Plan Review Details - Project Z22060027
Plan Review Stops For Project Z22060027
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 10-11-2022 Cont ID  
Sent By scwelter Date 06-28-2022 Time 14:44 Rev Time 0.00
Received By swelter Date 10-11-2022 Time 15:52 Sent To  
Notes
2022-10-11 15:51:54PUBLIC ART WILL BE ADMINISTERED THROUGH THE PUBLIC ART
 PROGRAM ARTLIFE WPB
2022-06-28 15:01:12THIS PUBLIC PROJECT IS SUBJECT TO THE PUBLIC ART
 REQUIREMENT AS PER CITY ORDINANCE. EMAIL
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 10-07-2022 Cont ID  
Sent By rbrown Date 10-07-2022 Time 19:32 Rev Time 0.00
Received By rbrown Date 10-07-2022 Time 19:31 Sent To  
Notes
2022-10-07 19:32:46DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS
 SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT
 REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH
 COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963,
 OR BY EMAIL: [email protected]
  
 3. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 4. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE
 REQUIRED. FOR INFORMATION ON THE REQUIRED TYPE, SIZE
 AND LOCATION, PLEASE CONTACT RYAN BROWN, CHIEF PLUMBING
 INSPECTOR, DEVELOPMENT SERVICES DEPARTMENT, AT (561)
 805-6692, OR BY EMAIL: [email protected]
  
 5. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 6. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION
 OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING,
 CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT
 (561) 805 6659, OR BY EMAIL: [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 07-13-2022 Cont ID  
Sent By rbrown Date 07-13-2022 Time 19:46 Rev Time 0.00
Received By rbrown Date 07-13-2022 Time 19:46 Sent To  
Notes
2022-07-13 19:57:05DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS
 SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT
 REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH
 COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963,
 OR BY EMAIL: [email protected]
  
 3. NUMBER OF ACCESSIBLE PARKING SPACES. NO PARKING
 SPACE COUNT HAS BEEN PROVIDED FROM WHICH TO DETERMINE
 THE NUMBER OF ACCESSIBLE PARKING SPACES REQUIRED. THE
 MINIMUM NUMBER OF ACCESSIBLE PARKING SPACES PROVIDED
 SHALL BE IN ACCORDANCE WITH SECTION 208.2 OF FLORIDA
 ACCESSIBILITY CODE.
  
 4. LOCATION OF ACCESSIBLE PARKING SPACES. PER SECTION
 208.3 OF FLORIDA ACCESSIBILITY CODE, ACCESSIBLE PARKING
 SPACES ARE TO BE LOCATED ON THE SHORTEST POSSIBLE ROUTE
 OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE
 ENTRANCE. THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL
 COMPLY WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE
  
 5. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 6. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE
 REQUIRED. FOR INFORMATION ON THE REQUIRED TYPE, SIZE
 AND LOCATION, PLEASE CONTACT RYAN BROWN, CHIEF PLUMBING
 INSPECTOR, DEVELOPMENT SERVICES DEPARTMENT, AT (561)
 805-6692, OR BY EMAIL: [email protected]
  
 7. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 8. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION
 OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING,
 CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT
 (561) 805 6659, OR BY EMAIL: [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status P Date 09-14-2022 Cont ID  
Sent By rrossano Date 09-14-2022 Time   Rev Time 0.00
Received By rrossano Date 09-14-2022 Time   Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 07-07-2022 Cont ID  
Sent By rrossano Date 07-07-2022 Time   Rev Time  
Received By rrossano Date 07-07-2022 Time   Sent To  
Notes
2022-07-07 12:57:40COMMENTS FROM RICK ROSSANO, SR. PROJECT COORDINATOR,
 ENGINEERING SERVICES AT 561-494-1098 [email protected]
 GENERAL:
 O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (Z-XXXXXXXX).
 O THE CITY OF WEST PALM BEACH HAS A NUMBER OF
 REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY
 AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND
 WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE
 DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK
 BELOW:
 A. HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WP
 B_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FUL
 L-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97
 B1960045731D3658206F27451722716EF
 B. THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE
 FOUND HERE:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
 C. ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM
 BEACH, FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08,
 ADOPTED SEPT. 22, 2008. (SUPPLEMENT NO. 18)
 CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL,
 SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER
 SERVICE FACILITIES OF THE CITY.
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
 O AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, REFER TO THE LINK BELOW:
 A. HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PU
 BLICATIONS/BACKFLOW-CROSS-CONNECTION- CONTROL-MANUAL
 O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1079 FOR FURTHER
 ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION
 ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD
 SURVEY, POT-HOLING, SOFT DIGS ETC.
 O PROVIDE EXISTING AND PROPOSED PERVIOUS AND IMPERVIOUS
 DATA.
  
 BACKFLOW ASSEMBLY AND METERS:
 O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER
 SERVICES AND WATER METERS, ALONG WITH WHAT IS HAPPENING
 TO THEM.
 O SHOW EXISTING AND PROPOSED DEDICATED UTILITY
 EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO
 PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO
 STRUCTURES WITHIN EASEMENT.
 O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION
 OF WATER METER AND BACKFLOW
 PREVENTION.
 O BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY
 OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER
 METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO
 PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE
 INSTALLED ABOVE-GROUND ONLY.
 O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE
 NOTE USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA.
  
 WATER/WASTEWATER PLAN:
 O PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE
 STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC.
 O PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND
 DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND
 SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH
 PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE
 AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS,
 BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO
 BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS,
 DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS,
 ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT
 ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF
 SANITARY SEWER LINES.
 O GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR
 SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW.
 O DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN
 VIEW FOR ALL SANITARY AND STORM SEWERS.
 O SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL.
 O PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED
 UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC,
 ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION
 FACILITIES LOCATED ON THE RIGHT-OF-WAY.
 O PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER
 AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD
 DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS.
 O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY
 TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT
 APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING
 AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE,
 MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS
 SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008
 FOR WATER.
 O PROVIDE FIRE FLOW TEST DATA (AS APPLICABLE).
 O CUT AND CAP UTILITIES NOT IN USE AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 ROW.
 O WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL
 BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY
 PROPOSED LENGTH IN FEET.
 O CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY
 SEWER ARE REQUIRED.
 O PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE
 JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET.
 O ADD NOTE TO PLANS SPECIFYING CITY?S DOWNSTREAM LIFT
 STATION NUMBER.
 O PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR
 PROPOSED SANITARY LATERALS.
 O LABEL WATER LINES AS PRIVATE WHERE APPLICABLE.
 O PLEASE SHOW AND LABEL EXISTING AND PROPOSED GREASE
 TRAPS (IF ANY).
 O PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN
 OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 11-03-2022 Cont ID  
Sent By pleduc Date 11-03-2022 Time 14:31 Rev Time 0.00
Received By pleduc Date 11-03-2022 Time 14:31 Sent To  
Notes
2022-11-03 14:31:55AFTER A REVIEW OF THE PPRC RESPONSE PACKET FOR THIS
 PROJECT, THE PREVIOUSLY SUBMITTED FIRE PREVENTION
 BUREAU COMMENTS APPEAR TO HAVE BEEN ADDRESSED.
  
 HOWEVER, THE BUREAU'S APPROVAL OF THIS SUBMITTED
 PROJECT DOES NOT CONSTITUTE ITS FINAL REVIEW OR
 APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE DEPARTMENT
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 09-22-2022 Cont ID  
Sent By pleduc Date 09-22-2022 Time   Rev Time 0.00
Received By pleduc Date 09-22-2022 Time 10:05 Sent To  
Notes
2022-09-22 10:05:42AFTER A REVIEW OF THE PPRC RESPONSE PACKET FOR THIS
 PROJECT, THE PREVIOUSLY SUBMITTED FIRE PREVENTION
 BUREAU COMMENTS APPEAR TO HAVE BEEN ADDRESSED.
  
 HOWEVER, THE BUREAU'S APPROVAL OF THIS SUBMITTED
 PROJECT DOES NOT CONSTITUTE ITS FINAL REVIEW OR
 APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE DEPARTMENT
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 07-01-2022 Cont ID  
Sent By pleduc Date 07-01-2022 Time   Rev Time 0.00
Received By pleduc Date 07-01-2022 Time 15:04 Sent To  
Notes
2022-07-01 15:07:10THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE DEPARTMENT.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT. THE FOLLOWING COMMENTS ARE INTENDED
 TO PROVIDE GUIDANCE FOR BUILDING PLAN SUBMITTAL.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING(S) SHALL COMPLY
 WITH THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION
 CODE, INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE
 CODES.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE PER THE FLORIDA FIRE PREVENTION CODE.
  
 7. ANY EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 8. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM,
 ENSURE THEY COMPLY WITH THE REQUIREMENTS OF F.A.C. 61G
 AND SUBMITTED WITH THE MASTER PERMIT.
  
 9. COMPLETE LIFE SAFETY PLANS FOR THE OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, EXIT SEPARATION DISTANCES, COMMON PATHS OF
 TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, EMERGENCY
 LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE
 EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES
 AND EQUIPMENT.
  
 10. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE
 SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY
 DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS.
  
 11. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
 12. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 3 Status P Date 11-15-2022 Cont ID  
Sent By rcaranci Date 11-15-2022 Time 14:31 Rev Time 0.00
Received By rcaranci Date 11-15-2022 Time 14:31 Sent To  
Notes
2022-11-15 14:32:16FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: GAINES PARK Z22060027
 NOVEMBER 15, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. CITY POLICY 10-2 PREFERS THE USE OF
 FLORIDA NATIVE PLANTS WHERE POSSIBLE.
  
 2. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE
 TREES AND PALMS IN GOOD CONDITION TO BE PRESERVED ON
 SITE OR RELOCATED. PROVIDE AN ARBORISTS REPORT RATING
 THE CONDITION AND RELOCATION POTENTIAL FOR THE NATIVE
 TREES AND PALMS. THERE ARE LIVE OAKS, SABAL PALMS, AND
 ROYAL PALMS THAT ARE INDICATED TO BE REMOVED. AN
 ACCURATE EVALUATION MUST BE PROVIDED AS TO CONDITION
 AND WHY THESE TREES CANNOT BE RELOCATED.
 7 SABAL PALMS ARE TO BE RELOCATED.
  
  
 3. SATISFIED. REVISE SHEETS TD-1 AND TD-2 TO REFLECT
 CHANGES TO THE DISPOSITION CHART ON SHEET TD-3.
 THERE ARE DISCREPANCIES BETWEEN THE DISPOSITION CHART
 AND THE DISPOSITION PLAN.
  
 4. SATISFIED. PROVIDE THE MITIGATION SQUARE FOOTAGE DUE
 FOR TREES AND PALMS TO BE REMOVED AND PROVIDE THE
 MITIGATION SQUARE FOOTAGE CREDIT BASED ON THE PLANT
 LIST.
 THERE ARE DISCREPANCIES IN THE MITIGATION CHART.
  
