Plan Review Details - Project Z22040017
| Plan Review Stops For Project Z22040017 |
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
1 |
Status |
N |
Date |
05-12-2022 |
|
|
Cont ID |
|
| Sent By |
scwelter |
Date |
05-12-2022 |
Time |
11:45 |
Rev Time |
0.00 |
| Received By |
scwelter |
Date |
05-12-2022 |
Time |
11:46 |
Sent To |
|
|
| Notes |
| 2022-05-12 11:46:09 | INTERIOR NOT APPLICABLE TO PUBLIC ART REQUIREMENT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
05-11-2022 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
05-11-2022 |
Time |
19:47 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
05-11-2022 |
Time |
19:47 |
Sent To |
|
|
| Notes |
| 2022-05-11 19:51:46 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. THE ADDITION TO THE EXISTING BUILDING IS COVERED BY | | | CHAPTER 11 OF THE FLORIDA EXISTING BUILDING CODE. THE | | | HEIGHT AND/OR AREA INCREASE DUE TO THE PROPOSED | | | ADDITION SHALL NOT INCREASE THE TOTAL BUILDING HEIGHT | | | AND/OR AREA BEYOND THAT ALLOWED UNDER THE APPLICABLE | | | PROVISIONS OF CHAPTER 5 OF THE FLORIDA BUILDING CODE | | | FOR THE TYPE OF CONSTRUCTION USED. | | | | | | 3. GREASE/PETROLEUM INTERCEPTOR. A LARGER | | | GREASE/PETROLUEM INTERCEPTOR MAYL BE REQUIRED. FOR | | | INFORMATION ON THE REQUIRED TYPE, SIZE AND LOCATION, | | | PLEASE CONTACT RYAN BROWN, CHIEF PLUMBING INSPECTOR, | | | DEVELOPMENT SERVICES DEPARTMENT, AT (561) 805-6692, OR | | | BY EMAIL: [email protected] | | | | | | 4. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, | | | FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, | | | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, | | | SITE IRRIGATION, ETC. | | | | | | 5. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND | | | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF | | | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL | | | NEIGHBORING PROPERTIES. | | | | | | 6. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT | | | TO ART LIFE ASSESSMENT UNDER THE CITY OF WEST PALM | | | BEACH ART IN PUBLIC PLACES (AIPP) PROGRAM. FOR ADVICE | | | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP | | | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC | | | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
F |
Date |
05-23-2023 |
|
|
Cont ID |
|
| Sent By |
lquinone |
Date |
05-23-2023 |
Time |
13:31 |
Rev Time |
0.00 |
| Received By |
lquinone |
Date |
05-23-2023 |
Time |
13:31 |
Sent To |
|
|
| Notes |
| 2023-05-23 13:32:58 | NO RESPONSE LETTER WAS PROVIDED. | | | | | | REPEATED COMMENTS: | | | | | | O LINDA QUI??ONES-CINTRON, PROJECT COORDINATOR, | | | ENGINEERING SERVICES DEPARTMENT AT 561-494-1085 | | | [email protected] | | | GENERAL: | | | O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND | | | INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER | | | (Z-XXXXXXXX). | | | O THE CITY OF WEST PALM BEACH HAS A NUMBER OF | | | REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY | | | AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND | | | WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE | | | DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK | | | BELOW: | | | A. HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WP | | | B_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FUL | | | L-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97 | | | B1960045731D3658206F27451722716EF | | | B. THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE | | | FOUND HERE: | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | C. ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM | | | BEACH, FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, | | | ADOPTED SEPT. 22, 2008. (SUPPLEMENT NO. 18) | | | CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL, | | | SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER | | | SERVICE FACILITIES OF THE CITY. | | | THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE | | | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY | | | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, | | | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. | | | O AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR | | | MORE INFORMATION, REFER TO THE LINK BELOW: | | | A. HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PU | | | BLICATIONS/BACKFLOW-CROSS-CONNECTION- CONTROL-MANUAL | | | O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY | | | OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC | | | RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF | | | YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE | | | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL | | | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT | | | [email protected] OR 561-494-1079 FOR FURTHER | | | ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION | | | ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD | | | SURVEY, POT-HOLING, SOFT DIGS ETC. | | | O PROVIDE EXISTING AND PROPOSED PERVIOUS/IMPERVIOUS | | | CALCULATIONS. | | | | | | BACKFLOW ASSEMBLY AND METERS: | | | O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER | | | SERVICES AND WATER METERS, ALONG WITH WHAT IS HAPPENING | | | TO THEM. | | | O SHOW EXISTING AND PROPOSED DEDICATED UTILITY | | | EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO | | | PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO | | | STRUCTURES WITHIN EASEMENT. | | | O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION | | | OF WATER METER AND BACKFLOW | | | PREVENTION. | | | O BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY | | | OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER | | | METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO | | | PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE | | | INSTALLED ABOVE-GROUND ONLY. | | | O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE | | | NOTE USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA. | | | | | | WATER/WASTEWATER PLAN: | | | O PROVIDE VERTICAL DATUM AND DATUM CONVERSION | | | INFORMATION (NAVD 1988 AND NGVD 1929). | | | O SHOW PROJECT ADDRESS ON ALL PLAN SHEETS. | | | O PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE | | | STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC. | | | O PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND | | | DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND | | | SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH | | | PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE | | | AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS, | | | BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO | | | BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS, | | | DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS, | | | ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT | | | ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF | | | SANITARY SEWER LINES. | | | O GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR | | | SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE | | | PROFILE VIEW. | | | O DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN | | | VIEW FOR ALL SANITARY AND STORM SEWERS. | | | O SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT | | | MATERIAL. | | | O PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED | | | UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC, | | | ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION | | | FACILITIES LOCATED ON THE RIGHT-OF-WAY. | | | O PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER | | | AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD | | | DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS. | | | O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY | | | TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT | | | APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING | | | AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, | | | MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS | | | SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 | | | FOR WATER. | | | O PROVIDE FIRE FLOW TEST DATA. | | | O WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL | | | BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY | | | PROPOSED LENGTH IN FEET. | | | O CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY | | | SEWER ARE REQUIRED. | | | O PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE | | | JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET. | | | O ADD NOTE TO PLANS SPECIFYING CITY???S DOWNSTREAM LIFT | | | STATION NUMBER. | | | O PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR | | | PROPOSED SANITARY LATERALS. | | | O LABEL WATER LINES AS PRIVATE WHERE APPLICABLE. | | | O PLEASE SHOW AND LABEL EXISTING AND PROPOSED GREASE | | | TRAPS (IF ANY). | | | O PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN | | | OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER. | | | | | | FORMAL ENGINEERING REVIEW: | | | O FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES | | | NOI REQUIREMENTS WILL BE ENFORCED. | | | - AN NOI IS REQUIRED FOR PROJECTS THAT: | | | - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS | | | THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF | | | DEVELOPMENT OR SALE; | | | - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE | | | STATE OR TO SURFACE WATERS OF THE STATE THROUGH A | | | MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4). | | | - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF | | | CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION | | | THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL | | | SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT | | | OF THE 10-2 CERTIFICATION. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF | | | WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING | | | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT | | | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING | | | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED | | | LEAD-FREE DESIGN. | | | | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
05-09-2022 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
05-09-2022 |
Time |
|
Rev Time |
|
| Received By |
rrossano |
Date |
05-09-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-05-09 11:51:34 | O RICK ROSSANO, SR. PROJECT COORDINATOR, ENGINEERING | | | SERVICES DEPARTMENT AT 561-494-1098 [email protected] | | | GENERAL: | | | O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND | | | INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER | | | (Z-XXXXXXXX). | | | O THE CITY OF WEST PALM BEACH HAS A NUMBER OF | | | REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY | | | AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND | | | WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE | | | DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK | | | BELOW: | | | A. HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WP | | | B_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FUL | | | L-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97 | | | B1960045731D3658206F27451722716EF | | | B. THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE | | | FOUND HERE: | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | C. ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM | | | BEACH, FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, | | | ADOPTED SEPT. 22, 2008. (SUPPLEMENT NO. 18) | | | CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL, | | | SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER | | | SERVICE FACILITIES OF THE CITY. | | | THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE | | | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY | | | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, | | | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. | | | O AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR | | | MORE INFORMATION, REFER TO THE LINK BELOW: | | | A. HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PU | | | BLICATIONS/BACKFLOW-CROSS-CONNECTION- CONTROL-MANUAL | | | O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY | | | OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC | | | RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF | | | YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE | | | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL | | | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT | | | [email protected] OR 561-494-1079 FOR FURTHER | | | ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION | | | ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD | | | SURVEY, POT-HOLING, SOFT DIGS ETC. | | | O PROVIDE EXISTING AND PROPOSED PERVIOUS/IMPERVIOUS | | | CALCULATIONS. | | | | | | BACKFLOW ASSEMBLY AND METERS: | | | O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER | | | SERVICES AND WATER METERS, ALONG WITH WHAT IS HAPPENING | | | TO THEM. | | | O SHOW EXISTING AND PROPOSED DEDICATED UTILITY | | | EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO | | | PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO | | | STRUCTURES WITHIN EASEMENT. | | | O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION | | | OF WATER METER AND BACKFLOW | | | PREVENTION. | | | O BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY | | | OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER | | | METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO | | | PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE | | | INSTALLED ABOVE-GROUND ONLY. | | | O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE | | | NOTE USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA. | | | | | | WATER/WASTEWATER PLAN: | | | O PROVIDE VERTICAL DATUM AND DATUM CONVERSION | | | INFORMATION (NAVD 1988 AND NGVD 1929). | | | O SHOW PROJECT ADDRESS ON ALL PLAN SHEETS. | | | O PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE | | | STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC. | | | O PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND | | | DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND | | | SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH | | | PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE | | | AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS, | | | BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO | | | BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS, | | | DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS, | | | ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT | | | ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF | | | SANITARY SEWER LINES. | | | O GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR | | | SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE | | | PROFILE VIEW. | | | O DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN | | | VIEW FOR ALL SANITARY AND STORM SEWERS. | | | O SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT | | | MATERIAL. | | | O PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED | | | UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC, | | | ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION | | | FACILITIES LOCATED ON THE RIGHT-OF-WAY. | | | O PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER | | | AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD | | | DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS. | | | O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY | | | TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT | | | APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING | | | AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, | | | MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS | | | SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 | | | FOR WATER. | | | O PROVIDE FIRE FLOW TEST DATA. | | | O WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL | | | BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY | | | PROPOSED LENGTH IN FEET. | | | O CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY | | | SEWER ARE REQUIRED. | | | O PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE | | | JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET. | | | O ADD NOTE TO PLANS SPECIFYING CITY?S DOWNSTREAM LIFT | | | STATION NUMBER. | | | O PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR | | | PROPOSED SANITARY LATERALS. | | | O LABEL WATER LINES AS PRIVATE WHERE APPLICABLE. | | | O PLEASE SHOW AND LABEL EXISTING AND PROPOSED GREASE | | | TRAPS (IF ANY). | | | O PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN | | | OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER. | | | | | | FORMAL ENGINEERING REVIEW: | | | O FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES | | | NOI REQUIREMENTS WILL BE ENFORCED. | | | - AN NOI IS REQUIRED FOR PROJECTS THAT: | | | - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS | | | THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF | | | DEVELOPMENT OR SALE; | | | - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE | | | STATE OR TO SURFACE WATERS OF THE STATE THROUGH A | | | MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4). | | | - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF | | | CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION | | | THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL | | | SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT | | | OF THE 10-2 CERTIFICATION. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF | | | WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING | | | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT | | | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING | | | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED | | | LEAD-FREE DESIGN. | | | | | | COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE | | | SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, | | | 561-822-2262 OR [email protected] | | | -WHAT DAYS AND TIMES ARE THE ACCESS GATES CLOSED? | | | | | | -IS THERE A CURRENT AGREEMENT TO USE NEIGHBOR?S SEWER | | | INFRASTRUCTURE? IF SO, PLEASE PROVIDE COPY. | | | | | | -IS THERE A CURRENT ACCESS AGREEMENT OR EASEMENT TO | | | TRAVERSE NEIGHBOR?S PROPERTY TO THE NORTH? IF SO, | | | PLEASE PROVIDE DOCUMENTATION AND UPDATE SURVEY AND | | | ENGINEERING PLAN. | | | | | | -ARE EXISTING WATER AND SEWER INFRACTURE SUFFICIENT FOR | | | ANY INCREASED DEMAND? | | | | | | -SHOW AND LABEL EXISTING DOMESTIC WATER SERVICE, SEWER | | | MAIN, CLEANOUT, WATER MAIN, METER BOX, AND BACKFLOW | | | ASSEMBLY ON ENGINEERING PLAN. | | | | | | -LP1 CALLS OUT THREE (5) NEW CHRISTMAS PALM TREE. | | | | | | -EXISTING DCDA IS 4 INCH SIZE. IF PROPOSED BUILDING | | | WILL HAVE FIRE SPRINKLERS, IS DCDA SIZE SUFFICIENT? | | | | | | -DOMESTIC BACKFLOW ASSEMBLY IS SHOWING AS OVERDUE FOR | | | ANNUAL TESTING. IF IT WILL REMAIN THROUGH THE PROJECT, | | | THEN NEEDS TO BE TESTED BY LICENSED PLUMBER. | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
05-15-2023 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
05-15-2023 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
05-15-2023 |
Time |
12:47 |
Sent To |
|
|
| Notes |
| 2023-05-15 12:49:47 | FIRE HAS NO OBJECTIONS TO THE PROPOSED AND APPROVES. | | | | | | FIRE'S APPROVAL OF THIS SUBMITTED PROJECT MAY NOT | | | CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | IF APPLICABLE, FIRE SHALL REVIEW ALL SUBMITTED PROJECT | | | PLANS AT THE APPLICABLE TIME AND IN ACCORDANCE WITH THE | | | REQUIREMENTS OF ALL APPLICABLE FIRE CODES AND | | | STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
05-04-2022 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
05-04-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
05-04-2022 |
Time |
12:08 |
Sent To |
|
|
| Notes |
| 2022-05-04 12:16:23 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE DEPARTMENT. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. THE FOLLOWING COMMENTS ARE INTENDED | | | TO PROVIDE GUIDANCE FOR BUILDING PLAN SUBMITTAL. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING(S) SHALL COMPLY | | | WITH THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION | | | CODE, INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE | | | CODES. | | | | | | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE | | | OCCUPANCY TYPE PER THE FLORIDA FIRE PREVENTION CODE. | | | | | | 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE | | | LOAD CALCULATION IS INCLUDED, AND THAT ADEQUATE WATER | | | SUPPLY IS EXISTING OR WILL BE PROVIDED. | | | | | | 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | ANY PROPOSED LOCATION OF NEW FIRE HYDRANT(S) AND/OR | | | FDC(S) SHALL BE WITHIN 100' OF EACH OTHER AND CLOSELY | | | COORDINATED WITH THE BUREAU OF FIRE PREVENTION. | | | | | | 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER | | | THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY | | | ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM, | | | ENSURE THEY COMPLY WITH THE REQUIREMENTS OF F.A.C. 61G | | | AND SUBMITTED WITH THE MASTER PERMIT. | | | | | | 9A. ANY NEW LOCATION OF ANY APPLICABLE DDCV AND FIRE | | | LINE LOCATIONS SHALL MEET AND BE INSTALLED PER THE | | | REQUIREMENTS OF NFPA 24 AND SHALL BE COORDINATED WITH | | | THE OFFICE OF FIRE MARSHAL, THE CITY'S ENGINEERS | | | OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S PLANNING | | | AND ZONING OFFICE. | | | | | | 10. COMPLETE LIFE SAFETY PLANS FOR THE OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, EXIT SEPARATION DISTANCES, COMMON PATHS OF | | | TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, EMERGENCY | | | LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE | | | EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES | | | AND EQUIPMENT. | | | | | | 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE | | | SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY | | | DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS. | | | | | | 12. ANY PASSENGER ELEVATORS SHALL CONFORM TO THE FIRE | | | FIGHTER?S EMERGENCY OPERATIONS REQUIREMENTS OF ASME | | | A17.1/CSA B44, SAFETY CODE FOR ELEVATORS. | | | | | | ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN | | | WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL | | | LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET | | | MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER | | | ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN | | | AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE | | | IN THE HORIZONTAL POSITION. | | | | | | 13. TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEMS. | | | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY | | | RADIO ENHANCEMENT SERVICES. | | | 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM | | | RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT | | | COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL | | | DETERMINED BY THE AHJ. | | | | | | CONTACT WILL NEED TO BE MADE TO MARK FILLA, PALM BEACH | | | COUNTY PUBLIC SAFETY RADIO SYSTEMS MANAGER, | | | [email protected], 561-233-0837; AS OUR RADIOS OPERATE | | | ON THEIR SYSTEM FOR DETAILED RADIO FREQUENCY AND | | | INSTALLATION INSTRUCTIONS. | | | | | | 14. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL. | | | | | | 15. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
F |
Date |
06-07-2023 |
|
|
Cont ID |
|
| Sent By |
kdefranc |
Date |
06-07-2023 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
kdefranc |
Date |
06-07-2023 |
Time |
09:19 |
Sent To |
|
|
| Notes |
| 2023-06-07 09:22:06 | FROM: KEVIE DEFRANC, SENIOR PLANNER 561-822-1449 | | | PROJECT: 2345 OKEECHOBEE Z22040017 | | | JUNE 7, 2023 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | | | | 1. NOT SATISFIED. PROVIDE A SEPARATE TREE DISPOSITION | | | PLAN AND LIST. SECTION 94-448 (D)(3) REQUIRES NATIVE | | | TREES AND PALMS IN GOOD CONDITION TO BE PRESERVED ON | | | SITE OR RELOCATED. ANSI A 300 (PART 5) STANDARDS | | | SPECIFY EXAMPLES OF SUITABILITY RATINGS OF GOOD, | | | MODERATE, OR POOR FOR RELOCATION. PROVIDE AN ARBORISTS | | | REPORT RATING THE CONDITION AND RELOCATION POTENTIAL | | | FOR THE NATIVE TREES AND PALMS IF THERE ARE PROPOSED | | | REMOVALS. | | | | | | 6/7/23 NO TREE DISPOSITION PLAN WITH THE INFORMATION | | | REQUESTED HAS BEEN PROVIDED. | | | | | | 2. NOT SATISFIED. IDENTIFY RELOCATED TREES OR PALMS ON | | | THE PLANT LIST AND COUNT THEM TOWARD THE REQUIRED | | | TREES. | | | | | | 6/7/23 LABEL RELOCATED TREES ACCORDING TO DISPOSITION | | | NUMBER THEY ARE GIVEN FROM TREE DISPOSITION PLAN. | | | | | | 3. NOT SATISFIED. ALL EXISTING LANDSCAPING MUST BE | | | SHOWN ON THE LANDSCAPE PLAN TO PROVIDE A COMPLETE PLAN | | | SHOWING COMPLIANCE WITH CURRENT CODE REQUIREMENTS. | | | | | | 6/7/23 PROVIDE LIST OF EXISTING TREES/PALMS. | | | | | | 4. NOT SATISFIED. PROVIDE A CODE COMPLIANCE CHART WITH | | | THE BUFFER LENGTHS AND CALCULATION FOR THE NUMBER OF | | | REQUIRED TREES AND HEDGES FOR ALL FOUR BUFFERS AND SHOW | | | THE NUMBER PROVIDED. | | | | | | 5. NOT SATISFIED. PROVIDE THE MINIMUM CALCULATIONS FOR | | | REQUIRED LANDSCAPING ON THE SITE, INCLUDING NUMBER OF | | | SHADE AND FLOWERING TREES BASED ON 40% REQUIRED OPEN | | | SPACE AND THE SQUARE FOOTAGE AND PERCENTAGE OF | | | LANDSCAPE AREA. | | | | | | 6. SATISFIED. SHOW ALL EXISTING AND PROPOSED WATER AND | | | SEWER AND DRAINAGE LINES ON THE LANDSCAPE PLAN. SHOW | | | LOCATIONS OF BACKFLOWS AND ADJUST LOCATIONS OF UTILITY | | | LINES TO RESOLVE CONFLICTS WITH EXISTING AND PROPOSED | | | TREES AND LANDSCAPING. | | | | | | 7. SATISFIED. PROVIDE THE 50 REQUIRED FLORIDA FRIENDLY | | | POINTS BASED ON THE FINAL PLANT LIST PER SECTION | | | 94-443(G). | | | | | | 8. NOT SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 | | | L. PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT | | | MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT | | | TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE | | | LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH | | | FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH | | | FLORIDA LANDSCAPES. PROVIDE THE ACTUAL PERCENTAGE BASED | | | ON THE PLANT LIST. | | | | | | 6/7/23 CANNOT CLAIM CREDIT FOR SELECTING MULTIPLE | | | OPTIONS IN THE SAME CATEGORY. | | | | | | 9. NOT SATISFIED. ALL SURFACE PARKING MUST MEET THE | | | REQUIREMENTS OF SECTION 94-443(C)(3) A. INCLUDING | | | TERMINAL LANDSCAPE ISLANDS, INTERIOR ISLANDS AND SHADE | | | TREES. SHOW ALL MODIFIED AREAS MEET REQUIREMENTS ON THE | | | LANDSCAPE PLAN. EACH LANDSCAPE ISLAND REQUIRES A TREE, | | | AND AT LEAST 75% MUST BE CATEGORY 1 SHADE TREES. | | | | | | 10. NOT SATISFIED. PROVIDE AN EXHIBIT SHOWING THE | | | PARKING AREA SURFACE CALCULATIONS, PARKING SPACE AREAS | | | AND LANDSCAPE AREAS PROVIDED TO DEMONSTRATE COMPLIANCE | | | WITH SECTIONS 94-443 (C)(3) AND (4). PROVIDE THE | | | CALCULATIONS IN THE LANDSCAPE REQUIREMENT CHART. REFER | | | TO FIGURE XIV-1. | | | | | | 11. NOT SATISFIED. PROVIDE SCREENING HEDGES FOR ALL | | | GROUND MOUNTED VALVES AND EQUIPMENT AND ADD A NOTE THAT | | | ALL EQUIPMENT WILL BE SCREENED. | | | | | | 6/7/23 SHOW GROUND EQUIPMENT ON PLANS. | | | | | | 12. NOT SATISFIED. FOUNDATION LANDSCAPE REQUIREMENT | | | NEEDS TO SHOW TOTAL LINEAR FOOTAGE FOR EACH BUILDING | | | AND SHOW THAT AT LEAST 30% OF THAT IS LANDSCAPED AREA. | | | | | | 13. NOT SATISFIED. ALL TREES MUST MEET THE MINIMUM 12 | | | FT HEIGHT REQUIREMENT. SILVER BUTTONWOOD SHOWN AT 10 | | | FT. | | | | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | | | | 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF ANY | | | RIGHT OF WAY LANDSCAPING AND IRRIGATION APPROVED WITH | | | THIS PETITION. | | | | | | 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE MAINTENANCE OF ANY RIGHT OF WAY | | | LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A | | | SEPARATE MAINTENANCE AGREEMENT WITH THE CITY. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
05-11-2022 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
05-11-2022 |
Time |
17:07 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
05-11-2022 |
Time |
17:06 |
Sent To |
|
|
| Notes |
| 2022-05-11 17:11:14 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: 2345 OKEECHOBEE Z22040017 | | | MAY 11, 2022 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | | | | 1. PROVIDE A SEPARATE TREE DISPOSITION PLAN AND LIST. | | | SECTION 94-448 (D)(3) REQUIRES NATIVE TREES AND PALMS | | | IN GOOD CONDITION TO BE PRESERVED ON SITE OR RELOCATED. | | | ANSI A 300 (PART 5) STANDARDS SPECIFY EXAMPLES OF | | | SUITABILITY RATINGS OF GOOD, MODERATE, OR POOR FOR | | | RELOCATION. PROVIDE AN ARBORISTS REPORT RATING THE | | | CONDITION AND RELOCATION POTENTIAL FOR THE NATIVE TREES | | | AND PALMS IF THERE ARE PROPOSED REMOVALS. | | | | | | 2. IDENTIFY RELOCATED TREES OR PALMS ON THE PLANT LIST | | | AND COUNT THEM TOWARD THE REQUIRED TREES. | | | | | | 3. ALL EXISTING LANDSCAPING MUST BE SHOWN ON THE | | | LANDSCAPE PLAN TO PROVIDE A COMPLETE PLAN SHOWING | | | COMPLIANCE WITH CURRENT CODE REQUIREMENTS. | | | | | | | | | 4. PROVIDE A CODE COMPLIANCE CHART WITH THE BUFFER | | | LENGTHS AND CALCULATION FOR THE NUMBER OF REQUIRED | | | TREES AND HEDGES FOR ALL FOUR BUFFERS AND SHOW THE | | | NUMBER PROVIDED. | | | | | | 5. PROVIDE THE MINIMUM CALCULATIONS FOR REQUIRED | | | LANDSCAPING ON THE SITE, INCLUDING NUMBER OF SHADE AND | | | FLOWERING TREES BASED ON 40% REQUIRED OPEN SPACE AND | | | THE SQUARE FOOTAGE AND PERCENTAGE OF LANDSCAPE AREA. | | | | | | | | | 6. SHOW ALL EXISTING AND PROPOSED WATER AND SEWER AND | | | DRAINAGE LINES ON THE LANDSCAPE PLAN. SHOW LOCATIONS OF | | | BACKFLOWS AND ADJUST LOCATIONS OF UTILITY LINES TO | | | RESOLVE CONFLICTS WITH EXISTING AND PROPOSED TREES AND | | | LANDSCAPING. | | | | | | | | | 7. PROVIDE THE 50 REQUIRED FLORIDA FRIENDLY POINTS | | | BASED ON THE FINAL PLANT LIST PER SECTION 94-443(G). | | | | | | | | | 8. SHOW COMPLIANCE WITH SECTION 94-445 L. PLANT | | | SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL | | | ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT | | | SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF | | | SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA | | | WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA | | | LANDSCAPES. PROVIDE THE ACTUAL PERCENTAGE BASED ON THE | | | PLANT LIST. | | | | | | | | | | | | 9. ALL SURFACE PARKING MUST MEET THE REQUIREMENTS OF | | | SECTION 94-443(C)(3) A. INCLUDING TERMINAL LANDSCAPE | | | ISLANDS, INTERIOR ISLANDS AND SHADE TREES. SHOW ALL | | | MODIFIED AREAS MEET REQUIREMENTS ON THE LANDSCAPE PLAN. | | | EACH LANDSCAPE ISLAND REQUIRES A TREE, AND AT LEAST 75% | | | MUST BE CATEGORY 1 SHADE TREES. | | | | | | 10. PROVIDE AN EXHIBIT SHOWING THE PARKING AREA SURFACE | | | CALCULATIONS, PARKING SPACE AREAS AND LANDSCAPE AREAS | | | PROVIDED TO DEMONSTRATE COMPLIANCE WITH SECTIONS 94-443 | | | (C)(3) AND (4). PROVIDE THE CALCULATIONS IN THE | | | LANDSCAPE REQUIREMENT CHART. REFER TO FIGURE XIV-1. | | | | | | 11. PROVIDE SCREENING HEDGES FOR ALL GROUND MOUNTED | | | VALVES AND EQUIPMENT AND ADD A NOTE THAT ALL EQUIPMENT | | | WILL BE SCREENED. | | | | | | | | | 12. FOUNDATION LANDSCAPE REQUIREMENT NEEDS TO SHOW | | | TOTAL LINEAR FOOTAGE FOR EACH BUILDING AND SHOW THAT AT | | | LEAST 30% OF THAT IS LANDSCAPED AREA. | | | | | | 13. ALL TREES MUST MEET THE MINIMUM 12 FT HEIGHT | | | REQUIREMENT. SILVER BUTTONWOOD SHOWN AT 10 FT. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF ANY | | | RIGHT OF WAY LANDSCAPING AND IRRIGATION APPROVED WITH | | | THIS PETITION. | | | | | | 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE MAINTENANCE OF ANY RIGHT OF WAY | | | LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A | | | SEPARATE MAINTENANCE AGREEMENT WITH THE CITY. | | | | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
mtechnow |
Date |
05-11-2022 |
Time |
15:42 |
Sent To |
|
|
| Notes |
| 2022-05-11 15:41:44 | -WILL REVIEW THE PROPOSED WATER/WASTEWATER PLAN WHEN | | | PROVIDED. |
|
|
| Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
| Rev No |
1 |
Status |
F |
Date |
05-19-2023 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
05-19-2023 |
Time |
13:22 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2023-05-19 13:22:42 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | -RESPONSE LETTER WAS NOT PROVIDED FOR THE FOLLOWING | | | REVIEW COMMENTS FROM INITIAL SUBMITTAL. PLEASE RESPOND | | | TO THOSE NOW: | | | *WHAT DAYS AND TIMES ARE THE ACCESS GATES CLOSED? | | | *IS THERE A CURRENT AGREEMENT TO USE NEIGHBOR???S SEWER | | | INFRASTRUCTURE? IF SO, PLEASE PROVIDE COPY. | | | *IS THERE A CURRENT ACCESS AGREEMENT OR EASEMENT TO | | | TRAVERSE NEIGHBOR???S PROPERTY TO THE NORTH? IF SO, | | | PLEASE PROVIDE DOCUMENTATION AND UPDATE SURVEY AND | | | ENGINEERING PLAN. | | | *ARE EXISTING WATER AND SEWER INFRACTURE SUFFICIENT FOR | | | ANY INCREASED DEMAND? | | | *SHOW AND LABEL EXISTING DOMESTIC WATER SERVICE, SEWER | | | MAIN, CLEANOUT, WATER MAIN, METER BOX, AND BACKFLOW | | | ASSEMBLY ON ENGINEERING PLAN. | | | *LP1 CALLS OUT THREE (5) NEW CHRISTMAS PALM TREE. | | | *EXISTING DCDA IS 4 INCH SIZE. IF PROPOSED BUILDING | | | WILL HAVE FIRE SPRINKLERS, IS DCDA SIZE SUFFICIENT? | | | *DOMESTIC BACKFLOW ASSEMBLY IS SHOWING AS OVERDUE FOR | | | ANNUAL TESTING. IF IT WILL REMAIN THROUGH THE PROJECT, | | | THEN NEEDS TO BE TESTED BY LICENSED PLUMBER. | | | RESPECTFULLY, | | | MARK HURLEY [email protected] |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
F |
Date |
06-02-2023 |
|
|
Cont ID |
|
| Sent By |
jbjoseph |
Date |
06-02-2023 |
Time |
12:21 |
Rev Time |
|
| Received By |
jbjoseph |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2023-06-02 12:23:11 | PLEASE PROVIDE THE FOLLOWING: | | | 1. DUMPSTER ENCLOSURE DETAILS FOR SANITATION SERVICE | | | (I.E. SOLID WASTE CONTAINER(S) TYPE, COLLECTION | | | LOCATION, ETC.). FOR A FREESTANDING SITE DUMPSTER | | | ENCLOSURE. THE ENCLOSURE SHALL COMPLY WITH THE LATEST | | | REVISION OF CITY OF WEST PALM BEACH GENERAL | | | CONSTRUCTION GARBAGE ENCLOSURE STANDARD. GC-7 | | | 2. PROVIDE AN AUTOTURN PLAN.?? TRAVEL PATHS SHOULD | | | BEGIN OUTSIDE THE SITE ILLUSTRATING THE TURN ONTO THE | | | PRIMARY ENTRY ROAD/DRIVE, MANEUVERING AROUND THE SITE, | | | AND COMPLETED WITH AN ILLUSTRATION DEMONSTRATING | | | EXITING THE SITE. | | | PATHS MUST ILLUSTRATE THE FULL VEHICLE SWEPT PATH | | | (INCLUDING WHEEL TRACKS AND OUT-TO-OUT VEHICLE OVERHANG | | | SWEEP) AND MUST INDICATE A CLEAR, UNOBSTRUCTED TRAVEL | | | AROUND THE SITE WITHOUT IMPACT/COLLISIONS TO BUILDINGS, | | | CURBS, LANDSCAPING, PARKING SPACES, VEHICLES, ETC??? | | | AUTOTURN EXHIBIT WITH DYNAMIC ENVELOPE AND THE | | | VEHICLE'S WHEEL PATH IDENTIFIED WITH DIFFERENT COLORS | | | FOR THE SANITATION SERVICE, FRONT LOADER TRUCK WITH THE | | | FOLLOWING SPECS: | | | - DUAL AXLES | | | - TRUCK LENGTH: 35 FT | | | -TIRE PATH WIDTH: 8FT | | | - DYNAMIC ENVELOPE WIDTH: 11 FT | | | - TURNING RADIUS: | | | - SAE TURNING RADIUS: 325FT | | | - CURB TO CURB DIAMETER: 74 FT | | | - WALL TO WAII DIAMETER: 86 3FT | | | | | | BRUCELY A. JOSEPH | | | PUBLIC WORKS PROGRAM MANAGER | | | [email protected] |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
