Plan Review Details - Project Z22070019
Plan Review Stops For Project Z22070019
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 2 Status P Date 07-11-2023 Cont ID  
Sent By swelter Date 07-11-2023 Time 17:06 Rev Time 0.00
Received By swelter Date 07-11-2023 Time 17:09 Sent To  
Notes
2023-07-11 17:09:24PROJECT ELECTED OPTION #2 - CONTRIBUTION
 ART ASSESSMENT RCVD. WITH RESUBMITTAL APPLICATION
  
 ART FEES DUE BEFORE OR AT TIME OF BUILDING PERMIT FEES
  
 [email protected]

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status F Date 08-09-2022 Cont ID  
Sent By scwelter Date 08-09-2022 Time 14:43 Rev Time 0.00
Received By scwelter Date 08-11-2022 Time 10:07 Sent To  
Notes
2022-08-11 10:07:09PUBLIC ART REQUIREMENT:
 TOTAL CONSTRUCTION COSTS OF THIS DEVELOPMENT ARE OVER
 $500,000 IT IS SUBJECT TO THE PUBLIC ART REQUIREMENT AS
 PER CITY ORDINANCE.
 SECTION 78-129: ALL PRIVATE DEVELOPMENT PROJECTS,
 INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR
 IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL
 CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000 ARE SUBJECT TO THE PUBLIC ART REQUIREMENT.
 OPTION 1: INSTALL ARTWORK ON THE DEVELOPMENT SITE
 VALUED IN AN AMOUNT NOT LESS THAN ONE PERCENT OF THE
 TOTAL CONSTRUCTION COSTS.
 FOR SITE PLAN APPROVAL PUBLIC ART NEEDS TO BE
 IDENTIFIED ON THE SITE PLAN.
 OPTION 2: CONTRIBUTE AN AMOUNT EQUAL TO 75 PERCENT OF
 ONE PERCENT OF THE TOTAL CONSTRUCTION COSTS FOR DEPOSIT
 TO THE PUBLIC ART ACCOUNT.
 FOR SITE PLAN APPROVAL AN EMAIL TO [email protected]
 STATING THAT THE DEVELOPER IS CHOSEN OPTION IS
 REQUIRED.
  
 FOR EITHER OPTION A COMPLETED PUBLIC ART ASSESSMENT
 APPLICATION ALONG WITH EITHER THE ESCROW OF THE 1% OR
 IF CHOSEN OPTION 2 CONTRIBUTION INTO THE PUBLIC ART
 FUND IS REQUIRED AT TIME OF BUILDING PERMIT SUBMITTAL.
  
 CONTACT SYBILLE WELTER, ADMINISTRATOR OF PUBLIC ART &
 CULTURE AT [email protected] WITH FURTHER QUESTIONS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 07-12-2023 Cont ID  
Sent By rbrown Date 07-12-2023 Time 22:23 Rev Time 0.00
Received By rbrown Date 07-12-2023 Time 22:23 Sent To  
Notes
2023-07-12 22:26:45DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 3. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND
 OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT,
 COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF
 OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED.
  
 4. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 5. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND
 CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF
 CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL
 NEIGHBORING PROPERTIES.
  
 6. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 7. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION
 OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING,
 CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT
 (561) 805 6659, OR BY EMAIL: [email protected]
  
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 08-11-2022 Cont ID  
Sent By rbrown Date 08-11-2022 Time 12:02 Rev Time 0.00
Received By rbrown Date 08-11-2022 Time 12:02 Sent To  
Notes
2022-08-11 12:11:10DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. UNITY OF TITLE. FOR ANY BUILDING CROSSING A PROPERTY
 LINE, EITHER A RECORDED UNITY OF TITLE, OR SOME OTHER
 APPROVED LEGAL INSTRUMENT, SHALL BE INCLUDED WITH THE
 PERMIT APPLICATION, OR THE BUILDING MUST HAVE A FIRE
 WALL ALONG THE PROPERTY LINE, PER SECTION 202 OF
 FLORIDA BUILDING CODE, BUILDING, FIRE SEPARATION
 DISTANCE.
  
 3. STAIR EXIT DISCHARGE TO RIGHT OF WAY. GROUND FLOOR
 PLAN, SHEET A1-1.01, SHOWS BOTH STAIRS DISCHARGING INTO
 THE PARKING GARAGE. A FIRE-RATED EXIT PASSAGEWAY WOULD
 BE REQUIRED BECAUSE NO MORE THAN 50% OF THE EXIT
 CAPACITY IA ALLOWED TO DISCHARGE WITHIN THE BUILDING
 PER SECTION 1028.1 OF FLORIDA BUILDING CODE.
  
 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 5. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND
 OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT,
 COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF
 OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED.
  
 6. ENCLOSED PARKING GARAGES. IT APPEARS THAT THE
 PARKING GARAGE DOES NOT HAVE SUFFICIENT WALL OPENINGS
 TO MEET THE DEFINITION OF AN OPEN PARKING GARAGE. IF
 THAT IS THE CASE. IT WILL BE CONSIDERED AN ENCLOSED
 PARKING GARAGE AND MUST HAVE EXHAUST SYSTEMS. THE
 EXHAUST SYSTEMS SHALL BE DESIGNED TO MINIMIZE NOISE
 LEVELS USING INLINE FAN SILENCERS OR OTHER APPROVED
 METHODS.
  
 7. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 8. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND
 CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF
 CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL
 NEIGHBORING PROPERTIES.
  
 9. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 10. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION
 OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING,
 CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT
 (561) 805 6659, OR BY EMAIL: [email protected]
  
 11. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT
 TO ART LIFE ASSESSMENT UNDER THE CITY OF WEST PALM
 BEACH ART IN PUBLIC PLACES (AIPP) PROGRAM. FOR ADVICE
 ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP
 ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status P Date 07-12-2023 Cont ID  
Sent By lquinone Date 07-12-2023 Time 12:02 Rev Time 0.00
Received By lquinone Date 07-12-2023 Time 12:02 Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 07-27-2022 Cont ID  
Sent By rrossano Date 07-27-2022 Time   Rev Time  
Received By rrossano Date 07-27-2022 Time   Sent To  
Notes
2022-07-27 10:18:43Z22070019 - 5179 BROADWAY, MIXED USE 7.26.22 SUB
  
 COMMENTS FROM RICK ROSSANO, SR. PROJECT COORDINATOR,
 ENGINEERING SERVICES AT 561-494-1098 [email protected]
 GENERAL:
 O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (Z-XXXXXXXX).
 O THE CITY OF WEST PALM BEACH HAS A NUMBER OF
 REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY
 AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND
 WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE
 DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK
 BELOW:
 A. HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WP
 B_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FUL
 L-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97
 B1960045731D3658206F27451722716EF
 B. THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE
 FOUND HERE:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
 C. ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM
 BEACH, FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08,
 ADOPTED SEPT. 22, 2008. (SUPPLEMENT NO. 18)
 CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL,
 SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER
 SERVICE FACILITIES OF THE CITY.
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
 O AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, REFER TO THE LINK BELOW:
 A. HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PU
 BLICATIONS/BACKFLOW-CROSS-CONNECTION- CONTROL-MANUAL
 O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1079 FOR FURTHER
 ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION
 ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD
 SURVEY, POT-HOLING, SOFT DIGS ETC.
 O PROVIDE EXISTING AND PROPOSED PERVIOUS AND IMPERVIOUS
 DATA.
  
 BACKFLOW ASSEMBLY AND METERS:
 O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER
 SERVICES AND WATER METERS, ALONG WITH WHAT IS HAPPENING
 TO THEM.
 O SHOW EXISTING AND PROPOSED DEDICATED UTILITY
 EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO
 PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO
 STRUCTURES WITHIN EASEMENT.
 O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION
 OF WATER METER AND BACKFLOW
 PREVENTION.
 O BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY
 OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER
 METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO
 PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE
 INSTALLED ABOVE-GROUND ONLY.
 O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE
 NOTE USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA.
  
