Plan Review Details - Project Z22020024
Plan Review Stops For Project Z22020024
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 03-11-2022 Cont ID  
Sent By scwelter Date 03-10-2022 Time 12:01 Rev Time 0.00
Received By scwelter Date 03-11-2022 Time 16:49 Sent To  
Notes
2022-03-10 12:02:34ART ASSESSMENT APPLICATION HAS BEEN COMPLETED. OPTION 2
 - INVOICE 3.11.2022
  
 TOTAL CONSTRUCTION COSTS OF THIS DEVELOPMENT ARE OVER
 $500,000 IT IS SUBJECT TO THE PUBLIC ART REQUIREMENT AS
 PER CITY ORDINANCE.
 SECTION 78-129: ALL PRIVATE DEVELOPMENT PROJECTS,
 INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR
 IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL
 CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000 ARE SUBJECT TO THE PUBLIC ART REQUIREMENT.
 OPTION 1: INSTALL ARTWORK ON THE DEVELOPMENT SITE
 VALUED IN AN AMOUNT NOT LESS THAN ONE PERCENT OF THE
 TOTAL CONSTRUCTION COSTS; OR
 OPTION 2: CONTRIBUTE AN AMOUNT EQUAL TO 75 PERCENT OF
 ONE PERCENT OF THE TOTAL CONSTRUCTION COSTS FOR DEPOSIT
 TO THE PUBLIC ART ACCOUNT.
 A COMPLETED PUBLIC ART ASSESSMENT APPLICATION IS
 REQUIRED AT TIME OF BUILDING PERMIT SUBMITTAL.
  
 CONTACT SYBILLE WELTER, ADMINISTRATOR OF PUBLIC ART &
 CULTURE AT [email protected] TO OBTAIN AN ART ASSESSMENT
 APPLICATION AND REVIEW THE REQUIREMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 03-09-2022 Cont ID  
Sent By rbrown Date 03-09-2022 Time 19:23 Rev Time 0.00
Received By rbrown Date 03-09-2022 Time 19:23 Sent To  
Notes
2022-03-09 19:29:43DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS
 SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT
 REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH
 COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963,
 OR BY EMAIL: [email protected]
  
 3. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 4. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND
 OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT,
 COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF
 OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED.
  
 5. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 6. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 7. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION
 OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING,
 CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT
 (561) 805 6659, OR BY EMAIL: [email protected]
  
 8. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT
 TO ART LIFE ASSESSMENT UNDER THE CITY OF WEST PALM
 BEACH ART IN PUBLIC PLACES (AIPP) PROGRAM. FOR ADVICE
 ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP
 ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status P Date 04-01-2022 Cont ID  
Sent By rrossano Date 04-01-2022 Time   Rev Time 0.00
Received By rrossano Date 04-01-2022 Time   Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 03-07-2022 Cont ID  
Sent By ldeloren Date 03-07-2022 Time   Rev Time  
Received By ldeloren Date 03-07-2022 Time   Sent To  
Notes
2022-03-07 13:10:26Z22020024 ? BANYAN VIEW AMENDMENT ? 2-23-22 REVIEW
 RICK ROSSANO, SR. PROJECT COORDINATOR, ENG. SERVICES
 DEPT., 561-494-1098 [email protected]
 PLEASE ADVISE ON ANY IMPACT TO PREVIOUSLY PROPOSED
 UTILITIES ? WATER, SEWER, STORM, ETC.
 MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR;
 561-822-2262, [email protected]
 CIVIL ENGINEER PLAN SUBMITTED IS DIFFERENT THAN CIVIL
 ENGINEERING PLAN SUBMITTED FOR E21080021. FOR EXAMPLE,
 THE METER AND BACKFLOW SIZES SAY TO BE DETERMINED, BUT
 THEY WERE ALREADY DETERMINED DURING ENGINEERING
 SUBMITTAL. THE LAYOUT OF THE WATER SERVICES IS ALSO
 DIFFERENT. ADVISE IF CHANGES NEED TO BE MADE TO
 E21080021 PLANS, AND IF THERE ARE ANY CONFLICTS CREATED
 BY THIS DIFFERENCE.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 04-04-2022 Cont ID  
Sent By pleduc Date 04-04-2022 Time   Rev Time 0.00
Received By pleduc Date 04-04-2022 Time 09:44 Sent To  
Notes
2022-04-04 10:07:50FIRE HAS NO OBJECTIONS TO THE PROPOSED AND APPROVES.
  
 FIRE'S APPROVAL OF THIS SUBMITTED PROJECT MAY NOT
 CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 FIRE SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT THE
 APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE FIRE CODES AND
 STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 02-28-2022 Cont ID  
Sent By pleduc Date 02-28-2022 Time   Rev Time 0.00
Received By pleduc Date 02-28-2022 Time 13:58 Sent To  
Notes
2022-02-28 14:03:21THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE DEPARTMENT.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT. THE FOLLOWING COMMENTS ARE INTENDED
 TO PROVIDE GUIDANCE FOR BUILDING PLAN SUBMITTAL.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING(S) SHALL COMPLY
 WITH THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION
 CODE, INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE
 CODES.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE PER THE FLORIDA FIRE PREVENTION CODE.
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED, AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 THE LOCATION OF THE FIRE HYDRANTS AND PROPOSED FDC'S
 APPEAR TO BE WITHIN 100' AND IF CONFRIMED WOULD BE
 ACCEPTABLE TO THE BUREAU OF FIRE PREVENTION.
  
 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM,
 ENSURE THEY COMPLY WITH THE REQUIREMENTS OF F.A.C. 61G
 AND SUBMITTED WITH THE MASTER PERMIT.
  
 9A. THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE
 LOCATIONS SHALL MEET AND BE INSTALLED PER THE
 REQUIREMENTS OF NFPA 24 AND SHALL BE COORDINATED WITH
 THE OFFICE OF FIRE MARSHAL, THE CITY'S ENGINEERS
 OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S PLANNING
 AND ZONING OFFICE.
  
 10. COMPLETE LIFE SAFETY PLANS FOR THE OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, EXIT SEPARATION DISTANCES, COMMON PATHS OF
 TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, EMERGENCY
 LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE
 EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES
 AND EQUIPMENT.
  
 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE
 SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY
 DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS.
  
 12. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7
 KEYWAY SYSTEM.
 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTER?S
 EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA
 B44, SAFETY CODE FOR ELEVATORS.
 ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET
 MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN
 AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE
 IN THE HORIZONTAL POSITION.
  
 13. TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEMS.
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
  
 CONTACT WILL NEED TO BE MADE TO MARK FILLA, PALM BEACH
 COUNTY PUBLIC SAFETY RADIO SYSTEMS MANAGER,
 [email protected], 561-233-0837; AS OUR RADIOS OPERATE
 ON THEIR SYSTEM FOR DETAILED RADIO FREQUENCY AND
 INSTALLATION INSTRUCTIONS.
  
 14. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
 15. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 2 Status P Date 04-04-2022 Cont ID  
Sent By rcaranci Date 04-04-2022 Time 13:55 Rev Time 0.00
Received By rcaranci Date 04-04-2022 Time 13:55 Sent To  
Notes
2022-04-04 13:56:03FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: BANYAN CAY RPD/CPD MINOR PD AMENDMENT
 Z22020024
 APRIL 4, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. SATISFIED. THE TERMINAL LANDSCAPE ISLAND AT THE
 NORTHWEST CORNER OF THE SITE APPEARS TO BE LACKING THE
 REQUIRED TREE. THE ROYAL PALM IS REQUIRED IN THE
 LANDSCAPE BUFFER SO CANNOT BE COUNTED. PROVIDE THE
 REQUIRED TREE.
  
 2. SATISFIED. THE TOTAL TREE COUNT FOR THE SITE AS
 APPROVED IS 289. THIS AMENDMENT HAS DROPPED TO 287.
 PROVIDE THE ADDITIONAL 2 TREES.
  
  
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 03-07-2022 Cont ID  
Sent By rcaranci Date 03-07-2022 Time 11:55 Rev Time 0.00
Received By rcaranci Date 03-07-2022 Time 11:55 Sent To  
Notes
2022-03-07 11:55:52FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: BANYAN CAY RPD/CPD MINOR PD AMENDMENT
 Z22020024
 MARCH 7, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. THE TERMINAL LANDSCAPE ISLAND AT THE NORTHWEST
 CORNER OF THE SITE APPEARS TO BE LACKING THE REQUIRED
 TREE. THE ROYAL PALM IS REQUIRED IN THE LANDSCAPE
 BUFFER SO CANNOT BE COUNTED. PROVIDE THE REQUIRED TREE.
  
 2. THE TOTAL TREE COUNT FOR THE SITE AS APPROVED IS
 289. THIS AMENDMENT HAS DROPPED TO 287. PROVIDE THE
 ADDITIONAL 2 TREES.
  
  

Review Stop PU PUBLIC UTILITIES
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By mtechnow Date 03-09-2022 Time 13:43 Sent To  
Notes
2022-03-09 13:44:31-SHOW LOS TABLE ON SHEET 3.
 -SEE LIST OF STANDARD COMMENTS.
  
 CONTACT MIKE TECHNOW WITH QUESTIONS AT [email protected]
 OR 561-494-1047

Review Stop PW PUBLIC WORKS
Rev No 2 Status P Date 05-11-2022 Cont ID  
Sent By   Date 05-11-2022 Time   Rev Time 0.00
Received By   Date 05-11-2022 Time   Sent To  
Notes
2022-05-11 13:08:55NO FURTHER COMMENTS.
  
 MATT HEJAZI
 [email protected]
 561-822-2045

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 03-07-2022 Cont ID  
Sent By   Date 03-07-2022 Time   Rev Time  
Received By   Date 03-07-2022 Time   Sent To  
Notes
2022-03-07 09:13:201- PLEASE PROVIDE A REVISED SITE PLAN, SHEET SP-9, TO
 OMIT THE STOP BAR ON THE BULK TRASH ENCLOSURE
 DETAIL,GC-7
 2- COMPACTOR CONTAINERS SHALL BE FRONT LOAD TYPE IN
 ORDER FOR THE CITY`S COLLECTION VEHICLES TO BE ABLE TO
 PROVIDE THE SERVICE.
  
 MATT HEJAZI
 [email protected]
 561-822-2045

Review Stop STORM STORMWATER
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status F Date 03-09-2022 Cont ID  
Sent By tward Date 03-09-2022 Time 17:36 Rev Time 0.00
Received By tward Date 03-09-2022 Time 17:37 Sent To  
Notes
2022-03-09 17:37:14THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
 1. ANY CONDITIONS FROM PREVIOUS SITE PLAN APPROVAL
 STORMWATER REVIEWS WOULD APPLY TO THIS SITE PLAN.
 2. CROSS WALK STRIPING DOES NOT APPEAR TO ALIGN WITH
 CART PATH ON OPPOSITE SIDE OF PRESIDENTIAL WAY.
 3. PROVIDE A CROSS SECTION SIMILAR TO A-A BUT THROUGH
 THE CART PATH ALONG THE EAST PROPERTY LINE.
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP
 CRITERIA. STORMWATER CALCULATIONS WILL BE REVIEWED WITH
 THE ENGINEERING PERMIT SUBMITTAL.
  
 2. PROVIDE COPY OF SFWMD ERP MODIFICATION BEFORE START
 OF CONSTRUCTION, IF REQUIRED.
  
 3. PROVIDE AN EROSION CONTROL PLAN WITH DETAILS.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 1 Status P Date 03-09-2022 Cont ID  
Sent By vnoel Date 03-09-2022 Time 08:42 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2022-03-09 08:44:33GRANT OF DRAINAGE EASEMENT TO PRESIDENTIAL WAY ASSN.
 SHOULD BE RECORDED SHORTLY. THE CITY WILL THEN
 TERMINATE ITS RIGHTS TO THE EASEMENT.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status P Date 04-01-2022 Cont ID  
Sent By   Date 04-01-2022 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2022-04-01 10:07:00VALERIO - NO COMMENTS
  
 XAVIER - SIGHT DISTANCE AT DRIVEWAYS: SATISFIED.
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status P Date 03-09-2022 Cont ID  
Sent By   Date 03-09-2022 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2022-03-09 15:42:00NO COMMENTS.
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***