Plan Review Details - Project Z22070019
| Plan Review Stops For Project Z22070019 |
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
2 |
Status |
P |
Date |
07-11-2023 |
|
|
Cont ID |
|
| Sent By |
swelter |
Date |
07-11-2023 |
Time |
17:06 |
Rev Time |
0.00 |
| Received By |
swelter |
Date |
07-11-2023 |
Time |
17:09 |
Sent To |
|
|
| Notes |
| 2023-07-11 17:09:24 | PROJECT ELECTED OPTION #2 - CONTRIBUTION | | | ART ASSESSMENT RCVD. WITH RESUBMITTAL APPLICATION | | | | | | ART FEES DUE BEFORE OR AT TIME OF BUILDING PERMIT FEES | | | | | | [email protected] |
|
|
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
1 |
Status |
F |
Date |
08-09-2022 |
|
|
Cont ID |
|
| Sent By |
scwelter |
Date |
08-09-2022 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
scwelter |
Date |
08-11-2022 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2022-08-11 10:07:09 | PUBLIC ART REQUIREMENT: | | | TOTAL CONSTRUCTION COSTS OF THIS DEVELOPMENT ARE OVER | | | $500,000 IT IS SUBJECT TO THE PUBLIC ART REQUIREMENT AS | | | PER CITY ORDINANCE. | | | SECTION 78-129: ALL PRIVATE DEVELOPMENT PROJECTS, | | | INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR | | | IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL | | | CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN | | | $500,000 ARE SUBJECT TO THE PUBLIC ART REQUIREMENT. | | | OPTION 1: INSTALL ARTWORK ON THE DEVELOPMENT SITE | | | VALUED IN AN AMOUNT NOT LESS THAN ONE PERCENT OF THE | | | TOTAL CONSTRUCTION COSTS. | | | FOR SITE PLAN APPROVAL PUBLIC ART NEEDS TO BE | | | IDENTIFIED ON THE SITE PLAN. | | | OPTION 2: CONTRIBUTE AN AMOUNT EQUAL TO 75 PERCENT OF | | | ONE PERCENT OF THE TOTAL CONSTRUCTION COSTS FOR DEPOSIT | | | TO THE PUBLIC ART ACCOUNT. | | | FOR SITE PLAN APPROVAL AN EMAIL TO [email protected] | | | STATING THAT THE DEVELOPER IS CHOSEN OPTION IS | | | REQUIRED. | | | | | | FOR EITHER OPTION A COMPLETED PUBLIC ART ASSESSMENT | | | APPLICATION ALONG WITH EITHER THE ESCROW OF THE 1% OR | | | IF CHOSEN OPTION 2 CONTRIBUTION INTO THE PUBLIC ART | | | FUND IS REQUIRED AT TIME OF BUILDING PERMIT SUBMITTAL. | | | | | | CONTACT SYBILLE WELTER, ADMINISTRATOR OF PUBLIC ART & | | | CULTURE AT [email protected] WITH FURTHER QUESTIONS. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
07-12-2023 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
07-12-2023 |
Time |
22:23 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
07-12-2023 |
Time |
22:23 |
Sent To |
|
|
| Notes |
| 2023-07-12 22:26:45 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, | | | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR | | | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, | | | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE | | | FLORIDA BUILDING CODE. | | | | | | 3. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND | | | OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT, | | | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF | | | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF | | | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE | | | VERIFIED. | | | | | | 4. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, | | | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND | | | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, | | | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. | | | | | | 5. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND | | | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF | | | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL | | | NEIGHBORING PROPERTIES. | | | | | | 6. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER | | | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, | | | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE | | | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF | | | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION | | | THAT MAY AFFECT THE USE OF THEIR PROPERTY. | | | | | | 7. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT | | | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL | | | HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION | | | OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING, | | | CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT | | | (561) 805 6659, OR BY EMAIL: [email protected] | | | | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
08-11-2022 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
08-11-2022 |
Time |
12:02 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
08-11-2022 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2022-08-11 12:11:10 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. UNITY OF TITLE. FOR ANY BUILDING CROSSING A PROPERTY | | | LINE, EITHER A RECORDED UNITY OF TITLE, OR SOME OTHER | | | APPROVED LEGAL INSTRUMENT, SHALL BE INCLUDED WITH THE | | | PERMIT APPLICATION, OR THE BUILDING MUST HAVE A FIRE | | | WALL ALONG THE PROPERTY LINE, PER SECTION 202 OF | | | FLORIDA BUILDING CODE, BUILDING, FIRE SEPARATION | | | DISTANCE. | | | | | | 3. STAIR EXIT DISCHARGE TO RIGHT OF WAY. GROUND FLOOR | | | PLAN, SHEET A1-1.01, SHOWS BOTH STAIRS DISCHARGING INTO | | | THE PARKING GARAGE. A FIRE-RATED EXIT PASSAGEWAY WOULD | | | BE REQUIRED BECAUSE NO MORE THAN 50% OF THE EXIT | | | CAPACITY IA ALLOWED TO DISCHARGE WITHIN THE BUILDING | | | PER SECTION 1028.1 OF FLORIDA BUILDING CODE. | | | | | | 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, | | | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR | | | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, | | | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE | | | FLORIDA BUILDING CODE. | | | | | | 5. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND | | | OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT, | | | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF | | | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF | | | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE | | | VERIFIED. | | | | | | 6. ENCLOSED PARKING GARAGES. IT APPEARS THAT THE | | | PARKING GARAGE DOES NOT HAVE SUFFICIENT WALL OPENINGS | | | TO MEET THE DEFINITION OF AN OPEN PARKING GARAGE. IF | | | THAT IS THE CASE. IT WILL BE CONSIDERED AN ENCLOSED | | | PARKING GARAGE AND MUST HAVE EXHAUST SYSTEMS. THE | | | EXHAUST SYSTEMS SHALL BE DESIGNED TO MINIMIZE NOISE | | | LEVELS USING INLINE FAN SILENCERS OR OTHER APPROVED | | | METHODS. | | | | | | 7. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, | | | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND | | | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, | | | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. | | | | | | 8. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND | | | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF | | | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL | | | NEIGHBORING PROPERTIES. | | | | | | 9. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER | | | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, | | | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE | | | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF | | | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION | | | THAT MAY AFFECT THE USE OF THEIR PROPERTY. | | | | | | 10. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT | | | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL | | | HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION | | | OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING, | | | CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT | | | (561) 805 6659, OR BY EMAIL: [email protected] | | | | | | 11. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT | | | TO ART LIFE ASSESSMENT UNDER THE CITY OF WEST PALM | | | BEACH ART IN PUBLIC PLACES (AIPP) PROGRAM. FOR ADVICE | | | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP | | | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC | | | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