 WATER/WASTEWATER PLAN:
 O PROVIDE VERTICAL DATUM AND DATUM CONVERSION
 INFORMATION (NAVD 1988 AND NGVD 1929).
 O SHOW PROJECT ADDRESS ON ALL PLAN SHEETS.
 O PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE
 STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC.
 O PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND
 DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND
 SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH
 PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE
 AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS,
 BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO
 BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS,
 DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS,
 ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT
 ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF
 SANITARY SEWER LINES.
 O GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR
 SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW.
 O DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN
 VIEW FOR ALL SANITARY AND STORM SEWERS.
 O SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL.
 O PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED
 UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC,
 ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION
 FACILITIES LOCATED ON THE RIGHT-OF-WAY.
 O PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER
 AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD
 DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS.
 O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY
 TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT
 APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING
 AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE,
 MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS
 SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008
 FOR WATER.
 O PROVIDE FIRE FLOW TEST DATA.
 O PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER ALONG
 ENTIRE PROJECT FRONTAGE (CONDITION OF SITE PLAN
 APPROVAL).
 O CUT AND CAP UTILITIES NOT IN USE AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 ROW.
 O WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL
 BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY
 PROPOSED LENGTH IN FEET.
 O CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY
 SEWER ARE REQUIRED.
 O PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE
 JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET.
 O ADD NOTE TO PLANS SPECIFYING CITY?S DOWNSTREAM LIFT
 STATION NUMBER.
 O PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR
 PROPOSED SANITARY LATERALS.
 O LABEL WATER LINES AS PRIVATE WHERE APPLICABLE.
 O PLEASE SHOW AND LABEL EXISTING AND PROPOSED GREASE
 TRAPS (IF ANY).
 O PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN
 OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER.
  
 FORMAL ENGINEERING REVIEW:
 O FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES
 NOI REQUIREMENTS WILL BE ENFORCED.
 - AN NOI IS REQUIRED FOR PROJECTS THAT:
 - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS
 THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF
 DEVELOPMENT OR SALE;
 - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE
 STATE OR TO SURFACE WATERS OF THE STATE THROUGH A
 MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4).
 - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF
 CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION
 THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL
 SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT
 OF THE 10-2 CERTIFICATION.
 O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE
 EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS.
 O FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF
 WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS.
 O FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING
 APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT
 SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING
 SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED
 LEAD-FREE DESIGN.
 O FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO PROVIDE
 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF
 PROPOSED TRENCH IN CITY MAINTAINED ROADWAY AREAS PER
 CITY OF WPB STANDARD DETAIL GC-8.
 O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE
 CALCULATIONS OF PERVIOUS AND IMPERVIOUS AREAS FOR
 PROPOSED IMPROVED AREAS.
  
  
  
 QUESTIONS AND COORDINATION CONTACTS:
 O MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR WITH
 CITY OF WPB PUBLIC UTILITIES, REGARDING PLACEMENT OF
 BACKFLOW DEVICES AND WATER METERS. CONTACT HIM AT
 561-822-2262 OR [email protected]
 O MIKE TECHNOW, PROJECT ENGINEER, PUBLIC UTILITIES
 DEPARTMENT AT 561-494-1047 OR [email protected]
 O TRACY WARD, SR. STORMWATER ENGINEER, ENGINEERING
 SERVICES DEPT. AT 561-494-1120 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 07-07-2023 Cont ID  
Sent By pleduc Date 07-07-2023 Time   Rev Time 0.00
Received By pleduc Date 07-07-2023 Time 14:43 Sent To  
Notes
2023-07-07 14:46:23THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE DEPARTMENT.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT. THE FOLLOWING COMMENTS ARE INTENDED
 TO PROVIDE GUIDANCE FOR BUILDING PLAN SUBMITTAL.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE PER THE FLORIDA FIRE PREVENTION CODE.
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED, AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 THE PROPOSED LOCATION OF THE FIRE HYDRANT IS ACCEPTABLE
 IF THE FDC IS WITHIN 100' AND, IF APPLICABLE, CLOSELY
 COORDINATED WITH THE BUREAU OF FIRE PREVENTION.
  
 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM,
 ENSURE THEY COMPLY WITH THE REQUIREMENTS OF F.A.C. 61G
 AND SUBMITTED WITH THE MASTER PERMIT.
  
 9A. THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE
 LOCATIONS SHALL MEET AND BE INSTALLED PER THE
 REQUIREMENTS OF NFPA 24 AND SHALL BE COORDINATED WITH
 THE OFFICE OF FIRE MARSHAL, THE CITY'S ENGINEERS
 OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S PLANNING
 AND ZONING OFFICE.
  
 10. COMPLETE LIFE SAFETY PLANS FOR THE OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, EXIT SEPARATION DISTANCES, COMMON PATHS OF
 TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, EMERGENCY
 LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE
 EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES
 AND EQUIPMENT.
  
 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE
 SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY
 DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS.
  
 12. ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE
 FIGHTER?S EMERGENCY OPERATIONS REQUIREMENTS OF ASME
 A17.1/CSA B44, SAFETY CODE FOR ELEVATORS.
  
 ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET
 MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN
 AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE
 IN THE HORIZONTAL POSITION.
  
 13. TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEMS.
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
  
 IF APPLICABLE, CONTACT WILL NEED TO BE MADE TO KEN
 DECKER, , PALM BEACH COUNTY PUBLIC SAFETY RADIO SYSTEMS
 MANAGER, [email protected], 561-233-0837; AS OUR
 RADIOS OPERATE ON THEIR SYSTEM FOR DETAILED RADIO
 FREQUENCY AND INSTALLATION INSTRUCTIONS.
  
 14. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
 15. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 08-01-2022 Cont ID  
Sent By pleduc Date 08-01-2022 Time   Rev Time 0.00
Received By pleduc Date 08-01-2022 Time 14:30 Sent To  
Notes
2022-08-01 14:33:42THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE DEPARTMENT.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT. THE FOLLOWING COMMENTS ARE INTENDED
 TO PROVIDE GUIDANCE FOR BUILDING PLAN SUBMITTAL.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE PER THE FLORIDA FIRE PREVENTION CODE.
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED, AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
 THE PROPOSED LOCATION OF THE FIRE HYDRANT AND FDC SHALL
 BE WITHIN 100' OF EACH OTHER AND CLOSELY COORDINATED
 WITH THE BUREAU OF FIRE PREVENTION.
  
 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM,
 ENSURE THEY COMPLY WITH THE REQUIREMENTS OF F.A.C. 61G
 AND SUBMITTED WITH THE MASTER PERMIT.
  
 9A. THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE
 LOCATIONS SHALL MEET AND BE INSTALLED PER THE
 REQUIREMENTS OF NFPA 24 AND SHALL BE COORDINATED WITH
 THE OFFICE OF FIRE MARSHAL, THE CITY'S ENGINEERS
 OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S PLANNING
 AND ZONING OFFICE.
  
 10. COMPLETE LIFE SAFETY PLANS FOR THE OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, EXIT SEPARATION DISTANCES, COMMON PATHS OF
 TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, EMERGENCY
 LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE
 EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES
 AND EQUIPMENT.
  
 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE
 SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY
 DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS.
  
 12. ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE
 FIGHTER?S EMERGENCY OPERATIONS REQUIREMENTS OF ASME
 A17.1/CSA B44, SAFETY CODE FOR ELEVATORS.
  
 ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET
 MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN
 AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE
 IN THE HORIZONTAL POSITION.
  
 13. TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEMS.
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
  
 IF APPLICABLE, CONTACT WILL NEED TO BE MADE TO MARK
 FILLA, PALM BEACH COUNTY PUBLIC SAFETY RADIO SYSTEMS
 MANAGER, [email protected], 561-233-0837; AS OUR RADIOS
 OPERATE ON THEIR SYSTEM FOR DETAILED RADIO FREQUENCY
 AND INSTALLATION INSTRUCTIONS.
  
