Plan Review Details - Project Z21100021
Plan Review Stops For Project Z21100021
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 11-29-2022 Cont ID  
Sent By scwelter Date 11-10-2021 Time 10:34 Rev Time 0.00
Received By swelter Date 11-29-2022 Time 11:27 Sent To  
Notes
2022-11-29 11:27:11SITE PLAN SHOWED POSSIBLE ART LOCATIONS.
 AT TIME OF BUDILING PERMIT FEES DEVELOPER MUST SUBMIT
 AN ART ASSESSMENT APPLICATION ALONG WITH EVIDENCE OF
 THE 1% ESCROW.
  
2021-11-10 10:38:54TOTAL CONSTRUCTION COSTS OF THIS DEVELOPMENT ARE OVER
 $500,000 IT IS SUBJECT TO THE PUBLIC ART REQUIREMENT AS
 PER CITY ORDINANCE.
 SECTION 78-129: ALL PRIVATE DEVELOPMENT PROJECTS,
 INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR
 IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL
 CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000 ARE SUBJECT TO THE PUBLIC ART REQUIREMENT.
 OPTION 1: INSTALL ARTWORK ON THE DEVELOPMENT SITE
 VALUED IN AN AMOUNT NOT LESS THAN ONE PERCENT OF THE
 TOTAL CONSTRUCTION COSTS; OR
 OPTION 2: CONTRIBUTE AN AMOUNT EQUAL TO 75 PERCENT OF
 ONE PERCENT OF THE TOTAL CONSTRUCTION COSTS FOR DEPOSIT
 TO THE PUBLIC ART ACCOUNT.
 A COMPLETED PUBLIC ART ASSESSMENT APPLICATION IS
 REQUIRED AT TIME OF BUILDING PERMIT SUBMITTAL.
  
 CONTACT SYBILLE WELTE, ADMINISTRATOR OF PUBLIC ART &
 CULTURE AT [email protected] TO OBTAIN AN ART ASSESSMENT
 APPLICATION AND TO REVIEW THE REQUIREMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 11-17-2021 Cont ID  
Sent By rbrown Date 11-17-2021 Time 19:48 Rev Time 0.00
Received By rbrown Date 11-17-2021 Time 19:48 Sent To  
Notes
2021-11-17 20:06:19DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. EGRESS FROM NEW OFFICE BUILDING. PLAN SHEET A0.05,
 PROJECT SITE PLAN, SHOWS BOTH STAIRS DISCHARGING WITHIN
 THE BUILDING. PER SECTION 1028.1 OF FLORIDA BUILDING
 CODE, AT LEAST 50% OF THE EXIT CAPACITY OF THE STAIRS
 MUST DISCHARGED TO THE OUTSIDE OF THE BUILDING WITHOUT
 OCCUPANTS HAVING TO TRAVERSE THROUGH THE BUILIDING
 AFTER LEAVING THE STAIR.
  
 3. LOCATION OF ACCESSIBLE PARKING SPACES. THE PLANS DO
 NOT CURRENTLY SHOW WHERE THE PROPOSED 22 ACCESSIBLE
 PARKING SPACES WILL BE LOCATED. PER SECTION 208.3 OF
 FLORIDA ACCESSIBILITY CODE, ACCESSIBLE PARKING SPACES
 ARE TO BE LOCATED ON THE SHORTEST POSSIBLE ROUTE OF
 TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE ENTRANCE.
 THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL COMPLY
 WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE.
  
 4. VAN ACCESSIBLE PARKING SPACES. THE PLANS DO NOT
 CURRENTLY SHOW ANY VAN ACCESSIBLE PARKING SPACES. PER
 SECTION 208.2.4 OF FLORIDA ACCESSIBILITY CODE, ONE IN
 EVERY SIX REQUIRED ACCESSIBLE SPACES (AT LEAST ONE) IN
 A PARKING STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND
 DESIGNED IN ACCORDANCE WITH SECTION OF 502 OF FLORIDA
 ACCESSIBILITY CODE (VERTICAL CLEARANCE NOT LESS THAN 98
 INCHES AT SPACE AND VEHICULAR ACCESS ROUTE)
  
 5. ACCESSIBLE PARKING SPACE AISLE. THE PLANS DO NOT
 CURRENTLY SHOW THE ACCESSIBLE PARKING SPACES AND
 ACCESSAISLES. ACCESSIBLE PARKING SPACE ACCESS AISLES
 SHALL BE LOCATED SO THAT THE USER IS NOT COMPELLED TO
 WALK OR WHEEL BEHIND ANOTHER PARKED VEHICLE OR IN THE
 TRAVEL LANE. THE ACCESS AISLES SHALL ALSO COMPLY WITH
 THE OTHER PROVISIONS OF SECTION OF 502.3 OF FLORIDA
 ACCESSIBILITY CODE.
  
 6. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 7. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES
 NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO
 MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL
 BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE
 EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED
 TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR
 OTHER APPROVED METHODS.
  
 8. THE ADDITION TO THE EXISTING BUILDING IS COVERED BY
 CHAPTER 11 OF THE FLORIDA EXISTING BUILDING CODE. THE
 HEIGHT AND/OR AREA INCREASE DUE TO THE PROPOSED
 ADDITION SHALL NOT INCREASE THE TOTAL BUILDING HEIGHT
 AND/OR AREA BEYOND THAT ALLOWED UNDER THE APPLICABLE
 PROVISIONS OF CHAPTER 5 OF THE FLORIDA BUILDING CODE
 FOR THE TYPE OF CONSTRUCTION USED.
  
 9. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 10. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND
 CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF
 CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL
 NEIGHBORING PROPERTIES.
  
 11. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 12. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT
 TO ART LIFE ASSESSMENT UNDER THE CITY OF WEST PALM
 BEACH ART IN PUBLIC PLACES (AIPP) PROGRAM. FOR ADVICE
 ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP
 ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 4 Status P Date 04-22-2022 Cont ID  
Sent By rrossano Date 04-22-2022 Time   Rev Time 0.00
Received By rrossano Date 04-22-2022 Time   Sent To  
Notes
2022-04-22 13:21:45CONDITIONS OF APPROVAL / PROVISO COMMENTS AS FOLLOWS:
  
 -PROPOSED WATER METER AND BACKFLOW ASSEMBLY LOCATIONS
 FOR 25 STORY BUILDING ARE NOT ACCEPTABLE AND WILL BE
 RELOCATED TO LOCATION REQUESTED BY CITY DURING FORMAL
 ENGINEERING SUBMITTAL.
  
 -WATER SERVICE TAPS AND PIPE DESIGN TO BE REVISED AS
 REQUESTED BY CITY DURING FORMAL ENGINEERING SUBMITTAL.
  
 -NO UTILITY EASEMENTS WILL BE VACATED WITHOUT APPROVAL
 OF WPB ENGINEERING DEPARTMENT.
  
 MARK HURLEY
 FIELD CUSTOMER SERVICE SUPERVISOR
 CITY OF WEST PALM BEACH PUBLIC UTILITIES
 561-822-2262
  
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 3 Status F Date 03-25-2022 Cont ID  
Sent By rrossano Date 03-25-2022 Time   Rev Time 0.00
Received By rrossano Date 03-25-2022 Time   Sent To  
Notes
2022-03-25 07:40:17NO COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR,
 ENG. SERVICES DEPT., 561-494-1098 [email protected]
  
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPERVISOR, [email protected]; 561-822-2262
  
 -THE TURN LANE ADDITION AND SIDEWALK RELOCATION ON
 OKEECHOBEE HAS SOME UNRESOLVED ISSUES: CIVIL PLAN SHOWS
 A COUPLE EXISTING LIGHT POLES IN THE TURN LANE PAVEMENT
 AND SOME EXISTING TREES IN THE PROPOSED CURBING; THE
 SIDEWALK RELOCATION WENT FROM RIGHT OF WAY TO PRIVATE
 PROPERTY SO A SIDEWALK EASEMENT MAY BE NEEDED; THERE IS
 CURRENTLY AN ELEVATION CHANGE BETWEEN SIDEWALK AND
 PROPERTY MAY CONFLICT WITH TURN LANE; EXISTING DOWNWARD
 STAIRS STILL SHOWING IN TURN LANE; SOUTH PROPERTY LINE
 IN MIDDLE OF TURN LANE ? WILL IT REMAIN LIKE THAT OR IS
 ADDITIONAL RIGHT OF WAY BEING DEDICATED AS MENTIONED IN
 OKEECHOBEE BLVD IMPROVEMENT LETTER - IF SO, SHOW
 PROPOSED BOUNDARIES; TWO EXISTING DRAINAGE STRUCTURES
 ARE LISTED TO REMAIN IN PROPOSED SIDEWALK; CALLOUT
 WIDTH OF PROPOSED PARKWAY BETWEEN SIDEWALK AND RIGHT
 TURN LANE AND MAKE SURE WIDTH MATCHES LANDSCAPING PLAN.
  
 -COULD NOT FIND UP-TO-DATE RESPONSE LETTER OR SUMMARY
 OF CHANGES IN RESUBMITTAL PACKAGE. PLEASE SUBMIT.
  
 -WPB PUBLIC UTILITIES HAD MEETING WITH APPLICANT?S
 CIVIL ENGINEERS WHERE CONCERNS WITH THE WATER SERVICES
 WERE DISCUSSED. CIVIL ENGINEERS TO EVALUATE FURTHER AND
 LIKELY REVISE WATER PLAN BEFORE PPRC CONCLUSION.
  
 -CIVIL PLAN SHOWS PROPOSED CURBING OVER EXISTING
 CONFLICT STRUCTURE NUMBER 19 NEAR SOUTH END OF NORTH
 ENTRANCE ISLAND.
  
 -CIVIL PLAN DOES NOT SHOW SIDEWALK ALONG NORTH SIDE OF
 NORTHWEST PROPOSED BUILDING THAT IS SHOWN ON HARDSCAPE
 AND ARCHITECTURAL PLANS. PLAN SETS SHOULD MATCH.
  
 -WHY DOES THE SIDEWALK EXTEND ALMOST THE FULL LENGTH OF
 THE NORTHWEST BUILDING ON THE NORTH SIDE. IS THERE A
 DOOR NOT SHOWN NEAR THE NORTHWEST CORNER OF BUILDING?
  
 -LANDSCAPE PLAN CONFLICTS WITH HARDSCAPE PLAN ON
 NORTHERN SIDE OF PROPOSED BUILDINGS. THERE ARE SOME
 BUSHES BLOCKING DOORS AND BUSHES PLANTED MIDDLE OF
 SIDEWALKS.
  
  
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status F Date 02-10-2022 Cont ID  
Sent By ldeloren Date 02-10-2022 Time   Rev Time 0.00
Received By ldeloren Date 02-10-2022 Time   Sent To  
Notes
2022-02-10 08:43:47COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR, ENG.
 SERVICES DEPT., 561-494-1098 [email protected] :
  
 PLEASE SEND CCTV FILES AND REPORTS TO ME AT RICK
 ROSSANO, PROJECT COORDINATOR, ENG. SERVICES DEPT., 401
 CLEMATIS ST., 4TH FL., 561-494-1098 [email protected].
 FLASH DRIVE, DISC OR D/L LINK ARE ALL OK.
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPERVISOR, [email protected]; 561-822-2262
  
 -EXISTING FIRELINE LOCATED NORTH OF RESTAURANT SHOWING
 AS 8 INCH IN OUR COMPUTER SYSTEM. SECTION OF WATER
 PIPING RUNNING SOUTH FROM NORTH ENTRANCE CANNOT
 ACCOMMODATE TWO ADDITIONAL FIRELINES SINCE THE WATER
 MAIN BRANCH IS ONLY 8 INCH. UPGRADES OR REVISIONS ARE
 NEEDED.
  
 -ON WATER PLAN, PLEASE LABEL ABOVE-GROUND CATV UTILITY
 BOX SOUTHEAST OF FIRE HYDRANT NEAR NORTH ENTRANCE.
  
 -PER WPB SANITARY COLLECTIONS DEPARTMENT, CITY
 INFRASTRUCTURE RUNS FROM EXISTING SANITARY MANHOLE
 NUMBER 8 NORTHWARD. ALL EXISTING AND PROPOSED SANITARY
 SEWER PIPES AND MANHOLES RUNNING SOUTHWEST AND
 SOUTHEAST FROM SANITARY MANHOLE NUMBER 8 WOULD BE
 PRIVATELY-OWNED.
  
 -UTILITY EASEMENTS NOT REQUIRED FOR PRIVATELY-OWNED
 SANITARY SEWER INFRASTRUCTURE ON SITE.
  
 -ARE THERE ANY SEWER LATERALS BETWEEN EXISTING BUILDING
 AND EXISTING SANITARY MANHOLE NUMBER 10?
  
 -IS THE PROPOSED UNDERGROUND STORAGE FOR OBJECTS OR FOR
 STORMWATER?
  
 -CIVIL PLANS SHOW FOUR LARGE ELECTRIC TRANSFORMERS IN
 THE ROUNDABOUT NEAR SOUTHEAST CORNER OF PROPERTY.
  
 -CONTRACTORS ARE CURRENTLY REPLACING THE LARGE UTILITY
 POLES NEAR EAST SIDE OF PROPERTY WITH BIGGER POLES.
 SHOW THE POLES ON THE CIVIL PLANS AND ENSURE NO
 CONFLICTS. ENSURE THAT ANY TREES PLANTED NEAR THEM WILL
 NOT TOUCH THE OVERHEAD WIRES.
  
 -PLANS SHOW CAF? IN PROPOSED CONFERENCE BUILDING.
 VERIFY IF GREASE TRAP NEEDED AND SHOW ON PLANS IF
 OUTDOORS.
  
 -PRIOR SUBMITTED REVIEW COMMENT ABOUT CONCRETE PAD.
 STILL DO NOT SEE IT ON PLANS. IT?S LOCATED AT THE FAR
 NORTHWEST CORNER OF PROPERTY NORTH OF CHILLER.
  
 -SHOW ALL EXISTING AND PROPOSED FDC. THERE ARE SOME
 NEAR THE NORTHWEST AREA OF EXISTING BUILDING NOT SHOWN
 ON WATER PLAN. CANNOT SEE ANY FOR GARAGE BUILDING OR 25
 STORY BUILDING.
  
 -LANDSCAPE PLANS SHOW IMPROVEMENTS ON CITY PROPERTY AT
 EAST SIDE. DID APPLICANT GET APPROVAL FROM CITY WPB AND
 LESSEE?
  
 -PROPOSED LANDSCAPING APPEARS TO ENCROACH ONTO FDOT
 PROPERTY AT NORTHEAST AREA OF PROPERTY. DOES FDOT
 APPROVE OF THAT?
  
 -SOME ASPECTS OF CIVIL PLANS DO NOT MATCH LANDSCAPING
 PLANS. PLEASE ENSURE THEY ARE BOTH UPDATED. CIVIL PLANS
 DO NOT SHOW CROSSWALK GOING TO GARAGE BUILDING FROM THE
 EAST OR THE LONG SIDEWALK ON CITY PARCEL.
  
 -CROSSWALK NEAR SOUTHEAST CORNER OF GARAGE BUILDING
 SEEMS TO DEADEND DUE TO LANDSCAPING BUSHES.
  
 -ENSURE NO TREES ARE PROPOSED TO BE PLANTED ABOVE 36
 INCH WATER MAIN.
  
 -LANDSCAPING APPEARS TO CONFLICT WITH PROPOSED METERS
 AND BACKFLOWS FOR 25 STORY BUILDING.
  
 -DOES THE GARAGE BUILDING NEED A METERED WATER SERVICE
 FOR DOMESTIC WATER?
  
 -IS A METERED WATER SERVICE FOR IRRIGATION NEEDED?
  
 -PLEASE PROVIDE THE VEHICLE CLEARANCE HEIGHT OF THE
 PEDESTRIAN BRIDGE AND THE GARAGE CROSSING.
  
 -WILL 25 STORY BUILDING HAVE RESTAURANT OR FOOD SERVICE
 REQUIRING GREASE TRAP? IF ONE REQUIRED AND WILL BE
 INSTALLED OUTDOORS, SHOW ON CIVIL PLANS.
  
 -SITE PLANS INDICATE WATER FEATURES IN ROUNDABOUT
 ISLANDS NEAR SOUTH SIDE OF PROPERTY, BUT LANDSCAPING
 PLANS SHOW TREES THERE. ARE THEY INCORRECT, OR ARE
 THERE BOTH TREES AND WATER FEATURES IN THE ISLANDS?
  
 -RECEIVED REVIEW COMMENT RESPONSE THAT EXISTING
 FIRELINE HAS A BACKFLOW ASSEMBLY. VISITED SITE AND
 COULD ONLY LOCATE SWING CHECK IN SIDEWALK VAULT. IT IS
 NOT A BACKFLOW ASSEMBLY AND DOES NOT OFFER THAT LEVEL
 OF WATER SYSTEM PROTECTION. UPON FURTHER REVIEW MAY
 NEED TO BE UPGRADED TO ABOVE-GROUND DCDA BACKFLOW
 ASSEMBLY. RECOMMEND PLANNING AHEAD OF TIME ESPECIALLY
 BECAUSE RELOCATION OUT OF SIDEWALK WOULD BE LIKELY.
  
 -SOME ASPECTS OF PROPOSED WATER SERVICES FOR 25 STORY
 BUILDING AND CONFERENCE BUILDING SEEM PROBLEMATIC AND
 SUBOPTIMAL. WOULD LIKE TO REVIEW IN MORE DETAIL WITH
 ENGINEER OF RECORD NOW TO PREVENT SIGNIFICANT CHANGES
 AT FORMAL ENGINEERING SUBMITTAL. PLEASE CONTACT
 [email protected].
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 11-17-2021 Cont ID  
Sent By rrossano Date 11-17-2021 Time   Rev Time  
Received By rrossano Date 11-17-2021 Time   Sent To  
Notes
2021-11-17 13:08:34COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR, ENG.
 SERVICES DEPT., 561-494-1098 [email protected] :
  
 PLEASE PROVIDE SEPARATE SHEETS FOR UTILITIES.
  
 GENERAL:
 O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (Z-XXXXXXXX).
 O THE CITY OF WEST PALM BEACH HAS A NUMBER OF
 REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY
 AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND
 WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE
 DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK
 BELOW:
 A. HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WP
 B_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FUL
 L-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97
 B1960045731D3658206F27451722716EF
 B. THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE
 FOUND HERE:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
 C. ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM
 BEACH, FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08,
 ADOPTED SEPT. 22, 2008. (SUPPLEMENT NO. 18)
 CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL,
 SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER
 SERVICE FACILITIES OF THE CITY.
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
 O AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, REFER TO THE LINK BELOW:
 A. HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PU
 BLICATIONS/BACKFLOW-CROSS-CONNECTION- CONTROL-MANUAL
 O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1079 FOR FURTHER
 ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION
 ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD
 SURVEY, POT-HOLING, SOFT DIGS ETC.
  
 BACKFLOW ASSEMBLY AND METERS:
  
 O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER
 SERVICES AND WATER METERS FOR THE PARKING LOTS, ALONG
 WITH WHAT IS HAPPENING TO THEM.
 O SHOW EXISTING AND PROPOSED DEDICATED UTILITY
 EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO
 PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO
 STRUCTURES WITHIN EASEMENT.
 O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION
 OF WATER METER AND BACKFLOW
 PREVENTION.
 O BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY
 OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER
 METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO
 PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE
 INSTALLED ABOVE-GROUND ONLY.
 O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE
 NOTE USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA.
  
  
  
 WATER/WASTEWATER PLAN:
 O PROVIDE VERTICAL DATUM AND DATUM CONVERSION
 INFORMATION (NAVD 1988 AND NGVD 1929).
 O SHOW PROJECT ADDRESS ON ALL PLAN SHEETS.
 O PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE
 STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC.
 O PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND
 DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND
 SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH
 PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE
 AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS,
 BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO
 BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS,
 DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS,
 ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT
 ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF
 SANITARY SEWER LINES.
 O GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR
 SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW.
 O DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN
 VIEW FOR ALL SANITARY AND STORM SEWERS.
 O SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL.
 O PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED
 UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC,
 ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION
 FACILITIES LOCATED ON THE RIGHT-OF-WAY.
 O PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER
 AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD
 DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS.
 O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY
 TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT
 APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING
 AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE,
 MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS
 SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008
 FOR WATER.
 O PROVIDE FIRE FLOW TEST DATA.
 O PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND
 STORMWATER INFRASTRUCTURE ALONG ENTIRE PROJECT
 FRONTAGE.
 O CUT AND CAP UTILITIES NOT IN USE AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 ROW.
 O WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL
 BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY
 PROPOSED LENGTH IN FEET.
 O CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY
 SEWER ARE REQUIRED.
 O PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE
 JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET.
 O ADD NOTE TO PLANS SPECIFYING CITY?S DOWNSTREAM LIFT
 STATION NUMBER.
 O PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR
 PROPOSED SANITARY LATERALS.
 O LABEL WATER LINES AS PRIVATE WHERE APPLICABLE.
 O PLEASE SHOW AND LABEL EXISTING AND PROPOSED GREASE
 TRAPS (IF ANY).
 O PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN
 OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER.
  