P |
Date |
07-12-2023 |
|
|
Cont ID |
|
| Sent By |
lquinone |
Date |
07-12-2023 |
Time |
12:02 |
Rev Time |
0.00 |
| Received By |
lquinone |
Date |
07-12-2023 |
Time |
12:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
07-27-2022 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
07-27-2022 |
Time |
|
Rev Time |
|
| Received By |
rrossano |
Date |
07-27-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-07-27 10:18:43 | Z22070019 - 5179 BROADWAY, MIXED USE 7.26.22 SUB | | | | | | COMMENTS FROM RICK ROSSANO, SR. PROJECT COORDINATOR, | | | ENGINEERING SERVICES AT 561-494-1098 [email protected] | | | GENERAL: | | | O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND | | | INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER | | | (Z-XXXXXXXX). | | | O THE CITY OF WEST PALM BEACH HAS A NUMBER OF | | | REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY | | | AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND | | | WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE | | | DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK | | | BELOW: | | | A. HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WP | | | B_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FUL | | | L-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97 | | | B1960045731D3658206F27451722716EF | | | B. THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE | | | FOUND HERE: | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | C. ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM | | | BEACH, FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, | | | ADOPTED SEPT. 22, 2008. (SUPPLEMENT NO. 18) | | | CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL, | | | SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER | | | SERVICE FACILITIES OF THE CITY. | | | THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE | | | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY | | | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, | | | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. | | | O AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR | | | MORE INFORMATION, REFER TO THE LINK BELOW: | | | A. HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PU | | | BLICATIONS/BACKFLOW-CROSS-CONNECTION- CONTROL-MANUAL | | | O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY | | | OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC | | | RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF | | | YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE | | | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL | | | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT | | | [email protected] OR 561-494-1079 FOR FURTHER | | | ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION | | | ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD | | | SURVEY, POT-HOLING, SOFT DIGS ETC. | | | O PROVIDE EXISTING AND PROPOSED PERVIOUS AND IMPERVIOUS | | | DATA. | | | | | | BACKFLOW ASSEMBLY AND METERS: | | | O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER | | | SERVICES AND WATER METERS, ALONG WITH WHAT IS HAPPENING | | | TO THEM. | | | O SHOW EXISTING AND PROPOSED DEDICATED UTILITY | | | EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO | | | PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO | | | STRUCTURES WITHIN EASEMENT. | | | O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION | | | OF WATER METER AND BACKFLOW | | | PREVENTION. | | | O BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY | | | OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER | | | METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO | | | PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE | | | INSTALLED ABOVE-GROUND ONLY. | | | O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE | | | NOTE USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA. | | | | | | WATER/WASTEWATER PLAN: | | | O PROVIDE VERTICAL DATUM AND DATUM CONVERSION | | | INFORMATION (NAVD 1988 AND NGVD 1929). | | | O SHOW PROJECT ADDRESS ON ALL PLAN SHEETS. | | | O PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE | | | STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC. | | | O PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND | | | DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND | | | SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH | | | PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE | | | AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS, | | | BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO | | | BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS, | | | DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS, | | | ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT | | | ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF | | | SANITARY SEWER LINES. | | | O GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR | | | SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE | | | PROFILE VIEW. | | | O DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN | | | VIEW FOR ALL SANITARY AND STORM SEWERS. | | | O SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT | | | MATERIAL. | | | O PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED | | | UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC, | | | ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION | | | FACILITIES LOCATED ON THE RIGHT-OF-WAY. | | | O PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER | | | AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD | | | DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS. | | | O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY | | | TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT | | | APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING | | | AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, | | | MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS | | | SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 | | | FOR WATER. | | | O PROVIDE FIRE FLOW TEST DATA. | | | O PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER ALONG | | | ENTIRE PROJECT FRONTAGE (CONDITION OF SITE PLAN | | | APPROVAL). | | | O CUT AND CAP UTILITIES NOT IN USE AND REMOVE ANY | | | ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY | | | ROW. | | | O WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL | | | BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY | | | PROPOSED LENGTH IN FEET. | | | O CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY | | | SEWER ARE REQUIRED. | | | O PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE | | | JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET. | | | O ADD NOTE TO PLANS SPECIFYING CITY?S DOWNSTREAM LIFT | | | STATION NUMBER. | | | O PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR | | | PROPOSED SANITARY LATERALS. | | | O LABEL WATER LINES AS PRIVATE WHERE APPLICABLE. | | | O PLEASE SHOW AND LABEL EXISTING AND PROPOSED GREASE | | | TRAPS (IF ANY). | | | O PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN | | | OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER. | | | | | | FORMAL ENGINEERING REVIEW: | | | O FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES | | | NOI REQUIREMENTS WILL BE ENFORCED. | | | - AN NOI IS REQUIRED FOR PROJECTS THAT: | | | - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS | | | THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF | | | DEVELOPMENT OR SALE; | | | - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE | | | STATE OR TO SURFACE WATERS OF THE STATE THROUGH A | | | MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4). | | | - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF | | | CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION | | | THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL | | | SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT | | | OF THE 10-2 CERTIFICATION. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF | | | WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING | | | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT | | | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING | | | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED | | | LEAD-FREE DESIGN. | | | O FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO PROVIDE | | | 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF | | | PROPOSED TRENCH IN CITY MAINTAINED ROADWAY AREAS PER | | | CITY OF WPB STANDARD DETAIL GC-8. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | CALCULATIONS OF PERVIOUS AND IMPERVIOUS AREAS FOR | | | PROPOSED IMPROVED AREAS. | | | | | | | | | | | | QUESTIONS AND COORDINATION CONTACTS: | | | O MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR WITH | | | CITY OF WPB PUBLIC UTILITIES, REGARDING PLACEMENT OF | | | BACKFLOW DEVICES AND WATER METERS. CONTACT HIM AT | | | 561-822-2262 OR [email protected] | | | O MIKE TECHNOW, PROJECT ENGINEER, PUBLIC UTILITIES | | | DEPARTMENT AT 561-494-1047 OR [email protected] | | | O TRACY WARD, SR. STORMWATER ENGINEER, ENGINEERING | | | SERVICES DEPT. AT 561-494-1120 OR [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
07-07-2023 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
07-07-2023 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
07-07-2023 |
Time |
14:43 |
Sent To |
|
|
| Notes |
| 2023-07-07 14:46:23 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE DEPARTMENT. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. THE FOLLOWING COMMENTS ARE INTENDED | | | TO PROVIDE GUIDANCE FOR BUILDING PLAN SUBMITTAL. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH | | | THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, | | | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. | | | | | | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE | | | OCCUPANCY TYPE PER THE FLORIDA FIRE PREVENTION CODE. | | | | | | 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE | | | LOAD CALCULATION IS INCLUDED, AND THAT ADEQUATE WATER | | | SUPPLY IS EXISTING OR WILL BE PROVIDED. | | | | | | 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | THE PROPOSED LOCATION OF THE FIRE HYDRANT IS ACCEPTABLE | | | IF THE FDC IS WITHIN 100' AND, IF APPLICABLE, CLOSELY | | | COORDINATED WITH THE BUREAU OF FIRE PREVENTION. | | | | | | 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER | | | THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY | | | ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM, | | | ENSURE THEY COMPLY WITH THE REQUIREMENTS OF F.A.C. 61G | | | AND SUBMITTED WITH THE MASTER PERMIT. | | | | | | 9A. THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE | | | LOCATIONS SHALL MEET AND BE INSTALLED PER THE | | | REQUIREMENTS OF NFPA 24 AND SHALL BE COORDINATED WITH | | | THE OFFICE OF FIRE MARSHAL, THE CITY'S ENGINEERS | | | OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S PLANNING | | | AND ZONING OFFICE. | | | | | | 10. COMPLETE LIFE SAFETY PLANS FOR THE OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, EXIT SEPARATION DISTANCES, COMMON PATHS OF | | | TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, EMERGENCY | | | LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE | | | EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES | | | AND EQUIPMENT. | | | | | | 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE | | | SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY | | | DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS. | | | | | | 12. ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE | | | FIGHTER?S EMERGENCY OPERATIONS REQUIREMENTS OF ASME | | | A17.1/CSA B44, SAFETY CODE FOR ELEVATORS. | | | | | | ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN | | | WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL | | | LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET | | | MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER | | | ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN | | | AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE | | | IN THE HORIZONTAL POSITION. | | | | | | 13. TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEMS. | | | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY | | | RADIO ENHANCEMENT SERVICES. | | | 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM | | | RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT | | | COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL | | | DETERMINED BY THE AHJ. | | | | | | IF APPLICABLE, CONTACT WILL NEED TO BE MADE TO KEN | | | DECKER, , PALM BEACH COUNTY PUBLIC SAFETY RADIO SYSTEMS | | | MANAGER, [email protected], 561-233-0837; AS OUR | | | RADIOS OPERATE ON THEIR SYSTEM FOR DETAILED RADIO | | | FREQUENCY AND INSTALLATION INSTRUCTIONS. | | | | | | 14. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL. | | | | | | 15. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
08-01-2022 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
08-01-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
08-01-2022 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2022-08-01 14:33:42 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE DEPARTMENT. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. THE FOLLOWING COMMENTS ARE INTENDED | | | TO PROVIDE GUIDANCE FOR BUILDING PLAN SUBMITTAL. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH | | | THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, | | | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. | | | | | | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE | | | OCCUPANCY TYPE PER THE FLORIDA FIRE PREVENTION CODE. | | | | | | 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE | | | LOAD CALCULATION IS INCLUDED, AND THAT ADEQUATE WATER | | | SUPPLY IS EXISTING OR WILL BE PROVIDED. | | | | | | 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | THE PROPOSED LOCATION OF THE FIRE HYDRANT AND FDC SHALL | | | BE WITHIN 100' OF EACH OTHER AND CLOSELY COORDINATED | | | WITH THE BUREAU OF FIRE PREVENTION. | | | | | | 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER | | | THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY | | | ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM, | | | ENSURE THEY COMPLY WITH THE REQUIREMENTS OF F.A.C. 61G | | | AND SUBMITTED WITH THE MASTER PERMIT. | | | | | | 9A. THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE | | | LOCATIONS SHALL MEET AND BE INSTALLED PER THE | | | REQUIREMENTS OF NFPA 24 AND SHALL BE COORDINATED WITH | | | THE OFFICE OF FIRE MARSHAL, THE CITY'S ENGINEERS | | | OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S PLANNING | | | AND ZONING OFFICE. | | | | | | 10. COMPLETE LIFE SAFETY PLANS FOR THE OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, EXIT SEPARATION DISTANCES, COMMON PATHS OF | | | TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, EMERGENCY | | | LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE | | | EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES | | | AND EQUIPMENT. | | | | | | 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE | | | SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY | | | DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS. | | | | | | 12. ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE | | | FIGHTER?S EMERGENCY OPERATIONS REQUIREMENTS OF ASME | | | A17.1/CSA B44, SAFETY CODE FOR ELEVATORS. | | | | | | ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN | | | WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL | | | LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET | | | MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER | | | ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN | | | AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE | | | IN THE HORIZONTAL POSITION. | | | | | | 13. TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEMS. | | | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY | | | RADIO ENHANCEMENT SERVICES. | | | 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM | | | RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT | | | COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL | | | DETERMINED BY THE AHJ. | | | | | | IF APPLICABLE, CONTACT WILL NEED TO BE MADE TO MARK | | | FILLA, PALM BEACH COUNTY PUBLIC SAFETY RADIO SYSTEMS | | | MANAGER, [email protected], 561-233-0837; AS OUR RADIOS | | | OPERATE ON THEIR SYSTEM FOR DETAILED RADIO FREQUENCY | | | AND INSTALLATION INSTRUCTIONS. | | | | | | 14. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL. | | | | | | 15. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
