Plan Review Details - Project Z22070022
| Plan Review Stops For Project Z22070022 |
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
1 |
Status |
F |
Date |
08-09-2022 |
|
|
Cont ID |
|
| Sent By |
scwelter |
Date |
08-09-2022 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
05-04-2023 |
Time |
19:49 |
Sent To |
|
|
| Notes |
| 2022-08-09 13:35:58 | | | | | | | THE NORA PROJECT IS UNDER ONE DEVELOPER AND PARTS OF | | | THE PROJECT ARE SUBJECT TO THE PUBLIC ART REQUIREMENT: | | | Z22070021 | | | Z22070022 | | | Z22070023 | | | Z22070024 | | | Z22070025 | | | IT IS MY UNDERSTANDING THAT THE DEVELOPER WILL ADD | | | PUBLIC ART WORKS. POTENTIAL ART SITES NEED TO BE | | | IDENTIFIED ON EACH OF THE SITE PLAN(S) FOR SITE PLAN | | | APPROVAL(S). | | | PLEASE EMAIL [email protected] FOR AN ART ASSESSMENT | | | APPLICATION. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
05-04-2023 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
05-04-2023 |
Time |
19:50 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
05-04-2023 |
Time |
19:50 |
Sent To |
|
|
| Notes |
| 2023-05-04 19:51:44 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. NUMBER OF ACCESSIBLE PARKING SPACES. SITE PLAN SHEET | | | SP1 STATES THAT 1 ACCESSIBLE PARKING SPACE WILL BE | | | PROVIDED AND THAT IT WILL BE OFF?SITE VALET PARKING. | | | ACCESSIBLE SELF PARKING MUST BE PROVIDED AS A VALET MAY | | | NOT BE ABLE TO OPERATE A VEHICLE THAT HAS UNDERGONE | | | ACCESSIBILITY MODIFICATIONS NEEDED FOR THE OWNER. THE | | | PLANS SHALL SHOW WHERE THE PARKING SPACES ARE LOCATED, | | | INCLUDING THE ACCESSIBLE PARKING. THE MINIMUM NUMBER OF | | | ACCESSIBLE PARKING SPACES PROVIDED SHALL BE IN | | | ACCORDANCE WITH SECTION 208.2 OF FLORIDA ACCESSIBILITY | | | CODE. | | | | | | 3. LOCATION OF ACCESSIBLE PARKING SPACES. PER SECTION | | | 208.3 OF FLORIDA ACCESSIBILITY CODE, ACCESSIBLE PARKING | | | SPACES ARE TO BE LOCATED ON THE SHORTEST POSSIBLE ROUTE | | | OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE | | | ENTRANCE. THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL | | | COMPLY WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE | | | | | | 4. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND | | | OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT, | | | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF | | | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF | | | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE | | | VERIFIED. | | | | | | 5. THE ADDITION TO THE EXISTING BUILDING IS COVERED BY | | | CHAPTER 11 OF THE FLORIDA EXISTING BUILDING CODE. THE | | | HEIGHT AND/OR AREA INCREASE DUE TO THE PROPOSED | | | ADDITION SHALL NOT INCREASE THE TOTAL BUILDING HEIGHT | | | AND/OR AREA BEYOND THAT ALLOWED UNDER THE APPLICABLE | | | PROVISIONS OF CHAPTER 5 OF THE FLORIDA BUILDING CODE | | | FOR THE TYPE OF CONSTRUCTION USED. | | | | | | 6. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE | | | REQUIRED. FOR INFORMATION ON THE REQUIRED TYPE, SIZE | | | AND LOCATION, PLEASE CONTACT RYAN BROWN, CHIEF PLUMBING | | | INSPECTOR, DEVELOPMENT SERVICES DEPARTMENT, AT (561) | | | 805-6692, OR BY EMAIL: [email protected] | | | | | | 7. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, | | | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND | | | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, | | | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. | | | | | | 8. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND | | | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF | | | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL | | | NEIGHBORING PROPERTIES. | | | | | | 9. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT | | | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL | | | HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION | | | OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING, | | | CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT | | | (561) 805 6659, OR BY EMAIL: [email protected] | | | | | | 10. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT | | | TO ART LIFE ASSESSMENT UNDER THE CITY OF WEST PALM | | | BEACH ART IN PUBLIC PLACES (AIPP) PROGRAM. FOR ADVICE | | | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP | | | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC | | | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
08-10-2022 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
08-10-2022 |
Time |
20:53 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
08-10-2022 |
Time |
20:53 |
Sent To |
|
|
| Notes |
| 2022-08-10 21:08:03 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. EAST EXIT DOOR. THE EXIT DOOR APPEARS TO BE | | | DISCHARGING ONTO THE ADJACENT PROPERTY. THE EXIT SHALL | | | DISCHARGE ON THE OWNER'S PROPERTY OR ONTO THE RIGHT OF | | | WAY IN ORDER TO COMPLY WITH SECTION 1028.5 OF FLORIDA | | | BUILDING CODE. | | | | | | 3. NUMBER OF ACCESSIBLE PARKING SPACES. SITE PLAN SHEET | | | SP1 STATES THAT 1 ACCESSIBLE PARKING SPACE WILL BE | | | PROVIDED AND THAT IT WILL BE OFF?SITE VALET PARKING. | | | ACCESSIBLE SELF PARKING MUST BE PROVIDED AS A VALET MAY | | | NOT BE ABLE TO OPERATE A VEHICLE THAT HAS UNDERGONE | | | ACCESSIBILITY MODIFICATIONS NEEDED FOR THE OWNER. THE | | | PLANS SHALL SHOW WHERE THE PARKING SPACES ARE LOCATED, | | | INCLUDING THE ACCESSIBLE PARKING. THE MINIMUM NUMBER OF | | | ACCESSIBLE PARKING SPACES PROVIDED SHALL BE IN | | | ACCORDANCE WITH SECTION 208.2 OF FLORIDA ACCESSIBILITY | | | CODE. | | | | | | 4. LOCATION OF ACCESSIBLE PARKING SPACES. PER SECTION | | | 208.3 OF FLORIDA ACCESSIBILITY CODE, ACCESSIBLE PARKING | | | SPACES ARE TO BE LOCATED ON THE SHORTEST POSSIBLE ROUTE | | | OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE | | | ENTRANCE. THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL | | | COMPLY WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE | | | | | | 5. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND | | | OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT, | | | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF | | | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF | | | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE | | | VERIFIED. | | | | | | 6. THE ADDITION TO THE EXISTING BUILDING IS COVERED BY | | | CHAPTER 11 OF THE FLORIDA EXISTING BUILDING CODE. THE | | | HEIGHT AND/OR AREA INCREASE DUE TO THE PROPOSED | | | ADDITION SHALL NOT INCREASE THE TOTAL BUILDING HEIGHT | | | AND/OR AREA BEYOND THAT ALLOWED UNDER THE APPLICABLE | | | PROVISIONS OF CHAPTER 5 OF THE FLORIDA BUILDING CODE | | | FOR THE TYPE OF CONSTRUCTION USED. | | | | | | 7. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE | | | REQUIRED. FOR INFORMATION ON THE REQUIRED TYPE, SIZE | | | AND LOCATION, PLEASE CONTACT RYAN BROWN, CHIEF PLUMBING | | | INSPECTOR, DEVELOPMENT SERVICES DEPARTMENT, AT (561) | | | 805-6692, OR BY EMAIL: [email protected] | | | | | | 8. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, | | | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND | | | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, | | | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. | | | | | | 9. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND | | | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF | | | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL | | | NEIGHBORING PROPERTIES. | | | | | | 10. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT | | | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL | | | HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION | | | OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING, | | | CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT | | | (561) 805 6659, OR BY EMAIL: [email protected] | | | | | | 11. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT | | | TO ART LIFE ASSESSMENT UNDER THE CITY OF WEST PALM | | | BEACH ART IN PUBLIC PLACES (AIPP) PROGRAM. FOR ADVICE | | | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP | | | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC | | | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
3 |
Status |
F |
Date |
07-27-2023 |
|
|
Cont ID |
|
| Sent By |
lquinone |
Date |
07-27-2023 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
lquinone |
Date |
07-27-2023 |
Time |
15:43 |
Sent To |
|
|
| Notes |
| 2023-07-27 15:44:27 | O PROVIDE CCTV VIDEO OF EXISTING STORMWATER | | | INFRASTRUCTURE ALONG ENTIRE PROJECT FRONTAGE (CONDITION | | | OF SITE PLAN APPROVAL). |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
F |
Date |
04-11-2023 |
|
|
Cont ID |
|
| Sent By |
lquinone |
Date |
04-11-2023 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
lquinone |
Date |
04-11-2023 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2023-04-11 10:32:46 | NO RESPONSE LETTER WAS SUBMITTED. | | | | | | COMMENTS FROM LINDA M. QUINONES-CINTRON, PROJECT | | | COORDINATOR, ENGINEERING SERVICES AT 561-494-1085 | | | [email protected] | | | | | | CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY SEWER | | | ARE REQUIRED. | | | | | | PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND | | | STORMWATER PIPES ALONG ENTIRE PROJECT FRONTAGE. | | | | | | COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE | | | SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING | | | PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT | | | HIM AT 561-494-2262 OR [email protected] | | | | | | FOR FORMAL ENGINEERING SUBMITTAL , PLANS SHALL SHOW | | | PROPOSED LOCATIONS AND DIMENSIONS OF ALL WATER, | | | STORMWATER, AND SANITARY AND SEWER LINES, INCLUDING | | | STUBS TO EACH PROPERTY LINE FOR WATER AND SANITARY | | | SEWERS, THE MAKE AND MODEL OF ALL VALVES, METERS, AND | | | OTHERS DEVICES TO BE INSTALLED ON THE SYSTEM, CATCH | | | BASINS, CULVERTS, DITCHES INCLUDING GRADES, PIPES | | | SIZES, MATERIALS, ELEVATIONS, ASSUMPTIONS, | | | CALCULATIONS, INVERT ELEVATIONS FOR ALL INLETS AND | | | MANHOLES AND PROFILES OF SANITARY SEWER LINES. ALL | | | AVAILABLE ELEVATION SHALL BE SHOWN ON THE PROFILE VIEW. | | | DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN | | | VIEW FOR ALL SANITARY AND STORM SEWERS. ADDITIONALLY, | | | PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED | | | UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC, | | | ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION | | | FACILITIES LOCATED ON THE RIGHT-OF-WAY. PROVIDE PROFILE | | | AND CLEARANCES AT ALL UTILITY CROSSINGS. | | | | | | PLEASE CLOUD/HIGHLIGHT PLAN REVISIONS OR CHANGES IN | | | SCOPE FOR RESUBMITTAL OF DRAWINGS. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL , CUT AND CAP | | | UTILITIES NOT IN USE, AND REMOVE ANY ABANDONED UTILITY | | | LINES LARGER THAN 2 INCHES FROM CITY RIGHT OF WAY. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE DEDICATED | | | UTILITY EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO | | | PROPOSED UTILITY WATER METERS. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | ENLARGED VIEW ON PLANS OF PROPOSED LOCATION OF WATER | | | METER AND BACKFLOW PREVENTION. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, PLEASE CALLOUT | | | DOMESTIC BACKFLOW PREVENTER AS RPPA AND FIRE BACKFLOW | | | PREVENTER AS DCDA. SPECIFY LEAD FREE DESIGN ON ALL | | | BACKFLOWS. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES | | | NOI REQUIREMENTS WILL BE ENFORCED. | | | | | | -AN NOI IS REQUIRED FOR PROJECTS THAT: | | | 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS | | | THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF | | | DEVELOPMENT OR SALE; AND | | | 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE | | | STATE OR TO SURFACE WATERS OF THE STATE THROUGH A | | | MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4). | | | -THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF | | | CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION | | | THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL | | | SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT | | | OF THE 10-2 CERTIFICATION. IF THE ENGINEERING PLANS DO | | | NOT INCLUDE AN EROSION CONTROL PLAN, THEN THE | | | CONTRACTOR SHOULD SUBMIT ONE PRIOR TO RECEIVING THE | | | ENGINEERING PERMIT. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF | | | PROPOSED AND EXISTING WATER AND SEWER WITHIN RIGHT OF | | | WAY AND SHOW ANY CROSSINGS/CONFLICTS. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING | | | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT | | | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING | | | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED | | | LEAD-FREE DESIGN. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL CLEARLY SHOW ROAD | | | RIGHT OF WAY. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL PROVIDE SANITARY | | | ELEVATIONS AT MANHOLE TIE-IN. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES | | | ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY | | | LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT | | | PARCELS. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, IF WATER LINES ARE | | | BEING REPLACED IN ROW, SHOW ADJACENT PARCEL ADDRESSES. | | | | | | FOR FORMAL ENGINEERING SUBMITTAL, WHEN TRENCHING IN IN | | | CITY MAINTAINED ROADWAY AREAS ADD NOTE TO PROVIDE 50 | | | FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF | | | PROPOSED TRENCH PER CURRENT CITY OF WPB STANDARD DETAIL | | | GC-8. | | | | | | PLEASE RESPOND TO ALL COMMENTS IN WRITING AND INCLUDE | | | PROJECT NAME, ADDRESS AND PERMIT NUMBER (Z-XXXXXXXX). | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
