Plan Review Details - Project Z21120021
Plan Review Stops For Project Z21120021
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 08-05-2022 Cont ID  
Sent By scwelter Date 08-05-2022 Time 11:22 Rev Time 0.00
Received By scwelter Date 08-05-2022 Time 11:23 Sent To  
Notes
2022-08-05 11:23:22THIS PROJECT IS AN AFFORDABLE HOUSING PROJECT RECEIVING
 TAX CREDIT FUNDS. THE PUBLIC ART WAIVER WOULD APPLY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date 07-19-2022 Cont ID  
Sent By rrossano Date 07-19-2022 Time 09:29 Rev Time 0.00
Received By rrossano Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 01-12-2022 Cont ID  
Sent By rbrown Date 01-12-2022 Time 19:02 Rev Time 0.00
Received By rbrown Date 01-12-2022 Time 19:02 Sent To  
Notes
2022-01-12 19:19:19DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. LOCATION MAP ON THE COVER SHEET AND SHEET SP-1 DOES
 NOT MATCH THE ACTUAL PROPOSED LOCATION OF THE PROJECT
 WHICH IS GRANT ST AND N. TAMARIND AVE.
  
 3. UNITY OF TITLE. FOR ANY BUILDING CROSSING A PROPERTY
 LINE, EITHER A RECORDED UNITY OF TITLE, OR SOME OTHER
 APPROVED LEGAL INSTRUMENT, SHALL BE INCLUDED WITH THE
 PERMIT APPLICATION, OR THE BUILDING MUST HAVE A FIRE
 WALL ALONG THE PROPERTY LINE, PER SECTION 202 OF
 FLORIDA BUILDING CODE, BUILDING, FIRE SEPARATION
 DISTANCE.
  
 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 5. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 6. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND
 CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF
 CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL
 NEIGHBORING PROPERTIES.
  
 7. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 8. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION
 OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING,
 CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT
 (561) 805 6659, OR BY EMAIL: [email protected]
  
 9. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT
 TO ART LIFE ASSESSMENT UNDER THE CITY OF WEST PALM
 BEACH ART IN PUBLIC PLACES (AIPP) PROGRAM. FOR ADVICE
 ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP
 ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 3 Status P Date 07-19-2022 Cont ID  
Sent By rrossano Date 07-19-2022 Time   Rev Time 0.00
Received By rrossano Date 07-19-2022 Time   Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status F Date 03-28-2022 Cont ID  
Sent By rrossano Date 03-28-2022 Time   Rev Time 0.00
Received By rrossano Date 03-28-2022 Time   Sent To  
Notes
2022-03-28 11:52:19Z21120021, 0016 - 1002 GRANT ST. RESUB 3.24.22
 COMMENTS FROM RICK ROSSANO, SR. PROJECT COORDINATOR,
 ENG. SERVICES DEPT., 561-494-1098 [email protected] :
 1. CONFIRM THAT A COMPLETED LOS ANALYSIS SUMMARY TABLE
 HAS BEEN SUBMITTED DIRECTLY TO ENGINEERING (SHEET 33 OF
 CITY OF WPB DEVELOPMENT APPLICATION).
 2. CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY
 SEWER ARE REQUIRED.
 3. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM
 AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE
 PER FAC 64E-8 FOR WATER AND PER FAC 64-E.008 FOR SEWER.
 4. PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND
 STORMWATER PIPES ALONG ENTIRE PROJECT FRONTAGE.
 5. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
 6. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING
 PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT
 HIM AT 561-494-2262 OR [email protected]
 1. FOR FORMAL ENGINEERING SUBMITTAL , PLANS SHALL SHOW
 PROPOSED LOCATIONS AND DIMENSIONS OF ALL WATER,
 STORMWATER, AND SANITARY AND SEWER LINES, INCLUDING
 STUBS TO EACH PROPERTY LINE FOR WATER AND SANITARY
 SEWERS, THE MAKE AND MODEL OF ALL VALVES, METERS, AND
 OTHERS DEVICES TO BE INSTALLED ON THE SYSTEM, CATCH
 BASINS, CULVERTS, DITCHES INCLUDING GRADES, PIPES
 SIZES, MATERIALS, ELEVATIONS, ASSUMPTIONS,
 CALCULATIONS, INVERT ELEVATIONS FOR ALL INLETS AND
 MANHOLES AND PROFILES OF SANITARY SEWER LINES. ALL
 AVAILABLE ELEVATION SHALL BE SHOWN ON THE PROFILE VIEW.
 DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN
 VIEW FOR ALL SANITARY AND STORM SEWERS. ADDITIONALLY,
 PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED
 UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC,
 ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION
 FACILITIES LOCATED ON THE RIGHT-OF-WAY. PROVIDE PROFILE
 AND CLEARANCES AT ALL UTILITY CROSSINGS.
 7. PLEASE CLOUD/HIGHLIGHT PLAN REVISIONS OR CHANGES IN
 SCOPE FOR RESUBMITTAL OF DRAWINGS.
 8. FOR FORMAL ENGINEERING SUBMITTAL , CUT AND CAP
 UTILITIES NOT IN USE, AND REMOVE ANY ABANDONED UTILITY
 LINES LARGER THAN 2 INCHES FROM CITY RIGHT OF WAY.
 9. FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE DEDICATED
 UTILITY EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO
 PROPOSED UTILITY WATER METERS.
 10. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE
 ENLARGED VIEW ON PLANS OF PROPOSED LOCATION OF WATER
 METER AND BACKFLOW PREVENTION.
 11. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE CALLOUT
 DOMESTIC BACKFLOW PREVENTER AS RPPA AND FIRE BACKFLOW
 PREVENTER AS DCDA. SPECIFY LEAD FREE DESIGN ON ALL
 BACKFLOWS.
 12. FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND
 NPDES NOI REQUIREMENTS WILL BE ENFORCED.
 - AN NOI IS REQUIRED FOR PROJECTS THAT:
 - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS
 THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF
 DEVELOPMENT OR SALE; AND
 - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE
 STATE OR TO SURFACE WATERS OF THE STATE THROUGH A
 MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4).
 - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF
 CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION
 THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL
 SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT
 OF THE 10-2 CERTIFICATION. IF THE ENGINEERING PLANS DO
 NOT INCLUDE AN EROSION CONTROL PLAN, THEN THE
 CONTRACTOR SHOULD SUBMIT ONE PRIOR TO RECEIVING THE
 ENGINEERING PERMIT.
 13. FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES
 OF PROPOSED AND EXISTING WATER AND SEWER WITHIN RIGHT
 OF WAY AND SHOW ANY CROSSINGS/CONFLICTS.
 14. FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING
 APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT
 SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING
 SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED
 LEAD-FREE DESIGN.
 15. FOR FORMAL ENGINEERING SUBMITTAL CLEARLY SHOW ROAD
 RIGHT OF WAY.
 16. FOR FORMAL ENGINEERING SUBMITTAL PROVIDE SANITARY
 ELEVATIONS AT MANHOLE TIE-IN.
 17. FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY
 INFRASTRUCTURE IS PROPOSED IN ROW PLEASE SHOW ADJACENT
 SANITARY LATERAL LOCATIONS AND SHOW ADDRESSES OF
 ADJACENT PARCELS.
 18. FOR FORMAL ENGINEERING SUBMITTAL, IF WATER
 INFRASTRUCTURE IS BEING REPLACED IN ROW, SHOW ADJACENT
 PARCEL ADDRESSES.
 19. FOR FORMAL ENGINEERING SUBMITTAL, WHEN TRENCHING IN
 IN CITY MAINTAINED ROADWAY AREAS ADD NOTE TO PROVIDE 50
 FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF
 PROPOSED TRENCH PER CURRENT CITY OF WPB STANDARD DETAIL
 GC-8.
 20. PLEASE RESPOND TO ALL COMMENTS IN WRITING AND
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (Z-XXXXXXXX).
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-494-2262 OR
 [email protected]:
  
 -SHOWING 3 INCH TAP AND SERVICE PIPING FOR 4 INCH
 METER. INCREASE TO 4.
  
 -RECOMMEND PARALLEL DOMESTIC BACKFLOW ASSEMBLIES TO
 MINIMIZE WATER OUTAGES DURING BACKFLOW MAINTENANCE.
  
 -ADD ABOVE-GROUND WORDING TO LABEL OF DOMESTIC WATER
 METER.
  
 -FOOTPRINT OF DOMESTIC WATER METER AND ASSOCIATED
 PIPING MAY BE LARGER THAN SHOWN ON WATER PLAN.
  
 -4 INCH DCDA SHOULD HAVE 4 INCH TAP AND 4 INCH SERVICE
 PIPING.
  
 -IS THERE SUFFICIENT CLEARANCE DISTANCE BETWEEN
 CROSSING OF SEWER LATERAL AND DRAINAGE PIPING?
  
 -INDICATE RELOCATION OF DRIVEWAY APPROACH AND
 CONVERSION OF PRIOR AREA TO SIDEWALK, CURBING, AND
 PARKWAY.
  
 -COULD NOT SEE FOLLOWUP TO PUBLIC UTILITIES COMMENT
 NUMBER 1 AS NOTED IN THE RESPONSE. THAT WORK WOULD
 LIKELY ALSO REQUIRE SOME SIDEWALK REPLACEMENT.
  
 -RESPONSE LETTER SAID IRRIGATION WILL BE FED FROM A
 SEPARATE METER, BUT DID NOT SEE ON PLANS. PLEASE ADD.
  
 QUESTIONS AND COORDINATION CONTACTS:
 O MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR WITH
 CITY OF WPB PUBLIC UTILITIES, REGARDING PLACEMENT OF
 BACKFLOW DEVICES AND WATER METERS. CONTACT HIM AT
 561-822-2262 OR [email protected]
 O RICK ROSSANO, SR. PROJECT COORDINATOR, ENGINEERING
 SERVICES DEPARTMENT AT 561-494-1098 [email protected]
 O MIKE TECHNOW, PROJECT ENGINEER, PUBLIC UTILITIES
 DEPARTMENT AT 561-494-1047 OR [email protected]
 O TRACY WARD, SR. STORMWATER ENGINEER, ENGINEERING
 SERVICES DEPT. AT 561-494-1120 OR [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 01-13-2022 Cont ID  
Sent By rrossano Date 01-13-2022 Time   Rev Time  
Received By rrossano Date 01-13-2022 Time   Sent To  
Notes
2022-01-13 08:21:16COMMENTS FROM RICK ROSSANO, SR. PROJECT COORDINATOR,
 ENG. SERVICES DEPT., 561-494-1098 [email protected] :
 GENERAL:
 O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (Z-XXXXXXXX).
 O THE CITY OF WEST PALM BEACH HAS A NUMBER OF
 REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY
 AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND
 WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE
 DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK
 BELOW:
 A. HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WP
 B_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FUL
 L-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97
 B1960045731D3658206F27451722716EF
 B. THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE
 FOUND HERE:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
 C. ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM
 BEACH, FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08,
 ADOPTED SEPT. 22, 2008. (SUPPLEMENT NO. 18)
 CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL,
 SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER
 SERVICE FACILITIES OF THE CITY.
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
 O AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, REFER TO THE LINK BELOW:
 A. HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PU
 BLICATIONS/BACKFLOW-CROSS-CONNECTION- CONTROL-MANUAL
 O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1079 FOR FURTHER
 ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION
 ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD
 SURVEY, POT-HOLING, SOFT DIGS ETC.
  
 BACKFLOW ASSEMBLY AND METERS:
 O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER
 SERVICES AND WATER METERS, ALONG WITH WHAT IS HAPPENING
 TO THEM.
 O SHOW EXISTING AND PROPOSED DEDICATED UTILITY
 EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO
 PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO
 STRUCTURES WITHIN EASEMENT.
 O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION
 OF WATER METER AND BACKFLOW
 PREVENTION.
 O BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY
 OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER
 METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO
 PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE
 INSTALLED ABOVE-GROUND ONLY.
 O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE
 NOTE USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA.
  
 WATER/WASTEWATER PLAN:
 O PROVIDE VERTICAL DATUM AND DATUM CONVERSION
 INFORMATION (NAVD 1988 AND NGVD 1929).
 O SHOW PROJECT ADDRESS ON ALL PLAN SHEETS.
 O PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE
 STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC.
 O PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND
 DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND
 SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH
 PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE
 AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS,
 BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO
 BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS,
 DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS,
 ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT
 ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF
 SANITARY SEWER LINES.
 O GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR
 SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW.
 O DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN
 VIEW FOR ALL SANITARY AND STORM SEWERS.
 O SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL.
 O PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED
 UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC,
 ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION
 FACILITIES LOCATED ON THE RIGHT-OF-WAY.
 O PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER
 AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD
 DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS.
 O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY
 TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT
 APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING
 AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE,
 MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS
 SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008
 FOR WATER.
 O PROVIDE FIRE FLOW TEST DATA.
 O PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND
 STORMWATER INFRASTRUCTURE ALONG ENTIRE PROJECT
 FRONTAGE.
 O CUT AND CAP UTILITIES NOT IN USE AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 ROW.
 O WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL
 BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY
 PROPOSED LENGTH IN FEET.
 O CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY
 SEWER ARE REQUIRED.
 O PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE
 JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET.
 O ADD NOTE TO PLANS SPECIFYING CITY?S DOWNSTREAM LIFT
 STATION NUMBER.
 O PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR
 PROPOSED SANITARY LATERALS.
 O LABEL WATER LINES AS PRIVATE WHERE APPLICABLE.
 O PLEASE SHOW AND LABEL EXISTING AND PROPOSED GREASE
 TRAPS (IF ANY).
 O PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN
 OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER.
  
 FORMAL ENGINEERING REVIEW:
 O FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES
 NOI REQUIREMENTS WILL BE ENFORCED.
 - AN NOI IS REQUIRED FOR PROJECTS THAT:
 - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS
 THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF
 DEVELOPMENT OR SALE;
 - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE
 STATE OR TO SURFACE WATERS OF THE STATE THROUGH A
 MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4).
 - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF
 CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION
 THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL
 SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT
 OF THE 10-2 CERTIFICATION.
 O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE
 EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS.
 O FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF
 WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS.
 O FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING
 APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT
 SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING
 SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED
 LEAD-FREE DESIGN.
 O FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES
 ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY
 LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT
 PARCELS.
 O FOR FORMAL ENGINEERING SUBMITTAL, IF WATER LINES ARE
 BEING REPLACED IN ROW, SHOW ADJACENT PARCEL ADDRESSES.
 O FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO PROVIDE
 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF
 PROPOSED TRENCH IN CITY MAINTAINED ROADWAY AREAS PER
 CITY OF WPB STANDARD DETAIL GC-8.
 O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE
 CALCULATIONS OF PERVIOUS AND IMPERVIOUS AREAS FOR
 PROPOSED IMPROVED AREAS.
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-494-2262 OR
 [email protected]:
  
 -PAVEMENT RESTORATION OF STATE ST. AND GRANT ST. WOULD
 BE REQUIRED FOR PROPOSED UTILITY WORK.
  
 -WATER SERVICE DESIGN IS NONSTANDARD. PLEASE USE
 STANDARD DESIGN FOR WATER SERVICES.
  
 -LS PLAN DESCRIBED FIRE SPRINKLERS. FIRE SPRINKLERS
 CANNOT BE FED FROM DOMESTIC WATER SERVICES. WOULD NEED
 AT LEAST ONE DEDICATED FIRE SERVICE WITH DETECTOR
 BACKFLOW ASSEMBLY.
  
 -GEO REPORT SAYS GFA SHOULD BE REQUESTED TO REVIEW DATA
 TO SEE IF RECOMMENDATIONS ARE VALID. WILL APPLICANT
 FOLLOWUP WITH THEM ONCE BUILDING DETAILS ARE FINALIZED?
  
 -LANDSCAPE PLAN IS MISSING FROM SUBMITTAL PACKAGE.
 PLEASE SUBMIT AND ENSURE NO CONFLICTS WITH UTILITIES.
  
 -THE ROW VACATION APPLICATION DOES NOT HAVE THE WRITTEN
 VERIFICATION FROM THE UTILITY COMPANIES THAT THERE ARE
 NO CONFLICTS. PLEASE SUBMIT.
  
 -THERE APPEARS TO BE AN EXISTING UTILITY BOX
 CONFLICTING WITH PROPOSED CURBING ON GRANT ST. NEAR THE
 MANHOLE.
  
 -TURN AROUND SPACE DOES NOT APPEAR USABLE. SEEMS
 VEHICLE WOULD HIT DUMPSTER STRUCTURE.
  
 -SIDEWALK CHANGE ON GRANT ST. MAY REQUIRE EASEMENT.
  
 -NOT SURE IF PARKING IS BEING PROPOSED ON TAMARIND
 WHERE THE AIR RELIEF MANHOLE STRUCTURES ARE LOCATED. IF
 SO, AND THE INTENT IS TO LOWER THE ELEVATION, THEN
 APPLICANT TEAM WOULD NEED TO VERIFY THAT THE STRUCTURE
 CAN BE LOWERED. THERE IS A SIMILAR ISSUE WITH A NEARBY
 VALVE BOX.
  
 -PLEASE PROVIDE MORE DETAIL ON THE METERED WATER
 SERVICES. THERE ARE ONLY FOUR DOMESTIC, BUT SIX
 DWELLING UNITS. IS THE INTENT TO HAVE A METER FOR EACH
 UNIT OR EACH FLOOR? IS THERE A SEPARATE METER FOR
 COMMON AREAS?
  
 -HOW WILL THE IRRIGATION UTILITY BILL BE HANDLED? WILL
 THERE BE AN HOA OR PROPERTY MANAGER?
  
 -SHOW AND LABEL BACKFLOW ASSEMBLIES FOR IRRIGATION
 SERVICE AND ALSO ANY WATER SERVICES FEEDING MULTIPLE
 DWELLING UNITS.
  
 -SHOW AND LABEL UTILITY EASEMENT FOR METERED WATER
 SERVICES ON PRIVATE PROPERTY.
  
 -SOME SIDEWALKS MAY REQUIRE REPLACEMENT DUE TO
 PROJECT?S UTILITY WORK.
  
 -HISTORIC PICTURES SHOW DRIVEWAY APPROACH ON STATE ST.
 CRACKED/DAMAGED.
  
 -SEWER LATERAL CLEANOUT NOT SHOWN ON CIVIL PLAN. PLEASE
 ADD AND LABEL.
  
 -PAVEMENT RESTORATION OF STATE ST. AND GRANT ST. WOULD
 BE REQUIRED FOR PROPOSED UTILITY WORK.
  
 -WATER SERVICE DESIGN IS NONSTANDARD. PLEASE USE
 STANDARD DESIGN FOR WATER SERVICES.
  
 -LS PLAN DESCRIBED FIRE SPRINKLERS. FIRE SPRINKLERS
 CANNOT BE FED FROM DOMESTIC WATER SERVICES. WOULD NEED
 AT LEAST ONE DEDICATED FIRE SERVICE WITH DETECTOR
 BACKFLOW ASSEMBLY.
  
 -GEO REPORT SAYS GFA SHOULD BE REQUESTED TO REVIEW DATA
 TO SEE IF RECOMMENDATIONS ARE VALID. WILL APPLICANT
 FOLLOWUP WITH THEM ONCE BUILDING DETAILS ARE FINALIZED?
  
 -LANDSCAPE PLAN IS MISSING FROM SUBMITTAL PACKAGE.
 PLEASE SUBMIT AND ENSURE NO CONFLICTS WITH UTILITIES.
  
 -THE ROW VACATION APPLICATION DOES NOT HAVE THE WRITTEN
 VERIFICATION FROM THE UTILITY COMPANIES THAT THERE ARE
 NO CONFLICTS. PLEASE SUBMIT.
  
 -THERE APPEARS TO BE AN EXISTING UTILITY BOX
 CONFLICTING WITH PROPOSED CURBING ON GRANT ST. NEAR THE
 MANHOLE.
  
 -TURN AROUND SPACE DOES NOT APPEAR USABLE. SEEMS
 VEHICLE WOULD HIT DUMPSTER STRUCTURE.
  
 -SIDEWALK CHANGE ON GRANT ST. MAY REQUIRE EASEMENT.
  
 -NOT SURE IF PARKING IS BEING PROPOSED ON TAMARIND
 WHERE THE AIR RELIEF MANHOLE STRUCTURES ARE LOCATED. IF
 SO, AND THE INTENT IS TO LOWER THE ELEVATION, THEN
 APPLICANT TEAM WOULD NEED TO VERIFY THAT THE STRUCTURE
 CAN BE LOWERED. THERE IS A SIMILAR ISSUE WITH A NEARBY
 VALVE BOX.
  
 -PLEASE PROVIDE MORE DETAIL ON THE METERED WATER
 SERVICES. THERE ARE ONLY FOUR DOMESTIC, BUT SIX
 DWELLING UNITS. IS THE INTENT TO HAVE A METER FOR EACH
 UNIT OR EACH FLOOR? IS THERE A SEPARATE METER FOR
 COMMON AREAS?
  
 -HOW WILL THE IRRIGATION UTILITY BILL BE HANDLED? WILL
 THERE BE AN HOA OR PROPERTY MANAGER?
  
 -SHOW AND LABEL BACKFLOW ASSEMBLIES FOR IRRIGATION
 SERVICE AND ALSO ANY WATER SERVICES FEEDING MULTIPLE
 DWELLING UNITS.
  
 -SHOW AND LABEL UTILITY EASEMENT FOR METERED WATER
 SERVICES ON PRIVATE PROPERTY.
  
 -SOME SIDEWALKS MAY REQUIRE REPLACEMENT DUE TO
 PROJECT?S UTILITY WORK.
  
 -HISTORIC PICTURES SHOW DRIVEWAY APPROACH ON STATE ST.
 CRACKED/DAMAGED.
  
 -SEWER LATERAL CLEANOUT NOT SHOWN ON CIVIL PLAN. PLEASE
 ADD AND LABEL.
  
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
  
  
 QUESTIONS AND COORDINATION CONTACTS:
 O MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR WITH
 CITY OF WPB PUBLIC UTILITIES, REGARDING PLACEMENT OF
 BACKFLOW DEVICES AND WATER METERS. CONTACT HIM AT
 561-822-2262 OR [email protected]
 O RICK ROSSANO, SR. PROJECT COORDINATOR, ENGINEERING
 SERVICES DEPARTMENT AT 561-494-1098 [email protected]
 O MIKE TECHNOW, PROJECT ENGINEER, PUBLIC UTILITIES
 DEPARTMENT AT 561-494-1047 OR [email protected]
 O TRACY WARD, SR. STORMWATER ENGINEER, ENGINEERING
 SERVICES DEPT. AT 561-494-1120 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 07-27-2022 Cont ID  
Sent By pleduc Date 07-27-2022 Time   Rev Time 0.00
Received By pleduc Date 07-27-2022 Time 15:19 Sent To  
Notes
2022-07-27 15:19:56FIRE HAS NO OBJECTIONS TO THE PROPOSED AND APPROVES.
  
 FIRE'S APPROVAL OF THIS SUBMITTED PROJECT MAY NOT
 CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 FIRE SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT THE
 APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE FIRE CODES AND
 STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 04-04-2022 Cont ID  
Sent By pleduc Date 04-04-2022 Time   Rev Time 0.00
Received By pleduc Date 04-04-2022 Time 10:11 Sent To  
Notes
2022-04-04 10:11:53FIRE HAS NO OBJECTIONS TO THE PROPOSED AND APPROVES.
  
 FIRE'S APPROVAL OF THIS SUBMITTED PROJECT MAY NOT
 CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 FIRE SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT THE
 APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE FIRE CODES AND
 STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 01-04-2022 Cont ID  
Sent By pleduc Date 01-04-2022 Time   Rev Time 0.00
Received By pleduc Date 01-04-2022 Time 13:50 Sent To  
Notes
2022-01-04 13:50:35THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE DEPARTMENT.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT. THE FOLLOWING COMMENTS ARE INTENDED
 TO PROVIDE GUIDANCE FOR BUILDING PLAN SUBMITTAL.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING(S) SHALL COMPLY
 WITH THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION
 CODE, INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE
 CODES.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE PER THE FLORIDA FIRE PREVENTION CODE.
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED, AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 THE PROPOSED LOCATION OF THE FIRE HYDRANT AND FDC SHALL
 BE WITHIN 100' OF EACH OTHER AND CLOSELY COORDINATED
 WITH THE BUREAU OF FIRE PREVENTION.
  
 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM,
 ENSURE THEY COMPLY WITH THE REQUIREMENTS OF F.A.C. 61G
 AND SUBMITTED WITH THE MASTER PERMIT.
  
 9A. THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE
 LOCATIONS SHALL MEET AND BE INSTALLED PER THE
 REQUIREMENTS OF NFPA 24 AND SHALL BE COORDINATED WITH
 THE OFFICE OF FIRE MARSHAL, THE CITY'S ENGINEERS
 OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S PLANNING
 AND ZONING OFFICE.
  
 10. COMPLETE LIFE SAFETY PLANS FOR THE OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, EXIT SEPARATION DISTANCES, COMMON PATHS OF
 TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, EMERGENCY
 LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE
 EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES
 AND EQUIPMENT.
  
 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE
 SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY
 DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS.
  
 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop L LANDSCAPING
Rev No 4 Status P Date 11-17-2022 Cont ID  
Sent By rcaranci Date 11-17-2022 Time 11:59 Rev Time 0.00
Received By rcaranci Date 11-17-2022 Time 11:59 Sent To  
Notes
2022-11-17 11:59:40FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 1002 GRANT ST. Z21120021
 NOVEMBER 17, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PROVIDE A SEPARATE TREE DISPOSITION PLAN
 SHOWING THE LOCATIONS OF THE EXISTING TREES AND INCLUDE
 THE FOLLOWING INFORMATION:
 ??? SATISFIED. ADD A COLUMN TO THE CHART FOR MITIGATION
 SQUARE FOOTAGE DUE AND SHOW THE AMOUNT FOR EACH TREE
 PROPOSED TO BE REMOVED BASED ON THE CATEGORY OR TREE
 CANOPY DIAMETER. COLUMN SHOULD BE LABELED MITIGATION
 DUE. TREES WITH A CANOPY 20 FEET OR MORE IN DIAMETER
 MUST HAVE THE ACTUAL SQUARE FOOTAGE CALCULATED AND
 ENTERED ON THE CHART.
 ??? SATISFIED. PROVIDE TOTAL OF MITIGATION SQUARE
 FOOTAGE DUE.
 ??? SATISFIED. PROVIDE A TOTAL OF MITIGATION SQUARE
 FOOTAGE PROVIDED BASED ON THE PLANT LIST.
 PROVIDE TOTAL FOR ALL TREES AFTER CORRECTIONS TO PLANT
 LIST.
  
 2. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE
 TREES IN GOOD CONDITION TO BE PRESERVED ON SITE OR
 RELOCATED. ANSI A 300 (PART 5) STANDARDS SPECIFY
 EXAMPLES OF SUITABILITY RATINGS OF GOOD, MODERATE, OR
 POOR FOR RELOCATION. PROVIDE AN ARBORIST REPORT SHOWING
 CONDITION FOR ALL TREES AND RELOCATION POTENTIAL FOR
 THE NATIVE TREES AND PALMS PROPOSED TO BE REMOVED.
  
 3. SATISFIED. PROVIDE THE CALCULATIONS FOR THE MINIMUM
 REQUIRED SHADE TREES, FLOWERING TREES AND SHRUBS FOR
 THE SITE BASED ON 40% OPEN SPACE PER SECTION
 94-442(C)(2)B. PROVIDE THE CALCULATIONS FOR THE OPEN
 SPACE BASED ON THE SITE SQUARE FOOTAGE. ADD THE
 MULTIFAMILY TREE REQUIREMENT TO THIS TOTAL.
  
 4. SATISFIED. PROVIDE THE NUMBER AND PERCENTAGE OF
 SUBSTITUTION OF PALMS FOR REQUIRED TREES. SECTION
 94-442(D) REQUIRES A 3:1 RATIO FOR SUBSTITUTION FOR
 PALMS EXCEPT THE LISTED 1:1 SPECIES.
  
  
 5. SATISFIED. PER SECTION 94-443(A)(2) LABEL THE
 REQUIRED 5 FOOT LANDSCAPE BUFFER ALONG EACH PROPERTY
 LINE AND CALCULATE THE NUMBER OF TREES REQUIRED AND
 PROVIDED FOR EACH BUFFER SEGMENT. THE TOTAL LENGTH OF
 THE PROPERTY LINE PER THE SURVEY MUST BE USED.
 CALCULATIONS FOR BUFFER LENGTHS AND REQUIRED NUMBER OF
 TREES ARE NOT CORRECT. NORTH AND SOUTH ARE 90 FEET
 REQUIRING 3 TREES EACH. EAST AND WEST ARE 89.66 FEET
 REQUIRING 3 TREES EACH. CORRECT THE CALCULATIONS AND
 PROVIDE THE THIRD REQUIRED TREE FOR THE NORTH BUFFER.
 PREVIOUS PLAN SUBMITTED MET THE REQUIREMENTS.
  
 6. SATISFIED. PER SECTION 94-443 (E)2., PROVIDE THE 30%
 FOUNDATION PLANTING CALCULATION REQUIRED AND PROVIDED
 FOR EACH BUILDING.
 THE PLAN MUST SHOW THE LINEAR FOOTAGE OF EACH BUILDING
 PERIMETER, REQUIRED LINEAR FOOTAGE AND PROVIDED.
 THE REQUIREMENT IS 40% PER SECTION 94-443(D)2.A.
  
 7. SATISFIED. PER SECTION 94-443(C)(3)A. AND B.,
 TERMINAL LANDSCAPE ISLANDS AND INTERIOR ISLANDS MUST
 HAVE AT LEAST 8 FEET WIDE LANDSCAPE AREA AND RUN THE
 FULL LENGTH OF THE ADJACENT PARKING SPACE. EACH AREA
 SHALL HAVE AT LEAST ONE SHADE OR FLOWERING TREE PER ROW
 OF PARKING. LANDSCAPE BUFFER OF 5 FEET MAY BE COUNTED
 AS PART OF THE TERMINAL ISLAND. SHOW DIMENSIONS ON THE
 LANDSCAPE PLAN.
 8/8/22 REDESIGN DOES NOT MEET THE REQUIREMENT NORTH OF
 THE ADA SPACE. PROVIDE THE TERMINAL LANDSCAPE ISLAND
 AND SHADE TREE.
  
 8. SATISFIED. A MINIMUM OF 75% OF ALL TREES REQUIRED TO
 BE PLANTED WITHIN THE PARKING AREA MUST BE CATEGORY 1
 SHADE TREES. SHOW THE PERCENTAGE PROVIDED.
 9. SATISFIED. PER SECTION 94-442(G) PROVIDE THE
 REQUIRED 50 POINTS FROM THE FLORIDA FRIENDLY DESIGN
 OPTIONS LIST AND SHOW THE TOTAL PROVIDED.
 10. SATISFIED. PROVIDE A SECTION IN A LANDSCAPE DATA
 CHART TO COMPLY WITH SECTION 94-445 L. PLANT SPECIES. A
 MINIMUM OF 60 PERCENT OF PLANT MATERIAL ADDED SHALL BE
 FLORIDA NATIVE OR DROUGHT TOLERANT SPECIES SELECTED
 FROM THE CITY LIST OR THE LIST OF SPECIES IN THE MOST
 RECENT EDITION OF SOUTH FLORIDA WATER MANAGEMENT
 DISTRICT WATERWISE SOUTH FLORIDA LANDSCAPES. PROVIDE
 THE TOTAL PERCENTAGE OF NATIVE AND DROUGHT TOLERANT
 PLANTS BASED ON FINAL PLANT LIST.
  
 11. SATISFIED. LOCATIONS OF PROPOSED UTILITY LINES
 INCLUDING WATER, SEWER AND DRAINAGE CONFLICT WITH
 REQUIRED LANDSCAPING. CIVIL ENGINEERING PLAN, SITE PLAN
 AND LANDSCAPE PLAN MUST BE CONSISTENT.
  
 UTILITIES MUST BE SHOWN ON THE LANDSCAPE PLAN AND
 CONFLICTS RESOLVED. UTILITY POSITIONS WILL REQUIRE
 ADJUSTMENT OF PLANTING LOCATIONS OF SOME REQUIRED
 TREES.
 8/8/22 SEWER LINE IS STILL IN CONFLICT WITH PROPOSED
 TREE.
  
 12. SATISFIED. SHOW AND LABEL ALL OVERHEAD POWER LINES
 THAT WILL LIMIT THE TREE SPECIES TO RIGHT TREE RIGHT
 PLACE GUIDELINES.
  
 13. SATISFIED. PER SECTION 94-443 (A)(1) A PROTECTIVE
 SCREEN WALL IS REQUIRED ALONG THE ADJACENT RESIDENTIAL
 PROPERTY LINES.
  
 ADDITIONAL COMMENTS 8/8/22:
  
 1. SATISFIED. ADD EXISTING LIVE OAK TO PLANT LIST.
  
 2. SATISFIED. MUST SHOW SCREENING OF ABOVE GROUND
 VALVES.
  
 3. SATISFIED. CRAPE MYRTLES NEED TO BE SHOWN AT 12 FT
 HEIGHT SPECIFICATION ON THE PLAN. ANY SUPPLY ISSUES MAY
 BE ADDRESSED AT TIME OF INSTALLATION.
  
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 3 Status F Date 08-08-2022 Cont ID  
Sent By rcaranci Date 08-08-2022 Time 12:29 Rev Time 0.00
Received By rcaranci Date 08-08-2022 Time 12:29 Sent To  
Notes
2022-08-08 12:29:45FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 1002 GRANT ST. Z21120021
 AUGUST 8, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PROVIDE A SEPARATE TREE DISPOSITION PLAN
 SHOWING THE LOCATIONS OF THE EXISTING TREES AND INCLUDE
 THE FOLLOWING INFORMATION:
 ? SATISFIED. ADD A COLUMN TO THE CHART FOR MITIGATION
 SQUARE FOOTAGE DUE AND SHOW THE AMOUNT FOR EACH TREE
 PROPOSED TO BE REMOVED BASED ON THE CATEGORY OR TREE
 CANOPY DIAMETER. COLUMN SHOULD BE LABELED MITIGATION
 DUE. TREES WITH A CANOPY 20 FEET OR MORE IN DIAMETER
 MUST HAVE THE ACTUAL SQUARE FOOTAGE CALCULATED AND
 ENTERED ON THE CHART.
 ? SATISFIED. PROVIDE TOTAL OF MITIGATION SQUARE FOOTAGE
 DUE.
 ? PARTIALLY SATISFIED. PROVIDE A TOTAL OF MITIGATION
 SQUARE FOOTAGE PROVIDED BASED ON THE PLANT LIST.
 PROVIDE TOTAL FOR ALL TREES AFTER CORRECTIONS TO PLANT
 LIST.
  
 2. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE
 TREES IN GOOD CONDITION TO BE PRESERVED ON SITE OR
 RELOCATED. ANSI A 300 (PART 5) STANDARDS SPECIFY
 EXAMPLES OF SUITABILITY RATINGS OF GOOD, MODERATE, OR
 POOR FOR RELOCATION. PROVIDE AN ARBORIST REPORT SHOWING
 CONDITION FOR ALL TREES AND RELOCATION POTENTIAL FOR
 THE NATIVE TREES AND PALMS PROPOSED TO BE REMOVED.
  
 3. SATISFIED. PROVIDE THE CALCULATIONS FOR THE MINIMUM
 REQUIRED SHADE TREES, FLOWERING TREES AND SHRUBS FOR
 THE SITE BASED ON 40% OPEN SPACE PER SECTION
 94-442(C)(2)B. PROVIDE THE CALCULATIONS FOR THE OPEN
 SPACE BASED ON THE SITE SQUARE FOOTAGE. ADD THE
 MULTIFAMILY TREE REQUIREMENT TO THIS TOTAL.
  
 4. SATISFIED. PROVIDE THE NUMBER AND PERCENTAGE OF
 SUBSTITUTION OF PALMS FOR REQUIRED TREES. SECTION
 94-442(D) REQUIRES A 3:1 RATIO FOR SUBSTITUTION FOR
 PALMS EXCEPT THE LISTED 1:1 SPECIES.
  
  
 5. NOT SATISFIED. PER SECTION 94-443(A)(2) LABEL THE
 REQUIRED 5 FOOT LANDSCAPE BUFFER ALONG EACH PROPERTY
 LINE AND CALCULATE THE NUMBER OF TREES REQUIRED AND
 PROVIDED FOR EACH BUFFER SEGMENT. THE TOTAL LENGTH OF
 THE PROPERTY LINE PER THE SURVEY MUST BE USED.
 CALCULATIONS FOR BUFFER LENGTHS AND REQUIRED NUMBER OF
 TREES ARE NOT CORRECT. NORTH AND SOUTH ARE 90 FEET
 REQUIRING 3 TREES EACH. EAST AND WEST ARE 89.66 FEET
 REQUIRING 3 TREES EACH. CORRECT THE CALCULATIONS AND
 PROVIDE THE THIRD REQUIRED TREE FOR THE NORTH BUFFER.
 PREVIOUS PLAN SUBMITTED MET THE REQUIREMENTS.
  
 6. SATISFIED. PER SECTION 94-443 (E)2., PROVIDE THE 30%
 FOUNDATION PLANTING CALCULATION REQUIRED AND PROVIDED
 FOR EACH BUILDING.
 THE PLAN MUST SHOW THE LINEAR FOOTAGE OF EACH BUILDING
 PERIMETER, REQUIRED LINEAR FOOTAGE AND PROVIDED.
 THE REQUIREMENT IS 40% PER SECTION 94-443(D)2.A.
  
 7. NOT SATISFIED. PER SECTION 94-443(C)(3)A. AND B.,
 TERMINAL LANDSCAPE ISLANDS AND INTERIOR ISLANDS MUST
 HAVE AT LEAST 8 FEET WIDE LANDSCAPE AREA AND RUN THE
 FULL LENGTH OF THE ADJACENT PARKING SPACE. EACH AREA
 SHALL HAVE AT LEAST ONE SHADE OR FLOWERING TREE PER ROW
 OF PARKING. LANDSCAPE BUFFER OF 5 FEET MAY BE COUNTED
 AS PART OF THE TERMINAL ISLAND. SHOW DIMENSIONS ON THE
 LANDSCAPE PLAN.
 8/8/22 REDESIGN DOES NOT MEET THE REQUIREMENT NORTH OF
 THE ADA SPACE. PROVIDE THE TERMINAL LANDSCAPE ISLAND
 AND SHADE TREE.
  
 8. SATISFIED. A MINIMUM OF 75% OF ALL TREES REQUIRED TO
 BE PLANTED WITHIN THE PARKING AREA MUST BE CATEGORY 1
 SHADE TREES. SHOW THE PERCENTAGE PROVIDED.
 9. SATISFIED. PER SECTION 94-442(G) PROVIDE THE
 REQUIRED 50 POINTS FROM THE FLORIDA FRIENDLY DESIGN
 OPTIONS LIST AND SHOW THE TOTAL PROVIDED.
 10. SATISFIED. PROVIDE A SECTION IN A LANDSCAPE DATA
 CHART TO COMPLY WITH SECTION 94-445 L. PLANT SPECIES. A
 MINIMUM OF 60 PERCENT OF PLANT MATERIAL ADDED SHALL BE
 FLORIDA NATIVE OR DROUGHT TOLERANT SPECIES SELECTED
 FROM THE CITY LIST OR THE LIST OF SPECIES IN THE MOST
 RECENT EDITION OF SOUTH FLORIDA WATER MANAGEMENT
 DISTRICT WATERWISE SOUTH FLORIDA LANDSCAPES. PROVIDE
 THE TOTAL PERCENTAGE OF NATIVE AND DROUGHT TOLERANT
 PLANTS BASED ON FINAL PLANT LIST.
  
 11. PARTIALLY SATISFIED. LOCATIONS OF PROPOSED UTILITY
 LINES INCLUDING WATER, SEWER AND DRAINAGE CONFLICT WITH
 REQUIRED LANDSCAPING. CIVIL ENGINEERING PLAN, SITE PLAN
 AND LANDSCAPE PLAN MUST BE CONSISTENT.
  
 UTILITIES MUST BE SHOWN ON THE LANDSCAPE PLAN AND
 CONFLICTS RESOLVED. UTILITY POSITIONS WILL REQUIRE
 ADJUSTMENT OF PLANTING LOCATIONS OF SOME REQUIRED
 TREES.
 8/8/22 SEWER LINE IS STILL IN CONFLICT WITH PROPOSED
 TREE.
  
 12. SATISFIED. SHOW AND LABEL ALL OVERHEAD POWER LINES
 THAT WILL LIMIT THE TREE SPECIES TO RIGHT TREE RIGHT
 PLACE GUIDELINES.
  
 13. SATISFIED. PER SECTION 94-443 (A)(1) A PROTECTIVE
 SCREEN WALL IS REQUIRED ALONG THE ADJACENT RESIDENTIAL
 PROPERTY LINES.
  
 ADDITIONAL COMMENTS 8/8/22:
  
 1. ADD EXISTING LIVE OAK TO PLANT LIST.
  
 2. MUST SHOW SCREENING OF ABOVE GROUND VALVES.
  
 3. CRAPE MYRTLES NEED TO BE SHOWN AT 12 FT HEIGHT
 SPECIFICATION ON THE PLAN. ANY SUPPLY ISSUES MAY BE
 ADDRESSED AT TIME OF INSTALLATION.
  
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 04-05-2022 Cont ID  
Sent By rcaranci Date 04-05-2022 Time 18:48 Rev Time 0.00
Received By rcaranci Date 04-05-2022 Time 18:48 Sent To  
Notes
2022-04-05 18:52:13FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 1002 GRANT ST. Z21120021
 APRIL 5, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PROVIDE A SEPARATE TREE DISPOSITION PLAN
 SHOWING THE LOCATIONS OF THE EXISTING TREES AND INCLUDE
 THE FOLLOWING INFORMATION:
 ? NOT SATISFIED. ADD A COLUMN TO THE CHART FOR
 MITIGATION SQUARE FOOTAGE DUE AND SHOW THE AMOUNT FOR
 EACH TREE PROPOSED TO BE REMOVED BASED ON THE CATEGORY
 OR TREE CANOPY DIAMETER. COLUMN SHOULD BE LABELED
 MITIGATION DUE. TREES WITH A CANOPY 20 FEET OR MORE IN
 DIAMETER MUST HAVE THE ACTUAL SQUARE FOOTAGE CALCULATED
 AND ENTERED ON THE CHART.
 ? NOT SATISFIED. PROVIDE TOTAL OF MITIGATION SQUARE
 FOOTAGE DUE.
 ? NOT SATISFIED. PROVIDE A TOTAL OF MITIGATION SQUARE
 FOOTAGE PROVIDED BASED ON THE PLANT LIST.
  
 2. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE
 TREES IN GOOD CONDITION TO BE PRESERVED ON SITE OR
 RELOCATED. ANSI A 300 (PART 5) STANDARDS SPECIFY
 EXAMPLES OF SUITABILITY RATINGS OF GOOD, MODERATE, OR
 POOR FOR RELOCATION. PROVIDE AN ARBORIST REPORT SHOWING
 CONDITION FOR ALL TREES AND RELOCATION POTENTIAL FOR
 THE NATIVE TREES AND PALMS PROPOSED TO BE REMOVED.
  
 3. SATISFIED. PROVIDE THE CALCULATIONS FOR THE MINIMUM
 REQUIRED SHADE TREES, FLOWERING TREES AND SHRUBS FOR
 THE SITE BASED ON 40% OPEN SPACE PER SECTION
 94-442(C)(2)B. PROVIDE THE CALCULATIONS FOR THE OPEN
 SPACE BASED ON THE SITE SQUARE FOOTAGE. ADD THE
 MULTIFAMILY TREE REQUIREMENT TO THIS TOTAL.
  
 4. SATISFIED. PROVIDE THE NUMBER AND PERCENTAGE OF
 SUBSTITUTION OF PALMS FOR REQUIRED TREES. SECTION
 94-442(D) REQUIRES A 3:1 RATIO FOR SUBSTITUTION FOR
 PALMS EXCEPT THE LISTED 1:1 SPECIES.
  
  
 5. SATISFIED. PER SECTION 94-443(A)(2) LABEL THE
 REQUIRED 5 FOOT LANDSCAPE BUFFER ALONG EACH PROPERTY
 LINE AND CALCULATE THE NUMBER OF TREES REQUIRED AND
 PROVIDED FOR EACH BUFFER SEGMENT. THE TOTAL LENGTH OF
 THE PROPERTY LINE PER THE SURVEY MUST BE USED.
  
 6. PARTIALLY SATISFIED. PER SECTION 94-443 (E)2.,
 PROVIDE THE 30% FOUNDATION PLANTING CALCULATION
 REQUIRED AND PROVIDED FOR EACH BUILDING.
 THE PLAN MUST SHOW THE LINEAR FOOTAGE OF EACH BUILDING
 PERIMETER, REQUIRED LINEAR FOOTAGE AND PROVIDED.
 THE REQUIREMENT IS 40% PER SECTION 94-443(D)2.A.
  
 7. SATISFIED. PER SECTION 94-443(C)(3)A. AND B.,
 TERMINAL LANDSCAPE ISLANDS AND INTERIOR ISLANDS MUST
 HAVE AT LEAST 8 FEET WIDE LANDSCAPE AREA AND RUN THE
 FULL LENGTH OF THE ADJACENT PARKING SPACE. EACH AREA
 SHALL HAVE AT LEAST ONE SHADE OR FLOWERING TREE PER ROW
 OF PARKING. LANDSCAPE BUFFER OF 5 FEET MAY BE COUNTED
 AS PART OF THE TERMINAL ISLAND. SHOW DIMENSIONS ON THE
 LANDSCAPE PLAN.
  
 8. SATISFIED. A MINIMUM OF 75% OF ALL TREES REQUIRED TO
 BE PLANTED WITHIN THE PARKING AREA MUST BE CATEGORY 1
 SHADE TREES. SHOW THE PERCENTAGE PROVIDED.
 9. SATISFIED. PER SECTION 94-442(G) PROVIDE THE
 REQUIRED 50 POINTS FROM THE FLORIDA FRIENDLY DESIGN
 OPTIONS LIST AND SHOW THE TOTAL PROVIDED.
 10. SATISFIED. PROVIDE A SECTION IN A LANDSCAPE DATA
 CHART TO COMPLY WITH SECTION 94-445 L. PLANT SPECIES. A
 MINIMUM OF 60 PERCENT OF PLANT MATERIAL ADDED SHALL BE
 FLORIDA NATIVE OR DROUGHT TOLERANT SPECIES SELECTED
 FROM THE CITY LIST OR THE LIST OF SPECIES IN THE MOST
 RECENT EDITION OF SOUTH FLORIDA WATER MANAGEMENT
 DISTRICT WATERWISE SOUTH FLORIDA LANDSCAPES. PROVIDE
 THE TOTAL PERCENTAGE OF NATIVE AND DROUGHT TOLERANT
 PLANTS BASED ON FINAL PLANT LIST.
  
 11. NOT SATISFIED. LOCATIONS OF PROPOSED UTILITY LINES
 INCLUDING WATER, SEWER AND DRAINAGE CONFLICT WITH
 REQUIRED LANDSCAPING. CIVIL ENGINEERING PLAN, SITE PLAN
 AND LANDSCAPE PLAN MUST BE CONSISTENT.
  
 UTILITIES MUST BE SHOWN ON THE LANDSCAPE PLAN AND
 CONFLICTS RESOLVED. UTILITY POSITIONS WILL REQUIRE
 ADJUSTMENT OF PLANTING LOCATIONS OF SOME REQUIRED
 TREES.
  
 12. SATISFIED. SHOW AND LABEL ALL OVERHEAD POWER LINES
 THAT WILL LIMIT THE TREE SPECIES TO RIGHT TREE RIGHT
 PLACE GUIDELINES.
  
 13. SATISFIED. PER SECTION 94-443 (A)(1) A PROTECTIVE
 SCREEN WALL IS REQUIRED ALONG THE ADJACENT RESIDENTIAL
 PROPERTY LINES.
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 01-12-2022 Cont ID  
Sent By rcaranci Date 01-12-2022 Time 13:44 Rev Time 0.00
Received By rcaranci Date 01-12-2022 Time 13:44 Sent To  
Notes
2022-01-12 13:45:13FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 1002 GRANT ST. Z21120021
 JANUARY 12, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PROVIDE A SEPARATE TREE DISPOSITION PLAN SHOWING THE
 LOCATIONS OF THE EXISTING TREES AND INCLUDE THE
 FOLLOWING INFORMATION:
 ? ADD A COLUMN TO THE CHART FOR MITIGATION SQUARE
 FOOTAGE DUE AND SHOW THE AMOUNT FOR EACH TREE PROPOSED
 TO BE REMOVED BASED ON THE CATEGORY OR TREE CANOPY
 DIAMETER. COLUMN SHOULD BE LABELED MITIGATION DUE.
 TREES WITH A CANOPY 20 FEET OR MORE IN DIAMETER MUST
 HAVE THE ACTUAL SQUARE FOOTAGE CALCULATED AND ENTERED
 ON THE CHART.
 ? PROVIDE TOTAL OF MITIGATION SQUARE FOOTAGE DUE.
 ? PROVIDE A TOTAL OF MITIGATION SQUARE FOOTAGE PROVIDED
 BASED ON THE PLANT LIST.
  
 2. SECTION 94-448 (D)(3) REQUIRES NATIVE TREES IN GOOD
 CONDITION TO BE PRESERVED ON SITE OR RELOCATED. ANSI A
 300 (PART 5) STANDARDS SPECIFY EXAMPLES OF SUITABILITY
 RATINGS OF GOOD, MODERATE, OR POOR FOR RELOCATION.
 PROVIDE AN ARBORIST REPORT SHOWING CONDITION FOR ALL
 TREES AND RELOCATION POTENTIAL FOR THE NATIVE TREES AND
 PALMS PROPOSED TO BE REMOVED.
  
 3. PROVIDE THE CALCULATIONS FOR THE MINIMUM REQUIRED
 SHADE TREES, FLOWERING TREES AND SHRUBS FOR THE SITE
 BASED ON 40% OPEN SPACE PER SECTION 94-442(C)(2)B.
 PROVIDE THE CALCULATIONS FOR THE OPEN SPACE BASED ON
 THE SITE SQUARE FOOTAGE. ADD THE MULTIFAMILY TREE
 REQUIREMENT TO THIS TOTAL.
  
 4. PROVIDE THE NUMBER AND PERCENTAGE OF SUBSTITUTION OF
 PALMS FOR REQUIRED TREES. SECTION 94-442(D) REQUIRES A
 3:1 RATIO FOR SUBSTITUTION FOR PALMS EXCEPT THE LISTED
 1:1 SPECIES.
  
  
 5. PER SECTION 94-443(A)(2) LABEL THE REQUIRED 5 FOOT
 LANDSCAPE BUFFER ALONG EACH PROPERTY LINE AND CALCULATE
 THE NUMBER OF TREES REQUIRED AND PROVIDED FOR EACH
 BUFFER SEGMENT. THE TOTAL LENGTH OF THE PROPERTY LINE
 PER THE SURVEY MUST BE USED.
  
 6. PER SECTION 94-443 (E)2., PROVIDE THE 30% FOUNDATION
 PLANTING CALCULATION REQUIRED AND PROVIDED FOR EACH
 BUILDING.
  
 7. PER SECTION 94-443(C)(3)A. AND B., TERMINAL
 LANDSCAPE ISLANDS AND INTERIOR ISLANDS MUST HAVE AT
 LEAST 8 FEET WIDE LANDSCAPE AREA AND RUN THE FULL
 LENGTH OF THE ADJACENT PARKING SPACE. EACH AREA SHALL
 HAVE AT LEAST ONE SHADE OR FLOWERING TREE PER ROW OF
 PARKING. LANDSCAPE BUFFER OF 5 FEET MAY BE COUNTED AS
 PART OF THE TERMINAL ISLAND. SHOW DIMENSIONS ON THE
 LANDSCAPE PLAN.
  
 8. A MINIMUM OF 75% OF ALL TREES REQUIRED TO BE PLANTED
 WITHIN THE PARKING AREA MUST BE CATEGORY 1 SHADE TREES.
 SHOW THE PERCENTAGE PROVIDED.
 9. PER SECTION 94-442(G) PROVIDE THE REQUIRED 50 POINTS
 FROM THE FLORIDA FRIENDLY DESIGN OPTIONS LIST AND SHOW
 THE TOTAL PROVIDED.
 10. PROVIDE A SECTION IN A LANDSCAPE DATA CHART TO
 COMPLY WITH SECTION 94-445 L. PLANT SPECIES. A MINIMUM
 OF 60 PERCENT OF PLANT MATERIAL ADDED SHALL BE FLORIDA
 NATIVE OR DROUGHT TOLERANT SPECIES SELECTED FROM THE
 CITY LIST OR THE LIST OF SPECIES IN THE MOST RECENT
 EDITION OF SOUTH FLORIDA WATER MANAGEMENT DISTRICT
 WATERWISE SOUTH FLORIDA LANDSCAPES. PROVIDE THE TOTAL
 PERCENTAGE OF NATIVE AND DROUGHT TOLERANT PLANTS BASED
 ON FINAL PLANT LIST.
  
 11. LOCATIONS OF PROPOSED UTILITY LINES INCLUDING
 WATER, SEWER AND DRAINAGE CONFLICT WITH REQUIRED
 LANDSCAPING. CIVIL ENGINEERING PLAN, SITE PLAN AND
 LANDSCAPE PLAN MUST BE CONSISTENT.
  
 12. SHOW AND LABEL ALL OVERHEAD POWER LINES THAT WILL
 LIMIT THE TREE SPECIES TO RIGHT TREE RIGHT PLACE
 GUIDELINES.
  
 13. PER SECTION 94-443 (A)(1) A PROTECTIVE SCREEN WALL
 IS REQUIRED ALONG THE ADJACENT RESIDENTIAL PROPERTY
 LINES.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop PU PUBLIC UTILITIES
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By mtechnow Date 01-05-2022 Time 17:00 Sent To  
Notes
2022-01-05 17:01:18CUT/CAP UNUSED SERVICES AT THE MAIN.
 -PROFILE OF THE TAP TO POINT OF SERVICE.
 -THE CITY DOES NOT ALLOW 3? SERVICES. PLEASE UPSIZE TO
 4?
 -SHOW/LABEL EASEMENT.
 -THE PLAN VIEW IS TOUGH TO READ. COULD YOU PLEASE MAKE
 IT MORE LEGIBLE?
 -PROVIDE POST CCTV OF THE LATERALS.
 -FOR THE STORMWATER SYSTEM, PLEASE SHOW THE TRUNK LINE
 ON THE PLANS.
 - FOR STORMWATER STRUCTURES CALL OUT STATIONING AND
 HORIZONTAL SEPARATION BETWEEN UTILITIES
  
 CONTACT MIKE TECHNOW 561-494-1047 OR [email protected]
 WITH ANY QUESTIONS.

Review Stop PW PUBLIC WORKS
Rev No 3 Status P Date 11-14-2022 Cont ID  
Sent By   Date 11-14-2022 Time   Rev Time 0.00
Received By   Date 11-14-2022 Time   Sent To  
Notes
2022-11-14 09:46:58NO FURTHER COMMENTS.
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS

Review Stop PW PUBLIC WORKS
Rev No 2 Status F Date 03-22-2022 Cont ID  
Sent By   Date 03-22-2022 Time   Rev Time 0.00
Received By   Date 03-22-2022 Time   Sent To  
Notes
2022-03-29 11:27:17PLEASE PROVIDE REVISED SHEET SP-2 TO REFLECT ALL THE
 REQUIREMENTS FOR THE DUMPSTER ENCOSURE PER THE LATEST
 REVISION OF GC-7. FOR A FREESTANDING SITE DUMPSTER
 ENCLOSURE, THE ENCLOSURE SHALL COMPLY WITH THE LATEST
 REVISION OF CITY OF WEST PALM BEACH GENERAL
 CONSTRUCTION-GARBAGE ENCLOSURE STANDARD, GC-7. (LINK TO
 THE LATEST REVISION OF THE GC-7 DOCUMENT: HTTPS://WWW.W
 PB.ORG/HOME/SHOWPUBLISHEDDOCUMENT/3690/6376290604221000
 00).
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 01-13-2022 Cont ID  
Sent By   Date 01-13-2022 Time   Rev Time  
Received By   Date 01-13-2022 Time   Sent To  
Notes
2022-01-13 10:29:09PLEASE PROVIDE THE FOLLOWINGS:
 - LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID
 WASTE VOLUME PRODUCED ALONG WITH THE SIZE AND TYPE OF
 THE CONTAINER (I.E. DUMPSTER/COMPACTOR) THAT WILL BE
 UTILIZED THAT WILL BE UTILIZED FOR THE SANITATION
 SERVICE.
 -AUTOTURN EXHIBIT (DYNAMIC ENVELOPE AND THE VEHICLE'S
 WHEEL PATH) FOR THE SANITATION SERVICE, FRONT LOADER
 TRUCK WITH THE FOLLOWING SPECS:
  * TRUCK LENGTH: 35 FT
  * TRUCK WITH: 11 FT
  * TURNING RADIUS:
  - SAE TURNING RADIUS: 32.5 FT
  - CURB-TO-CURB DIAMETER: 74 FT
  - WALL-TO-WALL DIAMETER: 86.3 FT
 - DESIGNATED LOCATION FOR THE BULK ITEM PICK UP AND
 RECYCLING CONTAINERS.
 - REVIESD ENCLOSURE DETAILS, SHEET SP-2, TO COMPLY WITH
 THE CG-7. FOR A FREESTANDING SITE DUMPSTER ENCLOSURE,
 THE ENCLOSURE SHALL COMPLY WITH THE LATEST REVISION OF
 CITY OF WEST PALM BEACH GENERAL CONSTRUCTION-GARBAGE
 ENCLOSURE STANDARD, CG-7.

Review Stop STORM STORMWATER
Rev No 4 Status P Date 12-13-2022 Cont ID  
Sent By tward Date 12-13-2022 Time 09:14 Rev Time 0.00
Received By tward Date 12-13-2022 Time 09:20 Sent To  
Notes
2022-12-13 09:20:13CONDITIONS FOR SITE PLAN APPROVAL:
 1. REMOVE CURB OR ADJUST CURB CALLOUT FOR THE DRIVEWAY
 APRON/SIDEWALK.
 2. SHOW CURBS, SIDEWALKS, GUTTERS, ETC. AT THEIR PROPER
 WIDTHS/DEPTHS ON THE PLANS AND CROSS SECTIONS.
 3. PROVIDE REFERENCE ELEVATION TO NGVD1929 (THE
 CITY???S VERTICAL DATUM) ON THE SURVEY.
 4. PROVIDE EXISTING INVERT AND BOTTOM ELEVATION FOR THE
 EXISTING DRAINAGE STRUCTURES TO BE CONNECTED TO.
 5. PROVIDE INVERT INFORMATION FOR THE PROPOSED SANITARY
 LATERAL, INCLUDING THE INVERT ELEVATION OF THE EXISTING
 MAIN AT THE WYE CONNECTION AND THE TOP AND BOP
 ELEVATIONS FOR THE CROSSING OF THE PROPOSED 15???
 STORM.
 6. STORM PIPE CONNECTION TO EXISTING CATCH BASIN ON
 STATE STREET TO BE EXCLUSIVE WITHIN ONLY ONE SIDE OF
 THE STRUCTURE (I.E. DO NOT REMOVE ANY OF THE CORNER OF
 THE STRUCTURE).
 7. SHOW AND LABEL THE LANDSCAPING OVERHANG (DASHED
 LINE) FOR THE PARKING SPACES ON ALL OF THE CIVIL PLAN
 SHEETS.
 9. LABEL (SIZE AND MATERIAL) ALL EXISTING UTILITIES IN
 THE R/W.
 10. PROVIDE A CROSS SECTION FOR THE DRIVEWAY FROM THE
 CENTERLINE OF THE R/W TO 5 FEET PAST THE HIGH POINT OF
 THE DRIVEWAY. CALLOUT SURFACE FEATURES AND PROVIDE
 DIMENSIONS FROM THE R/W TO THE BACK OF CURB, EDGE OF
 PAVEMENT, R/W CENTERLINE, HIGH POINT OF DRIVEWAY AND
 OTHER BREAKPINTS OF DRIVEWAY. SHOW AND LABEL LOCATION
 OF SIDEWALK CROSSING. LABEL STREET NAME OF THE R/W.
  
 THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 11/4/2022 SUBMITTAL. PREVIOUSLY SATISFIED COMMENTS ARE
 NOT LISTED.
  
 5. [PARTIALLY SATISFIED - SEE COMMENTS UNDER NEW
 COMMENTS BELOW] PROVIDE CROSS SECTIONS FROM:
 A. BUILDING TO EACH R/W CENTERLINE
 B. AT PROPOSED DRIVEWAY
 C. FROM GRANT ST CENTERLINE TO PARKING LOT
 D. FROM WEST PROPERTY LINE TO FACE OF BUILDING.
 E. BETWEEN THE TWO BUILDINGS
  
 LABEL STREETS, PROPERTY LINES, SURFACE FEATURES AND
 GENERAL SURFACE SLOPES. PROVIDE DIMENSIONS FOR
 CURBS/CURB AND GUTTER, SIDEWALKS AND DISTANCE FROM
 PROPERTY LINE TO FACE OF BUILDING. INCLUDE PROPOSED
 PARALLEL PARKING AREAS.
  
 6. {SATISFIED] SHOW MILL AND RESURFACING LIMITS WITHIN
 THE STREETS. ADDITIONAL COMMENT - THE EXISTING WATER
 SERVICE ON GRANT STREET MAY NEED TO BE REMOVED AND
 PLUGGED AT THE WATER MAIN.
  
  
 9. [SATISFIED ??? CORNER OF THE STRUCTURE IS NOT TO BE
 REMOVED IN ORDER TO CONNECT THE OUTFALL PIPE.] CONFIRM
 THE OUTFALL PIPE WILL NOT ENTER THE EXISTING STRUCTURE
 AT A CORNER OF THE STRUCTURE. ADDITIONAL COMMENT ? THE
 ANGLE OF THE PIPE TO THE STRUCTURE MAY REQUIRE THE HOLE
 OPENING (42 +/- INCHES) TO BE WIDER THAN THE INSIDE
 WALL DIMENSION.
  
 10. [SATISFIED ??? NOTE 13 ON SHEET C2.1 STATES ALL
 EXISTING SIDEWALKS TO BE REPLACED.] PROVIDE HATCHING
 PATTERNS FOR SIDEWALKS TO REMAIN AND FOR
 NEW/REPLACEMENT SIDEWALKS. ADDITIONAL COMMENT: ADD
 PATTERNS TO LEGEND. ADD DUMPSTER PAD HATCHING TO THE
 LEGEND.
  
  
 13. [NOT SATISFIED] THE CITY???S OFFICIAL VERTICAL
 DATUM IS NGVD1929. THE CITY HAS ALLOWED THE USE OF
 NAVD1988 AS LONG AS THE CONVERSION EQUATION TO NGVD1929
 AT THE PROJECT LOCATION IS PROVIDED. PROVIDE THE
 NAVD1988 TO NGVD1929 CONVERSION EQUATION ON THE SURVEY.
  
 14. [PARTIALLY SATISFIED] LABEL ANY NEW GUTTER OR CURB
 AND GUTTER IN THE RIGHT OF WAY. ADDITIONAL COMMENT -
 SHOW THE LINEWORK FOR THE PROPOSED VALLEY GUTTER ON
 GRANT ST. LABELED THE PROPOSED CURBING CREATED FOR THE
 ON-STREET PARKING. USE DIFFERENT LINE TYPE/WEIGHT
 BETWEEN EXISTING CURBING AND PROPOSED CURBING. DRAW THE
 VALLEY GUTTER WITH THE CORRECT WIDTH AND LOCATION.
  
  
 17. [NO LONGER APPLICABLE - SIDEWALK AREA NOT BEING
 MODIFIED FOR PARKING ON N. TAMARIND AVE] REVIEW
 AS-BUILT DRAWINGS FOR THE ARV TO DETERMINE IF THE
 STRUCTURE CAN BE MODIFIED TO LOWER THE RIM TO PROPOSED
 GRADE.
  
  
 NEW COMMENTS(3/24/22 SUBMITTAL):
  
 19. [NOT SATISFIED - REVISE FOR ENGINEERING PERMIT
 SUBMITTAL] REVISE FDOT INDEX NUMBERS TO CURRENT FDOT
 STANDARD PLAN NUMBERS ON THE SITE PLAN SHEETS AND
 ENGINEERING SHEETS.
  
  
 21. [SATISFIED] REMOVE THE HATCHING FOR THE PROPOSED
 R/W ABANDONMENT AREA ON THE ENGINEERING PLAN SHEETS.
  
 22. [NOT SATISFIED] PROVIDE THE EXISTING INVERT
 ELEVATION OF THE DRAINAGE STRUCTURE THE OUTFALL PIPE
 WILL CONNECT TO.
  
 23.[NOT SATISFIED] LIST THE WEIR ELEVATION WITH THE
 INFORMATION FOR STRUCTURE S-102.
  
 24. [NOT SATISFIED] CONFIRM THERE WILL BE SUFFICIENT
 VERTICAL CLEARANCE BETWEEN THE PROPOSED 15 INCH RCP
 OUTFALL PIPE AND 6 INCH SANITARY SEWER LATERAL.
 ADDITIONAL COMMENTS: SURVEY LISTS THE BOTTOM ELEVATION
 OF THE SANITARY SEWER MANHOLE NO. 2 AS 15.16 FT NAVD.
 THIS BOTTOM (OR MINIMUM INVERT ELEVATION FOR THE
 SANITARY LATERAL) IS LESS THAN 2 INCHES LOWER THAN THE
 TOP OF THE PROPOSED 6 INCH SANITARY LATERAL (AS LISTED
 ON THE WATER AND SEWER PLAN) WHERE THE LATERAL CROSSES
 THE PROPOSED 15 INCH RCP STORM PIPE.
  
  
 26. [NOT SATISFIED] SHOW THE 2-FT LANDSCAPE OVERHANG AT
 THE END OF THE PARKING SPACES. ADDITIONAL COMMENT ?
 OVERHANG WILL BE OVER THE SIDEWALK. SHOW THE DASHED
 LINE ON THE SIDEWALK.
  
  
 28. [NOT SATISFIED] SHOW WATER MAIN ON STATE STREET IN
 THE CORRECT LOCATION. SHOW THE VALVES FROM THE SURVEY.
  
 29. SHEET C2.3 GEOMETRIC, SIGNING AND STRIPING PLAN:
 A. [SATISFIED - EXTEND DOUBLE YELLOW TO 25 LF] PROVIDE
 STRIPING PLAN FOR MILL AND RESURFACE AREAS.
 B. [SATISFIED - SIGNS AND STOP BARS TO BE MINIMUM 4
 FEET FROM CROSS WALK] SHOW EXISTING STOP SIGNS FOR
 STATE STREET AND FOR GRANT STREET.
 E. [SATISFIED] REFERENCE THE CWPB TYPICAL 90 DEGREE
 PARKING STALL DETAIL.
  
 G. [NOT SATISFIED] TYPE D CURB CALLED OUT ACROSS
 SIDEWALK ON EAST SIDE OF PROPOSED DRIVEWAY.
 ADDITIONAL COMMENTS (7/19/22 SUBMITTAL):
 H. [NOT SATISFIED] SHARROWS SHOULD BE LOCATED AFTER THE
 INTERSECTION AND NOT IN THE INTERSECTION.
 I. [SATISFIED] CONSIDER REDUCING THE LENGTH OF THE STOP
 BAR IN THE PARKING LOT TO HALF THE WIDTH OF THE
 DRIVEWAY.
 J. [SATISFIED] CALLOUT FOR TYPE D CURB AT BACK OF
 PARALLEL PARKING SPACES ON GRANT STREET IS LOCATED ON
 TOP OF THE VALLEY GUTTER LINE WORK AND IS
 INDISCERNIBLE.
  
 30. [SATISFIED ? COMMENTS BELOW WERE MODIFIED FOR THE
 LATEST (7/19) SUBMITTAL] SECTION A (SHEET C3.2)
 A. [SATISFIED] VALLEY GUTTER NOT SHOWN OR LABELED FOR
 GRANT STREET.
 B. [SATISFIED] SHOW SLOPE DIRECTION FOR PARKING SPACE.
 C. {SATISFIED] VALLEY GUTTER FOR STATE STREET SHOWN AT
 CENTERLINE OF R/W.
 D. [SATISFIED] IS THICKENED-EDGE SIDEWALK PROPOSED FOR
 GRANT STREET? LABEL AS SUCH AND PROVIDE A DETAIL OF THE
 SIDEWALK.E. DOES THE EXISTING SIDEWALK ON STATE STREET
 HAVE CURBING AND THICKENED-EDGE AS SHOWN ON THE CROSS
 SECTION?
  
 31. [COMMENTS BELOW WERE MODIFIED FOR THE LATEST (7/19)
 SUBMITTAL] SECTION B (SHEET C3.2)
 A. [NOT SATISFIED] WILL NEW SIDEWALK HAVE THICKENED
 EDGE AT BACK OF WALK? LABEL SIDEWALK AS SUCH AND
 PROVIDE DETAIL.
  
  
  
 NEW COMMENTS (7/19/2024)
 38. [NOT SATISFIED] FOR ENGINEERING PERMIT SUBMITTAL,
 SHOW THE CURBING ON THE OTHER SIDE OF STATE STREET AND
 GRANT STREET.
  
 39. [NOT SATISFIED ??? 2015 AS-BUILT DRAWING SHOWS
 8-INCH WATER MAIN CONNECTING TO 6??? WATER MAIN ABOUT
 10 FEET WEST OF THE WEST R/W OF TAMARIND AVE] CONFIRM
 SIZE OF EXISTING WATER MAIN ON STATE STREET IS 8?.
  
 40. [NOT SATISFIED] LABEL SIZE AND MATERIAL OF ALL
 EXISTING UTILITIES ON STATE STREET, TAMARIND AVE AND
 GRANT STREET.
  
 41. [NOT SATISFIED] SHARROW STRIPING DETAIL TO BE
 PROVIDED WITH THE ENGINEERING PERMIT SUBMITTAL. BIKE
 STRIPING TO BE IN ACCORDANCE WITH CWPB STANDARD DETAILS
 AND MUTCD. PROPERLY SHOW WHERE THE MARKINGS AND SIGNAGE
 ARE TO BE PLACED.
  
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 [email protected]
  

Review Stop STORM STORMWATER
Rev No 3 Status F Date 08-01-2022 Cont ID  
Sent By tward Date 08-01-2022 Time 15:24 Rev Time 0.00
Received By tward Date 08-01-2022 Time 15:32 Sent To  
Notes
2022-08-01 15:32:14Z21120021 SITE G 1002 GRANT ST, 1001 STATE ST.
  
 THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 7/19/2022 SUBMITTAL:
  
 1. [SATISFIED] REMOVE REFERENCES TO VOW (VILLAGE OF
 WELLINGTON?) ON COVER.
  
 2. [SATISFIED ? AS BEST AS THEY CAN DO] PROJECT SITE ON
 PROJECT LOCATION MAP IS SHOWN ON THE EAST SIDE OF
 TAMARIND AVE. THE SITE IS ON THE WEST SIDE OF TAMARIND
 AVE.
  
 3. [SATISFIED] CONCEPTUAL ENGINEERING PLAN IS CONFUSING
 WITH EXISTING FEATURES SHOWN AND NOT SCREENED.
  
 4. [SATISFIED] PROVIDE FLOW ARROWS SHOWING DIRECTION OF
 SURFACE RUNOFF. ADDITIONAL COMMENT - ADD FLOW ARROWS
 FOR THE AREAS AROUND THE BUILDING.
  
 5. [PARTIALLY SATISFIED - SEE COMMENTS UNDER NEW
 COMMENTS BELOW] PROVIDE CROSS SECTIONS FROM:
 A. BUILDING TO EACH R/W CENTERLINE
 B. AT PROPOSED DRIVEWAY
 C. FROM GRANT ST CENTERLINE TO PARKING LOT
 D. FROM WEST PROPERTY LINE TO FACE OF BUILDING.
 E. BETWEEN THE TWO BUILDINGS
  
 LABEL STREETS, PROPERTY LINES, SURFACE FEATURES AND
 GENERAL SURFACE SLOPES. PROVIDE DIMENSIONS FOR
 CURBS/CURB AND GUTTER, SIDEWALKS AND DISTANCE FROM
 PROPERTY LINE TO FACE OF BUILDING. INCLUDE PROPOSED
 PARALLEL PARKING AREAS.
  
 6. {PARTIALLY SATISFIED] SHOW MILL AND RESURFACING
 LIMITS WITHIN THE STREETS. ADDITIONAL COMMENT - THE
 EXISTING WATER SERVICE ON GRANT STREET MAY NEED TO BE
 REMOVED AND PLUGGED AT THE WATER MAIN.
  
 7. [SATISFIED] IDENTIFY ON THE CONCEPTUAL ENGINEERING
 PLAN WHERE THE SPECIAL TYPE 'F' CURB AND GUTTER WILL BE
 CONSTRUCTED. REDRAW THE DETAIL IN ACAD AND PROVIDE
 ENGLISH UNITS. ADDITIONAL COMMENT: IF SPECIAL TYPE F
 CURB AND GUTTER IS NOT BEING CONSTRUCTED THEN DO NOT
 INCLUDE THE DETAIL FOR THE ITEM.
  
 8. [SATISFIED] LABEL WHERE THE DRAINAGE CONTROL
 STRUCTURE WILL BE LOCATED AND PROVIDE A DETAIL OF THE
 STRUCTURE. NOTE THE CITY DOES NOT ALLOW THE USE OF
 BLEEDERS WITH EXFILTRATION TRENCHES.
  
 9. [PARTIALLY SATISFIED] CONFIRM THE OUTFALL PIPE WILL
 NOT ENTER THE EXISTING STRUCTURE AT A CORNER OF THE
 STRUCTURE. ADDITIONAL COMMENT ? THE ANGLE OF THE PIPE
 TO THE STRUCTURE MAY REQUIRE THE HOLE OPENING (42 +/-
 INCHES) TO BE WIDER THAN THE INSIDE WALL DIMENSION.
  
 10. [NOT SATISFIED] PROVIDE HATCHING PATTERNS FOR
 SIDEWALKS TO REMAIN AND FOR NEW/REPLACEMENT SIDEWALKS.
 ADDITIONAL COMMENT: ADD PATTERNS TO LEGEND. ADD
 DUMPSTER PAD HATCHING TO THE LEGEND.
  
 11. [SATISFIED] PER FIGURE XV-2: GENERAL PARKING
 DIMENSIONS IN SECTION 94-485 OF THE CITY'S CODE OF
 ORDINANCES, THE CURB LENGTH OF PARALLEL PARKING SPACES
 IS 22 FEET. THE SITE PLAN SHOWS 25 FEET AND GAPS IN THE
 PARKING SPACES ON TAMARIND AVE.
  
 12. [SATISFIED] CONSIDER ANGLING THE CURBING AT EACH
 END OF PROPOSED PARALLEL PARKING SPACES TO FACILITATE
 ACCESS TO AND FROM THE END SPACES. ADDITIONAL COMMENT -
 INCREASE THE ANGLE OF THE END CURBING FROM 16 DEGREES
 FROM PERPENDICULAR TO 45 DEGREES FROM PERPENDICULAR AT
 BOTH ENDS OF THE PARKING AREA ON GRANT STREET.
  
 13. [NOT SATISFIED] THE CITY?S OFFICIAL VERTICAL DATUM
 IS NGVD1929. THE CITY HAS ALLOWED THE USE OF NAVD1988
 AS LONG AS THE CONVERSION EQUATION TO NGVD1929 AT THE
 PROJECT LOCATION IS PROVIDED. PROVIDE THE NAVD1988 TO
 NGVD1929 CONVERSION EQUATION ON THE SURVEY.
  
 14. [PARTIALLY SATISFIED] LABEL ANY NEW GUTTER OR CURB
 AND GUTTER IN THE RIGHT OF WAY. ADDITIONAL COMMENT -
 SHOW THE LINEWORK FOR THE PROPOSED VALLEY GUTTER ON
 GRANT ST. LABELED THE PROPOSED CURBING CREATED FOR THE
 ON-STREET PARKING. USE DIFFERENT LINE TYPE/WEIGHT
 BETWEEN EXISTING CURBING AND PROPOSED CURBING. DRAW THE
 VALLEY GUTTER WITH THE CORRECT WIDTH AND LOCATION.
  
 15. [SATISFIED] CONSIDER LOW IMPACT DEVELOPMENT
 DRAINAGE SYSTEMS IN LIEU OF EXFILTRATION TRENCHES.
  
 16. [SATISFIED] EASEMENT MAY BE NEEDED FOR THE SIDEWALK
 AND PARKING ON GRANT ST.
  
 17. [NO LONGER APPLICABLE - SIDEWALK AREA NOT BEING
 MODIFIED FOR PARKING ON N. TAMARIND AVE] REVIEW
 AS-BUILT DRAWINGS FOR THE ARV TO DETERMINE IF THE
 STRUCTURE CAN BE MODIFIED TO LOWER THE RIM TO PROPOSED
 GRADE.
  
 18. [SATISFIED] SHOW UTILITIES ON THE LANDSCAPE PLANS.
  
 NEW COMMENTS(3/24/22 SUBMITTAL):
  
 19. [NOT SATISFIED ? REVISE FOR ENGINEERING PERMIT
 SUBMITTAL] REVISE FDOT INDEX NUMBERS TO CURRENT FDOT
 STANDARD PLAN NUMBERS ON THE SITE PLAN SHEETS AND
 ENGINEERING SHEETS.
  
 20. [SATISFIED] SHEET SP-1 CALLS OUT A DETAIL NO. 4 ON
 SHEET SP-3. SHEET SP-3 DOES NOT HAVE A DETAIL NO. 4.
  
 21. [NOT SATISFIED] REMOVE THE HATCHING FOR THE
 PROPOSED R/W ABANDONMENT AREA ON THE ENGINEERING PLAN
 SHEETS.
  
 22. [NOT SATISFIED] PROVIDE THE EXISTING INVERT
 ELEVATION OF THE DRAINAGE STRUCTURE THE OUTFALL PIPE
 WILL CONNECT TO.
  
 23.[NOT SATISFIED] LIST THE WEIR ELEVATION WITH THE
 INFORMATION FOR STRUCTURE S-102.
  
 24. [NOT SATISFIED] CONFIRM THERE WILL BE SUFFICIENT
 VERTICAL CLEARANCE BETWEEN THE PROPOSED 15 INCH RCP
 OUTFALL PIPE AND 6 INCH SANITARY SEWER LATERAL.
 ADDITIONAL COMMENTS: SURVEY LISTS THE BOTTOM ELEVATION
 OF THE SANITARY SEWER MANHOLE NO. 2 AS 15.16 FT NAVD.
 THIS BOTTOM (OR MINIMUM INVERT ELEVATION FOR THE
 SANITARY LATERAL) IS LESS THAN 2? LOWER THAN THE TOP OF
 THE PROPOSED 6? SANITARY LATERAL (AS LISTED ON THE
 WATER AND SEWER PLAN) WHERE THE LATERAL CROSSES THE
 PROPOSED 15? RCP STORM PIPE.
  
 25. [SATISFIED] CAN S-102 AND S-101 SHIFT TO THE NORTH,
 AWAY FROM THE SOUTH PROPERTY LINE. THIS WILL REDUCE THE
 ANGLE OF THE OUTFALL PIPE CONNECTION TO THE EXISTING
 INLET. ADDITIONAL COMMENT ? STRUCTURE S-102 WILL NEED
 TO SHIFT NORTHWARD ABOUT 6 ? 8 MORE FEET SO THAT THE
 PIPE OPENING AT THE EXISTING CURB INLET WILL NOT EXCEED
 THE INSIDE HORIZONTAL DIMENSION OF THE WALL.
  
 26. [NOT SATISFIED] SHOW THE 2-FT LANDSCAPE OVERHANG AT
 THE END OF THE PARKING SPACES. ADDITIONAL COMMENT ?
 OVERHANG WILL BE OVER THE SIDEWALK. SHOW THE DASHED
 LINE ON THE SIDEWALK.
  
 27. [SATISFIED] SHOW CONCRETE FOR THE DRIVEWAY APRON
 AND SIDEWALK WITHIN THE R/W.
  
 28. [NOT SATISFIED] SHOW WATER MAIN ON STATE STREET IN
 THE CORRECT LOCATION. SHOW THE VALVES FROM THE SURVEY.
  
 29. SHEET C2.3 GEOMETRIC, SIGNING AND STRIPING PLAN:
 A. [PARTIAL SATISFIED ? EXTEND DOUBLE YELLOW TO 25 LF]
 PROVIDE STRIPING PLAN FOR MILL AND RESURFACE AREAS.
 B. [PARTIALLY SATISFIED ? SIGNS AND STOP BARS TO BE
 MINIMUM 4 FEET FROM CROSS WALK] SHOW EXISTING STOP
 SIGNS FOR STATE STREET AND FOR GRANT STREET.
 C. [SATISFIED] MOVE STOP BAR AND STOP SIGN FOR PARKING
 LOT TO BEHIND THE SIDEWALK.
 D. [SATISFIED] REMOVE REFERENCE TO CITY OF RIVIERA
 BEACH LAND DEVELOPMENT CODE FROM NOTES.
 E. REFERENCE THE CWPB TYPICAL 90 DEGREE PARKING STALL
 DETAIL.
 F. [SATISFIED] TYPE D CURB CALLED OUT FOR WEST EDGE OF
 PARKING LOT BUT THIS CURB IS NOT SHOWN ON THE PGD PLAN.
 G. [NOT SATISFIED] TYPE D CURB CALLED OUT ACROSS
 SIDEWALK ON EAST SIDE OF PROPOSED DRIVEWAY.
 ADDITIONAL COMMENTS (7/19/22 SUBMITTAL):
 H. SHARROWS SHOULD BE LOCATED AFTER THE INTERSECTION
 AND NOT IN THE INTERSECTION.
 I. CONSIDER REDUCING THE LENGTH OF THE STOP BAR IN THE
 PARKING LOT TO HALF THE WIDTH OF THE DRIVEWAY.
 J. CALLOUT FOR TYPE D CURB AT BACK OF PARALLEL PARKING
 SPACES ON GRANT STREET IS LOCATED ON TOP OF THE VALLEY
 GUTTER LINE WORK AND IS INDISCERNIBLE.
  
 30. [PARTIALLY SATISFIED ? COMMENTS BELOW WERE MODIFIED
 FOR THE LATEST (7/19) SUBMITTAL] SECTION A (SHEET C3.2)
 A. VALLEY GUTTER NOT SHOWN OR LABELED FOR GRANT STREET.
 B. SHOW SLOPE DIRECTION FOR PARKING SPACE.
 C. VALLEY GUTTER FOR STATE STREET SHOWN AT CENTERLINE
 OF R/W.
 D. IS THICKENED-EDGE SIDEWALK PROPOSED FOR GRANT
 STREET? LABEL AS SUCH AND PROVIDE A DETAIL OF THE
 SIDEWALK.E. DOES THE EXISTING SIDEWALK ON STATE STREET
 HAVE CURBING AND THICKENED-EDGE AS SHOWN ON THE CROSS
 SECTION?
  
 31. [PARTIALLY SATISFIED ? COMMENTS BELOW WERE MODIFIED
 FOR THE LATEST (7/19) SUBMITTAL] SECTION B (SHEET C3.2)
 A. WILL NEW SIDEWALK HAVE THICKENED EDGE AT BACK OF
 WALK? LABEL SIDEWALK AS SUCH AND PROVIDE DETAIL.
  
  
 36. [SATISFIED] SIZE OF OUTFALL PIPE SHOWN ON THE
 CONTROL STRUCTURE DETAIL DOES NOT MATCH WHAT IS CALLED
 OUT ON THE PGD PLAN. JUSTIFY ANY OUTFALL PIPE DIAMETER
 LARGER THAN 15 INCH.
  
 37. [SATISFIED]SHEET C4.1 EROSION CONTROL PLAN (CAN BE
 ADDRESSED WITH ENGINEERING PERMIT SUBMITTAL):
 A. PROVIDE ALTERNATIVE TO HAY BALES FOR INLET
 PROTECTION.
 B. IDENTIFY WHICH INLETS ARE TO BE PROTECTED (ONSITE
 AND WITHIN R/W)
 C. MOVE HATCHING FOR CONSTRUCTION ACCESS OUT OF THE
 R/W.
  
 NEW COMMENTS (7/19/2024)
 38. FOR ENGINEERING PERMIT SUBMITTAL, SHOW THE CURBING
 ON THE OTHER SIDE OF STATE STREET AND GRANT STREET.
  
 39. CONFIRM SIZE OF EXISTING WATER MAIN ON STATE STREET
 IS 8?.
  
 40. LABEL SIZE AND MATERIAL OF ALL EXISTING UTILITIES
 ON STATE STREET, TAMARIND AVE AND GRANT STREET.
  
 41. SHARROW STRIPING DETAIL TO BE PROVIDED WITH THE
 ENGINEERING PERMIT SUBMITTAL. BIKE STRIPING TO BE IN
 ACCORDANCE WITH CWPB STANDARD DETAILS AND MUTCD.
 PROPERLY SHOW WHERE THE MARKINGS AND SIGNAGE ARE TO BE
 PLACED.
  
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 [email protected]
  

Review Stop STORM STORMWATER
Rev No 2 Status F Date 04-27-2022 Cont ID  
Sent By tward Date 04-27-2022 Time 15:35 Rev Time 0.00
Received By tward Date 04-27-2022 Time 15:36 Sent To  
Notes
2022-04-27 15:36:17THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 3/24/2022 SUBMITTAL:
  
 1. [SATISFIED] REMOVE REFERENCES TO VOW (VILLAGE OF
 WELLINGTON?) ON COVER.
  
 2. [NOT SATISFIED] PROJECT SITE ON PROJECT LOCATION MAP
 IS SHOWN ON THE EAST SIDE OF TAMARIND AVE. THE SITE IS
 ON THE WEST SIDE OF TAMARIND AVE.
  
 3. [SATISFIED] CONCEPTUAL ENGINEERING PLAN IS CONFUSING
 WITH EXISTING FEATURES SHOWN AND NOT SCREENED.
  
 4. [PARTIALLY SATISFIED] PROVIDE FLOW ARROWS SHOWING
 DIRECTION OF SURFACE RUNOFF. ADDITIONAL COMMENT - ADD
 FLOW ARROWS FOR THE AREAS AROUND THE BUILDING.
  
 5. [PARTIALLY SATISFIED - SEE COMMENTS UNDER NEW
 COMMENTS BELOW] PROVIDE CROSS SECTIONS FROM:
 A. BUILDING TO EACH R/W CENTERLINE
 B. AT PROPOSED DRIVEWAY
 C. FROM GRANT ST CENTERLINE TO PARKING LOT
 D. FROM WEST PROPERTY LINE TO FACE OF BUILDING.
 E. BETWEEN THE TWO BUILDINGS
  
 LABEL STREETS, PROPERTY LINES, SURFACE FEATURES AND
 GENERAL SURFACE SLOPES. PROVIDE DIMENSIONS FOR
 CURBS/CURB AND GUTTER, SIDEWALKS AND DISTANCE FROM
 PROPERTY LINE TO FACE OF BUILDING. INCLUDE PROPOSED
 PARALLEL PARKING AREAS.
  
 6. {PARTIALLY SATISFIED] SHOW MILL AND RESURFACING
 LIMITS WITHIN THE STREETS. ADDITIONAL COMMENT - THE
 EXISTING WATER SERVICE ON GRANT STREET MAY NEED TO BE
 REMOVED AND PLUGGED AT THE WATER MAIN.
  
 7. [PARTIALLY SATISFIED] IDENTIFY ON THE CONCEPTUAL
 ENGINEERING PLAN WHERE THE SPECIAL TYPE 'F' CURB AND
 GUTTER WILL BE CONSTRUCTED. REDRAW THE DETAIL IN ACAD
 AND PROVIDE ENGLISH UNITS. ADDITIONAL COMMENT: IF
 SPECIAL TYPE ?F? CURB AND GUTTER IS NOT BEING
 CONSTRUCTED THEN DO NOT INCLUDE THE DETAIL FOR THE
 ITEM.
  
 8. [SATISFIED] LABEL WHERE THE DRAINAGE CONTROL
 STRUCTURE WILL BE LOCATED AND PROVIDE A DETAIL OF THE
 STRUCTURE. NOTE THE CITY DOES NOT ALLOW THE USE OF
 BLEEDERS WITH EXFILTRATION TRENCHES.
  
 9. [NOT SATISFIED] CONFIRM THE OUTFALL PIPE WILL NOT
 ENTER THE EXISTING STRUCTURE AT A CORNER OF THE
 STRUCTURE.
  
 10. [NOT SATISFIED] PROVIDE HATCHING PATTERNS FOR
 SIDEWALKS TO REMAIN AND FOR NEW/REPLACEMENT SIDEWALKS.
  
 11. [SATISFIED] PER FIGURE XV-2: GENERAL PARKING
 DIMENSIONS IN SECTION 94-485 OF THE CITY'S CODE OF
 ORDINANCES, THE CURB LENGTH OF PARALLEL PARKING SPACES
 IS 22 FEET. THE SITE PLAN SHOWS 25 FEET AND GAPS IN THE
 PARKING SPACES ON TAMARIND AVE.
  
 12. [NOT SATISFIED] CONSIDER ANGLING THE CURBING AT
 EACH END OF PROPOSED PARALLEL PARKING SPACES TO
 FACILITATE ACCESS TO AND FROM THE END SPACES.
 ADDITIONAL COMMENT - INCREASE THE ANGLE OF THE END
 CURBING FROM 16 DEGREES FROM PERPENDICULAR TO 45
 DEGREES FROM PERPENDICULAR AT BOTH ENDS OF THE PARKING
 AREA ON GRANT STREET.
  
 13. [NOT SATISFIED] THE CITY?S OFFICIAL VERTICAL DATUM
 IS NGVD1929. THE CITY HAS ALLOWED THE USE OF NAVD1988
 AS LONG AS THE CONVERSION EQUATION TO NGVD1929 AT THE
 PROJECT LOCATION IS PROVIDED. PROVIDE THE NAVD1988 TO
 NGVD1929 CONVERSION EQUATION ON THE SURVEY.
  
 14. [PARTIALLY SATISFIED] LABEL ANY NEW GUTTER OR CURB
 AND GUTTER IN THE RIGHT OF WAY. ADDITIONAL COMMENT -
 SHOW THE LINEWORK FOR THE PROPOSED VALLEY GUTTER ON
 GRANT ST. LABELED THE PROPOSED CURBING CREATED FOR THE
 ON-STREET PARKING. USE DIFFERENT LINE TYPE/WEIGHT
 BETWEEN EXISTING CURBING AND PROPOSED CURBING.
  
 15. [SATISFIED] CONSIDER LOW IMPACT DEVELOPMENT
 DRAINAGE SYSTEMS IN LIEU OF EXFILTRATION TRENCHES.
  
 16. [SATISFIED] EASEMENT MAY BE NEEDED FOR THE SIDEWALK
 AND PARKING ON GRANT ST.
  
 17. [NO LONGER APPLICABLE - SIDEWALK AREA NOT BEING
 MODIFIED FOR PARKING ON N. TAMARIND AVE] REVIEW
 AS-BUILT DRAWINGS FOR THE ARV TO DETERMINE IF THE
 STRUCTURE CAN BE MODIFIED TO LOWER THE RIM TO PROPOSED
 GRADE.
  
 18. [NOT SATISFIED] SHOW UTILITIES ON THE LANDSCAPE
 PLANS.
  
 NEW COMMENTS:
  
 19. REVISE FDOT INDEX NUMBERS TO CURRENT FDOT STANDARD
 PLAN NUMBERS ON THE SITE PLAN SHEETS AND ENGINEERING
 SHEETS.
  
 20. SHEET SP-1 CALLS OUT A DETAIL NO. 4 ON SHEET SP-3.
 SHEET SP-3 DOES NOT HAVE A DETAIL NO. 4.
  
 21. REMOVE THE HATCHING FOR THE PROPOSED R/W
 ABANDONMENT AREA ON THE ENGINEERING PLAN SHEETS.
  
 22. PROVIDE THE EXISTING INVERT ELEVATION OF THE
 DRAINAGE STRUCTURE THE OUTFALL PIPE WILL CONNECT TO.
  
 23. LIST THE WEIR ELEVATION WITH THE INFORMATION FOR
 STRUCTURE S-102.
  
 24. CONFIRM THERE WILL BE SUFFICIENT VERTICAL CLEARANCE
 BETWEEN THE PROPOSED 15 INCH RCP OUTFALL PIPE AND 6
 INCH SANITARY SEWER LATERAL.
  
 25. CAN S-102 AND S-101 SHIFT TO THE NORTH, AWAY FROM
 THE SOUTH PROPERTY LINE. THIS WILL REDUCE THE ANGLE OF
 THE OUTFALL PIPE CONNECTION TO THE EXISTING INLET.
  
 26. SHOW THE 2-FT LANDSCAPE OVERHANG AT THE END OF THE
 PARKING SPACES.
  
 27. SHOW CONCRETE FOR THE DRIVEWAY APRON AND SIDEWALK
 WITHIN THE R/W.
  
 28. SHOW WATER MAIN ON STATE STREET IN THE CORRECT
 LOCATION. SHOW THE VALVES FROM THE SURVEY.
  
 29. SHEET C2.3 GEOMETRIC, SIGNING AND STRIPING PLAN:
 A. PROVIDE STRIPING PLAN FOR MILL AND RESURFACE AREAS.
 B. SHOW EXISTING STOP SIGNS FOR STATE STREET AND FOR
 GRANT STREET.
 C. MOVE STOP BAR AND STOP SIGN FOR PARKING LOT TO
 BEHIND THE SIDEWALK.
 D. REMOVE REFERENCE TO CITY OF RIVIERA BEACH LAND
 DEVELOPMENT CODE FROM NOTES.
 E. REFERENCE THE CWPB TYPICAL 90 DEGREE PARKING STALL
 DETAIL.
 F. TYPE D CURB CALLED OUT FOR WEST EDGE OF PARKING LOT
 BUT THIS CURB IS NOT SHOWN ON THE PGD PLAN.
 G. TYPE D CURB CALLED OUT ACROSS SIDEWALK ON EAST SIDE
 OF PROPOSED DRIVEWAY.
  
 30. SECTION A (SHEET C3.2)
 A. VALLEY GUTTER SHOWN.
 B. ADD STREET NAME TO PUBLIC R/W.
 C. SHOW AND LABEL EXISTING AND PROPOSED R/W ? PROPERTY
 LINES AND THE WIDTH BETWEEN THE TWO.
 D. DIMENSION THE SIDEWALK WIDTH IN THE PUBLIC R/W,
 PROVIDE THE DISTANCE FROM EDGE OF PAVEMENT TO THE
 PROPOSED R/W LINE, DISTANCE FROM PROPOSED R/W TO FACE
 OF BUILDING.
 E. SHOW AND DIMENSION PATIO IN FRONT OF THE BUILDING.
  
 31. SECTION B (SHEET C3.2)
 A. SHOW, CALLOUT AND DIMENSION PROPOSED VALLEY GUTTER,
 PARKING AREA, CURBING BETWEEN PARKING AND SIDEWALK AND
 SIDEWALK.
 B. PROVIDE DIMENSIONS FROM GRANT STREET CENTERLINE TO
 PROPOSED VALLEY GUTTER.
 C. ADD STREET NAME TO PUBLIC R/W
 D. EXTEND SECTION TO INCLUDE PART OF THE PARKING LOT.
  
 32. SECTION C (SHEET C3.2)
 A. PARKING LOT GRADE DOES NOT MATCH WHAT IS SHOWN ON
 THE PGD PLAN.
 B. SHOW PROPOSED FENCE
 C. TYPE D CURB SHOWN ON THE SECTION BUT NOT SHOWN ON
 THE PGD PLAN.
 D. EXTEND SECTION TO WEST FACE OF THE BUILDING. SHOW
 GRADE BREAKS, DIMENSIONS, ETC.
 E. VALLEY GUTTER CALLED OUT FOR PARKING AREA.
  
 33. SECTION D (SHEET C3.2)
 A. DETAIL SHOULD MATCH PROPOSED DRIVEWAY.
 B. PROVIDE DISTANCE FROM EDGE OF PAVEMENT TO R/W
 C. ADD STREET NAME TO PUBLIC R/W.
 D. GRADES DO NOT APPEAR TO MATCH PGD PLAN.
  
 34. PROVIDE SECTION FROM CENTERLINE OF STATE STREET TO
 SOUTH FACE OF BUILDING. SHOW GROUND FEATURES, SURFACE
 SLOPE DIRECTIONS, GRADE BREAKS, DIMENSIONS, STREET
 NAME, ETC.
  
 35. PROVIDE SECTION FROM CENTERLINE OF GRANT STREET TO
 NORTH FACE OF THE BUILDING, OUTSIDE OF THE PROPOSED
 ON-STREET PARKING. SHOW AND LABEL GROUND FEATURES,
 SURFACE SLOPE DIRECTIONS, GRADE BREAKS, DIMENSIONS,
 STREET NAME, ETC.
  
 36. SIZE OF OUTFALL PIPE SHOWN ON THE CONTROL STRUCTURE
 DETAIL DOES NOT MATCH WHAT IS CALLED OUT ON THE PGD
 PLAN. JUSTIFY ANY OUTFALL PIPE DIAMETER LARGER THAN 15
 INCH.
  
 37. . SHEET C4.1 EROSION CONTROL PLAN (CAN BE ADDRESSED
 WITH ENGINEERING PERMIT SUBMITTAL):
 A. PROVIDE ALTERNATIVE TO HAY BALES FOR INLET
 PROTECTION.
 B. IDENTIFY WHICH INLETS ARE TO BE PROTECTED (ONSITE
 AND WITHIN R/W)
 C. MOVE HATCHING FOR CONSTRUCTION ACCESS OUT OF THE
 R/W.
  
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 [email protected]
  

Review Stop STORM STORMWATER
Rev No 1 Status F Date 01-13-2022 Cont ID  
Sent By tward Date 01-13-2022 Time 12:53 Rev Time 0.00
Received By tward Date 01-13-2022 Time 12:54 Sent To  
Notes
2022-01-13 12:54:09THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. REMOVE REFERENCES TO VOW (VILLAGE OF WELLINGTON?) ON
 COVER.
 2. PROJECT SITE ON PROJECT LOCATION MAP IS SHOWN ON THE
 EAST SIDE OF TAMARIND AVE. THE SITE IS ON THE WEST SIDE
 OF TAMARIND AVE.
 3. CONCEPTUAL ENGINEERING PLAN IS CONFUSING WITH
 EXISTING FEATURES SHOWN AND NOT SCREENED.
 4. PROVIDE FLOW ARROWS SHOWING DIRECTION OF SURFACE
 RUNOFF.
 5. PROVIDE CROSS SECTIONS FROM:
 A. BUILDING TO EACH R/W CENTERLINE
 B. AT PROPOSED DRIVEWAY
 C. FROM GRANT ST CENTERLINE TO PARKING LOT
 D. FROM WEST PROPERTY LINE TO FACE OF BUILDING.
 E. BETWEEN THE TWO BUILDINGS
  
 LABEL STREETS, PROPERTY LINES, SURFACE FEATURES AND
 GENERAL SURFACE SLOPES. PROVIDE DIMENSIONS FOR
 CURBS/CURB AND GUTTER, SIDEWALKS AND DISTANCE FROM
 PROPERTY LINE TO FACE OF BUILDING. INCLUDE PROPOSED
 PARALLEL PARKING AREAS.
 6. SHOW MILL AND RESURFACING LIMITS WITHIN THE STREETS.
 7. IDENTIFY ON THE CONCEPTUAL ENGINEERING PLAN WHERE
 THE SPECIAL TYPE ?F? CURB AND GUTTER WILL BE
 CONSTRUCTED. REDRAW THE DETAIL IN ACAD AND PROVIDE
 ENGLISH UNITS.
 8. LABEL WHERE THE DRAINAGE CONTROL STRUCTURE WILL BE
 LOCATED AND PROVIDE A DETAIL OF THE STRUCTURE. NOTE THE
 CITY DOES NOT ALLOW THE USE OF BLEEDERS WITH
 EXFILTRATION TRENCHES.
 9. CONFIRM THE OUTFALL PIPE WILL NOT ENTER THE EXISTING
 STRUCTURE AT A CORNER OF THE STRUCTURE.
 10. PROVIDE HATCHING PATTERNS FOR SIDEWALKS TO REMAIN
 AND FOR NEW/REPLACEMENT SIDEWALKS.
 11. PER FIGURE XV-2: GENERAL PARKING DIMENSIONS IN
 SECTION 94-485 OF THE CITY?S CODE OF ORDINANCES, THE
 CURB LENGTH OF PARALLEL PARKING SPACES IS 22 FEET. THE
 SITE PLAN SHOWS 25 FEET AND GAPS IN THE PARKING SPACES
 ON TAMARIND AVE.
 12. CONSIDER ANGLING THE CURBING AT EACH END OF
 PROPOSED PARALLEL PARKING SPACES TO FACILITATE ACCESS
 TO AND FROM THE END SPACES.
 13. THE CITY?S OFFICIAL VERTICAL DATUM IS NGVD1929. THE
 CITY HAS ALLOWED THE USE OF NAVD1988 AS LONG AS THE
 CONVERSION EQUATION TO NGVD1929 AT THE PROJECT LOCATION
 IS PROVIDED. PROVIDE THE NAVD1988 TO NGVD1929
 CONVERSION EQUATION ON THE SURVEY.
 14. LABEL ANY NEW GUTTER OR CURB AND GUTTER IN THE
 RIGHT OF WAY.
 15. CONSIDER LOW IMPACT DEVELOPMENT DRAINAGE SYSTEMS IN
 LIEU OF EXFILTRATION TRENCHES.
 16. EASEMENT MAY BE NEEDED FOR THE SIDEWALK AND PARKING
 ON GRANT ST.
 17. REVIEW AS-BUILT DRAWINGS FOR THE ARV TO DETERMINE
 IF THE STRUCTURE CAN BE MODIFIED TO LOWER THE RIM TO
 PROPOSED GRADE.
 18. SHOW UTILITIES ON THE LANDSCAPE PLANS.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP
 CRITERIA. STORMWATER CALCULATIONS WILL BE REVIEWED WITH
 THE ENGINEERING PERMIT SUBMITTAL.
  
 2. PROVIDE COPY OF SFWMD ERP PERMIT BEFORE START OF
 CONSTRUCTION, IF REQUIRED.
  
 3. PROVIDE AN EROSION CONTROL PLAN WITH DETAILS.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 3 Status P Date 09-27-2022 Cont ID  
Sent By vnoel Date 09-27-2022 Time 09:42 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2022-09-27 09:42:37PASSED WITH CONDITION OF REPLAT PRIOR TO C.O.

Review Stop SURVEY SURVEYING
Rev No 2 Status F Date 04-26-2022 Cont ID  
Sent By vnoel Date 04-26-2022 Time 07:04 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2022-04-26 07:30:391. THERE ARE 3 METERS SHOWN ON SURVEY THAT ARE NOT
 ADDRESSED.
 2. ADD PROPOSED UTILITIES TO LANDSCAPE PLAN.
 3. ADJACENT SIDEWALKS WILL NEED TO BE REPLACED.
 4. MAINTENANCE AGREEMENT WILL BE REQUIRED FOR
 IMPROVEMENTS/LANDSCAPING IN THE R/W.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 01-10-2022 Cont ID  
Sent By vnoel Date 01-10-2022 Time 09:50 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2022-01-10 09:54:451. REVISE SURVEY AND ALL PLANS TO SHOW MAINTENANCE MAP
 RIGHT-OF-WAY IN ROAD PLAT BOOK 11/94.
 2. MASTER METER MAY BE REQUIRED. METER BANK CONFLICTS
 WITH PROPOSED LANDSCAPING.
 3. CHANGE LINE WEIGHT OF PROPERTY LINE FOR BETTER
 DELINEATION. DIVIDE CONCEPTUAL PLAN INTO SEPARATE P&G
 AND W&S PLANS.
 4. NEED TO SEE CROSS-SECTIONS ON ALL SIDES DUE TO GRADE
 DIFFERENCES.
 5. SURVEY NEEDS TO BE SIGNED/SEALED.
 6. ADD CONVERSION TO NGVD-29 TO ALL PLANS.
 7. REPLAT MAY BE REQUIRED.
 8. CIVIL PLANS ALMOST ILLEGIBLE.
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 4 Status P Date 12-07-2022 Cont ID  
Sent By   Date 12-07-2022 Time   Rev Time 0.00
Received By   Date 12-07-2022 Time   Sent To  
Notes
2022-12-07 18:36:41APPROVED WITH THE FOLLOWING CONDITION:
 1) THE NEWLY PROPOSED PARKING STALL AREA ALONG GRANT ST
 MUST BE LOCATED 20-FEET FROM THE EXISTING PEDESTRIAN
 CROSSWALK BY THE TAMARIND INTERSECTION, PER FDOT
 REGULATIONS. PLEASE SHOW SUCH MINIMUM DISTANCE ON THE
 SITE PLAN
 2) PROVIDE BUSH SHELTER DETAILS AND OBTAIN APPROVAL
 FROM PALM TRAN BY COORDINATING WITH YASH NAGAL
 ([email protected]). PLEASE COPY ENGINEERING SERVICES
 IN THE CORRESPONDENCE
  
 PREVIOUS COMMENTS
 1) SATISFIED. PROVIDE TRAFFIC STUDY. LATEST SUBMISSION
 DID NOT CONTAIN A TRAFFIC STUDY
 2) SATISFIED. PROVIDE COUNTY TPS LETTER. LETTER WAS NOT
 PROVIDED IN THE LATEST RESUBMISSION
 3) SATISFIED. PROVIDE A SEPARATE SITE PLAN SHOWCASING
 PROPOSED TRANSPORTATION FEATURES (I.E. ROAD, PARKING
 STALLS, SIDEWALK, CURB, DRIVEWAY) PROPERLY LABELED AND
 EXACT WIDTHS SHOWCASED. IF ALREADY PROVIDED, PLEASE
 INDICATE SPECIFIC FILE NAME AND/OR SHEET NUMBER(S).
 4) SATISFIED. ON THE SITE PLAN, PLEASE SHOWCASE BASIC
 CURB DETAILS (I.E. DRIVEWAY AND PARKING STALLS) ON THE
 OPPOSITE SIDE OF THE ROADS SURROUNDING THE PROPOSED
 DEVELOPMENT. PLEASE PROVIDE DOCUMENT NAME AND SHEET
 NUMBER SHOWCASING SUCH FEATURES.
 5) SATISFIED. PROVIDE AUTOTURN ANALYSIS FOR GARBAGE
 TRUCK AND/OR SERVICE VEHICLES DRIVING IN AND OUT OF THE
 PROPOSED DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES
 CLEARLY DEFINED. ANALYSIS SHOULD BE PROVIDED IN A
 SEPARATE FILE/DRAWING. PLEASE PROVIDE DOCUMENT NAME AND
 SHEET NUMBER SHOWCASING THE ANALYSIS. LATEST ANALYSIS
 WAS NOT PROVIDED IN A SEPARATE FILE. BOTH VEHICLES???
 PATH AND MANEUVERING ARE NOT CLEAR. IF NEEDED,
 ENGINEERING SERVICES CAN PROVIDE AN EXAMPLE OF AN
 ACCEPTABLE ANALYSIS.
 6) SATISFIED. PROVIDE PARKING TABLE SHOWCASING THE
 NUMBER OF REQUIRED AND PROVIDED PARKING SPACES,
 INCLUSIVE OF ADA AND BICYCLE ONES
 7) SATISFIED. THE CITY BICYCLE MASTERPLAN ENVISIONS
 SHARED BICYCLE LANES ALONG TAMARIND AVENUE. IF NEEDED
 OR MISSING PROVIDE CORRESPONDING SIGNAGE AND PAVEMENT
 MARKINGS ACCORDING TO CITY STANDARDS ALONG THE BLOCK
 FRONTING THE PROPOSED DEVELOPMENT. INSERT REQUIRED
 PAVEMENT MARKINGS AND SIGN LOCATIONS IN THE SITE PLAN.
 8) NOT APPLICABLE. PROVIDE AN UPGRADED BUS STOP,
 INCLUSIVE OF A SHELTER. THE PROPOSED CURB CUT ON THE
 WEST SIDE OF TAMARIND SHALL BE CONVERTED TO A BUS
 PULL-OVER AREA
 9) SATISFIED. GIVEN THE ABANDONMENT ALONG TAMARIND AVE
 AND CONSIDERING THE PRESENCE OF A BUS STOP, USE PORTION
 OF THE AVAILABLE GREEN AREA TO EXPAND THE SIDEWALK TO
 10 FEET WIDE. PLEASE ELABORATE THE RESPONSE ON THIS
 MATTER, AS LATEST ONE IS UNCLEAR
 10) SITE PLANS DO NOT MATCH CIVIL PLANS WITH RESPECT TO
 THE ABANDONMENT AREA
 11) SATISFIED. IS THE BUS STOP BEING RELOCATED?
 12) PARTIALLY SATISFIED. EXPLAIN THE USE OF THE
 ABANDONED AREA. ARE PARKING STALLS BEING ESTABLISHED?
 OR IS IT A BUS PULLOVER BAY?
 13) SATISFIED. A MINIMUM OF 5 FEET SIDEWALK SHALL BE
 ESTABLISHED AROUND THE PROPOSED DEVELOPMENT FRONTAGE.
 PLEASE INDICATE DOCUMENT NAME AND SHEET NUMBER
 SHOWCASING SUCH FEATURE, PROPERLY DIMENSIONED.
 14) SATISFIED. PLACE A SHELTER AT THE BUS STOP
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 3 Status F Date 08-09-2022 Cont ID  
Sent By   Date 08-09-2022 Time   Rev Time 0.00
Received By   Date 08-09-2022 Time   Sent To  
Notes
2022-08-09 23:46:181) SATISFIED. PROVIDE TRAFFIC STUDY. LATEST SUBMISSION
 DID NOT CONTAIN A TRAFFIC STUDY
 2) NOT SATISFIED. PROVIDE COUNTY TPS LETTER. LETTER WAS
 NOT PROVIDED IN THE LATEST RESUBMISSION
 3) SATISFIED. PROVIDE A SEPARATE SITE PLAN SHOWCASING
 PROPOSED TRANSPORTATION FEATURES (I.E. ROAD, PARKING
 STALLS, SIDEWALK, CURB, DRIVEWAY) PROPERLY LABELED AND
 EXACT WIDTHS SHOWCASED. IF ALREADY PROVIDED, PLEASE
 INDICATE SPECIFIC FILE NAME AND/OR SHEET NUMBER(S).
 4) SATISFIED. ON THE SITE PLAN, PLEASE SHOWCASE BASIC
 CURB DETAILS (I.E. DRIVEWAY AND PARKING STALLS) ON THE
 OPPOSITE SIDE OF THE ROADS SURROUNDING THE PROPOSED
 DEVELOPMENT. PLEASE PROVIDE DOCUMENT NAME AND SHEET
 NUMBER SHOWCASING SUCH FEATURES.
 5) SATISFIED. PROVIDE AUTOTURN ANALYSIS FOR GARBAGE
 TRUCK AND/OR SERVICE VEHICLES DRIVING IN AND OUT OF THE
 PROPOSED DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES
 CLEARLY DEFINED. ANALYSIS SHOULD BE PROVIDED IN A
 SEPARATE FILE/DRAWING. PLEASE PROVIDE DOCUMENT NAME AND
 SHEET NUMBER SHOWCASING THE ANALYSIS. LATEST ANALYSIS
 WAS NOT PROVIDED IN A SEPARATE FILE. BOTH VEHICLES?
 PATH AND MANEUVERING ARE NOT CLEAR. IF NEEDED,
 ENGINEERING SERVICES CAN PROVIDE AN EXAMPLE OF AN
 ACCEPTABLE ANALYSIS.
 6) SATISFIED. PROVIDE PARKING TABLE SHOWCASING THE
 NUMBER OF REQUIRED AND PROVIDED PARKING SPACES,
 INCLUSIVE OF ADA AND BICYCLE ONES
 7) NOT SATISFIED. THE CITY BICYCLE MASTERPLAN ENVISIONS
 SHARED BICYCLE LANES ALONG TAMARIND AVENUE. IF NEEDED
 OR MISSING PROVIDE CORRESPONDING SIGNAGE AND PAVEMENT
 MARKINGS ACCORDING TO CITY STANDARDS ALONG THE BLOCK
 FRONTING THE PROPOSED DEVELOPMENT. INSERT REQUIRED
 PAVEMENT MARKINGS AND SIGN LOCATIONS IN THE SITE PLAN.
 8) NOT APPLICABLE. PROVIDE AN UPGRADED BUS STOP,
 INCLUSIVE OF A SHELTER. THE PROPOSED CURB CUT ON THE
 WEST SIDE OF TAMARIND SHALL BE CONVERTED TO A BUS
 PULL-OVER AREA
 9) NOT SATISFIED. GIVEN THE ABANDONMENT ALONG TAMARIND
 AVE AND CONSIDERING THE PRESENCE OF A BUS STOP, USE
 PORTION OF THE AVAILABLE GREEN AREA TO EXPAND THE
 SIDEWALK TO 10 FEET WIDE. PLEASE ELABORATE THE RESPONSE
 ON THIS MATTER, AS LATEST ONE IS UNCLEAR
 10) SITE PLANS DO NOT MATCH CIVIL PLANS WITH RESPECT TO
 THE ABANDONMENT AREA
 11) IS THE BUS STOP BEING RELOCATED?
 12) EXPLAIN THE USE OF THE ABANDONED AREA. ARE PARKING
 STALLS BEING ESTABLISHED? OR IS IT A BUS PULLOVER BAY?
 13) A MINIMUM OF 5 FEET WIDE SIDEWALK SHALL BE
 ESTABLISHED AROUND THE PROPOSED DEVELOPMENT FRONTAGE.
 PLEASE INDICATE DOCUMENT NAME AND SHEET NUMBER
 SHOWCASING SUCH FEATURE, PROPERLY DIMENSIONED
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status F Date 04-15-2022 Cont ID  
Sent By   Date 04-15-2022 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2022-04-15 16:27:16TRAFFIC COMMENTS
 1) NOT SATISFIED. PROVIDE TRAFFIC STUDY. LATEST
 SUBMISSION DID NOT CONTAIN A TRAFFIC STUDY
 2) NOT SATISFIED. PROVIDE COUNTY TPS LETTER
 3) SATISFIED. PROVIDE A SEPARATE SITE PLAN SHOWCASING
 PROPOSED TRANSPORTATION FEATURES (I.E. ROAD, PARKING
 STALLS, SIDEWALK, CURB, DRIVEWAY) PROPERLY LABELED AND
 EXACT WIDTHS SHOWCASED. IF ALREADY PROVIDED, PLEASE
 INDICATE SPECIFIC FILE NAME AND/OR SHEET NUMBER(S).
 4) SATISFIED. ON THE SITE PLAN, PLEASE SHOWCASE BASIC
 CURB DETAILS (I.E. DRIVEWAY AND PARKING STALLS) ON THE
 OPPOSITE SIDE OF THE ROADS SURROUNDING THE PROPOSED
 DEVELOPMENT. PLEASE PROVIDE DOCUMENT NAME AND SHEET
 NUMBER SHOWCASING SUCH FEATURES.
 5) NOT SATISFIED. PROVIDE AUTOTURN ANALYSIS FOR GARBAGE
 TRUCK AND/OR SERVICE VEHICLES DRIVING IN AND OUT OF THE
 PROPOSED DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES
 CLEARLY DEFINED. ANALYSIS SHOULD BE PROVIDED IN A
 SEPARATE FILE/DRAWING. PLEASE PROVIDE DOCUMENT NAME AND
 SHEET NUMBER SHOWCASING THE ANALYSIS. LATEST ANALYSIS
 WAS NOT PROVIDED IN A SEPARATE FILE. BOTH VEHICLES PATH
 AND MANEUVERING ARE NOT CLEAR. IF NEEDED, ENGINEERING
 SERVICES CAN PROVIDE AN EXAMPLE OF AN ACCEPTABLE
 ANALYSIS.
 6) SATISFIED. PROVIDE PARKING TABLE SHOWCASING THE
 NUMBER OF REQUIRED AND PROVIDED PARKING SPACES,
 INCLUSIVE OF ADA AND BICYCLE ONES
 7) NOT SATISFIED. THE CITY BICYCLE MASTERPLAN ENVISIONS
 SHARED BICYCLE LANES ALONG TAMARIND AVENUE. IF NEEDED
 OR MISSING PROVIDE CORRESPONDING SIGNAGE AND PAVEMENT
 MARKINGS ACCORDING TO CITY STANDARDS ALONG THE BLOCK
 FRONTING THE PROPOSED DEVELOPMENT. INSERT REQUIRED
 PAVEMENT MARKINGS AND SIGN LOCATIONS IN THE SITE PLAN.
 8) NOT APPLICABLE. PROVIDE AN UPGRADED BUS STOP,
 INCLUSIVE OF A SHELTER. THE PROPOSED CURB CUT ON THE
 WEST SIDE OF TAMARIND SHALL BE CONVERTED TO A BUS
 PULL-OVER AREA
 9) GIVEN THE ABANDONMENT ALONG TAMARIND AVE AND
 CONSIDERING THE PRESENCE OF A BUS STOP, USE PORTION OF
 THE AVAILABLE GREEN AREA TO EXPAND THE SIDEWALK TO 10
 FEET WIDE.
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 01-06-2022 Cont ID  
Sent By   Date 01-06-2022 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2022-01-06 20:16:21TRAFFIC COMMENTS
 1) PROVIDE TRAFFIC STUDY
 2) PROVIDE COUNTY TPS LETTER
 SITE COMMENTS
 3) PROVIDE A SEPARATE SITE PLAN SHOWCASING PROPOSED
 TRANSPORTATION FEATURES (I.E. ROAD, PARKING STALLS,
 SIDEWALK, CURB, DRIVEWAY) PROPERLY LABELED AND EXACT
 WIDTHS SHOWCASED. IF ALREADY PROVIDED, PLEASE INDICATE
 SPECIFIC FILE NAME AND/OR SHEET NUMBER(S).
 4) ON THE SITE PLAN, PLEASE SHOWCASE BASIC CURB DETAILS
 (I.E. DRIVEWAY AND PARKING STALLS) ON THE OPPOSITE SIDE
 OF THE ROADS SURROUNDING THE PROPOSED DEVELOPMENT.
 PLEASE PROVIDE DOCUMENT NAME AND SHEET NUMBER
 SHOWCASING SUCH FEATURES.
 5) PROVIDE AUTOTURN ANALYSIS FOR GARBAGE TRUCK AND/OR
 SERVICE VEHICLES DRIVING IN AND OUT OF THE PROPOSED
 DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES CLEARLY
 DEFINED. ANALYSIS SHOULD BE PROVIDED IN A SEPARATE
 FILE/DRAWING. PLEASE PROVIDE DOCUMENT NAME AND SHEET
 NUMBER SHOWCASING THE ANALYSIS.
 6) PROVIDE PARKING TABLE SHOWCASING THE NUMBER OF
 REQUIRED AND PROVIDED PARKING SPACES, INCLUSIVE OF ADA
 AND BICYCLE ONES
 7) THE CITY BICYCLE MASTERPLAN ENVISIONS SHARED BICYCLE
 LANES ALONG TAMARIND AVENUE. IF MISSING OR NEEDED,
 PROVIDE CORRESPONDING SIGNAGE AND PAVEMENT MARKINGS
 ACCORDING TO CITY STANDARDS ALONG THE BLOCK FRONTING
 THE PROPOSED DEVELOPMENT
 8) PROVIDE AN UPGRADED BUS STOP, INCLUSIVE OF A
 SHELTER. THE PROPOSED CURB CUT ON THE WEST SIDE OF
 TAMARIND SHALL BE DEDICATED TO A BUS PULL-OVER AREA
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  
  
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 12-07-2022 Cont ID  
Sent By jroach Date 12-07-2022 Time 13:01 Rev Time 0.00
Received By jroach Date 12-07-2022 Time 13:00 Sent To  
Notes
2022-12-07 13:00:51PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW
 ________________________________________
  
 DATE OF REVIEW: 12.07.2022
 PROJECT NO.: Z21120021 AND Z21120016
 CASE NO.: ISPR 21-16 AND PB 1907
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 1. SATISFIED - APPROVAL LETTER FROM PALM BEACH COUNTY
 SHALL BE PROVIDED INDICATING THAT THE PROJECT COMPLIES
 WITH THE TRANSPORTATION PERFORMANCE STANDARDS (TRAFFIC
 CONCURRENCY).
  
 2. SATISFIED (NOTE THEIR CONDITION OF APPROVAL) -
 APPROVED SCHOOL CAPACITY AVAILABILITY DETERMINATION
 SHALL BE PROVIDED FROM THE SCHOOL DISTRICT OF PALM
 BEACH COUNTY.
  
 3. SATISFIED (SUBJECT TO CONDITION OF APPROVAL -
 EASEMENTS REQUIRED) - LETTERS FROM ALL UTILITY
 COMPANIES SHALL BE PROVIDED INDICATING THAT THE
 PROPOSED PROJECT DOES NOT ENCROACH INTO THEIR EASEMENTS
 OR OTHERWISE INTERFERE WITH THEIR ABILITY TO PROVIDE
 SERVICES.
  
 4. SATISFIED - JUSTIFICATION STATEMENT IS TO INCLUDE
 RESPONSES INDICATING HOW THE PROPOSED DEVELOPMENT
 COMPLIES WITH THE SITE PLAN REVIEW STANDARDS FOR CODE
 COMPLIANCE [SEC. 94-35(C)].
  
 5. SATISFIED (CONCERNS STILL EXIST BUT ALL CODE
 REQUIREMENTS HAVE BEEN MET) - STAFF WOULD LIKE TO WORK
 WITH THE ARCHITECT ON THE VARIOUS ELEMENTS OF THE
 ARCHITECTURAL STYLING. CONCERNS INCLUDE:
  
 5.1. SATISFIED (CONCERNS STILL EXIST BUT ALL CODE
 REQUIREMENTS HAVE BEEN MET) - ALL OF THE PROJECTS IS
 EXACTLY THE SAME. ALTERNATIVE STYLES, OR VARIATIONS,
 SHOULD BE CONSIDERED ACROSS ALL OF THE PROJECTS AS THEY
 ARE SEPARATE SITES ALONG THE CORRIDOR AND READ
 INDEPENDENTLY OF ONE ANOTHER.
  
 5.1.1 SATISFIED - THE RENDERINGS PROVIDED DO NOT
 ACCURATELY DEPICT WHAT IS SHOWN IN THE ELEVATIONS,
 LANDSCAPE PLANS, ETC.
  
 5.1.2. SATISFIED - THE ELEVATIONS DO NOT CORRESPOND
 WITH WHAT IS SHOWN IN THE FLOOR PLAN
 (WINDOW/DOOR/STOREFRONT CONFIGURATIONS).
  
 5.2.. SATISFIED - ADDITIONAL WINDOWS/OPENING ARE NEEDED
 ON THE SIDES/REAR OF THE BUILDING TO PROVIDE BETTER
 ARCHITECTURAL STYLING, NATURAL SURVEILLANCE, VISUAL
 ENHANCEMENT TO THE NON-RESIDENTIAL SPACES, ETC.
  
 5.3. SATISFIED - GROUND FLOOR RESIDENTIAL UNITS FACING
 TAMARIND AVENUE SHOULD INDIVIDUALLY READ AS WALK-UP
 UNITS WITH THEIR FRONT/MAIN ENTRANCE FACING THE
 RIGHT-OF-WAY.
  
 6. SATISFIED - PHOTOMETRIC LEVELS NEED TO BE SHOWN AT
 THE PROPERTY LINE. LEVELS SHALL NOT EXCEED 0.5
 FOOTCANDLES WHEN MEASURED AT THE PROPERTY LINE ADJACENT
 TO A RESIDENTIAL ZONING DISTRICT.
  
 7. SATISFIED - THE SQUARE FOOTAGE OF THE AREA TO BE
 ABANDONED SHOWN ON THE SITE PLAN IS NOT CONSISTENT WHAT
 IS DESCRIBED IN THE SKETCH/LEGAL OF THE ABANDONMENT.
 ENSURE THAT ALL PLANS/DOCUMENTS ARE ACCURATE AND
 CONSISTENT.
  
 8. SATISFIED (SUBJECT TO CONDITION OF APPROVAL) - THE
 RELOCATION OF THE BUS STOP SHALL BE APPROVED BY PALM
 TRAN AND THE CITY?S ENGINEERING SERVICES DEPARTMENT.
  
 9. SATISFIED - PURSUANT TO SEC. 94-222(H)(5) ALL
 WINDOWS ARE TO BE VERTICAL OR SQUARE IN PROPORTION.
  
 10. SATISFIED - PURSUANT TO SEC. 94-222(H)(6) ALL
 WINDOWS ARE TO BE RECESSED A MINIMUM OF 2 INCHES FROM
 THE EXTERIOR FACE OF THE FA?ADE. PLEASE PROVIDE A
 DETAIL.
  
 11. SATISFIED - PURSUANT TO SEC. 94-222(H)(7) ALL
 WINDOWS ARE TO BE OPERABLE. PLEASE PROVIDE A
 DETAIL/NOTE.
  
 12. SATISFIED - PURSUANT TO SEC. 94-222(H)(10) SLIDING
 DOORS ARE ONLY ALLOWED ON THE REAR FA?ADE.
  
 13. SATISFIED - PURSUANT TO SEC. 94-231(C)(6)(A) THE
 MINIMUM FRONT SETBACK IS 10 FEET; THE PROPOSED BUILDING
 ONLY COMPLIES IF THE PROPOSED ABANDONMENT IS APPROVED.
  
 14. SATISFIED - THE FAR CALCULATION IS INCORRECT.
  
 15. SATISFIED (SUBJECT TO APPROVAL BY THE ENGINEERING
 SERVICES DEPARTMENT) - THE CONSTRUCTION OF THE NEW
 ON-STREET PARKING IS SUBJECT TO THE APPROVAL OF THE
 CITY?S ENGINEERING SERVICES DEPARTMENT.
  
 16. SATISFIED - PLEASE CLEARLY IDENTIFY THE LOCATION OF
 THE PROPOSED PROPERTY LINE ALONG TAMARIND AVENUE (IF
 ABANDONMENT IS APPROVED).
  
 17. SATISFIED - THE TURNAROUND SPACE AND THE DUMPSTER
 ENCLOSURE APPEAR TO CONFLICT WITH EACH OTHER AND NOT
 PROVIDE SUFFICIENT MANEUVERING. PLEASE PROVIDE AN
 AUTO-TURN ANALYSIS OR MODIFY ACCORDINGLY.
  
 17.1 SATISFIED - TURNAROUND SPACE SHALL BE PROVIDED.
 PLEASE MARK THE TURNAROUND SPACE WITH A CROSS-HATCH
 INDICATING "NO PARKING".
  
 18. SATISFIED - BICYCLE PARKING SHALL BE PROVIDED IN
 ACCORDANCE WITH SEC. 94-485(Q). INDICATE ALL LOCATIONS.
  
 18.1 SATISFIED - THE PAD FOR THE BIKE RACKS SHOULD BE A
 MINIMUM OF 72 INCHES IN LENGTH AND AT AT LEAST 24
 INCHES ON EITHER SIDE OF THE RACK. IF MORE THAN ONE
 RACK IS PROVIDED, THERE SHALL BE AT LEAST 30 INCHES
 BETWEEN THE RACKS.
  
 19. SATISFIED - ENSURE THAT PLANS SHOW ALL WALLS,
 FENCES, ETC. IF RETAINING WALLS ARE PROPOSED,
 DETAILS/CROSS SECTIONS NEED TO BE PROVIDED.
  
 20. SATISFIED - PARKING STRIPING DETAIL DOES NOT
 CONFORM TO THE CITY?S MINIMUM STANDARDS.
  
 21. SATISFIED - PLEASE CLARIFY THE DUMPSTER ENCLOSURE
 DETAIL, IT LOOKS LIKE THE GATES CONSIST OF CHAIN LINK;
 SUCH MATERIAL IS NOT PERMITTED. THE GATE NEEDS TO BE A
 SOLID/OPAQUE MATERIAL.
  
 22. SATISFIED - PLEASE IDENTIFY THE VISIBILITY
 TRIANGLES (AS DEFINED BY THE CITY?S ZLDRS) AT THE
 INTERSECTIONS OF THE RIGHTS-OF-WAY. NO OBJECTS WITHIN
 THE VISIBILITY TRIANGLE SHALL EXIST BETWEEN A HEIGHT OF
 18 INCHES AND 8 FEET.
  
 23. SATISFIED - SCREEN WALLS SHALL BE PROVIDED ALONG
 THE WEST PROPERTY LINE SEPARATING THE PARKING FROM THE
 ADJACENT RESIDENTIAL USES [SEC. 94-443(A)(1)].
  
 24. SATISFIED - PLEASE PROVIDE A CROSS SECTION THROUGH
 THE ENTIRE SITE TO SHOW THE ELEVATION PROFILE, ETC. AS
 THE PROPERTY SLOPES EAST/WEST.
  
 25. SATISFIED - ALL BALCONIES, ROOF OVERHANGS, AWNINGS,
 ETC. NEED TO BE SHOWN AND DIMENSIONED ON THE SITE PLAN.
 PURSUANT TO SEC. 94-305(B)(2) SUCH ENCROACHMENTS SHALL
 NOT EXTEND MORE THAN 3 FEET INTO A REQUIRED SETBACK.
  
 26. SATISFIED - IT IS THE CITY?S POLICY FOR
 RIGHT-OF-WAY ABANDONMENTS THAT THE PETITIONER PAY TO
 THE CITY THE APPRAISED VALUE OF THE RIGHT-OF-WAY.
 PLEASE COORDINATE WITH VINCE NOEL ON OBTAINING THE
 APPRAISAL, ETC.
  
 27. SATISFIED - THE LEFT GATE OF THE DUMPSTER ENCLOSURE
 IMPEDES WITH THE INGRESS TRAVEL LANE FROM STATE STREET.
  
 28. SATISFIED - THE SCALE ON THE SITE PLAN IS
 INCORRECT.
  
 29. SATISFIED - THE HEIGHT OF THE BUILDING APPEARS TO
 HAVE INCREASED SIGNIFICANTLY AND EXCEEDS THE MAXIMUM
 BUILDING HEIGHT. PURSUANT TO SEC. 94-231, THE MAXIMUM
 HEIGHT WITHIN THE CP-NC ZONING DISTRICT IS 30 FEET,
 WITH AN ADDITIONAL 10% ALLOWED FOR DECORATIVE ELEMENTS,
 PARAPETS, ETC.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 04-26-2022 Cont ID  
Sent By jroach Date 04-26-2022 Time 15:33 Rev Time 0.00
Received By jroach Date 04-26-2022 Time 15:33 Sent To  
Notes
2022-04-26 15:33:40PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW
 ________________________________________
  
 DATE OF REVIEW: 04.26.2022
 PROJECT NO.: Z21120021 AND Z21120016
 CASE NO.: ISPR 21-16 AND PB 1907
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 1. SATISFIED - APPROVAL LETTER FROM PALM BEACH COUNTY
 SHALL BE PROVIDED INDICATING THAT THE PROJECT COMPLIES
 WITH THE TRANSPORTATION PERFORMANCE STANDARDS (TRAFFIC
 CONCURRENCY).
  
 2. SATISFIED (NOTE THEIR CONDITION OF APPROVAL) -
 APPROVED SCHOOL CAPACITY AVAILABILITY DETERMINATION
 SHALL BE PROVIDED FROM THE SCHOOL DISTRICT OF PALM
 BEACH COUNTY.
  
 3. SATISFIED (SUBJECT TO CONDITION OF APPROVAL -
 EASEMENTS REQUIRED) - LETTERS FROM ALL UTILITY
 COMPANIES SHALL BE PROVIDED INDICATING THAT THE
 PROPOSED PROJECT DOES NOT ENCROACH INTO THEIR EASEMENTS
 OR OTHERWISE INTERFERE WITH THEIR ABILITY TO PROVIDE
 SERVICES.
  
 4. SATISFIED - JUSTIFICATION STATEMENT IS TO INCLUDE
 RESPONSES INDICATING HOW THE PROPOSED DEVELOPMENT
 COMPLIES WITH THE SITE PLAN REVIEW STANDARDS FOR CODE
 COMPLIANCE [SEC. 94-35(C)].
  
 5. PARTIALLY SATISFIED - STAFF WOULD LIKE TO WORK WITH
 THE ARCHITECT ON THE VARIOUS ELEMENTS OF THE
 ARCHITECTURAL STYLING. CONCERNS INCLUDE:
  
 5.1. PARTIALLY SATISFIED - ALL OF THE PROJECTS IS
 EXACTLY THE SAME. ALTERNATIVE STYLES, OR VARIATIONS,
 SHOULD BE CONSIDERED ACROSS ALL OF THE PROJECTS AS THEY
 ARE SEPARATE SITES ALONG THE CORRIDOR AND READ
 INDEPENDENTLY OF ONE ANOTHER.
  
 5.1.1 NEW COMMENT - THE RENDERINGS PROVIDED DO NOT
 ACCURATELY DEPICT WHAT IS SHOWN IN THE ELEVATIONS,
 LANDSCAPE PLANS, ETC.
  
 5.1.2. NEW COMMENT - THE ELEVATIONS DO NOT CORRESPOND
 WITH WHAT IS SHOWN IN THE FLOOR PLAN
 (WINDOW/DOOR/STOREFRONT CONFIGURATIONS).
  
 5.2.. SATISFIED - ADDITIONAL WINDOWS/OPENING ARE NEEDED
 ON THE SIDES/REAR OF THE BUILDING TO PROVIDE BETTER
 ARCHITECTURAL STYLING, NATURAL SURVEILLANCE, VISUAL
 ENHANCEMENT TO THE NON-RESIDENTIAL SPACES, ETC.
  
 5.3. PARTIALLY SATISFIED - GROUND FLOOR RESIDENTIAL
 UNITS FACING TAMARIND AVENUE SHOULD INDIVIDUALLY READ
 AS WALK-UP UNITS WITH THEIR FRONT/MAIN ENTRANCE FACING
 THE RIGHT-OF-WAY.
  
 6. SATISFIED - PHOTOMETRIC LEVELS NEED TO BE SHOWN AT
 THE PROPERTY LINE. LEVELS SHALL NOT EXCEED 0.5
 FOOTCANDLES WHEN MEASURED AT THE PROPERTY LINE ADJACENT
 TO A RESIDENTIAL ZONING DISTRICT.
  
 7. SATISFIED - THE SQUARE FOOTAGE OF THE AREA TO BE
 ABANDONED SHOWN ON THE SITE PLAN IS NOT CONSISTENT WHAT
 IS DESCRIBED IN THE SKETCH/LEGAL OF THE ABANDONMENT.
 ENSURE THAT ALL PLANS/DOCUMENTS ARE ACCURATE AND
 CONSISTENT.
  
 8. NO LONGER APPLICABLE - THE RELOCATION OF THE BUS
 STOP SHALL BE APPROVED BY PALM TRAN AND THE CITY?S
 ENGINEERING SERVICES DEPARTMENT.
  
 9. SATISFIED - PURSUANT TO SEC. 94-222(H)(5) ALL
 WINDOWS ARE TO BE VERTICAL OR SQUARE IN PROPORTION.
  
 10. SATISFIED - PURSUANT TO SEC. 94-222(H)(6) ALL
 WINDOWS ARE TO BE RECESSED A MINIMUM OF 2 INCHES FROM
 THE EXTERIOR FACE OF THE FA?ADE. PLEASE PROVIDE A
 DETAIL.
  
 11. SATISFIED - PURSUANT TO SEC. 94-222(H)(7) ALL
 WINDOWS ARE TO BE OPERABLE. PLEASE PROVIDE A
 DETAIL/NOTE.
  
 12. SATISFIED - PURSUANT TO SEC. 94-222(H)(10) SLIDING
 DOORS ARE ONLY ALLOWED ON THE REAR FA?ADE.
  
 13. SATISFIED (SUBJECT TO APPROVAL OF THE ROW
 ABANDONMENT) - PURSUANT TO SEC. 94-231(C)(6)(A) THE
 MINIMUM FRONT SETBACK IS 10 FEET; THE PROPOSED BUILDING
 ONLY COMPLIES IF THE PROPOSED ABANDONMENT IS APPROVED.
  
 14. NOT SATISFIED - THE FAR CALCULATION IS INCORRECT.
  
 15. SATISFIED (SUBJECT TO APPROVAL BY THE ENGINEERING
 SERVICES DEPARTMENT) - THE CONSTRUCTION OF THE NEW
 ON-STREET PARKING IS SUBJECT TO THE APPROVAL OF THE
 CITY?S ENGINEERING SERVICES DEPARTMENT.
  
 16. SATISFIED - PLEASE CLEARLY IDENTIFY THE LOCATION OF
 THE PROPOSED PROPERTY LINE ALONG TAMARIND AVENUE (IF
 ABANDONMENT IS APPROVED).
  
 17. PARTIALLY SATISFIED - THE TURNAROUND SPACE AND THE
 DUMPSTER ENCLOSURE APPEAR TO CONFLICT WITH EACH OTHER
 AND NOT PROVIDE SUFFICIENT MANEUVERING. PLEASE PROVIDE
 AN AUTO-TURN ANALYSIS OR MODIFY ACCORDINGLY.
  
 17.1 NEW COMMENT - TURNAROUND SPACE SHALL BE PROVIDED.
 PLEASE MARK THE TURNAROUND SPACE WITH A CROSS-HATCH
 INDICATING "NO PARKING".
  
 18. PARTIALLY SATISFIED - BICYCLE PARKING SHALL BE
 PROVIDED IN ACCORDANCE WITH SEC. 94-485(Q). INDICATE
 ALL LOCATIONS.
  
 18.1 NEW COMMENT - THE PAD FOR THE BIKE RACKS SHOULD BE
 A MINIMUM OF 72 INCHES IN LENGTH AND AT AT LEAST 24
 INCHES ON EITHER SIDE OF THE RACK. IF MORE THAN ONE
 RACK IS PROVIDED, THERE SHALL BE AT LEAST 30 INCHES
 BETWEEN THE RACKS.
  
 19. SATISFIED - ENSURE THAT PLANS SHOW ALL WALLS,
 FENCES, ETC. IF RETAINING WALLS ARE PROPOSED,
 DETAILS/CROSS SECTIONS NEED TO BE PROVIDED.
  
 20. SATISFIED - PARKING STRIPING DETAIL DOES NOT
 CONFORM TO THE CITY?S MINIMUM STANDARDS.
  
 21. SATISFIED - PLEASE CLARIFY THE DUMPSTER ENCLOSURE
 DETAIL, IT LOOKS LIKE THE GATES CONSIST OF CHAIN LINK;
 SUCH MATERIAL IS NOT PERMITTED. THE GATE NEEDS TO BE A
 SOLID/OPAQUE MATERIAL.
  
 22. NOT SATISFIED - PLEASE IDENTIFY THE VISIBILITY
 TRIANGLES (AS DEFINED BY THE CITY?S ZLDRS) AT THE
 INTERSECTIONS OF THE RIGHTS-OF-WAY. NO OBJECTS WITHIN
 THE VISIBILITY TRIANGLE SHALL EXIST BETWEEN A HEIGHT OF
 18 INCHES AND 8 FEET.
  
 23. SATISFIED - SCREEN WALLS SHALL BE PROVIDED ALONG
 THE WEST PROPERTY LINE SEPARATING THE PARKING FROM THE
 ADJACENT RESIDENTIAL USES [SEC. 94-443(A)(1)].
  
 24. NOT SATISFIED - PLEASE PROVIDE A CROSS SECTION
 THROUGH THE ENTIRE SITE TO SHOW THE ELEVATION PROFILE,
 ETC. AS THE PROPERTY SLOPES EAST/WEST.
  
 25. SATISFIED - ALL BALCONIES, ROOF OVERHANGS, AWNINGS,
 ETC. NEED TO BE SHOWN AND DIMENSIONED ON THE SITE PLAN.
 PURSUANT TO SEC. 94-305(B)(2) SUCH ENCROACHMENTS SHALL
 NOT EXTEND MORE THAN 3 FEET INTO A REQUIRED SETBACK.
  
 26. SATISFIED (SUBJECT TO PAYMENT OF APPRAISED VALUE
 UPON APPROVAL BY CITY COMMISSION) - IT IS THE CITY?S
 POLICY FOR RIGHT-OF-WAY ABANDONMENTS THAT THE
 PETITIONER PAY TO THE CITY THE APPRAISED VALUE OF THE
 RIGHT-OF-WAY. PLEASE COORDINATE WITH VINCE NOEL ON
 OBTAINING THE APPRAISAL, ETC.
  
 27. NEW COMMENT - THE LEFT GATE OF THE DUMPSTER
 ENCLOSURE IMPEDES WITH THE INGRESS TRAVEL LANE FROM
 STATE STREET.
  
 28. NEW COMMENT - THE SCALE ON THE SITE PLAN IS
 INCORRECT.
  
 29. NEW COMMENT - THE HEIGHT OF THE BUILDING APPEARS TO
 HAVE INCREASED SIGNIFICANTLY AND EXCEEDS THE MAXIMUM
 BUILDING HEIGHT. PURSUANT TO SEC. 94-231, THE MAXIMUM
 HEIGHT WITHIN THE CP-NC ZONING DISTRICT IS 30 FEET,
 WITH AN ADDITIONAL 10% ALLOWED FOR DECORATIVE ELEMENTS,
 PARAPETS, ETC.
 ________________________________________
  
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
  
 B) ELECTRONIC COPY OF ALL PLANS AND DOCUMENTS SHALL BE
 PROVIDED UPON RESUBMITTAL.
  
 C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
  
 D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 01-13-2022 Cont ID  
Sent By jroach Date 01-13-2022 Time 11:25 Rev Time 0.00
Received By jroach Date 01-13-2022 Time 11:25 Sent To  
Notes
2022-01-13 11:27:30PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW
 ________________________________________
  
 DATE OF REVIEW: 01.13.2022
 PROJECT NO.: Z21120021 AND Z21120016
 CASE NO.: ISPR 21-16 AND PB 1907
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 1. APPROVAL LETTER FROM PALM BEACH COUNTY SHALL BE
 PROVIDED INDICATING THAT THE PROJECT COMPLIES WITH THE
 TRANSPORTATION PERFORMANCE STANDARDS (TRAFFIC
 CONCURRENCY).
  
 2. APPROVED SCHOOL CAPACITY AVAILABILITY DETERMINATION
 SHALL BE PROVIDED FROM THE SCHOOL DISTRICT OF PALM
 BEACH COUNTY.
  
 3. LETTERS FROM ALL UTILITY COMPANIES SHALL BE PROVIDED
 INDICATING THAT THE PROPOSED PROJECT DOES NOT ENCROACH
 INTO THEIR EASEMENTS OR OTHERWISE INTERFERE WITH THEIR
 ABILITY TO PROVIDE SERVICES.
  
 4. JUSTIFICATION STATEMENT IS TO INCLUDE RESPONSES
 INDICATING HOW THE PROPOSED DEVELOPMENT COMPLIES WITH
 THE SITE PLAN REVIEW STANDARDS FOR CODE COMPLIANCE
 [SEC. 94-35(C)].
  
 5. STAFF WOULD LIKE TO WORK WITH THE ARCHITECT ON THE
 VARIOUS ELEMENTS OF THE ARCHITECTURAL STYLING. CONCERNS
 INCLUDE:
  
 6. ALL OF THE PROJECTS IS EXACTLY THE SAME. ALTERNATIVE
 STYLES, OR VARIATIONS, SHOULD BE CONSIDERED ACROSS ALL
 OF THE PROJECTS AS THEY ARE SEPARATE SITES ALONG THE
 CORRIDOR AND READ INDEPENDENTLY OF ONE ANOTHER.
  
 7. ADDITIONAL WINDOWS/OPENING ARE NEEDED ON THE
 SIDES/REAR OF THE BUILDING TO PROVIDE BETTER
 ARCHITECTURAL STYLING, NATURAL SURVEILLANCE, VISUAL
 ENHANCEMENT TO THE NON-RESIDENTIAL SPACES, ETC.
  
 8. GROUND FLOOR RESIDENTIAL UNITS FACING TAMARIND
 AVENUE SHOULD INDIVIDUALLY READ AS WALK-UP UNITS WITH
 THEIR FRONT/MAIN ENTRANCE FACING THE RIGHT-OF-WAY.
  
 9. PHOTOMETRIC LEVELS NEED TO BE SHOWN AT THE PROPERTY
 LINE. LEVELS SHALL NOT EXCEED 0.5 FOOTCANDLES WHEN
 MEASURED AT THE PROPERTY LINE ADJACENT TO A RESIDENTIAL
 ZONING DISTRICT.
  
 10. THE SQUARE FOOTAGE OF THE AREA TO BE ABANDONED
 SHOWN ON THE SITE PLAN IS NOT CONSISTENT WHAT IS
 DESCRIBED IN THE SKETCH/LEGAL OF THE ABANDONMENT.
 ENSURE THAT ALL PLANS/DOCUMENTS ARE ACCURATE AND
 CONSISTENT.
  
 11. THE RELOCATION OF THE BUS STOP SHALL BE APPROVED BY
 PALM TRAN AND THE CITY?S ENGINEERING SERVICES
 DEPARTMENT.
  
 12. PURSUANT TO SEC. 94-222(H)(5) ALL WINDOWS ARE TO BE
 VERTICAL OR SQUARE IN PROPORTION.
  
 13. PURSUANT TO SEC. 94-222(H)(6) ALL WINDOWS ARE TO BE
 RECESSED A MINIMUM OF 2 INCHES FROM THE EXTERIOR FACE
 OF THE FA?ADE. PLEASE PROVIDE A DETAIL.
  
 14. PURSUANT TO SEC. 94-222(H)(7) ALL WINDOWS ARE TO BE
 OPERABLE. PLEASE PROVIDE A DETAIL/NOTE.
  
 15. PURSUANT TO SEC. 94-222(H)(10) SLIDING DOORS ARE
 ONLY ALLOWED ON THE REAR FA?ADE.
  
 16. PURSUANT TO SEC. 94-231(C)(6)(A) THE MINIMUM FRONT
 SETBACK IS 10 FEET; THE PROPOSED BUILDING ONLY COMPLIES
 IF THE PROPOSED ABANDONMENT IS APPROVED.
  
 17. THE FAR CALCULATION IS INCORRECT.
  
 18. THE CONSTRUCTION OF THE NEW ON-STREET PARKING IS
 SUBJECT TO THE APPROVAL OF THE CITY?S ENGINEERING
 SERVICES DEPARTMENT.
  
 19. PLEASE CLEARLY IDENTIFY THE LOCATION OF THE
 PROPOSED PROPERTY LINE ALONG TAMARIND AVENUE (IF
 ABANDONMENT IS APPROVED).
  
 20. THE TURNAROUND SPACE AND THE DUMPSTER ENCLOSURE
 APPEAR TO CONFLICT WITH EACH OTHER AND NOT PROVIDE
 SUFFICIENT MANEUVERING. PLEASE PROVIDE AN AUTO-TURN
 ANALYSIS OR MODIFY ACCORDINGLY.
  
 21. BICYCLE PARKING SHALL BE PROVIDED IN ACCORDANCE
 WITH SEC. 94-485(Q). INDICATE ALL LOCATIONS.
  
 22. ENSURE THAT PLANS SHOW ALL WALLS, FENCES, ETC. IF
 RETAINING WALLS ARE PROPOSED, DETAILS/CROSS SECTIONS
 NEED TO BE PROVIDED.
  
 23. PARKING STRIPING DETAIL DOES NOT CONFORM TO THE
 CITY?S MINIMUM STANDARDS.
  
 24. PLEASE CLARIFY THE DUMPSTER ENCLOSURE DETAIL, IT
 LOOKS LIKE THE GATES CONSIST OF CHAIN LINK; SUCH
 MATERIAL IS NOT PERMITTED. THE GATE NEEDS TO BE A
 SOLID/OPAQUE MATERIAL.
  
 25. PLEASE IDENTIFY THE VISIBILITY TRIANGLES (AS
 DEFINED BY THE CITY?S ZLDRS) AT THE INTERSECTIONS OF
 THE RIGHTS-OF-WAY. NO OBJECTS WITHIN THE VISIBILITY
 TRIANGLE SHALL EXIST BETWEEN A HEIGHT OF 18 INCHES AND
 8 FEET.
  
 26. SCREEN WALLS SHALL BE PROVIDED ALONG THE WEST
 PROPERTY LINE SEPARATING THE PARKING FROM THE ADJACENT
 RESIDENTIAL USES [SEC. 94-443(A)(1)].
  
 27. PLEASE PROVIDE A CROSS SECTION THROUGH THE ENTIRE
 SITE TO SHOW THE ELEVATION PROFILE, ETC. AS THE
 PROPERTY SLOPES EAST/WEST.
  
 28. ALL BALCONIES, ROOF OVERHANGS, AWNINGS, ETC. NEED
 TO BE SHOWN AND DIMENSIONED ON THE SITE PLAN. PURSUANT
 TO SEC. 94-305(B)(2) SUCH ENCROACHMENTS SHALL NOT
 EXTEND MORE THAN 3 FEET INTO A REQUIRED SETBACK.
  
 29. IT IS THE CITY?S POLICY FOR RIGHT-OF-WAY
 ABANDONMENTS THAT THE PETITIONER PAY TO THE CITY THE
 APPRAISED VALUE OF THE RIGHT-OF-WAY. PLEASE COORDINATE
 WITH VINCE NOEL ON OBTAINING THE APPRAISAL, ETC.
 ________________________________________
  
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
  
 B) ELECTRONIC COPY OF ALL PLANS AND DOCUMENTS SHALL BE
 PROVIDED UPON RESUBMITTAL.
  
 C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
  
 D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147