F |
Date |
07-13-2023 |
|
|
Cont ID |
|
| Sent By |
avolcy |
Date |
07-12-2023 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
avolcy |
Date |
07-12-2023 |
Time |
11:44 |
Sent To |
|
|
| Notes |
| 2023-07-13 11:45:30 | LANDSCAPE PLAN REVIEW | | | ________________________________________ | | | | | | DATE OF REVIEW: 07.12.2023 | | | PRJECT NUMBER: Z22070019 | | | ________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. PRIOR TO THE REMOVAL OF ANY EXISTING TREES ON THE | | | PROPERTY, A TREE ALTERATION PERMIT SHALL BE OBTAINED | | | FROM THE DEVELOPMENT SERVICES DEPARTMENT PLANNING | | | DIVISION. PLEASE CONTACT SMITH AMISIAL, LANDSCAPE | | | PLANNER, AT 561.822.1562 OR [email protected] | | | | | | 2. A SEPARATE LANDSCAPE PERMIT SHALL BE OBTAIN FOR | | | INSTALLATION OF ALL LANDSCAPE MATERIAL REQUIRED BY | | | ARTICLE XIV OF THE CITYS ZONING AND LAND DEVELOPMENT | | | REGULATIONS. | | | | | | 3. PROVIDE LOCATIONS AND SCREENING FOR ALL ABOVE GROUND | | | UTILITY VALVES, BACKFLOW PREVENTERS, AND IRRIGATION | | | BACKFLOWS. | | | | | | ________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN | | | RESUBMITTING: | | | A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL | | | DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION. | | | B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED | | | MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG | | | WITH ONE (1) REDUCED COPY (11 IN X 17 IN). | | | C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO | | | ADDITIONAL COMMENTS. | | | D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE | | | ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE | | | CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL | | | REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION. | | | ________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | GAISHA (ANNE-CLERISSE) VOLCY, PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1552 | | | TTY: 800.955.8771 | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
08-10-2022 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
08-10-2022 |
Time |
17:52 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
08-10-2022 |
Time |
17:52 |
Sent To |
|
|
| Notes |
| 2022-08-10 17:52:42 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: 5111 BROADWAY MIXED USE Z22070019 | | | AUGUST 10, 2022 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. REMOVE REFERENCES TO DADE COUNTY IN THE LANDSCAPE | | | LEGEND. | | | | | | 2. PROVIDE HOW THE PREPARER OF THE LANDSCAPE PLANS | | | QUALIFIES PER FS 481 PART 2. | | | | | | 3. PROVIDE CALCULATIONS FOR REQUIRED BUFFER TREES AT | | | ONE FOR EVERY 30 FEET OR PORTION THEREOF FOR EACH | | | BUFFER LENGTH, AND SHOW THE NUMBER PROVIDED. BMUD CODE | | | REQUIRES THE TREES IN THE SETBACKS ADJACENT TO THE | | | ROAD. SHRUBS MAY BE PLACED BETWEEN THE CURB AND | | | SIDEWALK AS PART OF ROADWAY BEAUTIFICATION TO SEPARATE | | | THE PUBLIC OPEN SPACE AREAS FROM TRAFFIC. | | | | | | 4. PROVIDE CALCULATIONS FOR SHADE TREES, FLOWERING | | | TREES AND SHRUBS BASED ON REQUIRED OPEN SPACE OF 40% | | | PER SECTION 94-442 (C)(2)B. | | | | | | 5. SHOW THE TOTAL PERVIOUS LANDSCAPE AREA FOR THE SITE | | | AND THE PERCENTAGE OF SITE FOR THE MINIMUM 15% | | | REQUIRED. | | | | | | 6. SOD AREA EXCEEDS THE 60% LIMIT PER SECTION | | | 94-442(C)(2)B.3. | | | | | | 7. MULTIFAMILY REQUIREMENTS OF SECTION 94-443(D) SHALL | | | APPLY FOR THE ADDITIONAL TREES REQUIRED AT ONE PER UNIT | | | ADDED TO THE OVERALL SHADE TREE AND FLOWERING TREE | | | REQUIREMENT. SHOW TOTAL REQUIRED AND PROVIDED. | | | | | | 8. SHOW LINEAR FOOTAGE OF LANDSCAPED AREA ADJACENT TO | | | THE BUILDING MEETS THE REQUIREMENT OF 40 PERCENT PER | | | SECTION 94-443(D)(2) B. | | | | | | 9. PROVIDE THE PLANT MATERIAL SIZES AT INSTALLATION AND | | | SPECIFY FLORIDA GRADE#1 OR BETTER PER SECTION | | | 94-445(4). | | | | | | 10. PROVIDE THE FLORIDA FRIENDLY LANDSCAPE DESIGN | | | OPTIONS CHART SECTION 94-446 (G) AND PROVIDE THE | | | REQUIRED 50 POINTS. | | | | | | 11. SHOW COMPLIANCE WITH SECTION 94-445 L. PLANT | | | SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL | | | ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT | | | SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF | | | SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA | | | WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA | | | LANDSCAPES. | | | | | | 12. SHOW THE LOCATIONS OF WATER AND SEWER LINES ON THE | | | LANDSCAPE AND RESOLVE ANY CONFLICTS WITH TREES AND | | | LANDSCAPING. RELOCATE UTILITY LOCATIONS OR EXPAND | | | LANDSCAPE AREAS TO ACCOMMODATE REQUIRED LANDSCAPING. | | | SHOW LOCATIONS OF FPL TRANSFORMERS ON THE LANDSCAPE | | | PLAN AND RESOLVE CONFLICTS WITH LANDSCAPING. | | | | | | 13. PROVIDE A DETAIL AND LOCATIONS OF ROOT BARRIERS TO | | | SEPARATE LANDSCAPING FROM UTILITY LINES. | | | | | | 14. PROVIDE SCREENING FOR ALL GROUND MOUNTED VALVES AND | | | EQUIPMENT. | | | | | | | | | 15. SHOW THE LOCATIONS OF ALL SITE LIGHTING ON THE | | | LANDSCAPE PLAN AND RESOLVE ANY CONFLICTS WITH TREES. | | | |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
2 |
Status |
F |
Date |
07-13-2023 |
|
|
Cont ID |
|
| Sent By |
relizond |
Date |
07-13-2023 |
Time |
12:28 |
Rev Time |
0.00 |
| Received By |
relizond |
Date |
07-13-2023 |
Time |
12:23 |
Sent To |
|
|
| Notes |
| 2023-07-13 12:28:48 | -PROVIDE DEMOLITION/EXISTING CONDITIONS PLAN SHEET | | | -SHOW ALL EXISTING LATERALS/SERVICES ALONG AMIN | | | FRONTING PROJECT BOUNDARY | | | -SHOW ALL EXISTING AND PROPOSED VALVES AND | | | APPURTENANCES LEGIBLY | | | -SPECIFY MEANS OF CONNECTION TO SEWER | | | -4" TAPS PROPOSED WHEN EXISTING MAIN IS 6" | | | -REFER TO WS STANDARD DETAILS FOR PROPER LOCZTION OF | | | METER INSTALLATION | | | -DENOTE SERVICES AS PRIVATE, AS APPLICABLE | | | -ALL LATERALS/SERVICES NOT TO BE USED MUST BE CUT AND | | | CAP AT THE MAIN | | | -SHOW ALL DRY UTILITIES WITHIN PROJECT LIMITS | | | -PROVIDE CCTV TO CONFIRM LATERAL LOCATIONS | | | -DENOTE SAMPLE POINT LOCATIONS | | | -PROVIDE ALL UTILITY CROSSINGS | | | -PROVIDE DEMAND CALCULATIONS IN ORDER TO DETERMINE | | | SUFFICIENT INCOMING FLOW FROM EXISTING MAIN | | | -PROVIDE SOFT DIG INFORMATION AT POINTS OF CONNECTION |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
mtechnow |
Date |
08-12-2022 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2022-08-12 14:17:21 | -PLEASE SUBMIT CCTV VIDEO FOR GRAVITY MAIN ON 51ST ST. | | | PER RECORDS THE MAIN IS FROM 1926 AND WILL BE REQUIRED | | | TO BE REHABBED OR REPLACED PRIOR TO CONNECTION. | | | -PER RECORDS WATER MAIN IS FROM 1926 AND WILL BE | | | REQUIRED TO BE REPLACED PRIOR TO CONNECTION. PLEASE | | | NOTE THAT A CALCULATED IMPACT FEE WILL BE ASSESSED FOR | | | THIS DEVELOPMENT'S PORTION OF THE COST. |
|
|
| Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
| Rev No |
2 |
Status |
F |
Date |
07-06-2023 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