 14. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
 15. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 07-13-2023 Cont ID  
Sent By avolcy Date 07-12-2023 Time 11:44 Rev Time 0.00
Received By avolcy Date 07-12-2023 Time 11:44 Sent To  
Notes
2023-07-13 11:45:30LANDSCAPE PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 07.12.2023
 PRJECT NUMBER: Z22070019
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PRIOR TO THE REMOVAL OF ANY EXISTING TREES ON THE
 PROPERTY, A TREE ALTERATION PERMIT SHALL BE OBTAINED
 FROM THE DEVELOPMENT SERVICES DEPARTMENT PLANNING
 DIVISION. PLEASE CONTACT SMITH AMISIAL, LANDSCAPE
 PLANNER, AT 561.822.1562 OR [email protected]
  
 2. A SEPARATE LANDSCAPE PERMIT SHALL BE OBTAIN FOR
 INSTALLATION OF ALL LANDSCAPE MATERIAL REQUIRED BY
 ARTICLE XIV OF THE CITYS ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 3. PROVIDE LOCATIONS AND SCREENING FOR ALL ABOVE GROUND
 UTILITY VALVES, BACKFLOW PREVENTERS, AND IRRIGATION
 BACKFLOWS.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN
 RESUBMITTING:
 A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
 B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED
 MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG
 WITH ONE (1) REDUCED COPY (11 IN X 17 IN).
 C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
 D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 GAISHA (ANNE-CLERISSE) VOLCY, PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1552
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 08-10-2022 Cont ID  
Sent By rcaranci Date 08-10-2022 Time 17:52 Rev Time 0.00
Received By rcaranci Date 08-10-2022 Time 17:52 Sent To  
Notes
2022-08-10 17:52:42FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 5111 BROADWAY MIXED USE Z22070019
 AUGUST 10, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. REMOVE REFERENCES TO DADE COUNTY IN THE LANDSCAPE
 LEGEND.
  
 2. PROVIDE HOW THE PREPARER OF THE LANDSCAPE PLANS
 QUALIFIES PER FS 481 PART 2.
  
 3. PROVIDE CALCULATIONS FOR REQUIRED BUFFER TREES AT
 ONE FOR EVERY 30 FEET OR PORTION THEREOF FOR EACH
 BUFFER LENGTH, AND SHOW THE NUMBER PROVIDED. BMUD CODE
 REQUIRES THE TREES IN THE SETBACKS ADJACENT TO THE
 ROAD. SHRUBS MAY BE PLACED BETWEEN THE CURB AND
 SIDEWALK AS PART OF ROADWAY BEAUTIFICATION TO SEPARATE
 THE PUBLIC OPEN SPACE AREAS FROM TRAFFIC.
  
 4. PROVIDE CALCULATIONS FOR SHADE TREES, FLOWERING
 TREES AND SHRUBS BASED ON REQUIRED OPEN SPACE OF 40%
 PER SECTION 94-442 (C)(2)B.
  
 5. SHOW THE TOTAL PERVIOUS LANDSCAPE AREA FOR THE SITE
 AND THE PERCENTAGE OF SITE FOR THE MINIMUM 15%
 REQUIRED.
  
 6. SOD AREA EXCEEDS THE 60% LIMIT PER SECTION
 94-442(C)(2)B.3.
  
 7. MULTIFAMILY REQUIREMENTS OF SECTION 94-443(D) SHALL
 APPLY FOR THE ADDITIONAL TREES REQUIRED AT ONE PER UNIT
 ADDED TO THE OVERALL SHADE TREE AND FLOWERING TREE
 REQUIREMENT. SHOW TOTAL REQUIRED AND PROVIDED.
  
 8. SHOW LINEAR FOOTAGE OF LANDSCAPED AREA ADJACENT TO
 THE BUILDING MEETS THE REQUIREMENT OF 40 PERCENT PER
 SECTION 94-443(D)(2) B.
  
 9. PROVIDE THE PLANT MATERIAL SIZES AT INSTALLATION AND
 SPECIFY FLORIDA GRADE#1 OR BETTER PER SECTION
 94-445(4).
  
 10. PROVIDE THE FLORIDA FRIENDLY LANDSCAPE DESIGN
 OPTIONS CHART SECTION 94-446 (G) AND PROVIDE THE
 REQUIRED 50 POINTS.
  
 11. SHOW COMPLIANCE WITH SECTION 94-445 L. PLANT
 SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL
 ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT
 SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF
 SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA
 WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA
 LANDSCAPES.
  
 12. SHOW THE LOCATIONS OF WATER AND SEWER LINES ON THE
 LANDSCAPE AND RESOLVE ANY CONFLICTS WITH TREES AND
 LANDSCAPING. RELOCATE UTILITY LOCATIONS OR EXPAND
 LANDSCAPE AREAS TO ACCOMMODATE REQUIRED LANDSCAPING.
 SHOW LOCATIONS OF FPL TRANSFORMERS ON THE LANDSCAPE
 PLAN AND RESOLVE CONFLICTS WITH LANDSCAPING.
  
 13. PROVIDE A DETAIL AND LOCATIONS OF ROOT BARRIERS TO
 SEPARATE LANDSCAPING FROM UTILITY LINES.
  
 14. PROVIDE SCREENING FOR ALL GROUND MOUNTED VALVES AND
 EQUIPMENT.
  
  
 15. SHOW THE LOCATIONS OF ALL SITE LIGHTING ON THE
 LANDSCAPE PLAN AND RESOLVE ANY CONFLICTS WITH TREES.
  

Review Stop PU PUBLIC UTILITIES
Rev No 2 Status F Date 07-13-2023 Cont ID  
Sent By relizond Date 07-13-2023 Time 12:28 Rev Time 0.00
Received By relizond Date 07-13-2023 Time 12:23 Sent To  
Notes
2023-07-13 12:28:48-PROVIDE DEMOLITION/EXISTING CONDITIONS PLAN SHEET
 -SHOW ALL EXISTING LATERALS/SERVICES ALONG AMIN
 FRONTING PROJECT BOUNDARY
 -SHOW ALL EXISTING AND PROPOSED VALVES AND
 APPURTENANCES LEGIBLY
 -SPECIFY MEANS OF CONNECTION TO SEWER
 -4" TAPS PROPOSED WHEN EXISTING MAIN IS 6"
 -REFER TO WS STANDARD DETAILS FOR PROPER LOCZTION OF
 METER INSTALLATION
 -DENOTE SERVICES AS PRIVATE, AS APPLICABLE
 -ALL LATERALS/SERVICES NOT TO BE USED MUST BE CUT AND
 CAP AT THE MAIN
 -SHOW ALL DRY UTILITIES WITHIN PROJECT LIMITS
 -PROVIDE CCTV TO CONFIRM LATERAL LOCATIONS
 -DENOTE SAMPLE POINT LOCATIONS
 -PROVIDE ALL UTILITY CROSSINGS
 -PROVIDE DEMAND CALCULATIONS IN ORDER TO DETERMINE
 SUFFICIENT INCOMING FLOW FROM EXISTING MAIN
 -PROVIDE SOFT DIG INFORMATION AT POINTS OF CONNECTION

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By mtechnow Date 08-12-2022 Time 14:17 Sent To  
Notes
2022-08-12 14:17:21-PLEASE SUBMIT CCTV VIDEO FOR GRAVITY MAIN ON 51ST ST.
 PER RECORDS THE MAIN IS FROM 1926 AND WILL BE REQUIRED
 TO BE REHABBED OR REPLACED PRIOR TO CONNECTION.
 -PER RECORDS WATER MAIN IS FROM 1926 AND WILL BE
 REQUIRED TO BE REPLACED PRIOR TO CONNECTION. PLEASE
 NOTE THAT A CALCULATED IMPACT FEE WILL BE ASSESSED FOR
 THIS DEVELOPMENT'S PORTION OF THE COST.

Review Stop PU-CS PUBLIC UTILITIES CUSTOMER SRVC
Rev No 2 Status F Date 07-06-2023 Cont ID  
Sent By mhurley Date 07-06-2023 Time 11:12 Rev Time 0.00
Received By mhurley Date   Time   Sent To  
Notes
2023-07-06 11:12:39PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -DOMESTIC BACKFLOW ASSEMBLY SHOULD NOT BE IN THE
 SIDEWALK AND SHOULD BE ON PRIVATE PROPERTY. RELOCATE
 SOUTH JUST PAST THE PROPERTY LINE. ENSURE COORDINATE
 WITH LANDSCAPING PLAN AS THERE MAY BE BUSH NEARBY.
 -ADD GRAPHIC SCALE / VISUAL MEASUREMENT ICON TO CIVIL
 PLAN SHEET C204.
 -DID NOT SEE FDC ON PLANS. SHOW AND LABEL IF ONE IS
 NEEDED OR REQUIRED.
 -VERIFY PRIVATE FIRE SYSTEM WILL NOT HAVE ANY ADDED
 CHEMICALS OR AUXILIARY WATER SUPPLIES SUCH AS WELLS.
 -SHOW AND LABEL ANY PROPOSED GREASE TRAPS OR
 TRANSFORMER PADS IF THEY ARE OUTSIDE BUILDING.
 -WILL IRRIGATION WATER BE FED BY THE DOMESTIC METERED
 WATER SERVICE?
 -ADD WATER AND SEWER DEMAND CALCULATIONS TO SHEET C204.
 RESPECTFULLY,
 MARK HURLEY [email protected]

