Plan Review Details - Project Z22070024
| Plan Review Stops For Project Z22070024 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
05-04-2023 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
05-04-2023 |
Time |
19:42 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
05-04-2023 |
Time |
19:42 |
Sent To |
|
|
| Notes |
| 2023-05-04 19:43:20 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS | | | SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT | | | REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH | | | COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963, | | | OR BY EMAIL: [email protected] | | | | | | 3. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, | | | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR | | | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, | | | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE | | | FLORIDA BUILDING CODE. | | | | | | 4. GREASE INTERCEPTOR. IF ANY OF THE UNITS WILL BE A | | | RESTAURANT A GREASE INTERCEPTOR WILL BE REQUIRED. FOR | | | INFORMATION ON THE REQUIRED TYPE, SIZE AND LOCATION, | | | PLEASE CONTACT RYAN BROWN, CHIEF PLUMBING INSPECTOR, | | | DEVELOPMENT SERVICES DEPARTMENT, AT (561) 805-6692, OR | | | BY EMAIL: [email protected] | | | | | | 5. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, | | | FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, | | | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, | | | SITE IRRIGATION, ETC. | | | | | | 6. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND | | | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF | | | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL | | | NEIGHBORING PROPERTIES. | | | | | | 7. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER | | | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, | | | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE | | | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF | | | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION | | | THAT MAY AFFECT THE USE OF THEIR PROPERTY. | | | | | | 8. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT | | | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL | | | HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION | | | OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING, | | | CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT | | | (561) 805 6659, OR BY EMAIL: [email protected] | | | | | | 9. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT | | | TO ART LIFE ASSESSMENT UNDER THE CITY OF WEST PALM | | | BEACH ART IN PUBLIC PLACES (AIPP) PROGRAM. FOR ADVICE | | | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP | | | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC | | | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
08-11-2022 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
08-11-2022 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
08-11-2022 |
Time |
10:38 |
Sent To |
|
|
| Notes |
| 2022-08-11 10:41:51 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS | | | SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT | | | REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH | | | COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963, | | | OR BY EMAIL: [email protected] | | | | | | 3. UNITY OF TITLE. FOR ANY BUILDING CROSSING A PROPERTY | | | LINE, EITHER A RECORDED UNITY OF TITLE, OR SOME OTHER | | | APPROVED LEGAL INSTRUMENT, SHALL BE INCLUDED WITH THE | | | PERMIT APPLICATION, OR THE BUILDING MUST HAVE A FIRE | | | WALL ALONG THE PROPERTY LINE, PER SECTION 202 OF | | | FLORIDA BUILDING CODE, BUILDING, FIRE SEPARATION | | | DISTANCE. | | | | | | 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, | | | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR | | | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, | | | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE | | | FLORIDA BUILDING CODE. | | | | | | 5. GREASE INTERCEPTOR. IF ANY OF THE UNITS WILL BE A | | | RESTAURANT A GREASE INTERCEPTOR WILL BE REQUIRED. FOR | | | INFORMATION ON THE REQUIRED TYPE, SIZE AND LOCATION, | | | PLEASE CONTACT RYAN BROWN, CHIEF PLUMBING INSPECTOR, | | | DEVELOPMENT SERVICES DEPARTMENT, AT (561) 805-6692, OR | | | BY EMAIL: [email protected] | | | | | | 6. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, | | | FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, | | | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, | | | SITE IRRIGATION, ETC. | | | | | | 7. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND | | | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF | | | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL | | | NEIGHBORING PROPERTIES. | | | | | | 8. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER | | | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, | | | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE | | | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF | | | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION | | | THAT MAY AFFECT THE USE OF THEIR PROPERTY. | | | | | | 9. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT | | | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL | | | HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION | | | OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING, | | | CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT | | | (561) 805 6659, OR BY EMAIL: [email protected] | | | | | | 10. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT | | | TO ART LIFE ASSESSMENT UNDER THE CITY OF WEST PALM | | | BEACH ART IN PUBLIC PLACES (AIPP) PROGRAM. FOR ADVICE | | | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP | | | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC | | | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
3 |
Status |
F |
Date |
07-27-2023 |
|
|
Cont ID |
|
| Sent By |
lquinone |
Date |
07-27-2023 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
lquinone |
Date |
07-27-2023 |
Time |
13:24 |
Sent To |
|
|
| Notes |
| 2023-07-27 13:24:55 | PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND | | | STORMWATER PIPES ALONG ENTIRE PROJECT FRONTAGE. |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
F |
Date |
04-11-2023 |
|
|
Cont ID |
|
| Sent By |
lquinone |
Date |
04-11-2023 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
lquinone |
Date |
04-11-2023 |
Time |
10:29 |
Sent To |
|
|
| Notes |
