Plan Review Details - Project Z23030025
| Plan Review Stops For Project Z23030025 |
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
1 |
Status |
F |
Date |
03-29-2023 |
|
|
Cont ID |
|
| Sent By |
swelter |
Date |
03-29-2023 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
|
Date |
04-12-2023 |
Time |
13:11 |
Sent To |
|
|
| Notes |
| 2023-03-29 14:02:53 | DEVELOPMENT SUBJECT TO PUBLIC ART REQUIREMENT: | | | | | | DEVELOPER MUST INDICATE CLEARLY IN WRITING (MEMO) IF | | | THEY ARE CHOOSING: | | | | | | OPTION 1: ART ON SITE AT 1% OF THE TOTAL CONSTRUCTION | | | COSTS OR | | | OPTION 2: CONTRIBUTION INTO THE PUBLIC ART FUND AT .75% | | | | | | OPTION 1 DOES REQUIRE PROPOSED ART LOCATION FOR SITE | | | PLAN APPROVAL. IF DEVELOPER CHOOSES OPTION #1 IT MUST | | | BE CLEARLY MARKED (PROPOSED FUTURE PUBLIC ART SITE) ON | | | ALL SITE PLANS. FURTHER THE PROPOSED LOCATION MUST MEET | | | THE PUBLIC ART REQUIREMENTS. | | | | | | OF NOTE ARTWORK FOR COMPLIANCE WITH THE ART LIFE | | | ORDINANCE SHALL NOT BE CONSIDERED AS COMPLIANCE WITH | | | ANY REQUIREMENTS OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS RELATING TO THE PARKING GARAGE STRUCTURE | | | DESIGN. THE SCREENING OF THE GARAGE IS A SEPERATE | | | REQUIREMENT AND MAY NOT BE CONSIDERED AS MEETING THE | | | PUBLIC ART REQUIRMENT. | | | | | | PLEASE CONTACT SYBILLE WELTER | | | [email protected] | | | 561.822.1521 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
04-12-2023 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
04-12-2023 |
Time |
18:34 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
04-12-2023 |
Time |
18:34 |
Sent To |
|
|
| Notes |
| 2023-04-12 18:37:28 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. VAN ACCESSIBLE PARKING SPACES. WHEN SUBMITTED FOR | | | PERMIT AT LEAST ONE OF THE ACCESSIBLE PARKING SPACES | | | SHALL BE DESIGNATED AS VAN ACCESSIBLE. PER SECTION | | | 208.2.4 OF FLORIDA ACCESSIBILITY CODE, ONE IN EVERY SIX | | | REQUIRED ACCESSIBLE SPACES (AT LEAST ONE) IN A PARKING | | | STRUCTURE, SHALL BE ???VAN ACCESSIBLE??? AND DESIGNED | | | IN ACCORDANCE WITH SECTION OF 502 OF FLORIDA | | | ACCESSIBILITY CODE (VERTICAL CLEARANCE NOT LESS THAN 98 | | | INCHES AT SPACE AND VEHICULAR ACCESS ROUTE) | | | | | | 3. ELECTRIC VEHICLE CHARGING STATION. IF ELECTRIC | | | VEHICLE (EV) CHARGING STATIONS ARE PROVIDED AT LEAST 1 | | | IN 25 MUST COMPLY WITH ACCESSIBLE PARKING SPACE | | | REQUIREMENTS. | | | | | | 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, | | | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR | | | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, | | | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE | | | FLORIDA BUILDING CODE. | | | | | | 5. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND | | | OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT, | | | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF | | | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF | | | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE | | | VERIFIED. | | | | | | 6. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES | | | NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO | | | MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL | | | BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE | | | EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED | | | TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR | | | OTHER APPROVED METHODS. | | | | | | 7. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, | | | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND | | | OTHER FIRE SUPPRESSION SYSTEMS, BACKFLOW PREVENTERS, | | | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, | | | SITE IRRIGATION, ETC. | | | | | | 8. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND | | | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF | | | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL | | | NEIGHBORING PROPERTIES. THE CONTRACTOR SHALL SUBMIT A | | | CONSTRUCTION PARKING PLAN TO THE ENGINEERING SERVICES | | | DEPARTMENT. | | | | | | 9. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER | | | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, | | | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE | | | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF | | | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION | | | THAT MAY AFFECT THE USE OF THEIR PROPERTY. | | | | | | 10. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT | | | TO ART LIFE ASSESSMENT UNDER THE CITY OF WEST PALM | | | BEACH ART IN PUBLIC PLACES (AIPP) PROGRAM. FOR ADVICE | | | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP | | | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC | | | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
P |
Date |
06-22-2023 |
|
|
Cont ID |
|
| Sent By |
lquinone |
Date |
06-22-2023 |
Time |
19:21 |
Rev Time |
0.00 |
| Received By |
lquinone |
Date |
06-22-2023 |
Time |
19:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
03-31-2023 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
03-31-2023 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
03-31-2023 |
Time |
|
Sent To |
|
|
| Notes |
| 2023-03-31 11:04:12 | Z23030025 500 CLEARWATER, 28 STORY RES BLDG ??? 3.31.23 | | | 1ST REVIEW | | | | | | COMMENTS FROM LINDA QUINONES-CINTRON, PROJ. COORD., ENG | | | SERVICES, [email protected]: | | | GENERAL: | | | O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND | | | INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER | | | (Z-XXXXXXXX). | | | O THE CITY OF WEST PALM BEACH HAS A NUMBER OF | | | REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY | | | AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND | | | WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE | | | DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK | | | BELOW: | | | A. HTTPS://WWW.WPB.ORG/HOME/SHOWPUBLISHEDDOCUMENT/3266/ | | | 637521981284930000 | | | B. THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE | | | FOUND HERE: | | | HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING/ENGINEERING- | | | FORMS-PERMITS-AND-APPLICATIONS | | | C. ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM | | | BEACH, FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, | | | ADOPTED SEPT. 22, 2008. (SUPPLEMENT NO. 18) | | | CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL, | | | SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER | | | SERVICE FACILITIES OF THE CITY. | | | THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE | | | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY | | | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, | | | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. | | | O AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR | | | MORE INFORMATION, REFER TO THE LINK BELOW: | | | A. HTTPS://WWW.WPB.ORG/GOVERNMENT/PUBLIC-UTILITIES/BACK | | | FLOW-PREVENTION-AND-CROSS-CONNECTION | | | O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY | | | OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC | | | RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF | | | YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE | | | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL | | | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT | | | [email protected] OR 561-494-1079 FOR FURTHER | | | ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION | | | ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD | | | SURVEY, POT-HOLING, SOFT DIGS ETC. | | | O PROVIDE EXISTING AND PROPOSED PERVIOUS AND IMPERVIOUS | | | DATA. | | | | | | BACKFLOW ASSEMBLY AND METERS: | | | O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER | | | SERVICES AND WATER METERS, ALONG WITH WHAT IS HAPPENING | | | TO THEM. | | | O SHOW EXISTING AND PROPOSED DEDICATED UTILITY | | | EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO | | | PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO | | | STRUCTURES WITHIN EASEMENT. | | | O BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY | | | OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER | | | METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO | | | PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE | | | INSTALLED ABOVE-GROUND ONLY. | | | O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE | | | NOTE USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA. | | | | | | WATER/WASTEWATER PLAN: | | | O PLEASE SHOW PROJECT ADDRESS ON ALL PLAN SHEETS. | | | O PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE | | | STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC. | | | O PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND | | | DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND | | | SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH | | | PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE | | | AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS, | | | BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO | | | BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS, | | | DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS, | | | ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT | | | ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF | | | SANITARY SEWER LINES. | | | O GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR | | | SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE | | | PROFILE VIEW. | | | O DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN | | | VIEW FOR ALL SANITARY AND STORM SEWERS. | | | O SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT | | | MATERIAL. | | | O PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED | | | UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC, | | | ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION | | | FACILITIES INCLUDING PIPE SIZE AND MATERIAL LOCATED IN | | | THE RIGHT-OF-WAY. | | | O PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER | | | AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD | | | DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS. PLEASE | | | INCLUDE FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION & | | | TELECOMMUNICATION FACILITIES INCLUDING PIPE SIZE AND | | | MATERIAL LOCATED IN THE RIGHT-OF-WAY. | | | O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY | | | TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT | | | APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING | | | AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, | | | MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS | | | SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 | | | FOR WATER. | | | O PROVIDE FIRE FLOW TEST DATA. | | | O RECEIVED CCTV REPORT; PLEASE PROVIDE CCTV VIDEO OF | | | EXISTING SANITARY SEWER AND STORMWATER INFRASTRUCTURE | | | ALONG ENTIRE PROJECT FRONTAGE (CONDITION OF SITE PLAN | | | APPROVAL). | | | O CUT AND CAP UTILITIES NOT IN USE AND REMOVE ANY | | | ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY | | | ROW. | | | O WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL | | | BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY | | | PROPOSED LENGTH IN FEET. | | | O CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY | | | SEWER ARE REQUIRED. | | | O PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE | | | JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET. | | | O ADD NOTE TO PLANS SPECIFYING CITY???S DOWNSTREAM LIFT | | | STATION NUMBER. | | | O PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR | | | PROPOSED SANITARY LATERALS. | | | O LABEL WATER LINES AS PRIVATE WHERE APPLICABLE. | | | O PLEASE SHOW AND LABEL EXISTING AND PROPOSED GREASE | | | TRAPS (IF ANY). | | | O PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN | | | OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER. | | | | | | FORMAL ENGINEERING REVIEW: | | | O FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES | | | NOI REQUIREMENTS WILL BE ENFORCED. | | | - AN NOI IS REQUIRED FOR PROJECTS THAT: | | | - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS | | | THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF | | | DEVELOPMENT OR SALE; | | | - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE | | | STATE OR TO SURFACE WATERS OF THE STATE THROUGH A | | | MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4). | | | - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF | | | CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION | | | THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL | | | SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT | | | OF THE 10-2 CERTIFICATION. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF | | | WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING | | | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT | | | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING | | | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED | | | LEAD-FREE DESIGN. | | | O FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES | | | ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY | | | LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT | | | PARCELS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, IF WATER LINES ARE | | | BEING REPLACED IN ROW, SHOW ADJACENT PARCEL ADDRESSES. | | | O FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO PROVIDE | | | 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF | | | PROPOSED TRENCH IN CITY MAINTAINED ROADWAY AREAS PER | | | CITY OF WPB STANDARD DETAIL GC-8. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | CALCULATIONS OF PERVIOUS AND IMPERVIOUS AREAS FOR | | | PROPOSED IMPROVED AREAS. | | | QUESTIONS AND COORDINATION CONTACTS: | | | O MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR WITH | | | CITY OF WPB PUBLIC UTILITIES, REGARDING PLACEMENT OF | | | BACKFLOW DEVICES AND WATER METERS. CONTACT HIM AT | | | 561-822-2262 OR [email protected] | | | O COMMENTS FROM RICKY ELIZONDO, PUB. UTILITIES PLANS | | | EXAMINER, [email protected] , 561-494-1101: | | | O COMMENTS FROM TRACY WARD, SR. STORMWATER ENGINEER, | | | ENG. SERVICES DEPT. AT 561-494-1120 OR [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
06-01-2023 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
06-01-2023 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
06-01-2023 |
Time |
12:37 |
Sent To |
|
|
| Notes |
| 2023-06-01 12:37:43 | FIRE HAS NO OBJECTIONS TO THE PROPOSED AND APPROVES. | | | | | | FIRE'S APPROVAL OF THIS SUBMITTED PROJECT MAY NOT | | | CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | IF APPLICABLE, FIRE SHALL REVIEW ALL SUBMITTED PROJECT | | | PLANS AT THE APPLICABLE TIME AND IN ACCORDANCE WITH THE | | | REQUIREMENTS OF ALL APPLICABLE FIRE CODES AND | | | STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
04-06-2023 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
04-06-2023 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
04-06-2023 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2023-04-06 10:35:42 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE RESCUE. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT; HOWEVER, THE FOLLOWING COMMENTS ARE | | | PROVIDED AND MAY NEED FURTHER CLARIFICATIONS WHERE | | | APPLICABLE. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH | | | THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, | | | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. | | | | | | 6. ALL PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A, | | | PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE, | | | INCLUDING MORE SPECIFICALLY, CHAPTER 42 STORAGE | | | OCCUPANCIES (PARKING STRUCTURES) | | | | | | 7. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA | | | 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THIS | | | STRUCTURE. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE | | | BUILDING REACHES THREE LEVELS OR THIRTY FEET WHILE | | | BEING CONSTRUCTED. SEPARATE SHOP DRAWINGS, ARE REQUIRED | | | TO BE SUBMITTED, REVIEWED AND APPROVED BY THE FIRE | | | PREVENTION BUREAU PRIOR TO ANY INSTALLATION. | | | | | | IT IS RECOMMENDED FOR HIGH RISES HAVE TWO SEPARATE FDC | | | LOCATIONS REMOTELY LOCATED TO SERVE THE STANDPIPE | | | SYSTEM. | | | | | | 7A. PER NFPA 14 | | | 6.4.5.4* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED | | | NOT MORE THAN 100 FT (30.5 M) FROM THE NEAREST FIRE | | | HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY. | | | | | | 7B. PER NFPA 1 | | | 18.3 WATER SUPPLIES. | | | | | | 18.3.1* AN APPROVED WATER SUPPLY CAPABLE OF SUPPLYING | | | THE REQUIRED FIRE FLOW FOR FIRE PROTECTION SHALL BE | | | PROVIDED TO ALL PREMISES UPON WHICH FACILITIES, | | | BUILDINGS, OR PORTIONS OF BUILDINGS ARE HEREAFTER | | | CONSTRUCTED OR MOVED INTO THE JURISDICTION. THE | | | APPROVED WATER SUPPLY SHALL BE IN ACCORDANCE WITH | | | SECTION 18.4. | | | | | | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, | | | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE | | | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF | | | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, | | | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER | | | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) | | | AND ANY PERFORMANCE BASED INFORMATION SUCH AS | | | PRE-ENGINEERED SYSTEMS. | | | FOR THE PROPOSED FIRE PUMP(S) , WHAT IS(ARE) THE | | | PRIMARY AND SECONDARY POWER SOURCES? | | | | | | 7C. THE LOCATION OF THE DDCV FIRE LINE LOCATION SHALL | | | MEET THE REQUIREMENTS OF NFPA 24 AND SHALL BE | | | COORDINATED WITH THE OFFICE OF FIRE MARSHAL, THE CITY'S | | | ENGINEERS OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S | | | PLANNING AND ZONING OFFICE. | | | | | | 8. A NFPA 72 COMPLIANT MONITORED FIRE ALARM SYSTEM IS | | | REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP DRAWINGS, | | | ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY | | | THE FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION. | | | | | | 9. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7 | | | KEYWAY SYSTEM FOR BUILDING 6 OR MORE STORIES. | | | | | | ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTERS | | | EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA | | | B44, SAFETY CODE FOR ELEVATORS. | | | | | | ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN | | | WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL | | | LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET | | | MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER | | | ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN | | | AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE | | | IN THE HORIZONTAL POSITION. | | | | | | 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, | | | EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A | | | PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE | | | SAFETY FEATURES AND EQUIPMENT. | | | | | | 11. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | ALL NEW FIRE HYDRANTS AND FDCS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE | | | BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND | | | FDCS SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET | | | OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER | | | ARRIVING EMERGENCY VEHICLES. | | | | | | 12. EMERGENCY COMMUNCATION CENTER - COMMAND ROOM | | | | | | THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1, | | | CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN | | | THE FOLLOWING FEATURES: | | | | | | 11.9.1 THE LOCATION, DESIGN, CONTENT, AND FIRE | | | DEPARTMENT ACCESS OF THE EMERGENCY COMMAND CENTER SHALL | | | BE APPROVED BY THE FIRE DEPARTMENT. | | | | | | 11.9.2 THE EMERGENCY COMMAND CENTER SHALL BE SEPARATED | | | FROM THE REMAINDER OF THE BUILDING BY A FIRE BARRIER | | | HAVING A FIRE RESISTANCE RATING OF NOT LESS THAN 1 | | | HOUR. | | | | | | 11.9.3 THE EMERGENCY COMMAND CENTER ROOM SHALL BE A | | | MINIMUM OF 200 FT2 (19 M2) WITH A MINIMUM DIMENSION OF | | | 10 FT (3050 MM). | | | | | | 11.9.4 THE FOLLOWING SHALL BE PROVIDED IN THE EMERGENCY | | | COMMAND CENTER. | | | (1) THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM. | | | (2) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED | | | ACCESS TO THE PUBLIC TELEPHONE SYSTEM | | | (3) SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL | | | FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF | | | EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING | | | EQUIPMENT AND FIRE DEPARTMENT ACCESS | | | (4) WORK TABLE. | | | (5) IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN | | | FOR THE BUILDING. | | | 11.9.5 WHERE OTHERWISE REQUIRED, THE FOLLOWING DEVICES | | | OR FUNCTIONS SHALL BE PROVIDED WITHIN THE EMERGENCY | | | COMMAND CENTER. | | | (1) THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM | | | CONTROL UNIT. | | | (2) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT. | | | (3) ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION | | | OF THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL | | | (4) STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING | | | SYSTEMS. | | | (5) CONTROLS FOR UNLOCKING STAIRWAY DOORS | | | SIMULTANEOUSLY | | | (6) SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY | | | PANELS | | | (7) EMERGENCY AND STANDBY POWER STATUS INDICATORS | | | (8) FIRE PUMP STATUS INDICATORS | | | (9) GENERATOR SUPERVISION DEVICES AND MANUAL START AND | | | TRANSFER FEATURES. | | | (10) PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED | | | BY OTHER SECTIONS OF THIS CODE | | | (11) CONTROLS REQUIRED FOR SMOKE CONTROL | | | | | | AND NFPA 101 | | | | | | 11.8.6* EMERGENCY COMMAND CENTER. | | | 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED | | | IN A | | | LOCATION APPROVED BY THE FIRE DEPARTMENT. | | | 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE | | | FOLLOWING: | | | (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS | | | (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION | | | SERVICE | | | PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER SECTION | | | OF THIS | | | CODE | | | (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION | | | PANELS | | | (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS | | | (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME | | | A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS | | | (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE | | | PROVIDED | | | IN ACCORDANCE WITH ASME A17.1/CSA B44 | | | (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS | | | (8) EMERGENCY GENERATOR STATUS INDICATORS | | | (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING | | | SYSTEM | | | (10) FIRE PUMP STATUS INDICATORS | | | (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED | | | ACCESS TO THE | | | PUBLIC TELEPHONE SYSTEM | | | (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY | | | 11.8.8 | | | 13. TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEMS. | | | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY | | | RADIO ENHANCEMENT SERVICES. | | | 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM | | | RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT | | | COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL | | | DETERMINED BY THE AHJ. | | | NFPA 72, 24.9 TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT | | | SYSTEMS. | | | 24.9.1 GENERAL. | | | 24.9.1.1 NON-INTERFERENCE. NO AMPLIFICATION SYSTEM | | | CAPABLE | | | OF OPERATING ON FREQUENCIES OR CAUSING INTERFERENCE ON | | | FREQUENCIES | | | ASSIGNED TO THE JURISDICTION BY THE FCC SHALL BE | | | INSTALLED | | | WITHOUT PRIOR COORDINATION AND APPROVAL OF THE | | | AUTHORITY | | | HAVING JURISDICTION. THE BUILDING MANAGER/OWNER SHALL | | | SUSPEND AND CORRECT OTHER EQUIPMENT INSTALLATIONS THAT | | | DEGRADE | | | THE PERFORMANCE OF THE PUBLIC SAFETY RADIO SYSTEM OR | | | PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM. | | | 24.9.1.2 APPROVAL AND PERMIT. PLANS SHALL BE SUBMITTED | | | FOR | | | APPROVAL PRIOR TO INSTALLATION. AT THE CONCLUSION OF | | | SUCCESSFUL | | | ACCEPTANCE TESTING, A RENEWABLE PERMIT SHALL BE ISSUED | | | FOR THE | | | PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM WHERE REQUIRED | | | BY | | | THE AUTHORITY HAVING JURISDICTION. | | | | | | THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL | | | STRENGTH OF THE RADIO SYSTEM USED BY WEST PALM BEACH | | | FIRE DEPARTMENT. TESTING SHALL BE BY AN ACCEPTABLE | | | NATIONAL STANDARD DOCUMENTING PERCENTAGES NOTED ABOVE | | | AND BY ACTUAL RADIO TESTING BY FIRE PERSONNEL. IF THE | | | MINIMUM CANNOT BE MAINTAINED, A BI-DIRECTIONAL | | | AMPLIFIED SYSTEM SHALL BE INSTALLED WITH A MINIMUM | | | 2-HOUR RUN TIME BATTERY BACK-UP. | | | | | | PLEASE CONTACT MARK FILLA, PALM BEACH COUNTY PUBLIC | | | SAFETY RADIO SYSTEMS MANAGER, [email protected], | | | 561-233-0837; AS OUR RADIOS OPERATE ON THEIR SYSTEM FOR | | | DETAILED RADIO FREQUENCY AND INSTALLATION INSTRUCTIONS. | | | | | | | | | 14. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS | | | BUILDING. | | | | | | ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS, | | | PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS. | | | | | | 15. THE SMOKE CONTROL SYSTEM SHALL COMPLY WITH NFPA | | | 101, CHAPTER 9, BUILDING SERVICE AND FIRE PROTECTION | | | EQUIPMENT, INCLUDING: | | | | | | THE SMOKE CONTROL SYSTEMS SHALL BE INSTALLED, | | | INSPECTED, TESTED, AND MAINTAINED IN ACCORDANCE WITH | | | NFPA 92, STANDARD FOR SMOKE CONTROL SYSTEMS; NFPA 204, | | | STANDARD FOR SMOKE AND HEAT VENTING; OR NATIONALLY | | | RECOGNIZED STANDARDS, ENGINEERING GUIDES, OR | | | RECOMMENDED PRACTICES, AS APPROVED BY THE AUTHORITY | | | HAVING JURISDICTION. | | | | | | THE ENGINEER OF RECORD SHALL CLEARLY IDENTIFY THE | | | INTENT OF THE SYSTEM, THE DESIGN METHOD USED, THE | | | APPROPRIATENESS OF THE METHOD USED, AND THE REQUIRED | | | MEANS OF INSPECTING, TESTING, AND MAINTAINING THE | | | SYSTEM. | | | | | | ACCEPTANCE TESTING SHALL BE PERFORMED BY A SPECIAL | | | INSPECTOR IN ACCORDANCE WITH NFPA 101 SECTION 9.13. | | | | | | 16. AREAS OF REFUGE SHALL COMPLY WHERE APPLICABLE PER | | | THE BUILDING CODE AND NFPA 101, CH 7, MEANS OF EGRESS. | | | | | | 17. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | 18. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
F |
Date |
06-29-2023 |
|
|
Cont ID |
|
| Sent By |
cibaven |
Date |
06-29-2023 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
cibaven |
Date |
06-29-2023 |
Time |
16:57 |
Sent To |
|
|
| Notes |
| 2023-06-29 17:01:12 | LANDSCAPE COMMENTS | | | | | | 1.SECTION 94-448 (D)(3) REQUIRES NATIVE TREES AND PALMS | | | IN GOOD CONDITION TO BE PRESERVED ON SITE OR RELOCATED. | | | ANSI 300 (PART 5) STANDARDS SPECIFY EXAMPLES OF | | | SUITABILITY RATINGS OF GOOD, MODERATE, OR POOR FOR | | | RELOCATION. MITIGATION SHOULD BE RECALCULATED UPON | | | RECEIPT OF ARBORIST REPORT. | | | | | | APPLICANT RESPONSE: DUE TO THE AREA CONSTRAINTS OF THE | | | SITE (LIMITED SPACE TO PLANT) AND THE QUALITY OF THE | | | EXISTING LANDSCAPING PROPOSED, ONLY ONE TREE IS | | | PROPOSED TO BE SAVED. ALL OTHERS WILL BE REMOVED. SEE | | | THE ARBORIST REPORT INCLUDED WITH THIS SUBMITTAL FOR | | | TREE RATINGS AND DETAILS. | | | | | | [NOT SATISFIED] TREE DISPOSITION CHART ON LP-1 LISTS | | | TREES 1,8,9, AND 11 IN GOOD CONDITION. TREES IN GOOD | | | CONDITION MUST BE PRESERVED OR RELOCATED ON SITE. THE | | | TREES LISTED ON THE DISPOSITION ARE NOT NUMBERED THE | | | SAME AS THE ARBORIST REPORT SO IT IS DIFFICULT TO TELL | | | WHICH TREE IS WHICH AS THE REPORT CONFLICTS WITH THE | | | RATINGS ON THE CHART. THE TREE RATINGS (SHOULD BE | | | LISTED AS GOOF, FAIR, POOR, ETC AND NOT IN A | | | PERCENTAGE) SHOULD COME FROM THE ARBORIST REPORT. | | | | | | | | | NEW COMMENT: TREE CANOPY SIZE LISTED ON THE TREE | | | DISPOSITION ARE INACCURATE AND DO NOT MATCH THE TREES | | | SHOWN IN THE IMAGES OF THE ARBORIST REPORT. PLEASE | | | PROVIDE CORRECT TREE CANOPY SQUARE FOOTAGE OF EXISTING | | | TREES. STAFF WILL SPOT CHECK IN THE FIELD TO VERIFY. | | | | | | | | | CONDITION OF APPROVAL: ARTIFICIAL TURF CANNOT BE VIEWED | | | FROM THE STREET OR ROAD. SCREENING SUBJECT TO FINAL | | | INSPECTION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
04-26-2023 |
|
|
Cont ID |
|
| Sent By |
cibaven |
Date |
04-26-2023 |
Time |
10:17 |
Rev Time |