Review Stop PU-CS PUBLIC UTILITIES CUSTOMER SRVC
Rev No 1 Status F Date 08-05-2022 Cont ID  
Sent By mhurley Date 08-05-2022 Time 17:58 Rev Time 0.00
Received By mhurley Date   Time   Sent To  
Notes
2022-08-05 17:58:43PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -THE FIRST SURVEY GENERAL NOTE SAYS NO SEARCH OF PUBLIC
 RECORD HAS BEEN MADE. WHEN WILL SEARCH BE CONDUCTED?
 -FOR ENGINEERING DEVELOPMENT SUBMITTAL: VERIFY WATER
 MAIN PIPE SIZE AND MATERIAL TYPE ? WPB GIS SAYS 6 INCH
 CAST IRON FROM 1926; VERIFY SANITARY SEWER MAIN PIPE
 SIZE AND MATERIAL TYPE ? WPB GIS SAYS 12 INCH VCP FROM
 1925; VERIFY LOCATION OF WATER AND SEWER MAINS.
 -ADD VISUAL MEASUREMENT SCALE ICONS TO CIVIL PLAN
 SHEETS.
 -ADD GATE VALVE ON PROPOSED FIRELINE JUST INSIDE
 PROPERTY LINE. LABEL IT FIRELINE POINT OF SERVICE GATE
 VALVE.
 -CITY DOES NOT OFFER 1.25 INCH WATER METERS. COULD DO
 EITHER 1 INCH METER WITH 1 INCH SERVICE LINE OR 1.5
 INCH METER WITH 2 INCH SERVICE LINE.
 -CALLOUT FIRELINE PIPE BETWEEN TAP AND PROPERTY LINE AS
 DIP. ALSO ADD SIZE TO THAT LABEL.
 -ENLARGED WATER SEWER PLAN SHOWS BUSH AND WATER METER
 BOX OVERLAPPING. PLEASE PROVIDE CLEARANCE DISTANCE.
 -ON WATER SEWER PLAN, CALLOUT THE MINIMUM HORIZONTAL
 CLEARANCE DISTANCE BETWEEN THE TWO WATER TAPS. ALSO
 CALLOUT THE MINIMUM HORIZONTAL CLEARANCE DISTANCE
 BETWEEN THE SANITARY SEWER SERVICE AND FIRELINE WATER
 SERVICE.
 -ON CIVIL PLANS, CLEARLY SHOW THE TERMINAL ENDS OF THE
 6 FOOT WOODEN FENCE NEAR THE SOUTHEAST AND NORTHWEST
 AREAS OF PROPERTY. ENSURE FENCE DOES NOT CONFLICT WITH
 BACKFLOW ASSEMBLIES.
 -SHOW BOUNDARIES OF PAVEMENT RESTORATION ON 51ST ST
 RELATED TO THE PROPOSED UTILITY WORK. BOUNDARIES SHOULD
 COMPLY WITH STANDARD DETAIL P-4.
 -ON WATER PLAN, SHOW AND LABEL THE NEAREST FIRE
 HYDRANT.
 -SHOW FULL WIDTH OF 51ST ST INCLUDING OPPOSITE CURB
 AREA.
 -APPLICANT MAY BE REQUIRED TO UPGRADE EXISTING WATER OR
 SEWER MAINS UPON REVIEW OF CITY OR EOR AT ENGINEERING
 DEVELOPMENT SUBMITTAL.
 -DID NOT SEE FDC ON CIVIL PLANS. IF IT IS NEEDED OR
 REQUIRED, SHOW AND LABEL IT. VERIFY IT IS AN ACCEPTABLE
 DISTANCE FROM NEAREST FIRE HYDRANT.
 -SHOW AND LABEL PROPOSED UTILITY EASEMENT. BACKFLOW
 ASSEMBLIES SHOULD NOT BE IN UTILITY EASEMENT.
 -VERIFY NO AUXILIARY WATER SUPPLIES SUCH AS WELLS WILL
 BE CONNECTED TO FIRE SYSTEM.
 -SITE PLAN SHOWS AN EASEMENT NEAR EAST PROPERTY LINE.
 WHAT TYPE OF EASEMENT IS IT? ALSO SHOW THE BOUNDARIES
 MORE CLEARLY.
 -HISTORIC PICTURES SHOW OVERHEAD UTILITIES NEAR SOUTH
 PROPERTY LINE EXTENDING OUT NORTH FROM POLES. WILL
 PROPOSED BUILDING ENCROACH ON THEM?
 -PROPERTY APPRAISER SHOWS ADDRESS AS 5111 BROADWAY. IS
 THE ADDRESS CHANGING?
 -SHOW AND LABEL ALL EXISTING UTILITIES SUCH AS EXISTING
 METER BOX NEAR NORTHWEST AREA OF PROPERTY AND CLEANOUTS
 LABELED ON SURVEY. ADD WHAT IS HAPPENING TO THEM ON
 LABELS.
 -SHOW AND LABEL ANY PROPOSED GREASE TRAPS IF THEY ARE
 OUTSIDE BUILDING.
 -VERIFY IF THERE IS AN EXISTING UTILITY EASEMENT ALONG
 SOUTH SIDE OF PROPERTY.
 -VERIFY DIRECTION FACING ON A2-1.02, A2 1.03, A2 1.04
 -POSITION OF TREES BETWEEN DIFFERENT PLAN SETS DOES NOT
 LOOK SIMILAR. PLEASE MAKE SURE ALL PLANS SETS SHOW
 UTILITIES AND TREES IN THE SAME POSITIONS. ENSURE THERE
 IS ADEQUATE SPACING BETWEEN THEM.
 -WILL IRRIGATION ALSO RUN OFF THE DOMESTIC WATER
 SERVICE?
 -SHOW AND LABEL EXISTING STORMWATER UTILITIES INCLUDING
 THE STRUCTURES AND PIPE ON 51ST ST.
 -AT THE DATUM STATEMENTS ON EACH SHEET ALSO ADD
 CONVERSION EQUATION.
 -HISTORIC PICTURES SHOW COUPLE OF DRIVEWAY APPROACHES
 AT EAST SIDE OF PROPERTY. VERIFY THE INTENTION IS TO
 ADD CURBING AND SHOW THAT BETTER ON PLANS.
 RESPECTFULLY,
 MARK HURLEY
 [email protected]
  

Review Stop PW PUBLIC WORKS
Rev No 2 Status P Date 07-14-2023 Cont ID  
Sent By   Date 07-14-2023 Time   Rev Time 0.00
Received By   Date 07-14-2023 Time   Sent To  
Notes
2023-07-14 09:56:32NO FURTHER COMMENTS FROM DEPARTMENT OF PUBLIC WORKS.
  
 DEPT. OF PUBLIC WORKS
 MATT HEJAZI
 [email protected]

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 08-10-2022 Cont ID  
Sent By   Date 08-10-2022 Time   Rev Time  
Received By   Date 08-10-2022 Time   Sent To  
Notes
2022-08-10 07:11:10 
 PLEASE PROVIDE THE FOLLOWINGS:
 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID
 WASTE VOLUME PRODUCED ALONG WITH THE SIZE, TYPE AND
 QUANTITY OF THE CONTAINER (I.E. DUMPSTER/COMPACTOR)
 THAT WILL BE UTILIZED FOR THE SANITATION SERVICE.
 2- DETAILS FOR SANITATION SERVICE (I.E. SOLID WASTE
 CONTAINER(S) TYPE, COLLECTION LOCATION, ETC.). FOR A
 FREESTANDING SITE DUMPSTER ENCLOSURE, THE ENCLOSURE
 SHALL COMPLY WITH THE LATEST REVISION OF CITY OF WEST
 PALM BEACH GENERAL CONSTRUCTION-GARBAGE ENCLOSURE
 STANDARD, GC-7. (LINK TO THE LATEST REVISION OF THE
 GC-7 DOCUMENT: HTTPS://WWW.WPB.ORG/HOME/SHOWPUBLISHEDDO
 CUMENT/3690/637629060422100000)
 3- DESIGNATED LOCATION FOR THE BULK ITEM PICK UP AND
 RECYCLING CONTAINERS
 4- OWNERS AND/OR OCCUPANTS OF PROPERTY THAT REQUIRE
 GREASE HAULING SERVICES SHALL ENSURE THAT THEIR GREASE
 TANKS OR CONTAINERS REMAIN CLEAN, AND ARE ENCLOSED AND
 NOT IN PUBLIC VIEW.
 5- IN CASE OF PROPOSING ADDITION OF ANY NEW CAN(S) IN
 THE CITY`S RIGHT-OF-WAY , THE LOCATION AND QUANTITY OF
 THE CAN(S) SHALL BE REVIEWED AND APPROVED BY PUBLIC
 WORKS DEPARTMENT AND THE CAN(S) SHALL BE TYPE, SIZE AND
 COLOR APPROVED BY PUBLIC WORKS DEPARTMENT. THE BUILDING
 MAINTENANCE IS RESPONSIBLE TO MAINTAIN AND SERVICE THE
 CAN(S).
 6- ALL THE PARKING STALL PAINTING SHALL COMPLY WITH THE
 CITY`S MUNICIPAL CODE SECTION 94-485 AND FLORIDA
 STATUES [553.5041 F.S.].
 7- ALL STRIPING AND SIGNAGE SHALL COMPLY WITH THE
 LATEST CITY OF WEST PALM BEACH STANDARD DETAILS AND
 MEET THE M.U.T.C.D. LATEST EDITION.
 8- ALL PAVEMENT MARKING , SIGNING AND SIDEWALK DAMAGED
 DURING CONSTRUCTION SHALL BE RESTORED.
  
