Plan Review Details - Project Z22070014
Plan Review Stops For Project Z22070014
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 08-11-2022 Cont ID  
Sent By vbroglia Date 08-11-2022 Time 12:16 Rev Time 0.00
Received By vbroglia Date 08-11-2022 Time 12:15 Sent To  
Notes
2022-08-11 12:20:03DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS
 SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT
 REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH
 COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963,
 OR BY EMAIL: [email protected]
  
 3. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 4. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 5. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION
 OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING,
 CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT
 (561) 805 6659, OR BY EMAIL: [email protected]
  
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status P Date 09-14-2022 Cont ID  
Sent By rrossano Date 09-14-2022 Time   Rev Time 0.00
Received By rrossano Date 09-14-2022 Time   Sent To  
Notes
2022-09-14 08:25:38PASSED WITH PROVISO: PLEASE CLEARLY SHOW ON ENGINEERING
 PLANS THE EXISTING AND PROPOSED LIFT STATIONS. INDICATE
 IF EXISTING LIFT STATION IS TO REMAIN OR BE REMOVED.

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 07-27-2022 Cont ID  
Sent By rrossano Date 07-27-2022 Time   Rev Time  
Received By rrossano Date 07-27-2022 Time   Sent To  
Notes
2022-07-27 10:16:43Z22070014 - FPL BLDG, 5950 N MILITARY 7.26.22 SUB
 COMMENTS FROM RICK ROSSANO, SR. PROJECT COORDINATOR,
 ENGINEERING SERVICES AT 561-494-1098 [email protected]
  
 PLEASE ADVISE WHAT IS HAPPENING WITH THE EXISTING LIFT
 STATION ON THE NW AREA OF THE PROPERTY.
  
 GENERAL:
 O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (Z-XXXXXXXX).
 O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1079 FOR FURTHER
 ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION
 ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD
 SURVEY, POT-HOLING, SOFT DIGS ETC.
 O PROVIDE EXISTING AND PROPOSED PERVIOUS AND IMPERVIOUS
 DATA.
 O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY
 TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT
 APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING
 AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE,
 MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS
 SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008
 FOR WATER.
 O IT APPEARS THAT THERE ARE NO POTABLE WATER OR SEWER
 CONNECTIONS PROPOSED, PLEASE CONFIRM.
  
 FORMAL ENGINEERING REVIEW:
 O FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES
 NOI REQUIREMENTS WILL BE ENFORCED.
 - AN NOI IS REQUIRED FOR PROJECTS THAT:
 - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS
 THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF
 DEVELOPMENT OR SALE;
 - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE
 STATE OR TO SURFACE WATERS OF THE STATE THROUGH A
 MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4).
 - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF
 CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION
 THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL
 SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT
 OF THE 10-2 CERTIFICATION.
 O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE
 CALCULATIONS OF PERVIOUS AND IMPERVIOUS AREAS FOR
 PROPOSED IMPROVED AREAS.
 QUESTIONS AND COORDINATION CONTACTS:
 O MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR WITH
 CITY OF WPB PUBLIC UTILITIES, REGARDING PLACEMENT OF
 BACKFLOW DEVICES AND WATER METERS. CONTACT HIM AT
 561-822-2262 OR [email protected]
 O MIKE TECHNOW, PROJECT ENGINEER, PUBLIC UTILITIES
 DEPARTMENT AT 561-494-1047 OR [email protected]
 O TRACY WARD, SR. STORMWATER ENGINEER, ENGINEERING
 SERVICES DEPT. AT 561-494-1120 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 08-01-2022 Cont ID  
Sent By pleduc Date 08-01-2022 Time   Rev Time 0.00
Received By pleduc Date 08-01-2022 Time 14:37 Sent To  
Notes
2022-08-01 14:39:04THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE DEPARTMENT.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT. THE FOLLOWING COMMENTS ARE INTENDED
 TO PROVIDE GUIDANCE FOR BUILDING PLAN SUBMITTAL.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE PER THE FLORIDA FIRE PREVENTION CODE.
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED, AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
 THE PROPOSED LOCATION OF THE FIRE HYDRANT AND FDC SHALL
 BE WITHIN 100' OF EACH OTHER AND CLOSELY COORDINATED
 WITH THE BUREAU OF FIRE PREVENTION.
  
 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM,
 ENSURE THEY COMPLY WITH THE REQUIREMENTS OF F.A.C. 61G
 AND SUBMITTED WITH THE MASTER PERMIT.
  
 9A. THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE
 LOCATIONS SHALL MEET AND BE INSTALLED PER THE
 REQUIREMENTS OF NFPA 24 AND SHALL BE COORDINATED WITH
 THE OFFICE OF FIRE MARSHAL, THE CITY'S ENGINEERS
 OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S PLANNING
 AND ZONING OFFICE.
  
 10. COMPLETE LIFE SAFETY PLANS FOR THE OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, EXIT SEPARATION DISTANCES, COMMON PATHS OF
 TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, EMERGENCY
 LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE
 EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES
 AND EQUIPMENT.
  
 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE
 SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY
 DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS.
  
 12. TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEMS.
  
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
  
 IF APPLICABLE, CONTACT WILL NEED TO BE MADE TO MARK
 FILLA, PALM BEACH COUNTY PUBLIC SAFETY RADIO SYSTEMS
 MANAGER, [email protected], 561-233-0837; AS OUR RADIOS
 OPERATE ON THEIR SYSTEM FOR DETAILED RADIO FREQUENCY
 AND INSTALLATION INSTRUCTIONS.
  
 13. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
 14. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 2 Status P Date 09-19-2022 Cont ID  
Sent By rcaranci Date 09-19-2022 Time 13:34 Rev Time 0.00
Received By rcaranci Date 09-19-2022 Time 13:33 Sent To  
Notes
2022-09-19 13:34:18FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 5950 N MILITARY TR, CAYMAN SUBSTATION
 Z22070014
 SEPTEMBER 19, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. SATISFIED. SECTION 94-443(C)(3) REQUIRES THAT A
 MINIMUM OF 75 PERCENT OF ALL TREES THAT ARE REQUIRED TO
 BE PLANTED WITHIN THE INTERIOR OF AN OFF STREET PARKING
 AREA SHALL BE CATEGORY 1 SHADE TREES. SHOW THE
 PERCENTAGE OF CATEGORY 1 TREES PROVIDED FOR THE
 REQUIRED LANDSCAPE AREAS AS REQUIRED BY SECTION
 94-443(C)(3) FOR TERMINAL AND INTERIOR ISLANDS.
  
 THE NONCONFORMITY IS BEING REDUCED WITH PLACEMENT OF
 TREES WITHIN THE PARKING AREA.
 GIVEN THE CLEARANCES WITH THE OVERHEAD TRANSMISSION
 LINES, GREEN BUTTONWOOD OR SEAGRAPE TREES MAY BE
 POSSIBLE IN THE ISLANDS TO MEET THE 75% SHADE TREE
 REQUIREMENT BUT MAY STILL FIT WITHIN THE RIGHT TREE
 RIGHT PLACE CLEARANCE GUIDELINES.
  
 2. SATISFIED. CORRECT THE BUFFER REQUIREMENTS CHART TO
 SHOW THE LENGTH OF EACH BUFFER SEGMENT, AND THE
 REQUIRED AND PROVIDED TREES FOR EACH SEGMENT. THERE ARE
 6 SEGMENTS, BUT ONLY 5 SHOWN ON THE CHART. GRAMERCY
 BUFFER INDICATES 25 TREES, BUT ONLY 24 ARE SHOWN ON THE
 PLAN.
  
 3. SATISFIED. IDENTIFYING TAGS ARE CUT OFF FOR TREES ON
 THE GRAMERCY BUFFER. REVISE.
  
 4. SATISFIED. INDICATE IF THE BUILDING PERIMETER
 MEASUREMENT HAS CHANGED WITH THE NEW BUILDING PROPOSED
 AND RECALCULATE THE NEW LENGTH, REQUIRED AND PROVIDED
 PLANTING PER SECTION 94-443 (E)2. FOR 20% FOUNDATION
 PLANTING CALCULATION REQUIRED FOR INDUSTRIAL ZONING.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 08-08-2022 Cont ID  
Sent By rcaranci Date 08-08-2022 Time 15:02 Rev Time 0.00
Received By rcaranci Date 08-08-2022 Time 15:02 Sent To  
Notes
2022-08-08 15:03:17FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 5950 N MILITARY TR, CAYMAN SUBSTATION
 Z22070014
 AUGUST 8, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. SECTION 94-443(C)(3) REQUIRES THAT A MINIMUM OF 75
 PERCENT OF ALL TREES THAT ARE REQUIRED TO BE PLANTED
 WITHIN THE INTERIOR OF AN OFF STREET PARKING AREA SHALL
 BE CATEGORY 1 SHADE TREES. SHOW THE PERCENTAGE OF
 CATEGORY 1 TREES PROVIDED FOR THE REQUIRED LANDSCAPE
 AREAS AS REQUIRED BY SECTION 94-443(C)(3) FOR TERMINAL
 AND INTERIOR ISLANDS.
  
 THE NONCONFORMITY IS BEING REDUCED WITH PLACEMENT OF
 TREES WITHIN THE PARKING AREA.
 GIVEN THE CLEARANCES WITH THE OVERHEAD TRANSMISSION
 LINES, GREEN BUTTONWOOD OR SEAGRAPE TREES MAY BE
 POSSIBLE IN THE ISLANDS TO MEET THE 75% SHADE TREE
 REQUIREMENT BUT MAY STILL FIT WITHIN THE RIGHT TREE
 RIGHT PLACE CLEARANCE GUIDELINES.
  
 2. CORRECT THE BUFFER REQUIREMENTS CHART TO SHOW THE
 LENGTH OF EACH BUFFER SEGMENT, AND THE REQUIRED AND
 PROVIDED TREES FOR EACH SEGMENT. THERE ARE 6 SEGMENTS,
 BUT ONLY 5 SHOWN ON THE CHART. GRAMERCY BUFFER
 INDICATES 25 TREES, BUT ONLY 24 ARE SHOWN ON THE PLAN.
  
 3. IDENTIFYING TAGS ARE CUT OFF FOR TREES ON THE
 GRAMERCY BUFFER. REVISE.
  
 4. INDICATE IF THE BUILDING PERIMETER MEASUREMENT HAS
 CHANGED WITH THE NEW BUILDING PROPOSED AND RECALCULATE
 THE NEW LENGTH, REQUIRED AND PROVIDED PLANTING PER
 SECTION 94-443 (E)2. FOR 20% FOUNDATION PLANTING
 CALCULATION REQUIRED FOR INDUSTRIAL ZONING.
  
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PU PUBLIC UTILITIES
Rev No 2 Status P Date 09-26-2022 Cont ID  
Sent By vbroglia Date   Time   Rev Time 0.00
Received By   Date 09-26-2022 Time   Sent To  
Notes
2022-09-26 14:06:04SENT EMAIL FOR RESUBMITAL REVIEW DEADLINE TO BE
 SEPTEMBER 19 BY NOON, NO REVIEW WAS DONE
 FOLLOWED UP EMAIL AND PHONE CALL ON SEPTEMBER 23, BUT
 NO RESPONSE/ANSWER
  
 1ST REVIEW COMMENTS MENTIONED IN THE APPROVAL LETTER
  
 VALENTINA BROGLIA
 [email protected]

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status F Date 08-12-2022 Cont ID  
Sent By mtechnow Date 08-12-2022 Time 14:25 Rev Time 0.00
Received By mtechnow Date 08-12-2022 Time 14:23 Sent To  
Notes
2022-08-12 14:25:12-PLEASE SHOW/CALL OUT LIFT STATION ON ENGINEERING PLANS
 AS WELL AS ANY UTILITY CONNECTIONS, VALVE BOXES ETC. ON
 SITE.

Review Stop PU-CS PUBLIC UTILITIES CUSTOMER SRVC
Rev No 2 Status P Date 09-20-2022 Cont ID  
Sent By mhurley Date 09-20-2022 Time 14:51 Rev Time 0.00
Received By mhurley Date   Time   Sent To  
Notes
***NONE***

Review Stop PU-CS PUBLIC UTILITIES CUSTOMER SRVC
Rev No 1 Status F Date 08-05-2022 Cont ID  
Sent By mhurley Date 08-05-2022 Time 19:11 Rev Time 0.00
Received By mhurley Date   Time   Sent To  
Notes
2022-08-05 19:11:13PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -VERIFY THAT THE PROPOSED BUILDING WILL NOT HAVE FIRE
 SPRINKLERS.
 -VERIFY THAT EXISTING WATER SERVICE IS SUFFICIENT FOR
 PROPOSED BUILDING.
 -VERIFY THAT WASTEWATER USED BY PROPERTY WILL FLOW TO
 SEWER MANHOLE ON UP THE GROVE.
 -IS EXISTING LIFT STATION CURRENTLY FUNCTIONAL AND IN
 USE DAY TO DAY?
 -WILL THERE BE AN IRRIGATION SYSTEM AND WILL IT RUN OFF
 THE EXISTING METERED WATER SERVICE?
 -PROVIDE PLANS FOR THE PROPOSED LIFT STATION.
 -HAS FENCE BEEN REROUTED AROUND WATER METER BOX YET?
 -HISTORIC PICTURES SHOW GUY WIRES COMING OFF ONE OF THE
 LARGE UTILITY POLES NEAR NORTHWEST AREA OF PROPERTY. IF
 THEY ARE STILL THERE SHOW ON PLANS AND ENSURE NO
 LANDSCAPING CONFLICTS.
 -LANDSCAPING PLANS SHOW MORE ENCROACHMENTS INTO
 MAINTENANCE AND ACCESS EASEMENT. VERIFY THAT NORTHERN
 PBC IMPROVEMENT DISTRICT IS ALRIGHT WITH THE PROPOSED
 PLANS. ALSO VERIFY IF THEY CURRENTLY ACCESS THE AREA
 WITH VEHICLES OR MACHINERY. IF SO, ENSURE THAT THEY
 WILL CONTINUE TO BE ABLE TO AFTER PROJECT IS COMPLETE.
 -LANDSCAPING PLANS SHOW 30 FOOT SUBSTATION CLEAR ZONE.
 PLEASE DESCRIBE WHAT THAT IS AND VERIFY THAT THE CLEAR
 ZONE REQUIREMENTS WILL BE MET.
 RESPECTFULLY,
 MARK HURLEY
 [email protected]
  

Review Stop PW PUBLIC WORKS
Rev No 2 Status P Date 09-19-2022 Cont ID  
Sent By   Date 09-19-2022 Time   Rev Time 0.00
Received By   Date 09-19-2022 Time   Sent To  
Notes
2022-09-19 11:42:12NO FURTHER COMMENTS.
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 08-09-2022 Cont ID  
Sent By   Date 08-09-2022 Time   Rev Time  
Received By   Date 08-09-2022 Time   Sent To  
Notes
2022-08-09 15:07:18PLEASE PROVIDE THE FOLLOWINGS:
 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID
 WASTE VOLUME PRODUCED ALONG WITH THE SIZE, TYPE AND
 QUANTITY OF THE CONTAINER (I.E. DUMPSTER/COMPACTOR)
 THAT WILL BE UTILIZED FOR THE SANITATION SERVICE.
 2- DETAILS FOR SANITATION SERVICE (I.E. SOLID WASTE
 CONTAINER(S) TYPE, COLLECTION LOCATION, ETC.). FOR A
 FREESTANDING SITE DUMPSTER ENCLOSURE, THE ENCLOSURE
 SHALL COMPLY WITH THE LATEST REVISION OF CITY OF WEST
 PALM BEACH GENERAL CONSTRUCTION-GARBAGE ENCLOSURE
 STANDARD, GC-7. (LINK TO THE LATEST REVISION OF THE
 GC-7 DOCUMENT: HTTPS://WWW.WPB.ORG/HOME/SHOWPUBLISHEDDO
 CUMENT/3690/637629060422100000)
 3- ALL THE PARKING STALL PAINTING SHALL COMPLY WITH THE
 CITY`S MUNICIPAL CODE SECTION 94-485 AND FLORIDA
 STATUES [553.5041 F.S.]
 4- ALL STRIPING AND SIGNAGE SHALL COMPLY WITH THE
 LATEST CITY OF WEST PALM BEACH STANDARD DETAILS AND
 MEET THE M.U.T.C.D. LATEST EDITION.
 5- ALL PAVEMENT MARKING , SIGNING AND SIDEWALK DAMAGED
 DURING CONSTRUCTION SHALL BE RESTORED.
 6- IN CASE OF PROPOSING ADDITION OF ANY NEW CAN(S) IN
 THE CITY`S RIGHT-OF-WAY , THE LOCATION AND QUANTITY OF
 THE CAN(S) SHALL BE REVIEWED AND APPROVED BY PUBLIC
 WORKS DEPARTMENT AND THE CAN(S) SHALL BE TYPE, SIZE AND
 COLOR APPROVED BY PUBLIC WORKS DEPARTMENT. THE BUILDING
 MAINTENANCE IS RESPONSIBLE TO MAINTAIN AND SERVICE THE
 CAN(S).
  
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045

Review Stop STORM STORMWATER
Rev No 2 Status P Date 09-29-2022 Cont ID  
Sent By tward Date 09-29-2022 Time 09:19 Rev Time 0.00
Received By tward Date 09-29-2022 Time 09:25 Sent To  
Notes
2022-09-29 09:23:25COMMENT ON THE 9-12-2022 SUBMITTAL:
  
 1. THE PROPOSED GRADING FOR THE HANDICAP PARKING SPACE
 EXCEEDS THE MAXIMUM ALLOWABLE SLOPE FOR A HANDICAP
 PARKING SPACE (2% OR FLATTER IN ALL DIRECTIONS). THE
 GRADING CAN BE CORRECTED FOR THE ENGINEERING PERMIT
 SUBMITTAL.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 [email protected]

Review Stop STORM STORMWATER
Rev No 1 Status P Date 08-15-2022 Cont ID  
Sent By tward Date 08-15-2022 Time 15:20 Rev Time 0.00
Received By tward Date 08-15-2022 Time 15:31 Sent To  
Notes
2022-08-15 15:31:091. NPBCID TO APPROVE OUTFALL INTO THE CANAL.
  
 2. OUTFALL PROFILE ON SHEET 4 OF 6 APPEARS TO SHOW
 MINIMAL COVER OVER THE STORM PIPE AT THE CONTROL
 STRUCTURE.
  
 3. SHOW WALKWAY BETWEEN THE HANDICAP PARKING SPACE
 NORTHWEST OF THE PROPOSED BUILDING TO THE PROPOSED
 BUILDING.
  
 4. LIST THE FFE OF THE PROPOSED BUILDING.
  
 5. MILITARY TRAIL RIGHT OF WAY IS MAINTAINED BY FDOT.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 [email protected]

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 09-19-2022 Cont ID  
Sent By vnoel Date 09-19-2022 Time 10:35 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
***NONE***

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 08-09-2022 Cont ID  
Sent By vnoel Date 08-09-2022 Time 13:54 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2022-08-09 14:21:581. ADD CONVERSION TO NGVD-29 TO PLANS.
 2. SITE PLAN SHOWS PROPOSED LIFT STATION.
 3. ENGINEERING PLANS DO NOT SHOW PROPOSED WATER AND
 SEWER CONNECTIONS OR LIFT STATION.
 4. NOT ALL PROPERTY CORNERS ARE LABELED.
 5. SEE SPELLING OF SURVEYOR'S NAME UNDER DIGITAL
 SIGNATURE.
 6. CORRECT OVER-WRITE WITH SCALE BAR.
 7.LINES MAY BE MISSING, I.E. E LINE, NW 1/4, NW 1/4 OF
 NE 1/4

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status P Date 09-23-2022 Cont ID  
Sent By vbroglia Date 09-23-2022 Time 13:39 Rev Time 0.00
Received By vbroglia Date 09-23-2022 Time 12:03 Sent To  
Notes
2022-09-23 13:43:44VALERIO EMAILED ME ON 9/19 STATING THE FOLLOWING:
  
 HI VALENTINA,
  
 COMMUNITY+ IS STILL DOWN. NONETHELESS, ALL MY COMMENTS
 HAVE BEEN SATISFIED, NO FURTHER ONES.
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 08-11-2022 Cont ID  
Sent By   Date 08-11-2022 Time   Rev Time  
Received By   Date 08-11-2022 Time   Sent To  
Notes
2022-08-11 04:24:481) PROVIDE COUNTY TPS LETTER, ONCE AVAILABLE
 2) PROVIDE FDOT ACCESS MANAGEMENT LETTER PERTAINING THE
 DRIVEWAY ON N MILITARY TRAIL
 3) PROVIDE AND CLEARLY MARK A WALKWAY FROM THE ADA
 STALL IN THE EASTERN PARKING LOT TO THE BUILDING
 4) PROVIDE AUTOTURN ANALYSIS FOR GARBAGE TRUCK AND/OR
 SERVICE VEHICLES DRIVING IN AND OUT OF THE PROPOSED
 DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES AND WHEEL
 PATHS CLEARLY DISTINCT AND DEFINED. ANALYSIS SHOULD BE
 PROVIDED IN A SEPARATE FILE/DRAWING. PLEASE PROVIDE
 DOCUMENT NAME AND SHEET NUMBER SHOWCASING THE ANALYSIS
 5) CLEARLY MARK THE LOADING ZONE(S) AND PROVIDE
 DIMENSIONS
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 08-04-2022 Cont ID  
Sent By vbroglia Date 08-04-2022 Time 15:49 Rev Time 0.00
Received By vbroglia Date 08-04-2022 Time 15:49 Sent To  
Notes
2022-08-11 11:24:11COMMENT FORM FDOT:
  
 THE ISSUANCE OF PERMITS FROM FDOT MAY BE REQUIRED FOR
 ACTIVITIES THAT MAY BE CONDUCTED WITHIN FDOT RIGHT OF
 WAY. THE APPLICANT CAN OBTAIN PERMIT INFORMATION AT THE
 FOLLOWING WEB SITE: HTTPS://OSP.FDOT.GOV/#/CONTENTPAGE/
 18CCF98B-9DBA-48A8-B5EA-A78E01198699. THIS IS THE
 DEPARTMENT?S ?ONE-STOP PERMITTING? WEB SITE. PLEASE
 FEEL FREE TO CONTACT MS. PATRICIA MOORE, THE FDOT
 PERMITS COORDINATOR FOR PALM BEACH COUNTY AT (954)
 777-4372 IF YOU HAVE ANY PERMIT RELATED QUESTION.

  Print