07-27-2022 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
07-27-2022 |
Time |
|
Rev Time |
|
| Received By |
rrossano |
Date |
07-27-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-07-27 10:48:07 | Z22070022 - RESTAURANT, 439 7TH ST 7.26.22 SUB | | | COMMENTS FROM RICK ROSSANO, SR. PROJECT COORDINATOR, | | | ENGINEERING SERVICES AT 561-494-1098 [email protected] | | | GENERAL: | | | O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND | | | INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER | | | (Z-XXXXXXXX). | | | O THE CITY OF WEST PALM BEACH HAS A NUMBER OF | | | REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY | | | AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND | | | WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE | | | DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK | | | BELOW: | | | A. HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WP | | | B_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FUL | | | L-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97 | | | B1960045731D3658206F27451722716EF | | | B. THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE | | | FOUND HERE: | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | C. ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM | | | BEACH, FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, | | | ADOPTED SEPT. 22, 2008. (SUPPLEMENT NO. 18) | | | CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL, | | | SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER | | | SERVICE FACILITIES OF THE CITY. | | | THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE | | | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY | | | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, | | | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. | | | O AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR | | | MORE INFORMATION, REFER TO THE LINK BELOW: | | | A. HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PU | | | BLICATIONS/BACKFLOW-CROSS-CONNECTION- CONTROL-MANUAL | | | O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY | | | OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC | | | RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF | | | YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE | | | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL | | | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT | | | [email protected] OR 561-494-1079 FOR FURTHER | | | ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION | | | ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD | | | SURVEY, POT-HOLING, SOFT DIGS ETC. | | | | | | BACKFLOW ASSEMBLY AND METERS: | | | O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER | | | SERVICES AND WATER METERS, ALONG WITH WHAT IS HAPPENING | | | TO THEM. | | | O SHOW EXISTING AND PROPOSED DEDICATED UTILITY | | | EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO | | | PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO | | | STRUCTURES WITHIN EASEMENT. | | | O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION | | | OF WATER METER AND BACKFLOW | | | PREVENTION. | | | O BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY | | | OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER | | | METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO | | | PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE | | | INSTALLED ABOVE-GROUND ONLY. | | | O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE | | | NOTE USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA. | | | | | | WATER/WASTEWATER PLAN: | | | O PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE | | | STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC. | | | O PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND | | | DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND | | | SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH | | | PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE | | | AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS, | | | BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO | | | BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS, | | | DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS, | | | ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT | | | ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF | | | SANITARY SEWER LINES. | | | O GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR | | | SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE | | | PROFILE VIEW. | | | O DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN | | | VIEW FOR ALL SANITARY AND STORM SEWERS. | | | O SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT | | | MATERIAL. | | | O PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED | | | UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC, | | | ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION | | | FACILITIES LOCATED ON THE RIGHT-OF-WAY. | | | O PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER | | | AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD | | | DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS. | | | O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY | | | TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT | | | APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING | | | AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, | | | MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS | | | SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 | | | FOR WATER. | | | O PROVIDE FIRE FLOW TEST DATA. | | | O PROVIDE CCTV VIDEO OF EXISTING STORMWATER | | | INFRASTRUCTURE ALONG ENTIRE PROJECT FRONTAGE (CONDITION | | | OF SITE PLAN APPROVAL). | | | O CUT AND CAP UTILITIES NOT IN USE AND REMOVE ANY | | | ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY | | | ROW. | | | O WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL | | | BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY | | | PROPOSED LENGTH IN FEET. | | | O CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY | | | SEWER ARE REQUIRED. | | | O PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE | | | JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET. | | | O ADD NOTE TO PLANS SPECIFYING CITY?S DOWNSTREAM LIFT | | | STATION