Plan Review Details - Project Z23010017
Plan Review Stops For Project Z23010017
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 06-30-2023 Cont ID  
Sent By rbrown Date 06-30-2023 Time 19:42 Rev Time 0.00
Received By rbrown Date 06-30-2023 Time 19:42 Sent To  
Notes
2023-06-30 19:43:05DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 02-08-2023 Cont ID  
Sent By rbrown Date 02-08-2023 Time 19:02 Rev Time 0.00
Received By rbrown Date 02-08-2023 Time 19:02 Sent To  
Notes
2023-02-08 19:03:15DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 02-08-2023 Cont ID  
Sent By asangele Date 02-08-2023 Time 09:27 Rev Time  
Received By asangele Date   Time   Sent To  
Notes
2023-02-08 09:46:09FAILED
 2/8/2023
  
 PLEASE PROVIDE A TABLE FOR THE PARKING WHAT IS CURRNTLY
 EXISTING AND WHAT IS REQUIRED AND WHAT IS BEING
 PROPOSED. ALSO PLEASE SHOW THE DIMENSIONS OF THE
 PROPSED NEW PARKING SPOTS.
  
 6 ADDITIONAL UNITS WOULD NOT BE ALLOWED TO BE ADDED
 BECAUSE THE DENSITY DOES NOT ALLOW IT.
 5 UNITS WOULD BE THE MAXIUM ALLOWED TO BE ADDED TO THE
 PROPERTY BECAUSE THAT IS THE MAXIIMUM UNITS THE DENSITY
 ALLOWED IN MULTIFAMILY HIGH DENSITY (MF32) RESIDENTIAL
 ZOING.
  
 EXISTING UNITS = 252
  
 32.27 X 7.970 = 257.19
 ARTICLE III. SECTION 94-77
  
 257.19 - 252 = 5.19
  
 MAX ALLOWED UNITS TO BE ADDED= 5
  
 ALEXIS SANGELEER
 PLANNER
 [email protected]
  
  
  
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status P Date 01-30-2023 Cont ID  
Sent By rrossano Date 01-30-2023 Time   Rev Time  
Received By rrossano Date 01-30-2023 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 06-26-2023 Cont ID  
Sent By pleduc Date 06-26-2023 Time   Rev Time 0.00
Received By pleduc Date 06-26-2023 Time 16:11 Sent To  
Notes
2023-06-26 16:12:06FIRE HAS NO OBJECTIONS TO THE PROPOSED AND APPROVES.
  
 FIRE'S APPROVAL OF THIS SUBMITTED PROJECT MAY NOT
 CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 IF APPLICABLE, FIRE SHALL REVIEW ALL SUBMITTED PROJECT
 PLANS AT THE APPLICABLE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE FIRE CODES AND
 STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 02-07-2023 Cont ID  
Sent By pleduc Date 02-07-2023 Time   Rev Time 0.00
Received By pleduc Date 02-07-2023 Time 09:58 Sent To  
Notes
2023-02-07 10:07:09THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE DEPARTMENT.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT. THE FOLLOWING COMMENTS ARE INTENDED
 TO PROVIDE GUIDANCE FOR BUILDING PLAN SUBMITTAL.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING(S) SHALL COMPLY
 WITH THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION
 CODE, INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE
 CODES.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE PER THE FLORIDA FIRE PREVENTION CODE.
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED, AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
 8. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM,
 ENSURE THEY COMPLY WITH THE REQUIREMENTS OF F.A.C. 61G
 AND SUBMITTED WITH THE MASTER PERMIT.
  
 9. COMPLETE LIFE SAFETY PLANS FOR THE OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, EXIT SEPARATION DISTANCES, COMMON PATHS OF
 TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, EMERGENCY
 LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE
 EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES
 AND EQUIPMENT.
  
