Plan Review Details - Project Z22090018
| Plan Review Stops For Project Z22090018 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
05-04-2023 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
05-04-2023 |
Time |
17:57 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
05-04-2023 |
Time |
17:57 |
Sent To |
|
|
| Notes |
| 2023-05-04 17:57:40 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS | | | SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT | | | REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH | | | COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963, | | | OR BY EMAIL: [email protected] | | | | | | 3. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, | | | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR | | | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, | | | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE | | | FLORIDA BUILDING CODE. | | | | | | 4. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND | | | OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT, | | | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF | | | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF | | | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE | | | VERIFIED. | | | | | | 5. GREASE INTERCEPTOR. IF THE USE IS TO INLCUDE | | | RESTAURANT A GREASE INTERCEPTOR WILL BE REQUIRED. FOR | | | INFORMATION ON THE REQUIRED TYPE, SIZE AND LOCATION, | | | PLEASE CONTACT RYAN BROWN, CHIEF PLUMBING INSPECTOR, | | | DEVELOPMENT SERVICES DEPARTMENT, AT (561) 805-6692, OR | | | BY EMAIL: [email protected] | | | | | | 6. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, | | | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND | | | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, | | | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. | | | | | | 7. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND | | | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF | | | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL | | | NEIGHBORING PROPERTIES. | | | | | | 8. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER | | | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, | | | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE | | | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF | | | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION | | | THAT MAY AFFECT THE USE OF THEIR PROPERTY. | | | | | | 9. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT | | | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL | | | HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION | | | OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING, | | | CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT | | | (561) 805 6659, OR BY EMAIL: [email protected] | | | | | | 10. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT | | | TO ART LIFE ASSESSMENT UNDER THE CITY OF WEST PALM | | | BEACH ART IN PUBLIC PLACES (AIPP) PROGRAM. FOR ADVICE | | | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP | | | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC | | | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
10-12-2022 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
10-12-2022 |
Time |
21:22 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
10-12-2022 |
Time |
21:22 |
Sent To |
|
|
| Notes |
| 2022-10-12 21:26:28 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS | | | SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT | | | REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH | | | COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963, | | | OR BY EMAIL: [email protected] | | | | | | 3. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, | | | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR | | | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, | | | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE | | | FLORIDA BUILDING CODE. | | | | | | 4. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND | | | OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT, | | | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF | | | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF | | | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE | | | VERIFIED. | | | | | | 5. GREASE INTERCEPTOR. IF THE USE IS TO INLCUDE | | | RESTAURANT A GREASE INTERCEPTOR WILL BE REQUIRED. FOR | | | INFORMATION ON THE REQUIRED TYPE, SIZE AND LOCATION, | | | PLEASE CONTACT RYAN BROWN, CHIEF PLUMBING INSPECTOR, | | | DEVELOPMENT SERVICES DEPARTMENT, AT (561) 805-6692, OR | | | BY EMAIL: [email protected] | | | | | | 6. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, | | | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND | | | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, | | | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. | | | | | | 7. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND | | | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF | | | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL | | | NEIGHBORING PROPERTIES. | | | | | | 8. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER | | | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, | | | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE | | | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF | | | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION | | | THAT MAY AFFECT THE USE OF THEIR PROPERTY. | | | | | | 9. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT | | | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL | | | HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION | | | OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING, | | | CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT | | | (561) 805 6659, OR BY EMAIL: [email protected] | | | | | | 10. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT | | | TO ART LIFE ASSESSMENT UNDER THE CITY OF WEST PALM | | | BEACH ART IN PUBLIC PLACES (AIPP) PROGRAM. FOR ADVICE | | | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP | | | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC | | | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
F |
Date |
04-11-2023 |
|
|
Cont ID |
|
| Sent By |