 5. SATISFIED. LIVE OAKS 5504 AND 5505 HAVE A DRAINAGE
 LINE PROPOSED THAT WILL BE IN CONFLICT WITH THE ROOT
 SYSTEMS OF THE TREES. REDESIGN TO AVOID DAMAGING THE
 ROOT SYSTEM OF THE TREES TO REMAIN.
 DRAINAGE LINE LOCATIONS HAVE BEEN MODIFIED, BUT STILL
 CUT THROUGH THE CRITICAL ROOT ZONE OF EACH TREE. IF
 OPEN TRENCH IS USED FOR INSTALLATION, THEY WILL BE TOO
 CLOSE TO THE TREES.
  
 6. SATISFIED. DRAINAGE LINES PROPOSED ON THE SOUTH SIDE
 OF THE ENTRANCE ARE ALSO IN CONFLICT WITH PROPOSED
 TREES AND PALMS AND EXISTING ROYAL PALMS.
 ROYAL PALM SOUTH OF ENTRANCE IS STILL IN CONFLICT.
  
 7. SATISFIED. USE CLEAR SYMBOLS ON THE PLANS TO
 REPRESENT TREES AND PALMS TO REMAIN.
  
 8. SATISFIED. ADD COLUMN FOR DROUGHT TOLERANCE TO THE
 PLANT LIST.
  
 9. SATISFIED. PER SECTION 94-443(G) PROVIDE THE FLORIDA
 FRIENDLY LANDSCAPE REQUIREMENTS DESIGN OPTIONS IN A
 CHART MEETING THE 50 REQUIRED POINTS.
 CHART WAS ADDED, BUT INCORRECT AND DUPLICATE OPTION
 POINTS ARE INDICATED. REVISE.
  
 10. SATISFIED. PROVIDE A SECTION IN A LANDSCAPE DATA
 CHART TO COMPLY WITH SECTION 94-445 L. PLANT SPECIES. A
 MINIMUM OF 60 PERCENT OF PLANT MATERIAL ADDED SHALL BE
 FLORIDA NATIVE OR DROUGHT TOLERANT SPECIES SELECTED
 FROM THE CITY LIST OR THE LIST OF SPECIES IN THE MOST
 RECENT EDITION OF SOUTH FLORIDA WATER MANAGEMENT
 DISTRICT WATERWISE SOUTH FLORIDA LANDSCAPES. PROVIDE
 THE TOTAL PERCENTAGE OF NATIVE AND DROUGHT TOLERANT
 PLANTS BASED ON THE FINAL PLANT LIST.
 PERCENTAGE COULD NOT BE LOCATED ON THE PLANS. BEST IF
 PLACED ON THE PLANT LIST SHEET.
  
 11. SATISFIED. PER SECTION 94-443 (E)2., PROVIDE THE
 30% FOUNDATION PLANTING CALCULATION REQUIRED AND
 PROVIDED FOR EACH BUILDING.
 PROVIDED THE LENGTHS BUT PROVIDED LENGTHS DO NOT MAKE
 SENSE. PROVIDE THE TOTAL FOUNDATION LENGTH FOR EACH
 BUILDING AND THE LINEAR FOOTAGE OF LANDSCAPE PROVIDED.
  
  
 12. SATISFIED. ADJUST LOCATIONS OF UTILITY LINES ON THE
 LANDSCAPE PLAN INCLUDING WATER AND SEWER TO RESOLVE
 CONFLICTS WITH EXISTING LANDSCAPING. SHOW LOCATIONS OF
 ALL ROOT BARRIERS PROPOSED.
 SOME LOCATIONS ADJUSTED, BUT OTHERS STILL IN CONFLICT.
 ROOT BARRIER LOCATIONS DO NOT MEET CITY STANDARD OF 5
 FEET SEPARATION FROM LINE. TREE OR PALM IS THEN LOCATED
 TO ALLOW PROPER ROOT ZONE TO DEVELOP.
  
  
 ADDITIONAL COMMENTS 9/23/22:
  
 13. SATISFIED. SIZES OF ALL TREES MUST BE 12 FEET
 HEIGHT, FLORIDA GRADE #1 AS REQUIRED BY SECTION
 94-445(4)A.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 09-23-2022 Cont ID  
Sent By rcaranci Date 09-23-2022 Time 16:49 Rev Time 0.00
Received By rcaranci Date 09-23-2022 Time 16:49 Sent To  
Notes
2022-09-23 16:50:02FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: GAINES PARK Z22060027
 SEPTEMBER 23, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. CITY POLICY 10-2 PREFERS THE USE OF
 FLORIDA NATIVE PLANTS WHERE POSSIBLE.
  
 2. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE
 TREES AND PALMS IN GOOD CONDITION TO BE PRESERVED ON
 SITE OR RELOCATED. PROVIDE AN ARBORISTS REPORT RATING
 THE CONDITION AND RELOCATION POTENTIAL FOR THE NATIVE
 TREES AND PALMS. THERE ARE LIVE OAKS, SABAL PALMS, AND
 ROYAL PALMS THAT ARE INDICATED TO BE REMOVED. AN
 ACCURATE EVALUATION MUST BE PROVIDED AS TO CONDITION
 AND WHY THESE TREES CANNOT BE RELOCATED.
 7 SABAL PALMS ARE TO BE RELOCATED.
  
  
 3. PARTIALLY SATISFIED. REVISE SHEETS TD-1 AND TD-2 TO
 REFLECT CHANGES TO THE DISPOSITION CHART ON SHEET TD-3.
 THERE ARE DISCREPANCIES BETWEEN THE DISPOSITION CHART
 AND THE DISPOSITION PLAN.
  
 4. PARTIALLY SATISFIED. PROVIDE THE MITIGATION SQUARE
 FOOTAGE DUE FOR TREES AND PALMS TO BE REMOVED AND
 PROVIDE THE MITIGATION SQUARE FOOTAGE CREDIT BASED ON
 THE PLANT LIST.
 THERE ARE DISCREPANCIES IN THE MITIGATION CHART.
  
 5. PARTIALLY SATISFIED. LIVE OAKS 5504 AND 5505 HAVE A
 DRAINAGE LINE PROPOSED THAT WILL BE IN CONFLICT WITH
 THE ROOT SYSTEMS OF THE TREES. REDESIGN TO AVOID
 DAMAGING THE ROOT SYSTEM OF THE TREES TO REMAIN.
 DRAINAGE LINE LOCATIONS HAVE BEEN MODIFIED, BUT STILL
 CUT THROUGH THE CRITICAL ROOT ZONE OF EACH TREE. IF
 OPEN TRENCH IS USED FOR INSTALLATION, THEY WILL BE TOO
 CLOSE TO THE TREES.
  
 6. PARTIALLY SATISFIED. DRAINAGE LINES PROPOSED ON THE
 SOUTH SIDE OF THE ENTRANCE ARE ALSO IN CONFLICT WITH
 PROPOSED TREES AND PALMS AND EXISTING ROYAL PALMS.
 ROYAL PALM SOUTH OF ENTRANCE IS STILL IN CONFLICT.
  
 7. SATISFIED. USE CLEAR SYMBOLS ON THE PLANS TO
 REPRESENT TREES AND PALMS TO REMAIN.
  
 8. SATISFIED. ADD COLUMN FOR DROUGHT TOLERANCE TO THE
 PLANT LIST.
  
 9. PARTIALLY SATISFIED. PER SECTION 94-443(G) PROVIDE
 THE FLORIDA FRIENDLY LANDSCAPE REQUIREMENTS DESIGN
 OPTIONS IN A CHART MEETING THE 50 REQUIRED POINTS.
 CHART WAS ADDED, BUT INCORRECT AND DUPLICATE OPTION
 POINTS ARE INDICATED. REVISE.
  
 10. NOT SATISFIED. PROVIDE A SECTION IN A LANDSCAPE
 DATA CHART TO COMPLY WITH SECTION 94-445 L. PLANT
 SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL
 ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT
 SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF
 SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA
 WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA
 LANDSCAPES. PROVIDE THE TOTAL PERCENTAGE OF NATIVE AND
 DROUGHT TOLERANT PLANTS BASED ON THE FINAL PLANT LIST.
 PERCENTAGE COULD NOT BE LOCATED ON THE PLANS. BEST IF
 PLACED ON THE PLANT LIST SHEET.
  
 11. PARTIALLY SATISFIED. PER SECTION 94-443 (E)2.,
 PROVIDE THE 30% FOUNDATION PLANTING CALCULATION
 REQUIRED AND PROVIDED FOR EACH BUILDING.
 PROVIDED THE LENGTHS BUT PROVIDED LENGTHS DO NOT MAKE
 SENSE. PROVIDE THE TOTAL FOUNDATION LENGTH FOR EACH
 BUILDING AND THE LINEAR FOOTAGE OF LANDSCAPE PROVIDED.
  
  
 12. PARTIALLY SATISFIED. ADJUST LOCATIONS OF UTILITY
 LINES ON THE LANDSCAPE PLAN INCLUDING WATER AND SEWER
 TO RESOLVE CONFLICTS WITH EXISTING LANDSCAPING. SHOW
 LOCATIONS OF ALL ROOT BARRIERS PROPOSED.
 SOME LOCATIONS ADJUSTED, BUT OTHERS STILL IN CONFLICT.
 ROOT BARRIER LOCATIONS DO NOT MEET CITY STANDARD OF 5
 FEET SEPARATION FROM LINE. TREE OR PALM IS THEN LOCATED
 TO ALLOW PROPER ROOT ZONE TO DEVELOP.
  
  
 ADDITIONAL COMMENTS 9/23/22:
  
 13. SIZES OF ALL TREES MUST BE 12 FEET HEIGHT, FLORIDA
 GRADE #1 AS REQUIRED BY SECTION 94-445(4)A.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 07-11-2022 Cont ID  
Sent By rcaranci Date 07-11-2022 Time 16:26 Rev Time 0.00
Received By rcaranci Date 07-11-2022 Time 16:26 Sent To  
Notes
2022-07-11 16:27:13FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: GAINES PARK CONCESSION Z22060027
 JULY 11, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. CITY POLICY 10-2 PREFERS THE USE OF FLORIDA NATIVE
 PLANTS WHERE POSSIBLE.
  
 2. SECTION 94-448 (D)(3) REQUIRES NATIVE TREES AND
 PALMS IN GOOD CONDITION TO BE PRESERVED ON SITE OR
 RELOCATED. PROVIDE AN ARBORISTS REPORT RATING THE
 CONDITION AND RELOCATION POTENTIAL FOR THE NATIVE TREES
 AND PALMS. THERE ARE LIVE OAKS, SABAL PALMS, AND ROYAL
 PALMS THAT ARE INDICATED TO BE REMOVED. AN ACCURATE
 EVALUATION MUST BE PROVIDED AS TO CONDITION AND WHY
 THESE TREES CANNOT BE RELOCATED.
  
