Plan Review Details - Project Z21120020
| Plan Review Stops For Project Z21120020 |
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
1 |
Status |
N |
Date |
08-05-2022 |
|
|
Cont ID |
|
| Sent By |
scwelter |
Date |
08-05-2022 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
scwelter |
Date |
08-05-2022 |
Time |
11:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
01-12-2022 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
01-12-2022 |
Time |
18:39 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
01-12-2022 |
Time |
18:38 |
Sent To |
|
|
| Notes |
| 2022-01-12 18:42:16 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS | | | SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT | | | REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH | | | COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963, | | | OR BY EMAIL: [email protected] | | | | | | 3. UNITY OF TITLE. FOR ANY BUILDING CROSSING A PROPERTY | | | LINE, EITHER A RECORDED UNITY OF TITLE, OR SOME OTHER | | | APPROVED LEGAL INSTRUMENT, SHALL BE INCLUDED WITH THE | | | PERMIT APPLICATION, OR THE BUILDING MUST HAVE A FIRE | | | WALL ALONG THE PROPERTY LINE, PER SECTION 202 OF | | | FLORIDA BUILDING CODE, BUILDING, FIRE SEPARATION | | | DISTANCE. | | | | | | 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, | | | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR | | | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, | | | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE | | | FLORIDA BUILDING CODE. | | | | | | 5. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, | | | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND | | | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, | | | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. | | | | | | 6. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND | | | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF | | | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL | | | NEIGHBORING PROPERTIES. | | | | | | 7. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER | | | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, | | | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE | | | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF | | | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION | | | THAT MAY AFFECT THE USE OF THEIR PROPERTY. | | | | | | 8. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT | | | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL | | | HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION | | | OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING, | | | CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT | | | (561) 805 6659, OR BY EMAIL: [email protected] | | | | | | 9. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT | | | TO ART LIFE ASSESSMENT UNDER THE CITY OF WEST PALM | | | BEACH ART IN PUBLIC PLACES (AIPP) PROGRAM. FOR ADVICE | | | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP | | | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC | | | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
3 |
Status |
P |
Date |
07-19-2022 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
07-19-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
07-19-2022 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
F |
Date |
04-01-2022 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
04-01-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
04-01-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-04-01 13:28:46 | Z21120020, 0015 - RESUB 3.24.22 | | | | | | COMMENTS FROM RICK ROSSANO, SR. PROJECT COORDINATOR, | | | ENG. SERVICES DEPT., 561-494-1098 [email protected] : | | | | | | 1. CONFIRM THAT A COMPLETED LOS ANALYSIS SUMMARY TABLE | | | HAS BEEN SUBMITTED DIRECTLY TO ENGINEERING (SHEET 33 OF | | | CITY OF WPB DEVELOPMENT APPLICATION). | | | 2. CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY | | | SEWER ARE REQUIRED. | | | 3. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND | | | PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM | | | AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE | | | PER FAC 64E-8 FOR WATER AND PER FAC 64-E.008 FOR SEWER. | | | 4. PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND | | | STORMWATER PIPES ALONG ENTIRE PROJECT FRONTAGE. | | | 5. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND | | | IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED | | | AREAS. | | | 6. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE | | | SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING | | | PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT | | | HIM AT 561-494-2262 OR [email protected] | | | 1. FOR FORMAL ENGINEERING SUBMITTAL , PLANS SHALL SHOW | | | PROPOSED LOCATIONS AND DIMENSIONS OF ALL WATER, | | | STORMWATER, AND SANITARY AND SEWER LINES, INCLUDING | | | STUBS TO EACH PROPERTY LINE FOR WATER AND SANITARY | | | SEWERS, THE MAKE AND MODEL OF ALL VALVES, METERS, AND | | | OTHERS DEVICES TO BE INSTALLED ON THE SYSTEM, CATCH | | | BASINS, CULVERTS, DITCHES INCLUDING GRADES, PIPES | | | SIZES, MATERIALS, ELEVATIONS, ASSUMPTIONS, | | | CALCULATIONS, INVERT ELEVATIONS FOR ALL INLETS AND | | | MANHOLES AND PROFILES OF SANITARY SEWER LINES. ALL | | | AVAILABLE ELEVATION SHALL BE SHOWN ON THE PROFILE VIEW. | | | DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN | | | VIEW FOR ALL SANITARY AND STORM SEWERS. ADDITIONALLY, | | | PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED | | | UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC, | | | ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION | | | FACILITIES LOCATED ON THE RIGHT-OF-WAY. PROVIDE PROFILE | | | AND CLEARANCES AT ALL UTILITY CROSSINGS. | | | 7. PLEASE CLOUD/HIGHLIGHT PLAN REVISIONS OR CHANGES IN | | | SCOPE FOR RESUBMITTAL OF DRAWINGS. | | | 8. FOR FORMAL ENGINEERING SUBMITTAL , CUT AND CAP | | | UTILITIES NOT IN USE, AND REMOVE ANY ABANDONED UTILITY | | | LINES LARGER THAN 2 INCHES FROM CITY RIGHT OF WAY. | | | 9. FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE DEDICATED | | | UTILITY EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO | | | PROPOSED UTILITY WATER METERS. | | | 10. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | ENLARGED VIEW ON PLANS OF PROPOSED LOCATION OF WATER | | | METER AND BACKFLOW PREVENTION. | | | 11. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE CALLOUT | | | DOMESTIC BACKFLOW PREVENTER AS RPPA AND FIRE BACKFLOW | | | PREVENTER AS DCDA. SPECIFY LEAD FREE DESIGN ON ALL | | | BACKFLOWS. | | | 12. FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND | | | NPDES NOI REQUIREMENTS WILL BE ENFORCED. | | | - AN NOI IS REQUIRED FOR PROJECTS THAT: | | | - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS | | | THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF | | | DEVELOPMENT OR SALE; AND | | | - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE | | | STATE OR TO SURFACE WATERS OF THE STATE THROUGH A | | | MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4). | | | - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF | | | CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION | | | THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL | | | SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT | | | OF THE 10-2 CERTIFICATION. IF THE ENGINEERING PLANS DO | | | NOT INCLUDE AN EROSION CONTROL PLAN, THEN THE | | | CONTRACTOR SHOULD SUBMIT ONE PRIOR TO RECEIVING THE | | | ENGINEERING PERMIT. | | | 13. FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES | | | OF PROPOSED AND EXISTING WATER AND SEWER WITHIN RIGHT | | | OF WAY AND SHOW ANY CROSSINGS/CONFLICTS. | | | 14. FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING | | | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT | | | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING | | | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED | | | LEAD-FREE DESIGN. | | | 15. FOR FORMAL ENGINEERING SUBMITTAL CLEARLY SHOW ROAD | | | RIGHT OF WAY. | | | 16. FOR FORMAL ENGINEERING SUBMITTAL PROVIDE SANITARY | | | ELEVATIONS AT MANHOLE TIE-IN. | | | 17. FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY | | | INFRASTRUCTURE IS PROPOSED IN ROW PLEASE SHOW ADJACENT | | | SANITARY LATERAL LOCATIONS AND SHOW ADDRESSES OF | | | ADJACENT PARCELS. | | | 18. FOR FORMAL ENGINEERING SUBMITTAL, IF WATER | | | INFRASTRUCTURE IS BEING REPLACED IN ROW, SHOW ADJACENT | | | PARCEL ADDRESSES. | | | 19. FOR FORMAL ENGINEERING SUBMITTAL, WHEN TRENCHING IN | | | IN CITY MAINTAINED ROADWAY AREAS ADD NOTE TO PROVIDE 50 | | | FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF | | | PROPOSED TRENCH PER CURRENT CITY OF WPB STANDARD DETAIL | | | GC-8. | | | 20. PLEASE RESPOND TO ALL COMMENTS IN WRITING AND | | | INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER | | | (Z-XXXXXXXX). | | | | | | COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE | | | SUPER., WPB PUBLIC UTILITIES, 561-494-2262 OR | | | [email protected]: | | | | | | -RESPONSE LETTER DOES NOT CONTAIN REVIEW COMMENTS FROM | | | FIRST SUBMISSION. PLEASE RESUBMIT RESPONSE LETTER WITH | | | ALL COMMENTS AND RESPONSES. | | | | | | -ON CIVIL PLANS, PLEASE ALSO INCLUDE THE NUMBERED | | | STREET NAME WITH TAFT AVENUE. MAPS I AM ACCESSING DO | | | NOT REFER TO IT AS TAFT. | | | | | | -ARE VEHICLES TRAVELING WEST ON 19TH ST ALLOWED TO MAKE | | | U TURN AFTER MEDIAN INTO THE DRIVEWAY. IF SO, WILL | | | LARGER VEHICLES BE ABLE TO MAKE THAT MANEUVER? | | | | | | -SHOW AND LABEL LOCATION OF PROPOSED IRRIGATION METERED | | | WATER SERVICE. ALSO SHOW AND LABEL RP BACKFLOW ASSEMBLY | | | FOR IT. | | | | | | -WATER PLAN AND SITE PLAN HAVE RECTANGULAR OBJECT | | | BETWEEN THE PROPOSED WATER SERVICES. VERIFY IF THAT IS | | | CORRECT. | | | | | | -CIVIL PLANS DO NOT IDENTIFY THE DRIVEWAY APPROACH | | | CONVERSION TO PARKWAY AND CURB NEAR THE WATER SERVICES. | | | | | | -PROPOSED WATER METER IS ENCROACHING IN SIDEWALK. | | | | | | -ADD WORDING ABOVE-GROUND TO LABEL OF 4 INCH METER. | | | | | | -ADD STANDARD DETAIL FOR LARGE ABOVE GROUND WATER METER | | | AND FIRELINE BACKFLOW ASSEMBLY. | | | | | | -FOOTPRINT OF 4 INCH METER AND PIPING MAY BE LARGER | | | THAN SHOWN ON WATER PLAN. | | | | | | -PARALLEL BACKFLOW ASSEMBLIES ARE RECOMMENDED ON | | | DOMESTIC WATER SERVICE TO MINIMIZE WATER OUTAGES DURING | | | BACKFLOW MAINTENANCE. | | | | | | -DOMESTIC BACKFLOW ASSEMBLY SHOULD NOT BE INSIDE | | | PROPOSED UTILITY EASEMENT. | | | | | | -LANDSCAPE PLAN DOES NOT SHOW UTILITIES. PLEASE ENSURE | | | NO CONFLICTS BETWEEN UTILITIES AND PROPOSED TREES. ADD | | | CLEARANCE DISTANCE AND ROOT BARRIERS AS NEEDED. | | | | | | -ADD DEMO PLAN IF THERE WILL BE DEMOLITION. | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
01-13-2022 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
01-13-2022 |
Time |
|
Rev Time |
|
| Received By |
rrossano |
Date |
01-13-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-01-13 08:23:39 | COMMENTS FROM RICK ROSSANO, SR. PROJECT COORDINATOR, | | | ENG. SERVICES DEPT., 561-494-1098 [email protected] : | | | | | | GENERAL: | | | O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND | | | INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER | | | (Z-XXXXXXXX). | | | O THE CITY OF WEST PALM BEACH HAS A NUMBER OF | | | REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY | | | AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND | | | WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE | | | DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK | | | BELOW: | | | A. HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WP | | | B_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FUL | | | L-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97 | | | B1960045731D3658206F27451722716EF | | | B. THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE | | | FOUND HERE: | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | C. ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM | | | BEACH, FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, | | | ADOPTED SEPT. 22, 2008. (SUPPLEMENT NO. 18) | | | CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL, | | | SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER | | | SERVICE FACILITIES OF THE CITY. | | | THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE | | | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY | | | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, | | | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. | | | O AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR | | | MORE INFORMATION, REFER TO THE LINK BELOW: | | | A. HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PU | | | BLICATIONS/BACKFLOW-CROSS-CONNECTION- CONTROL-MANUAL | | | O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY | | | OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC | | | RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF | | | YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE | | | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL | | | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT | | | [email protected] OR 561-494-1079 FOR FURTHER | | | ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION | | | ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD | | | SURVEY, POT-HOLING, SOFT DIGS ETC. | | | | | | BACKFLOW ASSEMBLY AND METERS: | | | O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER | | | SERVICES AND WATER METERS, ALONG WITH WHAT IS HAPPENING | | | TO THEM. | | | O SHOW EXISTING AND PROPOSED DEDICATED UTILITY | | | EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO | | | PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO | | | STRUCTURES WITHIN EASEMENT. | | | O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION | | | OF WATER METER AND BACKFLOW | | | PREVENTION. | | | O BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY | | | OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER | | | METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO | | | PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE | | | INSTALLED ABOVE-GROUND ONLY. | | | O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE | | | NOTE USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA. | | | | | | WATER/WASTEWATER PLAN: | | | O PROVIDE VERTICAL DATUM AND DATUM CONVERSION | | | INFORMATION (NAVD 1988 AND NGVD 1929). | | | O SHOW PROJECT ADDRESS ON ALL PLAN SHEETS. | | | O PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE | | | STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC. | | | O PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND | | | DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND | | | SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH | | | PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE | | | AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS, | | | BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO | | | BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS, | | | DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS, | | | ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT | | | ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF | | | SANITARY SEWER LINES. | | | O GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR | | | SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE | | | PROFILE VIEW. | | | O DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN | | | VIEW FOR ALL SANITARY AND STORM SEWERS. | | | O SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT | | | MATERIAL. | | | O PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED | | | UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC, | | | ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION | | | FACILITIES LOCATED ON THE RIGHT-OF-WAY. | | | O PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER | | | AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD | | | DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS. | | | O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY | | | TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT | | | APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING | | | AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, | | | MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS | | | SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 | | | FOR WATER. | | | O PROVIDE FIRE FLOW TEST DATA. | | | O PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND | | | STORMWATER INFRASTRUCTURE ALONG ENTIRE PROJECT | | | FRONTAGE. | | | O CUT AND CAP UTILITIES NOT IN USE AND REMOVE ANY | | | ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY | | | ROW. | | | O WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL | | | BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY | | | PROPOSED LENGTH IN FEET. | | | O CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY | | | SEWER ARE REQUIRED. | | | O PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE | | | JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET. | | | O ADD NOTE TO PLANS SPECIFYING CITY?S DOWNSTREAM LIFT | | | STATION NUMBER. | | | O PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR | | | PROPOSED SANITARY LATERALS. | | | O LABEL WATER LINES AS PRIVATE WHERE APPLICABLE. | | | O PLEASE SHOW AND LABEL EXISTING AND PROPOSED GREASE | | | TRAPS (IF ANY). | | | O PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN | | | OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER. | | | | | | FORMAL ENGINEERING REVIEW: | | | O FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES | | | NOI REQUIREMENTS WILL BE ENFORCED. | | | - AN NOI IS REQUIRED FOR PROJECTS THAT: | | | - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS | | | THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF | | | DEVELOPMENT OR SALE; | | | - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE | | | STATE OR TO SURFACE WATERS OF THE STATE THROUGH A | | | MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4). | | | - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF | | | CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION | | | THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL | | | SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT | | | OF THE 10-2 CERTIFICATION. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF | | | WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING | | | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT | | | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING | | | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED | | | LEAD-FREE DESIGN. | | | O FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES | | | ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY | | | LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT | | | PARCELS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, IF WATER LINES ARE | | | BEING REPLACED IN ROW, SHOW ADJACENT PARCEL ADDRESSES. | | | O FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO PROVIDE | | | 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF | | | PROPOSED TRENCH IN CITY MAINTAINED ROADWAY AREAS PER | | | CITY OF WPB STANDARD DETAIL GC-8. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | CALCULATIONS OF PERVIOUS AND IMPERVIOUS AREAS FOR | | | PROPOSED IMPROVED AREAS. | | | | | | | | | COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE | | | SUPER., WPB PUBLIC UTILITIES, 561-494-2262 OR | | | [email protected]: | | | | | | -GEO REPORT SAYS GFA SHOULD BE REQUESTED TO REVIEW DATA | | | TO SEE IF RECOMMENDATIONS ARE VALID. WILL APPLICANT | | | FOLLOWUP WITH THEM ONCE BUILDING DETAILS ARE FINALIZED? | | | | | | -SUBMIT DEMO PLAN IF THERE WILL BE DEMOLITION. | | | | | | -PLANS DO NOT SHOW WHAT WILL BE HAPPENING TO EXISTING | | | CURB CUT DRIVEWAYS ON TAMARIND AND 19TH ST. | | | | | | -PLANS SAY THAT THERE IS A COVERED SIDEWALK, BUT COULD | | | NOT DETERMINE HOW. IS THERE A PROJECTION OFF THE | | | BUILDING OR A STANDALONE COVERING? | | | | | | -SITE PLAN SHOWS SOMETHING THAT LOOKS LIKE LANDSCAPING | | | PLANTS IN MIDDLE OF PARKING LOT DRIVING AREA. | | | | | | -SIDEWALK EASEMENT OR AGREEMENT MAY BE REQUIRED FOR | | | PROPOSED SIDEWALK ON 19TH ST. | | | | | | -GREASE TRAPS/INTERCEPTORS MAY BE REQUIRED IF THE | | | RETAIL UNIT HAS FOOD SERVICE. | | | | | | -PLANS DESCRIBED FIRE SPRINKLERS. FIRE SPRINKLERS | | | CANNOT BE FED FROM DOMESTIC WATER SERVICES. WOULD NEED | | | AT LEAST ONE DEDICATED FIRE SERVICE WITH DETECTOR | | | BACKFLOW ASSEMBLY. THOSE REQUIRE UTILITY BILLING | | | ACCOUNTS. | | | | | | -SHOW AND LABEL ALL EXISTING AND PROPOSED SEWER LATERAL | | | CLEANOUTS. | | | | | | -SHOW AND LABEL UTILITY EASEMENT FOR METERED WATER | | | SERVICES ON PROPERTY. | | | | | | -WATER DESIGN IS NONSTANDARD AND MAY REQUIRE REVISION | | | AT FORMAL ENGINEERING SUBMITTAL. | | | | | | -RETAIL AND IRRIGATION METERED WATER SERVICES WOULD | | | NEED BACKFLOW ASSEMBLIES. PLEASE SHOW AND LABEL ON | | | PLANS. ALSO ANY METERED WATER SERVICE FEEDING MULTIPLE | | | DWELLING UNITS WOULD NEED BACKFLOW ASSEMBLY AS WELL. | | | | | | -CIVIL PLANS SHOWS 10 WATER METERS (9 DOMESTIC AND 1 | | | IRRIGATION), BUT THERE ARE 12 RESIDENTIAL DWELLING | | | UNITS AND A RETAIL SPACE. PLEASE DETAIL BETTER HOW THE | | | METERS ARE GOING TO BE USED. | | | | | | -PAVEMENT RESTORATION WILL BE NEEDED ON 19TH ST DUE TO | | | PROPOSED UTILITY WORK. | | | | | | -SITE PLANS SHOW PROPOSED PARKING ON 19TH ST, BUT NOT | | | DEPICTED ON CIVIL PLANS. PLEASE MAKE SURE ALL PLAN SETS | | | MATCH AND UPDATE AS NEEDED. | | | | | | -CIVIL PLANS SHOWS A LARGE UTILITY POLE IN PROPOSED | | | DRIVEWAY APPROACH ON 19TH ST. | | | | | | -CHECK SIDEWALK DESIGN AND LABELING ON CIVIL PLANS. | | | THEY ARE DIFFICULT TO DISTINGUISH AND DO NOT SEEM TO | | | MATCH SITE PLANS. | | | | | | -LANDSCAPE PLAN IS MISSING FROM SUBMITTAL PACKAGE. | | | PLEASE SUBMIT AND ENSURE NO CONFLICTS BETWEEN | | | LANDSCAPING AND UTILITIES. | | | | | | -UNUSED EXISTING WATER SERVICES FOR PROPERTY MAY | | | REQUIRE REMOVAL. | | | | | | -SOME SIDEWALKS MAY REQUIRE REPLACEMENT DUE TO | | | PROJECT?S UTILITY WORK. | | | | | | -SHOW LOCATION OF NEAREST FIRE HYDRANT ON ENGINEERING | | | PLAN. | | | | | | -19TH ST CURRENTLY HAS ACCESSIBLE SIDEWALK ON NORTH | | | SIDE OF PROPERTY. PLEASE VERIFY IT WILL STILL REMAIN | | | USABLE AFTER PROJECT AND WILL NOT HAVE RAISED CURBING | | | AT SIDES OF DRIVEWAY APPROACH. | | | | | | -NORTHWEST AREA OF DRIVEWAY MAY CONFLICT WITH | | | NEIGHBORING PROPERTY DRIVEWAY. IT ALSO EXTENDS PAST | | | WESTERN PROPERTY LINE. | | | | | | -ARE VEHICLES TRAVELING WEST ON 19TH ST ALLOWED TO MAKE | | | U TURN AFTER MEDIAN INTO THE DRIVEWAY. IF SO, WILL | | | LARGER VEHICLES BE ABLE TO MAKE THAT MANEUVER? | | | | | | -BBQ AREA LOOKS DIFFERENTLY DESIGNED ON CIVIL PLANS AND | | | SITE PLAN. PLEASE MAKE SURE DESIGN MATCHES ON ALL PLANS | | | AND UPDATE AS NECESSARY. | | | | | | -WILL THERE BE CURBING BETWEEN PARKING LOT AND BBQ | | | AREA? | | | | | | -HOW WILL THE IRRIGATION UTILITY BILL BE HANDLED? WILL | | | THERE BE AN HOA OR PROPERTY MANAGER? | | | | | | -THE ROW VACATION APPLICATION DOES NOT HAVE THE WRITTEN | | | VERIFICATION FROM THE UTILITY COMPANIES THAT THERE ARE | | | NO CONFLICTS. PLEASE SUBMIT. | | | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | | CONCERNS, THANKS. | | | | | | QUESTIONS AND COORDINATION CONTACTS: | | | O MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR WITH | | | CITY OF WPB PUBLIC UTILITIES, REGARDING PLACEMENT OF | | | BACKFLOW DEVICES AND WATER METERS. CONTACT HIM AT | | | 561-822-2262 OR [email protected] | | | O RICK ROSSANO, SR. PROJECT COORDINATOR, ENGINEERING | | | SERVICES DEPARTMENT AT 561-494-1098 [email protected] | | | O MIKE TECHNOW, PROJECT ENGINEER, PUBLIC UTILITIES | | | DEPARTMENT AT 561-494-1047 OR [email protected] | | | O TRACY WARD, SR. STORMWATER ENGINEER, ENGINEERING | | | SERVICES DEPT. AT 561-494-1120 OR [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
07-27-2022 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
07-27-2022 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
07-27-2022 |
Time |
15:19 |
Sent To |
|
|
| Notes |
| 2022-07-27 15:19:18 | FIRE HAS NO OBJECTIONS TO THE PROPOSED AND APPROVES. | | | | | | FIRE'S APPROVAL OF THIS SUBMITTED PROJECT MAY NOT | | | CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | FIRE SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT THE | | | APPROPRIATE TIME AND IN ACCORDANCE WITH THE | | | REQUIREMENTS OF ALL APPLICABLE FIRE CODES AND | | | STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
04-04-2022 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
04-04-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
04-04-2022 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2022-04-04 10:10:58 | FIRE HAS NO OBJECTIONS TO THE PROPOSED AND APPROVES. | | | | | | FIRE'S APPROVAL OF THIS SUBMITTED PROJECT MAY NOT | | | CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | FIRE SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT THE | | | APPROPRIATE TIME AND IN ACCORDANCE WITH THE | | | REQUIREMENTS OF ALL APPLICABLE FIRE CODES AND | | | STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
01-04-2022 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
01-04-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
01-04-2022 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2022-01-04 13:45:09 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE DEPARTMENT. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. THE FOLLOWING COMMENTS ARE INTENDED | | | TO PROVIDE GUIDANCE FOR BUILDING PLAN SUBMITTAL. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING(S) SHALL COMPLY | | | WITH THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION | | | CODE, INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE | | | CODES. | | | | | | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE | | | OCCUPANCY TYPE PER THE FLORIDA FIRE PREVENTION CODE. | | | | | | 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE | | | LOAD CALCULATION IS INCLUDED, AND THAT ADEQUATE WATER | | | SUPPLY IS EXISTING OR WILL BE PROVIDED. | | | | | | 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | THE PROPOSED LOCATION OF THE FIRE HYDRANT AND FDC SHALL | | | BE WITHIN 100' OF EACH OTHER AND CLOSELY COORDINATED | | | WITH THE BUREAU OF FIRE PREVENTION. | | | | | | 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER | | | THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY | | | ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM, | | | ENSURE THEY COMPLY WITH THE REQUIREMENTS OF F.A.C. 61G | | | AND SUBMITTED WITH THE MASTER PERMIT. | | | | | | 9A. THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE | | | LOCATIONS SHALL MEET AND BE INSTALLED PER THE | | | REQUIREMENTS OF NFPA 24 AND SHALL BE COORDINATED WITH | | | THE OFFICE OF FIRE MARSHAL, THE CITY'S ENGINEERS | | | OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S PLANNING | | | AND ZONING OFFICE. | | | | | | 10. COMPLETE LIFE SAFETY PLANS FOR THE OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, EXIT SEPARATION DISTANCES, COMMON PATHS OF | | | TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, EMERGENCY | | | LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE | | | EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES | | | AND EQUIPMENT. | | | | | | 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE | | | SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY | | | DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS. | | | | | | 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL. | | | | | | 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
4 |
Status |
P |
Date |
11-17-2022 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
11-17-2022 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
11-17-2022 |
Time |
11:44 |
Sent To |
|
|
| Notes |
| 2022-11-17 11:44:34 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: 1004 19TH ST. Z21120020 | | | NOVEMBER 17, 2022 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. SATISFIED. PROVIDE A SEPARATE TREE DISPOSITION PLAN | | | SHOWING THE LOCATIONS OF THE EXISTING TREES AND INCLUDE | | | THE FOLLOWING INFORMATION: | | | | | | ??? SATISFIED. ADD A COLUMN TO THE CHART FOR MITIGATION | | | SQUARE FOOTAGE DUE AND SHOW THE AMOUNT FOR EACH TREE | | | PROPOSED TO BE REMOVED BASED ON THE CATEGORY OR TREE | | | CANOPY DIAMETER. COLUMN SHOULD BE LABELED MITIGATION | | | DUE. TREES WITH A CANOPY 20 FEET OR MORE IN DIAMETER | | | MUST HAVE THE ACTUAL SQUARE FOOTAGE CALCULATED AND | | | ENTERED ON THE CHART. | | | ALL TREES PROPOSED TO BE REMOVED MUST SHOW THE CANOPY | | | MITIGATION DUE. TREES 1 (300 SQ FT), 5 (300 SQ FT), 6 | | | (300 SQ FT), 7 (300 SQ FT), 8 (300 SQ FT), MUST BE | | | SHOWN. INCLUDE 2 (707 SQ FT) AND 3 (314 SQ FT) | | | SABAL PALM #9 IS IN GOOD CONDITION SO IS REQUIRED TO BE | | | RELOCATED. | | | | | | ??? SATISFIED. PROVIDE TOTAL OF MITIGATION SQUARE | | | FOOTAGE DUE. | | | TOTAL WILL BE 2521 SQ FT. | | | | | | ??? SATISFIED. PROVIDE A TOTAL OF MITIGATION SQUARE | | | FOOTAGE PROVIDED BASED ON THE PLANT LIST. | | | 8 PIGEON PLUM- 8 X150 =1200 | | | 7 LIVE OAK- 7 X300 = 2100 | | | 5 WILD TAMARIND- 5X 300 = 1500 | | | 7 PINK TAB- 7 X 150= 1050 | | | TOTAL IS 5850 SQ FT. SHOW ON TD-1. | | | | | | | | | 2. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE | | | TREES IN GOOD CONDITION TO BE PRESERVED ON SITE OR | | | RELOCATED. ANSI A 300 (PART 5) STANDARDS SPECIFY | | | EXAMPLES OF SUITABILITY RATINGS OF GOOD, MODERATE, OR | | | POOR FOR RELOCATION. PROVIDE AN ARBORIST REPORT SHOWING | | | CONDITION FOR ALL TREES AND RELOCATION POTENTIAL FOR | | | THE NATIVE TREES AND PALMS PROPOSED TO BE REMOVED. | | | | | | 3. SATISFIED. PROVIDE THE CALCULATIONS FOR THE MINIMUM | | | REQUIRED SHADE TREES, FLOWERING TREES AND SHRUBS FOR | | | THE SITE BASED ON 40% OPEN SPACE PER SECTION | | | 94-442(C)(2)B. PROVIDE THE CALCULATIONS FOR THE OPEN | | | SPACE BASED ON THE SITE SQUARE FOOTAGE. ADD THE | | | MULTIFAMILY TREE REQUIREMENT TO THIS TOTAL. | | | | | | 4. SATISFIED. PROVIDE THE NUMBER AND PERCENTAGE OF | | | SUBSTITUTION OF PALMS FOR REQUIRED TREES. SECTION | | | 94-442(D) REQUIRES A 3:1 RATIO FOR SUBSTITUTION FOR | | | PALMS EXCEPT THE LISTED 1:1 SPECIES. | | | | | | | | | 5. SATISFIED. PER SECTION 94-443(A)(2) LABEL THE | | | REQUIRED 5 FOOT LANDSCAPE BUFFER ALONG EACH PROPERTY | | | LINE AND CALCULATE THE NUMBER OF TREES REQUIRED AND | | | PROVIDED FOR EACH BUFFER SEGMENT. THE TOTAL LENGTH OF | | | THE PROPERTY LINE PER THE SURVEY MUST BE USED. | | | | | | 6. SATISFIED. PER SECTION 94-443 (E)2., PROVIDE THE 40% | | | FOUNDATION PLANTING CALCULATION REQUIRED AND PROVIDED | | | FOR EACH BUILDING. | | | THE PLAN MUST SHOW THE LINEAR FOOTAGE OF EACH BUILDING | | | PERIMETER, REQUIRED LINEAR FOOTAGE AND PROVIDED. | | | THE REQUIREMENT IS 40% PER SECTION 94-443(D)2.A. | | | | | | 7. SATISFIED. PER SECTION 94-443(C)(3)A. AND B., | | | TERMINAL LANDSCAPE ISLANDS AND INTERIOR ISLANDS MUST | | | HAVE AT LEAST 8 FEET WIDE LANDSCAPE AREA AND RUN THE | | | FULL LENGTH OF THE ADJACENT PARKING SPACE. EACH AREA | | | SHALL HAVE AT LEAST ONE SHADE OR FLOWERING TREE PER ROW | | | OF PARKING. LANDSCAPE BUFFER OF 5 FEET MAY BE COUNTED | | | AS PART OF THE TERMINAL ISLAND. SHOW DIMENSIONS ON THE | | | LANDSCAPE PLAN. | | | | | | 8. SATISFIED. A MINIMUM OF 75% OF ALL TREES REQUIRED TO | | | BE PLANTED WITHIN THE PARKING AREA MUST BE CATEGORY 1 | | | SHADE TREES. SHOW THE PERCENTAGE PROVIDED. | | | 9. SATISFIED. PER SECTION 94-442(G) PROVIDE THE | | | REQUIRED 50 POINTS FROM THE FLORIDA FRIENDLY DESIGN | | | OPTIONS LIST AND SHOW THE TOTAL PROVIDED. | | | 10. SATISFIED. PROVIDE A SECTION IN A LANDSCAPE DATA | | | CHART TO COMPLY WITH SECTION 94-445 L. PLANT SPECIES. A | | | MINIMUM OF 60 PERCENT OF PLANT MATERIAL ADDED SHALL BE | | | FLORIDA NATIVE OR DROUGHT TOLERANT SPECIES SELECTED | | | FROM THE CITY LIST OR THE LIST OF SPECIES IN THE MOST | | | RECENT EDITION OF SOUTH FLORIDA WATER MANAGEMENT | | | DISTRICT WATERWISE SOUTH FLORIDA LANDSCAPES. PROVIDE | | | THE TOTAL PERCENTAGE OF NATIVE AND DROUGHT TOLERANT | | | PLANTS BASED ON FINAL PLANT LIST. | | | | | | 11. SATISFIED. LOCATIONS OF PROPOSED UTILITY LINES | | | INCLUDING WATER, SEWER AND DRAINAGE CONFLICT WITH | | | REQUIRED LANDSCAPING. CIVIL ENGINEERING PLAN, SITE PLAN | | | AND LANDSCAPE PLAN MUST BE CONSISTENT. | | | | | | UTILITIES MUST BE SHOWN ON THE LANDSCAPE PLAN AND | | | CONFLICTS RESOLVED. UTILITY POSITIONS WILL REQUIRE | | | ADJUSTMENT OF PLANTING LOCATIONS OF SOME REQUIRED | | | TREES. | | | 8/8/22 CONFLICTS WITH SEWER LINES ALONG TAMARIND. | | | | | | 12. SATISFIED. SHOW AND LABEL ALL OVERHEAD POWER LINES | | | THAT WILL LIMIT THE TREE SPECIES TO RIGHT TREE RIGHT | | | PLACE GUIDELINES. | | | | | | 13. SATISFIED. PER SECTION 94-443 (A)(1) A PROTECTIVE | | | SCREEN WALL IS REQUIRED ALONG THE ADJACENT RESIDENTIAL | | | PROPERTY LINES. | | | ADDITIONAL COMMENTS 8/8/22: | | | | | | 14. SATISFIED. MUST SHOW SCREENING OF ABOVE GROUND | | | VALVES. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE | | | STREET TREES AND RIGHT OF WAY LANDSCAPING AND | | | IRRIGATION APPROVED WITH THIS PETITION. | | | 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF | | | WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A | | | SEPARATE MAINTENANCE AGREEMENT WITH THE CITY. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
3 |
Status |
F |
Date |
08-08-2022 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
08-08-2022 |
Time |
11:54 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
08-08-2022 |
Time |
11:54 |
Sent To |
|
|
| Notes |
| 2022-08-08 11:54:43 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: 1004 19TH ST. Z21120020 | | | AUGUST 8, 2022 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. SATISFIED. PROVIDE A SEPARATE TREE DISPOSITION PLAN | | | SHOWING THE LOCATIONS OF THE EXISTING TREES AND INCLUDE | | | THE FOLLOWING INFORMATION: | | | | | | ? PARTIALLY SATISFIED. ADD A COLUMN TO THE CHART FOR | | | MITIGATION SQUARE FOOTAGE DUE AND SHOW THE AMOUNT FOR | | | EACH TREE PROPOSED TO BE REMOVED BASED ON THE CATEGORY | | | OR TREE CANOPY DIAMETER. COLUMN SHOULD BE LABELED | | | MITIGATION DUE. TREES WITH A CANOPY 20 FEET OR MORE IN | | | DIAMETER MUST HAVE THE ACTUAL SQUARE FOOTAGE CALCULATED | | | AND ENTERED ON THE CHART. | | | ALL TREES PROPOSED TO BE REMOVED MUST SHOW THE CANOPY | | | MITIGATION DUE. TREES 1 (300 SQ FT), 5 (300 SQ FT), 6 | | | (300 SQ FT), 7 (300 SQ FT), 8 (300 SQ FT), MUST BE | | | SHOWN. INCLUDE 2 (707 SQ FT) AND 3 (314 SQ FT) | | | SABAL PALM #9 IS IN GOOD CONDITION SO IS REQUIRED TO BE | | | RELOCATED. | | | | | | ? PARTIALLY SATISFIED. PROVIDE TOTAL OF MITIGATION | | | SQUARE FOOTAGE DUE. | | | TOTAL WILL BE 2521 SQ FT. | | | | | | ? PARTIALLY SATISFIED. PROVIDE A TOTAL OF MITIGATION | | | SQUARE FOOTAGE PROVIDED BASED ON THE PLANT LIST. | | | 8 PIGEON PLUM- 8 X150 =1200 | | | 7 LIVE OAK- 7 X300 = 2100 | | | 5 WILD TAMARIND- 5X 300 = 1500 | | | 7 PINK TAB- 7 X 150= 1050 | | | TOTAL IS 5850 SQ FT. SHOW ON TD-1. | | | | | | | | | 2. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE | | | TREES IN GOOD CONDITION TO BE PRESERVED ON SITE OR | | | RELOCATED. ANSI A 300 (PART 5) STANDARDS SPECIFY | | | EXAMPLES OF SUITABILITY RATINGS OF GOOD, MODERATE, OR | | | POOR FOR RELOCATION. PROVIDE AN ARBORIST REPORT SHOWING | | | CONDITION FOR ALL TREES AND RELOCATION POTENTIAL FOR | | | THE NATIVE TREES AND PALMS PROPOSED TO BE REMOVED. | | | | | | 3. SATISFIED. PROVIDE THE CALCULATIONS FOR THE MINIMUM | | | REQUIRED SHADE TREES, FLOWERING TREES AND SHRUBS FOR | | | THE SITE BASED ON 40% OPEN SPACE PER SECTION | | | 94-442(C)(2)B. PROVIDE THE CALCULATIONS FOR THE OPEN | | | SPACE BASED ON THE SITE SQUARE FOOTAGE. ADD THE | | | MULTIFAMILY TREE REQUIREMENT TO THIS TOTAL. | | | | | | 4. SATISFIED. PROVIDE THE NUMBER AND PERCENTAGE OF | | | SUBSTITUTION OF PALMS FOR REQUIRED TREES. SECTION | | | 94-442(D) REQUIRES A 3:1 RATIO FOR SUBSTITUTION FOR | | | PALMS EXCEPT THE LISTED 1:1 SPECIES. | | | | | | | | | 5. SATISFIED. PER SECTION 94-443(A)(2) LABEL THE | | | REQUIRED 5 FOOT LANDSCAPE BUFFER ALONG EACH PROPERTY | | | LINE AND CALCULATE THE NUMBER OF TREES REQUIRED AND | | | PROVIDED FOR EACH BUFFER SEGMENT. THE TOTAL LENGTH OF | | | THE PROPERTY LINE PER THE SURVEY MUST BE USED. | | | | | | 6. SATISFIED. PER SECTION 94-443 (E)2., PROVIDE THE 40% | | | FOUNDATION PLANTING CALCULATION REQUIRED AND PROVIDED | | | FOR EACH BUILDING. | | | THE PLAN MUST SHOW THE LINEAR FOOTAGE OF EACH BUILDING | | | PERIMETER, REQUIRED LINEAR FOOTAGE AND PROVIDED. | | | THE REQUIREMENT IS 40% PER SECTION 94-443(D)2.A. | | | | | | 7. SATISFIED. PER SECTION 94-443(C)(3)A. AND B., | | | TERMINAL LANDSCAPE ISLANDS AND INTERIOR ISLANDS MUST | | | HAVE AT LEAST 8 FEET WIDE LANDSCAPE AREA AND RUN THE | | | FULL LENGTH OF THE ADJACENT PARKING SPACE. EACH AREA | | | SHALL HAVE AT LEAST ONE SHADE OR FLOWERING TREE PER ROW | | | OF PARKING. LANDSCAPE BUFFER OF 5 FEET MAY BE COUNTED | | | AS PART OF THE TERMINAL ISLAND. SHOW DIMENSIONS ON THE | | | LANDSCAPE PLAN. | | | | | | 8. SATISFIED. A MINIMUM OF 75% OF ALL TREES REQUIRED TO | | | BE PLANTED WITHIN THE PARKING AREA MUST BE CATEGORY 1 | | | SHADE TREES. SHOW THE PERCENTAGE PROVIDED. | | | 9. SATISFIED. PER SECTION 94-442(G) PROVIDE THE | | | REQUIRED 50 POINTS FROM THE FLORIDA FRIENDLY DESIGN | | | OPTIONS LIST AND SHOW THE TOTAL PROVIDED. | | | 10. SATISFIED. PROVIDE A SECTION IN A LANDSCAPE DATA | | | CHART TO COMPLY WITH SECTION 94-445 L. PLANT SPECIES. A | | | MINIMUM OF 60 PERCENT OF PLANT MATERIAL ADDED SHALL BE | | | FLORIDA NATIVE OR DROUGHT TOLERANT SPECIES SELECTED | | | FROM THE CITY LIST OR THE LIST OF SPECIES IN THE MOST | | | RECENT EDITION OF SOUTH FLORIDA WATER MANAGEMENT | | | DISTRICT WATERWISE SOUTH FLORIDA LANDSCAPES. PROVIDE | | | THE TOTAL PERCENTAGE OF NATIVE AND DROUGHT TOLERANT | | | PLANTS BASED ON FINAL PLANT LIST. | | | | | | 11. PARTIALLY SATISFIED. LOCATIONS OF PROPOSED UTILITY | | | LINES INCLUDING WATER, SEWER AND DRAINAGE CONFLICT WITH | | | REQUIRED LANDSCAPING. CIVIL ENGINEERING PLAN, SITE PLAN | | | AND LANDSCAPE PLAN MUST BE CONSISTENT. | | | | | | UTILITIES MUST BE SHOWN ON THE LANDSCAPE PLAN AND | | | CONFLICTS RESOLVED. UTILITY POSITIONS WILL REQUIRE | | | ADJUSTMENT OF PLANTING LOCATIONS OF SOME REQUIRED | | | TREES. | | | 8/8/22 CONFLICTS WITH SEWER LINES ALONG TAMARIND. | | | | | | 12. SATISFIED. SHOW AND LABEL ALL OVERHEAD POWER LINES | | | THAT WILL LIMIT THE TREE SPECIES TO RIGHT TREE RIGHT | | | PLACE GUIDELINES. | | | | | | 13. SATISFIED. PER SECTION 94-443 (A)(1) A PROTECTIVE | | | SCREEN WALL IS REQUIRED ALONG THE ADJACENT RESIDENTIAL | | | PROPERTY LINES. | | | ADDITIONAL COMMENTS 8/8/22: | | | | | | 14. MUST SHOW SCREENING OF ABOVE GROUND VALVES. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE | | | STREET TREES AND RIGHT OF WAY LANDSCAPING AND | | | IRRIGATION APPROVED WITH THIS PETITION. | | | 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF | | | WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A | | | SEPARATE MAINTENANCE AGREEMENT WITH THE CITY. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
F |
Date |
04-05-2022 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
04-05-2022 |
Time |
18:33 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
04-05-2022 |
Time |
18:33 |
Sent To |
|
|
| Notes |
| 2022-04-05 18:34:12 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: 1004 19TH ST. Z21120020 | | | APRIL 5, 2022 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. SATISFIED. PROVIDE A SEPARATE TREE DISPOSITION PLAN | | | SHOWING THE LOCATIONS OF THE EXISTING TREES AND INCLUDE | | | THE FOLLOWING INFORMATION: | | | ? NOT SATISFIED. ADD A COLUMN TO THE CHART FOR | | | MITIGATION SQUARE FOOTAGE DUE AND SHOW THE AMOUNT FOR | | | EACH TREE PROPOSED TO BE REMOVED BASED ON THE CATEGORY | | | OR TREE CANOPY DIAMETER. COLUMN SHOULD BE LABELED | | | MITIGATION DUE. TREES WITH A CANOPY 20 FEET OR MORE IN | | | DIAMETER MUST HAVE THE ACTUAL SQUARE FOOTAGE CALCULATED | | | AND ENTERED ON THE CHART. | | | ? NOT SATISFIED. PROVIDE TOTAL OF MITIGATION SQUARE | | | FOOTAGE DUE. | | | ? NOT SATISFIED. PROVIDE A TOTAL OF MITIGATION SQUARE | | | FOOTAGE PROVIDED BASED ON THE PLANT LIST. | | | | | | 2. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE | | | TREES IN GOOD CONDITION TO BE PRESERVED ON SITE OR | | | RELOCATED. ANSI A 300 (PART 5) STANDARDS SPECIFY | | | EXAMPLES OF SUITABILITY RATINGS OF GOOD, MODERATE, OR | | | POOR FOR RELOCATION. PROVIDE AN ARBORIST REPORT SHOWING | | | CONDITION FOR ALL TREES AND RELOCATION POTENTIAL FOR | | | THE NATIVE TREES AND PALMS PROPOSED TO BE REMOVED. | | | | | | 3. SATISFIED. PROVIDE THE CALCULATIONS FOR THE MINIMUM | | | REQUIRED SHADE TREES, FLOWERING TREES AND SHRUBS FOR | | | THE SITE BASED ON 40% OPEN SPACE PER SECTION | | | 94-442(C)(2)B. PROVIDE THE CALCULATIONS FOR THE OPEN | | | SPACE BASED ON THE SITE SQUARE FOOTAGE. ADD THE | | | MULTIFAMILY TREE REQUIREMENT TO THIS TOTAL. | | | | | | 4. SATISFIED. PROVIDE THE NUMBER AND PERCENTAGE OF | | | SUBSTITUTION OF PALMS FOR REQUIRED TREES. SECTION | | | 94-442(D) REQUIRES A 3:1 RATIO FOR SUBSTITUTION FOR | | | PALMS EXCEPT THE LISTED 1:1 SPECIES. | | | | | | | | | 5. SATISFIED. PER SECTION 94-443(A)(2) LABEL THE | | | REQUIRED 5 FOOT LANDSCAPE BUFFER ALONG EACH PROPERTY | | | LINE AND CALCULATE THE NUMBER OF TREES REQUIRED AND | | | PROVIDED FOR EACH BUFFER SEGMENT. THE TOTAL LENGTH OF | | | THE PROPERTY LINE PER THE SURVEY MUST BE USED. | | | | | | 6. PARTIALLY SATISFIED. PER SECTION 94-443 (E)2., | | | PROVIDE THE 30% FOUNDATION PLANTING CALCULATION | | | REQUIRED AND PROVIDED FOR EACH BUILDING. | | | THE PLAN MUST SHOW THE LINEAR FOOTAGE OF EACH BUILDING | | | PERIMETER, REQUIRED LINEAR FOOTAGE AND PROVIDED. | | | THE REQUIREMENT IS 40% PER SECTION 94-443(D)2.A. | | | | | | 7. SATISFIED. PER SECTION 94-443(C)(3)A. AND B., | | | TERMINAL LANDSCAPE ISLANDS AND INTERIOR ISLANDS MUST | | | HAVE AT LEAST 8 FEET WIDE LANDSCAPE AREA AND RUN THE | | | FULL LENGTH OF THE ADJACENT PARKING SPACE. EACH AREA | | | SHALL HAVE AT LEAST ONE SHADE OR FLOWERING TREE PER ROW | | | OF PARKING. LANDSCAPE BUFFER OF 5 FEET MAY BE COUNTED | | | AS PART OF THE TERMINAL ISLAND. SHOW DIMENSIONS ON THE | | | LANDSCAPE PLAN. | | | | | | 8. SATISFIED. A MINIMUM OF 75% OF ALL TREES REQUIRED TO | | | BE PLANTED WITHIN THE PARKING AREA MUST BE CATEGORY 1 | | | SHADE TREES. SHOW THE PERCENTAGE PROVIDED. | | | 9. SATISFIED. PER SECTION 94-442(G) PROVIDE THE | | | REQUIRED 50 POINTS FROM THE FLORIDA FRIENDLY DESIGN | | | OPTIONS LIST AND SHOW THE TOTAL PROVIDED. | | | 10. SATISFIED. PROVIDE A SECTION IN A LANDSCAPE DATA | | | CHART TO COMPLY WITH SECTION 94-445 L. PLANT SPECIES. A | | | MINIMUM OF 60 PERCENT OF PLANT MATERIAL ADDED SHALL BE | | | FLORIDA NATIVE OR DROUGHT TOLERANT SPECIES SELECTED | | | FROM THE CITY LIST OR THE LIST OF SPECIES IN THE MOST | | | RECENT EDITION OF SOUTH FLORIDA WATER MANAGEMENT | | | DISTRICT WATERWISE SOUTH FLORIDA LANDSCAPES. PROVIDE | | | THE TOTAL PERCENTAGE OF NATIVE AND DROUGHT TOLERANT | | | PLANTS BASED ON FINAL PLANT LIST. | | | | | | 11. NOT SATISFIED. LOCATIONS OF PROPOSED UTILITY LINES | | | INCLUDING WATER, SEWER AND DRAINAGE CONFLICT WITH | | | REQUIRED LANDSCAPING. CIVIL ENGINEERING PLAN, SITE PLAN | | | AND LANDSCAPE PLAN MUST BE CONSISTENT. | | | | | | UTILITIES MUST BE SHOWN ON THE LANDSCAPE PLAN AND | | | CONFLICTS RESOLVED. UTILITY POSITIONS WILL REQUIRE | | | ADJUSTMENT OF PLANTING LOCATIONS OF SOME REQUIRED | | | TREES. | | | | | | 12. SATISFIED. SHOW AND LABEL ALL OVERHEAD POWER LINES | | | THAT WILL LIMIT THE TREE SPECIES TO RIGHT TREE RIGHT | | | PLACE GUIDELINES. | | | | | | 13. SATISFIED. PER SECTION 94-443 (A)(1) A PROTECTIVE | | | SCREEN WALL IS REQUIRED ALONG THE ADJACENT RESIDENTIAL | | | PROPERTY LINES. | | | | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE | | | STREET TREES AND RIGHT OF WAY LANDSCAPING AND | | | IRRIGATION APPROVED WITH THIS PETITION. | | | 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF | | | WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A | | | SEPARATE MAINTENANCE AGREEMENT WITH THE CITY. | | | | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
01-12-2022 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
01-12-2022 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
01-12-2022 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2022-01-12 13:38:28 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: 1004 19TH ST. Z21120020 | | | JANUARY 12, 2022 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. PROVIDE A SEPARATE TREE DISPOSITION PLAN SHOWING THE | | | LOCATIONS OF THE EXISTING TREES AND INCLUDE THE | | | FOLLOWING INFORMATION: | | | ? ADD A COLUMN TO THE CHART FOR MITIGATION SQUARE | | | FOOTAGE DUE AND SHOW THE AMOUNT FOR EACH TREE PROPOSED | | | TO BE REMOVED BASED ON THE CATEGORY OR TREE CANOPY | | | DIAMETER. COLUMN SHOULD BE LABELED MITIGATION DUE. | | | TREES WITH A CANOPY 20 FEET OR MORE IN DIAMETER MUST | | | HAVE THE ACTUAL SQUARE FOOTAGE CALCULATED AND ENTERED | | | ON THE CHART. | | | ? PROVIDE TOTAL OF MITIGATION SQUARE FOOTAGE DUE. | | | ? PROVIDE A TOTAL OF MITIGATION SQUARE FOOTAGE PROVIDED | | | BASED ON THE PLANT LIST. | | | | | | 2. SECTION 94-448 (D)(3) REQUIRES NATIVE TREES IN GOOD | | | CONDITION TO BE PRESERVED ON SITE OR RELOCATED. ANSI A | | | 300 (PART 5) STANDARDS SPECIFY EXAMPLES OF SUITABILITY | | | RATINGS OF GOOD, MODERATE, OR POOR FOR RELOCATION. | | | PROVIDE AN ARBORIST REPORT SHOWING CONDITION FOR ALL | | | TREES AND RELOCATION POTENTIAL FOR THE NATIVE TREES AND | | | PALMS PROPOSED TO BE REMOVED. | | | | | | 3. PROVIDE THE CALCULATIONS FOR THE MINIMUM REQUIRED | | | SHADE TREES, FLOWERING TREES AND SHRUBS FOR THE SITE | | | BASED ON 40% OPEN SPACE PER SECTION 94-442(C)(2)B. | | | PROVIDE THE CALCULATIONS FOR THE OPEN SPACE BASED ON | | | THE SITE SQUARE FOOTAGE. ADD THE MULTIFAMILY TREE | | | REQUIREMENT TO THIS TOTAL. | | | | | | 4. PROVIDE THE NUMBER AND PERCENTAGE OF SUBSTITUTION OF | | | PALMS FOR REQUIRED TREES. SECTION 94-442(D) REQUIRES A | | | 3:1 RATIO FOR SUBSTITUTION FOR PALMS EXCEPT THE LISTED | | | 1:1 SPECIES. | | | | | | | | | 5. PER SECTION 94-443(A)(2) LABEL THE REQUIRED 5 FOOT | | | LANDSCAPE BUFFER ALONG EACH PROPERTY LINE AND CALCULATE | | | THE NUMBER OF TREES REQUIRED AND PROVIDED FOR EACH | | | BUFFER SEGMENT. THE TOTAL LENGTH OF THE PROPERTY LINE | | | PER THE SURVEY MUST BE USED. | | | | | | 6. PER SECTION 94-443 (E)2., PROVIDE THE 30% FOUNDATION | | | PLANTING CALCULATION REQUIRED AND PROVIDED FOR EACH | | | BUILDING. | | | | | | 7. PER SECTION 94-443(C)(3)A. AND B., TERMINAL | | | LANDSCAPE ISLANDS AND INTERIOR ISLANDS MUST HAVE AT | | | LEAST 8 FEET WIDE LANDSCAPE AREA AND RUN THE FULL | | | LENGTH OF THE ADJACENT PARKING SPACE. EACH AREA SHALL | | | HAVE AT LEAST ONE SHADE OR FLOWERING TREE PER ROW OF | | | PARKING. LANDSCAPE BUFFER OF 5 FEET MAY BE COUNTED AS | | | PART OF THE TERMINAL ISLAND. SHOW DIMENSIONS ON THE | | | LANDSCAPE PLAN. | | | | | | 8. A MINIMUM OF 75% OF ALL TREES REQUIRED TO BE PLANTED | | | WITHIN THE PARKING AREA MUST BE CATEGORY 1 SHADE TREES. | | | SHOW THE PERCENTAGE PROVIDED. | | | 9. PER SECTION 94-442(G) PROVIDE THE REQUIRED 50 POINTS | | | FROM THE FLORIDA FRIENDLY DESIGN OPTIONS LIST AND SHOW | | | THE TOTAL PROVIDED. | | | 10. PROVIDE A SECTION IN A LANDSCAPE DATA CHART TO | | | COMPLY WITH SECTION 94-445 L. PLANT SPECIES. A MINIMUM | | | OF 60 PERCENT OF PLANT MATERIAL ADDED SHALL BE FLORIDA | | | NATIVE OR DROUGHT TOLERANT SPECIES SELECTED FROM THE | | | CITY LIST OR THE LIST OF SPECIES IN THE MOST RECENT | | | EDITION OF SOUTH FLORIDA WATER MANAGEMENT DISTRICT | | | WATERWISE SOUTH FLORIDA LANDSCAPES. PROVIDE THE TOTAL | | | PERCENTAGE OF NATIVE AND DROUGHT TOLERANT PLANTS BASED | | | ON FINAL PLANT LIST. | | | | | | 11. LOCATIONS OF PROPOSED UTILITY LINES INCLUDING | | | WATER, SEWER AND DRAINAGE CONFLICT WITH REQUIRED | | | LANDSCAPING. CIVIL ENGINEERING PLAN, SITE PLAN AND | | | LANDSCAPE PLAN MUST BE CONSISTENT. | | | | | | 12. SHOW AND LABEL ALL OVERHEAD POWER LINES THAT WILL | | | LIMIT THE TREE SPECIES TO RIGHT TREE RIGHT PLACE | | | GUIDELINES. | | | | | | 13. PER SECTION 94-443 (A)(1) A PROTECTIVE SCREEN WALL | | | IS REQUIRED ALONG THE ADJACENT RESIDENTIAL PROPERTY | | | LINES. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE | | | STREET TREES AND RIGHT OF WAY LANDSCAPING AND | | | IRRIGATION APPROVED WITH THIS PETITION. | | | 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF | | | WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A | | | SEPARATE MAINTENANCE AGREEMENT WITH THE CITY. | | | |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
mtechnow |
Date |
01-05-2022 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2022-01-05 16:56:55 | -PROVIDE LEVEL OF SERVICE CALCULATIONS. | | | - SHOW EXISTING UTILITIES ON TAMARIND. | | | - REPLACE/LINE EXISTING LATERALS AS REQUIRED. PROVIDE | | | POST CCTV FOOTAGE. | | | -ADD NOTE TO CUT AND CAP EXISTING DOUBLE WATER METER AT | | | MAIN. | | | -CONFIRM THAT THE EXISTING 6? LATERAL IS SUFFICIENT FOR | | | PROPOSED FLOW. REFERENCE DOUBLE SERVICE DETAIL. | | | -TELEVISE AND CONFIRM CONDITION OF EXISTING LATERALS | | | AND VERIFY THAT IT IS ADEQUATE. | | | -SHOW PROFILE OF 4? CONNECTION FROM TAP TO POINT OF | | | SERVICE. | | | -SHOW EXISTING VALVES. | | | -CUSTOMER SERVICE TO COMMENT ON MASTER METER VS | | | INDIVIDUAL METER. | | | -TELEVISE EXISTING UTILITY FRONTING PROPERTY FROM | | | MANHOLE TO MANHOLE. | | | -SHOW PROPERTY LINE ON 19TH ST. | | | -PLEASE UPSIZE THE 6? WM TO 8? WITHIN PROJECT LIMITS. | | | -MISSING LEVEL OF SERVICE CALC SHEET. | | | - FOR STORMWATER STRUCTURES CALL OUT STATIONING AND | | | HORIZONTAL SEPARATION BETWEEN UTILITIES | | | | | | CONTACT MIKE TECHNOW 561-494-1047 WITH ANY QUESTIONS. |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
3 |
Status |
P |
Date |
11-14-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
11-14-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
11-14-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-11-14 09:40:16 | NO FURTHER COMMENTS. | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
2 |
Status |
F |
Date |
03-29-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
03-29-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
03-29-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-03-29 11:16:57 | PLEASE PROVIDE REVISED SHEET SP-2 TO REFLECT ALL THE | | | REQUIREMENTS FOR THE DUMPSTER ENCOSURE PER THE LATEST | | | REVISION OF GC-7. FOR A FREESTANDING SITE DUMPSTER | | | ENCLOSURE, THE ENCLOSURE SHALL COMPLY WITH THE LATEST | | | REVISION OF CITY OF WEST PALM BEACH GENERAL | | | CONSTRUCTION-GARBAGE ENCLOSURE STANDARD, GC-7. (LINK TO | | | THE LATEST REVISION OF THE GC-7 DOCUMENT: HTTPS://WWW.W | | | PB.ORG/HOME/SHOWPUBLISHEDDOCUMENT/3690/6376290604221000 | | | 00). | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] | | | 561-822-2045 |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
F |
Date |
01-13-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
01-13-2022 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
01-13-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-01-13 09:53:06 | PLEASE PROVIDE THE FOLLOWINGS: | | | 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID | | | WASTE VOLUME PRODUCED ALONG WITH THE SIZE AND TYPE OF | | | THE CONTAINER (I.E. DUMPSTER/COMPACTOR) THAT WILL BE | | | UTILIZED THAT WILL BE UTILIZED FOR THE SANITATION | | | SERVICE. | | | 2- REVISED LOCATION/ORIENTATION OF THE DUMPSTER | | | ENCLOSURE TO MINIMIZE BACKUPS AND SHORT RADUIS TURNS. | | | 3- AUTOTURN EXHIBIT (DYNAMIC ENVELOPE AND THE VEHICLE'S | | | WHEEL PATH) FOR THE SANITATION SERVICE, FRONT LOADER | | | TRUCK WITH THE FOLLOWING SPECS: | | | * TRUCK LENGTH: 35 FT | | | * TRUCK WITH: 11 FT | | | * TURNING RADIUS: | | | - SAE TURNING RADIUS: 32.5 FT | | | - CURB-TO-CURB DIAMETER: 74 FT | | | - WALL-TO-WALL DIAMETER: 86.3 FT | | | 4- DESIGNATED LOCATION FOR THE BULK ITEM PICK UP AND | | | RECYCLING CONTAINERS. | | | 5- REVIESD ENCLOSURE DETAILS, SHEET SP-2, TO COMPLY | | | WITH THE CG-7. FOR A FREESTANDING SITE DUMPSTER | | | ENCLOSURE, THE ENCLOSURE SHALL COMPLY WITH THE LATEST | | | REVISION OF CITY OF WEST PALM BEACH GENERAL | | | CONSTRUCTION-GARBAGE ENCLOSURE STANDARD, CG-7. | | | | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] | | | 561-822-2045 |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
4 |
Status |
P |
Date |
12-13-2022 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
12-13-2022 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
12-13-2022 |
Time |
09:38 |
Sent To |
|
|
| Notes |
| 2022-12-13 09:37:27 | CONDITIONS FOR SITE PLAN APPROVAL: | | | 1. PROVIDE A REFERENCE ELEVATION TO NGVD1929 ON THE | | | SURVEY. | | | 2. CONFIRM RUNOFF FROM THE SIDEWALK ALONG THE WEST SIDE | | | OF THE BUILDING WILL FLOW TO AN ONSITE DRAINAGE | | | STRUCTURE. | | | 3. IN ORDER TO PROPERLY MAINTAIN THE SWALE ALONG THE | | | SOUTH PROPERTY LINE, THE SIDES SHOULD BE SLOPED 4:1 OR | | | FLATTER. | | | 4. IDENTIFY THE MATERIAL TO BE USED TO CONSTRUCT THE | | | PATH FROM THE BUILDING TO THE TOT LOT. | | | 5. DRIVEWAY APRON WITHIN THE R/W TO BE COMPOSED OF | | | CONCRETE. | | | 6. REMOVE THE CALLOUT OR DEFINE THE LIMITS OF THE | | | COLORED STAMPED ASPHALT AS CALLED OUT ON SHEET C2.1. | | | | | | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE | | | 11/4/2022 SUBMITTAL. PREVIOUSLY SATISFIED COMMENTS ARE | | | NOT LISTED. | | | | | | 7. [PARTIALLY SATISFIED - SEE MORE COMMENTS UNDER NEW | | | COMMENTS BELOW.] PROVIDE CROSS SECTIONS FROM: | | | A. FACE OF BUILDING TO TAMARIND AVE CENTERLINE | | | B. FACE OF BUILDING TO GRANT ST CENTERLINE | | | C. AT PROPOSED DRIVEWAY | | | D. FROM WEST PROPERTY LINE TO FACE OF BUILDING | | | E. FROM SOUTH PROPERTY LINE TO PARKING LOT | | | F. FROM SOUTH PROPERTY LINE TO FACE OF BUILDING | | | LABEL STREETS, PROPERTY LINES, SURFACE FEATURES AND | | | GENERAL SURFACE SLOPES. PROVIDE DIMENSIONS FOR | | | CURBS/CURB AND GUTTER, SIDEWALKS AND DISTANCE FROM | | | PROPERTY LINE TO FACE OF BUILDING. INCLUDE PROPOSED | | | PARALLEL PARKING AREAS. | | | | | | 10. [SATISFIED ??? NOTE 13 ON SHEET C2.1 STATES ALL | | | SIDEWALKS ADJACENT TO THE PROPERTY ARE TO BE REPLACED.] | | | PROVIDE HATCHING PATTERNS FOR SIDEWALKS TO REMAIN AND | | | FOR NEW/REPLACEMENT SIDEWALKS. ADDITIONAL COMMENT - | | | SHOW CONCRETE FOR THE PROPOSED DRIVEWAY APRON WITHIN | | | THE R/W. SIDEWALKS AT EXISTING DRIVEWAY APRONS TO BE | | | REPLACED IF CROSS SLOPE EXCEEDS 2%. | | | | | | 15. [NOT SATISFIED] THE CITY'S OFFICIAL VERTICAL DATUM | | | IS NGVD1929. THE CITY HAS ALLOWED THE USE OF NAVD1988 | | | AS LONG AS THE CONVERSION EQUATION TO NGVD1929 AT THE | | | PROJECT LOCATION IS PROVIDED. PROVIDE THE NAVD1988 TO | | | NGVD1929 CONVERSION EQUATION ON THE SURVEY. | | | | | | | | | NEW COMMENTS (3/19/22 SUBMITTAL): | | | | | | 19. [NOT SATISFIED - PROVIDE ON ENGINEERING PERMIT | | | SUBMITTAL.] REVISE FDOT INDEX NUMBERS TO CURRENT FDOT | | | STANDARD PLAN NUMBERS ON THE SITE PLAN SHEETS AND | | | ENGINEERING SHEETS. | | | | | | | | | 25. SHEET C2.3 GEOMETRIC, SIGNING AND STRIPING PLAN: | | | A. [SATISFIED - STRIPING NEEDED AROUND THE MEDIAN | | | ISLAND] PROVIDE STRIPING PLAN FOR MILL AND RESURFACE | | | AREAS. | | | | | | 26. [PARTIALLY SATISFIED ? COMMENTS BELOW ARE FOR THE | | | REVISED SECTION A ON SHEET C3.2 IN 7/19 SUBMITTAL] | | | SECTION A (SHEET C3.2) | | | A. [SATISFIED] SIDEWALK ALONG TAMARIND AVE APPEARS TO | | | SHOW THICKENED EDGE AT BACK OF SIDEWALK. | | | B. [SATISFIED] ADJUST HATCH PATTERN TO THE SPOT GRADE | | | FOR THE EXISTING PROPERTY WEST OF THE WEST PROPERTY | | | LINE. | | | C. [SATISFIED] SPOT GRADE OF PARKING LOT DRIVE | | | CENTERLINE LOWER THAN THE GRATE ELEVATIONS OF THE CATCH | | | BASIN INLETS. | | | D. [NOT SATISFIED] TOP OF CURB ELEVATION ALONG EAST | | | SIDE OF THE PARKING LOT IS HIGHER THAN THE SIDEWALK | | | ELEVATION ALONG THE WEST SIDE OF THE BUILDING. | | | | | | | | | 27. {PARTIALLY SATISFIED ? COMMENTS BELOW ARE FOR THE | | | REVISED SECTION B ON SHEET C3.2 IN 7/19/SUBMITTAL} | | | SECTION B (SHEET C3.2) | | | A. [PARTIALLY SATISFIED ??? GRADING PLAN SHOWS NORTH | | | SWALE BANK DESIGNED TO HAVE 2:1 (STEEP) SLOPE] PROVIDE | | | SWALE ALONG THE SOUTH PROPERTY LINE TO KEEP RUNOFF FROM | | | FLOWING ONTO ADJACENT PROPERTY. | | | B. [SATISFIED] SIDEWALK ON 19TH STREET APPEARS TO HAVE | | | CURB ALONG THE FRONT OF THE SIDEWALK AND THICKENED EDGE | | | ALONG THE BACK OF SIDEWALK. CALL THESE OUT ON THE | | | SECTION AND PROVIDE DETAIL FOR THICKENED EDGE SIDEWALK. | | | | | | 31. SHEET C4.1 EROSION CONTROL PLAN (CAN BE ADDRESSED | | | WITH ENGINEERING PERMIT SUBMITTAL): | | | C. [SATISFIED] MOVE HATCHING FOR CONSTRUCTION ACCESS | | | OUT OF THE R/W. | | | | | | NEW COMMENTS ON 7-19-2022 SUBMITTAL: | | | 32. [SATISFIED] SHEET C2.1 SHOWS FLOW ARROW TOWARD | | | ADJACENT PROPERTY. SURFACE RUNOFF MAY NOT FLOW ONTO | | | ADJACENT PROPERTY. | | | | | | 33. [NOT SATISFIED] SHOW CONCRETE FOR DRIVEWAY WITHIN | | | THE RIGHT OF WAY. | | | | | | 34. [SATISFIED] RIM ELEVATION FOR STRUCTURE S-102 | | | SHOULD BE LOWER THAN THE BACK OF SIDEWALK ELEVATION OF | | | 19TH STREET. RIM ELEVATION CALLED OUT AS 21.4 FT NAVD | | | BUT PROPOSED SPOT GRADE IS 19.5 FT NAVD AT STRUCTURE. | | | | | | 35. [SATISFIED] PROVIDE SPOT GRADES FOR BBQ AND TOT LOT | | | AREAS. THE EXISTING GRADES ALONG THE PROPERTY LINE ARE | | | 3 FEET +/- LOWER THAN THE PROPOSED TOP OF CURB | | | ELEVATION FOR THE PARKING LOT. | | | | | | 36. [SATISFIED] CHECK THE SLOPE OF THE SIDEWALK FROM | | | THE HANDICAP ACCESS AISLE TO THE COVER WALKWAY ALONG | | | THE WEST SIDE OF THE BUILDING. THE SLOPE APPEARS TO | | | EXCEED 5%. | | | | | | 37. [NOT SATISFIED] LABEL (INCLUDING SURFACE TREATMENT) | | | THE PATH FROM THE COVERED WALKWAY TO THE TOT LOT. | | | | | | 38. [ NOT APPLICABLE ??? MIDBLOCK CROSS WALK REMOVED | | | FROM THE PLANS] CALLOUT THE FDOT CURB RAMP NUMBER FOR | | | THE MIDBLOCK CROSSWALK. | | | | | | 39. [NOT SATISFIED] BICYCLE STRIPING TO BE PER CWPB | | | STANDARD DETAILS AND THE MUTCD. SHOW THE APPROPRIATE | | | LOCATIONS OF THESE MARKINGS ON SHEET C2.3. | | | | | | 40. [NOT APPLICABLE ??? CROSS WALK REMOVED FROM THE | | | PLANS.]SHOW STRIPING AND SIGNAGE FOR MIDBLOCK | | | CROSSWALK. | | | NEW COMMENT (11-4-2022) | | | 41. SHEET C2.1 CALLS OUT COLORED STAMPED ASPHALT FOR | | | THE ON-STREET PARKING ON TAMARIND AVE. SHOW THE EXTENT | | | OF THE STAMPED ASPHALT. DEVELOPER MAY BE RESPONSIBLE TO | | | MAINTAIN THE STAMPED ASPHALT. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | [email protected] | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
3 |
Status |
F |
Date |
08-01-2022 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
08-01-2022 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
08-01-2022 |
Time |
15:21 |
Sent To |
|
|
| Notes |
| 2022-08-01 15:20:44 | Z21120020 SITE D 1004 19TH ST. | | | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE | | | 7/19/2022 SUBMITTAL. | | | | | | 1. [SATISFIED] REMOVE REFERENCES TO VOW (VILLAGE OF | | | WELLINGTON) ON COVER. | | | | | | 2. [SATISFIED ? AS BEST AS THEY CAN DO.] PROJECT SITE | | | ON PROJECT LOCATION MAP IS SHOWN ON THE EAST SIDE OF | | | TAMARIND AVE. THE SITE IS ON THE WEST SIDE OF TAMARIND | | | AVE. | | | | | | 3. [SATISFIED] CONCEPTUAL ENGINEERING PLAN IS CONFUSING | | | WITH EXISTING FEATURES SHOWN AND NOT SCREENED. | | | | | | 4. [SATISFIED] LABEL WHERE THE EXISTING POWER POLE WILL | | | BE RELOCATED WHEN THE DRIVEWAY APRON IS CONSTRUCTED. | | | | | | 5. [SATISFIED] REMOVE EXISTING DRIVEWAY APRONS AND | | | INSTALL CURB OR CURB AND GUTTER. ADDITONAL COMMENT ? | | | SPECIFY CURB TYPE FOR ENGINEERING PERMIT SUBMITTAL. | | | | | | 6. [SATISFIED] CIVIL SITE PLAN DOES NOT MATCH THE | | | ARCHITECTURAL SITE PLAN. | | | | | | 7. [PARTIALLY SATISFIED - SEE MORE COMMENTS UNDER NEW | | | COMMENTS BELOW.] PROVIDE CROSS SECTIONS FROM: | | | A. FACE OF BUILDING TO TAMARIND AVE CENTERLINE | | | B. FACE OF BUILDING TO GRANT ST CENTERLINE | | | C. AT PROPOSED DRIVEWAY | | | D. FROM WEST PROPERTY LINE TO FACE OF BUILDING | | | E. FROM SOUTH PROPERTY LINE TO PARKING LOT | | | F. FROM SOUTH PROPERTY LINE TO FACE OF BUILDING | | | LABEL STREETS, PROPERTY LINES, SURFACE FEATURES AND | | | GENERAL SURFACE SLOPES. PROVIDE DIMENSIONS FOR | | | CURBS/CURB AND GUTTER, SIDEWALKS AND DISTANCE FROM | | | PROPERTY LINE TO FACE OF BUILDING. INCLUDE PROPOSED | | | PARALLEL PARKING AREAS. | | | | | | 8. [SATISFIED] SHOW MILL AND RESURFACING LIMITS WITHIN | | | THE STREETS. ADDITIONAL COMMENT - MILL AND RESURFACE | | | LIMITS TO EXTEND FOR FULL TRAVEL LANE WIDTH. | | | | | | 9. [SATISFIED] IDENTIFY ON THE CONCEPTUAL ENGINEERING | | | PLAN WHERE THE SPECIAL TYPE 'F' CURB AND GUTTER WILL BE | | | CONSTRUCTED. REDRAW THE DETAIL IN ACAD AND PROVIDE | | | ENGLISH UNITS. ADDITIONAL COMMENT - SHOW ON THE PGD | | | PLAN WHERE THE CURB WILL BE CONSTRUCTED. | | | | | | 10. [NOT SATISFIED ? SHOW LIMITS OF SIDEWALK REMOVAL ON | | | ENGINEERING PERMIT SUBMITTAL.] PROVIDE HATCHING | | | PATTERNS FOR SIDEWALKS TO REMAIN AND FOR | | | NEW/REPLACEMENT SIDEWALKS. ADDITIONAL COMMENT - SHOW | | | CONCRETE FOR THE PROPOSED DRIVEWAY APRON WITHIN THE | | | R/W. SIDEWALKS AT EXISTING DRIVEWAY APRONS TO BE | | | REPLACED IF CROSS SLOPE EXCEEDS 2%. | | | | | | 11. [SATISFIED] PER FIGURE XV-2: GENERAL PARKING | | | DIMENSIONS IN SECTION 94-485 OF THE CITY'S CODE OF | | | ORDINANCES, THE CURB LENGTH OF PARALLEL PARKING SPACES | | | IS 22 FEET. THE SITE PLAN SHOWS 25 FEET AND GAPS IN THE | | | PARKING SPACES ON TAMARIND AVE. | | | | | | 12. [SATISFIED] CONSIDER ANGLING THE CURBING AT EACH | | | END OF PROPOSED PARALLEL PARKING SPACES TO FACILITATE | | | ACCESS TO AND FROM THE END SPACES. | | | | | | 15. [NOT SATISFIED] THE CITY'S OFFICIAL VERTICAL DATUM | | | IS NGVD1929. THE CITY HAS ALLOWED THE USE OF NAVD1988 | | | AS LONG AS THE CONVERSION EQUATION TO NGVD1929 AT THE | | | PROJECT LOCATION IS PROVIDED. PROVIDE THE NAVD1988 TO | | | NGVD1929 CONVERSION EQUATION ON THE SURVEY. | | | | | | 16. [SATISFIED] LABEL ANY NEW CURBS/CURB AND GUTTER | | | WITHIN THE RIGHT OF WAYS. ADDITIONAL COMMENT - SEE | | | COMMENT 5 ABOVE. | | | | | | 17. [SATISFIED] CONSIDER LOW IMPACT DEVELOPMENT | | | DRAINAGE SYSTEMS IN LIEU OF EXFILTRATION TRENCHES. | | | | | | 18. [SATISFIED] SHOW UTILITIES ON THE LANDSCAPE PLANS. | | | | | | | | | NEW COMMENTS (3/19/22 SUBMITTAL): | | | | | | 19. [NOT SATISFIED ? PROVIDE ON ENGINEERING PERMIT | | | SUBMITTAL.] REVISE FDOT INDEX NUMBERS TO CURRENT FDOT | | | STANDARD PLAN NUMBERS ON THE SITE PLAN SHEETS AND | | | ENGINEERING SHEETS. | | | | | | 20. [SATISFIED] SHEET SP-1 CALLS OUT A DETAIL NO. 4 ON | | | SHEET SP-3. SHEET SP-3 DOES NOT HAVE A DETAIL NO. 4. | | | | | | 21. [SATISFIED] LABEL 19TH STREET ON THE ENGINEERING | | | PLANS. | | | | | | 22. [SATISFIED] PRB WALLS MISLABELED FOR STRUCTURES | | | S-101 AND S-102. | | | | | | 23. {SATISFIED] CALLOUT COLORED STAMP ASPHALT FOR THE | | | CROSSWALK ACROSS 19TH STREET. | | | | | | 24. [SATISFIED] SUGGEST ADDING SPOT GRADES FOR HANDICAP | | | PARKING SPACE. MAXIMUM SLOPE IN ANY DIRECTION FOR | | | HANDICAP SPACE IS 2%. | | | | | | 25. SHEET C2.3 GEOMETRIC, SIGNING AND STRIPING PLAN: | | | A. [PARTIALLY SATISFIED ? STRIPING NEEDED AROUND THE | | | MEDIAN ISLAND] PROVIDE STRIPING PLAN FOR MILL AND | | | RESURFACE AREAS. | | | B. [SATISFIED] ADD RIGHT TURN ONLY SIGN TO STOP SIGN IN | | | PARKING LOT. | | | C. [SATISFIED] STOP BAR MEASURES 12 FEET LONG ON THE 20 | | | FT WIDE DRIVEWAY. STOP BAR SHOULD EXTEND TO CURB. | | | CONFIRM STOP BAR IS SUFFICIENT DISTANCE FROM SIDEWALK. | | | D. [SATISFIED] REMOVE THE OUTLINE SYMBOLS FOR STOP BAR, | | | LANE DIVIDER, DIRECTIONAL ARROWS IN THE PARKING LOT IF | | | THEY ARE NOT NEEDED. OTHERWISE, PROVIDE CALLOUTS FOR | | | THESE ITEMS. | | | E. [SATISFIED] PROVIDE SIGN AND STRIPING FOR TURNAROUND | | | SPACE IN THE PARKING LOT. | | | F. [SATISFIED] SHOW EXISTING STOP SIGN FOR 19TH STREET. | | | | | | 26. [PARTIALLY SATISFIED ? COMMENTS BELOW ARE FOR THE | | | REVISED SECTION A ON SHEET C3.2 IN 7/19 SUBMITTAL] | | | SECTION A (SHEET C3.2) | | | A. SIDEWALK ALONG TAMARIND AVE APPEARS TO SHOW | | | THICKENED EDGE AT BACK OF SIDEWALK. | | | B. ADJUST HATCH PATTERN TO THE SPOT GRADE FOR THE | | | EXISTING PROPERTY WEST OF THE WEST PROPERTY LINE. | | | C. SPOT GRADE OF PARKING LOT DRIVE CENTERLINE LOWER | | | THAN THE GRATE ELEVATIONS OF THE CATCH BASIN INLETS. | | | D. TOP OF CURB ELEVATION ALONG EAST SIDE OF THE PARKING | | | LOT IS HIGHER THAN THE SIDEWALK ELEVATION ALONG THE | | | WEST SIDE OF THE BUILDING. | | | | | | | | | 27. {PARTIALLY SATISFIED ? COMMENTS BELOW ARE FOR THE | | | REVISED SECTION B ON SHEET C3.2 IN 7/19/SUBMITTAL} | | | SECTION B (SHEET C3.2) | | | A. PROVIDE SWALE ALONG THE SOUTH PROPERTY LINE TO KEEP | | | RUNOFF FROM FLOWING ONTO ADJACENT PROPERTY. | | | B. SIDEWALK ON 19TH STREET APPEARS TO HAVE CURB ALONG | | | THE FRONT OF THE SIDEWALK AND THICKENED EDGE ALONG THE | | | BACK OF SIDEWALK. CALL THESE OUT ON THE SECTION AND | | | PROVIDE DETAIL FOR THICKENED EDGE SIDEWALK. | | | C. PROVIDE SWALE ALONG SOUTH PROPERTY LINE TO PREVENT | | | RUNOFF FROM FLOWING ONTO ADJACENT PROPERTY. | | | | | | 31. SHEET C4.1 EROSION CONTROL PLAN (CAN BE ADDRESSED | | | WITH ENGINEERING PERMIT SUBMITTAL): | | | A. [SATISFIED] PROVIDE ALTERNATIVE TO HAY BALES FOR | | | INLET PROTECTION. | | | B. [SATISFIED] IDENTIFY WHICH INLETS ARE TO BE | | | PROTECTED (ONSITE AND WITHIN R/W) | | | C. [NOT SATISFIED] MOVE HATCHING FOR CONSTRUCTION OUT | | | OF THE R/W. | | | D. [SATISFIED] DO NOT SHOW SIGNING AND STRIPING | | | CALLOUTS. | | | | | | NEW COMMENTS ON 7-19-2022 SUBMITTAL: | | | 32. SHEET C2.1 SHOWS FLOW ARROW TOWARD ADJACENT | | | PROPERTY. SURFACE RUNOFF MAY NOT FLOW ONTO ADJACENT | | | PROPERTY. | | | | | | 33. SHOW CONCRETE FOR DRIVEWAY WITHIN THE RIGHT OF WAY. | | | | | | 34. RIM ELEVATION FOR STRUCTURE S-102 SHOULD BE LOWER | | | THAN THE BACK OF SIDEWALK ELEVATION OF 19TH STREET. RIM | | | ELEVATION CALLED OUT AS 21.4 FT NAVD BUT PROPOSED SPOT | | | GRADE IS 19.5 FT NAVD AT STRUCTURE. | | | | | | 35. PROVIDE SPOT GRADES FOR BBQ AND TOT LOT AREAS. THE | | | EXISTING GRADES ALONG THE PROPERTY LINE ARE 3 FEET +/- | | | LOWER THAN THE PROPOSED TOP OF CURB ELEVATION FOR THE | | | PARKING LOT. | | | | | | 36. CHECK THE SLOPE OF THE SIDEWALK FROM THE HANDICAP | | | ACCESS AISLE TO THE COVER WALKWAY ALONG THE WEST SIDE | | | OF THE BUILDING. THE SLOPE APPEARS TO EXCEED 5%. | | | | | | 37. LABEL (INCLUDING SURFACE TREATMENT) THE PATH FROM | | | THE COVERED WALKWAY TO THE TOT LOT. | | | | | | 38. CALLOUT THE FDOT CURB RAMP NUMBER FOR THE MIDBLOCK | | | CROSSWALK. | | | | | | 39. BICYCLE STRIPING TO BE PER CWPB STANDARD DETAILS | | | AND THE MUTCD. SHOW THE APPROPRIATE LOCATIONS OF THESE | | | MARKINGS ON SHEET C2.3. | | | | | | 40. SHOW STRIPING AND SIGNAGE FOR MIDBLOCK CROSSWALK. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | [email protected] | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
F |
Date |
04-26-2022 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
04-26-2022 |
Time |
18:27 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
04-26-2022 |
Time |
18:32 |
Sent To |
|
|
| Notes |
| 2022-04-26 18:29:23 | THE FOLLOWING COMMENTS ARE FROM THE REVISW OF THE | | | 3/24/2022 SUBMITTAL. | | | | | | 1. [SATISFIED] REMOVE REFERENCES TO VOW (VILLAGE OF | | | WELLINGTON?) ON COVER. | | | | | | 2. [NOT SATISFIED] PROJECT SITE ON PROJECT LOCATION MAP | | | IS SHOWN ON THE EAST SIDE OF TAMARIND AVE. THE SITE IS | | | ON THE WEST SIDE OF TAMARIND AVE. | | | | | | 3. [SATISFIED] CONCEPTUAL ENGINEERING PLAN IS CONFUSING | | | WITH EXISTING FEATURES SHOWN AND NOT SCREENED. | | | | | | 4. [SATISFIED] LABEL WHERE THE EXISTING POWER POLE WILL | | | BE RELOCATED WHEN THE DRIVEWAY APRON IS CONSTRUCTED. | | | | | | 5. [NOT SATISFIED] REMOVE EXISTING DRIVEWAY APRONS AND | | | INSTALL CURB OR CURB AND GUTTER. | | | | | | 6. [SATISFIED] CIVIL SITE PLAN DOES NOT MATCH THE | | | ARCHITECTURAL SITE PLAN. | | | | | | 7. [PARTIALLY SATISFIED - SEE MORE COMMENTS UNDER NEW | | | COMMENTS BELOW.] PROVIDE CROSS SECTIONS FROM: | | | A. FACE OF BUILDING TO TAMARIND AVE CENTERLINE | | | B. FACE OF BUILDING TO GRANT ST CENTERLINE | | | C. AT PROPOSED DRIVEWAY | | | D. FROM WEST PROPERTY LINE TO FACE OF BUILDING | | | E. FROM SOUTH PROPERTY LINE TO PARKING LOT | | | F. FROM SOUTH PROPERTY LINE TO FACE OF BUILDING | | | LABEL STREETS, PROPERTY LINES, SURFACE FEATURES AND | | | GENERAL SURFACE SLOPES. PROVIDE DIMENSIONS FOR | | | CURBS/CURB AND GUTTER, SIDEWALKS AND DISTANCE FROM | | | PROPERTY LINE TO FACE OF BUILDING. INCLUDE PROPOSED | | | PARALLEL PARKING AREAS. | | | | | | 8. [PARTIALLY SATISFIED] SHOW MILL AND RESURFACING | | | LIMITS WITHIN THE STREETS. ADDITIONAL COMMENT - MILL | | | AND RESURFACE LIMITS TO EXTEND FOR FULL TRAVEL LANE | | | WIDTH. | | | | | | 9. [PARTIALLY SATISFIED] IDENTIFY ON THE CONCEPTUAL | | | ENGINEERING PLAN WHERE THE SPECIAL TYPE 'F' CURB AND | | | GUTTER WILL BE CONSTRUCTED. REDRAW THE DETAIL IN ACAD | | | AND PROVIDE ENGLISH UNITS. ADDITIONAL COMMENT - SHOW ON | | | THE PGD PLAN WHERE THE CURB WILL BE CONSTRUCTED. | | | | | | 10. [NOT SATISFIED] PROVIDE HATCHING PATTERNS FOR | | | SIDEWALKS TO REMAIN AND FOR NEW/REPLACEMENT SIDEWALKS. | | | ADDITIONAL COMMENT - SHOW CONCRETE FOR THE PROPOSED | | | DRIVEWAY APRON WITHIN THE R/W. SIDEWALKS AT EXISTING | | | DRIVEWAY APRONS TO BE REPLACED IF CROSS SLOPE EXCEEDS | | | 2%. | | | | | | 11. [SATISFIED] PER FIGURE XV-2: GENERAL PARKING | | | DIMENSIONS IN SECTION 94-485 OF THE CITY'S CODE OF | | | ORDINANCES, THE CURB LENGTH OF PARALLEL PARKING SPACES | | | IS 22 FEET. THE SITE PLAN SHOWS 25 FEET AND GAPS IN THE | | | PARKING SPACES ON TAMARIND AVE. | | | | | | 12. [SATISFIED] CONSIDER ANGLING THE CURBING AT EACH | | | END OF PROPOSED PARALLEL PARKING SPACES TO FACILITATE | | | ACCESS TO AND FROM THE END SPACES. | | | | | | 15. [NOT SATISFIED] THE CITY'S OFFICIAL VERTICAL DATUM | | | IS NGVD1929. THE CITY HAS ALLOWED THE USE OF NAVD1988 | | | AS LONG AS THE CONVERSION EQUATION TO NGVD1929 AT THE | | | PROJECT LOCATION IS PROVIDED. PROVIDE THE NAVD1988 TO | | | NGVD1929 CONVERSION EQUATION ON THE SURVEY. | | | | | | 16. [NOT SATISFIED] LABEL ANY NEW CURBS/CURB AND GUTTER | | | WITHIN THE RIGHT OF WAYS. ADDITIONAL COMMENT - SEE | | | COMMENT 5 ABOVE. | | | | | | 17. [NOT SATISFIED] CONSIDER LOW IMPACT DEVELOPMENT | | | DRAINAGE SYSTEMS IN LIEU OF EXFILTRATION TRENCHES. | | | | | | 18. [NOT SATISFIED] SHOW UTILITIES ON THE LANDSCAPE | | | PLANS. | | | | | | | | | NEW COMMENTS: | | | 19. REVISE FDOT INDEX NUMBERS TO CURRENT FDOT STANDARD | | | PLAN NUMBERS ON THE SITE PLAN SHEETS AND ENGINEERING | | | SHEETS. | | | | | | 20. SHEET SP-1 CALLS OUT A DETAIL NO. 4 ON SHEET SP-3. | | | SHEET SP-3 DOES NOT HAVE A DETAIL NO. 4. | | | | | | 21. LABEL 19TH STREET ON THE ENGINEERING PLANS. | | | | | | 22. PRB WALLS MISLABELED FOR STRUCTURES S-101 AND | | | S-102. | | | | | | 23. CALLOUT COLORED STAMP ASPHALT FOR THE CROSSWALK | | | ACROSS 19TH STREET. | | | | | | 24. SUGGEST ADDING SPOT GRADES FOR HANDICAP PARKING | | | SPACE. MAXIMUM SLOPE IN ANY DIRECTION FOR HANDICAP | | | SPACE IS 2%. | | | | | | 25. SHEET C2.3 GEOMETRIC, SIGNING AND STRIPING PLAN: | | | A. PROVIDE STRIPING PLAN FOR MILL AND RESURFACE AREAS. | | | B. ADD RIGHT TURN ONLY SIGN TO STOP SIGN IN PARKING | | | LOT. | | | C. STOP BAR MEASURES 12 FEET LONG ON THE 20 FT WIDE | | | DRIVEWAY. STOP BAR SHOULD EXTEND TO CURB. CONFIRM STOP | | | BAR IS SUFFICIENT DISTANCE FROM SIDEWALK. | | | D. REMOVE THE OUTLINE SYMBOLS FOR STOP BAR, LANE | | | DIVIDER, DIRECTIONAL ARROWS IN THE PARKING LOT IF THEY | | | ARE NOT NEEDED. OTHERWISE, PROVIDE CALLOUTS FOR THESE | | | ITEMS. | | | E. PROVIDE SIGN AND STRIPING FOR TURNAROUND SPACE IN | | | THE PARKING LOT. | | | F. SHOW EXISTING STOP SIGN FOR 19TH STREET. | | | | | | 26. SECTION A (SHEET C3.2) | | | A. VALLEY GUTTER SHOWN. | | | B. SHOW/LABEL EXISTING AND PROPOSED PROPERTY LINES. | | | C. ADD STREET NAME TO THE PUBLIC R/W. | | | D. PROVIDE DIMENSION FROM PROPERTY LINE TO FACE OF | | | BUILDING. | | | E. SHOW AND DIMENSION PATIO. | | | | | | 27. SECTION B (SHEET C3.2) | | | A. THIS SECTION DOES NOT MATCH WHAT IS OCCURRING ALONG | | | THE SOUTH PROPERTY LINE. | | | | | | 28. SECTION C (SHEET C3.2) | | | A. SHOW PROPOSED FENCE. | | | B. TYPE 'D' CURB SHOWN ON THE SECTION BUT IT IS NOT | | | SHOWN ON THE PGD PLAN. | | | C. EXTEND SECTION ACROSS THE PARKING LOT TO THE WEST | | | FACE OF THE BUILDING. SHOW GRADE BREAKS AND DIMENSIONS. | | | | | | 29. SECTION D (SHEET C3.2) | | | A. ADD STREET NAME TO THE PUBLIC R/W. | | | B. CALLOUT NEW CONCRETE DRIVEWAY APRON/SIDEWALK. | | | C. SHOW PAVEMENT FOR PARKING LOT. | | | D. EXTEND SECTION TO CENTERLINE OF 19TH STREET. SHOW | | | CURBED MEDIAN. DIMENSION PAVEMENT. | | | E. VERIFY LISTED PAVEMENT AND SIDEWALK ELEVATIONS. | | | | | | 30. PROVIDE SECTION FROM CENTERLINE OF 19TH STREET TO | | | NORTH FACE OF BUILDING. SHOW GRADE BREAKS, DIMENSIONS, | | | ETC. | | | | | | 31. SHEET C4.1 EROSION CONTROL PLAN (CAN BE ADDRESSED | | | WITH ENGINEERING PERMIT SUBMITTAL): | | | A. PROVIDE ALTERNATIVE TO HAY BALES FOR INLET | | | PROTECTION. | | | B. IDENTIFY WHICH INLETS ARE TO BE PROTECTED (ONSITE | | | AND WITHIN R/W) | | | C. MOVE HATCHING FOR CONSTRUCTION OUT OF THE R/W. | | | D. DO NOT SHOW SIGNING AND STRIPING CALLOUTS. | | | | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | [email protected] | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
01-13-2022 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
01-13-2022 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
01-13-2022 |
Time |
12:50 |
Sent To |
|
|
| Notes |
| 2022-01-13 12:50:43 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | 1. REMOVE REFERENCES TO VOW (VILLAGE OF WELLINGTON?) ON | | | COVER. | | | 2. PROJECT SITE ON PROJECT LOCATION MAP IS SHOWN ON THE | | | EAST SIDE OF TAMARIND AVE. THE SITE IS ON THE WEST SIDE | | | OF TAMARIND AVE. | | | 3. CONCEPTUAL ENGINEERING PLAN IS CONFUSING WITH | | | EXISTING FEATURES SHOWN AND NOT SCREENED. | | | 4. LABEL WHERE THE EXISTING POWER POLE WILL BE | | | RELOCATED WHEN THE DRIVEWAY APRON IS CONSTRUCTED. | | | 5. REMOVE EXISTING DRIVEWAY APRONS AND INSTALL CURB OR | | | CURB AND GUTTER. | | | 6. CIVIL SITE PLAN DOES NOT MATCH THE ARCHITECTURAL | | | SITE PLAN. | | | 7. PROVIDE CROSS SECTIONS FROM: | | | A. FACE OF BUILDING TO TAMARIND AVE CENTERLINE | | | B. FACE OF BUILDING TO GRANT ST CENTERLINE | | | C. AT PROPOSED DRIVEWAY | | | D. FROM WEST PROPERTY LINE TO FACE OF BUILDING | | | E. FROM SOUTH PROPERTY LINE TO PARKING LOT | | | F. FROM SOUTH PROPERTY LINE TO FACE OF BUILDING | | | LABEL STREETS, PROPERTY LINES, SURFACE FEATURES AND | | | GENERAL SURFACE SLOPES. PROVIDE DIMENSIONS FOR | | | CURBS/CURB AND GUTTER, SIDEWALKS AND DISTANCE FROM | | | PROPERTY LINE TO FACE OF BUILDING. INCLUDE PROPOSED | | | PARALLEL PARKING AREAS. | | | 8. SHOW MILL AND RESURFACING LIMITS WITHIN THE STREETS. | | | 9. IDENTIFY ON THE CONCEPTUAL ENGINEERING PLAN WHERE | | | THE SPECIAL TYPE ?F? CURB AND GUTTER WILL BE | | | CONSTRUCTED. REDRAW THE DETAIL IN ACAD AND PROVIDE | | | ENGLISH UNITS. | | | 10. PROVIDE HATCHING PATTERNS FOR SIDEWALKS TO REMAIN | | | AND FOR NEW/REPLACEMENT SIDEWALKS. | | | 11. PER FIGURE XV-2: GENERAL PARKING DIMENSIONS IN | | | SECTION 94-485 OF THE CITY?S CODE OF ORDINANCES, THE | | | CURB LENGTH OF PARALLEL PARKING SPACES IS 22 FEET. THE | | | SITE PLAN SHOWS 25 FEET AND GAPS IN THE PARKING SPACES | | | ON TAMARIND AVE. | | | 12. CONSIDER ANGLING THE CURBING AT EACH END OF | | | PROPOSED PARALLEL PARKING SPACES TO FACILITATE ACCESS | | | TO AND FROM THE END SPACES. | | | 15. THE CITY?S OFFICIAL VERTICAL DATUM IS NGVD1929. THE | | | CITY HAS ALLOWED THE USE OF NAVD1988 AS LONG AS THE | | | CONVERSION EQUATION TO NGVD1929 AT THE PROJECT LOCATION | | | IS PROVIDED. PROVIDE THE NAVD1988 TO NGVD1929 | | | CONVERSION EQUATION ON THE SURVEY. | | | 16. LABEL ANY NEW CURBS/CURB AND GUTTER WITHIN THE | | | RIGHT OF WAYS. | | | 17. CONSIDER LOW IMPACT DEVELOPMENT DRAINAGE SYSTEMS IN | | | LIEU OF EXFILTRATION TRENCHES. | | | 18. SHOW UTILITIES ON THE LANDSCAPE PLANS. | | | | | | | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP | | | CRITERIA. STORMWATER CALCULATIONS WILL BE REVIEWED WITH | | | THE ENGINEERING PERMIT SUBMITTAL. | | | | | | 2. PROVIDE COPY OF SFWMD ERP PERMIT BEFORE START OF | | | CONSTRUCTION, IF REQUIRED. | | | | | | 3. PROVIDE AN EROSION CONTROL PLAN WITH DETAILS. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | 561-351-0510 (M) | | | [email protected] | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
3 |
Status |
P |
Date |
09-27-2022 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
09-27-2022 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-09-27 09:39:27 | PASSED WITH CONDITION OF REPLAT PRIOR TO C.O. |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
2 |
Status |
F |
Date |
04-26-2022 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
04-26-2022 |
Time |
08:01 |
Rev Time |
0.00 |
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-04-26 08:13:08 | 1. SHOW PROPOSED UTILITIES ON LANDSCAPE PLAN. | | | 2. WHERE IS RELOCATED IRRIGATION METER GOING? | | | 3. METER ON TAMARIND NOT SHOWN ON ENG. PLANS. | | | 4. RELOCATE CLEANOUT OUT OF SIDEWALK. | | | 5. ADJOINING SIDEWALKS NEED TO BE REPLACED. |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
01-10-2022 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
01-10-2022 |
Time |
09:00 |
Rev Time |
|
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-01-10 09:18:15 | 1. REVISE SURVEY AND ALL PLANS TO SHOW MAINTENANCE MAP | | | RIGHT-OF-WAY IN ROAD PLAT BOOK 11/94. | | | 2. MASTER METER MAY BE REQUIRED. METER BANK CONFLICTS | | | WITH PROPOSED LANDSCAPING. | | | 3. CHANGE LINE WEIGHT OF PROPERTY LINE FOR BETTER | | | DELINEATION. DIVIDE CONCEPTUAL PLAN INTO SEPARATE P&G | | | AND W&S PLANS. | | | 4. NEED TO SEE CROSS-SECTIONS ON ALL SIDES DUE TO GRADE | | | DIFFERENCES. | | | 5. SURVEY NEEDS TO BE SIGNED/SEALED. | | | 6. ADD CONVERSION TO NGVD-29 TO ALL PLANS. CIVIL PLANS | | | ALMOST ILLEGIBLE DUE TO OVER-WRITES. | | | 7. REPLAT MAY BE REQUIRED. | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
4 |
Status |
P |
Date |
12-07-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
12-07-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
12-07-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-12-07 18:38:04 | APPROVED WITH THE FOLLOWING CONDITION: | | | 1) PROPERLY ALIGN THE CROSS WALK JUST SOUTH OF 19TH ST | | | ACROSS TAMARIND, SO TO BE PERPENDICULAR TO TAMARIND AVE | | | AND LANDING WITHIN THE SIDEWALK AREAS ON BOTH SIDES. | | | POTENTIAL MODIFICATION TO THE INTERSECTION SOUTH-WEST | | | CORNER RAMP, AND TO THE PLANTER AREA ON BOTH SIDES OF | | | THE ROAD MAY BE REQUIRED | | | | | | PREVIOUS COMMENTS | | | 1) SATISFIED. PROVIDE TRAFFIC STUDY | | | 2) SATISFIED. SUBMISSION ACKNOWLEDGED. PROVIDE COUNTY | | | TPS LETTER ONCE AVAILABLE. THE LATEST SUBMISSION DID | | | NOT PROVIDE THE LETTER | | | 3) SATISFIED. PROVIDE A SEPARATE SITE PLAN SHOWCASING | | | TRANSPORTATION FEATURES (I.E. ROAD, PARKING STALLS, | | | SIDEWALK, CURB, DRIVEWAY) PROPERLY LABELED AND | | | DIMENSIONED. IF ALREADY PROVIDED, PLEASE INDICATE | | | SPECIFIC FILE NAME AND/OR SHEET NUMBER(S). | | | 4) SATISFIED. ON THE SITE PLAN, PLEASE SHOWCASE BASIC | | | CURB DETAILS (I.E. DRIVEWAY AND PARKING STALLS) ON THE | | | OPPOSITE SIDE OF THE ROADS SURROUNDING THE PROPOSED | | | DEVELOPMENT. PLEASE PROVIDE DOCUMENT NAME AND SHEET | | | NUMBER SHOWCASING SUCH FEATURES. | | | 5) SATISFIED. PROVIDE AUTOTURN ANALYSIS FOR GARBAGE | | | TRUCK AND/OR SERVICE VEHICLES DRIVING IN AND OUT OF THE | | | PROPOSED DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES | | | CLEARLY DEFINED. ANALYSIS SHOULD BE PROVIDED IN A | | | SEPARATE FILE/DRAWING. PLEASE PROVIDE DOCUMENT NAME AND | | | SHEET NUMBER SHOWCASING THE ANALYSIS. LATEST ANALYSIS | | | WAS NOT PROVIDED IN A SEPARATE FILE. BOTH VEHICLES??? | | | PATH AND MANEUVERING ARE NOT CLEAR. IF NEEDED, | | | ENGINEERING SERVICES CAN PROVIDE AN EXAMPLE OF AN | | | ACCEPTABLE ANALYSIS. | | | 6) SATISFIED. PROVIDE PARKING TABLE SHOWCASING THE | | | NUMBER OF REQUIRED AND PROVIDED PARKING SPACES, | | | INCLUSIVE OF ADA AND BICYCLE ONES. SP-1 IS PARTIALLY | | | CUT-OUT, PLEASE RESUBMIT CORRECTED VERSION | | | 7) SATISFIED. THE CITY BICYCLE MASTERPLAN ENVISIONS | | | SHARED BICYCLE LANES ALONG TAMARIND AVENUE. IF NEEDED | | | OR MISSING PROVIDE CORRESPONDING SIGNAGE AND PAVEMENT | | | MARKINGS ACCORDING TO CITY STANDARDS ALONG THE BLOCK | | | FRONTING THE PROPOSED DEVELOPMENT. INSERT REQUIRED | | | PAVEMENT MARKINGS AND SIGN LOCATIONS IN THE SITE PLAN. | | | 8) PARTIALLY SATISFIED. PROVIDE A MID-BLOCK PEDESTRIAN | | | CROSSING, CONNECTING TO THE 1004 19TH ST PROPOSED | | | DEVELOPMENT. PROVIDE DIMENSIONS AND PROPER CROSSWALK | | | PAVEMENT MARKINGS, PLEASE REFER TO FDOT STANDARD PLANS | | | INDEX 711-001. NOTE: IF A MIDBLOCK CROSSING MAY NOT BE | | | PROVED FEASIBLE, DUE TO SIGNIFICANT IMPACTS TO EXISTING | | | SIDEWALK AND ROADWAY CONFIGURATION, INSTALL PEDESTRIAN | | | CROSSING ACROSS TAMARIND JUST SOUTH OF THE 19TH ST AND | | | JUST NORTH OF THE GRANT ST INTERSECTIONS. CROSSWALK AT | | | 19TH ST IS NOT PROPERLY INSTALLED/ALIGNED WITH EXISTING | | | SIDEWALK, AS IT CURRENTLY ENDS ON A TRAVEL LANE BY THE | | | EASTERN LANDING | | | 9) SATISFIED. SIDEWALK. MINIMUM UN-OBSTRUCTED WALKABLE | | | AREA WIDTH MUST BE 5 FEET. PLEASE UPDATE THE SITE PLAN | | | ACCORDINGLY AND CLEARLY DEPICT SIDEWALK MEASUREMENTS. | | | PLEASE PROVIDE DOCUMENT NAME AND SHEET NUMBER | | | SHOWCASING SUCH FEATURE | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
3 |
Status |
F |
Date |
08-09-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
08-09-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
08-09-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-09 23:28:38 | 1) SATISFIED. PROVIDE TRAFFIC STUDY | | | 2) PARTIALLY SATISFIED. SUBMISSION ACKNOWLEDGED. | | | PROVIDE COUNTY TPS LETTER ONCE AVAILABLE. THE LATEST | | | SUBMISSION DID NOT PROVIDE THE LETTER | | | 3) SATISFIED. PROVIDE A SEPARATE SITE PLAN SHOWCASING | | | TRANSPORTATION FEATURES (I.E. ROAD, PARKING STALLS, | | | SIDEWALK, CURB, DRIVEWAY) PROPERLY LABELED AND | | | DIMENSIONED. IF ALREADY PROVIDED, PLEASE INDICATE | | | SPECIFIC FILE NAME AND/OR SHEET NUMBER(S). | | | 4) SATISFIED. ON THE SITE PLAN, PLEASE SHOWCASE BASIC | | | CURB DETAILS (I.E. DRIVEWAY AND PARKING STALLS) ON THE | | | OPPOSITE SIDE OF THE ROADS SURROUNDING THE PROPOSED | | | DEVELOPMENT. PLEASE PROVIDE DOCUMENT NAME AND SHEET | | | NUMBER SHOWCASING SUCH FEATURES. | | | 5) SATISFIED. PROVIDE AUTOTURN ANALYSIS FOR GARBAGE | | | TRUCK AND/OR SERVICE VEHICLES DRIVING IN AND OUT OF THE | | | PROPOSED DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES | | | CLEARLY DEFINED. ANALYSIS SHOULD BE PROVIDED IN A | | | SEPARATE FILE/DRAWING. PLEASE PROVIDE DOCUMENT NAME AND | | | SHEET NUMBER SHOWCASING THE ANALYSIS. LATEST ANALYSIS | | | WAS NOT PROVIDED IN A SEPARATE FILE. BOTH VEHICLES? | | | PATH AND MANEUVERING ARE NOT CLEAR. IF NEEDED, | | | ENGINEERING SERVICES CAN PROVIDE AN EXAMPLE OF AN | | | ACCEPTABLE ANALYSIS. | | | 6) SATISFIED. PROVIDE PARKING TABLE SHOWCASING THE | | | NUMBER OF REQUIRED AND PROVIDED PARKING SPACES, | | | INCLUSIVE OF ADA AND BICYCLE ONES. SP-1 IS PARTIALLY | | | CUT-OUT, PLEASE RESUBMIT CORRECTED VERSION | | | 7) SATISFIED. THE CITY BICYCLE MASTERPLAN ENVISIONS | | | SHARED BICYCLE LANES ALONG TAMARIND AVENUE. IF NEEDED | | | OR MISSING PROVIDE CORRESPONDING SIGNAGE AND PAVEMENT | | | MARKINGS ACCORDING TO CITY STANDARDS ALONG THE BLOCK | | | FRONTING THE PROPOSED DEVELOPMENT. INSERT REQUIRED | | | PAVEMENT MARKINGS AND SIGN LOCATIONS IN THE SITE PLAN. | | | 8) SATISFIED. PROVIDE A MID-BLOCK PEDESTRIAN CROSSING, | | | CONNECTING TO THE 1004 19TH ST PROPOSED DEVELOPMENT. | | | PROVIDE DIMENSIONS AND PROPER CROSSWALK PAVEMENT | | | MARKINGS, PLEASE REFER TO FDOT STANDARD PLANS INDEX | | | 711-001. NOTE: IF A MIDBLOCK CROSSING MAY NOT BE PROVED | | | FEASIBLE, DUE TO SIGNIFICANT IMPACTS TO EXISTING | | | SIDEWALK AND ROADWAY CONFIGURATION, INSTALL PEDESTRIAN | | | CROSSING ACROSS TAMARIND JUST SOUTH OF THE 19TH ST AND | | | JUST NORTH OF THE GRANT ST INTERSECTIONS | | | 9) NOT SATISFIED. SIDEWALK. MINIMUM UN-OBSTRUCTED | | | WALKABLE AREA WIDTH MUST BE 5 FEET. PLEASE UPDATE THE | | | SITE PLAN ACCORDINGLY AND CLEARLY DEPICT SIDEWALK | | | MEASUREMENTS. PLEASE PROVIDE DOCUMENT NAME AND SHEET | | | NUMBER SHOWCASING SUCH FEATURE | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
2 |
Status |
F |
Date |
04-15-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
04-15-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-04-15 16:00:19 | | | | 1) SATISFIED. PROVIDE TRAFFIC STUDY | | | 2) PARTIALLY SATISFIED. SUBMISSION ACKNOWLEDGED. | | | PROVIDE COUNTY TPS LETTER ONCE AVAILABLE | | | 3) SATISFIED. PROVIDE A SEPARATE SITE PLAN SHOWCASING | | | TRANSPORTATION FEATURES (I.E. ROAD, PARKING STALLS, | | | SIDEWALK, CURB, DRIVEWAY) PROPERLY LABELED AND | | | DIMENSIONED. IF ALREADY PROVIDED, PLEASE INDICATE | | | SPECIFIC FILE NAME AND/OR SHEET NUMBER(S). | | | 4) SATISFIED. ON THE SITE PLAN, PLEASE SHOWCASE BASIC | | | CURB DETAILS (I.E. DRIVEWAY AND PARKING STALLS) ON THE | | | OPPOSITE SIDE OF THE ROADS SURROUNDING THE PROPOSED | | | DEVELOPMENT. PLEASE PROVIDE DOCUMENT NAME AND SHEET | | | NUMBER SHOWCASING SUCH FEATURES. | | | 5) NOT SATISFIED. PROVIDE AUTOTURN ANALYSIS FOR GARBAGE | | | TRUCK AND/OR SERVICE VEHICLES DRIVING IN AND OUT OF THE | | | PROPOSED DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES | | | CLEARLY DEFINED. ANALYSIS SHOULD BE PROVIDED IN A | | | SEPARATE FILE/DRAWING. PLEASE PROVIDE DOCUMENT NAME AND | | | SHEET NUMBER SHOWCASING THE ANALYSIS. LATEST ANALYSIS | | | WAS NOT PROVIDED IN A SEPARATE FILE. BOTH VEHICLES PATH | | | AND MANEUVERING ARE NOT CLEAR. IF NEEDED, ENGINEERING | | | SERVICES CAN PROVIDE AN EXAMPLE OF AN ACCEPTABLE | | | ANALYSIS. | | | 6) SATISFIED. PROVIDE PARKING TABLE SHOWCASING THE | | | NUMBER OF REQUIRED AND PROVIDED PARKING SPACES, | | | INCLUSIVE OF ADA AND BICYCLE ONES. SP-1 IS PARTIALLY | | | CUT-OUT, PLEASE RESUBMIT CORRECTED VERSION | | | 7) NOT SATISFIED. THE CITY BICYCLE MASTERPLAN ENVISIONS | | | SHARED BICYCLE LANES ALONG TAMARIND AVENUE. IF NEEDED | | | OR MISSING PROVIDE CORRESPONDING SIGNAGE AND PAVEMENT | | | MARKINGS ACCORDING TO CITY STANDARDS ALONG THE BLOCK | | | FRONTING THE PROPOSED DEVELOPMENT. INSERT REQUIRED | | | PAVEMENT MARKINGS AND SIGN LOCATIONS IN THE SITE PLAN. | | | 8) PARTIALLY SATISFIED. PROVIDE A MID-BLOCK PEDESTRIAN | | | CROSSING, CONNECTING TO THE 1004 19TH ST PROPOSED | | | DEVELOPMENT. PROVIDE DIMENSIONS AND PROPER CROSSWALK | | | PAVEMENT MARKINGS, PLEASE REFER TO FDOT STANDARD PLANS | | | INDEX 711-001. NOTE: IF A MIDBLOCK CROSSING MAY NOT BE | | | PROVED FEASIBLE, DUE TO SIGNIFICANT IMPACTS TO EXISTING | | | SIDEWALK AND ROADWAY CONFIGURATION, INSTALL PEDESTRIAN | | | CROSSING ACROSS TAMARIND JUST SOUTH OF THE 19TH ST AND | | | JUST NORTH OF THE GRANT ST INTERSECTIONS | | | 9) SIDEWALK. MINIMUM UN-OBSTRUCTED WALKABLE AREA WIDTH | | | MUST BE 5 FEET. PLEASE UPDATE THE SITE PLAN ACCORDINGLY | | | AND CLEARLY DEPICT SIDEWALK MEASUREMENTS | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
01-06-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
01-06-2022 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-01-06 20:17:29 | TRAFFIC COMMENTS | | | 1) PROVIDE TRAFFIC STUDY | | | 2) PROVIDE COUNTY TPS LETTER | | | SITE COMMENTS | | | 3) PROVIDE A SEPARATE SITE PLAN SHOWCASING | | | TRANSPORTATION FEATURES (I.E. ROAD, PARKING STALLS, | | | SIDEWALK, CURB, DRIVEWAY) PROPERLY LABELED AND | | | DIMENSIONED. IF ALREADY PROVIDED, PLEASE INDICATE | | | SPECIFIC FILE NAME AND/OR SHEET NUMBER(S). | | | 4) ON THE SITE PLAN, PLEASE SHOWCASE BASIC CURB DETAILS | | | (I.E. DRIVEWAY AND PARKING STALLS) ON THE OPPOSITE SIDE | | | OF THE ROADS SURROUNDING THE PROPOSED DEVELOPMENT. | | | PLEASE PROVIDE DOCUMENT NAME AND SHEET NUMBER | | | SHOWCASING SUCH FEATURES. | | | 5) PROVIDE AUTOTURN ANALYSIS FOR GARBAGE TRUCK AND/OR | | | SERVICE VEHICLES DRIVING IN AND OUT OF THE PROPOSED | | | DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES CLEARLY | | | DEFINED. ANALYSIS SHOULD BE PROVIDED IN A SEPARATE | | | FILE/DRAWING. PLEASE PROVIDE DOCUMENT NAME AND SHEET | | | NUMBER SHOWCASING THE ANALYSIS. | | | 6) PROVIDE PARKING TABLE SHOWCASING THE NUMBER OF | | | REQUIRED AND PROVIDED PARKING SPACES, INCLUSIVE OF ADA | | | AND BICYCLE ONES | | | 7) THE CITY BICYCLE MASTERPLAN ENVISIONS SHARED BICYCLE | | | LANES ALONG TAMARIND AVENUE. IF NEEDED OR MISSING, | | | PROVIDE CORRESPONDING SIGNAGE AND PAVEMENT MARKINGS | | | ACCORDING TO CITY STANDARDS ALONG THE BLOCK FRONTING | | | THE PROPOSED DEVELOPMENT | | | 8) PROVIDE A MID-BLOCK PEDESTRIAN CROSSING, CONNECTING | | | TO THE 1980 N TAMARIND PROPOSED DEVELOPMENT | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
12-07-2022 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
12-07-2022 |
Time |
12:44 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
12-07-2022 |
Time |
12:43 |
Sent To |
|
|
| Notes |
| 2022-12-07 12:43:51 | PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW | | | ________________________________________ | | | | | | DATE OF REVIEW: 12.07.2022 | | | PROJECT NO.: Z21120020 AND Z21120015 | | | CASE NO.: ISPR 21-15 AND PB 1906 | | | ________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS: | | | | | | 1. SATISFIED - APPROVAL LETTER FROM PALM BEACH COUNTY | | | SHALL BE PROVIDED INDICATING THAT THE PROJECT COMPLIES | | | WITH THE TRANSPORTATION PERFORMANCE STANDARDS (TRAFFIC | | | CONCURRENCY). | | | | | | 2. SATISFIED (NOTE THEIR CONDITION OF APPROVAL) - | | | APPROVED SCHOOL CAPACITY AVAILABILITY DETERMINATION | | | SHALL BE PROVIDED FROM THE SCHOOL DISTRICT OF PALM | | | BEACH COUNTY. | | | | | | 3. SATISFIED (SUBJECT TO CONDITION OF APPROVAL - | | | EASEMENTS REQUIRED) - LETTERS FROM ALL UTILITY | | | COMPANIES SHALL BE PROVIDED INDICATING THAT THE | | | PROPOSED PROJECT DOES NOT ENCROACH INTO THEIR EASEMENTS | | | OR OTHERWISE INTERFERE WITH THEIR ABILITY TO PROVIDE | | | SERVICES. | | | | | | 4. SATISFIED - JUSTIFICATION STATEMENT IS TO INCLUDE | | | RESPONSES INDICATING HOW THE PROPOSED DEVELOPMENT | | | COMPLIES WITH THE SITE PLAN REVIEW STANDARDS FOR CODE | | | COMPLIANCE [SEC. 94-35(C)]. | | | | | | 5. SATISFIED (CONCERNS STILL EXIST BUT ALL CODE | | | REQUIREMENTS HAVE BEEN MET) - STAFF WOULD LIKE TO WORK | | | WITH THE ARCHITECT ON THE VARIOUS ELEMENTS OF THE | | | ARCHITECTURAL STYLING. CONCERNS INCLUDE: | | | | | | 5.1. SATISFIED (CONCERNS STILL EXIST BUT ALL CODE | | | REQUIREMENTS HAVE BEEN MET) - ALL OF THE PROJECTS IS | | | EXACTLY THE SAME. ALTERNATIVE STYLES, OR VARIATIONS, | | | SHOULD BE CONSIDERED ACROSS ALL OF THE PROJECTS AS THEY | | | ARE SEPARATE SITES ALONG THE CORRIDOR AND READ | | | INDEPENDENTLY OF ONE ANOTHER. | | | | | | 5.1.1. SATISFIED - THE RENDERINGS PROVIDED DO NOT | | | ACCURATE DEPICT WHAT IS SHOWN IN THE ELEVATIONS, | | | LANDSCAPE PLANS, ETC. | | | | | | 5.1.2. SATISFIED - THE ELEVATIONS DO NOT CORRESPOND | | | WITH WHAT IS SHOWN IN THE FLOOR PLAN | | | (WINDOW/DOOR/STOREFRONT CONFIGURATIONS). | | | | | | 5.2. SATISFIED - ADDITIONAL WINDOWS/OPENING ARE NEEDED | | | ON THE SIDES/REAR OF THE BUILDING TO PROVIDE BETTER | | | ARCHITECTURAL STYLING, NATURAL SURVEILLANCE, VISUAL | | | ENHANCEMENT TO THE NON-RESIDENTIAL SPACES, ETC. | | | | | | 5.3. SATISFIED - GROUND FLOOR RESIDENTIAL UNITS FACING | | | TAMARIND AVENUE SHOULD INDIVIDUALLY READ AS WALK-UP | | | UNITS WITH THEIR FRONT/MAIN ENTRANCE FACING THE | | | RIGHT-OF-WAY. | | | | | | 5.3.1. SATISFIED - ARE YOU SURE THAT IT IS DESIREABLE | | | TO HAVE DOOR EXITING THE MASTER BEDROOM ONTO TAMARIND | | | AVENUE? SHOULDN'T THE WALKWAY CONNECT DIRECTLY FROM THE | | | TAMARIND AVENUE SIDEWALK TO THE DOORWAY LEADING TO THE | | | LIVING AREA, WITH A SMALL PATIO OFF TO THE SIDE? IT | | | SEEMS THAT SOME OF THE WALKWAYS LEAD UP TO THE BEDROOM. | | | | | | 6. SATISFIED - PHOTOMETRIC LEVELS NEED TO BE SHOWN AT | | | THE PROPERTY LINE. LEVELS SHALL NOT EXCEED 0.5 | | | FOOTCANDLES WHEN MEASURED AT THE PROPERTY LINE ADJACENT | | | TO A RESIDENTIAL ZONING DISTRICT. | | | | | | 7. SATISFIED - THE SQUARE FOOTAGE OF THE AREA TO BE | | | ABANDONED SHOWN ON THE SITE PLAN IS NOT CONSISTENT WHAT | | | IS DESCRIBED IN THE SKETCH/LEGAL OF THE ABANDONMENT. | | | ENSURE THAT ALL PLANS/DOCUMENTS ARE ACCURATE AND | | | CONSISTENT. | | | | | | 8. SATISFIED - PURSUANT TO SEC. 94-222(H)(5) ALL | | | WINDOWS ARE TO BE VERTICAL OR SQUARE IN PROPORTION. | | | | | | 9. SATISFIED - PURSUANT TO SEC. 94-222(H)(6) ALL | | | WINDOWS ARE TO BE RECESSED A MINIMUM OF 2 INCHES FROM | | | THE EXTERIOR FACE OF THE FA?ADE. PLEASE PROVIDE A | | | DETAIL. | | | | | | 10. SATISFIED - PURSUANT TO SEC. 94-222(H)(7) ALL | | | WINDOWS ARE TO BE OPERABLE. PLEASE PROVIDE A | | | DETAIL/NOTE. | | | | | | 11. SATISFIED - PURSUANT TO SEC. 94-222(H)(10) SLIDING | | | DOORS ARE ONLY ALLOWED ON THE REAR FA?ADE. | | | | | | 12. SATISFIED - STAFF HAS CONCERN THAT THE PROPOSED | | | RETAIL SPACE IS NOT OF SUFFICIENT SIZE TO PROVIDE FOR A | | | VIABLE/LEASABLE SPACE FOR A TENANT. PLEASE PROVIDE | | | INFORMATION INDICATING HOW THIS SPACE IS ENVISIONED TO | | | BE UTILIZED AND LEASED SUCCESSFULLY. | | | | | | 13. SATISFIED - THE FAR CALCULATION IS INCORRECT. | | | | | | 14. SATISFIED - THE CONSTRUCTION OF THE NEW ON-STREET | | | PARKING IS SUBJECT TO THE APPROVAL OF THE CITY?S | | | ENGINEERING SERVICES DEPARTMENT. | | | | | | 14.1. SATISFIED - ONLY FIVE (5) OF THE PARKING SPACES | | | ALONG TAMARIND AVENUE CAN BE COUNTED TOWARDS THE | | | PROJECT'S TOTAL PROVIDED AS ONLY THOSE SPACES THAT ARE | | | ENTIRELY WITHIN THE PROJECTS BOUNDARIES CAN BE COUNTED. | | | | | | 15. SATISFIED - PLEASE CLEARLY IDENTIFY THE LOCATION OF | | | THE PROPOSED PROPERTY LINE ALONG TAMARIND AVENUE (IF | | | ABANDONMENT IS APPROVED). | | | | | | 16. SATISFIED - BICYCLE PARKING SHALL BE PROVIDED IN | | | ACCORDANCE WITH SEC. 94-485(Q). INDICATE ALL LOCATIONS. | | | | | | 16.1. SATISFIED - BICYCLE PARKING SHOULD ALSO BE | | | PROVIDED IN A LOCATION THAT CAN EASILY BE FOUND AND | | | UTILIZED BY THE RETAIL USERS. | | | | | | 16.2. SATISFIED - THE PAD FOR THE BIKE RACKS SHOULD BE | | | A MINIMUM OF 72 INCHES IN LENGTH AND AT AT LEAST 24 | | | INCHES ON EITHER SIDE OF THE RACK. IF MORE THAN ONE | | | RACK IS PROVIDED, THERE SHALL BE AT LEAST 30 INCHES | | | BETWEEN THE RACKS. | | | | | | 17. SATISFIED - ENSURE THAT PLANS SHOW ALL WALLS, | | | FENCES, ETC. IF RETAINING WALLS ARE PROPOSED, | | | DETAILS/CROSS SECTIONS NEED TO BE PROVIDED. | | | | | | 18. SATISFIED - PARKING STRIPING DETAIL DOES NOT | | | CONFORM TO THE CITY?S MINIMUM STANDARDS. | | | | | | 19. SATISFIED - PLEASE CLARIFY THE DUMPSTER ENCLOSURE | | | DETAIL, IT LOOKS LIKE THE GATES CONSIST OF CHAIN LINK; | | | SUCH MATERIAL IS NOT PERMITTED. THE GATE NEEDS TO BE A | | | SOLID/OPAQUE MATERIAL. | | | | | | 20. SATISFIED - PLEASE IDENTIFY THE VISIBILITY | | | TRIANGLES (AS DEFINED BY THE CITY?S ZLDRS) AT THE | | | INTERSECTIONS OF THE RIGHTS-OF-WAY. NO OBJECTS WITHIN | | | THE VISIBILITY TRIANGLE SHALL EXIST BETWEEN A HEIGHT OF | | | 18 INCHES AND 8 FEET. | | | | | | 21. SATISFIED - SCREEN WALLS SHALL BE PROVIDED ALONG | | | THE EAST PROPERTY LINE SEPARATING THE PARKING FROM THE | | | ADJACENT RESIDENTIAL USES [SEC. 94-443(A)(1)]. | | | | | | 22. SATISFIED - PLEASE PROVIDE A CROSS SECTION THROUGH | | | THE ENTIRE SITE TO SHOW THE ELEVATION PROFILE, ETC. AS | | | THE PROPERTY SLOPES EAST/WEST. | | | | | | 23. SATISFIED - ALL BALCONIES, ROOF OVERHANGS, AWNINGS, | | | ETC. NEED TO BE SHOWN AND DIMENSIONED ON THE SITE PLAN. | | | PURSUANT TO SEC. 94-305(B)(2) SUCH ENCROACHMENTS SHALL | | | NOT EXTEND MORE THAN 3 FEET INTO A REQUIRED SETBACK. | | | | | | 24. SATISFIED - CONFIRM THAT THE SQUARE FOOTAGES OF THE | | | NON-RESIDENTIAL USES ARE ACCURATE AND CONSISTENT. THE | | | SITE PLAN DOESN?T APPEAR TO MATCH THE FLOOR PLAN, DATA | | | TABLE, ETC. | | | | | | 25. SATISFIED - IT IS THE CITY?S POLICY FOR | | | RIGHT-OF-WAY ABANDONMENTS THAT THE PETITIONER PAY TO | | | THE CITY THE APPRAISED VALUE OF THE RIGHT-OF-WAY. | | | PLEASE COORDINATE WITH VINCE NOEL ON OBTAINING THE | | | APPRAISAL, ETC. | | | | | | 26. SATISFIED - PLEASE MARK THE TURNAROUND SPACE WITH A | | | CROSS-HATCH INDICATING "NO PARKING". | | | | | | 27. SATISFIED - THE RIGHT GATE OF THE DUMPSTER | | | ENCLOSURE IMPEDES WITH THE EGRESS TRAVEL LANE. | | | | | | 28. SATISFIED - WHY ARE THE INGRESS AND EGRESS FROM THE | | | PARKING LOT DIFFERENT DIMENSIONS? IF A STRIPE IS BEING | | | PLACED BETWEEN THE TWO, SHOULDN'T IT BE PLACED IN THE | | | MIDDLE OF THE 20-FOOT DRIVE AISLE? | | | | | | 29. SATISFIED - ONLY FIVE (5) OF THE PARKING SPACES ON | | | TAMARIND AVENUE CAN COUNT TOWARD THE PROJECTS "PARKING | | | PROVIDED". PURSUANT TO THE ZLDRS, ONLY SPACES THAT ARE | | | ENTIRELY WITHIN THE BOUNDARY OF THE SUBJECT PROPERTY | | | CAN BE CONSIDERED. | | | | | | 30. SATISFIED - THE HEIGHT OF THE BUILDING EXCEEDS THE | | | MAXIMUM HEIGHT PERMITTED. THE MAXIMUM HEIGHT OF THE | | | BUILDING IS ALLOWED TO BE 30 FEET, WITH AN ADDITIONAL | | | 10% FOR DECORATIVE ELEMENTS, PARAPETS, ETC. AS SUCH, | | | THE TOP OF THE PARAPET IS NOT TO EXCEED 33 FEET. | | | ________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | TTY: 800.955.8771 | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
04-26-2022 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
04-26-2022 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
04-26-2022 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2022-04-25 15:54:50 | PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW | | | ________________________________________ | | | | | | DATE OF REVIEW: 04.25.2022 | | | PROJECT NO.: Z21120020 AND Z21120015 | | | CASE NO.: ISPR 21-15 AND PB 1906 | | | ________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS: | | | | | | 1. SATISFIED - APPROVAL LETTER FROM PALM BEACH COUNTY | | | SHALL BE PROVIDED INDICATING THAT THE PROJECT COMPLIES | | | WITH THE TRANSPORTATION PERFORMANCE STANDARDS (TRAFFIC | | | CONCURRENCY). | | | | | | 2. SATISFIED (NOTE THEIR CONDITION OF APPROVAL) - | | | APPROVED SCHOOL CAPACITY AVAILABILITY DETERMINATION | | | SHALL BE PROVIDED FROM THE SCHOOL DISTRICT OF PALM | | | BEACH COUNTY. | | | | | | 3. SATISFIED (SUBJECT TO CONDITION OF APPROVAL - | | | EASEMENTS REQUIRED) - LETTERS FROM ALL UTILITY | | | COMPANIES SHALL BE PROVIDED INDICATING THAT THE | | | PROPOSED PROJECT DOES NOT ENCROACH INTO THEIR EASEMENTS | | | OR OTHERWISE INTERFERE WITH THEIR ABILITY TO PROVIDE | | | SERVICES. | | | | | | 4. SATISFIED - JUSTIFICATION STATEMENT IS TO INCLUDE | | | RESPONSES INDICATING HOW THE PROPOSED DEVELOPMENT | | | COMPLIES WITH THE SITE PLAN REVIEW STANDARDS FOR CODE | | | COMPLIANCE [SEC. 94-35(C)]. | | | | | | 5. PARTIALLY SATISFIED - STAFF WOULD LIKE TO WORK WITH | | | THE ARCHITECT ON THE VARIOUS ELEMENTS OF THE | | | ARCHITECTURAL STYLING. CONCERNS INCLUDE: | | | | | | 5.1. PARTIALLY SATISFIED - ALL OF THE PROJECTS IS | | | EXACTLY THE SAME. ALTERNATIVE STYLES, OR VARIATIONS, | | | SHOULD BE CONSIDERED ACROSS ALL OF THE PROJECTS AS THEY | | | ARE SEPARATE SITES ALONG THE CORRIDOR AND READ | | | INDEPENDENTLY OF ONE ANOTHER. | | | | | | 5.1.1. NEW COMMENT - THE RENDERINGS PROVIDED DO NOT | | | ACCURATE DEPICT WHAT IS SHOWN IN THE ELEVATIONS, | | | LANDSCAPE PLANS, ETC. | | | | | | 5.1.2. NEW COMMENT - THE ELEVATIONS DO NOT CORRESPOND | | | WITH WHAT IS SHOWN IN THE FLOOR PLAN | | | (WINDOW/DOOR/STOREFRONT CONFIGURATIONS). | | | | | | 5.2. SATISFIED - ADDITIONAL WINDOWS/OPENING ARE NEEDED | | | ON THE SIDES/REAR OF THE BUILDING TO PROVIDE BETTER | | | ARCHITECTURAL STYLING, NATURAL SURVEILLANCE, VISUAL | | | ENHANCEMENT TO THE NON-RESIDENTIAL SPACES, ETC. | | | | | | 5.3. PARTIALLY SATISFIED - GROUND FLOOR RESIDENTIAL | | | UNITS FACING TAMARIND AVENUE SHOULD INDIVIDUALLY READ | | | AS WALK-UP UNITS WITH THEIR FRONT/MAIN ENTRANCE FACING | | | THE RIGHT-OF-WAY. | | | | | | 5.3.1. NEW COMMENT - ARE YOU SURE THAT IT IS DESIREABLE | | | TO HAVE DOOR EXITING THE MASTER BEDROOM ONTO TAMARIND | | | AVENUE? SHOULDN'T THE WALKWAY CONNECT DIRECTLY FROM THE | | | TAMARIND AVENUE SIDEWALK TO THE DOORWAY LEADING TO THE | | | LIVING AREA, WITH A SMALL PATIO OFF TO THE SIDE? IT | | | SEEMS THAT SOME OF THE WALKWAYS LEAD UP TO THE BEDROOM. | | | | | | 6. SATISFIED - PHOTOMETRIC LEVELS NEED TO BE SHOWN AT | | | THE PROPERTY LINE. LEVELS SHALL NOT EXCEED 0.5 | | | FOOTCANDLES WHEN MEASURED AT THE PROPERTY LINE ADJACENT | | | TO A RESIDENTIAL ZONING DISTRICT. | | | | | | 7. SATISFIED - THE SQUARE FOOTAGE OF THE AREA TO BE | | | ABANDONED SHOWN ON THE SITE PLAN IS NOT CONSISTENT WHAT | | | IS DESCRIBED IN THE SKETCH/LEGAL OF THE ABANDONMENT. | | | ENSURE THAT ALL PLANS/DOCUMENTS ARE ACCURATE AND | | | CONSISTENT. | | | | | | 8. SATISFIED - PURSUANT TO SEC. 94-222(H)(5) ALL | | | WINDOWS ARE TO BE VERTICAL OR SQUARE IN PROPORTION. | | | | | | 9. SATISFIED - PURSUANT TO SEC. 94-222(H)(6) ALL | | | WINDOWS ARE TO BE RECESSED A MINIMUM OF 2 INCHES FROM | | | THE EXTERIOR FACE OF THE FA?ADE. PLEASE PROVIDE A | | | DETAIL. | | | | | | 10. SATISFIED - PURSUANT TO SEC. 94-222(H)(7) ALL | | | WINDOWS ARE TO BE OPERABLE. PLEASE PROVIDE A | | | DETAIL/NOTE. | | | | | | 11. SATISFIED - PURSUANT TO SEC. 94-222(H)(10) SLIDING | | | DOORS ARE ONLY ALLOWED ON THE REAR FA?ADE. | | | | | | 12. STAFF HAS CONCERN THAT THE PROPOSED RETAIL SPACE IS | | | NOT OF SUFFICIENT SIZE TO PROVIDE FOR A VIABLE/LEASABLE | | | SPACE FOR A TENANT. PLEASE PROVIDE INFORMATION | | | INDICATING HOW THIS SPACE IS ENVISIONED TO BE UTILIZED | | | AND LEASED SUCCESSFULLY. | | | | | | 13. NOT SATISFIED - THE FAR CALCULATION IS INCORRECT. | | | | | | 14. PARTIALLY SATISFIED - THE CONSTRUCTION OF THE NEW | | | ON-STREET PARKING IS SUBJECT TO THE APPROVAL OF THE | | | CITY?S ENGINEERING SERVICES DEPARTMENT. | | | | | | 14.1. NEW COMMENT - ONLY FIVE (5) OF THE PARKING SPACES | | | ALONG TAMARIND AVENUE CAN BE COUNTED TOWARDS THE | | | PROJECT'S TOTAL PROVIDED AS ONLY THOSE SPACES THAT ARE | | | ENTIRELY WITHIN THE PROJECTS BOUNDARIES CAN BE COUNTED. | | | | | | 15. SATISFIED - PLEASE CLEARLY IDENTIFY THE LOCATION OF | | | THE PROPOSED PROPERTY LINE ALONG TAMARIND AVENUE (IF | | | ABANDONMENT IS APPROVED). | | | | | | 16. PARTIALLY SATISFIED - BICYCLE PARKING SHALL BE | | | PROVIDED IN ACCORDANCE WITH SEC. 94-485(Q). INDICATE | | | ALL LOCATIONS. | | | | | | 16.1. NEW COMMENT - BICYCLE PARKING SHOULD ALSO BE | | | PROVIDED IN A LOCATION THAT CAN EASILY BE FOUND AND | | | UTILIZED BY THE RETAIL USERS. | | | | | | 16.2. NEW COMMENT - THE PAD FOR THE BIKE RACKS SHOULD | | | BE A MINIMUM OF 72 INCHES IN LENGTH AND AT AT LEAST 24 | | | INCHES ON EITHER SIDE OF THE RACK. IF MORE THAN ONE | | | RACK IS PROVIDED, THERE SHALL BE AT LEAST 30 INCHES | | | BETWEEN THE RACKS. | | | | | | 17. SATISFIED - ENSURE THAT PLANS SHOW ALL WALLS, | | | FENCES, ETC. IF RETAINING WALLS ARE PROPOSED, | | | DETAILS/CROSS SECTIONS NEED TO BE PROVIDED. | | | | | | 18. SATISFIED - PARKING STRIPING DETAIL DOES NOT | | | CONFORM TO THE CITY?S MINIMUM STANDARDS. | | | | | | 19. SATISFIED - PLEASE CLARIFY THE DUMPSTER ENCLOSURE | | | DETAIL, IT LOOKS LIKE THE GATES CONSIST OF CHAIN LINK; | | | SUCH MATERIAL IS NOT PERMITTED. THE GATE NEEDS TO BE A | | | SOLID/OPAQUE MATERIAL. | | | | | | 20. NOT SATISFIED - PLEASE IDENTIFY THE VISIBILITY | | | TRIANGLES (AS DEFINED BY THE CITY?S ZLDRS) AT THE | | | INTERSECTIONS OF THE RIGHTS-OF-WAY. NO OBJECTS WITHIN | | | THE VISIBILITY TRIANGLE SHALL EXIST BETWEEN A HEIGHT OF | | | 18 INCHES AND 8 FEET. | | | | | | 21. SATISFIED - SCREEN WALLS SHALL BE PROVIDED ALONG | | | THE EAST PROPERTY LINE SEPARATING THE PARKING FROM THE | | | ADJACENT RESIDENTIAL USES [SEC. 94-443(A)(1)]. | | | | | | 22. NOT SATISFIED - PLEASE PROVIDE A CROSS SECTION | | | THROUGH THE ENTIRE SITE TO SHOW THE ELEVATION PROFILE, | | | ETC. AS THE PROPERTY SLOPES EAST/WEST. | | | | | | 23. SATISFIED - ALL BALCONIES, ROOF OVERHANGS, AWNINGS, | | | ETC. NEED TO BE SHOWN AND DIMENSIONED ON THE SITE PLAN. | | | PURSUANT TO SEC. 94-305(B)(2) SUCH ENCROACHMENTS SHALL | | | NOT EXTEND MORE THAN 3 FEET INTO A REQUIRED SETBACK. | | | | | | 24. NOT SATISFIED - CONFIRM THAT THE SQUARE FOOTAGES OF | | | THE NON-RESIDENTIAL USES ARE ACCURATE AND CONSISTENT. | | | THE SITE PLAN DOESN?T APPEAR TO MATCH THE FLOOR PLAN, | | | DATA TABLE, ETC. | | | | | | 25. SATISFIED (SUBJECT TO PAYMENT OF APPRAISED VALUE | | | UPON APPROVAL BY CITY COMMISSION) - IT IS THE CITY?S | | | POLICY FOR RIGHT-OF-WAY ABANDONMENTS THAT THE | | | PETITIONER PAY TO THE CITY THE APPRAISED VALUE OF THE | | | RIGHT-OF-WAY. PLEASE COORDINATE WITH VINCE NOEL ON | | | OBTAINING THE APPRAISAL, ETC. | | | | | | 26. NEW COMMENT - PLEASE MARK THE TURNAROUND SPACE WITH | | | A CROSS-HATCH INDICATING "NO PARKING". | | | | | | 27. NEW COMMENT - THE RIGHT GATE OF THE DUMPSTER | | | ENCLOSURE IMPEDES WITH THE EGRESS TRAVEL LANE. | | | | | | 28. NEW COMMENT - WHY ARE THE INGRESS AND EGRESS FROM | | | THE PARKING LOT DIFFERENT DIMENSIONS? IF A STRIPE IS | | | BEING PLACED BETWEEN THE TWO, SHOULDN'T IT BE PLACED IN | | | THE MIDDLE OF THE 20-FOOT DRIVE AISLE? | | | | | | 29. NEW COMMENT - ONLY FIVE (5) OF THE PARKING SPACES | | | ON TAMARIND AVENUE CAN COUNT TOWARD THE PROJECTS | | | "PARKING PROVIDED". PURSUANT TO THE ZLDRS, ONLY SPACES | | | THAT ARE ENTIRELY WITHIN THE BOUNDARY OF THE SUBJECT | | | PROPERTY CAN BE CONSIDERED. | | | | | | 30. NEW COMMENT - THE HEIGHT OF THE BUILDING EXCEEDS | | | THE MAXIMUM HEIGHT PERMITTED. THE MAXIMUM HEIGHT OF THE | | | BUILDING IS ALLOWED TO BE 30 FEET, WITH AN ADDITIONAL | | | 10% FOR DECORATIVE ELEMENTS, PARAPETS, ETC. AS SUCH, | | | THE TOP OF THE PARAPET IS NOT TO EXCEED 33 FEET. | | | | | | ________________________________________ | | | | | | PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING: | | | | | | A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL | | | DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION. | | | | | | B) ELECTRONIC COPY OF ALL PLANS AND DOCUMENTS SHALL BE | | | PROVIDED UPON RESUBMITTAL. | | | | | | C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO | | | ADDITIONAL COMMENTS. | | | | | | D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE | | | ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE | | | CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL | | | REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION. | | | | | | E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20% OF THE ORIGINAL APPLICATION FEE. | | | ________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | TTY: 800.955.8771 | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
01-13-2022 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
01-13-2022 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
01-13-2022 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2022-01-13 11:22:56 | PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW | | | ________________________________________ | | | | | | DATE OF REVIEW: 01.13.2022 | | | PROJECT NO.: Z21120020 AND Z21120015 | | | CASE NO.: ISPR 21-15 AND PB 1906 | | | ________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS: | | | | | | 1. APPROVAL LETTER FROM PALM BEACH COUNTY SHALL BE | | | PROVIDED INDICATING THAT THE PROJECT COMPLIES WITH THE | | | TRANSPORTATION PERFORMANCE STANDARDS (TRAFFIC | | | CONCURRENCY). | | | | | | 2. APPROVED SCHOOL CAPACITY AVAILABILITY DETERMINATION | | | SHALL BE PROVIDED FROM THE SCHOOL DISTRICT OF PALM | | | BEACH COUNTY. | | | | | | 3. LETTERS FROM ALL UTILITY COMPANIES SHALL BE PROVIDED | | | INDICATING THAT THE PROPOSED PROJECT DOES NOT ENCROACH | | | INTO THEIR EASEMENTS OR OTHERWISE INTERFERE WITH THEIR | | | ABILITY TO PROVIDE SERVICES. | | | | | | 4. JUSTIFICATION STATEMENT IS TO INCLUDE RESPONSES | | | INDICATING HOW THE PROPOSED DEVELOPMENT COMPLIES WITH | | | THE SITE PLAN REVIEW STANDARDS FOR CODE COMPLIANCE | | | [SEC. 94-35(C)]. | | | | | | 5. STAFF WOULD LIKE TO WORK WITH THE ARCHITECT ON THE | | | VARIOUS ELEMENTS OF THE ARCHITECTURAL STYLING. CONCERNS | | | INCLUDE: | | | | | | 6. ALL OF THE PROJECTS IS EXACTLY THE SAME. ALTERNATIVE | | | STYLES, OR VARIATIONS, SHOULD BE CONSIDERED ACROSS ALL | | | OF THE PROJECTS AS THEY ARE SEPARATE SITES ALONG THE | | | CORRIDOR AND READ INDEPENDENTLY OF ONE ANOTHER. | | | | | | 7. ADDITIONAL WINDOWS/OPENING ARE NEEDED ON THE | | | SIDES/REAR OF THE BUILDING TO PROVIDE BETTER | | | ARCHITECTURAL STYLING, NATURAL SURVEILLANCE, VISUAL | | | ENHANCEMENT TO THE NON-RESIDENTIAL SPACES, ETC. | | | | | | 8. GROUND FLOOR RESIDENTIAL UNITS FACING TAMARIND | | | AVENUE SHOULD INDIVIDUALLY READ AS WALK-UP UNITS WITH | | | THEIR FRONT/MAIN ENTRANCE FACING THE RIGHT-OF-WAY. | | | | | | 9. PHOTOMETRIC LEVELS NEED TO BE SHOWN AT THE PROPERTY | | | LINE. LEVELS SHALL NOT EXCEED 0.5 FOOTCANDLES WHEN | | | MEASURED AT THE PROPERTY LINE ADJACENT TO A RESIDENTIAL | | | ZONING DISTRICT. | | | | | | 10. THE SQUARE FOOTAGE OF THE AREA TO BE ABANDONED | | | SHOWN ON THE SITE PLAN IS NOT CONSISTENT WHAT IS | | | DESCRIBED IN THE SKETCH/LEGAL OF THE ABANDONMENT. | | | ENSURE THAT ALL PLANS/DOCUMENTS ARE ACCURATE AND | | | CONSISTENT. | | | | | | 11. PURSUANT TO SEC. 94-222(H)(5) ALL WINDOWS ARE TO BE | | | VERTICAL OR SQUARE IN PROPORTION. | | | | | | 12. PURSUANT TO SEC. 94-222(H)(6) ALL WINDOWS ARE TO BE | | | RECESSED A MINIMUM OF 2 INCHES FROM THE EXTERIOR FACE | | | OF THE FA?ADE. PLEASE PROVIDE A DETAIL. | | | | | | 13. PURSUANT TO SEC. 94-222(H)(7) ALL WINDOWS ARE TO BE | | | OPERABLE. PLEASE PROVIDE A DETAIL/NOTE. | | | | | | 14. PURSUANT TO SEC. 94-222(H)(10) SLIDING DOORS ARE | | | ONLY ALLOWED ON THE REAR FA?ADE. | | | | | | 15. STAFF HAS CONCERN THAT THE PROPOSED RETAIL SPACE IS | | | NOT OF SUFFICIENT SIZE TO PROVIDE FOR A VIABLE/LEASABLE | | | SPACE FOR A TENANT. PLEASE PROVIDE INFORMATION | | | INDICATING HOW THIS SPACE IS ENVISIONED TO BE UTILIZED | | | AND LEASED SUCCESSFULLY. | | | | | | 16. THE FAR CALCULATION IS INCORRECT. | | | | | | 17. THE CONSTRUCTION OF THE NEW ON-STREET PARKING IS | | | SUBJECT TO THE APPROVAL OF THE CITY?S ENGINEERING | | | SERVICES DEPARTMENT. | | | | | | 18. PLEASE CLEARLY IDENTIFY THE LOCATION OF THE | | | PROPOSED PROPERTY LINE ALONG TAMARIND AVENUE (IF | | | ABANDONMENT IS APPROVED). | | | | | | 19. BICYCLE PARKING SHALL BE PROVIDED IN ACCORDANCE | | | WITH SEC. 94-485(Q). INDICATE ALL LOCATIONS. | | | | | | 20. ENSURE THAT PLANS SHOW ALL WALLS, FENCES, ETC. IF | | | RETAINING WALLS ARE PROPOSED, DETAILS/CROSS SECTIONS | | | NEED TO BE PROVIDED. | | | | | | 21. PARKING STRIPING DETAIL DOES NOT CONFORM TO THE | | | CITY?S MINIMUM STANDARDS. | | | | | | 22. PLEASE CLARIFY THE DUMPSTER ENCLOSURE DETAIL, IT | | | LOOKS LIKE THE GATES CONSIST OF CHAIN LINK; SUCH | | | MATERIAL IS NOT PERMITTED. THE GATE NEEDS TO BE A | | | SOLID/OPAQUE MATERIAL. | | | | | | 23. PLEASE IDENTIFY THE VISIBILITY TRIANGLES (AS | | | DEFINED BY THE CITY?S ZLDRS) AT THE INTERSECTIONS OF | | | THE RIGHTS-OF-WAY. NO OBJECTS WITHIN THE VISIBILITY | | | TRIANGLE SHALL EXIST BETWEEN A HEIGHT OF 18 INCHES AND | | | 8 FEET. | | | | | | 24. SCREEN WALLS SHALL BE PROVIDED ALONG THE EAST | | | PROPERTY LINE SEPARATING THE PARKING FROM THE ADJACENT | | | RESIDENTIAL USES [SEC. 94-443(A)(1)]. | | | | | | 25. PLEASE PROVIDE A CROSS SECTION THROUGH THE ENTIRE | | | SITE TO SHOW THE ELEVATION PROFILE, ETC. AS THE | | | PROPERTY SLOPES EAST/WEST. | | | | | | 26. ALL BALCONIES, ROOF OVERHANGS, AWNINGS, ETC. NEED | | | TO BE SHOWN AND DIMENSIONED ON THE SITE PLAN. PURSUANT | | | TO SEC. 94-305(B)(2) SUCH ENCROACHMENTS SHALL NOT | | | EXTEND MORE THAN 3 FEET INTO A REQUIRED SETBACK. | | | | | | 27. CONFIRM THAT THE SQUARE FOOTAGES OF THE | | | NON-RESIDENTIAL USES ARE ACCURATE AND CONSISTENT. THE | | | SITE PLAN DOESN?T APPEAR TO MATCH THE FLOOR PLAN, DATA | | | TABLE, ETC. | | | | | | 28. IT IS THE CITY?S POLICY FOR RIGHT-OF-WAY | | | ABANDONMENTS THAT THE PETITIONER PAY TO THE CITY THE | | | APPRAISED VALUE OF THE RIGHT-OF-WAY. PLEASE COORDINATE | | | WITH VINCE NOEL ON OBTAINING THE APPRAISAL, ETC. | | | ________________________________________ | | | | | | PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING: | | | | | | A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL | | | DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION. | | | | | | B) ELECTRONIC COPY OF ALL PLANS AND DOCUMENTS SHALL BE | | | PROVIDED UPON RESUBMITTAL. | | | | | | C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO | | | ADDITIONAL COMMENTS. | | | | | | D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE | | | ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE | | | CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL | | | REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION. | | | | | | E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20% OF THE ORIGINAL APPLICATION FEE. | | | ________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | TTY: 800.955.8771 | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| |
Print |
|
Account Summary | Usage Policy | Privacy Policy