F |
Date |
06-27-2023 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
06-27-2023 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
06-27-2023 |
Time |
13:32 |
Sent To |
|
|
| Notes |
| 2023-06-27 13:29:16 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE | | | 5/9/2023 SUBMITTAL. | | | | | | 1. [PARTIALLY SATISFIED - ADD THE CONVERSION EQUATION | | | TO NGVD1929 TO THE ENGINEERING PLANS] THE CITY'S | | | OFFICIAL VERTICAL DATUM IS NGVD1929. THE CITY HAS | | | ALLOWED THE USE OF NAVD1988 AS LONG AS THE CONVERSION | | | EQUATION TO NGVD1929 AT THE PROJECT LOCATION IS | | | PROVIDED. PROVIDE VERTICAL DATUM REFERENCE AND | | | CONVERSION TO NGVD1929 ON THE ENGINEERING PLANS. | | | | | | 2. [SATISFIED - THE PARKING SPACES DO NOT APPEAR TO BE | | | REDUCED IN LENGTH TO REDUCE THE AMOUNT OF IMPERVIOUS | | | AREA] CONSIDER REDUCING THE PARKING SPACES AND PROVIDE | | | TWO FEET OF LANDSCAPED OVERHANG. | | | | | | 3. [NOT SATISFIED - PROVIDE A COPY OF THE DRAINAGE | | | EASEMENT] PROVIDE DOCUMENTATION OF PERMISSIBLE | | | CONNECTION OF THE DRAINAGE SYSTEM TO ADJACENT | | | PROPERTY'S DRAINAGE SYSTEM. | | | | | | 4. [SATISFIED] OKEECHOBEE BLVD IS MAINTAINED BY FDOT. | | | ANY WORK WITHIN THE RIGHT OF WAY MAY REQUIRE A PERMIT | | | FROM FDOT. | | | | | | 5. [PARTIALLY SATISFIED - PROPOSED STORM ON THE WEST | | | SIDE OF SITE IS NOT SHOWN.] SHOW EXISTING AND PROPOSED | | | UTILITIES ON THE LANDSCAPE PLANS. | | | | | | 6. [NOT SATISFIED] ON SECTION A-A, PROVIDE WIDTH OF | | | PAVEMENT (OR RANGE OF WIDTH IF IT VARIES) FROM FACE OF | | | CURB TO FACE OF CURB. PROVIDE SWALE ALONG WEST PROPERTY | | | LINE TO PREVENT DIRECT RUNOFF ONTO THE ADJACENT | | | PROPERTY. | | | | | | 7. [PARTIALLY SATISFIED] SECTION B-B, PROVIDE SWALE TO | | | PREVENT DIRECT RUNOFF ONTO THE ADJACENT SITE OR SHOW | | | 4:1 SLOPE FROM BACK OF CURB TO EXISTING GRADE TO ALLOW | | | RUNOFF FROM THE ADJACENT SITE TO CONTINUE TO FLOW ONTO | | | THE SITE. PROPOSED IMPROVEMENTS TO THE SITE SHALL NOT | | | CAUSE NEW PONDING TO OCCUR ON ADJACENT SITES. | | | | | | 8. [NOT SATISFIED] CONNECT ROOF DRAINS DIRECTLY TO | | | DRAINAGE STRUCTURES INSTEAD OF DISCHARGING ONTO THE | | | GROUND SURFACE. | | | | | | NEW COMMENTS (5/9/2023 SUBMITTAL): | | | | | | 9. PROVIDE WRITTEN COMMENTS DESCRIBING HOW EACH OF | | | THESE COMMENTS ARE ADDRESSED. | | | | | | 10. CONFIRM INSTALLATION OF PROPOSED EXFILTRATION | | | TRENCH SLONG THE WEST PROPERTLY LINE WILL DAMAGE THE | | | ROOT SYSTEM OF THE EXISTING TREES. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | [email protected] | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
05-12-2022 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
05-12-2022 |
Time |
12:59 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
05-12-2022 |
Time |
13:00 |
Sent To |
|
|
| Notes |
| 2022-05-12 13:00:22 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | 1. THE CITY?S OFFICIAL VERTICAL DATUM IS NGVD1929. THE | | | CITY HAS ALLOWED THE USE OF NAVD1988 AS LONG AS THE | | | CONVERSION EQUATION TO NGVD1929 AT THE PROJECT LOCATION | | | IS PROVIDED. PROVIDE VERTICAL DATUM REFERENCE AND | | | CONVERSION TO NGVD1929 ON THE ENGINEERING PLANS. | | | | | | 2. CONSIDER REDUCING THE PARKING SPACES AND PROVIDE TWO | | | FEET OF LANDSCAPED OVERHANG. | | | | | | 3. PROVIDE DOCUMENTATION OF PERMISSIBLE CONNECTION OF | | | THE DRAINAGE SYSTEM TO ADJACENT PROPERTY?S DRAINAGE | | | SYSTEM. | | | | | | 4. OKEECHOBEE BLVD IS MAINTAINED BY FDOT. ANY WORK | | | WITHIN THE RIGHT OF WAY MAY REQUIRE A PERMIT FROM FDOT. | | | | | | 5. SHOW EXISTING AND PROPOSED UTILITIES ON THE | | | LANDSCAPE PLANS. | | | | | | 6. ON SECTION A-A, PROVIDE WIDTH OF PAVEMENT (OR RANGE | | | OF WIDTH IF IT VARIES) FROM FACE OF CURB TO FACE OF | | | CURB. PROVIDE SWALE ALONG WEST PROPERTY LINE TO PREVENT | | | DIRECT RUNOFF ONTO THE ADJACENT PROPERTY. | | | | | | 7. SECTION B-B, PROVIDE SWALE TO PREVENT DIRECT RUNOFF | | | ONTO THE ADJACENT SITE OR SHOW 4:1 SLOPE FROM BACK OF | | | CURB TO EXISTING GRADE TO ALLOW RUNOFF FROM THE | | | ADJACENT SITE TO CONTINUE TO FLOW ONTO THE SITE. | | | PROPOSED IMPROVEMENTS TO THE SITE SHALL NOT CAUSE NEW | | | PONDING TO OCCUR ON ADJACENT SITES. | | | | | | 8. CONNECT ROOF DRAINS DIRECTLY TO DRAINAGE STRUCTURES | | | INSTEAD OF DISCHARGING ONTO THE GROUND SURFACE. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP | | | CRITERIA. STORMWATER CALCULATIONS WILL BE REVIEWED WITH | | | THE ENGINEERING PERMIT SUBMITTAL. | | | | | | 2. PROVIDE COPY OF SFWMD ERP PERMIT BEFORE START OF | | | CONSTRUCTION. | | | | | | 3. PROVIDE EROSION CONTROL PLAN WITH THE ENGINEERING | | | PERMIT SUBMITTAL. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | 561-351-0510 (M) | | | [email protected] | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
05-10-2022 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
05-10-2022 |
Time |
09:53 |
Rev Time |
|
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-05-10 11:56:17 | 1, LIMITS OF EASEMENT ALONG EAST PROPERTY LINE SEEM TO | | | DIFFER FROM ADJOINING SURVEY. | | | 2. PROVIDE COPY OF EASEMENT/DOCUMENTATION OF USE OF | | | PARCEL BETWEEN PROPERTY AND ALLEY | | | 3. IS THERE A CROSS UTILITY AGREEMENT FOR THE SANITARY | | | TO THE WEST? | | | 4. DO NOT SEE WATER/SEWER SERVICE TO NEW BLDG'S. |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
05-06-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
05-06-2022 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-05-06 15:13:51 | TRAFFIC STUDY COMMENTS | | | 1) INSERT PROPOSED SITE PLAN IN THE APPENDIX | | | 2) PROVIDE COUNTY TPS LETTER | | | | | | SITE PLAN COMMENTS | | | 3) IS THERE AN ACCESS EASEMENT WITH THE NEIGHBORING | | | PROPERTY FOR THE NORTHERN ALLY DRIVEWAY? IF SO, PLEASE | | | PROVIDE IT | | | 4) PROVIDE AUTOTURN ANALYSIS FOR GARBAGE TRUCK AND/OR | | | SERVICE VEHICLES DRIVING IN AND OUT OF THE PROPOSED | | | DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES CLEARLY | | | DEFINED. ANALYSIS SHOULD BE PROVIDED IN A SEPARATE | | | FILE/DRAWING. PLEASE PROVIDE DOCUMENT NAME AND SHEET | | | NUMBER SHOWCASING THE ANALYSIS. | | | 5) PROVIDE WIDTH OF EACH DRIVEWAY IN THE SITE PLAN. | | | PLEASE PROVIDE DOCUMENT NAME AND SHEET NUMBER | | | 6) PROVIDE ADA RAMP(S) IF REQUIRED OR NECESSARY TO | | | ACCESS THE SIDEWALK FROM THE PROPOSED ADA PARKING | | | STALLS | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
06-01-2023 |
|
|
Cont ID |
|
| Sent By |
kdefranc |
Date |
06-01-2023 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
kdefranc |
Date |
06-01-2023 |
Time |
11:27 |
Sent To |
|
|
| Notes |