 3. REVISE SHEETS TD-1 AND TD-2 TO REFLECT CHANGES TO
 THE DISPOSITION CHART ON SHEET TD-3.
  
 4. PROVIDE THE MITIGATION SQUARE FOOTAGE DUE FOR TREES
 AND PALMS TO BE REMOVED AND PROVIDE THE MITIGATION
 SQUARE FOOTAGE CREDIT BASED ON THE PLANT LIST.
  
 5. LIVE OAKS 5504 AND 5505 HAVE A DRAINAGE LINE
 PROPOSED THAT WILL BE IN CONFLICT WITH THE ROOT SYSTEMS
 OF THE TREES. REDESIGN TO AVOID DAMAGING THE ROOT
 SYSTEM OF THE TREES TO REMAIN.
  
 6. DRAINAGE LINES PROPOSED ON THE SOUTH SIDE OF THE
 ENTRANCE ARE ALSO IN CONFLICT WITH PROPOSED TREES AND
 PALMS AND EXISTING ROYAL PALMS
  
 7. USE CLEAR SYMBOLS ON THE PLANS TO REPRESENT TREES
 AND PALMS TO REMAIN.
  
 8. ADD COLUMN FOR DROUGHT TOLERANCE TO THE PLANT LIST.
  
 9. PER SECTION 94-443(G) PROVIDE THE FLORIDA FRIENDLY
 LANDSCAPE REQUIREMENTS DESIGN OPTIONS IN A CHART
 MEETING THE 50 REQUIRED POINTS.
  
 10. PROVIDE A SECTION IN A LANDSCAPE DATA CHART TO
 COMPLY WITH SECTION 94-445 L. PLANT SPECIES. A MINIMUM
 OF 60 PERCENT OF PLANT MATERIAL ADDED SHALL BE FLORIDA
 NATIVE OR DROUGHT TOLERANT SPECIES SELECTED FROM THE
 CITY LIST OR THE LIST OF SPECIES IN THE MOST RECENT
 EDITION OF SOUTH FLORIDA WATER MANAGEMENT DISTRICT
 WATERWISE SOUTH FLORIDA LANDSCAPES. PROVIDE THE TOTAL
 PERCENTAGE OF NATIVE AND DROUGHT TOLERANT PLANTS BASED
 ON THE FINAL PLANT LIST.
  
 11. PER SECTION 94-443 (E)2., PROVIDE THE 30%
 FOUNDATION PLANTING CALCULATION REQUIRED AND PROVIDED
 FOR EACH BUILDING.
  
 12. ADJUST LOCATIONS OF UTILITY LINES ON THE LANDSCAPE
 PLAN INCLUDING WATER AND SEWER TO RESOLVE CONFLICTS
 WITH EXISTING LANDSCAPING. SHOW LOCATIONS OF ALL ROOT
 BARRIERS PROPOSED.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PU PUBLIC UTILITIES
Rev No 2 Status P Date 10-17-2022 Cont ID  
Sent By mtechnow Date 10-17-2022 Time 12:31 Rev Time 0.00
Received By mtechnow Date 10-17-2022 Time 12:31 Sent To  
Notes
***NONE***

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status F Date 07-14-2022 Cont ID  
Sent By mtechnow Date 07-14-2022 Time 11:01 Rev Time 0.00
Received By mtechnow Date 07-14-2022 Time 10:59 Sent To  
Notes
2022-07-14 11:00:57-PLEASE SHOW THE EXISTING MAIN SIZE/TYPE AND PROVIDE
 LOS CALCULATIONS.
 -ADD NOTE THIS IS WITHIN LS 46 SERVICE AREA.
  
 MIKE TECHNOW [email protected] 561-494-1047

Review Stop PU-CS PUBLIC UTILITIES CUSTOMER SRVC
Rev No 3 Status P Date 10-30-2022 Cont ID  
Sent By mhurley Date 10-30-2022 Time 09:01 Rev Time 0.00
Received By mhurley Date   Time   Sent To  
Notes
2022-10-30 09:00:58THE FIRELINE AND DDCV PROPOSED WORK IS STILL UNCLEAR
 AFTER READING PRIOR RESPONSES AND LOOKING AT REVISED
 PLANS. AT ENGINEERING DEVELOPMENT SUBMITTAL PLEASE MAKE
 MORE CLEAR IF INTENDING TO REMOVE EXISTING FIRELINE
 WATER SERVICE AND DDCV AT SOUTHWEST AREA OF BUILDING.
 IF NOT, UTILITY DESIGN MAY NEED TO BE REVISED.
  
 RESPECTFULLY,
 MARK HURLEY [email protected]

Review Stop PU-CS PUBLIC UTILITIES CUSTOMER SRVC
Rev No 2 Status F Date 09-20-2022 Cont ID  
Sent By mhurley Date 09-20-2022 Time 08:11 Rev Time 0.00
Received By mhurley Date   Time   Sent To  
Notes
2022-09-20 08:11:38PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING:
 -SHEET UT1: IS LEADER LINE FOR PROPOSED FIRE SERVICE
 POINTED CORRECTLY?
 -EXISTING WATER MAIN INFRASTRUCTURE DOES NOT APPEAR TO
 BE ABLE TO FACILITATE AN ADDITIONAL LARGE DIAMETER FIRE
 SERVICE. THE NEARBY WATER MAIN IS SHOWING AS 6 INCH AND
 IS NOT LOOPED PER WPB GIS. THERE IS ALREADY A 6 INCH
 FIRE SERVICE, MULTIPLE METERS, AND A COUPLE FIRE
 HYDRANTS, AS WELL AS ADDITIONAL PROPOSED METERS.
 -SHEET UT2: SHOW ANY EXISTING OR PROPOSED HARDSCAPE
 NEAR PROPOSED 1.5 INCH METER AND BACKFLOW. NEED
 VERIFICATION THAT METER AND BACKFLOW WILL BE IN
 LANDSCAPE INSTEAD OF HARDSCAPE AND NOT IN PEDESTRIAN
 TRAFFIC.
 -COULD NOT FIND ANY FDC ON UT1. SHOW AND LABEL IF ANY
 ARE NEEDED OR REQUIRED.
 RESPECTFULLY,
 MARK HURLEY [email protected]

Review Stop PU-CS PUBLIC UTILITIES CUSTOMER SRVC
Rev No 1 Status F Date 07-08-2022 Cont ID  
Sent By mhurley Date 07-08-2022 Time 15:30 Rev Time 0.00
Received By mhurley Date 07-08-2022 Time 15:28 Sent To  
Notes
2022-07-08 15:29:25-ON UTILITY PLAN UT1: SHOW AND LABEL WASTEWATER PUMP
 STATION NO. 29
 -ON UTILITY PLANS: SHOW AND LABEL ALL EXISTING WATER
 SERVICES LINES, WATER METERS, WATER METER BOXES, SEWER
 LATERAL CLEANOUTS, MANHOLES, AND BACKFLOW ASSEMBLIES AS
 SOME ARE MISSING.
 -ON SHEET UT1 NEAR NE AREA OF BUILDING THERE IS A DDCV
 LABELED. THE 3 INCH BACKFLOW ASSEMBLY IS NOT A DDCV
 TYPE AND APPEARS TO BE A DOMESTIC WATER RP CONNECTED TO
 2 INCH METER ADJACENT. NOTES IN SYSTEM SAY THE BACKFLOW
 VALVE IS TURNED OFF AND IN DISREPAIR. PLAN DESIGNER
 NEEDS TO INVESTIGATE FURTHER WHAT IT CURRENTLY SERVES
 AND IF IT IS NEEDED.
 -CONSIDER REPLACING ANY NON LEAD-FREE BACKFLOW
 ASSEMBLIES FOR WATER SERVICES THAT WILL BE USED FOR
 FOOD SERVICE OR DRINKING FOUNTAINS.
 -THERE IS FIRELINE DDCV NOT LABELED ON UT1 NEAR
 SOUTHWEST AREA OF SHEET UT1. IT ALSO HAS A LEAKING OSY
 VALVE THAT NEEDS REPAIR.
 -LABEL FIRE HYDRANTS AND ADD THE SYMBOL TO LEGEND.
 THERE IS A FIRE HYDRANT THAT IS NOT SHOWN ON UT1 NEAR
 THE SOUTHWEST DDCV. PLEASE SHOW AND LABEL ON UT1. CAN
 EXPAND AREA OR ADD MATCHLINE AND SEPARATE SHEET IF
 NEEDED.
 -VERIFY EXISTING PUMPING STATION AND FORCE MAIN ARE
 SUFFICIENT FOR ANY INCREASED SEWER DEMAND.
 -SHEET UT1: FOR THE SEWER LATERALS THAT ARE BEING
 REMOVED, IS THE SEWER PLUMBING BEING REROUTED INSIDE
 THE BUILDING TO THE NORTHEAST END OF THE BUILDING?
 -REVIEW THE CALLOUTS, LABELS, AND LEADER LINES FOR THE
 SANITARY SEWER WORK NEAR NORTHEAST AREA OF UT1. THEY
 MAY BE POINTED OR LABELED INCORRECTLY.
 -VERIFY EXISTING METERED WATER SERVICES WILL BE
 SUFFICIENT FOR ANY INCREASED WATER DEMAND.
 -IF THERE ARE ANY HOSE BIBS FOR PUMP STATION
 MAINTENANCE, RECOMMEND VERIFYING THEY HAVE ADEQUATE
 BACKFLOW PROTECTION.
 -SHEET UT2: ADD SIZING OF PROPOSED METER; ADD SIZING OF
 PROPOSED BACKFLOW ASSEMBLY; ADD RP TO LABEL OF PROPOSED
 BACKFLOW ASSEMBLY. SHOW HARDSCAPE NEAR PROPOSED METER
 AND BACKFLOW ASSEMBLY AND ENSURE LOCATION OF METER AND
 BACKFLOW WILL BE IN LANDSCAPING; SHOW EXISTING LARGE
 UTILITY BOX BETWEEN WATER FOUNTAIN AND EXISTING
 BACKFLOW ASSEMBLY FOR COURTS; SHOW EXISTING WATER LINES
 FOR WATER FOUNTAIN AND TENNIS COURT BACKFLOW ASSEMBLY
 AND WHAT IS HAPPENING TO THEM. ALSO ENSURE THOSE WATER
 LINES ARE DOWNSTREAM OF A WATER METER.
 -SHEET UT3: ENSURE ALL SYMBOLS AND ABBREVIATIONS ARE ON
 SHEET LEGEND.
 -CANNOT FIND DEMO PLAN SHEET. PLEASE ADD TO PLAN SET.
 -UT1 DOES NOT SHOW SIZE OF EXISTING GAS SERVICE NEAR
 SOUTH SIDE. IS IT SUFFICIENT?
 -SHEET UT2: SHOW AND LABEL 42 INCH FORCE MAIN.
 -SHOW RAISED ELEVATION AREA NEAR POOL ON PGD1.
 -ADD WPB STANDARD DETAILS TO CIVIL DETAILS SHEETS FOR:
 FIRE HYDRANT, SMALL METERED WATER SERVICE, FIRELINE
 DETECTOR BACKFLOW, SMALL BACKFLOW ASSEMBLY, LARGE
 BACKFLOW ASSEMBLY.

