Plan Review Details - Project Z23020027
Plan Review Stops For Project Z23020027
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 05-04-2023 Cont ID  
Sent By swelter Date 03-08-2023 Time 15:36 Rev Time 0.00
Received By swelter Date 05-18-2023 Time 10:55 Sent To  
Notes
2023-03-09 08:38:24PROJECT EXEMPT - RCVD. JUSTIFICATION LETTER.
 UPON FURTHER REVIEW THIS PROJECT IS NOT REQUIRED TO
 SATISFY THE PUBLIC ART. SCW
 CONSTRUCTION OF NEW STORAGE BUILDING #3 WITH 3,000
 SQUARE FEET OF STORAGE SPACE IS SUBJECT TO THE PUBLIC
 ART REQUIREMENT.
 CONTACT SYBILLE WELTER 561.822.1521 OR [email protected]
 TO REVIEW THE REQUIREMENT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 05-04-2023 Cont ID  
Sent By rbrown Date 05-04-2023 Time 17:02 Rev Time 0.00
Received By rbrown Date 05-04-2023 Time 17:02 Sent To  
Notes
2023-05-04 17:02:42DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS
 SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT
 REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH
 COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963,
 OR BY EMAIL: [email protected]
  
 3. FLOOD ZONE. ACCORDING TO THE ADOPTED FLOOD INSURANCE
 RATE MAPS (FIRMS), THE PROPOSED BUILDING IS IN FLOOD
 ZONE AE, WITH A BASE FLOOD ELEVATION OF 14 FT NAVD. THE
 FIRST FLOOR OF THE BUILDING AND ALL ASSOCIATED
 MECHANICAL EQUIPMENT (CHILLERS, GENERATORS ETC.) SHALL
 BE 24 INCHES (FREEBOARD) ABOVE THE BASE FLOOD
 ELEVATION.
  
 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 5. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 6. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION
 OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING,
 CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT
 (561) 805 6659, OR BY EMAIL: [email protected]
  
 7. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT
 TO ART LIFE ASSESSMENT UNDER THE CITY OF WEST PALM
 BEACH ART IN PUBLIC PLACES (AIPP) PROGRAM. FOR ADVICE
 ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP
 ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 03-08-2023 Cont ID  
Sent By rbrown Date 03-08-2023 Time 15:53 Rev Time 0.00
Received By rbrown Date 03-08-2023 Time 15:53 Sent To  
Notes
2023-03-08 16:06:44DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS
 SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT
 REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH
 COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963,
 OR BY EMAIL: [email protected]
  
 3. FLOOD ZONE. ACCORDING TO THE ADOPTED FLOOD INSURANCE
 RATE MAPS (FIRMS), THE PROPOSED BUILDING IS IN FLOOD
 ZONE AE, WITH A BASE FLOOD ELEVATION OF 14 FT NAVD. THE
 FIRST FLOOR OF THE BUILDING AND ALL ASSOCIATED
 MECHANICAL EQUIPMENT (CHILLERS, GENERATORS ETC.) SHALL
 BE 24 INCHES (FREEBOARD) ABOVE THE BASE FLOOD
 ELEVATION.
  
 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 5. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 6. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION
 OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING,
 CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT
 (561) 805 6659, OR BY EMAIL: [email protected]
  
 7. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT
 TO ART LIFE ASSESSMENT UNDER THE CITY OF WEST PALM
 BEACH ART IN PUBLIC PLACES (AIPP) PROGRAM. FOR ADVICE
 ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP
 ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status P Date 02-27-2023 Cont ID  
Sent By rrossano Date 02-27-2023 Time   Rev Time  
Received By rrossano Date 02-27-2023 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 05-05-2023 Cont ID  
Sent By pleduc Date 05-05-2023 Time   Rev Time 0.00
Received By pleduc Date 05-05-2023 Time 12:37 Sent To  
Notes
2023-05-05 12:39:362ND REVIEW RESPONSE
  
 AFTER A REVIEW OF THE PPRC RESPONSE PACKET FOR THIS
 PROJECT, THE PREVIOUSLY SUBMITTED FIRE PREVENTION
 BUREAU COMMENTS APPEAR TO HAVE BEEN ADDRESSED.
  
