Plan Review Details - Project Z22070023
| Plan Review Stops For Project Z22070023 |
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
1 |
Status |
F |
Date |
08-09-2022 |
|
|
Cont ID |
|
| Sent By |
scwelter |
Date |
08-09-2022 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
scwelter |
Date |
08-09-2022 |
Time |
14:19 |
Sent To |
|
|
| Notes |
| 2022-08-09 14:19:01 | THE NORA PROJECT IS UNDER ONE DEVELOPER AND PARTS OF | | | THE PROJECT ARE SUBJECT TO THE PUBLIC ART REQUIREMENT: | | | Z22070021 | | | Z22070022 | | | Z22070023 | | | Z22070024 | | | Z22070025 | | | IT IS MY UNDERSTANDING THAT THE DEVELOPER WILL ADD | | | PUBLIC ART WORKS. POTENTIAL ART SITES NEED TO BE | | | IDENTIFIED ON EACH OF THE SITE PLAN(S) FOR SITE PLAN | | | APPROVAL(S). | | | PLEASE EMAIL [email protected] FOR AN ART ASSESSMENT | | | APPLICATION. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
05-04-2023 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
05-04-2023 |
Time |
19:30 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
05-04-2023 |
Time |
19:30 |
Sent To |
|
|
| Notes |
| 2023-05-04 19:32:56 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2.BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND | | | OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT, | | | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF | | | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF | | | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE | | | VERIFIED. | | | | | | 3. GREASE INTERCEPTOR. IF THE RETAIL SPACE IS TO BE A | | | RESYAURANT A GREASE INTERCEPTOR WILL BE REQUIRED. FOR | | | INFORMATION ON THE REQUIRED TYPE, SIZE AND LOCATION, | | | PLEASE CONTACT RYAN BROWN, CHIEF PLUMBING INSPECTOR, | | | DEVELOPMENT SERVICES DEPARTMENT, AT (561) 805-6692, OR | | | BY EMAIL: [email protected] | | | | | | 4. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, | | | FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, | | | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, | | | SITE IRRIGATION, ETC. | | | | | | 5. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND | | | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF | | | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL | | | NEIGHBORING PROPERTIES. | | | | | | 6. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT | | | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL | | | HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION | | | OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING, | | | CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT | | | (561) 805 6659, OR BY EMAIL: [email protected] | | | | | | 7. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT | | | TO ART LIFE ASSESSMENT UNDER THE CITY OF WEST PALM | | | BEACH ART IN PUBLIC PLACES (AIPP) PROGRAM. FOR ADVICE | | | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP | | | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC | | | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
08-10-2022 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
08-10-2022 |
Time |
21:17 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
08-10-2022 |
Time |
21:16 |
Sent To |
|
|
| Notes |
| 2022-08-10 21:20:00 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. NUMBER OF ACCESSIBLE PARKING SPACES. SITE PLAN SHEET | | | CP1 STATES THAT 1 ACCESSIBLE PARKING SPACE WILL BE | | | PROVIDED AND THAT IT WILL BE OFF-SITE VALET PARKING. | | | ACCESSIBLE SELF PARKING MUST BE PROVIDED AS A VALET MAY | | | NOT BE ABLE TO OPERATE A VEHICLE THAT HAS UNDERGONE | | | ACCESSIBILITY MODIFICATIONS NEEDED FOR THE OWNER. THE | | | PLANS SHALL SHOW WHERE THE PARKING SPACES ARE LOCATED, | | | INCLUDING THE ACCESSIBLE PARKING. THE MINIMUM NUMBER OF | | | ACCESSIBLE PARKING SPACES PROVIDED SHALL BE IN | | | ACCORDANCE WITH SECTION 208.2 OF FLORIDA ACCESSIBILITY | | | CODE. | | | | | | 3. LOCATION OF ACCESSIBLE PARKING SPACES. PER SECTION | | | 208.3 OF FLORIDA ACCESSIBILITY CODE, ACCESSIBLE PARKING | | | SPACES ARE TO BE LOCATED ON THE SHORTEST POSSIBLE ROUTE | | | OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE | | | ENTRANCE. THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL | | | COMPLY WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE | | | | | | 4. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND | | | OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT, | | | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF | | | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF | | | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE | | | VERIFIED. | | | | | | 5. GREASE INTERCEPTOR. IF THE RETAIL SPACE IS TO BE A | | | RESYAURANT A GREASE INTERCEPTOR WILL BE REQUIRED. FOR | | | INFORMATION ON THE REQUIRED TYPE, SIZE AND LOCATION, | | | PLEASE CONTACT RYAN BROWN, CHIEF PLUMBING INSPECTOR, | | | DEVELOPMENT SERVICES DEPARTMENT, AT (561) 805-6692, OR | | | BY EMAIL: [email protected] | | | | | | 6. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, | | | FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, | | | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, | | | SITE IRRIGATION, ETC. | | | | | | 7. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND | | | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF | | | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL | | | NEIGHBORING PROPERTIES. | | | | | | 8. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT | | | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL | | | HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION | | | OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING, | | | CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT | | | (561) 805 6659, OR BY EMAIL: [email protected] | | | | | | 9. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT | | | TO ART LIFE ASSESSMENT UNDER THE CITY OF WEST PALM | | | BEACH ART IN PUBLIC PLACES (AIPP) PROGRAM. FOR ADVICE | | | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP | | | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC | | | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
3 |
Status |
F |
Date |
07-27-2023 |
|
|
Cont ID |
|
| Sent By |
lquinone |
Date |
07-27-2023 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
lquinone |