lquinone |
Date |
04-11-2023 |
Time |
09:20 |
Rev Time |
0.00 |
| Received By |
lquinone |
Date |
04-11-2023 |
Time |
09:20 |
Sent To |
|
|
| Notes |
| 2023-04-11 09:03:36 | NO RESPONSE LETTER WAS PROVIDED. | | | | | | O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND | | | INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER | | | (Z-XXXXXXXX). | | | O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY | | | OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC | | | RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF | | | YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE | | | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL | | | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT | | | [email protected] OR 561-494-1079 FOR FURTHER | | | ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION | | | ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD | | | SURVEY, POT-HOLING, SOFT DIGS ETC. | | | O PROVIDE EXISTING AND PROPOSED PERVIOUS AND IMPERVIOUS | | | DATA. | | | | | | BACKFLOW ASSEMBLY AND METERS: | | | O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER | | | SERVICES AND WATER METERS, ALONG WITH WHAT IS HAPPENING | | | TO THEM. | | | O SHOW EXISTING AND PROPOSED DEDICATED UTILITY | | | EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO | | | PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO | | | STRUCTURES WITHIN EASEMENT. | | | O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION | | | OF WATER METER AND BACKFLOW PREVENTION. | | | | | | WATER/WASTEWATER PLAN: | | | O PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND | | | DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND | | | SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH | | | PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE | | | AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS, | | | BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO | | | BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS, | | | DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS, | | | ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT | | | ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF | | | SANITARY SEWER LINES. | | | O GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR | | | SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE | | | PROFILE VIEW. | | | O DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW FOR ALL | | | SANITARY AND STORM SEWERS. | | | O SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT | | | MATERIAL. | | | O PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED | | | UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC, | | | ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION | | | FACILITIES INCLUDING PIPE SIZE AND MATERIAL LOCATED IN | | | THE RIGHT-OF-WAY. | | | O PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER | | | AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD | | | DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS. PLEASE | | | INCLUDE FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION & | | | TELECOMMUNICATION FACILITIES INCLUDING PIPE SIZE AND | | | MATERIAL LOCATED IN THE RIGHT-OF-WAY. | | | O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY | | | TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT | | | APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING | | | AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, | | | MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS | | | SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 | | | FOR WATER. | | | O PROVIDE FIRE FLOW TEST DATA. | | | O PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND | | | STORMWATER INFRASTRUCTURE ALONG ENTIRE PROJECT FRONTAGE | | | (CONDITION OF SITE PLAN APPROVAL). | | | O CUT AND CAP UTILITIES NOT IN USE AND REMOVE ANY | | | ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY | | | ROW. | | | O WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL | | | BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY | | | PROPOSED LENGTH IN FEET. | | | O CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY | | | SEWER ARE REQUIRED. | | | O PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE | | | JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET. | | | O ADD NOTE TO PLANS SPECIFYING CITY???S DOWNSTREAM LIFT | | | STATION NUMBER. | | | O PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR | | | PROPOSED SANITARY LATERALS. | | | | | | | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
09-26-2022 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
09-26-2022 |
Time |
|
Rev Time |
|
| Received By |
rrossano |
Date |
09-26-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-09-26 13:28:53 | Z22090018 ??? 925 RAILROAD AVE ??? 9.26.22 SUBMITTAL | | | | | | COMMENTS FROM RICK ROSSANO, SR. PROJECT COORDINATOR, | | | ENGINEERING SERVICES AT 561-494-1098 [email protected] | | | GENERAL: | | | O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND | | | INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER | | | (Z-XXXXXXXX). | | | O THE CITY OF WEST PALM BEACH HAS A NUMBER OF | | | REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY | | | AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND | | | WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE | | | DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK | | | BELOW: | | | A. HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WP | | | B_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FUL | | | L-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97 | | | B1960045731D3658206F27451722716EF | | | B. THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE | | | FOUND HERE: | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | C. ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM | | | BEACH, FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, | | | ADOPTED SEPT. 22, 2008. (SUPPLEMENT NO. 18) | | | CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL, | | | SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER | | | SERVICE FACILITIES OF THE CITY. | | | THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE | | | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY | | | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, | | | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. | | | O AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR | | | MORE INFORMATION, REFER TO THE LINK BELOW: | | | A. HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PU | | | BLICATIONS/BACKFLOW-CROSS-CONNECTION- CONTROL-MANUAL | | | O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY | | | OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC | | | RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF | | | YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE | | | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL | | | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT | | | [email protected] OR 561-494-1079 FOR FURTHER | | | ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION | | | ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD | | | SURVEY, POT-HOLING, SOFT DIGS ETC. | | | O PROVIDE EXISTING AND PROPOSED PERVIOUS AND IMPERVIOUS | | | DATA. | | | | | | BACKFLOW ASSEMBLY AND METERS: | | | O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER | | | SERVICES AND WATER METERS, ALONG WITH WHAT IS HAPPENING | | | TO THEM. | | | O SHOW EXISTING AND PROPOSED DEDICATED UTILITY | | | EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO | | | PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO | | | STRUCTURES WITHIN EASEMENT. | | | O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION | | | OF WATER METER AND BACKFLOW | | | PREVENTION. | | | O BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY | | | OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER | | | METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO | | | PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE | | | INSTALLED ABOVE-GROUND ONLY. | | | O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE | | | NOTE USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA. | | | | | | WATER/WASTEWATER PLAN: | | | O PROVIDE VERTICAL DATUM AND DATUM CONVERSION | | | INFORMATION (NAVD 1988 AND NGVD 1929). | | | O SHOW PROJECT ADDRESS ON ALL PLAN SHEETS. | | | O PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE | | | STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC. | | | O PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND | | | DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND | | | SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH | | | PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE | | | AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS, | | | BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO | | | BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS, | | | DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS, | | | ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT | | | ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF | | | SANITARY SEWER LINES. | | | O GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR | | | SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE | | | PROFILE VIEW. | | | O DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN | | | VIEW FOR ALL SANITARY AND STORM SEWERS. | | | O SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT | | | MATERIAL. | | | O PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED | | | UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC, | | | ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION | | | FACILITIES INCLUDING PIPE SIZE AND MATERIAL LOCATED IN | | | THE RIGHT-OF-WAY. | | | O PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER | | | AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD | | | DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS. PLEASE | | | INCLUDE FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION & | | | TELECOMMUNICATION FACILITIES INCLUDING PIPE SIZE AND | | | MATERIAL LOCATED IN THE RIGHT-OF-WAY. | | | O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY | | | TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT | | | APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING | | | AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, | | | MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS | | | SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 | | | FOR WATER. | | | O PROVIDE FIRE FLOW TEST DATA. | | | O PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND | | | STORMWATER INFRASTRUCTURE ALONG ENTIRE PROJECT FRONTAGE | | | (CONDITION OF SITE PLAN APPROVAL). | | | O CUT AND CAP UTILITIES NOT IN USE AND REMOVE ANY | | | ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY | | | ROW. | | | O WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL | | | BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY | | | PROPOSED LENGTH IN FEET. | | | O CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY | | | SEWER ARE REQUIRED. | | | O PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE | | | JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET. | | | O ADD NOTE TO PLANS SPECIFYING CITY???S DOWNSTREAM LIFT | | | STATION NUMBER. | | | O PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR | | | PROPOSED SANITARY LATERALS. | | | O LABEL WATER LINES AS PRIVATE WHERE APPLICABLE. | | | O PLEASE SHOW AND LABEL EXISTING AND PROPOSED GREASE | | | TRAPS (IF ANY). | | | O PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN | | | OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER. | | | | | | FORMAL ENGINEERING REVIEW: | | | O FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES | | | NOI REQUIREMENTS WILL BE ENFORCED. | | | - AN NOI IS REQUIRED FOR PROJECTS THAT: | | | - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS | | | THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF | | | DEVELOPMENT OR SALE; | | | - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE | | | STATE OR TO SURFACE WATERS OF THE STATE THROUGH A | | | MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4). | | | - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF | | | CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION | | | THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL | | | SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT | | | OF THE 10-2 CERTIFICATION. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF | | | WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING | | | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT | | | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING | | | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED | | | LEAD-FREE DESIGN. | | | O FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES | | | ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY | | | LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT | | | PARCELS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, IF WATER LINES ARE | | | BEING REPLACED IN ROW, SHOW ADJACENT PARCEL ADDRESSES. | | | O FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO PROVIDE | | | 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF | | | PROPOSED TRENCH IN CITY MAINTAINED ROADWAY AREAS PER | | | CITY OF WPB STANDARD DETAIL GC-8. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | CALCULATIONS OF PERVIOUS AND IMPERVIOUS AREAS FOR | | | PROPOSED IMPROVED AREAS. | | | | | | QUESTIONS AND COORDINATION CONTACTS: | | | O MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR WITH | | | CITY OF WPB PUBLIC UTILITIES, REGARDING PLACEMENT OF | | | BACKFLOW DEVICES AND WATER METERS. CONTACT HIM AT | | | 561-822-2262 OR [email protected] | | | O MIKE TECHNOW, PROJECT ENGINEER, PUBLIC UTILITIES | | | DEPARTMENT AT 561-494-1047 OR [email protected] | | | O TRACY WARD, SR. STORMWATER ENGINEER, ENGINEERING | | | SERVICES DEPT. AT 561-494-1120 OR [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
09-29-2022 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
09-29-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
09-29-2022 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2022-09-29 14:25:42 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE DEPARTMENT. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. THE FOLLOWING COMMENTS ARE INTENDED | | | TO PROVIDE GUIDANCE FOR BUILDING PLAN SUBMITTAL. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING(S) SHALL COMPLY | | | WITH THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION | | | CODE, INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE | | | CODES. | | | | | | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE | | | OCCUPANCY TYPE PER THE FLORIDA FIRE PREVENTION CODE. | | | | | | 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE | | | LOAD CALCULATION IS INCLUDED, AND THAT ADEQUATE WATER | | | SUPPLY IS EXISTING OR WILL BE PROVIDED. | | | | | | 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | ANY PROPOSED LOCATIONS OF THE FIRE HYDRANT AND FDC | | | SHALL BE WITHIN 100' OF EACH OTHER AND CLOSELY | | | COORDINATED WITH THE BUREAU OF FIRE PREVENTION. | | | | | | 9. IF APPLICABLE, PROVIDE FOR A FIRE SPRINKLER AND/OR | | | FIRE ALARM PER THE APPLICABLE OCCUPANCY CODE. | | | | | | FOR ANY LIFE SAFETY ENGINEERED SYSTEM, I.E FIRE | | | SPRINKLER AND FIRE ALARM, ENSURE THEY COMPLY WITH THE | | | REQUIREMENTS OF F.A.C. 61G AND SUBMITTED WITH THE | | | MASTER PERMIT. | | | | | | 9A. THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE | | | LOCATIONS SHALL MEET AND BE INSTALLED PER THE | | | REQUIREMENTS OF NFPA 24 AND SHALL BE COORDINATED WITH | | | THE OFFICE OF FIRE MARSHAL, THE CITY'S ENGINEERS | | | OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S PLANNING | | | AND ZONING OFFICE. | | | | | | 10. COMPLETE LIFE SAFETY PLANS FOR THE OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, EXIT SEPARATION DISTANCES, COMMON PATHS OF | | | TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, EMERGENCY | | | LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE | | | EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES | | | AND EQUIPMENT. | | | | | | 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE | | | SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY | | | DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS. | | | | | | 12. AREAS OF REFUGE SHALL BE PROVIDED AS REQUIRED B THE | | | FLORIDA BUILDING CODE AND NFPA 101, CH 7, MEANS OF | | | EGRESS. | | | | | | 13. TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEMS. | | | | | | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY | | | RADIO ENHANCEMENT SERVICES. | | | | | | 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM | | | RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT | | | COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL | | | DETERMINED BY THE AHJ. | | | | | | CONTACT WILL NEED TO BE MADE TO MARK FILLA, PALM BEACH | | | COUNTY PUBLIC SAFETY RADIO SYSTEMS MANAGER, | | | [email protected], 561-233-0837; AS OUR RADIOS OPERATE | | | ON THEIR SYSTEM FOR DETAILED RADIO FREQUENCY AND | | | INSTALLATION INSTRUCTIONS. | | | | | | 14. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL. | | | | | | 15. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
10-04-2022 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
10-04-2022 |
Time |
12:25 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
10-04-2022 |
Time |
12:24 |
Sent To |
|
|
| Notes |
| 2022-10-04 12:26:06 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: 925 RAILROAD AVE NORA Z22090018 | | | OCTOBER 3, 2022 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. PROVIDE A SITE PLAN AND LANDSCAPE PLAN SHOWING THE | | | REQUIRED 15% PRIVATE OPEN SPACE FOR THE NORA 5 | | | DISTRICT. LANDSCAPE PLAN MUST MEET THE LANDSCAPE | | | REQUIREMENTS. | | | 2. THE SITE PLAN SUBMITTED SHOWS PROPOSED IMPROVEMENTS | | | ONTO THE ADJACENT LOT AT 1009 N RAILROAD. CLARIFY THE | | | AREA OF APPLICATION. | | | | | | | | | CONDITIONS OF APPROVAL | | | 1. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF | | | WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A | | | SEPARATE MAINTENANCE AGREEMENT WITH THE CITY. | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
mtechnow |
Date |
10-13-2022 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2022-10-13 11:05:33 | -REFLECT THE PROPOSED UTILITY WORK FROM NORA | | | STREETSCAPE PROJECT ON PLAN SHEETS. | | | -REFERENCE PLAN SUBMITTAL CHECKLIST FOR PLAN | | | GUIDELINES. | | | | | | MICHAEL TECHNOW [email protected] |
|
|
| Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
| Rev No |
3 |
Status |
F |
Date |
07-25-2023 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
07-25-2023 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2023-07-25 13:09:00 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | -RESPONSE LETTER SAID WATER AND SEWER DEMAND | | | CALCULATIONS WERE ADDED TO SHEET C1.2, BUT CANNOT FIND | | | THEM. PLEASE ADD. | | | -RESPONSE LETTER SAID FDC IS AT SOUTHEAST BUILDING | | | CORNER ON SHEET C1.2, BUT CANNOT FIND IT. PLEASE SHOW | | | AND LABEL. | | | -LANDSCAPE PLANS DO NOT SHOW UPDATED UTILITIES FROM | | | ENGINEERING PLANS. PLEASE UPDATE LANDSCAPING PLANS TO | | | SHOW PROPOSED UTILITIES. | | | -PROPOSED 8 INCH FIRELINE WATER SERVICE WOULD NEED 8 | | | INCH DETECTOR FIRELINE BACKFLOW ASSEMBLY. SHOW AND | | | LABEL IT NEAR THE NORTHEAST AREA OF PROPERTY. | | | -ENGINEERING PLANS SHOW TWO SETS OF WATER METERS. LOOKS | | | LIKE REVISED SYMBOLS WERE ADDED, BUT THE OLD SYMBOLS | | | WERE NOT REMOVED AND THE CALLOUT LABELS NOT | | | TRANSFERRED. PLEASE UPDATE ENGINEERING PLANS. | | | -CONTAINMENT BACKFLOW ASSEMBLY LOCATIONS ARE NOT | | | ACCEPTABLE NEAR THE WESTERN PROPERTY LINE. NEEDS TO BE | | | NEAR THE EASTERN PROPERTY LINE. WHEN DETERMINING | | | BACKFLOW LOCATIONS IT MAY HELP TO ALSO CONSIDER THE | | | LANDSCAPING PLAN LAYOUT. | | | -PE PIPE MATERIAL IS NOT ACCEPTABLE BETWEEN WATER METER | | | AND DOMESTIC BACKFLOW ASSEMBLY. | | | -LABEL WATER MAIN WITH PIPE SIZE AND MATERIAL TYPE. | | | -UPDATE E22030048 WITH ANY CHANGES APPROVED THROUGH | | | THIS PPRC PROJECT. | | | RESPECTFULLY, | | | MARK HURLEY [email protected] |
|
|
| Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
| Rev No |
2 |
Status |
F |
Date |
04-14-2023 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
04-14-2023 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2023-04-14 16:17:26 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | -WATER METER BOX LOCATIONS ARE NOT ACCEPTABLE. DISTANCE | | | TO WATER MAIN SHOULD BE MINIMIZED. REVISE LOCATIONS AND | | | MAKE SURE MATCHES E22030048. | | | -ADD ADDRESS TO LABEL OF EACH WATER METER. | | | -BACKFLOW ASSEMBLY LOCATIONS WOULD NEED TO BE REVISED | | | TO MINIMIZE DISTANCE TO NEW METER BOX LOCATIONS AND | | | FOLLOW WPB STANDARDS. | | | -REVISE CALLOUT THAT SAY 4??? FIRE METER AND DDCA. | | | UTILITY DOES NOT TYPICALLY PROVIDE 4 INCH FIRE METERS. | | | USUALLY PROVIDE DETECTOR METERS ON FIRELINE BACKFLOW | | | ASSEMBLIES. ADD SIZE TO OTHER FIRELINE BACKFLOW | | | ASSEMBLY. | | | -WHEN REVISING ENGINEERING PLANS, ENSURE THERE ARE NOT | | | TWO DETECTOR METERS AND FIRELINE BACKFLOW ASSEMBLIES ON | | | ONE FIRELINE WATER SERVICE. | | | -VERIFY PRIVATE FIRE SYSTEMS WILL NOT HAVE ADDED | | | CHEMICALS OR AUXILIARY WATER SUPPLIES SUCH AS WELLS. | | | -CANNOT TELL IF THERE ARE ANY FIRELINES. IF THERE WILL | | | BE FIRELINES, SHOW AND LABEL THEM ON PLANS ALONG FIRE | | | FIRELINE BACKFLOW ASSEMBLY. ALSO SHOW AND LABEL FDC IF | | | ANY ARE NEEDED OR REQUIRED. | | | -WILL NEED TO UPDATE LANDSCAPING PLANS WITH REVISED | | | UTILITY LOCATIONS AND UTILITIES AND TREES ARE SEPARATED | | | WITH SUFFICIENT DISTANCE. | | | -SHIFTING PROPERTY LINE IS NOT CALLED OUT ON | | | ENGINEERING PLAN LIKE IT IS ON SITE PLAN. PLEASE ADD | | | THAT CALLOUT. | | | -SP-1 IS TITLED LANDSCAPE PLAN INSTEAD OF SITE PLAN. | | | LANDSCAPE PLAN SEEMS TO BE LP-1. PLEASE UPDATE. | | | -ON REVISED ENGINEERING PLANS, ENSURE THAT UTILITIES DO | | | NOT INTERFERE WITH OPERATION OF DOORS. | | | -A.101 WOULD NEED REVISION FOR CHANGING WATER METER AND | | | BACKFLOW ASSEMBLY LOCATIONS. | | | -RESPONSE LETTER SAID FDC WAS ADDED BUT CANNOT FIND ON | | | ENGINEERING PLANS. SHOW AND LABEL ON SHEET C1.2 | | | -RESPONSE LETTER SAID WATER AND SEWER DEMAND | | | CALCULATIONS WERE ADDED, BUT STILL CANNOT FIND. PLEASE | | | ADD TO SHEET C1.2 | | | -ON ENGINEERING PLAN, SHOW THE UPDATED DOOR LOCATIONS. | | | RESPECTFULLY, | | | MARK HURLEY [email protected] |
|
|
| Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
| Rev No |
1 |
Status |
F |
Date |
10-11-2022 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
10-11-2022 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-10-11 10:15:18 | PLEASE PROVIDE WRITTEN RESPONSES FOR THE FOLLOWING: | | | -SHOW AND LABEL WATER METER BOX ON SHEET C1.1. SHOULD | | | BE LOCATED OUTSIDE OF BUILDING AND PREFERABLY AWAY FROM | | | PEDESTRIAN TRAFFIC. | | | -SHOW AND LABEL BACKFLOW ASSEMBLIES ON SHEET C1.1. | | | -SHOW AND LABEL PROPERTY LINE ON SHEET C1.1. | | | -ADD WATER AND SEWER DEMAND CALCULATIONS ON SHEET C1.1. | | | -IF FDC ARE NEEDED OR REQUIRED, THEN SHOW AND LABEL ON | | | PLANS. | | | -IS EXISTING BUILDING BEING DEMOLISHED AND NEW BUILDING | | | BEING BUILT? | | | -DOORS SHOULD NOT OPEN INTO RIGHT OF WAY. PLEASE UPDATE | | | SITE PLAN. | | | -COULD NOT LOCATE A LANDSCAPING PLAN IN SUBMITTAL | | | PACKAGE. PLEASE ADD ONE WITH RESUBMITTAL. | | | RESPECTFULLY, | | | MARK HURLEY [email protected] |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
3 |
Status |
F |
Date |
07-17-2023 |
|
|
Cont ID |
|
| Sent By |
|
Date |
07-17-2023 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
07-17-2023 |
Time |
|
Sent To |
|
|
| Notes |