  
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045
  

Review Stop STORM STORMWATER
Rev No 2 Status F Date 07-13-2023 Cont ID  
Sent By tward Date 07-13-2023 Time 09:26 Rev Time 0.00
Received By tward Date 07-13-2023 Time 09:32 Sent To  
Notes
2023-07-13 09:26:44THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. BROADWAY AVE R/W IS MAINTAINED BY FDOT. ANY
 IMPROVEMENTS WITHIN THE R/W ARE TO BE APPROVED BY FDOT.
  
 2. SHOW MILL AND RESURFACING LIMITS ON THE PUBLIC ROADS
 DUE TO THE UTILITY TRENCH CUTS.
  
 3. LABEL THE STORM PIPES (SIZE, MATERIAL) ON SHEET
 C-201.
  
 4. SHOW THE EXISTING DRAINAGE STRUCTURES IN THE RIGHT
 OF WAY.
  
 5. SHOW AND LABEL (SIZE, MATERIAL, TYPE) EXISTING
 UTILITIES IN THE R/W???S.
  
 6. CALL OUT TO REPLACE DRIVEWAY APRON AND DROP CURB
 WITH TYPE F CURB AND GUTTER OUTSIDE OF THE PROPOSED
 DRIVEWAY ON 51ST ST.
  
 7. CALL OUT TO REPLACE THE DROP CURB AND SIDEWALK ON
 THE BROADWAY AVE. FRONTAGE WITH TYPE F CURB AND GUTTER
 AND SIDEWALK WITH CROSS SLOPE OF 2% OR FLATTER.
  
 8. SHOW DROP CURB ACROSS THE PROPOSED DRIVEWAY.
  
 9. NOTE STRIPING IS CALLED OUT AS 24 INCH WHITE STRIPE
 ON THE STRIPING PLAN, SHEET C-202.
  
 10. CIVIL PLANS HAVE A DRAFT WATERMARK.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP
 CRITERIA. STORMWATER CALCULATIONS WILL BE REVIEWED WITH
 THE ENGINEERING PERMIT SUBMITTAL.
  
 2. PROVIDE COPY OF SFWMD ERP AND FDEP NPDES
 CONSTRUCTION PERMIT, IF APPLICABLE, BEFORE START OF
 CONSTRUCTION.
  
 3. PROVIDE EROSION AND SEDIMENT CONTROL PLAN WITH THE
 ENGINEERING PERMIT SUBMITTAL.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 [email protected]
  

Review Stop STORM STORMWATER
Rev No 1 Status F Date 08-12-2022 Cont ID  
Sent By tward Date 08-12-2022 Time 10:25 Rev Time 0.00
Received By tward Date 08-12-2022 Time 10:31 Sent To  
Notes
2022-08-12 10:26:08THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. THE CITY'S OFFICIAL VERTICAL DATUM IS NGVD1929. THE
 CITY HAS ALLOWED THE USE OF NAVD1988 AS LONG AS THE
 CONVERSION EQUATION TO NGVD1929 AT THE PROJECT LOCATION
 IS PROVIDED. PROVIDE THE VERTICAL DATUM CONVERSION TO
 NGVD1929 ON THE SURVEY. LIST THE REFERENCED VERTICAL
 DATUM AND CONVERSION EQUATION TO NGVD1929 ON ALL SHEETS
 WITH ELEVATION INFORMATION.
  
 2. SHOW THE EXISTING CATCH BASINS AND STORM PIPE ON
 51ST ST ON ALL OF THE PLAN SHEETS.
  
 3. EXISTING DRIVEWAY AND DROP CURB ON 51ST ST APPEARS
 WIDER THAN WHAT IS NEEDED FOR THE DEVELOPMENT. REMOVE
 THE EXCESS DRIVEWAY APRON AND DROP CURB AND REPLACE
 WITH LANDSCAPING AND TYPE F CURB AND GUTTER (INCLUDING
 TRANSITIONS TO DROP CURB). SHOW CURB AND GUTTER ON 51ST
 ST AND ON BROADWAY AVE.
  
 4. BROADWAY AVE IS MAINTAINED BY FDOT. ANY IMPROVEMENTS
 WITH THE BROADWAY AVE ARE TO BE APPROVED BY FDOT.
 COORDINATE WITH FDOT THE EXISTING CURB CUTS ON BROADWAY
 AVE.
  
 5. DRAWING NO. S-100
 A. CAN YOU PROVIDE A COPY OF THE TOPOGRAPHIC SURVEY BY
 PREMIER DESIGN SOLUTIONS INC. REFERENCED IN THE FIFTH
 PARAGRAPH UNDER GENERAL NOTES?
 B. CAN YOU PROVIDE THE CTA SURVEY REFERENCED IN THE
 FIRST PARAGRAPH UNDER CITY OF WEST PALM BEACH WATER
 MAIN SYSTEM NOTES?
 C. MINIMUM DEPTH OF COVER FOR ALL WATER MAINS IS 36
 INCHES.
 D. "MAXIMUM DEFECTION (SIC) PER EACH JOINT SHALL BE 3'
 WHERE DEFLECTION IS REQUIRED." WHAT DOES THIS MEAN?
 E. TWO DIFFERENT PHONE NUMBERS LISTED FOR ONE CALL
 SUNSHINE.
 F. MINIMUM CLEARANCE BETWEEN STORM STRUCTURES AND WATER
 MAINS SHALL BE 3 FEET, NOT 2 FEET.
 G. MINIMUM VERTICAL CLEARANCE FOR WATER MAINS PASSING
 UNDER OTHER UTILITIES IS 12 INCHES (OUTSIDE WALL TO
 OUTSIDE WALL), NOT 18 INCHES.
  
 6. DRAWING NO. S-101
 A. UNDER "GENERAL CONDITIONS" 'REPLANTING' OR
 'REPLATTING'
 B. UNDER "CIVIL DESIGN CRITERIA" - WHAT AGENCY GOES BY
 THE LETTERS S.F.W.M.D.C.?
 C. UNDER "APPLICABLE CODES" - NAVD1988 IS THE
 ABBREVIATION FOR NORTH AMERICAN VERTICAL DATUM 1988.
 NGVD1929 IS NATIONAL GEODETIC VERTICAL DATUM 1929.
 D. UNDER "TEMPORARY FACILITIES" - REMOVE REFERENCE TO
 POMPANO BEACH.
 E. UNDER "STORM DRAINAGE INSTALLATIONS:", WHAT IS BCPS?
  
 7. DRAWING NO. S-200:
 A. LABEL THE PARALLEL LINES RUNNING EAST-WEST AND
 NORTH-SOUTH THROUGH THE SIDEWALK AND DRIVEWAY ALONG
 51ST STREET.
 B. SEVERAL PROPOSED SPOT GRADES ON THE SIDEWALKS ARE
 LISTED AS F.F.E.
 C. WHAT DOES THE 'X+' REPRESENT FOR THE EXISTING AND
 PROPOSED ELEVATIONS?
 D. PROVIDE EXISTING SPOT GRADES ALONG THE EDGE OF
 PAVEMENT OF BROADWAY AVE AND 51ST ST
 E. PROVIDE EXISTING SPOT GRADES ALONG THE SOUTH AND
 WEST PROPERTY LINES.
 F. PROVIDE CROSS SECTIONS FOR ALL FOUR PROPERTY LINES.
 EXTEND FROM FACE OF THE BUILDING TO 5 FEET BEYOND THE
 SOUTH AND WEST PROPERTY LINES AND TO THE CENTERLINES OF
 BROADWAY AVE AND 51ST ST. SHOW AND LABEL PROPERTY
 LINES, STREET R/W NAME, ALL GRADE BREAKS AND SURFACE
 FEATURES (FENCE, SIDEWALK, CURB AND GUTTER,
 LANDSCAPING, SIDEWALK, BUILDING WALL AND F.F.E.).
 PROVIDE DIMENSIONS FROM PROPERTY LINE TO THE SURFACE
 FEATURES.
  
 8. DRAWING NO. S-202
 A. PARKING STRIPE DETAIL - CITY STANDARD IS PARALLEL 4
 INCH STRIPES SEPARATED BY 12 INCHES CLEAR AND JOINED AT
 ONE END WITH A 4 INCH STRIPE. DETAIL ON THE PLANS SHOWS
 16 INCH CLEAR SPACE WITH NO CONNECTING STRIPE.
 B. NORTH EDGE OF STOP BAR STRIPE SHOULD BE 4 FEET FROM
 THE BACK OF SIDEWALK. PLAN SHOWS THE SOUTH EDGE AT 4
 FEET FROM THE BACK OF SIDEWALK.
 C. HANDICAP SIGN MISSPELLED (SING).
 D. WHAT ARE THE PROPOSED 24 INCH WHITE STRIPES CALLED
 OUT ON THE RIGHT SIDE OF THE PLAN VIEW?
  
 9. DRAWING NO. S-204:
 A. SHOW LIMITS OF MILLING AND RESURFACING
 B. CALL OUT AN EASEMENT FOR THE WATER METER AND SEWER
 CLEANOUT.
 C. PVC MISSPELLED (PCV) FOR 6 INCH LATERAL.
  
 10. DRAWING NO. C-500, STANDARD DETAIL ST-8 - CONFIRM
 THE 20 FEET DEPTH IN THE TRENCH SCHEDULE.
  
 11. DRAWING NO. C-501: DRAINAGE TABLE -
 A. SWITCH COLUMN HEADINGS FOR NORTH AND SOUTH.
 B. SWITCH COLUMN HEADINGS FOR EAST AND WEST.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP
 CRITERIA. STORMWATER CALCULATIONS WILL BE REVIEWED WITH
 THE ENGINEERING PERMIT SUBMITTAL.
  
 2. PROVIDE COPY OF SFWMD ERP PERMIT BEFORE START OF
 CONSTRUCTION.
  
 3. PROVIDE EROSION AND SEDIMENT CONTROL PLAN WITH THE
 ENGINEERING PERMIT SUBMITTAL.
  
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 2 Status F Date 07-10-2023 Cont ID  
Sent By vnoel Date 07-10-2023 Time 10:42 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2023-07-10 10:58:121. PLEASE PROVIDE COPY OF TITLE POLICY.
 2. ADDITIONAL BROADWAY RIGHT-OF-WAY (APPROX. 7' ) WAS
 TAKEN PER MAINTENANCE MAP IN ROAD PLAT BOOK 7, PG. 1 -
 REFLECT ON SURVEY AND ALL PLANS.
 3. LEGAL DIMENSION OF E-W LOTS ARE 100' PER PLAT, NOT
 95.59' PER LEGAL. CHECK SPELLING OF LEGAL.
 4. ADD PARENT BENCHMARK INFORMATION.
  
 WILL BE ADDITIONAL REVIEW AFTER RECEIPT OF TITLE POLICY
 AND REVISED SURVEY.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 08-09-2022 Cont ID  
Sent By vnoel Date 08-09-2022 Time 12:38 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2022-08-09 12:51:541. SURVEY DOES NOT MEET STANDARDS OF PRACTICE
 2. NO BEARINGS/ANGLES SHOWN. SHOW DIFFERENCE BETWEEN
 MEASURED AND PLAT DISTANCES.
 3. FLOOD DATA IS NOT TOWN OF LANTANA.
 4. SURVEY CALL OUT PINE STREET HOMES?
 5. ADD CONVERSION TO NGVD-29.
 6. UNUSED WATER AND SEWER SERVICES TO BE CUT BACK TO
 MAIN.
 7. UNITY OF TITLE WILL BE REQUIRED.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status F Date 07-13-2023 Cont ID  
Sent By   Date 07-13-2023 Time   Rev Time 0.00
Received By   Date 07-13-2023 Time   Sent To  
Notes
2023-07-13 07:47:121) PROVIDE A CLEAN TRANSPORTATION SPECIFIC SITE PLAN
 FOR THE GROUND FLOOR. SHOWCASING TRANSPORTATION RELATED
 FEATURES (E.G. ROADWAY, DRIVING AISLES, PARKING STALLS,
 SIDEWALK, CURB, GUTTER, DRIVEWAY, GATES, ETC.) PROPERLY
 LABELED AND DIMENSIONED. SHEET C-202 IS A STARTING
 POINT, BUT NEEDS TO BE LARGER. PLEASE REMOVE ANY
 NON-RELEVANT CALLOUTS
 2) IN THE TRANSPORTATION SITE PLAN, PLEASE SHOWCASE
 BASIC CURB DETAILS (E.G. DRIVEWAY, CURB CUTS, PAVEMENT
 MARKINGS, PARKING STALLS, ETC.) ON THE OPPOSITE SIDE OF
 THE ROADS SURROUNDING THE PROPOSED DEVELOPMENT
 3) PROVIDE PARKING TABLE SHOWCASING THE NUMBER OF
 REQUIRED AND PROVIDED PARKING SPACES, INCLUSIVE OF ADA
 AND BICYCLE ONES
 4) PROVIDE A TURNAROUND SPACE AT THE DEAD-END OF THE
 PARKING LOT AND MARK IT OR CALL IT OUT ACCORDINGLY
 5) PER FDOT LETTER, THE 51ST ST DRIVEWAY SHOULD BE
 RIGHT-IN/RIGHT-OUT. PLEASE INSTALL SIGNAGE AND PAVEMENT
 MARKINGS ACCORDINGLY
 6) THE NORTHERN PARKING STALLS, INCLUSIVE OF THE ADA
 ONE, ARE TOO CLOSE TO THE EDGE OF THE ROAD. PER FDOT
 LETTER, A MINIMUM OF 25 FEET DRIVEWAY THROAT MUST BE
 PROVIDED. SUCH DISTANCE IS CALCULATED BETWEEN THE EDGE
 OF THE TRAVEL LANE ABUTTING THE DRIVEWAY AND THE FIRST
 CONFLICT POINT WITHIN THE PARKING LOT. PLEASE DEPICT
 SUCH DISTANCE AND REVISE PARKING STALLS CONFIGURATION,
 IF NECESSARY
 7) PER CITY CODE 94-305(E), NO CONSTRUCTION, PLACEMENT,
 OR MAINTENANCE OF A STRUCTURE WALL, SIGN, FENCE, BERM,
 PLANT MATERIAL, SHRUBS, OR ANY SIMILAR ITEM BETWEEN 18
 INCHES OR EIGHT FEET IN HEIGHT WITHIN THE VISIBILITY
 TRIANGLE. THE PLACEMENT AND SHAPE OF THE PROPOSED ART
 INSTALLATION MAY NOT COMPLY WITH SUCH REQUIREMENT.
 PLEASE REVISE OR PROVIDE FURTHER DETAILS
 8) INSTALL NO-PARKING SIGNS EAST AND WEST OF THE
 PROPOSED DRIVEWAY
 9) PROVIDE AUTOTURN ANALYSIS FOR GARBAGE TRUCK AND/OR
 SERVICE VEHICLES DRIVING IN AND OUT OF THE PROPOSED
 DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES AND WHEEL
 PATHS CLEARLY DISTINCT AND DEFINED IN DIFFERENT COLORS.
 PLEASE PROVIDE DOCUMENT NAME AND SHEET NUMBER
 10) PROVIDE A CONSTRUCTION MANAGEMENT PLAN. PLEASE
 REFER TO CITY CODE 86-246 FOR DETAILS
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 08-11-2022 Cont ID  
Sent By   Date 08-11-2022 Time   Rev Time  
Received By   Date 08-11-2022 Time   Sent To  
Notes
2022-08-11 03:56:361) PROVIDE A TRANSPORTATION SPECIFIC SITE PLAN FOR THE
 GROUND FLOOR. SHOWCASING TRANSPORTATION RELATED
 FEATURES (E.G. ROADWAY, DRIVING AISLES, PARKING STALLS,
 SIDEWALK, CURB, GUTTER, DRIVEWAY, GATES, ETC.) PROPERLY
 LABELED AND DIMENSIONED. SHEET S-202 IS A STARTING
 POINT
 2) IN THE TRANSPORTATION SITE PLAN, PLEASE SHOWCASE
 BASIC CURB DETAILS (E.G. DRIVEWAY, CURB CUTS, PAVEMENT
 MARKINGS, PARKING STALLS, ETC.) ON THE OPPOSITE SIDE OF
 THE ROADS SURROUNDING THE PROPOSED DEVELOPMENT
 3) PROVIDE PARKING TABLE SHOWCASING THE NUMBER OF
 REQUIRED AND PROVIDED PARKING SPACES, INCLUSIVE OF ADA
 AND BICYCLE ONES
 4) PROVIDE A TURNAROUND SPACE AT THE DEAD-END OF THE
 PARKING LOT
 5) S-202 PAVEMENT MARKING AT THE EXIT LANE IS
 INCORRECT, VEHICLES SHOULD BE ALLOWED TO TURN LEFT AND
 RIGHT. PLEASE REVISE
 6) THE NORTHERN PARKING STALLS, INCLUSIVE OF THE ADA
 ONE, ARE TOO CLOSE TO THE EDGE OF THE ROAD. PER FDOT
 ACCESS MANAGEMENT GUIDELINES, A MINIMUM OF 30 FEET
 DRIVEWAY THROAT MUST BE PROVIDED. SUCH DISTANCE IS
 CALCULATED FROM THE EDGE OF PAVEMENT TO THE FIRST
 CONFLICT POINT WITHIN THE PARKING LOT. PLEASE DEPICT
 SUCH DISTANCE AND REVISE PARKING STALLS CONFIGURATION
 ACCORDINGLY
 7) PER CITY CODE 94-305(E), NO CONSTRUCTION, PLACEMENT,
 OR MAINTENANCE OF A STRUCTURE WALL, SIGN, FENCE, BERM,
 PLANT MATERIAL, SHRUBS, OR ANY SIMILAR ITEM BETWEEN 18
 INCHES OR EIGHT FEET IN HEIGHT WITHIN THE VISIBILITY
 TRIANGLE. THE PLACEMENT AND SHAPE OF THE PROPOSED ART
 INSTALLATION MAY NOT COMPLY WITH SUCH REQUIREMENT.
 PLEASE REVISE OR PROVIDE FURTHER DETAILS
 8) INSTALL NO-PARKING SIGNS EAST AND WEST OF THE
 PROPOSED DRIVEWAY
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 07-13-2023 Cont ID  
Sent By avolcy Date 07-12-2023 Time 09:50 Rev Time 0.00
Received By avolcy Date 07-11-2023 Time 11:47 Sent To  
Notes
2023-07-13 09:03:39PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW
 ________________________________________
  