| 2023-04-11 10:30:17 | NO RESPONSE LETTER WAS SUBMITTED. | | | | | | COMMENTS FROM LINDA M. QUINONES-CINTRON, PROJECT | | | COORDINATOR, ENGINEERING SERVICES AT 561-494-1085 | | | [email protected] | | | | | | CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY SEWER | | | ARE REQUIRED. | | | | | | PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND | | | STORMWATER PIPES ALONG ENTIRE PROJECT FRONTAGE. | | | | | | COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE | | | SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING | | | PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT | | | HIM AT 561-494-2262 OR [email protected] | | | | | | FOR FORMAL ENGINEERING SUBMITTAL , PLANS SHALL SHOW | | | PROPOSED LOCATIONS AND DIMENSIONS OF ALL WATER, | | | STORMWATER, AND SANITARY AND SEWER LINES, INCLUDING | | | STUBS TO EACH PROPERTY LINE FOR WATER AND SANITARY | | | SEWERS, THE MAKE AND MODEL OF ALL VALVES, METERS, AND | | | OTHERS DEVICES TO BE INSTALLED ON THE SYSTEM, CATCH | | | BASINS, CULVERTS, DITCHES INCLUDING GRADES, PIPES | | | SIZES, MATERIALS, ELEVATIONS, ASSUMPTIONS, | | | CALCULATIONS, INVERT ELEVATIONS FOR ALL INLETS AND | | | MANHOLES AND PROFILES OF SANITARY SEWER LINES. ALL | | | AVAILABLE ELEVATION SHALL BE SHOWN ON THE PROFILE VIEW. | | | DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN | | | VIEW FOR ALL SANITARY AND STORM SEWERS. ADDITIONALLY, | | | PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED | | | UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC, | | | ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION | | | FACILITIES LOCATED ON THE RIGHT-OF-WAY. PROVIDE PROFILE | | | AND CLEARANCES AT ALL UTILITY CROSSINGS. | | | | | | PLEASE CLOUD/HIGHLIGHT PLAN REVISIONS OR CHANGES IN | | | SCOPE FOR RESUBMITTAL OF DRAWINGS. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL , CUT AND CAP | | | UTILITIES NOT IN USE, AND REMOVE ANY ABANDONED UTILITY | | | LINES LARGER THAN 2 INCHES FROM CITY RIGHT OF WAY. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE DEDICATED | | | UTILITY EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO | | | PROPOSED UTILITY WATER METERS. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | ENLARGED VIEW ON PLANS OF PROPOSED LOCATION OF WATER | | | METER AND BACKFLOW PREVENTION. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, PLEASE CALLOUT | | | DOMESTIC BACKFLOW PREVENTER AS RPPA AND FIRE BACKFLOW | | | PREVENTER AS DCDA. SPECIFY LEAD FREE DESIGN ON ALL | | | BACKFLOWS. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES | | | NOI REQUIREMENTS WILL BE ENFORCED. | | | | | | -AN NOI IS REQUIRED FOR PROJECTS THAT: | | | 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS | | | THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF | | | DEVELOPMENT OR SALE; AND | | | 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE | | | STATE OR TO SURFACE WATERS OF THE STATE THROUGH A | | | MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4). | | | -THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF | | | CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION | | | THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL | | | SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT | | | OF THE 10-2 CERTIFICATION. IF THE ENGINEERING PLANS DO | | | NOT INCLUDE AN EROSION CONTROL PLAN, THEN THE | | | CONTRACTOR SHOULD SUBMIT ONE PRIOR TO RECEIVING THE | | | ENGINEERING PERMIT. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF | | | PROPOSED AND EXISTING WATER AND SEWER WITHIN RIGHT OF | | | WAY AND SHOW ANY CROSSINGS/CONFLICTS. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING | | | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT | | | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING | | | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED | | | LEAD-FREE DESIGN. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL CLEARLY SHOW ROAD | | | RIGHT OF WAY. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL PROVIDE SANITARY | | | ELEVATIONS AT MANHOLE TIE-IN. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES | | | ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY | | | LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT | | | PARCELS. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, IF WATER LINES ARE | | | BEING REPLACED IN ROW, SHOW ADJACENT PARCEL ADDRESSES. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, WHEN TRENCHING IN IN | | | CITY MAINTAINED ROADWAY AREAS ADD NOTE TO PROVIDE 50 | | | FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF | | | PROPOSED TRENCH PER CURRENT CITY OF WPB STANDARD DETAIL | | | GC-8. | | | | | | PLEASE RESPOND TO ALL COMMENTS IN WRITING AND INCLUDE | | | PROJECT NAME, ADDRESS AND PERMIT NUMBER (Z-XXXXXXXX). | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
07-27-2022 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
07-27-2022 |
Time |
|
Rev Time |
|
| Received By |
rrossano |
Date |
07-27-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-07-27 10:44:03 | Z22070024 - 444 10TH ST, MIXED USE 7.26.22 SUB | | | COMMENTS FROM RICK ROSSANO, SR. PROJECT COORDINATOR, | | | ENGINEERING SERVICES AT 561-494-1098 [email protected] | | | GENERAL: | | | O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND | | | INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER | | | (Z-XXXXXXXX). | | | O THE CITY OF WEST PALM BEACH HAS A NUMBER OF | | | REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY | | | AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND | | | WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE | | | DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK | | | BELOW: | | | A. HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WP | | | B_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FUL | | | L-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97 | | | B1960045731D3658206F27451722716EF | | | B. THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE | | | FOUND HERE: | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | C. ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM | | | BEACH, FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, | | | ADOPTED SEPT. 22, 2008. (SUPPLEMENT NO. 18) | | | CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL, | | | SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER | | | SERVICE FACILITIES OF THE CITY. | | | THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE | | | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY | | | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, | | | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. | | | O AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR | | | MORE INFORMATION, REFER TO THE LINK BELOW: | | | A. HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PU | | | BLICATIONS/BACKFLOW-CROSS-CONNECTION- CONTROL-MANUAL | | | O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY | | | OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC | | | RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF | | | YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE | | | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL | | | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT | | | [email protected] OR 561-494-1079 FOR FURTHER | | | ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION | | | ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD | | | SURVEY, POT-HOLING, SOFT DIGS ETC. | | | O PROVIDE EXISTING AND PROPOSED PERVIOUS AND IMPERVIOUS | | | DATA. | | | | | | BACKFLOW ASSEMBLY AND METERS: | | | O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER | | | SERVICES AND WATER METERS, ALONG WITH WHAT IS HAPPENING | | | TO THEM. | | | O SHOW EXISTING AND PROPOSED DEDICATED UTILITY | | | EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO | | | PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO | | | STRUCTURES WITHIN EASEMENT. | | | O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION | | | OF WATER METER AND BACKFLOW | | | PREVENTION. | | | O BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY | | | OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER | | | METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO | | | PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE | | | INSTALLED ABOVE-GROUND ONLY. | | | O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE | | | NOTE USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA. | | | | | | WATER/WASTEWATER PLAN: | | | O PROVIDE VERTICAL DATUM AND DATUM CONVERSION | | | INFORMATION (NAVD 1988 AND NGVD 1929). | | | O SHOW PROJECT ADDRESS ON ALL PLAN SHEETS. | | | O PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE | | | STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC. | | | O PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND | | | DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND | | | SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH | | | PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE | | | AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS, | | | BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO | | | BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS, | | | DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS, | | | ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT | | | ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF | | | SANITARY SEWER LINES. | | | O GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR | | | SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE | | | PROFILE VIEW. | | | O DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN | | | VIEW FOR ALL SANITARY AND STORM SEWERS. | | | O SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT | | | MATERIAL. | | | O PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED | | | UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC, | | | ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION | | | FACILITIES LOCATED ON THE RIGHT-OF-WAY. | | | O PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER | | | AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD | | | DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS. | | | O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY | | | TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT | | | APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING | | | AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, | | | MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS | | | SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 | | | FOR WATER. | | | O PROVIDE FIRE FLOW TEST DATA. | | | O PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND | | | STORMWATER INFRASTRUCTURE ALONG ENTIRE PROJECT FRONTAGE | | | (CONDITION OF SITE PLAN APPROVAL). | | | O CUT AND CAP UTILITIES NOT IN USE AND REMOVE ANY | | | ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY | | | ROW. | | | O WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL | | | BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY | | | PROPOSED LENGTH IN FEET. | | | O CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY | | | SEWER ARE REQUIRED. | | | O PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE | | | JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET. | | | O ADD NOTE TO PLANS SPECIFYING CITY?S DOWNSTREAM LIFT | | | STATION NUMBER. | | | O PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR | | | PROPOSED SANITARY LATERALS. | | | O LABEL WATER LINES AS PRIVATE WHERE APPLICABLE. | | | O PLEASE SHOW AND LABEL EXISTING AND PROPOSED GREASE | | | TRAPS (IF ANY). | | | O PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN | | | OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER. | | | | | | FORMAL ENGINEERING REVIEW: | | | O FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES | | | NOI REQUIREMENTS WILL BE ENFORCED. | | | - AN NOI IS REQUIRED FOR PROJECTS THAT: | | | - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS | | | THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF | | | DEVELOPMENT OR SALE; | | | - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE | | | STATE OR TO SURFACE WATERS OF THE STATE THROUGH A | | | MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4). | | | - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF | | | CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION | | | THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL | | | SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT | | | OF THE 10-2 CERTIFICATION. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF | | | WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING | | | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT | | | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING | | | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED | | | LEAD-FREE DESIGN. | | | O FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES | | | ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY | | | LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT | | | PARCELS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, IF WATER LINES ARE | | | BEING REPLACED IN ROW, SHOW ADJACENT PARCEL ADDRESSES. | | | O FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO PROVIDE | | | 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF | | | PROPOSED TRENCH IN CITY MAINTAINED ROADWAY AREAS PER | | | CITY OF WPB STANDARD DETAIL GC-8. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | CALCULATIONS OF PERVIOUS AND IMPERVIOUS AREAS FOR | | | PROPOSED IMPROVED AREAS. | | | | | | | | | | | | QUESTIONS AND COORDINATION CONTACTS: | | | O MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR WITH | | | CITY OF WPB PUBLIC UTILITIES, REGARDING PLACEMENT OF | | | BACKFLOW DEVICES AND WATER METERS. CONTACT HIM AT | | | 561-822-2262 OR [email protected] | | | O MIKE TECHNOW, PROJECT ENGINEER, PUBLIC UTILITIES | | | DEPARTMENT AT 561-494-1047 OR [email protected] | | | O TRACY WARD, SR. STORMWATER ENGINEER, ENGINEERING | | | SERVICES DEPT. AT 561-494-1120 OR [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