 HOWEVER, THE BUREAU'S APPROVAL OF THIS SUBMITTED
 PROJECT DOES NOT CONSTITUTE ITS FINAL REVIEW OR
 APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE DEPARTMENT
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 03-03-2023 Cont ID  
Sent By pleduc Date 03-03-2023 Time   Rev Time 0.00
Received By pleduc Date 03-03-2023 Time 12:29 Sent To  
Notes
2023-03-03 12:35:54THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE DEPARTMENT.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT. THE FOLLOWING COMMENTS ARE INTENDED
 TO PROVIDE GUIDANCE FOR BUILDING PLAN SUBMITTAL.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING(S) SHALL COMPLY
 WITH THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION
 CODE, INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE
 CODES.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE PER THE FLORIDA FIRE PREVENTION CODE.
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED, AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 AN EXISTING FIRE HYDRANT WAS INDICATED ON THE ACCESS
 ROAD; HOWEVER, THE FLOW CAPACITY FROM THAT HYDRANT IS
 NOT KNOWN TO SUPPORT THE ADDITIONAL BUILDINGS.
  
 9. IF REQUIRED, PROVIDE FOR A FIRE SPRINKLER AND/OR
 FIRE ALARM PER THE APPLICABLE OCCUPANCY CODE. FOR ANY
 LIFE SAFETY ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND
 FIRE ALARM, ENSURE THEY COMPLY WITH THE REQUIREMENTS OF
 F.A.C. 61G AND SUBMITTED WITH THE MASTER PERMIT.
  
 9A. THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE
 LOCATIONS SHALL MEET AND BE INSTALLED PER THE
 REQUIREMENTS OF NFPA 24 AND SHALL BE COORDINATED WITH
 THE OFFICE OF FIRE MARSHAL, THE CITY'S ENGINEERS
 OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S PLANNING
 AND ZONING OFFICE.
  
 10. COMPLETE LIFE SAFETY PLANS FOR THE OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, EXIT SEPARATION DISTANCES, COMMON PATHS OF
 TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, EMERGENCY
 LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE
 EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES
 AND EQUIPMENT.
  
 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE
 SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY
 DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS.
  
 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 2 Status P Date 05-18-2023 Cont ID  
Sent By asangele Date 05-18-2023 Time 16:12 Rev Time 0.00
Received By asangele Date 05-18-2023 Time 16:12 Sent To  
Notes
2023-05-18 16:15:56PROJECT: BEAR LAKES MAINTENANCE FACILITY Z23020027
 5/18/2023
  
  
 1. SATISFIED
 SECTION 94-443(C)(3) REQUIRES THAT A MINIMUM OF 75
 PERCENT OF ALL TREES THAT ARE REQUIRED TO BE PLANTED
 WITHIN THE INTERIOR OF AN OFF STREET PARKING AREA SHALL
 BE CATEGORY 1 SHADE TREES. SHOW THE PERCENTAGE OF
 CATEGORY 1 TREES PROVIDED FOR THE REQUIRED LANDSCAPE
 AREAS FOR THE UPDATED PLAN. UPDATE THE LANDSCAPE
 REQUIREMENT CHART TO SHOW THERE ARE NOW 8 TERMINAL AND
 INTERIOR ISLANDS REQUIRING TREES FOR PARKING.
  
 2. SATISFIED
 INDICATE TYPE D CURBS SURROUNDING THE FIVE NEW
 LANDSCAPE TERMINAL AND DIVIDER ISLANDS TO MEET THE CODE
 REQUIREMENTS OF SECTION 94-443(C)(5). THE CURBS MUST BE
 OUTSIDE THE 8 FOOT WIDTH OF LANDSCAPE AREA.
  