Review Stop PW PUBLIC WORKS
Rev No 3 Status P Date 10-31-2022 Cont ID  
Sent By   Date 10-31-2022 Time   Rev Time 0.00
Received By   Date 10-31-2022 Time   Sent To  
Notes
2022-10-31 12:14:35CONDITIONS OF APPROVAL:
 1- SHALL SUBMIT A PERMIT FOR THE DUMPSTER ENCLOSURE.
 FOR A FREESTANDING SITE DUMPSTER ENCLOSURE, THE
 ENCLOSURE SHALL COMPLY WITH THE LATEST REVISION OF CITY
 OF WEST PALM BEACH GENERAL CONSTRUCTION-GARBAGE
 ENCLOSURE STANDARD, GC-7. (LINK TO THE LATEST REVISION
 OF THE GC-7 DOCUMENT: HTTPS://WWW.WPB.ORG/HOME/SHOWPUBL
 ISHEDDOCUMENT/3690/637629060422100000)
 2- THE LOCATION AND ORIENTATION OF THE ENCLOSURE TO BE
 DETERMINED BY PUBLIC WORKS.
  
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]

Review Stop PW PUBLIC WORKS
Rev No 2 Status P Date 09-19-2022 Cont ID  
Sent By   Date 09-19-2022 Time   Rev Time 0.00
Received By   Date 09-19-2022 Time   Sent To  
Notes
2022-09-19 11:45:51CONDITIONS OF APPROVAL:
 1- SHALL SUBMIT A PERMIT FOR THE DUMPSTER ENCLOSURE.
 FOR A FREESTANDING SITE DUMPSTER ENCLOSURE, THE
 ENCLOSURE SHALL COMPLY WITH THE LATEST REVISION OF CITY
 OF WEST PALM BEACH GENERAL CONSTRUCTION-GARBAGE
 ENCLOSURE STANDARD, GC-7. (LINK TO THE LATEST REVISION
 OF THE GC-7 DOCUMENT: HTTPS://WWW.WPB.ORG/HOME/SHOWPUBL
 ISHEDDOCUMENT/3690/637629060422100000)
 2- THE LOCATION AND ORIENTATION OF THE ENCLOSURE TO BE
 DETERMINED BY PUBLIC WORKS.
  
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]

Review Stop PW PUBLIC WORKS
Rev No 1 Status P Date 07-07-2022 Cont ID  
Sent By   Date 07-07-2022 Time   Rev Time  
Received By   Date 07-07-2022 Time   Sent To  
Notes
2022-07-07 08:45:12CONDITIONS OF APPROVAL:
 1- SHALL SUBMIT A PERMIT FOR THE DUMPSTER ENCLOSURE.
 FOR A FREESTANDING SITE DUMPSTER ENCLOSURE, THE
 ENCLOSURE SHALL COMPLY WITH THE LATEST REVISION OF CITY
 OF WEST PALM BEACH GENERAL CONSTRUCTION-GARBAGE
 ENCLOSURE STANDARD, GC-7. (LINK TO THE LATEST REVISION
 OF THE GC-7 DOCUMENT: HTTPS://WWW.WPB.ORG/HOME/SHOWPUBL
 ISHEDDOCUMENT/3690/637629060422100000)
 2- THE LOCATION AND ORIENTATION OF THE ENCLOSURE TO BE
 DETERMINED BY PUBLIC WORKS.
  
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]

Review Stop STORM STORMWATER
Rev No 2 Status P Date 09-29-2022 Cont ID  
Sent By tward Date 09-29-2022 Time 16:11 Rev Time 0.00
Received By tward Date 09-29-2022 Time 16:16 Sent To  
Notes
2022-09-29 16:16:29THE FOLLOWING COMMENT IS FROM THE REVIEW OF THE
 9/14/2022 RRESUBMITTAL:
  
 1. THE PARK DRAINAGE SYSTEM DISCAHRGES INTO THE GAINES
 PARK CANAL WHICH FLOWS INTO THE CARVER CANAL. BOTH THE
 CARVER CANAL AND GAINES PARK CANAL ARE AT THEIR MAXIMUM
 CAPACITY FOR THE 25-YEAR 1-DAY DESIGN STORM. ANY
 ADDITIONAL RUNOFF VOLUME FOR THIS DESIGN STORM,
 GENERATED BY THIS PROJECT, WILL NEED TO BE STORED
 ONSITE.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 [email protected]
  

Review Stop STORM STORMWATER
Rev No 1 Status F Date 07-14-2022 Cont ID  
Sent By tward Date 07-14-2022 Time 08:58 Rev Time 0.00
Received By tward Date 07-14-2022 Time 08:59 Sent To  
Notes
2022-07-14 08:59:38THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. THE CITY?S OFFICIAL VERTICAL DATUM IS NGVD1929. THE
 CITY HAS ALLOWED THE USE OF NAVD1988 AS LONG AS THE
 CONVERSION EQUATION TO NGVD1929 AT THE PROJECT LOCATION
 IS PROVIDED. PROVIDE VERTICAL DATUM REFERENCE AND
 CONVERSION TO NGVD1929 ON EVERY SHEET WITH ELEVATION
 INFORMATION (NEEDED ON SHEETS SP-1 AND SP-2).
  
 2. WILL BOLLARDS BE LOCATED ALONG THE BACK OF THE
 FLUSHED CONCRETE CURB EAST OF THE NEW COMMUNITY CENTER?
  
 3. REPLACE ANY VCP DRAINAGE PIPES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP
 CRITERIA. STORMWATER CALCULATIONS WILL BE REVIEWED WITH
 THE ENGINEERING PERMIT SUBMITTAL.
  
 2. PROVIDE COPY OF SFWMD ERP PERMIT MODIFICATION BEFORE
 START OF CONSTRUCTION.
  
 3. PROVIDE EROSION AND SEDIMENT CONTROL PLAN WITH THE
 ENGINEERING PERMIT SUBMITTAL.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 10-13-2022 Cont ID  
Sent By vnoel Date 10-13-2022 Time 14:36 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2022-10-13 14:37:48SURVEY HAS NOTE THAT AS OF 6/10 22 THAT FIELDWORK WAS
 STILL ONGOING. IF COMPLETED, PROVIDE SURVEY WITH NOTE
 REMOVED.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 07-05-2022 Cont ID  
Sent By vnoel Date 07-05-2022 Time 10:49 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2022-07-05 11:06:581. SURVEY SHOULD BE SIGNED AND SEALED WHEN COMPLETED.
 2. ADD CONVERSION TO NGVD-29 TO ALL PLANS.
 3. IS THE WESTERLY PORTION OF THE EXISTING FACILITY
 REMAINING?

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status P Date 10-12-2022 Cont ID  
Sent By   Date 10-12-2022 Time   Rev Time 0.00
Received By   Date 10-12-2022 Time   Sent To  
Notes
2022-10-12 00:24:23NO FURTHER COMMENTS.
  
 1) SATISFIED. IDENTIFY AND DESIGNATE AN EASILY
 ACCESSIBLE MICRO-MOBILITY STATION AREA (MINIMUM 8 X 20
 FEET) NEARBY THE MAIN BUILDING ENTRANCE AND PROVIDE
 BASIC ELECTRIFICATION READINESS. MORE SPECIFICS ABOUT
 ELECTRIFICATION: A CONDUIT (2 INCH SCHEDULE 40 PVC) TO
 THE POWER SOURCE WITH AN ELECTRICAL PULL BOX (240V ???
 10,000W CIRCUIT). PLEASE HIGHLIGHT OR CALLOUT THE TWO
 EXISTING MICROMOBILITY STATIONS AND PROVIDE DOCUMENT
 NAME AND SHEET NUMBER SHOWCASING THEM.
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 07-08-2022 Cont ID  
Sent By   Date 07-08-2022 Time   Rev Time  
Received By   Date 07-08-2022 Time   Sent To  
Notes
2022-07-08 13:27:191) IDENTIFY AND DESIGNATE AN EASILY ACCESSIBLE
 MICRO-MOBILITY STATION AREA (MINIMUM 8 X 20 FEET)
 NEARBY THE MAIN BUILDING ENTRANCE AND PROVIDE BASIC
 ELECTRIFICATION READINESS. MORE SPECIFICS ABOUT
 ELECTRIFICATION: A CONDUIT (2? SCHEDULE 40 PVC) TO THE
 POWER SOURCE WITH AN ELECTRICAL PULL BOX (240V ?
 10,000W CIRCUIT). PLEASE PROVIDE DOCUMENT NAME AND
 SHEET NUMBER SHOWCASING SUCH FEATURE.
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status P Date 12-12-2022 Cont ID  
Sent By kdefranc Date 12-12-2022 Time 08:19 Rev Time 0.00
Received By kdefranc Date 12-12-2022 Time 08:15 Sent To  
Notes
2022-12-12 08:18:4812/12/22 ??? PASSED
  
  
 PREVIOUS REVIEW COMMENTS:
 PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN
 RESUBMITTING:
 A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
 B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED
 MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG
 WITH ONE (1) REDUCED COPY (11 IN X 17 IN).
 C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
 D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
 E. PLEASE NOTE THAT YOU ARE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. A RESUBMITTAL FEE OF
 20% OF THE ORIGINAL APPLICATION FEE WILL BE ASSESSED
 AFTER THE FIRST RESUBMITTAL.
  
 REQUIRED MATERIALS MUST BE PROVIDED:
 F. PLEASE PROVIDE LETTERS FROM PUBLIC UTILITIES
 (FLORIDA PUBLIC UTILITIES, FLORIDA POWER & LIGHT
 COMPANY, AND COMCAST CABLE COMMUNICATIONS) CONFIRMING
 THAT THE PROPOSED PROJECT DOES NOT ENCROACH INTO THEIR
 EASEMENTS OR OTHERWISE INTERFERE WITH THE PROVISIONS OF
 THEIR SERVICES. [SATISFIED PER PLANNING AND ZONING
 ADMINISTRATOR, ANGELLA JONES-VANN???S DIRECTION]
 G. PLEASE PROVIDE A TRAFFIC CONCURRENCY/PERFORMANCE
 STANDARD REVIEW (TPS) LETTER FROM THE PALM BEACH COUNTY
 TRAFFIC DIVISION FOR THE SUBJECT PROJECT. [SATISFIED]
 H. PLEASE PROVIDE REVISED PLANS ADDRESSING THE REVIEW
 COMMENTS BELOW. [PARTIALLY SATISFIED]
 I. PLEASE PROVIDE/INDICATE/DEMONSTRATE CONSISTENT
 INFORMATION ON ALL THE DIFFERENT PLANS AND REQUIRED
 MATERIALS WITHIN THE APPLICATION PACKET RESUBMITTAL.
 [SATISFIED]
  
 PLANS REVIEW COMMENTS MUST BE ADDRESSED:
 1. PLEASE PROVIDE A SITE PLAN OF THE ENTIRE GAINES PARK
 SITE/PROPERTY IDENTIFYING/INDICATING/DEMONSTRATING WHAT
 IS EXISTING AND PROPOSED AND DELINEATE/HIGHLIGHT/CLOUD
 THE AREAS OF THE PARK WHERE THE PROPOSED CHANGES ARE
 LOCATED. [SATISFIED]
 2. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF
 THE EXISTING PROPERTY LINE, EASEMENTS, AND WATER
 COURSES ON ALL THE DIFFERENT PLANS, ACCORDINGLY.
 [SATISFIED]
 3. PLEASE IDENTIFY ANY AREA OF THE SITE SUBJECT TO
 FLOODING OR HIGH GROUND WATER LEVEL ON ALL THE
 DIFFERENT PLANS, ACCORDINGLY. [SATISFIED]
 4. PLEASE PROVIDE A SCHEMATIC OF THE DRAINAGE SYSTEM ON
 ALL THE DIFFERENT PLANS, ACCORDINGLY. [SATISFIED]
 5. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 AND EXTENT OF ANY WETLANDS ON THE PROPERTY ON ALL THE
 DIFFERENT PLANS, ACCORDINGLY. [SATISFIED]
 6. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF
 EXISTING RIGHT-OF-WAY, STREETS, DRIVEWAYS,
 INTERSECTIONS, CURB CUTS AND TURNING LANES ON ALL THE
 DIFFERENT PLANS, ACCORDINGLY. [SATISFIED]
 7. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 AND DIMENSIONS OF ALL SIDEWALKS, FENCES, WALLS, AND
 BERMS ON ALL THE DIFFERENT PLANS, ACCORDINGLY.
 [SATISFIED]
 8. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LAYOUT AND
 LOCATION OF ALL OFF-STREET PARKING, DISABLED PARKING
 SPACES/RAMPS/SIGNS, BICYCLE PARKING, AND OTHER
 VEHICULAR USE AREAS ON ALL THE DIFFERENT PLANS,
 ACCORDINGLY. [SATISFIED]
 9. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE OUTLINES OF
 ALL BUILDINGS WITH USES, SETBACKS, DIMENSIONS, FLOOR
 AREA, NUMBER OF STORIES, HEIGHT AND POINTS OF ACCESS ON
 ALL THE DIFFERENT PLANS, ACCORDINGLY. [SATISFIED]
 10. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION,
 HEIGHT, AND SIZE OF ALL FREESTANDING SIGNS AND OTHER
 ACCESSORY STRUCTURES ON ALL THE DIFFERENT PLANS,
 ACCORDINGLY. [SATISFIED]
 11. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION,
 HEIGHT AND INTENSITY OF ALL OUTDOOR ILLUMINATION ON ALL
 THE DIFFERENT PLANS, ACCORDINGLY. [SATISFIED]
 12. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 OF EXISTING/PROPOSED FIRE HYDRANTS (OR OPERATIONAL
 EQUIVALENTS) WITHIN 250 FEET OF THE PROPOSED STRUCTURES
 ON ALL THE DIFFERENT PLANS, ACCORDINGLY. [SATISFIED]
 13. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 OF ANY SPECIAL UTILITY STRUCTURES SUCH AS VALVES,
 METERS, BACKFLOW CONNECTIONS, PUMP STATIONS,
 TRANSFORMERS, AND ALL ABOVE GROUND APPURTENANCES ON ALL
 THE DIFFERENT PLANS, ACCORDINGLY. [SATISFIED]
 14. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 AND SCREENING OF ALL GARBAGE RECEPTACLES ON ALL THE
 DIFFERENT PLANS, ACCORDINGLY. [SATISFIED]
 15. IN ACCORDANCE WITH THE AIPP REVIEW COMMENTS, PLEASE
 IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF ALL
 PUBLIC ART (AS PART OF THE CITY???S ARTLIFE REQUIREMENT
 CHAPTER 78, ARTICLE V OF THE CITY???S CODE OF
 ORDINANCES) ON ALL THE DIFFERENT PLANS, ACCORDINGLY.
 [SATISFIED]
 16. PLEASE PROVIDE THE STANDARD CITY DETAILS OF
 VEHICLE/BICYCLE PARKING (STANDARD AND ADA), ADA RAMPS,
 DRIVEWAYS, DUMPSTERS AND SIGNS ON SHEETS SP-3 OR SP-4.
 THE PROPOSED BIKE RACK DEMONSTRATED ON SHEET SP-3 IS
 NOT ALLOWED, THEREFORE, PLEASE REVISE ACCORDINGLY.
 [SATISFIED]
 17. PLEASE IDENTIFY/INDICATE THE TOTAL ACREAGE/SQUARE
 FOOTAGE AND PERCENTAGE OF WATER BODIES, OPEN SPACE,
 LANDSCAPING, IMPERMEABLE SURFACE AREA, AND BUILDING
 COVERAGE; TOTAL GROSS BUILDING SQUARE FOOTAGE; TOTAL
 FLOOR AREA RATIO; AND VEHICLE/BICYCLE PARKING
 COMPUTATION (REQUIRED, PROVIDED, ETC.) IN THE SITE DATA
 TABLE ON SHEET SP-1. [SATISFIED]
  
 ADDITIONAL REVIEW COMMENTS MUST BE ADDRESSED:
 18. PLEASE PROVIDE A SIGNED LETTER FROM THE FLORIDA
 POWER & LIGHT COMPANY AND FLORIDA PUBLIC UTILITIES.
 [SATISFIED PER PLANNING AND ZONING ADMINISTRATOR,
 ANGELLA JONES-VANN???S DIRECTION]
 19. PLEASE PROVIDE RECORD/ACCOUNT OF THE PALM BEACH
 COUNTY TRAFFIC DIVISION RECEIVING/ACKNOWLEDGING THE
 SITE PLAN WITH THE PROPOSED IMPROVEMENTS AND/OR
 CONSISTENT INFORMATION REFLECTING THE COMMUNITY CENTER
 BUILDING INCREASING IN SIZE AND THE NEW TENNIS CENTER
 BUILDING ASSOCIATED WITH THE TPS LETTER SUBMITTED.
 [SATISFIED]
 20. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE INTENSITY
 OF THE PROPOSED OUTDOOR ILLUMINATION TO THE PARK???S
 PROPERTY LINES ON THE ???COMMUNITY CNETER LIGHTING
 PLAN??? DRAWING NUMBER LT-1 OF 36 AND ???TENNIS CNETER
 LIGHTING PLAN??? DRAWING NUMBER LT-2 OF 36. [SATISFIED]
 21. PLEASE REMOVE THE ???POTENTIAL??? WORDING FROM THE
 LABEL INDICATING THE ???AREA FOR PROPOSED PUBLIC ART???
 ON THE ???OVERALL SITE PLAN??? DRAWING NUMBER OSP-1 OF
 32. [SATISFIED]
 22. PLEASE PROVIDE THE REQUIRED INFORMATION STATED IN
 PREVIOUS REVIEW COMMENT NUMBER 17 (REFLECTING THE
 EXISTING CONDITIONS AND PROPOSED CHANGES INFORMATION
 FOR THE ENTIRE GAINES PARK SITE/PROPERTY) AS WELL AS
 THE SETBACKS AND HEIGHTS INFORMATION IN THE ???SITE
 DATA??? TABLE ON THE ???COMMUNITY CENTER SITE PLAN???
 DRAWING NUMBER SP-1 OF 32. [SATISFIED]
 23. PLEASE IDENTIFY/INDICATE/LABEL THE BASEBALL FIELD
 BUILDING/CONCESSION STAND AND SHELTERS, WARREN HAWKINS
 AQUATIC CENTER BUILDING AND POOL DECK, MARY V. MCDONALD
 WILSON CENTER BUILDING AND OUTDOOR PLAZA, ISLAND
 PLAYGROUND, AND MISCELLANEOUS SHELTERS ON THE DRAWING
 NUMBER OSP-1. [SATISFIED]
 24. PLEASE CONFIRM IF THE PROPOSED COMMUNITY CENTER
 BUILDING IS ATTACHED/CONNECTED TO THE EXISTING BUILDING
 WEST OF IT. IF THEY ARE NOT ATTACHED/CONNECTED TO EACH
 OTHER, THEN PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE
 MINIMUM REQUIRED BUILDING SEPARATION DISTANCE DIMENSION
 BETWEEN THE BUILDINGS ACCORDING TO SUBSECTION
 94-204(2)(E) OF THE CITY???S ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR). [SATISFIED PER PLANNING
 AND ZONING ADMINISTRATOR, ANGELLA JONES-VANN???S
 DIRECTION]
 25. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE PROPERTY
 LINE ON THE DRAWING NUMBERS PGD-1, PGD-2, PGD-3, UT-1,
 UT-2, UT-3, TD-2, AND IRR-3. [SATISFIED]
 26. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE ANCHOR
 EASEMENT (IDENTIFIED ON PAGE 3 OF 7 OF THE SURVEY) ON
 THE DRAWING NUMBERS OSP-1, PGD-3, UT-3, LP-2, AND
 IRR-2. [SATISFIED]
 27. PLEASE CORRECT THE STREET LABEL ON THE DRAWING
 NUMBERS PGD-3 AND UT-3. [SATISFIED]
 28. PLEASE IDENTIFY/INDICATE/PROVIDE THE SAME LABEL (AS
 INDICATED ON THE DRAWING NUMBER LP-2 STATING
 ???EXISTING PLAYGROUND TO REMAIN TYP.???) ON THE
 DRAWING NUMBERS PGD-3, UT-3, AND IRR-2. [SATISFIED]
 29. PLEASE CONFIRM THE MAXIMUM HEIGHT PROPOSED OF 34
 FEET IS TO THE TOP OF THE ???CURVED STANDING SEAM METAL
 ROOF??? OF THE PROPOSED COMMUNITY CENTER (GYMNASIUM).
 IF THE MAXIMUM HEIGHT IS HIGHER, THEN PLEASE REVISE THE
 PLANS AND ELEVATIONS, ACCORDINGLY. [SATISFIED]
 30. PLEASE CORRECT THE REQUIRED PARKING INDICATION TO
 52 AND THE REQUIRED BICYCLE PARKING INDICATION TO 5 IN
 THE SITE DATA TABLE ON THE DRAWING NUMBER SP-1.
 [SATISFIED]
 31. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE STANDARD
 AND DISABLED PARKING STALL WIDTH AND DEPTH DIMENSIONS
 ACCORDING TO SECTION 94-485 OF THE ZLDR ON DRAWING
 NUMBER SP-1. [SATISFIED]
 32. THE PROPOSED BIKE RACK (WAVE TYPE) DEMONSTRATED ON
 SHEET SP-3 IS NOT ALLOWED, THEREFORE, PLEASE REVISE
 ACCORDINGLY. {NOTE: THE BIKE RACK (POST AND LOOP TYPE)
 DEMONSTRATED ON SHEET SP-3 OF YOUR FIRST RESUBMITTAL IS
 ALLOWED.} [SATISFIED]
 33. IT HAS BEEN IDENTIFIED THAT THE PROPOSED 12.5 FEET
 HIGH DIGITAL MARQUEE SIGN EXCEEDS THE MAXIMUM HEIGHT
 ALLOWED FOR FREESTANDING SIGNS WITHIN THE RECREATION
 AND OPEN SPACE ZONING DISTRICT ACCORDING TO SUBSECTION
 94-408(F), THEREFORE, PLEASE REVISE THE DIGITAL MARQUEE
 SIGN DETAIL ON SHEET A1.2.1, ACCORDINGLY. [SATISFIED]
 34. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE SETBACK
 DIMENSIONS FOR THE PROPOSED DIGITAL MARQUEE SIGN
 ACCORDING TO SUBSECTION 94-408(F) ON DRAWING NUMBER
 OSP-1. [SATISFIED]
  
  
 KEVIE DEFRANC
 SENIOR PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  

Review Stop Z ZONING
Rev No 3 Status F Date 11-15-2022 Cont ID  
Sent By kdefranc Date 11-15-2022 Time 20:06 Rev Time 0.00
Received By kdefranc Date 11-15-2022 Time 20:05 Sent To  
Notes
2022-11-15 20:05:5611/15/22 ??? FAILED
  
  
 PREVIOUS REVIEW COMMENTS:
 PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN
 RESUBMITTING:
 A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
 B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED
 MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG
 WITH ONE (1) REDUCED COPY (11 IN X 17 IN).
 C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
 D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
 E. PLEASE NOTE THAT YOU ARE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. A RESUBMITTAL FEE OF
 20% OF THE ORIGINAL APPLICATION FEE WILL BE ASSESSED
 AFTER THE FIRST RESUBMITTAL.
  
 REQUIRED MATERIALS MUST BE PROVIDED:
 F. PLEASE PROVIDE LETTERS FROM PUBLIC UTILITIES
 (FLORIDA PUBLIC UTILITIES, FLORIDA POWER & LIGHT
 COMPANY, AND COMCAST CABLE COMMUNICATIONS) CONFIRMING
 THAT THE PROPOSED PROJECT DOES NOT ENCROACH INTO THEIR
 EASEMENTS OR OTHERWISE INTERFERE WITH THE PROVISIONS OF
 THEIR SERVICES. [PARTIALLY SATISFIED]
 G. PLEASE PROVIDE A TRAFFIC CONCURRENCY/PERFORMANCE
 STANDARD REVIEW (TPS) LETTER FROM THE PALM BEACH COUNTY
 TRAFFIC DIVISION FOR THE SUBJECT PROJECT. [SATISFIED]
 H. PLEASE PROVIDE REVISED PLANS ADDRESSING THE REVIEW
 COMMENTS BELOW. [PARTIALLY SATISFIED]
 I. PLEASE PROVIDE/INDICATE/DEMONSTRATE CONSISTENT
 INFORMATION ON ALL THE DIFFERENT PLANS AND REQUIRED
 MATERIALS WITHIN THE APPLICATION PACKET RESUBMITTAL.
 [NOT SATISFIED]
  
 PLANS REVIEW COMMENTS MUST BE ADDRESSED:
 1. PLEASE PROVIDE A SITE PLAN OF THE ENTIRE GAINES PARK
 SITE/PROPERTY IDENTIFYING/INDICATING/DEMONSTRATING WHAT
 IS EXISTING AND PROPOSED AND DELINEATE/HIGHLIGHT/CLOUD
 THE AREAS OF THE PARK WHERE THE PROPOSED CHANGES ARE
 LOCATED. [PARTIALLY SATISFIED]
 2. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF
 THE EXISTING PROPERTY LINE, EASEMENTS, AND WATER
 COURSES ON ALL THE DIFFERENT PLANS, ACCORDINGLY.
 [PARTIALLY SATISFIED]
 3. PLEASE IDENTIFY ANY AREA OF THE SITE SUBJECT TO
 FLOODING OR HIGH GROUND WATER LEVEL ON ALL THE
 DIFFERENT PLANS, ACCORDINGLY. [SATISFIED]
 4. PLEASE PROVIDE A SCHEMATIC OF THE DRAINAGE SYSTEM ON
 ALL THE DIFFERENT PLANS, ACCORDINGLY. [SATISFIED]
 5. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 AND EXTENT OF ANY WETLANDS ON THE PROPERTY ON ALL THE
 DIFFERENT PLANS, ACCORDINGLY. [SATISFIED]
 6. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF
 EXISTING RIGHT-OF-WAY, STREETS, DRIVEWAYS,
 INTERSECTIONS, CURB CUTS AND TURNING LANES ON ALL THE
 DIFFERENT PLANS, ACCORDINGLY. [SATISFIED]
 7. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 AND DIMENSIONS OF ALL SIDEWALKS, FENCES, WALLS, AND
 BERMS ON ALL THE DIFFERENT PLANS, ACCORDINGLY.
 [SATISFIED]
 8. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LAYOUT AND
 LOCATION OF ALL OFF-STREET PARKING, DISABLED PARKING
 SPACES/RAMPS/SIGNS, BICYCLE PARKING, AND OTHER
 VEHICULAR USE AREAS ON ALL THE DIFFERENT PLANS,
 ACCORDINGLY. [PARTIALLY SATISFIED]
 9. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE OUTLINES OF
 ALL BUILDINGS WITH USES, SETBACKS, DIMENSIONS, FLOOR
 AREA, NUMBER OF STORIES, HEIGHT AND POINTS OF ACCESS ON
 ALL THE DIFFERENT PLANS, ACCORDINGLY. [PARTIALLY
 SATISFIED]
 10. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION,
 HEIGHT, AND SIZE OF ALL FREESTANDING SIGNS AND OTHER
 ACCESSORY STRUCTURES ON ALL THE DIFFERENT PLANS,
 ACCORDINGLY. [PARTIALLY SATISFIED]
 11. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION,
 HEIGHT AND INTENSITY OF ALL OUTDOOR ILLUMINATION ON ALL
 THE DIFFERENT PLANS, ACCORDINGLY. [SATISFIED]
 12. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 OF EXISTING/PROPOSED FIRE HYDRANTS (OR OPERATIONAL
 EQUIVALENTS) WITHIN 250 FEET OF THE PROPOSED STRUCTURES
 ON ALL THE DIFFERENT PLANS, ACCORDINGLY. [SATISFIED]
 13. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 OF ANY SPECIAL UTILITY STRUCTURES SUCH AS VALVES,
 METERS, BACKFLOW CONNECTIONS, PUMP STATIONS,
 TRANSFORMERS, AND ALL ABOVE GROUND APPURTENANCES ON ALL
 THE DIFFERENT PLANS, ACCORDINGLY. [SATISFIED]
 14. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 AND SCREENING OF ALL GARBAGE RECEPTACLES ON ALL THE
 DIFFERENT PLANS, ACCORDINGLY. [SATISFIED]
 15. IN ACCORDANCE WITH THE AIPP REVIEW COMMENTS, PLEASE
 IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF ALL
 PUBLIC ART (AS PART OF THE CITY???S ARTLIFE REQUIREMENT
 CHAPTER 78, ARTICLE V OF THE CITY???S CODE OF
 ORDINANCES) ON ALL THE DIFFERENT PLANS, ACCORDINGLY.
 [SATISFIED]
 16. PLEASE PROVIDE THE STANDARD CITY DETAILS OF
 VEHICLE/BICYCLE PARKING (STANDARD AND ADA), ADA RAMPS,
 DRIVEWAYS, DUMPSTERS AND SIGNS ON SHEETS SP-3 OR SP-4.
 THE PROPOSED BIKE RACK DEMONSTRATED ON SHEET SP-3 IS
 NOT ALLOWED, THEREFORE, PLEASE REVISE ACCORDINGLY.
 [PARTIALLY SATISFIED]
 17. PLEASE IDENTIFY/INDICATE THE TOTAL ACREAGE/SQUARE
 FOOTAGE AND PERCENTAGE OF WATER BODIES, OPEN SPACE,
 LANDSCAPING, IMPERMEABLE SURFACE AREA, AND BUILDING
 COVERAGE; TOTAL GROSS BUILDING SQUARE FOOTAGE; TOTAL
 FLOOR AREA RATIO; AND VEHICLE/BICYCLE PARKING
 COMPUTATION (REQUIRED, PROVIDED, ETC.) IN THE SITE DATA
 TABLE ON SHEET SP-1. [PARTIALLY SATISFIED]
  
 ADDITIONAL REVIEW COMMENTS MUST BE ADDRESSED:
 18. PLEASE PROVIDE A SIGNED LETTER FROM THE FLORIDA
 POWER & LIGHT COMPANY AND FLORIDA PUBLIC UTILITIES.
 [PARTIALLY SATISFIED]
 19. PLEASE PROVIDE RECORD/ACCOUNT OF THE PALM BEACH
 COUNTY TRAFFIC DIVISION RECEIVING/ACKNOWLEDGING THE
 SITE PLAN WITH THE PROPOSED IMPROVEMENTS AND/OR
 CONSISTENT INFORMATION REFLECTING THE COMMUNITY CENTER
 BUILDING INCREASING IN SIZE AND THE NEW TENNIS CENTER
 BUILDING ASSOCIATED WITH THE TPS LETTER SUBMITTED.
 [SATISFIED]
 20. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE INTENSITY
 OF THE PROPOSED OUTDOOR ILLUMINATION TO THE PARK???S
 PROPERTY LINES ON THE ???COMMUNITY CNETER LIGHTING
 PLAN??? DRAWING NUMBER LT-1 OF 36 AND ???TENNIS CNETER
 LIGHTING PLAN??? DRAWING NUMBER LT-2 OF 36. [SATISFIED]
 21. PLEASE REMOVE THE ???POTENTIAL??? WORDING FROM THE
 LABEL INDICATING THE ???AREA FOR PROPOSED PUBLIC ART???
 ON THE ???OVERALL SITE PLAN??? DRAWING NUMBER OSP-1 OF
 32. [SATISFIED]
 22. PLEASE PROVIDE THE REQUIRED INFORMATION STATED IN
 PREVIOUS REVIEW COMMENT NUMBER 17 (REFLECTING THE
 EXISTING CONDITIONS AND PROPOSED CHANGES INFORMATION
 FOR THE ENTIRE GAINES PARK SITE/PROPERTY) AS WELL AS
 THE SETBACKS AND HEIGHTS INFORMATION IN THE ???SITE
 DATA??? TABLE ON THE ???COMMUNITY CENTER SITE PLAN???
 DRAWING NUMBER SP-1 OF 32. [PARTIALLY SATISFIED]
 23. PLEASE IDENTIFY/INDICATE/LABEL THE BASEBALL FIELD
 BUILDING/CONCESSION STAND AND SHELTERS, WARREN HAWKINS
 AQUATIC CENTER BUILDING AND POOL DECK, MARY V. MCDONALD
 WILSON CENTER BUILDING AND OUTDOOR PLAZA, ISLAND
 PLAYGROUND, AND MISCELLANEOUS SHELTERS ON THE DRAWING
 NUMBER OSP-1.
 24. PLEASE CONFIRM IF THE PROPOSED COMMUNITY CENTER
 BUILDING IS ATTACHED/CONNECTED TO THE EXISTING BUILDING
 WEST OF IT. IF THEY ARE NOT ATTACHED/CONNECTED TO EACH
 OTHER, THEN PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE
 MINIMUM REQUIRED BUILDING SEPARATION DISTANCE DIMENSION
 BETWEEN THE BUILDINGS ACCORDING TO SUBSECTION
 94-204(2)(E) OF THE CITY???S ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR).
 25. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE PROPERTY
 LINE ON THE DRAWING NUMBERS PGD-1, PGD-2, PGD-3, UT-1,
 UT-2, UT-3, TD-2, AND IRR-3.
 26. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE ANCHOR
 EASEMENT (IDENTIFIED ON PAGE 3 OF 7 OF THE SURVEY) ON
 THE DRAWING NUMBERS OSP-1, PGD-3, UT-3, LP-2, AND
 IRR-2.
 27. PLEASE CORRECT THE STREET LABEL ON THE DRAWING
 NUMBERS PGD-3 AND UT-3.
 28. PLEASE IDENTIFY/INDICATE/PROVIDE THE SAME LABEL (AS
 INDICATED ON THE DRAWING NUMBER LP-2 STATING
 ???EXISTING PLAYGROUND TO REMAIN TYP.???) ON THE
 DRAWING NUMBERS PGD-3, UT-3, AND IRR-2.
 29. PLEASE CONFIRM THE MAXIMUM HEIGHT PROPOSED OF 34
 FEET IS TO THE TOP OF THE ???CURVED STANDING SEAM METAL
 ROOF??? OF THE PROPOSED COMMUNITY CENTER (GYMNASIUM).
 IF THE MAXIMUM HEIGHT IS HIGHER, THEN PLEASE REVISE THE
 PLANS AND ELEVATIONS, ACCORDINGLY.
 30. PLEASE CORRECT THE REQUIRED PARKING INDICATION TO
 52 AND THE REQUIRED BICYCLE PARKING INDICATION TO 5 IN
 THE SITE DATA TABLE ON THE DRAWING NUMBER SP-1.
 31. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE STANDARD
 AND DISABLED PARKING STALL WIDTH AND DEPTH DIMENSIONS
 ACCORDING TO SECTION 94-485 OF THE ZLDR ON DRAWING
 NUMBER SP-1.
 32. THE PROPOSED BIKE RACK (WAVE TYPE) DEMONSTRATED ON
 SHEET SP-3 IS NOT ALLOWED, THEREFORE, PLEASE REVISE
 ACCORDINGLY. {NOTE: THE BIKE RACK (POST AND LOOP TYPE)
 DEMONSTRATED ON SHEET SP-3 OF YOUR FIRST RESUBMITTAL IS
 ALLOWED.}
 33. IT HAS BEEN IDENTIFIED THAT THE PROPOSED 12.5 FEET
 HIGH DIGITAL MARQUEE SIGN EXCEEDS THE MAXIMUM HEIGHT
 ALLOWED FOR FREESTANDING SIGNS WITHIN THE RECREATION
 AND OPEN SPACE ZONING DISTRICT ACCORDING TO SUBSECTION
 94-408(F), THEREFORE, PLEASE REVISE THE DIGITAL MARQUEE
 SIGN DETAIL ON SHEET A1.2.1, ACCORDINGLY.
 34. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE SETBACK
 DIMENSIONS FOR THE PROPOSED DIGITAL MARQUEE SIGN
 ACCORDING TO SUBSECTION 94-408(F) ON DRAWING NUMBER
 OSP-1.
  
  
 KEVIE DEFRANC
 PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  

Review Stop Z ZONING
Rev No 2 Status F Date 09-29-2022 Cont ID  
Sent By kdefranc Date 09-29-2022 Time 14:58 Rev Time 0.00
Received By kdefranc Date 09-29-2022 Time 14:48 Sent To  
Notes
2022-09-29 14:58:029/29/22 ??? FAILED
  
  
 PREVIOUS REVIEW COMMENTS:
 PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN
 RESUBMITTING:
 A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
 B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED
 MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG
 WITH ONE (1) REDUCED COPY (11 IN X 17 IN).
 C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
 D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
 E. PLEASE NOTE THAT YOU ARE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. A RESUBMITTAL FEE OF
 20% OF THE ORIGINAL APPLICATION FEE WILL BE ASSESSED
 AFTER THE FIRST RESUBMITTAL.
  
 REQUIRED MATERIALS MUST BE PROVIDED:
 F. PLEASE PROVIDE LETTERS FROM PUBLIC UTILITIES
 (FLORIDA PUBLIC UTILITIES, FLORIDA POWER & LIGHT
 COMPANY, AND COMCAST CABLE COMMUNICATIONS) CONFIRMING
 THAT THE PROPOSED PROJECT DOES NOT ENCROACH INTO THEIR
 EASEMENTS OR OTHERWISE INTERFERE WITH THE PROVISIONS OF
 THEIR SERVICES. [PARTIALLY SATISFIED]
 G. PLEASE PROVIDE A TRAFFIC CONCURRENCY/PERFORMANCE
 STANDARD REVIEW (TPS) LETTER FROM THE PALM BEACH COUNTY
 TRAFFIC DIVISION FOR THE SUBJECT PROJECT. [PARTIALLY
 SATISFIED]
 H. PLEASE PROVIDE REVISED PLANS ADDRESSING THE REVIEW
 COMMENTS BELOW. [PARTIALLY SATISFIED]
 I. PLEASE PROVIDE/INDICATE/DEMONSTRATE CONSISTENT
 INFORMATION ON ALL THE DIFFERENT PLANS AND REQUIRED
 MATERIALS WITHIN THE APPLICATION PACKET RESUBMITTAL.
 [NOT SATISFIED]
  
 PLANS REVIEW COMMENTS MUST BE ADDRESSED:
 1. PLEASE PROVIDE A SITE PLAN OF THE ENTIRE GAINES PARK
 SITE/PROPERTY IDENTIFYING/INDICATING/DEMONSTRATING WHAT
 IS EXISTING AND PROPOSED AND DELINEATE/HIGHLIGHT/CLOUD
 THE AREAS OF THE PARK WHERE THE PROPOSED CHANGES ARE
 LOCATED. [PARTIALLY SATISFIED]
 2. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF
 THE EXISTING PROPERTY LINE, EASEMENTS, AND WATER
 COURSES ON ALL THE DIFFERENT PLANS, ACCORDINGLY.
 [PARTIALLY SATISFIED]
 3. PLEASE IDENTIFY ANY AREA OF THE SITE SUBJECT TO
 FLOODING OR HIGH GROUND WATER LEVEL ON ALL THE
 DIFFERENT PLANS, ACCORDINGLY. [SATISFIED]
 4. PLEASE PROVIDE A SCHEMATIC OF THE DRAINAGE SYSTEM ON
 ALL THE DIFFERENT PLANS, ACCORDINGLY. [SATISFIED]
 5. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 AND EXTENT OF ANY WETLANDS ON THE PROPERTY ON ALL THE
 DIFFERENT PLANS, ACCORDINGLY. [SATISFIED]
 6. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF
 EXISTING RIGHT-OF-WAY, STREETS, DRIVEWAYS,
 INTERSECTIONS, CURB CUTS AND TURNING LANES ON ALL THE
 DIFFERENT PLANS, ACCORDINGLY. [SATISFIED]
 7. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 AND DIMENSIONS OF ALL SIDEWALKS, FENCES, WALLS, AND
 BERMS ON ALL THE DIFFERENT PLANS, ACCORDINGLY.
 [PARTIALLY SATISFIED]
 8. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LAYOUT AND
 LOCATION OF ALL OFF-STREET PARKING, DISABLED PARKING
 SPACES/RAMPS/SIGNS, BICYCLE PARKING, AND OTHER
 VEHICULAR USE AREAS ON ALL THE DIFFERENT PLANS,
 ACCORDINGLY. [PARTIALLY SATISFIED]
 9. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE OUTLINES OF
 ALL BUILDINGS WITH USES, SETBACKS, DIMENSIONS, FLOOR
 AREA, NUMBER OF STORIES, HEIGHT AND POINTS OF ACCESS ON
 ALL THE DIFFERENT PLANS, ACCORDINGLY. [PARTIALLY
 SATISFIED]
 10. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION,
 HEIGHT, AND SIZE OF ALL FREESTANDING SIGNS AND OTHER
 ACCESSORY STRUCTURES ON ALL THE DIFFERENT PLANS,
 ACCORDINGLY. [PARTIALLY SATISFIED]
 11. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION,
 HEIGHT AND INTENSITY OF ALL OUTDOOR ILLUMINATION ON ALL
 THE DIFFERENT PLANS, ACCORDINGLY. [PARTIALLY SATISFIED]
 12. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 OF EXISTING/PROPOSED FIRE HYDRANTS (OR OPERATIONAL
 EQUIVALENTS) WITHIN 250 FEET OF THE PROPOSED STRUCTURES
 ON ALL THE DIFFERENT PLANS, ACCORDINGLY. [SATISFIED]
 13. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 OF ANY SPECIAL UTILITY STRUCTURES SUCH AS VALVES,
 METERS, BACKFLOW CONNECTIONS, PUMP STATIONS,
 TRANSFORMERS, AND ALL ABOVE GROUND APPURTENANCES ON ALL
 THE DIFFERENT PLANS, ACCORDINGLY. [SATISFIED]
 14. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 AND SCREENING OF ALL GARBAGE RECEPTACLES ON ALL THE
 DIFFERENT PLANS, ACCORDINGLY. [SATISFIED]
 15. IN ACCORDANCE WITH THE AIPP REVIEW COMMENTS, PLEASE
 IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF ALL
 PUBLIC ART (AS PART OF THE CITY???S ARTLIFE REQUIREMENT
 CHAPTER 78, ARTICLE V OF THE CITY???S CODE OF
 ORDINANCES) ON ALL THE DIFFERENT PLANS, ACCORDINGLY.
 [PARTIALLY SATISFIED]
 16. PLEASE PROVIDE THE STANDARD CITY DETAILS OF
 VEHICLE/BICYCLE PARKING (STANDARD AND ADA), ADA RAMPS,
 DRIVEWAYS, DUMPSTERS AND SIGNS ON SHEETS SP-3 OR SP-4.
 THE PROPOSED BIKE RACK DEMONSTRATED ON SHEET SP-3 IS
 NOT ALLOWED, THEREFORE, PLEASE REVISE ACCORDINGLY.
 [PARTIALLY SATISFIED]
 17. PLEASE IDENTIFY/INDICATE THE TOTAL ACREAGE/SQUARE
 FOOTAGE AND PERCENTAGE OF WATER BODIES, OPEN SPACE,
 LANDSCAPING, IMPERMEABLE SURFACE AREA, AND BUILDING
 COVERAGE; TOTAL GROSS BUILDING SQUARE FOOTAGE; TOTAL
 FLOOR AREA RATIO; AND VEHICLE/BICYCLE PARKING
 COMPUTATION (REQUIRED, PROVIDED, ETC.) IN THE SITE DATA
 TABLE ON SHEET SP-1. [NOT SATISFIED]
  
 ADDITIONAL REVIEW COMMENTS MUST BE ADDRESSED:
 18. PLEASE PROVIDE A SIGNED LETTER FROM THE FLORIDA
 POWER & LIGHT COMPANY AND FLORIDA PUBLIC UTILITIES.
 19. PLEASE PROVIDE RECORD/ACCOUNT OF THE PALM BEACH
 COUNTY TRAFFIC DIVISION RECEIVING/ACKNOWLEDGING THE
 SITE PLAN WITH THE PROPOSED IMPROVEMENTS AND/OR
 CONSISTENT INFORMATION REFLECTING THE COMMUNITY CENTER
 BUILDING INCREASING IN SIZE AND THE NEW TENNIS CENTER
 BUILDING ASSOCIATED WITH THE TPS LETTER SUBMITTED.
 20. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE INTENSITY
 OF THE PROPOSED OUTDOOR ILLUMINATION TO THE PARK???S
 PROPERTY LINES ON THE ???COMMUNITY CNETER LIGHTING
 PLAN??? DRAWING NUMBER LT-1 OF 36 AND ???TENNIS CNETER
 LIGHTING PLAN??? DRAWING NUMBER LT-2 OF 36.
 21. PLEASE REMOVE THE ???POTENTIAL??? WORDING FROM THE
 LABEL INDICATING THE ???AREA FOR PROPOSED PUBLIC ART???
 ON THE ???OVERALL SITE PLAN??? DRAWING NUMBER OSP-1 OF
 32.
 22. PLEASE PROVIDE THE REQUIRED INFORMATION STATED IN
 PREVIOUS REVIEW COMMENT NUMBER 17 (REFLECTING THE
 EXISTING CONDITIONS AND PROPOSED CHANGES INFORMATION
 FOR THE ENTIRE GAINES PARK SITE/PROPERTY) AS WELL AS
 THE SETBACKS AND HEIGHTS INFORMATION IN THE ???SITE
 DATA??? TABLE ON THE ???COMMUNITY CENTER SITE PLAN???
 DRAWING NUMBER SP-1 OF 32.
  
  
 KEVIE DEFRANC
 PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  

Review Stop Z ZONING
Rev No 1 Status F Date 07-07-2022 Cont ID  
Sent By kdefranc Date 07-07-2022 Time 10:38 Rev Time 0.00
Received By mhurley Date 07-08-2022 Time 15:25 Sent To  
Notes
2022-07-07 10:37:477/7/22 ? FAILED
  
  
 PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN
 RESUBMITTING:
 A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
 B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED
 MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG
 WITH ONE (1) REDUCED COPY (11 IN X 17 IN).
 C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
 D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
 E. PLEASE NOTE THAT YOU ARE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. A RESUBMITTAL FEE OF
 20% OF THE ORIGINAL APPLICATION FEE WILL BE ASSESSED
 AFTER THE FIRST RESUBMITTAL.
  
 REQUIRED MATERIALS MUST BE PROVIDED:
 F. PLEASE PROVIDE LETTERS FROM PUBLIC UTILITIES
 (FLORIDA PUBLIC UTILITIES, FLORIDA POWER & LIGHT
 COMPANY, AND COMCAST CABLE COMMUNICATIONS) CONFIRMING
 THAT THE PROPOSED PROJECT DOES NOT ENCROACH INTO THEIR
 EASEMENTS OR OTHERWISE INTERFERE WITH THE PROVISIONS OF
 THEIR SERVICES.
 G. PLEASE PROVIDE A TRAFFIC CONCURRENCY/PERFORMANCE
 STANDARD REVIEW (TPS) LETTER FROM THE PALM BEACH COUNTY
 TRAFFIC DIVISION FOR THE SUBJECT PROJECT.
 H. PLEASE PROVIDE REVISED PLANS ADDRESSING THE REVIEW
 COMMENTS BELOW.
 I. PLEASE PROVIDE/INDICATE/DEMONSTRATE CONSISTENT
 INFORMATION ON ALL THE DIFFERENT PLANS AND REQUIRED
 MATERIALS WITHIN THE APPLICATION PACKET RESUBMITTAL.
  
 PLANS REVIEW COMMENTS MUST BE ADDRESSED:
 1. PLEASE PROVIDE A SITE PLAN OF THE ENTIRE GAINES PARK
 SITE/PROPERTY IDENTIFYING/INDICATING/DEMONSTRATING WHAT
 IS EXISTING AND PROPOSED AND DELINEATE/HIGHLIGHT/CLOUD
 THE AREAS OF THE PARK WHERE THE PROPOSED CHANGES ARE
 LOCATED.
 2. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF
 THE EXISTING PROPERTY LINE, EASEMENTS, AND WATER
 COURSES ON ALL THE DIFFERENT PLANS, ACCORDINGLY.
 3. PLEASE IDENTIFY ANY AREA OF THE SITE SUBJECT TO
 FLOODING OR HIGH GROUND WATER LEVEL ON ALL THE
 DIFFERENT PLANS, ACCORDINGLY.
 4. PLEASE PROVIDE A SCHEMATIC OF THE DRAINAGE SYSTEM ON
 ALL THE DIFFERENT PLANS, ACCORDINGLY.
 5. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 AND EXTENT OF ANY WETLANDS ON THE PROPERTY ON ALL THE
 DIFFERENT PLANS, ACCORDINGLY.
 6. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF
 EXISTING RIGHT-OF-WAY, STREETS, DRIVEWAYS,
 INTERSECTIONS, CURB CUTS AND TURNING LANES ON ALL THE
 DIFFERENT PLANS, ACCORDINGLY.
 7. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 AND DIMENSIONS OF ALL SIDEWALKS, FENCES, WALLS, AND
 BERMS ON ALL THE DIFFERENT PLANS, ACCORDINGLY.
 8. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LAYOUT AND
 LOCATION OF ALL OFF-STREET PARKING, DISABLED PARKING
 SPACES/RAMPS/SIGNS, BICYCLE PARKING, AND OTHER
 VEHICULAR USE AREAS ON ALL THE DIFFERENT PLANS,
 ACCORDINGLY.
 9. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE OUTLINES OF
 ALL BUILDINGS WITH USES, SETBACKS, DIMENSIONS, FLOOR
 AREA, NUMBER OF STORIES, HEIGHT AND POINTS OF ACCESS ON
 ALL THE DIFFERENT PLANS, ACCORDINGLY.
 10. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION,
 HEIGHT, AND SIZE OF ALL FREESTANDING SIGNS AND OTHER
 ACCESSORY STRUCTURES ON ALL THE DIFFERENT PLANS,
 ACCORDINGLY.
 11. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION,
 HEIGHT AND INTENSITY OF ALL OUTDOOR ILLUMINATION ON ALL
 THE DIFFERENT PLANS, ACCORDINGLY.
 12. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 OF EXISTING/PROPOSED FIRE HYDRANTS (OR OPERATIONAL
 EQUIVALENTS) WITHIN 250 FEET OF THE PROPOSED STRUCTURES
 ON ALL THE DIFFERENT PLANS, ACCORDINGLY.
 13. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 OF ANY SPECIAL UTILITY STRUCTURES SUCH AS VALVES,
 METERS, BACKFLOW CONNECTIONS, PUMP STATIONS,
 TRANSFORMERS, AND ALL ABOVE GROUND APPURTENANCES ON ALL
 THE DIFFERENT PLANS, ACCORDINGLY.
 14. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 AND SCREENING OF ALL GARBAGE RECEPTACLES ON ALL THE
 DIFFERENT PLANS, ACCORDINGLY.
 15. IN ACCORDANCE WITH THE AIPP REVIEW COMMENTS, PLEASE
 IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF ALL
 PUBLIC ART (AS PART OF THE CITY?S ARTLIFE REQUIREMENT
 CHAPTER 78, ARTICLE V OF THE CITY?S CODE OF ORDINANCES)
 ON ALL THE DIFFERENT PLANS, ACCORDINGLY.
 16. PLEASE PROVIDE THE STANDARD CITY DETAILS OF
 VEHICLE/BICYCLE PARKING (STANDARD AND ADA), ADA RAMPS,
 DRIVEWAYS, DUMPSTERS AND SIGNS ON SHEETS SP-3 OR SP-4.
 THE PROPOSED BIKE RACK DEMONSTRATED ON SHEET SP-3 IS
 NOT ALLOWED, THEREFORE, PLEASE REVISE ACCORDINGLY.
 17. PLEASE IDENTIFY/INDICATE THE TOTAL ACREAGE/SQUARE
 FOOTAGE AND PERCENTAGE OF WATER BODIES, OPEN SPACE,
 LANDSCAPING, IMPERMEABLE SURFACE AREA, AND BUILDING
 COVERAGE; TOTAL GROSS BUILDING SQUARE FOOTAGE; TOTAL
 FLOOR AREA RATIO; AND VEHICLE/BICYCLE PARKING
 COMPUTATION (REQUIRED, PROVIDED, ETC.) IN THE SITE DATA
 TABLE ON SHEET SP-1.
  
  
 KEVIE DEFRANC
 PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  

  Print