Date |
07-27-2023 |
Time |
13:34 |
Sent To |
|
|
| Notes |
| 2023-07-27 13:34:35 | PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND | | | STORMWATER PIPES ALONG ENTIRE PROJECT FRONTAGE. |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
F |
Date |
04-11-2023 |
|
|
Cont ID |
|
| Sent By |
lquinone |
Date |
04-11-2023 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
lquinone |
Date |
04-11-2023 |
Time |
10:19 |
Sent To |
|
|
| Notes |
| 2023-04-11 10:24:30 | NO RESPONSE LETTER WAS SUBMITTED. | | | | | | COMMENTS FROM LINDA M. QUINONES-CINTRON, PROJECT | | | COORDINATOR, ENGINEERING SERVICES AT 561-494-1085 | | | [email protected] | | | | | | CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY SEWER | | | ARE REQUIRED. | | | | | | PROVIDE CALCULATIONS ON PLANS OF EXISTING AND PROPOSED | | | DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM AND PEAK) | | | AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE PER FAC | | | 64E-8 FOR WATER AND PER FAC 64-E.008 FOR SEWER. | | | | | | PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND | | | STORMWATER PIPES ALONG ENTIRE PROJECT FRONTAGE. | | | | | | COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE | | | SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING | | | PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT | | | HIM AT 561-494-2262 OR [email protected] | | | | | | FOR FORMAL ENGINEERING SUBMITTAL , PLANS SHALL SHOW | | | PROPOSED LOCATIONS AND DIMENSIONS OF ALL WATER, | | | STORMWATER, AND SANITARY AND SEWER LINES, INCLUDING | | | STUBS TO EACH PROPERTY LINE FOR WATER AND SANITARY | | | SEWERS, THE MAKE AND MODEL OF ALL VALVES, METERS, AND | | | OTHERS DEVICES TO BE INSTALLED ON THE SYSTEM, CATCH | | | BASINS, CULVERTS, DITCHES INCLUDING GRADES, PIPES | | | SIZES, MATERIALS, ELEVATIONS, ASSUMPTIONS, | | | CALCULATIONS, INVERT ELEVATIONS FOR ALL INLETS AND | | | MANHOLES AND PROFILES OF SANITARY SEWER LINES. ALL | | | AVAILABLE ELEVATION SHALL BE SHOWN ON THE PROFILE VIEW. | | | DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN | | | VIEW FOR ALL SANITARY AND STORM SEWERS. ADDITIONALLY, | | | PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED | | | UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC, | | | ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION | | | FACILITIES LOCATED ON THE RIGHT-OF-WAY. PROVIDE PROFILE | | | AND CLEARANCES AT ALL UTILITY CROSSINGS. | | | | | | PLEASE CLOUD/HIGHLIGHT PLAN REVISIONS OR CHANGES IN | | | SCOPE FOR RESUBMITTAL OF DRAWINGS. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL , CUT AND CAP | | | UTILITIES NOT IN USE, AND REMOVE ANY ABANDONED UTILITY | | | LINES LARGER THAN 2 INCHES FROM CITY RIGHT OF WAY. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE DEDICATED | | | UTILITY EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO | | | PROPOSED UTILITY WATER METERS. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | ENLARGED VIEW ON PLANS OF PROPOSED LOCATION OF WATER | | | METER AND BACKFLOW PREVENTION. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, PLEASE CALLOUT | | | DOMESTIC BACKFLOW PREVENTER AS RPPA AND FIRE BACKFLOW | | | PREVENTER AS DCDA. SPECIFY LEAD FREE DESIGN ON ALL | | | BACKFLOWS. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES | | | NOI REQUIREMENTS WILL BE ENFORCED. | | | | | | -AN NOI IS REQUIRED FOR PROJECTS THAT: | | | 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS | | | THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF | | | DEVELOPMENT OR SALE; AND | | | 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE | | | STATE OR TO SURFACE WATERS OF THE STATE THROUGH A | | | MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4). | | | -THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF | | | CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION | | | THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL | | | SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT | | | OF THE 10-2 CERTIFICATION. IF THE ENGINEERING PLANS DO | | | NOT INCLUDE AN EROSION CONTROL PLAN, THEN THE | | | CONTRACTOR SHOULD SUBMIT ONE PRIOR TO RECEIVING THE | | | ENGINEERING PERMIT. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF | | | PROPOSED AND EXISTING WATER AND SEWER WITHIN RIGHT OF | | | WAY AND SHOW ANY CROSSINGS/CONFLICTS. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING | | | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT | | | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING | | | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED | | | LEAD-FREE DESIGN. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL CLEARLY SHOW ROAD | | | RIGHT OF WAY. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL PROVIDE SANITARY | | | ELEVATIONS AT MANHOLE TIE-IN. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES | | | ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY | | | LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT | | | PARCELS. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, IF WATER LINES ARE | | | BEING REPLACED IN ROW, SHOW ADJACENT PARCEL ADDRESSES. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, WHEN TRENCHING IN IN | | | CITY MAINTAINED ROADWAY AREAS ADD NOTE TO PROVIDE 50 | | | FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF | | | PROPOSED TRENCH PER CURRENT CITY OF WPB STANDARD DETAIL | | | GC-8. | | | | | | PLEASE RESPOND TO ALL COMMENTS IN WRITING AND INCLUDE | | | PROJECT NAME, ADDRESS AND PERMIT NUMBER (Z-XXXXXXXX). | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
07-27-2022 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
07-27-2022 |
Time |
|
Rev Time |
|
| Received By |
rrossano |
Date |