| 2023-07-17 11:01:32 | PLEASE PROVIDE THE FOLLOWINGS: | | | 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID | | | WASTE VOLUME PRODUCED ALONG WITH THE SIZE, TYPE AND | | | QUANTITY OF THE CONTAINER (I.E. DUMPSTER/COMPACTOR) | | | THAT WILL BE UTILIZED FOR THE SANITATION SERVICE. | | | 2- DETAILS FOR SANITATION SERVICE (I.E. SOLID WASTE | | | CONTAINER(S) TYPE, COLLECTION LOCATION, ETC.). | | | 3- AUTOTURN EXHIBIT WITH DYNAMIC ENVELOPE AND THE | | | VEHICLE'S WHEEL PATH IDENTIFIED WITH DIFFERENT COLORS | | | FOR THE SANITATION SERVICE, FRONT LOADER TRUCK WITH THE | | | FOLLOWING SPECS: | | | - DUAL AXLES | | | - TRUCK LENGTH: 35 FT | | | - TRUCK WIDTH: 11 FT | | | - TURNING RADIUS: | | | - SAE TURNING RADIUS: 32.5 FT | | | - CURB-TO-CURB DIAMETER: 74 FT | | | - WALL-TO-WALL DIAMETER: 86.3 FT | | | 4- DESIGNATED LOCATION FOR THE BULK ITEM PICK UP AND | | | RECYCLING CONTAINERS | | | 5- OWNERS AND/OR OCCUPANTS OF PROPERTY THAT REQUIRE | | | GREASE HAULING SERVICES SHALL ENSURE THAT THEIR GREASE | | | TANKS OR CONTAINERS REMAIN CLEAN, AND ARE ENCLOSED AND | | | NOT IN PUBLIC VIEW. | | | 6- IN CASE OF PROPOSING ADDITION OF ANY NEW CAN(S) IN | | | THE CITY`S RIGHT-OF-WAY , THE LOCATION AND QUANTITY OF | | | THE CAN(S) SHALL BE REVIEWED AND APPROVED BY PUBLIC | | | WORKS DEPARTMENT AND THE CAN(S) SHALL BE TYPE, SIZE AND | | | COLOR APPROVED BY PUBLIC WORKS DEPARTMENT. THE BUILDING | | | MAINTENANCE IS RESPONSIBLE TO MAINTAIN AND SERVICE THE | | | CAN(S). | | | 7- ALL THE PARKING STALL PAINTING SHALL COMPLY WITH THE | | | CITY`S MUNICIPAL CODE SECTION 94-485 AND FLORIDA | | | STATUES [553.5041 F.S.]. | | | 8- ALL STRIPING AND SIGNAGE SHALL COMPLY WITH THE | | | LATEST CITY OF WEST PALM BEACH STANDARD DETAILS AND | | | MEET THE M.U.T.C.D. LATEST EDITION. | | | 9- ALL PAVEMENT MARKING , SIGNING AND SIDEWALK DAMAGED | | | DURING CONSTRUCTION SHALL BE RESTORED. | | | | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] | | | 561-822-2045 |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
2 |
Status |
F |
Date |
04-27-2023 |
|
|
Cont ID |
|
| Sent By |
|
Date |
04-27-2023 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
04-27-2023 |
Time |
|
Sent To |
|
|
| Notes |
| 2023-05-03 15:30:27 | PLEASE PROVIDE THE FOLLOWINGS: | | | 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID | | | WASTE VOLUME PRODUCED ALONG WITH THE SIZE, TYPE AND | | | QUANTITY OF THE CONTAINER (I.E. DUMPSTER/COMPACTOR) | | | THAT WILL BE UTILIZED FOR THE SANITATION SERVICE. | | | 2- DETAILS FOR SANITATION SERVICE (I.E. SOLID WASTE | | | CONTAINER(S) TYPE, COLLECTION LOCATION, ETC.). FOR A | | | FREESTANDING SITE DUMPSTER ENCLOSURE, THE ENCLOSURE | | | SHALL COMPLY WITH THE LATEST REVISION OF CITY OF WEST | | | PALM BEACH GENERAL CONSTRUCTION-GARBAGE ENCLOSURE | | | STANDARD, GC-7. (LINK TO THE LATEST REVISION OF THE | | | GC-7 DOCUMENT: HTTPS://WWW.WPB.ORG/HOME/SHOWPUBLISHEDDO | | | CUMENT/3690/637629060422100000) | | | 3- AUTOTURN EXHIBIT WITH DYNAMIC ENVELOPE AND THE | | | VEHICLE'S WHEEL PATH IDENTIFIED WITH DIFFERENT COLORS | | | FOR THE SANITATION SERVICE, FRONT LOADER TRUCK WITH THE | | | FOLLOWING SPECS: | | | - DUAL AXLES | | | - TRUCK LENGTH: 35 FT | | | - TRUCK WIDTH: 11 FT | | | - TURNING RADIUS: | | | - SAE TURNING RADIUS: 32.5 FT | | | - CURB-TO-CURB DIAMETER: 74 FT | | | - WALL-TO-WALL DIAMETER: 86.3 FT | | | 4- DESIGNATED LOCATION FOR THE BULK ITEM PICK UP AND | | | RECYCLING CONTAINERS | | | | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] | | | 561-822-2045 |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
F |
Date |
10-05-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
10-05-2022 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
10-05-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-10-05 13:57:37 | PLEASE PROVIDE THE FOLLOWINGS: | | | 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID | | | WASTE VOLUME PRODUCED ALONG WITH THE SIZE, TYPE AND | | | QUANTITY OF THE CONTAINER (I.E. DUMPSTER/COMPACTOR) | | | THAT WILL BE UTILIZED FOR THE SANITATION SERVICE. | | | 2- DETAILS FOR SANITATION SERVICE (I.E. SOLID WASTE | | | CONTAINER(S) TYPE, COLLECTION LOCATION, ETC.). FOR A | | | FREESTANDING SITE DUMPSTER ENCLOSURE, THE ENCLOSURE | | | SHALL COMPLY WITH THE LATEST REVISION OF CITY OF WEST | | | PALM BEACH GENERAL CONSTRUCTION-GARBAGE ENCLOSURE | | | STANDARD, GC-7. (LINK TO THE LATEST REVISION OF THE | | | GC-7 DOCUMENT: HTTPS://WWW.WPB.ORG/HOME/SHOWPUBLISHEDDO | | | CUMENT/3690/637629060422100000) | | | 3- AUTOTURN EXHIBIT WITH DYNAMIC ENVELOPE AND THE | | | VEHICLE'S WHEEL PATH IDENTIFIED WITH DIFFERENT COLORS | | | FOR THE SANITATION SERVICE, FRONT LOADER TRUCK WITH THE | | | FOLLOWING SPECS: | | | - DUAL AXLES | | | - TRUCK LENGTH: 35 FT | | | - TRUCK WIDTH: 11 FT | | | - TURNING RADIUS: | | | - SAE TURNING RADIUS: 32.5 FT | | | - CURB-TO-CURB DIAMETER: 74 FT | | | - WALL-TO-WALL DIAMETER: 86.3 FT | | | 4- DESIGNATED LOCATION FOR THE BULK ITEM PICK UP AND | | | RECYCLING CONTAINERS | | | 5- OWNERS AND/OR OCCUPANTS OF PROPERTY THAT REQUIRE | | | GREASE HAULING SERVICES SHALL ENSURE THAT THEIR GREASE | | | TANKS OR CONTAINERS REMAIN CLEAN, AND ARE ENCLOSED AND | | | NOT IN PUBLIC VIEW. | | | 6- IN CASE OF PROPOSING ADDITION OF ANY NEW CAN(S) IN | | | THE CITY`S RIGHT-OF-WAY , THE LOCATION AND QUANTITY OF | | | THE CAN(S) SHALL BE REVIEWED AND APPROVED BY PUBLIC | | | WORKS DEPARTMENT AND THE CAN(S) SHALL BE TYPE, SIZE AND | | | COLOR APPROVED BY PUBLIC WORKS DEPARTMENT. THE BUILDING | | | MAINTENANCE IS RESPONSIBLE TO MAINTAIN AND SERVICE THE | | | CAN(S). | | | 7- ALL THE PARKING STALL PAINTING SHALL COMPLY WITH THE | | | CITY`S MUNICIPAL CODE SECTION 94-485 AND FLORIDA | | | STATUES [553.5041 F.S.]. | | | 8- SIGNAGE PLAN. ALL STRIPING AND SIGNAGE SHALL COMPLY | | | WITH THE LATEST CITY OF WEST PALM BEACH STANDARD | | | DETAILS AND MEET THE M.U.T.C.D. LATEST EDITION. | | | 9- ALL PAVEMENT MARKING , SIGNING AND SIDEWALK DAMAGED | | | DURING CONSTRUCTION SHALL BE RESTORED. | | | | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] | | | 561-822-2045 |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
F |
Date |
05-07-2023 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
05-07-2023 |
Time |
19:46 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
05-08-2023 |
Time |
09:28 |
Sent To |
|
|
| Notes |