 FORMAL ENGINEERING REVIEW:
 O FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES
 NOI REQUIREMENTS WILL BE ENFORCED.
 - AN NOI IS REQUIRED FOR PROJECTS THAT:
 - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS
 THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF
 DEVELOPMENT OR SALE;
 - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE
 STATE OR TO SURFACE WATERS OF THE STATE THROUGH A
 MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4).
 - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF
 CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION
 THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL
 SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT
 OF THE 10-2 CERTIFICATION.
 O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE
 EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS.
 O FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF
 WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS.
 O FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING
 APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT
 SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING
 SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED
 LEAD-FREE DESIGN.
 O FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES
 ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY
 LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT
 PARCELS.
 O FOR FORMAL ENGINEERING SUBMITTAL, IF WATER LINES ARE
 BEING REPLACED IN ROW, SHOW ADJACENT PARCEL ADDRESSES.
 O FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO PROVIDE
 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF
 PROPOSED TRENCH IN CITY MAINTAINED ROADWAY AREAS PER
 CITY OF WPB STANDARD DETAIL GC-8.
 O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE
 CALCULATIONS OF PERVIOUS AND IMPERVIOUS AREAS FOR
 PROPOSED IMPROVED AREAS.
  
 QUESTIONS AND COORDINATION CONTACTS:
 O MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR WITH
 CITY OF WPB PUBLIC UTILITIES, REGARDING PLACEMENT OF
 BACKFLOW DEVICES AND WATER METERS. CONTACT HIM AT
 561-494-2262 OR [email protected]
 O RICK ROSSANO, SR. PROJECT COORDINATOR, ENGINEERING
 SERVICES DEPARTMENT AT 561-494-1098 [email protected]
 O MIKE TECHNOW, PROJECT ENGINEER, PUBLIC UTILITIES
 DEPARTMENT AT 561-494-1047 OR [email protected]
 O TRACY WARD, SR. STORMWATER ENGINEER, ENGINEERING
 SERVICES DEPT. AT 561-494-1120 OR [email protected]
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-494-2262 OR
 [email protected]:
  
 PLEASE PROVIDE WRITTEN RESPONSE TO THE FOLLOWING:
  
 -PLEASE SHOW ALL EXISTING AND PROPOSED GREASE
 TRAPS/INTERCEPTORS ON CIVIL PLANS.
  
 -PROPOSED WATER METERS AND BACKFLOW ASSEMBLIES NEED TO
 BE ADJACENT THE PROPERTY LINE. LOCATION SHOULD BE
 OUTSIDE OF ANY FENCES OR GATES AND EASILY ACCESSIBLE
 FROM THE ROW AND STREET. SMALL METER BOXES SHOULD NOT
 BE IN HARDSCAPE.
  
 -WATER METERS SIZED 3 INCH OR GREATER MUST BE INSTALLED
 ABOVE-GROUND AND ACCESSIBLE FROM THE STREET WITH CRANE
 TRUCK.
  
 -ENSURE THAT FIRELINE BACKFLOW ASSEMBLY LOCATIONS MEET
 NFPA REQUIREMENTS.
  
 -IF THERE WILL BE DEMOLITION, ADD DEMOLITION PLAN TO
 CIVIL PLAN SET.
  
 -SHOW ALL EXISTING AND PROPOSED UTILITIES ON SITE
 INCLUDING WATER METERS AND BACKFLOW ASSEMBLIES. PROVIDE
 ENLARGED DETAILS IN CIVIL PLANS OF AREAS AROUND METERS
 AND BACKFLOW ASSEMBLIES.
  
 -THERE IS A CONCRETE PAD IN NORTHWEST CORNER OF THE
 PROPERTY THAT IS NOT SHOWN IN SUBMITTAL PACKAGE
 INCLUDING SURVEY. PLANS SHOULD ADDRESS IT.
  
 -PROPOSED CONSTRUCTION ON EAST SIDE OF THE PROPERTY
 APPEARS TO CONFLICT WITH MULTIPLE EXISTING ELECTRIC
 UTILITIES AND ENCROACHES ON UTILITY EASEMENT.
  
 -IT IS DIFFICULT TO SEE DETAIL ON THE CIVIL PLAN.
 PLEASE ADD MORE SHEETS AND SEPARATE TYPES SUCH AS
 WATER/SEWER AND PAVING, GRADING, AND DRAINAGE.
  
 -PLEASE VERIFY IF ALL EXISTING FIRE HYDRANTS ON SITE
 ARE FED FROM THE EXISTING PRIVATE FIRELINE. UTILITY
 PLAN MAY NOT BE ACCURATELY DEPICTED.
  
 -ADD PRIVATE TO LABEL OF SEWER MANHOLES THAT ARE
 PRIVATELY MAINTAINED.
  
 -WATER MAIN SIZING AT CLEARWATER PARK RD MAY NOT BE
 ACCURATE AND LIMIT WATER SERVICE SIZING. RECOMMEND
 VERIFYING ALL PIPE SECTIONS NEAR THERE.
  
 -VERIFY EXISTING SEWER INFRASTRUCTURE (INCLUDING SEWER
 MAINS AND LIFT STATIONS) ARE SUFFICIENT FOR THE
 ADDITIONAL PROPOSED USAGE ON SITE.
  
 -SURVEY SHOWS CHILLER ENCROACHING ON UTILITY EASEMENT.
 PLEASE VERIFY THERE ARE NO CITY-OWNED UTILITIES
 UNDERNEATH CHILLER.
  
 -PLEASE VERIFY: IF THERE IS AN EXISTING FIRELINE
 BACKFLOW ASSEMBLY ON SITE; IF THE FIRELINE SYSTEM USES
 CHEMICAL ADDITIVES OR IS CONNECTED TO AN AUXILIARY
 WATER SYSTEM; WHEN THE EXISTING FIRE SYSTEM WAS LAST
 ALTERED.
  
 -FOR THE 10 FOOT UE THAT IS PROPOSED TO BE ABANDONED
 NEAR THE NORTH ENTRANCE, WHICH TYPE OF UTILITY IS IT
 FOR?
  
 -ARE ANY OUTSIDE GATES OR RESTRICTED AREAS PROPOSED ON
 SITE?
  
 -ADD WATER DEMAND CALCULATIONS TO WATER PLAN.
  
 -WPB GIS SHOWS LARGE DIAMETER SEWER PIPE RUNNING NEAR
 NORTHWEST CORNER OF PROPERTY. PLEASE SHOW ON SEWER
 PLAN.
  
 -VERIFY THERE ARE NO CONFLICTS BETWEEN TREES AND
 UTILITIES AND ADD SHEET IN LANDSCAPING PLANS THAT SHOW
 LOCATIONS OF TREES RELATIVE TO UTILITIES.
  
 -ARE THERE ANY EXISTING OR PROPOSED WELLS. IF SO, SHOW
 AND LABEL ON PLANS.
  
 COMMENTS FROM MICHAEL TECHNOW, PROJECT ENGINEER, WPB
 PUBLIC UTILITIES, 561-494-1047, [email protected] :
 PLEASE PROVIDE ADDITIONAL PLAN SHEETS WITH A SEPARATE
 UTILITY PLAN SHOWING EXISTING AND PROPOSED UTILITIES.
 COMMENTS FROM BURT BAIRD, CITY OF WPB UTILITIES O&M
 SUPERINTENDENT, 561-822-2056, [email protected] :
  
 ? PLEASE ENSURE ADDED FLOW CAN BE HANDLED BY LS# 41 AND
 LS# 43 - SEE EMAILED DOCUMENTS OF LS# 43 FLOW NUMBERS.
 ? LS# 43 IS ALREADY AT MAX FLOW NUMBERS ? SEE EMAILED
 BROWN AND CALDWELL STUDY
 ? LS# 41 AND LS# 43 NEED EXTENSIVE REPAIRS TO THE LIFT
 STATION BASED ON CONDITION ASSESSMENTS BY CDM SMITH
 ? REDESIGN THE WATER PLANTS BACK WASH SYSTEM FROM BEING
 DUMPED INTO THE WET WELL OF LS# 43
 ? LS# 43 OFTEN REQUIRES TWO PUMPS TO PUMP THE STATION
 DOWN- SEE EMAILED ?PUMP RUNS?
  
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By pleduc Date 11-10-2021 Time 15:29 Sent To  
Notes
2021-11-15 10:09:03THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT; HOWEVER, THE FOLLOWING COMMENTS ARE
 PROVIDED AND MAY NEED FURTHER CLARIFICATIONS WHERE
 APPLICABLE.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. ALL PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A,
 PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE,
 INCLUDING MORE SPECIFICALLY, CHAPTER 42 STORAGE
 OCCUPANCIES (PARKING STRUCTURES)
  
 7. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA
 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THIS
 STRUCTURE. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE
 BUILDING REACHES THREE LEVELS OR THIRTY FEET WHILE
 BEING CONSTRUCTED. SEPARATE SHOP DRAWINGS, ARE REQUIRED
 TO BE SUBMITTED, REVIEWED AND APPROVED BY THE FIRE
 PREVENTION BUREAU PRIOR TO ANY INSTALLATION.
  
 IT IS RECOMMENDED FOR HIGH RISES HAVE TWO SEPARATE FDC
 LOCATIONS REMOTELY LOCATED.
  
 7A. PER NFPA 14
 6.4.5.4* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED
 NOT MORE THAN 100 FT (30.5 M) FROM THE NEAREST FIRE
 HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY.
  
 7B. PER NFPA 1
  
 18.3 WATER SUPPLIES.
 18.3.1* AN APPROVED WATER SUPPLY CAPABLE OF SUPPLYING
 THE REQUIRED FIRE FLOW FOR FIRE PROTECTION SHALL BE
 PROVIDED TO ALL PREMISES UPON WHICH FACILITIES,
 BUILDINGS, OR PORTIONS OF BUILDINGS ARE HEREAFTER
 CONSTRUCTED OR MOVED INTO THE JURISDICTION. THE
 APPROVED WATER SUPPLY SHALL BE IN ACCORDANCE WITH
 SECTION 18.4.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 FOR THE PROPOSED FIRE PUMP(S) , WHAT IS(ARE) THE
 PRIMARY AND SECONDARY POWER SOURCES?
  
 7C. THE LOCATION OF THE DDCV FIRE LINE LOCATION SHALL
 MEET THE REQUIREMENTS OF NFPA 24 AND SHALL BE
 COORDINATED WITH THE OFFICE OF FIRE MARSHAL, THE CITY'S
 ENGINEERS OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S
 PLANNING AND ZONING OFFICE.
  
 8. A CLASS ?A? NFPA 72 COMPLIANT MONITORED FIRE ALARM
 SYSTEM IS REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP
 DRAWINGS, ARE REQUIRED TO BE SUBMITTED, REVIEWED AND
 APPROVED BY THE FIRE PREVENTION BUREAU PRIOR TO ANY
 INSTALLATION.
  
 9. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7
 KEYWAY SYSTEM FOR BUILDINGS OVER 6 FLOORS.
  
 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTER?S
 EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA
 B44, SAFETY CODE FOR ELEVATORS.
  
 ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET
 MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN
 AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE
 IN THE HORIZONTAL POSITION.
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 11. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE
 BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND
 FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET
 OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER
 ARRIVING EMERGENCY VEHICLES.
  
 12.HIGH RISE EMERGENCY COMMAND ROOM
  
 THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1,
 CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN
 THE FOLLOWING FEATURES:
  
 11.9.1 THE LOCATION, DESIGN, CONTENT, AND FIRE
 DEPARTMENT ACCESS OF THE EMERGENCY COMMAND CENTER SHALL
 BE APPROVED BY THE FIRE DEPARTMENT.
 11.9.2 THE EMERGENCY COMMAND CENTER SHALL BE SEPARATED
 FROM THE REMAINDER OF THE BUILDING BY A FIRE BARRIER
 HAVING A FIRE RESISTANCE RATING OF NOT LESS THAN 1
 HOUR.
 11.9.3 THE EMERGENCY COMMAND CENTER ROOM SHALL BE A
 MINIMUM OF 200 FT2 (19 M2) WITH A MINIMUM DIMENSION OF
 10 FT (3050 MM).
 11.9.4 THE FOLLOWING SHALL BE PROVIDED IN THE EMERGENCY
 COMMAND CENTER.
 (1) THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM.
 (2) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM
 (3) SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT AND FIRE DEPARTMENT ACCESS
 (4) WORK TABLE.
 (5) IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN
 FOR THE BUILDING.
 11.9.5 WHERE OTHERWISE REQUIRED, THE FOLLOWING DEVICES
 OR FUNCTIONS SHALL BE PROVIDED WITHIN THE EMERGENCY
 COMMAND CENTER.
 (1) THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 CONTROL UNIT.
 (2) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT.
 (3) ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION
 OF THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL
 (4) STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING
 SYSTEMS.
 (5) CONTROLS FOR UNLOCKING STAIRWAY DOORS
 SIMULTANEOUSLY
 (6) SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY
 PANELS
 (7) EMERGENCY AND STANDBY POWER STATUS INDICATORS
 (8) FIRE PUMP STATUS INDICATORS
 (9) GENERATOR SUPERVISION DEVICES AND MANUAL START AND
 TRANSFER FEATURES.
 (10) PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE
 (11) CONTROLS REQUIRED FOR SMOKE CONTROL
  
 NFPA 101
  
 11.8.6* EMERGENCY COMMAND CENTER.
 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED
 IN A
 LOCATION APPROVED BY THE FIRE DEPARTMENT.
 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE
 FOLLOWING:
 (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS
 (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION
 SERVICE
 PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER SECTION
 OF THIS
 CODE
 (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION
 PANELS
 (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS
 (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS
 (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE
 PROVIDED
 IN ACCORDANCE WITH ASME A17.1/CSA B44
 (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS
 (8) EMERGENCY GENERATOR STATUS INDICATORS
 (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING
 SYSTEM
 (10) FIRE PUMP STATUS INDICATORS
 (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE
 PUBLIC TELEPHONE SYSTEM
 (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY
 11.8.8
  
 13. EMERGENCY RADIO COMMUNICATIONS
  
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
  
 NFPA 72, 24.9 TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT
 SYSTEMS.
 24.9.1 GENERAL.
 24.9.1.1 NON-INTERFERENCE. NO AMPLIFICATION SYSTEM
 CAPABLE
 OF OPERATING ON FREQUENCIES OR CAUSING INTERFERENCE ON
 FREQUENCIES
 ASSIGNED TO THE JURISDICTION BY THE FCC SHALL BE
 INSTALLED
 WITHOUT PRIOR COORDINATION AND APPROVAL OF THE
 AUTHORITY
 HAVING JURISDICTION. THE BUILDING MANAGER/OWNER SHALL
 SUSPEND AND CORRECT OTHER EQUIPMENT INSTALLATIONS THAT
 DEGRADE
 THE PERFORMANCE OF THE PUBLIC SAFETY RADIO SYSTEM OR
 PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM.
 24.9.1.2 APPROVAL AND PERMIT. PLANS SHALL BE SUBMITTED
 FOR
 APPROVAL PRIOR TO INSTALLATION. AT THE CONCLUSION OF
 SUCCESSFUL
 ACCEPTANCE TESTING, A RENEWABLE PERMIT SHALL BE ISSUED
 FOR THE
 PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM WHERE REQUIRED
 BY
 THE AUTHORITY HAVING JURISDICTION.
  
 THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL
 STRENGTH OF -95 DBM FOR THE RADIO SYSTEM USED BY WEST
 PALM BEACH FIRE DEPARTMENT. TESTING SHALL BE BY AN
 ACCEPTABLE NATIONAL STANDARD DOCUMENTING PERCENTAGES
 NOTED ABOVE AND BY ACTUAL RADIO TESTING BY FIRE
 PERSONNEL. IF THE MINIMUM CANNOT BE MAINTAINED, A
 BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH
 A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP.
 PLEASE CONTACT MARK FILLA, PALM BEACH COUNTY PUBLIC
 SAFETY RADIO SYSTEMS MANAGER, [email protected],
 561-233-0837; AS OUR RADIOS OPERATE ON THEIR SYSTEM FOR
 DETAILED RADIO FREQUENCY AND INSTALLATION INSTRUCTIONS.
  
  
 14. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING.
  
 ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS,
 PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS.
  
 15. THE HIGH RISE SMOKE CONTROL SYSTEM SHALL COMPLY
 WITH NFPA 101, CHAPTER 9, BUILDING SERVICE AND FIRE
 PROTECTION EQUIPMENT, INCLUDING:
  
 THE SMOKE CONTROL SYSTEMS SHALL BE INSTALLED,
 INSPECTED, TESTED, AND MAINTAINED IN ACCORDANCE WITH
 NFPA 92, STANDARD FOR SMOKE CONTROL SYSTEMS; NFPA 204,
 STANDARD FOR SMOKE AND HEAT VENTING; OR NATIONALLY
 RECOGNIZED STANDARDS, ENGINEERING GUIDES, OR
 RECOMMENDED PRACTICES, AS APPROVED BY THE AUTHORITY
 HAVING JURISDICTION.
  
 THE ENGINEER OF RECORD SHALL CLEARLY IDENTIFY THE
 INTENT OF THE SYSTEM, THE DESIGN METHOD USED, THE
 APPROPRIATENESS OF THE METHOD USED, AND THE REQUIRED
 MEANS OF INSPECTING, TESTING, AND MAINTAINING THE
 SYSTEM.
  
 ACCEPTANCE TESTING SHALL BE PERFORMED BY A SPECIAL
 INSPECTOR IN ACCORDANCE WITH SECTION 9.9.
  
 16. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 17. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 5 Status P Date 05-16-2022 Cont ID  
Sent By rcaranci Date 05-16-2022 Time 16:18 Rev Time 0.00
Received By rcaranci Date 05-16-2022 Time 16:18 Sent To  
Notes
2022-05-16 16:19:47FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 1001 OKEECHOBEE Z21100021
 MAY 16, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE
 TREES AND PALMS IN GOOD CONDITION TO BE PRESERVED ON
 SITE OR RELOCATED. ANSI A 300 (PART 5) STANDARDS
 SPECIFY EXAMPLES OF SUITABILITY RATINGS OF GOOD,
 MODERATE, OR POOR FOR RELOCATION. PROVIDE AN ARBORISTS
 REPORT RATING THE CONDITION AND RELOCATION POTENTIAL
 FOR THE NATIVE TREES AND PALMS. THERE ARE LIVE OAKS,
 SABAL PALMS, FLORIDA THATCH PALMS, AND ROYAL PALMS THAT
 ARE INDICATED TO BE REMOVED. NON NATIVE TREES AND PALMS
 ARE NOT REQUIRED TO BE RELOCATED.
 DOCUMENTATION MUST BE SUBMITTED PRIOR TO SITE PLAN
 APPROVAL TO VERIFY CODE COMPLIANCE.
 THIS INFORMATION MUST BE SUBMITTED TO PROCEED FORWARD,
 AS IT WILL SUBSTANTIALLY ALTER THE LANDSCAPE PLAN.
 FICUS TREES ARE NOT REQUIRED OR RECOMMENDED TO BE
 RELOCATED.
  
 2. MAKE THE FOLLOWING CORRECTIONS TO THE TREE
 DISPOSITION LIST:
 ? SATISFIED. ONLY TREES PROPOSED TO BE REMOVED WITH A
 CANOPY DIAMETER OF 20 FEET OR MORE SHOULD HAVE THE
 MITIGATION SQUARE FOOTAGE CALCULATED BASED ON THE
 ACTUAL DIAMETER. TREES LESS THAN 20 FEET CANOPY
 DIAMETER AND PALMS SHOULD SHOW THE CATEGORY MITIGATION
 DUE.
 ? SATISFIED. MULTIPLE PALMS PLANTED TOGETHER MUST HAVE
 EACH SINGLE TRUNK COUNTED TOWARD MITIGATION. TRIPLE
 ADONIDIA WOULD BE 3 X 50 SQ FT.
  