| 2023-06-01 11:28:22 | 6/1/23 - FAILED | | | | | | | | | PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN | | | RESUBMITTING: | | | A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL | | | DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION. | | | B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED | | | MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG | | | WITH ONE (1) REDUCED COPY (11 IN X 17 IN). | | | C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO | | | ADDITIONAL COMMENTS. | | | D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE | | | ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE | | | CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL | | | REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION. | | | E. PLEASE NOTE THAT YOU ARE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. A RESUBMITTAL FEE OF | | | 20% OF THE ORIGINAL APPLICATION FEE WILL BE ASSESSED | | | AFTER THE FIRST RESUBMITTAL. | | | | | | REQUIRED MATERIALS MUST BE PROVIDED: | | | F. PLEASE PROVIDE LETTERS FROM PUBLIC UTILITIES | | | (FLORIDA PUBLIC UTILITIES, COMCAST CABLE | | | COMMUNICATIONS, CITY OF WEST PALM BEACH UTILITIES) | | | CONFIRMING THAT THE PROPOSED PROJECT DOES NOT ENCROACH | | | INTO THEIR EASEMENTS OR OTHERWISE INTERFERE WITH THE | | | PROVISIONS OF THEIR SERVICES. [NOT SATISFIED] | | | G. PLEASE PROVIDE A TRAFFIC CONCURRENCY/PERFORMANCE | | | STANDARD REVIEW (TPS) LETTER FROM THE PALM BEACH COUNTY | | | TRAFFIC DIVISION FOR THE SUBJECT PROJECT. [NOT | | | SATISFIED] | | | H. PLEASE PROVIDE REVISED PLANS ADDRESSING THE REVIEW | | | COMMENTS BELOW. [PARTIALLY SATISFIED] | | | I. PLEASE PROVIDE/INDICATE/DEMONSTRATE CONSISTENT | | | INFORMATION ON ALL THE DIFFERENT PLANS AND REQUIRED | | | MATERIALS WITHIN THE APPLICATION PACKET RESUBMITTAL. | | | [SATISFIED] | | | | | | PLANS REVIEW COMMENTS MUST BE ADDRESSED: | | | 1. PLEASE IDENTIFY/INDICATE/LABEL THE EXISTING PROPERTY | | | LINE ON THE SITE PLAN, SHEET SP-1 OF 1. [SATISFIED] | | | 2. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION | | | AND DIMENSIONS OF THE EXISTING AND PROPOSED PRIVATE AND | | | PUBLIC SIDEWALKS ON ALL THE DIFFERENT PLANS, | | | ACCORDINGLY. [PARTIALLY SATISFIED] | | | 3. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION | | | AND DIMENSIONS OF THE PROPOSED DISABLED PARKING SPACES | | | IN THE GRAPHIC ON ALL THE DIFFERENT PLANS, ACCORDINGLY. | | | [SATISFIED] | | | 4. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION, | | | DIMENSIONS, AND USE OF THE PROPOSED OUTDOOR STORAGE | | | SPACE/SURFACE DISPLAY AREA ON ALL THE DIFFERENT PLANS, | | | ACCORDINGLY. [SATISFIED] | | | 5. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION, | | | HEIGHT, AND SIZE OF ALL FREESTANDING SIGNS AND OTHER | | | ACCESSORY STRUCTURES (INCLUDING, BUT NOT LIMITED TO, | | | THE OUTDOOR ILLUMINATION) ON ALL THE DIFFERENT PLANS, | | | ACCORDINGLY. [PARTIALLY SATISFIED] | | | 6. PLEASE IDENTIFY/INDICATE/DEMONSTRATE EXISTING AND | | | PROPOSED FIRE HYDRANTS (OR OPERATIONAL EQUIVALENTS) | | | WITHIN 250 FEET OF THE PROPOSED STRUCTURES(S) ON THE | | | SITE PLAN, SHEET SP-1 OF 1. [SATISFIED] | | | 7. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF | | | ANY SPECIAL UTILITY STRUCTURES AND ABOVE GROUND | | | APPURTENANCES ON THE SITE PLAN, SHEET SP-1 OF 1. | | | [SATISFIED] | | | 8. PLEASE IDENTIFY/INDICATE/DEMONSTRATE DRIVEWAYS, CURB | | | CUTS, AND TURNING LANES ADJACENT TO AND ACROSS FROM THE | | | SUBJECT PROPERTY ON ALL THE DIFFERENT PLANS, | | | ACCORDINGLY. [PARTIALLY SATISFIED] | | | 9. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE PROPOSED | | | TRAFFIC DIRECTION PAVEMENT MARKINGS FOR THE WEST | | | DRIVEWAY NEAR THE OKEECHOBEE BOULEVARD ACCESS POINT ON | | | ALL THE DIFFERENT PLANS, ACCORDINGLY. [SATISFIED] | | | 10. PLEASE IDENTIFY/INDICATE THE FUTURE LAND USE IN THE | | | SITE DATA TABLE ON THE SITE PLAN, SHEET SP-1 OF 1. | | | [SATISFIED] | | | 11. PLEASE IDENTIFY/INDICATE THE EXISTING AND PROPOSED | | | USE IN THE SITE DATA TABLE ON THE SITE PLAN, SHEET SP-1 | | | OF 1. [SATISFIED] | | | 12. PLEASE IDENTIFY/INDICATE THE TOTAL LOT/PARCEL AREA | | | (NOT INCLUDING THE EXISTING EASEMENT AREA) IN THE SITE | | | DATA TABLE AND PROPERTY DEVELOPMENT REGULATIONS TABLE | | | ON THE SITE PLAN, SHEET SP-1 OF 1. [SATISFIED] | | | 13. PLEASE IDENTIFY/INDICATE EXISTING AND PROPOSED LOT | | | COVERAGE BY BUILDING (SQUARE FOOTAGE AND PERCENTAGE) IN | | | THE SITE DATA TABLE AND PROPERTY DEVELOPMENT | | | REGULATIONS TABLE (CONSISTENT WITH THE INFORMATION | | | IDENTIFIED/INDICATED/DEMONSTRATED IN THE GRAPHIC) ON | | | THE SITE PLAN, SHEET SP-1 OF 1. PLEASE REFER TO THE | | | DEFINITION OF LOT COVERAGE PROVIDED IN THE ZLDR SECTION | | | 94-145. [NOT SATISFIED] | | | 14. PLEASE IDENTIFY/INDICATE EXISTING AND PROPOSED LOT | | | COVERAGE BY IMPERMEABLE SURFACE (SQUARE FOOTAGE AND | | | PERCENTAGE) IN THE SITE DATA TABLE AND PROPERTY | | | DEVELOPMENT REGULATIONS TABLE (CONSISTENT WITH THE | | | INFORMATION IDENTIFIED/INDICATED/DEMONSTRATED IN THE | | | GRAPHIC) ON THE SITE PLAN, SHEET SP-1 OF 1. [NOT | | | SATISFIED] | | | 15. PLEASE IDENTIFY/INDICATE EXISTING AND PROPOSED | | | FLOOR AREA RATIO (SQUARE FOOTAGE AND RATIO) IN THE SITE | | | DATA TABLE AND PROPERTY DEVELOPMENT REGULATIONS TABLE | | | (CONSISTENT WITH THE INFORMATION | | | IDENTIFIED/INDICATED/DEMONSTRATED IN THE GRAPHIC) ON | | | THE SITE PLAN, SHEET SP-1 OF 1. PLEASE REFER TO THE | | | DEFINITION OF FLOOR AREA RATIO PROVIDED IN THE ZLDR | | | SECTION 94-145. [NOT SATISFIED] | | | 16. PLEASE IDENTIFY/INDICATE THE SQUARE FOOTAGE FOR THE | | | MINIMUM AND PROPOSED LANDSCAPE AREA AND OPEN SPACE AREA | | | IN THE SITE DATA TABLE AND PROPERTY DEVELOPMENT | | | REGULATIONS TABLE (CONSISTENT WITH THE INFORMATION | | | IDENTIFIED/INDICATED/DEMONSTRATED IN THE GRAPHIC) ON | | | THE SITE PLAN, SHEET SP-1 OF 1. [NOT SATISFIED] | | | 17. THE REQUIRED AND PROPOSED NUMBER OF BICYCLE PARKING | | | SPACES IDENTIFIED/INDICATED ARE NOT CONSISTENT WITH THE | | | MINIMUM NUMBER OF BICYCLE PARKING SPACES REQUIREMENT | | | PER THE ZLDR SUBSECTION 94-485(Q), SO PLEASE REVISE | | | ACCORDINGLY IN THE SITE DATA TABLE ON THE SITE PLAN, | | | SHEET SP-1 OF 1. [NOT SATISFIED] | | | 18. PLEASE PROVIDE THE BIKE RACK AREA DIMENSIONS FOR | | | THE PROPOSED BICYCLE PARKING SPACES IN THE TYPICAL BIKE | | | RACK DETAILS ON THE SITE PLAN, SHEET SP-1 OF 1. | | | [PARTIALLY SATISFIED] | | | 19. PLEASE PROVIDE THE STANDARD CITY DETAILS OF PARKING | | | (STANDARD AND ADA), ADA RAMPS, DRIVEWAYS, DUMPSTERS AND | | | SIGNS ON THE SITE PLAN, SHEET SP-1 OF 1 AND/OR SEPARATE | | | SHEET. [NOT SATISFIED] | | | | | | ADDITIONAL REVIEW COMMENTS MUST BE ADDRESSED: | | | 20. IN REFERENCE TO PREVIOUS REVIEW COMMENT 8., | | | IDENTIFY/INDICATE/DEMONSTRATE THE DRIVEWAY CURB CUT FOR | | | THE ADJACENT PARCEL TO THE WEST ON THE PLANS. | | | 21. IN REFERENCE TO PREVIOUS REVIEW COMMENT 18., THE | | | REQUIRED MINIMUM DISTANCE BETWEEN BIKE RACKS IS 30 | | | INCHES AND THE REQUIRE MINIMUM DEPTH FOR BIKE RACKS IS | | | 72 INCHES. THEREFORE, UPDATE THE BIKE RACK DETAILS, | | | ACCORDINGLY. | | | 22. IT HAS BEEN IDENTIFIED THAT THE PROPOSED TOTAL | | | ENCLOSED AREA (NOT INCLUDING THE SECOND AND THIRD | | | FLOORS) IS 33,936 SQUARE FEET. THEREFORE, PLEASE REVISE | | | THE PLANS AND PARKING DATA, ACCORDINGLY. | | | | | | | | | KEVIE DEFRANC | | | PLANNER - PLANNING DIVISION | | | [email protected] | | | 561-822-1449 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
05-06-2022 |
|
|
Cont ID |
|
| Sent By |
kdefranc |
Date |
05-06-2022 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
kdefranc |
Date |
05-06-2022 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2022-05-06 14:35:57 | 5/6/22 - FAILED | | | | | | | | | PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN | | | RESUBMITTING: | | | A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL | | | DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION. | | | B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED | | | MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG | | | WITH ONE (1) REDUCED COPY (11 IN X 17 IN). | | | C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO | | | ADDITIONAL COMMENTS. | | | D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE | | | ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE | | | CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL | | | REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION. | | | E. PLEASE NOTE THAT YOU ARE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. A RESUBMITTAL FEE OF | | | 20% OF THE ORIGINAL APPLICATION FEE WILL BE ASSESSED | | | AFTER THE FIRST RESUBMITTAL. | | | | | | REQUIRED MATERIALS MUST BE PROVIDED: | | | F. PLEASE PROVIDE LETTERS FROM PUBLIC UTILITIES | | | (FLORIDA PUBLIC UTILITIES, COMCAST CABLE | | | COMMUNICATIONS, CITY OF WEST PALM BEACH UTILITIES) | | | CONFIRMING THAT THE PROPOSED PROJECT DOES NOT ENCROACH | | | INTO THEIR EASEMENTS OR OTHERWISE INTERFERE WITH THE | | | PROVISIONS OF THEIR SERVICES. | | | G. PLEASE PROVIDE A TRAFFIC CONCURRENCY/PERFORMANCE | | | STANDARD REVIEW (TPS) LETTER FROM THE PALM BEACH COUNTY | | | TRAFFIC DIVISION FOR THE SUBJECT PROJECT. | | | H. PLEASE PROVIDE REVISED PLANS ADDRESSING THE REVIEW | | | COMMENTS BELOW. | | | I. PLEASE PROVIDE/INDICATE/DEMONSTRATE CONSISTENT | | | INFORMATION ON ALL THE DIFFERENT PLANS AND REQUIRED | | | MATERIALS WITHIN THE APPLICATION PACKET RESUBMITTAL. | | | | | | PLANS REVIEW COMMENTS MUST BE ADDRESSED: | | | 1. PLEASE IDENTIFY/INDICATE/LABEL THE EXISTING PROPERTY | | | LINE ON THE SITE PLAN, SHEET SP-1 OF 1. | | | 2. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION | | | AND DIMENSIONS OF THE EXISTING AND PROPOSED PRIVATE AND | | | PUBLIC SIDEWALKS ON ALL THE DIFFERENT PLANS, | | | ACCORDINGLY. | | | 3. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION | | | AND DIMENSIONS OF THE PROPOSED DISABLED PARKING SPACES | | | IN THE GRAPHIC ON ALL THE DIFFERENT PLANS, ACCORDINGLY. | | | 4. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION, | | | DIMENSIONS, AND USE OF THE PROPOSED OUTDOOR STORAGE | | | SPACE/SURFACE DISPLAY AREA ON ALL THE DIFFERENT PLANS, | | | ACCORDINGLY. | | | 5. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION, | | | HEIGHT, AND SIZE OF ALL FREESTANDING SIGNS AND OTHER | | | ACCESSORY STRUCTURES (INCLUDING, BUT NOT LIMITED TO, | | | THE OUTDOOR ILLUMINATION) ON ALL THE DIFFERENT PLANS, | | | ACCORDINGLY. | | | 6. PLEASE IDENTIFY/INDICATE/DEMONSTRATE EXISTING AND | | | PROPOSED FIRE HYDRANTS (OR OPERATIONAL EQUIVALENTS) | | | WITHIN 250 FEET OF THE PROPOSED STRUCTURES(S) ON THE | | | SITE PLAN, SHEET SP-1 OF 1. | | | 7. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF | | | ANY SPECIAL UTILITY STRUCTURES AND ABOVE GROUND | | | APPURTENANCES ON THE SITE PLAN, SHEET SP-1 OF 1. | | | 8. PLEASE IDENTIFY/INDICATE/DEMONSTRATE DRIVEWAYS, CURB | | | CUTS, AND TURNING LANES ADJACENT TO AND ACROSS FROM THE | | | SUBJECT PROPERTY ON ALL THE DIFFERENT PLANS, | | | ACCORDINGLY. | | | 9. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE PROPOSED | | | TRAFFIC DIRECTION PAVEMENT MARKINGS FOR THE WEST | | | DRIVEWAY NEAR THE OKEECHOBEE BOULEVARD ACCESS POINT ON | | | ALL THE DIFFERENT PLANS, ACCORDINGLY. | | | 10. PLEASE IDENTIFY/INDICATE THE FUTURE LAND USE IN THE | | | SITE DATA TABLE ON THE SITE PLAN, SHEET SP-1 OF 1. | | | 11. PLEASE IDENTIFY/INDICATE THE EXISTING AND PROPOSED | | | USE IN THE SITE DATA TABLE ON THE SITE PLAN, SHEET SP-1 | | | OF 1. | | | 12. PLEASE IDENTIFY/INDICATE THE TOTAL LOT/PARCEL AREA | | | (NOT INCLUDING THE EXISTING EASEMENT AREA) IN THE SITE | | | DATA TABLE AND PROPERTY DEVELOPMENT REGULATIONS TABLE | | | ON THE SITE PLAN, SHEET SP-1 OF 1. | | | 13. PLEASE IDENTIFY/INDICATE EXISTING AND PROPOSED LOT | | | COVERAGE BY BUILDING (SQUARE FOOTAGE AND PERCENTAGE) IN | | | THE SITE DATA TABLE AND PROPERTY DEVELOPMENT | | | REGULATIONS TABLE (CONSISTENT WITH THE INFORMATION | | | IDENTIFIED/INDICATED/DEMONSTRATED IN THE GRAPHIC) ON | | | THE SITE PLAN, SHEET SP-1 OF 1. PLEASE REFER TO THE | | | DEFINITION OF LOT COVERAGE PROVIDED IN THE ZLDR SECTION | | | 94-145. | | | 14. PLEASE IDENTIFY/INDICATE EXISTING AND PROPOSED LOT | | | COVERAGE BY IMPERMEABLE SURFACE (SQUARE FOOTAGE AND | | | PERCENTAGE) IN THE SITE DATA TABLE AND PROPERTY | | | DEVELOPMENT REGULATIONS TABLE (CONSISTENT WITH THE | | | INFORMATION IDENTIFIED/INDICATED/DEMONSTRATED IN THE | | | GRAPHIC) ON THE SITE PLAN, SHEET SP-1 OF 1. | | | 15. PLEASE IDENTIFY/INDICATE EXISTING AND PROPOSED | | | FLOOR AREA RATIO (SQUARE FOOTAGE AND RATIO) IN THE SITE | | | DATA TABLE AND PROPERTY DEVELOPMENT REGULATIONS TABLE | | | (CONSISTENT WITH THE INFORMATION | | | IDENTIFIED/INDICATED/DEMONSTRATED IN THE GRAPHIC) ON | | | THE SITE PLAN, SHEET SP-1 OF 1. PLEASE REFER TO THE | | | DEFINITION OF FLOOR AREA RATIO PROVIDED IN THE ZLDR | | | SECTION 94-145. | | | 16. PLEASE IDENTIFY/INDICATE THE SQUARE FOOTAGE FOR THE | | | MINIMUM AND PROPOSED LANDSCAPE AREA AND OPEN SPACE AREA | | | IN THE SITE DATA TABLE AND PROPERTY DEVELOPMENT | | | REGULATIONS TABLE (CONSISTENT WITH THE INFORMATION | | | IDENTIFIED/INDICATED/DEMONSTRATED IN THE GRAPHIC) ON | | | THE SITE PLAN, SHEET SP-1 OF 1. | | | 17. THE REQUIRED AND PROPOSED NUMBER OF BICYCLE PARKING | | | SPACES IDENTIFIED/INDICATED ARE NOT CONSISTENT WITH THE | | | MINIMUM NUMBER OF BICYCLE PARKING SPACES REQUIREMENT | | | PER THE ZLDR SUBSECTION 94-485(Q), SO PLEASE REVISE | | | ACCORDINGLY IN THE SITE DATA TABLE ON THE SITE PLAN, | | | SHEET SP-1 OF 1. | | | 18. PLEASE PROVIDE THE BIKE RACK AREA DIMENSIONS FOR | | | THE PROPOSED BICYCLE PARKING SPACES IN THE TYPICAL BIKE | | | RACK DETAILS ON THE SITE PLAN, SHEET SP-1 OF 1. | | | 19. PLEASE PROVIDE THE STANDARD CITY DETAILS OF PARKING | | | (STANDARD AND ADA), ADA RAMPS, DRIVEWAYS, DUMPSTERS AND | | | SIGNS ON THE SITE PLAN, SHEET SP-1 OF 1 AND/OR SEPARATE | | | SHEET. | | | | | | | | | KEVIE DEFRANC | | | PLANNER - PLANNING DIVISION | | | [email protected] | | | 561-822-1449 | | | |
|
|
| |