0.00 |
| Received By |
cibaven |
Date |
04-26-2023 |
Time |
10:16 |
Sent To |
|
|
| Notes |
| 2023-04-26 10:17:08 | PROJECT: 500 CLEARWATER PARK RD (Z23030025) | | | | | | LANDSCAPE COMMENTS | | | 1. SECTION 94-448 (D)(3) REQUIRES NATIVE TREES AND | | | PALMS IN GOOD CONDITION TO BE PRESERVED ON SITE OR | | | RELOCATED. ANSI A 300 (PART 5) STANDARDS SPECIFY | | | EXAMPLES OF SUITABILITY RATINGS OF GOOD, MODERATE, OR | | | POOR FOR RELOCATION. MITIGATION SHOULD BE RECALCULATED | | | UPON RECEIPT OF ARBORIST REPORT. | | | 2. LOCATION OF STREET TREES ARE IN CONFLICT WITH | | | DRAINAGE LINE ON THE FRONT OF THE BUILDING, PLEASE | | | REVISE. IN ADDITION, PLEASE SHOW ALL EXISTING AND | | | PROPOSED WATER AND SEWER AND DRAINAGE LINES ON THE | | | LANDSCAPE PLANS. SHOW LOCATIONS OF BACKFLOWS AND ADJUST | | | LOCATIONS OF UTILITY LINES TO RESOLVE CONFLICTS WITH | | | EXISTING AND PROPOSED TREES AND LANDSCAPING. | | | 3. PLEASE CONSIDER TO A DIFFERENT GROUNDCOVER OTHER | | | THAN SOD OR SHRUB PLANTING ON PLANTING BEDS/LANDSCAPE | | | STRIPS ADJACENT TO THE STREET DUE TO THE REMOVAL OF | | | STREET TREES. | | | 4. SILVER BUTTONWOOD TREES SHOULD NOT BE SPACED ANY | | | LESS THAN 10 FEET ON CENTER. | | | 5. ALL MECHANICAL EQUIPMENT ON THE GROUND FLOOR SHOULD | | | BE SHOWN ON THE LANDSCAPE PLANS AND SHOULD BE SCREENED | | | APPROPRIATELY PER SEC. 94-315(A). ALL WALL MOUNTED | | | EQUIPMENT SHALL BE SCREENED FROM VIEW WITH A SCREEN | | | EQUAL TO THE HEIGHT OF THE EQUIPMENT. | | | 6. ARTIFICIAL TURF AREAS PROPOSED MUST MEET THE | | | REQUIREMENTS OF SECTION 94-451, INCLUDING ALL AREAS | | | THAT ARE ALLOWED BY CODE MUST NOT BE VISIBLE FROM A | | | ROAD OR STREET. ARTIFICIAL TURF CANNOT BE PLACED IN | | | REQUIRED LANDSCAPE AREAS. | | | 7. ALL LANDSCAPED AREAS AND PLANT MATERIALS WITHIN OR | | | ADJACENT TO VEHICULAR USE AREAS SHALL BE PROTECTED FROM | | | VEHICULAR ENCROACHMENT BY WHEEL STOPS, CURBS, OR OTHER | | | SIMILAR DEVICES. | | | | | | |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2023-06-16 16:46:55 | -ENSURE THAT 36" MAIN IS SENTERED BETWEEN EXISTING | | | EASEMENT. PLAN VIEW MAKES IT APPEAR AS IF MAIN IS ON | | | EASTERN BIRDER OF EASEMENT. | | | -CONSIDER THE DEPTH OF THE 36" MAIN WHEN MILLING AND | | | RESURFACING, AS WELL AS OTHER PHASES OF CONSTRUCTION. | | | AVIBRATION IMPACT STUDY MAY BE NEEDED. | | | -COMMENT 6 NOT FULLY ADDRESSED. SOME CROSSING INFO | | | STILL MISSING | | | -COMMENT 8 NOT FULLY ADDRESSED. SHOW RELEVANT UTILITIES | | | CROSSED (INCLUDING FRANCHISE UTILITIES) | | | -COMMENT 15 NOT FULLY ADDRESSED, CCTV APPEARS TO SHOW | | | EXISTING LATERAL ON SITE. | | | | | | RICKY ELIZONDO | | | [email protected] | | | |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
1 |
Status |
F |
Date |
04-13-2023 |
|
|
Cont ID |
|
| Sent By |
relizond |
Date |
04-13-2023 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
relizond |
Date |
04-13-2023 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2023-04-13 11:38:49 | -PLEASE ADHERE TO DETAIL P-6 FOR PIGGING AND FLUSHING | | | ASSEMBLY | | | -PLEASE SUPPLY WATER AND SEWER DEMAND TABLE FOR | | | EXISTING AND PROPOSED CONDITIONS | | | -DENOTE THAT PROJECT FALLS WITHIN LIFT STATION 23 | | | BOUNDARIES | | | -SCALE PLAN VIEW SO THAT IT CAN BE PRINTED TO SCALE ON | | | 11X17 | | | -VERIFY EXISTING HYDRANT HAS ANCHOR TEE INSTALLED, ADD | | | ONE IF NOT | | | -CROSSING INFORMATION NEEDED AT ALL LOCATIONS WHERE | | | PROPOSED WORK WILL BE IN CONFLICT WITH EXISTING | | | UTILITIES | | | -SHOW AND LABEL ALL EXISTING AND PROPOSED UTILITY | | | EASEMENTS | | | -PROVIDE PROFILES FOR PROPOSED WATER AND SEWER LINES UP | | | TO R/W LINE | | | -PROVIDE AN ERP FOR THE 36" WM ON THE EAST SIDE OF THE | | | PROPERTY | | | -VERIFY LOCATION OF EXISTING SANITARY MANHOLE WITH | | | PROPOSED CONNECTION (IF MANHOLE EXISTS, IT WILL REQUIRE | | | REHABBING. IF NO MANHOLE EXISTS IN LOCATION SHOWN ON | | | PLANS, A DOGHOUSE MANHOLE WILL NEED TO BE PROPOSED. | | | -PROVIDE CCTV OF EXISTING SEWER LINE BETWEEN THE | | | NEAREST OFFSITE MANHOLE TO THE NORTH AND SOUTH OF THE | | | PROJECT LOCATION. | | | -CALL OUT ALL VALVES AND APPURTENANCES FOR EXISTING AND | | | PROPOSED UTILITIES | | | -8" CLEANOUT REQUIRED FOR 8" SANITARY SEWER LATERALS | | | -SOURCE SAMPLE POINT REQUIRED FOR DOMESTIC LINE PER P-6 | | | -EXISTING SEWER LATERAL NOT SHOWN, IT WILL NEED TO BE | | | CUT AND CAP AT THE MAIN. | | | -ADD LEGEND TO UTILITY PLAN | | | -SPECIFY THE WORK BEING PROPOSED TO THE EXISTING 12" | | | WATER MAIN | | | -CALL OUT PIPE SIZE AND MATERIAL FOR ALL EXISTING AND | | | PROPOSED UTILITIES |
|
|
| Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
| Rev No |
2 |
Status |
F |
Date |
06-07-2023 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
06-07-2023 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2023-06-07 15:59:46 | PLEASE PROVIDE WRITTEN RESPONSE TO THE FOLLOWING: | | | -LANDSCAPING PLANS SHOW PLANTS OR BUSHES WHERE METERED | | | WATER SERVICE AND BACKFLOW ASSEMBLIES ARE LOCATED. | | | PLEASE RELOCATE THOSE PLANTS AND UPDATE LANDSCAPING | | | PLAN. | | | -ADJUST PROPOSED UTILITY EASEMENT BOUNDARIES AND | | | RELOCATE FIRELINE BACKFLOW ASSEMBLY SLIGHTLY EAST SO IT | | | IS OUT OF UTILITY EASEMENT. | | | -ON CIVIL PLANS THERE ARE SOME CIRCULAR OBJECTS NEAR | | | THE WESTERN PROPERTY LINE. THOSE SEEM TO BE THE | | | MOVEABLE PLANTERS. PLEASE LABEL THEM OR ADD TO LEGEND. | | | RESPECTFULLY, | | | MARK HURLEY [email protected] |
|
|
| Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
| Rev No |
1 |
Status |
F |
Date |
04-07-2023 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
04-07-2023 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2023-04-07 14:01:46 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | -PLEASE CLEARLY SHOW AND LABEL WESTERN PROPERTY LINE ON | | | ENGINEERING PLAN SHEETS. | | | -SHOW AND LABEL EXISTING 10 FOOT UTILITY EASEMENT NEAR | | | WESTERN PROPERTY LINE ON ENGINEERING PLAN SHEETS. | | | -ADD LEGEND TO ENGINEERING PLAN SHEETS. PLEASE INCLUDE | | | PURPLE LETTERED SYMBOLS AND LINES ON IT. | | | -ADD GRAPHIC SCALE TO BLOWUP DETAIL ON SHEET C08. | | | -4 INCH WATER METER IS ON PRIVATE PROPERTY, BUT NOT | | | CONTAINED WITHIN A UTILITY EASEMENT. | | | -VERIFY PRIVATE FIRE SYSTEM WILL NOT HAVE ADDED | | | CHEMICALS AND WILL NOT BE CONNECTED TO AUXILIARY WATER | | | SUPPLY SUCH AS A WELL. | | | -LANDSCAPING APPEARS TO CONFLICT WITH PROPOSED METERED | | | WATER SERVICES AND BACKFLOW ASSEMBLIES. IN RESUBMITTAL | | | PACKAGE, ADD LANDSCAPING PLAN SHEET THAT SHOWS PROPOSED | | | UTILITIES AND PLANTS. ENSURE NO LOCATION CONFLICTS | | | BETWEEN TREES/BUSHES AND UTILITIES. | | | -A1.1 AND LP2 DO NOT SHOW SIMILAR DESIGN OF BIKE RACKS | | | NEAR EAST SIDE OF PROPERTY. ENSURE PLANS MATCH AND THEN | | | ADD THE BIKE RACKS TO SHEET C08. | | | -UTILITY BILLING SYSTEM SHOWS EXISTING 1 INCH METERED | | | IRRIGATION WATER SERVICE AT THE PROPERTY. SHOW ON | | | ENGINEERING PLANS AND LABEL WHAT IS HAPPENING TO IT. | | | -SHOW FDC IF ANY ARE NEEDED OR REQUIRED. | | | -SURVEY AND DEMO PLAN SHOW TRANSFORMER PAD NEAR | | | NORTHEAST CORNER OF PROPERTY, BUT THEY ARE NOT SHOWN ON | | | OTHER PLAN SHEETS. SHOW AND LABEL ON REST OF PLAN | | | SHEETS IF IT WILL REMAIN. | | | RESPECTFULLY, | | | MARK HURLEY [email protected] |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
2 |
Status |
P |
Date |
06-20-2023 |
|
|
Cont ID |
|
| Sent By |
jbjoseph |
Date |
06-20-2023 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
jbjoseph |
Date |
06-20-2023 |
Time |
08:55 |
Sent To |
|
|
| Notes |
| 2023-06-20 08:56:33 | NO COMMENTS |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
F |
Date |
04-12-2023 |
|
|
Cont ID |
|
| Sent By |
jbjoseph |
Date |
04-12-2023 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
jbjoseph |
Date |
04-12-2023 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2023-04-12 13:11:26 | PLEASE PROVIDE THE FOLLOWING: | | | 1. LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID | | | WASTE VOLUME PRODUCED ALONG WITH THE SIZE, TYPE AND | | | QUANTITY OF THE CONTAINER (I.E. DUMPSTER/COMPACTOR) | | | THAT WILL BE FOR THE SANITATION SERVICE. | | | 2. INDICATE STAGING LOCATION OF BULK TRASH | | | | | | BRUCELY A. JOSEPH | | | PW PROGRAM MANAGER | | | [email protected] | | | 561-494-1141 | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
F |
Date |
07-11-2023 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
07-10-2023 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
07-10-2023 |
Time |
12:32 |
Sent To |
|
|
| Notes |
