADD COPIES OF SURVEY AND
 WATER/SEWER PLANS. WILL PROVIDE MORE REVIEW COMMENTS
 ONCE ABLE TO REVIEW THOSE.
 -UTILITY BILLING SYSTEM SHOWS AN EXISTING 1 INCH
 DOMESTIC WATER METER AT THE PROPERTY.
 -BELOW IS A LIST OF SOME STANDARD REVIEW COMMENTS THAT
 MAY ASSIST YOU:
 *EXISTING AND PROPOSED METERED WATER SERVICES SHOWN AND
 LABELED.
 *DOMESTIC BACKFLOW ASSEMBLIES SHOULD BE LOCATED ON
 PRIVATE PROPERTY OUTSIDE OF ANY UTILITY EASEMENTS AND
 ADJACENT TO PROPERTY/ROW LINE WITH PIPE DISTANCE
 MINIMIZED TO METER.
 *DOMESTIC BACKFLOW ASSEMBLIES LABELED WITH ???RP???
 TYPE AND SIZE.
 *FIRELINE BACKFLOW ASSEMBLY LABELED WITH TYPE (DCDA OR
 RPDA) AND SIZE. IF DCDA TYPE PROPOSED, NEED
 VERIFICATION PRIVATE FIRE SYSTEM WILL HAVE NO ADDED
 CHEMICALS OR AUXILIARY WATER SUPPLIES SUCH AS WELLS.
 *WATER METERS LABELED WITH SIZE AND USE TYPE
 (DOMESTIC/IRRIGATION). METERS 3 INCHES OR LARGER
 LABELED ???ABOVE-GROUND???.
 *PROPERTY LINES, EASEMENTS, TRANSFORMERS, GREASE TRAPS,
 RIGHT OF WAYS, GUY ANCHOR WIRES, STREETS, FENCES,
 WALLS, POLES, FRANCHISE UTILITIES, SIDEWALKS, SIGNS,
 FDCS, DRIVEWAYS, CLEANOUTS, SANITARY SEWER LATERALS,
 AND STRUCTURES SHOWN AND LABELED.
 *FIRE SPRINKLERS MAY NOT RUN OFF DOMESTIC WATER METERS
 AND NEEDS TO BE ON A SEPARATE WATER SERVICE WITH
 DETECTOR STYLE BACKFLOW ASSEMBLY. IF NO FIRE SERVICE
 SHOWN ON PLANS, NEED VERIFICATION NO FIRE SPRINKLERS
 WILL BE IN BUILDINGS.
 *PLANS SHOULD HAVE NORTH DIRECTION ARROW, VISUAL SCALE
 MEASUREMENT ICON / GRAPHIC SCALE, ADDRESS, AND DATE.
 *DOMESTIC WATER METERS NOT LOCATED IN BUILDINGS OR
 DRIVEWAYS. PREFERRED LOCATION IN LANDSCAPE (NOT
 HARDSCAPE) ADJACENT PROPERTY LINE WITH DISTANCE
 MINIMIZED TO RIGHT OF WAY AND WATER MAIN.
 *ALL INSTALLED CONTAINMENT BACKFLOW ASSEMBLIES MUST BE
 LEAD-FREE AND USC-APPROVED (BY SIZE, MAKE, MODEL,
 ORIENTATION, VALVING, AND BYPASS).
 *TREES, TREE ROOTS, AND BUSHES NOT ENCROACHING ON WATER
 METERS AND BACKFLOW ASSEMBLIES. SHOW METERED WATER
 SERVICES AND BACKFLOW ASSEMBLIES ON
 LANDSCAPING/PLANTING PLANS.
 *FIRELINE BACKFLOW ASSEMBLY SHOULD BE INSTALLED ON
 PRIVATE PROPERTY OUTSIDE OF ANY UTILITY EASEMENTS AT A
 LOCATION COMPLIANT WITH FIRE CODE AND MINIMIZING PIPE
 DISTANCE TO WATER MAIN (ADJACENT PROPERTY/ROW LINE
 WHENEVER POSSIBLE).
 *POLES AND STRUCTURES MINIMUM 3 FEET AWAY FROM WATER
 METER BOXES.
 *DOMESTIC WATER METERS ACCESSIBLE FROM RIGHT OF WAY AND
 NOT LOCKED BEHIND ANY GATES, FENCES, OR WALLS.
 *WATER METERS 6 INCH OR LARGER NEED BE ACCESSIBLE AND
 REPLACEABLE BY FORD F350 CRANE TRUCK.
 *WATER METERS 8 INCHES AND LARGER ARE NOT STOCKED AND
 HAVE TO BE ORDERED AFTER UTILITY QUOTE IS PAID. LEAD
 TIMES MAY BE OVER 6 MONTHS FROM TIME OF PAYMENT.
 RESPECTFULLY,
 MARK HURLEY [email protected]
  

Review Stop PW PUBLIC WORKS
Rev No 2 Status F Date 06-22-2023 Cont ID  
Sent By jbjoseph Date 06-22-2023 Time 11:05 Rev Time 0.00
Received By jbjoseph Date 06-22-2023 Time 11:04 Sent To  
Notes
2023-06-22 11:05:45PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED.
  
 1. IF THE DUMPSTER IS TO BE ROLLED OUT FOR PICKUP, IT
 HAS TO BE ROLLED OUT TO A SAFE AND ACCESSIBLE LOCATION
 ON YOUR PROPERTY. ??PLEASE IDENTIFY LOCATION ON PLANS.
  