 3. SATISFIED. PROVIDE A DIAGRAM OF THE REQUIRED AND
 PROVIDED PUBLIC AND PRIVATE OPEN SPACE AREAS FOR CLD 25
 ZONING DISTRICT. IDENTIFY THE TYPE OF OPEN SPACE AS
 ALLOWED BY TABLE IV-7 AND DEFINITIONS IN SECTION
 94-109. SHOW HOW THE STANDARDS FOR THE TYPES OF OPEN
 SPACE ARE MET FOR VEGETATED AREAS AND TREE CANOPY
 SQUARE FOOTAGE BASED ON TABLE IV-8 ON THE LANDSCAPE
 PLAN. DIAGRAM ON SHEET A0.07 DOES NOT IDENTIFY THE OPEN
 SPACE TYPE OR CALL OUT HOW THE REQUIREMENTS OF THAT
 TYPE ARE MET.
 THE REQUIRED OPEN SPACE NEEDS TO BE QUANTIFIED,
 IDENTIFIED AS TO THE TYPE, AND ALL REQUIREMENTS NEED TO
 BE SHOWN FOR THAT OPEN SPACE TYPE. FOR OPEN SPACE SHOW
 THE TREE CANOPY SQUARE FOOTAGE FOR TREE TYPES BASED ON
 TABLE IV-8.
 GARDEN PLAZA HAS BEEN IDENTIFIED AS THE PUBLIC OPEN
 SPACE TYPE PROVIDED.
 50% OF THE SPACE IS REQUIRED TO BE VEGETATED AND 50% OF
 THE SQUARE FOOTAGE IN TREE CANOPY STANDARDS MUST BE
 DEMONSTRATED.
  
 3/25/22 GARDEN PLAZA HAS BEEN IDENTIFIED, BUT BREAKDOWN
 OF REQUIREMENTS WAS NOT SHOWN ON SHEETS A0.07 OR A0.08
 OR ON SHEET L-402. PUBLIC OPEN SPACE TYPE IS INCORRECT
 ON SHEET L-402.
  
 SEMI PUBLIC OPEN SPACE AND PRIVATE OPEN SPACE HAS BEEN
 INDICATED, BUT THE SPECIFIC TYPES HAVE NOT BEEN
 IDENTIFIED SO REQUIREMENTS CANNOT BE VERIFIED.
 ALL REQUIREMENTS MUST BE MET FOR OPEN SPACE BEING OPEN
 TO THE SKY, NO COVERED AREAS MAY BE COUNTED AS OPEN
 SPACE UNLESS THERE IS AN OVERHEAD COVER
  
 3/25/22 PRIVATE OPEN SPACE TYPES IDENTIFIED, BUT
 BREAKDOWN OF REQUIREMENTS MET WAS NOT COMPLETE FOR ALL
 TYPES. TERRACE AREAS WERE NOT DEFINED ON L-402.
  
 4. SATISFIED. IDENTIFY RELOCATED TREES OR PALMS ON THE
 PLANT LIST AND COUNT THEM TOWARD THE REQUIRED TREES.
 RELOCATIONS ARE NOT SHOWN AND CANNOT BE DETERMINED
 UNTIL ARBORIST?S REPORT IS RECEIVED.
  
 5. SATISFIED. ALL EXISTING LANDSCAPING MUST BE SHOWN ON
 THE LANDSCAPE PLAN TO PROVIDE A COMPLETE PLAN SHOWING
 COMPLIANCE WITH CURRENT CODE REQUIREMENTS.
 ALL LANDSCAPING FOR THE SITE MUST BE SHOWN ON THE
 LANDSCAPE PLAN.
  
 6. SATISFIED. ARTIFICIAL TURF AREAS PROPOSED MUST MEET
 THE REQUIREMENTS OF SECTION 94-451, INCLUDING ALL AREAS
 THAT ARE ALLOWED BY CODE MUST NOT BE VISIBLE FROM A
 ROAD OR STREET.
 REMOVED FROM PLANS.
  
 7. SATISFIED. BUFFER TREES AND HEDGES MUST BE PROVIDED
 ALONG ALL BUFFERS. THERE IS A LARGE GAP ADJACENT TO THE
 WEST PARKING GARAGE.
  
 8. SATISFIED. PROVIDE CALCULATIONS FOR REQUIRED STREET
 TREES AT MAXIMUM SPACING EVERY 30 FEET OR PORTION
 THEREOF FOR THE OKEECHOBEE STREETSCAPE LENGTH, AND SHOW
 THE NUMBER PROVIDED PER SECTION 94-113 AND 94-116.
 STREETSCAPE REQUIREMENTS MUST BE MET.
 13 STREET TREES REQUIRED, PLAN NOW SHOWS ONLY 11
 PROVIDED.
  
 9. SATISFIED. SHOW ALL EXISTING AND PROPOSED WATER AND
 SEWER AND DRAINAGE LINES ON THE LANDSCAPE PLAN. SHOW
 LOCATIONS OF BACKFLOWS AND ADJUST LOCATIONS OF UTILITY
 LINES TO RESOLVE CONFLICTS WITH EXISTING AND PROPOSED
 TREES AND LANDSCAPING.
 ONCE LOCATIONS ARE FINALIZED, MUST BE SHOWN ON
 LANDSCAPE PLAN.
 LOCATIONS OF UTILITIES CONFLICT WITH PROPOSED TREES IN
 MANY LOCATIONS, AND THE SCREENING OF ABOVE GROUND FIRE
 VALVES ON THE EAST SIDE OF THE BUILDING IS NOT SHOWN.
  
 10. SATISFIED. PLANT LIST NEEDS TO BE MODIFIED TO
 SEPARATE THE REQUIRED OPEN SPACE PLANT LISTS.
 PROVIDE A SEPARATE PLANT LIST FOR EACH OPEN SPACE AREA.
  
  
 11. SATISFIED. NATAL PLUM IS NOT A FLORIDA NATIVE
 PLANT.
  
 12. SATISFIED. SEAGRAPE IS SHOWN ON SHEET L-450, BUT NO
 SEAGRAPE IS PROPOSED ON PLANT LIST.
  
 13. SATISFIED. PROVIDE THE 50 REQUIRED FLORIDA FRIENDLY
 POINTS BASED ON THE FINAL PLANT LIST PER SECTION
 94-443(G).
 ADD A COLUMN FOR DROUGHT TOLERANCE TO THE PLANT LIST SO
 THAT IT CAN BE VERIFIED FOR EACH SPECIES.
  
 3/25/22 ADJUST POINTS FOR CHANGES TO PLANT LIST.
 4/18/22 ALL POINTS ARE INDICATED AS TAKEN. THIS IS
 INCORRECT.
  
 14. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L.
 PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES. PROVIDE THE ACTUAL PERCENTAGE BASED
 ON THE PLANT LIST.
  
 ADD A COLUMN FOR DROUGHT TOLERANCE TO THE PLANT LIST SO
 THAT IT CAN BE VERIFIED FOR EACH SPECIES. CALCULATIONS
 ARE TO BE BASED ON THE ENTIRE PLANT LIST, NOT JUST
 TREES.
  
 3/25/22 FORMAT IS AWKWARD, CHANGE HEADING TO ?DROUGHT
 TOLERANCE? AND ONLY PROVIDE THE LEVEL FOR EACH SPECIES.
  
  
 15. SATISFIED. ALL SURFACE PARKING MUST MEET THE
 REQUIREMENTS OF SECTION 94-443(C)(3) A. INCLUDING
 TERMINAL LANDSCAPE ISLANDS, INTERIOR ISLANDS AND SHADE
 TREES.
 ALL LANDSCAPE AREAS MUST BE SHOWN ON THE LANDSCAPE
 PLAN.
 TERMINAL LANDSCAPE ISLANDS MUST BE CREATED AT THE ENDS
 OF EACH ROW OF PARKING. INTERIOR ISLANDS MUST BE
 PROVIDED SO THERE ARE NO MORE THAN 10 SPACES IN A ROW.
 EACH LANDSCAPE ISLAND REQUIRES A TREE, AND AT LEAST 75%
 MUST BE CATEGORY 1 SHADE TREES.
  
 3/25/22 TERMINAL LANDSCAPE ISLANDS MUST BE CREATED AT
 THE ENDS OF EACH ROW OF PARKING.
 16. SATISFIED. PROVIDE AN EXHIBIT SHOWING THE PARKING
 AREA SURFACE CALCULATIONS, PARKING SPACE AREAS AND
 LANDSCAPE AREAS PROVIDED TO DEMONSTRATE COMPLIANCE WITH
 SECTIONS 94-443 (C)(3) AND (4). PROVIDE THE
 CALCULATIONS IN THE LANDSCAPE REQUIREMENT CHART. REFER
 TO FIGURE XIV-1.
 PARTIAL CALCULATIONS WERE SHOWN, BUT NOT COMPLETE AND
 EXHIBIT WAS NOT PROVIDED.
 3/25/22 PARTIAL CALCULATIONS WERE SHOWN, BUT NOT
 COMPLETE AND EXHIBIT WAS NOT PROVIDED.
 4/18/22 CALCULATIONS AND EXHIBIT ARE INCORRECT. PARKING
 SPACES TIMES 10 SQ FT REQUIRED LANDSCAPE AND ALL OTHER
 PAVED AREA MUST BE SHOWN AND SQUARE FOOTAGE DIVIDED BY
 100 TIMES 4 SQ FT.
 SHOW THE PARKING SPACES AS ONE AREA, THE DRIVE AISLE AS
 ONE AREA AND ONLY THE INTERIOR LANDSCAPE AREAS AS ONE
 AREA. BUFFERS CANNOT BE COUNTED.
  
 17. SATISFIED. PROVIDE SCREENING HEDGES FOR ALL GROUND
 MOUNTED VALVES AND EQUIPMENT AND ADD A NOTE THAT ALL
 EQUIPMENT WILL BE SCREENED.
 ADDITIONAL COMMENTS 2/23/22:
 18. SATISFIED. THE EAST LANDSCAPE BUFFER IS NOT ON THE
 PROPERTY, IT IS OUTSIDE THE SITE ON A CITY OWNED
 PARCEL. THIS MUST BE ADDRESSED AS TO HOW THE AREA IS TO
 BE APPROVED AND MAINTAINED.
 OWNERSHIP MUST BE RESOLVED. IF THE BUFFER IS TO BE
 PROVIDED OFFSITE, A VARIANCE MAY BE REQUIRED. IF THERE
 IS SEPARATE OWNERSHIP, THE OFF SITE PLAN AND PLANT LIST
 MUST BE SEPARATED.
  
 19. SATISFIED. REQUIRED OPEN SPACE PER SECTION 94-113
 IS DIFFERENT AND SEPARATE FROM THE OVERALL LANDSCAPE
 REQUIREMENTS FOR THE SITE. OPEN SPACE AND LANDSCAPE
 AREAS ON THE LANDSCAPE LEGEND SHEET L-401 NEEDS TO BE
 CORRECTED TO REFLECT THIS.
  
 20. SATISFIED. C. WEST BUFFER REQUIRES 26 TREES. SOUTH
 BUFFER SHOULD BE 13 TREES REQUIRED.
  
 21. SATISFIED. STREET TREES SHOULD BE 13 REQUIRED.
  
 22. SATISFIED. FOUNDATION LANDSCAPE REQUIREMENT NEEDS
 TO SHOW TOTAL LINEAR FOOTAGE FOR EACH BUILDING AND SHOW
 THAT AT LEAST 30% OF THAT IS LANDSCAPED AREA.
 INFORMATION PROVIDED IS NOT PART OF THE CODE
 REQUIREMENT. ONLY SUPPLY THE TOTAL LINEAR FOOTAGE FOR
 EACH BUILDING, SHOW THE REQUIRED 30% AND SHOW THE
 PROVIDED LINEAR FOOTAGE OF LANDSCAPE AREA.
 ADDITIONAL COMMENTS 3/25/22:
 23. SATISFIED. ALL TREES MUST MEET THE MINIMUM 12 FT
 HEIGHT REQUIREMENT. SIMPSON?S STOPPERS SHOWN AT 10 FT.
  
 24. SATISFIED. CHANGE STREET TREES TO LIVE OAKS TO
 MATCH DESIGN EAST OF TAMARIND.
  
 25. SATISFIED. AREAS BENEATH THE BUILDING AND PARKING
 STRUCTURE APPEAR TO HAVE FULL SIZE OAK TREES. PLEASE
 EXPLAIN HOW THIS IS POSSIBLE.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE STREET TREES AND
 RIGHT OF WAY LANDSCAPING AND IRRIGATION. THIS WILL BE
 THROUGH A SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  
  

Review Stop L LANDSCAPING
Rev No 4 Status F Date 04-18-2022 Cont ID  
Sent By rcaranci Date 04-18-2022 Time 14:42 Rev Time 0.00
Received By rcaranci Date 04-18-2022 Time 14:42 Sent To  
Notes
2022-04-18 14:45:08FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 1001 OKEECHOBEE Z21100021
 APRIL 18, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. NOT SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE
 TREES AND PALMS IN GOOD CONDITION TO BE PRESERVED ON
 SITE OR RELOCATED. ANSI A 300 (PART 5) STANDARDS
 SPECIFY EXAMPLES OF SUITABILITY RATINGS OF GOOD,
 MODERATE, OR POOR FOR RELOCATION. PROVIDE AN ARBORISTS
 REPORT RATING THE CONDITION AND RELOCATION POTENTIAL
 FOR THE NATIVE TREES AND PALMS. THERE ARE LIVE OAKS,
 SABAL PALMS, FLORIDA THATCH PALMS, AND ROYAL PALMS THAT
 ARE INDICATED TO BE REMOVED. NON NATIVE TREES AND PALMS
 ARE NOT REQUIRED TO BE RELOCATED.
 DOCUMENTATION MUST BE SUBMITTED PRIOR TO SITE PLAN
 APPROVAL TO VERIFY CODE COMPLIANCE.
 THIS INFORMATION MUST BE SUBMITTED TO PROCEED FORWARD,
 AS IT WILL SUBSTANTIALLY ALTER THE LANDSCAPE PLAN.
 FICUS TREES ARE NOT REQUIRED OR RECOMMENDED TO BE
 RELOCATED.
  
 2. MAKE THE FOLLOWING CORRECTIONS TO THE TREE
 DISPOSITION LIST:
 ? SATISFIED. ONLY TREES PROPOSED TO BE REMOVED WITH A
 CANOPY DIAMETER OF 20 FEET OR MORE SHOULD HAVE THE
 MITIGATION SQUARE FOOTAGE CALCULATED BASED ON THE
 ACTUAL DIAMETER. TREES LESS THAN 20 FEET CANOPY
 DIAMETER AND PALMS SHOULD SHOW THE CATEGORY MITIGATION
 DUE.
 ? SATISFIED. MULTIPLE PALMS PLANTED TOGETHER MUST HAVE
 EACH SINGLE TRUNK COUNTED TOWARD MITIGATION. TRIPLE
 ADONIDIA WOULD BE 3 X 50 SQ FT.
  
 3. SATISFIED. PROVIDE A DIAGRAM OF THE REQUIRED AND
 PROVIDED PUBLIC AND PRIVATE OPEN SPACE AREAS FOR CLD 25
 ZONING DISTRICT. IDENTIFY THE TYPE OF OPEN SPACE AS
 ALLOWED BY TABLE IV-7 AND DEFINITIONS IN SECTION
 94-109. SHOW HOW THE STANDARDS FOR THE TYPES OF OPEN
 SPACE ARE MET FOR VEGETATED AREAS AND TREE CANOPY
 SQUARE FOOTAGE BASED ON TABLE IV-8 ON THE LANDSCAPE
 PLAN. DIAGRAM ON SHEET A0.07 DOES NOT IDENTIFY THE OPEN
 SPACE TYPE OR CALL OUT HOW THE REQUIREMENTS OF THAT
 TYPE ARE MET.
 THE REQUIRED OPEN SPACE NEEDS TO BE QUANTIFIED,
 IDENTIFIED AS TO THE TYPE, AND ALL REQUIREMENTS NEED TO
 BE SHOWN FOR THAT OPEN SPACE TYPE. FOR OPEN SPACE SHOW
 THE TREE CANOPY SQUARE FOOTAGE FOR TREE TYPES BASED ON
 TABLE IV-8.
 GARDEN PLAZA HAS BEEN IDENTIFIED AS THE PUBLIC OPEN
 SPACE TYPE PROVIDED.
 50% OF THE SPACE IS REQUIRED TO BE VEGETATED AND 50% OF
 THE SQUARE FOOTAGE IN TREE CANOPY STANDARDS MUST BE
 DEMONSTRATED.
  
 3/25/22 GARDEN PLAZA HAS BEEN IDENTIFIED, BUT BREAKDOWN
 OF REQUIREMENTS WAS NOT SHOWN ON SHEETS A0.07 OR A0.08
 OR ON SHEET L-402. PUBLIC OPEN SPACE TYPE IS INCORRECT
 ON SHEET L-402.
  
 SEMI PUBLIC OPEN SPACE AND PRIVATE OPEN SPACE HAS BEEN
 INDICATED, BUT THE SPECIFIC TYPES HAVE NOT BEEN
 IDENTIFIED SO REQUIREMENTS CANNOT BE VERIFIED.
 ALL REQUIREMENTS MUST BE MET FOR OPEN SPACE BEING OPEN
 TO THE SKY, NO COVERED AREAS MAY BE COUNTED AS OPEN
 SPACE UNLESS THERE IS AN OVERHEAD COVER
  
 3/25/22 PRIVATE OPEN SPACE TYPES IDENTIFIED, BUT
 BREAKDOWN OF REQUIREMENTS MET WAS NOT COMPLETE FOR ALL
 TYPES. TERRACE AREAS WERE NOT DEFINED ON L-402.
  
 4. NOT SATISFIED. IDENTIFY RELOCATED TREES OR PALMS ON
 THE PLANT LIST AND COUNT THEM TOWARD THE REQUIRED
 TREES.
 RELOCATIONS ARE NOT SHOWN AND CANNOT BE DETERMINED
 UNTIL ARBORIST?S REPORT IS RECEIVED.
  
 5. NOT SATISFIED. ALL EXISTING LANDSCAPING MUST BE
 SHOWN ON THE LANDSCAPE PLAN TO PROVIDE A COMPLETE PLAN
 SHOWING COMPLIANCE WITH CURRENT CODE REQUIREMENTS.
 ALL LANDSCAPING FOR THE SITE MUST BE SHOWN ON THE
 LANDSCAPE PLAN.
  
 6. SATISFIED. ARTIFICIAL TURF AREAS PROPOSED MUST MEET
 THE REQUIREMENTS OF SECTION 94-451, INCLUDING ALL AREAS
 THAT ARE ALLOWED BY CODE MUST NOT BE VISIBLE FROM A
 ROAD OR STREET.
 REMOVED FROM PLANS.
  
 7. SATISFIED. BUFFER TREES AND HEDGES MUST BE PROVIDED
 ALONG ALL BUFFERS. THERE IS A LARGE GAP ADJACENT TO THE
 WEST PARKING GARAGE.
  
 8. PARTIALLY SATISFIED. PROVIDE CALCULATIONS FOR
 REQUIRED STREET TREES AT MAXIMUM SPACING EVERY 30 FEET
 OR PORTION THEREOF FOR THE OKEECHOBEE STREETSCAPE
 LENGTH, AND SHOW THE NUMBER PROVIDED PER SECTION 94-113
 AND 94-116.
 STREETSCAPE REQUIREMENTS MUST BE MET.
 13 STREET TREES REQUIRED, PLAN NOW SHOWS ONLY 11
 PROVIDED.
  
 9. SATISFIED. SHOW ALL EXISTING AND PROPOSED WATER AND
 SEWER AND DRAINAGE LINES ON THE LANDSCAPE PLAN. SHOW
 LOCATIONS OF BACKFLOWS AND ADJUST LOCATIONS OF UTILITY
 LINES TO RESOLVE CONFLICTS WITH EXISTING AND PROPOSED
 TREES AND LANDSCAPING.
 ONCE LOCATIONS ARE FINALIZED, MUST BE SHOWN ON
 LANDSCAPE PLAN.
 LOCATIONS OF UTILITIES CONFLICT WITH PROPOSED TREES IN
 MANY LOCATIONS, AND THE SCREENING OF ABOVE GROUND FIRE
 VALVES ON THE EAST SIDE OF THE BUILDING IS NOT SHOWN.
  
 10. SATISFIED. PLANT LIST NEEDS TO BE MODIFIED TO
 SEPARATE THE REQUIRED OPEN SPACE PLANT LISTS.
 PROVIDE A SEPARATE PLANT LIST FOR EACH OPEN SPACE AREA.
  
  
 11. SATISFIED. NATAL PLUM IS NOT A FLORIDA NATIVE
 PLANT.
  
 12. SATISFIED. SEAGRAPE IS SHOWN ON SHEET L-450, BUT NO
 SEAGRAPE IS PROPOSED ON PLANT LIST.
  
 13. PARTIALLY SATISFIED. PROVIDE THE 50 REQUIRED
 FLORIDA FRIENDLY POINTS BASED ON THE FINAL PLANT LIST
 PER SECTION 94-443(G).
 ADD A COLUMN FOR DROUGHT TOLERANCE TO THE PLANT LIST SO
 THAT IT CAN BE VERIFIED FOR EACH SPECIES.
  
 3/25/22 ADJUST POINTS FOR CHANGES TO PLANT LIST.
 4/18/22 ALL POINTS ARE INDICATED AS TAKEN. THIS IS
 INCORRECT.
  
 14. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L.
 PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES. PROVIDE THE ACTUAL PERCENTAGE BASED
 ON THE PLANT LIST.
  