| 2023-07-10 12:31:46 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE | | | 5/26/23 SUBMITTAL. | | | | | | 1. STAFF COULD NOT LOCATE THE NAVD1988 TO NGVD1929 | | | CONVERSION EQUATION ON THE SURVEY. PLEASE IDENTIFY THE | | | PAGE AND QUADRANT WHERE THE INFORMATION IS LOCATED. | | | | | | 2. PAVING, GRADING AND DRAINAGE PLAN (SHEET C-04) | | | A. ADJUST LEADER ARROWS TO POINT TO THE DRAINAGE | | | STRUCTURES (#1, #6). | | | | | | B. PROVIDE VERTICAL CLEARANCE BETWEEN OUTSIDES OF THE | | | PROPOSED 15-INCH RCP FROM STRUCTURE #6 AND THE EXISTING | | | 12-INCH WATER MAIN. | | | | | | C. LABEL THE WATER MAIN (SIZE, MATERIAL) AND OTHER | | | UTILITIES. | | | | | | D. CONFIRM THE PROPSED GUTTER ALONG THE CLEARWATER PARK | | | ROAD WILL HAVE MINIMUM 0.15% (PREFERABLY 0.3%) | | | LONGITUDINAL SLOPE TO PREVENT STANDING WATER. | | | | | | 3. CROSS SECTIONS (SHEET C-05) | | | A. PROVIDE FLOW ARROW FOR PROPOSED PASSENGER LOADING | | | ZONE IN SECTION B-B. | | | | | | B. PROVIDE THE DIMENSION BETWEEN THE BACK OF VALLEY | | | GUTTER AND THE BACK OF THE TYPE D CURB IN SECTION B-B. | | | | | | 4. PAVING, GRADING AND DRAINAGE DETAILS (SHEET C-07) | | | A. ACCESSIBLE PARKING SPACE - ADA COMPLIANT DETAIL | | | I. LEADER LABELS CALLOUT OUT 4" DBL WHITE AND 6" DBL | | | BLUE STRIPES. DOES DBL STAND FOR DOUBLE? SINGLE WHITE | | | AND BLUE STRIPES MAY BE APPROPRIATE. | | | II. THE ENDS OF THE STIPING SHOULD BE CONNECTED WITH | | | 12" LONG STRIPE AS INDICATED IN THE CITY OF WEST PALM | | | BEACH PARKING STALL SIZES DETAIL. | | | | | | 5. TRAFFIC FEATURES PLAN (SHEET T-1.0) - ANY SIGNAGE | | | PROPOSED FOR THE PASSENGER LOADING ZONE? | | | | | | 6. THE EXISTING STORM PIPE UNDER THE SWALE GOES FROM | | | THE CATCH BASIN EAST OF STRUCTURE #5 TO THE CATCH BASIN | | | IN THE DRIVEWAY SOUTH OF 500 DLEARWATER PARK DRIVE. THE | | | DESIGN PLANS FOR THIS PIPE SHOW THE INVERT OF THE SOUTH | | | END OF THE PIPE (NORTH INVERT IN THE DRIVEWAY CATCH | | | BASIN) AS BEING 4.4 FEET BELOW THE GRATE ELEVATION AND | | | THE INVERT OF THE NORTH END OF THE PIPE (SOUTH INVERT | | | OF THE SWALE CATCH BASIN) AS BEING 2.73 FEET BELOW THE | | | GRATE ELEVATION. THIS STORM PIPE MAY BE IN CONFLICT | | | WITH THE PROPOSED SANITARY MH#2. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
04-12-2023 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
04-12-2023 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
04-12-2023 |
Time |
13:46 |
Sent To |
|
|
| Notes |
| 2023-04-12 13:45:23 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | 1. THE CITY???S OFFICIAL VERTICAL DATUM PER CITY CODE | | | IS NGVD1929. THE NAVD1988 VERTICAL DATUM MAY BE USED IF | | | THE CONVERSION EQUATION BETWEEN NAVD1988 AND NGVD1929 | | | IS PROVIDED. PROVIDE THE CONVERSION EQUATION TO | | | NGVD1929 ON THE SURVEY. | | | | | | 2. VICINITY SKETCH MISSING ON THE SURVEY. | | | | | | 3. PROVIDE PROPOSED GRADES OR FLOW ARROWS ON THE PGD | | | PLAN. SUGGEST MOVING CATCH BASIN NO. 1 EASTWARD TO THE | | | OPEN PARKING AREA OR INSTALL A TRENCH DRAIN ACROSS THE | | | OPENING TO INTERCEPT SURFACE FLOW BEFORE IT ENTERS THE | | | COVERED PARKING AREA. | | | | | | 4. PROVIDE A CROSS SECTIONS AT THE DRIVEWAY AND AT THE | | | ON-STREET PARKING SPACE FROM THE CENTERLINE OF | | | CLEARWATER PARK ROAD TO 5 FEET BEYOND THE HIGH POINT OF | | | THE DRIVEWAY. SHOW BREAK POINTS, LABEL SURFACE FEATURES | | | SUCH AS GUTTERS, SIDEWALK AREAS, FACE OF BUILDING, | | | RIGHT OF WAY, ETC. PROVIDE DIMENSIONS FROM R/W TO EDGE | | | OF PAVEMENT, TO FRONT OF SIDEWALK AREA, TO FACE OF | | | BUILDING, TO HIGH POINT OF DRIVEWAY. PROVIDE SLOPE | | | ARROWS TO SHOW HOW THE SURFACES ARE TO DRAIN. | | | | | | 5. REPLACE THE CMP PIPE IN THE R/W WITH RCP PIPE. | | | | | | 6. GARAGE GROUND FLOOR TO HAVE SUFFICIENT VERTICAL | | | CLEARANCE TO ALLOW MAINTENANCE AND EVENTUAL REPLACEMENT | | | OF THE EXFILTRATION TRENCH SYSTEM WHEN IT NO LONGER | | | FUNCTIONS AS DESIGNED. | | | | | | 7. THE CITY DOES NOT ALLOW THE USE OF BLEEDERS WITH | | | EXFILTRATION SYSTEMS. | | | | | | 8. IT APPEARS THE PROPOSED 8 INCH SANITARY MAIN WILL BE | | | IN CONFLICT WITH THE EXISTING 24 INCH STORM PIPE. | | | | | | 9. THE FIRE HYDRANT EXTENSION MAY BE IN CONFLICT WITH | | | THE 24 INCH STORM PIPE. CONSIDER MOVING THE FH TO THE | | | UTILITY EASEMENT AT THE BACK OF SIDEWALK. | | | | | | 10. ON-STREET PARKING SPACE SHOULD BE ASPHALT INSTEAD | | | OF CONCRETE. | | | | | | 11. SHOW MILL AND RESURFACE LIMITS PER THE CITY???S | | | PIPE TRENCH DETAIL. | | | | | | 12. PROVIDE A DETAIL OF THE CONTROL STRUCTURE. PRB'S | | | SHOULD BE USED AT THE ENDS OF EXFILTRATION TRENCHES TO | | | EXTEND THE LIFE OF THE TRENCHES. | | | | | | 13. SHEET C-06 - UPDATE REFERENCES TO FDOT STANDARD | | | INDEX NUMBERS TO FDOT STANDARD PLAN NUMBERS | | | A. INDEX 17355 = PLAN 700-102 | | | B. INDEX 17346 = PLAN 711-001 | | | | | | 14. ON PMS PLAN (SHEET C-16) , PLACE THE 24??? STOP BAR | | | ON THE NORTH SIDE OF THE DOUBLE YELLOW FOR THE TRAFFIC | | | EXITING THE GARAGE. | | | | | | 15. SHEET C-17, EROSION CONTROL PLAN: | | | A. MOVE THE SOIL TRACKING PREVENTION DEVICE OUT OF THE | | | R/W. | | | B. SHOW THE EXISTING DRAINAGE STRUCTURES AND PROTECTION | | | ON ALL OF THE INLET STRUCTURES THAT CAN RECEIVE RUNOFF | | | FROM THE SITE OR FROM THE RIGHT OF WAY ADJACENT TO THE | | | SITE. | | | | | | 16. SHOW PROPOSED UTILITIES ON THE LANDSCAPE PLANS. | | | AVOID PLANTING TREES OVER OR NEAR THE EXISTING STORM | | | PIPE AND OTHER UTILITIES. ROOT BARRIER SHOULD BE | | | INSTALLED NO CLOSER THAN FIVE FEET TO THE OUTSIDE OF | | | UTILITY PIPES. | | | | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP | | | CRITERIA. STORMWATER CALCULATIONS WILL BE REVIEWED WITH | | | THE ENGINEERING PERMIT SUBMITTAL. | | | | | | 2. PROVIDE COPY OF SFWMD ERP AND FDEP NPDES | | | CONSTRUCTION PERMIT BEFORE START OF CONSTRUCTION. | | | | | | 3. PROVIDE EROSION AND SEDIMENT CONTROL PLAN WITH THE | | | ENGINEERING PERMIT SUBMITTAL. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | [email protected] | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
2 |
Status |
P |
Date |
07-10-2023 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
07-10-2023 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2023-07-10 13:53:43 | PASSED WITH CONDITIONS: | | | 1. APPROVAL DOES NOT CONSENT TO LANDSCAPING IN MOVEABLE | | | CONTAINERS. | | | 2. EASEMENT CONSENT WILL BE REQUIRED BY ALL UTILITY | | | CO.'S FOR PROPOSED STORMWATER IN EXISTING 10' UE. | | | 3. MAINTENANCE AGREEMENT FOR ALL IMPROVEMENTS WITHIN | | | RIGHT-OF-WAY. |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
04-11-2023 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
04-11-2023 |
Time |
08:30 |
Rev Time |
0.00 |
| Received By |
cibaven |
Date |
04-12-2023 |
Time |
12:55 |
Sent To |
|
|
| Notes |
| 2023-04-11 08:30:19 | 1. SHOW PROPOSED UTILITIES ON LANDSCAPE PLAN. | | | 2. LANDSCAPING IN R/W APPEARS TO CONFLICT WITH EXISTING | | | DRAINAGE. | | | 3. SURVEY NEEDS TO BE SIGNED AND SEALED. | | | 4. MAINTENANCE AGREEMENT WILL BE REQUIRED FOR | | | IMPROVEMENTS IN THE R/W. | | | 5. CARE NEEDS TO BE TAKEN WITH ANY DEMO/NEW | | | CONSTRUCTION OVER THE EXISTING 36" WATER MAIN. |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
2 |
Status |
F |
Date |
06-29-2023 |
|
|
Cont ID |
|
| Sent By |
|
Date |
06-29-2023 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
06-29-2023 |
Time |
|
Sent To |
|
|
| Notes |
| 2023-06-29 06:28:12 | TRAFFIC COMMENTS | | | 1) SATISFIED. PROVIDE COUNTY TPS LETTER. | | | 2) CONDITIONALLY SATISFIED. A CONDITION WILL BE PLACED | | | ON THIS ITEM, SPECIFICALLY: OWNER TO INSTALL A | | | SOUTHBOUND LEFT-TURN LANE IN THE CASE OF INCREASING | | | TRAFFIC VOLUMES ON CLEARWATER PARK RD OR SIGNIFICANT | | | VEHICULAR CONFLICTS BY THE PROPOSED DRIVEWAY CAUSING | | | CONGESTION AND/OR SAFETY ISSUES AS DETERMINED BY THE | | | CITY TRAFFIC ENGINEER. SUCH CONDITION SHALL EXPIRE | | | AFTER 5-YEARS FROM PROJECT COMPLETION DATE. | | | | | | SITE COMMENTS | | | 3) PARTIALLY SATISFIED. PROVIDE A TRANSPORTATION | | | SPECIFIC SITE PLAN FOR THE GROUND FLOOR. SHOWCASING | | | TRANSPORTATION RELATED FEATURES (E.G. ROADWAY WIDTHS, | | | DRIVING AISLES, PARKING STALLS, SIDEWALK, CURB, GUTTER, | | | DRIVEWAY, GATES, CROSSWALKS, VISIBILITY TRIANGLE, | | | CORNER & DRIVEWAY SEPARATION DISTANCES, SLOPES, ETC.) | | | PROPERLY LABELED AND DIMENSIONED. THE SITE PLAN SHOULD | | | BE NAMED T-1.0. SIDEWALK WIDTHS ARE MISSING. | | | 4) SATISFIED. IN THE T-1.0 SITE PLAN, PLEASE SHOWCASE | | | BASIC CURB DETAILS (E.G. DRIVEWAY, CURB CUTS, PAVEMENT | | | MARKINGS, PARKING STALLS, ETC.) ON THE OPPOSITE SIDE OF | | | THE ROADS SURROUNDING THE PROPOSED DEVELOPMENT | | | 5) PARTIALLY SATISFIED. PROVIDE A SIGNAGE AND PAVEMENT | | | MARKING PLAN. INCLUSIVE OF ALL FEATURES WITHIN THE | | | PROPOSED DEVELOPMENT AND ALONG ALL ROADS FRONTING THE | | | SITE. SUCH PLAN IS PART OF THE TRANSPORTATION REVIEW | | | AND SHOULD BE NAMED ACCORDINGLY (E.G. T-1.1 OR T-2.0). | | | PROVIDE SIGNAGE DETAILS PERTAINING THE PASSENGER | | | LOADING ZONE, AS WELL AS A BRIEF EXPLANATION OF ITS | | | PARKING POLICY, MONITORING AND ENFORCEMENT, IF ANY | | | 6) PARTIALLY SATISFIED. PROVIDE AUTOTURN ANALYSIS FOR | | | GARBAGE TRUCK AND/OR SERVICE VEHICLES DRIVING IN AND | | | OUT OF THE PROPOSED DEVELOPMENT WITH VEHICLE DYNAMIC | | | ENVELOPES AND WHEEL PATHS CLEARLY DISTINCT AND DEFINED | | | IN DIFFERENT COLORS. PROVIDE THE ANALYSIS IN A SEPARATE | | | SHEET. SUCH PLAN(S) CONTAINING THE ANALYSIS ARE PART OF | | | THE TRANSPORTATION REVIEW AND SHOULD BE NAMED | | | ACCORDINGLY (E.G. T1.2, T-3.0). ENCROACHMENT WITH CURB | | | SHOWN WHEN BACKING OUT. | | | 7) CONDITIONALLY SATISFIED. PROVIDE ENGINEERING | | | REFERENCE AND SPECS SHEETS FOR EACH OF THE PROPOSED | | | TRANSPORTATION FEATURES (E.G. CURB, RAMP, GATE, | | | SIGNAGE, PAVEMENT MARKING, SIGNAL, ETC.). TO BE | | | SATISFIED AT ENGINEERING PERMITTING STAGE. | | | 8) PARTIALLY SATISFIED. IDENTIFY AND DESIGNATE AN | | | EASILY ACCESSIBLE MICRO-MOBILITY STATION AREA (MINIMUM | | | 8 X 20 FEET) AND PROVIDE BASIC ELECTRIFICATION | | | READINESS WITH THE FOLLOWING SPECS: A CONDUIT (2-INCH | | | SCHEDULE 40 PVC) TO THE POWER SOURCE WITH AN ELECTRICAL | | | PULL BOX (240V / 10,000W CIRCUIT). PLEASE INSERT THIS | | | FEATURE IN THE T-1.0 OR T1.1 SITE PLAN. PLEASE SHOWCASE | | | ITS DIMENSIONS. | | | 9) SATISFIED. PROVIDE A PARKING TABLE SHOWCASING THE | | | NUMBER OF REQUIRED AND PROVIDED PARKING SPACES, | | | INCLUSIVE OF ADA AND BICYCLE ONES | | | 10) SATISFIED. IN THE PAVEMENT, MARKING & SIGN PLAN, | | | PROVIDE A TABLE SHOWCASING THE NUMBER OF EXISTING AND | | | PROPOSED ON-STREET PARKING STALLS. PROVIDE THE NUMBER | | | OF METERED STALLS THAT ARE BEING REMOVED OR RELOCATED, | | | IF ANY | | | 11) SATISFIED. ARE THERE ANY GATES PROPOSED? IF SO, | | | CLEARLY SHOWCASE THE REQUIRED 20 FEET SETBACK DISTANCE | | | FROM THE BACK OF THE SIDEWALK | | | 12) SATISFIED. IS VALET SERVICE PROPOSED? IF SO, | | | PROVIDE A THOROUGH OPERATIONAL ANALYSIS. DETAILS OF THE | | | ANALYSIS SHOULD BE DISCUSSED DURING THE METHODOLOGY | | | MEETING | | | 13) SATISFIED. ARE THERE ANY BUS STOPS BEING IMPACTED? | | | 14) SATISFIED. IS THE PROPOSED DEVELOPMENT IMPACTING AN | | | EXISTING BICYCLE FACILITY? | | | 15) CONDITIONALLY SATISFIED. PROVIDE A CONSTRUCTION | | | MANAGEMENT PLAN. PLEASE REFER TO CITY CODE 86-246 FOR | | | DETAILS. TO BE PROVIDED AT ENGINEERING PERMITTING | | | STAGE. | | | 16) SATISFIED. PER CITY CODE SEC94-111(C)(1): ???IN | | | THOSE CASES WHERE THE SIDE OF ANY STALL IS ADJACENT TO | | | A WALL, FENCE, BUILDING, OR OTHER PHYSICAL OBSTRUCTION, | | | THE STALL WIDTHS SHALL BE INCREASED BY A MINIMUM OF ONE | | | FOOT. WHERE THERE IS AN OBSTRUCTION ON BOTH SIDES OF | | | THE STALL, THE STALL WIDTHS SHALL BE INCREASED BY A | | | MINIMUM OF TWO FEET.??? | | | 17) PARTIALLY SATISFIED. LOADING ZONE(S), IF REQUIRED, | | | SHOULD BE PROVIDED WITHIN THE PROPOSED DEVELOPMENT, NOT | | | ON PUBLIC ROW. RESPONSE SEEMS INCOMPLETE; PLEASE | | | PROVIDE AUTOTURN ANALYSIS SHOWCASING AN SU-30 VEHICLE | | | MODEL MANEUVERING IN AND OUT OF THE LOADING ZONE | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected]. | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
04-17-2023 |
|
|
Cont ID |
|
| Sent By |
|
Date |
04-17-2023 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
04-17-2023 |
Time |
|
Sent To |
|
|
| Notes |
| 2023-04-17 19:59:19 | 1) PROVIDE COUNTY TPS LETTER | | | 2) PROVIDE APPROVAL FROM COUNTY (I.E. EMAIL | | | CORRESPONDENCE) OR REQUEST A SPECIFIC COMMENT IN THE | | | TPS LETTER ADDRESSING THE LEFT-TURN LANE REQUIREMENT | | | 3) PROVIDE A TRANSPORTATION SPECIFIC SITE PLAN FOR THE | | | GROUND FLOOR. SHOWCASING TRANSPORTATION RELATED | | | FEATURES (E.G. ROADWAY WIDTHS, DRIVING AISLES, PARKING | | | STALLS, SIDEWALK, CURB, GUTTER, DRIVEWAY, GATES, | | | CROSSWALKS, VISIBILITY TRIANGLE, CORNER & DRIVEWAY | | | SEPARATION DISTANCES, SLOPES, ETC.) PROPERLY LABELED | | | AND DIMENSIONED. THE SITE PLAN SHOULD BE NAMED T-1.0 | | | 4) IN THE T-1.0 SITE PLAN, PLEASE SHOWCASE BASIC CURB | | | DETAILS (E.G. DRIVEWAY, CURB CUTS, PAVEMENT MARKINGS, | | | PARKING STALLS, ETC.) ON THE OPPOSITE SIDE OF THE ROADS | | | SURROUNDING THE PROPOSED DEVELOPMENT | | | 5) PROVIDE A SIGNAGE AND PAVEMENT MARKING PLAN. | | | INCLUSIVE OF ALL FEATURES WITHIN THE PROPOSED | | | DEVELOPMENT AND ALONG ALL ROADS FRONTING THE SITE. SUCH | | | PLAN IS PART OF THE TRANSPORTATION REVIEW AND SHOULD BE | | | NAMED ACCORDINGLY (E.G. T-1.1 OR T-2.0) | | | 6) PROVIDE AUTOTURN ANALYSIS FOR GARBAGE TRUCK AND/OR | | | SERVICE VEHICLES DRIVING IN AND OUT OF THE PROPOSED | | | DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES AND WHEEL | | | PATHS CLEARLY DISTINCT AND DEFINED IN DIFFERENT COLORS. | | | PROVIDE THE ANALYSIS IN A SEPARATE SHEET. SUCH PLAN(S) | | | CONTAINING THE ANALYSIS ARE PART OF THE TRANSPORTATION | | | REVIEW AND SHOULD BE NAMED ACCORDINGLY (E.G. T1.2, | | | T-3.0) | | | 7) PROVIDE ENGINEERING REFERENCE AND SPECS SHEETS FOR | | | EACH OF THE PROPOSED TRANSPORTATION FEATURES (E.G. | | | CURB, RAMP, GATE, SIGNAGE, PAVEMENT MARKING, SIGNAL, | | | ETC.) | | | 8) IDENTIFY AND DESIGNATE AN EASILY ACCESSIBLE | | | MICRO-MOBILITY STATION AREA (MINIMUM 8 X 20 FEET) AND | | | PROVIDE BASIC ELECTRIFICATION READINESS WITH THE | | | FOLLOWING SPECS: A CONDUIT (2-INCH SCHEDULE 40 PVC) TO | | | THE POWER SOURCE WITH AN ELECTRICAL PULL BOX (240V / | | | 10,000W CIRCUIT). PLEASE INSERT THIS FEATURE IN THE | | | T-1.0 OR T1.1 SITE PLAN | | | 9) PROVIDE A PARKING TABLE SHOWCASING THE NUMBER OF | | | REQUIRED AND PROVIDED PARKING SPACES, INCLUSIVE OF ADA | | | AND BICYCLE ONES | | | 10) IN THE PAVEMENT, MARKING & SIGN PLAN, PROVIDE A | | | TABLE SHOWCASING THE NUMBER OF EXISTING AND PROPOSED | | | ON-STREET PARKING STALLS. PROVIDE THE NUMBER OF METERED | | | STALLS THAT ARE BEING REMOVED OR RELOCATED, IF ANY | | | 11) ARE THERE ANY GATES PROPOSED? IF SO, CLEARLY | | | SHOWCASE THE REQUIRED 20 FEET SETBACK DISTANCE FROM THE | | | BACK OF THE SIDEWALK | | | 12) IS VALET SERVICE PROPOSED? IF SO, PROVIDE A | | | THOROUGH OPERATIONAL ANALYSIS. DETAILS OF THE ANALYSIS | | | SHOULD BE DISCUSSED DURING THE METHODOLOGY MEETING | | | 13) ARE THERE ANY BUS STOPS BEING IMPACTED? | | | 14) IS THE PROPOSED DEVELOPMENT IMPACTING AN EXISTING | | | BICYCLE FACILITY? | | | 15) PROVIDE A CONSTRUCTION MANAGEMENT PLAN. PLEASE | | | REFER TO CITY CODE 86-246 FOR DETAILS. | | | 16) PER CITY CODE SEC94-111(C)(1): ???IN THOSE CASES | | | WHERE THE SIDE OF ANY STALL IS ADJACENT TO A WALL, | | | FENCE, BUILDING, OR OTHER PHYSICAL OBSTRUCTION, THE | | | STALL WIDTHS SHALL BE INCREASED BY A MINIMUM OF ONE | | | FOOT. WHERE THERE IS AN OBSTRUCTION ON BOTH SIDES OF | | | THE STALL, THE STALL WIDTHS SHALL BE INCREASED BY A | | | MINIMUM OF TWO FEET.??? | | | 17) LOADING ZONE(S), IF REQUIRED, SHOULD BE PROVIDED | | | WITHIN THE PROPOSED DEVELOPMENT, NOT ON PUBLIC ROW | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
06-28-2023 |
|
|
Cont ID |
|
| Sent By |
cibaven |
Date |
06-28-2023 |
Time |
13:20 |
Rev Time |
0.00 |
| Received By |
cibaven |
Date |
06-28-2023 |
Time |
13:17 |
Sent To |
|
|
| Notes |
| 2023-06-28 13:17:37 | ZONING AND PLANNING | | | PROJECT: 500 CLEARWATER PARK RD (Z23030025) | | | DATE: JUNE 28, 2023 | | | CONTACT: CLAUDIA IBAVEN, CITY URBAN DESIGNER, AT | | | 561-822-1402 OR VIA [email protected]. | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | | | | GENERAL COMMENTS | | | 1. TPS LETTER WILL NEED TO BE UPDATED TO REFLECT THE | | | ACCURATE NUMBER OF UNITS. NOTE, PROJECT FACT SHEET | | | STATES TOTAL OF 222 UNITS VS TPS LETTER STATES 231 | | | UNITS. | | | 2. PENDING TO RECEIVED SCAD AND FAA LETTERS. | | | 3. PLEASE UPDATE RENDERINGS TO MATCH ACCURATE DESIGN | | | INCLUDING PROPOSED LANDSCAPE. | | | | | | | | | ZONING DIAGRAMS AND TABLES | | | 1. PLEASE ADD THE ENTRY/EXIT COVERED AREA OF YOUR | | | PARKING TO YOUR BUILDING FOOTPRINT CALCULATIONS. | | | | | | 2. PLEASE NOTE, YOUR 6TH FLOOR IS NOT EXACTLY THE SAME | | | AS YOUR 3RD TO 5TH LEVELS, AS THEY INCLUDE A MECHANICAL | | | AREA FRONTING THE STREET. PLEASE ADD THE 6TH LEVEL | | | FLOOR PLAN ON ITS OWN TO YOUR FOOTPRINT (G-1.4 SHEET) | | | AND FAR (G1-5 SHEET) DIAGRAMS. IT LOOKS LIKE THE AREAS | | | ARE CORRECT ON YOUR TABLES AND CALCULATIONS, BUT BY | | | PROVIDING THE DIAGRAM YOU WILL BE ABLE TO SHOW HOW THE | | | 6TH LEVEL MEETS IS THE REQUIREMENT. | | | | | | 3. FOR ARCHITECTURAL TREATMENT PROVIDED TO SCREEN | | | NON-ACTIVE USES, FACADE ELEVATIONS NEED TO BE | | | INTEGRATED WITH THE DESIGN OF ADJACENT ACTIVE USE | | | FACADE AS PER SEC. 94-109, 'ARCHITECTURAL TREATMENT' | | | DEFINITION. THERE ARE TWO CLEAR VOLUMES | | | (PARKING/NON-ACTIVE USE AND TOWER) SHOWING DIFFERENT | | | DESIGN, BOTH FACADE ELEVATIONS WILL NEED TO BE BETTER | | | INTEGRATED. IN ADDITION, PLEASE PROPOSED ALTERNATIVES | | | TO BREAK THE MASSING OF BOTH VOLUMES, ESPECIALLY THE | | | 6TH AND 7TH FLOORS WHERE CONDITIONAL SETBACKS SHOULD | | | APPLY AS THE INTENT IS TO HAVE ACTIVE USE FRONTING THE | | | STREET. EXPLORE DIFFERENT ALTERNATIVES FOR MATERIALS | | | USED AS ARCHITECTURAL TREATMENT TO HELP BREAK THE | | | MASSING. AND FOR THE TOWER, EXPLORE ALTERNATIVES TO | | | HELP BREAK THE MASSING AND REPETITION OF THE VOLUME. | | | | | | 4. ACTIVE USE LINER DEPTH ON GROUND FLOOR REQUIRED IS | | | 25', SP-1 SHOWS A PROVIDED DEPTH OF 54' BUT IT IS NOT | | | CLEAR WHERE THAT DIMENSION CAME FROM. PLEASE REFENCE A | | | PLAN WHERE THIS DIMENSION IS SHOWN. NOTE ON FLOORPLANS | | | IT LOOKS LIKE IT IS LESS THAN 54'. | | | | | | 5. SHEET G-1.6 SHOWS TABLE (WEST) TWICE AND DOES NOT | | | INCLUDE NORTH FACADE. PLEASE REVISE. NOTE THE GROUND | | | FLOOR FACADE FACING THE WESTSIDE DOES HAVE TRANSPARENCY | | | AND FENESTRATION REQUIREMENTS THAT YOU SHOW YOU MEET, | | | AND TABLE SAYS, 'NOT APPLICABLE'. PLEASE REVISE. | | | | | | 6. PLEASE PROVIDE THE AREA PERCENTAGE OF THE NORTH | | | ELEVATION WITH STUCCO SCORING ABSENT FROM FENESTRATION | | | TO MAKE SURE IT DOES COMPLY WITH BLANK WALL | | | REQUIREMENTS AS PER SEC. 94-109, 'BLANK WALL' | | | DEFINITION. | | | | | | 7. PLEASE NOT, FAUX TREATMENTS, SUCH AS THE SYNTHETIC | | | GREEN WALL TREATMENT IS NOT CONSIDERED AN ARCHITECTURAL | | | TREATMENT, PLEASE REVISE ELEVATIONS AND CONSIDER ADDING | | | A LIVING GREEN WALL AS DEFINED IN SEC. 94-109. | | | | | | 8. MINOR EDIT, ON SP-1, ROW 'FOOTPRINT LENGTH', | | | 'MAXIMUM' DOES NOT SHOW THE REQUIRED. | | | | | | 9. PLEASE CLARIFY IF THERE IS ANY VEGETATION OR | | | FURNITURE PROPOSED UNDERNEATH THE 'COVERED LOGGIA'. | | | | | | 10. MINOR EDIT, ON SP-1, TITLE 'MINIMUM ACTIVE USE' IS | | | MISSING. | | | | | | 11. MINOR EDIT, PLEASE REFERENCE THE CORRECT PLAN WHICH | | | IS G-1.6 ON SP-1 SHEET IN THE TABLE, TRANSPARENCY ROW. | | | | | | | | | | | | LANDSCAPE & STREETSCAPE | | | | | | 1. IN COORDINATION WITH THE CITY, PLEASE REEVALUATE IF | | | DRAINAGE LINE, CONFLICTING WITH SHADE STREET TREES, CAN | | | BE RELOCATED TO ALLOW THE PLANTING OF TREES. | | | | | | 2. THE PROPOSED DEVELOPMENT DOES NOT MEET THE REQUIRED | | | PLANTING BEDS/LANDSCAPE STRIPS ADJACENT TO THE STREET | | | AS A DROP OFF AREA HAS BEEN PROPOSED. PLEASE REEVALUATE | | | DROP-OFF AREA TO BE INCLUDED INSIDE THE PROPERTY. IN | | | ADDITION, PLEASE PROPOSE ANOTHER ALTERNATIVE FOR THE | | | BIKE SHARE STATION TO NOT CONFLICT WITH LANDSCAPE | | | TRIPS. | | | | | | 3. THE PROPOSED ARTWORK CONFLICTS WITH THE VISIBILITY | | | TRIANGLES AND THERE IS A STOP SIGN IN THE ARTWORK AREA. | | | PLEASE FIND A DIFFERENT LOCATION FOR THE ARTWORK AND | | | ADD VISIBILITY TRIANGLES TO SITE PLAN. SEE SEC. 94-113 | | | (C) FOR MORE INFO ABOUT VISIBILITY TRIANGLES. | | | | | | 4. PLEASE MAKE SURE THAT ANY METERS OR OTHER EQUIPMENT | | | DOES NOT CONFLICT WITH PROPOSED LANDSCAPE. SHEET C-08 | | | SHOWS GROUND METERS ON THE NORTHWEST CORNER THAT ARE | | | NOT SHOWN ON LANDSCAPE PLANS OR ARCHITECTURAL DRAWINGS. | | | OUTDOOR MECHANICAL EQUIPMENT SHALL BE SCREEN AS PER | | | SEC. 94-315 (A) AND SHOULD NOT CONFLICT WITH REQUIRED | | | LANDSCAPING. | | | | | | 5. THERE SEEMS TO BE A GATE NOTED AS 'ACCESS TO | | | MONTECITO RESIDENTS', PLEASE CLARIFY IF THERE IS A | | | FENCE OR BARRIER ON THE PROPERTY LINE SURROUNDING THE | | | SITE. IF FENCES ARE PROPOSED, PLEASE REVIEW DEFINITION | | | OF FENCE ON SEC. 94-109. | | | | | | 6. ON SHEET LP-2, DOG FENCE DETAIL DOES NOT SPECIFY THE | | | TYPE OF FENCE AND HEIGHT, PLEASE ADD DETAILS, AND MAKE | | | SURE MEET REQUIREMENTS ON SEC. 94-109. | | | | | | 7. PLEASE CLARIFY IF YOU ARE PROPOSING LANDSCAPING | | | ADJACENT TO THE STREET ON THE NORTH SIDE OF YOUR | | | PROPERTY. SEE LP-2 SHEET. | | | | | | 8. PLEASE NOTE, PER SEC. 94-113, THE REQUIREMENT IS TO | | | ILLUMINATE ENTRANCES AND ADJACENT SIDEWALKS AT A | | | MINIMUM OF 0.6 FOOTCANDLES, THE SITE PLAN ??? | | | PHOTOMETRICS SHOWS ON THE SIDEWALK LESS THAN 0.6FC. | | | PLEASE REVISE. IN ADDITION, MINOR EDIT, THIS SHEET DOES | | | NOT HAVE SHEET #. | | | | | | 9. PLEASE MAKE SURE THAT THE BIKE RACK ON THE FRONT OF | | | THE BUILDING IS SHOWN ON GROUND FLOOR PLANS, LANDSCAPE | | | PLANS, AND CIVIL PLANS. AND, THAT LOCATION ALLOWS FOR A | | | BICYCLE TO BE LOCKED ON BOTH SIDES OF THE RACK. MINOR | | | EDIT ON SHEET A-1.1, REVISE LABEL OF BIKE RACK SHARE | | | STATION TO ONLY BIKE RACK. | | | | | | 10. PLEASE PROPOSED SHADE TREES, AT LEAST IN 30-FOOT | | | INTERVALS, ALONG THE LANDSCAPE BUFFER AROUND THE | | | PERIMETER OF THE PROPERTY TO HELP WITH BREAKING THE | | | VIEW OF THE PARKING STRUCTURE. | | | | | | | | | PARKING | | | | | | 1. PLEASE CLARIFY WHY ON THE SP-1 SHEET A LABEL CALLS | | | OUT A ???TEMPORARY TRASH PICK-UP??? ON DROP-FF AREA. | | | | | | 2. BECAUSE THE AMOUNT OF RESIDENTIAL UNITS WAS REDUCED, | | | PLEASE REVISE YOUR CAR-SHARE STATION CALCULATIONS. AS | | | PER SEC. 94-106 (8)(A), A PROJECT WITH RESIDENTIAL | | | MICRO-UNITS SHALL PROVIDE ON-SITE CAR-SHARE STATIONS ON | | | A RATIO OF ONE PER EVERY 13 UNITS. THE TOTAL AMOUNT OF | | | CAR-SHARE STATIONS MAY BE REDUCED BY ONE CAR-SHARE | | | STATION PER EVERY 13 ON-SITE PARKING SPACES PROVIDED. | | | THE PROPOSED DEVELOPMENT INCLUDES 106 MICRO-UNITS, | | | WHICH MEANS THAT 8 CAR-SHARE STATIONS NEED TO BE | | | PROVIDED. HOWEVER, CAR-SHARE STATIONS CAN BE REDUCE | | | BASED ON PARKING SPACES PROVIDED FOR MICRO-UNITS (TOTAL | | | OF 53 PARKING SPACES, 53/13=4), WHICH MEANS 4 CAR-SHARE | | | STATIONS WILL NEED TO BE PROVIDED. | | | | | | 3. ONE BIKE-SHARE STATION IS REQUIRED ON SITE. PLANS | | | SHOW THE LOCATION IS PROPOSED WHERE REQUIRED | | | LANDSCAPING SHOULD BE, PLEASE EXPLORE AN ALTERNATIVE | | | FOR LOCATION. | | | | | | 4. PLEASE CLARIFY IF 6TH LEVEL PARKING SPACES ON THE | | | SOUTHWEST AREA ARE TANDEM PARKING. IF SO, PLEASE MAKE | | | SURE TO REVIEW SEC. 94-111: FOR RESIDENTIAL USES, | | | TANDEM PARKING, IF PROVIDED, MAY COUNT AS TWO SPACES, | | | PROVIDED BOTH SPACES ARE DEDICATED TO THE SAME | | | RESIDENTIAL UNIT, AND A RESTRICTIVE COVENANT IS | | | RECORDED ON CITY APPROVED FORMS, AND RECORDED IN THE | | | PUBLIC RECORDS. | | | | | | 5. PLEASE NOTE FLOOR PLANS (SHEETS A-1.1 TO A-1.4) SHOW | | | DIFFERENT AMOUNTS OF STANDARD AND COMPACT SPACES AND | | | ADA SPACES COMPARED TO TABLE ON SHEET G-1.3. PLEASE | | | REVIEW AND REVISE ACCORDINGLY. | | | | | | | | | OTHER COMMENTS | | | PLEASE NOTE, AS PER SEC. 94-54 (A)(1), THE APPLICANT | | | SHALL ADDRESS ANY COMMENTS OF THE PPRC AND SUBMIT A | | | REVISED APPLICATION WITHIN 60 DAYS OF THE DATE OF SUCH | | | COMMENTS. FAILURE TO MAKE THE REQUIRED SUBMITTALS | | | WITHIN THE 60-DAY DEADLINE WILL DEEM THE APPLICATION AS | | | WITHDRAWN. AT LEAST 15 DAYS PRIOR TO THE EXPIRATION OF | | | THE 60-DAY REVISION PERIOD, THE APPLICANT MAY REQUEST A | | | 30-DAY EXTENSION. NO FURTHER EXTENSION REQUEST IS | | | PERMITTED. COMMENTS RELATING TO REVISED APPLICATIONS | | | SHALL BE ADDRESSED WITHIN 30 DAYS OF THE DATE OF SUCH | | | COMMENTS. | | | | | | WHEN RESUBMITTING, WRITTEN RESPONSES TO COMMENTS NEED | | | TO BE PROVIDED AS WELL AS A MINIMUM OF TWO (2) PAPER | | | COPIES AND AN ELECTRONIC COPY IN .PNG/.PDF FORMAT OF | | | ALL PLANS AND ALL DOCUMENTATION REQUIRED IN THE | | | APPLICATION. PLEASE NOTE THAT CHANGES ON THE | | | RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS | | | TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | LASTLY, YOU WERE PERMITTED ONE (1) RESUBMITTAL AT NO | | | ADDITIONAL COST. AS PREVIOUSLY ISSUED COMMENTS CONTINUE | | | TO NOT BE SUFFICIENTLY ADDRESSED, THE APPLICANT WILL BE | | | ASSESSED A RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF THE | | | ORIGINAL APPLICATION FEE, WHICH IS $300. | | | | | | --END OF COMMENTS-- | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
04-12-2023 |
|
|
Cont ID |
|
| Sent By |
cibaven |
Date |
04-12-2023 |
Time |
13:02 |
Rev Time |
0.00 |
| Received By |
cibaven |
Date |
04-12-2023 |
Time |
12:56 |
Sent To |
|
|
| Notes |
| 2023-04-12 12:57:14 | ZONING AND PLANNING | | | PROJECT: 500 CLEARWATER PARK RD (Z23030025) | | | DATE: APRIL 12, 2023 | | | CONTACT: CLAUDIA IBAVEN, CITY URBAN DESIGNER, AT | | | 561-822-1402 OR VIA [email protected]. | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | GENERAL COMMENTS | | | 1. APPLICANT ACKNOWLEDGED THAT TPS, SCAD, AND OTHER | | | MISSING UTILITIES LETTERS WILL BE PROVIDED. SO FAR, WE | | | HAVE RECEIVED, AT&T AND FPL LETTERS. (NOTE, STAFF WILL | | | PROVIDE YOU WITH NEEDED SIGNATURE FOR THE SCAD LETTER). | | | | | | 2. PLEASE PROVIDE ANY DOCUMENTATION YOU MAY HAVE FOR | | | THE PUBLIC OUTREACH PERFORMED ON 3/1 AND 3/10 (LETTER, | | | FLYER, SIGN IN SHEET, ETC). | | | | | | 3. THE PROJECT IS SUBJECT TO THE CITY OF WPB???S ART | | | LIFE ASSESSMENT. PLEASE CONTACT SYBILLE WELTER, ART IN | | | PUBLIC PLACES COORDINATOR AT 561-822-1521 OR VIA EMAIL | | | AT [email protected]. | | | | | | | | | JUSTIFICATION STATEMENT | | | 1. NOTE, PAGE 1 MENTIONS 1 VARIANCE, BUT ON LATER PAGES | | | 2 VARIANCES ARE REQUESTED, PLEASE REVISE. | | | | | | 2. AS PER SEC. 94-38, PLEASE CLARIFY THE DEPARTURE FROM | | | THE DIMENSIONAL OR NUMERICAL REQUIREMENT FOR EACH | | | VARIANCE YOU ARE REQUESTING. FOR EXAMPLE, VARIANCE NO. | | | 1, THE REQUIRED CONDITIONAL SETBACK ABOVE 5TH (68 FEET) | | | LEVEL IS 27 FEET, THE VARIANCE IS 11 FEET (27 FEET-16 | | | FEET) FROM THE 27 FEET CONDITIONAL SETBACK REQUIRED ON | | | THE 6TH AND 7TH FLOOR. | | | | | | 3. PLEASE NOTE, YOU WILL NEED TO RESPOND TO THE | | | 'CRITERIA FOR GRANTING VARIANCES' FOR EACH VARIANCE YOU | | | ARE REQUESTING, PLEASE REVISE JUSTIFICATION. AND SEE | | | COMMENTS RELATED TO VARIANCE NO. 2 AS IT MIGHT NOT BE | | | NECESSARY TO REQUEST IT. | | | | | | 4. PLEASE NOTE, YOU MENTIONED A DOG PARK IS PROPOSED | | | WITH ARTIFICIAL TURF, BUT ARCHITECTURAL DRAWINGS DO NOT | | | SHOW THIS AREA, AND IF FENCING IS PROPOSED, PLEASE | | | REVISE DRAWINGS AND PROVIDE MORE INFORMATION. | | | | | | 5. PLEASE PROVIDE WRITTEN DOCUMENTATION FROM THE FIRE | | | DEPARTMENT THAT THE SIDE SETBACK PROVIDED COMPARE TO | | | THE 15 FEET REQUIRED IS ACCEPTABLE AS PER NFPA | | | STANDARDS. | | | | | | | | | | | | ZONING DIAGRAMS AND TABLES | | | 1. FAR CALCULATIONS ON SHEET G-1.5 AND SHEET G-1.3 ARE | | | MISSING AREAS FROM THE 2ND TO 7TH FLOORS (ELEVATOR, | | | LOBBY AND STAIRS COUNT TOWARDS FAR CALCULATIONS). | | | | | | 2. PLEASE ADD YOUR BIKE STORAGE AREA ON GROUND FLOOR TO | | | YOUR GBA AND FAR CALCULATIONS. | | | | | | 3. NOTE, ON THE 7TH FLOOR, TENANT STORAGE ROOM WILL | | | NEED TO COUNT TOWARDS THE GBA AND FAR CALCULATIONS. | | | | | | 4. MINOR EDIT, ON THE TABLE ON SHEET SP-1, NUMBERS FOR | | | THE PROPOSED SETBACKS ARE MISSING ON THE 'SECONDARY | | | STREET' ROW. | | | | | | 5. ON SHEET SP-1, OPEN SPACE SECTION NOTES SHEET LP-1, | | | SHEET LP-1 IS A TREE DISPOSITION PLAN AND SHEET INDEX | | | WHICH DOES NOT PROVIDE OPEN SPACE INFORMATION. | | | | | | 6. PLEASE CHANGE TO A DIFFERENT COLOR THE DASHED LINE | | | SHOWING THE OPEN SPACE (SHEET LP-3), IT IS DIFFICULT TO | | | SEE WHAT AREA IS DESIGNATED AS OPEN SPACE. AND PLEASE | | | CLARIFY IF THERE IS ANY VEGETATION OR FURNITURE | | | PROPOSED UNDERNEATH THE 'COVERED LOGGIA'. | | | | | | 7. PLEASE REVISE ACTIVE USE LENGTH ON SHEET G-1.3 TABLE | | | TO THE LENGTH OF YOUR LOBBY FRONTING THE STREET, WHICH | | | IS 47 FEET-3 INCHES ACCORDING TO SHEET A-1.1. | | | | | | 8. PLEASE NOTE ON SHEET G-1.3, TRANSPARENCY SHOWS AS | | | LENGTH AND NOT AREA OR PERCENTAGE OF THE STOREFRONT | | | FACADE AREA. AND, SHEET SP-1 SHOWS PERCENTAGE BUT | | | REFERENCES SHEET A-1.1 WHICH DOES NOT SHOW THE DIAGRAM | | | THAT EXPLAINS WHERE THE CALCULATIONS ARE COMING FROM. | | | THE TABLE (WEST) ON SHEET A-1.1 DO NOT HAVE ANY | | | TRANSPARENCY PROVIDED. PLEASE REVISE. | | | | | | 9. THE LOBBY IS CONSIDERED ACTIVE USE-RESIDENTIAL, | | | PLEASE REVISE TABLE ON SHEET SP-1. PLEASE NOTE, ON | | | SHEET G-1.3, THIS REQUIREMENT DOES NOT SHOW. A | | | SUGGESTION IS TO MERGE BOTH TABLES INTO ONE SHEET TO | | | AVOID DISCREPANCIES BETWEEN TABLES. | | | | | | 10. PLEASE NOTE, GROUND FLOOR FACADES THAT CONTAIN | | | NON-ACTIVE USES WILL ALSO NEED TO PROVIDE AT LEAST 2 | | | ARCHITECTURAL TREATMENTS, SEE DEFINITION OF | | | ARCHITECTURAL TREATMENT ON SEC. 94-109, TO AVOID BLANK | | | WALLS. | | | | | | 11. SHEETS A-2.1, A-2.2, AND A-3.1 SHOW REQUIRED | | | SETBACK ONLY ON 7TH LEVEL, PLEASE REVISE TO SHOW ON 6TH | | | AND 7TH LEVELS. | | | | | | | | | LANDSCAPE & STREETSCAPE | | | 1. PLEASE PROVIDE A PHOTOMETRIC PLAN TO MEET EXTERIOR | | | LIGHTING REQUIREMENT AS PER SEC. 94-113 (B). | | | | | | 2. LOCATION OF STREET TREES ARE IN CONFLICT WITH | | | DRAINAGE LINE ON THE FRONT OF THE BUILDING, PLEASE | | | REVISE. IN ADDITION, PLEASE SHOW ALL EXISTING AND | | | PROPOSED WATER AND SEWER AND DRAINAGE LINES ON THE | | | LANDSCAPE PLAN. SHOW LOCATIONS OF BACKFLOWS AND ADJUST | | | LOCATIONS OF UTILITY LINES TO RESOLVE CONFLICTS WITH | | | EXISTING AND PROPOSED TREES AND LANDSCAPING. | | | | | | 3. PLANTING BEDS/LANDSCAPE STRIPS ADJACENT TO STREET | | | SHALL BE PLANTED WITH SHRUBS AND/OR GROUNDCOVERS, AS | | | PER SEC. 94-113 (D)(3). PLEASE REVISE LANDSCAPE PLANS | | | AND ANY OTHER APPLICABLE PLANS. | | | 4. PLEASE CLARIFY HOW YOU MEET THE STREET LIGHT | | | REQUIREMENT AS PER SEC. 94-113. | | | | | | 5. NOTE, THERE ARE IRRIGATION AND MAINTENANCE | | | REQUIREMENTS AS PER SEC. 94-113 (D)(6-7). | | | | | | 6. FOR BICYCLE PARKING ON STREETSCAPE, PLEASE CONTACT | | | CLAUDIA D. IBAVEN TO PROVIDE YOU WITH THE CITY'S | | | BICYCLE PARKING GUIDELINES. A BICYCLE RACK DETAIL | | | SHOWING THE TYPE OF RACK AND RACK AREA WITH DIMENSIONS | | | WILL NEED TO BE PROVIDED. | | | | | | 7. CONFIGURATION OF THE DRIVEWAY'S TURN RADIUS OF THE | | | PROPOSED DEVELOPMENT DOES NOT TAKE IN CONSIDERATION | | | NEIGHBORING PROPERTY'S DRIVEWAY. PLEASE CLEARLY SHOW | | | HOW NEIGHBORING SIDEWALKS AND DRIVEWAYS WILL INTEGRATE | | | WITH THE PROPOSED DESIGN. | | | | | | 8. LANDSCAPE BUFFER OF 5 FEET AROUND THE PERIMETER OF | | | THE SURFACE PARKING ON THE REAR GROUND FLOOR WILL ALSO | | | NEED TO PROVIDE SHADE TREES IN 30-FOOT INTERVALS AS PER | | | SEC. 94-113. PLEASE REVISE DRAWINGS. | | | | | | 9. PLEASE NOTE, ALL LANDSCAPED AREAS AND PLANT | | | MATERIALS WITHIN OR ADJACENT TO VEHICULAR USE AREAS | | | SHALL BE PROTECTED FROM VEHICULAR ENCROACHMENT BY WHEEL | | | STOPS, CURBS, OR OTHER SIMILAR DEVICES. | | | | | | 10. OUTDOOR MECHANICAL EQUIPMENT SHALL BE SCREEN AS PER | | | SEC. 94-315 (A). ON THE NORTHWEST SIDE OF THE BUILDING, | | | ON SHEET A-1.1, EQUIPMENT IS SHOWING WITH NO SCREENING | | | AND NOT SHOWN ON ELEVATIONS. PLEASE PROVIDE SCREENING | | | HEDGES FOR ALL GROUND MOUNTED VALVES AND EQUIPMENT AND | | | ADD A NOTE THAT ALL EQUIPMENT WILL BE SCREENED. | | | | | | 11. SECTION 94-448 (D)(3) REQUIRES NATIVE TREES AND | | | PALMS IN GOOD CONDITION TO BE PRESERVED ON SITE OR | | | RELOCATED. ANSI A 300 (PART 5) STANDARDS SPECIFY | | | EXAMPLES OF SUITABILITY RATINGS OF GOOD, MODERATE, OR | | | POOR FOR RELOCATION. PROVIDE AN ARBORISTS REPORT RATING | | | THE CONDITION AND RELOCATION POTENTIAL FOR THE NATIVE | | | TREES AND PALMS. | | | | | | 12. ARTIFICIAL TURF AREAS PROPOSED MUST MEET THE | | | REQUIREMENTS OF SECTION 94-451, INCLUDING ALL AREAS | | | THAT ARE ALLOWED BY CODE MUST NOT BE VISIBLE FROM A | | | ROAD OR STREET. ARTIFICIAL TURF CANNOT BE PLACED IN | | | REQUIRED LANDSCAPE AREAS. | | | | | | | | | | | | PARKING | | | 1. PLEASE CLARIFY IF NO GATES WILL BE INSTALLED IN | | | DRIVEWAYS TO ACCESS THE PARKING GARAGE. | | | | | | 2. PLEASE NOTE, IF GROUND FLOOR PARKING LEVEL IS | | | ENCLOSED AND PART OF THE PARKING GARAGE, THEN THE REAR | | | 5 PARKING STALLS MAY NOT NEED TO COMPLY WITH SEC. | | | 94-443 TERMINAL AND INTERIOR ISLANDS REQUIREMENTS | | | BECAUSE THEY ARE LESS THAN 12 INTERIOR SPACES. | | | | | | 3. AS PER SEC. 94-106 (8)(A), A PROJECT WITH | | | RESIDENTIAL MICRO-UNITS SHALL PROVIDE ON-SITE CAR-SHARE | | | STATIONS ON A RATIO OF ONE PER EVERY 13 UNITS. THE | | | TOTAL AMOUNT OF CAR-SHARE STATIONS MAY BE REDUCED BY | | | ONE CAR-SHARE STATION PER EVERY 13 ON-SITE PARKING | | | SPACES PROVIDED. THE PROPOSED DEVELOPMENT INCLUDES 109 | | | MICRO-UNITS, WHICH MEANS THAT 8 CAR-SHARE STATIONS NEED | | | TO BE PROVIDED. HOWEVER, CAR-SHARE STATIONS CAN BE | | | REDUCE BASED ON PARKING SPACES PROVIDED FOR MICRO-UNITS | | | (TOTAL OF 61 PARKING SPACES, 61/13=5), WHICH MEANS 3 | | | CAR-SHARE STATIONS WILL NEED TO BE PROVIDED. | | | | | | 4. PLEASE NOTE, THE MAX GUEST PARKING ALLOWED PER | | | MICRO-UNIT PROVIDED IS 1 PER 20 UNITS WHICH IS 109/20=6 | | | MAX. SHEET G-1.3 SHOWS 22, PLEASE REVISE. | | | | | | 5. NOTE MINOR EDIT, THE REQUIREMENT IS 0.5 BICYCLE | | | PARKING SPACES PER EVERY MICRO-UNIT, YOUR CALCULATION | | | IS CORRECT, 55 BICYCLE SPACES ARE REQUIRED, BUT THE | | | DESCRIPTION OF THE REQUIREMENT SAYS "ONE" PER EVERY | | | MICRO-UNIT, PLEASE REVISE. | | | | | | 6. PER SEC. 94-111, ALL REQUIRED BICYCLE PARKING SHALL | | | BE PROVIDED IN A SECURED AREA, COVERED FROM THE | | | ELEMENTS, THE PROPOSED DEVELOPMENT SHOWS BIKE RACKS ON | | | THE REAR SIDE OF THE BUILDING THAT ARE NOT SECURED FROM | | | ALL ELEMENTS, PLEASE REVISE. IN ADDITION, SHEET A-1.1 | | | SHOWS A DIFFERENT AREA COMPARED TO SHEET LP-1 AND SP-1, | | | PLEASE MAKE SURE ALL DRAWINGS ARE CONSISTENT. LAST, | | | PLEASE CONTACT CLAUDIA D. IBAVEN TO PROVIDE YOU WITH | | | THE CITY'S BICYCLE PARKING GUIDELINES. A DETAIL SHOWING | | | THE TYPE OF RACK AND BICYCLE STORAGE AREA WITH | | | DIMENSIONS WILL NEED TO BE PROVIDED. | | | | | | 7. A PROJECT WITH RESIDENTIAL MICRO-UNITS SHALL PROVIDE | | | ONE BIKE-SHARE STATION ON-SITE. THE DRAWINGS SHOW ONE | | | BICYCLE RACK LABELED AS BIKE-SHARE STATION ON SHEET | | | A-1.1, PLEASE NOTE, ONE BICYCLE RACK IS REQUIRED PER | | | SEC. 94-113, AND IN ADDITION, A BIKE-SHARE STATION IS | | | ALSO REQUIRED. | | | | | | 8. NOTE, A PROJECT WITH RESIDENTIAL MICRO-UNITS SHALL | | | CONTRIBUTE A TROLLEY FEE PER UNIT PER MONTH TO SUPPORT | | | THE OPERATION OF THE CITY'S TROLLEY SYSTEM, AS | | | ESTABLISHED BY RESOLUTION OF THE CITY COMMISSION FROM | | | TIME TO TIME. THIS WILL BE A CONDITION OF SITE PLAN | | | APPROVAL. | | | | | | 9. NOTE PER SEC. 94-111, ALL PARKING STRUCTURE | | | ENTRANCES FACING A STREET FRONTAGE SHALL BE REQUIRED TO | | | TREAT THE INTERIOR PORTION OF THE GARAGE ENTRY TO A | | | DEPTH OF AT LEAST 20 FEET FROM THE BUILDING FACADE. | | | | | | 10. PLEASE NOTE, AS YOU ARE PROVIDING 231 TOTAL PARKING | | | SPACES, YOU ARE REQUIRED TO PROVIDE 8 ADA SPACES PER | | | SEC. 94-485. | | | | | | 11. AS PER SEC. 94-485, IF THE TOTAL PARKING | | | REQUIREMENT IS MORE THAN 100 SPACES, 30 PERCENT OF THE | | | SPACES MAY BE DESIGNATED FOR SMALL CAR USE (8 FEET X 16 | | | FEET STALL DIMENSION). THE REQUIRED PARKING IS 129 | | | SPACES, WHICH MEANS THAT 30% OR 39 SPACES CAN BE | | | DESIGNATED FOR SMALL CAR USE. AS OF RIGHT 79 ARE BEING | | | PROPOSED AS SHOWN ON SHEET G-1.3. | | | | | | 12. MAXIMUM SLOPES FOR PARKING RAMPS SHALL BE IN | | | ACCORDANCE WITH ADA REQUIREMENTS AND SHALL NOT EXCEED | | | SIX PERCENT. NON-PARKING RAMPS SHALL NOT EXCEED 16 | | | PERCENT. IF THE RAMP IS GREATER THAN 14 PERCENT, A | | | BREAK-OVER TRANSITION SHALL BE REQUIRED. THE PREFERRED | | | STANDARD IS TEN PERCENT FOR NON-PARKING RAMP SLOPES | | | (SEC. 94-111). PLEASE REVISE DRAWINGS. | | | | | | 13. PER SEC. 97-111, GUEST PARKING SHALL BE DESIGNATED | | | AND PROMINENTLY MARKED ON-SITE AS "GUEST PARKING" AND | | | SHALL NOT BE RESTRICTED IN ANY MANNER TO USE BY A | | | SINGLE TENANT, OWNER, UNIT, OR OTHER USER. | | | | | | | | | OTHER COMMENTS | | | PLEASE NOTE, AS PER SEC. 94-54 (A)(1), THE APPLICANT | | | SHALL ADDRESS ANY COMMENTS OF THE PPRC AND SUBMIT A | | | REVISED APPLICATION WITHIN 60 DAYS OF THE MEETING | | | SCHEDULED ON 4/13/2023. FAILURE TO MAKE THE REQUIRED | | | SUBMITTALS WITHIN THE 60-DAY DEADLINE WILL DEEM THE | | | APPLICATION AS WITHDRAWN. AT LEAST 15 DAYS PRIOR TO THE | | | EXPIRATION OF THE 60-DAY REVISION PERIOD, THE APPLICANT | | | MAY REQUEST A 30-DAY EXTENSION. NO FURTHER EXTENSION | | | REQUEST IS PERMITTED. COMMENTS RELATING TO REVISED | | | APPLICATIONS SHALL BE ADDRESSED WITHIN 30 DAYS OF THE | | | DATE OF SUCH COMMENTS. | | | | | | WHEN RESUBMITTING, WRITTEN RESPONSES TO COMMENTS NEED | | | TO BE PROVIDED AS WELL AS A MINIMUM OF TWO (2) PAPER | | | COPIES AND AN ELECTRONIC COPY IN .PNG/.PDF FORMAT OF | | | ALL PLANS AND ALL DOCUMENTATION REQUIRED IN THE | | | APPLICATION. PLEASE NOTE THAT CHANGES ON THE | | | RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS | | | TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20% OF THE ORIGINAL APPLICATION FEE. | | | | | | --END OF COMMENTS-- | | | |
|
|
| |
Print |
|