 2. PROVIDE LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT
 THE SOLID WASTE VOLUME PRODUCED ALONG WITH THE SIZE,
 TYPE AND QUANTITY OF THE CONTAINER (I.E.
 DUMPSTER/COMPACTOR) THAT WILL BE UTILIZED FOR THE
 SANITATION SERVICE.
  
 BRUCELY A. JOSEPH
 PUBLIC WORKS PROGRAM MANAGER
 [email protected]
  
  

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 05-10-2023 Cont ID  
Sent By jbjoseph Date 05-10-2023 Time 16:09 Rev Time 0.00
Received By jbjoseph Date 05-10-2023 Time 16:07 Sent To  
Notes
2023-05-10 16:08:43PLEASE PROVIDE THE FOLLOWING:
 1. DUMPSTER ENCLOSURE DETAILS FOR SANITATION SERVICE
 (I.E. SOLID WASTE CONTAINER(S) TYPE, COLLECTION
 LOCATION, ETC.). FOR A FREESTANDING SITE DUMPSTER
 ENCLOSURE. THE ENCLOSURE SHALL COMPLY WITH THE LATEST
 REVISION OF CITY OF WEST PALM BEACH GENERAL
 CONSTRUCTION GARBAGE ENCLOSURE STANDARD. GC-7
 2. LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID
 WASTE VOLUME PRODUCED ALONG WITH THE SIZE, TYPE AND
 QUANTITY OF THE CONTAINER (I.E. DUMPSTER/COMPACTOR)
 THAT WILL BE UTILIZED FOR THE SANITATION SERVICE.
 3. PROVIDE AN AUTOTURN PLAN.?? TRAVEL PATHS SHOULD
 BEGIN OUTSIDE THE SITE ILLUSTRATING THE TURN ONTO THE
 PRIMARY ENTRY ROAD/DRIVE, MANEUVERING AROUND THE SITE,
 AND COMPLETED WITH AN ILLUSTRATION DEMONSTRATING
 EXITING THE SITE. PATHS MUST ILLUSTRATE THE FULL
 VEHICLE SWEPT PATH (INCLUDING WHEEL TRACKS AND
 OUT-TO-OUT VEHICLE OVERHANG SWEEP) AND MUST INDICATE A
 CLEAR, UNOBSTRUCTED TRAVEL AROUND THE SITE WITHOUT
 IMPACT/COLLISIONS TO BUILDINGS, CURBS, LANDSCAPING,
 PARKING SPACES, VEHICLES, ETC???
  
 AUTOTURN EXHIBIT WITH DYNAMIC ENVELOPE AND THE
 VEHICLE'S WHEEL PATH IDENTIFIED WITH DIFFERENT COLORS
 FOR THE SANITATION SERVICE, FRONT LOADER TRUCK WITH THE
 FOLLOWING SPECS:
 - DUAL AXLES
 - TRUCK LENGTH: 35 FT
 - TIRE PATH WIDTH: 8FT
 - DYNAMIC ENVELOPE WIDTH: 11 FT
 - TURNING RADIUS:
 - SAE TURNING RADIUS: 325FT
 - CURB TO CURB DIAMETER: 74 FT
 - WALL TO WAII DIAMETER: 86 3FT
  
 BRUCELY A. JOSEPH
 PUBLIC WORKS PROGRAM MANAGER
 [email protected]
  
  

Review Stop STORM STORMWATER
Rev No 2 Status F Date 06-27-2023 Cont ID  
Sent By tward Date 06-27-2023 Time 12:21 Rev Time 0.00
Received By tward Date 06-27-2023 Time 12:23 Sent To  
Notes
2023-06-27 12:21:45THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 6/2/2023 SUBMITTAL.
  
 1. [SATISFIED] 45TH ST. IS MAINTAINED BY PALM BEACH
 COUNTY. ANY WORK PROPOSED IN THE R/W WILL NEED TO BE
 PERMITTED BY PBC.
  
 2. [NOT SATISFIED - PAVING MARKING AND SIGNAGE PLAN
 REFERS TO BCTED] REMOVE REFERENCES TO BROWARD COUNTY.
  
 3. [SATISFIED] IF SITE IS WITHIN A SPECIAL FLOOD HAZARD
 AREA THEN THE BUILDINGS AND MECHANICAL EQUIPMENT ARE TO
 BE LOCATED A MINIMUM OF TWO FEET ABOVE THE BASE FLOOD
 ELEVATIONS (2 FEET OF FREEBOARD). SITE DOES NOT APPEAR
 TO BE WITHIN A SFHA.
  
 4. [NOT SATISFIED - RESPONSE INDICATED LETTER WAS
 FORTHCOMING] PROVIDE LETTER FROM ADJACENT PROPERTY
 OWNER TO THE SOUTH (SCHOOL BOARD OF PALM BEACH COUNTY)
 OR OWNER OF ANY DRAINAGE EASEMENT APPROVING THE
 DRAINAGE CONNECTION AND DISCHARGE ONTO THEIR SITE OR
 EASEMENT. PROVIDE A COPY OF THE EASEMENT IF APPLICABLE.
  
 5. [SATISFIED] LABEL MH#9 ON SHEET C-1.
  
 6. [NOT SATISFIED - SECTIONS ON SHEET C-2 SHOW THE
 FOOTER CROSSING THE PROPERTY LINE.] WALL FOOTERS SHOULD
 BE CONSTRUCTED ENTIRELY WITHIN THE PROPERTY BOUNDARY.
  
 7. [PARTIALLY SATISFIED - CONTOURS REMOVED FROM PGD
 PLAN BUT SECTIONS ON SHEET C-2 SHOW DEPRESSED AREAS AND
 THE PGD PLAN SHOWS STORM PIPES EXTENDING INTO THE
 FORMALLY GRADED AREAS.] EXPLAIN OR SHOW HOW THE
 RETENTION AREAS WILL DRAIN. RE-LABEL AS DETENTION AREAS
 IF THERE WILL BE CONNECTIONS TO THE ONSITE DRAINAGE
 SYSTEM AND OUTFALL PIPE.
  
 8. [SATISFIED] CREATE A SWALE ALONG THE BACK OF
 SIDEWALK ALONG 45TH STREET TO PREVENT DIRECT RUNOFF
 ONTO THE SIDEWALK.
  
 9. [SATISFIED] LABEL THE LANDSCAPE BUFFER ON SECTION
 B-B.
  
 10. [SATISFIED] ADD TO SHEET C-2 THE VERTICAL DATUM
 CONVERSION EQUATION TO NGVD1929.
  
 11. [SATISFIED - PARKING STALLS DO NOT APPEAR TO BE
 REDUCED IN LENGTH] CONSIDER REDUCING THE AMOUNT OF
 IMPERVIOUS AREA BY REDUCING THE PARKING STALL DEPTHS
 AND PROVIDING TWO FEET OF LANDSCAPED OVERHANG. THE
 RAISED CURB CAN FUNCTION AS THE WHEEL STOPS.
  
 12.[NOT SATISFIED - THIS INFORMATION WILL BE NEEDED ON
 THE ENGINEERING PERMIT SET OF DRAWINGS] LABEL TOP AND
 BOTTOM ELEVATIONS OF THE EXFILTRATION TRENCH AND TRENCH
 WIDTH ON THE EXFILTRATION TRENCH DETAIL. ADD THE
 VERTICAL DATUM AND CONVERSION EQUATION TO NGVD1929 TO
 THE SHEET.
  
 13. [NOT SATISFIED - SHEETS C-1 AND C-4 SHOW THE STOP
 BAR RIGHT BEHIND THE SIDEWALK ALONG 45TH ST.] MOVE STOP
 SIGN/STOP BAR 4 FEET FROM BACK OF SIDEWALK.
  
 14. [PARTIALLY SATISFIED - SHOW DRIVEWAY APRON WITHIN
 THE RIGHT OF WAY AS CONCRETE] PROVIDE A CROSS SECTION
 OF THE DRIVEWAY. SHOW AND LABEL RIGHT OF WAY (45TH ST),
 SURFACE BREAKS, DIMENSIONS BETWEEN SURFACE BREAK
 POINTS, GENERAL SURFACE SLOPES AND MATERIAL, HIGH POINT
 OF DRIVEWAY AND DISTANCE FROM THE R/W. MINIMIZE THE
 DISTANCE TO THE DRIVEWAY HIGH POINT BY MAXIMIZING THE
 DRIVEWAY SLOPE BEHIND THE SIDEWALK. PROVIDE ADA
 COMPLIANT SIDEWALK ACROSS THE DRIVEWAY APRON.
  
 15. [SATISFIED] PROVIDE PARKING SPACE STRIPING DETAIL
 AS SHOWN IN SECTION 94-485 OF THE CITY'S CODE OF
 ORDINANCES.
  
 16. [SATISFIED] NO SURVEY WAS PROVIDED.
  
 17. [SATISFIED] NO WATER AND SEWER PLAN WAS PROVIDED.
  
 NEW COMMENTS (6/2/2023 SUBMITTAL):
  
 18. ON EVERY SHEET WITH ELEVATION INFORMATION, PROVIDE
 THE VERTICAL DATUM REFERENCE AND CONVERSION EQUATION TO
 NGVD1929.
  
 19. BUILDING OUTLINES ARE NOT SHOWN ON THE CIVIL PLANS.
  
 20. LANDSCAPE PLANS DO NOT SHOW ALL OF THE UTILITIES.
  
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 [email protected]
  

Review Stop STORM STORMWATER
Rev No 1 Status F Date 05-10-2023 Cont ID  
Sent By tward Date 05-10-2023 Time 17:07 Rev Time 0.00
Received By tward Date 05-10-2023 Time 17:08 Sent To  
Notes
2023-05-10 17:07:34THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. 45TH ST. IS MAINTAINED BY PALM BEACH COUNTY. ANY
 WORK PROPOSED IN THE R/W WILL NEED TO BE PERMITTED BY
 PBC.
  
 2. REMOVE REFERENCES TO BROWARD COUNTY.
  
 3. IF SITE IS WITHIN A SPECIAL FLOOD HAZARD AREA THEN
 THE BUILDINGS AND MECHANICAL EQUIPMENT ARE TO BE
 LOCATED A MINIMUM OF TWO FEET ABOVE THE BASE FLOOD
 ELEVATIONS (2 FEET OF FREEBOARD). SITE DOES NOT APPEAR
 TO BE WITHIN A SFHA.
  
 4. PROVIDE LETTER FROM ADJACENT PROPERTY OWNER TO THE
 SOUTH (SCHOOL BOARD OF PALM BEACH COUNTY) OR OWNER OF
 ANY DRAINAGE EASEMENT APPROVING THE DRAINAGE CONNECTION
 AND DISCHARGE ONTO THEIR SITE OR EASEMENT. PROVIDE A
 COPY OF THE EASEMENT IF APPLICABLE.
  
