| Plan Review Stops For Project Z22070014 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
08-11-2022 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
08-11-2022 |
Time |
12:16 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
08-11-2022 |
Time |
12:15 |
Sent To |
|
|
| Notes |
| 2022-08-11 12:20:03 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS | | | SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT | | | REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH | | | COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963, | | | OR BY EMAIL: [email protected] | | | | | | 3. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, | | | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR | | | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, | | | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE | | | FLORIDA BUILDING CODE. | | | | | | 4. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, | | | FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, | | | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, | | | SITE IRRIGATION, ETC. | | | | | | 5. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT | | | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL | | | HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION | | | OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING, | | | CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT | | | (561) 805 6659, OR BY EMAIL: [email protected] | | | | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
P |
Date |
09-14-2022 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
09-14-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
09-14-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-09-14 08:25:38 | PASSED WITH PROVISO: PLEASE CLEARLY SHOW ON ENGINEERING | | | PLANS THE EXISTING AND PROPOSED LIFT STATIONS. INDICATE | | | IF EXISTING LIFT STATION IS TO REMAIN OR BE REMOVED. |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
07-27-2022 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
07-27-2022 |
Time |
|
Rev Time |
|
| Received By |
rrossano |
Date |
07-27-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-07-27 10:16:43 | Z22070014 - FPL BLDG, 5950 N MILITARY 7.26.22 SUB | | | COMMENTS FROM RICK ROSSANO, SR. PROJECT COORDINATOR, | | | ENGINEERING SERVICES AT 561-494-1098 [email protected] | | | | | | PLEASE ADVISE WHAT IS HAPPENING WITH THE EXISTING LIFT | | | STATION ON THE NW AREA OF THE PROPERTY. | | | | | | GENERAL: | | | O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND | | | INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER | | | (Z-XXXXXXXX). | | | O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY | | | OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC | | | RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF | | | YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE | | | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL | | | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT | | | [email protected] OR 561-494-1079 FOR FURTHER | | | ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION | | | ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD | | | SURVEY, POT-HOLING, SOFT DIGS ETC. | | | O PROVIDE EXISTING AND PROPOSED PERVIOUS AND IMPERVIOUS | | | DATA. | | | O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY | | | TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT | | | APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING | | | AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, | | | MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS | | | SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 | | | FOR WATER. | | | O IT APPEARS THAT THERE ARE NO POTABLE WATER OR SEWER | | | CONNECTIONS PROPOSED, PLEASE CONFIRM. | | | | | | FORMAL ENGINEERING REVIEW: | | | O FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES | | | NOI REQUIREMENTS WILL BE ENFORCED. | | | - AN NOI IS REQUIRED FOR PROJECTS THAT: | | | - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS | | | THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF | | | DEVELOPMENT OR SALE; | | | - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE | | | STATE OR TO SURFACE WATERS OF THE STATE THROUGH A | | | MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4). | | | - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF | | | CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION | | | THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL | | | SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT | | | OF THE 10-2 CERTIFICATION. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | CALCULATIONS OF PERVIOUS AND IMPERVIOUS AREAS FOR | | | PROPOSED IMPROVED AREAS. | | | QUESTIONS AND COORDINATION CONTACTS: | | | O MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR WITH | | | CITY OF WPB PUBLIC UTILITIES, REGARDING PLACEMENT OF | | | BACKFLOW DEVICES AND WATER METERS. CONTACT HIM AT | | | 561-822-2262 OR [email protected] | | | O MIKE TECHNOW, PROJECT ENGINEER, PUBLIC UTILITIES | | | DEPARTMENT AT 561-494-1047 OR [email protected] | | | O TRACY WARD, SR. STORMWATER ENGINEER, ENGINEERING | | | SERVICES DEPT. AT 561-494-1120 OR [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
08-01-2022 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
08-01-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
08-01-2022 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2022-08-01 14:39:04 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE DEPARTMENT. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. THE FOLLOWING COMMENTS ARE INTENDED | | | TO PROVIDE GUIDANCE FOR BUILDING PLAN SUBMITTAL. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH | | | THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, | | | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. | | | | | | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE | | | OCCUPANCY TYPE PER THE FLORIDA FIRE PREVENTION CODE. | | | | | | 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE | | | LOAD CALCULATION IS INCLUDED, AND THAT ADEQUATE WATER | | | SUPPLY IS EXISTING OR WILL BE PROVIDED. | | | | | | 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | THE PROPOSED LOCATION OF THE FIRE HYDRANT AND FDC SHALL | | | BE WITHIN 100' OF EACH OTHER AND CLOSELY COORDINATED | | | WITH THE BUREAU OF FIRE PREVENTION. | | | | | | 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER | | | THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY | | | ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM, | | | ENSURE THEY COMPLY WITH THE REQUIREMENTS OF F.A.C. 61G | | | AND SUBMITTED WITH THE MASTER PERMIT. | | | | | | 9A. THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE | | | LOCATIONS SHALL MEET AND BE INSTALLED PER THE | | | REQUIREMENTS OF NFPA 24 AND SHALL BE COORDINATED WITH | | | THE OFFICE OF FIRE MARSHAL, THE CITY'S ENGINEERS | | | OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S PLANNING | | | AND ZONING OFFICE. | | | | | | 10. COMPLETE LIFE SAFETY PLANS FOR THE OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, EXIT SEPARATION DISTANCES, COMMON PATHS OF | | | TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, EMERGENCY | | | LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE | | | EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES | | | AND EQUIPMENT. | | | | | | 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE | | | SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY | | | DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS. | | | | | | 12. TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEMS. | | | | | | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY | | | RADIO ENHANCEMENT SERVICES. | | | 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM | | | RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT | | | COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL | | | DETERMINED BY THE AHJ. | | | | | | IF APPLICABLE, CONTACT WILL NEED TO BE MADE TO MARK | | | FILLA, PALM BEACH COUNTY PUBLIC SAFETY RADIO SYSTEMS | | | MANAGER, [email protected], 561-233-0837; AS OUR RADIOS | | | OPERATE ON THEIR SYSTEM FOR DETAILED RADIO FREQUENCY | | | AND INSTALLATION INSTRUCTIONS. | | | | | | 13. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL. | | | | | | 14. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
P |
Date |
09-19-2022 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
09-19-2022 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
09-19-2022 |
Time |
13:33 |
Sent To |
|
|
| Notes |
| 2022-09-19 13:34:18 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: 5950 N MILITARY TR, CAYMAN SUBSTATION | | | Z22070014 | | | SEPTEMBER 19, 2022 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | | | | 1. SATISFIED. SECTION 94-443(C)(3) REQUIRES THAT A | | | MINIMUM OF 75 PERCENT OF ALL TREES THAT ARE REQUIRED TO | | | BE PLANTED WITHIN THE INTERIOR OF AN OFF STREET PARKING | | | AREA SHALL BE CATEGORY 1 SHADE TREES. SHOW THE | | | PERCENTAGE OF CATEGORY 1 TREES PROVIDED FOR THE | | | REQUIRED LANDSCAPE AREAS AS REQUIRED BY SECTION | | | 94-443(C)(3) FOR TERMINAL AND INTERIOR ISLANDS. | | | | | | THE NONCONFORMITY IS BEING REDUCED WITH PLACEMENT OF | | | TREES WITHIN THE PARKING AREA. | | | GIVEN THE CLEARANCES WITH THE OVERHEAD TRANSMISSION | | | LINES, GREEN BUTTONWOOD OR SEAGRAPE TREES MAY BE | | | POSSIBLE IN THE ISLANDS TO MEET THE 75% SHADE TREE | | | REQUIREMENT BUT MAY STILL FIT WITHIN THE RIGHT TREE | | | RIGHT PLACE CLEARANCE GUIDELINES. | | | | | | 2. SATISFIED. CORRECT THE BUFFER REQUIREMENTS CHART TO | | | SHOW THE LENGTH OF EACH BUFFER SEGMENT, AND THE | | | REQUIRED AND PROVIDED TREES FOR EACH SEGMENT. THERE ARE | | | 6 SEGMENTS, BUT ONLY 5 SHOWN ON THE CHART. GRAMERCY | | | BUFFER INDICATES 25 TREES, BUT ONLY 24 ARE SHOWN ON THE | | | PLAN. | | | | | | 3. SATISFIED. IDENTIFYING TAGS ARE CUT OFF FOR TREES ON | | | THE GRAMERCY BUFFER. REVISE. | | | | | | 4. SATISFIED. INDICATE IF THE BUILDING PERIMETER | | | MEASUREMENT HAS CHANGED WITH THE NEW BUILDING PROPOSED | | | AND RECALCULATE THE NEW LENGTH, REQUIRED AND PROVIDED | | | PLANTING PER SECTION 94-443 (E)2. FOR 20% FOUNDATION | | | PLANTING CALCULATION REQUIRED FOR INDUSTRIAL ZONING. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
08-08-2022 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
08-08-2022 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
08-08-2022 |
Time |
15:02 |
Sent To |
|
|
| Notes |
