Plan Review Details - Project Z22040023
Plan Review Stops For Project Z22040023
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 05-11-2022 Cont ID  
Sent By rbrown Date 05-11-2022 Time 20:05 Rev Time 0.00
Received By rbrown Date 05-11-2022 Time 20:05 Sent To  
Notes
2022-05-11 20:08:22DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS
 SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT
 REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH
 COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963,
 OR BY EMAIL: [email protected]
  
 3. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 4. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND
 OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT,
 COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF
 OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED.
  
 5. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 6. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND
 CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF
 CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL
 NEIGHBORING PROPERTIES.
  
 7. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 8. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION
 OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING,
 CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT
 (561) 805 6659, OR BY EMAIL: [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 05-09-2022 Cont ID  
Sent By rrossano Date 05-09-2022 Time   Rev Time  
Received By rrossano Date 05-09-2022 Time   Sent To  
Notes
2022-05-09 11:37:07O COMMENTS FROM RICK ROSSANO, SR. PROJECT COORDINATOR,
 ENGINEERING SERVICES 561-494-1098 [email protected]
 GENERAL:
 O PLEASE PROVIDE CIVIL DRAWINGS FOR REVIEW AS PER
 BELOW.
 O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (Z-XXXXXXXX).
 O THE CITY OF WEST PALM BEACH HAS A NUMBER OF
 REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY
 AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND
 WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE
 DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK
 BELOW:
 A. HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WP
 B_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FUL
 L-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97
 B1960045731D3658206F27451722716EF
 B. THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE
 FOUND HERE:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
 C. ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM
 BEACH, FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08,
 ADOPTED SEPT. 22, 2008. (SUPPLEMENT NO. 18)
 CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL,
 SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER
 SERVICE FACILITIES OF THE CITY.
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
 O AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, REFER TO THE LINK BELOW:
 A. HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PU
 BLICATIONS/BACKFLOW-CROSS-CONNECTION- CONTROL-MANUAL
 O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1079 FOR FURTHER
 ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION
 ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD
 SURVEY, POT-HOLING, SOFT DIGS ETC.
  
 BACKFLOW ASSEMBLY AND METERS:
 O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER
 SERVICES AND WATER METERS, ALONG WITH WHAT IS HAPPENING
 TO THEM.
 O SHOW EXISTING AND PROPOSED DEDICATED UTILITY
 EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO
 PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO
 STRUCTURES WITHIN EASEMENT.
 O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION
 OF WATER METER AND BACKFLOW PREVENTION.
 O BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY
 OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER
 METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO
 PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE
 INSTALLED ABOVE-GROUND ONLY.
 O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE
 NOTE USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA.
  
 WATER/WASTEWATER PLAN:
 O PROVIDE VERTICAL DATUM AND DATUM CONVERSION
 INFORMATION (NAVD 1988 AND NGVD 1929).
 O SHOW PROJECT ADDRESS ON ALL PLAN SHEETS.
 O PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE
 STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC.
 O PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND
 DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND
 SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH
 PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE
 AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS,
 BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO
 BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS,
 DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS,
 ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT
 ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF
 SANITARY SEWER LINES.
 O GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR
 SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW.
 O DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN
 VIEW FOR ALL SANITARY AND STORM SEWERS.
 O SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL.
 O PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED
 UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC,
 ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION
 FACILITIES LOCATED ON THE RIGHT-OF-WAY.
 O PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER
 AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD
 DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS.
 O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY
 TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT
 APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING
 AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE,
 MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS
 SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008
 FOR WATER.
 O PROVIDE FIRE FLOW TEST DATA.
 O PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND
 STORMWATER INFRASTRUCTURE ALONG ENTIRE PROJECT
 FRONTAGE.
 O CUT AND CAP UTILITIES NOT IN USE AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 ROW.
 O WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL
 BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY
 PROPOSED LENGTH IN FEET.
 O CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY
 SEWER ARE REQUIRED.
 O PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE
 JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET.
 O ADD NOTE TO PLANS SPECIFYING CITY?S DOWNSTREAM LIFT
 STATION NUMBER.
 O PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR
 PROPOSED SANITARY LATERALS.
 O LABEL WATER LINES AS PRIVATE WHERE APPLICABLE.
 O PLEASE SHOW AND LABEL EXISTING AND PROPOSED GREASE
 TRAPS (IF ANY).
 O PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN
 OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER.
 FORMAL ENGINEERING REVIEW:
 O FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES
 NOI REQUIREMENTS WILL BE ENFORCED.
 - AN NOI IS REQUIRED FOR PROJECTS THAT:
 - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS
 THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF
 DEVELOPMENT OR SALE;
 - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE
 STATE OR TO SURFACE WATERS OF THE STATE THROUGH A
 MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4).
 - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF
 CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION
 THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL
 SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT
 OF THE 10-2 CERTIFICATION.
 O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE
 EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS.
 O FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF
 WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS.
 O FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING
 APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT
 SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING
 SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED
 LEAD-FREE DESIGN.
 O FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO PROVIDE
 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF
 PROPOSED TRENCH IN CITY MAINTAINED ROADWAY AREAS PER
 CITY OF WPB STANDARD DETAIL GC-8.
 O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE
 CALCULATIONS OF PERVIOUS AND IMPERVIOUS AREAS FOR
 PROPOSED IMPROVED AREAS.
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES,
 561-822-2262 OR [email protected]
 -THERE IS NO UTILITY LETTER FOR WPB UTILITIES.
  
 -SURVEY NOTE 8 SAYS SURVEYOR DID NOT SEARCH PUBLIC
 RECORDS. WHEN WILL SEARCH BE CONDUCTED?
  
 -IS THE INTENTION FOR CARS TO DRIVE ON THE PAVER
 WALKWAY?
  
 -SUBMIT CIVIL ENGINEERING PLAN SHOWING WATER AND SEWER
 SERVICE.
  
 -WILL THERE BE FIRE SPRINKLERS IN THE BUILDINGS?
  
 -SHOW BACKFLOW ASSEMBLIES ON PLANS.
  
 -PROPOSED WEST PAVER ENTRANCE WOULD DISPLACE NEW CITY
 LANDSCAPING INCLUDING TREES. WHERE WILL THERE BE
 RELOCATED TO?
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 05-04-2022 Cont ID  
Sent By pleduc Date 05-04-2022 Time   Rev Time 0.00
Received By pleduc Date 05-04-2022 Time 12:30 Sent To  
Notes
2022-05-04 12:47:33THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE DEPARTMENT.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT. THE FOLLOWING COMMENTS ARE INTENDED
 TO PROVIDE GUIDANCE FOR BUILDING PLAN SUBMITTAL.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING(S) SHALL COMPLY
 WITH THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION
 CODE, INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE
 CODES.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE PER THE FLORIDA FIRE PREVENTION CODE.
  
 7. ALL EXISTING AND/OR NEW FIRE HYDRANTS PLANNED FOR
 THIS DEVELOPMENT SHALL BE CLEARLY INDICATED AND
 IDENTIFIED ON THE CIVIL PLAN AND, IF APPLICABLE,
 CLOSELY COORDINATED WITH THE BUREAU OF FIRE PREVENTION.
  
 8. A COMPLETE LIFE SAFETY PLAN FOR THE OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, EXIT SEPARATION DISTANCES, COMMON PATHS OF
 TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, EMERGENCY
 LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE
 EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES
 AND EQUIPMENT.
  
 9. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
 10. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 05-09-2022 Cont ID  
Sent By rcaranci Date 05-09-2022 Time 16:10 Rev Time 0.00
Received By rcaranci Date 05-09-2022 Time 16:10 Sent To  
Notes
2022-05-09 16:11:12FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 614 7TH ST Z22040023
 MAY 9, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. REVISE THE TREE MITIGATION PLAN TO INCLUDE THE
 CONDITION RATING ON #2 SABAL PALM.
  
 2. THE TREE MITIGATION PLAN SHOWS ONE TREE TO BE
 RELOCATED FROM THE ADJACENT PROPERTY OWNED BY THE CRA.
 THE FINAL LOCATION PROPOSED FOR THE RELOCATE IS LOCATED
 ON THE SUBJECT PROPERTY. TO AVOID OWNERSHIP ISSUES,
 RELOCATE THE TREE ON THE SAME PROPERTY. THERE ARE ALSO
 MORE TREES IN THE BUFFER THAT WERE APPROVED AND
 INSTALLED THAT MUST BE SHOWN ON THE PLAN FOR THIS AREA.
  