  
  
  
 ALEXIS SANGELEER
 PLANNER
 [email protected]
 561-822-1443

Review Stop L LANDSCAPING
Rev No 1 Status F Date 03-01-2023 Cont ID  
Sent By rcaranci Date 03-01-2023 Time 14:51 Rev Time 0.00
Received By rcaranci Date 03-01-2023 Time 14:51 Sent To  
Notes
2023-03-01 14:51:36FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: BEAR LAKES MAINTENANCE FACILITY Z23020027
 MARCH 1, 2023
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SECTION 94-443(C)(3) REQUIRES THAT A MINIMUM OF 75
 PERCENT OF ALL TREES THAT ARE REQUIRED TO BE PLANTED
 WITHIN THE INTERIOR OF AN OFF STREET PARKING AREA SHALL
 BE CATEGORY 1 SHADE TREES. SHOW THE PERCENTAGE OF
 CATEGORY 1 TREES PROVIDED FOR THE REQUIRED LANDSCAPE
 AREAS FOR THE UPDATED PLAN. UPDATE THE LANDSCAPE
 REQUIREMENT CHART TO SHOW THERE ARE NOW 8 TERMINAL AND
 INTERIOR ISLANDS REQUIRING TREES FOR PARKING.
  
 2. INDICATE TYPE D CURBS SURROUNDING THE FIVE NEW
 LANDSCAPE TERMINAL AND DIVIDER ISLANDS TO MEET THE CODE
 REQUIREMENTS OF SECTION 94-443(C)(5). THE CURBS MUST BE
 OUTSIDE THE 8 FOOT WIDTH OF LANDSCAPE AREA.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status P Date 03-09-2023 Cont ID  
Sent By relizond Date 03-09-2023 Time 08:22 Rev Time 0.00
Received By relizond Date 03-09-2023 Time 08:22 Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 2 Status P Date 05-19-2023 Cont ID  
Sent By   Date 05-19-2023 Time   Rev Time 0.00
Received By   Date 05-19-2023 Time   Sent To  
Notes
2023-05-19 14:54:40NO FURTHER COMMENTS FROM PUBLIC WORKS.

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 03-09-2023 Cont ID  
Sent By   Date 03-09-2023 Time   Rev Time  
Received By   Date 03-09-2023 Time   Sent To  
Notes
2023-03-09 11:26:38 
 PLEASE PROVIDE THE FOLLOWINGS:
 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID
 WASTE VOLUME PRODUCED ALONG WITH THE SIZE, TYPE AND
 QUANTITY OF THE CONTAINER (I.E. DUMPSTER/COMPACTOR)
 THAT WILL BE UTILIZED FOR THE SANITATION SERVICE.
 2- DUMPSTER ENCLOSURE DETAIL. DETAILS FOR SANITATION
 SERVICE (I.E. SOLID WASTE CONTAINER(S) TYPE, COLLECTION
 LOCATION, ETC.). FOR A FREESTANDING SITE DUMPSTER
 ENCLOSURE, THE ENCLOSURE SHALL COMPLY WITH THE LATEST
 REVISION OF CITY OF WEST PALM BEACH GENERAL
 CONSTRUCTION-GARBAGE ENCLOSURE STANDARD, GC-7. (LINK TO
 THE LATEST REVISION OF THE GC-7 DOCUMENT: HTTPS://WWW.W
 PB.ORG/HOME/SHOWPUBLISHEDDOCUMENT/3690/6376290604221000
 00)
 3- AUTOTURN EXHIBIT WITH DYNAMIC ENVELOPE AND THE
 VEHICLE`S WHEEL PATH IDENTIFIED WITH DIFFERENT COLORS
 FOR THE SANITATION SERVICE, FRONT LOADER TRUCK WITH THE
 FOLLOWING SPECS:
 - DUAL AXLES
 - TRUCK LENGTH: 35 FT
 - TIRE PATH WIDTH: 8 FT
 - DYNAMIC ENVELOP WIDTH: 11 FT
 - TURNING RADIUS:
 - SAE TURNING RADIUS: 32.5 FT
 - CURB-TO-CURB DIAMETER: 74 FT
 - WALL-TO-WALL DIAMETER: 86.3 FT
  
 MATT HEJAZI
 DEPT OF PUBLIC WORKS
 [email protected]