08-01-2022 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
08-01-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
08-01-2022 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2022-08-01 12:05:43 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE DEPARTMENT. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. THE FOLLOWING COMMENTS ARE INTENDED | | | TO PROVIDE GUIDANCE FOR BUILDING PLAN SUBMITTAL. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING(S) SHALL COMPLY | | | WITH THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION | | | CODE, INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE | | | CODES. | | | | | | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE | | | OCCUPANCY TYPE PER THE FLORIDA FIRE PREVENTION CODE. | | | | | | 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE | | | LOAD CALCULATION IS INCLUDED, AND THAT ADEQUATE WATER | | | SUPPLY IS EXISTING OR WILL BE PROVIDED. | | | | | | 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | THE PROPOSED LOCATION OF THE FIRE HYDRANT AND FDC SHALL | | | BE WITHIN 100' OF EACH OTHER AND CLOSELY COORDINATED | | | WITH THE BUREAU OF FIRE PREVENTION. | | | | | | 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER | | | THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY | | | ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM, | | | ENSURE THEY COMPLY WITH THE REQUIREMENTS OF F.A.C. 61G | | | AND SUBMITTED WITH THE MASTER PERMIT. | | | | | | 9A. THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE | | | LOCATIONS SHALL MEET AND BE INSTALLED PER THE | | | REQUIREMENTS OF NFPA 24 AND SHALL BE COORDINATED WITH | | | THE OFFICE OF FIRE MARSHAL, THE CITY'S ENGINEERS | | | OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S PLANNING | | | AND ZONING OFFICE. | | | | | | 10. COMPLETE LIFE SAFETY PLANS FOR THE OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, EXIT SEPARATION DISTANCES, COMMON PATHS OF | | | TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, EMERGENCY | | | LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE | | | EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES | | | AND EQUIPMENT. | | | | | | 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE | | | SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY | | | DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS. | | | | | | 12. ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE | | | FIGHTER?S EMERGENCY OPERATIONS REQUIREMENTS OF ASME | | | A17.1/CSA B44, SAFETY CODE FOR ELEVATORS. | | | | | | ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN | | | WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL | | | LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET | | | MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER | | | ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN | | | AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE | | | IN THE HORIZONTAL POSITION. | | | | | | 13. TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEMS. | | | | | | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY | | | RADIO ENHANCEMENT SERVICES. | | | 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM | | | RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT | | | COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL | | | DETERMINED BY THE AHJ. | | | | | | IF APPLICABLE, CONTACT WILL NEED TO BE MADE TO MARK | | | FILLA, PALM BEACH COUNTY PUBLIC SAFETY RADIO SYSTEMS | | | MANAGER, [email protected], 561-233-0837; AS OUR RADIOS | | | OPERATE ON THEIR SYSTEM FOR DETAILED RADIO FREQUENCY | | | AND INSTALLATION INSTRUCTIONS. | | | | | | 14. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL. | | | | | | 15. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
08-10-2022 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
08-10-2022 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
08-10-2022 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2022-08-10 14:14:33 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: 444 10TH ST NORA Z22070024 | | | AUGUST 10, 2022 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. PROVIDE A TREE SURVEY AND TREE DISPOSITION PLAN TO | | | IDENTIFY ALL EXISTING TREES AND PALMS. IDENTIFY | | | EXISTING TREES IN THE RIGHT OF WAY. IF ON THE ADJACENT | | | PROPERTY, SHOW THEM ON THE LANDSCAPE PLAN PER SECTION | | | 94-442(B)(2)Q. | | | | | | 2. LIST ANY VARIANCES REQUESTED FOR LANDSCAPING ON THE | | | LANDSCAPE PLAN. | | | | | | 3. PER SECTION 94-443 (A)(1) A PROTECTIVE SCREEN WALL | | | IS REQUIRED ALONG THE ADJACENT RESIDENTIAL PROPERTY | | | LINE. | | | | | | 4. STREETSCAPE MUST BE PROVIDED ADJACENT TO THE | | | PROPERTY INCLUDING SIDEWALKS AND STREET TREES FOR 10TH | | | ST. | | | | | | 5. SHOW LOCATIONS OF ALL UTILITIES ON THE LANDSCAPE | | | PLAN, AS THERE ARE MULTIPLE CONFLICTS WITH REQUIRED | | | LANDSCAPING. | | | | | | 6. TREE IN THE TERMINAL ISLAND AT THE END OF THE ROW OF | | | PARKING CANNOT BE DOUBLE COUNTED TOWARD BUFFER | | | REQUIREMENT. | | | | | | 7. PER SECTION 94-443 (E)2., PROVIDE THE 30% FOUNDATION | | | PLANTING CALCULATION REQUIRED AND PROVIDED FOR THE | | | BUILDING. | | | | | | 8. PROVIDE A SECTION IN A LANDSCAPE DATA CHART TO | | | COMPLY WITH SECTION 94-445 L. PLANT SPECIES. A MINIMUM | | | OF 60 PERCENT OF PLANT MATERIAL ADDED SHALL BE FLORIDA | | | NATIVE OR DROUGHT TOLERANT SPECIES SELECTED FROM THE | | | CITY LIST OR THE LIST OF SPECIES IN THE MOST RECENT | | | EDITION OF SOUTH FLORIDA WATER MANAGEMENT DISTRICT | | | WATERWISE SOUTH FLORIDA LANDSCAPES. PROVIDE THE TOTAL | | | PERCENTAGE OF NATIVE AND DROUGHT TOLERANT PLANTS BASED | | | ON FINAL PLANT LIST. | | | | | | 9. CASSIA NEEDS TO BE SHOWN AT 12 FT HEIGHT | | | SPECIFICATION ON THE PLAN. ANY SUPPLY ISSUES MAY BE | | | ADDRESSED AT TIME OF INSTALLATION. | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE | | | STREET TREES AND RIGHT OF WAY LANDSCAPING AND | | | IRRIGATION APPROVED WITH THIS PETITION. | | | 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF | | | WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A | | | SEPARATE MAINTENANCE AGREEMENT WITH THE CITY. | | | | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
1 |
Status |
P |
Date |
08-12-2022 |
|
|
Cont ID |
|
| Sent By |
mtechnow |
Date |
08-12-2022 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
mtechnow |
Date |
08-12-2022 |
Time |
11:42 |
Sent To |
|
|
| Notes |
| 2022-08-12 12:00:36 | CONCEPTUAL REVIEW PASSED. PLEASE REFER TO CHECKLIST | | | PROVIDED BY RICK ROSSANO FOR ENGINEERING SUBMITTAL | | | GUIDELINES. |
|
|
| Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
| Rev No |
3 |
Status |
F |
Date |
07-14-2023 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
07-14-2023 |
Time |
13:11 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2023-07-14 13:11:29 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | | | | -THE LOCATION CONFLICT BETWEEN BIKE RACK AND FIRE | | | HYDRANT BROUGHT UP DURING PREVIOUS SUBMITTAL IS STILL | | | SHOWING ON THE VARIOUS PLAN SETS. PLEASE RESOLVE SUCH | | | THAT BIKE RACK IS NOT IN FIRE HYDRANT CLEAR ZONE. ALSO | | | BE AWARE OF THE NEARBY FDC AND ENSURE FIX WILL BE | | | UPDATED ON E22030048 PLANS. | | | | | | RESPECTFULLY, | | | MARK HURLEY [email protected] |
|
|
| Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
| Rev No |
2 |
Status |
F |
Date |
04-13-2023 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
04-13-2023 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2023-04-13 10:27:46 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | -BIKE RACK APPEARS TO BE ENCROACHING ON FIRE HYDRANT | | | CLEAR OBSTRUCTION AREA ON VARIOUS PLAN SETS. PLEASE | | | UPDATE. | | | -WATER METER SIZE AND LOCATION AS WELL AS BACKFLOW | | | ASSEMBLY LOCATIONS MAY BE CHANGING BASED ON REVISIONS | | | IN E22030048. VERIFY AND UPDATE PLANS AS NEEDED. | | | -SITE PLAN LOCATIONS OF WATER METERS AND BACKFLOW | | | ASSEMBLIES NEED TO BE UPDATE TO REFLECT UPDATED CIVIL | | | ENGINEERING PLAN LOCATIONS. | | | RESPECTFULLY, | | | MARK HURLEY [email protected] |
|
|
| Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
| Rev No |
1 |
Status |
F |
Date |
08-10-2022 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
08-10-2022 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-10 13:54:32 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | -JUSTIFICATION LETTER SAYS 444 N RAILROAD. WILL THE | | | CURRENT ADDRESS BE CHANGING? | | | -SITE PLAN SHOWS DOOR OPENING UP INTO SIDEWALK AND | | | RAILROAD AVE RIGHT OF WAY. | | | -CLEARLY SHOW AND LABEL EXISTING AND PROPOSED FIRE | | | HYDRANTS ON PLANS. ENSURE THAT MINIMUM FIRE HYDRANT | | | CLEARANCE DISTANCES ARE MET. | | | -CLEARLY LABEL PROPERTY LINES ON PLANS. | | | -SHOW UTILITIES ON LANDSCAPE PLAN AND ENSURE NO | | | CONFLICTS BETWEEN TREES AND UTILITIES. | | | -FOOTPRINT OF 3 INCH METER AND BACKFLOW WOULD LIKELY BE | | | MUCH LARGER THAN SHOWN. | | | -ADD WORDING ABOVE GROUND TO LABEL OF PROPOSED 3 INCH | | | METER. | | | -ENSURE FDC IS AN ACCEPTABLE DISTANCE FROM CITY FIRE | | | HYDRANT. | | | -SURVEY SHOWS UTILITY POLE AND GUY WIRES NEAR SOUTH | | | PROPERTY LINE. SHOW AND LABEL THOSE ON PLANS. | | | -WHAT TYPE OF SIGN IS ACROSS THE ALLEY FROM THE GREASE | | | TRAPS? | | | -ADD FIRELINE BACKFLOW AND ABOVE-GROUND WATER METER | | | STANDARD DETAILS TO ENGINEERING PLAN SET. | | | -VERIFY PROPERTY IS NOT CURRENTLY OWNED BY THIRD | | | PARTIES NOT RELATED TO THE PROJECT. | | | RESPECTFULLY, | | | MARK HURLEY | | | [email protected] |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
2 |
Status |
F |
Date |
04-28-2023 |
|
|
Cont ID |
|
| Sent By |
|
Date |
04-28-2023 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
04-28-2023 |
Time |
|
Sent To |
|
|
| Notes |
| 2023-05-03 16:08:39 | | | | PLEASE PROVIDE THE FOLLOWINGS: | | | 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID | | | WASTE VOLUME PRODUCED ALONG WITH THE SIZE, TYPE AND | | | QUANTITY OF THE CONTAINER (I.E. DUMPSTER/COMPACTOR) | | | THAT WILL BE UTILIZED FOR THE SANITATION SERVICE. | | | 2- DETAILS FOR SANITATION SERVICE (I.E. SOLID WASTE | | | CONTAINER(S) TYPE, COLLECTION LOCATION, ETC.). FOR A | | | FREESTANDING SITE DUMPSTER ENCLOSURE, THE ENCLOSURE | | | SHALL COMPLY WITH THE LATEST REVISION OF CITY OF WEST | | | PALM BEACH GENERAL CONSTRUCTION-GARBAGE ENCLOSURE | | | STANDARD, GC-7. (LINK TO THE LATEST REVISION OF THE | | | GC-7 DOCUMENT: HTTPS://WWW.WPB.ORG/HOME/SHOWPUBLISHEDDO | | | CUMENT/3690/637629060422100000) | | | 3- AUTOTURN EXHIBIT (DYNAMIC ENVELOPE AND THE VEHICLE?S | | | WHEEL PATH) FOR THE SANITATION SERVICE, FRONT LOADER | | | TRUCK WITH THE FOLLOWING SPECS: | | | - DUAL AXLES | | | - TRUCK LENGTH: 35 FT | | | - TRUCK WIDTH: 11 FT | | | - TURNING RADIUS: | | | - SAE TURNING RADIUS: 32.5 FT | | | - CURB-TO-CURB DIAMETER: 74 FT | | | - WALL-TO-WALL DIAMETER: 86.3 FT | | | | | | | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] | | | 561-822-2045 | | | |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
F |
Date |
08-09-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
08-09-2022 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