07-06-2023 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2023-07-06 11:12:39 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | -DOMESTIC BACKFLOW ASSEMBLY SHOULD NOT BE IN THE | | | SIDEWALK AND SHOULD BE ON PRIVATE PROPERTY. RELOCATE | | | SOUTH JUST PAST THE PROPERTY LINE. ENSURE COORDINATE | | | WITH LANDSCAPING PLAN AS THERE MAY BE BUSH NEARBY. | | | -ADD GRAPHIC SCALE / VISUAL MEASUREMENT ICON TO CIVIL | | | PLAN SHEET C204. | | | -DID NOT SEE FDC ON PLANS. SHOW AND LABEL IF ONE IS | | | NEEDED OR REQUIRED. | | | -VERIFY PRIVATE FIRE SYSTEM WILL NOT HAVE ANY ADDED | | | CHEMICALS OR AUXILIARY WATER SUPPLIES SUCH AS WELLS. | | | -SHOW AND LABEL ANY PROPOSED GREASE TRAPS OR | | | TRANSFORMER PADS IF THEY ARE OUTSIDE BUILDING. | | | -WILL IRRIGATION WATER BE FED BY THE DOMESTIC METERED | | | WATER SERVICE? | | | -ADD WATER AND SEWER DEMAND CALCULATIONS TO SHEET C204. | | | RESPECTFULLY, | | | MARK HURLEY [email protected] |
|
|
| Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
| Rev No |
1 |
Status |
F |
Date |
08-05-2022 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
08-05-2022 |
Time |
17:58 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-05 17:58:43 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | -THE FIRST SURVEY GENERAL NOTE SAYS NO SEARCH OF PUBLIC | | | RECORD HAS BEEN MADE. WHEN WILL SEARCH BE CONDUCTED? | | | -FOR ENGINEERING DEVELOPMENT SUBMITTAL: VERIFY WATER | | | MAIN PIPE SIZE AND MATERIAL TYPE ? WPB GIS SAYS 6 INCH | | | CAST IRON FROM 1926; VERIFY SANITARY SEWER MAIN PIPE | | | SIZE AND MATERIAL TYPE ? WPB GIS SAYS 12 INCH VCP FROM | | | 1925; VERIFY LOCATION OF WATER AND SEWER MAINS. | | | -ADD VISUAL MEASUREMENT SCALE ICONS TO CIVIL PLAN | | | SHEETS. | | | -ADD GATE VALVE ON PROPOSED FIRELINE JUST INSIDE | | | PROPERTY LINE. LABEL IT FIRELINE POINT OF SERVICE GATE | | | VALVE. | | | -CITY DOES NOT OFFER 1.25 INCH WATER METERS. COULD DO | | | EITHER 1 INCH METER WITH 1 INCH SERVICE LINE OR 1.5 | | | INCH METER WITH 2 INCH SERVICE LINE. | | | -CALLOUT FIRELINE PIPE BETWEEN TAP AND PROPERTY LINE AS | | | DIP. ALSO ADD SIZE TO THAT LABEL. | | | -ENLARGED WATER SEWER PLAN SHOWS BUSH AND WATER METER | | | BOX OVERLAPPING. PLEASE PROVIDE CLEARANCE DISTANCE. | | | -ON WATER SEWER PLAN, CALLOUT THE MINIMUM HORIZONTAL | | | CLEARANCE DISTANCE BETWEEN THE TWO WATER TAPS. ALSO | | | CALLOUT THE MINIMUM HORIZONTAL CLEARANCE DISTANCE | | | BETWEEN THE SANITARY SEWER SERVICE AND FIRELINE WATER | | | SERVICE. | | | -ON CIVIL PLANS, CLEARLY SHOW THE TERMINAL ENDS OF THE | | | 6 FOOT WOODEN FENCE NEAR THE SOUTHEAST AND NORTHWEST | | | AREAS OF PROPERTY. ENSURE FENCE DOES NOT CONFLICT WITH | | | BACKFLOW ASSEMBLIES. | | | -SHOW BOUNDARIES OF PAVEMENT RESTORATION ON 51ST ST | | | RELATED TO THE PROPOSED UTILITY WORK. BOUNDARIES SHOULD | | | COMPLY WITH STANDARD DETAIL P-4. | | | -ON WATER PLAN, SHOW AND LABEL THE NEAREST FIRE | | | HYDRANT. | | | -SHOW FULL WIDTH OF 51ST ST INCLUDING OPPOSITE CURB | | | AREA. | | | -APPLICANT MAY BE REQUIRED TO UPGRADE EXISTING WATER OR | | | SEWER MAINS UPON REVIEW OF CITY OR EOR AT ENGINEERING | | | DEVELOPMENT SUBMITTAL. | | | -DID NOT SEE FDC ON CIVIL PLANS. IF IT IS NEEDED OR | | | REQUIRED, SHOW AND LABEL IT. VERIFY IT IS AN ACCEPTABLE | | | DISTANCE FROM NEAREST FIRE HYDRANT. | | | -SHOW AND LABEL PROPOSED UTILITY EASEMENT. BACKFLOW | | | ASSEMBLIES SHOULD NOT BE IN UTILITY EASEMENT. | | | -VERIFY NO AUXILIARY WATER SUPPLIES SUCH AS WELLS WILL | | | BE CONNECTED TO FIRE SYSTEM. | | | -SITE PLAN SHOWS AN EASEMENT NEAR EAST PROPERTY LINE. | | | WHAT TYPE OF EASEMENT IS IT? ALSO SHOW THE BOUNDARIES | | | MORE CLEARLY. | | | -HISTORIC PICTURES SHOW OVERHEAD UTILITIES NEAR SOUTH | | | PROPERTY LINE EXTENDING OUT NORTH FROM POLES. WILL | | | PROPOSED BUILDING ENCROACH ON THEM? | | | -PROPERTY APPRAISER SHOWS ADDRESS AS 5111 BROADWAY. IS | | | THE ADDRESS CHANGING? | | | -SHOW AND LABEL ALL EXISTING UTILITIES SUCH AS EXISTING | | | METER BOX NEAR NORTHWEST AREA OF PROPERTY AND CLEANOUTS | | | LABELED ON SURVEY. ADD WHAT IS HAPPENING TO THEM ON | | | LABELS. | | | -SHOW AND LABEL ANY PROPOSED GREASE TRAPS IF THEY ARE | | | OUTSIDE BUILDING. | | | -VERIFY IF THERE IS AN EXISTING UTILITY EASEMENT ALONG | | | SOUTH SIDE OF PROPERTY. | | | -VERIFY DIRECTION FACING ON A2-1.02, A2 1.03, A2 1.04 | | | -POSITION OF TREES BETWEEN DIFFERENT PLAN SETS DOES NOT | | | LOOK SIMILAR. PLEASE MAKE SURE ALL PLANS SETS SHOW | | | UTILITIES AND TREES IN THE SAME POSITIONS. ENSURE THERE | | | IS ADEQUATE SPACING BETWEEN THEM. | | | -WILL IRRIGATION ALSO RUN OFF THE DOMESTIC WATER | | | SERVICE? | | | -SHOW AND LABEL EXISTING STORMWATER UTILITIES INCLUDING | | | THE STRUCTURES AND PIPE ON 51ST ST. | | | -AT THE DATUM STATEMENTS ON EACH SHEET ALSO ADD | | | CONVERSION EQUATION. | | | -HISTORIC PICTURES SHOW COUPLE OF DRIVEWAY APPROACHES | | | AT EAST SIDE OF PROPERTY. VERIFY THE INTENTION IS TO | | | ADD CURBING AND SHOW THAT BETTER ON PLANS. | | | RESPECTFULLY, | | | MARK HURLEY | | | [email protected] | | | |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
2 |
Status |
P |
Date |
07-14-2023 |
|
|
Cont ID |
|
| Sent By |
|
Date |
07-14-2023 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
07-14-2023 |
Time |
|
Sent To |
|
|
| Notes |
| 2023-07-14 09:56:32 | NO FURTHER COMMENTS FROM DEPARTMENT OF PUBLIC WORKS. | | | | | | DEPT. OF PUBLIC WORKS | | | MATT HEJAZI | | | [email protected] |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
F |
Date |
08-10-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
08-10-2022 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
08-10-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-10 07:11:10 | | | | PLEASE PROVIDE THE FOLLOWINGS: | | | 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID | | | WASTE VOLUME PRODUCED ALONG WITH THE SIZE, TYPE AND | | | QUANTITY OF THE CONTAINER (I.E. DUMPSTER/COMPACTOR) | | | THAT WILL BE UTILIZED FOR THE SANITATION SERVICE. | | | 2- DETAILS FOR SANITATION SERVICE (I.E. SOLID WASTE | | | CONTAINER(S) TYPE, COLLECTION LOCATION, ETC.). FOR A | | | FREESTANDING SITE DUMPSTER ENCLOSURE, THE ENCLOSURE | | | SHALL COMPLY WITH THE LATEST REVISION OF CITY OF WEST | | | PALM BEACH GENERAL CONSTRUCTION-GARBAGE ENCLOSURE | | | STANDARD, GC-7. (LINK TO THE LATEST REVISION OF THE | | | GC-7 DOCUMENT: HTTPS://WWW.WPB.ORG/HOME/SHOWPUBLISHEDDO | | | CUMENT/3690/637629060422100000) | | | 3- DESIGNATED LOCATION FOR THE BULK ITEM PICK UP AND | | | RECYCLING CONTAINERS | | | 4- OWNERS AND/OR OCCUPANTS OF PROPERTY THAT REQUIRE | | | GREASE HAULING SERVICES SHALL ENSURE THAT THEIR GREASE | | | TANKS OR CONTAINERS REMAIN CLEAN, AND ARE ENCLOSED AND | | | NOT IN PUBLIC VIEW. | | | 5- IN CASE OF PROPOSING ADDITION OF ANY NEW CAN(S) IN | | | THE CITY`S RIGHT-OF-WAY , THE LOCATION AND QUANTITY OF | | | THE CAN(S) SHALL BE REVIEWED AND APPROVED BY PUBLIC | | | WORKS DEPARTMENT AND THE CAN(S) SHALL BE TYPE, SIZE AND | | | COLOR APPROVED BY PUBLIC WORKS DEPARTMENT. THE BUILDING | | | MAINTENANCE IS RESPONSIBLE TO MAINTAIN AND SERVICE THE | | | CAN(S). | | | 6- ALL THE PARKING STALL PAINTING SHALL COMPLY WITH THE | | | CITY`S MUNICIPAL CODE SECTION 94-485 AND FLORIDA | | | STATUES [553.5041 F.S.]. | | | 7- ALL STRIPING AND SIGNAGE SHALL COMPLY WITH THE | | | LATEST CITY OF WEST PALM BEACH STANDARD DETAILS AND | | | MEET THE M.U.T.C.D. LATEST EDITION. | | | 8- ALL PAVEMENT MARKING , SIGNING AND SIDEWALK DAMAGED | | | DURING CONSTRUCTION SHALL BE RESTORED. | | | | | | | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] | | | 561-822-2045 | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
F |
Date |
07-13-2023 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
07-13-2023 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
07-13-2023 |
Time |
09:32 |
Sent To |
|
|
| Notes |
| 2023-07-13 09:26:44 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | 1. BROADWAY AVE R/W IS MAINTAINED BY FDOT. ANY | | | IMPROVEMENTS WITHIN THE R/W ARE TO BE APPROVED BY FDOT. | | | | | | 2. SHOW MILL AND RESURFACING LIMITS ON THE PUBLIC ROADS | | | DUE TO THE UTILITY TRENCH CUTS. | | | | | | 3. LABEL THE STORM PIPES (SIZE, MATERIAL) ON SHEET | | | C-201. | | | | | | 4. SHOW THE EXISTING DRAINAGE STRUCTURES IN THE RIGHT | | | OF WAY. | | | | | | 5. SHOW AND LABEL (SIZE, MATERIAL, TYPE) EXISTING | | | UTILITIES IN THE R/W???S. | | | | | | 6. CALL OUT TO REPLACE DRIVEWAY APRON AND DROP CURB | | | WITH TYPE F CURB AND GUTTER OUTSIDE OF THE PROPOSED | | | DRIVEWAY ON 51ST ST. | | | | | | 7. CALL OUT TO REPLACE THE DROP CURB AND SIDEWALK ON | | | THE BROADWAY AVE. FRONTAGE WITH TYPE F CURB AND GUTTER | | | AND SIDEWALK WITH CROSS SLOPE OF 2% OR FLATTER. | | | | | | 8. SHOW DROP CURB ACROSS THE PROPOSED DRIVEWAY. | | | | | | 9. NOTE STRIPING IS CALLED OUT AS 24 INCH WHITE STRIPE | | | ON THE STRIPING PLAN, SHEET C-202. | | | | | | 10. CIVIL PLANS HAVE A DRAFT WATERMARK. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP | | | CRITERIA. STORMWATER CALCULATIONS WILL BE REVIEWED WITH | | | THE ENGINEERING PERMIT SUBMITTAL. | | | | | | 2. PROVIDE COPY OF SFWMD ERP AND FDEP NPDES | | | CONSTRUCTION PERMIT, IF APPLICABLE, BEFORE START OF | | | CONSTRUCTION. | | | | | | 3. PROVIDE EROSION AND SEDIMENT CONTROL PLAN WITH THE | | | ENGINEERING PERMIT SUBMITTAL. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | [email protected] | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
08-12-2022 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
08-12-2022 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
08-12-2022 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2022-08-12 10:26:08 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | 1. THE CITY'S OFFICIAL VERTICAL DATUM IS NGVD1929. THE | | | CITY HAS ALLOWED THE USE OF NAVD1988 AS LONG AS THE | | | CONVERSION EQUATION TO NGVD1929 AT THE PROJECT LOCATION | | | IS PROVIDED. PROVIDE THE VERTICAL DATUM CONVERSION TO | | | NGVD1929 ON THE SURVEY. LIST THE REFERENCED VERTICAL | | | DATUM AND CONVERSION EQUATION TO NGVD1929 ON ALL SHEETS | | | WITH ELEVATION INFORMATION. | | | | | | 2. SHOW THE EXISTING CATCH BASINS AND STORM PIPE ON | | | 51ST ST ON ALL OF THE PLAN SHEETS. | | | | | | 3. EXISTING DRIVEWAY AND DROP CURB ON 51ST ST APPEARS | | | WIDER THAN WHAT IS NEEDED FOR THE DEVELOPMENT. REMOVE | | | THE EXCESS DRIVEWAY APRON AND DROP CURB AND REPLACE | | | WITH LANDSCAPING AND TYPE F CURB AND GUTTER (INCLUDING | | | TRANSITIONS TO DROP CURB). SHOW CURB AND GUTTER ON 51ST | | | ST AND ON BROADWAY AVE. | | | | | | 4. BROADWAY AVE IS MAINTAINED BY FDOT. ANY IMPROVEMENTS | | | WITH THE BROADWAY AVE ARE TO BE APPROVED BY FDOT. | | | COORDINATE WITH FDOT THE EXISTING CURB CUTS ON BROADWAY | | | AVE. | | | | | | 5. DRAWING NO. S-100 | | | A. CAN YOU PROVIDE A COPY OF THE TOPOGRAPHIC SURVEY BY | | | PREMIER DESIGN SOLUTIONS INC. REFERENCED IN THE FIFTH | | | PARAGRAPH UNDER GENERAL NOTES? | | | B. CAN YOU PROVIDE THE CTA SURVEY REFERENCED IN THE | | | FIRST PARAGRAPH UNDER CITY OF WEST PALM BEACH WATER | | | MAIN SYSTEM NOTES? | | | C. MINIMUM DEPTH OF COVER FOR ALL WATER MAINS IS 36 | | | INCHES. | | | D. "MAXIMUM DEFECTION (SIC) PER EACH JOINT SHALL BE 3' | | | WHERE DEFLECTION IS REQUIRED." WHAT DOES THIS MEAN? | | | E. TWO DIFFERENT PHONE NUMBERS LISTED FOR ONE CALL | | | SUNSHINE. | | | F. MINIMUM CLEARANCE BETWEEN STORM STRUCTURES AND WATER | | | MAINS SHALL BE 3 FEET, NOT 2 FEET. | | | G. MINIMUM VERTICAL CLEARANCE FOR WATER MAINS PASSING | | | UNDER OTHER UTILITIES IS 12 INCHES (OUTSIDE WALL TO | | | OUTSIDE WALL), NOT 18 INCHES. | | | | | | 6. DRAWING NO. S-101 | | | A. UNDER "GENERAL CONDITIONS" 'REPLANTING' OR | | | 'REPLATTING' | | | B. UNDER "CIVIL DESIGN CRITERIA" - WHAT AGENCY GOES BY | | | THE LETTERS S.F.W.M.D.C.? | | | C. UNDER "APPLICABLE CODES" - NAVD1988 IS THE | | | ABBREVIATION FOR NORTH AMERICAN VERTICAL DATUM 1988. | | | NGVD1929 IS NATIONAL GEODETIC VERTICAL DATUM 1929. | | | D. UNDER "TEMPORARY FACILITIES" - REMOVE REFERENCE TO | | | POMPANO BEACH. | | | E. UNDER "STORM DRAINAGE INSTALLATIONS:", WHAT IS BCPS? | | | | | | 7. DRAWING NO. S-200: | | | A. LABEL THE PARALLEL LINES RUNNING EAST-WEST AND | | | NORTH-SOUTH THROUGH THE SIDEWALK AND DRIVEWAY ALONG | | | 51ST STREET. | | | B. SEVERAL PROPOSED SPOT GRADES ON THE SIDEWALKS ARE | | | LISTED AS F.F.E. | | | C. WHAT DOES THE 'X+' REPRESENT FOR THE EXISTING AND | | | PROPOSED ELEVATIONS? | | | D. PROVIDE EXISTING SPOT GRADES ALONG THE EDGE OF | | | PAVEMENT OF BROADWAY AVE AND 51ST ST | | | E. PROVIDE EXISTING SPOT GRADES ALONG THE SOUTH AND | | | WEST PROPERTY LINES. | | | F. PROVIDE CROSS SECTIONS FOR ALL FOUR PROPERTY LINES. | | | EXTEND FROM FACE OF THE BUILDING TO 5 FEET BEYOND THE | | | SOUTH AND WEST PROPERTY LINES AND TO THE CENTERLINES OF | | | BROADWAY AVE AND 51ST ST. SHOW AND LABEL PROPERTY | | | LINES, STREET R/W NAME, ALL GRADE BREAKS AND SURFACE | | | FEATURES (FENCE, SIDEWALK, CURB AND GUTTER, | | | LANDSCAPING, SIDEWALK, BUILDING WALL AND F.F.E.). | | | PROVIDE DIMENSIONS FROM PROPERTY LINE TO THE SURFACE | | | FEATURES. | | | | | | 8. DRAWING NO. S-202 | | | A. PARKING STRIPE DETAIL - CITY STANDARD IS PARALLEL 4 | | | INCH STRIPES SEPARATED BY 12 INCHES CLEAR AND JOINED AT | | | ONE END WITH A 4 INCH STRIPE. DETAIL ON THE PLANS SHOWS | | | 16 INCH CLEAR SPACE WITH NO CONNECTING STRIPE. | | | B. NORTH EDGE OF STOP BAR STRIPE SHOULD BE 4 FEET FROM | | | THE BACK OF SIDEWALK. PLAN SHOWS THE SOUTH EDGE AT 4 | | | FEET FROM THE BACK OF SIDEWALK. | | | C. HANDICAP SIGN MISSPELLED (SING). | | | D. WHAT ARE THE PROPOSED 24 INCH WHITE STRIPES CALLED | | | OUT ON THE RIGHT SIDE OF THE PLAN VIEW? | | | | | | 9. DRAWING NO. S-204: | | | A. SHOW LIMITS OF MILLING AND RESURFACING | | | B. CALL OUT AN EASEMENT FOR THE WATER METER AND SEWER | | | CLEANOUT. | | | C. PVC MISSPELLED (PCV) FOR 6 INCH LATERAL. | | | | | | 10. DRAWING NO. C-500, STANDARD DETAIL ST-8 - CONFIRM | | | THE 20 FEET DEPTH IN THE TRENCH SCHEDULE. | | | | | | 11. DRAWING NO. C-501: DRAINAGE TABLE - | | | A. SWITCH COLUMN HEADINGS FOR NORTH AND SOUTH. | | | B. SWITCH COLUMN HEADINGS FOR EAST AND WEST. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP | | | CRITERIA. STORMWATER CALCULATIONS WILL BE REVIEWED WITH | | | THE ENGINEERING PERMIT SUBMITTAL. | | | | | | 2. PROVIDE COPY OF SFWMD ERP PERMIT BEFORE START OF | | | CONSTRUCTION. | | | | | | 3. PROVIDE EROSION AND SEDIMENT CONTROL PLAN WITH THE | | | ENGINEERING PERMIT SUBMITTAL. | | | | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | 561-351-0510 (M) | | | [email protected] | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
2 |
Status |
F |
Date |
07-10-2023 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
07-10-2023 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2023-07-10 10:58:12 | 1. PLEASE PROVIDE COPY OF TITLE POLICY. | | | 2. ADDITIONAL BROADWAY RIGHT-OF-WAY (APPROX. 7' ) WAS | | | TAKEN PER MAINTENANCE MAP IN ROAD PLAT BOOK 7, PG. 1 - | | | REFLECT ON SURVEY AND ALL PLANS. | | | 3. LEGAL DIMENSION OF E-W LOTS ARE 100' PER PLAT, NOT | | | 95.59' PER LEGAL. CHECK SPELLING OF LEGAL. | | | 4. ADD PARENT BENCHMARK INFORMATION. | | | | | | WILL BE ADDITIONAL REVIEW AFTER RECEIPT OF TITLE POLICY | | | AND REVISED SURVEY. |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
08-09-2022 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
08-09-2022 |
Time |
12:38 |
Rev Time |
|
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-09 12:51:54 | 1. SURVEY DOES NOT MEET STANDARDS OF PRACTICE | | | 2. NO BEARINGS/ANGLES SHOWN. SHOW DIFFERENCE BETWEEN | | | MEASURED AND PLAT DISTANCES. | | | 3. FLOOD DATA IS NOT TOWN OF LANTANA. | | | 4. SURVEY CALL OUT PINE STREET HOMES? | | | 5. ADD CONVERSION TO NGVD-29. | | | 6. UNUSED WATER AND SEWER SERVICES TO BE CUT BACK TO | | | MAIN. | | | 7. UNITY OF TITLE WILL BE REQUIRED. |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
2 |
Status |
F |
Date |
07-13-2023 |
|
|
Cont ID |
|
| Sent By |
|
Date |
07-13-2023 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
07-13-2023 |
Time |
|
Sent To |
|
|
| Notes |
| 2023-07-13 07:47:12 | 1) PROVIDE A CLEAN TRANSPORTATION SPECIFIC SITE PLAN | | | FOR THE GROUND FLOOR. SHOWCASING TRANSPORTATION RELATED | | | FEATURES (E.G. ROADWAY, DRIVING AISLES, PARKING STALLS, | | | SIDEWALK, CURB, GUTTER, DRIVEWAY, GATES, ETC.) PROPERLY | | | LABELED AND DIMENSIONED. SHEET C-202 IS A STARTING | | | POINT, BUT NEEDS TO BE LARGER. PLEASE REMOVE ANY | | | NON-RELEVANT CALLOUTS | | | 2) IN THE TRANSPORTATION SITE PLAN, PLEASE SHOWCASE | | | BASIC CURB DETAILS (E.G. DRIVEWAY, CURB CUTS, PAVEMENT | | | MARKINGS, PARKING STALLS, ETC.) ON THE OPPOSITE SIDE OF | | | THE ROADS SURROUNDING THE PROPOSED DEVELOPMENT | | | 3) PROVIDE PARKING TABLE SHOWCASING THE NUMBER OF | | | REQUIRED AND PROVIDED PARKING SPACES, INCLUSIVE OF ADA | | | AND BICYCLE ONES | | | 4) PROVIDE A TURNAROUND SPACE AT THE DEAD-END OF THE | | | PARKING LOT AND MARK IT OR CALL IT OUT ACCORDINGLY | | | 5) PER FDOT LETTER, THE 51ST ST DRIVEWAY SHOULD BE | | | RIGHT-IN/RIGHT-OUT. PLEASE INSTALL SIGNAGE AND PAVEMENT | | | MARKINGS ACCORDINGLY | | | 6) THE NORTHERN PARKING STALLS, INCLUSIVE OF THE ADA | | | ONE, ARE TOO CLOSE TO THE EDGE OF THE ROAD. PER FDOT | | | LETTER, A MINIMUM OF 25 FEET DRIVEWAY THROAT MUST BE | | | PROVIDED. SUCH DISTANCE IS CALCULATED BETWEEN THE EDGE | | | OF THE TRAVEL LANE ABUTTING THE DRIVEWAY AND THE FIRST | | | CONFLICT POINT WITHIN THE PARKING LOT. PLEASE DEPICT | | | SUCH DISTANCE AND REVISE PARKING STALLS CONFIGURATION, | | | IF NECESSARY | | | 7) PER CITY CODE 94-305(E), NO CONSTRUCTION, PLACEMENT, | | | OR MAINTENANCE OF A STRUCTURE WALL, SIGN, FENCE, BERM, | | | PLANT MATERIAL, SHRUBS, OR ANY SIMILAR ITEM BETWEEN 18 | | | INCHES OR EIGHT FEET IN HEIGHT WITHIN THE VISIBILITY | | | TRIANGLE. THE PLACEMENT AND SHAPE OF THE PROPOSED ART | | | INSTALLATION MAY NOT COMPLY WITH SUCH REQUIREMENT. | | | PLEASE REVISE OR PROVIDE FURTHER DETAILS | | | 8) INSTALL NO-PARKING SIGNS EAST AND WEST OF THE | | | PROPOSED DRIVEWAY | | | 9) PROVIDE AUTOTURN ANALYSIS FOR GARBAGE TRUCK AND/OR | | | SERVICE VEHICLES DRIVING IN AND OUT OF THE PROPOSED | | | DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES AND WHEEL | | | PATHS CLEARLY DISTINCT AND DEFINED IN DIFFERENT COLORS. | | | PLEASE PROVIDE DOCUMENT NAME AND SHEET NUMBER | | | 10) PROVIDE A CONSTRUCTION MANAGEMENT PLAN. PLEASE | | | REFER TO CITY CODE 86-246 FOR DETAILS | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
08-11-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
08-11-2022 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
08-11-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-11 03:56:36 | 1) PROVIDE A TRANSPORTATION SPECIFIC SITE PLAN FOR THE | | | GROUND FLOOR. SHOWCASING TRANSPORTATION RELATED | | | FEATURES (E.G. ROADWAY, DRIVING AISLES, PARKING STALLS, | | | SIDEWALK, CURB, GUTTER, DRIVEWAY, GATES, ETC.) PROPERLY | | | LABELED AND DIMENSIONED. SHEET S-202 IS A STARTING | | | POINT | | | 2) IN THE TRANSPORTATION SITE PLAN, PLEASE SHOWCASE | | | BASIC CURB DETAILS (E.G. DRIVEWAY, CURB CUTS, PAVEMENT | | | MARKINGS, PARKING STALLS, ETC.) ON THE OPPOSITE SIDE OF | | | THE ROADS SURROUNDING THE PROPOSED DEVELOPMENT | | | 3) PROVIDE PARKING TABLE SHOWCASING THE NUMBER OF | | | REQUIRED AND PROVIDED PARKING SPACES, INCLUSIVE OF ADA | | | AND BICYCLE ONES | | | 4) PROVIDE A TURNAROUND SPACE AT THE DEAD-END OF THE | | | PARKING LOT | | | 5) S-202 PAVEMENT MARKING AT THE EXIT LANE IS | | | INCORRECT, VEHICLES SHOULD BE ALLOWED TO TURN LEFT AND | | | RIGHT. PLEASE REVISE | | | 6) THE NORTHERN PARKING STALLS, INCLUSIVE OF THE ADA | | | ONE, ARE TOO CLOSE TO THE EDGE OF THE ROAD. PER FDOT | | | ACCESS MANAGEMENT GUIDELINES, A MINIMUM OF 30 FEET | | | DRIVEWAY THROAT MUST BE PROVIDED. SUCH DISTANCE IS | | | CALCULATED FROM THE EDGE OF PAVEMENT TO THE FIRST | | | CONFLICT POINT WITHIN THE PARKING LOT. PLEASE DEPICT | | | SUCH DISTANCE AND REVISE PARKING STALLS CONFIGURATION | | | ACCORDINGLY | | | 7) PER CITY CODE 94-305(E), NO CONSTRUCTION, PLACEMENT, | | | OR MAINTENANCE OF A STRUCTURE WALL, SIGN, FENCE, BERM, | | | PLANT MATERIAL, SHRUBS, OR ANY SIMILAR ITEM BETWEEN 18 | | | INCHES OR EIGHT FEET IN HEIGHT WITHIN THE VISIBILITY | | | TRIANGLE. THE PLACEMENT AND SHAPE OF THE PROPOSED ART | | | INSTALLATION MAY NOT COMPLY WITH SUCH REQUIREMENT. | | | PLEASE REVISE OR PROVIDE FURTHER DETAILS | | | 8) INSTALL NO-PARKING SIGNS EAST AND WEST OF THE | | | PROPOSED DRIVEWAY | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
07-13-2023 |
|
|
Cont ID |
|
| Sent By |
avolcy |
Date |
07-12-2023 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
avolcy |
Date |
07-11-2023 |
Time |
11:47 |
Sent To |
|
|
| Notes |
| 2023-07-13 09:03:39 | PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW | | | ________________________________________ | | | | | | DATE OF REVIEW: 07.12.2023 | | | PROJECT NO.: Z22070019 | | | ________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. PER THE CITYS ZLDR SECTION 94-221(D)(10) DUMPSTERS | | | AND STORAGE AREAS SHALL BE LOCATED AT THE REAR OF THE | | | PROPERTY AND SHALL BE ENCLOSED IN THE BUILDING OR A | | | STRUCTURE CONSISTENT WITH THE ARCHITECTURE OF THE | | | BUILDING. DUMPSTERS FOR FOOD SERVICE BUSINESSES SHALL | | | BE FULLY ENCLOSED AND AIR-CONDITIONED. | | | | | | 2. PROVIDE A NARRATIVE ON HOW THIS PROJECT MEETS THE | | | ARCHITECTURAL STANDARDS OF BMUD TYPE II ZONING | | | DISTRICT. REFER TO SECTION 94-221(D) | | | | | | 3. UPDATE THE SITE DATA TABLE TO INCLUDE THE REQUIRED | | | AND PROPOSED BICYCLE PARKING. REFER TO THE CITYS ZLDR | | | SECTION 94-485(Q). | | | | | | 4. BICYLE RACK SHALL MEET THE GUIDLEINES SET FORTH IN | | | THE CITYS ZLDR SECTION 94-485(Q). THEY ARE TO BE | | | LOCATED IN CONVENIENT, HIGHLY-VISIBLE, ACTIVE, | | | WELL-LIGHTED AREAS AND AS NEAR TO THE PRINCIPAL | | | ENTRANCE OF THE BUILDING AS PRACTICABLE. | | | | | | 5. PROVIDE ELEVATIONS / DETAILS OF BICYCLE PARKING | | | FACILITY. | | | | | | 6. PROVIDE WEST ELEVATION WALL DETAIL AND MATERIAL. | | | | | | 7. A PRE-APPLICATION MEETING IS NECESSARY BEFORE THE | | | APPLICANT CAN APPLY FOR A PERMIT FROM THE DEPARTMENT | | | (FDOT) FOR ACCESS TO STATE ROAD 5/U.S. 1 FOR THE | | | PROPOSED DEVELOPMENT. THE APPLICANT SHOULD CONTACT FDOT | | | TO REQUEST AN ACCESS PRE-APPLICATION MEETING TO | | | EVALUATE PROPOSED CONNECTIONS. | | | 7.1. ACCESS PRE-APPLICATION MEETINGS ARE HELD EVERY | | | THURSDAY IN PERSON AND VIA MICROSOFT TEAMS. | | | PRE-APPLICATION MEETINGS ARE TYPICALLY SCHEDULED TWO | | | WEEKS AFTER AN APPLICATION IS RECEIVED. A NOTIFICATION | | | EMAIL WITH THE DATE AND TIME OF PRE-APPLICATION MEETING | | | WILL BE SENT OUT EACH MONDAY FOR THE FOLLOWING WEEK | | | PRE-APPLICATION MEETING. | | | | | | ________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN | | | RESUBMITTING: | | | A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL | | | DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION. | | | B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED | | | MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG | | | WITH ONE (1) REDUCED COPY (11 IN X 17 IN). | | | C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO | | | ADDITIONAL COMMENTS. | | | D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE | | | ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE | | | CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL | | | REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION. | | | | | | ________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | GAISHA (ANNE-CLERISSE) VOLCY, PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1552 | | | TTY: 800.955.8771 | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
08-11-2022 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