 ADD A COLUMN FOR DROUGHT TOLERANCE TO THE PLANT LIST SO
 THAT IT CAN BE VERIFIED FOR EACH SPECIES. CALCULATIONS
 ARE TO BE BASED ON THE ENTIRE PLANT LIST, NOT JUST
 TREES.
  
 3/25/22 FORMAT IS AWKWARD, CHANGE HEADING TO ?DROUGHT
 TOLERANCE? AND ONLY PROVIDE THE LEVEL FOR EACH SPECIES.
  
  
 15. SATISFIED. ALL SURFACE PARKING MUST MEET THE
 REQUIREMENTS OF SECTION 94-443(C)(3) A. INCLUDING
 TERMINAL LANDSCAPE ISLANDS, INTERIOR ISLANDS AND SHADE
 TREES.
 ALL LANDSCAPE AREAS MUST BE SHOWN ON THE LANDSCAPE
 PLAN.
 TERMINAL LANDSCAPE ISLANDS MUST BE CREATED AT THE ENDS
 OF EACH ROW OF PARKING. INTERIOR ISLANDS MUST BE
 PROVIDED SO THERE ARE NO MORE THAN 10 SPACES IN A ROW.
 EACH LANDSCAPE ISLAND REQUIRES A TREE, AND AT LEAST 75%
 MUST BE CATEGORY 1 SHADE TREES.
  
 3/25/22 TERMINAL LANDSCAPE ISLANDS MUST BE CREATED AT
 THE ENDS OF EACH ROW OF PARKING.
 16. PARTIALLY SATISFIED. PROVIDE AN EXHIBIT SHOWING THE
 PARKING AREA SURFACE CALCULATIONS, PARKING SPACE AREAS
 AND LANDSCAPE AREAS PROVIDED TO DEMONSTRATE COMPLIANCE
 WITH SECTIONS 94-443 (C)(3) AND (4). PROVIDE THE
 CALCULATIONS IN THE LANDSCAPE REQUIREMENT CHART. REFER
 TO FIGURE XIV-1.
 PARTIAL CALCULATIONS WERE SHOWN, BUT NOT COMPLETE AND
 EXHIBIT WAS NOT PROVIDED.
 3/25/22 PARTIAL CALCULATIONS WERE SHOWN, BUT NOT
 COMPLETE AND EXHIBIT WAS NOT PROVIDED.
 4/18/22 CALCULATIONS AND EXHIBIT ARE INCORRECT. PARKING
 SPACES TIMES 10 SQ FT REQUIRED LANDSCAPE AND ALL OTHER
 PAVED AREA MUST BE SHOWN AND SQUARE FOOTAGE DIVIDED BY
 100 TIMES 4 SQ FT.
 SHOW THE PARKING SPACES AS ONE AREA, THE DRIVE AISLE AS
 ONE AREA AND ONLY THE INTERIOR LANDSCAPE AREAS AS ONE
 AREA. BUFFERS CANNOT BE COUNTED.
  
 17. SATISFIED. PROVIDE SCREENING HEDGES FOR ALL GROUND
 MOUNTED VALVES AND EQUIPMENT AND ADD A NOTE THAT ALL
 EQUIPMENT WILL BE SCREENED.
 ADDITIONAL COMMENTS 2/23/22:
 18. PARTIALLY SATISFIED. THE EAST LANDSCAPE BUFFER IS
 NOT ON THE PROPERTY, IT IS OUTSIDE THE SITE ON A CITY
 OWNED PARCEL. THIS MUST BE ADDRESSED AS TO HOW THE AREA
 IS TO BE APPROVED AND MAINTAINED.
 OWNERSHIP MUST BE RESOLVED. IF THE BUFFER IS TO BE
 PROVIDED OFFSITE, A VARIANCE MAY BE REQUIRED. IF THERE
 IS SEPARATE OWNERSHIP, THE OFF SITE PLAN AND PLANT LIST
 MUST BE SEPARATED.
  
 19. SATISFIED. REQUIRED OPEN SPACE PER SECTION 94-113
 IS DIFFERENT AND SEPARATE FROM THE OVERALL LANDSCAPE
 REQUIREMENTS FOR THE SITE. OPEN SPACE AND LANDSCAPE
 AREAS ON THE LANDSCAPE LEGEND SHEET L-401 NEEDS TO BE
 CORRECTED TO REFLECT THIS.
  
 20. SATISFIED. C. WEST BUFFER REQUIRES 26 TREES. SOUTH
 BUFFER SHOULD BE 13 TREES REQUIRED.
  
 21. SATISFIED. STREET TREES SHOULD BE 13 REQUIRED.
  
 22. SATISFIED. FOUNDATION LANDSCAPE REQUIREMENT NEEDS
 TO SHOW TOTAL LINEAR FOOTAGE FOR EACH BUILDING AND SHOW
 THAT AT LEAST 30% OF THAT IS LANDSCAPED AREA.
 INFORMATION PROVIDED IS NOT PART OF THE CODE
 REQUIREMENT. ONLY SUPPLY THE TOTAL LINEAR FOOTAGE FOR
 EACH BUILDING, SHOW THE REQUIRED 30% AND SHOW THE
 PROVIDED LINEAR FOOTAGE OF LANDSCAPE AREA.
 ADDITIONAL COMMENTS 3/25/22:
 23. SATISFIED. ALL TREES MUST MEET THE MINIMUM 12 FT
 HEIGHT REQUIREMENT. SIMPSON?S STOPPERS SHOWN AT 10 FT.
  
 24. SATISFIED. CHANGE STREET TREES TO LIVE OAKS TO
 MATCH DESIGN EAST OF TAMARIND.
  
 25. SATISFIED. AREAS BENEATH THE BUILDING AND PARKING
 STRUCTURE APPEAR TO HAVE FULL SIZE OAK TREES. PLEASE
 EXPLAIN HOW THIS IS POSSIBLE.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
  
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE STREET TREES AND
 RIGHT OF WAY LANDSCAPING AND IRRIGATION. THIS WILL BE
 THROUGH A SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  
  

Review Stop L LANDSCAPING
Rev No 3 Status F Date 03-25-2022 Cont ID  
Sent By rcaranci Date 03-25-2022 Time 16:34 Rev Time 0.00
Received By rcaranci Date 03-25-2022 Time 16:33 Sent To  
Notes
2022-03-25 16:36:49FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 1001 OKEECHOBEE Z21100021
 MARCH 25, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. NOT SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE
 TREES AND PALMS IN GOOD CONDITION TO BE PRESERVED ON
 SITE OR RELOCATED. ANSI A 300 (PART 5) STANDARDS
 SPECIFY EXAMPLES OF SUITABILITY RATINGS OF GOOD,
 MODERATE, OR POOR FOR RELOCATION. PROVIDE AN ARBORISTS
 REPORT RATING THE CONDITION AND RELOCATION POTENTIAL
 FOR THE NATIVE TREES AND PALMS. THERE ARE LIVE OAKS,
 SABAL PALMS, FLORIDA THATCH PALMS, AND ROYAL PALMS THAT
 ARE INDICATED TO BE REMOVED. NON NATIVE TREES AND PALMS
 ARE NOT REQUIRED TO BE RELOCATED.
 DOCUMENTATION MUST BE SUBMITTED PRIOR TO SITE PLAN
 APPROVAL TO VERIFY CODE COMPLIANCE.
 THIS INFORMATION MUST BE SUBMITTED TO PROCEED FORWARD,
 AS IT WILL SUBSTANTIALLY ALTER THE LANDSCAPE PLAN.
  
 2. MAKE THE FOLLOWING CORRECTIONS TO THE TREE
 DISPOSITION LIST:
 ? SATISFIED. ONLY TREES PROPOSED TO BE REMOVED WITH A
 CANOPY DIAMETER OF 20 FEET OR MORE SHOULD HAVE THE
 MITIGATION SQUARE FOOTAGE CALCULATED BASED ON THE
 ACTUAL DIAMETER. TREES LESS THAN 20 FEET CANOPY
 DIAMETER AND PALMS SHOULD SHOW THE CATEGORY MITIGATION
 DUE.
 ? SATISFIED. MULTIPLE PALMS PLANTED TOGETHER MUST HAVE
 EACH SINGLE TRUNK COUNTED TOWARD MITIGATION. TRIPLE
 ADONIDIA WOULD BE 3 X 50 SQ FT.
  
 3. PARTIALLY SATISFIED. PROVIDE A DIAGRAM OF THE
 REQUIRED AND PROVIDED PUBLIC AND PRIVATE OPEN SPACE
 AREAS FOR CLD 25 ZONING DISTRICT. IDENTIFY THE TYPE OF
 OPEN SPACE AS ALLOWED BY TABLE IV-7 AND DEFINITIONS IN
 SECTION 94-109. SHOW HOW THE STANDARDS FOR THE TYPES OF
 OPEN SPACE ARE MET FOR VEGETATED AREAS AND TREE CANOPY
 SQUARE FOOTAGE BASED ON TABLE IV-8 ON THE LANDSCAPE
 PLAN. DIAGRAM ON SHEET A0.07 DOES NOT IDENTIFY THE OPEN
 SPACE TYPE OR CALL OUT HOW THE REQUIREMENTS OF THAT
 TYPE ARE MET.
 THE REQUIRED OPEN SPACE NEEDS TO BE QUANTIFIED,
 IDENTIFIED AS TO THE TYPE, AND ALL REQUIREMENTS NEED TO
 BE SHOWN FOR THAT OPEN SPACE TYPE. FOR OPEN SPACE SHOW
 THE TREE CANOPY SQUARE FOOTAGE FOR TREE TYPES BASED ON
 TABLE IV-8.
 GARDEN PLAZA HAS BEEN IDENTIFIED AS THE PUBLIC OPEN
 SPACE TYPE PROVIDED.
 50% OF THE SPACE IS REQUIRED TO BE VEGETATED AND 50% OF
 THE SQUARE FOOTAGE IN TREE CANOPY STANDARDS MUST BE
 DEMONSTRATED.
  
 3/25/22 GARDEN PLAZA HAS BEEN IDENTIFIED, BUT BREAKDOWN
 OF REQUIREMENTS WAS NOT SHOWN ON SHEETS A0.07 OR A0.08
 OR ON SHEET L-402. PUBLIC OPEN SPACE TYPE IS INCORRECT
 ON SHEET L-402.
  
 SEMI PUBLIC OPEN SPACE AND PRIVATE OPEN SPACE HAS BEEN
 INDICATED, BUT THE SPECIFIC TYPES HAVE NOT BEEN
 IDENTIFIED SO REQUIREMENTS CANNOT BE VERIFIED.
 ALL REQUIREMENTS MUST BE MET FOR OPEN SPACE BEING OPEN
 TO THE SKY, NO COVERED AREAS MAY BE COUNTED AS OPEN
 SPACE UNLESS THERE IS AN OVERHEAD COVER
  
 3/25/22 PRIVATE OPEN SPACE TYPES IDENTIFIED, BUT
 BREAKDOWN OF REQUIREMENTS MET WAS NOT COMPLETE FOR ALL
 TYPES. TERRACE AREAS WERE NOT DEFINED ON L-402.
  
 4. NOT SATISFIED. IDENTIFY RELOCATED TREES OR PALMS ON
 THE PLANT LIST AND COUNT THEM TOWARD THE REQUIRED
 TREES.
 RELOCATIONS ARE NOT SHOWN AND CANNOT BE DETERMINED
 UNTIL ARBORIST?S REPORT IS RECEIVED.
  
 5. NOT SATISFIED. ALL EXISTING LANDSCAPING MUST BE
 SHOWN ON THE LANDSCAPE PLAN TO PROVIDE A COMPLETE PLAN
 SHOWING COMPLIANCE WITH CURRENT CODE REQUIREMENTS.
 ALL LANDSCAPING FOR THE SITE MUST BE SHOWN ON THE
 LANDSCAPE PLAN.
  
 6. SATISFIED. ARTIFICIAL TURF AREAS PROPOSED MUST MEET
 THE REQUIREMENTS OF SECTION 94-451, INCLUDING ALL AREAS
 THAT ARE ALLOWED BY CODE MUST NOT BE VISIBLE FROM A
 ROAD OR STREET.
 REMOVED FROM PLANS.
  
 7. SATISFIED. BUFFER TREES AND HEDGES MUST BE PROVIDED
 ALONG ALL BUFFERS. THERE IS A LARGE GAP ADJACENT TO THE
 WEST PARKING GARAGE.
  
 8. SATISFIED. PROVIDE CALCULATIONS FOR REQUIRED STREET
 TREES AT MAXIMUM SPACING EVERY 30 FEET OR PORTION
 THEREOF FOR THE OKEECHOBEE STREETSCAPE LENGTH, AND SHOW
 THE NUMBER PROVIDED PER SECTION 94-113 AND 94-116.
 STREETSCAPE REQUIREMENTS MUST BE MET.
  
 9. PARTIALLY SATISFIED. SHOW ALL EXISTING AND PROPOSED
 WATER AND SEWER AND DRAINAGE LINES ON THE LANDSCAPE
 PLAN. SHOW LOCATIONS OF BACKFLOWS AND ADJUST LOCATIONS
 OF UTILITY LINES TO RESOLVE CONFLICTS WITH EXISTING AND
 PROPOSED TREES AND LANDSCAPING.
 ONCE LOCATIONS ARE FINALIZED, MUST BE SHOWN ON
 LANDSCAPE PLAN.
 LOCATIONS OF UTILITIES CONFLICT WITH PROPOSED TREES IN
 MANY LOCATIONS, AND THE SCREENING OF ABOVE GROUND FIRE
 VALVES ON THE EAST SIDE OF THE BUILDING IS NOT SHOWN.
  
 10. SATISFIED. PLANT LIST NEEDS TO BE MODIFIED TO
 SEPARATE THE REQUIRED OPEN SPACE PLANT LISTS.
 PROVIDE A SEPARATE PLANT LIST FOR EACH OPEN SPACE AREA.
  
  
 11. SATISFIED. NATAL PLUM IS NOT A FLORIDA NATIVE
 PLANT.
  
 12. SATISFIED. SEAGRAPE IS SHOWN ON SHEET L-450, BUT NO
 SEAGRAPE IS PROPOSED ON PLANT LIST.
  
 13. PARTIALLY SATISFIED. PROVIDE THE 50 REQUIRED
 FLORIDA FRIENDLY POINTS BASED ON THE FINAL PLANT LIST
 PER SECTION 94-443(G).
 ADD A COLUMN FOR DROUGHT TOLERANCE TO THE PLANT LIST SO
 THAT IT CAN BE VERIFIED FOR EACH SPECIES.
  
 3/25/22 ADJUST POINTS FOR CHANGES TO PLANT LIST.
  
 14. PARTIALLY SATISFIED. SHOW COMPLIANCE WITH SECTION
 94-445 L. PLANT SPECIES. A MINIMUM OF 60 PERCENT OF
 PLANT MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES. PROVIDE THE ACTUAL PERCENTAGE BASED
 ON THE PLANT LIST.
  
 ADD A COLUMN FOR DROUGHT TOLERANCE TO THE PLANT LIST SO
 THAT IT CAN BE VERIFIED FOR EACH SPECIES. CALCULATIONS
 ARE TO BE BASED ON THE ENTIRE PLANT LIST, NOT JUST
 TREES.
  
 3/25/22 FORMAT IS AWKWARD, CHANGE HEADING TO ?DROUGHT
 TOLERANCE? AND ONLY PROVIDE THE LEVEL FOR EACH SPECIES.
  
  
 15. NOT SATISFIED. ALL SURFACE PARKING MUST MEET THE
 REQUIREMENTS OF SECTION 94-443(C)(3) A. INCLUDING
 TERMINAL LANDSCAPE ISLANDS, INTERIOR ISLANDS AND SHADE
 TREES.
 ALL LANDSCAPE AREAS MUST BE SHOWN ON THE LANDSCAPE
 PLAN.
 TERMINAL LANDSCAPE ISLANDS MUST BE CREATED AT THE ENDS
 OF EACH ROW OF PARKING. INTERIOR ISLANDS MUST BE
 PROVIDED SO THERE ARE NO MORE THAN 10 SPACES IN A ROW.
 EACH LANDSCAPE ISLAND REQUIRES A TREE, AND AT LEAST 75%
 MUST BE CATEGORY 1 SHADE TREES.
  
 3/25/22 TERMINAL LANDSCAPE ISLANDS MUST BE CREATED AT
 THE ENDS OF EACH ROW OF PARKING.
 16. NOT SATISFIED. PROVIDE AN EXHIBIT SHOWING THE
 PARKING AREA SURFACE CALCULATIONS, PARKING SPACE AREAS
 AND LANDSCAPE AREAS PROVIDED TO DEMONSTRATE COMPLIANCE
 WITH SECTIONS 94-443 (C)(3) AND (4). PROVIDE THE
 CALCULATIONS IN THE LANDSCAPE REQUIREMENT CHART. REFER
 TO FIGURE XIV-1.
 PARTIAL CALCULATIONS WERE SHOWN, BUT NOT COMPLETE AND
 EXHIBIT WAS NOT PROVIDED.
 3/25/22 PARTIAL CALCULATIONS WERE SHOWN, BUT NOT
 COMPLETE AND EXHIBIT WAS NOT PROVIDED.
  
  
 17. SATISFIED. PROVIDE SCREENING HEDGES FOR ALL GROUND
 MOUNTED VALVES AND EQUIPMENT AND ADD A NOTE THAT ALL
 EQUIPMENT WILL BE SCREENED.
 ADDITIONAL COMMENTS 2/23/22:
 18. NOT SATISFIED. THE EAST LANDSCAPE BUFFER IS NOT ON
 THE PROPERTY, IT IS OUTSIDE THE SITE ON A CITY OWNED
 PARCEL. THIS MUST BE ADDRESSED AS TO HOW THE AREA IS TO
 BE APPROVED AND MAINTAINED.
 OWNERSHIP MUST BE RESOLVED. IF THE BUFFER IS TO BE
 PROVIDED OFFSITE, A VARIANCE MAY BE REQUIRED. IF THERE
 IS SEPARATE OWNERSHIP, THE OFF SITE PLAN AND PLANT LIST
 MUST BE SEPARATED.
  
 19. SATISFIED. REQUIRED OPEN SPACE PER SECTION 94-113
 IS DIFFERENT AND SEPARATE FROM THE OVERALL LANDSCAPE
 REQUIREMENTS FOR THE SITE. OPEN SPACE AND LANDSCAPE
 AREAS ON THE LANDSCAPE LEGEND SHEET L-401 NEEDS TO BE
 CORRECTED TO REFLECT THIS.
  
 20. SATISFIED. C. WEST BUFFER REQUIRES 26 TREES. SOUTH
 BUFFER SHOULD BE 13 TREES REQUIRED.
  
 21. SATISFIED. STREET TREES SHOULD BE 13 REQUIRED.
  
 22. PARTIALLY SATISFIED. FOUNDATION LANDSCAPE
 REQUIREMENT NEEDS TO SHOW TOTAL LINEAR FOOTAGE FOR EACH
 BUILDING AND SHOW THAT AT LEAST 30% OF THAT IS
 LANDSCAPED AREA.
 INFORMATION PROVIDED IS NOT PART OF THE CODE
 REQUIREMENT. ONLY SUPPLY THE TOTAL LINEAR FOOTAGE FOR
 EACH BUILDING, SHOW THE REQUIRED 30% AND SHOW THE
 PROVIDED LINEAR FOOTAGE OF LANDSCAPE AREA.
 ADDITIONAL COMMENTS 3/25/22:
 23. ALL TREES MUST MEET THE MINIMUM 12 FT HEIGHT
 REQUIREMENT. SIMPSON?S STOPPERS SHOWN AT 10 FT.
  
 24. CHANGE STREET TREES TO LIVE OAKS TO MATCH DESIGN
 EAST OF TAMARIND.
  
 25. AREAS BENEATH THE BUILDING AND PARKING STRUCTURE
 APPEAR TO HAVE FULL SIZE OAK TREES. PLEASE EXPLAIN HOW
 THIS IS POSSIBLE.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 02-23-2022 Cont ID  
Sent By rcaranci Date 02-23-2022 Time 16:41 Rev Time 0.00
Received By rcaranci Date 02-23-2022 Time 16:41 Sent To  
Notes
2022-02-23 16:41:30FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 1001 OKEECHOBEE Z21100021
 FEBRUARY 23, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. NOT SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE
 TREES AND PALMS IN GOOD CONDITION TO BE PRESERVED ON
 SITE OR RELOCATED. ANSI A 300 (PART 5) STANDARDS
 SPECIFY EXAMPLES OF SUITABILITY RATINGS OF GOOD,
 MODERATE, OR POOR FOR RELOCATION. PROVIDE AN ARBORISTS
 REPORT RATING THE CONDITION AND RELOCATION POTENTIAL
 FOR THE NATIVE TREES AND PALMS. THERE ARE LIVE OAKS,
 SABAL PALMS, FLORIDA THATCH PALMS, AND ROYAL PALMS THAT
 ARE INDICATED TO BE REMOVED. NON NATIVE TREES AND PALMS
 ARE NOT REQUIRED TO BE RELOCATED.
 DOCUMENTATION MUST BE SUBMITTED PRIOR TO SITE PLAN
 APPROVAL TO VERIFY CODE COMPLIANCE.
 2. MAKE THE FOLLOWING CORRECTIONS TO THE TREE
 DISPOSITION LIST:
 ? SATISFIED. ONLY TREES PROPOSED TO BE REMOVED WITH A
 CANOPY DIAMETER OF 20 FEET OR MORE SHOULD HAVE THE
 MITIGATION SQUARE FOOTAGE CALCULATED BASED ON THE
 ACTUAL DIAMETER. TREES LESS THAN 20 FEET CANOPY
 DIAMETER AND PALMS SHOULD SHOW THE CATEGORY MITIGATION
 DUE.
 ? SATISFIED. MULTIPLE PALMS PLANTED TOGETHER MUST HAVE
 EACH SINGLE TRUNK COUNTED TOWARD MITIGATION. TRIPLE
 ADONIDIA WOULD BE 3 X 50 SQ FT.
  