 DATE OF REVIEW: 07.12.2023
 PROJECT NO.: Z22070019
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PER THE CITYS ZLDR SECTION 94-221(D)(10) DUMPSTERS
 AND STORAGE AREAS SHALL BE LOCATED AT THE REAR OF THE
 PROPERTY AND SHALL BE ENCLOSED IN THE BUILDING OR A
 STRUCTURE CONSISTENT WITH THE ARCHITECTURE OF THE
 BUILDING. DUMPSTERS FOR FOOD SERVICE BUSINESSES SHALL
 BE FULLY ENCLOSED AND AIR-CONDITIONED.
  
 2. PROVIDE A NARRATIVE ON HOW THIS PROJECT MEETS THE
 ARCHITECTURAL STANDARDS OF BMUD TYPE II ZONING
 DISTRICT. REFER TO SECTION 94-221(D)
  
 3. UPDATE THE SITE DATA TABLE TO INCLUDE THE REQUIRED
 AND PROPOSED BICYCLE PARKING. REFER TO THE CITYS ZLDR
 SECTION 94-485(Q).
  
 4. BICYLE RACK SHALL MEET THE GUIDLEINES SET FORTH IN
 THE CITYS ZLDR SECTION 94-485(Q). THEY ARE TO BE
 LOCATED IN CONVENIENT, HIGHLY-VISIBLE, ACTIVE,
 WELL-LIGHTED AREAS AND AS NEAR TO THE PRINCIPAL
 ENTRANCE OF THE BUILDING AS PRACTICABLE.
  
 5. PROVIDE ELEVATIONS / DETAILS OF BICYCLE PARKING
 FACILITY.
  
 6. PROVIDE WEST ELEVATION WALL DETAIL AND MATERIAL.
  
 7. A PRE-APPLICATION MEETING IS NECESSARY BEFORE THE
 APPLICANT CAN APPLY FOR A PERMIT FROM THE DEPARTMENT
 (FDOT) FOR ACCESS TO STATE ROAD 5/U.S. 1 FOR THE
 PROPOSED DEVELOPMENT. THE APPLICANT SHOULD CONTACT FDOT
 TO REQUEST AN ACCESS PRE-APPLICATION MEETING TO
 EVALUATE PROPOSED CONNECTIONS.
 7.1. ACCESS PRE-APPLICATION MEETINGS ARE HELD EVERY
 THURSDAY IN PERSON AND VIA MICROSOFT TEAMS.
 PRE-APPLICATION MEETINGS ARE TYPICALLY SCHEDULED TWO
 WEEKS AFTER AN APPLICATION IS RECEIVED. A NOTIFICATION
 EMAIL WITH THE DATE AND TIME OF PRE-APPLICATION MEETING
 WILL BE SENT OUT EACH MONDAY FOR THE FOLLOWING WEEK
 PRE-APPLICATION MEETING.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN
 RESUBMITTING:
 A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
 B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED
 MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG
 WITH ONE (1) REDUCED COPY (11 IN X 17 IN).
 C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
 D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 GAISHA (ANNE-CLERISSE) VOLCY, PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1552
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 08-11-2022 Cont ID  
Sent By jroach Date 08-11-2022 Time 11:24 Rev Time 0.00
Received By jroach Date 08-11-2022 Time 11:24 Sent To  
Notes
2022-08-11 11:24:58PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW
 ________________________________________
  
 DATE OF REVIEW: 08.11.2022
 PROJECT NO.: Z22070019
 CASE NO.: ISPR 22-06
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 1. NUMEROUS AMOUNTS OF INFORMATION IS MISSING FROM THE
 SITE DATA TABLE. PLEASE REFER TO THE SITE PLAN
 CHECKLIST CONTAINED WITHIN THE DEVELOPMENT APPLICATION.
  
 2. THE SQUARE FOOTAGES OF THE RETAIL USE DIFFER BETWEEN
 THE JUSTIFICATION STATEMENT, THE PROJECT FACT SHEET,
 THE COUNTY?S TPS LETTER, ETC. ALL PLANS/DOCUMENTS SHALL
 BE CONSISTENT WITH THE CORRECT INFORMATION.
  
 3. PURSUANT TO COMMENTS BY JUSTIN STROH, PLANNING
 SPECIALIST II WITH THE FLORIDA DEPARTMENT OF
 TRANSPORTATION (FDOT), A PRE-APPLICATION MEETING IS
 NECESSARY BEFORE THE APPLICANT CAN APPLY FOR A PERMIT
 FROM THE DEPARTMENT FOR ACCESS TO BROADWAY AVENUE
 (US-1). THE APPLICANT SHOULD CONTACT FDOT TO REQUEST AN
 ACCESS PRE-APPLICATION MEETING TO COORDINATE THE
 PROPOSED CONNECTIONS. CONTACT INFORMATION WILL BE
 PROVIDED BY EMAIL.
  
 4. WHY WAS THERE A SCHOOL CAPACITY AVAILABILITY
 DETERMINATION (SCAD) ISSUED FOR A FUTURE LAND USE MAP
 AMENDMENT AND REZONING? THE SCAD SHOULD HAVE ONLY BEEN
 FOR THE DEVELOPMENT ORDER APPROVAL. PLEASE PROVIDE A
 REVISED/CORRECTED SCAD APPROVAL.
  
 5. THE OWNER?S CONSENT FORM IS INCOMPLETE AND DOES NOT
 PROVIDE THE NAME OF THE OWNER, THE AGENT/APPLICANT,
 ETC. PLEASE PROVIDE A COMPLETE AND ACCURATE OWNER?S
 CONSENT FORM.
  
 6. THE DOCUMENT FROM FLORIDA PUBLIC UTILITIES (GAS) IS
 A DEMOLITION CLEARANCE. A LETTER FROM FPU IS TO BE
 PROVIDED INDICATING THAT THE PROPOSED DEVELOPMENT DOES
 NOT ENCROACH INTO THEIR EASEMENT OR OTHERWISE INTERFERE
 WITH THEIR PROVISION OF SERVICES.
  
 7. A CONFIRMATION LETTER SHALL BE PROVIDED FROM AT&T
 INDICATING THAT THE PROPOSED DEVELOPMENT DOES NOT
 ENCROACH INTO THEIR EASEMENT OR OTHERWISE INTERFERE
 WITH THEIR PROVISION OF SERVICES.
  
 8. YOUR LANDSCAPE PLANS APPEAR TO SHOW TREES WITH
 GRATES, ETC. ALONG BOTH STREET FRONTAGES, BUT THIS IS
 NOT DEPICTED ON THE CIVIL PLANS.
  
 9. THE SIDEWALK ALONG BROADWAY NEEDS TO BE A MINIMUM OF
 8 FEET CLEAR (NO OBSTRUCTIONS). THE ?FRONTAGE LINE?
 (NOT PROPERTY LINE) FOR THE PURPOSE OF MEASURING THE
 BUILDING SETBACK SHIFTS TO THE EDGE OF THE SIDEWALK. 65
 PERCENT OF THE BUILDING NEEDS TO BE WITHIN 5 FEET OF
 THIS ADJUSTED FRONTAGE LINE. PLEASE DEPICT ACCORDINGLY
 ON THE SITE PLAN.
  
 10. ALONG THE FRONTAGE, WHERE THERE IS NO BUILDING, A
 STREETWALL SHALL BE PROVIDED THAT IS 34-72 INCHES IN
 HEIGHT.
  
 11. THE REQUIRED REAR SETBACK (ALONG WEST PROPERTY
 LINE) IS 15 FEET.
  
 12. PLEASE CLARIFY THE EASEMENT LINE THAT IS SHOWN ON
 THE SITE PLAN ALONG BROADWAY AVENUE.
  
 13. PROVIDE THE DIMENSION FROM THE BUILDING TO THE
 CENTERLINE OF THE ADJACENT STREETS (BROADWAY ? 40 FOOT
 MINIMUM).
  
 14. WALLS SHALL BE LIMITED TO 2 MATERIALS.
  
 15. STOREFRONTS ARE REQUIRED ALONG BOTH STREET
 FRONTAGES AND SHALL HAVE GLAZING ALONG A MINIMUM OF 70
 PERCENT OF THE FA?ADE LENGTH BETWEEN 2 AND 8 FEET FROM
 THE GROUND. PLANS SHALL INDICATE SUCH DIMENSIONS, AND
 THE 51ST STREET FRONTAGE DOES NOT PROVIDE ANY
 STOREFRONT.
  
 16. THE DIRECTIONS INDICATED ON THE ELEVATIONS ARE
 INCORRECT (NORTH VS. SOUTH ? EAST VS. WEST).
  
 17. STORIES ABOVE THE FIRST FLOOR SHALL HAVE CLEAR
 GLAZED AREA AND OPENINGS BETWEEN 25 PERCENT AND 45
 PERCENT OF THE FACADE AREA. PLEASE PROVIDE SUCH
 CALCULATIONS.
  
 18. WINDOWS, EXCEPT STOREFRONTS, SHALL BE OPERABLE.
  
 19. WINDOWS SHALL BE RECESSED A MINIMUM OF 2 INCHES,
 PLEASE PROVIDE A DETAIL.
  
 20. THE ELEVATION APPEARS TO SHOW AN OVERHEAD DOOR.
 THIS PRESENTS MULTIPLE CONCERNS WITH HOW THE PARKING IS
 ACCESSED, STACKING IN THE STREET, ETC.
  
 21. PLEASE CLARIFY THE FA?ADE TREATMENT ON THE GROUND
 FLOOR ALONG 51ST STREET WHERE THE PARKING IS LOCATED?
 THE PARKING NEEDS TO BE CONCEALED WITH A STREETWALL.
  
 22. THE SITE PLAN DOES NOT CLEARLY INDICATE THE
 OVERHANG PROJECTION ON THE FIRST FLOOR.
  
 23. MULTIPLE PLANS SHOW MULTIPLE PORTIONS OF THE
 BUILDING, OVERHANGS, ETC. EXTENDING OUTSIDE OF THE
 PROPERTY LINE. ALL BUILDINGS AND ASSOCIATED
 IMPROVEMENTS SHALL BE WITHIN THE PROPERTY LINE AND MEET
 THE MINIMUM SETBACK REQUIREMENTS.
  
 24. THE SITE PLAN SHOWS THE TRASH BEING ROLLED OUT INTO
 A LANDSCAPE AREA/STREET.
  
 25. A MINIMUM OF 18 PARKING SPACES SHALL BE PROVIDED,
 ONLY 16 ARE SHOWN.
  
 26. THE DRIVE AISLE IN THE PARKING AREA SHALL BE A
 MINIMUM OF 24 FEET WIDE.
  
 27. A TURN-AROUND SPACE SHALL BE PROVIDED AT THE
 DEAD-END OF THE DRIVE AISLE.
  
 28. PARKING STRIPING DETAIL SHALL BE PROVIDED.
  
 29. AT LEAST 1 LOADING SPACE SHALL BE PROVIDED (10 FEET
 X 25 FEET).
  
 30. BIKE RACKS SHALL BE PROVIDED (1 PER 20 PARKING
 SPACES). THE LOCATION SHALL BE INDICATED AND A DETAIL
 SHALL BE INCLUDED SHOWING THE TYPE OF RACK, THE
 DIMENSIONAL CLEARANCE TO SURROUNDING OBSTRUCTIONS, ETC.
  
 31. THE ACCESSIBLE PARKING SPACE SHOWS COLUMNS IN THE
 SPACE. THE SPACE SHALL BE A MINIMUM OF 12 FEET IN CLEAR
 WIDTH AND SHALL HAVE AN ADJACENT AISLE OF AT LEAST 5
 FEET IN CLEAR WIDTH.
  
 32. WHEEL STOPS SHALL BE 2 FEET FROM THE FRONT OF THE
 PARKING SPACE.
  
 33. THERE ARE NUMEROUS CONFLICTS BETWEEN THE LANDSCAPE
 PLANS AND THE ARCHITECTURAL DESIGN OF THE BUILDING,
 SPECIFICALLY THE OVERHANGS/PROJECTIONS AND THE PLANTING
 OF TREES, ETC.
  
 34. NO PORTION OF THE BUILDING SHALL EXTEND INTO THE
 VISIBILITY TRIANGLE BETWEEN A HEIGHT OF 18 INCHES AND 8
 FEET.
  
 35. PLEASE CLARIFY THE BUILDING SECTION LABELING THE
 ROOF DECK AS THE TERRACE LEVEL; IS THERE ACCESS TO THE
 ROOF (OTHER THAN MAINTENANCE)?
  
 36. PLEASE SHOW ON THE BUILDING SECTION/ELEVATIONS THE
 LOCATION AND SIZE OF THE ROOF-TOP MECHANICAL EQUIPMENT
 TO SHOW THAT IT WILL BE COMPLETELY SCREENED FROM VIEW
 BY THE PROPOSED PARAPET.
  
 37. THE ELEVATIONS INDICATE A FENCE ALONG THE ADJACENT
 PROPERTY WEST AND SOUTH PROPERTY LINES, BUT THIS IS NOT
 SHOWN ON THE SITE PLAN. SUCH FENCING SHALL BE
 DIMENSIONED. ALONG THE WEST PROPERTY LINE THERE SHALL
 BE A 72-INCH HIGH WALL (NOT FENCE).
 ________________________________________
  
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
  
 B) ELECTRONIC COPIES OF REVISED PLANS AND/OR DOCUMENTS
 SHALL BE PROVIDED.
  
 C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
  
 D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION