Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 12-09-2021 Cont ID  
Sent By rbrown Date 12-09-2021 Time 11:44 Rev Time 0.00
Received By rbrown Date 12-09-2021 Time 11:44 Sent To  
Notes
2021-12-09 11:48:07DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. THE ADDITION TO THE EXISTING BUILDING IS COVERED BY
 CHAPTER 11 OF THE FLORIDA EXISTING BUILDING CODE. THE
 HEIGHT AND/OR AREA INCREASE DUE TO THE PROPOSED
 ADDITION SHALL NOT INCREASE THE TOTAL BUILDING HEIGHT
 AND/OR AREA BEYOND THAT ALLOWED UNDER THE APPLICABLE
 PROVISIONS OF CHAPTER 5 OF THE FLORIDA BUILDING CODE
 FOR THE TYPE OF CONSTRUCTION USED.
  
 3. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 4. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND
 CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF
 CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL
 NEIGHBORING PROPERTIES.
  
 5. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 4 Status P Date 08-04-2022 Cont ID  
Sent By rrossano Date 08-04-2022 Time   Rev Time 0.00
Received By rrossano Date 08-04-2022 Time   Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 3 Status F Date 06-08-2022 Cont ID  
Sent By rrossano Date 06-08-2022 Time   Rev Time 0.00
Received By rrossano Date 06-08-2022 Time   Sent To  
Notes
2022-06-08 16:31:23COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPT., 561-494-1098
 [email protected] :
  
 GENERAL:
 O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (Z-XXXXXXXX).
 O THE CITY OF WEST PALM BEACH HAS A NUMBER OF
 REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY
 AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND
 WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE
 DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK
 BELOW:
 A. HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WP
 B_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FUL
 L-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97
 B1960045731D3658206F27451722716EF
 B. THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE
 FOUND HERE:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
 C. ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM
 BEACH, FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08,
 ADOPTED SEPT. 22, 2008. (SUPPLEMENT NO. 18)
 CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL,
 SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER
 SERVICE FACILITIES OF THE CITY.
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
 O AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, REFER TO THE LINK BELOW:
 A. HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PU
 BLICATIONS/BACKFLOW-CROSS-CONNECTION- CONTROL-MANUAL
 O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1079 FOR FURTHER
 ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION
 ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD
 SURVEY, POT-HOLING, SOFT DIGS ETC.
  
 BACKFLOW ASSEMBLY AND METERS (IF ANY):
 O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER
 SERVICES AND WATER METERS FOR THE PARKING LOTS, ALONG
 WITH WHAT IS HAPPENING TO THEM.
 O SHOW EXISTING AND PROPOSED DEDICATED UTILITY
 EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO
 PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO
 STRUCTURES WITHIN EASEMENT.
 O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION
 OF WATER METER AND BACKFLOW
 PREVENTION.
 O BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY
 OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER
 METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO
 PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE
 INSTALLED ABOVE-GROUND ONLY.
 O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE
 NOTE USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA.
  
 WATER/WASTEWATER PLAN:
 O PROVIDE VERTICAL DATUM AND DATUM CONVERSION
 INFORMATION (NAVD 1988 AND NGVD 1929).
 O SHOW PROJECT ADDRESS ON ALL PLAN SHEETS.
 O PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE
 STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC.
 O PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND
 DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND
 SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH
 PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE
 AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS,
 BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO
 BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS,
 DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS,
 ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT
 ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF
 SANITARY SEWER LINES.
 O GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR
 SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW.
 O DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN
 VIEW FOR ALL SANITARY AND STORM SEWERS.
 O SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL.
 O PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED
 UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC,
 ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION
 FACILITIES LOCATED ON THE RIGHT-OF-WAY.
 O PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER
 AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD
 DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS.
 O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY
 TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT
 APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING
 AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE,
 MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS
 SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008
 FOR WATER.
 O PROVIDE FIRE FLOW TEST DATA.
 O PLEASE CLEARLY INDICATE PROPOSED UTILITY CONNECTIONS
 (WATER, SEWER, STORMWATER).
 O PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND
 STORMWATER INFRASTRUCTURE ALONG ENTIRE PROJECT FRONTAGE
 IF CONNECTIONS ARE PROPOSED.
 O CUT AND CAP UTILITIES NOT IN USE AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 ROW.
 O WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL
 BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY
 PROPOSED LENGTH IN FEET.
 O CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY
 SEWER ARE REQUIRED.
 O PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE
 JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET.
 O ADD NOTE TO PLANS SPECIFYING CITY?S DOWNSTREAM LIFT
 STATION NUMBER.
 O PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR
 PROPOSED SANITARY LATERALS.
 O LABEL WATER LINES AS PRIVATE WHERE APPLICABLE.
 O PLEASE SHOW AND LABEL EXISTING AND PROPOSED GREASE
 TRAPS (IF ANY).
 O PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN
 OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER.
  
  
 QUESTIONS AND COORDINATION CONTACTS:
 O MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR WITH
 CITY OF WPB PUBLIC UTILITIES, REGARDING PLACEMENT OF
 BACKFLOW DEVICES AND WATER METERS. CONTACT HIM AT
 561-494-2262 OR [email protected]
 O RICK ROSSANO, SR. PROJECT COORDINATOR, ENGINEERING
 SERVICES DEPARTMENT AT 561-494-1098 [email protected]
 O MIKE TECHNOW, PROJECT ENGINEER, PUBLIC UTILITIES
 DEPARTMENT AT 561-494-1047 OR [email protected]
 O TRACY WARD, SR. STORMWATER ENGINEER, ENGINEERING
 SERVICES DEPT. AT 561-494-1120 OR [email protected]:
  
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status F Date 02-25-2022 Cont ID  
Sent By ldeloren Date 02-25-2022 Time   Rev Time 0.00
Received By ldeloren Date 02-25-2022 Time   Sent To  
Notes
2022-02-25 09:25:20COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPT., 561-494-1098
 [email protected] :
  
 PLEASE PROVIDE RESPONSES TO PREVIOUS REVIEW.
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-822-2262 OR
 [email protected]:
  
 -BACKFLOW ASSEMBLY LISTED ON IRRIGATION PLAN SAYS
 INDOOR INSTALLATION. INDOOR INSTALLATION IS NOT
 APPROVED IF IT IS A CONTAINMENT ASSEMBLY.
  
 -IF THE IRRIGATION BACKFLOW ASSEMBLY IS A CONTAINMENT
 DEVICE, THEN IT MUST BE RP TYPE INSTEAD OF PVB AND THE
 UPSTREAM PIPING MUST BE COMPLIANT TYPE INSTEAD OF PVC.
  
 -SURVEY SAYS THE BUILDING IS ENCROACHING IN 30 FOOT
 UTILITY EASEMENT. IF THE PROPOSED BUILDING CONSTRUCTION
 AREA WOULD ALSO ENCROACH IN THE EASEMENT, THEN
 IDENTIFY: UTILITIES IN EASEMENT, PURPOSE OF EASEMENT,
 AND APPROVAL OBTAINED TO BUILD IN EASEMENT.
  
 -VERIFY THAT TREE LOCATIONS ARE DISTANCED SUFFICIENTLY
 SO ROOTS WILL NOT DAMAGE METERED WATER SERVICES. CAN
 ALSO ADD ROOT BARRIERS AS NECESSARY.
  
 -WPB GIS INDICATES WATER MAIN IN ROAD IS NOT 2 INCH
 PVC. PLEASE UPDATE PLANS.
  
 -DID NOT RECEIVE WRITTEN RESPONSES FOR PRIOR REVIEW
 COMMENTS. ALSO SUBMIT WRITTEN RESPONSES FOR THE
 FOLLOWING:
  
 SUBMITTAL PACKAGE IS MISSING PROJECT NARRATIVE,
 JUSTIFICATION, AND SURVEY.
  
 PLANS DO NOT SHOW BLACK METAL FENCE AND GATES THAT ARE
 INSTALLED ALONG EASTERN SIDES OF PROPERTY. PLEASE
 UPDATE PLANS.
  
 METERED WATER SERVICE FOR PROPERTY DOES NOT HAVE AN
 ACTIVE USAGE ACCOUNT SETUP WITH CITY WPB UTILITY
 BILLING. APPLICANT WOULD NEED TO SET ONE UP AND PAY ALL
 APPLICABLE CHARGES, FEES, AND DEPOSITS BEFORE USING
 WATER SERVICE.
  
 BACKFLOW ASSEMBLY DOES NOT APPEAR TO BE INSTALLED FOR
 WATER SERVICE. APPLICANT WOULD NEED TO HAVE LICENSED
 PLUMBER INSTALL BEFORE WATER CAN BE USED. SHOW PROPOSED
 LOCATION ON PLANS.
  
 VERIFY EXISTING WATER AND SEWER INFRASTRUCTURE IS
 SUFFICIENT FOR PROPOSED IMPROVEMENTS. IF SERVICE
 UPGRADES ARE NEEDED, SUBMIT ENGINEERING PLAN SHOWING
 PROPOSED CHANGES.
  
 SOME OF THE LANDSCAPING TREES APPEAR TO BE PROPOSED IN
 LOCATIONS THAT ARE CURRENTLY HARDSCAPE.
  
 THERE ARE A FEW UTILITY POLES AT EAST PROPERTY LINE NOT
 SHOWN ON SITE PLAN. THE ONES AT TOWARD THE SOUTHEAST
 CORNER OF PROPERTY MAY CONFLICT WITH LANDSCAPING.
 PLEASE SHOW ON PLANS.
  