 3. PARTIALLY SATISFIED. PROVIDE A DIAGRAM OF THE
 REQUIRED AND PROVIDED PUBLIC AND PRIVATE OPEN SPACE
 AREAS FOR CLD 25 ZONING DISTRICT. IDENTIFY THE TYPE OF
 OPEN SPACE AS ALLOWED BY TABLE IV-7 AND DEFINITIONS IN
 SECTION 94-109. SHOW HOW THE STANDARDS FOR THE TYPES OF
 OPEN SPACE ARE MET FOR VEGETATED AREAS AND TREE CANOPY
 SQUARE FOOTAGE BASED ON TABLE IV-8 ON THE LANDSCAPE
 PLAN. DIAGRAM ON SHEET A0.07 DOES NOT IDENTIFY THE OPEN
 SPACE TYPE OR CALL OUT HOW THE REQUIREMENTS OF THAT
 TYPE ARE MET.
 THE REQUIRED OPEN SPACE NEEDS TO BE QUANTIFIED,
 IDENTIFIED AS TO THE TYPE, AND ALL REQUIREMENTS NEED TO
 BE SHOWN FOR THAT OPEN SPACE TYPE. FOR OPEN SPACE SHOW
 THE TREE CANOPY SQUARE FOOTAGE FOR TREE TYPES BASED ON
 TABLE IV-8.
 GARDEN PLAZA HAS BEEN IDENTIFIED AS THE PUBLIC OPEN
 SPACE TYPE PROVIDED.
 50% OF THE SPACE IS REQUIRED TO BE VEGETATED AND 50% OF
 THE SQUARE FOOTAGE IN TREE CANOPY STANDARDS MUST BE
 DEMONSTRATED.
 SEMI PUBLIC OPEN SPACE AND PRIVATE OPEN SPACE HAS BEEN
 INDICATED, BUT THE SPECIFIC TYPES HAVE NOT BEEN
 IDENTIFIED SO REQUIREMENTS CANNOT BE VERIFIED.
 ALL REQUIREMENTS MUST BE MET FOR OPEN SPACE BEING OPEN
 TO THE SKY, NO COVERED AREAS MAY BE COUNTED AS OPEN
 SPACE UNLESS THERE IS AN OVERHEAD COVER
  
 4. NOT SATISFIED. IDENTIFY RELOCATED TREES OR PALMS ON
 THE PLANT LIST AND COUNT THEM TOWARD THE REQUIRED
 TREES.
 RELOCATIONS ARE NOT SHOWN AND CANNOT BE DETERMINED
 UNTIL ARBORIST?S REPORT IS RECEIVED.
  
 5. NOT SATISFIED. ALL EXISTING LANDSCAPING MUST BE
 SHOWN ON THE LANDSCAPE PLAN TO PROVIDE A COMPLETE PLAN
 SHOWING COMPLIANCE WITH CURRENT CODE REQUIREMENTS.
 ALL LANDSCAPING FOR THE SITE MUST BE SHOWN ON THE
 LANDSCAPE PLAN.
  
 6. SATISFIED. ARTIFICIAL TURF AREAS PROPOSED MUST MEET
 THE REQUIREMENTS OF SECTION 94-451, INCLUDING ALL AREAS
 THAT ARE ALLOWED BY CODE MUST NOT BE VISIBLE FROM A
 ROAD OR STREET.
 REMOVED FROM PLANS.
  
 7. SATISFIED. BUFFER TREES AND HEDGES MUST BE PROVIDED
 ALONG ALL BUFFERS. THERE IS A LARGE GAP ADJACENT TO THE
 WEST PARKING GARAGE.
  
 8. NOT SATISFIED. PROVIDE CALCULATIONS FOR REQUIRED
 STREET TREES AT MAXIMUM SPACING EVERY 30 FEET OR
 PORTION THEREOF FOR THE OKEECHOBEE STREETSCAPE LENGTH,
 AND SHOW THE NUMBER PROVIDED PER SECTION 94-113 AND
 94-116.
 STREETSCAPE REQUIREMENTS MUST BE MET.
  
 9. PARTIALLY SATISFIED. SHOW ALL EXISTING AND PROPOSED
 WATER AND SEWER AND DRAINAGE LINES ON THE LANDSCAPE
 PLAN. SHOW LOCATIONS OF BACKFLOWS AND ADJUST LOCATIONS
 OF UTILITY LINES TO RESOLVE CONFLICTS WITH EXISTING AND
 PROPOSED TREES AND LANDSCAPING.
 ONCE LOCATIONS ARE FINALIZED, MUST BE SHOWN ON
 LANDSCAPE PLAN.
  
 10. NOT SATISFIED. PLANT LIST NEEDS TO BE MODIFIED TO
 SEPARATE THE REQUIRED OPEN SPACE PLANT LISTS.
 PROVIDE A SEPARATE PLANT LIST FOR EACH OPEN SPACE AREA.
  
  
 11. SATISFIED. NATAL PLUM IS NOT A FLORIDA NATIVE
 PLANT.
  
 12. SATISFIED. SEAGRAPE IS SHOWN ON SHEET L-450, BUT NO
 SEAGRAPE IS PROPOSED ON PLANT LIST.
  
 13. PARTIALLY SATISFIED. PROVIDE THE 50 REQUIRED
 FLORIDA FRIENDLY POINTS BASED ON THE FINAL PLANT LIST
 PER SECTION 94-443(G).
 ADD A COLUMN FOR DROUGHT TOLERANCE TO THE PLANT LIST SO
 THAT IT CAN BE VERIFIED FOR EACH SPECIES.
  
 14. PARTIALLY SATISFIED. SHOW COMPLIANCE WITH SECTION
 94-445 L. PLANT SPECIES. A MINIMUM OF 60 PERCENT OF
 PLANT MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES. PROVIDE THE ACTUAL PERCENTAGE BASED
 ON THE PLANT LIST.
  
 ADD A COLUMN FOR DROUGHT TOLERANCE TO THE PLANT LIST SO
 THAT IT CAN BE VERIFIED FOR EACH SPECIES. CALCULATIONS
 ARE TO BE BASED ON THE ENTIRE PLANT LIST, NOT JUST
 TREES.
  
  
 15. NOT SATISFIED. ALL SURFACE PARKING MUST MEET THE
 REQUIREMENTS OF SECTION 94-443(C)(3) A. INCLUDING
 TERMINAL LANDSCAPE ISLANDS, INTERIOR ISLANDS AND SHADE
 TREES.
 ALL LANDSCAPE AREAS MUST BE SHOWN ON THE LANDSCAPE
 PLAN.
 TERMINAL LANDSCAPE ISLANDS MUST BE CREATED AT THE ENDS
 OF EACH ROW OF PARKING. INTERIOR ISLANDS MUST BE
 PROVIDED SO THERE ARE NO MORE THAN 10 SPACES IN A ROW.
 EACH LANDSCAPE ISLAND REQUIRES A TREE, AND AT LEAST 75%
 MUST BE CATEGORY 1 SHADE TREES.
 16. NOT SATISFIED. PROVIDE AN EXHIBIT SHOWING THE
 PARKING AREA SURFACE CALCULATIONS, PARKING SPACE AREAS
 AND LANDSCAPE AREAS PROVIDED TO DEMONSTRATE COMPLIANCE
 WITH SECTIONS 94-443 (C)(3) AND (4). PROVIDE THE
 CALCULATIONS IN THE LANDSCAPE REQUIREMENT CHART. REFER
 TO FIGURE XIV-1.
 PARTIAL CALCULATIONS WERE SHOWN, BUT NOT COMPLETE AND
 EXHIBIT WAS NOT PROVIDED.
  
 17. SATISFIED. PROVIDE SCREENING HEDGES FOR ALL GROUND
 MOUNTED VALVES AND EQUIPMENT AND ADD A NOTE THAT ALL
 EQUIPMENT WILL BE SCREENED.
 ADDITIONAL COMMENTS 2/23/22:
 18. THE EAST LANDSCAPE BUFFER IS NOT ON THE PROPERTY,
 IT IS OUTSIDE THE SITE ON A CITY OWNED PARCEL. THIS
 MUST BE ADDRESSED AS TO HOW THE AREA IS TO BE APPROVED
 AND MAINTAINED.
  
 19. REQUIRED OPEN SPACE PER SECTION 94-113 IS DIFFERENT
 AND SEPARATE FROM THE OVERALL LANDSCAPE REQUIREMENTS
 FOR THE SITE. OPEN SPACE AND LANDSCAPE AREAS ON THE
 LANDSCAPE LEGEND SHEET L-401 NEEDS TO BE CORRECTED TO
 REFLECT THIS.
  
 20. C. WEST BUFFER REQUIRES 26 TREES. SOUTH BUFFER
 SHOULD BE 13 TREES REQUIRED.
  
 21. STREET TREES SHOULD BE 13 REQUIRED.
  
 22. FOUNDATION LANDSCAPE REQUIREMENT NEEDS TO SHOW
 TOTAL LINEAR FOOTAGE FOR EACH BUILDING AND SHOW THAT AT
 LEAST 30% OF THAT IS LANDSCAPED AREA.
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 11-15-2021 Cont ID  
Sent By rcaranci Date 11-15-2021 Time 16:57 Rev Time 0.00
Received By rcaranci Date 11-15-2021 Time 16:57 Sent To  
Notes
2021-11-15 16:57:37FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 1001 OKEECHOBEE Z21100021
 NOVEMBER 15, 2021
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. SECTION 94-448 (D)(3) REQUIRES NATIVE TREES AND
 PALMS IN GOOD CONDITION TO BE PRESERVED ON SITE OR
 RELOCATED. ANSI A 300 (PART 5) STANDARDS SPECIFY
 EXAMPLES OF SUITABILITY RATINGS OF GOOD, MODERATE, OR
 POOR FOR RELOCATION. PROVIDE AN ARBORISTS REPORT RATING
 THE CONDITION AND RELOCATION POTENTIAL FOR THE NATIVE
 TREES AND PALMS. THERE ARE LIVE OAKS, SABAL PALMS,
 FLORIDA THATCH PALMS, AND ROYAL PALMS THAT ARE
 INDICATED TO BE REMOVED. NON NATIVE TREES AND PALMS ARE
 NOT REQUIRED TO BE RELOCATED.
 2. MAKE THE FOLLOWING CORRECTIONS TO THE TREE
 DISPOSITION LIST:
 ? ONLY TREES PROPOSED TO BE REMOVED WITH A CANOPY
 DIAMETER OF 20 FEET OR MORE SHOULD HAVE THE MITIGATION
 SQUARE FOOTAGE CALCULATED BASED ON THE ACTUAL DIAMETER.
 TREES LESS THAN 20 FEET CANOPY DIAMETER AND PALMS
 SHOULD SHOW THE CATEGORY MITIGATION DUE.
 ? MULTIPLE PALMS PLANTED TOGETHER MUST HAVE EACH SINGLE
 TRUNK COUNTED TOWARD MITIGATION. TRIPLE ADONIDIA WOULD
 BE 3 X 50 SQ FT.
  
 3. PROVIDE A DIAGRAM OF THE REQUIRED AND PROVIDED
 PUBLIC AND PRIVATE OPEN SPACE AREAS FOR CLD 25 ZONING
 DISTRICT. IDENTIFY THE TYPE OF OPEN SPACE AS ALLOWED BY
 TABLE IV-7 AND DEFINITIONS IN SECTION 94-109. SHOW HOW
 THE STANDARDS FOR THE TYPES OF OPEN SPACE ARE MET FOR
 VEGETATED AREAS AND TREE CANOPY SQUARE FOOTAGE BASED ON
 TABLE IV-8 ON THE LANDSCAPE PLAN. DIAGRAM ON SHEET
 A0.07 DOES NOT IDENTIFY THE OPEN SPACE TYPE OR CALL OUT
 HOW THE REQUIREMENTS OF THAT TYPE ARE MET.
 THE REQUIRED OPEN SPACE NEEDS TO BE QUANTIFIED,
 IDENTIFIED AS TO THE TYPE, AND ALL REQUIREMENTS NEED TO
 BE SHOWN FOR THAT OPEN SPACE TYPE. FOR OPEN SPACE SHOW
 THE TREE CANOPY SQUARE FOOTAGE FOR TREE TYPES BASED ON
 TABLE IV-8.
  
 4. IDENTIFY RELOCATED TREES OR PALMS ON THE PLANT LIST
 AND COUNT THEM TOWARD THE REQUIRED TREES.
 5. ALL EXISTING LANDSCAPING MUST BE SHOWN ON THE
 LANDSCAPE PLAN TO PROVIDE A COMPLETE PLAN SHOWING
 COMPLIANCE WITH CURRENT CODE REQUIREMENTS.
  
 6. ARTIFICIAL TURF AREAS PROPOSED MUST MEET THE
 REQUIREMENTS OF SECTION 94-451, INCLUDING ALL AREAS
 THAT ARE ALLOWED BY CODE MUST NOT BE VISIBLE FROM A
 ROAD OR STREET.
  
  
  
 7. BUFFER TREES AND HEDGES MUST BE PROVIDED ALONG ALL
 BUFFERS. THERE IS A LARGE GAP ADJACENT TO THE WEST
 PARKING GARAGE.
  
 8. PROVIDE CALCULATIONS FOR REQUIRED STREET TREES AT
 MAXIMUM SPACING EVERY 30 FEET OR PORTION THEREOF FOR
 THE OKEECHOBEE STREETSCAPE LENGTH, AND SHOW THE NUMBER
 PROVIDED PER SECTION 94-113 AND 94-116.
  
  
 9. SHOW ALL EXISTING AND PROPOSED WATER AND SEWER AND
 DRAINAGE LINES ON THE LANDSCAPE PLAN. SHOW LOCATIONS OF
 BACKFLOWS AND ADJUST LOCATIONS OF UTILITY LINES TO
 RESOLVE CONFLICTS WITH EXISTING AND PROPOSED TREES AND
 LANDSCAPING.
  
 10. PLANT LIST NEEDS TO BE MODIFIED TO SEPARATE THE
 REQUIRED OPEN SPACE PLANT LISTS.
  
 11. NATAL PLUM IS NOT A FLORIDA NATIVE PLANT.
  
 12. SEAGRAPE IS SHOWN ON SHEET L-450, BUT NO SEAGRAPE
 IS PROPOSED ON PLANT LIST.
  
 13. PROVIDE THE 50 REQUIRED FLORIDA FRIENDLY POINTS
 BASED ON THE FINAL PLANT LIST PER SECTION 94-443(G).
  
 14. SHOW COMPLIANCE WITH SECTION 94-445 L. PLANT
 SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL
 ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT
 SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF
 SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA
 WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA
 LANDSCAPES. PROVIDE THE ACTUAL PERCENTAGE BASED ON THE
 PLANT LIST.
  
  
 15. ALL SURFACE PARKING MUST MEET THE REQUIREMENTS OF
 SECTION 94-443(C)(3) A. INCLUDING TERMINAL LANDSCAPE
 ISLANDS, INTERIOR ISLANDS AND SHADE TREES.
 16. PROVIDE AN EXHIBIT SHOWING THE PARKING AREA SURFACE
 CALCULATIONS, PARKING SPACE AREAS AND LANDSCAPE AREAS
 PROVIDED TO DEMONSTRATE COMPLIANCE WITH SECTIONS 94-443
 (C)(3) AND (4). PROVIDE THE CALCULATIONS IN THE
 LANDSCAPE REQUIREMENT CHART. REFER TO FIGURE XIV-1.
  
 17. PROVIDE SCREENING HEDGES FOR ALL GROUND MOUNTED
 VALVES AND EQUIPMENT AND ADD A NOTE THAT ALL EQUIPMENT
 WILL BE SCREENED.
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By mtechnow Date 02-07-2022 Time 14:55 Sent To  
Notes
2022-02-07 14:54:51-SPLIT PLAN SHEETS. AT A MINIMUM, THE WATER AND
 WASTEWATER PLAN SHOULD BE ON A SEPARATE SHEET.
 -PROVIDE A REFERENCE/CALL OUT/NUMBER ON SHEET TO LINK
 THE EXISTING MH?S AND LINE SEGMENTS TO THE CCTV VIDEOS.
 -CALL OUT FOR VCP SEWER MAIN ON CLEARWATER PARK RD TO
 BE LINED FROM MH TO MH.
 -PROPOSED CONNECTIONS/ IMPROVEMENTS SEEM TO BE IN LINE
 WITH CITY STANDARDS. A MORE THOROUGH REVIEW WILL BE
 DONE WHEN PLANS MOVE FROM CONCEPTUAL.
  
  

Review Stop PW PUBLIC WORKS
Rev No 4 Status P Date 04-28-2022 Cont ID  
Sent By   Date 04-28-2022 Time   Rev Time 0.00
Received By   Date 04-28-2022 Time   Sent To  
Notes
2022-04-27 15:01:38CONDITION OF APPROVAL:
 EXCACT GARBAGE CONTAINER(S) LOCATION TO BE DETERMINED
 BY DEPARTMENT OF PUBLIC WORKS
  
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045

Review Stop PW PUBLIC WORKS
Rev No 3 Status F Date 03-14-2022 Cont ID  
Sent By   Date 03-14-2022 Time   Rev Time 0.00
Received By   Date 03-14-2022 Time   Sent To  
Notes
2022-03-14 12:24:57PLEASE PROVIDE DETAILS FOR SANITATION SERVICE (I.E.
 SOLID WASTE CONTAINER(S) TYPE, COLLECTION LOCATION,
 ETC.).
  
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045
  
  

Review Stop PW PUBLIC WORKS
Rev No 2 Status F Date 02-11-2022 Cont ID  
Sent By   Date 02-11-2022 Time   Rev Time 0.00
Received By   Date 02-11-2022 Time   Sent To  
Notes
2022-02-11 09:43:51 
 PLEASE PROVIDE THE FOLLOWINGS:
 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID
 WASTE VOLUME PRODUCED ALONG WITH THE SIZE AND TYPE OF
 THE CONTAINER (I.E. DUMPSTER/COMPACTOR) THAT WILL BE
 UTILIZED FOR THE SANITATION SERVICE.
  
 2- DETAILS FOR SANITATION SERVICE (I.E. SOLID WASTE
 CONTAINER(S) TYPE, COLLECTION LOCATION, ETC.).
  
 3- AUTO TURN (DYNAMIC ENVELOPE AND THE TIRES PATH) FOR
 THE SANITATION SERVICE, COLLECTION TRUCK (FRON OR REAR
 LOADER?).
  
 4- DESIGNATED LOCATION FOR THE BULK ITEM PICK UP.
  
 5- IN CASE OF PROPOSING ADDITION OF ANY NEW CAN(S) IN
 THE CITY`S RIGHT-OF-WAY , THE LOCATION AND QUANTITY OF
 THE CAN(S) SHALL BE REVIEWED AND APPROVED BY PUBLIC
 WORKS DEPARTMENT AND THE CAN(S) SHALL BE TYPE, SIZE AND
 COLOR APPROVED BY PUBLIC WORKS DEPARTMENT. THE BUILDING
 MAINTENANCE IS RESPONSIBLE TO MAINTAIN AND SERVICE THE
 CAN(S).
  
 6- OWNERS AND/OR OCCUPANTS OF PROPERTY THAT REQUIRE
 GREASE HAULING SERVICES SHALL ENSURE THAT THEIR GREASE
 TANKS OR CONTAINERS REMAIN CLEAN, AND ARE ENCLOSED AND
 NOT IN PUBLIC VIEW.
  
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 11-17-2021 Cont ID  
Sent By   Date 11-17-2021 Time   Rev Time  
Received By   Date 11-17-2021 Time   Sent To  
Notes
2021-11-17 14:33:30 
 PLEASE PROVIDE THE FOLLOWINGS:
 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID
 WASTE VOLUME PRODUCED ALONG WITH THE SIZE AND TYPE OF
 THE CONTAINER (I.E. DUMPSTER/COMPACTOR) THAT WILL BE
 UTILIZED FOR THE SANITATION SERVICE.
  
 2- DETAILS FOR SANITATION SERVICE (I.E. SOLID WASTE
 CONTAINER(S) TYPE, COLLECTION LOCATION, ETC.).
  
 3- AUTO TURN (DYNAMIC ENVELOPE AND THE TIRES PATH) FOR
 THE SANITATION SERVICE, FRONT LOADER TRUCK WITH THE
 FOLLOWING SPECS:
 - TRUCK LENGTH: 35 FT
 - TRUCK WIDTH: 11 FT
 - TURNING RADIUS:
 - SAE TURNING RADIUS: 32.5 FT
 - CURB-TO-CURB DIAMETER: 74 FT
 - WALL-TO-WALL DIAMETER: 86.3 FT
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045
  

Review Stop STORM STORMWATER
Rev No 2 Status P Date 11-28-2022 Cont ID  
Sent By tward Date 11-28-2022 Time 11:29 Rev Time 0.00
Received By tward Date 11-28-2022 Time 11:39 Sent To  
Notes
2022-11-28 11:38:56THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 4-12-2022 SUBMITTAL:
  
 1. [SATISFIED] THE CITY'S OFFICIAL VERTICAL DATUM PER
 CITY CODE IS NGVD1929. THE CITY IS ALLOWING SURVEYS AND
 PLANS TO USE NAVD1988 PROVIDED THE CONVERSION EQUATION
 BETWEEN NAVD1988 AND NGVD1929 IS ALSO PROVIDED. LIST
 THE CONVERSION EQUATION TO NGVD1929 ON THE SURVEY AND
 ON THE ENGINEERING PLAN.
  
 2. [SATISFIED] CONSIDER RELOCATING THE PROPOSED STORM
 CHAMBERS OUTSIDE OF THE UTILITY EASEMENT.
  
 3. [SATISFIED] ARE THE OVERHEAD LINES WITHIN AN
 EASEMENT?
  
 4. [SATISFIED] OKEECHOBEE BLVD IS MAINTAINED BY FDOT.
 PROVIDE PERMIT FROM FDOT PRIOR TO ENGINEERING PERMIT
 ISSUANCE FOR WORK WITHIN THE R/W.
  
 5. [SATISFIED] AUSTRALIAN AVE IS MAINTAINED BY PALM
 BEACH COUNTY. PROVIDE PERMIT FROM THE COUNTY PRIOR TO
 ENGINEERING PERMIT ISSUANCE FOR WORK WITHIN THE R/W.
  
 6. [SATISFIED - FLOW ARROWS WERE REMOVED FROM THE
 CONCEPTUAL P&D PLAN. THE AMOUNT OF RUNOIFF FLOWING TO
 OKEECHOBEE BLVD SHALL BE MINIMIZED.] ARE FLOW ARROWS
 SHOWN CORRECTLY FOR DRIVE LANES GOING TOWARD OKEECHOBEE
 BLVD?
  
 7. INDICATE IF ALL OF THE STORAGE CHAMBERS WILL BE
 INTERCONNECTED TO BALANCE OUT THE RUNOFF TO THE SYSTEM
 AND, IF NOT ALL INTERCONNECTED, THE INDIVIDUAL STORAGE
 CHAMBER AREAS ARE APPROPRIATELY SIZED FOR THE RUNOFF
 EXPECTED TO DRAIN TO THEM.
  
 8. [SATISFIED] CONDITION ASSESSMENT PERFORMED ON THE
 EXISTING CMP STORM PIPE TO REMAIN TO DETERMINE IF THE
 STORM PIPES SHOULD BE REPLACED OR LINED.
  
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  

Review Stop STORM STORMWATER
Rev No 1 Status F Date 11-18-2021 Cont ID  
Sent By tward Date 11-18-2021 Time 12:48 Rev Time 0.00
Received By tward Date 11-18-2021 Time 12:50 Sent To  
Notes
2021-11-18 12:50:191. THE CITY?S OFFICIAL VERTICAL DATUM PER CITY CODE IS
 NGVD1929. THE CITY IS ALLOWING SURVEYS AND PLANS TO USE
 NAVD1988 PROVIDED THE CONVERSION EQUATION BETWEEN
 NAVD1988 AND NGVD1929 IS ALSO PROVIDED. LIST THE
 CONVERSION EQUATION TO NGVD1929 ON THE SURVEY AND ON
 THE ENGINEERING PLAN.
  
 2. CONSIDER RELOCATING THE PROPOSED STORM CHAMBERS
 OUTSIDE OF THE UTILITY EASEMENT.
  
 3. ARE THE OVERHEAD LINES WITHIN AN EASEMENT?
  
 4. OKEECHOBEE BLVD IS MAINTAINED BY FDOT. PROVIDE
 PERMIT FROM FDOT PRIOR TO ENGINEERING PERMIT ISSUANCE
 FOR WORK WITHIN THE R/W.
  
 5. AUSTRALIAN AVE IS MAINTAINED BY PALM BEACH COUNTY.
 PROVIDE PERMIT FROM THE COUNTY PRIOR TO ENGINEERING
 PERMIT ISSUANCE FOR WORK WITHIN THE R/W.
  
 6. ARE FLOW ARROWS SHOWN CORRECTLY FOR DRIVE LANES
 GOING TOWARD OKEECHOBEE BLVD?
  
 7. INDICATE IF ALL OF THE STORAGE CHAMBERS WILL BE
 INTERCONNECTED TO BALANCE OUT THE RUNOFF TO THE SYSTEM
 AND, IF NOT ALL INTERCONNECTED, THE INDIVIDUAL STORAGE
 CHAMBER AREAS ARE APPROPRIATELY SIZED FOR THE RUNOFF
 EXPECTED TO DRAIN TO THEM.
  
 8. CONDITION ASSESSMENT PERFORMED ON THE EXISTING CMP
 STORM PIPE TO REMAIN TO DETERMINE IF THE STORM PIPES
 SHOULD BE REPLACED OR LINED.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. PROVIDE COPY OF SFWMD ERP PERMIT MODIFICATION BEFORE
 START OF CONSTRUCTION.
  
 2. PROVIDE A COPY OF THE DRAINAGE CALCULATIONS WITH THE
 ENGINEERING PERMIT APPLICATION.
  
 3. SWPPP REQUIRED WITH THE ENGINEERING PERMIT
 APPLICATION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 04-27-2022 Cont ID  
Sent By vnoel Date 04-27-2022 Time 07:16 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2022-04-27 07:17:56CONDITIONS OF APPROVAL:
  
 REPLAT PRIOR TO CO.
 EASEMENT ABANDONMENT PRIOR TO CO

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 11-09-2021 Cont ID  
Sent By vnoel Date 11-09-2021 Time 12:35 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2021-11-09 13:48:151. SURVEY INCLUDED CLEARWATER PARK ROAD. ARE THERE ANY
 PROPOSED IMPROVEMENTS?
 2. PROVIDE COPY OF TITLE SEARCH AND PROVIDE THE
 DATE/COMPANY/REPORT NUMBER ON SURVEY.
 3. ADD CONVERSION TO NGVD-29.
 4. THERE IS A LEASE AGREEMENT WITH THE CITY FOR THE
 ADJACENT GATEWAY PARK. WHAT ARE THE PLANS FOR THIS?
 5. SHOW IMPROVEMENTS IN CITY PARCEL ADJACENT TO EAST
 PROPERTY LINE.
 6. SEPARATE ENGINEERING PLANS INTO WATER & SEWER,
 PAVING & DRAINAGE.
 7. EASEMENTS TO BE ABANDONED WILL REQUIRE APPLICATION
 THROUGH ENGINEERING.
 8. REPLAT WILL BE REQUIRED AND CAN BE A CONDITION OF
 C.O.
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 3 Status F Date 05-02-2022 Cont ID  
Sent By   Date 05-02-2022 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2022-03-25 16:56:18TRAFFIC COMMENTS
 1) SATISFIED. PROVIDE COUNTY TPS LETTER ONCE AVAILABLE.
 2) SATISFIED. PROVIDE A FULL TRAFFIC STUDY ACCORDING TO
 ARTICLE 12. EXCEPTION FROM COUNTY CONCURRENCY DOES NOT
 PRECLUDE THE CITY TO REQUIRE AN IN-DEPTH ANALYSIS.
 MAJOR INTERSECTIONS WITHIN THE RDI SHALL BE INCLUDED IN
 THE ANALYSIS
 A. SATISFIED. PLEASE CAPTION EACH FIGURE. FIGURE 1
 SHOWCASING THE RDI SEEMS MISSING
 B. SATISFIED. PLEASE CLEARLY DENOMINATE AND ANALYZE
 EACH OF THE FOLLOWING SCENARIO IN THE ANALYSIS:
 EXISTING, FUTURE, FUTURE PLUS PROJECT
 C. SATISFIED. COORDINATE WITH COUNTY TRAFFIC SIGNAL
 DIVISION PERTAINING THE VALIDITY AND FEASIBILITY OF THE
 ADOPTED TRAFFIC SIGNAL OPTIMIZATIONS. PLEASE PROVIDE
 PROOF OF APPROVAL/ACKNOWLEDGMENT FROM THE COUNTY
 TRAFFIC SIGNAL DIVISION.
 D. SATISFIED. PROVIDE A SEPARATE FUTURE SCENARIO FOR
 THE AUSTRALIAN/CLEARWATER INTERSECTION INCLUSIVE OF THE
 FERN ST EXTENSION. TO BE FURTHER DISCUSSED.
 E. SATISFIED. THE FERN STREET EXTENSION SHALL BE
 CAPTURED AND ANALYZED. TO BE FURTHER DISCUSSED.
 F. SATISFIED. PER THE OKEECHOBEE BLVD EASTBOUND LEFT
 TURN LANE EXTENSION. PROVIDE MORE DETAILED ENGINEERING
 DRAWINGS. TO BE FURTHER DISCUSSED.
 G. SATISFIED. PER THE OKEECHOBEE BLVD EASTBOUND LEFT
 TURN LANE EXTENSION. PROVIDE A MORE IN-DEPTH QUEUE
 ANALYSIS, SHOWCASING RESULTS (I.E. BACK OF THE QUEUE)
 IN TABULAR AND GRAPHICAL FORM
 3) PARTIALLY SATISFIED. PROPOSED DEVELOPMENT IS
 GENERATING A SIGNIFICANT NUMBER OF NEW TRIPS, WHICH MAY
 SIGNIFICANTLY IMPACT THE EXISTING ROADWAY SYSTEM. IN
 THAT CASE, PROVIDE TDM STRATEGIES AND ROADWAY
 IMPROVEMENTS TO MITIGATE SUCH IMPACTS. FURTHER TDM
 MEASUREMENTS SHALL BE DISCUSSED AND ADOPTED. TO BE
 FURTHER DISCUSSED. APPLICANT TO PROVIDE A DRAFT TDM
 DOCUMENT PRIOR TO CONDITIONAL APPROVAL.
 4) SATISFIED. A METHODOLOGY MEETING SHOULD BE SCHEDULED
 PRIOR TO THE TRAFFIC STUDY REVISION AND TDM STRATEGIES
 PROPOSAL.
 SITE COMMENTS
 5) SATISFIED. PROVIDE A CLEAN SITE PLAN, SHOWCASING
 ONLY TRANSPORTATION FEATURES (I.E. ROAD, CURB, GUTTER,
 SIDEWALK, DRIVEWAY, PAVEMENT MARKING, SIGNAGE, PATHWAY,
 WALKWAY, PEDESTRIAN CROSSING, LOADING ZONE,
 PICK-UP/DROP-OFF AREA) AND CORRESPONDING DIMENSIONS.
 LATEST SUBMISSION (2/21/2022) DOES NOT SHOW STOP OR
 YIELD PAVEMENT MARKINGS, NOR THE CORRESPONDING SIGNAGE.
 LATEST SUBMISSION (3/11/2022) DOES NOT HAVE ALL THE
 REQUESTED FEATURES OR THEY ARE NOT CLEARLY LEGIBLE &
 IDENTIFIABLE, PLEASE PROVIDE A SEPARATE PLAN WITHIN THE
 TRANSPORTATION FOLDER, WITHOUT NON-RELEVANT ITEMS (E.G.
 DRAINAGE, UTILITIES, ETC.)
 6) SATISFIED. ON THE SITE PLAN, PLEASE SHOWCASE BASIC
 CURB DETAILS (I.E. DRIVEWAY AND PARKING STALLS) ON THE
 OPPOSITE SIDE OF THE ROADS SURROUNDING THE PROPOSED
 DEVELOPMENT. PLEASE PROVIDE DOCUMENT NAME AND SHEET
 NUMBER SHOWCASING SUCH FEATURES.
 7) SATISFIED. PROVIDE AUTOTURN ANALYSIS FOR GARBAGE
 TRUCK AND/OR SERVICE VEHICLES DRIVING IN AND OUT OF THE
 PROPOSED DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES
 CLEARLY DEFINED. ANALYSIS SHOULD BE PROVIDED IN A
 SEPARATE FILE/DRAWING. PLEASE PROVIDE DOCUMENT NAME AND
 SHEET NUMBER SHOWCASING THE ANALYSIS.
 8) SATISFIED. IDENTIFY AND DESIGNATE AN EASILY
 ACCESSIBLE MICRO-MOBILITY STATION AREA (MINIMUM 8 X 20
 FEET) AND PROVIDE BASIC ELECTRIFICATION READINESS. FOR
 THE LATTER ITEM, MORE SPECIFICALLY: A CONDUIT (2?
 SCHEDULE 40 PVC) TO THE POWER SOURCE WITH AN ELECTRICAL
 PULL BOX (240V CIRCUIT). PLEASE PROVIDE DOCUMENT NAME
 AND SHEET NUMBER SHOWCASING SUCH FEATURE. THE PROPOSED
 PAD IS NOT EASILY ACCESSIBLE BY THE PUBLIC, IT MUST BE
 RELOCATED NEARBY THE HOTEL OR CONFERENCE CENTER
 ENTRANCES BY THE ROUNDABOUT. CONSIDERING THE EXTENT OF
 THE PROPOSED DEVELOPMENT A LARGER AREA SHOULD BE
 DEDICATED (E.G. 15 X 30)
 9) SATISFIED. PROVIDE PARKING TABLE SHOWCASING THE
 NUMBER OF REQUIRED AND PROVIDED PARKING SPACES,
 INCLUSIVE OF ADA AND BICYCLE ONES. JUSTIFICATION
 STATEMENT DOES NOT PROVIDE ADA NOR BICYCLE PARKING
 BREAKDOWN. PLEASE REVISE AND PROPERLY MARK THE LOCATION
 OF BICYCLE STALLS AND CORRESPONDING DOCUMENT NAME AND
 SHEET NUMBER. PERTAINING ADA PARKING REQUIREMENTS,
 PLEASE PROVIDE EXACT TOTAL NUMBER OF SPACES, AS "OVER
 1,000" IS NOT ACCEPTABLE CONSIDERING THE ADA CRITERIA
 (ONE FOR EACH 100 OVER 1,000). NOTE: THE ADA PARKING
 SPACES FOR GATEWAY PARK SHOULD NOT BE INCLUDED IN THE
 REQUIRED TOTAL FOR THE PROPOSED DEVELOPMENT. SHEET
 A0.02 DOES NOT CONTAIN THE REQUESTED INFORMATION.
 10) SATISFIED. PROVIDE A DECELERATION LANE FOR THE
 OKEECHOBEE BLVD DRIVEWAY
 11) SATISFIED. PLEASE INSTALL A FULL ROUNDABOUT SO TO
 ALLOW ALL MOVEMENTS
 12) SATISFIED. PROVIDE A MULTIUSE PATH ALONG OKEECHOBEE
 BLVD SIMILAR, IF NOT EXACTLY AS THE ONE EAST OF
 TAMARIND AVE. COMMENT WILL BE SATISFIED ONCE THE
 MULTIUSE PATH IS SHOWN ON SITE PLANS AND A DETAILED
 PROFILE DRAWING PROVIDED. COMMENT WILL BE SATISFIED
 ONCE PACKAGE IS PROVIDED OR WILL BE CONVERTED AS A
 CONDITIONAL APPROVAL
 13) PARTIALLY SATISFIED. PROVIDE DETAILS OF SIGNAGE AND
 WAYFINDING FOR PARK PATRONS NEARBY SITE ENTRANCE AND BY
 THE SURFACE PARKING LOT. COMMENT WILL BE SATISFIED ONCE
 PACKAGE IS PROVIDED OR WILL BE CONVERTED AS A
 CONDITIONAL APPROVAL
 14) PARTIALLY SATISFIED. INSTALL SIGNAGE RESTRICTING
 USAGE OF CITY STALLS TO PARK PATRONS ONLY AND
 PROHIBITING OVERNIGHT PARKING. COMMENT WILL BE
 SATISFIED ONCE PACKAGE IS PROVIDED OR WILL BE CONVERTED
 AS A CONDITIONAL APPROVAL
 15) SATISFIED. DESIGNATE TWO OF THE CITY STALLS NEARBY
 THE PARK ENTRANCE AS HANDICAP, DESIGN THEM PER ADA
 STANDARDS ACCORDINGLY. PLEASE MOVE SUCH SPACES CLOSER
 OR IN FRONT OF PARK ENTRANCE
 16) SATISFIED. ON SHEET A0.06 THE PARKING STALLS ON THE
 NORTH-EAST CORNER OF THE GARAGE SEEMS IN CONFLICT,
 PLEASE REVISE AND CLEARLY INDICATE THE PEDESTRIAN-ONLY
 AREA SURROUNDING THE STAIRCASE ACCESS
 17) SATISFIED. INSERT VEHICULAR DIRECTIONAL MARKINGS IN
 SHEET A0.08, SIMILAR TO SHEET A0.05
 18) SATISFIED. THE TURNING RADIUS AND VEHICLE
 MANEUVERING ON AND OFF THE GARAGE RAMP SEEMS EXTREMELY
 TIGHT AND DANGEROUS. PROVIDE AUTOTURN ANALYSIS
 DEPICTING A VEHICLE ACCESSING THE GARAGE, DRIVING UP
 AND THROUGH THE SECOND FLOOR AND BACK OUT. PLEASE
 PROVIDE GARAGE AUTOTURN DRAWINGS AS MENTIONED IN THE
 COMMENT RESPONSE OR INDICATE SHEET NUMBER IF ALREADY
 PROVIDED
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status F Date 02-16-2022 Cont ID  
Sent By   Date 02-16-2022 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2022-02-16 23:53:58TRAFFIC COMMENTS
 1) PARTIALLY SATISFIED. PROVIDE COUNTY TPS LETTER ONCE
 AVAILABLE.
 2) PARTIALLY SATISFIED. PROVIDE A FULL TRAFFIC STUDY
 ACCORDING TO ARTICLE 12. EXCEPTION FROM COUNTY
 CONCURRENCY DOES NOT PRECLUDE THE CITY TO REQUIRE AN
 IN-DEPTH ANALYSIS. MAJOR INTERSECTIONS WITHIN THE RDI
 SHALL BE INCLUDED IN THE ANALYSIS
 A. PLEASE CAPTION EACH FIGURE. FIGURE 1 SHOWCASING THE
 RDI SEEMS MISSING
 B. PLEASE CLEARLY DENOMINATE AND ANALYZE EACH OF THE
 FOLLOWING SCENARIO IN THE ANALYSIS: EXISTING, FUTURE,
 FUTURE PLUS PROJECT
 C. COORDINATE WITH COUNTY TRAFFIC SIGNAL DIVISION
 PERTAINING THE VALIDITY AND FEASIBILITY OF THE ADOPTED
 TRAFFIC SIGNAL OPTIMIZATIONS
 D. PROVIDE A SEPARATE FUTURE SCENARIO FOR THE
 AUSTRALIAN/CLEARWATER INTERSECTION INCLUSIVE OF THE
 FERN ST EXTENSION
 E. THE FERN STREET EXTENSION SHALL BE CAPTURED AND
 ANALYZED FOR THE
 F. PER THE OKEECHOBEE BLVD EASTBOUND LEFT TURN LANE
 EXTENSION. PROVIDE MORE DETAILED ENGINEERING DRAWINGS
 G. PER THE OKEECHOBEE BLVD EASTBOUND LEFT TURN LANE
 EXTENSION. PROVIDE A MORE IN-DEPTH QUEUE ANALYSIS,
 SHOWCASING RESULTS (I.E. BACK OF THE QUEUE) IN TABULAR
 AND GRAPHICAL FORM
 3) PARTIALLY SATISFIED. PROPOSED DEVELOPMENT IS
 GENERATING A SIGNIFICANT NUMBER OF NEW TRIPS, WHICH MAY
 SIGNIFICANTLY IMPACT THE EXISTING ROADWAY SYSTEM. IN
 THAT CASE, PROVIDE TDM STRATEGIES AND ROADWAY
 IMPROVEMENTS TO MITIGATE SUCH IMPACTS. FURTHER TDM
 MEASUREMENTS SHALL BE DISCUSSED AND ADOPTED.
 4) SATISFIED. A METHODOLOGY MEETING SHOULD BE SCHEDULED
 PRIOR TO THE TRAFFIC STUDY REVISION AND TDM STRATEGIES
 PROPOSAL
 SITE COMMENTS
 5) PARTIALLY SATISFIED. PROVIDE A CLEAN SITE PLAN,
 SHOWCASING ONLY TRANSPORTATION FEATURES (I.E. ROAD,
 CURB, GUTTER, SIDEWALK, DRIVEWAY, PAVEMENT MARKING,
 SIGNAGE, PATHWAY, WALKWAY, PEDESTRIAN CROSSING, LOADING
 ZONE, PICK-UP/DROP-OFF AREA) AND CORRESPONDING
 DIMENSIONS. LATEST SUBMISSION DOES NOT SHOW STOP OR
 YIELD PAVEMENT MARKINGS, NOR THE CORRESPONDING SIGNAGE
 6) SATISFIED. ON THE SITE PLAN, PLEASE SHOWCASE BASIC
 CURB DETAILS (I.E. DRIVEWAY AND PARKING STALLS) ON THE
 OPPOSITE SIDE OF THE ROADS SURROUNDING THE PROPOSED
 DEVELOPMENT. PLEASE PROVIDE DOCUMENT NAME AND SHEET
 NUMBER SHOWCASING SUCH FEATURES.
 7) SATISFIED. PROVIDE AUTOTURN ANALYSIS FOR GARBAGE
 TRUCK AND/OR SERVICE VEHICLES DRIVING IN AND OUT OF THE
 PROPOSED DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES
 CLEARLY DEFINED. ANALYSIS SHOULD BE PROVIDED IN A
 SEPARATE FILE/DRAWING. PLEASE PROVIDE DOCUMENT NAME AND
 SHEET NUMBER SHOWCASING THE ANALYSIS.
 8) PARTIALLY SATISFIED. IDENTIFY AND DESIGNATE AN
 EASILY ACCESSIBLE MICRO-MOBILITY STATION AREA (MINIMUM
 8 X 20 FEET) AND PROVIDE BASIC ELECTRIFICATION
 READINESS. FOR THE LATTER ITEM, MORE SPECIFICALLY: A
 CONDUIT (2' SCHEDULE 40 PVC) TO THE POWER SOURCE WITH
 AN ELECTRICAL PULL BOX (240V CIRCUIT). PLEASE PROVIDE
 DOCUMENT NAME AND SHEET NUMBER SHOWCASING SUCH FEATURE.
 THE PROPOSED PAD IS NOT EASILY ACCESSIBLE BY THE
 PUBLIC, IT MUST BE RELOCATED NEARBY THE HOTEL OR
 CONFERENCE CENTER ENTRANCES BY THE ROUNDABOUT.
 CONSIDERING THE EXTENT OF THE PROPOSED DEVELOPMENT A
 LARGER AREA SHOULD BE DEDICATED (E.G. 15 X 30)
 9) NOT SATISFIED. PROVIDE PARKING TABLE SHOWCASING THE
 NUMBER OF REQUIRED AND PROVIDED PARKING SPACES,
 INCLUSIVE OF ADA AND BICYCLE ONES. JUSTIFICATION
 STATEMENT DOES NOT PROVIDE ADA NOR BICYCLE PARKING
 BREAKDOWN. PLEASE REVISE AND PROPERLY MARK THE LOCATION
 OF BICYCLE STALLS AND CORRESPONDING DOCUMENT NAME AND
 SHEET NUMBER
 10) SATISFIED. PROVIDE A DECELERATION LANE FOR THE
 OKEECHOBEE BLVD DRIVEWAY
 11) SATISFIED. PLEASE INSTALL A FULL ROUNDABOUT SO TO
 ALLOW ALL MOVEMENTS
 12) PROVIDE A MULTIUSE PATH ALONG OKEECHOBEE BLVD
 SIMILAR, IF NOT EXACTLY AS THE ONE EAST OF TAMARIND AVE
 13) PROVIDE DETAILS OF SIGNAGE AND WAYFINDING FOR PARK
 PATRONS NEARBY SITE ENTRANCE AND BY THE SURFACE PARKING
 LOT
 14) INSTALL SIGNAGE RESTRICTING USAGE OF CITY STALLS TO
 PARK PATRONS ONLY AND PROHIBITING OVERNIGHT PARKING
 15) DESIGNATE TWO OF THE CITY STALLS NEARBY THE PARK
 ENTRANCE AS HANDICAP, DESIGN THEM PER ADA STANDARDS
 ACCORDINGLY
 16) ON SHEET A0.06 THE PARKING STALLS ON THE NORTH-EAST
 CORNER OF THE GARAGE SEEMS IN CONFLICT, PLEASE REVISE
 AND CLEARLY INDICATE THE PEDESTRIAN-ONLY AREA
 SURROUNDING THE STAIRCASE ACCESS
 17) INSERT VEHICULAR DIRECTIONAL MARKINGS IN SHEET
 A0.08, SIMILAR TO SHEET A0.05
 18) THE TURNING RADIUS AND VEHICLE MANEUVERING ON AND
 OFF THE GARAGE RAMP SEEMS EXTREMELY TIGHT AND
 DANGEROUS. PROVIDE AUTOTURN ANALYSIS DEPICTING A
 VEHICLE ACCESSING THE GARAGE, DRIVING UP AND THROUGH
 THE SECOND FLOOR AND BACK OUT.
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 11-18-2021 Cont ID  
Sent By   Date 11-18-2021 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2021-11-18 12:21:08TRAFFIC COMMENTS
 1) PROVIDE COUNTY TPS LETTER
 2) PROVIDE A FULL TRAFFIC STUDY ACCORDING TO ARTICLE
 12. EXCEPTION FROM COUNTY CONCURRENCY DOES NOT PRECLUDE
 THE CITY TO REQUIRE AN IN-DEPTH ANALYSIS. MAJOR
 INTERSECTIONS WITHIN THE RDI SHALL BE INCLUDED IN THE
 ANALYSIS
 3) PROPOSED DEVELOPMENT IS GENERATING A SIGNIFICANT
 NUMBER OF NEW TRIPS, WHICH MAY SIGNIFICANTLY IMPACT THE
 EXISTING ROADWAY SYSTEM. IN THAT CASE, PROVIDE TDM
 STRATEGIES AND ROADWAY IMPROVEMENTS TO MITIGATE SUCH
 IMPACTS.
 4) A METHODOLOGY MEETING SHOULD BE SCHEDULED PRIOR TO
 THE TRAFFIC STUDY REVISION AND TDM STRATEGIES PROPOSAL
  
 SITE COMMENTS
 5) PROVIDE A CLEAN SITE PLAN, SHOWCASING ONLY
 TRANSPORTATION FEATURES (I.E. ROAD, CURB, GUTTER,
 SIDEWALK, DRIVEWAY, PAVEMENT MARKING, SIGNAGE, PATHWAY,
 WALKWAY, PEDESTRIAN CROSSING, LOADING ZONE,
 PICK-UP/DROP-OFF AREA) AND CORRESPONDING DIMENSIONS
 6) ON THE SITE PLAN, PLEASE SHOWCASE BASIC CURB DETAILS
 (I.E. DRIVEWAY AND PARKING STALLS) ON THE OPPOSITE SIDE
 OF THE ROADS SURROUNDING THE PROPOSED DEVELOPMENT.
 PLEASE PROVIDE DOCUMENT NAME AND SHEET NUMBER
 SHOWCASING SUCH FEATURES.
 7) PROVIDE AUTOTURN ANALYSIS FOR GARBAGE TRUCK AND/OR
 SERVICE VEHICLES DRIVING IN AND OUT OF THE PROPOSED
 DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES CLEARLY
 DEFINED. ANALYSIS SHOULD BE PROVIDED IN A SEPARATE
 FILE/DRAWING. PLEASE PROVIDE DOCUMENT NAME AND SHEET
 NUMBER SHOWCASING THE ANALYSIS.
 8) IDENTIFY AND DESIGNATE AN EASILY ACCESSIBLE
 MICRO-MOBILITY STATION AREA (MINIMUM 8 X 20 FEET) AND
 PROVIDE BASIC ELECTRIFICATION READINESS. FOR THE LATTER
 ITEM, MORE SPECIFICALLY: A CONDUIT (2? SCHEDULE 40 PVC)
 TO THE POWER SOURCE WITH AN ELECTRICAL PULL BOX (240V
 CIRCUIT). PLEASE PROVIDE DOCUMENT NAME AND SHEET NUMBER
 SHOWCASING SUCH FEATURE.
 9) PROVIDE PARKING TABLE SHOWCASING THE NUMBER OF
 REQUIRED AND PROVIDED PARKING SPACES, INCLUSIVE OF ADA
 AND BICYCLE ONES
 10) PROVIDE A DECELERATION LANE FOR THE OKEECHOBEE BLVD
 DRIVEWAY
 11) PLEASE INSTALL A FULL ROUNDABOUT SO TO ALLOW ALL
 MOVEMENTS
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status F Date 03-31-2022 Cont ID  
Sent By aaponte Date 03-31-2022 Time 15:26 Rev Time 0.00
Received By aaponte Date 03-08-2022 Time 14:19 Sent To  
Notes
2022-03-31 15:26:191. PARTIALLY SATISFIED- PLEASE CONFIRM THE LISTED
 356,864SF INCLUDES TRACK A AND B, AND LOT 7 AND 8.
 PREVIOUS COMMENT - PLEASE UPDATE SURVEY TO INCLUDE
 TOTAL SQUARE FOOTAGE OF PARCEL (TRACK A + B) .
 -PREVIOUS COMMENT (PC)- PLEASE CONFIRM THE PROPERTY
 LINE INDICATED IN DRAWINGS ACCURATELY REFLECT THE
 LOCATION OF THE PROPERTY LINE ACCORDING TO SURVEY.
 2. PARTIALLY SATISFIED - PLEASE CONFIRM THE CORE OF THE
 OFFICE TOWER IN FLOORS 3 TO 7 ARE INCLUDED. SCHEMATICS
 FOR THOSE FLOORS WERE NOT INCLUDED. -PREVIOUS COMMENT-
 PLEASE CONFIRM THE SQUARE FOOTAGE OF THE EXISTING
 BUILDING REFLECTS THE GBA DEFINITION IN CURRENT CODE -
 PC -PLEASE PROVIDE A GBA TABLE WITH THE INFORMATION OF
 EXISTING ALLOWABLE GBA FOR SITE, EXISTING GBA FOR
 MARRIOTT, AND PROPOSED GBA.
 3. PARTIALLY SATISFIED -PLEASE CONFIRM THE CORE OF THE
 OFFICE TOWER IN FLOORS 3 TO 7 ARE INCLUDED. SCHEMATICS
 FOR THOSE FLOORS WERE NOT INCLUDED. -PREVIOUS COMMENTS-
 VERTICAL CIRCULATION THROUGH THE GARAGE LEVELS SHALL BE
 COUNTED IN THE GBA NUMBERS. PLEASE IDENTIFY IF THE CORE
 (NOT COLORED IN GROSS FLOOR PLAN SHEETS) IS ALL
 INCLUDED IN THE GBA. MECHANICAL ROOMS CAN BE EXCLUDED.
 PLEASE LABEL EACH OF THE SPACES THAT ARE NOT CLEARLY
 IDENTIFIABLE- PC- PLEASE PROVIDE A FLOOR BY FLOOR PLAN
 AND TABLE INDICATING THE AREAS THAT ARE INCLUDED IN THE
 GBA CALCULATION ACCORDING TO THE GBA DEFINITION IN
 SECTION 94-109. CALL OUT THE USE IN EACH OF THE AREAS.
 GBA IN SHEETS A0.14, A0.15 AND A0.16 DO NOT MATCH THE
 GBA DEFINITION BY CODE.
 4. NOT SATISFIED ? SEE COMMENTS BELOW UNDER NO. 28.-
 PREVIOUS COMMENT -PUBLIC OPEN SPACE DOES NOT COMPLY
 WITH THE REQUIREMENTS ACCORDING TO SECTION 94-109 OR
 TABLE IV-7. PROPOSED PUBLIC OPEN SPACE DOES NOT ABUT AN
 ACTIVE USE OR COMPLIES WITH MINIMUM PROPORTIONS.
 5. PARTIALLY SATISFIED ? INFORMATION TO CONFIRM
 COMPLIANCE HAS NOT BEEN PROVIDED. SEE LANDSCAPE REVIEW
 COMMENTS. PRIVATE OPEN SPACE WEST OF THE NEW POOL
 BUILDING IS LOCATED ALONG LOT FRONTAGE THEREFORE IT
 SHALL BE DESIGNED IN COMPLIANCE WITH THE POS STANDARDS
 AND BE ACCESSIBLE TO THE PUBLIC. PLEASE VERIFY
 COMPLIANCE ? PREVIOUS COMMENT - PLEASE CLASSIFY THE
 PRIVATE OPEN SPACE TYPE PROPOSED ACCORDING TO TABLE
 IV-7. GREEN/ LANDSCAPE BUFFERS DO NOT QUALIFY AS
 PRIVATE OPEN SPACE. LANDSCAPE EDGE SOUTH OF THE NEW
 HOTEL POOL BUILDING OR LANDSCAPE EAST OF THE EXISTING
 HOTEL ENTRANCE ARE REALLY LEFT OVER AREAS NOT PRIVATE
 OPEN SPACES. - PC- PROJECT DOES NOT COMPLY WITH THE
 PRIVATE OPEN SPACE MINIMUM REQUIREMENTS. PLEASE EXPLAIN
 THE HARDSHIPS JUSTIFYING THE VARIANCE REQUEST.
 6. PARTIALLY SATISFIED ? FOR DAC SUBMITTAL PLEASE
 PROVIDE BLOW OUT DETAILS OF THE MOST IMPORTANT GROUND
 FLOOR AREAS AND MOST IMPORTANT FEATURES OF BUILDING
 DESIGN SUCH AS METAL TRIM LOUVERS AND CURTAIN WALL,
 TERRACE PLANTERS. PREVIOUS COMMENT: COLORED ELEVATIONS
 NOT PROVIDED. - PC- PLEASE PROVIDE COLORED ELEVATIONS
 WITH CALL OUT MATERIALS FOR ALL ELEVATIONS. PLEASE
 INCLUDE PHOTOS OF PROPOSED MATERIALS.
 7. SATISFIED - PLEASE STUDY THE EFFICIENCY OF THE
 GARAGE LAYOUT FOR POSSIBLE REDUCTION ON TOTAL NUMBER OF
 FLOORS. NORTHERN GARAGE LAYOUT DOES NOT SEEM TO
 FUNCTION.
 8. NOT SATISFIED- VARIANCE JUSTIFICATION SHALL BE
 PROVIDED AND DAC APPROVAL NEEDED - GARAGE STRUCTURE
 EXCEEDS THE MAXIMUM FOOTPRINT LENGTH OF 350 FEET
 ALLOWED AND DOES NOT COMPLY WITH MINIMUM 60 FEET
 SEPARATION. A BREAK IS RECOMMENDED AND A VARIANCE WILL
 BE NEEDED - PC- PLEASE PROVIDE INFORMATION TO CONFIRM
 THE PROJECT COMPLIES WITH THE MAXIMUM 350 FEET
 FOOTPRINT LENGTH ALLOWED IN THE DISTRICT.
 9. NOT SATISFIED ? VARIANCE JUSTIFICATION SHALL BE
 PROVIDED AND DAC APPROVAL NEEDED- PC - PROJECT EXCEEDS
 THE MAXIMUM SETBACK ALLOWED ALONG OKEECHOBEE BLVD,
 CREATING A SUBURBAN CONFIGURATION DUE TO THE LOCATION
 OF THE VEHICULAR ACCESS DRIVES IN FRONT OF THE
 BUILDING.
 10. SATISFIED - PC - PLEASE PROVIDE INFORMATION TO
 CONFIRM COMPLIANCE WITH MAXIMUM BUILDING FOOTPRINTS
 ALLOWED.
 11. SATISFIED. PLEASE INCLUDE THE OVERALL BUILDING
 HEIGHT TO CONFIRM COMPLIANCE WITH MAXIMUM VERTICAL
 PROJECTIONS- PC - ON FA?ADE, PLEASE INDICATE THE
 ELEVATION OF EACH FLOOR LEVEL.
 12. SATISFIED - PC - PROPOSED PROJECT REMOVED THE TURN
 AROUND SPACE AT THE END OF CLEARWATER PARK ROAD. IF A
 GATE AT THE ENTRANCE OF THE PROPERTY IS INSTALLED,
 VEHICLES DO NOT HAVE SPACE TO TURN AROUND.
 13. NOT SATISFIED ? VARIANCE JUSTIFICATION SHALL BE
 PROVIDED, AND DAC APPROVAL NEEDED ? PC-PLEASE PROVIDE
 INFORMATION TO CONFIRM THE PROJECT COMPLIES WITH THE
 MINIMUM ACTIVE USE REQUIRED ALONG THE AVENUE
 DESIGNATION AND THE CSX FRONTAGE.
 14. NOT SATISFIED ? OKEECHOBEE FRONTAGE LISTED AS 552
 LINEAR FEET THEREFORE 19 TREES REQUIRED ALONG THE
 FRONTAGE NEXT TO THE CURB WITHIN A PLANTING AREA. ONLY
 13 TREES PROVIDED. A 12 FOOT WIDE MULTIPURPOSE PATH
 SHALL BE PROVIDED. - PREVIOUS COMMENT- IMPROVEMENTS
 NEED TO BE INDICATED IN THE LANDSCAPE AND HARDSCAPE
 PLAN FOR REVIEW DRUING THE SITE PLAN APPROVAL PROCESS.-
 PC- STREETSCAPE ALONG OKEECHOBEE SHALL BE DESIGNED TO
 CONTINUE THE RECENT DESIGN IMPLEMENTED BETWEEN TAMARIND
 AND ROSEMARY. STREET TREES PLANTED EVERY 30 FEET, A
 CONTINUOUS HEDGE OR GROUND COVER ALONG OKEECHOBEE AND A
 MULTIPURPOSE PATH OF 12 FEET IN WIDTH.
 15. SATISFIED - PLEASE PROVIDE BUILDING SECTION.
 16. SATISFIED - PC-PLEASE PROVIDE GRAPHIC INFORMATION
 TO CONFIRM COMPLIANCE WITH THE PLANAR BREAK
 REQUIREMENTS.
 17. SATISFIED - PLEASE NOTE THAT MINIMUM SETBACKS ARE
 ALSO APPLICABLE TO GARAGE STRUCTURES. CHECK INFORMATION
 PROVIDED IN SHEET A0.01 REGARDING INTERIOR SETBACK.
 18. PARTIALLY SATISFIED ? THE 552 LINEAR FEET OF
 FRONTAGE ALONG OKEECHOBEE REQUIRES 6 PUBLIC BIKE
 PARKING SPACES. THESE SPACES SHALL BE LOCATED CLOSE TO
 THE OFFICE AND CONVENTION CENTER ENTRANCE. THE FINAL
 LOCATION OF THE MICRO-MOBILITY STATION SHALL BE
 DISCUSSED WITH THE PROVIDER. PREVIOUS COMMENT -PLEASE
 INDICATE THE LOCATION OF THE REQUIRED PUBLIC BIKE
 PARKING SPACES 1/100? FEET OF FRONTAGE.
 19. PARTIALLY SATISFIED ? COMPLIANCE TABLE IS SHEET
 A0.01 INDICATE THAT 71 BIKE PARKING SPACES ARE REQUIRED
 FOR THE PROJECT. PLEASE CLEARLY INDICATE THE LOCATION
 OF THE SECURE BIKE ROOM. ONLY SPACE FOR 46 BIKES
 IDENTIFIED IN SHEET A0.05. PREVIOUS COMMENT- PLEASE
 INDICATE THE LOCATION OF THE REQUIRED SECURED BIKE
 PARKING FOR THE OFFICE USE AT A RATIO OF 1/15 PARKING
 SPACES PROVIDED (74 BIKE SPACES REQUIRED).
 20. SATISFIED - FOR THE PARKING CALCULATIONS, PLEASE
 LIST EACH OF THE EXISTING AND PROPOSED USES (WITH NET
 SQUARE FOOTAGE OR NUMBER OF ROOMS) AND THE REQUIRED AND
 PROVIDED PARKING.
 21. PARTIALLY SATISFIED ? PLEASE INCLUDE A CONNECTION
 ON THE WEST SIDE OF THE ACCESS ROAD FROM THE GARAGE
 ALONG THE LOADING AS IT IS THE FASTEST ROUTE. PREVIOUS
 COMMENT - PLEASE IDENTIFY THE ROUTE OF PEDESTRIAN
 ACCESS TO THE HOTEL AND OFFICE FROM CLEARWATER PARK
 ROAD.
 22. NOT SATISFIED - PLEASE PROVIDE NARRATIVE JUSTIFYING
 THE REQUESTED VARIANCES. DETAILED COMPLIANCE WITH
 VARIANCE STANDARDS WILL BE REQUIRED FOR DAC REVIEW.
 NEW COMMENTS FOR 2-1-22
 23. SATISFIED - MONUMENT SIGNS ARE NOT PERMITTED IN THE
 DOWNTOWN MASTER PLAN AREA.
 24. SATISFIED - PROPOSED SIDEWALK ALONG THE EAST SIDE
 OF THE PROPERTY IS WITHIN CITY-OWNED PROPERTY THAT IS
 CURRENTLY USED BY THE TRI-RAIL MAINTENANCE YARD.
 25. NOT SATISFIED- EXISTING CHILLER SHALL BE SCREENED
 AND A LANDSCAPE BUFFER SHALL BE PROVIDED AROUND.
  
 ADDITIONAL COMMENTS FOR 3-8-22 RESUBMITTAL
 26. PLEASE REMOVE THE SEMI-PUBLIC OPEN SPACE FROM THE
 OPEN SPACE TABLE AS IT IS NOT APPLICABLE FOR THIS
 PROJECT.
 27. PLEASE PROVIDE INFORMATION ON THE PROPOSED PLANTER
 ALONG THE EDGE OF THE TERRACES AND PARKING GARAGE.
 DETAILS NEEDED ON PROPOSED INSTALLATION SYSTEM,
 IRRIGATION AND PROPOSED LANDSCAPE MATERIAL.
 28. COMPLIANCE WITH POS: STAFF SUGGESTS APPLICANT TO
 UTILIZE THE SPACE NEXT TO THE ROW TO COMPLY WITH THE
 POS REQUIREMENT AND ASK FOR NECESSARY VARIANCES (ACTIVE
 USE ABUTMENT). ALL OTHER STANDARDS CAN BE MET.
 IMPROVEMENTS SHALL BE DONE TO PEDESTRIAN AREA IN FRONT
 OF BUILDINGS, THE DROP-OFF AREA AND ACCESS ROAD TO
 MINIMIZE THE NEGATIVE IMPACT ON THE POS. FOR EXAMPLE:
 TREATMENT OF BLANK WALL AT SOUTH END OF HOTEL BUILDING;
 IDENTIFY THE TREATMENT OF THE WEST CONFERENCE CENTER
 WALL; PROVISION OF TREES ALONG THE ACCESS ROAD. IN
 ADDITION, POS NEXT TO OKEECHOBEE WEST OF ACCESS DRIVE
 SHALL BE INTEGRATED TO THE EXISTING CITY PARK ON WEST
 SIDE.
 29. ADA ACCESS SHALL BE PROVIDED FROM THE OKEECHOBEE
 SIDEWALK TO THE OFFICE ENTRANCE.
 30. PEDESTRIAN ACCESS SHALL BE PROVIDED ALSO ALONG THE
 WEST SIDE OF THE ACCESS ROAD. SCREENING OF LOADING
 RECOMMENDED, POSSIBLY REMOVAL OF CURB CUT EAST OF
 LOADING. RENDERING SHOW SOME ENCLOSURE BUT DRAWINGS DO
 NOT INDICATE ANYTHING.
 31. RENDERINGS SHOW THAT THE WEST ELEVATION OF THE
 GARAGE ABOVE THE CONFERENCE CENTER IS VISIBLE FROM THE
 STREET. ARCHITECTURAL TREATMENT SHALL BE PROVIDED TO
 SCREEN THE NON-ACTIVE USES.
 32. RENDERINGS SHALL BE UPDATED TO ACCURATELY REFLECT
 PROJECT AND SURROUNDING CONDITIONS (LEFT TURN MOVEMENT
 ON OKEECHOBEE SHOWN, VIEW FROM AMENITY DECK DOES NOT
 ACCURATELY REFLECT SURROUNDINGS.
 33. ALL LANDSCAPE INDICATED WITHIN THE CITY PROPERTY
 (EAST OF THE SITE) SHALL BE CALLED OUT AS SUBJECT TO
 SEPARATE AGREEMENT. IN ADDITION, NOT ALL THE PROPOSED
 LANDSCAPE BUFFER IS POSSIBLE DUE TO THE EXISTING TRAIN
 FACILITY. IMPROVEMENTS SHALL BE INDICATED AS TWO PHASES
 IN CASE THE TRAIN FACILITY IS NOT MOVED OUT BY THE TIME
 THE BUILDING IS UNDER CONSTRUCTION.
 FOR RESUBMITTAL, PLEASE PROVIDE A RESPONSE SHEET
 ADDRESSING ALL COMMENTS. PLEASE INDICATE WHERE IN THE
 DRAWINGS THE UPDATED INFORMATION CAN BE FOUND IF
 POSSIBLE. SUBMIT ONE LARGE COLORED PRINTED SET AND ONE
 CD WITH THE ELECTRONIC COPY OF THE DRAWING AND ALL
 SUPPORT INFORMATION (INCLUDING RESPONSE LETTER).
 BEFORE THE PROJECT CAN BE SCHEDULED FOR DAC ALL
 COMMENTS SHALL BE ADDRESSED. REVISED DRAWINGS SHALL BE
 SUBMITTED BY APRIL 12 ADDRESSING ALL OUTSTANDING
 COMMENTS FOR THE PROJECT TO BE SCHEDULED FOR MAY 11
 DAC.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.
  

Review Stop Z ZONING
Rev No 2 Status F Date 02-23-2022 Cont ID  
Sent By aaponte Date 02-23-2022 Time 17:06 Rev Time 0.00
Received By aaponte Date 02-23-2022 Time 11:16 Sent To  
Notes
2022-02-23 11:29:011. PARTIALLY SATISFIED- PLEASE UPDATE SURVEY TO INCLUDE
 TOTAL SQUARE FOOTAGE OF PARCEL (TRACK A + B) .
 -PREVIOUS COMMENT (PC)- PLEASE CONFIRM THE PROPERTY
 LINE INDICATED IN DRAWINGS ACCURATELY REFLECT THE
 LOCATION OF THE PROPERTY LINE ACCORDING TO SURVEY.
 2. PARTIALLY SATISFIED - PLEASE CONFIRM THE SQUARE
 FOOTAGE OF THE EXISTING BUILDING REFLECTS THE GBA
 DEFINITION IN CURRENT CODE - PC -PLEASE PROVIDE A GBA
 TABLE WITH THE INFORMATION OF EXISTING ALLOWABLE GBA
 FOR SITE, EXISTING GBA FOR MARRIOTT, AND PROPOSED GBA.
 3. PARTIALLY SATISFIED -VERTICAL CIRCULATION THROUGH
 THE GARAGE LEVELS SHALL BE COUNTED IN THE GBA
 NUMBERS.PLEASE IDENTIFY IF THE CORE (NOT COLORED IN
 GROSS FLOOR PLAN SHEETS) IS ALL INCLUDED IN THE GBA.
 MECHANICAL ROOMS CAN BE EXCLUDED. PLEASE LABEL EACH OF
 THE SPACES THAT ARE NOT CLEARLY IDENTIFIABLE- PC-
 PLEASE PROVIDE A FLOOR BY FLOOR PLAN AND TABLE
 INDICATING THE AREAS THAT ARE INCLUDED IN THE GBA
 CALCULATION ACCORDING TO THE GBA DEFINITION IN SECTION
 94-109. CALL OUT THE USE IN EACH OF THE AREAS. GBA IN
 SHEETS A0.14, A0.15 AND A0.16 DO NOT MATCH THE GBA
 DEFINITION BY CODE.
 4. NOT SATISFIED - PUBLIC OPEN SPACE DOES NOT COMPLY
 WITH THE REQUIREMENTS ACCORDING TO SECTION 94-109 OR
 TABLE IV-7. PROPOSED PUBLIC OPEN SPACE DOES NOT ABUT AN
 ACTIVE USE OR COMPLIES WITH MINIMUM PROPORTIONS.
 5. NOT SATISFIED - PLEASE CLASIFY THE PRIVATE OPEN
 SPACE TYPE PROPOSED ACCORDING TO TABLE IV-7. GREEN/
 LANDSCAPE BUFFERS DO NOT QUALIFY AS PRIVATE OPEN SPACE.
 LANDSCAPE EDGE SOUTH OF THE NEW HOTEL POOL BUILDING OR
 LANDSCAPE EAST OF THE EXISTING HOTEL ENTRANCE ARE
 REALLY LEFT OVER AREAS NOT PRIVATE OPEN SPACES. - PC-
 PROJECT DOES NOT COMPLY WITH THE PRIVATE OPEN SPACE
 MINIMUM REQUIREMENTS. PLEASE EXPLAIN THE HARDSHIPS
 JUSTIFYING THE VARIANCE REQUEST.
 6. PARTIALLY SATISFIED - COLORED ELEVATIONS NOT
 PROVIDED. - PC- PLEASE PROVIDE COLORED ELEVATIONS WITH
 CALL OUT MATERIALS FOR ALL ELEVATIONS. PLEASE INCLUDE
 PHOTOS OF PROPOSED MATERIALS.
 7. NOT SATISFIED - PLEASE STUDY THE EFFICIENCY OF THE
 GARAGE LAYOUT FOR POSSIBLE REDUCTION ON TOTAL NUMBER OF
 FLOORS. NORTHERN GARAGE LAYOUT DOES NOT SEEM TO
 FUNCTION.
 8. NOT SATISFIED- GARAGE STRUCTURE EXCEEDS THE MAXIMUM
 FOOTPRINT LENGHT OF 350 FEET ALLOWED AND DOES NOT
 COMPLY WITH MINIMUM 60 FEET SEPARATION.A BREAK IS
 RECOMMENDED AND A VARIANCE WILL BE NEEDED - PC- PLEASE
 PROVIDE INFORMATION TO CONFIRM THE PROJECT COMPLIES
 WITH THE MAXIMUM 350 FEET FOOTPRINT LENGTH ALLOWED IN
 THE DISTRICT.
 9. NOT SATISFIED - PC - PROJECT EXCEEDS THE MAXIMUM
 SETBACK ALLOWED ALONG OKEECHOBEE BLVD, CREATING A
 SUBURBAN CONFIGURATION DUE TO THE LOCATION OF THE
 VEHICULAR ACCESS DRIVES IN FRONT OF THE BUILDING.
 10. NOT SATISFIED - PC - PLEASE PROVIDE INFORMATION TO
 CONFIRM COMPLIANCE WITH MAXIMUM BUILDING FOOTPRINTS
 ALLOWED.
 11. PARTIALLY SATISFIED. PLEASE INCLUDE THE OVERALL
 BUILDING HEIGHT TO CONFIRM COMPLIANCE WITH MAXIMUM
 VERTICAL PROJECTIONS- PC - ON FA?ADE, PLEASE INDICATE
 THE ELEVATION OF EACH FLOOR LEVEL.
 12. SATISFIED - PC - PROPOSED PROJECT REMOVED THE TURN
 AROUND SPACE AT THE END OF CLEARWATER PARK ROAD. IF A
 GATE AT THE ENTRANCE OF THE PROPERTY IS INSTALLED,
 VEHICLES DO NOT HAVE SPACE TO TURN AROUND.
 13. SATISFIED - PLEASE PROVIDE INFORMATION TO CONFIRM
 THE PROJECT COMPLIES WITH THE MINIMUM ACTIVE USE
 REQUIRED ALONG THE AVENUE DESIGNATION AND THE CSX
 FRONTAGE.
 14. NOT SATISFIED - IMPROVEMENTS NEED TO BE INDICATED
 IN THE LANDSCAPE AND HARDSCAPE PLAN FOR REVIEW DRUING
 THE SITE PLAN APPROVAL PROCESS.- PC- STREETSCAPE ALONG
 OKEECHOBEE SHALL BE DESIGNED TO CONTINUE THE RECENT
 DESIGN IMPLEMENTED BETWEEN TAMARIND AND ROSEMARY.
 STREET TREES PLANTED EVERY 30 FEET, A CONTINUOUS HEDGE
 OR GROUND COVER ALONG OKEECHOBEE AND A MULTIPURPOSE
 PATH OF 12 FEET IN WIDTH.
 15. SATISFIED - PLEASE PROVIDE BUILDING SECTION.
 16. NOT SATISFIED - PC-PLEASE PROVIDE GRAPHIC
 INFORMATION TO CONFIRM COMPLIANCE WITH THE PLANAR BREAK
 REQUIREMENTS.
 17. SATISFIED - PLEASE NOTE THAT MINIMUM SETBACKS ARE
 ALSO APPLICABLE TO GARAGE STRUCTURES. CHECK INFORMATION
 PROVIDED IN SHEET A0.01 REGARDING INTERIOR SETBACK.
 18. NOT SATISFIED - PLEASE INDICATE THE LOCATION OF THE
 REQUIRED PUBLIC BIKE PARKING SPACES 1/100? FEET OF
 FRONTAGE.
 19. NOT SATISFIED - PLEASE INDICATE THE LOCATION OF THE
 REQUIRED SECURED BIKE PARKING FOR THE OFFICE USE AT A
 RATIO OF 1/15 PARKING SPACES PROVIDED (74 BIKE SPACES
 REQUIRED).
 20. PARTIALLY SATISFIED - FOR THE PARKING CALCULATIONS,
 PLEASE LIST EACH OF THE EXISTING AND PROPOSED USES
 (WITH NET SQUARE FOOTAGE OR NUMBER OF ROOMS) AND THE
 REQUIRED AND PROVIDED PARKING.
 21. NOT SATISFIED - PLEASE IDENTIFY THE ROUTE OF
 PEDESTRIAN ACCESS TO THE HOTEL AND OFFICE FROM
 CLEARWATER PARK ROAD.
 22. NOT SATISFIED - PLEASE PROVIDE NARRATIVE JSUTIFYING
 THE REQUESTED VARIANCES. DETAILED COMPLIANCE WITH
 VARIANCE STANDARDS WILL BE REQUIRED FOR DAC REVIEW.
 NEW COMMENTSFOR 2-1-22
 23. MONUMENT SIGNS ARE NOT PERMITTED IN THE DOWNTOWN
 MASTER PLAN AREA.
 24. PROPOSED SIDEWALK ALONG THE EAST SIDE OF THE
 PROPERTY IS WITHIN CITY-OWNED PROPERTY THAT IS
 CURRENTLY USED BY THE TRI-RAIL MAINTENANCE YARD.
 25. EXISTING CHILLER SHALL BE SCREEN AND A LANDSCAPE
 BUFFER SHALL BE PROVIDED AROUND.
  
 FOR RESUBMITTAL, PLEASE PROVIDE A RESPONSE SHEET
 ADDRESSING ALL COMMENTS. PLEASE INDICATE WHERE IN THE
 DRAWINGS THE UPDATED INFORMATION CAN BE FOUND IF
 POSSIBLE. SUBMIT ONE LARGE COLORED PRINTED SET AND ONE
 CD WITH THE ELECTRONIC COPY OF THE DRAWING AND ALL
 SUPPORT INFORMATION (INCLUDING RESPONSE LETTER).
 BEFORE THE PROJECT CAN BE SCHEDULED FOR DAC ALL
 COMMENTS SHALL BE ADDRESSED.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 1 Status F Date 11-18-2021 Cont ID  
Sent By aaponte Date 11-18-2021 Time 12:35 Rev Time 0.00
Received By aaponte Date 10-12-2021 Time 12:35 Sent To  
Notes
2021-11-18 12:36:081. PLEASE CONFIRM THE PROPERTY LINE INDICATED IN
 DRAWINGS ACCURATELY REFLECT THE LOCATION OF THE
 PROPERTY LINE ACCORDING TO SURVEY.
 2. PLEASE PROVIDE A GBA TABLE WITH THE INFORMATION OF
 EXISTING ALLOWABLE GBA FOR SITE, EXISTING GBA FOR
 MARRIOTT, AND PROPOSED GBA.
 3. PLEASE PROVIDE A FLOOR BY FLOOR PLAN AND TABLE
 INDICATING THE AREAS THAT ARE INCLUDED IN THE GBA
 CALCULATION ACCORDING TO THE GBA DEFINITION IN SECTION
 94-109. CALL OUT THE USE IN EACH OF THE AREAS. GBA IN
 SHEETS A0.14, A0.15 AND A0.16 DO NOT MATCH THE GBA
 DEFINITION BY CODE.
 4. PUBLIC OPEN SPACE DOES NOT COMPLY WITH THE
 REQUIREMENTS ACCORDING TO SECTION 94-109 OR TABLE IV-7.
 PROPOSED PUBLIC OPEN SPACE DOES NOT ABUT AN ACTIVE USE
 OR COMPLIES WITH MINIMUM PROPORTIONS.
 5. PROJECT DOES NOT COMPLY WITH THE PRIVATE OPEN SPACE
 MINIMUM REQUIREMENTS. PLEASE EXPLAIN THE HARDSHIPS
 JUSTIFYING THE VARIANCE REQUEST.
 6. PLEASE PROVIDE COLORED ELEVATIONS WITH CALL OUT
 MATERIALS FOR ALL ELEVATIONS. PLEASE INCLUDE PHOTOS OF
 PROPOSED MATERIALS.
 7. PLEASE STUDY THE EFFICIENCY OF THE GARAGE LAYOUT FOR
 POSSIBLE REDUCTION ON TOTAL NUMBER OF FLOORS. NORTHERN
 GARAGE LAYOUT DOES NOT SEEM TO FUNCTION.
 8. PLEASE PROVIDE INFORMATION TO CONFIRM THE PROJECT
 COMPLIES WITH THE MAXIMUM 350 FEET FOOTPRINT LENGTH
 ALLOWED IN THE DISTRICT.
 9. PROJECT EXCEEDS THE MAXIMUM SETBACK ALLOWED ALONG
 OKEECHOBEE BLVD, CREATING A SUBURBAN CONFIGURATION DUE
 TO THE LOCATION OF THE VEHICULAR ACCESS DRIVES IN FRONT
 OF THE BUILDING.
 10. PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE
 WITH MAXIMUM BUILDING FOOTPRINTS ALLOWED.
 11. ON FA?ADE, PLEASE INDICATE THE ELEVATION OF EACH
 FLOOR LEVEL.
 12. PROPOSED PROJECT REMOVED THE TURN AROUND SPACE AT
 THE END OF CLEARWATER PARK ROAD. IF A GATE AT THE
 ENTRANCE OF THE PROPERTY IS INSTALLED, VEHICLES DO NOT
 HAVE SPACE TO TURN AROUND.
 13. PLEASE PROVIDE INFORMATION TO CONFIRM THE PROJECT
 COMPLIES WITH THE MINIMUM ACTIVE USE REQUIRED ALONG THE
 AVENUE DESIGNATION AND THE CSX FRONTAGE.
 14. STREETSCAPE ALONG OKEECHOBEE SHALL BE DESIGNED TO
 CONTINUE THE RECENT DESIGN IMPLEMENTED BETWEEN TAMARIND
 AND ROSEMARY. STREET TREES PLANTED EVERY 30 FEET, A
 CONTINUOUS HEDGE OR GROUND COVER ALONG OKEECHOBEE AND A
 MULTIPURPOSE PATH OF 12 FEET IN WIDTH.
 15. PLEASE PROVIDE BUILDING SECTION.
 16. PLEASE PROVIDE GRAPHIC INFORMATION TO CONFIRM
 COMPLIANCE WITH THE PLANAR BREAK REQUIREMENTS.
 17. PLEASE NOTE THAT MINIMUM SETBACKS ARE ALSO
 APPLICABLE TO GARAGE STRUCTURES. CHECK INFORMATION
 PROVIDED IN SHEET A0.01 REGARDING INTERIOR SETBACK.
 18. PLEASE INDICATE THE LOCATION OF THE REQUIRED PUBLIC
 BIKE PARKING SPACES 1/100? FEET OF FRONTAGE.
 19. PLEASE INDICATE THE LOCATION OF THE REQUIRED
 SECURED BIKE PARKING FOR THE OFFICE USE AT A RATIO OF
 1/15 PARKING SPACES PROVIDED (74 BIKE SPACES REQUIRED).
 20. FOR THE PARKING CALCULATIONS, PLEASE LIST EACH OF
 THE EXISTING AND PROPOSED USES (WITH NET SQUARE FOOTAGE
 OR NUMBER OF ROOMS) AND THE REQUIRED AND PROVIDED
 PARKING.
 21. PLEASE IDENTIFY THE ROUTE OF PEDESTRIAN ACCESS TO
 THE HOTEL AND OFFICE FROM CLEARWATER PARK ROAD.
 22. PLEASE PROVIDE NARRATIVE JSUTIFYING THE REQUESTED
 VARIANCES. DETAILED COMPLIANCE WITH VARIANCE STANDARDS
 WILL BE REQUIRED FOR DAC REVIEW.
 FOR RESUBMITTAL, PLEASE PROVIDE A RESPONSE SHEET
 ADDRESSING ALL COMMENTS. PLEASE INDICATE WHERE IN THE
 DRAWINGS THE UPDATED INFORMATION CAN BE FOUND IF
 POSSIBLE. SUBMIT ONE LARGE PRINTED SET AND ONE CD WITH
 THE ELECTRONIC COPY OF THE DRAWING AND ALL SUPPORT
 INFORMATION (INCLUDING RESPONSE LETTER).
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.
  