| 2022-08-08 15:03:17 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: 5950 N MILITARY TR, CAYMAN SUBSTATION | | | Z22070014 | | | AUGUST 8, 2022 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | | | | 1. SECTION 94-443(C)(3) REQUIRES THAT A MINIMUM OF 75 | | | PERCENT OF ALL TREES THAT ARE REQUIRED TO BE PLANTED | | | WITHIN THE INTERIOR OF AN OFF STREET PARKING AREA SHALL | | | BE CATEGORY 1 SHADE TREES. SHOW THE PERCENTAGE OF | | | CATEGORY 1 TREES PROVIDED FOR THE REQUIRED LANDSCAPE | | | AREAS AS REQUIRED BY SECTION 94-443(C)(3) FOR TERMINAL | | | AND INTERIOR ISLANDS. | | | | | | THE NONCONFORMITY IS BEING REDUCED WITH PLACEMENT OF | | | TREES WITHIN THE PARKING AREA. | | | GIVEN THE CLEARANCES WITH THE OVERHEAD TRANSMISSION | | | LINES, GREEN BUTTONWOOD OR SEAGRAPE TREES MAY BE | | | POSSIBLE IN THE ISLANDS TO MEET THE 75% SHADE TREE | | | REQUIREMENT BUT MAY STILL FIT WITHIN THE RIGHT TREE | | | RIGHT PLACE CLEARANCE GUIDELINES. | | | | | | 2. CORRECT THE BUFFER REQUIREMENTS CHART TO SHOW THE | | | LENGTH OF EACH BUFFER SEGMENT, AND THE REQUIRED AND | | | PROVIDED TREES FOR EACH SEGMENT. THERE ARE 6 SEGMENTS, | | | BUT ONLY 5 SHOWN ON THE CHART. GRAMERCY BUFFER | | | INDICATES 25 TREES, BUT ONLY 24 ARE SHOWN ON THE PLAN. | | | | | | 3. IDENTIFYING TAGS ARE CUT OFF FOR TREES ON THE | | | GRAMERCY BUFFER. REVISE. | | | | | | 4. INDICATE IF THE BUILDING PERIMETER MEASUREMENT HAS | | | CHANGED WITH THE NEW BUILDING PROPOSED AND RECALCULATE | | | THE NEW LENGTH, REQUIRED AND PROVIDED PLANTING PER | | | SECTION 94-443 (E)2. FOR 20% FOUNDATION PLANTING | | | CALCULATION REQUIRED FOR INDUSTRIAL ZONING. | | | | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
2 |
Status |
P |
Date |
09-26-2022 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
09-26-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-09-26 14:06:04 | SENT EMAIL FOR RESUBMITAL REVIEW DEADLINE TO BE | | | SEPTEMBER 19 BY NOON, NO REVIEW WAS DONE | | | FOLLOWED UP EMAIL AND PHONE CALL ON SEPTEMBER 23, BUT | | | NO RESPONSE/ANSWER | | | | | | 1ST REVIEW COMMENTS MENTIONED IN THE APPROVAL LETTER | | | | | | VALENTINA BROGLIA | | | [email protected] |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
1 |
Status |
F |
Date |
08-12-2022 |
|
|
Cont ID |
|
| Sent By |
mtechnow |
Date |
08-12-2022 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
mtechnow |
Date |
08-12-2022 |
Time |
14:23 |
Sent To |
|
|
| Notes |
| 2022-08-12 14:25:12 | -PLEASE SHOW/CALL OUT LIFT STATION ON ENGINEERING PLANS | | | AS WELL AS ANY UTILITY CONNECTIONS, VALVE BOXES ETC. ON | | | SITE. |
|
|
| Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
| Rev No |
2 |
Status |
P |
Date |
09-20-2022 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
09-20-2022 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
| Rev No |
1 |
Status |
F |
Date |
08-05-2022 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
08-05-2022 |
Time |
19:11 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-05 19:11:13 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | -VERIFY THAT THE PROPOSED BUILDING WILL NOT HAVE FIRE | | | SPRINKLERS. | | | -VERIFY THAT EXISTING WATER SERVICE IS SUFFICIENT FOR | | | PROPOSED BUILDING. | | | -VERIFY THAT WASTEWATER USED BY PROPERTY WILL FLOW TO | | | SEWER MANHOLE ON UP THE GROVE. | | | -IS EXISTING LIFT STATION CURRENTLY FUNCTIONAL AND IN | | | USE DAY TO DAY? | | | -WILL THERE BE AN IRRIGATION SYSTEM AND WILL IT RUN OFF | | | THE EXISTING METERED WATER SERVICE? | | | -PROVIDE PLANS FOR THE PROPOSED LIFT STATION. | | | -HAS FENCE BEEN REROUTED AROUND WATER METER BOX YET? | | | -HISTORIC PICTURES SHOW GUY WIRES COMING OFF ONE OF THE | | | LARGE UTILITY POLES NEAR NORTHWEST AREA OF PROPERTY. IF | | | THEY ARE STILL THERE SHOW ON PLANS AND ENSURE NO | | | LANDSCAPING CONFLICTS. | | | -LANDSCAPING PLANS SHOW MORE ENCROACHMENTS INTO | | | MAINTENANCE AND ACCESS EASEMENT. VERIFY THAT NORTHERN | | | PBC IMPROVEMENT DISTRICT IS ALRIGHT WITH THE PROPOSED | | | PLANS. ALSO VERIFY IF THEY CURRENTLY ACCESS THE AREA | | | WITH VEHICLES OR MACHINERY. IF SO, ENSURE THAT THEY | | | WILL CONTINUE TO BE ABLE TO AFTER PROJECT IS COMPLETE. | | | -LANDSCAPING PLANS SHOW 30 FOOT SUBSTATION CLEAR ZONE. | | | PLEASE DESCRIBE WHAT THAT IS AND VERIFY THAT THE CLEAR | | | ZONE REQUIREMENTS WILL BE MET. | | | RESPECTFULLY, | | | MARK HURLEY | | | [email protected] | | | |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
2 |
Status |
P |
Date |
09-19-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
09-19-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
09-19-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-09-19 11:42:12 | NO FURTHER COMMENTS. | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
F |
Date |
08-09-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
08-09-2022 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
08-09-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-09 15:07:18 | PLEASE PROVIDE THE FOLLOWINGS: | | | 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID | | | WASTE VOLUME PRODUCED ALONG WITH THE SIZE, TYPE AND | | | QUANTITY OF THE CONTAINER (I.E. DUMPSTER/COMPACTOR) | | | THAT WILL BE UTILIZED FOR THE SANITATION SERVICE. | | | 2- DETAILS FOR SANITATION SERVICE (I.E. SOLID WASTE | | | CONTAINER(S) TYPE, COLLECTION LOCATION, ETC.). FOR A | | | FREESTANDING SITE DUMPSTER ENCLOSURE, THE ENCLOSURE | | | SHALL COMPLY WITH THE LATEST REVISION OF CITY OF WEST | | | PALM BEACH GENERAL CONSTRUCTION-GARBAGE ENCLOSURE | | | STANDARD, GC-7. (LINK TO THE LATEST REVISION OF THE | | | GC-7 DOCUMENT: HTTPS://WWW.WPB.ORG/HOME/SHOWPUBLISHEDDO | | | CUMENT/3690/637629060422100000) | | | 3- ALL THE PARKING STALL PAINTING SHALL COMPLY WITH THE | | | CITY`S MUNICIPAL CODE SECTION 94-485 AND FLORIDA | | | STATUES [553.5041 F.S.] | | | 4- ALL STRIPING AND SIGNAGE SHALL COMPLY WITH THE | | | LATEST CITY OF WEST PALM BEACH STANDARD DETAILS AND | | | MEET THE M.U.T.C.D. LATEST EDITION. | | | 5- ALL PAVEMENT MARKING , SIGNING AND SIDEWALK DAMAGED | | | DURING CONSTRUCTION SHALL BE RESTORED. | | | 6- IN CASE OF PROPOSING ADDITION OF ANY NEW CAN(S) IN | | | THE CITY`S RIGHT-OF-WAY , THE LOCATION AND QUANTITY OF | | | THE CAN(S) SHALL BE REVIEWED AND APPROVED BY PUBLIC | | | WORKS DEPARTMENT AND THE CAN(S) SHALL BE TYPE, SIZE AND | | | COLOR APPROVED BY PUBLIC WORKS DEPARTMENT. THE BUILDING | | | MAINTENANCE IS RESPONSIBLE TO MAINTAIN AND SERVICE THE | | | CAN(S). | | | | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] | | | 561-822-2045 |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
P |
Date |
09-29-2022 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
09-29-2022 |
Time |
09:19 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
09-29-2022 |
Time |
09:25 |
Sent To |
|
|
| Notes |
| 2022-09-29 09:23:25 | COMMENT ON THE 9-12-2022 SUBMITTAL: | | | | | | 1. THE PROPOSED GRADING FOR THE HANDICAP PARKING SPACE | | | EXCEEDS THE MAXIMUM ALLOWABLE SLOPE FOR A HANDICAP | | | PARKING SPACE (2% OR FLATTER IN ALL DIRECTIONS). THE | | | GRADING CAN BE CORRECTED FOR THE ENGINEERING PERMIT | | | SUBMITTAL. | | | | | | TRACY WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | [email protected] |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
P |
Date |
08-15-2022 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
08-15-2022 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
08-15-2022 |
Time |
15:31 |
Sent To |
|
|
| Notes |
| 2022-08-15 15:31:09 | 1. NPBCID TO APPROVE OUTFALL INTO THE CANAL. | | | | | | 2. OUTFALL PROFILE ON SHEET 4 OF 6 APPEARS TO SHOW | | | MINIMAL COVER OVER THE STORM PIPE AT THE CONTROL | | | STRUCTURE. | | | | | | 3. SHOW WALKWAY BETWEEN THE HANDICAP PARKING SPACE | | | NORTHWEST OF THE PROPOSED BUILDING TO THE PROPOSED | | | BUILDING. | | | | | | 4. LIST THE FFE OF THE PROPOSED BUILDING. | | | | | | 5. MILITARY TRAIL RIGHT OF WAY IS MAINTAINED BY FDOT. | | | | | | TRACY WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | [email protected] |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
2 |
Status |
P |
Date |
09-19-2022 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
09-19-2022 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
08-09-2022 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
08-09-2022 |
Time |
13:54 |
Rev Time |
|
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-09 14:21:58 | 1. ADD CONVERSION TO NGVD-29 TO PLANS. | | | 2. SITE PLAN SHOWS PROPOSED LIFT STATION. | | | 3. ENGINEERING PLANS DO NOT SHOW PROPOSED WATER AND | | | SEWER CONNECTIONS OR LIFT STATION. | | | 4. NOT ALL PROPERTY CORNERS ARE LABELED. | | | 5. SEE SPELLING OF SURVEYOR'S NAME UNDER DIGITAL | | | SIGNATURE. | | | 6. CORRECT OVER-WRITE WITH SCALE BAR. | | | 7.LINES MAY BE MISSING, I.E. E LINE, NW 1/4, NW 1/4 OF | | | NE 1/4 |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
2 |
Status |
P |
Date |
09-23-2022 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
09-23-2022 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
09-23-2022 |
Time |
12:03 |
Sent To |
|
|
| Notes |
| 2022-09-23 13:43:44 | VALERIO EMAILED ME ON 9/19 STATING THE FOLLOWING: | | | | | | HI VALENTINA, | | | | | | COMMUNITY+ IS STILL DOWN. NONETHELESS, ALL MY COMMENTS | | | HAVE BEEN SATISFIED, NO FURTHER ONES. | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
08-11-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
08-11-2022 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
08-11-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-11 04:24:48 | 1) PROVIDE COUNTY TPS LETTER, ONCE AVAILABLE | | | 2) PROVIDE FDOT ACCESS MANAGEMENT LETTER PERTAINING THE | | | DRIVEWAY ON N MILITARY TRAIL | | | 3) PROVIDE AND CLEARLY MARK A WALKWAY FROM THE ADA | | | STALL IN THE EASTERN PARKING LOT TO THE BUILDING | | | 4) PROVIDE AUTOTURN ANALYSIS FOR GARBAGE TRUCK AND/OR | | | SERVICE VEHICLES DRIVING IN AND OUT OF THE PROPOSED | | | DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES AND WHEEL | | | PATHS CLEARLY DISTINCT AND DEFINED. ANALYSIS SHOULD BE | | | PROVIDED IN A SEPARATE FILE/DRAWING. PLEASE PROVIDE | | | DOCUMENT NAME AND SHEET NUMBER SHOWCASING THE ANALYSIS | | | 5) CLEARLY MARK THE LOADING ZONE(S) AND PROVIDE | | | DIMENSIONS | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
08-04-2022 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
08-04-2022 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
08-04-2022 |
Time |
15:49 |
Sent To |
|
|
| Notes |
| 2022-08-11 11:24:11 | COMMENT FORM FDOT: | | | | | | THE ISSUANCE OF PERMITS FROM FDOT MAY BE REQUIRED FOR | | | ACTIVITIES THAT MAY BE CONDUCTED WITHIN FDOT RIGHT OF | | | WAY. THE APPLICANT CAN OBTAIN PERMIT INFORMATION AT THE | | | FOLLOWING WEB SITE: HTTPS://OSP.FDOT.GOV/#/CONTENTPAGE/ | | | 18CCF98B-9DBA-48A8-B5EA-A78E01198699. THIS IS THE | | | DEPARTMENT?S ?ONE-STOP PERMITTING? WEB SITE. PLEASE | | | FEEL FREE TO CONTACT MS. PATRICIA MOORE, THE FDOT | | | PERMITS COORDINATOR FOR PALM BEACH COUNTY AT (954) | | | 777-4372 IF YOU HAVE ANY PERMIT RELATED QUESTION. |
|
|
| |