07-27-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-07-27 10:46:57 | Z22070023 - 818 N RAILROAD AVE, MIXED USE 7.26.22 SUB | | | COMMENTS FROM RICK ROSSANO, SR. PROJECT COORDINATOR, | | | ENGINEERING SERVICES AT 561-494-1098 [email protected] | | | GENERAL: | | | O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND | | | INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER | | | (Z-XXXXXXXX). | | | O THE CITY OF WEST PALM BEACH HAS A NUMBER OF | | | REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY | | | AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND | | | WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE | | | DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK | | | BELOW: | | | A. HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WP | | | B_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FUL | | | L-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97 | | | B1960045731D3658206F27451722716EF | | | B. THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE | | | FOUND HERE: | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | C. ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM | | | BEACH, FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, | | | ADOPTED SEPT. 22, 2008. (SUPPLEMENT NO. 18) | | | CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL, | | | SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER | | | SERVICE FACILITIES OF THE CITY. | | | THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE | | | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY | | | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, | | | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. | | | O AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR | | | MORE INFORMATION, REFER TO THE LINK BELOW: | | | A. HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PU | | | BLICATIONS/BACKFLOW-CROSS-CONNECTION- CONTROL-MANUAL | | | O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY | | | OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC | | | RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF | | | YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE | | | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL | | | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT | | | [email protected] OR 561-494-1079 FOR FURTHER | | | ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION | | | ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD | | | SURVEY, POT-HOLING, SOFT DIGS ETC. | | | O PROVIDE EXISTING AND PROPOSED PERVIOUS AND IMPERVIOUS | | | DATA. | | | | | | BACKFLOW ASSEMBLY AND METERS: | | | O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER | | | SERVICES AND WATER METERS, ALONG WITH WHAT IS HAPPENING | | | TO THEM. | | | O SHOW EXISTING AND PROPOSED DEDICATED UTILITY | | | EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO | | | PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO | | | STRUCTURES WITHIN EASEMENT. | | | O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION | | | OF WATER METER AND BACKFLOW | | | PREVENTION. | | | O BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY | | | OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER | | | METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO | | | PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE | | | INSTALLED ABOVE-GROUND ONLY. | | | O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE | | | NOTE USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA. | | | | | | WATER/WASTEWATER PLAN: | | | O PROVIDE VERTICAL DATUM AND DATUM CONVERSION | | | INFORMATION (NAVD 1988 AND NGVD 1929). | | | O SHOW PROJECT ADDRESS ON ALL PLAN SHEETS. | | | O PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE | | | STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC. | | | O PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND | | | DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND | | | SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH | | | PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE | | | AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS, | | | BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO | | | BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS, | | | DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS, | | | ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT | | | ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF | | | SANITARY SEWER LINES. | | | O GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR | | | SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE | | | PROFILE VIEW. | | | O DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN | | | VIEW FOR ALL SANITARY AND STORM SEWERS. | | | O SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT | | | MATERIAL. | | | O PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED | | | UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC, | | | ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION | | | FACILITIES LOCATED ON THE RIGHT-OF-WAY. | | | O PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER | | | AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD | | | DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS. | | | O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY | | | TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT | | | APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING | | | AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, | | | MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS | | | SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 | | | FOR WATER. | | | O PROVIDE FIRE FLOW TEST DATA. | | | O PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND | | | STORMWATER INFRASTRUCTURE ALONG ENTIRE PROJECT FRONTAGE | | | (CONDITION OF SITE PLAN APPROVAL). | | | O CUT AND CAP UTILITIES NOT IN USE AND REMOVE ANY | | | ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY | | | ROW. | | | O WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL | | | BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY | | | PROPOSED LENGTH IN FEET. | | | O CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY | | | SEWER ARE REQUIRED. | | | O PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE | | | JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET. | | | O ADD NOTE TO PLANS SPECIFYING CITY?S DOWNSTREAM LIFT | | | STATION NUMBER. | | | O PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR | | | PROPOSED SANITARY LATERALS. | | | O LABEL WATER LINES AS PRIVATE WHERE APPLICABLE. | | | O PLEASE SHOW AND LABEL EXISTING AND PROPOSED GREASE | | | TRAPS (IF ANY). | | | O PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN | | | OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER. | | | | | | FORMAL ENGINEERING REVIEW: | | | O FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES | | | NOI REQUIREMENTS WILL BE ENFORCED. | | | - AN NOI IS REQUIRED FOR PROJECTS THAT: | | | - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS | | | THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF | | | DEVELOPMENT OR SALE; | | | - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE | | | STATE OR TO SURFACE WATERS OF THE STATE THROUGH A | | | MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4). | | | - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF | | | CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION | | | THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL | | | SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT | | | OF THE 10-2 CERTIFICATION. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF | | | WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING | | | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT | | | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING | | | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED | | | LEAD-FREE DESIGN. | | | O FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES | | | ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY | | | LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT | | | PARCELS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, IF WATER LINES ARE | | | BEING REPLACED IN ROW, SHOW ADJACENT PARCEL ADDRESSES. | | | O FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO PROVIDE | | | 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF | | | PROPOSED TRENCH IN CITY MAINTAINED ROADWAY AREAS PER | | | CITY OF WPB STANDARD DETAIL GC-8. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | CALCULATIONS OF PERVIOUS AND IMPERVIOUS AREAS FOR | | | PROPOSED IMPROVED AREAS. | | | | | | | | | | | | QUESTIONS AND COORDINATION CONTACTS: | | | O MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR WITH | | | CITY OF WPB PUBLIC UTILITIES, REGARDING PLACEMENT OF | | | BACKFLOW DEVICES AND WATER METERS. CONTACT HIM AT | | | 561-822-2262 OR [email protected] | | | O MIKE TECHNOW, PROJECT ENGINEER, PUBLIC UTILITIES | | | DEPARTMENT AT 561-494-1047 OR [email protected] | | | O TRACY WARD, SR. STORMWATER ENGINEER, ENGINEERING | | | SERVICES DEPT. AT 561-494-1120 OR [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
08-01-2022 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
08-01-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
08-01-2022 |
Time |
11:15 |
Sent To |
|
|
| Notes |
| 2022-08-01 11:20:14 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE DEPARTMENT. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. THE FOLLOWING COMMENTS ARE INTENDED | | | TO PROVIDE GUIDANCE FOR BUILDING PLAN SUBMITTAL. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING(S) SHALL COMPLY | | | WITH THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION | | | CODE, INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE | | | CODES. | | | | | | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE | | | OCCUPANCY TYPE PER THE FLORIDA FIRE PREVENTION CODE. | | | | | | 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE | | | LOAD CALCULATION IS INCLUDED, AND THAT ADEQUATE WATER | | | SUPPLY IS EXISTING OR WILL BE PROVIDED. | | | | | | 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | THE PROPOSED LOCATION OF THE FIRE HYDRANT AND FDC SHALL | | | BE WITHIN 100' OF EACH OTHER AND CLOSELY COORDINATED | | | WITH THE BUREAU OF FIRE PREVENTION. | | | | | | 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER | | | THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY | | | ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM, | | | ENSURE THEY COMPLY WITH THE REQUIREMENTS OF F.A.C. 61G | | | AND SUBMITTED WITH THE MASTER PERMIT. | | | | | | 9A. THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE | | | LOCATIONS SHALL MEET AND BE INSTALLED PER THE | | | REQUIREMENTS OF NFPA 24 AND SHALL BE COORDINATED WITH | | | THE OFFICE OF FIRE MARSHAL, THE CITY'S ENGINEERS | | | OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S PLANNING | | | AND ZONING OFFICE. | | | | | | 10. COMPLETE LIFE SAFETY PLANS FOR THE OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, EXIT SEPARATION DISTANCES, COMMON PATHS OF | | | TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, EMERGENCY | | | LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE | | | EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES | | | AND EQUIPMENT. | | | | | | 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE | | | SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY | | | DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS. | | | | | | 12. ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE | | | FIGHTER?S EMERGENCY OPERATIONS REQUIREMENTS OF ASME | | | A17.1/CSA B44, SAFETY CODE FOR ELEVATORS. | | | | | | ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN | | | WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL | | | LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET | | | MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER | | | ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN | | | AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE | | | IN THE HORIZONTAL POSITION. | | | | | | 13. TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEMS. | | | | | | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY | | | RADIO ENHANCEMENT SERVICES. | | | 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM | | | RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT | | | COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL | | | DETERMINED BY THE AHJ. | | | | | | IF APPLICABLE, CONTACT WILL NEED TO BE MADE TO MARK | | | FILLA, PALM BEACH COUNTY PUBLIC SAFETY RADIO SYSTEMS | | | MANAGER, [email protected], 561-233-0837; AS OUR RADIOS | | | OPERATE ON THEIR SYSTEM FOR DETAILED RADIO FREQUENCY | | | AND INSTALLATION INSTRUCTIONS. | | | | | | 14. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL. | | | | | | 15. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
08-10-2022 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
08-10-2022 |
Time |
13:28 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
08-10-2022 |
Time |
13:28 |
Sent To |
|
|
| Notes |
| 2022-08-10 13:29:25 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: 818 N RAILROAD NORA Z22070023 | | | AUGUST 10, 2022 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. PROVIDE A TREE SURVEY AND TREE DISPOSITION PLAN TO | | | IDENTIFY ALL EXISTING TREES AND PALMS. IDENTIFY | | | EXISTING TREES IN THE RIGHT OF WAY. IF ON THE ADJACENT | | | PROPERTY, SHOW THEM ON THE LANDSCAPE PLAN PER SECTION | | | 94-442(B)(2)Q. | | | | | | 2. PROVIDE A DATA TABLE SHOWING ALL REQUIRED | | | INFORMATION FOR CODE COMPLIANCE REVIEW. | | | | | | 3. LIST ANY VARIANCES REQUESTED FOR LANDSCAPING. | | | | | | 4. STREETSCAPE MUST BE PROVIDED ADJACENT TO THE | | | PROPERTY INCLUDING SIDEWALKS AND STREET TREES. | | | | | | 5. SHOW LOCATIONS OF ALL UTILITIES ON THE LANDSCAPE | | | PLAN, AS THERE ARE MULTIPLE CONFLICTS WITH REQUIRED | | | LANDSCAPING. | | | | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE | | | STREET TREES AND RIGHT OF WAY LANDSCAPING AND | | | IRRIGATION APPROVED WITH THIS PETITION. | | | 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF | | | WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A | | | SEPARATE MAINTENANCE AGREEMENT WITH THE CITY. | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
1 |
Status |
P |
Date |
08-12-2022 |
|
|
Cont ID |
|
| Sent By |
mtechnow |
Date |
08-12-2022 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
mtechnow |
Date |
08-12-2022 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2022-08-12 11:38:26 | NO ISSUE WITH CONCEPTUAL REVIEW. PLEASE REFERENCE | | | CHECKLIST FOR ENGINEERING SUBMITTAL REQUIREMENTS. |
|
|
| Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
| Rev No |
2 |
Status |
P |
Date |
04-13-2023 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
04-13-2023 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2023-04-13 09:43:32 | -SITE PLAN NEEDS TO BE UPDATED TO REFLECT UPDATED WATER | | | METER AND BACKFLOW ASSEMBLY LOCATIONS ON CIVIL | | | ENGINEERING PLAN. | | | | | | -ENGINEERING PLANS MAY NEED REVISION AT ENGINEERING | | | DEVELOPMENT SUBMITTAL. |
|
|
| Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
| Rev No |
1 |
Status |
F |
Date |
08-08-2022 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
08-08-2022 |
Time |
19:00 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-08 18:59:56 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | -ARCHITECTURAL DRAWINGS DO NOT MATCH SITE PLAN LAYOUT | | | WITH REGARD TO PARKING LOT AREA. PLEASE ENSURE PLANS | | | HAVE SAME GENERAL LAYOUT. | | | -BACKFLOW ASSEMBLIES ON ENGINEERING PLAN APPEAR TO | | | CONFLICT WITH PLANTS ON LANDSCAPING PLAN. ARCHITECTURAL | | | PERSPECTIVE 3 ALSO SHOWS LARGE BUILDING OPENING ON | | | NORTH SIDE OF BACKFLOW ASSEMBLIES. | | | -WHY ARE GREASE TRAPS PROPOSED? | | | -PLANS PROPOSE A SHARED SEWER LATERAL BETWEEN | | | NEIGHBORING PROPERTIES. EACH PROPERTY MAY BE ADVERSELY | | | AFFECTED BY ACTIONS OF THE OTHER PROPERTY OWNERS. THE | | | SIZING IS ALSO LESS THAN WOULD HAVE WITH SEPARATE SEWER | | | LATERALS. | | | -IF FDC ARE NEEDED OR REQUIRED, THEN SHOW AND LABEL ON | | | PLANS. | | | -ON ENGINEERING PLAN, LABEL PROPERTY LINES OF 818 N | | | RAILROAD AS WELL AS THE PROPERTY TO THE SOUTH ACROSS | | | THE ALLEY. | | | -CALLOUT MINIMUM CLEARANCE DISTANCE BETWEEN END OF | | | PROPOSED WATER MAIN AND EXISTING SANITARY SEWER | | | MANHOLE. | | | -RECENT PICTURES OF AREA SHOW UTILITY POLES AND GUY | | | WIRES NEAR SOUTH SIDE OF ALLEY. | | | RESPECTFULLY, | | | MARK HURLEY | | | [email protected] | | | |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
2 |
Status |
F |
Date |
04-28-2023 |
|
|
Cont ID |
|
| Sent By |
|
Date |
04-28-2023 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
04-28-2023 |
Time |
|
Sent To |
|
|
| Notes |
| 2023-05-03 16:04:35 | | | | PLEASE PROVIDE THE FOLLOWINGS: | | | 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID | | | WASTE VOLUME PRODUCED ALONG WITH THE SIZE, TYPE AND | | | QUANTITY OF THE CONTAINER (I.E. DUMPSTER/COMPACTOR) | | | THAT WILL BE UTILIZED FOR THE SANITATION SERVICE. | | | 2- DUMPSTER ENCLOSURE DETAIL. DETAILS FOR SANITATION | | | SERVICE (I.E. SOLID WASTE CONTAINER(S) TYPE, COLLECTION | | | LOCATION, ETC.). FOR A FREESTANDING SITE DUMPSTER | | | ENCLOSURE, THE ENCLOSURE SHALL COMPLY WITH THE LATEST | | | REVISION OF CITY OF WEST PALM BEACH GENERAL | | | CONSTRUCTION-GARBAGE ENCLOSURE STANDARD, GC-7. (LINK TO | | | THE LATEST REVISION OF THE GC-7 DOCUMENT: HTTPS://WWW.W | | | PB.ORG/HOME/SHOWPUBLISHEDDOCUMENT/3690/6376290604221000 | | | 00) | | | 3- AUTOTURN EXHIBIT (DYNAMIC ENVELOPE AND THE VEHICLE?S | | | WHEEL PATH) FOR THE SANITATION SERVICE, FRONT LOADER | | | TRUCK WITH THE FOLLOWING SPECS: | | | - DUAL AXLES | | | - TRUCK LENGTH: 35 FT | | | - TRUCK WIDTH: 11 FT | | | - TURNING RADIUS: | | | - SAE TURNING RADIUS: 32.5 FT | | | - CURB-TO-CURB DIAMETER: 74 FT | | | - WALL-TO-WALL DIAMETER: 86.3 FT | | | 4- CONTINGENCY PLAN, FOR WHEN THE COMPACTOR IS OUT OF | | | SERVICE (I.E. CITY DUMPSTER, ROLL-OFF CONTAINER) | | | 5- DESIGNATED LOCATION FOR THE BULK ITEM PICK UP AND | | | RECYCLING CONTAINERS | | | 6- OWNERS AND/OR OCCUPANTS OF PROPERTY THAT REQUIRE | | | GREASE HAULING SERVICES SHALL ENSURE THAT THEIR GREASE | | | TANKS OR CONTAINERS REMAIN CLEAN, AND ARE ENCLOSED AND | | | NOT IN PUBLIC VIEW. | | | 7- IN CASE OF PROPOSING ADDITION OF ANY NEW CAN(S) IN | | | THE CITY`S RIGHT-OF-WAY , THE LOCATION AND QUANTITY OF | | | THE CAN(S) SHALL BE REVIEWED AND APPROVED BY PUBLIC | | | WORKS DEPARTMENT AND THE CAN(S) SHALL BE TYPE, SIZE AND | | | COLOR APPROVED BY PUBLIC WORKS DEPARTMENT. THE BUILDING | | | MAINTENANCE IS RESPONSIBLE TO MAINTAIN AND SERVICE THE | | | CAN(S). | | | 8- ALL THE PARKING STALL PAINTING SHALL COMPLY WITH THE | | | CITY`S MUNICIPAL CODE SECTION 94-485 AND FLORIDA | | | STATUES [553.5041 F.S.]. | | | 9- ALL STRIPING AND SIGNAGE SHALL MEET THE M.U.T.C.D. | | | LATEST EDITION. | | | 10- ALL PAVEMENT MARKING , SIGNING AND SIDEWALK DAMAGED | | | DURING CONSTRUCTION SHALL BE RESTORED. | | | | | | | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] | | | 561-822-2045 | | | |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
F |
Date |
08-09-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
08-09-2022 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
08-09-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-09 11:50:51 | | | | PLEASE PROVIDE THE FOLLOWINGS: | | | 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID | | | WASTE VOLUME PRODUCED ALONG WITH THE SIZE, TYPE AND | | | QUANTITY OF THE CONTAINER (I.E. DUMPSTER/COMPACTOR) | | | THAT WILL BE UTILIZED FOR THE SANITATION SERVICE. | | | 2- DUMPSTER ENCLOSURE DETAIL. DETAILS FOR SANITATION | | | SERVICE (I.E. SOLID WASTE CONTAINER(S) TYPE, COLLECTION | | | LOCATION, ETC.). FOR A FREESTANDING SITE DUMPSTER | | | ENCLOSURE, THE ENCLOSURE SHALL COMPLY WITH THE LATEST | | | REVISION OF CITY OF WEST PALM BEACH GENERAL | | | CONSTRUCTION-GARBAGE ENCLOSURE STANDARD, GC-7. (LINK TO | | | THE LATEST REVISION OF THE GC-7 DOCUMENT: HTTPS://WWW.W | | | PB.ORG/HOME/SHOWPUBLISHEDDOCUMENT/3690/6376290604221000 | | | 00) | | | 3- AUTOTURN EXHIBIT (DYNAMIC ENVELOPE AND THE VEHICLE?S | | | WHEEL PATH) FOR THE SANITATION SERVICE, FRONT LOADER | | | TRUCK WITH THE FOLLOWING SPECS: | | | - DUAL AXLES | | | - TRUCK LENGTH: 35 FT | | | - TRUCK WIDTH: 11 FT | | | - TURNING RADIUS: | | | - SAE TURNING RADIUS: 32.5 FT | | | - CURB-TO-CURB DIAMETER: 74 FT | | | - WALL-TO-WALL DIAMETER: 86.3 FT | | | 4- CONTINGENCY PLAN, FOR WHEN THE COMPACTOR IS OUT OF | | | SERVICE (I.E. CITY DUMPSTER, ROLL-OFF CONTAINER) | | | 5- DESIGNATED LOCATION FOR THE BULK ITEM PICK UP AND | | | RECYCLING CONTAINERS | | | 6- OWNERS AND/OR OCCUPANTS OF PROPERTY THAT REQUIRE | | | GREASE HAULING SERVICES SHALL ENSURE THAT THEIR GREASE | | | TANKS OR CONTAINERS REMAIN CLEAN, AND ARE ENCLOSED AND | | | NOT IN PUBLIC VIEW. | | | 7- IN CASE OF PROPOSING ADDITION OF ANY NEW CAN(S) IN | | | THE CITY`S RIGHT-OF-WAY , THE LOCATION AND QUANTITY OF | | | THE CAN(S) SHALL BE REVIEWED AND APPROVED BY PUBLIC | | | WORKS DEPARTMENT AND THE CAN(S) SHALL BE TYPE, SIZE AND | | | COLOR APPROVED BY PUBLIC WORKS DEPARTMENT. THE BUILDING | | | MAINTENANCE IS RESPONSIBLE TO MAINTAIN AND SERVICE THE | | | CAN(S). | | | 8- ALL THE PARKING STALL PAINTING SHALL COMPLY WITH THE | | | CITY`S MUNICIPAL CODE SECTION 94-485 AND FLORIDA | | | STATUES [553.5041 F.S.]. | | | 9- ALL STRIPING AND SIGNAGE SHALL MEET THE M.U.T.C.D. | | | LATEST EDITION. | | | 10- ALL PAVEMENT MARKING , SIGNING AND SIDEWALK DAMAGED | | | DURING CONSTRUCTION SHALL BE RESTORED. | | | | | | | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] | | | 561-822-2045 | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
F |
Date |
05-06-2023 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
05-06-2023 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
05-06-2023 |
Time |
14:50 |
Sent To |
|
|
| Notes |
| 2023-05-06 14:48:52 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE | | | 3-28-2023 SUBMITTAL: | | | | | | 1. [NOT SATISFIED] THE CITY'S OFFICIAL VERTICAL DATUM | | | IS NGVD1929. THE CITY HAS ALLOWED THE USE OF NAVD1988 | | | AS LONG AS THE CONVERSION EQUATION TO NGVD1929 AT THE | | | PROJECT LOCATION IS PROVIDED. PROVIDE THE VERTICAL | | | DATUM CONVERSION TO NGVD1929 ON THE SURVEY. | | | | | | 2. [PARTIALLY SATISFIED - RECESSED DOORS NOT SHOWN ON | | | THE ENGINEERING PLANS.] ENGINEERING PLAN AND LANDSCAPE | | | PLAN DO NOT MATCH ARCHITECTURAL SITE PLAN. | | | | | | 3. [SATISFIED] 24 FEET NEEDED AS BACKUP SPACE FOR | | | 90-DEGREE PARKING. | | | | | | 4. [SATISFIED] ENGINEERING PLAN SHOWS DOORS OPENING AT | | | BOTTOM OF EXTERIOR STAIRS. | | | | | | 5. [SATISFIED] SHOW UTILITIES ON THE LANDSCAPE PLANS | | | AND COORDINATE PLANTINGS WITH THE UTILITIES. | | | | | | 6. [NOT SATISFIED - NOT FOUND ON SHEET C2.1] PROVIDE A | | | CONTROL STRUCTURE DETAIL. | | | | | | 7. [NOT SATISFIED - NOT FOUND ON SHEET C1.1] PROVIDE | | | CROSS SECTIONS FROM CENTERLINE OF RIGHTS OF WAY TO THE | | | BUILDING FACES. SHOW AND LABEL SURFACE FEATURES, GRADE | | | BREAKS, GENERAL SURFACE SLOPES, FINISHED FLOOR | | | ELEVATION, RIGHT OF WAY LINES WITH THE STREET | | | IDENTIFIED, DIMENSIONS FROM RIGHT OF WAY TO SURFACE | | | FEATURES. | | | | | | 8. [SATISFIED] IDENTIFY THE GREEN DASHED LINE RUNNING | | | NORTH-SOUTH BETWEEN THE GREASE TRAPS AND DRAINAGE | | | SYSTEM ON SHEET C1.1. | | | | | | 9. [NOT SATISFIED] SHOW MILL AND RESURFACE LIMITS. | | | | | | 10. [PARTIALLY SATISFIED] CALLOUT WHERE NEW OR | | | REPLACEMENT SIDEWALK WILL BE CONSTRUCTED AS PART OF | | | THIS PROJECT. ADDITIONAL COMMENT: DRIVEWAY FOR THIS | | | DEVELOPMENT IS NOT IN THE SAME LOCATION AS THE PROPOSED | | | PARKING LOT THAT IS SHOWN ON THE STREETSCAPE PLANS. THE | | | 6-INCH THICK SIDEWALK ACROSS THE DRIVEWAY WILL NOT LINE | | | UP WITH THIS DEVELOPMENT. | | | | | | NEW COMMENTS (3-28-2023 SUBMITTAL): | | | | | | 11. THE CITY DOES NOT ALLOW THE USE OF BLEEDERS WITH | | | EXFILTRATION TRENCH SYSTEMS. | | | | | | 12. REMOVE THE LARGE BLACK ARROW ON NORTH SIDE OF | | | BUILDING ON SHEET C1.1. | | | | | | 13. WEST INVERT MISSING FOR STRUCTURE CS-2. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | [email protected] | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
08-11-2022 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
08-11-2022 |
Time |
06:47 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
08-11-2022 |
Time |
06:51 |
Sent To |
|
|
| Notes |
| 2022-08-11 06:50:55 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | 1. THE CITY?S OFFICIAL VERTICAL DATUM IS NGVD1929. THE | | | CITY HAS ALLOWED THE USE OF NAVD1988 AS LONG AS THE | | | CONVERSION EQUATION TO NGVD1929 AT THE PROJECT LOCATION | | | IS PROVIDED. PROVIDE THE VERTICAL DATUM CONVERSION TO | | | NGVD1929 ON THE SURVEY. | | | | | | 2. ENGINEERING PLAN AND LANDSCAPE PLAN DO NOT MATCH | | | ARCHITECTURAL SITE PLAN. | | | | | | 3. 24 FEET NEEDED AS BACKUP SPACE FOR 90-DEGREE | | | PARKING. | | | | | | 4. ENGINEERING PLAN SHOWS DOORS OPENING AT BOTTOM OF | | | EXTERIOR STAIRS. | | | | | | 5. SHOW UTILITIES ON THE LANDSCAPE PLANS AND COORDINATE | | | PLANTINGS WITH THE UTILITIES. | | | | | | 6. PROVIDE A CONTROL STRUCTURE DETAIL. | | | | | | 7. PROVIDE CROSS SECTIONS FROM CENTERLINE OF RIGHTS OF | | | WAY TO THE BUILDING FACES. SHOW AND LABEL SURFACE | | | FEATURES, GRADE BREAKS, GENERAL SURFACE SLOPES, | | | FINISHED FLOOR ELEVATION, RIGHT OF WAY LINES WITH THE | | | STREET IDENTIFIED, DIMENSIONS FROM RIGHT OF WAY TO | | | SURFACE FEATURES. | | | | | | 8. IDENTIFY THE GREEN DASHED LINE RUNNING NORTH-SOUTH | | | BETWEEN THE GREASE TRAPS AND DRAINAGE SYSTEM ON SHEET | | | C1.1. | | | | | | 9. SHOW MILL AND RESURFACE LIMITS. | | | | | | 10. CALLOUT WHERE NEW OR REPLACEMENT SIDEWALK WILL BE | | | CONSTRUCTED AS PART OF THIS PROJECT. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP | | | CRITERIA. STORMWATER CALCULATIONS WILL BE REVIEWED WITH | | | THE ENGINEERING PERMIT SUBMITTAL. | | | | | | 2. PROVIDE COPY OF SFWMD ERP PERMIT MODIFICATION BEFORE | | | START OF CONSTRUCTION. | | | | | | 3. PROVIDE EROSION AND SEDIMENT CONTROL PLAN WITH THE | | | ENGINEERING PERMIT SUBMITTAL. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | 561-351-0510 (M) | | | [email protected] | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
08-09-2022 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
08-09-2022 |
Time |
07:53 |
Rev Time |
|
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-09 08:02:50 | 1. SURVEY SHOULD BE JUST OF SUBJECT SITE. | | | 2. SANITARY SERVICES NEED TO BE SEPARATE. | | | 3. CITY DOES NOT WANT ADDITIONAL WATER MAIN IN ALLEY. | | | RELOCATE SERVICES TO N. RAILROAD AVE. | | | 4. DRIVEWAY FLAIR SHOULD NOT EXTEND INTO ADJOINING | | | PROPERTY. |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
08-10-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
08-10-2022 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
08-10-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-10 22:26:10 | TRAFFIC COMMENTS | | | 1) CORRECT THE EXEMPTION REFERENCE AS IT IS TRAFFIC | | | CONCURRENCY EXCEPTION AREA (TCEA), NOT CRA. | | | 2) SCHEDULE A METHODOLOGY MEETING. A FULL TRAFFIC STUDY | | | IS NEEDED; EXEMPTION FROM COUNTY CONCURRENCY DOES NOT | | | PRECLUDE THE CITY TO REQUEST MORE IN-DEPTH ANALYSIS, | | | GIVEN THE SIGNIFICANT CHANGE IN LAND USE AND TRIP | | | GENERATION TOGETHER WITH IMPACT TO THE SURROUNDING | | | ROADWAY NETWORK | | | 3) ALL CONCERNS AND COMMENTS PROVIDED BY THE COUNTY IN | | | THE TPS LETTER SHALL BE ADDRESSED | | | 4) MORE DETAILED TRANSPORTATION DEMAND MANAGEMENT (TDM) | | | MEASURES SHALL BE DISCUSSED AND AGREED WITH CITY | | | PLANNING AND ENGINEERING DEPARTMENTS | | | 5) TRAFFIC SIGNAL WARRANT ANALYSES SHALL BE CONDUCTED | | | AT EACH IMPACTED UNSIGNALIZED INTERSECTION ALONG PALM | | | BEACH LAKES BLVD AND DIXIE HIGHWAY | | | | | | SITE COMMENTS | | | 6) PROVIDE A CLEAN TRANSPORTATION SPECIFIC SITE PLAN. | | | SHOWCASING TRANSPORTATION RELATED FEATURES (E.G. | | | ROADWAY, DRIVING AISLES, PARKING STALLS, SIDEWALK, | | | CURB, GUTTER, DRIVEWAY, GATES, ETC.) PROPERLY LABELED | | | AND DIMENSIONED. PLEASE DO NOT SHOW ALL UNDERGROUND | | | UTILITY LAYERS | | | 7) IN THE TRANSPORTATION SITE PLAN, PLEASE SHOWCASE | | | BASIC CURB DETAILS (E.G. DRIVEWAY, CURB CUTS, PAVEMENT | | | MARKINGS, PARKING STALLS, ETC.) ON THE OPPOSITE SIDE OF | | | THE ROADS SURROUNDING THE PROPOSED DEVELOPMENT. | | | INCLUDING ALLEYWAYS. | | | 8) PROVIDE AUTOTURN ANALYSIS FOR GARBAGE TRUCK AND/OR | | | DELIVERY VEHICLES SERVICING THE PROPOSED DEVELOPMENT | | | WITH VEHICLE DYNAMIC ENVELOPES AND WHEEL PATHS CLEARLY | | | DISTINCT AND DEFINED. ANALYSIS SHOULD BE PROVIDED IN A | | | SEPARATE FILE/DRAWING. PLEASE PROVIDE DOCUMENT NAME AND | | | SHEET NUMBER SHOWCASING THE ANALYSIS | | | 9) CLEARLY MARK AND DIMENSION THE DESIGNATED LOADING | | | ZONE | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
05-01-2023 |
|
|
Cont ID |
|
| Sent By |
ckimmerl |
Date |
05-01-2023 |
Time |
12:47 |
Rev Time |
0.00 |
| Received By |
ckimmerl |
Date |
05-01-2023 |
Time |
12:46 |
Sent To |
|
|
| Notes |
| 2023-05-01 12:47:24 | 1. FLOOR PLAN DOES NOT MATCH SITE PLAN, PLEASE | | | COORDINATE PLANS APPROPRIATELY. | | | - SHOWS STAIRWELL IN PATH OF DRIVE AISLE AND | | | INGRESS/EGRESS | | | RESPONSE: ACKNOWLEDGED. SEE UPDATED PLANS THAT ARE | | | FULLY RECONCILED. | | | 1. ZONING REVIEW 5.1.23 ??? [SATISFIED] | | | - SHOWS TWO-WAY TRAFFIC FLOW | | | RESPONSE: ACKNOWLEDGED | | | 1A. ZONING REVIEW 5.1.23 ??? [SATISFIED] | | | | | | - SHOWS 8 PARKING SPACES ON SITE, DOES NOT PROVIDE ADA | | | SPACE | | | RESPONSE: ACKNOWLEDGED. A SINGLE ADA PARKING SPACE HAS | | | BEEN PROVIDED AT THE REAR OF THE SITE. ALL OTHER | | | REQUIRED PARKING SPACES ARE TO BE PROVIDED WITHIN THE | | | OFF-SITE PARKING LOTS, SUBJECT TO SEPARATE APPROVAL. | | | 1B. ZONING REVIEW 5.1.23 ??? [SATISFIED] | | | | | | ??? SERVICE COURT/PARKING LOT APPEARS TO EXTEND ACROSS | | | THE PROPERTY FROM 8TH TO ALLEY | | | RESPONSE: ACKNOWLEDGED | | | 1C. ZONING REVIEW 5.1.23 ??? [SATISFIED] | | | | | | | | | 2. SETBACKS | | | - PLEASE PROVIDE SETBACK LINES ON SITE PLAN AND | | | ARCHITECTURAL DRAWINGS | | | RESPONSE: ACKNOWLEDGED. ALL SETBACKS HAVE BEEN | | | PROVIDED ON THE SITE PLAN. | | | 2. ZONING REVIEW 5.1.23 ??? [SATISFIED] | | | | | | - SETBACKS NEED TO BE RECALCULATED AND LABELED | | | RESPONSE: ACKNOWLEDGED. SEE UPDATED SITE PLAN. | | | 2A. ZONING REVIEW 5.1.23 ??? [SATISFIED] | | | | | | - NORTH RAILROAD AVENUE, REQUIRES 0FT SETBACK | | | RESPONSE: ACKNOWLEDGED. SITE DATA HAS BEEN UPDATED | | | ACCORDINGLY. | | | 2B. ZONING REVIEW 5.1.23 ??? [SATISFIED] | | | | | | - REAR, REQUIRES 20FT SETBACK | | | RESPONSE: ACKNOWLEDGED. SITE DATA HAS BEEN UPDATED | | | ACCORDINGLY. | | | 2C. ZONING REVIEW 5.1.23 ??? [PARTIALLY SATISFIED] | | | PLEASE ADJUST THIS TO READ AS SIDE INTERIOR SETBACK. | | | WILL REQUIRE 25 FT. | | | | | | - ALLEY FOR COMMERCIAL USES, REQUIRES 5FT SETBACK | | | RESPONSE: ACKNOWLEDGED. SITE DATA HAS BEEN UPDATED | | | ACCORDINGLY. | | | 2D. ZONING REVIEW 5.1.23 ??? [SATISFIED] | | | | | | - SIDE RESIDENTIAL STREET (10TH), REQUIRES 10FT | | | RESPONSE: ACKNOWLEDGED. SITE DATA HAS BEEN UPDATED | | | ACCORDINGLY. | | | 2E. ZONING REVIEW 5.1.23 ??? [SATISFIED] | | | | | | | | | 3. SITE PLAN MENTIONS PARKING REQUIREMENTS BEING MET | | | WITH VALET SERVICE OFFSITE, PLEASE INDICATE WHERE THE | | | OFF-SITE PARKING IS LOCATED. - IS ALL OF THE PARKING | | | UNDER A VALET SERVICE? | | | RESPONSE: ACKNOWLEDGED. THE OFFSITE PARKING WILL BE | | | PROVIDED IN THE ADJACENT PARKING LOTS WHICH AREA A | | | COMBINATION OF PUBLIC ACCESS AND VALET PARKING. | | | 3. ZONING REVIEW 5.1.23 ??? [SATISFIED] OFFSITE PARKING | | | TO GO BEFORE DAC | | | | | | | | | 4. WHERE IS THE LOADING OPERATION LOCATED? DETAIL IS | | | SHOWN ON SITE PLAN, BUT NO LOCATION INDICATED. PLEASE | | | CLARIFY IS THE SERVICE COURT ALSO SERVING AS LOADING | | | SPACE? | | | RESPONSE: ACKNOWLEDGED. THE LOADING SPACE IS LOCATED | | | ADJACENT TO THE REAR OF THE BUILDING | | | 4. ZONING REVIEW 5.1.23 ??? [NOT SATISFIED] WHAT IS THE | | | DEPTH OF THE 12FT. WIDE SPACE AT THE REAR OF THE | | | BUILDING? IS THIS THE LOADING? LOADING SPACE OPERATES | | | AS THE TURNAROUND SPACE FOR THE ADA PARKING, IF ENOUGH | | | DEPTH IS PROVIDED. | | | OPERATIONAL CONCERNS WITH LOADING AND ADA. IF EITHER | | | THE PARKING SPOT OR LOADING BAY ARE OCCUPIED, NEITHER | | | USER CAN EFFECTIVELY MANEUVER IN OR OUT. | | | LOADING CAN BE DONE FROM ALLEYWAY. | | | ADA PATH TO AN ACCESSIBLE ENTRY TO BUILDING APPEARS TO | | | BE INEFFICIENT OR POSES MANY OBSTACLES | | | | | | | | | 5. PHOTOMETRIC ANALYSIS SHOWS SOUTHEASTERN CORNER OF | | | PROPERTY ALONG ALLEY/ADJACENT TO HVL WITH AREAS BELOW | | | REQUIRED 0.6 FOOTCANDLES. | | | RESPONSE: ACKNOWLEDGED. SEE UPDATED PHOTOMETRIC PLAN. | | | 5. ZONING REVIEW 5.1.23 ??? [NOT SATISFIED] | | | MINOR FIX NEEDED: PHOTOMETRIC PLAN SHOWS 0.5 FOOTCANDLE | | | ADJACENT TO ADA SPACE/AISLE. | | | | | | | | | 6. PLEASE PROVIDE AUTOTURN ANALYSIS FOR | | | SANITATION/LOADING ACCESS | | | RESPONSE: ACKNOWLEDGED. | | | 6. ZONING REVIEW 5.1.23 ??? [NOT SATISFIED] NO AUTOTURN | | | ANALYSIS PROVIDED | | | | | | | | | 7. PLEASE INDICATE WHERE REQUIRED BIKE PARKING SPACES | | | ARE LOCATED. | | | RESPONSE: ACKNOWLEDGED. BIKE PARKING HAS BEEN ADDED AT | | | THE NORTH END OF THE SITE ADJACENT TO THE 8TH STREET | | | SIDEWALK. | | | 7. ZONING REVIEW 5.1.23 ??? [SATISFIED] | | | | | | | | | 8. PLEASE PROVIDE STREETSCAPE LANDSCAPING DETAILS FOR N | | | RAILROAD AVE. AND 8TH ST. FRONTAGES. | | | RESPONSE: ACKNOWLEDGED. ALL HARDSCAPE AND LANDSCAPE | | | BACKGROUNDS HAVE BEEN ADDED ACCORDINGLY. | | | 8. ZONING REVIEW 5.1.23 ??? [SATISFIED] | | | | | | | | | 9. PLEASE PROVIDE COMPLETE LANDSCAPE PLAN WITH CHARTS | | | AND CALCULATIONS. | | | RESPONSE: ACKNOWLEDGED. SEE UPDATED LANDSCAPE | | | PLANS/LANDSCAPE DETAILS/TREE DISPOSITION PLANS WITH | | | ASSOCIATED DETAILS. | | | 9. ZONING REVIEW 5.1.23 ??? [PARTIALLY SATISFIED] | | | SEC.94-113(D.) AND SEC.94-113(G.) APPLIES | | | SEC. 94-443(A.)(1.) PROTECTIVE SCREEN WALLS AND | | | (2.)LANDSCAPE BUFFER APPLIES; THESE SECTIONS PROVIDE | | | MORE DETAIL ON THE REQUIREMENTS OF SEC. 94-113(G.) | | | PLEASE AMEND LP-1 & LP-2 TO REFLECT THE THREE | | | APPLICABLE CODE SECTIONS ABOVE AND THEIR REQUIREMENTS. | | | THE REFERENCE TO 94-442 CAN BE REMOVED. | | | PLEASE SHOW ON LP-1 THE LOCATION OF THE SHRUBS AND | | | TREES AS SHOWN ON SHEET 818 (SITE ANALYSIS EXHIBITS) | | | TRANSFORMERS AND HVL TO BE SCREENED BY LANDSCAPING | | | HEDGES | | | PLEASE PROVIDE HEIGHT DETAIL OF MASONRY WALL | | | | | | 10. 5FT. LANDSCAPE BUFFER BETWEEN ADJACENT TO | | | RESIDENTIAL USES REQUIRES INSTALLATION OF A WALL | | | RESPONSE: ACKNOWLEDGED. SEE UPDATED LANDSCAPE PLAN | | | WITH 5 FOOT WALL INCLUDED IN BUFFER DESIGN. | | | 10. ZONING REVIEW 5.1.23 ??? [PARTIALLY SATISFIED] | | | PLEASE PROVIDE HEIGHT DETAIL OF MASONRY WALL IN | | | DRAWINGS | | | | | | | | | NEW ZONING COMMENTS 5.1.23: | | | 1. PLEASE PROVIDE PROJECTION DETAILS OR DIMENSIONS FOR | | | THE CANOPY ELEMENTS SHOWN ON THE ELEVATIONS. BE SURE | | | THAT THESE ELEMENTS MEET THE STANDARDS IN SEC. 94-109 | | | TABLE IV-5. ELEVATIONS PROVIDED, PLEASE SHOW | | | PROJECTIONS. | | | | | | 2. ANY ROOFTOP MECHANICAL EQUIPMENT SHALL BE SCREENED | | | FROM VIEW. PER SEC. 94-109 PROJECTION, VERTICAL: | | | MECHANICAL EQUIPMENT AND APPURTENANCES NECESSARY TO THE | | | OPERATION OR MAINTENANCE OF THE BUILDING OR STRUCTURE | | | ITSELF SUCH AS, BUT NOT LIMITED TO, COOLING TOWERS, | | | ELEVATORS, STAIRS AND MECHANICAL PENTHOUSES, VENT | | | STACKS AND ANTENNAS SHALL BE ENCLOSED AND SCREENED IN | | | SUCH A MANNER THAT THE ENCLOSURE IS DESIGNED AS AN | | | INTEGRAL PART OF THE OVERALL BUILDING DESIGN. | | | | | | CHRIS KIMMERLY, AICP | | | URBAN DESIGN PLANNER | | | 822.1426 [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
08-08-2022 |
|
|
Cont ID |
|
| Sent By |
ckimmerl |
Date |
08-08-2022 |
Time |
12:11 |
Rev Time |
|
| Received By |
ckimmerl |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-08 12:08:56 | 1. FLOOR PLAN DOES NOT MATCH SITE PLAN, PLEASE | | | COORDINATE PLANS APPROPRIATELY. | | | - SHOWS STAIRWELL IN PATH OF DRIVE AISLE AND | | | INGRESS/EGRESS | | | - SHOWS TWO-WAY TRAFFIC FLOW | | | - SHOWS 8 PARKING SPACES ON SITE, DOES NOT PROVIDE ADA | | | SPACE | | | - SERVICE COURT/PARKING LOT APPEARS TO EXTEND ACROSS | | | THE PROPERTY FROM 8TH TO ALLEY | | | | | | 2. SETBACKS | | | - PLEASE PROVIDE SETBACK LINES ON SITE PLAN AND | | | ARCHITECTURAL DRAWINGS | | | - SETBACKS NEED TO BE RECALCULATED AND LABELED | | | - NORTH RAILROAD AVENUE, REQUIRES 0FT SETBACK | | | - REAR, REQUIRES 20FT SETBACK | | | - ALLEY FOR COMMERCIAL USES, REQUIRES 5FT SETBACK | | | - SIDE RESIDENTIAL STREET (10TH), REQUIRES 10FT | | | | | | 3. SITE PLAN MENTIONS PARKING REQUIREMENTS BEING MET | | | WITH VALET SERVICE OFFSITE, PLEASE INDICATE WHERE THE | | | OFF-SITE PARKING IS LOCATED. | | | - IS ALL OF THE PARKING UNDER A VALET SERVICE? | | | | | | 4. WHERE IS THE LOADING OPERATION LOCATED? DETAIL IS | | | SHOWN ON SITE PLAN, BUT NO LOCATION INDICATED. PLEASE | | | CLARIFY IS THE SERVICE COURT ALSO SERVING AS LOADING | | | SPACE? | | | | | | 5. PHOTOMETRIC ANALYSIS SHOWS SOUTHEASTERN CORNER OF | | | PROPERTY ALONG ALLEY/ADJACENT TO HVL WITH AREAS BELOW | | | REQUIRED 0.6 FOOTCANDLES. | | | | | | 6. PLEASE PROVIDE AUTOTURN ANALYSIS FOR | | | SANITATION/LOADING ACCESS | | | | | | 7. PLEASE INDICATE WHERE REQUIRED BIKE PARKING SPACES | | | ARE LOCATED. | | | | | | 8. PLEASE PROVIDE STREETSCAPE LANDSCAPING DETAILS FOR N | | | RAILROAD AVE. AND 8TH ST. FRONTAGES. | | | | | | 9. PLEASE PROVIDE COMPLETE LANDSCAPE PLAN WITH CHARTS | | | AND CALCULATIONS. | | | | | | 10. 5FT. LANDSCAPE BUFFER BETWEEN ADJACENT TO | | | RESIDENTIAL USES REQUIRES INSTALLATION OF A WALL. |
|
|
| |