NUMBER. | | | O PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR | | | PROPOSED SANITARY LATERALS. | | | O LABEL WATER LINES AS PRIVATE WHERE APPLICABLE. | | | O PLEASE SHOW AND LABEL EXISTING AND PROPOSED GREASE | | | TRAPS (IF ANY). | | | O PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN | | | OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER. | | | | | | FORMAL ENGINEERING REVIEW: | | | O FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES | | | NOI REQUIREMENTS WILL BE ENFORCED. | | | - AN NOI IS REQUIRED FOR PROJECTS THAT: | | | - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS | | | THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF | | | DEVELOPMENT OR SALE; | | | - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE | | | STATE OR TO SURFACE WATERS OF THE STATE THROUGH A | | | MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4). | | | - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF | | | CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION | | | THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL | | | SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT | | | OF THE 10-2 CERTIFICATION. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF | | | WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING | | | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT | | | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING | | | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED | | | LEAD-FREE DESIGN. | | | O FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES | | | ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY | | | LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT | | | PARCELS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, IF WATER LINES ARE | | | BEING REPLACED IN ROW, SHOW ADJACENT PARCEL ADDRESSES. | | | O FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO PROVIDE | | | 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF | | | PROPOSED TRENCH IN CITY MAINTAINED ROADWAY AREAS PER | | | CITY OF WPB STANDARD DETAIL GC-8. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | CALCULATIONS OF PERVIOUS AND IMPERVIOUS AREAS FOR | | | PROPOSED IMPROVED AREAS. | | | | | | | | | | | | QUESTIONS AND COORDINATION CONTACTS: | | | O MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR WITH | | | CITY OF WPB PUBLIC UTILITIES, REGARDING PLACEMENT OF | | | BACKFLOW DEVICES AND WATER METERS. CONTACT HIM AT | | | 561-822-2262 OR [email protected] | | | O MIKE TECHNOW, PROJECT ENGINEER, PUBLIC UTILITIES | | | DEPARTMENT AT 561-494-1047 OR [email protected] | | | O TRACY WARD, SR. STORMWATER ENGINEER, ENGINEERING | | | SERVICES DEPT. AT 561-494-1120 OR [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
08-01-2022 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
08-01-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
08-01-2022 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2022-08-01 11:28:11 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE DEPARTMENT. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. THE FOLLOWING COMMENTS ARE INTENDED | | | TO PROVIDE GUIDANCE FOR BUILDING PLAN SUBMITTAL. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING(S) SHALL COMPLY | | | WITH THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION | | | CODE, INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE | | | CODES. | | | | | | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE | | | OCCUPANCY TYPE PER THE FLORIDA FIRE PREVENTION CODE. | | | | | | 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE | | | LOAD CALCULATION IS INCLUDED, AND THAT ADEQUATE WATER | | | SUPPLY IS EXISTING OR WILL BE PROVIDED. | | | | | | 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | THE PROPOSED LOCATION OF THE FIRE HYDRANT AND FDC SHALL | | | BE WITHIN 100' OF EACH OTHER AND CLOSELY COORDINATED | | | WITH THE BUREAU OF FIRE PREVENTION. | | | | | | 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER | | | THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY | | | ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM, | | | ENSURE THEY COMPLY WITH THE REQUIREMENTS OF F.A.C. 61G | | | AND SUBMITTED WITH THE MASTER PERMIT. | | | | | | 9A. THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE | | | LOCATIONS SHALL MEET AND BE INSTALLED PER THE | | | REQUIREMENTS OF NFPA 24 AND SHALL BE COORDINATED WITH | | | THE OFFICE OF FIRE MARSHAL, THE CITY'S ENGINEERS | | | OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S PLANNING | | | AND ZONING OFFICE. | | | | | | 10. COMPLETE LIFE SAFETY PLANS FOR THE OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, EXIT SEPARATION DISTANCES, COMMON PATHS OF | | | TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, EMERGENCY | | | LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE | | | EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES | | | AND EQUIPMENT. | | | | | | 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE | | | SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY | | | DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS. | | | | | | 12. TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEMS. | | | | | | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY | | | RADIO ENHANCEMENT SERVICES. | | | | | | 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM | | | RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT | | | COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL | | | DETERMINED BY THE AHJ. | | | | | | IF APPLICABLE, CONTACT WILL NEED TO BE MADE TO MARK | | | FILLA, PALM BEACH COUNTY PUBLIC SAFETY RADIO SYSTEMS | | | MANAGER, [email protected], 561-233-0837; AS OUR RADIOS | | | OPERATE ON THEIR SYSTEM FOR DETAILED RADIO FREQUENCY | | | AND INSTALLATION INSTRUCTIONS. | | | | | | 13. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL. | | | | | | 14. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
08-10-2022 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
08-10-2022 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