08-09-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-09 11:59:25 | | | | PLEASE PROVIDE THE FOLLOWINGS: | | | 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID | | | WASTE VOLUME PRODUCED ALONG WITH THE SIZE, TYPE AND | | | QUANTITY OF THE CONTAINER (I.E. DUMPSTER/COMPACTOR) | | | THAT WILL BE UTILIZED FOR THE SANITATION SERVICE. | | | 2- DETAILS FOR SANITATION SERVICE (I.E. SOLID WASTE | | | CONTAINER(S) TYPE, COLLECTION LOCATION, ETC.). FOR A | | | FREESTANDING SITE DUMPSTER ENCLOSURE, THE ENCLOSURE | | | SHALL COMPLY WITH THE LATEST REVISION OF CITY OF WEST | | | PALM BEACH GENERAL CONSTRUCTION-GARBAGE ENCLOSURE | | | STANDARD, GC-7. (LINK TO THE LATEST REVISION OF THE | | | GC-7 DOCUMENT: HTTPS://WWW.WPB.ORG/HOME/SHOWPUBLISHEDDO | | | CUMENT/3690/637629060422100000) | | | 3- AUTOTURN EXHIBIT (DYNAMIC ENVELOPE AND THE VEHICLE?S | | | WHEEL PATH) FOR THE SANITATION SERVICE, FRONT LOADER | | | TRUCK WITH THE FOLLOWING SPECS: | | | - DUAL AXLES | | | - TRUCK LENGTH: 35 FT | | | - TRUCK WIDTH: 11 FT | | | - TURNING RADIUS: | | | - SAE TURNING RADIUS: 32.5 FT | | | - CURB-TO-CURB DIAMETER: 74 FT | | | - WALL-TO-WALL DIAMETER: 86.3 FT | | | 4- OWNERS AND/OR OCCUPANTS OF PROPERTY THAT REQUIRE | | | GREASE HAULING SERVICES SHALL ENSURE THAT THEIR GREASE | | | TANKS OR CONTAINERS REMAIN CLEAN, AND ARE ENCLOSED AND | | | NOT IN PUBLIC VIEW. | | | 6- IN CASE OF PROPOSING ADDITION OF ANY NEW CAN(S) IN | | | THE CITY`S RIGHT-OF-WAY , THE LOCATION AND QUANTITY OF | | | THE CAN(S) SHALL BE REVIEWED AND APPROVED BY PUBLIC | | | WORKS DEPARTMENT AND THE CAN(S) SHALL BE TYPE, SIZE AND | | | COLOR APPROVED BY PUBLIC WORKS DEPARTMENT. THE BUILDING | | | MAINTENANCE IS RESPONSIBLE TO MAINTAIN AND SERVICE THE | | | CAN(S). | | | 7- ALL THE PARKING STALL PAINTING SHALL COMPLY WITH THE | | | CITY`S MUNICIPAL CODE SECTION 94-485 AND FLORIDA | | | STATUES [553.5041 F.S.]. | | | 8- ALL STRIPING AND SIGNAGE SHALL MEET THE M.U.T.C.D. | | | LATEST EDITION. | | | 9- ALL PAVEMENT MARKING , SIGNING AND SIDEWALK DAMAGED | | | DURING CONSTRUCTION SHALL BE RESTORED. | | | | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] | | | 561-822-2045 | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
F |
Date |
05-07-2023 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
05-07-2023 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
05-07-2023 |
Time |
15:48 |
Sent To |
|
|
| Notes |
| 2023-05-07 15:47:08 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE | | | 3/28/2023 SUBMITTAL: | | | | | | 1. [NOT SATISFIED - DESPITE WHAT THE RESPONSE LETTER | | | STATED, A REVISED SURVEY WAS NOT SUBMITTED.] THE CITY'S | | | OFFICIAL VERTICAL DATUM IS NGVD1929. THE CITY HAS | | | ALLOWED THE USE OF NAVD1988 AS LONG AS THE CONVERSION | | | EQUATION TO NGVD1929 AT THE PROJECT LOCATION IS | | | PROVIDED. PROVIDE THE VERTICAL DATUM CONVERSION TO | | | NGVD1929 ON THE SURVEY. | | | | | | 2.[NOT SATISFIED - DESPITE WHAT THE RESPONSE LETTER | | | STATED, NO CROSS SECTIONS WERE PROVIDED ON THE UPDATED | | | CIVIL ENGINEERING PLAN.] PROVIDE CROSS SECTIONS FROM | | | CENTERLINE OF RIGHTS OF WAY AND WEST PROPERTY LINE TO | | | THE BUILDING FACES. SHOW AND LABEL SURFACE FEATURES, | | | GRADE BREAKS, GENERAL SURFACE SLOPES, FINISHED FLOOR | | | ELEVATION, RIGHT OF WAY LINES WITH THE STREET | | | IDENTIFIED, DIMENSIONS FROM RIGHT OF WAY TO SURFACE | | | FEATURES. NOTE THERE IS OVER A FOOT DIFFERENCE BETWEEN | | | THE PROPOSED FFE AND THE EXISTING GRADES ON 10TH ST. | | | | | | 3. [PARTIALLY SATISFIED - TREES PROPOSED OVER SANITARY | | | SEWER LATERAL AND STAFF SUGGESTS INSTALLING ROOT | | | BARRIERS TO PROTECT THE STORM PIPES FROM OTHER PROPOSED | | | TREES.] SHOW UTILITIES ON THE LANDSCAPE PLANS AND | | | COORDINATE PLANTINGS WITH THE UTILITIES. | | | | | | 4. [SATISFIED - DESPITE THAT THE RESPONSE LETTER STATED | | | THAT THE PARKING SPACES WERE REDUCED IN LENGTH TO | | | INCLUDE OVERHANG OF THE RAISED CURB AND HARDSCAPE | | | AREAS, THE PARKING SPACES ARE DIMENSIONED TO BE 18 FEET | | | DEEP TO THE FACE OF CURB.] CONSIDER REDUCING THE | | | PARKING SPACE DEPTHS FROM 18.5 FEET TO 18 FEET | | | (INCLUDING THE 2 FEET OF OVERHANG). | | | | | | 5. [SATISFIED] SOUTH DRIVEWAY ENCROACHING ONTO ADJACENT | | | PROPERTY. | | | | | | 6. [NOT SATISFIED - NO HATCHING SHOWN TO SHOW CONCRETE | | | MATERIAL.] DRIVEWAY APRON WITHIN THE RIGHT OF WAY | | | SHOULD BE CONCRETE. | | | | | | 7. [NOT SATISFIED - CURBING TYPE NOT CALLED OUT ON THE | | | ENGINEERING PLAN.] INSTALL TYPE F CURB AND GUTTER ALONG | | | THE FRONTAGE OF 10TH STREET. | | | | | | 8. [SATISFIED] REMOVE CONCRETE WALKWAY BETWEEN CURB AND | | | SIDEWALK ON 10TH STREET. | | | | | | 9. [NOT SATISFIED] LABEL PROPOSED SIDEWALKS, CURB | | | TYPES, ETC. ON- AND OFF-SITE THAT WILL INCLUDED WITH | | | THIS PROJECT. | | | | | | 10. [PARTIALLY SATISFIED - INCLUDE HATCH PATTERNS OF | | | LANDSCAPE AREAS AND OF THE AREAS ADJACENT TO THE NORTH | | | AND EAST SIDES OF THE BUILDING] ON ENGINEERING PLANS, | | | INCLUDE ALL HATCHING PATTERNS IN THE SHEET LEGEND. THE | | | LEGEND INCLUDES PROPOSED TRUEGRID. IDENTIFY WHERE THIS | | | WILL BE INSTALLED AND PROVIDE DETAILS FOR IT. | | | | | | 11. [SATISFIED] STOP BAR AND SIGN WILL BE NEEDED. | | | | | | 12. [NOT SATISFIED] PROVIDE EXISTING SPOT GRADES FOR | | | THE ALLEY. | | | | | | NEW COMMENTS (3/28.2023 UBMITTAL): | | | | | | 13. EXPLAIN FLARE LINE ON THE EAST SIDE OF THE SOUTH | | | DRIVEWAY TO THE PROPOSED SPOT GRADE 14.70 FT NAVD. | | | | | | 14. ADJUST SPOT GRADE LEADERS TO WHERE THE GRADES ARE | | | TO BE SHOWN. FOR EXAMPLE, THERE IS A PROPOSED SPOT | | | GRADE THE SAME AS THE GRATE ELEVATION OF S-205 BUT | | | POINTING TO THE PAVEMENT 2 FEET EAST OF THE STRUCTURE. | | | ANOTHER EXAMPLE, THERE IS A PROPOSED SPOT GRADE OF | | | 16.20 FT NAVD POINTING TO THE SOUTH WALL OF THE | | | BUILDING. OTHER PROPOSED SPOT GRADES IN THE PARKING | | | SPACES ARE SHOWN 1.5 FEET FROM THE CURB. | | | | | | 15. WHEEL STOPS WILL BE NEEDED IN THE PARKING SPACES TO | | | PREVENT VEHICLES FROM PARKING OVER THE SIDEWALK. | | | | | | 16. EXTEND THE HANDICAP PARKING ACCESS AISLE STRIPING | | | ALL THE WAY TO THE END OF THE ACCESS AISLE. FBC SECTION | | | 502.4 PROHIBITS CURB RAMPS WITHIN THE HANDICAP PARKING | | | ACCESS AISLE. | | | | | | 17. COORDINATE THE OUTFALL PIPE FROM STRUCTURE S-201 | | | WITH THE NORTH RAILROAD STREETSCAPE PLANS, INCLUDING | | | THE LOCATION OF THE PIPE OPENING AT THE EXISTING | | | STRUCTURE S-101 THAT THE OUTFALL PIPE CONNECTS TO. | | | | | | 18. COORDINATE LOCATIONS OF OTHER OFFSITE UTILITIES | | | WITH THE NORTH RAILROAD STREETSCAPE PLANS. | | | | | | 19. PROVIDE SAFE SEPARATION BETWEEN STOP BAR AND BACK | | | OF SIDEWALK. | | | | | | 20. PAVEMENT HATCHING FOR SOUTH DRIVEWAY APPEARS TO | | | HIDE CURBING ALONG THE DRIVEWAY FLARES. | | | | | | 21. ENGINEERING PLAN DOES NOT MATCH THE SITE PLAN WITH | | | REGARDS TO THE RECESSED DOOR OPENINGS. | | | | | | 22. PROVIDE DETAIL OF THE CONTROL STRUCTURE. NOTE THE | | | CITY DOES NOT ALLOW THE USE OF BLEEDERS WITH | | | EXFILTRATION TRENCH SYSTEMS. | | | | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | [email protected] | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
08-11-2022 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
08-11-2022 |
Time |
06:53 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
08-11-2022 |
Time |
06:53 |
Sent To |
|
|
| Notes |
| 2022-08-11 06:53:32 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | 1. THE CITY?S OFFICIAL VERTICAL DATUM IS NGVD1929. THE | | | CITY HAS ALLOWED THE USE OF NAVD1988 AS LONG AS THE | | | CONVERSION EQUATION TO NGVD1929 AT THE PROJECT LOCATION | | | IS PROVIDED. PROVIDE THE VERTICAL DATUM CONVERSION TO | | | NGVD1929 ON THE SURVEY. | | | | | | 2. PROVIDE CROSS SECTIONS FROM CENTERLINE OF RIGHTS OF | | | WAY AND WEST PROPERTY LINE TO THE BUILDING FACES. SHOW | | | AND LABEL SURFACE FEATURES, GRADE BREAKS, GENERAL | | | SURFACE SLOPES, FINISHED FLOOR ELEVATION, RIGHT OF WAY | | | LINES WITH THE STREET IDENTIFIED, DIMENSIONS FROM RIGHT | | | OF WAY TO SURFACE FEATURES. NOTE THERE IS OVER A FOOT | | | DIFFERENCE BETWEEN THE PROPOSED FFE AND THE EXISTING | | | GRADES ON 10TH ST. | | | | | | 3. SHOW UTILITIES ON THE LANDSCAPE PLANS AND COORDINATE | | | PLANTINGS WITH THE UTILITIES. | | | | | | 4. CONSIDER REDUCING THE PARKING SPACE DEPTHS FROM 18.5 | | | FEET TO 18 FEET (INCLUDING THE 2 FEET OF OVERHANG). | | | | | | 5. SOUTH DRIVEWAY ENCROACHING ONTO ADJACENT PROPERTY. | | | | | | 6. DRIVEWAY APRON WITHIN THE RIGHT OF WAY SHOULD BE | | | CONCRETE. | | | | | | 7. INSTALL TYPE F CURB AND GUTTER ALONG THE FRONTAGE OF | | | 10TH STREET. | | | | | | 8. REMOVE CONCRETE WALKWAY BETWEEN CURB AND SIDEWALK ON | | | 10TH STREET. | | | | | | 9. LABEL PROPOSED SIDEWALKS, CURB TYPES, ETC. ON- AND | | | OFF-SITE THAT WILL INCLUDED WITH THIS PROJECT. | | | | | | 10. ON ENGINEERING PLANS, INCLUDE ALL HATCHING PATTERNS | | | IN THE SHEET LEGEND. THE LEGEND INCLUDES PROPOSED | | | TRUEGRID. IDENTIFY WHERE THIS WILL BE INSTALLED AND | | | PROVIDE DETAILS FOR IT. | | | | | | 11. STOP BAR AND SIGN WILL BE NEEDED. | | | | | | 12. PROVIDE EXISTING SPOT GRADES FOR THE ALLEY. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP | | | CRITERIA. STORMWATER CALCULATIONS WILL BE REVIEWED WITH | | | THE ENGINEERING PERMIT SUBMITTAL. | | | | | | 2. PROVIDE COPY OF SFWMD ERP PERMIT MODIFICATION BEFORE | | | START OF CONSTRUCTION. | | | | | | 3. PROVIDE EROSION AND SEDIMENT CONTROL PLAN WITH THE | | | ENGINEERING PERMIT SUBMITTAL. | | | | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | 561-351-0510 (M) | | | [email protected] | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
08-09-2022 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
08-09-2022 |
Time |
08:03 |
Rev Time |
|
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-09 08:25:09 | 1. ADD CONVERSION TO NGVD-29 ON SURVEY AND ENG. PLANS. | | | 2. SURVEY NEEDS TO LABEL CORNER MONUMENTATION. | | | 3. UNITY OF TITLE WILL BE REQUIRED. | | | 4. DRIVEWAY FLAIR CANNOT CROSS INTO ADJOINING PROPERTY. | | | 5. UTILITIES MAY NOT WANT WATER CONNECTIONS IN ALLEY. |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
08-10-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
08-10-2022 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
08-10-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-10 22:27:36 | TRAFFIC COMMENTS | | | 1) CORRECT THE EXEMPTION REFERENCE AS IT IS TRAFFIC | | | CONCURRENCY EXCEPTION AREA (TCEA), NOT CRA. | | | 2) SCHEDULE A METHODOLOGY MEETING. A FULL TRAFFIC STUDY | | | IS NEEDED; EXEMPTION FROM COUNTY CONCURRENCY DOES NOT | | | PRECLUDE THE CITY TO REQUEST MORE IN-DEPTH ANALYSIS, | | | GIVEN THE SIGNIFICANT CHANGE IN LAND USE AND TRIP | | | GENERATION TOGETHER WITH IMPACT TO THE SURROUNDING | | | ROADWAY NETWORK | | | 3) ALL CONCERNS AND COMMENTS PROVIDED BY THE COUNTY IN | | | THE TPS LETTER SHALL BE ADDRESSED | | | 4) MORE DETAILED TRANSPORTATION DEMAND MANAGEMENT (TDM) | | | MEASURES SHALL BE DISCUSSED AND AGREED WITH CITY | | | PLANNING AND ENGINEERING DEPARTMENTS | | | 5) TRAFFIC SIGNAL WARRANT ANALYSES SHALL BE CONDUCTED | | | AT EACH IMPACTED UNSIGNALIZED INTERSECTION ALONG PALM | | | BEACH LAKES BLVD AND DIXIE HIGHWAY | | | | | | SITE COMMENTS | | | 6) PROVIDE A CLEAN TRANSPORTATION SPECIFIC SITE PLAN. | | | SHOWCASING TRANSPORTATION RELATED FEATURES (E.G. | | | ROADWAY, DRIVING AISLES, PARKING STALLS, SIDEWALK, | | | CURB, GUTTER, DRIVEWAY, GATES, ETC.) PROPERLY LABELED | | | AND DIMENSIONED. PLEASE DO NOT SHOW ALL UNDERGROUND | | | UTILITY LAYERS | | | 7) IN THE TRANSPORTATION SITE PLAN, PLEASE SHOWCASE | | | BASIC CURB DETAILS (E.G. DRIVEWAY, CURB CUTS, PAVEMENT | | | MARKINGS, PARKING STALLS, ETC.) ON THE OPPOSITE SIDE OF | | | THE ROADS SURROUNDING THE PROPOSED DEVELOPMENT. | | | INCLUDING ALLEYWAYS. | | | 8) PROVIDE AUTOTURN ANALYSIS FOR GARBAGE TRUCK AND/OR | | | DELIVERY VEHICLES SERVICING THE PROPOSED DEVELOPMENT | | | WITH VEHICLE DYNAMIC ENVELOPES AND WHEEL PATHS CLEARLY | | | DISTINCT AND DEFINED. ANALYSIS SHOULD BE PROVIDED IN A | | | SEPARATE FILE/DRAWING. PLEASE PROVIDE DOCUMENT NAME AND | | | SHEET NUMBER SHOWCASING THE ANALYSIS | | | 9) CLEARLY MARK AND DIMENSION THE DESIGNATED LOADING | | | ZONE | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
05-01-2023 |
|
|
Cont ID |
|
| Sent By |
ckimmerl |
Date |
05-01-2023 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
ckimmerl |
Date |
05-01-2023 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2023-05-01 15:34:42 | 1. SETBACKS: | | | - PLEASE PROVIDE SETBACK LINES ON SITE PLAN AND | | | ARCHITECTURAL DRAWINGS | | | - SETBACKS NEED TO BE RECALCULATED AND LABELED: | | | - 10TH STREET IS FRONT, MIN. 20 FT. SETBACK REQUIRED | | | - RAILROAD AVENUE IS SIDE STREET, 0 FT. SETBACK | | | REQUIRED | | | - ALLEY, 5 FT. MIN. SETBACK REQUIRED - SIDE INTERIOR | | | MIN. 25 FT. SETBACK REQUIRED FOR MIXED USE FRONTING RR | | | AVE. | | | RESPONSE: IN ORDER TO ENCOURAGE AND DIRECT PUBLIC | | | ACTIVITY AND MOVEMENT ALONG N. RAILROAD AVENUE, THE | | | APPLICANT ORIENTED THE PUBLIC ACCESS TO 444 ALONG N. | | | RAILROAD AVENUE AND PLACED ALL BACK-OF-HOUSE SERVICES | | | (I.E. LOADING, PARKING, TRASH ENCLOSURE, UTILITIES) TO | | | THE REAR OF THE PROPERTY. AS SUCH, THE ALLEY AND 10TH | | | STREET FRONTAGES HAVE BEEN TREATED AS ???SIDE STREET | | | RESIDENTIAL??? AND ???ALLEY??? BUFFERS BASED ON THIS | | | UPDATED BUILDING AND SITE PROGRAMMING. THE APPLICANT | | | RESPECTFULLY REQUESTS THAT THE NORTH BUFFER BE | | | CONSIDERED A ???SIDE RESIDENTIAL STREET??? BUFFER TO | | | MAXIMIZE THE AMOUNT OF ACTIVE BUILDING FRONTAGE THAT | | | CAN BE CREATED/PROGRAMMED ALONG N. RAILROAD FOR THE | | | BENEFIT OF THE URBAN STREETSCAPE THAT IS ATTEMPTING TO | | | BE CREATED ALONG THIS CORRIDOR. | | | 1. ZONING REVIEW 5.1.23 ??? [PARTIALLY SATISFIED] | | | AFTER STAFF REVIEW OF BPD-R PROVISIONS; SETBACKS SHALL | | | BE SUCH: | | | RAILROAD AVENUE ??? 0??? | | | ALLEY ??? 5??? | | | SIDE RESIDENTIAL STREET (10TH ST. FRONTAGE) ??? 10??? | | | SIDE INTERIOR SETBACK (EASTERN PROPERTY LINE) ??? 25??? | | | NO REAR OR FRONT SETBACKS BY CODE BECAUSE OF COMMERCIAL | | | PROPERTY FRONTING RAILROAD. | | | STAIRCASE ENCROACHES INTO SIDE INTERIOR SETBACK BY | | | 1.5FT. PLEASE ADJUST. | | | | | | 2. PARKING REQUIREMENTS: | | | - PLEASE PROVIDE BREAKDOWN OF OFFICE AND RETAIL SF. | | | BOTH 7,900 SF? | | | - WHAT IS WIDTH OF PARKING DRIVE? APPEARS TO BE 24FT | | | BUT PLEASE BE SURE TO FALL UNDER 25FT MAXIMUM WIDTH. | | | - PAINTING/STRIPING DETAILS NEED TO MEET CITY STANDARD | | | FOR STALL | | | - SITE PLAN MENTIONS PARKING REQUIREMENTS BEING MET | | | WITH VALET SERVICE OFFSITE, PLEASE INDICATE WHERE THE | | | OFF-SITE PARKING IS LOCATED. | | | RESPONSE: THE BUILDING SQUARE FOOTAGE IS DIVIDED | | | EQUALLY INTO GROUND FLOOR RETAIL/RESTAURANT AND SECOND | | | STORY OFFICE USES (7,900 SF RESPECTIVELY). THE PARKING | | | DRIVE AISLE IS 24 FEET WIDE AND A DIMENSION HAS BEEN | | | ADDED TO THE PLAN TO IDENTIFY SAID WIDTH. THE PARKING | | | STRIPING HAS BEEN UPDATED TO MATCH THE CITY STANDARDS. | | | A NOTE HAS BEEN ADDED TO THE SITE PLAN INDICATING THE | | | LOCATION OF THE OFFSITE PUBLIC AND VALET PARKING LOTS | | | THAT SERVE THE VARIOUS USES WITHIN NORA. | | | 2. ZONING REVIEW 5.1.23 ??? [SATISFIED] | | | | | | 3. SANITATION/LOADING: PLEASE PROVIDE AUTOTURN ANALYSIS | | | FOR ALLEY AND LOADING AREA. | | | RESPONSE: ACKNOWLEDGED. AN AUTOTURN ANALYSIS HAS BEEN | | | PREPARED TO IDENTIFY THE ABILITY OF UTILITY VEHICLES TO | | | ACCESS THE TRASH ENCLOSURE AND THE LOADING ZONE. | | | 3. ZONING REVIEW 5.1.23 ??? [NOT SATISFIED] NO AUTOTURN | | | PROVIDED IN SUBMITTAL PACKAGE | | | | | | 4. PHOTOMETRIC ANALYSIS SHOWS PROPERTY AS A 1-STORY | | | 10,185 SF BUILDING, PLEASE BE CONSISTENT ACROSS PLAN | | | SETS. | | | RESPONSE: ACKNOWLEDGED. THE PHOTOMETRIC PLAN SHALL BE | | | UPDATED FOR BACKGROUND CONSISTENCY. | | | 4. ZONING REVIEW 5.1.23 ??? [SATISFIED] | | | | | | 5. CURB CUT FOR TRASHCAN/ALLEY CUTS INTO ADJACENT | | | RESIDENTIAL PROPERTY. PLEASE ADJUST. | | | RESPONSE: ACKNOWLEDGED. THE RADIAL CURB HAS BEEN | | | REPLACED WITH A FLARE TO AVOID CONFLICT/ENCROACHMENT | | | WITH THE ADJACENT PROPERTY TO THE EAST. SEE UPDATED | | | SITE AND LANDSCAPE PLANS. | | | ZONING REVIEW 5.1.23 ??? [SATISFIED] | | | | | | 6. PLEASE INDICATE WHERE REQUIRED BIKE PARKING SPACES | | | ARE LOCATED | | | RESPONSE: ACKNOWLEDGED. BIKE RACK HAVE BEEN PROVIDED | | | THROUGHOUT NORA WITHIN THE PREVIOUSLY APPROVED | | | STREETSCAPE PLAN AND PUBLIC OFF-STREET PARKING PLAN | | | PROJECTS. AN ADDITIONAL BIKE RACK HAS BEEN SPECIFIED AT | | | THE REAR OF THE BUILDING IN THE PAVER PLAZA AREA. | | | ZONING REVIEW 5.1.23 ??? [SATISFIED] | | | | | | 7. PLEASE PROVIDE STREETSCAPE LANDSCAPING DETAILS FOR N | | | RAILROAD AVE. AND 10TH ST. FRONTAGES. | | | RESPONSE: ACKNOWLEDGED. LANDSCAPE DETAILS HAVE BEEN | | | PROVIDED FOR BOTH RIGHTS-OF-WAYS ALONG THE BOUNDARY OF | | | THE SUBJECT SITE. | | | ZONING REVIEW 5.1.23 ??? [SATISFIED] | | | | | | 8. 5FT. LANDSCAPE BUFFER BETWEEN ADJACENT TO | | | RESIDENTIAL USES REQUIRES INSTALLATION OF A WALL. | | | RESPONSE: ACKNOWLEDGED. A WALL SHALL BE ADDED ALONG | | | THE EAST PROPERTY BOUNDARY AS REQUIRED. SEE UPDATED | | | SITE AND LANDSCAPE PLAN. | | | PLEASE PROVIDE HEIGHT DETAIL OF MASONRY WALL | | | | | | NEW ZONING COMMENTS 5.1.23: | | | 1. PLEASE PROVIDE PROJECTION DETAILS OR DIMENSIONS FOR | | | THE CANOPY ELEMENTS SHOWN ON THE ELEVATIONS. BE SURE | | | THAT THESE ELEMENTS MEET THE STANDARDS IN SEC. 94-109 | | | TABLE IV-5. ELEVATIONS PROVIDED, PLEASE SHOW | | | PROJECTIONS. | | | | | | 2. ANY ROOFTOP MECHANICAL EQUIPMENT SHALL BE SCREENED | | | FROM VIEW. PER SEC. 94-109 PROJECTION, VERTICAL: | | | MECHANICAL EQUIPMENT AND APPURTENANCES NECESSARY TO THE | | | OPERATION OR MAINTENANCE OF THE BUILDING OR STRUCTURE | | | ITSELF SUCH AS, BUT NOT LIMITED TO, COOLING TOWERS, | | | ELEVATORS, STAIRS AND MECHANICAL PENTHOUSES, VENT | | | STACKS AND ANTENNAS SHALL BE ENCLOSED AND SCREENED IN | | | SUCH A MANNER THAT THE ENCLOSURE IS DESIGNED AS AN | | | INTEGRAL PART OF THE OVERALL BUILDING DESIGN. | | | 3. FOR THE LANDSCAPING ON SHEET LP-1: | | | SEC.94-113(D.) AND SEC.94-113(G.) APPLIES | | | SEC. 94-443(A.)(1.) PROTECTIVE SCREEN WALLS AND | | | (2.)LANDSCAPE BUFFER APPLIES; THESE SECTIONS PROVIDE | | | MORE DETAIL ON THE REQUIREMENTS OF SEC. 94-113(G.) | | | PLEASE AMEND LP-1 & LP-2 TO REFLECT THE THREE | | | APPLICABLE CODE SECTIONS ABOVE AND THEIR REQUIREMENTS. | | | THE REFERENCE TO 94-442 CAN BE REMOVED. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
08-08-2022 |
|
|
Cont ID |
|
| Sent By |
ckimmerl |
Date |
08-08-2022 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
ckimmerl |
Date |
08-08-2022 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2022-08-08 15:07:53 | 1. SETBACKS: | | | - PLEASE PROVIDE SETBACK LINES ON SITE PLAN AND | | | ARCHITECTURAL DRAWINGS | | | - SETBACKS NEED TO BE RECALCULATED AND LABELED: | | | - 10TH STREET IS FRONT, MIN. 20 FT. SETBACK REQUIRED | | | - RAILROAD AVENUE IS SIDE STREET, 0 FT. SETBACK | | | REQUIRED | | | - ALLEY, 5 FT. MIN. SETBACK REQUIRED | | | - SIDE INTERIOR MIN. 25 FT. SETBACK REQUIRED FOR MIXED | | | USE FRONTING RR AVE. | | | | | | 2. PARKING REQUIREMENTS: | | | - PLEASE PROVIDE BREAKDOWN OF OFFICE AND RETAIL SF. | | | BOTH 7,900 SF? | | | - WHAT IS WIDTH OF PARKING DRIVE? APPEARS TO BE 24FT | | | BUT PLEASE BE SURE TO FALL UNDER 25FT MAXIMUM WIDTH. | | | - PAINTING/STRIPING DETAILS NEED TO MEET CITY STANDARD | | | FOR STALL | | | - SITE PLAN MENTIONS PARKING REQUIREMENTS BEING MET | | | WITH VALET SERVICE OFFSITE, PLEASE INDICATE WHERE THE | | | OFF-SITE PARKING IS LOCATED. | | | | | | 3. SANITATION/LOADING: | | | - PLEASE PROVIDE AUTOTURN ANALYSIS FOR ALLEY AND | | | LOADING AREA. | | | | | | 4. PHOTOMETRIC ANALYSIS SHOWS PROPERTY AS A 1-STORY | | | 10,185 SF BUILDING, PLEASE BE CONSISTENT ACROSS PLAN | | | SETS. | | | | | | 5. CURB CUT FOR TRASHCAN/ALLEY CUTS INTO ADJACENT | | | RESIDENTIAL PROPERTY. PLEASE ADJUST. | | | | | | 6. PLEASE INDICATE WHERE REQUIRED BIKE PARKING SPACES | | | ARE LOCATED. | | | | | | 7. PLEASE PROVIDE STREETSCAPE LANDSCAPING DETAILS FOR N | | | RAILROAD AVE. AND 10TH ST. FRONTAGES. | | | | | | 8. 5FT. LANDSCAPE BUFFER BETWEEN ADJACENT TO | | | RESIDENTIAL USES REQUIRES INSTALLATION OF A WALL. | | | | | | CHRIS KIMMERLY, AICP | | | URBAN DESIGN PLANNER | | | 822.1426 [email protected] |
|
|
| |
Print |
|
Account Summary | Usage Policy | Privacy Policy