Review Stop STORM STORMWATER
Rev No 1 Status P Date 03-08-2023 Cont ID  
Sent By tward Date 03-08-2023 Time 09:41 Rev Time 0.00
Received By tward Date 03-08-2023 Time 09:45 Sent To  
Notes
2023-03-08 09:45:12THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. SURVEY IDENTIFIES THE SITE WITHIN A SPECIAL FLOOD
 HAZARD AREA (SFHA) WITH A BASE FLOOD ELEVATION OF 14 FT
 NAVD1988. STRUCTURES WITHIN A SFHA ARE TO HAVE A
 MINIMUM OF 2 FEET OF FREEBOARD ABOVE THE BASE FLOOD
 ELEVATION.
  
 2. CONFIRM NPBCID APPROVES THE DEPTH OF THE OUTFALL
 INTO THE LAKE SYSTEM. THE PROVIDED DETAIL DRAWING NO.
 N-003 SHOWS THE TOP OF THE PIPE IS TO BE 2 FEET BELOW
 THE CONTROL ELEVATION OF THE LAKE.
  
 3. COMPLETE THE SCALE BAR ON SHEET C-201.
  
 4. ADA STRIPING DETAIL SHOULD MATCH CITY LAND
 DEVELOPMENT CODE SECTION 94-485.
  
  
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP
 CRITERIA. STORMWATER CALCULATIONS WILL BE REVIEWED WITH
 THE ENGINEERING PERMIT SUBMITTAL.
  
 2. PROVIDE COPY OF SFWMD ERP PERMIT BEFORE START OF
 CONSTRUCTION.
  
 3. PROVIDE COPY OF NPBCID PERMIT BEFORE START OF
 CONSTRUCTION.
  
 4. PROVIDE EROSION AND SEDIMENT CONTROL PLAN WITH THE
 ENGINEERING PERMIT SUBMITTAL.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 [email protected]
  
  

Review Stop SURVEY SURVEYING
Rev No 1 Status P Date 03-08-2023 Cont ID  
Sent By vnoel Date 03-08-2023 Time 13:16 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
***NONE***

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status P Date 03-09-2023 Cont ID  
Sent By   Date 03-09-2023 Time   Rev Time  
Received By   Date 03-09-2023 Time   Sent To  
Notes
2023-03-09 18:40:55NO COMMENTS
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 05-23-2023 Cont ID  
Sent By asangele Date 05-18-2023 Time 16:23 Rev Time 0.00
Received By asangele Date 05-23-2023 Time 14:34 Sent To  
Notes
2023-05-18 17:22:43GENERAL COMMENTS:
  
 APPROVAL WITH CONDITION A LETTER FROM THE PALM BEACH
 COUNTY - TRAFFIC DIVISION, STATING THAT THE PROPOSED
 PROJECT MEETS THE TRAFFIC PERFORMANCE STANDARDS (TPS)
 OF THE COUNTY IS REQUIRED PRIOR TO MOVING FORWARD TO
 THE PUBLIC HEARING STAGE IS PROVIDED.
  
  
 1.) SATISFIED
  
 PLEASE ADDRESS THE FOLLOWING IN THE JUSTIFICATION
 STATEMENT:
  
  
 1A) SATISFIED
  
 ADDRESS OF THE AFFECTED AREA (1401 BRANDYWINE RD.
 APPEARS TO BE THE ADDRESS OF THE SUBJECT PROPERTY - NOT
 1901 VILLAGE BOULEVARD).
  
  
 1 B) SATISFIED
  
 THE STORAGE SPACE CALCULATIONS ARE INACCURATE IN THE
 PROPERTY HISTORY SECTION.
  
 2.) NOT SATISFIED
  
 A LETTER FROM THE PALM BEACH COUNTY - TRAFFIC DIVISION,
 STATING THAT THE PROPOSED PROJECT MEETS THE TRAFFIC
 PERFORMANCE STANDARDS (TPS) OF THE COUNTY IS REQUIRED
 PRIOR TO MOVING FORWARD TO THE PUBLIC HEARING STAGE.
  