 5. LABEL MH#9 ON SHEET C-1.
  
 6. WALL FOOTERS SHOULD BE CONSTRUCTED ENTIRELY WITHIN
 THE PROPERTY BOUNDARY.
  
 7. EXPLAIN OR SHOW HOW THE RETENTION AREAS WILL DRAIN.
 RE-LABEL AS DETENTION AREAS IF THERE WILL BE
 CONNECTIONS TO THE ONSITE DRAINAGE SYSTEM AND OUTFALL
 PIPE.
  
 8. CREATE A SWALE ALONG THE BACK OF SIDEWALK ALONG 45TH
 STREET TO PREVENT DIRECT RUNOFF ONTO THE SIDEWALK.
  
 9. LABEL THE LANDSCAPE BUFFER ON SECTION B-B.
  
 10. ADD TO SHEET C-2 THE VERTICAL DATUM CONVERSION
 EQUATION TO NGVD1929.
  
 11. CONSIDER REDUCING THE AMOUNT OF IMPERVIOUS AREA BY
 REDUCING THE PARKING STALL DEPTHS AND PROVIDING TWO
 FEET OF LANDSCAPED OVERHANG. THE RAISED CURB CAN
 FUNCTION AS THE WHEEL STOPS.
  
 12. LABEL TOP AND BOTTOM ELEVATIONS OF THE EXFILTRATION
 TRENCH AND TRENCH WIDTH ON THE EXFILTRATION TRENCH
 DETAIL. ADD THE VERTICAL DATUM AND CONVERSION EQUATION
 TO NGVD1929 TO THE SHEET.
  
 13. MOVE STOP SIGN/STOP BAR 4 FEET FROM BACK OF
 SIDEWALK.
  
 14. PROVIDE A CROSS SECTION OF THE DRIVEWAY. SHOW AND
 LABEL RIGHT OF WAY (45TH ST), SURFACE BREAKS,
 DIMENSIONS BETWEEN SURFACE BREAK POINTS, GENERAL
 SURFACE SLOPES AND MATERIAL, HIGH POINT OF DRIVEWAY AND
 DISTANCE FROM THE R/W. MINIMIZE THE DISTANCE TO THE
 DRIVEWAY HIGH POINT BY MAXIMIZING THE DRIVEWAY SLOPE
 BEHIND THE SIDEWALK. PROVIDE ADA COMPLIANT SIDEWALK
 ACROSS THE DRIVEWAY APRON.
  
 15. PROVIDE PARKING SPACE STRIPING DETAIL AS SHOWN IN
 SECTION 94-485 OF THE CITY'S CODE OF ORDINANCES.
  
 16. NO SURVEY WAS PROVIDED.
  
 17. NO WATER AND SEWER PLAN WAS PROVIDED.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP
 CRITERIA. STORMWATER CALCULATIONS WILL BE REVIEWED WITH
 THE ENGINEERING PERMIT SUBMITTAL.
  
 2. PROVIDE COPY OF SFWMD ERP PERMIT BEFORE START OF
 CONSTRUCTION.
  
 3. PROVIDE EROSION AND SEDIMENT CONTROL PLAN WITH THE
 ENGINEERING PERMIT SUBMITTAL.
  
  
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2023-06-30 10:49:161. ENG. AND ARCH. PLANS HAVE 2 DIFFERENT SURVEYS.
 SURVEY NEEDS TO BE SIGNED AND SEALED.
 2. ADD CONVERSION TO NGVD-29 ON SURVEY.
 3. PIPING PLAN(PART OF ENG. PLANS) REFERS TO ENG. PLANS
 FOR LOCATION OF UTILITIES IN 45TH STREET. NO CITY OR
 OTHER UTILITIES SHOWN FOR 45TH STREET.
 4. NEED INFORMATION FOR CANAL TO THE SOUTH FOR YOUR
 ABILITY TO UTILIZE.
 5. UNITY OF TITLE WILL BE REQUIRED. APPLICATION IS MADE
 THROUGH THIS OFFICE.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 05-10-2023 Cont ID  
Sent By vnoel Date 05-10-2023 Time 13:33 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
***NONE***

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status F Date 06-21-2023 Cont ID  
Sent By   Date 06-21-2023 Time   Rev Time 0.00
Received By   Date 06-21-2023 Time   Sent To  
Notes
2023-06-21 23:37:36TRAFFIC COMMENTS
 1) SATISFIED. THE TRAFFIC STUDY IS MISSING TABLES AND
 FIGURES. PLEASE REVISE
 2) PARTIALLY SATISFIED. PROVIDE COUNTY TPS LETTER, ONCE
 RECEIVED
 3) NOT SATISFIED. DUE TO THE PARKING VARIANCE REQUEST,
 PROPER TRANSPORTATION DEMAND MANAGEMENT MEASURES MUST
 BE CONTEMPLATED AND IMPLEMENTED. PLEASE PROVIDE A DRAFT
 DOCUMENT WITH PROPOSED TDM MEASURES; AND SETUP A
 FOLLOW-UP MEETING FOR REVIEW, DISCUSSION AND
 FINALIZATION PURPOSES
  
 SITE COMMENTS
 4) NOT SATISFIED. PROVIDE A TRANSPORTATION SPECIFIC
 SITE PLAN FOR THE GROUND FLOOR. SHOWCASING
 TRANSPORTATION RELATED FEATURES (E.G. ROADWAY WIDTHS,
 DRIVING AISLES, PARKING STALLS, SIDEWALK, CURB, GUTTER,
 DRIVEWAY, GATES, CROSSWALKS, VISIBILITY TRIANGLE,
 CORNER & DRIVEWAY SEPARATION DISTANCES, SLOPES, ETC.)
 PROPERLY LABELED AND DIMENSIONED. THE SITE PLAN SHOULD
 BE NAMED T-1.0. PLEASE PROVIDE DOCUMENT NAME AND/OR
 SHEET NUMBER
 5) NOT SATISFIED. PROVIDE A SIGNING & PAVEMENT MARKING
 PLAN. INCLUSIVE OF ALL FEATURES WITHIN THE PROPOSED
 DEVELOPMENT AND ALONG ALL ROADS FRONTING THE SITE. SUCH
 PLAN CAN BE INTEGRATED IN THE TRANSPORTATION SITE PLAN.
 PLEASE PROVIDE DOCUMENT NAME AND/OR SHEET NUMBER
 6) NOT SATISFIED. PROVIDE AUTOTURN ANALYSIS FOR GARBAGE
 TRUCK AND/OR SERVICE VEHICLES DRIVING IN AND OUT OF THE
 PROPOSED DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES AND
 WHEEL PATHS CLEARLY DISTINCT AND DEFINED IN DIFFERENT
 COLORS
 7) SATISFIED. PROVIDE A DEDICATED TURNAROUND SPACE AT
 EACH PARKING LOT DEAD-END
 8) SATISFIED. ARE THERE ANY BUS STOPS BEING IMPACTED?
 9) SATISFIED. IS THE PROPOSED DEVELOPMENT IMPACTING AN
 EXISTING BICYCLE FACILITY?
 10) NOT SATISFIED. PROVIDE A CONSTRUCTION MANAGEMENT
 PLAN. PLEASE REFER TO CITY CODE 86-246 FOR DETAILS.
 11) PROVIDE A PARKING TABLE SHOWCASING THE NUMBER OF
 REQUIRED AND PROVIDED PARKING STALLS. PLEASE PROVIDE
 DOCUMENT NAME OR SHEET NUMBER SHOWCASING SUCH
 INFORMATION
 12) A DEDICATED TURN-AROUND SPACE MUST BE PROVIDED AT
 EACH PARKING LOT DEAD-END; SUCH SPACE MUST BE CLEARLY
 MARKED AND SIGNED
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 05-11-2023 Cont ID  
Sent By   Date 05-11-2023 Time   Rev Time  
Received By   Date 05-11-2023 Time   Sent To  
Notes
2023-05-11 01:47:13TRAFFIC COMMENTS
 1) THE TRAFFIC STUDY IS MISSING TABLES AND FIGURES.
 PLEASE REVISE
 2) PROVIDE COUNTY TPS LETTER
 3) DUE TO THE PARKING VARIANCE REQUEST, PROPER
 TRANSPORTATION DEMAND MANAGEMENT MEASURES MUST BE
 CONTEMPLATED AND IMPLEMENTED
  
 SITE COMMENTS
 4) PROVIDE A TRANSPORTATION SPECIFIC SITE PLAN FOR THE
 GROUND FLOOR. SHOWCASING TRANSPORTATION RELATED
 FEATURES (E.G. ROADWAY WIDTHS, DRIVING AISLES, PARKING
 STALLS, SIDEWALK, CURB, GUTTER, DRIVEWAY, GATES,
 CROSSWALKS, VISIBILITY TRIANGLE, CORNER & DRIVEWAY
 SEPARATION DISTANCES, SLOPES, ETC.) PROPERLY LABELED
 AND DIMENSIONED. THE SITE PLAN SHOULD BE NAMED T-1.0
 5) PROVIDE A SIGNING & PAVEMENT MARKING PLAN. INCLUSIVE
 OF ALL FEATURES WITHIN THE PROPOSED DEVELOPMENT AND
 ALONG ALL ROADS FRONTING THE SITE. SUCH PLAN CAN BE
 INTEGRATED IN THE TRANSPORTATION SITE PLAN
 6) PROVIDE AUTOTURN ANALYSIS FOR GARBAGE TRUCK AND/OR
 SERVICE VEHICLES DRIVING IN AND OUT OF THE PROPOSED
 DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES AND WHEEL
 PATHS CLEARLY DISTINCT AND DEFINED IN DIFFERENT COLORS
 7) PROVIDE A DEDICATED TURNAROUND SPACE AT EACH PARKING
 LOT DEAD-END
 8) ARE THERE ANY BUS STOPS BEING IMPACTED?
 9) IS THE PROPOSED DEVELOPMENT IMPACTING AN EXISTING
 BICYCLE FACILITY?
 10) PROVIDE A CONSTRUCTION MANAGEMENT PLAN. PLEASE
 REFER TO CITY CODE 86-246 FOR DETAILS.
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 06-20-2023 Cont ID  
Sent By kdefranc Date 06-20-2023 Time 17:00 Rev Time 0.00
Received By kdefranc Date 06-20-2023 Time 16:59 Sent To  
Notes
2023-06-20 16:59:546/20/23 - FAILED
  
  
 PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN
 RESUBMITTING:
 A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
 B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED
 MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG
 WITH ONE (1) REDUCED COPY (11 IN X 17 IN).
 C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
 D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
 E. PLEASE NOTE THAT YOU ARE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. A RESUBMITTAL FEE OF
 20% OF THE ORIGINAL APPLICATION FEE WILL BE ASSESSED
 AFTER THE FIRST RESUBMITTAL.
  
 REQUIRED MATERIALS MUST BE PROVIDED:
 F. PLEASE PROVIDE A COPY OF THE LAST RECORDED WARRANTY
 DEED FOR THE SUBJECT PROPERTY. THE PROPERTY OWNER
 INFORMATION PROVIDED ON THE APPLICATION AND THE
 OWNER???S CONSENT FORM DO NOT MATCH THE PROPERTY OWNER
 INFORMATION IN THE WARRANTY DEED SUBMITTED. [NOT
 SATISFIED]
 G. PLEASE PROVIDE AN ELECTRONIC COPY OF THE SURVEY.
 [SATISFIED]
 H. PLEASE PROVIDE AN ENGINEERING
 (WATER/WASTEWATER-SPECIFIC) PLAN. [SATISFIED]
 I. PLEASE PROVIDE PHYSICAL HARDCOPIES OF THE LANDSCAPE
 PLANS. [SATISFIED]
 J. PLEASE PROVIDE A TRAFFIC CONCURRENCY/PERFORMANCE
 STANDARD REVIEW (TPS) LETTER FROM THE PALM BEACH COUNTY
 TRAFFIC DIVISION FOR THE SUBJECT PROJECT. [NOT
 SATISFIED]
 K. PLEASE PROVIDE A SCHOOL CAPACITY AVAILABILITY
 DETERMINATION (SCAD) PROVIDED BY THE SCHOOL DISTRICT OF
 PALM BEACH COUNTY FOR THE SUBJECT PROJECT. [NOT
 SATISFIED]
 L. PLEASE PROVIDE THE CITY SERVICE AND PUBLIC UTILITY
 LETTERS (FROM FLORIDA PUBLIC UTILITIES, FLORIDA POWER &
 LIGHT COMPANY, AND COMCAST CABLE COMMUNICATION) FOR THE
 SUBJECT PROJECT. [NOT SATISFIED]
 M. IF A REZONING OF THE SUBJECT PROPERTY IS BEING
 REQUESTED, THEN A SEPARATE REZONING TYPE OF APPLICATION
 MUST BE SUBMITTED. [NOT SATISFIED]
 N. PLEASE PROVIDE REVISED PLANS ADDRESSING THE REVIEW
 COMMENTS BELOW. [PARTIALLY SATISFIED]
 O. PLEASE PROVIDE/INDICATE/DEMONSTRATE CONSISTENT
 INFORMATION ON ALL THE DIFFERENT PLANS AND REQUIRED
 MATERIALS WITHIN THE APPLICATION PACKET RESUBMITTAL.
 [NOT SATISFIED]
  
 PLANS REVIEW COMMENTS MUST BE ADDRESSED:
 1. IN REFERENCE TO REVIEW COMMENT M., THE PLANS
 SUBMITTED INDICATE A PROPOSED REZONING OF THE SUBJECT
 PROPERTY. THEREFORE, PLEASE CONFIRM IF A REZONING IS
 BEING REQUESTED. IF SO, A SEPARATE REZONING TYPE OF
 APPLICATION MUST BE SUBMITTED. IF NOT, PLEASE CORRECT
 THE INFORMATION INDICATED IN THE PLANS ACCORDINGLY.
 [NOT SATISFIED]
 2. IN ACCORDANCE WITH RESOLUTION NO. 306-22, THE MF32
 ZONING DISTRICT BUILDING HEIGHT REGULATIONS APPLY TO
 THE PROPOSED PROJECT. BASED ON THE CITY???S ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR) SECTION
 94-77(A)(3), THE PROPOSED PROJECT IS IN COMPLIANCE WITH
 THE MAXIMUM BUILDING HEIGHT ALLOWANCE OF THE MF32
 ZONING DISTRICT. THEREFORE, PLEASE SUBMIT A REVISED
 JUSTIFICATION LETTER BECAUSE THE REQUESTED VARIANCE TO
 THE MAXIMUM BUILDING HEIGHT ALLOWANCE IS NOT NECESSARY.
 [SATISFIED]
 3. PLEASE IDENTIFY/INDICATE THE EXISTING/PROPOSED
 EASEMENTS ON THE PLANS. [NOT SATISFIED]
 4. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF
 THE PROPOSED PUBLIC ART ON THE PLANS. [WITHDRAWN]
 5. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF
 THE EXISTING AND PROPOSED FIRE HYDRANTS WITHIN 250 FEET
 OF THE PROPOSED STRUCTURES ON THE PLANS. [SATISFIED]
 6. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF
 THE PROPOSED SPECIAL UTILITY STRUCTURES / ABOVE GROUND
 APPURTENANCES ON THE PLANS. [PARTIALLY SATISFIED]
 7. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION,
 HEIGHT, AND INTENSITY OF THE PROPOSED OUTDOOR
 ILLUMINATION ON THE PLANS. [PARTIALLY SATISFIED]
 8. IN ACCORDANCE WITH THE ZLDR SECTION 94-485(Q),
 PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF
 THE PROPOSED BICYCLE PARKING FACILITIES ON THE PLANS.
 IDENTIFY/INDICATE THE PROPOSED NUMBER OF BICYCLE
 PARKING IN THE PARKING TABULATION. [PARTIALLY
 SATISFIED]
 9. IN REGARDS TO THE PROVIDED JUSTIFICATION LETTER FOR
 THE PARKING REQUIREMENTS, THE SUBJECT PROPERTY IS NOT
 LOCATED WITHIN THE CITY CENTER DISTRICT. THE CITYWIDE
 DISTRICT SPECIFIC MINIMUM PARKING REQUIREMENTS APPLY TO
 THE PROPOSED PROJECT. THEREFORE, PLEASE REVISE THE
 SUBJECT JUSTIFICATION LETTER. [NOT SATISFIED]
 10. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 OF THE DRIVEWAYS, CURB CUTS, AND TURNING LANES ADJACENT
 TO OR ACROSS FROM THE SUBJECT PROPERTY ON THE PLANS.
 [NOT SATISFIED]
 11. PLEASE PROVIDE THE STANDARD CITY DETAILS/ELEVATIONS
 OF THE PROPOSED BICYCLE PARKING ON THE PLANS. [NOT
 SATISFIED]
 12. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 OF EXISTING AND PROPOSED PUBLIC TRANSIT FACILITIES
 WITHIN THE IMMEDIATE VICINITY OF THE SUBJECT PROPERTY
 ON THE PLANS. [NOT SATISFIED]
 13. IN ACCORDANCE WITH RESOLUTION NO. 306-22, PLEASE
 IDENTIFY/INDICATE THE PROPOSED NUMBER OF AFFORDABLE
 DESIGNATED DWELLING UNITS IN THE SITE CALCULATIONS.
 [NOT SATISFIED]
 14. IN ACCORDANCE WITH RESOLUTION NO. 306-22, PLEASE
 PROVIDE THE DENSITY CALCULATIONS IN THE SITE
 CALCULATIONS. [NOT SATISFIED]
 15. IN ACCORDANCE WITH RESOLUTION NO. 306-22, PLEASE
 CONFIRM THE RESTRICTED UNIT???S AFFORDABILITY PERIOD.
 [SATISFIED]
 16. PLEASE PROVIDE CONSISTENT INFORMATION ON THE SITE
 PLAN (SHEET NO. SP-1) AND ARCHITECTURAL SITE PLAN
 (SHEET NO. A100.00) FOR RESUBMITTAL OR DO NOT PROVIDE
 AN ARCHITECTURAL SITE PLAN AS PART OF THE RESUBMITTAL.
 [NOT SATISFIED]
  
 ADDITIONAL REVIEW COMMENTS MUST BE ADDRESSED:
 17. IN REFERENCE TO PREVIOUS REVIEW COMMENT 6., PLEASE
 IDENTIFY/INDICATE/DEMONSTRATE CONSISTENT INFORMATION
 REGARDING THE LOCATION OF THE PROPOSED SPECIAL UTILITY
 STRUCTURES / ABOVE GROUND APPURTENANCES ON THE SITE
 PLANS, LANDSCAPE PLANS, AND UTILITIES PLANS.
 18. IN REFERENCE TO PREVIOUS REVIEW COMMENT 7., PLEASE
 IDENTIFY/INDICATE/DEMONSTRATE CONSISTENT INFORMATION
 REGARDING THE LOCATION, HEIGHT, AND INTENSITY OF THE
 PROPOSED OUTDOOR ILLUMINATION ON THE SITE PLANS,
 LANDSCAPE PLANS, AND UTILITIES PLANS.
 19. IN REFERENCE TO PREVIOUS REVIEW COMMENT 8., PLEASE
 IDENTIFY/INDICATE/DEMONSTRATE CONSISTENT INFORMATION
 REGARDING THE LOCATION OF THE PROPOSED BICYCLE PARKING
 FACILITIES ON THE SITE PLANS AND LANDSCAPE PLANS.
 PLEASE CORRECT THE REQUIRED NUMBER OF BICYCLE PARKING
 INFORMATION IN THE PARKING TABULATION.
  
  
 KEVIE DEFRANC
 SENIOR PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  

Review Stop Z ZONING
Rev No 1 Status F Date 05-05-2023 Cont ID  
Sent By kdefranc Date 05-05-2023 Time 11:02 Rev Time 0.00
Received By kdefranc Date 05-05-2023 Time 11:01 Sent To  
Notes
2023-05-05 11:02:025/5/23 ??? FAILED
  
  
 PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN
 RESUBMITTING:
 A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
 B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED
 MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG
 WITH ONE (1) REDUCED COPY (11 IN X 17 IN).
 C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
 D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
 E. PLEASE NOTE THAT YOU ARE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. A RESUBMITTAL FEE OF
 20% OF THE ORIGINAL APPLICATION FEE WILL BE ASSESSED
 AFTER THE FIRST RESUBMITTAL.
  
 REQUIRED MATERIALS MUST BE PROVIDED:
 F. PLEASE PROVIDE A COPY OF THE LAST RECORDED WARRANTY
 DEED FOR THE SUBJECT PROPERTY. THE PROPERTY OWNER
 INFORMATION PROVIDED ON THE APPLICATION AND THE
 OWNER???S CONSENT FORM DO NOT MATCH THE PROPERTY OWNER
 INFORMATION IN THE WARRANTY DEED SUBMITTED.
 G. PLEASE PROVIDE AN ELECTRONIC COPY OF THE SURVEY.
 H. PLEASE PROVIDE AN ENGINEERING
 (WATER/WASTEWATER-SPECIFIC) PLAN.
 I. PLEASE PROVIDE PHYSICAL HARDCOPIES OF THE LANDSCAPE
 PLANS.
 J. PLEASE PROVIDE A TRAFFIC CONCURRENCY/PERFORMANCE
 STANDARD REVIEW (TPS) LETTER FROM THE PALM BEACH COUNTY
 TRAFFIC DIVISION FOR THE SUBJECT PROJECT.
 K. PLEASE PROVIDE A SCHOOL CAPACITY AVAILABILITY
 DETERMINATION (SCAD) PROVIDED BY THE SCHOOL DISTRICT OF
 PALM BEACH COUNTY FOR THE SUBJECT PROJECT.
 L. PLEASE PROVIDE THE CITY SERVICE AND PUBLIC UTILITY
 LETTERS (FROM FLORIDA PUBLIC UTILITIES, FLORIDA POWER &
 LIGHT COMPANY, AND COMCAST CABLE COMMUNICATION) FOR THE
 SUBJECT PROJECT.
 M. IF A REZONING OF THE SUBJECT PROPERTY IS BEING
 REQUESTED, THEN A SEPARATE REZONING TYPE OF APPLICATION
 MUST BE SUBMITTED.
 N. PLEASE PROVIDE REVISED PLANS ADDRESSING THE REVIEW
 COMMENTS BELOW.
 O. PLEASE PROVIDE/INDICATE/DEMONSTRATE CONSISTENT
 INFORMATION ON ALL THE DIFFERENT PLANS AND REQUIRED
 MATERIALS WITHIN THE APPLICATION PACKET RESUBMITTAL.
  
 PLANS REVIEW COMMENTS MUST BE ADDRESSED:
 1. IN REFERENCE TO REVIEW COMMENT M., THE PLANS
 SUBMITTED INDICATE A PROPOSED REZONING OF THE SUBJECT
 PROPERTY. THEREFORE, PLEASE CONFIRM IF A REZONING IS
 BEING REQUESTED. IF SO, A SEPARATE REZONING TYPE OF
 APPLICATION MUST BE SUBMITTED. IF NOT, PLEASE CORRECT
 THE INFORMATION INDICATED IN THE PLANS ACCORDINGLY.
 2. IN ACCORDANCE WITH RESOLUTION NO. 306-22, THE MF32
 ZONING DISTRICT BUILDING HEIGHT REGULATIONS APPLY TO
 THE PROPOSED PROJECT. BASED ON THE CITY???S ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR) SECTION
 94-77(A)(3), THE PROPOSED PROJECT IS IN COMPLIANCE WITH
 THE MAXIMUM BUILDING HEIGHT ALLOWANCE OF THE MF32
 ZONING DISTRICT. THEREFORE, PLEASE SUBMIT A REVISED
 JUSTIFICATION LETTER BECAUSE THE REQUESTED VARIANCE TO
 THE MAXIMUM BUILDING HEIGHT ALLOWANCE IS NOT NECESSARY.
 3. PLEASE IDENTIFY/INDICATE THE EXISTING/PROPOSED
 EASEMENTS ON THE PLANS.
 4. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF
 THE PROPOSED PUBLIC ART ON THE PLANS.
 5. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF
 THE EXISTING AND PROPOSED FIRE HYDRANTS WITHIN 250 FEET
 OF THE PROPOSED STRUCTURES ON THE PLANS.
 6. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF
 THE PROPOSED SPECIAL UTILITY STRUCTURES / ABOVE GROUND
 APPURTENANCES ON THE PLANS.
 7. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION,
 HEIGHT, AND INTENSITY OF THE PROPOSED OUTDOOR
 ILLUMINATION ON THE PLANS.
 8. IN ACCORDANCE WITH THE ZLDR SECTION 94-485(Q),
 PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF
 THE PROPOSED BICYCLE PARKING FACILITIES ON THE PLANS.
 IDENTIFY/INDICATE THE PROPOSED NUMBER OF BICYCLE
 PARKING IN THE PARKING TABULATION.
 9. IN REGARDS TO THE PROVIDED JUSTIFICATION LETTER FOR
 THE PARKING REQUIREMENTS, THE SUBJECT PROPERTY IS NOT
 LOCATED WITHIN THE CITY CENTER DISTRICT. THE CITYWIDE
 DISTRICT SPECIFIC MINIMUM PARKING REQUIREMENTS APPLY TO
 THE PROPOSED PROJECT. THEREFORE, PLEASE REVISE THE
 SUBJECT JUSTIFICATION LETTER.
 10. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 OF THE DRIVEWAYS, CURB CUTS, AND TURNING LANES ADJACENT
 TO OR ACROSS FROM THE SUBJECT PROPERTY ON THE PLANS.
 11. PLEASE PROVIDE THE STANDARD CITY DETAILS/ELEVATIONS
 OF THE PROPOSED BICYCLE PARKING ON THE PLANS.
 12. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 OF EXISTING AND PROPOSED PUBLIC TRANSIT FACILITIES
 WITHIN THE IMMEDIATE VICINITY OF THE SUBJECT PROPERTY
 ON THE PLANS.
 13. IN ACCORDANCE WITH RESOLUTION NO. 306-22, PLEASE
 IDENTIFY/INDICATE THE PROPOSED NUMBER OF AFFORDABLE
 DESIGNATED DWELLING UNITS IN THE SITE CALCULATIONS.
 14. IN ACCORDANCE WITH RESOLUTION NO. 306-22, PLEASE
 PROVIDE THE DENSITY CALCULATIONS IN THE SITE
 CALCULATIONS.
 15. IN ACCORDANCE WITH RESOLUTION NO. 306-22, PLEASE
 CONFIRM THE RESTRICTED UNIT???S AFFORDABILITY PERIOD.
 16. PLEASE PROVIDE CONSISTENT INFORMATION ON THE SITE
 PLAN (SHEET NO. SP-1) AND ARCHITECTURAL SITE PLAN
 (SHEET NO. A100.00) FOR RESUBMITTAL OR DO NOT PROVIDE
 AN ARCHITECTURAL SITE PLAN AS PART OF THE RESUBMITTAL.
  
  
 KEVIE DEFRANC
 SENIOR PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  
  

  Print