 ARE THERE ANY EXISTING OR PROPOSED FIRE SPRINKLERS FOR
 THE BUILDINGS?
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 12-02-2021 Cont ID  
Sent By rrossano Date 12-02-2021 Time   Rev Time  
Received By rrossano Date 12-02-2021 Time   Sent To  
Notes
2021-12-02 20:17:48Z21110003 - 2617 DIVISION AVE, SECOND FLOOR ADDITION
  
 COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR, ENG.
 SERVICES DEPT., 561-494-1098 [email protected] :
  
 GENERAL:
 O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (Z-XXXXXXXX).
 O THE CITY OF WEST PALM BEACH HAS A NUMBER OF
 REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY
 AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND
 WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE
 DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK
 BELOW:
 A. HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WP
 B_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FUL
 L-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97
 B1960045731D3658206F27451722716EF
 B. THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE
 FOUND HERE:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
 C. ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM
 BEACH, FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08,
 ADOPTED SEPT. 22, 2008. (SUPPLEMENT NO. 18)
 CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL,
 SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER
 SERVICE FACILITIES OF THE CITY.
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
 O AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, REFER TO THE LINK BELOW:
 A. HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PU
 BLICATIONS/BACKFLOW-CROSS-CONNECTION- CONTROL-MANUAL
 O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1079 FOR FURTHER
 ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION
 ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD
 SURVEY, POT-HOLING, SOFT DIGS ETC.
 O PLEASE PROVIDE ENGINEERING PLANS FOR REVIEW.
  
 BACKFLOW ASSEMBLY AND METERS (IF ANY):
 O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER
 SERVICES AND WATER METERS FOR THE PARKING LOTS, ALONG
 WITH WHAT IS HAPPENING TO THEM.
 O SHOW EXISTING AND PROPOSED DEDICATED UTILITY
 EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO
 PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO
 STRUCTURES WITHIN EASEMENT.
 O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION
 OF WATER METER AND BACKFLOW
 PREVENTION.
 O BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY
 OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER
 METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO
 PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE
 INSTALLED ABOVE-GROUND ONLY.
 O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE
 NOTE USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA.
  
 WATER/WASTEWATER PLAN:
 O PROVIDE VERTICAL DATUM AND DATUM CONVERSION
 INFORMATION (NAVD 1988 AND NGVD 1929).
 O SHOW PROJECT ADDRESS ON ALL PLAN SHEETS.
 O PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE
 STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC.
 O PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND
 DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND
 SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH
 PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE
 AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS,
 BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO
 BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS,
 DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS,
 ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT
 ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF
 SANITARY SEWER LINES.
 O GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR
 SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW.
 O DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN
 VIEW FOR ALL SANITARY AND STORM SEWERS.
 O SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL.
 O PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED
 UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC,
 ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION
 FACILITIES LOCATED ON THE RIGHT-OF-WAY.
 O PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER
 AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD
 DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS.
 O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY
 TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT
 APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING
 AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE,
 MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS
 SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008
 FOR WATER.
 O PROVIDE FIRE FLOW TEST DATA.
 O PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND
 STORMWATER INFRASTRUCTURE ALONG ENTIRE PROJECT FRONTAGE
 IF CONNECTIONS ARE PROPOSED.
 O CUT AND CAP UTILITIES NOT IN USE AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 ROW.
 O WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL
 BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY
 PROPOSED LENGTH IN FEET.
 O CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY
 SEWER ARE REQUIRED.
 O PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE
 JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET.
 O ADD NOTE TO PLANS SPECIFYING CITY?S DOWNSTREAM LIFT
 STATION NUMBER.
 O PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR
 PROPOSED SANITARY LATERALS.
 O LABEL WATER LINES AS PRIVATE WHERE APPLICABLE.
 O PLEASE SHOW AND LABEL EXISTING AND PROPOSED GREASE
 TRAPS (IF ANY).
 O PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN
 OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER.
  
 FORMAL ENGINEERING REVIEW:
 O FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES
 NOI REQUIREMENTS WILL BE ENFORCED.
 - AN NOI IS REQUIRED FOR PROJECTS THAT:
 - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS
 THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF
 DEVELOPMENT OR SALE;
 - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE
 STATE OR TO SURFACE WATERS OF THE STATE THROUGH A
 MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4).
 - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF
 CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION
 THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL
 SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT
 OF THE 10-2 CERTIFICATION.
 O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE
 EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS.
 O FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF
 WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS.
 O FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING
 APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT
 SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING
 SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED
 LEAD-FREE DESIGN.
 O FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES
 ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY
 LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT
 PARCELS.
 O FOR FORMAL ENGINEERING SUBMITTAL, IF WATER LINES ARE
 BEING REPLACED IN ROW, SHOW ADJACENT PARCEL ADDRESSES.
 O FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO PROVIDE
 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF
 ANY PROPOSED TRENCH IN CITY MAINTAINED ROADWAY AREAS
 PER CITY OF WPB STANDARD DETAIL GC-8.
 O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE
 CALCULATIONS OF PERVIOUS AND IMPERVIOUS AREAS FOR
 PROPOSED IMPROVED AREAS.
  
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-494-2262 OR
 [email protected]:
  
 -SUBMITTAL PACKAGE IS MISSING PROJECT NARRATIVE,
 JUSTIFICATION, AND SURVEY.
 -PLANS DO NOT SHOW BLACK METAL FENCE AND GATES THAT ARE
 INSTALLED ALONG EASTERN SIDES OF PROPERTY. PLEASE
 UPDATE PLANS.
 -METERED WATER SERVICE FOR PROPERTY DOES NOT HAVE AN
 ACTIVE USAGE ACCOUNT SETUP WITH CITY WPB UTILITY
 BILLING. APPLICANT WOULD NEED TO SET ONE UP AND PAY ALL
 APPLICABLE CHARGES, FEES, AND DEPOSITS BEFORE USING
 WATER SERVICE.
 -BACKFLOW ASSEMBLY DOES NOT APPEAR TO BE INSTALLED FOR
 WATER SERVICE. APPLICANT WOULD NEED TO HAVE LICENSED
 PLUMBER INSTALL BEFORE WATER CAN BE USED. SHOW PROPOSED
 LOCATION ON PLANS.
 -VERIFY EXISTING WATER AND SEWER INFRASTRUCTURE IS
 SUFFICIENT FOR PROPOSED IMPROVEMENTS. IF SERVICE
 UPGRADES ARE NEEDED, SUBMIT ENGINEERING PLAN SHOWING
 PROPOSED CHANGES.
 -SOME OF THE LANDSCAPING TREES APPEAR TO BE PROPOSED IN
 LOCATIONS THAT ARE CURRENTLY HARDSCAPE.
 -THERE ARE A FEW UTILITY POLES AT EAST PROPERTY LINE
 NOT SHOWN ON SITE PLAN. THE ONES AT TOWARD THE
 SOUTHEAST CORNER OF PROPERTY MAY CONFLICT WITH
 LANDSCAPING. PLEASE SHOW ON PLANS.
 -ARE THERE ANY EXISTING OR PROPOSED FIRE SPRINKLERS FOR
 THE BUILDINGS?
  
 NO COMMENTS FROM MICHAEL TECHNOW, PROJECT ENGINEER, WPB
 PUBLIC UTILITIES, 561-494-1047, [email protected]
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 QUESTIONS AND COORDINATION CONTACTS:
 O MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR WITH
 CITY OF WPB PUBLIC UTILITIES, REGARDING PLACEMENT OF
 BACKFLOW DEVICES AND WATER METERS. CONTACT HIM AT
 561-494-2262 OR [email protected]
 O RICK ROSSANO, SR. PROJECT COORDINATOR, ENGINEERING
 SERVICES DEPARTMENT AT 561-494-1098 [email protected]
 O MIKE TECHNOW, PROJECT ENGINEER, PUBLIC UTILITIES
 DEPARTMENT AT 561-494-1047 OR [email protected]
 O TRACY WARD, SR. STORMWATER ENGINEER, ENGINEERING
 SERVICES DEPT. AT 561-494-1120 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 08-02-2022 Cont ID  
Sent By pleduc Date 08-02-2022 Time 12:27 Rev Time 0.00
Received By pleduc Date 08-02-2022 Time 12:27 Sent To  
Notes
2022-08-02 12:30:51FIRE HAS NO OBJECTIONS TO THE PROPOSED AND APPROVES.
  
 HOWEVER, THERE IS A CONCERN REGARDING THE NORTH EXIT
 PATH BEYOND THE CONCRETE PAD.
  
 PLEASE ENSURE THE NORTH EXIT LEADS TO A PUBLIC WAY AND
 IS ACCESSIBLE PER NFPA AND BUILDING CODES WHEN BUILDING
 PERMIT IS APPLIED FOR.
  
 FIRE'S APPROVAL OF THIS SUBMITTED PROJECT MAY NOT
 CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 IF APPLICABLE, FIRE SHALL REVIEW ALL SUBMITTED PROJECT
 PLANS AT THE APPLICABLE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE FIRE CODES AND
 STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 12-06-2021 Cont ID  
Sent By pleduc Date 12-06-2021 Time   Rev Time 0.00
Received By pleduc Date 12-06-2021 Time 09:55 Sent To  
Notes
2021-12-06 09:59:20FIRE HAS NO OBJECTIONS TO THE PROPOSED AND APPROVES.
  
 FIRE'S APPROVAL OF THIS SUBMITTED PROJECT MAY NOT
 CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 FIRE SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT THE
 APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE FIRE CODES AND
 STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 3 Status P Date 06-10-2022 Cont ID  
Sent By rcaranci Date 06-10-2022 Time 15:14 Rev Time 0.00
Received By rcaranci Date 06-10-2022 Time 15:14 Sent To  
Notes
2022-06-10 15:15:14FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 2617 DIVISION AVE. Z21110003
 MARCH 8, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. FOR PERMIT 21100050, THE VALUE FOR THE
 ADDITION IS $250,000.00, AND THE VALUE OF THE
 STRUCTURES IS $440,284 FOR 2021 PER THE PALM BEACH
 COUNTY PROPERTY APPRAISER. THIS TRIGGERS COMPLIANCE
 WITH THE LANDSCAPE CODE FOR THE PROPERTY PER SECTION
 94-441(C)(2) AS THE EXEMPTION UP TO 50% HAS BEEN
 EXCEEDED.
  
 2. SATISFIED. ANY NEW PARKING CREATED SHOULD HAVE
 LANDSCAPING PROVIDED TO MEET THE REQUIREMENTS OF
 SECTION 94-443(C).
  
 3. SATISFIED. SUBMIT A LANDSCAPE PLAN MEETING THE
 REQUIREMENTS OF SECTION 94-442(B).
  
 4. SATISFIED. PROVIDE THE CALCULATIONS FOR THE MINIMUM
 REQUIRED SHADE TREES, FLOWERING TREES AND SHRUBS FOR
 THE SITE BASED ON 40% OPEN SPACE PER SECTION
 94-442(C)(2)B.
  
 5. PARTIALLY SATISFIED. PER SECTION 94-443(B) PROVIDE
 THE 5 FOOT LANDSCAPE BUFFER ALONG THE NORTH AND SOUTH
 PROPERTY LINE, AND THE 10 FOOT LANDSCAPE BUFFER
 ADJACENT TO THE DIVISION AVE. PUBLIC THOROUGHFARE FOR
 THE PORTIONS OF THE BUFFER THAT ARE NOT COVERED BY THE
 BUILDING AT ZERO SETBACK TO THE EXTENT POSSIBLE ON THE
 SITE.
  
 THE SITE PLAN AND THE LANDSCAPE PLAN DO NOT MATCH. IF
 THE SITE PLAN LAYOUT FOR THE PARKING IS CORRECT, THERE
 IS ADEQUATE SPACE TO PROVIDE THE 5 FOOT LANDSCAPE
 BUFFER ON THE SOUTH SIDE.
  
 6. SATISFIED. PER SECTION 94-443 (E)2., PROVIDE THE 20%
 FOUNDATION PLANTING CALCULATION REQUIRED AND PROVIDED
 FOR THE ENTIRE BUILDING.
  
 7. SATISFIED. PER SECTION 94-442(G) PROVIDE THE
 REQUIRED 50 POINTS FROM THE FLORIDA FRIENDLY DESIGN
 OPTIONS LIST.
  
 8. SATISFIED. PROVIDE A SECTION IN A LANDSCAPE DATA
 CHART TO COMPLY WITH SECTION 94-445 L. PLANT SPECIES. A
 MINIMUM OF 60 PERCENT OF PLANT MATERIAL ADDED SHALL BE
 FLORIDA NATIVE OR DROUGHT TOLERANT SPECIES SELECTED
 FROM THE CITY LIST OR THE LIST OF SPECIES IN THE MOST
 RECENT EDITION OF SOUTH FLORIDA WATER MANAGEMENT
 DISTRICT WATERWISE SOUTH FLORIDA LANDSCAPES. PROVIDE
 THE TOTAL PERCENTAGE OF NATIVE AND DROUGHT TOLERANT
 PLANTS BASED ON FINAL PLANT LIST.
  
  
  
 9. SATISFIED. PROVIDE THE NUMBER AND PERCENTAGE OF
 SUBSTITUTION OF PALMS FOR REQUIRED TREES. SECTION
 94-442(D) REQUIRES A 3:1 RATIO FOR SUBSTITUTION FOR
 PALMS EXCEPT THE LISTED 1:1 SPECIES.
  
 10. SATISFIED. PROVIDE LOCATIONS OF UTILITY LINES
 INCLUDING WATER, SEWER AND DRAINAGE AND RESOLVE
 CONFLICTS WITH LANDSCAPING.
  
 SHOW WATER LINE AND BACKFLOW AND SEWER LINE ON THE
 LANDSCAPE PLAN.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 03-08-2022 Cont ID  
Sent By rcaranci Date 03-08-2022 Time 14:25 Rev Time 0.00
Received By rcaranci Date 03-08-2022 Time 14:25 Sent To  
Notes
2022-03-08 14:34:37FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 2617 DIVISION AVE. Z21110003
 MARCH 8, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. FOR PERMIT 21100050, THE VALUE FOR THE
 ADDITION IS $250,000.00, AND THE VALUE OF THE
 STRUCTURES IS $440,284 FOR 2021 PER THE PALM BEACH
 COUNTY PROPERTY APPRAISER. THIS TRIGGERS COMPLIANCE
 WITH THE LANDSCAPE CODE FOR THE PROPERTY PER SECTION
 94-441(C)(2) AS THE EXEMPTION UP TO 50% HAS BEEN
 EXCEEDED.
  
 2. SATISFIED. ANY NEW PARKING CREATED SHOULD HAVE
 LANDSCAPING PROVIDED TO MEET THE REQUIREMENTS OF
 SECTION 94-443(C).
  
 3. SATISFIED. SUBMIT A LANDSCAPE PLAN MEETING THE
 REQUIREMENTS OF SECTION 94-442(B).
  
 4. SATISFIED. PROVIDE THE CALCULATIONS FOR THE MINIMUM
 REQUIRED SHADE TREES, FLOWERING TREES AND SHRUBS FOR
 THE SITE BASED ON 40% OPEN SPACE PER SECTION
 94-442(C)(2)B.
  
 5. PARTIALLY SATISFIED. PER SECTION 94-443(B) PROVIDE
 THE 5 FOOT LANDSCAPE BUFFER ALONG THE NORTH AND SOUTH
 PROPERTY LINE, AND THE 10 FOOT LANDSCAPE BUFFER
 ADJACENT TO THE DIVISION AVE. PUBLIC THOROUGHFARE FOR
 THE PORTIONS OF THE BUFFER THAT ARE NOT COVERED BY THE
 BUILDING AT ZERO SETBACK TO THE EXTENT POSSIBLE ON THE
 SITE.
  
 THE SITE PLAN AND THE LANDSCAPE PLAN DO NOT MATCH. IF
 THE SITE PLAN LAYOUT FOR THE PARKING IS CORRECT, THERE
 IS ADEQUATE SPACE TO PROVIDE THE 5 FOOT LANDSCAPE
 BUFFER ON THE SOUTH SIDE.
  
 6. SATISFIED. PER SECTION 94-443 (E)2., PROVIDE THE 20%
 FOUNDATION PLANTING CALCULATION REQUIRED AND PROVIDED
 FOR THE ENTIRE BUILDING.
  
 7. SATISFIED. PER SECTION 94-442(G) PROVIDE THE
 REQUIRED 50 POINTS FROM THE FLORIDA FRIENDLY DESIGN
 OPTIONS LIST.
  
 8. SATISFIED. PROVIDE A SECTION IN A LANDSCAPE DATA
 CHART TO COMPLY WITH SECTION 94-445 L. PLANT SPECIES. A
 MINIMUM OF 60 PERCENT OF PLANT MATERIAL ADDED SHALL BE
 FLORIDA NATIVE OR DROUGHT TOLERANT SPECIES SELECTED
 FROM THE CITY LIST OR THE LIST OF SPECIES IN THE MOST
 RECENT EDITION OF SOUTH FLORIDA WATER MANAGEMENT
 DISTRICT WATERWISE SOUTH FLORIDA LANDSCAPES. PROVIDE
 THE TOTAL PERCENTAGE OF NATIVE AND DROUGHT TOLERANT
 PLANTS BASED ON FINAL PLANT LIST.
  
  
  
 9. SATISFIED. PROVIDE THE NUMBER AND PERCENTAGE OF
 SUBSTITUTION OF PALMS FOR REQUIRED TREES. SECTION
 94-442(D) REQUIRES A 3:1 RATIO FOR SUBSTITUTION FOR
 PALMS EXCEPT THE LISTED 1:1 SPECIES.
  
 10. PARTIALLY SATISFIED. PROVIDE LOCATIONS OF UTILITY
 LINES INCLUDING WATER, SEWER AND DRAINAGE AND RESOLVE
 CONFLICTS WITH LANDSCAPING.
  
 SHOW WATER LINE AND BACKFLOW AND SEWER LINE ON THE
 LANDSCAPE PLAN.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 12-03-2021 Cont ID  
Sent By rcaranci Date 12-03-2021 Time 09:41 Rev Time 0.00
Received By rcaranci Date 12-03-2021 Time 09:41 Sent To  
Notes
2021-12-03 09:42:08FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 2617 DIVISION AVE. Z21110003
 DECEMBER 1, 2021
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. FOR PERMIT 21100050, THE VALUE FOR THE ADDITION IS
 $250,000.00, AND THE VALUE OF THE STRUCTURES IS
 $440,284 FOR 2021 PER THE PALM BEACH COUNTY PROPERTY
 APPRAISER. THIS TRIGGERS COMPLIANCE WITH THE LANDSCAPE
 CODE FOR THE PROPERTY PER SECTION 94-441(C)(2) AS THE
 EXEMPTION UP TO 50% HAS BEEN EXCEEDED.
  
 2. ANY NEW PARKING CREATED SHOULD HAVE LANDSCAPING
 PROVIDED TO MEET THE REQUIREMENTS OF SECTION 94-443(C).
  
 3. SUBMIT A LANDSCAPE PLAN MEETING THE REQUIREMENTS OF
 SECTION 94-442(B).
  
 4. PROVIDE THE CALCULATIONS FOR THE MINIMUM REQUIRED
 SHADE TREES, FLOWERING TREES AND SHRUBS FOR THE SITE
 BASED ON 40% OPEN SPACE PER SECTION 94-442(C)(2)B.
  
 5. PER SECTION 94-443(B) PROVIDE THE 5 FOOT LANDSCAPE
 BUFFER ALONG THE NORTH AND SOUTH PROPERTY LINE, AND THE
 10 FOOT LANDSCAPE BUFFER ADJACENT TO THE DIVISION AVE.
 PUBLIC THOROUGHFARE FOR THE PORTIONS OF THE BUFFER THAT
 ARE NOT COVERED BY THE BUILDING AT ZERO SETBACK TO THE
 EXTENT POSSIBLE ON THE SITE.
  
 6. PER SECTION 94-443 (E)2., PROVIDE THE 20% FOUNDATION
 PLANTING CALCULATION REQUIRED AND PROVIDED FOR THE
 ENTIRE BUILDING.
  
 7. PER SECTION 94-442(G) PROVIDE THE REQUIRED 50 POINTS
 FROM THE FLORIDA FRIENDLY DESIGN OPTIONS LIST.
  
 8. PROVIDE A SECTION IN A LANDSCAPE DATA CHART TO
 COMPLY WITH SECTION 94-445 L. PLANT SPECIES. A MINIMUM
 OF 60 PERCENT OF PLANT MATERIAL ADDED SHALL BE FLORIDA
 NATIVE OR DROUGHT TOLERANT SPECIES SELECTED FROM THE
 CITY LIST OR THE LIST OF SPECIES IN THE MOST RECENT
 EDITION OF SOUTH FLORIDA WATER MANAGEMENT DISTRICT
 WATERWISE SOUTH FLORIDA LANDSCAPES. PROVIDE THE TOTAL
 PERCENTAGE OF NATIVE AND DROUGHT TOLERANT PLANTS BASED
 ON FINAL PLANT LIST.
  
  
  
 9. PROVIDE THE NUMBER AND PERCENTAGE OF SUBSTITUTION OF
 PALMS FOR REQUIRED TREES. SECTION 94-442(D) REQUIRES A
 3:1 RATIO FOR SUBSTITUTION FOR PALMS EXCEPT THE LISTED
 1:1 SPECIES.
  
 10. PROVIDE LOCATIONS OF UTILITY LINES INCLUDING WATER,
 SEWER AND DRAINAGE AND RESOLVE CONFLICTS WITH
 LANDSCAPING.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PU-CS PUBLIC UTILITIES CUSTOMER SRVC
Rev No 1 Status P Date 08-15-2022 Cont ID  
Sent By mhurley Date 08-15-2022 Time 16:18 Rev Time 0.00
Received By mhurley Date   Time   Sent To  
Notes
2022-08-15 16:17:56CONDITION OF APPROVAL:
  
 ALL INSTALLED CONTAINMENT BACKFLOW ASSEMBLIES WILL BE
 RP TYPE AND LEAD-FREE.

Review Stop PW PUBLIC WORKS
Rev No 3 Status P Date 08-02-2022 Cont ID  
Sent By   Date 08-02-2022 Time   Rev Time 0.00
Received By   Date 08-02-2022 Time   Sent To  
Notes
2022-08-02 11:28:50CONDITIONS OF APPROVAL:
  
 1- ALL THE PARKING STALL PAINTING SHALL COMPLY WITH THE
 CITY`S MUNICIPAL CODE SECTION 94-485 AND FLORIDA
 STATUES [553.5041 F.S.].
 2- ALL STRIPING AND SIGNAGE SHALL MEET THE M.U.T.C.D.
 LATEST EDITION.
 3- ALL PAVEMENT MARKING AND SIGNING DAMAGED DURING
 CONSTRUCTION SHALL BE RESTORED.
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045
  

Review Stop PW PUBLIC WORKS
Rev No 2 Status F Date 06-01-2022 Cont ID  
Sent By   Date 06-01-2022 Time   Rev Time 0.00
Received By   Date 06-01-2022 Time   Sent To  
Notes
2022-06-01 12:14:50PLEASE PROVIDE:
 1- DUMPSTER(S) SOTORAGE AND STAGING AREA FOR SERVICE.
 2- DUMPSTER ENCLOSURE DETAIL, IF APPLICBLE. DETAILS FOR
 SANITATION SERVICE (I.E. SOLID WASTE CONTAINER(S) TYPE,
 COLLECTION LOCATION, ETC.). FOR A FREESTANDING SITE
 DUMPSTER ENCLOSURE, THE ENCLOSURE SHALL COMPLY WITH THE
 LATEST REVISION OF CITY OF WEST PALM BEACH GENERAL
 CONSTRUCTION-GARBAGE ENCLOSURE STANDARD, GC-7. (LINK TO
 THE LATEST REVISION OF THE GC-7 DOCUMENT: HTTPS://WWW.W
 PB.ORG/HOME/SHOWPUBLISHEDDOCUMENT/3690/6376290604221000
 00).
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045
  

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 12-08-2021 Cont ID  
Sent By   Date 12-08-2021 Time   Rev Time  
Received By   Date 12-08-2021 Time   Sent To  
Notes
2021-12-08 16:34:51PLEASE PROVIDE THE FOLLOWINGS:
 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID
 WASTE VOLUME PRODUCED ALONG WITH THE SIZE, TYPE AND
 QUANTITY OF THE CONTAINER (I.E. DUMPSTER/COMPACTOR)
 THAT WILL BE UTILIZED THAT WILL BE UTILIZED FOR THE
 SANITATION SERVICE.
 2- DETAILS FOR SANITATION SERVICE (I.E. SOLID WASTE
 CONTAINER(S) TYPE, COLLECTION LOCATION, ETC.).
  
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045

Review Stop STORM STORMWATER
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop SURVEY SURVEYING
Rev No 3 Status P Date 08-09-2022 Cont ID  
Sent By vnoel Date 08-09-2022 Time 13:51 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
***NONE***

Review Stop SURVEY SURVEYING
Rev No 2 Status F Date 03-07-2022 Cont ID  
Sent By vnoel Date 03-07-2022 Time 08:42 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2022-03-07 08:46:1330 FOOT EASEMENT IN REAR WAS PARTIALLY ABANDONED PER
 RESOLUTION 144-61. REDUCED FROM 30 FEET TO 6 FEET. COPY
 WAS PROVIDED TO PLANNER KEVIE DEFRANC.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 12-03-2021 Cont ID  
Sent By vnoel Date 12-03-2021 Time 09:04 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2021-12-03 09:04:411. NO SURVEY PROVIDED.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 3 Status P Date 08-09-2022 Cont ID  
Sent By   Date 08-09-2022 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2022-08-09 15:51:20**NO FURTHER COMMENTS**
  
 1) SATISFIED. PROVIDE TRAFFIC STUDY/STATEMENT
 2) SATISFIED. PROVIDE COUNTY TPS LETTER
 3) SATISFIED. ON THE SITE PLAN, PLEASE SHOWCASE BASIC
 CURB DETAILS (I.E. DRIVEWAY AND PARKING STALLS) ON THE
 OPPOSITE SIDE OF THE ROADS SURROUNDING THE PROPOSED
 DEVELOPMENT. PLEASE PROVIDE DOCUMENT NAME AND SHEET
 NUMBER SHOWCASING SUCH FEATURES.
 4) SATISFIED. MAXIMUM ALLOWABLE DRIVEWAY WIDTH IS 25
 FEET. PLEASE REVISE THE SITE PLAN ACCORDINGLY. LATEST
 SITE PLAN SHOWCASES A 22?6? DRIVEWAY.
 5) SATISFIED. CLEARLY IDENTIFY AND SHOWCASE DIMENSIONS
 OF THE DESIGNATED LOADING ZONE
 6) SATISFIED. PROVIDE AUTOTURN ANALYSIS FOR GARBAGE
 TRUCK AND/OR SERVICE VEHICLES DRIVING IN AND OUT OF THE
 PROPOSED DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES
 CLEARLY DEFINED. ANALYSIS SHOULD BE PROVIDED IN A
 SEPARATE FILE/DRAWING. PLEASE PROVIDE DOCUMENT NAME AND
 SHEET NUMBER SHOWCASING THE ANALYSIS.
 7) SATISFIED. PROVIDE PARKING TABLE SHOWCASING THE
 NUMBER OF EXISTING, REQUIRED AND PROVIDED PARKING
 SPACES, INCLUSIVE OF ADA AND BICYCLE ONES
 8) SATISFIED. THE CURB CUT ON THE NORTH SIDE OF THE
 PROPERTY MUST BE CLOSED. PER CITY CODE SEC
 914-312(1)(A), NONRESIDENTIAL DEVELOPMENTS WITH LESS
 THAN 300 REQUIRED PARKING SPACES CAN ONLY HAVE ONE
 ACCESS POINT INTO PUBLIC ROW
 9) SATISFIED. PARKING MANEUVERING ISSUE: STALLS #5 AND
 #6 ARE IN CONFLICT, AS VEHICLES MANEUVERING IN/OUT OF
 THE FORMER MAY BE OBSTRUCTED BY ANOTHER PARKED IN THE
 LATTER. PARKING STALLS #8 AND #9 SEEM TO HAVE SIMILAR
 MANEUVERABILITY ISSUES. PLEASE REVISE THE SITE PLAN TO
 SOLVE SUCH ISSUES ACCORDINGLY. OTHERWISE PROVIDE
 AUTOTURN ANALYSIS PROOFING SUCH PARKING STALLS
 CONFIGURATION FEASIBILITY.
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status F Date 06-10-2022 Cont ID  
Sent By   Date 06-10-2022 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2022-06-10 15:28:41TRAFFIC COMMENTS
 1) SATISFIED. PROVIDE TRAFFIC STUDY/STATEMENT
 2) NOT SATISFIED. PROVIDE COUNTY TPS LETTER
  
 SITE COMMENTS
 3) NOT SATISFIED. ON THE SITE PLAN, PLEASE SHOWCASE
 BASIC CURB DETAILS (I.E. DRIVEWAY AND PARKING STALLS)
 ON THE OPPOSITE SIDE OF THE ROADS SURROUNDING THE
 PROPOSED DEVELOPMENT. PLEASE PROVIDE DOCUMENT NAME AND
 SHEET NUMBER SHOWCASING SUCH FEATURES.
 4) SATISFIED. MAXIMUM ALLOWABLE DRIVEWAY WIDTH IS 25
 FEET. PLEASE REVISE THE SITE PLAN ACCORDINGLY. LATEST
 SITE PLAN SHOWCASES A 22?6? DRIVEWAY.
 5) NOT SATISFIED. CLEARLY IDENTIFY AND SHOWCASE
 DIMENSIONS OF THE DESIGNATED LOADING ZONE
 6) NOT SATISFIED. PROVIDE AUTOTURN ANALYSIS FOR GARBAGE
 TRUCK AND/OR SERVICE VEHICLES DRIVING IN AND OUT OF THE
 PROPOSED DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES
 CLEARLY DEFINED. ANALYSIS SHOULD BE PROVIDED IN A
 SEPARATE FILE/DRAWING. PLEASE PROVIDE DOCUMENT NAME AND
 SHEET NUMBER SHOWCASING THE ANALYSIS.
 7) SATISFIED. PROVIDE PARKING TABLE SHOWCASING THE
 NUMBER OF EXISTING, REQUIRED AND PROVIDED PARKING
 SPACES, INCLUSIVE OF ADA AND BICYCLE ONES
 8) THE CURB CUT ON THE NORTH SIDE OF THE PROPERTY MUST
 BE CLOSED. PER CITY CODE SEC 914-312(1)(A),
 NONRESIDENTIAL DEVELOPMENTS WITH LESS THAN 300 REQUIRED
 PARKING SPACES CAN ONLY HAVE ONE ACCESS POINT INTO
 PUBLIC ROW
 9) PARKING MANEUVERING ISSUE: STALLS #5 AND #6 ARE IN
 CONFLICT, AS VEHICLES MANEUVERING IN/OUT OF THE FORMER
 MAY BE OBSTRUCTED BY ANOTHER PARKED IN THE LATTER.
 PARKING STALLS #8 AND #9 SEEM TO HAVE SIMILAR
 MANEUVERABILITY ISSUES. PLEASE REVISE THE SITE PLAN TO
 SOLVE SUCH ISSUES ACCORDINGLY. OTHERWISE PROVIDE
 AUTOTURN ANALYSIS PROOFING SUCH PARKING STALLS
 CONFIGURATION FEASIBILITY.
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 12-09-2021 Cont ID  
Sent By   Date 12-09-2021 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2021-12-09 12:27:41TRAFFIC COMMENTS
 1) PROVIDE TRAFFIC STUDY/STATEMENT
 2) PROVIDE COUNTY TPS LETTER
  
 SITE COMMENTS
 3) ON THE SITE PLAN, PLEASE SHOWCASE BASIC CURB DETAILS
 (I.E. DRIVEWAY AND PARKING STALLS) ON THE OPPOSITE SIDE
 OF THE ROADS SURROUNDING THE PROPOSED DEVELOPMENT.
 PLEASE PROVIDE DOCUMENT NAME AND SHEET NUMBER
 SHOWCASING SUCH FEATURES.
 4) MAXIMUM ALLOWABLE DRIVEWAY WIDTH IS 25 FEET. PLEASE
 REVISE THE SITE PLAN ACCORDINGLY.
 5) CLEARLY IDENTIFY AND SHOWCASE DIMENSIONS OF THE
 DESIGNATED LOADING ZONE
 6) PROVIDE AUTOTURN ANALYSIS FOR GARBAGE TRUCK AND/OR
 SERVICE VEHICLES DRIVING IN AND OUT OF THE PROPOSED
 DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES CLEARLY
 DEFINED. ANALYSIS SHOULD BE PROVIDED IN A SEPARATE
 FILE/DRAWING. PLEASE PROVIDE DOCUMENT NAME AND SHEET
 NUMBER SHOWCASING THE ANALYSIS.
 7) PROVIDE PARKING TABLE SHOWCASING THE NUMBER OF
 EXISTING, REQUIRED AND PROVIDED PARKING SPACES,
 INCLUSIVE OF ADA AND BICYCLE ONES
  
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status P Date 08-11-2022 Cont ID  
Sent By kdefranc Date 08-11-2022 Time 10:56 Rev Time 0.00
Received By kdefranc Date 08-11-2022 Time 10:54 Sent To  
Notes
2022-08-11 10:56:218/11/22 ? PASSED
  
  
 PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN
 RESUBMITTING:
 A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
 B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED
 MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG
 WITH ONE (1) REDUCED COPY (11 IN X 17 IN).
 C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
 D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
 E. PLEASE NOTE THAT YOU ARE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. A RESUBMITTAL FEE OF
 20% OF THE ORIGINAL APPLICATION FEE WILL BE ASSESSED
 AFTER THE FIRST RESUBMITTAL. THEREFORE, PLEASE PROVIDE
 THE RESUBMITTAL FEE PAYMENT TO THE CITY.
  
 REQUIRED MATERIALS FOR INFORMAL SITE PLAN REVIEW
 APPLICATION PACKET SUBMITTAL MUST BE PROVIDED:
 F. PLEASE PROVIDE A COPY OF THE LAST RECORDED WARRANTY
 DEED FOR THE SUBJECT PROPERTY. [SATISFIED]
 G. PLEASE PROVIDE THE JUSTIFICATION STATEMENT LETTER,
 WHICH INCLUDES A GENERAL DESCRIPTION OF THE REQUEST,
 RELATED BACKGROUND INFORMATION ON THE PROJECT AND SITE,
 AND JUSTIFICATION, SPECIAL REASONS, OR BASIS FOR THE
 REQUEST. [SATISFIED]
 H. PLEASE PROVIDE A TRAFFIC CONCURRENCY/PERFORMANCE
 STANDARD REVIEW (TPS) LETTER FROM THE PALM BEACH COUNTY
 TRAFFIC DIVISION FOR THE SUBJECT PROJECT, AS STATED IN
 THE TRAFFIC ENGINEERING REVIEW COMMENTS. [SATISFIED PER
 TRANSPORTATION ENGINEERING REVIEW COMMENTS]
 I. PLEASE PROVIDE A REVISED/UPDATED/CURRENT SURVEY,
 ACCORDINGLY, AS STATED IN THE SURVEYING REVIEW
 COMMENTS. [SATISFIED]
 J. PLEASE PROVIDE A REVISED SITE PLAN ADDRESSING THE
 REVIEW COMMENTS BELOW. [PARTIALLY SATISFIED]
 K. PLEASE PROVIDE AN ENGINEERING PLAN, AS STATED IN THE
 ENGINEERING REVIEW COMMENTS. [SATISFIED PER ENGINEERING
 REVIEW]
 L. PLEASE PROVIDE ARCHITECTURAL DRAWINGS (ELEVATIONS,
 FLOOR PLANS, AND/OR PERSPECTIVES) OF THE PROPOSED
 BUILDING, SIGNS, FENCES/WALLS, AND OTHER STRUCTURES FOR
 THE PROJECT. [SATISFIED]
 M. PLEASE PROVIDE/INDICATE/DEMONSTRATE CONSISTENT
 INFORMATION ON THE DIFFERENT TYPES OF PLANS AND
 REQUIRED MATERIALS WITHIN THE APPLICATION PACKET
 RESUBMITTAL. [PARTIALLY SATISFIED]
  
 PREVIOUS REVIEW COMMENTS MUST BE ADDRESSED:
 1. PROVIDE A CURRENT SURVEY OF THE PROPERTY.
 [SATISFIED]
 2. THE SITE PLAN STATES, ?WAREHOUSE USE?. WHAT IS THE
 DEFINED/SPECIFIC USE OF THE BUSINESS GOING INTO THIS
 SPACE? [SATISFIED]
 3. THE ADDED SQUARE FOOTAGE WILL REQUIRE ADDITIONAL
 PARKING. (FOR WAREHOUSING - ONE SPACE PER 1000 SQ/FT ?
 2 ADDITIONAL SPACES) [SATISFIED]
 4. SHOW CURRENT AND PROPOSED PARKING ON SITE PLAN, WITH
 THE CITY?S APPROVED TYPICAL DIMENSIONS. [SATISFIED]
 5. THE VALUE OF THE PROJECT/DEVELOPMENT TRIGGERS
 LANDSCAPING REQUIREMENTS SET BY CODE. PLEASE SEE THE
 COMMENTS GENERATED BY LANDSCAPING. [SATISFIED PER
 LANDSCAPING REVIEW COMMENTS]
  
