| 2022-05-09 11:35:26 | COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR, |
| | ENGINEERING SERVICES DEPT., 561-494-1098 |
| | [email protected] : |
| | |
| | GENERAL: |
| | O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND |
| | INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER |
| | (Z-XXXXXXXX). |
| | O THE CITY OF WEST PALM BEACH HAS A NUMBER OF |
| | REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY |
| | AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND |
| | WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE |
| | DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK |
| | BELOW: |
| | A. HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WP |
| | B_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FUL |
| | L-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97 |
| | B1960045731D3658206F27451722716EF |
| | B. THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE |
| | FOUND HERE: |
| | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR |
| | MS,-PERMITS-APPLICATIONS |
| | C. ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM |
| | BEACH, FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, |
| | ADOPTED SEPT. 22, 2008. (SUPPLEMENT NO. 18) |
| | CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL, |
| | SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER |
| | SERVICE FACILITIES OF THE CITY. |
| | THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE |
| | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY |
| | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, |
| | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. |
| | O AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH |
| | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, |
| | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR |
| | MORE INFORMATION, REFER TO THE LINK BELOW: |
| | A. HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PU |
| | BLICATIONS/BACKFLOW-CROSS-CONNECTION- CONTROL-MANUAL |
| | O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY |
| | OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC |
| | RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF |
| | YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE |
| | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL |
| | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT |
| | [email protected] OR 561-494-1079 FOR FURTHER |
| | ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION |
| | ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD |
| | SURVEY, POT-HOLING, SOFT DIGS ETC. |
| | |
| | BACKFLOW ASSEMBLY AND METERS: |
| | O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER |
| | SERVICES (MATERIAL AND SIZE) AND WATER METERS, ALONG |
| | WITH WHAT IS HAPPENING TO THEM. |
| | O SHOW EXISTING AND PROPOSED DEDICATED UTILITY |
| | EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO |
| | PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO |
| | STRUCTURES WITHIN EASEMENT. |
| | O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION |
| | OF WATER METER AND BACKFLOW |
| | PREVENTION. |
| | O BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY |
| | OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER |
| | METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO |
| | PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE |
| | INSTALLED ABOVE-GROUND ONLY. |
| | O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE |
| | NOTE USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA. |
| | |
| | WATER/WASTEWATER PLAN: |
| | O PROVIDE VERTICAL DATUM AND DATUM CONVERSION |
| | INFORMATION (NAVD 1988 AND NGVD 1929). |
| | O SHOW PROJECT ADDRESS ON ALL PLAN SHEETS. |
| | O PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE |
| | STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC. |
| | O PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND |
| | DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND |
| | SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH |
| | PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE |
| | AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS, |
| | BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO |
| | BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS, |
| | DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS, |
| | ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT |
| | ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF |
| | SANITARY SEWER LINES. |
| | O GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR |
| | SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE |
| | PROFILE VIEW. |
| | O DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW FOR ALL |
| | SANITARY AND STORM SEWERS. |
| | O SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT |
| | MATERIAL. |
| | O PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED |
| | UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC, |
| | ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION |
| | FACILITIES LOCATED ON THE RIGHT-OF-WAY. |
| | O PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER |
| | AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD |
| | DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS. |
| | O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY |
| | TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT |
| | APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING |
| | AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, |
| | MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS |
| | SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 |
| | FOR WATER. |
| | O PROVIDE FIRE FLOW TEST DATA. |
| | O WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL |
| | BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY |
| | PROPOSED LENGTH IN FEET. |
| | O CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY |
| | SEWER ARE REQUIRED. |
| | O PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE |
| | JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET. |
| | O ADD NOTE TO PLANS SPECIFYING CITY?S DOWNSTREAM LIFT |
| | STATION NUMBER. |
| | O LABEL WATER LINES AS PRIVATE WHERE APPLICABLE. |
| | O PLEASE SHOW AND LABEL EXISTING AND PROPOSED GREASE |
| | TRAPS (IF ANY). |
| | O PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN |
| | OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER. |
| | O PLEASE RESPOND TO ALL COMMENTS IN WRITING AND INCLUDE |
| | PROJECT NAME, ADDRESS AND PERMIT NUMBER (Z-XXXXXXXX). |
| | O ADD ALL RELEVANT CITY OF WEST PALM BEACH STANDARD |
| | DETAILS FOR WATER & SEWER. |
| | O PROVIDE UPDATED (EXISTING AND PROPOSED) PERVIOUS & |
| | IMPERVIOUS DATA. |
| | |
| | COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE |
| | SUPER., WPB PUBLIC UTILITIES, 561-822-2262 OR |
| | [email protected]: |
| | |
| | -WILL THE CONCESSION BUILDING HAVE FIRE SPRINKLERS? |
| | |
| | -IF THERE WILL BE A GREASE TRAP OUTSIDE, SHOW IT ON THE |
| | CIVIL PLANS. |
| | |
| | -IS THERE A HARDSCAPE PATH TO THE ACCESSIBLE BATHROOM? |
| | |
| | -SURVEY REPORT NOTE 6 SAYS THAT NO SEARCH OF PUBLIC |
| | RECORDS HAS BEEN PERFORMED. WHEN WILL IT BE PERFORMED? |
| | |
| | -ALL OF THE POTABLE WATER WORK APPEARS TO BE PLUMBING. |
| | NOT AWARE OF ANY WPB WATER METERS IN CLOSE PROXIMITY TO |
| | THAT BUILDING. WPB UTILITIES CANNOT PROVIDE ANY METERS |
| | THERE. |
| | |
| | |