 3. SUBMIT A DRAWING SHOWING THE LOCATION OF THE 12%
 PRIVATE OPEN SPACE REQUIRED FOR NWD-2C DISTRICT.
 IDENTIFY THE TYPE OF PRIVATE OPEN SPACE AS ALLOWED IN
 TABLE IV-6 AND SHOW COMPLIANCE WITH STANDARDS FOR THAT
 TYPE PER TABLE IV-7.
  
 4. CORRECT THE FLORIDA FRIENDLY DESIGN OPTIONS CHART SO
 THAT 51% IS NOT COUNTED MORE THAN ONCE IN EACH CATEGORY
 FOR SHRUBS AND TREES.
  
 5. PROVIDE THE CALCULATIONS TO SHOW AT LEAST 30% OF THE
 LINEAR FOOTAGE OF THE PERIMETER OF THE BUILDING IS
 LANDSCAPED.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By mtechnow Date 05-11-2022 Time 15:40 Sent To  
Notes
2022-05-11 15:40:16-NO UTILITY PLANS SUBMITTED. WILL PROVIDE COMMENTS WHEN
 RECEIVED.

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 05-02-2022 Cont ID  
Sent By   Date 05-02-2022 Time   Rev Time  
Received By   Date 05-02-2022 Time   Sent To  
Notes
2022-05-02 14:57:35PLEASE PROVIDE THE FOLLOWINGS:
 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID
 WASTE VOLUME PRODUCED ALONG WITH THE SIZE, TYPE AND
 QUANTITY OF THE CONTAINER (I.E. DUMPSTER/COMPACTOR)
 THAT WILL BE UTILIZED FOR THE SANITATION SERVICE.
  
 2- DESIGNATED LOCATION FOR THE BULK ITEM PICK UP AND
 RECYCLING CONTAINERS
  
 3- IN CASE OF PROPOSING ADDITION OF ANY NEW CAN(S) IN
 THE CITY`S RIGHT-OF-WAY , THE LOCATION AND QUANTITY OF
 THE CAN(S) SHALL BE REVIEWED AND APPROVED BY PUBLIC
 WORKS DEPARTMENT AND THE CAN(S) SHALL BE TYPE, SIZE AND
 COLOR APPROVED BY PUBLIC WORKS DEPARTMENT. THE BUILDING
 MAINTENANCE IS RESPONSIBLE TO MAINTAIN AND SERVICE THE
 CAN(S).
  
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045
  

Review Stop STORM STORMWATER
Rev No 1 Status F Date 04-21-2022 Cont ID  
Sent By tward Date 04-21-2022 Time 16:26 Rev Time 0.00
Received By tward Date 04-21-2022 Time 16:43 Sent To  
Notes
2022-04-21 16:42:471. SURVEY
 A. DATED 2018.
 B. UPDATE THE FLOOD ZONE INFOMRATION. REVISED FIRMS
 WERE ISSUED IN 2017.
 C. REVIEW LOT DIMENSIONS (100 FT X 140 FT) AND LOT AREA
 (0.32 ACRES, 14000 S.F.) .
  
 2. NO DRAINAGE PLAN OR GRADING PLAN PROVIDED. DRAINAGE
 SYSTEM TO BE DESIGNED TO MEET SFWMD ERP CRITERIA.
  
 3. NO ENGINEEERING PLANS PROVIDED.
  
 4. THE CITY'S OFFICIAL VERTICAL DATUM IS NGVD1929. THE
 CITY HAS ALLOWED THE USE OF NAVD1988 PROVIDED A
 CONVERSION EQUATION BETWEEN NAVD1988 AND NGVD1929 IS
 SHOWN ON THE PLANS. THE VERTICAL DATUM AND CONVERSION
 EQUATION SHALL BE PROVIDED ON EVERY SHEET WITH
 ELEVATION INFORMATION.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 05-11-2022 Cont ID  
Sent By vnoel Date 05-11-2022 Time 06:55 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2022-05-11 06:59:001. REFERENCE ADJACENT STYX ALLEY PLAT.
 2. NO ENGINEERING PLANS PROVIDED.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 05-06-2022 Cont ID  
Sent By   Date 05-06-2022 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2022-05-06 15:16:40TRAFFIC COMMENTS
 1) PROVIDE TRAFFIC STUDY
 2) PROVIDE COUNTY TPS LETTER
  