 10. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
 11. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 06-29-2023 Cont ID  
Sent By asangele Date 06-29-2023 Time 10:14 Rev Time 0.00
Received By asangele Date 06-29-2023 Time 10:14 Sent To  
Notes
2023-06-29 10:18:45FROM: SMITH ARMISIAL LANDSCAPE PLANNER
 PROJECT: UPTOWN 22 Z23010017
 JUNE 26 2023
  
 SATISFIED
 THIS SITE WAS REQUIRED BY CONDITION OF APPROVAL THROUGH
 A CLASS B SPECIAL USE APPROVAL TO BRING THE LANDSCAPING
 ON SITE INTO COMPLIANCE WITH THE APPROVED LANDSCAPE
 PLANS. THIS WAS ACCOMPLISHED THROUGH A LANDSCAPE PERMIT
 15040126 THAT ALLOWED UPDATING OF SPECIES TO PROVIDE A
 BETTER, SUSTAINABLE LANDSCAPE WHERE POSSIBLE. INVASIVE
 EXOTICS WERE REMOVED FROM THE SITE AND THE WATER
 RETENTION AREA CLEANED. FINAL INSPECTION WAS CONDUCTED
 ON 10/14/2016. THE LANDSCAPE PERMIT PLAN SHOULD BE USED
 AS THE BASE FOR THE REQUIRED LANDSCAPE ON THE SITE AS
 THERE ARE MISSING TREES IN THE AREA SHOWN WITH THIS
 REQUEST.
  
 NOT SATISFIED
 PROVIDE CALCULATIONS TO SHOW THE SITE COMPLIES WITH
 SECTION 94-443 (D)(2)A. FOR THE NUMBER OF TREES
 REQUIRED FOR THE NUMBER OF UNITS PROVIDED. PROVIDE
 CALCULATIONS FOR THE ENTIRE SITE FOR REQUIRED TREES PER
 REQUIRED OPEN SPACE AND REQUIRED ADDITIONAL TREES FOR
 TOTAL UNITS THEN SHOW THE ACTUAL NUMBER OF TREES
 PROVIDED ON SITE.
  
 ADDITIONAL COMMENT REGARDING THIS COMMENT
 PLEASE SEPARATE THE CALCULATIONS FOR THE OPEN SPACE
 TREE REQUIREMENTS AND THE TREES FOR TOTAL UNIT
 REQUIREMENTS AND SHOW WHAT IS PROVIDED FOR EACH
 CATEGORY. DO NOT LUMP THEM TOGETHER IN YOUR
 CALCULATIONS.
  
 SATISFIED
 THE NEW PARKING PROPOSED SHOWS 18 FOOT LENGTH SPACES
 WITH A CURB. THE CURB MAY BE AT 16 FEET LENGTH WITH AN
 OVERHANG TO REDUCE THE PAVED AREA.
  
 SATISFIED
 THE TREE SHOWN TO REMAIN HAS THE PROPOSED CURB CLOSE TO
 THE BASE OF THE TREE. PROVIDE INFORMATION ON HOW THE
 TREE ROOT ZONE WOULD BE PROTECTED DURING CONSTRUCTION
 AND HOW THE LOCATION OF THE CURB WILL NOT HARM
  
  
  
  
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 02-06-2023 Cont ID  
Sent By rcaranci Date 02-06-2023 Time 14:15 Rev Time 0.00
Received By rcaranci Date 02-06-2023 Time 14:15 Sent To  
Notes
2023-02-06 14:15:43FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 PROJECT: UPTOWN 22 Z23010017
 FEBRUARY 6, 2023
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. THIS SITE WAS REQUIRED BY CONDITION OF APPROVAL
 THROUGH A CLASS B SPECIAL USE APPROVAL TO BRING THE
 LANDSCAPING ON SITE INTO COMPLIANCE WITH THE APPROVED
 LANDSCAPE PLANS. THIS WAS ACCOMPLISHED THROUGH A
 LANDSCAPE PERMIT 15040126 THAT ALLOWED UPDATING OF
 SPECIES TO PROVIDE A BETTER, SUSTAINABLE LANDSCAPE
 WHERE POSSIBLE. INVASIVE EXOTICS WERE REMOVED FROM THE
 SITE AND THE WATER RETENTION AREA CLEANED. FINAL
 INSPECTION WAS CONDUCTED ON 10/14/2016. THE LANDSCAPE
 PERMIT PLAN SHOULD BE USED AS THE BASE FOR THE REQUIRED
 LANDSCAPE ON THE SITE AS THERE ARE MISSING TREES IN THE
 AREA SHOWN WITH THIS REQUEST.
  
 2. PROVIDE CALCULATIONS TO SHOW THE SITE COMPLIES WITH
 SECTION 94-443 (D)(2)A. FOR THE NUMBER OF TREES
 REQUIRED FOR THE NUMBER OF UNITS PROVIDED. PROVIDE
 CALCULATIONS FOR THE ENTIRE SITE FOR REQUIRED TREES PER
 REQUIRED OPEN SPACE AND REQUIRED ADDITIONAL TREES FOR
 TOTAL UNITS THEN SHOW THE ACTUAL NUMBER OF TREES
 PROVIDED ON SITE.
  
 3. THE NEW PARKING PROPOSED SHOWS 18 FOOT LENGTH SPACES
 WITH A CURB. THE CURB MAY BE AT 16 FEET LENGTH WITH AN
 OVERHANG TO REDUCE THE PAVED AREA.
  
 4. THE TREE SHOWN TO REMAIN HAS THE PROPOSED CURB CLOSE
 TO THE BASE OF THE TREE. PROVIDE INFORMATION ON HOW THE
 TREE ROOT ZONE WOULD BE PROTECTED DURING CONSTRUCTION
 AND HOW THE LOCATION OF THE CURB WILL NOT HARM THE
 TREE.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status P Date 02-08-2023 Cont ID  
Sent By relizond Date 02-08-2023 Time 15:42 Rev Time 0.00
Received By relizond Date 02-08-2023 Time 15:42 Sent To  
Notes
2023-02-08 15:44:07APPROVAL CONDITIONAL OF WATER AND SEWER DEMAND SHEET
 BEING PROVIDED THAT COMPARES EXISTING CONDITIONS WITH
 PROPOSED CONDTIONS.

Review Stop PU-CS PUBLIC UTILITIES CUSTOMER SRVC
Rev No 1 Status P Date 02-03-2023 Cont ID  
Sent By mhurley Date 02-03-2023 Time 07:09 Rev Time 0.00
Received By mhurley Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status P Date 02-09-2023 Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date 02-09-2023 Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 2 Status P Date 07-10-2023 Cont ID  
Sent By tward Date 07-10-2023 Time 12:53 Rev Time 0.00
Received By tward Date 07-10-2023 Time 13:03 Sent To  
Notes
2023-07-10 13:02:01THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 6/16/2023 SUBMITTAL. THEY CAN BE ADDRESSED WITH THE
 NEXT SUBMITTAL FOR SITE PLAN APPROVAL OR FOR
 ENGINEERING PERMIT.
  
 1. [SATISFIED] THE CITY'S OFFICIAL VERTICAL DATUM PER
 CITY CODE IS NGVD1929. THE NAVD1988 VERTICAL DATUM MAY
 BE USED IF THE CONVERSION EQUATION BETWEEN NAVD1988 AND
 NGVD1929 IS PROVIDED. ON EVERY SHEET WITH ELEVATION
 INFORMATION, LIST THE VERTICAL DATUM REFERENCE AND THE
 CONVERSION EQUATION TO NGVD1929 IF DIFFERENT FROM
 NGVD1929.
  
 2. [SATISFIED - THE SURVEY IDENTIFIES THE FLOOD ZONE A
 AS COVERING THE DRAINAGE DETENTION AREA AND A PORTION
 OF THE NORTH PROPERTY LINE. NONE OF THE PROPOSED
 IMPROVEMENTS ARE LOCATED IN ZONE A] THE SITE IS WITHIN
 A SPECIAL FLOOD HAZARD AREA (SFHA) ZONE A WITH AN
 INDETERMINATE BASE FLOOD ELEVATION. STRUCTURES LOCATED
 WITHIN A SFHA ARE TO HAVE TWO FEET OF FREEBOARD ABOVE
 THE BASE FLOOD ELEVATION.
  
 3. [PARTIALLY SATISFIED - STRIPING DETAIL ON SHEET
 C1.02 SHOWS 8 INCHES BETWEEN PARALLEL STRIPES. THE
 CITY'S STRIPING DETAIL SHOWS 12 INCHES.] PARKING SPACE
 STRIPING DIMENSIONS DO NOT MEET CITY CODE. SEE SECTION
 94-485 OF THE CODE OF ORDINANCES.
  
 NEW COMMENT:
  
 4. N. AUSTRALIAN AVE RIGHT OF WAY IS MAINTAINED BY PALM
 BEACH COUNTY. ANY IMPROVEMENTS WITHIN THE RIGHT OF WAY
 WILL HAVE TO BE APPROVED/PERMITTED BY THE COUNTY. NOTE
 THE COUNTY HAS PLANS FOR IMPROVING AUSTRALIAN AVE
 BETWEEN BANYAN BLVD AND 45TH ST.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 [email protected]
  

Review Stop STORM STORMWATER
Rev No 1 Status P Date 02-09-2023 Cont ID  
Sent By tward Date 02-09-2023 Time 09:49 Rev Time 0.00
Received By tward Date 02-09-2023 Time 09:50 Sent To  
Notes
2023-02-09 09:49:58THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. THE CITY'S OFFICIAL VERTICAL DATUM PER CITY CODE IS
 NGVD1929. THE NAVD1988 VERTICAL DATUM MAY BE USED IF
 THE CONVERSION EQUATION BETWEEN NAVD1988 AND NGVD1929
 IS PROVIDED. ON EVERY SHEET WITH ELEVATION INFORMATION,
 LIST THE VERTICAL DATUM REFERENCE AND THE CONVERSION
 EQUATION TO NGVD1929 IF DIFFERENT FROM NGVD1929.
  
 2. THE SITE IS WITHIN A SPECIAL FLOOD HAZARD AREA
 (SFHA) ZONE A WITH AN INDETERMINATE BASE FLOOD
 ELEVATION. STRUCTURES LOCATED WITHIN A SFHA ARE TO HAVE
 TWO FEET OF FREEBOARD ABOVE THE BASE FLOOD ELEVATION.
  
 3. PARKING SPACE STRIPING DIMENSIONS DO NOT MEET CITY
 CODE. SEE SECTION 94-485 OF THE CODE OF ORDINANCES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. PROVIDE COPY OF SFWMD ERP MODIFICATION BEFORE START
 OF CONSTRUCTION.
  
 2. PROVIDE EROSION AND SEDIMENT CONTROL PLAN WITH THE
 ENGINEERING PERMIT SUBMITTAL.
  
  
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 [email protected]
 ===============================================
  

Review Stop SURVEY SURVEYING
Rev No 1 Status P Date 02-08-2023 Cont ID  
Sent By vnoel Date 02-08-2023 Time 12:40 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2023-02-08 12:40:54NO COMMENTS.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 3 Status P Date 07-12-2023 Cont ID  
Sent By   Date 07-12-2023 Time   Rev Time 0.00
Received By   Date 07-12-2023 Time   Sent To  
Notes
2023-07-12 14:38:07APPROVED WITH THE FOLLOWING CONDITION:
 1) TO PROVIDE TPS LETTER AT ENGINEERING PERMITTING
  
