Plan Review Details - Project Z22030030
| Plan Review Stops For Project Z22030030 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
05-11-2022 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
05-11-2022 |
Time |
19:26 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
05-11-2022 |
Time |
19:26 |
Sent To |
|
|
| Notes |
| 2022-05-11 19:32:00 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. ACCESSIBLE ROUTE. SITE PLAN, SHEET SP.1, DOES NOT | | | SHOW A WHEELCHAIR ACCESSIBLE ROUTE FROM THE SIDEWALK TO | | | THE BUILDING ENTRANCE. WHEN SUBMITTED FOR PERMIT, THE | | | PLANS SHALL SHOW AT LEAST ONE ACCESSIBLE ROUTE, | | | COMPLYING WITH SECTIONS 206.2 AND 402.2 OF FLORIDA | | | ACCESSIBILITY CODE, FROM THE PUBLIC RIGHT-OF-WAY TO ALL | | | ACCESSIBLE BUILDING OR FACILITY ENTRANCES. | | | | | | 3. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, | | | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR | | | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, | | | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE | | | FLORIDA BUILDING CODE. | | | | | | 4. GREASE INTERCEPTOR. WITH THE PROPOSED USE BEING | | | RESTAURANT, A GREASE INTERCEPTOR WILL BE REQUIRED. FOR | | | INFORMATION ON THE REQUIRED TYPE, SIZE AND LOCATION, | | | PLEASE CONTACT RYAN BROWN, CHIEF PLUMBING INSPECTOR, | | | DEVELOPMENT SERVICES DEPARTMENT, AT (561) 805-6692, OR | | | BY EMAIL: [email protected] | | | | | | 5. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, | | | FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, | | | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, | | | SITE IRRIGATION, ETC. | | | | | | 6. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND | | | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF | | | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL | | | NEIGHBORING PROPERTIES. | | | | | | 7. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT | | | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL | | | HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION | | | OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING, | | | CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT | | | (561) 805 6659, OR BY EMAIL: [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
P |
Date |
05-09-2022 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
05-09-2022 |
Time |
|
Rev Time |
|
| Received By |
rrossano |
Date |
05-09-2022 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
08-02-2022 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
08-02-2022 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
08-02-2022 |
Time |
12:21 |
Sent To |
|
|
| Notes |
| 2022-08-02 12:22:08 | FIRE HAS NO OBJECTIONS TO THE PROPOSED AND APPROVES. | | | | | | FIRE'S APPROVAL OF THIS SUBMITTED PROJECT MAY NOT | | | CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | IF APPLICABLE, FIRE SHALL REVIEW ALL SUBMITTED PROJECT | | | PLANS AT THE APPLICABLE TIME AND IN ACCORDANCE WITH THE | | | REQUIREMENTS OF ALL APPLICABLE FIRE CODES AND | | | STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
05-04-2022 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
05-04-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
05-04-2022 |
Time |
11:56 |
Sent To |
|
|
| Notes |
| 2022-05-04 12:03:05 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE DEPARTMENT. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. THE FOLLOWING COMMENTS ARE INTENDED | | | TO PROVIDE GUIDANCE FOR BUILDING PLAN SUBMITTAL. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING(S) SHALL COMPLY | | | WITH THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION | | | CODE, INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE | | | CODES. | | | | | | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE | | | OCCUPANCY TYPE PER THE FLORIDA FIRE PREVENTION CODE. | | | | | | 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE | | | LOAD CALCULATION IS INCLUDED, AND THAT ADEQUATE WATER | | | SUPPLY IS EXISTING OR WILL BE PROVIDED. | | | | | | 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER | | | THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY | | | ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM, | | | ENSURE THEY COMPLY WITH THE REQUIREMENTS OF F.A.C. 61G | | | AND SUBMITTED WITH THE MASTER PERMIT. | | | | | | A PROPOSED NIGHTCLUB, IF APPLICABLE, REQUIRES A FIRE | | | SPRINKLER SYSTEM. | | | | | | 9A. THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE | | | LOCATIONS SHALL MEET AND BE INSTALLED PER THE | | | REQUIREMENTS OF NFPA 24 AND SHALL BE COORDINATED WITH | | | THE OFFICE OF FIRE MARSHAL, THE CITY'S ENGINEERS | | | OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S PLANNING | | | AND ZONING OFFICE. | | | | | | 10. COMPLETE LIFE SAFETY PLANS FOR THE OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, EXIT SEPARATION DISTANCES, COMMON PATHS OF | | | TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, EMERGENCY | | | LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE | | | EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES | | | AND EQUIPMENT. | | | | | | 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE | | | SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY | | | DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS. | | | | | | 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL. | | | | | | 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
P |
Date |
07-06-2022 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
07-06-2022 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
07-06-2022 |
Time |
14:22 |
Sent To |
|
|
| Notes |
| 2022-07-06 14:22:51 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: 2649 ELECTRONICS WAY Z22030030 | | | JULY 6, 2022 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. SATISFIED. PROVIDE THE LOT SQUARE FOOTAGE AND OPEN | | | SPACE CALCULATIONS ON THE SITE AND LANDSCAPE PLAN AND | | | MAKE SURE THEY ARE CONSISTENT. INDICATE IF LOT SQUARE | | | FOOTAGE IS FOR THE ENTIRE PARCEL OR EACH PHASE. IF | | | PROPOSING A SEPARATE LOT, LANDSCAPE BUFFERS MUST BE | | | PROVIDED ALONG ALL LOT LINES. | | | | | | 2. SATISFIED. SHOW THE CALCULATIONS FOR MINIMUM SHADE | | | TREE AND FLOWERING TREE REQUIREMENTS PER SECTION | | | 94-443(C)(2)B. BASED ON REQUIRED OPEN SPACE OF 40%. | | | LANDSCAPE PLAN SHOWS A DIFFERENT NUMBER FROM THE SITE | | | PLAN. | | | | | | 3. SATISFIED. SHOW THE LOCATIONS OF REQUIRED 10 FOOT | | | AND 5 FOOT LANDSCAPE BUFFERS ON THE SITE PLAN AND | | | LANDSCAPE PLAN PER SECTION 94-443(D) FOR THE ENTIRE | | | PARCEL. THE CONSTRUCTION MAY NEED TO BE PHASED FOR THE | | | FINAL INSTALLATION OF THE BUFFERS. | | | EAST BUFFER IS 133 FT REQUIRING 5 TREES | | | WEST BUFFER MUST BE INCLUDED, CAN BE OUTSIDE | | | MAINTENANCE EASEMENT. 84.83 FEET REQUIRES 3 TREES. | | | SOUTH BUFFER IS 369.26 FEET, REQUIRES 13 TREES. | | | | | | | | | 4. SATISFIED. SHOW LOCATIONS OF ALL PROPOSED WATER, | | | SEWER AND DRAINAGE LINES ON THE LANDSCAPE PLAN. | | | | | | | | | 5. SATISFIED. SHOW LOCATIONS OF FPL TRANSFORMER ON THE | | | LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH LANDSCAPING. | | | PROVIDE SCREENING. | | | TRANSFORMER WAS NOT LOCATED. | | | | | | | | | 6. SATISFIED. PROVIDE SCREENING FOR ALL GROUND MOUNTED | | | VALVES AND EQUIPMENT. LOCATIONS OF BACKFLOWS NEEDS TO | | | BE SHOWN. | | | | | | 7. SATISFIED. FLORIDA FRIENDLY POINTS TAKEN FOR | | | ADDITIONAL TREES IN PARKING AREA, COULD NOT VERIFY. | | | | | | ADDITIONAL COMMENTS 4/30/21: | | | | | | 8. SATISFIED. HEDGE MUST BE PROVIDED ON THE 3 NON | | | ACCESS SIDES OF THE DUMPSTER ENCLOSURE. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
05-09-2022 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
05-09-2022 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
05-09-2022 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2022-05-09 10:58:59 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: 2649 ELECTRONICS WAY Z22030030 | | | MAY 9, 2022 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. SHOW LOCATION OF FPL TRANSFORMER ON THE LANDSCAPE | | | PLAN AND RESOLVE CONFLICTS WITH LANDSCAPING. PROVIDE | | | SCREENING. | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
P |
Date |
05-02-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
05-02-2022 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
05-02-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-05-02 13:27:56 | PUBLIC WORKS HAS NO OBJECTION TO THE PROPOSED | | | AMENDMENT. | | | | | | MATT HEJZI | | | DEPT.OF PUBLIC WORKS | | | [email protected] | | | 561-822-2045 |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
3 |
Status |
P |
Date |
08-02-2022 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
08-02-2022 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
08-02-2022 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2022-08-02 16:12:50 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE | | | 7/15/2022 SUBMITTAL: | | | | | | 1. [SATISFIED - AN EXTRA PIPE WAS ADDED TO THE CATCH | | | BASIN ON THE NORTH SIDE OF 27TH STREET. ADVISE WHERE | | | THIS INFORMATION CAME FROM.] REVISE THE LAYOUT OF THE | | | EXISTING STORM PIPE CROSSING 27TH STREET BY MOVING THE | | | NORTH END OF THE PIPE FROM THE CATCH BASIN (WITH RIM | | | ELEVATION 12.28 FT NAVD) TO A MANHOLE THAT IS LOCATED | | | IN THE SWALE OF ELECTRONICS WAY EAST OF THE CATCH | | | BASIN. THEN ADD AN EXISTING 36 INCH RCP PIPE BETWEEN | | | THE MANHOLE AND THE CATCH BASIN TO THE WEST. | | | | | | 2. [SATISFIED] REVIEW THE PROPOSED GRADING OF THE | | | INTERIOR SWALE ALONG THE NORTH PERIMETER. NEARLY 12.5 | | | FEET IS NEEDED BETWEEN THE CORNER OF THE SIDEWALK (AT | | | NORTHWEST CORNER OF THE BUILDING) AND THE NORTH | | | PROPERTY LINE BUT THERE IS ONLY ABOUT 10.5 FEET. | | | APPROXIMATELY 12.5 FEET IS NEEDED BETWEEN THE BIKE RACK | | | AND NORTH PROPERTY LINE BUT ONLY 10 FEET IS AVAILABLE | | | (SECTION B-B). | | | | | | 3. [SATISFIED] SECTION D-D - INDICATE HOW THE GROUND | | | WILL SLOPE BETWEEN THE FENCE AND BACK OF CURB. PROVIDE | | | A SWALE BETWEEN THE FENCE AND THE SOUTH PROPERTY LINE | | | TO PREVENT DIRECT RUNOFF ONTO THE ADJACENT PROPERTY. | | | | | | 4. [SATISFIED] CONSIDER REDUCING THE PARKING SPACES | | | ALONG THE WEST PROPERTY LINE AND PROVIDE 2 FEET OF | | | OVERHANG. TYPE D CURB COULD REPLACE THE WHEEL STOPS. | | | | | | 5. [SATISFIED] MOVE THE HIGH POINT OF THE DRIVEWAY | | | CLOSER TO THE EAST PROPERTY LINE SO THAT A PORTION OR | | | ALL OF THE LOADING PARKING SPACE WILL DRAIN TO THE | | | INTERIOR OF THE SITE INSTEAD OF THE RIGHT OF WAY. | | | | | | 6. [SATISFIED] LIST THE TOP OF TRENCH ELEVATION AND | | | BOTTOM OF TRENCH ELEVATION ON THE EXFILTRATION TRENCH | | | DETAIL CROSS SECTION. | | | | | | 7. [SATISFIED] THE CITY DOES NOT ALLOW THE USE OF | | | BLEEDERS WITH EXFILTRATION TRENCH SYSTEMS. | | | | | | 8. [SATISFIED] ON SHEETS 4 AND 5, WHAT DOES THE HEAVY | | | SINGLE SHORT DASH - LONG DASH LINE REPRESENT THAT IS | | | SHOWN IN THE INTERIOR OF THE WEST PARCEL? | | | | | | 9. [SATISFIED] SITE IS LOCATED WITHIN A SPECIAL FLOOD | | | HAZARD AREA. MINIMUM TWO FEET OF FREEBOARD ARE REQUIRED | | | ABOVE THE BASE FLOOD ELEVATION. | | | | | | NEW COMMENTS (06/08/22 SUBMITTAL): | | | | | | 10. [SATISFIED] CIVIL PLANS DO NOT MATCH THE | | | ARCHITECTURAL PLANS OR LANDSCAPE PLANS. THE CIVIL PLANS | | | REMOVED THE SIDEWALK ON THE NORTH SIDE OF THE BUILDING. | | | THIS MAY AFFECT THE LIFE SAFETY PLAN AND LANDSCAPE | | | PLAN. | | | | | | 11. [SATISFIED] ADD VERTICAL DATUM REFERENCE AND | | | CONVERSION EQUATION TO ENGINEERING SHEET 7. | | | | | | NEW COMMENTS (7/15/22 SUBMITTAL): | | | | | | 12. FOR ENGINEERING PERMIT SUBMITTAL,COORDINATE THE | | | LISTED PRB'S AND WEIRS ON THE PAVING, GRADING AND | | | DRAINAGE PLAN AND THE CORRESPONDING ITEMS' DETAIL NAME | | | ON THE DETAIL SHEET. FOR EXAMPLE, THE TYPE E INLET AT | | | THE NORTH END OF THE PARKING LOT CALLS OUT PRBS AND AN | | | INVERTED WEIR AND THE CS-1 STRUCTURE CALLS OUT A WEIR. | | | THE CORRESPONDING DETAILS ON SHEET 7 APPEAR TO BE | | | CALLED "POLLUTION CONTROL BAFFLE" AND INVERTED | | | POLLUTION CONTROL BAFFLE WEIR". WILL THE INLET AT THE | | | NORTH END OF THE PARKING LOT HAVE A WEIR? WHICH WALL | | | WILL IT BE LOCATED ON? | | | | | | 13. FOR ENGINEERING PERMIT SUBMITTAL, NUMBER THE | | | DRAINAGE AND SANITARY STRUCTURES FOR EASE OF REFERENCE, | | | INCLUDING EXISTING STRUCTURES THAT MAY OR MAY NOT BE | | | IMPACTED BY THE DEVELOPMENT. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | 561-351-0510 (M) | | | [email protected] | | | | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
F |
Date |
07-08-2022 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
07-08-2022 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
07-08-2022 |
Time |
15:22 |
Sent To |
|
|
| Notes |
| 2022-07-08 15:22:07 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE | | | 6/8/2022 SUBMITTAL: | | | | | | 1. [PARTIALLY SATISFIED - AN EXTRA PIPE WAS ADDED TO | | | THE CATCH BASIN ON THE NORTH SIDE OF 27TH STREET. | | | ADVISE WHERE THIS INFORMATION CAME FROM.] REVISE THE | | | LAYOUT OF THE EXISTING STORM PIPE CROSSING 27TH STREET | | | BY MOVING THE NORTH END OF THE PIPE FROM THE CATCH | | | BASIN (WITH RIM ELEVATION 12.28 FT NAVD) TO A MANHOLE | | | THAT IS LOCATED IN THE SWALE OF ELECTRONICS WAY EAST OF | | | THE CATCH BASIN. THEN ADD AN EXISTING 36 INCH RCP PIPE | | | BETWEEN THE MANHOLE AND THE CATCH BASIN TO THE WEST. | | | | | | 2. [SATISFIED] REVIEW THE PROPOSED GRADING OF THE | | | INTERIOR SWALE ALONG THE NORTH PERIMETER. NEARLY 12.5 | | | FEET IS NEEDED BETWEEN THE CORNER OF THE SIDEWALK (AT | | | NORTHWEST CORNER OF THE BUILDING) AND THE NORTH | | | PROPERTY LINE BUT THERE IS ONLY ABOUT 10.5 FEET. | | | APPROXIMATELY 12.5 FEET IS NEEDED BETWEEN THE BIKE RACK | | | AND NORTH PROPERTY LINE BUT ONLY 10 FEET IS AVAILABLE | | | (SECTION B-B). | | | | | | 3. [SATISFIED] SECTION D-D - INDICATE HOW THE GROUND | | | WILL SLOPE BETWEEN THE FENCE AND BACK OF CURB. PROVIDE | | | A SWALE BETWEEN THE FENCE AND THE SOUTH PROPERTY LINE | | | TO PREVENT DIRECT RUNOFF ONTO THE ADJACENT PROPERTY. | | | | | | 4. [SATISFIED] CONSIDER REDUCING THE PARKING SPACES | | | ALONG THE WEST PROPERTY LINE AND PROVIDE 2 FEET OF | | | OVERHANG. TYPE D CURB COULD REPLACE THE WHEEL STOPS. | | | | | | 5. [SATISFIED] MOVE THE HIGH POINT OF THE DRIVEWAY | | | CLOSER TO THE EAST PROPERTY LINE SO THAT A PORTION OR | | | ALL OF THE LOADING PARKING SPACE WILL DRAIN TO THE | | | INTERIOR OF THE SITE INSTEAD OF THE RIGHT OF WAY. | | | | | | 6. [SATISFIED] LIST THE TOP OF TRENCH ELEVATION AND | | | BOTTOM OF TRENCH ELEVATION ON THE EXFILTRATION TRENCH | | | DETAIL CROSS SECTION. | | | | | | 7. [SATISFIED] THE CITY DOES NOT ALLOW THE USE OF | | | BLEEDERS WITH EXFILTRATION TRENCH SYSTEMS. | | | | | | 8. [SATISFIED] ON SHEETS 4 AND 5, WHAT DOES THE HEAVY | | | SINGLE SHORT DASH - LONG DASH LINE REPRESENT THAT IS | | | SHOWN IN THE INTERIOR OF THE WEST PARCEL? | | | | | | 9. [SATISFIED] SITE IS LOCATED WITHIN A SPECIAL FLOOD | | | HAZARD AREA. MINIMUM TWO FEET OF FREEBOARD ARE REQUIRED | | | ABOVE THE BASE FLOOD ELEVATION. | | | | | | NEW COMMENTS: | | | | | | 10. CIVIL PLANS DO NOT MATCH THE ARCHITECTURAL PLANS OR | | | LANDSCAPE PLANS. THE CIVIL PLANS REMOVED THE SIDEWALK | | | ON THE NORTH SIDE OF THE BUILDING. THIS MAY AFFECT THE | | | LIFE SAFETY PLAN AND LANDSCAPE PLAN. | | | | | | 11. ADD VERTICAL DATUM REFERENCE AND CONVERSION | | | EQUATION TO ENGINEERING SHEET 7. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | 561-351-0510 (M) | | | [email protected] | | | | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
05-12-2022 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
05-12-2022 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
05-12-2022 |
Time |
12:55 |
Sent To |
|
|
| Notes |
| 2022-05-12 12:55:17 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | 1. REVISE THE LAYOUT OF THE EXISTING STORM PIPE | | | CROSSING 27TH STREET BY MOVING THE NORTH END OF THE | | | PIPE FROM THE CATCH BASIN (WITH RIM ELEVATION 12.28 FT | | | NAVD) TO A MANHOLE THAT IS LOCATED IN THE SWALE OF | | | ELECTRONICS WAY EAST OF THE CATCH BASIN. THEN ADD AN | | | EXISTING 36 INCH RCP PIPE BETWEEN THE MANHOLE AND THE | | | CATCH BASIN TO THE WEST. | | | | | | 2. REVIEW THE PROPOSED GRADING OF THE INTERIOR SWALE | | | ALONG THE NORTH PERIMETER. NEARLY 12.5 FEET IS NEEDED | | | BETWEEN THE CORNER OF THE SIDEWALK (AT NORTHWEST CORNER | | | OF THE BUILDING) AND THE NORTH PROPERTY LINE BUT THERE | | | IS ONLY ABOUT 10.5 FEET. APPROXIMATELY 12.5 FEET IS | | | NEEDED BETWEEN THE BIKE RACK AND NORTH PROPERTY LINE | | | BUT ONLY 10 FEET IS AVAILABLE (SECTION B-B). | | | | | | 3. SECTION D-D - INDICATE HOW THE GROUND WILL SLOPE | | | BETWEEN THE FENCE AND BACK OF CURB. PROVIDE A SWALE | | | BETWEEN THE FENCE AND THE SOUTH PROPERTY LINE TO | | | PREVENT DIRECT RUNOFF ONTO THE ADJACENT PROPERTY. | | | | | | 4. CONSIDER REDUCING THE PARKING SPACES ALONG THE WEST | | | PROPERTY LINE AND PROVIDE 2 FEET OF OVERHANG. TYPE D | | | CURB COULD REPLACE THE WHEEL STOPS. | | | | | | 5. MOVE THE HIGH POINT OF THE DRIVEWAY CLOSER TO THE | | | EAST PROPERTY LINE SO THAT A PORTION OR ALL OF THE | | | LOADING PARKING SPACE WILL DRAIN TO THE INTERIOR OF THE | | | SITE INSTEAD OF THE RIGHT OF WAY. | | | | | | 6. LIST THE TOP OF TRENCH ELEVATION AND BOTTOM OF | | | TRENCH ELEVATION ON THE EXFILTRATION TRENCH DETAIL | | | CROSS SECTION. | | | | | | 7. THE CITY DOES NOT ALLOW THE USE OF BLEEDERS WITH | | | EXFILTRATION TRENCH SYSTEMS. | | | | | | 8. ON SHEETS 4 AND 5, WHAT DOES THE HEAVY SINGLE SHORT | | | DASH - LONG DASH LINE REPRESENT THAT IS SHOWN IN THE | | | INTERIOR OF THE WEST PARCEL? | | | | | | 9. SITE IS LOCATED WITHIN A SPECIAL FLOOD HAZARD AREA. | | | MINIMUM TWO FEET OF FREEBOARD ARE REQUIRED ABOVE THE | | | BASE FLOOD ELEVATION. | | | | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP | | | CRITERIA. STORMWATER CALCULATIONS WILL BE REVIEWED WITH | | | THE ENGINEERING PERMIT SUBMITTAL. | | | | | | 2. PROVIDE COPY OF SFWMD ERP PERMIT MODIFICATION BEFORE | | | START OF CONSTRUCTION. | | | | | | 3. PROVIDE AN EROSION CONTROL PLAN WITH THE ENGINEEINRG | | | PERMIT SUBMITTAL. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | 561-351-0510 (M) | | | [email protected] | | | | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
2 |
Status |
P |
Date |
07-11-2022 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
07-11-2022 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
05-10-2022 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
05-10-2022 |
Time |
09:28 |
Rev Time |
|
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-05-10 09:36:34 | 1. SURVEY SHOULD BE JUST SUBJECT PARCEL, NOT ENTIRE | | | PROPERTY. |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
P |
Date |
05-06-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
05-06-2022 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-05-06 14:54:39 | NO COMMENTS. | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
08-03-2022 |
|
|
Cont ID |
|
| Sent By |
kdefranc |
Date |
08-03-2022 |
Time |
07:58 |
Rev Time |
0.00 |
| Received By |
kdefranc |
Date |
08-03-2022 |
Time |
07:56 |
Sent To |
|
|
| Notes |
| 2022-08-03 07:58:18 | 8/3/22 ? PASSED | | | | | | | | | PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN | | | RESUBMITTING: | | | A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL | | | DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION. | | | B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED | | | MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG | | | WITH ONE (1) REDUCED COPY (11 IN X 17 IN). | | | C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO | | | ADDITIONAL COMMENTS. | | | D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE | | | ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE | | | CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL | | | REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION. | | | E. PLEASE NOTE THAT YOU ARE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. A RESUBMITTAL FEE OF | | | 20% OF THE ORIGINAL APPLICATION FEE WILL BE ASSESSED | | | AFTER THE FIRST RESUBMITTAL. | | | | | | REQUIRED MATERIALS MUST BE PROVIDED: | | | F. PLEASE PROVIDE LETTERS FROM ALL PUBLIC UTILITIES | | | (FLORIDA POWER & LIGHT COMPANY, FLORIDA PUBLIC | | | UTILITIES, AT&T TELECOMMUNICATION, COMCAST CABLE | | | COMMUNICATIONS, CITY OF WEST PALM BEACH UTILITIES) | | | CONFIRMING THAT THE PROPOSED PROJECT DOES NOT ENCROACH | | | INTO THEIR EASEMENTS OR OTHERWISE INTERFERE WITH THE | | | PROVISIONS OF THEIR SERVICES. [SATISFIED] | | | G. PLEASE PROVIDE A TRAFFIC CONCURRENCY/PERFORMANCE | | | STANDARD REVIEW (TPS) LETTER FROM THE PALM BEACH COUNTY | | | TRAFFIC DIVISION FOR THE SUBJECT PROJECT. [SATISFIED] | | | H. PLEASE PROVIDE REVISED PLANS ADDRESSING THE REVIEW | | | COMMENTS BELOW. [SATISFIED] | | | I. PLEASE PROVIDE/INDICATE/DEMONSTRATE CONSISTENT | | | INFORMATION ON ALL THE DIFFERENT PLANS AND REQUIRED | | | MATERIALS WITHIN THE APPLICATION PACKET RESUBMITTAL. | | | [SATISFIED] | | | | | | PLANS REVIEW COMMENTS MUST BE ADDRESSED: | | | 1. PLEASE CORRECTLY IDENTIFY/INDICATE/DEMONSTRATE THE | | | EXISTING PROPERTY LINE ON ALL THE DIFFERENT PLANS, | | | ACCORDINGLY. [SATISFIED] | | | 2. PLEASE IDENTIFY/INDICATE THE PROPOSED USE(S) FOR | | | BOTH ?PHASE 1? AND ?PHASE 2? IN THE SITE DATA TABLE ON | | | THE SITE PLAN, SHEET # SP.1. [SATISFIED] | | | 3. IN ACCORDANCE WITH THE CITY?S ZONING AND LAND | | | DEVELOPMENT REGULATIONS (ZLDR) SUBSECTION 94-35(C)(9), | | | PLEASE IDENTIFY/INDICATE/DEMONSTRATE A CONNECTION | | | BETWEEN THE EXISTING PUBLIC SIDEWALK AND THE PROPOSED | | | ON-SITE PRIVATE SIDEWALK ON ALL THE DIFFERENT PLANS, | | | ACCORDINGLY. [SATISFIED] | | | 4. PLEASE IDENTIFY/INDICATE/DEMONSTRATE A | | | SINGLE/PEDESTRIAN GATE OR OPENING IN THE PROPOSED ?6? | | | HT. BLACK CHAIN LINK FENCE? FOR THE SIDEWALK CONNECTION | | | ON ALL THE DIFFERENT PLANS, ACCORDINGLY. [SATISFIED] | | | 5. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION, | | | HEIGHT, AND INTENSITY OF ALL OUTDOOR ILLUMINATION ON | | | ALL THE DIFFERENT PLANS, ACCORDINGLY. [SATISFIED] | | | 6. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF | | | EXISTING AND PROPOSED FIRE HYDRANTS (OR OPERATIONAL | | | EQUIVALENTS) WITHIN 250 FEET OF THE PROPOSED | | | STRUCTURE(S) ON THE SITE PLAN, SHEET # SP.1. | | | [SATISFIED] | | | 7. THE APPROVED SITE PLAN | | | IDENTIFIES/INDICATES/DEMONSTRATES A ?FPL TRANSFORMER W/ | | | 10? X 15? EASEMENT?. THEREFORE, PLEASE | | | IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF THE | | | PROPOSED ?FPL TRANSFORMER W/ 10? X 15? EASEMENT? ON ALL | | | THE DIFFERENT PLANS, ACCORDINGLY. [RESPONSE PROVIDED] | | | 8. PLEASE CORRECT THE ?TOTAL SITE AREA? CALCULATION (BY | | | PROVIDING THE AREA CALCULATIONS FOR THE ENTIRE SITE AND | | | BOTH PHASES SEPARATELY) IN THE ?SITE DATA? TABLE ON THE | | | SITE PLAN, SHEET # SP.1. [SATISFIED] | | | 9. PLEASE CORRECT THE ?MAX. IMPERVIOUS AREA? AND | | | ?PROPOSED IMPERVIOUS AREA? CALCULATIONS (BY PROVIDING | | | THE IMPERVIOUS AREA CALCULATIONS FOR THE ENTIRE SITE | | | AND BOTH PHASES SEPARATELY) IN THE ?SITE DATA? TABLE ON | | | THE SITE PLAN, SHEET # SP.1. [SATISFIED] | | | 10. PLEASE CORRECT THE ?PROPOSED BUILDING COVERAGE? | | | CALCULATION (BY PROVIDING THE BUILDING COVERAGE | | | CALCULATIONS FOR THE ENTIRE SITE AND BOTH PHASES | | | SEPARATELY) IN THE ?SITE DATA? TABLE ON THE SITE PLAN, | | | SHEET # SP.1. [SATISFIED] | | | 11. PLEASE CORRECT THE ?PROPOSED BUILDING FAR? | | | CALCULATION (BY PROVIDING THE FLOOR AREA RATIO | | | CALCULATION FOR THE ENTIRE SITE AND BOTH PHASES | | | SEPARATELY) IN THE ?SITE DATA? TABLE ON THE SITE PLAN, | | | SHEET # SP.1. THE PROPOSED 756 SQUARE FOOT ?COVERED | | | PATIO? AREA SHALL NOT BE INCLUDED IN THE FLOOR AREA | | | RATIO CALCULATION. [SATISFIED] | | | 12. PLEASE CORRECT THE ?REQUIRED OPEN SPACE? AND | | | ?PROPOSED OPEN SPACE? CALCULATIONS (BY PROVIDING THE | | | OPEN SPACE CALCULATIONS FOR THE ENTIRE SITE AND BOTH | | | PHASES SEPARATELY) IN THE ?SITE DATA? TABLE ON THE SITE | | | PLAN, SHEET # SP.1. [SATISFIED] | | | 13. PLEASE CORRECT THE ?REQUIRED PARKING? CALCULATION | | | IN THE ?SITE DATA? TABLE ON THE SITE PLAN, SHEET # | | | SP.1. THE MINIMUM PARKING REQUIREMENT FOR THE PROPOSED | | | USE OF ?RESTAURANTS SERVING A LIMITED CLIENTELE | | | (PRIVATE CLUBS AND LODGES)? IS 1 SPACE PER 200 GROSS | | | SQUARE FEET (THE PROPOSED GROSS SQUARE FOOTAGE | | | INDICATED IS 3,264 SQUARE FEET). [SATISFIED] | | | 14. PLEASE CORRECT THE ?REQUIRED VEHICULAR LANDSCAPE | | | AREA? CALCULATIONS (FROM ?209.6 SF? TO 209.7 SF AND | | | FROM ?499.6 TOTAL SF? TO 499.7 TOTAL SF) IN THE ?SITE | | | DATA? TABLE ON THE SITE PLAN, SHEET # SP.1. [SATISFIED] | | | | | | ADDITIONAL REVIEW COMMENT MUST BE ADDRESSED: | | | 15. PLEASE ADDRESS STORMWATER REVIEW COMMENTS. | | | [SATISFIED] | | | | | | | | | KEVIE DEFRANC | | | PLANNER - PLANNING DIVISION | | | [email protected] | | | 561-822-1449 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
07-11-2022 |
|
|
Cont ID |
|
| Sent By |
kdefranc |
Date |
07-11-2022 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
kdefranc |
Date |
07-11-2022 |
Time |
10:19 |
Sent To |
|
|
| Notes |
| 2022-07-11 10:20:23 | 7/11/22 ? FAILED | | | | | | | | | PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN | | | RESUBMITTING: | | | A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL | | | DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION. | | | B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED | | | MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG | | | WITH ONE (1) REDUCED COPY (11 IN X 17 IN). | | | C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO | | | ADDITIONAL COMMENTS. | | | D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE | | | ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE | | | CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL | | | REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION. | | | E. PLEASE NOTE THAT YOU ARE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. A RESUBMITTAL FEE OF | | | 20% OF THE ORIGINAL APPLICATION FEE WILL BE ASSESSED | | | AFTER THE FIRST RESUBMITTAL. | | | | | | REQUIRED MATERIALS MUST BE PROVIDED: | | | F. PLEASE PROVIDE LETTERS FROM ALL PUBLIC UTILITIES | | | (FLORIDA POWER & LIGHT COMPANY, FLORIDA PUBLIC | | | UTILITIES, AT&T TELECOMMUNICATION, COMCAST CABLE | | | COMMUNICATIONS, CITY OF WEST PALM BEACH UTILITIES) | | | CONFIRMING THAT THE PROPOSED PROJECT DOES NOT ENCROACH | | | INTO THEIR EASEMENTS OR OTHERWISE INTERFERE WITH THE | | | PROVISIONS OF THEIR SERVICES. [SATISFIED] | | | G. PLEASE PROVIDE A TRAFFIC CONCURRENCY/PERFORMANCE | | | STANDARD REVIEW (TPS) LETTER FROM THE PALM BEACH COUNTY | | | TRAFFIC DIVISION FOR THE SUBJECT PROJECT. [SATISFIED] | | | H. PLEASE PROVIDE REVISED PLANS ADDRESSING THE REVIEW | | | COMMENTS BELOW. [SATISFIED] | | | I. PLEASE PROVIDE/INDICATE/DEMONSTRATE CONSISTENT | | | INFORMATION ON ALL THE DIFFERENT PLANS AND REQUIRED | | | MATERIALS WITHIN THE APPLICATION PACKET RESUBMITTAL. | | | [PARTIALLY SATISFIED] | | | | | | PLANS REVIEW COMMENTS MUST BE ADDRESSED: | | | 1. PLEASE CORRECTLY IDENTIFY/INDICATE/DEMONSTRATE THE | | | EXISTING PROPERTY LINE ON ALL THE DIFFERENT PLANS, | | | ACCORDINGLY. [SATISFIED] | | | 2. PLEASE IDENTIFY/INDICATE THE PROPOSED USE(S) FOR | | | BOTH ?PHASE 1? AND ?PHASE 2? IN THE SITE DATA TABLE ON | | | THE SITE PLAN, SHEET # SP.1. [SATISFIED] | | | 3. IN ACCORDANCE WITH THE CITY?S ZONING AND LAND | | | DEVELOPMENT REGULATIONS (ZLDR) SUBSECTION 94-35(C)(9), | | | PLEASE IDENTIFY/INDICATE/DEMONSTRATE A CONNECTION | | | BETWEEN THE EXISTING PUBLIC SIDEWALK AND THE PROPOSED | | | ON-SITE PRIVATE SIDEWALK ON ALL THE DIFFERENT PLANS, | | | ACCORDINGLY. [SATISFIED] | | | 4. PLEASE IDENTIFY/INDICATE/DEMONSTRATE A | | | SINGLE/PEDESTRIAN GATE OR OPENING IN THE PROPOSED ?6? | | | HT. BLACK CHAIN LINK FENCE? FOR THE SIDEWALK CONNECTION | | | ON ALL THE DIFFERENT PLANS, ACCORDINGLY. [SATISFIED] | | | 5. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION, | | | HEIGHT, AND INTENSITY OF ALL OUTDOOR ILLUMINATION ON | | | ALL THE DIFFERENT PLANS, ACCORDINGLY. [SATISFIED] | | | 6. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF | | | EXISTING AND PROPOSED FIRE HYDRANTS (OR OPERATIONAL | | | EQUIVALENTS) WITHIN 250 FEET OF THE PROPOSED | | | STRUCTURE(S) ON THE SITE PLAN, SHEET # SP.1. | | | [SATISFIED] | | | 7. THE APPROVED SITE PLAN | | | IDENTIFIES/INDICATES/DEMONSTRATES A ?FPL TRANSFORMER W/ | | | 10? X 15? EASEMENT?. THEREFORE, PLEASE | | | IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF THE | | | PROPOSED ?FPL TRANSFORMER W/ 10? X 15? EASEMENT? ON ALL | | | THE DIFFERENT PLANS, ACCORDINGLY. [RESPONSE PROVIDED] | | | 8. PLEASE CORRECT THE ?TOTAL SITE AREA? CALCULATION (BY | | | PROVIDING THE AREA CALCULATIONS FOR THE ENTIRE SITE AND | | | BOTH PHASES SEPARATELY) IN THE ?SITE DATA? TABLE ON THE | | | SITE PLAN, SHEET # SP.1. [SATISFIED] | | | 9. PLEASE CORRECT THE ?MAX. IMPERVIOUS AREA? AND | | | ?PROPOSED IMPERVIOUS AREA? CALCULATIONS (BY PROVIDING | | | THE IMPERVIOUS AREA CALCULATIONS FOR THE ENTIRE SITE | | | AND BOTH PHASES SEPARATELY) IN THE ?SITE DATA? TABLE ON | | | THE SITE PLAN, SHEET # SP.1. [SATISFIED] | | | 10. PLEASE CORRECT THE ?PROPOSED BUILDING COVERAGE? | | | CALCULATION (BY PROVIDING THE BUILDING COVERAGE | | | CALCULATIONS FOR THE ENTIRE SITE AND BOTH PHASES | | | SEPARATELY) IN THE ?SITE DATA? TABLE ON THE SITE PLAN, | | | SHEET # SP.1. [SATISFIED] | | | 11. PLEASE CORRECT THE ?PROPOSED BUILDING FAR? | | | CALCULATION (BY PROVIDING THE FLOOR AREA RATIO | | | CALCULATION FOR THE ENTIRE SITE AND BOTH PHASES | | | SEPARATELY) IN THE ?SITE DATA? TABLE ON THE SITE PLAN, | | | SHEET # SP.1. THE PROPOSED 756 SQUARE FOOT ?COVERED | | | PATIO? AREA SHALL NOT BE INCLUDED IN THE FLOOR AREA | | | RATIO CALCULATION. [SATISFIED] | | | 12. PLEASE CORRECT THE ?REQUIRED OPEN SPACE? AND | | | ?PROPOSED OPEN SPACE? CALCULATIONS (BY PROVIDING THE | | | OPEN SPACE CALCULATIONS FOR THE ENTIRE SITE AND BOTH | | | PHASES SEPARATELY) IN THE ?SITE DATA? TABLE ON THE SITE | | | PLAN, SHEET # SP.1. [SATISFIED] | | | 13. PLEASE CORRECT THE ?REQUIRED PARKING? CALCULATION | | | IN THE ?SITE DATA? TABLE ON THE SITE PLAN, SHEET # | | | SP.1. THE MINIMUM PARKING REQUIREMENT FOR THE PROPOSED | | | USE OF ?RESTAURANTS SERVING A LIMITED CLIENTELE | | | (PRIVATE CLUBS AND LODGES)? IS 1 SPACE PER 200 GROSS | | | SQUARE FEET (THE PROPOSED GROSS SQUARE FOOTAGE | | | INDICATED IS 3,264 SQUARE FEET). [SATISFIED] | | | 14. PLEASE CORRECT THE ?REQUIRED VEHICULAR LANDSCAPE | | | AREA? CALCULATIONS (FROM ?209.6 SF? TO 209.7 SF AND | | | FROM ?499.6 TOTAL SF? TO 499.7 TOTAL SF) IN THE ?SITE | | | DATA? TABLE ON THE SITE PLAN, SHEET # SP.1. [SATISFIED] | | | | | | ADDITIONAL REVIEW COMMENT MUST BE ADDRESSED: | | | 15. PLEASE ADDRESS STORMWATER REVIEW COMMENTS. | | | | | | | | | KEVIE DEFRANC | | | PLANNER - PLANNING DIVISION | | | [email protected] | | | 561-822-1449 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
05-05-2022 |
|
|
Cont ID |
|
| Sent By |
kdefranc |
Date |
05-05-2022 |
Time |
11:54 |
Rev Time |
0.00 |
| Received By |
kdefranc |
Date |
05-05-2022 |
Time |
11:53 |
Sent To |
|
|
| Notes |
| 2022-05-05 11:53:57 | 5/5/22 - FAILED | | | | | | | | | PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN | | | RESUBMITTING: | | | A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL | | | DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION. | | | B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED | | | MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG | | | WITH ONE (1) REDUCED COPY (11 IN X 17 IN). | | | C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO | | | ADDITIONAL COMMENTS. | | | D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE | | | ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE | | | CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL | | | REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION. | | | E. PLEASE NOTE THAT YOU ARE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. A RESUBMITTAL FEE OF | | | 20% OF THE ORIGINAL APPLICATION FEE WILL BE ASSESSED | | | AFTER THE FIRST RESUBMITTAL. | | | | | | REQUIRED MATERIALS MUST BE PROVIDED: | | | F. PLEASE PROVIDE LETTERS FROM ALL PUBLIC UTILITIES | | | (FLORIDA POWER & LIGHT COMPANY, FLORIDA PUBLIC | | | UTILITIES, AT&T TELECOMMUNICATION, COMCAST CABLE | | | COMMUNICATIONS, CITY OF WEST PALM BEACH UTILITIES) | | | CONFIRMING THAT THE PROPOSED PROJECT DOES NOT ENCROACH | | | INTO THEIR EASEMENTS OR OTHERWISE INTERFERE WITH THE | | | PROVISIONS OF THEIR SERVICES. | | | G. PLEASE PROVIDE A TRAFFIC CONCURRENCY/PERFORMANCE | | | STANDARD REVIEW (TPS) LETTER FROM THE PALM BEACH COUNTY | | | TRAFFIC DIVISION FOR THE SUBJECT PROJECT. | | | H. PLEASE PROVIDE REVISED PLANS ADDRESSING THE REVIEW | | | COMMENTS BELOW. | | | I. PLEASE PROVIDE/INDICATE/DEMONSTRATE CONSISTENT | | | INFORMATION ON ALL THE DIFFERENT PLANS AND REQUIRED | | | MATERIALS WITHIN THE APPLICATION PACKET RESUBMITTAL. | | | | | | PLANS REVIEW COMMENTS MUST BE ADDRESSED: | | | 1. PLEASE CORRECTLY IDENTIFY/INDICATE/DEMONSTRATE THE | | | EXISTING PROPERTY LINE ON ALL THE DIFFERENT PLANS, | | | ACCORDINGLY. | | | 2. PLEASE IDENTIFY/INDICATE THE PROPOSED USE(S) FOR | | | BOTH ?PHASE 1? AND ?PHASE 2? IN THE SITE DATA TABLE ON | | | THE SITE PLAN, SHEET # SP.1. | | | 3. IN ACCORDANCE WITH THE CITY?S ZONING AND LAND | | | DEVELOPMENT REGULATIONS (ZLDR) SUBSECTION 94-35(C)(9), | | | PLEASE IDENTIFY/INDICATE/DEMONSTRATE A CONNECTION | | | BETWEEN THE EXISTING PUBLIC SIDEWALK AND THE PROPOSED | | | ON-SITE PRIVATE SIDEWALK ON ALL THE DIFFERENT PLANS, | | | ACCORDINGLY. | | | 4. PLEASE IDENTIFY/INDICATE/DEMONSTRATE A | | | SINGLE/PEDESTRIAN GATE OR OPENING IN THE PROPOSED ?6? | | | HT. BLACK CHAIN LINK FENCE? FOR THE SIDEWALK CONNECTION | | | ON ALL THE DIFFERENT PLANS, ACCORDINGLY. | | | 5. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION, | | | HEIGHT, AND INTENSITY OF ALL OUTDOOR ILLUMINATION ON | | | ALL THE DIFFERENT PLANS, ACCORDINGLY. | | | 6. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF | | | EXISTING AND PROPOSED FIRE HYDRANTS (OR OPERATIONAL | | | EQUIVALENTS) WITHIN 250 FEET OF THE PROPOSED | | | STRUCTURE(S) ON THE SITE PLAN, SHEET # SP.1. | | | 7. THE APPROVED SITE PLAN | | | IDENTIFIES/INDICATES/DEMONSTRATES A ?FPL TRANSFORMER W/ | | | 10? X 15? EASEMENT?. THEREFORE, PLEASE | | | IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION OF THE | | | PROPOSED ?FPL TRANSFORMER W/ 10? X 15? EASEMENT? ON ALL | | | THE DIFFERENT PLANS, ACCORDINGLY. | | | 8. PLEASE CORRECT THE ?TOTAL SITE AREA? CALCULATION (BY | | | PROVIDING THE AREA CALCULATIONS FOR THE ENTIRE SITE AND | | | BOTH PHASES SEPARATELY) IN THE ?SITE DATA? TABLE ON THE | | | SITE PLAN, SHEET # SP.1. | | | 9. PLEASE CORRECT THE ?MAX. IMPERVIOUS AREA? AND | | | ?PROPOSED IMPERVIOUS AREA? CALCULATIONS (BY PROVIDING | | | THE IMPERVIOUS AREA CALCULATIONS FOR THE ENTIRE SITE | | | AND BOTH PHASES SEPARATELY) IN THE ?SITE DATA? TABLE ON | | | THE SITE PLAN, SHEET # SP.1. | | | 10. PLEASE CORRECT THE ?PROPOSED BUILDING COVERAGE? | | | CALCULATION (BY PROVIDING THE BUILDING COVERAGE | | | CALCULATIONS FOR THE ENTIRE SITE AND BOTH PHASES | | | SEPARATELY) IN THE ?SITE DATA? TABLE ON THE SITE PLAN, | | | SHEET # SP.1. | | | 11. PLEASE CORRECT THE ?PROPOSED BUILDING FAR? | | | CALCULATION (BY PROVIDING THE FLOOR AREA RATIO | | | CALCULATION FOR THE ENTIRE SITE AND BOTH PHASES | | | SEPARATELY) IN THE ?SITE DATA? TABLE ON THE SITE PLAN, | | | SHEET # SP.1. THE PROPOSED 756 SQUARE FOOT ?COVERED | | | PATIO? AREA SHALL NOT BE INCLUDED IN THE FLOOR AREA | | | RATIO CALCULATION. | | | 12. PLEASE CORRECT THE ?REQUIRED OPEN SPACE? AND | | | ?PROPOSED OPEN SPACE? CALCULATIONS (BY PROVIDING THE | | | OPEN SPACE CALCULATIONS FOR THE ENTIRE SITE AND BOTH | | | PHASES SEPARATELY) IN THE ?SITE DATA? TABLE ON THE SITE | | | PLAN, SHEET # SP.1. | | | 13. PLEASE CORRECT THE ?REQUIRED PARKING? CALCULATION | | | IN THE ?SITE DATA? TABLE ON THE SITE PLAN, SHEET # | | | SP.1. THE MINIMUM PARKING REQUIREMENT FOR THE PROPOSED | | | USE OF ?RESTAURANTS SERVING A LIMITED CLIENTELE | | | (PRIVATE CLUBS AND LODGES)? IS 1 SPACE PER 200 GROSS | | | SQUARE FEET (THE PROPOSED GROSS SQUARE FOOTAGE | | | INDICATED IS 3,264 SQUARE FEET). | | | 14. PLEASE CORRECT THE ?REQUIRED VEHICULAR LANDSCAPE | | | AREA? CALCULATIONS (FROM ?209.6 SF? TO 209.7 SF AND | | | FROM ?499.6 TOTAL SF? TO 499.7 TOTAL SF) IN THE ?SITE | | | DATA? TABLE ON THE SITE PLAN, SHEET # SP.1. | | | | | | | | | KEVIE DEFRANC | | | PLANNER - PLANNING DIVISION | | | [email protected] | | | 561-822-1449 | | | |
|
|
| |