| 2023-05-08 09:25:59 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE | | | 3-28-2023 SUBMITTAL: | | | | | | 1. [SATISFIED] NO PGD PLAN PROVIDED. | | | | | | 2. [SATISFIED] SHOW THE BOUNDARY FOR THE 925 N. | | | RAILROAD AVE. PARCEL. | | | | | | 3. [SATISFIED] LABEL THE FINISHED FLOOR ELEVATION. | | | | | | 4. [SATISFIED - PARCEL WILL BE RE-PLATTED] BUILDING | | | EXTENDS NORTH OF THE 925 N. RAILROAD AVE PARCEL. | | | | | | 5. [NOT SATISFIED] PROVIDE A CROSS SECTION FROM THE | | | CENTERLINE OF N. RAILROAD AVE TO THE BUILDING FACE. | | | SHOW GRADE BREAKS, R/W LINE, NAME OF R/W, DISTANCES | | | FROM R/W TO BACK OF CURB, TO FACE OF BUILDING, ETC. USE | | | THE PROPOSED DESIGN OF N. RAILROAD AVE. | | | | | | 6. [PARTIALLY SATISFIED - LABEL UTILITIES WITHIN THE | | | R/W ALSO] LABEL ALL UTILITIES (SIZE, MATERIAL). | | | | | | NEW COMMENTS (3/28/2023 SUBMITTAL): | | | | | | 7. CLEAN UP THE GHOST IMAGES (BUILDING, UTILITIES, | | | ETC.) ON THE ENGINEERING PLANS. | | | | | | 8. ENGINEERING PLANS DO NOT MATCH THE SITE PLAN WITH | | | RESPECT TO RECESSED DOOR OPENINGS. | | | | | | 8. COORDINATE LOCATION OF OFFSITE UTILITIES WITH THE | | | NORTH RAILROAD STREETSCAPE PLANS (E22030048) AND WITH | | | THE SERVICE COURT (Z22070020) DEVELOPMENT PLANS. | | | IDENTIFY THE UTILITIES THAT WILL BE CONSTRUCTED WITH | | | THE 925 N. RAILROAD AVE DEVELOPMENT. | | | | | | 9. COORDINATE DIMENSIONS OF THE EXFILTRATION TRENCH | | | CALLED OUT ON THE PDG PLAN AND ON THE EXFILTRATION | | | TRENCH DETAIL. | | | | | | 10. VERIFY SIZE OF PROPOSED GREASE TRAPS AND DRAW TO | | | SCALE ON THE ENGINEERING PLANS. | | | | | | 11. PROVIDE DETAIL OF THE CONTROL STRUCTURE. NOTE THE | | | CITY DOES NOT ALLOW THE USE OF BLEEDERS WITH | | | EXFILTRATION TRENCH SYSTEMS. | | | | | | 12. PROVIDE PROPOSED GRADES OR FLOW ARROWS ON THE PGD | | | PLAN SHOWING DIRECTION OF SURFACE SLOPES. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | [email protected] | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
10-12-2022 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
10-12-2022 |
Time |
23:58 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
10-13-2022 |
Time |
00:00 |
Sent To |
|
|
| Notes |
| 2022-10-13 00:00:02 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | 1. NO PGD PLAN PROVIDED. | | | | | | 2. SHOW THE BOUNDARY FOR THE 925 N. RAILROAD AVE. | | | PARCEL. | | | | | | 3. LABEL THE FINISHED FLOOR ELEVATION. | | | | | | 4. BUILDING EXTENDS NORTH OF THE 925 N. RAILROAD AVE | | | PARCEL. | | | | | | 5. PROVIDE A CROSS SECTION FROM THE CENTERLINE OF N. | | | RAILROAD AVE TO THE BUILDING FACE. SHOW GRADE BREAKS, | | | R/W LINE, NAME OF R/W, DISTANCES FROM R/W TO BACK OF | | | CURB, TO FACE OF BUILDING, ETC. USE THE PROPOSED DESIGN | | | OF N. RAILROAD AVE. | | | | | | 6. LABEL ALL UTILITIES (SIZE, MATERIAL). | | | | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP | | | CRITERIA. STORMWATER CALCULATIONS WILL BE REVIEWED WITH | | | THE ENGINEERING PERMIT SUBMITTAL. | | | | | | 2. PROVIDE COPY OF SFWMD ERP PERMIT BEFORE START OF | | | CONSTRUCTION. | | | | | | 3. PROVIDE EROSION AND SEDIMENT CONTROL PLAN WITH THE | | | ENGINEERING PERMIT SUBMITTAL. | | | | | | | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | [email protected] | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
10-11-2022 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
10-11-2022 |
Time |
12:38 |
Rev Time |
|
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-10-11 12:47:28 | 1. PROPERTY CORNERS NOT SHOWN AS FOUND OR SET ON | | | SURVEY. | | | 2. RELOCATE GREASE TRAP INTO COURTYARD AREA. | | | 3. DOOR SHOULD NOT OPEN INTO SIDEWALK. |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
10-13-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
10-13-2022 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
10-13-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-10-13 04:15:47 | TRAFFIC COMMENTS | | | 1) SETUP A METHODOLOGY MEETING | | | 2) CORRECT THE EXEMPTION REFERENCE AS IT IS TRAFFIC | | | CONCURRENCY EXCEPTION AREA (TCEA), NOT CRA. | | | 3) SCHEDULE A METHODOLOGY MEETING. A FULL TRAFFIC STUDY | | | IS NEEDED; EXEMPTION FROM COUNTY CONCURRENCY DOES NOT | | | PRECLUDE THE CITY TO REQUEST MORE IN-DEPTH ANALYSIS, | | | GIVEN THE SIGNIFICANT CHANGE IN LAND USE AND TRIP | | | GENERATION TOGETHER WITH IMPACT TO THE SURROUNDING | | | ROADWAY NETWORK | | | 4) ALL CONCERNS AND COMMENTS PROVIDED BY THE COUNTY IN | | | THE TPS LETTER SHALL BE ADDRESSED | | | 5) MORE DETAILED TRANSPORTATION DEMAND MANAGEMENT (TDM) | | | MEASURES SHALL BE DISCUSSED AND AGREED WITH CITY | | | PLANNING AND ENGINEERING DEPARTMENTS | | | 6) TRAFFIC SIGNAL WARRANT ANALYSES SHALL BE CONDUCTED | | | AT EACH IMPACTED UNSIGNALIZED INTERSECTION ALONG PALM | | | BEACH LAKES BLVD AND DIXIE HIGHWAY | | | | | | SITE COMMENTS | | | 7) PROVIDE A TRANSPORTATION SPECIFIC SITE PLAN FOR THE | | | GROUND FLOOR. SHOWCASING TRANSPORTATION RELATED | | | FEATURES (E.G. ROADWAY WIDTHS, DRIVING AISLES, PARKING | | | STALLS, SIDEWALK, CURB, GUTTER, DRIVEWAY, GATES, | | | CROSSWALKS, VISIBILITY TRIANGLE, CORNER & DRIVEWAY | | | SEPARATION DISTANCES, SLOPES, ETC.) PROPERLY LABELED | | | AND DIMENSIONED. THE SITE PLAN SHOULD BE NAMED T-1.0 | | | 8) IN THE T-1.0 SITE PLAN, PLEASE SHOWCASE BASIC CURB | | | DETAILS (E.G. DRIVEWAY, CURB CUTS, PAVEMENT MARKINGS, | | | PARKING STALLS, ETC.) ON THE OPPOSITE SIDE OF THE ROADS | | | SURROUNDING THE PROPOSED DEVELOPMENT | | | 9) PROVIDE A SIGNAGE AND PAVEMENT MARKING PLAN. | | | INCLUSIVE OF ALL FEATURES WITHIN THE PROPOSED | | | DEVELOPMENT AND ALONG ALL ROADS FRONTING THE SITE. SUCH | | | PLAN IS PART OF THE TRANSPORTATION REVIEW AND SHOULD BE | | | NAMED ACCORDINGLY (E.G. T-1.1 OR T-2.0) | | | 10) PROVIDE AUTOTURN ANALYSIS FOR GARBAGE TRUCK AND/OR | | | SERVICE VEHICLES DRIVING IN AND OUT OF THE PROPOSED | | | DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES AND WHEEL | | | PATHS CLEARLY DISTINCT AND DEFINED IN DIFFERENT COLORS. | | | PROVIDE THE ANALYSIS IN A SEPARATE SHEET. SUCH PLAN(S) | | | CONTAINING THE ANALYSIS ARE PART OF THE TRANSPORTATION | | | REVIEW AND SHOULD BE NAMED ACCORDINGLY (E.G. T1.2, | | | T-3.0) | | | 11) PROVIDE ENGINEERING REFERENCE AND SPECS SHEETS FOR | | | EACH OF THE PROPOSED TRANSPORTATION FEATURES (E.G. | | | CURB, RAMP, GATE, SIGNAGE, PAVEMENT MARKING, SIGNAL, | | | ETC.) | | | 12) PROVIDE A PARKING TABLE SHOWCASING THE NUMBER OF | | | REQUIRED AND PROVIDED PARKING SPACES, INCLUSIVE OF ADA | | | AND BICYCLE ONES | | | 13) IS VALET SERVICE PROPOSED? IF SO, PROVIDE AN | | | OPERATIONAL ANALYSIS. DETAILS OF THE ANALYSIS SHOULD BE | | | DISCUSSED DURING THE METHODOLOGY MEETING | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
04-28-2023 |
|
|
Cont ID |
|
| Sent By |
ckimmerl |
Date |
04-28-2023 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
ckimmerl |
Date |
04-28-2023 |
Time |
14:07 |
Sent To |
|
|
| Notes |