 FOLLOWING ARE PREVIOUS COMMENTS.
 1) CONDITIONALLY SATISFIED. PROVIDE COUNTY TPS LETTER,
 ONCE AVAILABLE
 2) SATISFIED. PROVIDE A PARKING TABLE SHOWCASING THE
 NUMBER OF REQUIRED AND PROVIDED PARKING SPACES,
 INCLUSIVE OF ADA AND BICYCLE ONES FOR THE WHOLE
 RESIDENTIAL DEVELOPMENT, INCLUSIVE OF THE PROPOSED
 EXPANSION
 3) SATISFIED. DESIGNATE, AND MARK ACCORDINGLY ON THE
 SITE PLAN, A DEDICATED TURN-AROUND SPACE AT THE
 DEAD-END OF THE EXISTING NORTHERN PARKING LOT
 4) SATISFIED. PAINT A PEDESTRIAN CROSSWALK ACROSS THE
 AUSTRALIAN AVE DRIVEWAY
 5) SATISFIED. PAINT DIRECTIONAL PAVEMENT MARKINGS AT
 THE AUSTRALIAN AVE DRIVEWAY, DESIGNATING THE LEFT-TURN
 AND RIGHT-TURN LANES
 6) SATISFIED. INSTALL MUTCD COMPLIANT STOP SIGNS ON
 BOTH SIDES OF THE EXIT DRIVEWAY
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status F Date 07-07-2023 Cont ID  
Sent By   Date 07-07-2023 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2023-07-07 06:26:041) PARTIALLY SATISFIED. PROVIDE COUNTY TPS LETTER, ONCE
 AVAILABLE
 2) NOT SATISFIED. PROVIDE A PARKING TABLE SHOWCASING
 THE NUMBER OF REQUIRED AND PROVIDED PARKING SPACES,
 INCLUSIVE OF ADA AND BICYCLE ONES FOR THE WHOLE
 RESIDENTIAL DEVELOPMENT, INCLUSIVE OF THE PROPOSED
 EXPANSION. PLEASE ADDRESS THE COMMENT BY INSERTING A
 COLUMN WITH THE REQUIRED NUMBER OF SPACES. IF
 AVAILABLE, PLEASE PROVIDE THE PARKING TABLE AND/OR
 CALCULATIONS FOR THE JOSEPH VILLAGE APPROVED SITE PLAN
 DATED 6/16/2016
 3) SATISFIED. DESIGNATE, AND MARK ACCORDINGLY ON THE
 SITE PLAN, A DEDICATED TURN-AROUND SPACE AT THE
 DEAD-END OF THE EXISTING NORTHERN PARKING LOT
 4) SATISFIED. PAINT A PEDESTRIAN CROSSWALK ACROSS THE
 AUSTRALIAN AVE DRIVEWAY
 5) SATISFIED. PAINT DIRECTIONAL PAVEMENT MARKINGS AT
 THE AUSTRALIAN AVE DRIVEWAY, DESIGNATING THE LEFT-TURN
 AND RIGHT-TURN LANES
 6) SATISFIED. INSTALL MUTCD COMPLIANT STOP SIGNS ON
 BOTH SIDES OF THE EXIT DRIVEWAY
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 02-10-2023 Cont ID  
Sent By   Date 02-10-2023 Time   Rev Time  
Received By   Date 02-10-2023 Time   Sent To  
Notes
2023-02-10 19:02:531) PROVIDE COUNTY TPS LETTER, ONCE AVAILABLE
 2) PROVIDE A PARKING TABLE SHOWCASING THE NUMBER OF
 REQUIRED AND PROVIDED PARKING SPACES, INCLUSIVE OF ADA
 AND BICYCLE ONES FOR THE WHOLE RESIDENTIAL DEVELOPMENT,
 INCLUSIVE OF THE PROPOSED EXPANSION
 3) DESIGNATE, AND MARK ACCORDINGLY ON THE SITE PLAN, A
 DEDICATED TURN-AROUND SPACE AT THE DEAD-END OF THE
 EXISTING NORTHERN PARKING LOT
 4) PAINT A PEDESTRIAN CROSSWALK ACROSS THE AUSTRALIAN
 AVE DRIVEWAY
 5) PAINT DIRECTIONAL PAVEMENT MARKINGS AT THE
 AUSTRALIAN AVE DRIVEWAY, DESIGNATING THE LEFT-TURN AND
 RIGHT-TURN LANES
 6) INSTALL MUTCD COMPLIANT STOP SIGNS ON BOTH SIDES OF
 THE EXIT DRIVEWAY
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 06-27-2023 Cont ID  
Sent By asangele Date 06-27-2023 Time 13:29 Rev Time 0.00
Received By asangele Date 06-27-2023 Time 13:29 Sent To  
Notes
2023-06-27 13:38:086/27/2023
 UPTOWN 22
 Z23010017
 ISPR 1709B
  
 ALL COMMENTS REGARDING ZONING WERE ADDRESSED AND
 SATISFIED!
  
 SATISFIED
 PLEASE PROVIDE A TABLE FOR THE PARKING WHAT IS CURRNTLY
 EXISTING AND WHAT IS REQUIRED AND WHAT IS BEING
 PROPOSED. ALSO PLEASE SHOW THE DIMENSIONS OF THE
 PROPSED NEW PARKING SPOTS.
  
 SATISFIED (ONLY 5 UNITS WILL BE ADDED)
 6 ADDITIONAL UNITS WOULD NOT BE ALLOWED TO BE ADDED
 BECAUSE THE DENSITY DOES NOT ALLOW IT.
 5 UNITS WOULD BE THE MAXIUM ALLOWED TO BE ADDED TO THE
 PROPERTY BECAUSE THAT IS THE MAXIIMUM UNITS THE DENSITY
 ALLOWED IN MULTIFAMILY HIGH DENSITY (MF32) RESIDENTIAL
 ZOING.
  
 EXISTING UNITS = 252
  
 32.27 X 7.970 = 257.19
 ARTICLE III. SECTION 94-77
  
 257.19 - 252 = 5.19
  
 MAX ALLOWED UNITS TO BE ADDED= 5
  
  
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF THREE
 (3) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG/.PDF
 FORMAT OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($369.60).
  
  
  
  
 ALEXIS SANGELEER
 PLANNER
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 02-09-2023 Cont ID  
Sent By asangele Date 02-09-2023 Time 08:28 Rev Time 0.00
Received By asangele Date 02-09-2023 Time 08:28 Sent To  
Notes
2023-02-09 08:28:51FAILED
 2/8/2023
  
 PLEASE PROVIDE A TABLE FOR THE PARKING WHAT IS CURRNTLY
 EXISTING AND WHAT IS REQUIRED AND WHAT IS BEING
 PROPOSED. ALSO PLEASE SHOW THE DIMENSIONS OF THE
 PROPSED NEW PARKING SPOTS.
  
 6 ADDITIONAL UNITS WOULD NOT BE ALLOWED TO BE ADDED
 BECAUSE THE DENSITY DOES NOT ALLOW IT.
 5 UNITS WOULD BE THE MAXIUM ALLOWED TO BE ADDED TO THE
 PROPERTY BECAUSE THAT IS THE MAXIIMUM UNITS THE DENSITY
 ALLOWED IN MULTIFAMILY HIGH DENSITY (MF32) RESIDENTIAL
 ZOING.
  
 EXISTING UNITS = 252
  
 32.27 X 7.970 = 257.19
 ARTICLE III. SECTION 94-77
  
 257.19 - 252 = 5.19
  
 MAX ALLOWED UNITS TO BE ADDED= 5
  
 ALEXIS SANGELEER
 PLANNER
 [email protected]