08-11-2022 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
08-11-2022 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2022-08-11 11:24:58 | PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW | | | ________________________________________ | | | | | | DATE OF REVIEW: 08.11.2022 | | | PROJECT NO.: Z22070019 | | | CASE NO.: ISPR 22-06 | | | ________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS: | | | | | | 1. NUMEROUS AMOUNTS OF INFORMATION IS MISSING FROM THE | | | SITE DATA TABLE. PLEASE REFER TO THE SITE PLAN | | | CHECKLIST CONTAINED WITHIN THE DEVELOPMENT APPLICATION. | | | | | | 2. THE SQUARE FOOTAGES OF THE RETAIL USE DIFFER BETWEEN | | | THE JUSTIFICATION STATEMENT, THE PROJECT FACT SHEET, | | | THE COUNTY?S TPS LETTER, ETC. ALL PLANS/DOCUMENTS SHALL | | | BE CONSISTENT WITH THE CORRECT INFORMATION. | | | | | | 3. PURSUANT TO COMMENTS BY JUSTIN STROH, PLANNING | | | SPECIALIST II WITH THE FLORIDA DEPARTMENT OF | | | TRANSPORTATION (FDOT), A PRE-APPLICATION MEETING IS | | | NECESSARY BEFORE THE APPLICANT CAN APPLY FOR A PERMIT | | | FROM THE DEPARTMENT FOR ACCESS TO BROADWAY AVENUE | | | (US-1). THE APPLICANT SHOULD CONTACT FDOT TO REQUEST AN | | | ACCESS PRE-APPLICATION MEETING TO COORDINATE THE | | | PROPOSED CONNECTIONS. CONTACT INFORMATION WILL BE | | | PROVIDED BY EMAIL. | | | | | | 4. WHY WAS THERE A SCHOOL CAPACITY AVAILABILITY | | | DETERMINATION (SCAD) ISSUED FOR A FUTURE LAND USE MAP | | | AMENDMENT AND REZONING? THE SCAD SHOULD HAVE ONLY BEEN | | | FOR THE DEVELOPMENT ORDER APPROVAL. PLEASE PROVIDE A | | | REVISED/CORRECTED SCAD APPROVAL. | | | | | | 5. THE OWNER?S CONSENT FORM IS INCOMPLETE AND DOES NOT | | | PROVIDE THE NAME OF THE OWNER, THE AGENT/APPLICANT, | | | ETC. PLEASE PROVIDE A COMPLETE AND ACCURATE OWNER?S | | | CONSENT FORM. | | | | | | 6. THE DOCUMENT FROM FLORIDA PUBLIC UTILITIES (GAS) IS | | | A DEMOLITION CLEARANCE. A LETTER FROM FPU IS TO BE | | | PROVIDED INDICATING THAT THE PROPOSED DEVELOPMENT DOES | | | NOT ENCROACH INTO THEIR EASEMENT OR OTHERWISE INTERFERE | | | WITH THEIR PROVISION OF SERVICES. | | | | | | 7. A CONFIRMATION LETTER SHALL BE PROVIDED FROM AT&T | | | INDICATING THAT THE PROPOSED DEVELOPMENT DOES NOT | | | ENCROACH INTO THEIR EASEMENT OR OTHERWISE INTERFERE | | | WITH THEIR PROVISION OF SERVICES. | | | | | | 8. YOUR LANDSCAPE PLANS APPEAR TO SHOW TREES WITH | | | GRATES, ETC. ALONG BOTH STREET FRONTAGES, BUT THIS IS | | | NOT DEPICTED ON THE CIVIL PLANS. | | | | | | 9. THE SIDEWALK ALONG BROADWAY NEEDS TO BE A MINIMUM OF | | | 8 FEET CLEAR (NO OBSTRUCTIONS). THE ?FRONTAGE LINE? | | | (NOT PROPERTY LINE) FOR THE PURPOSE OF MEASURING THE | | | BUILDING SETBACK SHIFTS TO THE EDGE OF THE SIDEWALK. 65 | | | PERCENT OF THE BUILDING NEEDS TO BE WITHIN 5 FEET OF | | | THIS ADJUSTED FRONTAGE LINE. PLEASE DEPICT ACCORDINGLY | | | ON THE SITE PLAN. | | | | | | 10. ALONG THE FRONTAGE, WHERE THERE IS NO BUILDING, A | | | STREETWALL SHALL BE PROVIDED THAT IS 34-72 INCHES IN | | | HEIGHT. | | | | | | 11. THE REQUIRED REAR SETBACK (ALONG WEST PROPERTY | | | LINE) IS 15 FEET. | | | | | | 12. PLEASE CLARIFY THE EASEMENT LINE THAT IS SHOWN ON | | | THE SITE PLAN ALONG BROADWAY AVENUE. | | | | | | 13. PROVIDE THE DIMENSION FROM THE BUILDING TO THE | | | CENTERLINE OF THE ADJACENT STREETS (BROADWAY ? 40 FOOT | | | MINIMUM). | | | | | | 14. WALLS SHALL BE LIMITED TO 2 MATERIALS. | | | | | | 15. STOREFRONTS ARE REQUIRED ALONG BOTH STREET | | | FRONTAGES AND SHALL HAVE GLAZING ALONG A MINIMUM OF 70 | | | PERCENT OF THE FA?ADE LENGTH BETWEEN 2 AND 8 FEET FROM | | | THE GROUND. PLANS SHALL INDICATE SUCH DIMENSIONS, AND | | | THE 51ST STREET FRONTAGE DOES NOT PROVIDE ANY | | | STOREFRONT. | | | | | | 16. THE DIRECTIONS INDICATED ON THE ELEVATIONS ARE | | | INCORRECT (NORTH VS. SOUTH ? EAST VS. WEST). | | | | | | 17. STORIES ABOVE THE FIRST FLOOR SHALL HAVE CLEAR | | | GLAZED AREA AND OPENINGS BETWEEN 25 PERCENT AND 45 | | | PERCENT OF THE FACADE AREA. PLEASE PROVIDE SUCH | | | CALCULATIONS. | | | | | | 18. WINDOWS, EXCEPT STOREFRONTS, SHALL BE OPERABLE. | | | | | | 19. WINDOWS SHALL BE RECESSED A MINIMUM OF 2 INCHES, | | | PLEASE PROVIDE A DETAIL. | | | | | | 20. THE ELEVATION APPEARS TO SHOW AN OVERHEAD DOOR. | | | THIS PRESENTS MULTIPLE CONCERNS WITH HOW THE PARKING IS | | | ACCESSED, STACKING IN THE STREET, ETC. | | | | | | 21. PLEASE CLARIFY THE FA?ADE TREATMENT ON THE GROUND | | | FLOOR ALONG 51ST STREET WHERE THE PARKING IS LOCATED? | | | THE PARKING NEEDS TO BE CONCEALED WITH A STREETWALL. | | | | | | 22. THE SITE PLAN DOES NOT CLEARLY INDICATE THE | | | OVERHANG PROJECTION ON THE FIRST FLOOR. | | | | | | 23. MULTIPLE PLANS SHOW MULTIPLE PORTIONS OF THE | | | BUILDING, OVERHANGS, ETC. EXTENDING OUTSIDE OF THE | | | PROPERTY LINE. ALL BUILDINGS AND ASSOCIATED | | | IMPROVEMENTS SHALL BE WITHIN THE PROPERTY LINE AND MEET | | | THE MINIMUM SETBACK REQUIREMENTS. | | | | | | 24. THE SITE PLAN SHOWS THE TRASH BEING ROLLED OUT INTO | | | A LANDSCAPE AREA/STREET. | | | | | | 25. A MINIMUM OF 18 PARKING SPACES SHALL BE PROVIDED, | | | ONLY 16 ARE SHOWN. | | | | | | 26. THE DRIVE AISLE IN THE PARKING AREA SHALL BE A | | | MINIMUM OF 24 FEET WIDE. | | | | | | 27. A TURN-AROUND SPACE SHALL BE PROVIDED AT THE | | | DEAD-END OF THE DRIVE AISLE. | | | | | | 28. PARKING STRIPING DETAIL SHALL BE PROVIDED. | | | | | | 29. AT LEAST 1 LOADING SPACE SHALL BE PROVIDED (10 FEET | | | X 25 FEET). | | | | | | 30. BIKE RACKS SHALL BE PROVIDED (1 PER 20 PARKING | | | SPACES). THE LOCATION SHALL BE INDICATED AND A DETAIL | | | SHALL BE INCLUDED SHOWING THE TYPE OF RACK, THE | | | DIMENSIONAL CLEARANCE TO SURROUNDING OBSTRUCTIONS, ETC. | | | | | | 31. THE ACCESSIBLE PARKING SPACE SHOWS COLUMNS IN THE | | | SPACE. THE SPACE SHALL BE A MINIMUM OF 12 FEET IN CLEAR | | | WIDTH AND SHALL HAVE AN ADJACENT AISLE OF AT LEAST 5 | | | FEET IN CLEAR WIDTH. | | | | | | 32. WHEEL STOPS SHALL BE 2 FEET FROM THE FRONT OF THE | | | PARKING SPACE. | | | | | | 33. THERE ARE NUMEROUS CONFLICTS BETWEEN THE LANDSCAPE | | | PLANS AND THE ARCHITECTURAL DESIGN OF THE BUILDING, | | | SPECIFICALLY THE OVERHANGS/PROJECTIONS AND THE PLANTING | | | OF TREES, ETC. | | | | | | 34. NO PORTION OF THE BUILDING SHALL EXTEND INTO THE | | | VISIBILITY TRIANGLE BETWEEN A HEIGHT OF 18 INCHES AND 8 | | | FEET. | | | | | | 35. PLEASE CLARIFY THE BUILDING SECTION LABELING THE | | | ROOF DECK AS THE TERRACE LEVEL; IS THERE ACCESS TO THE | | | ROOF (OTHER THAN MAINTENANCE)? | | | | | | 36. PLEASE SHOW ON THE BUILDING SECTION/ELEVATIONS THE | | | LOCATION AND SIZE OF THE ROOF-TOP MECHANICAL EQUIPMENT | | | TO SHOW THAT IT WILL BE COMPLETELY SCREENED FROM VIEW | | | BY THE PROPOSED PARAPET. | | | | | | 37. THE ELEVATIONS INDICATE A FENCE ALONG THE ADJACENT | | | PROPERTY WEST AND SOUTH PROPERTY LINES, BUT THIS IS NOT | | | SHOWN ON THE SITE PLAN. SUCH FENCING SHALL BE | | | DIMENSIONED. ALONG THE WEST PROPERTY LINE THERE SHALL | | | BE A 72-INCH HIGH WALL (NOT FENCE). | | | ________________________________________ | | | | | | PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING: | | | | | | A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL | | | DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION. | | | | | | B) ELECTRONIC COPIES OF REVISED PLANS AND/OR DOCUMENTS | | | SHALL BE PROVIDED. | | | | | | C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO | | | ADDITIONAL COMMENTS. | | | | | | D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE | | | ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE | | | CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL | | | REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION. | | | | | | E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20% OF THE ORIGINAL APPLICATION FEE. | | | ________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | TTY: 800.955.8771 | | | E: [email protected] | | | | | | W: WPB.ORG |
|
|
| |