08-10-2022 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2022-08-10 13:11:14 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: 439 7TH ST NORA Z22070022 | | | AUGUST 10, 2022 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. PROVIDE A TREE SURVEY AND TREE DISPOSITION PLAN TO | | | IDENTIFY ALL EXISTING TREES AND PALMS. IF ON THE | | | ADJACENT PROPERTY, SHOW THEM ON THE LANDSCAPE PLAN PER | | | SECTION 94-442(B)(2)Q. | | | | | | 2. SHOW THE PROPERTY LINE CLEARLY ON THE SITE AND | | | LANDSCAPE PLAN. BUFFER TREES MUST BE WITHIN THE | | | PROPERTY LINE. | | | | | | 3. PROVIDE A DATA TABLE SHOWING ALL REQUIRED | | | INFORMATION FOR CODE COMPLIANCE REVIEW. | | | | | | 4. STREETSCAPE MUST BE PROVIDED ADJACENT TO THE | | | PROPERTY INCLUDING SIDEWALKS AND STREET TREES. | | | | | | 5. SHOW LOCATIONS OF ALL UTILITIES ON THE LANDSCAPE | | | PLAN, AS THERE ARE MULTIPLE CONFLICTS WITH REQUIRED | | | LANDSCAPING. | | | | | | 6. FOR BPD 5 DISTRICT, 12% PRIVATE OPEN SPACE IS | | | REQUIRED. SHOW LOCATION AND DETAILS. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE | | | STREET TREES AND RIGHT OF WAY LANDSCAPING AND | | | IRRIGATION APPROVED WITH THIS PETITION. | | | 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF | | | WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A | | | SEPARATE MAINTENANCE AGREEMENT WITH THE CITY. | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
1 |
Status |
P |
Date |
08-12-2022 |
|
|
Cont ID |
|
| Sent By |
mtechnow |
Date |
08-12-2022 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
mtechnow |
Date |
08-12-2022 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2022-08-12 11:22:02 | NO ISSUE WITH THE CONCEPTUAL LEVEL PLAN. PLEASE REFER | | | TO CHECKLIST PROVIDED BY RICK ROSSANO FOR ENG SUBMITTAL | | | GUIDELINES. |
|
|
| Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
| Rev No |
2 |
Status |
P |
Date |
04-13-2023 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
04-13-2023 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2023-04-13 10:40:46 | -RESPONSE LETTER SAID EXISTING FIRE HYDRANT NEAR | | | SOUTHEAST CORNER OF PROPERTY WAS ADDED TO ENGINEERING | | | PLANS, BUT STILL CANNOT FIND IT. ADD AT ENGINEERING | | | DEVELOPMENT SUBMITTAL. | | | -LABEL MONUMENT SIGN ON ENGINEERING PLANS AT | | | ENGINEERING DEVELOPMENT SUBMITTAL. | | | -ENGINEERING PLANS MAY NEED REVISION AT ENGINEERING | | | DEVELOPMENT SUBMITTAL. |
|
|
| Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
| Rev No |
1 |
Status |
F |
Date |
08-10-2022 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
08-10-2022 |
Time |
13:30 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-10 13:30:29 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | -ENSURE FDC IS ACCEPTABLE DISTANCE FROM CITY FIRE | | | HYDRANT. | | | -CLEARLY SHOW AND LABEL PROPERTY LINES ON PLANS. | | | -RECENT PICTURES SHOW CHAIN LINK FENCE AROUND PARTS OF | | | THE PROPERTY. WILL IT REMAIN? | | | -THERE APPEARS TO BE A PRIVATE FIRE HYDRANT NEAR | | | SOUTHEAST AREA OF PROPERTY. PLEASE LABEL IT ON | | | ENGINEERING PLAN. | | | -ON SHEET C1.1 LABEL THE UTILITY RUNNING UNDER THE BIKE | | | RACK AND NEAR THE CROSSWALK. | | | -SHOW UTILITIES ON LANDSCAPE PLAN AND ENSURE NO | | | CONFLICTS BETWEEN TREES AND UTILITIES. | | | -CALLOUT MINIMUM HORIZONTAL CLEARANCE DISTANCE BETWEEN | | | END OF WATER MAIN AND SEWER MANHOLE IN ALLEY. | | | -CURRENTLY THERE ARE UTILITY POLES AND OVERHEAD | | | UTILITIES ALONG NORTH SIDE OF BUILDING. THEY MAY | | | CONFLICT WITH PROPOSED IMPROVEMENTS. | | | -ADD SEWER LATERAL CLEANOUT ADJACENT PROPERTY LINE. | | | -SITE PLAN SHOWS DUMPSTER DETAIL, BUT DOES NOT SHOW | | | LOCATION ON PLAN. | | | -ARCHITECTURAL PERSPECTIVE 1 SHOWS LARGE NORA MONUMENT | | | SIGN, BUT IT IS NOT SHOWN AND LABELED ON PLAN SETS. | | | -ON LANDSCAPE PLAN, CLEARLY SHOW AREAS OF LANDSCAPE AND | | | HARDSCAPE. | | | RESPECTFULLY, | | | MARK HURLEY | | | [email protected] |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
2 |
Status |
F |
Date |
04-28-2023 |
|
|
Cont ID |
|
| Sent By |
|
Date |
04-28-2023 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
04-28-2023 |
Time |
|
Sent To |
|
|
| Notes |
| 2023-05-03 16:00:32 | PLEASE PROVIDE: | | | 1- LOCATION AND ORIENTATION OF THE DUMPSTER ENCLOSURE | | | ON THE SITE PLAN ALONG WITH THE STAGING AREA FOR THE | | | DUMPSTERS, WHERE THEY GET SERVICED. | | | 2- AUTOTURN EXHIBIT (DYNAMIC ENVELOPE AND THE VEHICLE?S | | | WHEEL PATH) FOR THE SANITATION SERVICE, FRONT LOADER | | | TRUCK WITH THE FOLLOWING SPECS: | | | - DUAL AXLES | | | - TRUCK LENGTH: 35 FT | | | - TRUCK WIDTH: 11 FT | | | - TURNING RADIUS: | | | - SAE TURNING RADIUS: 32.5 FT | | | - CURB-TO-CURB DIAMETER: 74 FT | | | - WALL-TO-WALL DIAMETER: 86.3 FT | | | 3- DESIGNATED LOCATION FOR THE BULK ITEM PICK UP AND | | | RECYCLING CONTAINERS | | | | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] | | | 561-822-2045 | | | |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
F |
Date |
08-09-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
08-09-2022 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
08-09-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-09 11:34:21 | PLEASE PROVIDE: | | | 1- LOCATION AND ORIENTATION OF THE DUMPSTER ENCLOSURE | | | ON THE SITE PLAN ALONG WITH THE STAGING AREA FOR THE | | | DUMPSTERS, WHERE THEY GET SERVICED. | | | 2- AUTOTURN EXHIBIT (DYNAMIC ENVELOPE AND THE VEHICLE?S | | | WHEEL PATH) FOR THE SANITATION SERVICE, FRONT LOADER | | | TRUCK WITH THE FOLLOWING SPECS: | | | - DUAL AXLES | | | - TRUCK LENGTH: 35 FT | | | - TRUCK WIDTH: 11 FT | | | - TURNING RADIUS: | | | - SAE TURNING RADIUS: 32.5 FT | | | - CURB-TO-CURB DIAMETER: 74 FT | | | - WALL-TO-WALL DIAMETER: 86.3 FT | | | 3- DESIGNATED LOCATION FOR THE BULK ITEM PICK UP AND | | | RECYCLING CONTAINERS | | | 4- OWNERS AND/OR OCCUPANTS OF PROPERTY THAT REQUIRE | | | GREASE HAULING SERVICES SHALL ENSURE THAT THEIR GREASE | | | TANKS OR CONTAINERS REMAIN CLEAN, AND ARE ENCLOSED AND | | | NOT IN PUBLIC VIEW. | | | 5- IN CASE OF PROPOSING ADDITION OF ANY NEW CAN(S) IN | | | THE CITY`S RIGHT-OF-WAY , THE LOCATION AND QUANTITY OF | | | THE CAN(S) SHALL BE REVIEWED AND APPROVED BY PUBLIC | | | WORKS DEPARTMENT AND THE CAN(S) SHALL BE TYPE, SIZE AND | | | COLOR APPROVED BY PUBLIC WORKS DEPARTMENT. THE BUILDING | | | MAINTENANCE IS RESPONSIBLE TO MAINTAIN AND SERVICE THE | | | CAN(S). | | | 6- ALL THE PARKING STALL PAINTING SHALL COMPLY WITH THE | | | CITY`S MUNICIPAL CODE SECTION 94-485 AND FLORIDA | | | STATUES [553.5041 F.S.]. | | | 7- ALL STRIPING AND SIGNAGE SHALL MEET THE M.U.T.C.D. | | | LATEST EDITION. | | | 8- ALL PAVEMENT MARKING , SIGNING AND SIDEWALK DAMAGED | | | DURING CONSTRUCTION SHALL BE RESTORED. | | | | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] | | | 561-822-2045 | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
F |
Date |
05-06-2023 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
05-06-2023 |
Time |
08:15 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
05-06-2023 |
Time |
08:22 |
Sent To |
|
|
| Notes |