 3.) SATISFIED
  
 PROVIDE WRITTEN CONFIRMATION THAT THE PUBLIC UTILITIES
 DEPARTMENT HAS REVIEWED THE PROPOSAL FOR WATER, SEWAGE
 TREATMENT, STORM DRAINAGE AND GARBAGE COLLECTION
 SERVICES. THE LETTER PROVIDED IN THE APPLICATION IS
 OUTDATED AND WILL NOT SUFFICE. PLEASE CONTACT THE CITY
 OF WEST PALM BEACH ENGINEERING SERVICES DEPARTMENT
 (561-494-1040) ON HOW TO OBTAIN THE REQUIRED LETTER.
  
 4.) SATISFIED
  
 PROVIDE WRITTEN LETTERS FROM ALL PUBLIC UTILITIES
 CONFIRMING THAT THE PROPOSED PROJECT DOES NOT ENCROACH
 INTO THEIR EASEMENTS OR OTHERWISE INTERFERE WITH THE
 PROVISIONS OF THEIR SERVICES: AT&T, FPU, FPL AND
 COMCAST. THE LETTERS PROVIDED IN THE APPLICATION IS
 OUTDATED AND WILL NOT SUFFICE.
  
  
 SITE PLAN COMMENTS:
  
 1.) SATISFIED
  
 IT SHOULD BE NOTED IN THE SITE PLAN WHICH BUILDINGS ARE
 EXISTING, PROPOSED FOR DEMO AND RE-BUILT TO THE SAME
 FOOTPRINT AND PROPOSED NEW FOR CLARITY WITH THE
 SCOPE/DESCRIPTION OF WORK.
  
 2.) SATISFIED
  
 PROVIDE THE BUILDING SETBACK FROM PROPOSED BUILDING #3
 TO THE PROPERTY LINE TO DEMONSTRATE COMPLIANCE WITH THE
 SETBACK REQUIREMENTS OF THE ZLDRS. THE PROPERTY LINE
 SHALL BE MEASURED AS THE SHORTEST DISTANCE FROM THE
 FACE OF THE BUILDING TO THE PROPERTY LINE.
  
 3.) SATFISFIED
  
 WHAT IS THE BUILDING SEPARATION BETWEEN THE EXISTING
 COVERED WASHING STATION (CANOPY) AND PROPOSED BUILDING
 #3? PLEASE PROVIDE THE DIMENSION FOR THE BUILDING
 SEPARATION IN THE PLAN. THE BUILDING SEPARATION MUST BE
 A MINIMUM OF 15 FT. [ZLDR S.94-202]
  
 4.) SATISFIED
  
 PLEASE ADDRESS THE FOLLOWING IN THE SITE DATA TABULAR:
  
  
 4A) SATISFIED
  
 THE PROPOSED BUILDING HEIGHT IS NOTED AS 30 FT.,
 HOWEVER, THE BUILDING HEIGHT OF THE TALLEST PROPOSED
 STRUCTURE APPEARS TO BE CLOSER TO 16 FT.
  
  
 4B) SATISFIED
  
 CLARIFICATION IS NEEDED ON THE 110.5 SQ. FT.
 PREFABRICATED STORAGE BUILDING ATTACHED TO PROPOSED
 BUILDING #3 (AS NOTED IN THE ARCHITECTURAL PLANS). IF
 THE INTENT IS TO PROVIDE THIS PREFAB BUILDING, THE
 ADDITIONAL STORAGE SQUARE FOOTAGE MUST BE ACCOUNTED
 FOR.
  
 5.) SATISFIED
  
 THE PROPOSED BUILDING HEIGHT IN THE SITE DATA TABULAR
 IS NOTED AS 30 FT.; HOWEVER, THE PROPOSED BUILDING
 HEIGHT (ACCORDING TO THE ARCHITECTURAL DRAWINGS) APPEAR
 TO BE CLOSER TO 16 FT. PLEASE ADDRESS FOR CONSISTENCY.
  
 6.) SATISFIED
  
 ALL PROPOSED STRUCTURES (I.E. LIGHT POLE FIXTURES,
 ETC.) MUST BE SHOWN IN THE PLANS AT THIS TIME TO
 DETERMINE IF THE LOCATION/PLACEMENT OF ANY STRUCTURES
 CONFLICT WITH UTILITIES LANDSCAPING, ETC.
  
  
 ARCHITECTURAL PLAN COMMENTS:
  
 1.) SATISFIED
  
 AN "EXISTING PREFAB CHEMICAL STORAGE UNIT" IS SHOWN
 ATTACHED TO PROPOSED BUILDING #3 ON THE SOUTH SIDE OF
 THE BUILDING; HOWEVER, THIS IS STORAGE UNIT IS NOT
 REFLECTED IN THE SQUARE FOOTAGE CALCULATIONS, THE SITE
 PLAN, LANDSCAPE PLAN, CIVIL PLAN OR SURVEY. PLEASE
 ADDRESS FOR CONSISTENCY.
  
 2.) SATISFIED
  
 LABELED ELEVATIONS FOR BUILDING #3 (CHEMICAL STORAGE
 BUILDING) APPEAR TO BE INCORRECT. PLEASE REVIEW SHEETS
 A1.2 AND A5.2 AND ADDRESS FOR CONSISTENCY.
  
 3.) SATISFIED
  
 LABELED ELEVATIONS FOR BUILDING #1 (MAINTENANCE
 BUILDING) APPEAR TO BE INCORRECT. PLEASE REVIEW SHEETS
 A1.1 AND A5.1 AND ADDRESS FOR CONSISTENCY.
  
  
 LANDSCAPE PLAN COMMENTS:
  
 1.) SATISFIED
  
 THE BUILDING SQUARE FOOTAGE BREAKDOWN ON SHEET LP.1 IS
 INCONSISTENT WITH THE INFORMATION PROVIDED ON SHEET
 SP.1. PLEASE ADDRESS FOR CONSISTENCY.
  
 2.) SATISFIED
  
 THE FLOATING NOTE "PROPOSED WASH DOWN STATION" NEEDS TO
 BE REMOVED ON SHEET LP.1. THIS NOTE IS FROM THE
 PREVIOUS (EXPIRED) APPROVAL (REFERENCE: PB 770F), WHICH
 IS NO LONGER APPLICABLE TO THIS APPLICATION.
  
  
 INSTRUCTIONS FOR RESUBMITTAL:
  
 * PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 * WHEN REVISING ANY PLAN SHEETS, PLEASE MAKE SURE ANY
 CHANGES ARE REFLECTED IN ALL PLAN SETS.
  
 * WHEN REVISING ANY PLAN SHEETS/SETS, PLEASE BE SURE TO
 PROVIDE THE REVISION DATE.
  
 * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FOUR
 (4) PAPER COPIES, ONE (1) REDUCED COPY IN 11 INCHES X
 17 INCHES, AND AN ELECTRONIC COPY OF ALL PLANS AND
 DOCUMENTS.
  
 * PLEASE NOTE THAT CHANGES ON THE RESUBMITTED PLANS MAY
 RESULT IN ADDITIONAL COMMENTS.
  
 * YOU WILL BE PERMITTED ONE (1) RESUBMITTAL AT NO
 ADDITIONAL COST. IF PREVIOUSLY-ISSUED COMMENTS CONTINUE
 TO NOT BE SUFFICIENTLY ADDRESSED, THE APPLICANT WILL BE
 ASSESSED A RESUBMITTAL FEE. SUCH FEE WILL BE 20 PERCENT
 OF THE ORIGINAL APPLICATION FEE.
  
 ALEXIS SANGELEER
 PLANNER
 [email protected]
 561-822-1443

Review Stop Z ZONING
Rev No 1 Status F Date 03-02-2023 Cont ID  
Sent By llouie Date 03-02-2023 Time   Rev Time  
Received By llouie Date 03-02-2023 Time   Sent To  
Notes
2023-03-02 10:48:36GENERAL COMMENTS:
  
 1.) PLEASE ADDRESS THE FOLLOWING IN THE JUSTIFICATION
 STATEMENT: A) ADDRESS OF THE AFFECTED AREA (1401
 BRANDYWINE RD. APPEARS TO BE THE ADDRESS OF THE SUBJECT
 PROPERTY - NOT 1901 VILLAGE BOULEVARD). B) THE STORAGE
 SPACE CALCULATIONS ARE INACCURATE IN THE PROPERTY
 HISTORY SECTION.
  
 2.) A LETTER FROM THE PALM BEACH COUNTY - TRAFFIC
 DIVISION, STATING THAT THE PROPOSED PROJECT MEETS THE
 TRAFFIC PERFORMANCE STANDARDS (TPS) OF THE COUNTY IS
 REQUIRED PRIOR TO MOVING FORWARD TO THE PUBLIC HEARING
 STAGE.
  
 3.) PROVIDE WRITTEN CONFIRMATION THAT THE PUBLIC
 UTILITIES DEPARTMENT HAS REVIEWED THE PROPOSAL FOR
 WATER, SEWAGE TREATMENT, STORM DRAINAGE AND GARBAGE
 COLLECTION SERVICES. THE LETTER PROVIDED IN THE
 APPLICATION IS OUTDATED AND WILL NOT SUFFICE. PLEASE
 CONTACT THE CITY OF WEST PALM BEACH ENGINEERING
 SERVICES DEPARTMENT (561-494-1040) ON HOW TO OBTAIN THE
 REQUIRED LETTER.
  
 4.) PROVIDE WRITTEN LETTERS FROM ALL PUBLIC UTILITIES
 CONFIRMING THAT THE PROPOSED PROJECT DOES NOT ENCROACH
 INTO THEIR EASEMENTS OR OTHERWISE INTERFERE WITH THE
 PROVISIONS OF THEIR SERVICES: AT&T, FPU, FPL AND
 COMCAST. THE LETTERS PROVIDED IN THE APPLICATION IS
 OUTDATED AND WILL NOT SUFFICE.
  
  
 SITE PLAN COMMENTS:
  
 1.) IT SHOULD BE NOTED IN THE SITE PLAN WHICH BUILDINGS
 ARE EXISTING, PROPOSED FOR DEMO AND RE-BUILT TO THE
 SAME FOOTPRINT AND PROPOSED NEW FOR CLARITY WITH THE
 SCOPE/DESCRIPTION OF WORK.
  
 2.) PROVIDE THE BUILDING SETBACK FROM PROPOSED BUILDING
 #3 TO THE PROPERTY LINE TO DEMONSTRATE COMPLIANCE WITH
 THE SETBACK REQUIREMENTS OF THE ZLDRS. THE PROPERTY
 LINE SHALL BE MEASURED AS THE SHORTEST DISTANCE FROM
 THE FACE OF THE BUILDING TO THE PROPERTY LINE.
  
 3.) WHAT IS THE BUILDING SEPARATION BETWEEN THE
 EXISTING COVERED WASHING STATION (CANOPY) AND PROPOSED
 BUILDING #3? PLEASE PROVIDE THE DIMENSION FOR THE
 BUILDING SEPARATION IN THE PLAN. THE BUILDING
 SEPARATION MUST BE A MINIMUM OF 15 FT. [ZLDR S.94-202]
  
 4.) PLEASE ADDRESS THE FOLLOWING IN THE SITE DATA
 TABULAR: A) THE PROPOSED BUILDING HEIGHT IS NOTED AS
 30 FT., HOWEVER, THE BUILDING HEIGHT OF THE TALLEST
 PROPOSED STRUCTURE APPEARS TO BE CLOSER TO 16 FT.
 PLEASE ADDRESS FOR CONSISTENCY. B) CLARIFICATION IS
 NEEDED ON THE 110.5 SQ. FT. PREFABRICATED STORAGE
 BUILDING ATTACHED TO PROPOSED BUILDING #3 (AS NOTED IN
 THE ARCHITECTURAL PLANS). IF THE INTENT IS TO PROVIDE
 THIS PREFAB BUILDING, THE ADDITIONAL STORAGE SQUARE
 FOOTAGE MUST BE ACCOUNTED FOR.
  
 5.) THE PROPOSED BUILDING HEIGHT IN THE SITE DATA
 TABULAR IS NOTED AS 30 FT.; HOWEVER, THE PROPOSED
 BUILDING HEIGHT (ACCORDING TO THE ARCHITECTURAL
 DRAWINGS) APPEAR TO BE CLOSER TO 16 FT. PLEASE ADDRESS
 FOR CONSISTENCY.
  
 6.) ALL PROPOSED STRUCTURES (I.E. LIGHT POLE FIXTURES,
 ETC.) MUST BE SHOWN IN THE PLANS AT THIS TIME TO
 DETERMINE IF THE LOCATION/PLACEMENT OF ANY STRUCTURES
 CONFLICT WITH UTILITIES LANDSCAPING, ETC.
  
  
 ARCHITECTURAL PLAN COMMENTS:
  
 1.) AN "EXISTING PREFAB CHEMICAL STORAGE UNIT" IS SHOWN
 ATTACHED TO PROPOSED BUILDING #3 ON THE SOUTH SIDE OF
 THE BUILDING; HOWEVER, THIS IS STORAGE UNIT IS NOT
 REFLECTED IN THE SQUARE FOOTAGE CALCULATIONS, THE SITE
 PLAN, LANDSCAPE PLAN, CIVIL PLAN OR SURVEY. PLEASE
 ADDRESS FOR CONSISTENCY.
  
 2.) LABELED ELEVATIONS FOR BUILDING #3 (CHEMICAL
 STORAGE BUILDING) APPEAR TO BE INCORRECT. PLEASE REVIEW
 SHEETS A1.2 AND A5.2 AND ADDRESS FOR CONSISTENCY.
  
 3.) LABELED ELEVATIONS FOR BUILDING #1 (MAINTENANCE
 BUILDING) APPEAR TO BE INCORRECT. PLEASE REVIEW SHEETS
 A1.1 AND A5.1 AND ADDRESS FOR CONSISTENCY.
  
  
 LANDSCAPE PLAN COMMENTS:
  
 1.) THE BUILDING SQUARE FOOTAGE BREAKDOWN ON SHEET LP.1
 IS INCONSISTENT WITH THE INFORMATION PROVIDED ON SHEET
 SP.1. PLEASE ADDRESS FOR CONSISTENCY.
  
 2.) THE FLOATING NOTE "PROPOSED WASH DOWN STATION"
 NEEDS TO BE REMOVED ON SHEET LP.1. THIS NOTE IS FROM
 THE PREVIOUS (EXPIRED) APPROVAL (REFERENCE: PB 770F),
 WHICH IS NO LONGER APPLICABLE TO THIS APPLICATION.
  
  
 INSTRUCTIONS FOR RESUBMITTAL:
  
 * PLEASE NOTE THAT ALEXIS SANGELEER, PLANNER, WILL BE
 THE PROJECT PLANNER ON THIS APPLICATION MOVING FORWARD.
  
 * PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 * WHEN REVISING ANY PLAN SHEETS, PLEASE MAKE SURE ANY
 CHANGES ARE REFLECTED IN ALL PLAN SETS.
  
 * WHEN REVISING ANY PLAN SHEETS/SETS, PLEASE BE SURE TO
 PROVIDE THE REVISION DATE.
  
 * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FOUR
 (4) PAPER COPIES, ONE (1) REDUCED COPY IN 11 INCHES X
 17 INCHES, AND AN ELECTRONIC COPY OF ALL PLANS AND
 DOCUMENTS.
  
 * PLEASE NOTE THAT CHANGES ON THE RESUBMITTED PLANS MAY
 RESULT IN ADDITIONAL COMMENTS.
  
 * YOU WILL BE PERMITTED ONE (1) RESUBMITTAL AT NO
 ADDITIONAL COST. IF PREVIOUSLY-ISSUED COMMENTS CONTINUE
 TO NOT BE SUFFICIENTLY ADDRESSED, THE APPLICANT WILL BE
 ASSESSED A RESUBMITTAL FEE. SUCH FEE WILL BE 20 PERCENT
 OF THE ORIGINAL APPLICATION FEE.
  
 * CONTACT ALEXIS SANGELEER @ (561) 822-1443 IF THERE
 ARE ANY QUESTIONS.
  
  