 SITE COMMENTS
 3) PROVIDE DRIVEWAY WIDTH AND EXPLAIN ITS USE
 4) ARE VEHICLES ALLOWED TO DRIVE INTO THE PAVER
 COURTYARD WALKWAY AREA?
 5) PROVIDE AUTOTURN ANALYSIS FOR GARBAGE TRUCK AND/OR
 SERVICE VEHICLES DRIVING IN/OUT OF THE PROPOSED
 DEVELOPMENT OR TRAVERSING THROUGH HENRIETTA ST
 EXTENSION
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 05-06-2022 Cont ID  
Sent By ckimmerl Date 05-06-2022 Time 10:31 Rev Time 0.00
Received By ckimmerl Date 05-06-2022 Time 10:29 Sent To  
Notes
2022-05-06 10:31:511. THE SETBACKS ON ROADWAYS IN THIS DISTRICT SHALL BE
 MEASURED FROM THE BACK OF CURB, NOT THE PROPERTY LINE.
 POTENTIALLY HAVE MORE ROOM TO WORK WITH.
 2. REQUIRED FRONT SETBACK ON RESIDENTIAL STREET (7TH
 STREET) IS MIN. 17'. PROPOSED SETBACK AT 15'9" WHY IS A
 CONTEXTUAL SETBACK USED? SHOULD BE OKAY ONCE MEASURED
 FROM BACK OF CURB.
 3. REAR MINIMUM SETBACK IS ONLY 5' (PROPOSED 14' IS
 OKAY)
 4. 12% PRIVATE OPEN SPACE REQUIREMENT - 840 SF:
 I. PER SEC.94-109 - DEFINITIONS AND MINIMUM
 REQUIREMENTS - OPEN SPACE, PRIVATE: IF PRIVATE OPEN
 SPACE IS LOCATED ON THE GROUND FLOOR AND LOCATED ALONG
 THE LOT FRONTAGE, IT SHALL BE DESIGNED IN COMPLIANCE
 WITH THE PUBLIC OPEN SPACE REQUIREMENTS, AND IT SHALL
 BE ACCESSIBLE BY THE PUBLIC FOR PUBLIC USE.
 II. COURTYARD REQUIRES 25% VEGETATED AREA, 10% MIN. AND
 20% MAX OVERHEAD COVERAGE, 1 LN FT. OF SEATING FOR
 EVERY 30 SF OF OPEN SPACE, AND 30% TREE CANOPY.
 III. PER SEC.94-109 - DEFINITIONS AND MINIMUM
 REQUIREMENTS ? OPEN SPACE, PUBLIC:
 (1) PUBLIC OPEN SPACES SHALL NOT PROVIDE VEHICULAR
 ACCESS NOT SPECIFICALLY RELATED TO THE MAINTENANCE OF
 THE PUBLIC OPEN SPACE.
 (2) PUBLIC OPEN SPACES SHALL NOT BE LOCATED ADJOINING
 CURB CUTS, DRIVEWAYS, OR PARKING ACCESS RAMPS, EXCEPT
 OUTDOOR PASSENGER DROP-OFF AREAS.
 IV. PROVIDE TABLE IDENTIFYING WHAT THE OPEN SPACE TYPE
 IS UTILIZED AND HOW THE REQUIREMENTS ARE BEING MET.
 4. SURFACE PARKING LOTS REQUIRE A 5-FT LANDSCAPE BUFFER
 WITH 36" HEDGES PLANTED AT 2-3 FT. INTERVALS.
 5. WILL REQUIRE SEPARATE LANDSCAPE PERMITS, IRRIGATION,
 TREE ALTERATION, ETC.
 6. COVERSHEET EDIT, RICK GREENE IS THE DEVELOPMENT
 SERVICES DIRECTOR, NOT THE ASSISTANT CITY ADMINISTRATOR
 7. REQUIRE 1-SPACE FOR BIKE PARKING.
 8. HOW IS THE SITE GOING TO BE PARKED? TANDEM SPACES?
 UTILIZING ON-STREET SPACES? IS THERE PARKING ON THE
 COURTYARD? 3 REQUIRED SPACES; IF PARKING IS ONSITE 1
 SPACE IS REQUIRED TO MEET ADA REQUIREMENTS.
  
 CHRIS KIMMERLY, AICP
 URBAN DESIGN PLANNER - [email protected] - 822-1426