| 2023-05-06 08:18:01 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE | | | 3-28-2023 SUBMITTAL: | | | | | | 1. [SATISFIED] CHECK THE PARCEL NUMBER(S) LISTED IN THE | | | JUSTIFICATION STATEMENT. | | | | | | 2. [SATISFIED] THE REQUEST IN THE JUSTIFICATION | | | STATEMENT DESCRIBES EXPANDING THE EXISTING COMMERCIAL | | | BUILDING INTO A RESTAURANT USE. THE SURVEY SHOWS THE | | | EXISTING BUILDING 0.7 FEET SETBACK FROM THE NORTH | | | PROPERTY LINE. THE SITE PLAN SHOWS THE BUILDING SETBACK | | | AT LEAST 5 FEET FROM THE NORTH PROPERTY LINE. | | | | | | 3. [NOT SATISFIED] PROVIDE CROSS SECTIONS FROM | | | CENTERLINE OF RIGHTS OF WAY TO THE BUILDING FACES. SHOW | | | AND LABEL SURFACE FEATURES, GRADE BREAKS, GENERAL | | | SURFACE SLOPES, FINISHED FLOOR ELEVATION, RIGHT OF WAY | | | LINES WITH THE STREET IDENTIFIED, DIMENSIONS FROM RIGHT | | | OF WAY TO SURFACE FEATURES. | | | | | | 4. [SATISFIED - STREETSCAPE PROJECT WILL BE | | | CONSTRUCTING A PIPE STUB OUT TO WITHIN 5 FEET OF THE | | | PROPERTY LINE.] PROVIDE THE TOP AND BOTTOM ELEVATIONS | | | AND VERTICAL CLEARANCE BETWEEN THE PROPOSED OUTFALL | | | PIPE AND OTHER UTILITIES CROSS BE THE OUTALL PIPE. | | | | | | 5. [NOT SATISFIED] THE ROOF DRAIN SYSTEM SHOULD CONNECT | | | DIRECTLY INTO THE DRAINAGE SYSTEM. | | | | | | 6. [NOT SATISFIED] PROVIDE DETAIL OF THE CONTROL | | | STRUCTURE. | | | | | | 7. [SATISFIED] SHOW UTILITIES ON THE LANDSCAPE PLANS | | | AND COORDINATE PROPOSED PLANTINGS WITH THE UTILITY | | | LAYOUT. | | | | | | 8. [SATISFIED] DOOR ON EAST WALL APPEARS TO OPEN OVER | | | THE PROPERTY LINE. | | | | | | 9. [SATISFIED] SHOW AND LABEL PROPERTY LINES, RIGHT OF | | | WAY LINES, ALLEY WIDTH. | | | | | | 10. [NOT SATISFIED - INSUFFICIENT GRADES PROVIDED TO | | | DETERMINE SURFACE SLOPES.] WILL PORTION OF THE PATIO | | | NEED TO BE SLOPED A MAXIMUM OF 2 PERCENT FOR ADA | | | ACCESSIBILITY. SHOW WHERE THAT ADA PATH(S) WILL BE. | | | | | | 11. [NOT SATISFIED] REMOVE THE EXISTING DRIVEWAY APRON | | | ON 7TH STREET. CONSTRUCT CURBING TO MATCH ADJACENT CURB | | | TYPE. | | | | | | 12. [NOT SATISFIED] THE CITY'S OFFICIAL VERTICAL DATUM | | | IS NGVD1929. THE CITY HAS ALLOWED THE USE OF NAVD1988 | | | AS LONG AS THE CONVERSION EQUATION TO NGVD1929 AT THE | | | PROJECT LOCATION IS PROVIDED. PROVIDE THE VERTICAL | | | DATUM CONVERSION TO NGVD1929 ON THE SURVEY. | | | | | | 13. [NOT SATISFIED] SHOW MILL AND RESURFACE LIMITS. | | | | | | 14.[NOT SATISFIED] CALL OUT WHERE NEW OR REPLACEMENT | | | SIDEWALK WILL BE CONSTRUCTED AS PART OF THIS PROJECT. | | | | | | NEW COMMENTS (3/28/2023 SUBMITTAL): | | | | | | 15. WHEN PREPARING THE WRITTEN RESPONSES FOR ALL OF THE | | | COMMENTS, INCLUDE THE SHEET/PLAN NUMBER AND THE | | | QUADRANT (UPPER LEFT, UPPER RIGHT, LOWER LEFT, LOWER | | | RIGHT) ON THE SHEET WHERE THE INFORMATION IS SHOWN. | | | | | | 16. PROVIDE A DEMOLITION PLAN. | | | | | | 17. THE CITY DOES NOT ALLOW BLEEDERS WITH EXFILTRATION | | | TRENCH SYSTEMS. | | | | | | 18. SHOW THE OUTLINE OF THE EXFILTRATION TRENCHES AT | | | THEIR DESIGN WIDTHS ON THE PLANS. | | | | | | 19. PROVIDE A DETAIL OF THE EXFILTRATION TRENCH LISTING | | | THE TOP AND BOTTOM ELEVATIONS AND WIDTH OF THE TRENCH. | | | | | | 20. CIVIL PLAN DOES NOT MATCH THE SITE PLAN WITH | | | REGARDS TO THE DOOR ON THE NORTH WALL OF THE BUILDING. | | | | | | 21. THE CONSTRUCTION ACCESS DRIVEWAY IS SHOWN INSIDE | | | THE BUILDING ON THE EROSION CONTROL PLAN. | | | | | | 22. ALL ON-SITE DRAINAGE STRUCTURES ARE TO BE LOCATED | | | WITHIN THE PROPERTY BOUNDARY. THE CONTROL STRUCTURE | | | APPEARS TO BE OVER THE PROPERTY LINE. | | | | | | 23. PLEASE ADVISE IF THE YARD DRAIN STRUCTURES WILL BE | | | COVERED WITH CONCRETE PAVERS AND/OR LANDSCAPING. THE | | | YARD DRAIN IN THE SOUTHEAST CORNER OF THE SITE HAS A | | | RIM ELEVATION OF 15.5 FT NAVD AND THERE IS A SPOT GRADE | | | OF 16.2 FEET NAVD POINTING TO THE STRUCTURE. | | | | | | 24. OUTFALL PIPE ORIENTATION MAY NOT MATCH HOW IT IS | | | SHOWN ON THE NORA STREETSCAPE PLANS. | | | | | | 25. LABEL THE NORTH PIPE (SIZE/MATERIAL) AT STRUCTURE | | | CS-1. WHAT IS THIS PIPE FOR? | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | [email protected] | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
08-11-2022 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
08-11-2022 |
Time |
06:42 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
08-11-2022 |
Time |
06:45 |
Sent To |
|
|
| Notes |
| 2022-08-11 06:45:39 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | 1. CHECK THE PARCEL NUMBER(S) LISTED IN THE | | | JUSTIFICATION STATEMENT. | | | | | | 2. THE REQUEST IN THE JUSTIFICATION STATEMENT DESCRIBES | | | EXPANDING THE EXISTING COMMERCIAL BUILDING INTO A | | | RESTAURANT USE. THE SURVEY SHOWS THE EXISTING BUILDING | | | 0.7 FEET SETBACK FROM THE NORTH PROPERTY LINE. THE SITE | | | PLAN SHOWS THE BUILDING SETBACK AT LEAST 5 FEET FROM | | | THE NORTH PROPERTY LINE. | | | | | | 3. PROVIDE CROSS SECTIONS FROM CENTERLINE OF RIGHTS OF | | | WAY TO THE BUILDING FACES. SHOW AND LABEL SURFACE | | | FEATURES, GRADE BREAKS, GENERAL SURFACE SLOPES, | | | FINISHED FLOOR ELEVATION, RIGHT OF WAY LINES WITH THE | | | STREET IDENTIFIED, DIMENSIONS FROM RIGHT OF WAY TO | | | SURFACE FEATURES. | | | | | | 4. PROVIDE THE TOP AND BOTTOM ELEVATIONS AND VERTICAL | | | CLEARANCE BETWEEN THE PROPOSED OUTFALL PIPE AND OTHER | | | UTILITIES CROSS BE THE OUTALL PIPE. | | | | | | 5. THE ROOF DRAIN SYSTEM SHOULD CONNECT DIRECTLY INTO | | | THE DRAINAGE SYSTEM. | | | | | | 6. PROVIDE DETAIL OF THE CONTROL STRUCTURE. | | | | | | 7. SHOW UTILITIES ON THE LANDSCAPE PLANS AND COORDINATE | | | PROPOSED PLANTINGS WITH THE UTILITY LAYOUT. | | | | | | 8. DOOR ON EAST WALL APPEARS TO OPEN OVER THE PROPERTY | | | LINE. | | | | | | 9. SHOW AND LABEL PROPERTY LINES, RIGHT OF WAY LINES, | | | ALLEY WIDTH. | | | | | | 10. WILL PORTION OF THE PATIO NEED TO BE SLOPED A | | | MAXIMUM OF 2 PERCENT FOR ADA ACCESSIBILITY. SHOW WHERE | | | THAT ADA PATH(S) WILL BE. | | | | | | 11. REMOVE THE EXISTING DRIVEWAY APRON ON 7TH STREET. | | | CONSTRUCT CURBING TO MATCH ADJACENT CURB TYPE. | | | | | | 12. THE CITY?S OFFICIAL VERTICAL DATUM IS NGVD1929. THE | | | CITY HAS ALLOWED THE USE OF NAVD1988 AS LONG AS THE | | | CONVERSION EQUATION TO NGVD1929 AT THE PROJECT LOCATION | | | IS PROVIDED. PROVIDE THE VERTICAL DATUM CONVERSION TO | | | NGVD1929 ON THE SURVEY. | | | | | | 13. SHOW MILL AND RESURFACE LIMITS. | | | | | | 14. CALL OUT WHERE NEW OR REPLACEMENT SIDEWALK WILL BE | | | CONSTRUCTED AS PART OF THIS PROJECT. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP | | | CRITERIA. STORMWATER CALCULATIONS WILL BE REVIEWED WITH | | | THE ENGINEERING PERMIT SUBMITTAL. | | | | | | 2. PROVIDE COPY OF SFWMD ERP PERMIT MODIFICATION BEFORE | | | START OF CONSTRUCTION. | | | | | | 3. PROVIDE EROSION AND SEDIMENT CONTROL PLAN WITH THE | | | ENGINEERING PERMIT SUBMITTAL. | | | | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | 561-351-0510 (M) | | | [email protected] | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
08-09-2022 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
08-09-2022 |
Time |
07:43 |
Rev Time |
|
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-09 07:52:27 | 1. SURVEY NEEDS TO BE OF JUST THE SUBJECT SITE. | | | 2. SHOW PROPERTY LINES ON ALL PLANS. | | | 3. CITY DOES NOT WANT A NEW WATER MAIN IN ALLEY. | | | RELOCATE SERVICES TO N. RAILROAD. | | | 4. DOOR ON EAST SIDE CANNOT OPEN INTO ADJOINING | | | PROPERTY. | | | 5. PLANS SHOULD SHOW EXISTING AND PROPOSED ADDITION. | | | 6. SEPARATE SANITARY SERVICES. |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
08-10-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
08-10-2022 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
08-10-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-10 22:25:01 | TRAFFIC COMMENTS | | | 1) CORRECT THE EXEMPTION REFERENCE AS IT IS TRAFFIC | | | CONCURRENCY EXCEPTION AREA (TCEA), NOT CRA. | | | 2) SCHEDULE A METHODOLOGY MEETING. A FULL TRAFFIC STUDY | | | IS NEEDED; EXEMPTION FROM COUNTY CONCURRENCY DOES NOT | | | PRECLUDE THE CITY TO REQUEST MORE IN-DEPTH ANALYSIS, | | | GIVEN THE SIGNIFICANT CHANGE IN LAND USE AND TRIP | | | GENERATION TOGETHER WITH IMPACT TO THE SURROUNDING | | | ROADWAY NETWORK | | | 3) ALL CONCERNS AND COMMENTS PROVIDED BY THE COUNTY IN | | | THE TPS LETTER SHALL BE ADDRESSED | | | 4) MORE DETAILED TRANSPORTATION DEMAND MANAGEMENT (TDM) | | | MEASURES SHALL BE DISCUSSED AND AGREED WITH CITY | | | PLANNING AND ENGINEERING DEPARTMENTS | | | 5) TRAFFIC SIGNAL WARRANT ANALYSES SHALL BE CONDUCTED | | | AT EACH IMPACTED UNSIGNALIZED INTERSECTION ALONG PALM | | | BEACH LAKES BLVD AND DIXIE HIGHWAY | | | | | | SITE COMMENTS | | | 6) PROVIDE A CLEAN TRANSPORTATION SPECIFIC SITE PLAN. | | | SHOWCASING TRANSPORTATION RELATED FEATURES (E.G. | | | ROADWAY, DRIVING AISLES, PARKING STALLS, SIDEWALK, | | | CURB, GUTTER, DRIVEWAY, GATES, ETC.) PROPERLY LABELED | | | AND DIMENSIONED. PLEASE DO NOT SHOW ALL UNDERGROUND | | | UTILITY LAYERS | | | 7) IN THE TRANSPORTATION SITE PLAN, PLEASE SHOWCASE | | | BASIC CURB DETAILS (E.G. DRIVEWAY, CURB CUTS, PAVEMENT | | | MARKINGS, PARKING STALLS, ETC.) ON THE OPPOSITE SIDE OF | | | THE ROADS SURROUNDING THE PROPOSED DEVELOPMENT. | | | INCLUDING ALLEYWAYS. | | | 8) PROVIDE AUTOTURN ANALYSIS FOR GARBAGE TRUCK AND/OR | | | DELIVERY VEHICLES SERVICING THE PROPOSED DEVELOPMENT | | | WITH VEHICLE DYNAMIC ENVELOPES AND WHEEL PATHS CLEARLY | | | DISTINCT AND DEFINED. ANALYSIS SHOULD BE PROVIDED IN A | | | SEPARATE FILE/DRAWING. PLEASE PROVIDE DOCUMENT NAME AND | | | SHEET NUMBER SHOWCASING THE ANALYSIS | | | 9) WHERE IS THE DUMPSTER LOCATION? | | | 10) IS THE AREA IN FRONT OF THE RESTAURANT PEDESTRIAN | | | ONLY OR VEHICLES MAY ACCESS IT? | | | 11) SHOW THE TYPE OF CONTROL FOR EACH INTERSECTION | | | SURROUNDING THE PROPOSED DEVELOPMENT (I.E. PAVEMENT | | | MARKINGS AND SIGNAGE) | | | 12) HOW ARE DELIVERIES PERFORMED? CLEARLY MARK AND | | | DIMENSION THE DESIGNATED LOADING ZONE | | | 13) PROVIDE CROSSWALKS ACROSS 7TH ST | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
05-01-2023 |
|
|
Cont ID |
|
| Sent By |
ckimmerl |
Date |
05-01-2023 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
ckimmerl |
Date |
05-01-2023 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2023-05-01 16:21:20 | 1. SETBACKS | | | - PLEASE PROVIDE SETBACK LINES ON ALL SITE PLAN AND | | | ARCHITECTURAL DRAWINGS | | | SETBACKS NEED TO BE RECALCULATED AND LABELED: | | | - 7TH STREET IS FRONT, PRIMARY PEDESTRIAN ON THIS | | | FRONTAGE REQUIRES 16??? SETBACK | | | - NORTH RAILROAD AVENUE IS SIDE STREET, PRIMARY | | | PEDESTRIAN REQUIRES 16??? SETBACK | | | - REAR IS ALLEY, REQUIRES 5??? SETBACK | | | - SIDE INTERIOR IS EAST PROPERTY LINE, REQUIRES 0? OR | | | NFPA | | | RESPONSE: PER A MEETING WITH STAFF THE SETBACKS ARE | | | ALIGNED WITH THE APPLICANTS SITE PLAN PROGRAMMING WITH | | | N. RAILROAD AS A FRONT SETBACK (0???); 7TH STREET AS A | | | FRONT SETBACK (16???); ALLEY AT NORTH BOUNDARY AS SIDE | | | INTERIOR (5??? 0??? PROVIDED EXISTING CONDITION); AND, | | | EAST BOUNDARY AS REAR SETBACK (5??? FOR NON-RESIDENTIAL | | | / 5??? PROPOSED FOR ADDITION). | | | 1. ZONING REVIEW 5.1.23 ??? [NOT SATISFIED] | | | DISCUSSION WAS REGARDING THE BPD-R SETBACKS WHICH HAVE | | | A PROVISION SPECIFICALLY CALLING OUT RAILROAD AVE. | | | SETBACKS. THE BPD-5 SUBDISTRICT DOES NOT CALL OUT | | | RAILROAD AVE., HOWEVER BECAUSE THIS PROPERTY IS NOT IN | | | A RESIDENTIAL SUBDISTRICT THE SETBACKS ARE CALCULATED | | | FROM BACK OF CURB, NOT PROPERTY LINE. | | | SETBACKS STILL APPEAR TO BE MET, JUST NEED TO BE | | | PROPERLY LABELED. | | | RAILROAD AVE. IS A PRIMARY PEDESTRIAN STREET THEREFORE | | | 16??? IS REQUIRED ON THIS FRONTAGE (FROM CURB) | | | 7TH STREET IS A PRIMARY PEDESTRIAN SETBACK REQUIRES | | | 16??? SETBACK (FROM CURB) | | | ALLEY IS CONSIDERED REAR AND WOULD REQUIRE 5??? | | | (EXISTING STRUCTURE WOULD BE CONSIDERED LEGAL | | | NONCONFORMITY) | | | SIDE INTERIOR IS EASTERN PROPERTY LINE, REQUIRES 0??? | | | OR NFPA. | | | | | | 2. LANDSCAPING | | | - 12% PRIVATE OPEN SPACE REQUIREMENT. HOW IS THIS BEING | | | MET? PLEASE PROVIDE OPEN SPACE TYPE AND HOW IT MEETS | | | THE STANDARDS OF THAT TYPE. SEE. TABLE IV-6 AND TABLE | | | IV-7. | | | - PLEASE PROVIDE STREETSCAPE LANDSCAPING DETAILS FOR N | | | RAILROAD AVE. AND 7TH ST. FRONTAGES. | | | RESPONSE: ACKNOWLEDGED. SEE SITE ANALYSIS EXHIBIT | | | PROVIDED HEREIN. | | | 2. ZONING REVIEW 5.1.23 ??? [NOT SATISFIED] | | | PER SEC. 94-109 ??? OPEN SPACE, PRIVATE; IF PRIVATE | | | OPEN SPACE IS LOCATED ON THE GROUND FLOOR AND LOCATED | | | ALONG THE LOT FRONTAGE, IT SHALL BE DESIGNED IN | | | COMPLIANCE WITH THE PUBLIC OPEN SPACE REQUIREMENTS, AND | | | IT SHALL BE ACCESSIBLE BY THE PUBLIC FOR PUBLIC USE. | | | PLEASE PROVIDE CLARIFICATION AND IDENTIFY ON SITE PLAN | | | & LP-1 WHAT TYPOLOGY OF PUBLIC OPEN SPACE IS BEING | | | PROVIDED PER SEC. 94-109 TABLE IV-6 AND TABLE IV-7 | | | (I.E. PASSAGEWAY, GARDEN PLAZA, AND GARDEN COURTYARD); | | | PLEASE BE SURE TO MEET THE STANDARDS OF TABLE IV-7 FOR | | | THE SELECTED CLASSIFICATION. PLEASE REVISE SITE | | | ANALYSIS EXHIBITS SHEET AND LP-1 ACCORDINGLY. | | | MAX OVERHEAD COVER IS A PERCENTAGE; USUALLY 20% PLEASE | | | CLARIFY HOW MUCH OF THIS SPACE IS BEING COVERED BY | | | ROOFS OR OVERHEAD STRUCTURES. | | | | | | 3. TRANSPARENCY REQUIREMENTS - PLEASE PROVIDE | | | TRANSPARENCY CALCULATIONS; 50% ON N RAILROAD AND 50% ON | | | 7TH | | | RESPONSE: ACKNOWLEDGED. SEE SITE ANALYSIS EXHIBIT | | | PROVIDED HEREIN. | | | 3. ZONING REVIEW 5.1.23 ??? [PARTIALLY SATISFIED] | | | TRANSPARENCY CALCULATIONS APPEAR TO BE MET, PLEASE | | | PROVIDE MARKUP OF FIRST FLOOR ELEVATION THAT DIMENSIONS | | | THE BUILDING FRONTAGE AND FENESTRATION/TRANSPARENCY | | | (PLEASE REFERENCE SEC. 94-109 FIGURE IV-33) ONLY THE | | | ACTIVE USES AND FIRST 10FT. OF HEIGHT FROM SIDEWALK | | | ELEVATION NEEDS TO BE CALCULATED. | | | | | | | | | 4. SITE PLAN MENTIONS PARKING REQUIREMENTS BEING MET | | | WITH VALET SERVICE OFFSITE, PLEASE INDICATE WHERE THE | | | OFF-SITE PARKING IS LOCATED. - IS ALL OF THE PARKING | | | UNDER A VALET SERVICE? | | | RESPONSE: PARKING SHALL BE PROVIDED WITHIN THE CENTRAL | | | PARKING LOT; ON-STREET AND WITHIN THE TEMPORARY PARKING | | | LOT LOCATED AT THE NORTH END OF THE PROJECT. EACH | | | TENANT OR BUILDING WILL COORDINATE VALET PARKING | | | SERVICES FOR THEIR RESPECTIVE CUSTOMERS. | | | 4. ZONING REVIEW 5.1.23 ??? [SATISFIED] OFFSITE PARKING | | | TO GO BEFORE DAC | | | | | | 5. WHERE IS THE GARBAGE ENCLOSURE LOCATED? DETAIL IS | | | SHOWN ON SITE PLAN, BUT NO LOCATION INDICATED. PLEASE | | | CLARIFY LOCATION AND OPERATION. | | | RESPONSE: THE DUMPSTER DETAIL HAS BEEN REMOVED FROM | | | THE PLAN. A TRASH ROOM THAT WILL ACCOMMODATE GARBAGE; | | | RECYCLING AND BULK PICK UP ITEMS HAD BEEN FURNISHED AT | | | THE NORTH END OF THE BUILDING ACCESSING THE ALLEY. | | | 5. ZONING REVIEW 5.1.23 ??? [SATISFIED] ARE THE CANS TO | | | BE ROLLED OUT TO THE ALLEY? BE SURE SANITATION IS OKAY | | | WITH PROPOSAL. | | | | | | 6. WHERE IS THE LOADING OPERATION LOCATED? DETAIL IS | | | SHOWN ON SITE PLAN, BUT NO LOCATION INDICATED. PLEASE | | | CLARIFY LOCATION AND OPERATION. | | | RESPONSE: ACKNOWLEDGED. THE SITE WILL BE ACCESSED FROM | | | THE PUBLIC ALLEY FOR LOADING/UNLOADING AND TRASH | | | REMOVAL. SEE UPDATED SITE PLAN INDICATING THE LOCATION | | | OF THE SERVICE AREA OF THE BUILDING AND TRASH ROOM | | | ACCORDINGLY. | | | 6. ZONING REVIEW 5.1.23 ??? [SATISFIED] | | | | | | 7. PHOTOMETRIC ANALYSIS SHOWS SOUTHEASTERN CORNER OF | | | PROPERTY ALONG 7TH STREET WITH AREAS BELOW REQUIRED 0.6 | | | FOOTCANDLES. | | | RESPONSE: SEE UPDATED PHOTOMETRIC PLAN FOR | | | MODIFICATIONS TO THE AREAS OF THE PLAN NOT IN | | | COMPLIANCE WITH THE 0.6 FOOTCANDLE REQUIREMENT. | | | 7. ZONING REVIEW 5.1.23 ??? [NOT SATISFIED] | | | PHOTOMETRICS STILL SHOW AREAS AT 0.5 AT SOUTHEAST END | | | OF PROPERTY. | | | | | | 8. PLEASE INDICATE WHERE REQUIRED BIKE PARKING SPACES | | | ARE LOCATED. | | | | | | RESPONSE: BICYCLE PARKING EXISTS WITHIN THE R-O-W (UP | | | TO THREE BIKE RACKS ARE PROVIDED) IN CLOSE PROXIMITY TO | | | THE PUBLIC ENTRANCE TO THE SITE. SEE UPDATED SITE PLAN | | | AND ASSOCIATED STREETSCAPE PLAN. | | | 8. ZONING REVIEW 5.1.23 ??? [SATISFIED] BIKE PARKING | | | FACILITATED IN ROW; REQUIREMENT FOR THE TABLE IS 1 | | | SPACE FOR EVERY 100??? OF FRONTAGE; THEREFORE 2 SPACES | | | REQUIRED. THOSE ARE IN ROW. | | | | | | 9. RENDERING SHOWS NORA NEIGHBORHOOD SIGNAGE ONSITE, | | | PLEASE NOTE ANY SIGNAGE WILL BE UNDER A SEPARATE | | | PERMIT. | | | RESPONSE: ACKNOWLEDGED | | | 9. ZONING REVIEW 5.1.23 ??? [SATISFIED] | | | | | | | | | NEW ZONING COMMENTS 5.1.23: | | | 1. PLEASE PROVIDE PROJECTION DETAILS OR DIMENSIONS FOR | | | THE CANOPY ELEMENTS SHOWN ON THE ELEVATIONS. BE SURE | | | THAT THESE ELEMENTS MEET THE STANDARDS IN SEC. 94-109 | | | TABLE IV-5. ELEVATIONS PROVIDED, PLEASE SHOW | | | PROJECTIONS. | | | | | | 2. ANY ROOFTOP MECHANICAL EQUIPMENT SHALL BE SCREENED | | | FROM VIEW. PER SEC. 94-109 PROJECTION, VERTICAL: | | | MECHANICAL EQUIPMENT AND APPURTENANCES NECESSARY TO THE | | | OPERATION OR MAINTENANCE OF THE BUILDING OR STRUCTURE | | | ITSELF SUCH AS, BUT NOT LIMITED TO, COOLING TOWERS, | | | ELEVATORS, STAIRS AND MECHANICAL PENTHOUSES, VENT | | | STACKS AND ANTENNAS SHALL BE ENCLOSED AND SCREENED IN | | | SUCH A MANNER THAT THE ENCLOSURE IS DESIGNED AS AN | | | INTEGRAL PART OF THE OVERALL BUILDING DESIGN. | | | | | | 3. MECHANICAL EQUIPMENT ON THE GROUND CAN ENCROACH INTO | | | SETBACKS A MAXIMUM OF 4FT MUST LEAVE AT LEAST 1FT. BE | | | SURE THAT THE MECHANICAL EQUIPMENT MEETS THIS | | | ENCROACHMENT STANDARD. | | | | | | | | | CHRIS KIMMERLY, AICP | | | URBAN DESIGN PLANNER | | | 822.1426 [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
08-08-2022 |
|
|
Cont ID |
|
| Sent By |
ckimmerl |
Date |
08-08-2022 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
ckimmerl |
Date |
08-08-2022 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2022-08-08 11:45:44 | 1. SETBACKS | | | - PLEASE PROVIDE SETBACK LINES ON ALL SITE PLAN AND | | | ARCHITECTURAL DRAWINGS | | | SETBACKS NEED TO BE RECALCULATED AND LABELED: | | | - 7TH STREET IS FRONT, PRIMARY PEDESTRIAN ON THIS | | | FRONTAGE REQUIRES 16? SETBACK | | | - NORTH RAILROAD AVENUE IS SIDE STREET, PRIMARY | | | PEDESTRIAN REQUIRES 16? SETBACK | | | - REAR IS ALLEY, REQUIRES 5? SETBACK | | | - SIDE INTERIOR IS EAST PROPERTY LINE, REQUIRES 0? OR | | | NFPA | | | | | | 2. LANDSCAPING | | | - 12% PRIVATE OPEN SPACE REQUIREMENT. HOW IS THIS BEING | | | MET? PLEASE PROVIDE OPEN SPACE TYPE AND HOW IT MEETS | | | THE STANDARDS OF THAT TYPE. SEE. TABLE IV-6 AND TABLE | | | IV-7. | | | - PLEASE PROVIDE STREETSCAPE LANDSCAPING DETAILS FOR N | | | RAILROAD AVE. AND 7TH ST. FRONTAGES. | | | | | | 3. TRANSPARENCY REQUIREMENTS | | | - PLEASE PROVIDE TRANSPARENCY CALCULATIONS; 50% ON N | | | RAILROAD AND 50% ON 7TH | | | | | | 4. SITE PLAN MENTIONS PARKING REQUIREMENTS BEING MET | | | WITH VALET SERVICE OFFSITE, PLEASE INDICATE WHERE THE | | | OFF-SITE PARKING IS LOCATED. | | | - IS ALL OF THE PARKING UNDER A VALET SERVICE? | | | | | | 5. WHERE IS THE GARBAGE ENCLOSURE LOCATED? DETAIL IS | | | SHOWN ON SITE PLAN, BUT NO LOCATION INDICATED. PLEASE | | | CLARIFY LOCATION AND OPERATION. | | | | | | 6. WHERE IS THE LOADING OPERATION LOCATED? DETAIL IS | | | SHOWN ON SITE PLAN, BUT NO LOCATION INDICATED. PLEASE | | | CLARIFY LOCATION AND OPERATION. | | | | | | 7. PHOTOMETRIC ANALYSIS SHOWS SOUTHEASTERN CORNER OF | | | PROPERTY ALONG 7TH STREET WITH AREAS BELOW REQUIRED 0.6 | | | FOOTCANDLES. | | | | | | 8. PLEASE INDICATE WHERE REQUIRED BIKE PARKING SPACES | | | ARE LOCATED. | | | | | | 9. RENDER SHOWS NORA NEIGHBORHOOD SIGNAGE ONSITE, | | | PLEASE NOTE ANY SIGNAGE WILL BE UNDER A SEPARATE | | | PERMIT. | | | | | | | | | CHRIS KIMMERLY, AICP | | | URBAN DESIGN PLANNER | | | 822.1426 [email protected] |
|
|
| |