| 2023-04-28 14:03:23 | ZONING 4.28.23 REVIEW: | | | 1. NO RESPONSES GIVEN TO PREVIOUS ZONING COMMENTS. | | | PLEASE PROVIDE NARRATIVE/RESPONSES TO ALL REVIEW | | | COMMENTS. | | | | | | ZONING COMMENTS FROM 10.13.22 PPRC | | | INSUFFICIENT AND INCOMPLETE SUBMITTAL - PLEASE NOTE | | | THAT FUTURE SUBMITTALS SUCH AS THIS WILL NOT BE | | | ACCEPTED OR PUT ON FOR PPRC REVIEW. MISSING MANY | | | DRAWINGS AND DETAILS FOR THE PROPOSED DEVELOPMENT. | | | ZONING 4.28.23 ??? [SATISFIED] | | | | | | 1. PLEASE PROVIDE SEPARATE SHEETS AND SETS FOR: | | | ELEVATION DRAWINGS, SITE PLAN DRAWINGS, LANDSCAPE | | | DRAWINGS, CIVIL, SURVEY, PHOTOMETRICS, ETC. | | | ZONING 4.28.23 ??? [SATISFIED] APPLICABLE DRAWINGS | | | PROVIDED | | | | | | 2. PLEASE PROVIDE SHEETS FOR FACADE ARTICULATION, | | | FENESTRATION, TRANSPARENCY, AND ARCHITECTURAL FEATURES. | | | ZONING 4.28.23 ??? [PARTIALLY SATISFIED] APPLICABLE | | | DRAWINGS PROVIDED; | | | TRANSPARENCY CALCULATIONS APPEAR TO BE MET, PLEASE | | | PROVIDE MARKUP OF FIRST FLOOR ELEVATION THAT DIMENSIONS | | | THE BUILDING FRONTAGE AND FENESTRATION/TRANSPARENCY | | | (PLEASE REFERENCE SEC. 94-109 FIGURE IV-33) ONLY THE | | | ACTIVE USES AND FIRST 10FT. OF HEIGHT FROM SIDEWALK | | | ELEVATION NEEDS TO BE CALCULATED. | | | | | | 3. REQUIRE FULLY DIMENSIONED SITE PLANS WITH TABULAR | | | DATA AND CALCULATIONS SHOWING COMPLIANCE TO BUILDING | | | REQUIREMENTS TABLE FOR NORA-5 DISTRICT. | | | ZONING 4.28.23 ??? [PARTIALLY SATISFIED] TABLES | | | PROVIDED. | | | ACTIVE USE REQUIREMENT IS 65% FOR PROPERTY WITH LESS | | | THAN 250 LINEAR FT. OF FRONTAGE. | | | - N RAILROAD FRONTAGE LENGTH = APPROX. 134 FT. | | | - ACTIVE USE PROVIDED = APPROX. 82 FT. OF BUILDING | | | FRONTAGE | | | - ONLY 61% ACTIVE OF FRONTAGE IS ACTIVE | | | PER SEC. 94-109 ??? ACTIVE USE; ACTIVE USES ARE | | | REGULATED AS A PERCENTAGE OF THE BUILDABLE LOT | | | FRONTAGE. IN THOSE CASES WHERE PUBLIC OPEN SPACE IS | | | PROVIDED ALONG THE FRONTAGE LINE, THE OPEN SPACE MAY BE | | | COUNTED AS ACTIVE USE AS LONG AS ACTIVE USES ARE | | | PROVIDED ON THE FIRST FLOOR OF THE BUILDING ADJOINING | | | THE PUBLIC OPEN SPACE. | | | IN ORDER TO COUNT THE OPEN SPACE AREA INTO ACTIVE USE % | | | IT NEEDS TO BE DESIGNED AS A PUBLIC OPEN SPACE. | | | PER SEC. 94-109 ??? OPEN SPACE, PRIVATE; IF PRIVATE | | | OPEN SPACE IS LOCATED ON THE GROUND FLOOR AND LOCATED | | | ALONG THE LOT FRONTAGE, IT SHALL BE DESIGNED IN | | | COMPLIANCE WITH THE PUBLIC OPEN SPACE REQUIREMENTS, AND | | | IT SHALL BE ACCESSIBLE BY THE PUBLIC FOR PUBLIC USE. | | | PLEASE PROVIDE CLARIFICATION AND IDENTIFY ON SITE PLAN | | | & LP-1 WHAT TYPOLOGY OF PUBLIC OPEN SPACE IS BEING | | | PROVIDED PER SEC. 94-109 TABLE IV-6 AND TABLE IV-7 | | | (I.E. PASSAGEWAY, GARDEN PLAZA, COURTYARD, GARDEN | | | COURTYARD, AND PLAZA); PLEASE BE SURE TO MEET THE | | | STANDARDS OF TABLE IV-7 FOR THE SELECTED | | | CLASSIFICATION. PLEASE REVISE SITE ANALYSIS EXHIBITS | | | SHEET AND LP-1 ACCORDINGLY. | | | 4. PLEASE INDICATE SETBACKS, PROPERTY LINES, AND FULLY | | | DETAIL ANY PROJECTIONS WITHIN SITE PLANS. | | | ZONING 4.28.23 ??? [PARTIALLY SATISFIED] | | | | | | 5. PLEASE CLARIFY HOW OPEN SPACE REQUIREMENTS ARE MET | | | AND PROVIDE CALCULATIONS MEETING STANDARDS PER TABLE | | | IV-7. | | | ZONING 4.28.23 ??? SEE COMMENT #3. | | | LP-1 REFERENCES LANDSCAPE CODE THAT WILL NOT BE | | | APPLICABLE TO THIS SITE/PROJECT. ONLY SEC. 94-113 AND | | | THE OPEN SPACE STANDARDS OF 94-109 (TABLE IV-6 AND | | | TABLE IV-7) SHALL APPLY. | | | | | | NEW COMMENTS 4.28.23 | | | 1. THE 2 BICYCLE PARKING SPACE SHOWN TOWARD THE REAR OF | | | THE PROPERTY (NORTH SIDE NEAR FEC/SERVICE COURT), IS | | | THIS ADDITIONAL BIKE PARKING OR SATISFYING THE REQUIRED | | | (1 SPACE PER 100 LINEAR FEET OF FRONTAGE; PER SEC. | | | 94-113(D.)(9.))? IF IT IS SATISFYING THE REQUIREMENT, | | | THE BIKE RACKS NEED TO BE WITHIN THE FRONT ROW FOR | | | PUBLIC ACCESS. PLEASE PROVIDE BIKE RACK SPEC/DETAILS. | | | | | | 2. PLEASE PROVIDE PROJECTION DETAILS OR DIMENSIONS AND | | | CLEARNACE FOR THE CANOPY ELEMENTS SHOWN ON THE | | | ELEVATIONS. BE SURE THAT THESE ELEMENTS MEET THE | | | STANDARDS IN SEC. 94-109 TABLE IV-5. | | | | | | 3. POTENTIAL CONFLICTS WITH THE PROPOSED LANDSCAPING | | | ALONG THE NORTHERN PERIMETER IN RELATION TO THE FIRE, | | | STORM, AND SANITARY LATERAL LINES? | | | | | | 4. ANY ROOFTOP MECHANICAL EQUIPMENT SHALL BE SCREENED | | | FROM VIEW. PER SEC. 94-109 PROJECTION, VERTICAL: | | | MECHANICAL EQUIPMENT AND APPURTENANCES NECESSARY TO THE | | | OPERATION OR MAINTENANCE OF THE BUILDING OR STRUCTURE | | | ITSELF SUCH AS, BUT NOT LIMITED TO, COOLING TOWERS, | | | ELEVATORS, STAIRS AND MECHANICAL PENTHOUSES, VENT | | | STACKS AND ANTENNAS SHALL BE ENCLOSED AND SCREENED IN | | | SUCH A MANNER THAT THE ENCLOSURE IS DESIGNED AS AN | | | INTEGRAL PART OF THE OVERALL BUILDING DESIGN. | | | | | | CHRIS KIMMERLY, AICP | | | URBAN DESIGN PLANNER | | | 822-1426 [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
10-13-2022 |
|
|
Cont ID |
|
| Sent By |
ckimmerl |
Date |
10-13-2022 |
Time |
12:27 |
Rev Time |
0.00 |
| Received By |
ckimmerl |
Date |
10-13-2022 |
Time |
12:26 |
Sent To |
|
|
| Notes |
| 2022-10-13 12:27:11 | INSUFFICIENT AND INCOMPLETE SUBMITTAL ??? PLEASE NOTE | | | THAT FUTURE SUBMITTALS SUCH AS THIS WILL NOT BE | | | ACCEPTED OR PUT ON FOR PPRC REVIEW. MISSING MANY | | | DRAWINGS AND DETAILS FOR THE PROPOSED DEVELOPMENT. | | | | | | 1. PLEASE PROVIDE SEPARATE SHEETS AND SETS FOR: | | | ELEVATION DRAWINGS, SITE PLAN DRAWINGS, LANDSCAPE | | | DRAWINGS, CIVIL, SURVEY, PHOTOMETRICS, ETC. | | | | | | 2. PLEASE PROVIDE SHEETS FOR FA??ADE ARTICULATION, | | | FENESTRATION, TRANSPARENCY, AND ARCHITECTURAL FEATURES. | | | | | | 3. REQUIRE FULLY DIMENSIONED SITE PLANS WITH TABULAR | | | DATA AND CALCULATIONS SHOWING COMPLIANCE TO BUILDING | | | REQUIREMENTS TABLE FOR NORA-5 DISTRICT. | | | | | | 4. PLEASE INDICATE SETBACKS, PROPERTY LINES, AND FULLY | | | DETAIL ANY PROJECTIONS WITHIN SITE PLANS. | | | | | | 5. PLEASE CLARIFY HOW OPEN SPACE REQUIREMENTS ARE MET | | | AND PROVIDE CALCULATIONS MEETING STANDARDS PER TABLE | | | IV-7. | | | | | | | | | CHRIS KIMMERLY, AICP | | | URBAN DESIGN PLANNER | | | 822-1426 [email protected] |
|
|
| |