 SITE PLAN REVIEW COMMENTS MUST BE ADDRESSED:
 6. PLEASE IDENTIFY/INDICATE/DEFINE THE SPECIFIC
 (EXISTING AND PROPOSED) USE(S) FOR THE PRINCIPAL
 STRUCTURE ON THE SITE PLAN, SHEET SP-1. [SATISFIED]
 7. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE (EXISTING
 AND PROPOSED) SETBACK DIMENSIONS FOR THE PRINCIPAL
 STRUCTURE FROM ALL PROPERTY LINES ON THE SITE PLAN,
 SHEET SP-1. [SATISFIED]
 8. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE (EXISTING
 AND PROPOSED) HEIGHTS AND NUMBER OF STORIES FOR THE
 PRINCIPLE STRUCTURE ON THE SITE PLAN, SHEET SP-1.
 [SATISFIED]
 9. PLEASE IDENTIFY/INDICATE THE (EXISTING AND PROPOSED)
 POINTS OF ACCESS TO THE PRINCIPAL STRUCTURE ON THE SITE
 PLAN, SHEET SP-1. [SATISFIED]
 10. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION,
 HEIGHT, AND SIZE OF THE (EXISTING AND PROPOSED)
 FREESTANDING SIGNS AND OTHER ACCESSORY STRUCTURES ON
 THE SITE PLAN, SHEET SP-1. [SATISFIED]
 11. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION,
 HEIGHT AND INTENSITY OF ALL OUTDOOR ILLUMINATION ON THE
 SITE PLAN, SHEET SP-1. [SATISFIED]
 12. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION,
 DIMENSIONS, AND NUMBER OF BICYCLE PARKING SPACES ON THE
 SITE PLAN, SHEET SP-1. [SATISFIED]
 13. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 AND SCREENING OF THE GARBAGE RECEPTACLES ON THE SITE
 PLAN, SHEET SP-1. [SATISFIED]
 14. PLEASE PROVIDE THE STANDARD CITY DETAILS OF PARKING
 (ADA, STANDARD, AND BICYCLE), ADA RAMPS, DRIVEWAYS,
 DUMPSTERS, AND SIGNS. [SATISFIED]
 15. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION,
 HEIGHT, AND DIMENSIONS OF THE (EXISTING AND PROPOSED)
 FENCES, WALLS, AND SIDEWALKS ON THE SITE PLAN, SHEET
 SP-1. [SATISFIED]
 16. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE (EXISTING
 AND PROPOSED) EASEMENTS ON THE SITE PLAN, SHEET SP-1.
 [SATISFIED]
 17. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 OF ALL SPECIAL UTILITY AND ALL ABOVE GROUND
 APPURTENANCES ON THE SITE PLAN, SHEET SP-1. [SATISFIED]
 18. PLEASE INDIVIDUALLY IDENTIFY/INDICATE THE (EXISTING
 AND PROPOSED) PERCENT (WITH THE SQUARE FOOTAGE) OF OPEN
 SPACE IN THE SITE DATA TABLE ON THE SITE PLAN, SHEET
 SP-1. [PARTIALLY SATISFIED]
 19. PLEASE INDIVIDUALLY IDENTIFY/INDICATE THE (EXISTING
 AND PROPOSED) PERCENT (WITH THE SQUARE FOOTAGE) OF
 LANDSCAPING IN THE SITE DATA TABLE ON THE SITE PLAN,
 SHEET SP-1. [SATISFIED]
 20. PLEASE INDIVIDUALLY IDENTIFY/INDICATE THE (EXISTING
 AND PROPOSED) PERCENT (WITH THE SQUARE FOOTAGE) OF
 BUILDING COVERAGE IN THE SITE DATA TABLE ON THE SITE
 PLAN, SHEET SP-1. [PARTIALLY SATISFIED]
 21. PLEASE INDIVIDUALLY IDENTIFY/INDICATE THE (EXISTING
 AND PROPOSED) PERCENT (WITH THE SQUARE FOOTAGE) OF
 IMPERMEABLE SURFACE COVERAGE IN THE SITE DATA TABLE ON
 THE SITE PLAN, SHEET SP-1. [SATISFIED]
 22. PLEASE CORRECT THE INFORMATION PROVIDED FOR ACRES
 AND PERCENT OF WATER BODIES IN THE SITE DATA TABLE ON
 THE SITE PLAN, SHEET SP-1. [SATISFIED]
 23. PLEASE IDENTIFY/INDICATE THE REQUIRED STANDARD AND
 BICYCLE PARKING COMPUTATION AND PROPOSED BICYCLE
 PARKING COMPUTATION IN THE SITE DATA TABLE ON THE SITE
 PLAN, SHEET SP-1. [SATISFIED]
 24. PLEASE IDENTIFY/INDICATE THE (EXISTING AND
 PROPOSED) FLOOR AREA RATIOS (WITH THE SQUARE FOOTAGE)
 IN THE SITE DATA TABLE ON THE SITE PLAN, SHEET SP-1.
 [SATISFIED]
 25. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE (REQUIRED
 AND PROPOSED) LANDSCAPE BUFFERS ON THE SITE PLAN, SHEET
 SP-1, AND LANDSCAPE PLAN, SHEET L-1. [SATISFIED PER
 LANDSCAPING REVIEW COMMENTS]
 26. THE PROPOSED LOADING SPACE IS NOT MEETING THE
 MINIMUM LOADING SPACE DIMENSIONAL REQUIREMENTS PER THE
 CITY?S ZONING AND LAND DEVELOPMENT REGULATIONS
 SUBSECTION 94-485(P), SO PLEASE REVISE ACCORDINGLY ON
 THE SITE PLAN, SHEET SP-1. [SATISFIED]
  
 ADDITIONAL REVIEW COMMENT MUST BE ADDRESSED:
 27. PLEASE ROTATE/REPOSITION THE PROPOSED LOADING SPACE
 TO BE PERPENDICULAR TO DIVISION AVENUE OR RELOCATE TO
 AN AREA ON THE SITE WHERE IT WILL MEET THE MINIMUM
 REQUIRED LOADING SPACE DIMENSIONAL REQUIREMENTS AND
 HAVE NO ADVERSE IMPACT TO VEHICULAR
 MOVEMENT/MANEUVERING ON AND OFF SITE. [SATISFIED PER
 PLANNING AND ZONING ADMINISTRATOR, ANGELLA JONES-VANN?S
 DIRECTION]
  
 CONDITION OF APPROVAL:
 1. PRIOR TO ISSUANCE OF CONSTRUCTION AUTHORIZATION
 INCLUDING BUILDING PERMITS, PROVIDE CONSISTENT
 INFORMATION REGARDING THE OPEN SPACE CALCULATION ON THE
 SITE PLAN AND LANDSCAPE PLAN FOR THE MASTER BUILDING
 PERMIT AND LANDSCAPE SUB-PERMIT APPLICATION SUBMITTALS.
  
  
 KEVIE DEFRANC
 PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  

Review Stop Z ZONING
Rev No 3 Status F Date 06-14-2022 Cont ID  
Sent By kdefranc Date 06-14-2022 Time 10:21 Rev Time 0.00
Received By kdefranc Date 06-14-2022 Time 10:18 Sent To  
Notes
2022-06-14 10:20:456/14/22 ? FAILED
  
  
 PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN
 RESUBMITTING:
 A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
 B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED
 MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG
 WITH ONE (1) REDUCED COPY (11 IN X 17 IN).
 C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
 D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
 E. PLEASE NOTE THAT YOU ARE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. A RESUBMITTAL FEE OF
 20% OF THE ORIGINAL APPLICATION FEE WILL BE ASSESSED
 AFTER THE FIRST RESUBMITTAL. THEREFORE, PLEASE PROVIDE
 THE RESUBMITTAL FEE PAYMENT TO THE CITY.
  
 REQUIRED MATERIALS FOR INFORMAL SITE PLAN REVIEW
 APPLICATION PACKET SUBMITTAL MUST BE PROVIDED:
 F. PLEASE PROVIDE A COPY OF THE LAST RECORDED WARRANTY
 DEED FOR THE SUBJECT PROPERTY. [SATISFIED]
 G. PLEASE PROVIDE THE JUSTIFICATION STATEMENT LETTER,
 WHICH INCLUDES A GENERAL DESCRIPTION OF THE REQUEST,
 RELATED BACKGROUND INFORMATION ON THE PROJECT AND SITE,
 AND JUSTIFICATION, SPECIAL REASONS, OR BASIS FOR THE
 REQUEST. [SATISFIED]
 H. PLEASE PROVIDE A TRAFFIC CONCURRENCY/PERFORMANCE
 STANDARD REVIEW (TPS) LETTER FROM THE PALM BEACH COUNTY
 TRAFFIC DIVISION FOR THE SUBJECT PROJECT, AS STATED IN
 THE TRAFFIC ENGINEERING REVIEW COMMENTS. [NOT
 SATISFIED]
 I. PLEASE PROVIDE A REVISED/UPDATED/CURRENT SURVEY,
 ACCORDINGLY, AS STATED IN THE SURVEYING REVIEW
 COMMENTS. [SATISFIED]
 J. PLEASE PROVIDE A REVISED SITE PLAN ADDRESSING THE
 REVIEW COMMENTS BELOW. [PARTIALLY SATISFIED]
 K. PLEASE PROVIDE AN ENGINEERING PLAN, AS STATED IN THE
 ENGINEERING REVIEW COMMENTS. [NOT SATISFIED]
 L. PLEASE PROVIDE ARCHITECTURAL DRAWINGS (ELEVATIONS,
 FLOOR PLANS, AND/OR PERSPECTIVES) OF THE PROPOSED
 BUILDING, SIGNS, FENCES/WALLS, AND OTHER STRUCTURES FOR
 THE PROJECT. [SATISFIED]
 M. PLEASE PROVIDE/INDICATE/DEMONSTRATE CONSISTENT
 INFORMATION ON THE DIFFERENT TYPES OF PLANS AND
 REQUIRED MATERIALS WITHIN THE APPLICATION PACKET
 RESUBMITTAL. [PARTIALLY SATISFIED]
  
 PREVIOUS REVIEW COMMENTS MUST BE ADDRESSED:
 1. PROVIDE A CURRENT SURVEY OF THE PROPERTY.
 [SATISFIED]
 2. THE SITE PLAN STATES, ?WAREHOUSE USE?. WHAT IS THE
 DEFINED/SPECIFIC USE OF THE BUSINESS GOING INTO THIS
 SPACE? [SATISFIED]
 3. THE ADDED SQUARE FOOTAGE WILL REQUIRE ADDITIONAL
 PARKING. (FOR WAREHOUSING - ONE SPACE PER 1000 SQ/FT ?
 2 ADDITIONAL SPACES) [SATISFIED]
 4. SHOW CURRENT AND PROPOSED PARKING ON SITE PLAN, WITH
 THE CITY?S APPROVED TYPICAL DIMENSIONS. [SATISFIED]
 5. THE VALUE OF THE PROJECT/DEVELOPMENT TRIGGERS
 LANDSCAPING REQUIREMENTS SET BY CODE. PLEASE SEE THE
 COMMENTS GENERATED BY LANDSCAPING. [PARTIALLY
 SATISFIED]
  
 SITE PLAN REVIEW COMMENTS MUST BE ADDRESSED:
 6. PLEASE IDENTIFY/INDICATE/DEFINE THE SPECIFIC
 (EXISTING AND PROPOSED) USE(S) FOR THE PRINCIPAL
 STRUCTURE ON THE SITE PLAN, SHEET SP-1. [SATISFIED]
 7. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE (EXISTING
 AND PROPOSED) SETBACK DIMENSIONS FOR THE PRINCIPAL
 STRUCTURE FROM ALL PROPERTY LINES ON THE SITE PLAN,
 SHEET SP-1. [SATISFIED]
 8. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE (EXISTING
 AND PROPOSED) HEIGHTS AND NUMBER OF STORIES FOR THE
 PRINCIPLE STRUCTURE ON THE SITE PLAN, SHEET SP-1.
 [SATISFIED]
 9. PLEASE IDENTIFY/INDICATE THE (EXISTING AND PROPOSED)
 POINTS OF ACCESS TO THE PRINCIPAL STRUCTURE ON THE SITE
 PLAN, SHEET SP-1. [SATISFIED]
 10. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION,
 HEIGHT, AND SIZE OF THE (EXISTING AND PROPOSED)
 FREESTANDING SIGNS AND OTHER ACCESSORY STRUCTURES ON
 THE SITE PLAN, SHEET SP-1. [SATISFIED]
 11. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION,
 HEIGHT AND INTENSITY OF ALL OUTDOOR ILLUMINATION ON THE
 SITE PLAN, SHEET SP-1. [SATISFIED]
 12. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION,
 DIMENSIONS, AND NUMBER OF BICYCLE PARKING SPACES ON THE
 SITE PLAN, SHEET SP-1. [SATISFIED]
 13. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 AND SCREENING OF THE GARBAGE RECEPTACLES ON THE SITE
 PLAN, SHEET SP-1. [NOT SATISFIED]
 14. PLEASE PROVIDE THE STANDARD CITY DETAILS OF PARKING
 (ADA, STANDARD, AND BICYCLE), ADA RAMPS, DRIVEWAYS,
 DUMPSTERS, AND SIGNS. [PARTIALLY SATISFIED]
 15. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION,
 HEIGHT, AND DIMENSIONS OF THE (EXISTING AND PROPOSED)
 FENCES, WALLS, AND SIDEWALKS ON THE SITE PLAN, SHEET
 SP-1. [SATISFIED]
 16. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE (EXISTING
 AND PROPOSED) EASEMENTS ON THE SITE PLAN, SHEET SP-1.
 [SATISFIED]
 17. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 OF ALL SPECIAL UTILITY AND ALL ABOVE GROUND
 APPURTENANCES ON THE SITE PLAN, SHEET SP-1. [SATISFIED]
 18. PLEASE INDIVIDUALLY IDENTIFY/INDICATE THE (EXISTING
 AND PROPOSED) PERCENT (WITH THE SQUARE FOOTAGE) OF OPEN
 SPACE IN THE SITE DATA TABLE ON THE SITE PLAN, SHEET
 SP-1. [NOT SATISFIED]
 19. PLEASE INDIVIDUALLY IDENTIFY/INDICATE THE (EXISTING
 AND PROPOSED) PERCENT (WITH THE SQUARE FOOTAGE) OF
 LANDSCAPING IN THE SITE DATA TABLE ON THE SITE PLAN,
 SHEET SP-1. [SATISFIED]
 20. PLEASE INDIVIDUALLY IDENTIFY/INDICATE THE (EXISTING
 AND PROPOSED) PERCENT (WITH THE SQUARE FOOTAGE) OF
 BUILDING COVERAGE IN THE SITE DATA TABLE ON THE SITE
 PLAN, SHEET SP-1. [NOT SATISFIED]
 21. PLEASE INDIVIDUALLY IDENTIFY/INDICATE THE (EXISTING
 AND PROPOSED) PERCENT (WITH THE SQUARE FOOTAGE) OF
 IMPERMEABLE SURFACE COVERAGE IN THE SITE DATA TABLE ON
 THE SITE PLAN, SHEET SP-1. [SATISFIED]
 22. PLEASE CORRECT THE INFORMATION PROVIDED FOR ACRES
 AND PERCENT OF WATER BODIES IN THE SITE DATA TABLE ON
 THE SITE PLAN, SHEET SP-1. [SATISFIED]
 23. PLEASE IDENTIFY/INDICATE THE REQUIRED STANDARD AND
 BICYCLE PARKING COMPUTATION AND PROPOSED BICYCLE
 PARKING COMPUTATION IN THE SITE DATA TABLE ON THE SITE
 PLAN, SHEET SP-1. [SATISFIED]
 24. PLEASE IDENTIFY/INDICATE THE (EXISTING AND
 PROPOSED) FLOOR AREA RATIOS (WITH THE SQUARE FOOTAGE)
 IN THE SITE DATA TABLE ON THE SITE PLAN, SHEET SP-1.
 [SATISFIED]
 25. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE (REQUIRED
 AND PROPOSED) LANDSCAPE BUFFERS ON THE SITE PLAN, SHEET
 SP-1, AND LANDSCAPE PLAN, SHEET L-1. [PARTIALLY
 SATISFIED]
 26. THE PROPOSED LOADING SPACE IS NOT MEETING THE
 MINIMUM LOADING SPACE DIMENSIONAL REQUIREMENTS PER THE
 CITY?S ZONING AND LAND DEVELOPMENT REGULATIONS
 SUBSECTION 94-485(P), SO PLEASE REVISE ACCORDINGLY ON
 THE SITE PLAN, SHEET SP-1. [SATISFIED]
  
 ADDITIONAL REVIEW COMMENT MUST BE ADDRESSED:
 27. PLEASE ROTATE/REPOSITION THE PROPOSED LOADING SPACE
 TO BE PERPENDICULAR TO DIVISION AVENUE OR RELOCATE TO
 AN AREA ON THE SITE WHERE IT WILL MEET THE MINIMUM
 REQUIRED LOADING SPACE DIMENSIONAL REQUIREMENTS AND
 HAVE NO ADVERSE IMPACT TO VEHICULAR
 MOVEMENT/MANEUVERING ON AND OFF SITE.
  
  
 KEVIE DEFRANC
 PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  

Review Stop Z ZONING
Rev No 2 Status F Date 03-11-2022 Cont ID  
Sent By kdefranc Date 03-11-2022 Time 12:05 Rev Time 0.00
Received By kdefranc Date 03-11-2022 Time 12:03 Sent To  
Notes
2022-03-11 12:05:273/11/22 - FAILED
  
  
 PLEASE NOTE THE FOLLOWING PROCESS COMMENTS WHEN
 RESUBMITTING:
 A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
 B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND REQUIRED
 MATERIALS AND 2 SETS OF FOLDED PHYSICAL PLANS, ALONG
 WITH ONE (1) REDUCED COPY (11 IN X 17 IN).
 C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
 D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
 E. PLEASE NOTE THAT YOU ARE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. A RESUBMITTAL FEE OF
 20% OF THE ORIGINAL APPLICATION FEE WILL BE ASSESSED
 AFTER THE FIRST RESUBMITTAL. THEREFORE, PLEASE PROVIDE
 THE RESUBMITTAL FEE PAYMENT TO THE CITY.
  
 REQUIRED MATERIALS FOR INFORMAL SITE PLAN REVIEW
 APPLICATION PACKET SUBMITTAL MUST BE PROVIDED:
 F. PLEASE PROVIDE A COPY OF THE LAST RECORDED WARRANTY
 DEED FOR THE SUBJECT PROPERTY.
 G. PLEASE PROVIDE THE JUSTIFICATION STATEMENT LETTER,
 WHICH INCLUDES A GENERAL DESCRIPTION OF THE REQUEST,
 RELATED BACKGROUND INFORMATION ON THE PROJECT AND SITE,
 AND JUSTIFICATION, SPECIAL REASONS, OR BASIS FOR THE
 REQUEST.
 H. PLEASE PROVIDE A TRAFFIC CONCURRENCY/PERFORMANCE
 STANDARD REVIEW (TPS) LETTER FROM THE PALM BEACH COUNTY
 TRAFFIC DIVISION FOR THE SUBJECT PROJECT, AS STATED IN
 THE TRAFFIC ENGINEERING REVIEW COMMENTS.
 I. PLEASE PROVIDE A REVISED/UPDATED/CURRENT SURVEY,
 ACCORDINGLY, AS STATED IN THE SURVEYING REVIEW
 COMMENTS.
 J. PLEASE PROVIDE A REVISED SITE PLAN ADDRESSING THE
 REVIEW COMMENTS BELOW.
 K. PLEASE PROVIDE AN ENGINEERING PLAN, AS STATED IN THE
 ENGINEERING REVIEW COMMENTS.
 L. PLEASE PROVIDE ARCHITECTURAL DRAWINGS (ELEVATIONS,
 FLOOR PLANS, AND/OR PERSPECTIVES) OF THE PROPOSED
 BUILDING, SIGNS, FENCES/WALLS, AND OTHER STRUCTURES FOR
 THE PROJECT.
 M. PLEASE PROVIDE/INDICATE/DEMONSTRATE CONSISTENT
 INFORMATION ON THE DIFFERENT TYPES OF PLANS AND
 REQUIRED MATERIALS WITHIN THE APPLICATION PACKET
 RESUBMITTAL.
  
 PREVIOUS REVIEW COMMENTS MUST BE ADDRESSED:
 1. PROVIDE A CURRENT SURVEY OF THE PROPERTY. [PARTIALLY
 SATISFIED]
 2. THE SITE PLAN STATES, ?WAREHOUSE USE?. WHAT IS THE
 DEFINED/SPECIFIC USE OF THE BUSINESS GOING INTO THIS
 SPACE? [NOT SATISFIED]
 3. THE ADDED SQUARE FOOTAGE WILL REQUIRE ADDITIONAL
 PARKING. (FOR WAREHOUSING - ONE SPACE PER 1000 SQ/FT ?
 2 ADDITIONAL SPACES) [SATISFIED]
 4. SHOW CURRENT AND PROPOSED PARKING ON SITE PLAN, WITH
 THE CITY?S APPROVED TYPICAL DIMENSIONS. [PARTIALLY
 SATISFIED]
 5. THE VALUE OF THE PROJECT/DEVELOPMENT TRIGGERS
 LANDSCAPING REQUIREMENTS SET BY CODE. PLEASE SEE THE
 COMMENTS GENERATED BY LANDSCAPING. [PARTIALLY
 SATISFIED]
  
 SITE PLAN REVIEW COMMENTS MUST BE ADDRESSED:
 6. PLEASE IDENTIFY/INDICATE/DEFINE THE SPECIFIC
 (EXISTING AND PROPOSED) USE(S) FOR THE PRINCIPAL
 STRUCTURE ON THE SITE PLAN, SHEET SP-1.
 7. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE (EXISTING
 AND PROPOSED) SETBACK DIMENSIONS FOR THE PRINCIPAL
 STRUCTURE FROM ALL PROPERTY LINES ON THE SITE PLAN,
 SHEET SP-1.
 8. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE (EXISTING
 AND PROPOSED) HEIGHTS AND NUMBER OF STORIES FOR THE
 PRINCIPLE STRUCTURE ON THE SITE PLAN, SHEET SP-1.
 9. PLEASE IDENTIFY/INDICATE THE (EXISTING AND PROPOSED)
 POINTS OF ACCESS TO THE PRINCIPAL STRUCTURE ON THE SITE
 PLAN, SHEET SP-1.
 10. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION,
 HEIGHT, AND SIZE OF THE (EXISTING AND PROPOSED)
 FREESTANDING SIGNS AND OTHER ACCESSORY STRUCTURES ON
 THE SITE PLAN, SHEET SP-1.
 11. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION,
 HEIGHT AND INTENSITY OF ALL OUTDOOR ILLUMINATION ON THE
 SITE PLAN, SHEET SP-1.
 12. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION,
 DIMENSIONS, AND NUMBER OF BICYCLE PARKING SPACES ON THE
 SITE PLAN, SHEET SP-1.
 13. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 AND SCREENING OF THE GARBAGE RECEPTACLES ON THE SITE
 PLAN, SHEET SP-1.
 14. PLEASE PROVIDE THE STANDARD CITY DETAILS OF PARKING
 (ADA, STANDARD, AND BICYCLE), ADA RAMPS, DRIVEWAYS,
 DUMPSTERS, AND SIGNS.
 15. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION,
 HEIGHT, AND DIMENSIONS OF THE (EXISTING AND PROPOSED)
 FENCES, WALLS, AND SIDEWALKS ON THE SITE PLAN, SHEET
 SP-1.
 16. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE (EXISTING
 AND PROPOSED) EASEMENTS ON THE SITE PLAN, SHEET SP-1.
 17. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE LOCATION
 OF ALL SPECIAL UTILITY AND ALL ABOVE GROUND
 APPURTENANCES ON THE SITE PLAN, SHEET SP-1.
 18. PLEASE INDIVIDUALLY IDENTIFY/INDICATE THE (EXISTING
 AND PROPOSED) PERCENT (WITH THE SQUARE FOOTAGE) OF OPEN
 SPACE IN THE SITE DATA TABLE ON THE SITE PLAN, SHEET
 SP-1.
 19. PLEASE INDIVIDUALLY IDENTIFY/INDICATE THE (EXISTING
 AND PROPOSED) PERCENT (WITH THE SQUARE FOOTAGE) OF
 LANDSCAPING IN THE SITE DATA TABLE ON THE SITE PLAN,
 SHEET SP-1.
 20. PLEASE INDIVIDUALLY IDENTIFY/INDICATE THE (EXISTING
 AND PROPOSED) PERCENT (WITH THE SQUARE FOOTAGE) OF
 BUILDING COVERAGE IN THE SITE DATA TABLE ON THE SITE
 PLAN, SHEET SP-1.
 21. PLEASE INDIVIDUALLY IDENTIFY/INDICATE THE (EXISTING
 AND PROPOSED) PERCENT (WITH THE SQUARE FOOTAGE) OF
 IMPERMEABLE SURFACE COVERAGE IN THE SITE DATA TABLE ON
 THE SITE PLAN, SHEET SP-1.
 22. PLEASE CORRECT THE INFORMATION PROVIDED FOR ACRES
 AND PERCENT OF WATER BODIES IN THE SITE DATA TABLE ON
 THE SITE PLAN, SHEET SP-1.
 23. PLEASE IDENTIFY/INDICATE THE REQUIRED STANDARD AND
 BICYCLE PARKING COMPUTATION AND PROPOSED BICYCLE
 PARKING COMPUTATION IN THE SITE DATA TABLE ON THE SITE
 PLAN, SHEET SP-1.
 24. PLEASE IDENTIFY/INDICATE THE (EXISTING AND
 PROPOSED) FLOOR AREA RATIOS (WITH THE SQUARE FOOTAGE)
 IN THE SITE DATA TABLE ON THE SITE PLAN, SHEET SP-1.
 25. PLEASE IDENTIFY/INDICATE/DEMONSTRATE THE (REQUIRED
 AND PROPOSED) LANDSCAPE BUFFERS ON THE SITE PLAN, SHEET
 SP-1, AND LANDSCAPE PLAN, SHEET L-1.
 26. THE PROPOSED LOADING SPACE IS NOT MEETING THE
 MINIMUM LOADING SPACE DIMENSIONAL REQUIREMENTS PER THE
 CITY?S ZONING AND LAND DEVELOPMENT REGULATIONS
 SUBSECTION 94-485(P), SO PLEASE REVISE ACCORDINGLY ON
 THE SITE PLAN, SHEET SP-1.
  
  
 KEVIE DEFRANC
 PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1449
  

Review Stop Z ZONING
Rev No 1 Status F Date 12-06-2021 Cont ID  
Sent By awooten Date 12-06-2021 Time   Rev Time  
Received By awooten Date 12-06-2021 Time   Sent To  
Notes
2021-12-06 11:54:432617 DIVISION AVENUE PPRC DECEMBER 9, 2021
 INFORMAL SITE PLAN REVIEW
  
 PROVIDE A CURRENT SURVEY OF THE PROPERTY.
  
 THE SITE PLAN STATES, WAREHOUSE USE. WHAT IS THE
 DEFINED/SPECIFIC USE OF THE BUSINESS GOING INTO THIS
 SPACE?
  
 THE ADDED SQUARE FOOTAGE WILL REQUIRE ADDITIONAL
 PARKING. (FOR WAREHOUSING - ONE SPACE PER 1000 SQ/FT ?
 2 ADDITIONAL SPACES)
  SHOW CURRENT AND PROPOSED PARKING ON SITE PLAN, WITH
 THE CITY?S APPROVED TYPICAL DIMENSIONS.
  
 THE VALUE OF THE PROJECT/DEVELOPMENT TRIGGERS
 LANDSCAPING REQUIREMENTS SET BY CODE. PLEASE SEE THE
 COMMENTS GENERATED BY LANDSCAPING.
  
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  

  Print


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved