Plan Review Details - Project Z23040019
| Plan Review Stops For Project Z23040019 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
06-07-2023 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
06-07-2023 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
06-07-2023 |
Time |
16:32 |
Sent To |
|
|
| Notes |
| 2023-06-07 16:34:37 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, | | | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND | | | OTHER FIRE SUPPRESSION SYSTEMS, BACKFLOW PREVENTERS, | | | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, | | | SITE IRRIGATION, ETC. | | | | | | 3. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND | | | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF | | | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL | | | NEIGHBORING PROPERTIES. THE CONTRACTOR SHALL SUBMIT A | | | CONSTRUCTION PARKING PLAN TO THE ENGINEERING SERVICES | | | DEPARTMENT. | | | | | | 4. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER | | | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, | | | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE | | | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF | | | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION | | | THAT MAY AFFECT THE USE OF THEIR PROPERTY. | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
06-08-2023 |
|
|
Cont ID |
|
| Sent By |
lquinone |
Date |
06-08-2023 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
lquinone |
Date |
06-08-2023 |
Time |
11:32 |
Sent To |
|
|
| Notes |
| 2023-06-08 11:32:47 | Z#23040019 ??? SUBMITTAL PPRC STANDARD COMMENTS ??? 1ST | | | REVIEW | | | | | | COMMENTS FROM LINDA M. QUINONES- CINTRON, PROJECT | | | COORDINATOR, ENGINEERING SERVICES AT 561-494-1085 | | | [email protected] | | | GENERAL: | | | O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND | | | INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER | | | (Z-XXXXXXXX). | | | O THE CITY OF WEST PALM BEACH HAS A NUMBER OF | | | REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY | | | AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND | | | WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE | | | DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK | | | BELOW: | | | A. HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WP | | | B_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FUL | | | L-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97 | | | B1960045731D3658206F27451722716EF | | | B. THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE | | | FOUND HERE: | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | C. ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM | | | BEACH, FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, | | | ADOPTED SEPT. 22, 2008. (SUPPLEMENT NO. 18) | | | CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL, | | | SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER | | | SERVICE FACILITIES OF THE CITY. | | | THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE | | | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY | | | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, | | | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. | | | O AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR | | | MORE INFORMATION, REFER TO THE LINK BELOW: | | | A. HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PU | | | BLICATIONS/BACKFLOW-CROSS-CONNECTION- CONTROL-MANUAL | | | O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY | | | OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC | | | RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF | | | YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE | | | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL | | | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT | | | [email protected] OR 561-494-1079 FOR FURTHER | | | ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION | | | ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD | | | SURVEY, POT-HOLING, SOFT DIGS ETC. | | | O PROVIDE EXISTING AND PROPOSED PERVIOUS AND IMPERVIOUS | | | DATA. | | | | | | BACKFLOW ASSEMBLY AND METERS: | | | O SHOW EXISTING AND PROPOSED DEDICATED UTILITY | | | EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO | | | PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO | | | STRUCTURES WITHIN EASEMENT. | | | O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION | | | OF WATER METER AND BACKFLOW | | | PREVENTION. | | | | | | FORMAL ENGINEERING REVIEW: | | | O FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES | | | NOI REQUIREMENTS WILL BE ENFORCED. | | | - AN NOI IS REQUIRED FOR PROJECTS THAT: | | | - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS | | | THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF | | | DEVELOPMENT OR SALE; | | | - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE | | | STATE OR TO SURFACE WATERS OF THE STATE THROUGH A | | | MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4). | | | - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF | | | CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION | | | THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL | | | SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT | | | OF THE 10-2 CERTIFICATION. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF | | | WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING | | | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT | | | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING | | | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED | | | LEAD-FREE DESIGN. | | | O FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES | | | ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY | | | LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT | | | PARCELS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, IF WATER LINES ARE | | | BEING REPLACED IN ROW, SHOW ADJACENT PARCEL ADDRESSES. | | | O FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO PROVIDE | | | 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF | | | PROPOSED TRENCH IN CITY MAINTAINED ROADWAY AREAS PER | | | CITY OF WPB STANDARD DETAIL GC-8. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | CALCULATIONS OF PERVIOUS AND IMPERVIOUS AREAS FOR | | | PROPOSED IMPROVED AREAS. | | | QUESTIONS AND COORDINATION CONTACTS: | | | O MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR WITH | | | CITY OF WPB PUBLIC UTILITIES, REGARDING PLACEMENT OF | | | BACKFLOW DEVICES AND WATER METERS. CONTACT HIM AT | | | 561-822-2262 OR [email protected] | | | O MIKE TECHNOW, PROJECT ENGINEER, PUBLIC UTILITIES | | | DEPARTMENT AT 561-494-1047 OR [email protected] | | | O TRACY WARD, SR. STORMWATER ENGINEER, ENGINEERING | | | SERVICES DEPT. AT 561-494-1120 OR [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
06-01-2023 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
06-01-2023 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
06-01-2023 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2023-06-01 12:03:04 | FIRE HAS NO OBJECTIONS TO THE PROPOSED AND APPROVES. | | | | | | FIRE'S APPROVAL OF THIS SUBMITTED PROJECT MAY NOT | | | CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | IF APPLICABLE, FIRE SHALL REVIEW ALL SUBMITTED PROJECT | | | PLANS AT THE APPLICABLE TIME AND IN ACCORDANCE WITH THE | | | REQUIREMENTS OF ALL APPLICABLE FIRE CODES AND | | | STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
06-07-2023 |
|
|
Cont ID |
|
| Sent By |
kdefranc |
Date |
06-07-2023 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
kdefranc |
Date |
06-07-2023 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2023-06-07 14:48:41 | FROM: KEVIE DEFRANC, SENIOR PLANNER 561-822-1449 | | | PROJECT: PADEL NORTHWOOD Z23040019 | | | JUNE 7, 2023 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. UPDATE TREE DISPOSITION PLAN (SHEET NO. TD-1) TO | | | IDENTIFY/INDICATE/DEMONSTRATE CONSISTENT INFORMATION | | | REGARDING THE EXISTING MANGO TREE THAT IS SHOWN TO | | | REMAIN ON THE LANDSCAPE PLAN (SHEET NO. LP-1 OF 4) AND | | | SITE PLAN (SHEET NO. SP-1 OF 1). | | | | | | 2. PROVIDE THE TOTAL AREA CALCULATIONS FOR THE OVERALL | | | SITE (INCLUDING BOTH PARCELS) AND THE SEPARATE AREA | | | CALCULATIONS FOR EACH PARCEL ON THE LANDSCAPE PLAN | | | (SHEET NO. LP-1 OF 4). | | | | | | 3. PER SECTIONS 94-145(5) AND 94-442(C), UPDATE THE | | | OPEN SPACE AREA CALCULATIONS ON THE LANDSCAPE PLAN | | | (SHEET NO. LP-1 OF 4). | | | | | | 4. PER SECTIONS 94-145(5) AND 94-442(C), UPDATE THE | | | LANDSCAPE AREA CALCULATIONS ON THE LANDSCAPE PLAN | | | (SHEET NO. LP-1 OF 4). | | | | | | 5. PER SECTION 94-443(C)(3)(A), EACH ROW OF PARKING | | | SPACES SHALL BE TERMINATED BY LANDSCAPED ISLANDS OF NOT | | | LESS THAN EIGHT FEET IN WIDTH AND NOT LESS THAN THE | | | LENGTH OF THE ADJACENT PARKING STALL. EACH LANDSCAPED | | | ISLAND SHALL HAVE A MINIMUM RADIUS OF TWO AND ONE-HALF | | | FEET AT ITS END SO AS TO ALLOW CAR MANEUVERING. EACH | | | LANDSCAPED ISLAND SHALL CONTAIN AT LEAST ONE CATEGORY 1 | | | SHADE OR FLOWERING TREE PER ROW OF PARKING. THEREFORE, | | | REVISE THE LANDSCAPE PLAN (SHEET NO. LP-1 OF 4), | | | ACCORDINGLY, AND PROVIDE THE DIMENSIONS OF THE PROPOSED | | | TERMINAL LANDSCAPE ISLANDS. | | | | | | 6. IT HAS BEEN IDENTIFIED THAT THE LANDSCAPE | | | REQUIREMENTS CHART (ON THE LANDSCAPE PLAN) INDICATES | | | 80% OF THE PROVIDED PARKING LOT TREES ARE CATEGORY 1 | | | TREES, HOWEVER, NONE OF THE PARKING LOT TREES ARE | | | CATEGORY 1 TREES. THEREFORE, REVISE THE LANDSCAPE PLAN | | | (SHEET NO. LP-1 OF 4), ACCORDINGLY. | | | | | | 7. PER SECTION 94-443(E)(1), AT LEAST 30 PERCENT OF THE | | | LINEAR FEET AROUND THE EXTERIOR OF ALL COMMERCIAL | | | STRUCTURES SHALL BE PLANTED WITH TREES, SHRUBS OR | | | HEDGES. THEREFORE, REVISE THE LANDSCAPE PLAN (SHEET NO. | | | LP-1 OF 4), ACCORDINGLY. | | | | | | 8. SHOW EXISTING AND PROPOSED EASEMENTS ON THE | | | LANDSCAPE PLAN (SHEET NO. LP-1 OF 4). | | | | | | 9. SHOW EXISTING AND PROPOSED UTILITIES (NOT LIMITED TO | | | OVERHEAD LINES, WATER METERS, TRANSFORMERS, CHECK | | | VALVES, CLEAN???OUTS, FIRE HYDRANTS, LIGHT POLES AND | | | OTHER STRUCTURES) ON THE LANDSCAPE PLAN (SHEET NO. LP-1 | | | OF 4). | | | | | | 10. PROVIDE THE DELINEATION OF IRRIGATION COVERAGE, | | | SENSORS AND HIGH, MEDIUM AND LOW ZONES OF WATER USAGE. | | | INCLUDE A STATEMENT THAT ALL LANDSCAPE AREAS, EXCLUDING | | | THOSE AREAS WITH NATIVE NONINVASIVE PLANTS, WILL BE | | | PROVIDED WITH PERMANENT AUTOMATIC IRRIGATION, INCLUDING | | | ADJACENT RIGHTS???OF???WAY. | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
1 |
Status |
F |
Date |
06-08-2023 |
|
|
Cont ID |
|
| Sent By |
relizond |
Date |
06-08-2023 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
relizond |
Date |
06-08-2023 |
Time |
08:18 |
Sent To |
|
|
| Notes |
| 2023-06-08 08:20:35 | -EXISTING STORM INTERCONNECTING PIPE CALLED OUT AS | | | SANITARY SEWER PIPE ON EXISTING CONDITIONS SHEET. | | | -EXISTING CLEANOUT NOT LEGIBLY SHOWN | | | -EXISITING WATER MAIN NOT SHOWN ON PLANS |
|
|
| Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
| Rev No |
1 |
Status |
F |
Date |
06-05-2023 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
06-05-2023 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2023-06-05 09:23:51 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | -SHOW AND LABEL IRRIGATION METER BOX AND BACKFLOW | | | ASSEMBLY NEAR NORTH PROPERTY LINE. ALSO ADD UTILITY | | | EASEMENT AROUND METER BOX IF ON PRIVATE PROPERTY AND | | | NONE CURRENTLY EXIST. | | | -SHOW UTILITIES ON LANDSCAPING PLANS AND ENSURE NO | | | LOCATION CONFLICTS BETWEEN UTILITIES AND PLANTS. | | | SPECIFICALLY ENSURE TREE DOES NOT CONFLICT WITH METERED | | | IRRIGATION WATER SERVICE NEAR THE NORTHEAST AREA. | | | -HISTORIC PICTURES OF 20TH ST. SEEMS TO SHOW GUY WIRE | | | ANCHORS WHERE PARKING SPOTS ARE PROPOSED. | | | RESPECTFULLY, | | | MARK HURLEY [email protected] |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
F |
Date |
06-08-2023 |
|
|
Cont ID |
|
| Sent By |
jbjoseph |
Date |
06-08-2023 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
jbjoseph |
Date |
06-08-2023 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2023-06-08 11:50:16 | PLEASE PROVIDE THE FOLLOWING: | | | 1. LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID | | | WASTE VOLUME PRODUCED ALONG WITH THE SIZE, TYPE AND | | | QUANTITY OF THE CONTAINER (I.E. DUMPSTER/COMPACTOR) | | | THAT WILL BE FOR THE SANITATION SERVICE. | | | 2. NOTE INDICATES THAT ROLL OUT CONTAINER WILL BE | | | STORED WITHIN BUILDING. PROVIDE DETAILS OF DESIGNATED | | | TRASH ROOM/STORAGE AREA FOR THE CONTAINER. | | | | | | FURTHER COMMENTS MAY BE FORTHCOMING | | | | | | BRUCELY A. JOSEPH | | | PUBLIC WORKS PROGRAM MANAGER | | | [email protected] | | | 561-494-1141 | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
06-01-2023 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
06-01-2023 |
Time |
19:18 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
06-01-2023 |
Time |
19:20 |
Sent To |
|
|
| Notes |
| 2023-06-01 19:19:40 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | 1. THE CITY'S OFFICIAL VERTICAL DATUM PER CITY CODE IS | | | NGVD1929. THE NAVD1988 VERTICAL DATUM MAY BE USED IF | | | THE CONVERSION EQUATION BETWEEN NAVD1988 AND NGVD1929 | | | IS PROVIDED. PROVIDE THE CONVERSION EQUATION ON THE | | | SURVEY. PROVIDE VERTICAL DATUM REFERENCE AND CONVERSION | | | EQUATION ON SHEET C3.1 AND ANY OTHER SHEET WITH | | | ELEVATION INFORMATION. | | | | | | 2. ADD TO THE SURVEY THE CATCH BASIN LOCATED IN THE | | | ALLEY NEAR THE SOUTHWEST CORNER OF THE PROPERTY AND ANY | | | OTHER UTILITIES IN THE RIGHTS OF WAY SURROUNDING THE | | | PROPERTY. AT A MINIMUM PROVIDE THE RIM/GRATE/VALVE | | | COVER ELEVATION. INVERT ELEVATIONS WILL BE NEEDED IF | | | CONNECTIONS ARE MADE TO THE UTILITIES. | | | | | | 3. LEGAL DESCRIPTION MISSING FROM SHEET C1.0. | | | | | | 4. SHEET C2.0 APPEARS TO BE MISLABELED AS EXISTING | | | CONDITIONS PLAN. DRAWING INDEX ON SHEET C1.0 LABELS | | | SHEET C2.0 AS PAVING, GRADING & DRAINAGE PLAN. | | | | | | 5. LOCATIONS OF EXISTING UTILITY STRUCTURES DO NOT | | | MATCH BETWEEN THE CIVIL PLANS AND THE SURVEY. | | | | | | 6. EXISTING STORM PIPE CONNECTED TO INLET IN THE ALLEY | | | IS LABELED AS EXISTING 8-INCH PVC SAN. CONFIRM ALL | | | EXISTING UTILITIES ARE LABELED AND LABELED CORRECTLY. | | | | | | 7. SHOW AND LABEL ALL EXISTING UTILITY STRUCTURES | | | WITHIN THE RIGHTS OF WAY SURROUNDING THE SUBJECT PARCEL | | | ON THE SURVEY AND CIVIL PLANS. | | | | | | 8. PROVIDE SECTIONS AT BOTH DRIVEWAYS, A SECTION | | | THROUGH THE PROPOSED PARALLEL PARKING SPACES ON 20TH ST | | | AND A SECTION FROM THE 5 FEET WEST OF THE WEST PROPERTY | | | LINE TO THE EDGE OF PAVEMENT OF N. DIXIE HIGHWAY. LABEL | | | THE PROPERTY LINE/RIGHT OF WAY LINE, SURFACE FEATURES, | | | RIGHT OF WAY NAMES. DIMENSION FROM RIGHT OF WAY LINE OR | | | PROPERTY LINE TO THE EDGE OF PAVEMENT, TO THE BACK OF | | | SIDEWALK, TO BACK OF CURB, TO HIGH AND LOW POINTS, ETC. | | | | | | 9. LABEL ALL OF THE RIGHTS OF WAY ON THE CIVIL PLANS. | | | | | | 10. INDICATE IF THE SIDEWALK IN THE ALLEY WILL BE FLUSH | | | WITH THE ALLEY. | | | | | | 11. WILL THE SIDEWALK IN THE ALLEY ON THE EAST SIDE OF | | | THE DRIVEWAY CONNECT WITH THE EXISTING SIDEWALK WEST OF | | | THE DRIVEWAY? IF SO, THE SIDEWALK WILL NEED TO BE | | | PLACED BEHIND THE EXISTING DRAINAGE INLET OR THE INLET | | | BE RELOCATED SOUTH OF THE PROPOSED SIDEWALK. | | | | | | 12. DRIVEWAY APRONS IN THE RIGHT OF WAY TO BE CONCRETE | | | PER THE CITY STANDARD DETAIL. | | | | | | 13. THE DIMENSIONS OF THE PARKING SPACES SHALL MEET THE | | | MINIMUM DIMENSIONS PROVIDED IN CITY CODE SECTION | | | 94-485. | | | | | | 14. INCLUDE THE HERRING BONE HATCH PATTERN IN THE | | | LEGEND ON SHEET C2.0. | | | | | | 15. INDICATE WHERE THE NYLOPLAST STRUCTURES WILL BE | | | CONSTRUCTED. | | | | | | 16. PROVIDE A DETAIL OF THE DRAINAGE CONTROL STRUCTURE | | | AND LIST THE CONTROL (WEIR) ELEVATION ON THE PGD PLAN. | | | THE CITY DOES NOT ALLOW THE USE OF BLEEDERS WITH | | | EXFILTRATION TRENCH SYSTEMS. | | | | | | 17. THE 15-INCH RCP OUTFALL PIPE FROM STRUCTURE CS-1 | | | APPEARS TO BE AT AN ADVERSE SLOPE. | | | | | | 18. CONFIRM THE PROPOSED NORTH DRIVEWAY LINES UP WITH | | | THE EXISTING DRIVEWAY. THE 11.86 SPOT GRADE ON SHEET | | | C2.0 APPEARS TO OVERLAP THE 11.82 SPOT GRADE ON THE | | | SURVEY. | | | | | | 19. PROPERLY LABEL THE EXISTING CURBS ON SHEET C2.0. | | | | | | 20. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP | | | CRITERIA. | | | | | | 21. ON THE EROSION CONTROL PLAN, CALL OUT WHERE BMPS | | | ARE TO BE INSTALLED. PROVIDE AN ALTERNATIVE TO HAY | | | BALES AROUND DRAINAGE STRUCTURES. | | | | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. PROVIDE A COPY OF THE SFWMD ERP BEFORE START OF | | | CONSTRUCTION. | | | | | | 2. PROVIDE EROSION AND SEDIMENT CONTROL PLAN WITH THE | | | ENGINEERING PERMIT SUBMITTAL. | | | | | | 3. STORMWATER MANAGEMENT CALCULATIONS WILL BE REVIEWED | | | WITH THE ENGINEERING PERMIT SUBMITTAL. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | [email protected] | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
06-08-2023 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
06-08-2023 |
Time |
09:37 |
Rev Time |
|
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2023-06-08 09:40:19 | 1. SURVEY NEEDS TO REFLECT AREA FOR DIXIE R/W CLAIMED | | | BY THE CITY PER THE MAINTENANCE MAP IN ROAD PLAT BOOK | | | 8, PAGE 137. | | | 2. APPLICATION HAS BEEN RECEIVED FOR UNITY OF TITLE. |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
06-08-2023 |
|
|
Cont ID |
|
| Sent By |
|
Date |
06-08-2023 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
06-08-2023 |
Time |
|
Sent To |
|
|
| Notes |
| 2023-06-08 12:28:31 | Z23040019 - 2025 N DIXIE PARKING LOT - PPRC - | | | 2023-06-08 | | | 1)PROVIDE AN UPDATED COUNTY TPS LETTER. GIVEN THE UNITY | | | OF TITLE, THE PARKING LOT IS NOW PART OF THE PROPOSED | | | DEVELOPMENT; THUS, TRIPS GENERATED BY THE PARCEL MUST | | | BE PROPERLY RECORDED IN THE COUNTY DATABASE. LATEST TPS | | | LETTER SHOWS ZERO DAILY AND PEAK HOUR TRIPS | | | 2) PROVIDE AN UPDATED AND CORRECTED TRANSPORTATION SITE | | | PLAN. SIGNAGE AND PAVEMENT MARKINGS ARE NOT PROPERLY | | | SHOWN NOR CORRECT IN LATEST SUBMISSION | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
06-02-2023 |
|
|
Cont ID |
|
| Sent By |
kdefranc |
Date |
06-02-2023 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
kdefranc |
Date |
06-02-2023 |
Time |
11:35 |
Sent To |
|
|
| Notes |
| 2023-06-02 11:35:34 | 6/2/23 ??? FAILED | | | | | | | | | PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN | | | RESUBMITTING: | | | A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL | | | DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION. | | | B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED | | | MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG | | | WITH ONE (1) REDUCED COPY (11 IN X 17 IN). | | | C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO | | | ADDITIONAL COMMENTS. | | | D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE | | | ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE | | | CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL | | | REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION. | | | E. PLEASE NOTE THAT YOU ARE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. A RESUBMITTAL FEE OF | | | 20% OF THE ORIGINAL APPLICATION FEE WILL BE ASSESSED | | | AFTER THE FIRST RESUBMITTAL. | | | | | | REQUIRED MATERIALS MUST BE PROVIDED: | | | F. PLEASE PROVIDE PROOF OF AN APPROVED AND RECORDED | | | UNITY OF TITLE OF THE TWO (2) PARCELS (PER CONDITION | | | NO. 1 OF THE CLASS B SPECIAL USE PERMIT ??? ZONING | | | BOARD OF APPEALS CASE NO. (ZBA) 3418). | | | G. PLEASE PROVIDE A CURRENT SURVEY. | | | H. PLEASE PROVIDE REVISED PLANS ADDRESSING THE REVIEW | | | COMMENTS BELOW. | | | I. PLEASE PROVIDE/INDICATE/DEMONSTRATE CONSISTENT | | | INFORMATION ON ALL THE DIFFERENT PLANS AND REQUIRED | | | MATERIALS WITHIN THE APPLICATION PACKET RESUBMITTAL. | | | | | | REVIEW COMMENT MUST BE ADDRESSED: | | | 1. IT HAS BEEN IDENTIFIED THAT THE APPROXIMATELY | | | 12-FOOT WIDE BY 50-FOOT LONG AREA EAST OF THE EXISTING | | | BUILDING IS NOT A PART OF THE PRIVATE PROPERTY, | | | THEREFORE, PLEASE PROVIDE A CURRENT SURVEY AND REVISED | | | PLANS. | | | 2. PLEASE IDENTIFY/INDICATE THE EXISTING/PROPOSED | | | EASEMENTS ON THE PLANS. | | | 3. IT HAS BEEN IDENTIFIED THAT THE BUILDING FOOTPRINT | | | ON THE PROPOSED FLOOR PLAN (SHEET NUMBER A1.0) AND THE | | | OTHER PLANS PROVIDED DO NOT MATCH. THEREFORE, PLEASE | | | REVISE THE PLANS, ACCORDINGLY. | | | 4. PLEASE IDENTIFY/INDICATE HOGANS STREET ON THE PLANS, | | | ACCORDINGLY. | | | 5. IT HAS BEEN IDENTIFIED THAT THE PROPOSED 70-DEGREE | | | ANGLED PARKING SPACES (STANDARD AND ADA) ARE NOT IN | | | COMPLIANCE WITH THE MINIMUM OFF-STREET PARKING | | | DIMENSIONAL REQUIREMENTS OF THE ZLDR SUBSECTION | | | 94-485(N), THEREFORE PLEASE REVISE THE PLANS, | | | ACCORDINGLY. | | | 6. IT HAS BEEN IDENTIFIED THAT THE PROPOSED WALL | | | (DEMONSTRATED ON PARCEL NUMBER 74434316150010070) IS | | | CLOSER THAN THE MINIMUM SIX (6) INCHES DISTANCE | | | REQUIREMENT ALONG THE SIDE LOT LINE ACCORDING TO THE | | | ZLDR SUBSECTION 94-273(D)(54)(B)(14), THEREFORE PLEASE | | | REVISE THE PLANS, ACCORDINGLY. | | | 7. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE VISIBILITY | | | TRIANGLE AREAS/DIMENSIONS AND | | | IDENTIFY/INDICATE/DEMONSTRATE THE PROPOSED WALLS | | | OUTSIDE OF THESE AREAS ON THE DIFFERENT PLANS ACCORDING | | | TO THE ZLDR SUBSECTION 94-305(E). | | | 8. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION, | | | HEIGHT AND INTENSITY OF ALL OUTDOOR ILLUMINATION ON THE | | | PLANS, ACCORDINGLY. | | | 9. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF | | | THE EXISTING AND PROPOSED FIRE HYDRANTS WITHIN 250 FEET | | | OF THE PROPOSED STRUCTURE ON THE PLANS. | | | 10. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION | | | OF THE PROPOSED PUBLIC ART ON THE PLANS. | | | 11. PLEASE IDENTIFY/INDICATE THE FUTURE LAND USE | | | DESIGNATIONS IN THE SITE TABULAR DATA ON SHEET NUMBER | | | SP-1 OF 1. | | | 12. PLEASE IDENTIFY/INDICATE SEPARATE AREA | | | ACREAGE/SQUARE FOOTAGE CALCULATIONS FOR BOTH PARCEL | | | NUMBERS 74-43-43-16-15-001-0010 AND | | | 74-43-43-16-15-001-0070 IN THE SITE TABULAR DATA ON | | | SHEET NUMBER SP-1 OF 1. | | | 13. PLEASE IDENTIFY/INDICATE THE EXISTING IMPERMEABLE | | | SURFACE LOT COVERAGE SQUARE FOOTAGE AND PERCENTAGE | | | CALCULATION IN RELATION TO PARCEL NUMBER | | | 74-43-43-16-15-001-0010 IN THE SITE TABULAR DATA ON | | | SHEET NUMBER SP-1 OF 1. | | | 14. PLEASE IDENTIFY/INDICATE THE PROPOSED IMPERMEABLE | | | SURFACE LOT COVERAGE SQUARE FOOTAGE AND PERCENTAGE | | | CALCULATION IN RELATION TO PARCEL NUMBER | | | 74-43-43-16-15-001-0010 IN THE SITE TABULAR DATA ON | | | SHEET NUMBER SP-1 OF 1. | | | 15. PLEASE IDENTIFY/INDICATE THE PROPOSED OPEN SPACE | | | AREA SQUARE FOOTAGE AND PERCENTAGE CALCULATION IN | | | RELATION TO PARCEL NUMBER 74-43-43-16-15-001-0010 IN | | | THE SITE TABULAR DATA ON SHEET NUMBER SP-1 OF 1. | | | 16. PLEASE IDENTIFY/INDICATE THE PROPOSED LANDSCAPE | | | SPACE AREA SQUARE FOOTAGE AND PERCENTAGE CALCULATION IN | | | RELATION TO PARCEL NUMBER 74-43-43-16-15-001-0010 IN | | | THE SITE TABULAR DATA ON SHEET NUMBER SP-1 OF 1. | | | 17. PLEASE IDENTIFY/INDICATE THE EXISTING BUILDING LOT | | | COVERAGE SQUARE FOOTAGE AND PERCENTAGE CALCULATION IN | | | RELATION TO PARCEL NUMBER 74-43-43-16-15-001-0010 IN | | | THE SITE TABULAR DATA ON SHEET NUMBER SP-1 OF 1. | | | 18. PLEASE IDENTIFY/INDICATE THE PROPOSED BUILDING LOT | | | COVERAGE SQUARE FOOTAGE AND PERCENTAGE CALCULATION IN | | | RELATION TO PARCEL NUMBER 74-43-43-16-15-001-0010 IN | | | THE SITE TABULAR DATA ON SHEET NUMBER SP-1 OF 1. | | | 19. PLEASE IDENTIFY/INDICATE THE EXISTING BUILDING | | | FLOOR AREA SQUARE FOOTAGE CALCULATION IN RELATION TO | | | PARCEL NUMBER 74-43-43-16-15-001-0010 IN THE SITE | | | TABULAR DATA ON SHEET NUMBER SP-1 OF 1. | | | 20. PLEASE IDENTIFY/INDICATE THE PROPOSED BUILDING | | | FLOOR AREA SQUARE FOOTAGE CALCULATION IN RELATION TO | | | PARCEL NUMBER 74-43-43-16-15-001-0010 IN THE SITE | | | TABULAR DATA ON SHEET NUMBER SP-1 OF 1. | | | 21. PLEASE REVISE THE PROPERTY DEVELOPMENT REQUIREMENTS | | | TABLE ON SHEET NUMBER SP-1OF 1 BY SEPARATING OUT THE | | | CODE REQUIREMENTS FOR THE MF14 AND GC ZONING DISTRICTS. | | | | | | | | | KEVIE DEFRANC | | | SENIOR PLANNER ??? PLANNING DIVISION | | | [email protected] | | | 561-822-1449 | | | |
|
|
| |