Plan Review Details - Project Z21080015
| Plan Review Stops For Project Z21080015 |
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
4 |
Status |
P |
Date |
10-04-2022 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
09-26-2022 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
swelter |
Date |
10-04-2022 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2022-10-04 11:43:25 | PASSED WITH THE FOLLOWING CONDITIONS: | | | A COMPLETED ART ASSESSMENT APPLICATION MUST BE PROVIDED | | | BEFORE OR AT TIME OF BUILDING PERMIT FEES | | | EVIDENCE OF ESCROW MUST BE SUBMITTED AT TIME OF | | | BUILDING PERMIT FEES | | | IDENTIFIED AREAS FOR ART ARE SUBJECT TO CHANGE BY THE | | | ARTLIFE STAFF/COMMITTEE | | | ARTIST(S) AND CONCEPT PROPOSALS ARE SUBJECT TO THE | | | ARTLIFE APPROVAL PROCESS FOR PUBLIC ART | | | |
|
|
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
3 |
Status |
F |
Date |
08-08-2022 |
|
|
Cont ID |
|
| Sent By |
scwelter |
Date |
08-08-2022 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
scwelter |
Date |
08-08-2022 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2022-08-08 13:09:24 | THE SITE AND LANDSCAPE PLANS MUST INCLUDE THE ART | | | SITE(S) PRIOR TO SITE PLAN APPROVAL. THE RECENTLY | | | SUBMITTED PLANS DO NOT SHOW ANY POTENTIAL ART SITES. | | | SITE DO DO NEED TO BE PUBLICLY ACCESSIBLE. A FEW | | | CONSIDERATIONS: THE GARDEN AREA, 24TH STREET PASEO | | | TOWARDS THE RAILROAD, BROADWAY AND NORTHWOOD ROAD. THE | | | TYPE OF ART AND/OR ARTIST DOES NOT NEED TO BE INCLUDED | | | ONLY PROPOSED SITES. | | | THE ART ASSESSMENT APPLICATION WAS EMAILED TO JOSH | | | HORNING AND GILBERT BENHAMAU PAGE ONE NEEDS TO BE | | | COMPLTED AND RETURNED TO MY ATTENTION AT | | | [email protected]. |
|
|
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
2 |
Status |
F |
Date |
06-09-2022 |
|
|
Cont ID |
|
| Sent By |
scwelter |
Date |
06-09-2022 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
scwelter |
Date |
06-09-2022 |
Time |
11:49 |
Sent To |
|
|
| Notes |
| 2022-06-09 11:44:36 | SPOKE WITH GILBERT BENHAMOU DISCUSSED ART PROCESS ON | | | JUNE 3RD, 2022. | | | 1. MISSING ART ASSESSMENT APPLICATION SENT 6.9.2020 - | | | NEEDS TO BE COMPLETED INCLUDING ESCROW OF THE 1% DUE AT | | | TIME OF BUILDING PERMIT APPLICATION - PRINTING OF | | | PERMIT WILLL BE HELD UNTIL APPLICATION ALONG WITH | | | ESCROW IS COMPLETED. | | | 2. POTENTIAL ART SITES NEED TO BE MARKED ON THE SITE | | | PLAN FOR REVIEW. SITES NEED TO HAVE PUBLIC ACCESS. | | | IDENTIFIED SITES WIL BE REVIEWED BY ALL DEPARTMENTS FOR | | | ACCESSIBILITY, LANDSCAPE, UTILITIES, ETC. | | | | | | CONTACT [email protected] WITH ANY FURTHER QUESTIONS. | | | | | | |
|
|
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
1 |
Status |
F |
Date |
11-18-2021 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
11-18-2021 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
scwelter |
Date |
04-12-2022 |
Time |
12:50 |
Sent To |
|
|
| Notes |
| 2021-11-10 10:59:08 | CONTACT SYBILLE WELTER: [email protected] FOR ART | | | ASSESSMENT APPLICATION AND TO REVIEW ART REQUIREMENTS, | | | POTENTIAL ART SITES, ARTISTS, AND ARTWORKS. | | | | | | TOTAL CONSTRUCTION COSTS OF THIS DEVELOPMENT ARE OVER | | | $500,000 IT IS SUBJECT TO THE PUBLIC ART REQUIREMENT AS | | | PER CITY ORDINANCE. | | | SECTION 78-129: ALL PRIVATE DEVELOPMENT PROJECTS, | | | INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR | | | IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL | | | CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN | | | $500,000 ARE SUBJECT TO THE PUBLIC ART REQUIREMENT. | | | OPTION 1: INSTALL ARTWORK ON THE DEVELOPMENT SITE | | | VALUED IN AN AMOUNT NOT LESS THAN ONE PERCENT OF THE | | | TOTAL CONSTRUCTION COSTS; OR | | | OPTION 2: CONTRIBUTE AN AMOUNT EQUAL TO 75 PERCENT OF | | | ONE PERCENT OF THE TOTAL CONSTRUCTION COSTS FOR DEPOSIT | | | TO THE PUBLIC ART ACCOUNT. | | | A COMPLETED PUBLIC ART ASSESSMENT APPLICATION IS | | | REQUIRED AT TIME OF BUILDING PERMIT SUBMITTAL. | | | | | | CONTACT SYBILLE WELTER, ADMINISTRATOR OF PUBLIC ART AND | | | CULTURE AT [email protected] TO OBTAIN AN ART ASSESSMENT | | | APPLICATION AND REVIEW THE REQUIREMENTS. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
10-03-2022 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
10-03-2022 |
Time |
18:42 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
10-03-2022 |
Time |
18:42 |
Sent To |
|
|
| Notes |
| 2022-10-03 18:43:11 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. DEMOLITION OF THE EXISTING BUILDINGS. AN ASBESTOS | | | SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT | | | REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH | | | COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963, | | | OR BY EMAIL: [email protected] | | | | | | 3. REPLAT/UNITY OF TITLE. COMMENT NOT ADDRESSED. FOR | | | ANY BUILDING CROSSING A PROPERTY LINE, EITHER A | | | RECORDED UNITY OF TITLE, OR SOME OTHER APPROVED LEGAL | | | INSTRUMENT, SHALL BE INCLUDED WITH THE PERMIT | | | APPLICATION, OR THE BUILDING MUST HAVE A FIRE WALL | | | ALONG THE PROPERTY LINE, PER SECTION 202 OF FLORIDA | | | BUILDING CODE, BUILDING, FIRE SEPARATION DISTANCE. | | | | | | 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, | | | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR | | | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, | | | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE | | | FLORIDA BUILDING CODE. | | | | | | 5. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND | | | OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT, | | | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF | | | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF | | | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE | | | VERIFIED. | | | | | | 6. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES | | | NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO | | | MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL | | | BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE | | | EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED | | | TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR | | | OTHER APPROVED METHODS. | | | | | | 7. GREASE INTERCEPTOR. GREASE INTERCEPTORS WILL BE | | | REQUIRED. FOR INFORMATION ON THE REQUIRED TYPE, SIZE | | | AND LOCATION, PLEASE CONTACT RYAN BROWN, CHIEF PLUMBING | | | INSPECTOR, DEVELOPMENT SERVICES DEPARTMENT, AT (561) | | | 805-6692, OR BY EMAIL: [email protected] | | | | | | 8. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, | | | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND | | | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, | | | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. | | | | | | 9. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND | | | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF | | | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL | | | NEIGHBORING PROPERTIES. | | | | | | 10. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER | | | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, | | | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE | | | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF | | | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION | | | THAT MAY AFFECT THE USE OF THEIR PROPERTY. | | | | | | 11. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT | | | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL | | | HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION | | | OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING, | | | CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT | | | (561) 805 6659, OR BY EMAIL: [email protected] | | | | | | 12. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT | | | TO ART LIFE ASSESSMENT UNDER THE CITY OF WEST PALM | | | BEACH ART IN PUBLIC PLACES (AIPP) PROGRAM. FOR ADVICE | | | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP | | | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC | | | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
08-11-2022 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
08-11-2022 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
08-11-2022 |
Time |
17:02 |
Sent To |
|
|
| Notes |
| 2022-08-11 17:03:22 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. DEMOLITION OF THE EXISTING BUILDINGS. AN ASBESTOS | | | SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT | | | REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH | | | COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963, | | | OR BY EMAIL: [email protected] | | | | | | 3. REPLAT/UNITY OF TITLE. FOR ANY BUILDING CROSSING A | | | PROPERTY LINE, EITHER A RECORDED UNITY OF TITLE, OR | | | SOME OTHER APPROVED LEGAL INSTRUMENT, SHALL BE INCLUDED | | | WITH THE PERMIT APPLICATION, OR THE BUILDING MUST HAVE | | | A FIRE WALL ALONG THE PROPERTY LINE, PER SECTION 202 OF | | | FLORIDA BUILDING CODE, BUILDING, FIRE SEPARATION | | | DISTANCE. | | | | | | 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, | | | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR | | | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, | | | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE | | | FLORIDA BUILDING CODE. | | | | | | 5. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND | | | OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT, | | | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF | | | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF | | | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE | | | VERIFIED. | | | | | | 6. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES | | | NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO | | | MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL | | | BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE | | | EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED | | | TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR | | | OTHER APPROVED METHODS. | | | | | | 7. GREASE INTERCEPTOR. GREASE INTERCEPTORS WILL BE | | | REQUIRED. FOR INFORMATION ON THE REQUIRED TYPE, SIZE | | | AND LOCATION, PLEASE CONTACT RYAN BROWN, CHIEF PLUMBING | | | INSPECTOR, DEVELOPMENT SERVICES DEPARTMENT, AT (561) | | | 805-6692, OR BY EMAIL: [email protected] | | | | | | 8. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, | | | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND | | | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, | | | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. | | | | | | 9. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND | | | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF | | | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL | | | NEIGHBORING PROPERTIES. | | | | | | 10. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER | | | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, | | | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE | | | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF | | | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION | | | THAT MAY AFFECT THE USE OF THEIR PROPERTY. | | | | | | 11. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT | | | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL | | | HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION | | | OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING, | | | CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT | | | (561) 805 6659, OR BY EMAIL: [email protected] | | | | | | 12. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT | | | TO ART LIFE ASSESSMENT UNDER THE CITY OF WEST PALM | | | BEACH ART IN PUBLIC PLACES (AIPP) PROGRAM. FOR ADVICE | | | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP | | | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC | | | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
04-13-2022 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
04-13-2022 |
Time |
19:13 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
04-13-2022 |
Time |
19:13 |
Sent To |
|
|
| Notes |
| 2022-04-13 19:36:51 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. DEMOLITION OF THE EXISTING BUILDINGS. AN ASBESTOS | | | SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT | | | REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH | | | COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963, | | | OR BY EMAIL: [email protected] | | | | | | 3. REPLAT/UNITY OF TITLE. FOR ANY BUILDING CROSSING A | | | PROPERTY LINE, EITHER A RECORDED UNITY OF TITLE, OR | | | SOME OTHER APPROVED LEGAL INSTRUMENT, SHALL BE INCLUDED | | | WITH THE PERMIT APPLICATION, OR THE BUILDING MUST HAVE | | | A FIRE WALL ALONG THE PROPERTY LINE, PER SECTION 202 OF | | | FLORIDA BUILDING CODE, BUILDING, FIRE SEPARATION | | | DISTANCE. | | | | | | 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, | | | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR | | | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, | | | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE | | | FLORIDA BUILDING CODE. | | | | | | 5. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND | | | OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT, | | | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF | | | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF | | | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE | | | VERIFIED. | | | | | | 6. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES | | | NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO | | | MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL | | | BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE | | | EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED | | | TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR | | | OTHER APPROVED METHODS. | | | | | | 7. GREASE INTERCEPTOR. GREASE INTERCEPTORS WILL BE | | | REQUIRED. FOR INFORMATION ON THE REQUIRED TYPE, SIZE | | | AND LOCATION, PLEASE CONTACT RYAN BROWN, CHIEF PLUMBING | | | INSPECTOR, DEVELOPMENT SERVICES DEPARTMENT, AT (561) | | | 805-6692, OR BY EMAIL: [email protected] | | | | | | 8. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, | | | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND | | | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, | | | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. | | | | | | 9. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND | | | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF | | | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL | | | NEIGHBORING PROPERTIES. | | | | | | 10. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER | | | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, | | | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE | | | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF | | | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION | | | THAT MAY AFFECT THE USE OF THEIR PROPERTY. | | | | | | 11. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT | | | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL | | | HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION | | | OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING, | | | CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT | | | (561) 805 6659, OR BY EMAIL: [email protected] | | | | | | 12. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT | | | TO ART LIFE ASSESSMENT UNDER THE CITY OF WEST PALM | | | BEACH ART IN PUBLIC PLACES (AIPP) PROGRAM. FOR ADVICE | | | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP | | | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC | | | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
11-17-2021 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
11-17-2021 |
Time |
21:06 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
11-17-2021 |
Time |
21:06 |
Sent To |
|
|
| Notes |
| 2021-11-17 21:08:58 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. DEMOLITION OF THE EXISTING BUILDINGS. AN ASBESTOS | | | SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT | | | REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH | | | COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963, | | | OR BY EMAIL: [email protected] | | | | | | 3. REPLAT/UNITY OF TITLE. FOR ANY BUILDING CROSSING A | | | PROPERTY LINE, EITHER A RECORDED UNITY OF TITLE, OR | | | SOME OTHER APPROVED LEGAL INSTRUMENT, SHALL BE INCLUDED | | | WITH THE PERMIT APPLICATION, OR THE BUILDING MUST HAVE | | | A FIRE WALL ALONG THE PROPERTY LINE, PER SECTION 202 OF | | | FLORIDA BUILDING CODE, BUILDING, FIRE SEPARATION | | | DISTANCE. | | | | | | 4. EXIT TO THE STREET FROM THE EGRESS STAIRS. GROUND | | | FLOOR PLAN SHEET A103 DOES NOT CLEARLY SHOW THE EXIT | | | DISCHARGE POINT FROM EACH OF THE EXIT STAIRS (BUILDING | | | A AND BUILDING C IN PARTICULAR). PLEASE NOTE THAT, PER | | | SECTION 1028.1 OF FLORIDA BUILDING CODE, 50% OF THE | | | EXIT CAPACITY SHALL DISCHARGE TO THE RIGHT OF WAY SUCH | | | THAT OCCUPANTS ARE NOT REQUIRED TO TRAVERSE THE | | | BUILDING AFTER LEAVING THE STAIR. | | | | | | 5. ACCESSIBLE ROUTE. WHEN SUBMITTED FOR PERMIT, THE | | | PLANS SHALL SHOW AT LEAST ONE ACCESSIBLE ROUTE, | | | COMPLYING WITH SECTIONS 206.2 AND 402.2 OF FLORIDA | | | ACCESSIBILITY CODE, FROM THE PUBLIC RIGHT-OF-WAY TO ALL | | | ACCESSIBLE BUILDING OR FACILITY ENTRANCES. | | | | | | 6. ANY PART OF AN ACCESSIBLE ROUTE WITH A SLOPE GREATER | | | THAN 1:20 SHALL BE CONSIDERED A RAMP AND SHALL COMPLY | | | WITH SECTION 405 OF FLORIDA ACCESSIBILITY CODE. | | | | | | 7. NUMBER OF ACCESSIBLE PARKING SPACES. THE PLANS DO | | | NOT SHOW ANY ACCESSIBLE PARKING AT THIS TIME. THE | | | MINIMUM NUMBER OF ACCESSIBLE PARKING SPACES PROVIDED | | | SHALL BE IN ACCORDANCE WITH FAIR | | | HOUSING ACT AND SECTION 208.2 OF FLORIDA ACCESSIBILITY | | | CODE. | | | | | | 8. LOCATION OF ACCESSIBLE PARKING SPACES. THE PLANS DO | | | NOT SHOW ANY ACCESSIBLE PARKING AT THIS TIME. PER | | | SECTION 208.3 OF FLORIDA ACCESSIBILITY CODE, ACCESSIBLE | | | PARKING SPACES ARE TO BE LOCATED ON THE SHORTEST | | | POSSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING TO AN | | | ACCESSIBLE ENTRANCE. THE DESIGN OF ACCESSIBLE PARKING | | | SPACES SHALL COMPLY WITH SECTION 502 OF FLORIDA | | | ACCESSIBILITY CODE | | | | | | 9. VAN ACCESSIBLE PARKING SPACES. THE PLANS DO NOT SHOW | | | ANY VAN ACCESSIBLE PARKING AT THIS TIME. PER SECTION | | | 208.2.4 OF FLORIDA ACCESSIBILITY CODE, ONE IN EVERY SIX | | | REQUIRED ACCESSIBLE SPACES (AT LEAST ONE) IN A PARKING | | | STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND DESIGNED IN | | | ACCORDANCE WITH SECTION OF 502 OF FLORIDA ACCESSIBILITY | | | CODE (VERTICAL CLEARANCE NOT LESS THAN 98 INCHES AT | | | SPACE AND VEHICULAR ACCESS ROUTE) | | | | | | 10. ACCESSIBLE PARKING SPACE AISLE. ACCESSIBLE PARKING | | | SPACE ACCESS AISLES SHALL BE LOCATED SO THAT THE USER | | | IS NOT COMPELLED TO WALK OR WHEEL BEHIND ANOTHER PARKED | | | VEHICLE OR IN THE TRAVEL LANE. THE ACCESS AISLES SHALL | | | ALSO COMPLY WITH THE OTHER PROVISIONS OF SECTION OF | | | 502.3 OF FLORIDA ACCESSIBILITY CODE. | | | | | | 11. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, | | | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR | | | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, | | | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE | | | FLORIDA BUILDING CODE. | | | | | | 12. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND | | | OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT, | | | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF | | | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF | | | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE | | | VERIFIED. | | | | | | 13. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE | | | DOES NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL | | | OPENINGS TO MEET THE DEFINITION OF AN OPEN PARKING | | | GARAGE, IT WILL BE CONSIDERED AN ENCLOSED PARKING | | | GARAGE AND MUST HAVE EXHAUST SYSTEMS. THE EXHAUST | | | SYSTEMS SHALL BE DESIGNED TO MINIMIZE NOISE LEVELS | | | USING INLINE FAN SILENCERS OR OTHER APPROVED METHODS. | | | | | | 14. GREASE INTERCEPTOR. GREASE INTERCEPTORS WILL BE | | | REQUIRED. FOR INFORMATION ON THE REQUIRED TYPE, SIZE | | | AND LOCATION, PLEASE CONTACT TIM LARGE, CHIEF PLUMBING | | | INSPECTOR, DEVELOPMENT SERVICES DEPARTMENT, AT (561) | | | 805-6692, OR BY EMAIL: [email protected] | | | | | | 15. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, | | | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND | | | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, | | | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. | | | | | | 16. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND | | | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF | | | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL | | | NEIGHBORING PROPERTIES. | | | | | | 17. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER | | | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, | | | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE | | | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF | | | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION | | | THAT MAY AFFECT THE USE OF THEIR PROPERTY. | | | | | | 18. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT | | | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL | | | HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION | | | OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING, | | | CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT | | | (561) 805 6659, OR BY EMAIL: [email protected] | | | | | | 19. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT | | | TO ART LIFE ASSESSMENT UNDER THE CITY OF WEST PALM | | | BEACH ART IN PUBLIC PLACES (AIPP) PROGRAM. FOR ADVICE | | | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP | | | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC | | | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
5 |
Status |
P |
Date |
09-22-2022 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
09-22-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
09-22-2022 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
4 |
Status |
F |
Date |
07-19-2022 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
07-19-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
07-19-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-07-25 07:56:07 | PLANS ARE DATED 5/17/22. PLEASE SUBMIT REVISED PLANS. |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
3 |
Status |
F |
Date |
06-08-2022 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
06-08-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
06-08-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-06-12 12:38:18 | COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR, ENG. | | | SERVICES DEPT., 561-494-1098 [email protected] : | | | | | | PLEASE ADDRESS SECOND PART OF COMMENT 6: VERIFY THAT | | | THERE ARE NO STRUCTURES WITHIN EASEMENT. | | | PLEASE LABEL ALL STREETS AND ALLEYS ON ALL CIVIL | | | SHEETS. | | | DEMO SHEETS: | | | UPDATE DEMO NOTE 13 TO REFER TO CITY OF WEST PALM | | | BEACH. | | | ADD NOTE TO ALL DEMO SHEETS TO PROTECT STORMWATER | | | INLETS USING BMPS. | | | PLEASE PROVIDE A SUMMARY OF SCOPE CHANGE IN THE NEXT | | | RESUBMITTAL. | | | | | | | | | COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE | | | SUPER., WPB PUBLIC UTILITIES, 561-494-2262 OR | | | [email protected]: | | | | | | -SHEET C3.01. SOME CALLOUTS ARE GOING OFF TOP OF SHEET | | | AND UNREADABLE. PLEASE CORRECT. | | | | | | -CALLOUT REPLACEMENT OF FIRE HYDRANT AND PIPE LEADING | | | TO IT AT FAR NORTH SIDE OF SHEET C3.01. ALSO SHOW GATE | | | VALVE AND LABEL THE FITTING AT WATER MAIN. | | | | | | -AT FORMAL ENGINEERING SUBMITTAL: LABEL ALL WATER | | | SERVICES WITH PIPE SIZE AND MATERIAL TYPE; ADD GATE | | | VALVE AT 25TH ST WHERE PROPOSED 8 INCH DIP RUNNING WEST | | | TIES INTO EXISTING NORTH SOUTH DIP; LABEL EXISTING FM | | | NORTH OF 25TH ST WITH PIPE SIZE AND MATERIAL TYPE; SHOW | | | ALL WATER MAIN GATE VALVES AT 25TH AND PINEWOOD | | | INTERSECTION; ADD INVERT AND RIM ELEVATIONS TO ALL | | | EXISTING AND PROPOSED SANITARY SEWER MANHOLES; SHOW ALL | | | EXISTING WATER SERVICES AND LABEL WHAT IS HAPPENING TO | | | THEM (ESPECIALLY WATER SERVICE TAPS FOR NEIGHBORS THAT | | | MAY RESTRICT PROPOSED TAPS); VERIFY FORCE MAIN | | | DIRECTION OF FLOWL; | | | | | | -EXISTING 8 INCH DIP IN 25TH ST INTERSECTION SHOWS AS | | | 1926 8 INCH CAS IN WPB GIS. PLEASE VERIFY AT FORMAL | | | ENGINEERING SUBMITTAL. IF 1926 MAY NEED TO BE REPLACED | | | UPON REVIEW AND DIRECTION OF CITY OR EOR. | | | | | | -DCDAS ON 25TH ST ARE IN THE RIGHT OF WAY. THEY ARE | | | SUPPOSED TO BE ON PRIVATE PROPERTY. | | | | | | -VERIFY ALL PROPOSED FDC LOCATIONS ARE ACCEPTABLE | | | DISTANCE FROM FIRE HYDRANTS. SEE AT LEAST ONE THAT MAY | | | NOT BE. | | | | | | -EXISTING SANITARY SEWER MANHOLE AND PIPING NORTH OF IT | | | AT INTERSECTION OF 25TH AND PINEWOOD SAYS 1926 IN WPB | | | GIS MAY NEED TO BE IMPROVED UPON REVIEW OF CITY OR EOR | | | AT FORMAL ENGINEERING SUBMITTAL. | | | | | | -METER SIZE IS NOT CLEARLY SHOWN, BUT 3 INCH METERS | | | SHOULD HAVE 4 INCH TAPS AND SERVICE LINES PER WPB | | | STANDARD DETAILS. | | | | | | -THE NE AREA OF BROADWAY AND 25TH INTERSECTION APPEARS | | | TO BE FDOT ROW. | | | | | | -FIRE HYDRANT GATE VALVE LOCATED ADJACENT TACTILE PAD | | | ON BROADWAY. PLEASE RELOCATE. PREFER ADJACENT FIRE | | | HYDRANT IN LANDSCAPING IF POSSIBLE. | | | | | | -CHECK POSITION OF FPL MANHOLE AT INTERSECTION OF 25TH | | | AND BROADWAY TO CONFIRM WILL NOT CONFLICT WITH | | | STORMWATER PIPING NEXT TO IT. | | | | | | -FIRELINE BACKFLOW ON 24TH ST EAST OF BROADWAY IS IN | | | PEDESTRIAN TRAFFIC AND ALSO IN THE RIGHT OF WAY. | | | RELOCATE TO PRIVATE PROPERTY AND OUT OF PEDESTRIAN | | | TRAFFIC. | | | | | | -SHOW PAVEMENT RESTORATION ON 24TH ST EAST OF BROADWAY. | | | | | | -FIRELINE BACKFLOW ON BROADWAY IS IN RIGHT OF WAY. | | | RELOCATE TO PRIVATE PROPERTY. | | | | | | -PAVEMENT RESTORATION BOUNDARIES ON 23RD ST ARE NOT | | | SUFFICIENT FOR THE PROPOSED UTILITY WORK. | | | | | | -FOR FAR SOUTHWEST WATER SERVICE, WILL NEED TO GO TO | | | THE MAIN. EXISTING WATER SERVICE IS SMALL DIAMETER. | | | | | | -EXISTING 24 INCH WATER MAIN ON 23RD ST NEAR AREAS OF | | | PROPOSED WATER SERVICE TAPS IS LABELED 1926 AGE IN WPB | | | GIS AND A LARGER WATER MAIN. WOULD NEED APPROVAL FROM | | | MICHAEL TECHNOW TO CONNECT TO THE WATER MAINS THERE, | | | AND EXISTING 24 INCH WATER MAIN MAY NEED TO BE REPLACED | | | UPON REVIEW OF CITY OR EOR AT FORMAL ENGINEERING | | | SUBMITTAL. | | | | | | -SHEET C3.03. PROPOSED WATER SERVICES AND DOMESTIC | | | METER EAST OF PINEWOOD APPEAR TO BE IN CONFLICT WITH A | | | UTILITY POLE. | | | | | | -SHOW AND LABEL UTILITY EASEMENTS FOR DOMESTIC METERED | | | WATER SERVICES. MANY ARE MISSING. | | | | | | -FIRE HYDRANT AND PIPE TO IT WILL NEED REPLACEMENT. | | | CONSIDER RELOCATING IT TO DIFFERENT LANDSCAPING AREA | | | OUT OF SIDEWALK. | | | | | | -CALLOUT HORIZONTAL DISTANCE BETWEEN FM AND WM ON 23RD | | | ST. | | | | | | -FOOTPRINT OF ABOVE GROUND METERS MAY BE LARGER THAN | | | SHOWN ON PLANS. MAY BE NECESSARY TO ROTATE THEM OR | | | INCREASE PLANTER WIDTH SO THEY WILL FIT. | | | | | | -THERE ARE SOME WATER UTILITY CONFLICTS WITH | | | LANDSCAPING ON BROADWAY. SEE A TREE ON TOP OF A WATER | | | PIPE AS WELL AS A FIRELINE BACKFLOW IN CLOSE PROXIMITY | | | TO A TREE TRUNK. PLEASE CHECK PLANS FOR UTILITY | | | LANDSCAPING CONFLICTS AND RESOLVE. | | | | | | -SHOW AND LABEL THE PROPOSED ROAD AREA BETWEEN 23RD AND | | | NORTHWOOD THAT IS INTENDED TO BE DEDICATED TO THE CITY. | | | | | | -COULD NOT FIND ANY INFORMATION ON IRRIGATION WATER. | | | WILL IRRIGATION BE FED FROM THE DOMESTIC WATER | | | SERVICES? | | | | | | -CLEARLY SHOW AND LABEL ALL DOMESTIC BACKFLOW | | | ASSEMBLIES. THEY SHOULD ALL BE ON PRIVATE PROPERTY, | | | CLOSE TO METERS, OUTSIDE OF BUILDINGS, OUT OF UTILITY | | | EASEMENTS, AND AWAY FROM PEDESTRIAN TRAFFIC. FOR | | | IMPORTANT WATER SERVICES CONSIDER DUAL/PARALLEL | | | ASSEMBLIES TO MINIMIZE WATER OUTAGES DURING BACKFLOW | | | MAINTENANCE. | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
F |
Date |
04-09-2022 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
04-09-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
04-09-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-04-09 14:19:23 | Z21080015, 0017 - NORTHWOOD SQUARE, AND ABANDONMENTS | | | 3.30.22 SUBMITTAL | | | | | | PLEASE PROVIDE RESPONSES TO MY COMMENTS FROM NOV 2021 | | | SUBMITTAL: | | | | | | COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR, ENG. | | | SERVICES DEPT., 561-494-1098 [email protected] : | | | | | | GENERAL: | | | O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND | | | INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER | | | (Z-XXXXXXXX). | | | O THE CITY OF WEST PALM BEACH HAS A NUMBER OF | | | REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY | | | AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND | | | WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE | | | DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK | | | BELOW: | | | A. HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WP | | | B_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FUL | | | L-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97 | | | B1960045731D3658206F27451722716EF | | | B. THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE | | | FOUND HERE: | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | C. ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM | | | BEACH, FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, | | | ADOPTED SEPT. 22, 2008. (SUPPLEMENT NO. 18) | | | CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL, | | | SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER | | | SERVICE FACILITIES OF THE CITY. | | | THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE | | | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY | | | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, | | | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. | | | O AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR | | | MORE INFORMATION, REFER TO THE LINK BELOW: | | | A. HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PU | | | BLICATIONS/BACKFLOW-CROSS-CONNECTION- CONTROL-MANUAL | | | O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY | | | OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC | | | RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF | | | YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE | | | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL | | | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT | | | [email protected] OR 561-494-1079 FOR FURTHER | | | ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION | | | ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD | | | SURVEY, POT-HOLING, SOFT DIGS ETC. | | | | | | BACKFLOW ASSEMBLY AND METERS: | | | | | | O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER | | | SERVICES AND WATER METERS FOR THE PARKING LOTS, ALONG | | | WITH WHAT IS HAPPENING TO THEM. | | | O SHOW EXISTING AND PROPOSED DEDICATED UTILITY | | | EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO | | | PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO | | | STRUCTURES WITHIN EASEMENT. | | | O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION | | | OF WATER METER AND BACKFLOW | | | PREVENTION. | | | O BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY | | | OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER | | | METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO | | | PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE | | | INSTALLED ABOVE-GROUND ONLY. | | | O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE | | | NOTE USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA. | | | | | | WATER/WASTEWATER PLAN: | | | O PROVIDE VERTICAL DATUM AND DATUM CONVERSION | | | INFORMATION (NAVD 1988 AND NGVD 1929). | | | O SHOW PROJECT ADDRESS ON ALL PLAN SHEETS. | | | O PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE | | | STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC. | | | O PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND | | | DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND | | | SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH | | | PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE | | | AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS, | | | BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO | | | BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS, | | | DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS, | | | ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT | | | ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF | | | SANITARY SEWER LINES. | | | O GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR | | | SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE | | | PROFILE VIEW. | | | O DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN | | | VIEW FOR ALL SANITARY AND STORM SEWERS. | | | O SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT | | | MATERIAL. | | | O PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED | | | UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC, | | | ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION | | | FACILITIES LOCATED ON THE RIGHT-OF-WAY. | | | O PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER | | | AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD | | | DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS. | | | O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY | | | TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT | | | APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING | | | AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, | | | MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS | | | SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 | | | FOR WATER. | | | O PROVIDE FIRE FLOW TEST DATA. | | | O PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND | | | STORMWATER INFRASTRUCTURE ALONG ENTIRE PROJECT | | | FRONTAGE. | | | O CUT AND CAP UTILITIES NOT IN USE AND REMOVE ANY | | | ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY | | | ROW. | | | O WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL | | | BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY | | | PROPOSED LENGTH IN FEET. | | | O CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY | | | SEWER ARE REQUIRED. | | | O PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE | | | JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET. | | | O ADD NOTE TO PLANS SPECIFYING CITY?S DOWNSTREAM LIFT | | | STATION NUMBER. | | | O PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR | | | PROPOSED SANITARY LATERALS. | | | O LABEL WATER LINES AS PRIVATE WHERE APPLICABLE. | | | O PLEASE SHOW AND LABEL EXISTING AND PROPOSED GREASE | | | TRAPS (IF ANY). | | | O PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN | | | OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER. | | | | | | FORMAL ENGINEERING REVIEW: | | | O FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES | | | NOI REQUIREMENTS WILL BE ENFORCED. | | | - AN NOI IS REQUIRED FOR PROJECTS THAT: | | | - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS | | | THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF | | | DEVELOPMENT OR SALE; | | | - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE | | | STATE OR TO SURFACE WATERS OF THE STATE THROUGH A | | | MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4). | | | - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF | | | CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION | | | THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL | | | SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT | | | OF THE 10-2 CERTIFICATION. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF | | | WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING | | | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT | | | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING | | | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED | | | LEAD-FREE DESIGN. | | | O FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES | | | ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY | | | LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT | | | PARCELS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, IF WATER LINES ARE | | | BEING REPLACED IN ROW, SHOW ADJACENT PARCEL ADDRESSES. | | | O FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO PROVIDE | | | 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF | | | PROPOSED TRENCH IN CITY MAINTAINED ROADWAY AREAS PER | | | CITY OF WPB STANDARD DETAIL GC-8. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | CALCULATIONS OF PERVIOUS AND IMPERVIOUS AREAS FOR | | | PROPOSED IMPROVED AREAS. | | | | | | MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR WITH | | | CITY OF WPB PUBLIC UTILITIES, 561-494-2262 OR | | | [email protected] : | | | | | | -PINEWOOD AVE VACATION LEGAL DESCRIPTION STATES THAT | | | THE LANDS ARE IN MONROE COUNTY FLORIDA. PLEASE VERIFY | | | IT IS WORDED CORRECTLY OR UPDATE. | | | | | | -A0.02 SAYS 360 UNITS, BUT LOS ANALYSIS SAYS 370 UNITS. | | | PLEASE VERIFY BOTH AND UPDATE AS NEEDED. | | | | | | -SHOW AND LABEL PROPOSED AND EXISTING SIDEWALK | | | EASEMENTS ON CIVIL PLANS. SOME ADDITIONAL MAY BE | | | REQUIRED. | | | | | | -ARE THERE ANY OUTSIDE ADA PARKING SPOTS? IF NOT, ARE | | | ANY NEEDED OR REQUIRED? | | | | | | -A301 SHOWS GREENSPACE ISLANDS IN SOUTHWEST OUTSIDE | | | PARKING LOT BUT PGD PLAN DOES NOT. PLEASE MAKE SURE ALL | | | PLANS MATCH GENERAL DESIGN LAYOUT. | | | | | | -A301 HAS SOME HATCHED 20FT BY 20FT TRIANGLES. PLEASE | | | IDENTIFY THEM IN LEGEND. IF THEY ARE SIGHT TRIANGLES, | | | IS IT ALRIGHT FOR THE TREES TO BE IN THEM? | | | | | | -ON A402 AND A403 PLEASE CALLOUT DIMENSIONS OF PARKING | | | GARAGE ENTRANCE. | | | | | | -ON A404 PLEASE CALLOUT DIMENSIONS OF BROADWAY AVE | | | TUNNELS | | | | | | -CIVIL PLANS NOT SIGNED, SEALED, AND DATED. | | | | | | -ON C1.04 BETWEEN 550 AND 540 NORTHWOOD, DEMO PLAN SAYS | | | PARTY WALL. IF THAT IS A SHARED WALL, PLEASE HIGHLIGHT | | | BETTER AND ALSO INDICATE IF WALL WILL REMAIN OR BE | | | REPLACED. | | | | | | -ON C3.01 IS THE INTENT FOR THE PROPOSED 8 INCH PVC | | | WATER MAIN TO BE PRIVATELY OWNED AND MAINTAINED OR CITY | | | OWNED AND MAINTAINED? | | | | | | -CITY OWNED WATER MAINS AND WATER SERVICES LARGER THAN | | | 2 INCHES SHOULD BE DIP. | | | | | | -CALLOUT BACKFLOW ASSEMBLIES AND WATER METERS. ADD SIZE | | | TO LABEL. | | | | | | -C3.01 SOUTHWEST BUILDING A FIRE AND WATER SERVICE | | | LABELS APPEAR TO BE REVERSED. FIRELINE BACKFLOW | | | ASSEMBLY ALSO LOOKS CLOSE TO PARKING SPOT TRAFFIC. MAY | | | NEED INCREASE DISTANCE TO PREVENT DAMAGE. | | | | | | -WATER SERVICE LABELS ARE AMBIGUOUS AS TO WHICH | | | PORTIONS ARE PRIVATE. ALSO UNCLEAR AS TO SIZING WHEN | | | SAYING 3 INCH BUT THE TAP IS FOUR INCHES AND REQUIRED | | | PIPING WOULD BE AT LEAST 4 INCHES. | | | | | | -FOR ANY PROPOSED WATER METERS LARGER THAN 2 INCHES, | | | ADD WORDING ABOVE GROUND TO LABELS. | | | | | | -C3.01: ADD SMALL CIRCULAR OBJECTS IN SIDEWALK TO | | | LEGEND AND IDENTIFY THEM. | | | | | | -ENSURE ARCHITECTURAL PLANS COMPLY WITH NOTE 21 ON | | | UTILITY PLAN REGARDING VERTICAL CLEARANCE DISTANCES. | | | | | | -NOTE 20 ON UTILITY PLAN DOES NOT SEEM TO MAKE SENSE. A | | | DDCV IS A TYPE OF BACKFLOW PREVENTER. | | | | | | -NOTE 14 ON UTILITY PLAN: VERIFY IF THERE WILL BE ANY | | | COUNTY UTILITIES IN PROJECT AREA. IF NOT, THEN REVISE | | | OR REMOVE. | | | | | | -FIRELINE BACKFLOW ASSEMBLY LOCATIONS WOULD ONLY BE | | | ACCEPTABLE IF ROW IS ABANDONED AND AREA IS PRIVATELY | | | OWNED. | | | | | | -BACKFLOW ASSEMBLIES FOR DOMESTIC METERED WATER | | | SERVICES APPEAR TO BE MISSING. THEY SHOULD BE OUTSIDE | | | OF BUILDING, ADJACENT PROPERTY LINE, ON PRIVATE | | | PROPERTY, WITH DISTANCE MINIMIZED TO METER, BUT NOT | | | LOCATED IN SIDEWALK PEDESTRIAN TRAFFIC. CLEARLY SHOW | | | AND LABEL THEM. | | | | | | -FOR FIRELINE BACKFLOW ASSEMBLY AT NORTHEAST BUILDING | | | OFF BROADWAY, ATTEMPT TO RELOCATE SLIGHTLY NORTH TO | | | REDUCE PIPE DISTANCE. IF CANNOT EXPLAIN CONFLICT. | | | | | | -C3.02: FDC NEEDS TO BE ON PRIVATE PROPERTY AND OUT OF | | | PEDESTRIAN TRAFFIC AS WELL AS NOT IMPEDING VEHICLE | | | DOORS. IT MUST ALSO BE CLEARLY VISIBLE AND TYPICALLY | | | REQUIRES SIGNAGE. | | | | | | -C3.02: FIRELINE BACKFLOW ASSEMBLY LOOKS TO CONFLICT | | | WITH CURB OR GUTTER AND IS CLOSE TO VEHICLES. | | | | | | -C3.03: PROPOSED 24 INCH WATER MAIN SHOULD BE DIP | | | INSTEAD OF PVC; ADD 24 INCH VALVES AT 24 INCH TEES IN | | | OFFSET DIRECTIONS; | | | | | | -ADD NOTE ON UTILITY PLAN SHEETS THAT LINESTOPS OR | | | INSERTION VALVES MAY BE REQUIRED AS DIRECTED BY CITY OF | | | WEST PALM BEACH UTILITIES OR ENGINEER OF RECORD TO | | | MINIMIZE WATER OUTAGES. | | | | | | -THERE ARE SOME DOORS THAT OPEN TO PLAZA CLOSE TO A | | | LANDSCAPING AREA THAT WOULD SEEM TO BLOCK PEDESTRIAN | | | MOVEMENT. IS THAT ALRIGHT? | | | | | | -BUILDING B EAST FIRELINE LABELED 6 BY 4, BUT SHOULD BE | | | 8 BY 4; ALSO SHOW AND LABEL DOMESTIC BACKFLOW ASSEMBLY; | | | UTILITY EASEMENT FOR METER NOT SHOWN AND LABELED. | | | | | | -VERIFY BUILDING B WEST FDC LOCATION IS ACCEPTABLE WITH | | | WPB PLANNING. ALSO VERIFY BUILDING C SOUTH FDC LOCATION | | | WITH THEM. | | | | | | -BUILDING C 4 INCH WATER MAIN DOES NOT DEADEND PER WPB | | | GIS. PLEASE VERIFY AND UPDATE UTILITY PLAN AS NEEDED. | | | | | | -BUILDING CS CANNOT HAVE BACKFLOW ASSEMBLIES IN RIGHT | | | OF WAY. NEEDS TO BE ON PRIVATE PROPERTY. | | | | | | -DID NOT SEE FIRELINES WITH DCDAS FOR BUILDING CS. | | | VERIFY THEY ARE NOT NEEDED OR REQUIRED FOR THESE | | | BUILDINGS OVER 2 STORIES. | | | | | | -ARE ANY WERE LATERALS MISSING FOR BUILDINGS ON WEST | | | SIDE OF BROADWAY? | | | | | | -APPLICANT MUST FOLLOW ALL RULES REGARDING SUBMETERING | | | AND REMETERING | | | | | | -THERE ARE SPECIAL REQUIREMENTS AND RESTRICTIONS | | | REGARDING PLUMBING CROSSING RIGHT OF WAYS AND STREETS. | | | | | | -NOTE 16 MENTIONED A LIFT STATION. ARE THERE ANY | | | PROPOSED LIFT STATIONS FOR THIS PROJECT? | | | | | | -VERIFY ALL REQUIRED PAVEMENT RESTORATION FROM UTILITY | | | WORK IS SHOWN. LOOKS LIKE THERE IS AT LEAST SOME | | | MISSING ON 25TH ST. | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
11-17-2021 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
11-17-2021 |
Time |
|
Rev Time |
|
| Received By |
rrossano |
Date |
11-17-2021 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-11-17 13:11:07 | COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR, ENG. | | | SERVICES DEPT., 561-494-1098 [email protected] : | | | | | | GENERAL: | | | O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND | | | INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER | | | (Z-XXXXXXXX). | | | O THE CITY OF WEST PALM BEACH HAS A NUMBER OF | | | REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY | | | AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND | | | WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE | | | DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK | | | BELOW: | | | A. HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WP | | | B_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FUL | | | L-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97 | | | B1960045731D3658206F27451722716EF | | | B. THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE | | | FOUND HERE: | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | C. ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM | | | BEACH, FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, | | | ADOPTED SEPT. 22, 2008. (SUPPLEMENT NO. 18) | | | CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL, | | | SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER | | | SERVICE FACILITIES OF THE CITY. | | | THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE | | | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY | | | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, | | | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. | | | O AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR | | | MORE INFORMATION, REFER TO THE LINK BELOW: | | | A. HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PU | | | BLICATIONS/BACKFLOW-CROSS-CONNECTION- CONTROL-MANUAL | | | O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY | | | OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC | | | RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF | | | YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE | | | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL | | | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT | | | [email protected] OR 561-494-1079 FOR FURTHER | | | ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION | | | ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD | | | SURVEY, POT-HOLING, SOFT DIGS ETC. | | | | | | BACKFLOW ASSEMBLY AND METERS: | | | | | | O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER | | | SERVICES AND WATER METERS FOR THE PARKING LOTS, ALONG | | | WITH WHAT IS HAPPENING TO THEM. | | | O SHOW EXISTING AND PROPOSED DEDICATED UTILITY | | | EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO | | | PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO | | | STRUCTURES WITHIN EASEMENT. | | | O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION | | | OF WATER METER AND BACKFLOW | | | PREVENTION. | | | O BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY | | | OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER | | | METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO | | | PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE | | | INSTALLED ABOVE-GROUND ONLY. | | | O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE | | | NOTE USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA. | | | | | | WATER/WASTEWATER PLAN: | | | O PROVIDE VERTICAL DATUM AND DATUM CONVERSION | | | INFORMATION (NAVD 1988 AND NGVD 1929). | | | O SHOW PROJECT ADDRESS ON ALL PLAN SHEETS. | | | O PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE | | | STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC. | | | O PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND | | | DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND | | | SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH | | | PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE | | | AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS, | | | BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO | | | BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS, | | | DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS, | | | ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT | | | ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF | | | SANITARY SEWER LINES. | | | O GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR | | | SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE | | | PROFILE VIEW. | | | O DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN | | | VIEW FOR ALL SANITARY AND STORM SEWERS. | | | O SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT | | | MATERIAL. | | | O PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED | | | UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC, | | | ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION | | | FACILITIES LOCATED ON THE RIGHT-OF-WAY. | | | O PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER | | | AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD | | | DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS. | | | O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY | | | TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT | | | APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING | | | AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, | | | MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS | | | SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 | | | FOR WATER. | | | O PROVIDE FIRE FLOW TEST DATA. | | | O PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND | | | STORMWATER INFRASTRUCTURE ALONG ENTIRE PROJECT | | | FRONTAGE. | | | O CUT AND CAP UTILITIES NOT IN USE AND REMOVE ANY | | | ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY | | | ROW. | | | O WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL | | | BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY | | | PROPOSED LENGTH IN FEET. | | | O CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY | | | SEWER ARE REQUIRED. | | | O PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE | | | JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET. | | | O ADD NOTE TO PLANS SPECIFYING CITY?S DOWNSTREAM LIFT | | | STATION NUMBER. | | | O PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR | | | PROPOSED SANITARY LATERALS. | | | O LABEL WATER LINES AS PRIVATE WHERE APPLICABLE. | | | O PLEASE SHOW AND LABEL EXISTING AND PROPOSED GREASE | | | TRAPS (IF ANY). | | | O PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN | | | OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER. | | | | | | FORMAL ENGINEERING REVIEW: | | | O FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES | | | NOI REQUIREMENTS WILL BE ENFORCED. | | | - AN NOI IS REQUIRED FOR PROJECTS THAT: | | | - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS | | | THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF | | | DEVELOPMENT OR SALE; | | | - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE | | | STATE OR TO SURFACE WATERS OF THE STATE THROUGH A | | | MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4). | | | - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF | | | CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION | | | THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL | | | SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT | | | OF THE 10-2 CERTIFICATION. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF | | | WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING | | | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT | | | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING | | | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED | | | LEAD-FREE DESIGN. | | | O FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES | | | ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY | | | LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT | | | PARCELS. | | | O FOR FORMAL ENGINEERING SUBMITTAL, IF WATER LINES ARE | | | BEING REPLACED IN ROW, SHOW ADJACENT PARCEL ADDRESSES. | | | O FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO PROVIDE | | | 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF | | | PROPOSED TRENCH IN CITY MAINTAINED ROADWAY AREAS PER | | | CITY OF WPB STANDARD DETAIL GC-8. | | | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | CALCULATIONS OF PERVIOUS AND IMPERVIOUS AREAS FOR | | | PROPOSED IMPROVED AREAS. | | | | | | QUESTIONS AND COORDINATION CONTACTS: | | | O MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR WITH | | | CITY OF WPB PUBLIC UTILITIES, REGARDING PLACEMENT OF | | | BACKFLOW DEVICES AND WATER METERS. CONTACT HIM AT | | | 561-494-2262 OR [email protected] | | | O RICK ROSSANO, SR. PROJECT COORDINATOR, ENGINEERING | | | SERVICES DEPARTMENT AT 561-494-1098 [email protected] | | | O MIKE TECHNOW, PROJECT ENGINEER, PUBLIC UTILITIES | | | DEPARTMENT AT 561-494-1047 OR [email protected] | | | O TRACY WARD, SR. STORMWATER ENGINEER, ENGINEERING | | | SERVICES DEPT. AT 561-494-1120 OR [email protected] | | | | | | | | | COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE | | | SUPER., WPB PUBLIC UTILITIES, 561-494-2262 OR | | | [email protected]: | | | | | | -THERE ARE MANY MONITORING WELLS AS SHOWN ON THE | | | SURVEY. WILL THEY REMAIN? | | | | | | -FOR EASTERN BUILDING NUMBER 4 ON UTILITY PLAN: THE | | | LEADER LINES FOR THE WATER SERVICES APPEAR TO BE | | | POINTING WRONG; METER BOX SHOULD NOT BE IN | | | SIDEWALK/HARDSCAPE; BACKFLOW ASSEMBLIES NOT ALLOWED IN | | | PROPOSED LOCATION UNLESS SIDEWALK ENDS IMMEDIATELY EAST | | | OF BACKFLOW ASSEMBLIES AND WILL NOT BE CONTINUED; | | | UTILITY EASEMENT REQUIRED FOR WATER METER AND UPSTREAM | | | PIPING; SEWER LATER IS CLOSE TO TREE PLANTER; DISTANCE | | | CALLOUT NEEDED BETWEEN SEWER LATERAL AND WATER SERVICE. | | | | | | -UTILITY PLANS SHOW MULTIPLE BUILDINGS LABELED AS | | | NUMBER 4. | | | | | | -SEWER LATERAL FOR WESTERN BUILDING NUMBER 4 HAS SEWER | | | LATERAL RUNNING THROUGH TREE PLANTER. | | | | | | -ARE CROSS WALKS NEEDED AT NEW INTERSECTION OF BROADWAY | | | AND 23RD? (EITHER EAST-WEST OR NORTH-SOUTH) | | | | | | -EXISTING TRAFFIC SIGN AT NORTHWEST INTERSECTION OF | | | BROADWAY AND 23RD IS IN CLOSE PROXIMITY TO PROPOSED | | | STORMWATER UTILITY. | | | | | | -PROPOSED TREE PLANTER ON 23RD STREET IS CONFLICTING | | | WITH LARGE UTILITY POLE. | | | | | | -ALL OF THE SEWER MAINS IN THE AREA ARE OLDER AND MAY | | | REQUIRE UPGRADE OR REPLACEMENT AS ADVISED BY ENGINEER | | | OF RECORD AND/OR CITY OF WEST PALM BEACH. | | | | | | -SHEET C3.10, REPLACE STANDARD DETAIL WS-4 WITH WS-3. | | | METERS 3 INCHES OR LARGER NEED TO BE ABOVE-GROUND | | | INSTALLED. | | | | | | -SUBMIT SEPARATE LANDSCAPING PLAN SHOWING ALL EXISTING | | | AND PROPOSED TREES. ON ONE OF THE PLAN SHEETS HAVE | | | LANDSCAPING OVERLOAD ON UTILITIES SO CAN RECOGNIZE ANY | | | CONFLICTS. | | | | | | -ON NORTH SIDE OF WESTERN BUILDING 4, DO PLANTERS | | | PREVENT WALKING ALONG SIDEWALK? | | | | | | -SOME CANOPY OVERHANGS ON NORTHWOOD APPEAR TO EXTEND | | | INTO ROW. PLEASE VERIFY THAT IS ACCEPTABLE. | | | | | | -ADD PRIVATE TO LABEL OF ANY PRIVATELY OWNED AND | | | MAINTAINED UTILITY INFRASTRUCTURE. | | | | | | -DID NOT SEE ANY FDC. ARE ANY NEEDED OR REQUIRED? | | | | | | -UTILITY PLAN SHOWS STREET SIGN, UTILITY POLE, AND GUY | | | WIRES IN SIDEWALK AT NORTHWEST INTERSECTION OF PINEWOOD | | | AND 23RD. | | | | | | -SIDEWALK EASEMENT MAY BE REQUIRED FOR NORTHSIDE OF | | | 23RD ST. | | | | | | -ADJUST LOCATION OF FIRE HYDRANT AT NORTHWOOD AND | | | PINEWOOD INTERSECTION SUCH THAT IT DOES NOT ENCROACH IN | | | SIDEWALK AND HAS MORE CLEARANCE DISTANCE FROM | | | STORMWATER UTILITY. | | | | | | -BACKFLOW ASSEMBLIES MUST BE LOCATED ON PRIVATE | | | PROPERTY. CANNOT BE ONLY IN RIGHT OF WAY. | | | | | | -ENSURE FIRELINE BACKFLOW ASSEMBLY LOCATIONS ARE NFPA | | | COMPLIANT. | | | | | | -ADD PROPOSED METER SIZING. IF METERS ARE 3 INCHES OR | | | LARGER, THE SCALE FOOTPRINT IS LIKELY MUCH SMALLER THAN | | | WHEN BUILT OUT AND WOULD CONFLICT WITH PROPOSED | | | LOCATIONS. | | | | | | -LABEL ALL EXISTING AND PROPOSED FIRE HYDRANTS. SEE AT | | | LEAST ONE MISSING LABELING. | | | | | | -FIRE HYDRANT AT BROADWAY AND 24TH MAY NOT MEET | | | STANDARD DETAIL CLEARANCE REQUIREMENTS IF A TREE IS | | | PLANTED NEAR IT. | | | | | | -SHOW AND LABEL ALL EXISTING WATER SERVICE LINES, METER | | | BOXES, METERS, SEWER LATERALS, BACKFLOW ASSEMBLIES IN | | | THE PROJECT AREA AND LABEL WHAT IS HAPPENING TO THEM. | | | SEE MANY NOT SHOWN AND/OR LABELED. | | | | | | -BUILDING 3 FIRELINE CONFLICTS WITH A MONITORING WELL. | | | | | | -8 INCH FIRELINE: IS MISSING POINT OF SERVICE GATE | | | VALVE; CONFLICTING WITH SOME KIND OF UTILITY BOX; IS IN | | | MIDDLE OF SIDEWALK; DOES NOT HAVE PIPE DISTANCE | | | MINIMIZED BETWEEN BACKFLOW ASSEMBLY AND WATER MAIN. | | | | | | -UTILITY PLAN SHOWS STREET SIGN IN PROPOSED PARKING | | | SPOT AT BUILDING 2. | | | | | | -PROPOSE SEWER MANHOLE NEAR BUILDING 2 IS HALF IN | | | STREET AND SIDEWALK MAKING MAINTENANCE MORE DIFFICULT. | | | ALSO IF PRIVATE ADD TO LABEL. | | | | | | -TREE OR BUSH BLOCKING DRIVEWAY OF BUILDING 2 ON | | | UTILITY PLAN. | | | | | | -THERE ARE SMALL CIRCULAR OBJECTS ON UTILITY PLAN NEAR | | | PARKING SPOTS. IF THEY ARE BOLLARDS ADD TO LEGEND OR | | | LABEL THEM. | | | | | | -WATER MAIN IN PINEWOOD IS OLDER AND MAY REQUIRE | | | UPGRADE OR REPLACEMENT AS ADVISED BY ENGINEER OF RECORD | | | AND/OR CITY OF WEST PALM BEACH. | | | | | | -23RD ST IS ONE-WAY GOING WEST UNTIL PINEWOOD. MAKE | | | SURE PLANS ACCOUNT FOR THE ONE-WAY DRIVING DIRECTION. | | | | | | -SHOW LOCATIONS OF PROPOSED TRANSFORMER PADS WHEREVER | | | OVERHEAD ELECTRIC UTILITIES ARE BEING UNDERGROUNDED. | | | | | | -SHOW ALL EXISTING DRIVEWAY APPROACHES AND LABEL ANY | | | THAT ARE BEING REMOVED ON THE DEMO PLANS. FOR EXAMPLE, | | | CANNOT TELL WHAT IS HAPPENING TO THE DRIVEWAY APPROACH | | | AT 23RD ON THE SOUTH SIDE OF 701 23RD ST. | | | | | | -PLEASE MAKE SURE CURB TYPES ARE LABELED ON ALL SHEETS | | | OF THE PAVING, GRADING, AND DRAINAGE PLANS. | | | | | | -REMOVAL, RELOCATION, OR ALTERATION OF CITY WPB METERED | | | WATER SERVICES AND BACKFLOW ASSEMBLIES IN PROJECT AREA | | | WOULD REQUIRE APPROVAL FROM ASSOCIATED DEPARTMENT | | | REPRESENTATIVES. THEY TYPICALLY REQUIRE PROJECT TO PAY | | | ANY ASSOCIATED UTILITY BILLING CHARGES OR FEES. | | | | | | -ADD WATER DEMAND CALCULATIONS TO UTILITY PLAN SHEETS. | | | | | | -EASEMENTS MAY BE REQUIRED FOR BUILDING STRUCTURES | | | CROSSING RIGHT OF WAY. | | | | | | -PROVIDE VERTICAL CLEARANCE DISTANCE FOR ANY STRUCTURES | | | OVER STREETS, AND ENSURE LARGE UTILITY VEHICLES SUCH AS | | | VACUUM TRUCKS WILL HAVE SUFFICIENT CLEARANCE. | | | | | | -ON DEMO PLAN LABEL WHAT IS HAPPENING TO THE LARGE | | | UTILITY POLES AT THE NORTHWEST CORNER OF BUILDING 1 | | | LOADING DRIVEWAY. | | | | | | -SOME OF THE VEHICLE MOVEMENTS AND SIGNAGE ARE NOT | | | CLEAR FROM THE PLANS. FOR EXAMPLE, HOW WILL DRIVERS | | | HEADING EAST ON 25TH KNOW NOT TO PULL INTO LOADING BAY | | | FOR BUILDING 1. HOW WILL TRUCKS BACK UP INTO THAT BAY | | | WITHOUT CREATING TRAFFIC PROBLEMS? | | | | | | -WATER UTILITIES ON 24TH ST BETWEEN PINEWOOD AND | | | BROADWAY SHOULD BE REMOVED OR RELOCATED. | | | | | | -SHOW ALL GREASE TRAPS/INTERCEPTORS. | | | | | | -PROPOSED CURB DESIGN ON EAST SIDE OF PINEWOOD MAKES | | | EXCAVATION AND MAINTENANCE OF EXISTING WATER MAIN | | | DIFFICULT. | | | | | | -ALLEY BETWEEN 24TH AND NORTHWOOD HAS OVERHEAD | | | UTILITIES WITH POLES THAT LOOK TO CONFLICT WITH | | | PROPOSED BUILDINGS. | | | | | | -BUILDING 6 METERED WATER SERVICE NEEDS UTILITY | | | EASEMENT SHOWN AND LABELED. VERIFY AREA AROUND METER | | | BOX WILL BE LANDSCAPING AND NOT HARDSCAPE. | | | | | | -BUILDING 5 METERED WATER SERVICE NEEDS A UTILITY | | | EASEMENT IF ON PRIVATE PROPERTY. METER BOX SHOULD NOT | | | BE IN HARDSCAPE. METER BOX AND BACKFLOW ASSEMBLY SHOULD | | | NOT BE IN MIDDLE OF SIDEWALK TRAFFIC. | | | | | | -THERE IS A LOT OF GAS UTILITIES BUT NOT SHOWING ON | | | UTILITY PLANS. PLEASE SHOW ALL FRANCHISE AND DRY | | | UTILITIES. | | | | | | -SEWER CLEANOUT FOR BUILDING 5 IS IN FRONT OF DOOR | | | CREATING MAINTENANCE CONFLICT. | | | | | | -DID NOT SEE DEDICATED FIRELINES FOR BUILDINGS ON WEST | | | SIDE OF PINEWOOD. ARE ANY NEEDED OR REQUIRED? | | | | | | -SHOW PAVEMENT RESTORATION BOUNDARIES FOR ALL UTILITY | | | WORK INCLUDING 25TH ST AND 23RD ST. MAKE SURE THE | | | BOUNDARIES COMPLY WITH DISTANCE REQUIREMENTS ON | | | STANDARD DETAILS. | | | | | | -IS THE NEW CONNECTING ROAD BETWEEN NORTHWOOD AND 23RD | | | INTENDED FOR PUBLIC USE? ARE ANY EASEMENTS NEEDED FOR | | | IT SINCE ON PRIVATE PROPERTY? VERIFY IT WILL BE | | | PRIVATELY MAINTAINED. | | | | | | -SEWER MAINS IN ALLEYS MAY NEED RELOCATION AS ADVISED | | | BY ENGINEER OF RECORD AND/OR CITY OF WEST PALM BEACH. | | | | | | -SEWER MAIN IS SHOWN ON UTILITY PLANS ON WEST SIDE OF | | | BROADWAY IN PROPOSED SIDEWALK. LOCATION WOULD MAKE | | | EXCAVATION AND MAINTENANCE DIFFICULT. SOME PROPOSED | | | TREE PLANTER LOCATIONS ON TOP OF SEWER MAIN ALSO | | | CONFLICT WITH MAINTENANCE AS WELL AS SOME CURBING AT A | | | MANHOLE. | | | | | | -DOMESTIC WATER SERVICES TYPICALLY ARE NOT 3 INCH. 3 | | | INCH METERS HAVE 4 INCH DIP SERVICE PIPE SHOWN ON | | | STANDARD DETAILS. | | | | | | -ADD ELEVATION INFO TO SEWER MANHOLE LABELS. | | | | | | COMMENTS FROM MICHAEL TECHNOW, PROJECT ENGINEER, WPB | | | PUBLIC UTILITIES, 561-494-1047, [email protected] : | | | | | | PLEASE REPLACE 24? WM ON PINEWOOD WITHIN LIMITS OF THE | | | PROPOSED IMPROVEMENTS. | | | - PROVIDE PROFILE FROM TAP TO POINT OF SERVICE. | | | -REVISE UTILITY NOTES TO REFLECT ?CITY OF WEST PALM | | | BEACH? NOT PBCWUD/COUNTY. | | | - NO 3? SERVICES ALLOWED. USE EITHER 2? OR 4? WITH A | | | REDUCER. | | | -ADD NOTE TO CUT AND CAP ABANDONED SERVICES AT THE | | | MAIN. | | | | | | COMMENTS FROM BURT BAIRD, CITY OF WPB UTILITIES O&M | | | SUPERINTENDENT, 561-822-2056, [email protected] : | | | ? PLEASE ENSURE ADDED FLOW CAN BE HANDLED AT LS# 23 | | | ? KIMBERLY HORN MENTIONED AN ADDITIONAL FLOW OF 54000 | | | GALLONS ? SEE EMAILED DOCUMENT | | | ? THE COLLECTION SYSTEM AT THIS STATION EXPERIENCES | | | HIGH AMOUNTS OF I&I. ANY PLANS ON THIS BEING ADDRESSED? | | | ? I&I PUTS THE PUMPS AT THIS STATION ON LONG RUN TIMES | | | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | | CONCERNS, THANKS. | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
04-07-2022 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
04-07-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
04-07-2022 |
Time |
13:27 |
Sent To |
|
|
| Notes |
| 2022-04-07 13:28:19 | FIRE HAS NO OBJECTIONS TO THE PROPOSED AND APPROVES. | | | | | | FIRE'S APPROVAL OF THIS SUBMITTED PROJECT MAY NOT | | | CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | FIRE SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT THE | | | APPROPRIATE TIME AND IN ACCORDANCE WITH THE | | | REQUIREMENTS OF ALL APPLICABLE FIRE CODES AND | | | STANDARDS. | | | | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT; HOWEVER, THE FOLLOWING COMMENTS ARE | | | PROVIDED AND MAY NEED FURTHER CLARIFICATIONS WHERE | | | APPLICABLE. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF EACH BUILDING SHALL COMPLY WITH | | | THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, | | | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. | | | | | | 6. ALL PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A, | | | PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE, | | | INCLUDING MORE SPECIFICALLY, CHAPTER 42 STORAGE | | | OCCUPANCIES (PARKING STRUCTURES) | | | | | | 7. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA | | | 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THIS | | | STRUCTURE. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE | | | BUILDING REACHES THREE LEVELS OR THIRTY FEET WHILE | | | BEING CONSTRUCTED. SEPARATE SHOP DRAWINGS, ARE REQUIRED | | | TO BE SUBMITTED, REVIEWED AND APPROVED BY THE FIRE | | | PREVENTION BUREAU PRIOR TO ANY INSTALLATION. | | | | | | IT IS RECOMMENDED FOR HIGH RISES HAVE TWO SEPARATE FDC | | | LOCATIONS REMOTELY LOCATED. | | | | | | 7A. PER NFPA 14 | | | | | | 6.4.5.4* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED | | | NOT MORE THAN 100 FT (30.5 M) FROM THE NEAREST FIRE | | | HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY. | | | | | | 7B. PER NFPA 1 | | | | | | 18.3 WATER SUPPLIES. | | | 18.3.1* AN APPROVED WATER SUPPLY CAPABLE OF SUPPLYING | | | THE REQUIRED FIRE FLOW FOR FIRE PROTECTION SHALL BE | | | PROVIDED TO ALL PREMISES UPON WHICH FACILITIES, | | | BUILDINGS, OR PORTIONS OF BUILDINGS ARE HEREAFTER | | | CONSTRUCTED OR MOVED INTO THE JURISDICTION. THE | | | APPROVED WATER SUPPLY SHALL BE IN ACCORDANCE WITH | | | SECTION 18.4. | | | | | | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, | | | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE | | | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF | | | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, | | | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER | | | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) | | | AND ANY PERFORMANCE BASED INFORMATION SUCH AS | | | PRE-ENGINEERED SYSTEMS. | | | | | | FOR ANY PROPOSED FIRE PUMP(S) , WHAT IS(ARE) THE | | | PRIMARY AND SECONDARY POWER SOURCES? | | | | | | 7C. THE LOCATION OF THE DDCV FIRE LINE LOCATION SHALL | | | MEET THE REQUIREMENTS OF NFPA 24 AND SHALL BE | | | COORDINATED WITH THE OFFICE OF FIRE MARSHAL, THE CITY'S | | | ENGINEERS OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S | | | PLANNING AND ZONING OFFICE. | | | | | | 8. A CLASS ?A? NFPA 72 COMPLIANT MONITORED FIRE ALARM | | | SYSTEM IS REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP | | | DRAWINGS, ARE REQUIRED TO BE SUBMITTED, REVIEWED AND | | | APPROVED BY THE FIRE PREVENTION BUREAU PRIOR TO ANY | | | INSTALLATION. | | | | | | 9. ALL ELEVATORS OVER 6 FLOORS SHALL BE EQUIPPED WITH A | | | REGION 7 KEYWAY SYSTEM. | | | | | | ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTER?S | | | EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA | | | B44, SAFETY CODE FOR ELEVATORS. | | | | | | ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN | | | WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL | | | LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET | | | MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER | | | ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN | | | AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE | | | IN THE HORIZONTAL POSITION. | | | | | | 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, | | | EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A | | | PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE | | | SAFETY FEATURES AND EQUIPMENT. | | | | | | 11. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE | | | BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND | | | FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET | | | OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER | | | ARRIVING EMERGENCY VEHICLES. | | | | | | | | | 12. HIGH RISE EMERGENCY COMMAND ROOM | | | | | | THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1, | | | CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN | | | THE FOLLOWING FEATURES: | | | | | | 11.9.1 THE LOCATION, DESIGN, CONTENT, AND FIRE | | | DEPARTMENT ACCESS OF THE EMERGENCY COMMAND CENTER SHALL | | | BE APPROVED BY THE FIRE DEPARTMENT. | | | | | | 11.9.2 THE EMERGENCY COMMAND CENTER SHALL BE SEPARATED | | | FROM THE REMAINDER OF THE BUILDING BY A FIRE BARRIER | | | HAVING A FIRE RESISTANCE RATING OF NOT LESS THAN 1 | | | HOUR. | | | | | | 11.9.3 THE EMERGENCY COMMAND CENTER ROOM SHALL BE A | | | MINIMUM OF 200 FT2 (19 M2) WITH A MINIMUM DIMENSION OF | | | 10 FT (3050 MM). | | | | | | 11.9.4 THE FOLLOWING SHALL BE PROVIDED IN THE EMERGENCY | | | COMMAND CENTER. | | | (1) THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM. | | | (2) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED | | | ACCESS TO THE PUBLIC TELEPHONE SYSTEM | | | (3) SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL | | | FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF | | | EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING | | | EQUIPMENT AND FIRE DEPARTMENT ACCESS | | | (4) WORK TABLE. | | | (5) IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN | | | FOR THE BUILDING. | | | 11.9.5 WHERE OTHERWISE REQUIRED, THE FOLLOWING DEVICES | | | OR FUNCTIONS SHALL BE PROVIDED WITHIN THE EMERGENCY | | | COMMAND CENTER. | | | (1) THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM | | | CONTROL UNIT. | | | (2) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT. | | | (3) ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION | | | OF THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL | | | (4) STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING | | | SYSTEMS. | | | (5) CONTROLS FOR UNLOCKING STAIRWAY DOORS | | | SIMULTANEOUSLY | | | (6) SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY | | | PANELS | | | (7) EMERGENCY AND STANDBY POWER STATUS INDICATORS | | | (8) FIRE PUMP STATUS INDICATORS | | | (9) GENERATOR SUPERVISION DEVICES AND MANUAL START AND | | | TRANSFER FEATURES. | | | (10) PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED | | | BY OTHER SECTIONS OF THIS CODE | | | (11) CONTROLS REQUIRED FOR SMOKE CONTROL | | | | | | NFPA 101 | | | | | | 11.8.6* EMERGENCY COMMAND CENTER. | | | 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED | | | IN A | | | LOCATION APPROVED BY THE FIRE DEPARTMENT. | | | 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE | | | FOLLOWING: | | | (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS | | | (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION | | | SERVICE | | | PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER SECTION | | | OF THIS | | | CODE | | | (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION | | | PANELS | | | (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS | | | (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME | | | A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS | | | (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE | | | PROVIDED | | | IN ACCORDANCE WITH ASME A17.1/CSA B44 | | | (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS | | | (8) EMERGENCY GENERATOR STATUS INDICATORS | | | (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING | | | SYSTEM | | | (10) FIRE PUMP STATUS INDICATORS | | | (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED | | | ACCESS TO THE | | | PUBLIC TELEPHONE SYSTEM | | | (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY | | | 11.8.8 | | | | | | | | | 13. EMERGENCY RADIO COMMUNICATIONS | | | | | | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY | | | RADIO ENHANCEMENT SERVICES. | | | | | | 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM | | | RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT | | | COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL | | | DETERMINED BY THE AHJ. | | | NFPA 72, 24.9 TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT | | | SYSTEMS. | | | 24.9.1 GENERAL. | | | 24.9.1.1 NON-INTERFERENCE. NO AMPLIFICATION SYSTEM | | | CAPABLE | | | OF OPERATING ON FREQUENCIES OR CAUSING INTERFERENCE ON | | | FREQUENCIES | | | ASSIGNED TO THE JURISDICTION BY THE FCC SHALL BE | | | INSTALLED | | | WITHOUT PRIOR COORDINATION AND APPROVAL OF THE | | | AUTHORITY | | | HAVING JURISDICTION. THE BUILDING MANAGER/OWNER SHALL | | | SUSPEND AND CORRECT OTHER EQUIPMENT INSTALLATIONS THAT | | | DEGRADE | | | THE PERFORMANCE OF THE PUBLIC SAFETY RADIO SYSTEM OR | | | PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM. | | | 24.9.1.2 APPROVAL AND PERMIT. PLANS SHALL BE SUBMITTED | | | FOR | | | APPROVAL PRIOR TO INSTALLATION. AT THE CONCLUSION OF | | | SUCCESSFUL | | | ACCEPTANCE TESTING, A RENEWABLE PERMIT SHALL BE ISSUED | | | FOR THE | | | PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM WHERE REQUIRED | | | BY | | | THE AUTHORITY HAVING JURISDICTION. | | | | | | THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL | | | STRENGTH OF -95 DBM FOR THE RADIO SYSTEM USED BY WEST | | | PALM BEACH FIRE DEPARTMENT. TESTING SHALL BE BY AN | | | ACCEPTABLE NATIONAL STANDARD DOCUMENTING PERCENTAGES | | | NOTED ABOVE AND BY ACTUAL RADIO TESTING BY FIRE | | | PERSONNEL. IF THE MINIMUM CANNOT BE MAINTAINED, A | | | BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH | | | A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP. | | | PLEASE CONTACT MARK FILLA, PALM BEACH COUNTY PUBLIC | | | SAFETY RADIO SYSTEMS MANAGER, [email protected], | | | 561-233-0837; AS OUR RADIOS OPERATE ON THEIR SYSTEM FOR | | | DETAILED RADIO FREQUENCY AND INSTALLATION INSTRUCTIONS. | | | | | | | | | 14. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS | | | BUILDING. | | | | | | ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS, | | | PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS. | | | | | | 15.HIGH RISE SMOKE CONTROL SYSTEM SHALL COMPLY WITH | | | NFPA 101, CHAPTER 9, BUILDING SERVICE AND FIRE | | | PROTECTION EQUIPMENT, INCLUDING: | | | | | | THE SMOKE CONTROL SYSTEMS SHALL BE INSTALLED, | | | INSPECTED, TESTED, AND MAINTAINED IN ACCORDANCE WITH | | | NFPA 92, STANDARD FOR SMOKE CONTROL SYSTEMS; NFPA 204, | | | STANDARD FOR SMOKE AND HEAT VENTING; OR NATIONALLY | | | RECOGNIZED STANDARDS, ENGINEERING GUIDES, OR | | | RECOMMENDED PRACTICES, AS APPROVED BY THE AUTHORITY | | | HAVING JURISDICTION. | | | | | | THE ENGINEER OF RECORD SHALL CLEARLY IDENTIFY THE | | | INTENT OF THE SYSTEM, THE DESIGN METHOD USED, THE | | | APPROPRIATENESS OF THE METHOD USED, AND THE REQUIRED | | | MEANS OF INSPECTING, TESTING, AND MAINTAINING THE | | | SYSTEM. | | | | | | ACCEPTANCE TESTING SHALL BE PERFORMED BY A SPECIAL | | | INSPECTOR IN ACCORDANCE WITH SECTION 9.9. | | | | | | 16. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | 17. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
11-10-2021 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
11-10-2021 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
11-10-2021 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2021-11-10 15:46:26 | FIRE HAS NO OBJECTIONS TO THE PROPOSED AND APPROVES. | | | | | | FIRE'S APPROVAL OF THIS SUBMITTED PROJECT MAY NOT | | | CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | FIRE SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT THE | | | APPROPRIATE TIME AND IN ACCORDANCE WITH THE | | | REQUIREMENTS OF ALL APPLICABLE FIRE CODES AND | | | STANDARDS. | | | | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT; HOWEVER, THE FOLLOWING COMMENTS ARE | | | PROVIDED AND MAY NEED FURTHER CLARIFICATIONS WHERE | | | APPLICABLE. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF EACH BUILDING SHALL COMPLY WITH | | | THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, | | | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. | | | | | | 6. ALL PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A, | | | PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE, | | | INCLUDING MORE SPECIFICALLY, CHAPTER 42 STORAGE | | | OCCUPANCIES (PARKING STRUCTURES) | | | | | | 7. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA | | | 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THIS | | | STRUCTURE. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE | | | BUILDING REACHES THREE LEVELS OR THIRTY FEET WHILE | | | BEING CONSTRUCTED. SEPARATE SHOP DRAWINGS, ARE REQUIRED | | | TO BE SUBMITTED, REVIEWED AND APPROVED BY THE FIRE | | | PREVENTION BUREAU PRIOR TO ANY INSTALLATION. | | | | | | IT IS RECOMMENDED FOR HIGH RISES HAVE TWO SEPARATE FDC | | | LOCATIONS REMOTELY LOCATED. | | | | | | 7A. PER NFPA 14 | | | | | | 6.4.5.4* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED | | | NOT MORE THAN 100 FT (30.5 M) FROM THE NEAREST FIRE | | | HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY. | | | | | | 7B. PER NFPA 1 | | | | | | 18.3 WATER SUPPLIES. | | | 18.3.1* AN APPROVED WATER SUPPLY CAPABLE OF SUPPLYING | | | THE REQUIRED FIRE FLOW FOR FIRE PROTECTION SHALL BE | | | PROVIDED TO ALL PREMISES UPON WHICH FACILITIES, | | | BUILDINGS, OR PORTIONS OF BUILDINGS ARE HEREAFTER | | | CONSTRUCTED OR MOVED INTO THE JURISDICTION. THE | | | APPROVED WATER SUPPLY SHALL BE IN ACCORDANCE WITH | | | SECTION 18.4. | | | | | | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, | | | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE | | | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF | | | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, | | | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER | | | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) | | | AND ANY PERFORMANCE BASED INFORMATION SUCH AS | | | PRE-ENGINEERED SYSTEMS. | | | | | | FOR ANY PROPOSED FIRE PUMP(S) , WHAT IS(ARE) THE | | | PRIMARY AND SECONDARY POWER SOURCES? | | | | | | 7C. THE LOCATION OF THE DDCV FIRE LINE LOCATION SHALL | | | MEET THE REQUIREMENTS OF NFPA 24 AND SHALL BE | | | COORDINATED WITH THE OFFICE OF FIRE MARSHAL, THE CITY'S | | | ENGINEERS OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S | | | PLANNING AND ZONING OFFICE. | | | | | | 8. A CLASS ?A? NFPA 72 COMPLIANT MONITORED FIRE ALARM | | | SYSTEM IS REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP | | | DRAWINGS, ARE REQUIRED TO BE SUBMITTED, REVIEWED AND | | | APPROVED BY THE FIRE PREVENTION BUREAU PRIOR TO ANY | | | INSTALLATION. | | | | | | 9. ALL ELEVATORS OVER 6 FLOORS SHALL BE EQUIPPED WITH A | | | REGION 7 KEYWAY SYSTEM. | | | | | | ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTER?S | | | EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA | | | B44, SAFETY CODE FOR ELEVATORS. | | | | | | ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN | | | WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL | | | LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET | | | MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER | | | ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN | | | AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE | | | IN THE HORIZONTAL POSITION. | | | | | | 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, | | | EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A | | | PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE | | | SAFETY FEATURES AND EQUIPMENT. | | | | | | 11. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE | | | BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND | | | FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET | | | OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER | | | ARRIVING EMERGENCY VEHICLES. | | | | | | | | | 12. HIGH RISE EMERGENCY COMMAND ROOM | | | | | | THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1, | | | CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN | | | THE FOLLOWING FEATURES: | | | | | | 11.9.1 THE LOCATION, DESIGN, CONTENT, AND FIRE | | | DEPARTMENT ACCESS OF THE EMERGENCY COMMAND CENTER SHALL | | | BE APPROVED BY THE FIRE DEPARTMENT. | | | | | | 11.9.2 THE EMERGENCY COMMAND CENTER SHALL BE SEPARATED | | | FROM THE REMAINDER OF THE BUILDING BY A FIRE BARRIER | | | HAVING A FIRE RESISTANCE RATING OF NOT LESS THAN 1 | | | HOUR. | | | | | | 11.9.3 THE EMERGENCY COMMAND CENTER ROOM SHALL BE A | | | MINIMUM OF 200 FT2 (19 M2) WITH A MINIMUM DIMENSION OF | | | 10 FT (3050 MM). | | | | | | 11.9.4 THE FOLLOWING SHALL BE PROVIDED IN THE EMERGENCY | | | COMMAND CENTER. | | | (1) THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM. | | | (2) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED | | | ACCESS TO THE PUBLIC TELEPHONE SYSTEM | | | (3) SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL | | | FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF | | | EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING | | | EQUIPMENT AND FIRE DEPARTMENT ACCESS | | | (4) WORK TABLE. | | | (5) IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN | | | FOR THE BUILDING. | | | 11.9.5 WHERE OTHERWISE REQUIRED, THE FOLLOWING DEVICES | | | OR FUNCTIONS SHALL BE PROVIDED WITHIN THE EMERGENCY | | | COMMAND CENTER. | | | (1) THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM | | | CONTROL UNIT. | | | (2) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT. | | | (3) ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION | | | OF THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL | | | (4) STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING | | | SYSTEMS. | | | (5) CONTROLS FOR UNLOCKING STAIRWAY DOORS | | | SIMULTANEOUSLY | | | (6) SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY | | | PANELS | | | (7) EMERGENCY AND STANDBY POWER STATUS INDICATORS | | | (8) FIRE PUMP STATUS INDICATORS | | | (9) GENERATOR SUPERVISION DEVICES AND MANUAL START AND | | | TRANSFER FEATURES. | | | (10) PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED | | | BY OTHER SECTIONS OF THIS CODE | | | (11) CONTROLS REQUIRED FOR SMOKE CONTROL | | | | | | NFPA 101 | | | | | | 11.8.6* EMERGENCY COMMAND CENTER. | | | 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED | | | IN A | | | LOCATION APPROVED BY THE FIRE DEPARTMENT. | | | 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE | | | FOLLOWING: | | | (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS | | | (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION | | | SERVICE | | | PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER SECTION | | | OF THIS | | | CODE | | | (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION | | | PANELS | | | (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS | | | (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME | | | A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS | | | (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE | | | PROVIDED | | | IN ACCORDANCE WITH ASME A17.1/CSA B44 | | | (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS | | | (8) EMERGENCY GENERATOR STATUS INDICATORS | | | (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING | | | SYSTEM | | | (10) FIRE PUMP STATUS INDICATORS | | | (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED | | | ACCESS TO THE | | | PUBLIC TELEPHONE SYSTEM | | | (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY | | | 11.8.8 | | | | | | | | | 13. EMERGENCY RADIO COMMUNICATIONS | | | | | | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY | | | RADIO ENHANCEMENT SERVICES. | | | | | | 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM | | | RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT | | | COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL | | | DETERMINED BY THE AHJ. | | | NFPA 72, 24.9 TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT | | | SYSTEMS. | | | 24.9.1 GENERAL. | | | 24.9.1.1 NON-INTERFERENCE. NO AMPLIFICATION SYSTEM | | | CAPABLE | | | OF OPERATING ON FREQUENCIES OR CAUSING INTERFERENCE ON | | | FREQUENCIES | | | ASSIGNED TO THE JURISDICTION BY THE FCC SHALL BE | | | INSTALLED | | | WITHOUT PRIOR COORDINATION AND APPROVAL OF THE | | | AUTHORITY | | | HAVING JURISDICTION. THE BUILDING MANAGER/OWNER SHALL | | | SUSPEND AND CORRECT OTHER EQUIPMENT INSTALLATIONS THAT | | | DEGRADE | | | THE PERFORMANCE OF THE PUBLIC SAFETY RADIO SYSTEM OR | | | PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM. | | | 24.9.1.2 APPROVAL AND PERMIT. PLANS SHALL BE SUBMITTED | | | FOR | | | APPROVAL PRIOR TO INSTALLATION. AT THE CONCLUSION OF | | | SUCCESSFUL | | | ACCEPTANCE TESTING, A RENEWABLE PERMIT SHALL BE ISSUED | | | FOR THE | | | PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM WHERE REQUIRED | | | BY | | | THE AUTHORITY HAVING JURISDICTION. | | | | | | THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL | | | STRENGTH OF -95 DBM FOR THE RADIO SYSTEM USED BY WEST | | | PALM BEACH FIRE DEPARTMENT. TESTING SHALL BE BY AN | | | ACCEPTABLE NATIONAL STANDARD DOCUMENTING PERCENTAGES | | | NOTED ABOVE AND BY ACTUAL RADIO TESTING BY FIRE | | | PERSONNEL. IF THE MINIMUM CANNOT BE MAINTAINED, A | | | BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH | | | A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP. | | | PLEASE CONTACT MARK FILLA, PALM BEACH COUNTY PUBLIC | | | SAFETY RADIO SYSTEMS MANAGER, [email protected], | | | 561-233-0837; AS OUR RADIOS OPERATE ON THEIR SYSTEM FOR | | | DETAILED RADIO FREQUENCY AND INSTALLATION INSTRUCTIONS. | | | | | | | | | 14. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS | | | BUILDING. | | | | | | ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS, | | | PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS. | | | | | | 15.HIGH RISE SMOKE CONTROL SYSTEM SHALL COMPLY WITH | | | NFPA 101, CHAPTER 9, BUILDING SERVICE AND FIRE | | | PROTECTION EQUIPMENT, INCLUDING: | | | | | | THE SMOKE CONTROL SYSTEMS SHALL BE INSTALLED, | | | INSPECTED, TESTED, AND MAINTAINED IN ACCORDANCE WITH | | | NFPA 92, STANDARD FOR SMOKE CONTROL SYSTEMS; NFPA 204, | | | STANDARD FOR SMOKE AND HEAT VENTING; OR NATIONALLY | | | RECOGNIZED STANDARDS, ENGINEERING GUIDES, OR | | | RECOMMENDED PRACTICES, AS APPROVED BY THE AUTHORITY | | | HAVING JURISDICTION. | | | | | | THE ENGINEER OF RECORD SHALL CLEARLY IDENTIFY THE | | | INTENT OF THE SYSTEM, THE DESIGN METHOD USED, THE | | | APPROPRIATENESS OF THE METHOD USED, AND THE REQUIRED | | | MEANS OF INSPECTING, TESTING, AND MAINTAINING THE | | | SYSTEM. | | | | | | ACCEPTANCE TESTING SHALL BE PERFORMED BY A SPECIAL | | | INSPECTOR IN ACCORDANCE WITH SECTION 9.9. | | | | | | 16. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | 17. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
3 |
Status |
P |
Date |
09-27-2022 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
09-27-2022 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
09-27-2022 |
Time |
16:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
F |
Date |
08-15-2022 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
08-15-2022 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
08-15-2022 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2022-08-15 14:24:53 | ITEM APPROVED BY HPB, MODIFICATIONS IN LINE WITH | | | COMMENTS. HOWEVER, SHIFTING OF STRUCTURE ON NORTHWOOD | | | ROAD AND DEMOLITION OF LOT 23 RESULTING IN VACANT | | | LAND/THROUGH STREET REQUIRES UPDATED HPB APPROVAL. |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
F |
Date |
11-18-2021 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
11-18-2021 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
11-18-2021 |
Time |
09:49 |
Sent To |
|
|
| Notes |
| 2021-11-18 09:56:06 | TWO BUILDINGS OF OVERALL PROJECT EXTEND INTO NORTHWOOD | | | ROAD HISTORIC DISTRICT. DOES NOT MEET DESIGN GUIDLEINES | | | OR COMPATIBILITY STANDARDS IN MASSING, SIZE, SCALE OR | | | ARCHITECTURAL FEATURES. HAVE DISCUSSED WITH ARCHITECT | | | AND TEAM AND THEY WILL REVISE ACCORDINGINGLY FOR A | | | SMOOTHER TRANSITION AND FACADE TRAETMENT OF URBAN | | | RETAIL SPACE AT GROUND FLOOR AND OVERALL. NEW | | | CONSTRUCTION WILL NEED TO BE HARD AND APPROVED BY HPB, | | | CURRENTLY SCHEDULED FOR 12/15/21. | | | | | | QUESTIONS, CONTACT: | | | FRIEDERIKE MITTNER, CITY HISTORIC PRESERVATION PLANNER | | | (561) 822-1457 OR [email protected] |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
6 |
Status |
F |
Date |
01-05-2023 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
01-05-2023 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
01-05-2023 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2023-01-05 16:23:00 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: NORTHWOOD ANCHOR SITE Z21080015 | | | JANUARY 5, 2023 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | | | | 1. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE | | | TREES AND PALMS IN GOOD CONDITION TO BE PRESERVED ON | | | SITE OR RELOCATED. ANSI A 300 (PART 5) STANDARDS | | | SPECIFY EXAMPLES OF SUITABILITY RATINGS OF GOOD, | | | MODERATE, OR POOR FOR RELOCATION. PROVIDE AN ARBORISTS | | | REPORT RATING THE CONDITION AND RELOCATION POTENTIAL | | | FOR THE NATIVE TREES AND PALMS. THERE ARE LIVE OAKS, | | | SABAL PALMS, AND ROYAL PALMS THAT ARE INDICATED TO BE | | | REMOVED. NON NATIVE TREES AND PALMS ARE NOT REQUIRED TO | | | BE RELOCATED. | | | 2. MAKE THE FOLLOWING CORRECTIONS TO THE TREE | | | DISPOSITION LIST: | | | ??? SATISFIED. THERE ARE MULTIPLE TREES AND PALMS THAT | | | ARE MISIDENTIFIED ON THE TREE DISPOSITION LIST. | | | ??? SATISFIED. ONLY TREES PROPOSED TO BE REMOVED WITH A | | | CANOPY DIAMETER OF 20 FEET OR MORE SHOULD HAVE THE | | | MITIGATION SQUARE FOOTAGE CALCULATED BASED ON THE | | | ACTUAL DIAMETER. TREES LESS THAN 20 FEET CANOPY | | | DIAMETER AND PALMS SHOULD SHOW THE CATEGORY MITIGATION | | | DUE. | | | SHOW THE MITIGATION SQUARE FOOTAGE DUE FOR PALMS BY | | | CATEGORY (CATEGORY 3 IS 100 SQ FT, CATEGORY 4 IS 50 SQ | | | FT.) | | | ??? SATISFIED. MULTIPLE PALMS PLANTED TOGETHER MUST | | | HAVE EACH SINGLE TRUNK COUNTED TOWARD MITIGATION. | | | EXAMPLE: TRIPLE ADONIDIA WOULD BE 3 X 50 SQ FT. | | | ??? SATISFIED. PROVIDE THE TOTAL MITIGATION SQUARE | | | FOOTAGE DUE. | | | PROVIDE THE TOTAL MITIGATION SQUARE FOOTAGE DUE. | | | ??? SATISFIED. PROVIDE THE MITIGATION SQUARE FOOTAGE | | | PROVIDED BASED ON THE PLANT LIST. | | | | | | 3. SATISFIED. PROVIDE A DIAGRAM OF THE REQUIRED AND | | | PROVIDED PUBLIC, SEMI-PUBLIC, PRIVATE OPEN AREAS AND | | | URBAN GREENWAYS SYSTEM FOR EACH PARCEL IN THE NMUD | | | ZONING DISTRICT. IDENTIFY THE TYPE OF OPEN SPACE. 10% | | | COMMON PRIVATE OPEN SPACE IS REQUIRED. | | | THE REQUIRED OPEN SPACE NEEDS TO BE QUANTIFIED, | | | IDENTIFIED AS TO THE TYPE, AND ALL REQUIREMENTS NEED TO | | | BE SHOWN FOR THAT OPEN SPACE TYPE. | | | SURFACE PARKING AREAS CANNOT BE COUNTED TOWARD REQUIRED | | | OPEN SPACE. | | | 4/13/22 SHEET A103.0 COULD NOT BE LOCATED IN THE | | | SUBMITTAL. SHEET L102 SHOWS SURFACE PARKING AREA | | | COUNTED AS LANDSCAPE OPEN SPACE. | | | | | | 4. SATISFIED. SHOW THE ROOFTOP TERRACES AND INCLUDE HOW | | | THE REQUIREMENTS OF SECTION 94-210 P. 5. ARE MET, | | | INCLUDING 15% LANDSCAPE REQUIREMENT AND PROVIDE A | | | LANDSCAPE PLAN FOR EACH AREA. | | | | | | 5. SATISFIED. IDENTIFY RELOCATED TREES OR PALMS ON THE | | | PLANT LIST AND COUNT THEM TOWARD THE REQUIRED TREES. | | | | | | 6. SATISFIED. IF ANY ARTIFICIAL TURF AREAS ARE | | | PROPOSED, THEY MUST MEET THE REQUIREMENTS OF SECTION | | | 94-451, INCLUDING ALL AREAS THAT ARE ALLOWED BY CODE | | | MUST NOT BE VISIBLE FROM A ROAD OR STREET. | | | | | | 7. SATISFIED. BUFFER TREES AND HEDGES MUST BE PROVIDED | | | ALONG ALL BUFFERS. THERE IS A LARGE GAP IN THE TREES | | | ADJACENT TO THE WEST OF THE SURFACE PARKING LOT. THE | | | WEST PROPERTY LINE ADJACENT TO THE FEC RAILROAD RIGHT | | | OF WAY REQUIRES AT LEAST A 5 FOOT BUFFER STRIP PER | | | SECTION 94-209 2. F. 1. E. | | | | | | THE BUFFER ON THE SOUTH SIDE OF THE SURFACE PARKING LOT | | | DOES NOT MEET THE REQUIRED WIDTH. | | | | | | 8. SATISFIED. PROVIDE CALCULATIONS FOR REQUIRED STREET | | | TREES AT MAXIMUM SPACING EVERY 30 FEET OR PORTION | | | THEREOF AND SHOW THE NUMBER PROVIDED FOR EACH | | | STREETSCAPE LENGTH. SHOW THE REQUIRED PLANTING STRIP. | | | | | | 4/13/22 EACH BLOCK STREET SEGMENT MUST BE LISTED WITH | | | THE TOTAL LENGTH OF THE ADJACENT PROPERTY LINE AND THE | | | REQUIRED AND PROVIDED STREET TREES SHOWN. CANNOT | | | COMBINE SEGMENTS. THE NUMBER IN SOME SEGMENTS DOES NOT | | | MEET CODE. THE OVERALL INTENT IS TO PROVIDE MAXIMUM | | | TREE CANOPY COVERAGE FOR ALL SEGMENTS. | | | | | | 6/27/22 THE AREA ALONG 25TH STREET SHOWS A LONG GAP | | | BETWEEN TREES WITH UTILITY VALVES AND FIRE HYDRANT. | | | THIS NEEDS TO BE SPREAD OUT TO ALLOW TREES TO BE IN | | | BETWEEN VALVES. | | | STREET TREES ARE NOT SHOWN ON THE NORTHWOOD ROAD | | | SEGMENT. | | | | | | 9. SATISFIED. CORRECT THE CODE REQUIREMENTS CHART ON | | | SHEET L1.01TO UPDATE THE SHADE AND FLOWERING TREE | | | REQUIREMENTS OF SECTION 94-442 C. 2. B. TO CURRENT | | | CODE. | | | | | | | | | 10. SATISFIED. REMOVED FROM PLAN. CORRECT THE CODE | | | REQUIREMENTS CHART ON SHEET L1.01TO UPDATE THE SHADE | | | AND FLOWERING TREE REQUIREMENTS OF SECTION 94-443 C. 3. | | | TO CURRENT CODE. THE TREE PER 100 SQ FT REQUIREMENT WAS | | | REMOVED. | | | 4/13/22 THERE ARE 4 TERMINAL ISLANDS REQUIRED FOR THE | | | SURFACE PARKING AREA, CORRECT ON CHART. | | | | | | 11. SATISFIED. AUSTRALIAN TREE FERN DOES NOT MEET THE | | | DEFINITION OF TREE. | | | | | | 12. SATISFIED. SHOW ALL EXISTING AND PROPOSED WATER AND | | | SEWER AND DRAINAGE LINES ON THE LANDSCAPE PLAN. SHOW | | | LOCATIONS OF BACKFLOWS AND ADJUST LOCATIONS OF UTILITY | | | LINES TO RESOLVE CONFLICTS WITH EXISTING AND PROPOSED | | | TREES AND LANDSCAPING. | | | | | | FDC CONNECTIONS SHOULD BE MOVED TO THE BUILDING AND NOT | | | BE IN THE STREETSCAPE. | | | EXFILTRATION TRENCHES CANNOT BE LOCATED IN THE | | | STREETSCAPE AS THEY WILL RESTRICT THE ROOT SPACE | | | AVAILABLE FOR THE STREET TREES. | | | | | | 6/27/22 THERE ARE STILL CONFLICTS BETWEEN WATER, FIRE | | | AND SEWER LINES IN THE STREETSCAPE AND THE PLAZA IV | | | OPEN SPACE. | | | | | | 13. SATISFIED. PLANT LIST NEEDS TO BE MODIFIED TO | | | SEPARATE THE REQUIRED OPEN SPACE PLANT LISTS. | | | | | | | | | 14. SATISFIED. PROVIDE THE 50 REQUIRED FLORIDA FRIENDLY | | | POINTS BASED ON THE FINAL PLANT LIST PER SECTION | | | 94-443(G). AFTER MAKING THE FOLLOWING CORRECTIONS: | | | ??? 2 INDICATE WHERE THE AREAS ARE DESIGNATED. | | | ??? 3A AND 3C ARE NOT SUPPORTED BY THE PLANT LIST. | | | ??? 5B AND 5D ADD UP TO MORE THAN 100%, MUST REDUCE ONE | | | CATEGORY | | | ??? 6B IS NOT SUPPORTED BY THE PLAN SUBMITTED | | | | | | | | | 15. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L. | | | PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT | | | MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT | | | TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE | | | LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH | | | FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH | | | FLORIDA LANDSCAPES. PROVIDE THE ACTUAL PERCENTAGE BASED | | | ON THE PLANT LIST. | | | | | | | | | 16. SATISFIED. REMOVED FROM PLAN. ALL SURFACE PARKING | | | MUST MEET THE REQUIREMENTS OF SECTION 94-443(C)(3) A. | | | INCLUDING TERMINAL LANDSCAPE ISLANDS, INTERIOR ISLANDS | | | AND SHADE TREES. | | | MINIMUM BUFFER WIDTH IS NOT MET. | | | 17. SATISFIED. REMOVED FROM PLAN. PROVIDE AN EXHIBIT | | | SHOWING THE PARKING AREA SURFACE CALCULATIONS, PARKING | | | SPACE AREAS AND LANDSCAPE AREAS PROVIDED TO DEMONSTRATE | | | COMPLIANCE WITH SECTIONS 94-443 (C)(3) AND (4). PROVIDE | | | THE CALCULATIONS IN THE LANDSCAPE REQUIREMENT CHART. | | | REFER TO FIGURE XIV-1. SHOW THE ACTUAL PROVIDED | | | LANDSCAPE SQUARE FOOTAGE. | | | SEE THE REFERENCED FIGURE TO PROVIDE THE EXHIBIT AND | | | CORRECT CALCULATIONS. | | | | | | 18. SATISFIED. PROVIDE SCREENING HEDGES AND SHOW | | | LOCATIONS FOR ALL GROUND MOUNTED VALVES AND EQUIPMENT | | | AND ADD A NOTE THAT ALL EQUIPMENT WILL BE SCREENED. | | | | | | 19. SATISFIED. PORTIONS OF THE RIGHT OF WAY ON BROADWAY | | | AND 24TH STREET ARE FDOT RIGHT OF WAY AND ARE SUBJECT | | | TO REVIEW AND PERMITTING BY FDOT. PROVIDE PRELIMINARY | | | REVIEW OF ANY STREETSCAPE PROPOSED WITHIN THE FDOT | | | RIGHT OF WAY. | | | | | | 4/13/22 THIS COMMENT WAS NOT ADDRESSED IN THE RESPONSES | | | AS DISCUSSED AT THE PPRC MEETING. | | | 8/4/22 RESPONSES WERE NOT SHOWN ON THE SUBMITTED | | | MATERIAL. | | | 9/30/22 PRELIMINARY LETTER NEEDS TO BE SUBMITTED. | | | | | | ADDITIONAL COMMENTS 4/13/22: | | | 20. SATISFIED. STREET TREES MUST MEET THE MINIMUM CODE | | | REQUIREMENT OF 20 FEET ALONG MAIN ROADS, BUT ALL MUST | | | BE OF SUFFICIENT HEIGHT TO PROVIDE SAFE SIGHTLINES AND | | | TRAFFIC CLEARANCE FOR PEDESTRIANS AND VEHICLES. | | | CATHEDRAL LIVE OAKS MUST BE LISTED AT 20 FEET MINIMUM. | | | | | | 21. SATISFIED. STAFF PREFERS THAT THE GUMBO LIMBO | | | STREET TREES BE CHANGED TO GREEN BUTTONWOOD DUE TO ROOT | | | ISSUES IN CONFINED AREAS. | | | | | | ADDITIONAL COMMENTS 6/27/22: | | | 22. SATISFIED. RESPONSES TO LANDSCAPE COMMENTS WERE NOT | | | FOUND IN THE RESPONSE MEMO. | | | | | | 23. SATISFIED. SHOW LOCATIONS AND PROVIDE A DETAIL FOR | | | STRUCTURAL SOIL UNDER THE SIDEWALK/HARDSCAPE AREAS | | | ADJACENT TO THE STREET TREES. THIS SHOULD BE A 9 X 14 | | | FT AREA FOR EACH TREE ADJACENT TO THE CURB THAT WOULD | | | BE PLANTING AREA AND STRUCTURAL SOIL. | | | | | | ADDITIONAL COMMENTS 9/30/22: | | | | | | 24. SATISFIED. A CODE AMENDMENT IS PENDING REGARDING | | | THE REQUIREMENTS FOR PUBLIC OPEN SPACE. IF THE | | | AMENDMENT IS APPROVED, STAFF WILL NEED TO REVIEW THE | | | PUBLIC OPEN SPACE FOR COMPLIANCE WITH THE NEW CODE. | | | ADDITIONAL COMMENT 1/5/23: | | | 25. MAKE THE FOLLOWING CORRECTIONS TO THE TREE | | | DISPOSITION PLAN: | | | ??? A ROYAL POINCIANA IS MISSING FROM THE SURVEY AND | | | THE TREE DISPOSITION. THE TREE IS LOCATED OPPOSITE TREE | | | #22 ON THE EAST SIDE OF BROADWAY BETWEEN THE CURB AND | | | SIDEWALK. CALCULATE MITIGATION IF TO BE REMOVED AND | | | REVISE THE TOTAL MITIGATION DUE. SUBMIT REVISED PLAN | | | FOR THE TREE ALTERATION PERMIT. | | | | | | ??? TREE #13 THE MAHOGANY IS SHOWN WEST OF WHERE IT | | | ACTUALLY EXISTS. LOCATION IS OUTSIDE THE RIGHT OF WAY | | | SOUTH OF THE CONCRETE PAD. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE | | | STREET TREES AND RIGHT OF WAY LANDSCAPING AND | | | IRRIGATION APPROVED WITH THIS PETITION. | | | 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF | | | WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A | | | SEPARATE MAINTENANCE AGREEMENT WITH THE CITY. | | | | | | | | | | | | PROJECT: NORTHWOOD ANCHOR SITE ROW ABANDONMENT | | | Z21100023 | | | NO COMMENTS AT THIS TIME. | | | | | | | | | PROJECT: NORTHWOOD ANCHOR SITE VARIANCES Z21080018 | | | NO COMMENTS AT THIS TIME. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
5 |
Status |
F |
Date |
10-03-2022 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
10-03-2022 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
10-03-2022 |
Time |
09:48 |
Sent To |
|
|
| Notes |
| 2022-10-03 09:49:17 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: NORTHWOOD ANCHOR SITE DSI Z21080015 | | | SEPTEMBER 30, 2022 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | | | | 1. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE | | | TREES AND PALMS IN GOOD CONDITION TO BE PRESERVED ON | | | SITE OR RELOCATED. ANSI A 300 (PART 5) STANDARDS | | | SPECIFY EXAMPLES OF SUITABILITY RATINGS OF GOOD, | | | MODERATE, OR POOR FOR RELOCATION. PROVIDE AN ARBORISTS | | | REPORT RATING THE CONDITION AND RELOCATION POTENTIAL | | | FOR THE NATIVE TREES AND PALMS. THERE ARE LIVE OAKS, | | | SABAL PALMS, AND ROYAL PALMS THAT ARE INDICATED TO BE | | | REMOVED. NON NATIVE TREES AND PALMS ARE NOT REQUIRED TO | | | BE RELOCATED. | | | 2. MAKE THE FOLLOWING CORRECTIONS TO THE TREE | | | DISPOSITION LIST: | | | ??? SATISFIED. THERE ARE MULTIPLE TREES AND PALMS THAT | | | ARE MISIDENTIFIED ON THE TREE DISPOSITION LIST. | | | ??? SATISFIED. ONLY TREES PROPOSED TO BE REMOVED WITH A | | | CANOPY DIAMETER OF 20 FEET OR MORE SHOULD HAVE THE | | | MITIGATION SQUARE FOOTAGE CALCULATED BASED ON THE | | | ACTUAL DIAMETER. TREES LESS THAN 20 FEET CANOPY | | | DIAMETER AND PALMS SHOULD SHOW THE CATEGORY MITIGATION | | | DUE. | | | SHOW THE MITIGATION SQUARE FOOTAGE DUE FOR PALMS BY | | | CATEGORY (CATEGORY 3 IS 100 SQ FT, CATEGORY 4 IS 50 SQ | | | FT.) | | | ??? SATISFIED. MULTIPLE PALMS PLANTED TOGETHER MUST | | | HAVE EACH SINGLE TRUNK COUNTED TOWARD MITIGATION. | | | EXAMPLE: TRIPLE ADONIDIA WOULD BE 3 X 50 SQ FT. | | | ??? SATISFIED. PROVIDE THE TOTAL MITIGATION SQUARE | | | FOOTAGE DUE. | | | PROVIDE THE TOTAL MITIGATION SQUARE FOOTAGE DUE. | | | ??? SATISFIED. PROVIDE THE MITIGATION SQUARE FOOTAGE | | | PROVIDED BASED ON THE PLANT LIST. | | | | | | 3. SATISFIED. PROVIDE A DIAGRAM OF THE REQUIRED AND | | | PROVIDED PUBLIC, SEMI-PUBLIC, PRIVATE OPEN AREAS AND | | | URBAN GREENWAYS SYSTEM FOR EACH PARCEL IN THE NMUD | | | ZONING DISTRICT. IDENTIFY THE TYPE OF OPEN SPACE. 10% | | | COMMON PRIVATE OPEN SPACE IS REQUIRED. | | | THE REQUIRED OPEN SPACE NEEDS TO BE QUANTIFIED, | | | IDENTIFIED AS TO THE TYPE, AND ALL REQUIREMENTS NEED TO | | | BE SHOWN FOR THAT OPEN SPACE TYPE. | | | SURFACE PARKING AREAS CANNOT BE COUNTED TOWARD REQUIRED | | | OPEN SPACE. | | | 4/13/22 SHEET A103.0 COULD NOT BE LOCATED IN THE | | | SUBMITTAL. SHEET L102 SHOWS SURFACE PARKING AREA | | | COUNTED AS LANDSCAPE OPEN SPACE. | | | | | | 4. SATISFIED. SHOW THE ROOFTOP TERRACES AND INCLUDE HOW | | | THE REQUIREMENTS OF SECTION 94-210 P. 5. ARE MET, | | | INCLUDING 15% LANDSCAPE REQUIREMENT AND PROVIDE A | | | LANDSCAPE PLAN FOR EACH AREA. | | | | | | 5. SATISFIED. IDENTIFY RELOCATED TREES OR PALMS ON THE | | | PLANT LIST AND COUNT THEM TOWARD THE REQUIRED TREES. | | | | | | 6. SATISFIED. IF ANY ARTIFICIAL TURF AREAS ARE | | | PROPOSED, THEY MUST MEET THE REQUIREMENTS OF SECTION | | | 94-451, INCLUDING ALL AREAS THAT ARE ALLOWED BY CODE | | | MUST NOT BE VISIBLE FROM A ROAD OR STREET. | | | | | | 7. SATISFIED. BUFFER TREES AND HEDGES MUST BE PROVIDED | | | ALONG ALL BUFFERS. THERE IS A LARGE GAP IN THE TREES | | | ADJACENT TO THE WEST OF THE SURFACE PARKING LOT. THE | | | WEST PROPERTY LINE ADJACENT TO THE FEC RAILROAD RIGHT | | | OF WAY REQUIRES AT LEAST A 5 FOOT BUFFER STRIP PER | | | SECTION 94-209 2. F. 1. E. | | | | | | THE BUFFER ON THE SOUTH SIDE OF THE SURFACE PARKING LOT | | | DOES NOT MEET THE REQUIRED WIDTH. | | | | | | 8. SATISFIED. PROVIDE CALCULATIONS FOR REQUIRED STREET | | | TREES AT MAXIMUM SPACING EVERY 30 FEET OR PORTION | | | THEREOF AND SHOW THE NUMBER PROVIDED FOR EACH | | | STREETSCAPE LENGTH. SHOW THE REQUIRED PLANTING STRIP. | | | | | | 4/13/22 EACH BLOCK STREET SEGMENT MUST BE LISTED WITH | | | THE TOTAL LENGTH OF THE ADJACENT PROPERTY LINE AND THE | | | REQUIRED AND PROVIDED STREET TREES SHOWN. CANNOT | | | COMBINE SEGMENTS. THE NUMBER IN SOME SEGMENTS DOES NOT | | | MEET CODE. THE OVERALL INTENT IS TO PROVIDE MAXIMUM | | | TREE CANOPY COVERAGE FOR ALL SEGMENTS. | | | | | | 6/27/22 THE AREA ALONG 25TH STREET SHOWS A LONG GAP | | | BETWEEN TREES WITH UTILITY VALVES AND FIRE HYDRANT. | | | THIS NEEDS TO BE SPREAD OUT TO ALLOW TREES TO BE IN | | | BETWEEN VALVES. | | | STREET TREES ARE NOT SHOWN ON THE NORTHWOOD ROAD | | | SEGMENT. | | | | | | 9. SATISFIED. CORRECT THE CODE REQUIREMENTS CHART ON | | | SHEET L1.01TO UPDATE THE SHADE AND FLOWERING TREE | | | REQUIREMENTS OF SECTION 94-442 C. 2. B. TO CURRENT | | | CODE. | | | | | | | | | 10. SATISFIED. REMOVED FROM PLAN. CORRECT THE CODE | | | REQUIREMENTS CHART ON SHEET L1.01TO UPDATE THE SHADE | | | AND FLOWERING TREE REQUIREMENTS OF SECTION 94-443 C. 3. | | | TO CURRENT CODE. THE TREE PER 100 SQ FT REQUIREMENT WAS | | | REMOVED. | | | 4/13/22 THERE ARE 4 TERMINAL ISLANDS REQUIRED FOR THE | | | SURFACE PARKING AREA, CORRECT ON CHART. | | | | | | 11. SATISFIED. AUSTRALIAN TREE FERN DOES NOT MEET THE | | | DEFINITION OF TREE. | | | | | | 12. SATISFIED. SHOW ALL EXISTING AND PROPOSED WATER AND | | | SEWER AND DRAINAGE LINES ON THE LANDSCAPE PLAN. SHOW | | | LOCATIONS OF BACKFLOWS AND ADJUST LOCATIONS OF UTILITY | | | LINES TO RESOLVE CONFLICTS WITH EXISTING AND PROPOSED | | | TREES AND LANDSCAPING. | | | | | | FDC CONNECTIONS SHOULD BE MOVED TO THE BUILDING AND NOT | | | BE IN THE STREETSCAPE. | | | EXFILTRATION TRENCHES CANNOT BE LOCATED IN THE | | | STREETSCAPE AS THEY WILL RESTRICT THE ROOT SPACE | | | AVAILABLE FOR THE STREET TREES. | | | | | | 6/27/22 THERE ARE STILL CONFLICTS BETWEEN WATER, FIRE | | | AND SEWER LINES IN THE STREETSCAPE AND THE PLAZA IV | | | OPEN SPACE. | | | | | | 13. SATISFIED. PLANT LIST NEEDS TO BE MODIFIED TO | | | SEPARATE THE REQUIRED OPEN SPACE PLANT LISTS. | | | | | | | | | 14. SATISFIED. PROVIDE THE 50 REQUIRED FLORIDA FRIENDLY | | | POINTS BASED ON THE FINAL PLANT LIST PER SECTION | | | 94-443(G). AFTER MAKING THE FOLLOWING CORRECTIONS: | | | ??? 2 INDICATE WHERE THE AREAS ARE DESIGNATED. | | | ??? 3A AND 3C ARE NOT SUPPORTED BY THE PLANT LIST. | | | ??? 5B AND 5D ADD UP TO MORE THAN 100%, MUST REDUCE ONE | | | CATEGORY | | | ??? 6B IS NOT SUPPORTED BY THE PLAN SUBMITTED | | | | | | | | | 15. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L. | | | PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT | | | MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT | | | TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE | | | LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH | | | FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH | | | FLORIDA LANDSCAPES. PROVIDE THE ACTUAL PERCENTAGE BASED | | | ON THE PLANT LIST. | | | | | | | | | 16. SATISFIED. REMOVED FROM PLAN. ALL SURFACE PARKING | | | MUST MEET THE REQUIREMENTS OF SECTION 94-443(C)(3) A. | | | INCLUDING TERMINAL LANDSCAPE ISLANDS, INTERIOR ISLANDS | | | AND SHADE TREES. | | | MINIMUM BUFFER WIDTH IS NOT MET. | | | 17. SATISFIED. REMOVED FROM PLAN. PROVIDE AN EXHIBIT | | | SHOWING THE PARKING AREA SURFACE CALCULATIONS, PARKING | | | SPACE AREAS AND LANDSCAPE AREAS PROVIDED TO DEMONSTRATE | | | COMPLIANCE WITH SECTIONS 94-443 (C)(3) AND (4). PROVIDE | | | THE CALCULATIONS IN THE LANDSCAPE REQUIREMENT CHART. | | | REFER TO FIGURE XIV-1. SHOW THE ACTUAL PROVIDED | | | LANDSCAPE SQUARE FOOTAGE. | | | SEE THE REFERENCED FIGURE TO PROVIDE THE EXHIBIT AND | | | CORRECT CALCULATIONS. | | | | | | 18. SATISFIED. PROVIDE SCREENING HEDGES AND SHOW | | | LOCATIONS FOR ALL GROUND MOUNTED VALVES AND EQUIPMENT | | | AND ADD A NOTE THAT ALL EQUIPMENT WILL BE SCREENED. | | | | | | 19. NOT SATISFIED. PORTIONS OF THE RIGHT OF WAY ON | | | BROADWAY AND 24TH STREET ARE FDOT RIGHT OF WAY AND ARE | | | SUBJECT TO REVIEW AND PERMITTING BY FDOT. PROVIDE | | | PRELIMINARY REVIEW OF ANY STREETSCAPE PROPOSED WITHIN | | | THE FDOT RIGHT OF WAY. | | | | | | 4/13/22 THIS COMMENT WAS NOT ADDRESSED IN THE RESPONSES | | | AS DISCUSSED AT THE PPRC MEETING. | | | 8/4/22 RESPONSES WERE NOT SHOWN ON THE SUBMITTED | | | MATERIAL. | | | 9/30/22 PRELIMINARY LETTER NEEDS TO BE SUBMITTED. | | | | | | ADDITIONAL COMMENTS 4/13/22: | | | 20. SATISFIED. STREET TREES MUST MEET THE MINIMUM CODE | | | REQUIREMENT OF 20 FEET ALONG MAIN ROADS, BUT ALL MUST | | | BE OF SUFFICIENT HEIGHT TO PROVIDE SAFE SIGHTLINES AND | | | TRAFFIC CLEARANCE FOR PEDESTRIANS AND VEHICLES. | | | CATHEDRAL LIVE OAKS MUST BE LISTED AT 20 FEET MINIMUM. | | | | | | 21. SATISFIED. STAFF PREFERS THAT THE GUMBO LIMBO | | | STREET TREES BE CHANGED TO GREEN BUTTONWOOD DUE TO ROOT | | | ISSUES IN CONFINED AREAS. | | | | | | ADDITIONAL COMMENTS 6/27/22: | | | 22. SATISFIED. RESPONSES TO LANDSCAPE COMMENTS WERE NOT | | | FOUND IN THE RESPONSE MEMO. | | | | | | 23. SATISFIED. SHOW LOCATIONS AND PROVIDE A DETAIL FOR | | | STRUCTURAL SOIL UNDER THE SIDEWALK/HARDSCAPE AREAS | | | ADJACENT TO THE STREET TREES. THIS SHOULD BE A 9 X 14 | | | FT AREA FOR EACH TREE ADJACENT TO THE CURB THAT WOULD | | | BE PLANTING AREA AND STRUCTURAL SOIL. | | | | | | ADDITIONAL COMMENTS 9/30/22: | | | | | | 24. A CODE AMENDMENT IS PENDING REGARDING THE | | | REQUIREMENTS FOR PUBLIC OPEN SPACE. IF THE AMENDMENT IS | | | APPROVED, STAFF WILL NEED TO REVIEW THE PUBLIC OPEN | | | SPACE FOR COMPLIANCE WITH THE NEW CODE. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE | | | STREET TREES AND RIGHT OF WAY LANDSCAPING AND | | | IRRIGATION APPROVED WITH THIS PETITION. | | | 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF | | | WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A | | | SEPARATE MAINTENANCE AGREEMENT WITH THE CITY. | | | | | | | | | | | | PROJECT: NORTHWOOD ANCHOR SITE ROW ABANDONMENT | | | Z21100023 | | | NO COMMENTS AT THIS TIME. | | | | | | | | | PROJECT: NORTHWOOD ANCHOR SITE VARIANCES Z21080018 | | | NO COMMENTS AT THIS TIME. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
4 |
Status |
F |
Date |
08-04-2022 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
08-04-2022 |
Time |
16:00 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
08-04-2022 |
Time |
16:00 |
Sent To |
|
|
| Notes |
| 2022-08-04 16:01:09 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: NORTHWOOD ANCHOR SITE DSI Z21080015 | | | AUGUST 4, 2022 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | | | | 1. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE | | | TREES AND PALMS IN GOOD CONDITION TO BE PRESERVED ON | | | SITE OR RELOCATED. ANSI A 300 (PART 5) STANDARDS | | | SPECIFY EXAMPLES OF SUITABILITY RATINGS OF GOOD, | | | MODERATE, OR POOR FOR RELOCATION. PROVIDE AN ARBORISTS | | | REPORT RATING THE CONDITION AND RELOCATION POTENTIAL | | | FOR THE NATIVE TREES AND PALMS. THERE ARE LIVE OAKS, | | | SABAL PALMS, AND ROYAL PALMS THAT ARE INDICATED TO BE | | | REMOVED. NON NATIVE TREES AND PALMS ARE NOT REQUIRED TO | | | BE RELOCATED. | | | 2. MAKE THE FOLLOWING CORRECTIONS TO THE TREE | | | DISPOSITION LIST: | | | ? SATISFIED. THERE ARE MULTIPLE TREES AND PALMS THAT | | | ARE MISIDENTIFIED ON THE TREE DISPOSITION LIST. | | | ? SATISFIED. ONLY TREES PROPOSED TO BE REMOVED WITH A | | | CANOPY DIAMETER OF 20 FEET OR MORE SHOULD HAVE THE | | | MITIGATION SQUARE FOOTAGE CALCULATED BASED ON THE | | | ACTUAL DIAMETER. TREES LESS THAN 20 FEET CANOPY | | | DIAMETER AND PALMS SHOULD SHOW THE CATEGORY MITIGATION | | | DUE. | | | SHOW THE MITIGATION SQUARE FOOTAGE DUE FOR PALMS BY | | | CATEGORY (CATEGORY 3 IS 100 SQ FT, CATEGORY 4 IS 50 SQ | | | FT.) | | | ? SATISFIED. MULTIPLE PALMS PLANTED TOGETHER MUST HAVE | | | EACH SINGLE TRUNK COUNTED TOWARD MITIGATION. EXAMPLE: | | | TRIPLE ADONIDIA WOULD BE 3 X 50 SQ FT. | | | ? SATISFIED. PROVIDE THE TOTAL MITIGATION SQUARE | | | FOOTAGE DUE. | | | PROVIDE THE TOTAL MITIGATION SQUARE FOOTAGE DUE. | | | ? SATISFIED. PROVIDE THE MITIGATION SQUARE FOOTAGE | | | PROVIDED BASED ON THE PLANT LIST. | | | | | | 3. SATISFIED. PROVIDE A DIAGRAM OF THE REQUIRED AND | | | PROVIDED PUBLIC, SEMI-PUBLIC, PRIVATE OPEN AREAS AND | | | URBAN GREENWAYS SYSTEM FOR EACH PARCEL IN THE NMUD | | | ZONING DISTRICT. IDENTIFY THE TYPE OF OPEN SPACE. 10% | | | COMMON PRIVATE OPEN SPACE IS REQUIRED. | | | THE REQUIRED OPEN SPACE NEEDS TO BE QUANTIFIED, | | | IDENTIFIED AS TO THE TYPE, AND ALL REQUIREMENTS NEED TO | | | BE SHOWN FOR THAT OPEN SPACE TYPE. | | | SURFACE PARKING AREAS CANNOT BE COUNTED TOWARD REQUIRED | | | OPEN SPACE. | | | 4/13/22 SHEET A103.0 COULD NOT BE LOCATED IN THE | | | SUBMITTAL. SHEET L102 SHOWS SURFACE PARKING AREA | | | COUNTED AS LANDSCAPE OPEN SPACE. | | | | | | 4. SATISFIED. SHOW THE ROOFTOP TERRACES AND INCLUDE HOW | | | THE REQUIREMENTS OF SECTION 94-210 P. 5. ARE MET, | | | INCLUDING 15% LANDSCAPE REQUIREMENT AND PROVIDE A | | | LANDSCAPE PLAN FOR EACH AREA. | | | | | | 5. SATISFIED. IDENTIFY RELOCATED TREES OR PALMS ON THE | | | PLANT LIST AND COUNT THEM TOWARD THE REQUIRED TREES. | | | | | | 6. SATISFIED. IF ANY ARTIFICIAL TURF AREAS ARE | | | PROPOSED, THEY MUST MEET THE REQUIREMENTS OF SECTION | | | 94-451, INCLUDING ALL AREAS THAT ARE ALLOWED BY CODE | | | MUST NOT BE VISIBLE FROM A ROAD OR STREET. | | | | | | 7. SATISFIED. BUFFER TREES AND HEDGES MUST BE PROVIDED | | | ALONG ALL BUFFERS. THERE IS A LARGE GAP IN THE TREES | | | ADJACENT TO THE WEST OF THE SURFACE PARKING LOT. THE | | | WEST PROPERTY LINE ADJACENT TO THE FEC RAILROAD RIGHT | | | OF WAY REQUIRES AT LEAST A 5 FOOT BUFFER STRIP PER | | | SECTION 94-209 2. F. 1. E. | | | | | | THE BUFFER ON THE SOUTH SIDE OF THE SURFACE PARKING LOT | | | DOES NOT MEET THE REQUIRED WIDTH. | | | | | | 8. SATISFIED. PROVIDE CALCULATIONS FOR REQUIRED STREET | | | TREES AT MAXIMUM SPACING EVERY 30 FEET OR PORTION | | | THEREOF AND SHOW THE NUMBER PROVIDED FOR EACH | | | STREETSCAPE LENGTH. SHOW THE REQUIRED PLANTING STRIP. | | | | | | 4/13/22 EACH BLOCK STREET SEGMENT MUST BE LISTED WITH | | | THE TOTAL LENGTH OF THE ADJACENT PROPERTY LINE AND THE | | | REQUIRED AND PROVIDED STREET TREES SHOWN. CANNOT | | | COMBINE SEGMENTS. THE NUMBER IN SOME SEGMENTS DOES NOT | | | MEET CODE. THE OVERALL INTENT IS TO PROVIDE MAXIMUM | | | TREE CANOPY COVERAGE FOR ALL SEGMENTS. | | | | | | 6/27/22 THE AREA ALONG 25TH STREET SHOWS A LONG GAP | | | BETWEEN TREES WITH UTILITY VALVES AND FIRE HYDRANT. | | | THIS NEEDS TO BE SPREAD OUT TO ALLOW TREES TO BE IN | | | BETWEEN VALVES. | | | STREET TREES ARE NOT SHOWN ON THE NORTHWOOD ROAD | | | SEGMENT. | | | | | | 9. SATISFIED. CORRECT THE CODE REQUIREMENTS CHART ON | | | SHEET L1.01TO UPDATE THE SHADE AND FLOWERING TREE | | | REQUIREMENTS OF SECTION 94-442 C. 2. B. TO CURRENT | | | CODE. | | | | | | | | | 10. SATISFIED. REMOVED FROM PLAN. CORRECT THE CODE | | | REQUIREMENTS CHART ON SHEET L1.01TO UPDATE THE SHADE | | | AND FLOWERING TREE REQUIREMENTS OF SECTION 94-443 C. 3. | | | TO CURRENT CODE. THE TREE PER 100 SQ FT REQUIREMENT WAS | | | REMOVED. | | | 4/13/22 THERE ARE 4 TERMINAL ISLANDS REQUIRED FOR THE | | | SURFACE PARKING AREA, CORRECT ON CHART. | | | | | | 11. SATISFIED. AUSTRALIAN TREE FERN DOES NOT MEET THE | | | DEFINITION OF TREE. | | | | | | 12. SATISFIED. SHOW ALL EXISTING AND PROPOSED WATER AND | | | SEWER AND DRAINAGE LINES ON THE LANDSCAPE PLAN. SHOW | | | LOCATIONS OF BACKFLOWS AND ADJUST LOCATIONS OF UTILITY | | | LINES TO RESOLVE CONFLICTS WITH EXISTING AND PROPOSED | | | TREES AND LANDSCAPING. | | | | | | FDC CONNECTIONS SHOULD BE MOVED TO THE BUILDING AND NOT | | | BE IN THE STREETSCAPE. | | | EXFILTRATION TRENCHES CANNOT BE LOCATED IN THE | | | STREETSCAPE AS THEY WILL RESTRICT THE ROOT SPACE | | | AVAILABLE FOR THE STREET TREES. | | | | | | 6/27/22 THERE ARE STILL CONFLICTS BETWEEN WATER, FIRE | | | AND SEWER LINES IN THE STREETSCAPE AND THE PLAZA IV | | | OPEN SPACE. | | | | | | 13. SATISFIED. PLANT LIST NEEDS TO BE MODIFIED TO | | | SEPARATE THE REQUIRED OPEN SPACE PLANT LISTS. | | | | | | | | | 14. SATISFIED. PROVIDE THE 50 REQUIRED FLORIDA FRIENDLY | | | POINTS BASED ON THE FINAL PLANT LIST PER SECTION | | | 94-443(G). AFTER MAKING THE FOLLOWING CORRECTIONS: | | | ? 2 INDICATE WHERE THE AREAS ARE DESIGNATED. | | | ? 3A AND 3C ARE NOT SUPPORTED BY THE PLANT LIST. | | | ? 5B AND 5D ADD UP TO MORE THAN 100%, MUST REDUCE ONE | | | CATEGORY | | | ? 6B IS NOT SUPPORTED BY THE PLAN SUBMITTED | | | | | | | | | 15. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L. | | | PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT | | | MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT | | | TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE | | | LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH | | | FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH | | | FLORIDA LANDSCAPES. PROVIDE THE ACTUAL PERCENTAGE BASED | | | ON THE PLANT LIST. | | | | | | | | | 16. SATISFIED. REMOVED FROM PLAN. ALL SURFACE PARKING | | | MUST MEET THE REQUIREMENTS OF SECTION 94-443(C)(3) A. | | | INCLUDING TERMINAL LANDSCAPE ISLANDS, INTERIOR ISLANDS | | | AND SHADE TREES. | | | MINIMUM BUFFER WIDTH IS NOT MET. | | | 17. SATISFIED. REMOVED FROM PLAN. PROVIDE AN EXHIBIT | | | SHOWING THE PARKING AREA SURFACE CALCULATIONS, PARKING | | | SPACE AREAS AND LANDSCAPE AREAS PROVIDED TO DEMONSTRATE | | | COMPLIANCE WITH SECTIONS 94-443 (C)(3) AND (4). PROVIDE | | | THE CALCULATIONS IN THE LANDSCAPE REQUIREMENT CHART. | | | REFER TO FIGURE XIV-1. SHOW THE ACTUAL PROVIDED | | | LANDSCAPE SQUARE FOOTAGE. | | | SEE THE REFERENCED FIGURE TO PROVIDE THE EXHIBIT AND | | | CORRECT CALCULATIONS. | | | | | | 18. SATISFIED. PROVIDE SCREENING HEDGES AND SHOW | | | LOCATIONS FOR ALL GROUND MOUNTED VALVES AND EQUIPMENT | | | AND ADD A NOTE THAT ALL EQUIPMENT WILL BE SCREENED. | | | | | | 19. NOT SATISFIED. PORTIONS OF THE RIGHT OF WAY ON | | | BROADWAY AND 24TH STREET ARE FDOT RIGHT OF WAY AND ARE | | | SUBJECT TO REVIEW AND PERMITTING BY FDOT. PROVIDE | | | PRELIMINARY REVIEW OF ANY STREETSCAPE PROPOSED WITHIN | | | THE FDOT RIGHT OF WAY. | | | | | | 4/13/22 THIS COMMENT WAS NOT ADDRESSED IN THE RESPONSES | | | AS DISCUSSED AT THE PPRC MEETING. | | | 8/4/22 RESPONSES WERE NOT SHOWN ON THE SUBMITTED | | | MATERIAL. | | | | | | ADDITIONAL COMMENTS 4/13/22: | | | 20. SATISFIED. STREET TREES MUST MEET THE MINIMUM CODE | | | REQUIREMENT OF 20 FEET ALONG MAIN ROADS, BUT ALL MUST | | | BE OF SUFFICIENT HEIGHT TO PROVIDE SAFE SIGHTLINES AND | | | TRAFFIC CLEARANCE FOR PEDESTRIANS AND VEHICLES. | | | CATHEDRAL LIVE OAKS MUST BE LISTED AT 20 FEET MINIMUM. | | | | | | 21. SATISFIED. STAFF PREFERS THAT THE GUMBO LIMBO | | | STREET TREES BE CHANGED TO GREEN BUTTONWOOD DUE TO ROOT | | | ISSUES IN CONFINED AREAS. | | | | | | ADDITIONAL COMMENTS 6/27/22: | | | 22. NOT SATISFIED. RESPONSES TO LANDSCAPE COMMENTS WERE | | | NOT FOUND IN THE RESPONSE MEMO. | | | | | | 23. SATISFIED. SHOW LOCATIONS AND PROVIDE A DETAIL FOR | | | STRUCTURAL SOIL UNDER THE SIDEWALK/HARDSCAPE AREAS | | | ADJACENT TO THE STREET TREES. THIS SHOULD BE A 9 X 14 | | | FT AREA FOR EACH TREE ADJACENT TO THE CURB THAT WOULD | | | BE PLANTING AREA AND STRUCTURAL SOIL. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE | | | STREET TREES AND RIGHT OF WAY LANDSCAPING AND | | | IRRIGATION APPROVED WITH THIS PETITION. | | | 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF | | | WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A | | | SEPARATE MAINTENANCE AGREEMENT WITH THE CITY. | | | | | | | | | | | | PROJECT: NORTHWOOD ANCHOR SITE ROW ABANDONMENT | | | Z21100023 | | | NO COMMENTS AT THIS TIME. | | | | | | | | | PROJECT: NORTHWOOD ANCHOR SITE VARIANCES Z21080018 | | | NO COMMENTS AT THIS TIME. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
3 |
Status |
F |
Date |
06-27-2022 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
06-27-2022 |
Time |
12:36 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
06-27-2022 |
Time |
12:36 |
Sent To |
|
|
| Notes |
| 2022-06-27 12:37:37 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: NORTHWOOD ANCHOR SITE DSI Z21080015 | | | JUNE 27, 2022 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | | | | 1. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE | | | TREES AND PALMS IN GOOD CONDITION TO BE PRESERVED ON | | | SITE OR RELOCATED. ANSI A 300 (PART 5) STANDARDS | | | SPECIFY EXAMPLES OF SUITABILITY RATINGS OF GOOD, | | | MODERATE, OR POOR FOR RELOCATION. PROVIDE AN ARBORISTS | | | REPORT RATING THE CONDITION AND RELOCATION POTENTIAL | | | FOR THE NATIVE TREES AND PALMS. THERE ARE LIVE OAKS, | | | SABAL PALMS, AND ROYAL PALMS THAT ARE INDICATED TO BE | | | REMOVED. NON NATIVE TREES AND PALMS ARE NOT REQUIRED TO | | | BE RELOCATED. | | | 2. MAKE THE FOLLOWING CORRECTIONS TO THE TREE | | | DISPOSITION LIST: | | | ? SATISFIED. THERE ARE MULTIPLE TREES AND PALMS THAT | | | ARE MISIDENTIFIED ON THE TREE DISPOSITION LIST. | | | ? SATISFIED. ONLY TREES PROPOSED TO BE REMOVED WITH A | | | CANOPY DIAMETER OF 20 FEET OR MORE SHOULD HAVE THE | | | MITIGATION SQUARE FOOTAGE CALCULATED BASED ON THE | | | ACTUAL DIAMETER. TREES LESS THAN 20 FEET CANOPY | | | DIAMETER AND PALMS SHOULD SHOW THE CATEGORY MITIGATION | | | DUE. | | | SHOW THE MITIGATION SQUARE FOOTAGE DUE FOR PALMS BY | | | CATEGORY (CATEGORY 3 IS 100 SQ FT, CATEGORY 4 IS 50 SQ | | | FT.) | | | ? SATISFIED. MULTIPLE PALMS PLANTED TOGETHER MUST HAVE | | | EACH SINGLE TRUNK COUNTED TOWARD MITIGATION. EXAMPLE: | | | TRIPLE ADONIDIA WOULD BE 3 X 50 SQ FT. | | | ? PARTIALLY SATISFIED. PROVIDE THE TOTAL MITIGATION | | | SQUARE FOOTAGE DUE. | | | PROVIDE THE TOTAL MITIGATION SQUARE FOOTAGE DUE. | | | ? SATISFIED. PROVIDE THE MITIGATION SQUARE FOOTAGE | | | PROVIDED BASED ON THE PLANT LIST. | | | | | | 3. SATISFIED. PROVIDE A DIAGRAM OF THE REQUIRED AND | | | PROVIDED PUBLIC, SEMI-PUBLIC, PRIVATE OPEN AREAS AND | | | URBAN GREENWAYS SYSTEM FOR EACH PARCEL IN THE NMUD | | | ZONING DISTRICT. IDENTIFY THE TYPE OF OPEN SPACE. 10% | | | COMMON PRIVATE OPEN SPACE IS REQUIRED. | | | THE REQUIRED OPEN SPACE NEEDS TO BE QUANTIFIED, | | | IDENTIFIED AS TO THE TYPE, AND ALL REQUIREMENTS NEED TO | | | BE SHOWN FOR THAT OPEN SPACE TYPE. | | | SURFACE PARKING AREAS CANNOT BE COUNTED TOWARD REQUIRED | | | OPEN SPACE. | | | 4/13/22 SHEET A103.0 COULD NOT BE LOCATED IN THE | | | SUBMITTAL. SHEET L102 SHOWS SURFACE PARKING AREA | | | COUNTED AS LANDSCAPE OPEN SPACE. | | | | | | 4. SATISFIED. SHOW THE ROOFTOP TERRACES AND INCLUDE HOW | | | THE REQUIREMENTS OF SECTION 94-210 P. 5. ARE MET, | | | INCLUDING 15% LANDSCAPE REQUIREMENT AND PROVIDE A | | | LANDSCAPE PLAN FOR EACH AREA. | | | | | | 5. SATISFIED. IDENTIFY RELOCATED TREES OR PALMS ON THE | | | PLANT LIST AND COUNT THEM TOWARD THE REQUIRED TREES. | | | | | | 6. SATISFIED. IF ANY ARTIFICIAL TURF AREAS ARE | | | PROPOSED, THEY MUST MEET THE REQUIREMENTS OF SECTION | | | 94-451, INCLUDING ALL AREAS THAT ARE ALLOWED BY CODE | | | MUST NOT BE VISIBLE FROM A ROAD OR STREET. | | | | | | 7. SATISFIED. BUFFER TREES AND HEDGES MUST BE PROVIDED | | | ALONG ALL BUFFERS. THERE IS A LARGE GAP IN THE TREES | | | ADJACENT TO THE WEST OF THE SURFACE PARKING LOT. THE | | | WEST PROPERTY LINE ADJACENT TO THE FEC RAILROAD RIGHT | | | OF WAY REQUIRES AT LEAST A 5 FOOT BUFFER STRIP PER | | | SECTION 94-209 2. F. 1. E. | | | | | | THE BUFFER ON THE SOUTH SIDE OF THE SURFACE PARKING LOT | | | DOES NOT MEET THE REQUIRED WIDTH. | | | | | | 8. PARTIALLY SATISFIED. PROVIDE CALCULATIONS FOR | | | REQUIRED STREET TREES AT MAXIMUM SPACING EVERY 30 FEET | | | OR PORTION THEREOF AND SHOW THE NUMBER PROVIDED FOR | | | EACH STREETSCAPE LENGTH. SHOW THE REQUIRED PLANTING | | | STRIP. | | | | | | 4/13/22 EACH BLOCK STREET SEGMENT MUST BE LISTED WITH | | | THE TOTAL LENGTH OF THE ADJACENT PROPERTY LINE AND THE | | | REQUIRED AND PROVIDED STREET TREES SHOWN. CANNOT | | | COMBINE SEGMENTS. THE NUMBER IN SOME SEGMENTS DOES NOT | | | MEET CODE. THE OVERALL INTENT IS TO PROVIDE MAXIMUM | | | TREE CANOPY COVERAGE FOR ALL SEGMENTS. | | | | | | 6/27/22 THE AREA ALONG 25TH STREET SHOWS A LONG GAP | | | BETWEEN TREES WITH UTILITY VALVES AND FIRE HYDRANT. | | | THIS NEEDS TO BE SPREAD OUT TO ALLOW TREES TO BE IN | | | BETWEEN VALVES. | | | STREET TREES ARE NOT SHOWN ON THE NORTHWOOD ROAD | | | SEGMENT. | | | | | | 9. SATISFIED. CORRECT THE CODE REQUIREMENTS CHART ON | | | SHEET L1.01TO UPDATE THE SHADE AND FLOWERING TREE | | | REQUIREMENTS OF SECTION 94-442 C. 2. B. TO CURRENT | | | CODE. | | | | | | | | | 10. SATISFIED. REMOVED FROM PLAN. CORRECT THE CODE | | | REQUIREMENTS CHART ON SHEET L1.01TO UPDATE THE SHADE | | | AND FLOWERING TREE REQUIREMENTS OF SECTION 94-443 C. 3. | | | TO CURRENT CODE. THE TREE PER 100 SQ FT REQUIREMENT WAS | | | REMOVED. | | | 4/13/22 THERE ARE 4 TERMINAL ISLANDS REQUIRED FOR THE | | | SURFACE PARKING AREA, CORRECT ON CHART. | | | | | | 11. SATISFIED. AUSTRALIAN TREE FERN DOES NOT MEET THE | | | DEFINITION OF TREE. | | | | | | 12. PARTIALLY SATISFIED. SHOW ALL EXISTING AND PROPOSED | | | WATER AND SEWER AND DRAINAGE LINES ON THE LANDSCAPE | | | PLAN. SHOW LOCATIONS OF BACKFLOWS AND ADJUST LOCATIONS | | | OF UTILITY LINES TO RESOLVE CONFLICTS WITH EXISTING AND | | | PROPOSED TREES AND LANDSCAPING. | | | | | | FDC CONNECTIONS SHOULD BE MOVED TO THE BUILDING AND NOT | | | BE IN THE STREETSCAPE. | | | EXFILTRATION TRENCHES CANNOT BE LOCATED IN THE | | | STREETSCAPE AS THEY WILL RESTRICT THE ROOT SPACE | | | AVAILABLE FOR THE STREET TREES. | | | | | | 6/27/22 THERE ARE STILL CONFLICTS BETWEEN WATER, FIRE | | | AND SEWER LINES IN THE STREETSCAPE AND THE PLAZA IV | | | OPEN SPACE. | | | | | | 13. SATISFIED. PLANT LIST NEEDS TO BE MODIFIED TO | | | SEPARATE THE REQUIRED OPEN SPACE PLANT LISTS. | | | | | | | | | 14. SATISFIED. PROVIDE THE 50 REQUIRED FLORIDA FRIENDLY | | | POINTS BASED ON THE FINAL PLANT LIST PER SECTION | | | 94-443(G). AFTER MAKING THE FOLLOWING CORRECTIONS: | | | ? 2 INDICATE WHERE THE AREAS ARE DESIGNATED. | | | ? 3A AND 3C ARE NOT SUPPORTED BY THE PLANT LIST. | | | ? 5B AND 5D ADD UP TO MORE THAN 100%, MUST REDUCE ONE | | | CATEGORY | | | ? 6B IS NOT SUPPORTED BY THE PLAN SUBMITTED | | | | | | | | | 15. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L. | | | PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT | | | MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT | | | TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE | | | LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH | | | FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH | | | FLORIDA LANDSCAPES. PROVIDE THE ACTUAL PERCENTAGE BASED | | | ON THE PLANT LIST. | | | | | | | | | 16. SATISFIED. REMOVED FROM PLAN. ALL SURFACE PARKING | | | MUST MEET THE REQUIREMENTS OF SECTION 94-443(C)(3) A. | | | INCLUDING TERMINAL LANDSCAPE ISLANDS, INTERIOR ISLANDS | | | AND SHADE TREES. | | | MINIMUM BUFFER WIDTH IS NOT MET. | | | 17. SATISFIED. REMOVED FROM PLAN. PROVIDE AN EXHIBIT | | | SHOWING THE PARKING AREA SURFACE CALCULATIONS, PARKING | | | SPACE AREAS AND LANDSCAPE AREAS PROVIDED TO DEMONSTRATE | | | COMPLIANCE WITH SECTIONS 94-443 (C)(3) AND (4). PROVIDE | | | THE CALCULATIONS IN THE LANDSCAPE REQUIREMENT CHART. | | | REFER TO FIGURE XIV-1. SHOW THE ACTUAL PROVIDED | | | LANDSCAPE SQUARE FOOTAGE. | | | SEE THE REFERENCED FIGURE TO PROVIDE THE EXHIBIT AND | | | CORRECT CALCULATIONS. | | | | | | 18. SATISFIED. PROVIDE SCREENING HEDGES AND SHOW | | | LOCATIONS FOR ALL GROUND MOUNTED VALVES AND EQUIPMENT | | | AND ADD A NOTE THAT ALL EQUIPMENT WILL BE SCREENED. | | | | | | 19. NOT SATISFIED. PORTIONS OF THE RIGHT OF WAY ON | | | BROADWAY AND 24TH STREET ARE FDOT RIGHT OF WAY AND ARE | | | SUBJECT TO REVIEW AND PERMITTING BY FDOT. PROVIDE | | | PRELIMINARY REVIEW OF ANY STREETSCAPE PROPOSED WITHIN | | | THE FDOT RIGHT OF WAY. | | | | | | 4/13/22 THIS COMMENT WAS NOT ADDRESSED IN THE RESPONSES | | | AS DISCUSSED AT THE PPRC MEETING. | | | | | | ADDITIONAL COMMENTS 4/13/22: | | | 20. PARTIALLY SATISFIED. STREET TREES MUST MEET THE | | | MINIMUM CODE REQUIREMENT OF 20 FEET ALONG MAIN ROADS, | | | BUT ALL MUST BE OF SUFFICIENT HEIGHT TO PROVIDE SAFE | | | SIGHTLINES AND TRAFFIC CLEARANCE FOR PEDESTRIANS AND | | | VEHICLES. | | | CATHEDRAL LIVE OAKS MUST BE LISTED AT 20 FEET MINIMUM. | | | | | | 21. SATISFIED. STAFF PREFERS THAT THE GUMBO LIMBO | | | STREET TREES BE CHANGED TO GREEN BUTTONWOOD DUE TO ROOT | | | ISSUES IN CONFINED AREAS. | | | | | | ADDITIONAL COMMENTS 6/27/22: | | | 22. RESPONSES TO LANDSCAPE COMMENTS WERE NOT FOUND IN | | | THE RESPONSE MEMO. | | | | | | 23. SHOW LOCATIONS AND PROVIDE A DETAIL FOR STRUCTURAL | | | SOIL UNDER THE SIDEWALK/HARDSCAPE AREAS ADJACENT TO THE | | | STREET TREES. THIS SHOULD BE A 9 X 14 FT AREA FOR EACH | | | TREE ADJACENT TO THE CURB THAT WOULD BE PLANTING AREA | | | AND STRUCTURAL SOIL. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE | | | STREET TREES AND RIGHT OF WAY LANDSCAPING AND | | | IRRIGATION APPROVED WITH THIS PETITION. | | | 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF | | | WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A | | | SEPARATE MAINTENANCE AGREEMENT WITH THE CITY. | | | | | | | | | | | | PROJECT: NORTHWOOD ANCHOR SITE ROW ABANDONMENT | | | Z21100023 | | | NO COMMENTS AT THIS TIME. | | | | | | | | | PROJECT: NORTHWOOD ANCHOR SITE VARIANCES Z21080018 | | | NO COMMENTS AT THIS TIME. | | | | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
F |
Date |
04-13-2022 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
04-13-2022 |
Time |
17:40 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
04-13-2022 |
Time |
17:40 |
Sent To |
|
|
| Notes |
| 2022-04-13 17:41:26 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: NORTHWOOD ANCHOR SITE DSI Z21080015 | | | APRIL 13, 2022 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | | | | 1. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE | | | TREES AND PALMS IN GOOD CONDITION TO BE PRESERVED ON | | | SITE OR RELOCATED. ANSI A 300 (PART 5) STANDARDS | | | SPECIFY EXAMPLES OF SUITABILITY RATINGS OF GOOD, | | | MODERATE, OR POOR FOR RELOCATION. PROVIDE AN ARBORISTS | | | REPORT RATING THE CONDITION AND RELOCATION POTENTIAL | | | FOR THE NATIVE TREES AND PALMS. THERE ARE LIVE OAKS, | | | SABAL PALMS, AND ROYAL PALMS THAT ARE INDICATED TO BE | | | REMOVED. NON NATIVE TREES AND PALMS ARE NOT REQUIRED TO | | | BE RELOCATED. | | | 2. MAKE THE FOLLOWING CORRECTIONS TO THE TREE | | | DISPOSITION LIST: | | | ? SATISFIED. THERE ARE MULTIPLE TREES AND PALMS THAT | | | ARE MISIDENTIFIED ON THE TREE DISPOSITION LIST. | | | ? PARTIALLY SATISFIED. ONLY TREES PROPOSED TO BE | | | REMOVED WITH A CANOPY DIAMETER OF 20 FEET OR MORE | | | SHOULD HAVE THE MITIGATION SQUARE FOOTAGE CALCULATED | | | BASED ON THE ACTUAL DIAMETER. TREES LESS THAN 20 FEET | | | CANOPY DIAMETER AND PALMS SHOULD SHOW THE CATEGORY | | | MITIGATION DUE. | | | SHOW THE MITIGATION SQUARE FOOTAGE DUE FOR PALMS BY | | | CATEGORY (CATEGORY 3 IS 100 SQ FT, CATEGORY 4 IS 50 SQ | | | FT.) | | | ? SATISFIED. MULTIPLE PALMS PLANTED TOGETHER MUST HAVE | | | EACH SINGLE TRUNK COUNTED TOWARD MITIGATION. EXAMPLE: | | | TRIPLE ADONIDIA WOULD BE 3 X 50 SQ FT. | | | ? SATISFIED. PROVIDE THE TOTAL MITIGATION SQUARE | | | FOOTAGE DUE. | | | PROVIDE THE TOTAL MITIGATION SQUARE FOOTAGE DUE. | | | ? SATISFIED. PROVIDE THE MITIGATION SQUARE FOOTAGE | | | PROVIDED BASED ON THE PLANT LIST. | | | | | | 3. NOT SATISFIED. PROVIDE A DIAGRAM OF THE REQUIRED AND | | | PROVIDED PUBLIC, SEMI-PUBLIC, PRIVATE OPEN AREAS AND | | | URBAN GREENWAYS SYSTEM FOR EACH PARCEL IN THE NMUD | | | ZONING DISTRICT. IDENTIFY THE TYPE OF OPEN SPACE. 10% | | | COMMON PRIVATE OPEN SPACE IS REQUIRED. | | | THE REQUIRED OPEN SPACE NEEDS TO BE QUANTIFIED, | | | IDENTIFIED AS TO THE TYPE, AND ALL REQUIREMENTS NEED TO | | | BE SHOWN FOR THAT OPEN SPACE TYPE. | | | SURFACE PARKING AREAS CANNOT BE COUNTED TOWARD REQUIRED | | | OPEN SPACE. | | | 4/13/22 SHEET A103.0 COULD NOT BE LOCATED IN THE | | | SUBMITTAL. SHEET L102 SHOWS SURFACE PARKING AREA | | | COUNTED AS LANDSCAPE OPEN SPACE. | | | | | | 4. SATISFIED. SHOW THE ROOFTOP TERRACES AND INCLUDE HOW | | | THE REQUIREMENTS OF SECTION 94-210 P. 5. ARE MET, | | | INCLUDING 15% LANDSCAPE REQUIREMENT AND PROVIDE A | | | LANDSCAPE PLAN FOR EACH AREA. | | | | | | 5. SATISFIED. IDENTIFY RELOCATED TREES OR PALMS ON THE | | | PLANT LIST AND COUNT THEM TOWARD THE REQUIRED TREES. | | | | | | 6. SATISFIED. IF ANY ARTIFICIAL TURF AREAS ARE | | | PROPOSED, THEY MUST MEET THE REQUIREMENTS OF SECTION | | | 94-451, INCLUDING ALL AREAS THAT ARE ALLOWED BY CODE | | | MUST NOT BE VISIBLE FROM A ROAD OR STREET. | | | | | | 7. PARTIALLY SATISFIED. BUFFER TREES AND HEDGES MUST BE | | | PROVIDED ALONG ALL BUFFERS. THERE IS A LARGE GAP IN THE | | | TREES ADJACENT TO THE WEST OF THE SURFACE PARKING LOT. | | | THE WEST PROPERTY LINE ADJACENT TO THE FEC RAILROAD | | | RIGHT OF WAY REQUIRES AT LEAST A 5 FOOT BUFFER STRIP | | | PER SECTION 94-209 2. F. 1. E. | | | | | | THE BUFFER ON THE SOUTH SIDE OF THE SURFACE PARKING LOT | | | DOES NOT MEET THE REQUIRED WIDTH. | | | | | | 8. PARTIALLY SATISFIED. PROVIDE CALCULATIONS FOR | | | REQUIRED STREET TREES AT MAXIMUM SPACING EVERY 30 FEET | | | OR PORTION THEREOF AND SHOW THE NUMBER PROVIDED FOR | | | EACH STREETSCAPE LENGTH. SHOW THE REQUIRED PLANTING | | | STRIP. | | | | | | 4/13/22 EACH BLOCK STREET SEGMENT MUST BE LISTED WITH | | | THE TOTAL LENGTH OF THE ADJACENT PROPERTY LINE AND THE | | | REQUIRED AND PROVIDED STREET TREES SHOWN. CANNOT | | | COMBINE SEGMENTS. THE NUMBER IN SOME SEGMENTS DOES NOT | | | MEET CODE. THE OVERALL INTENT IS TO PROVIDE MAXIMUM | | | TREE CANOPY COVERAGE FOR ALL SEGMENTS. | | | | | | 9. SATISFIED. CORRECT THE CODE REQUIREMENTS CHART ON | | | SHEET L1.01TO UPDATE THE SHADE AND FLOWERING TREE | | | REQUIREMENTS OF SECTION 94-442 C. 2. B. TO CURRENT | | | CODE. | | | | | | | | | 10. PARTIALLY SATISFIED. CORRECT THE CODE REQUIREMENTS | | | CHART ON SHEET L1.01TO UPDATE THE SHADE AND FLOWERING | | | TREE REQUIREMENTS OF SECTION 94-443 C. 3. TO CURRENT | | | CODE. THE TREE PER 100 SQ FT REQUIREMENT WAS REMOVED. | | | 4/13/22 THERE ARE 4 TERMINAL ISLANDS REQUIRED FOR THE | | | SURFACE PARKING AREA, CORRECT ON CHART. | | | | | | 11. SATISFIED. AUSTRALIAN TREE FERN DOES NOT MEET THE | | | DEFINITION OF TREE. | | | | | | 12. PARTIALLY SATISFIED. SHOW ALL EXISTING AND PROPOSED | | | WATER AND SEWER AND DRAINAGE LINES ON THE LANDSCAPE | | | PLAN. SHOW LOCATIONS OF BACKFLOWS AND ADJUST LOCATIONS | | | OF UTILITY LINES TO RESOLVE CONFLICTS WITH EXISTING AND | | | PROPOSED TREES AND LANDSCAPING. | | | | | | FDC CONNECTIONS SHOULD BE MOVED TO THE BUILDING AND NOT | | | BE IN THE STREETSCAPE. | | | EXFILTRATION TRENCHES CANNOT BE LOCATED IN THE | | | STREETSCAPE AS THEY WILL RESTRICT THE ROOT SPACE | | | AVAILABLE FOR THE STREET TREES. | | | | | | 13. SATISFIED. PLANT LIST NEEDS TO BE MODIFIED TO | | | SEPARATE THE REQUIRED OPEN SPACE PLANT LISTS. | | | | | | | | | 14. SATISFIED. PROVIDE THE 50 REQUIRED FLORIDA FRIENDLY | | | POINTS BASED ON THE FINAL PLANT LIST PER SECTION | | | 94-443(G). AFTER MAKING THE FOLLOWING CORRECTIONS: | | | ? 2 INDICATE WHERE THE AREAS ARE DESIGNATED. | | | ? 3A AND 3C ARE NOT SUPPORTED BY THE PLANT LIST. | | | ? 5B AND 5D ADD UP TO MORE THAN 100%, MUST REDUCE ONE | | | CATEGORY | | | ? 6B IS NOT SUPPORTED BY THE PLAN SUBMITTED | | | | | | | | | 15. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L. | | | PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT | | | MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT | | | TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE | | | LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH | | | FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH | | | FLORIDA LANDSCAPES. PROVIDE THE ACTUAL PERCENTAGE BASED | | | ON THE PLANT LIST. | | | | | | | | | 16. PARTIALLY SATISFIED. ALL SURFACE PARKING MUST MEET | | | THE REQUIREMENTS OF SECTION 94-443(C)(3) A. INCLUDING | | | TERMINAL LANDSCAPE ISLANDS, INTERIOR ISLANDS AND SHADE | | | TREES. | | | MINIMUM BUFFER WIDTH IS NOT MET. | | | 17. NOT SATISFIED. PROVIDE AN EXHIBIT SHOWING THE | | | PARKING AREA SURFACE CALCULATIONS, PARKING SPACE AREAS | | | AND LANDSCAPE AREAS PROVIDED TO DEMONSTRATE COMPLIANCE | | | WITH SECTIONS 94-443 (C)(3) AND (4). PROVIDE THE | | | CALCULATIONS IN THE LANDSCAPE REQUIREMENT CHART. REFER | | | TO FIGURE XIV-1. SHOW THE ACTUAL PROVIDED LANDSCAPE | | | SQUARE FOOTAGE. | | | SEE THE REFERENCED FIGURE TO PROVIDE THE EXHIBIT AND | | | CORRECT CALCULATIONS. | | | | | | 18. SATISFIED. PROVIDE SCREENING HEDGES AND SHOW | | | LOCATIONS FOR ALL GROUND MOUNTED VALVES AND EQUIPMENT | | | AND ADD A NOTE THAT ALL EQUIPMENT WILL BE SCREENED. | | | | | | 19. NOT SATISFIED. PORTIONS OF THE RIGHT OF WAY ON | | | BROADWAY AND 24TH STREET ARE FDOT RIGHT OF WAY AND ARE | | | SUBJECT TO REVIEW AND PERMITTING BY FDOT. PROVIDE | | | PRELIMINARY REVIEW OF ANY STREETSCAPE PROPOSED WITHIN | | | THE FDOT RIGHT OF WAY. | | | | | | 4/13/22 THIS COMMENT WAS NOT ADDRESSED IN THE RESPONSES | | | AS DISCUSSED AT THE PPRC MEETING. | | | | | | ADDITIONAL COMMENTS 4/13/22: | | | 20. STREET TREES MUST MEET THE MINIMUM CODE REQUIREMENT | | | OF 20 FEET ALONG MAIN ROADS, BUT ALL MUST BE OF | | | SUFFICIENT HEIGHT TO PROVIDE SAFE SIGHTLINES AND | | | TRAFFIC CLEARANCE FOR PEDESTRIANS AND VEHICLES. | | | | | | 21. STAFF PREFERS THAT THE GUMBO LIMBO STREET TREES BE | | | CHANGED TO GREEN BUTTONWOOD DUE TO ROOT ISSUES IN | | | CONFINED AREAS. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE | | | STREET TREES AND RIGHT OF WAY LANDSCAPING AND | | | IRRIGATION APPROVED WITH THIS PETITION. | | | 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF | | | WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A | | | SEPARATE MAINTENANCE AGREEMENT WITH THE CITY. | | | | | | | | | | | | PROJECT: NORTHWOOD ANCHOR SITE ROW ABANDONMENT | | | Z21100023 | | | NO COMMENTS AT THIS TIME. | | | | | | | | | PROJECT: NORTHWOOD ANCHOR SITE VARIANCES Z21080018 | | | NO COMMENTS AT THIS TIME. | | | | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
11-17-2021 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
11-17-2021 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
11-17-2021 |
Time |
16:52 |
Sent To |
|
|
| Notes |
| 2021-11-17 16:52:54 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: NORTHWOOD ANCHOR SITE DSI Z21080015 | | | NOVEMBER 17, 2021 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | | | | 1. SECTION 94-448 (D)(3) REQUIRES NATIVE TREES AND | | | PALMS IN GOOD CONDITION TO BE PRESERVED ON SITE OR | | | RELOCATED. ANSI A 300 (PART 5) STANDARDS SPECIFY | | | EXAMPLES OF SUITABILITY RATINGS OF GOOD, MODERATE, OR | | | POOR FOR RELOCATION. PROVIDE AN ARBORISTS REPORT RATING | | | THE CONDITION AND RELOCATION POTENTIAL FOR THE NATIVE | | | TREES AND PALMS. THERE ARE LIVE OAKS, SABAL PALMS, AND | | | ROYAL PALMS THAT ARE INDICATED TO BE REMOVED. NON | | | NATIVE TREES AND PALMS ARE NOT REQUIRED TO BE | | | RELOCATED. | | | 2. MAKE THE FOLLOWING CORRECTIONS TO THE TREE | | | DISPOSITION LIST: | | | ? THERE ARE MULTIPLE TREES AND PALMS THAT ARE | | | MISIDENTIFIED ON THE TREE DISPOSITION LIST. | | | ? ONLY TREES PROPOSED TO BE REMOVED WITH A CANOPY | | | DIAMETER OF 20 FEET OR MORE SHOULD HAVE THE MITIGATION | | | SQUARE FOOTAGE CALCULATED BASED ON THE ACTUAL DIAMETER. | | | TREES LESS THAN 20 FEET CANOPY DIAMETER AND PALMS | | | SHOULD SHOW THE CATEGORY MITIGATION DUE. | | | ? MULTIPLE PALMS PLANTED TOGETHER MUST HAVE EACH SINGLE | | | TRUNK COUNTED TOWARD MITIGATION. EXAMPLE: TRIPLE | | | ADONIDIA WOULD BE 3 X 50 SQ FT. | | | ? PROVIDE THE TOTAL MITIGATION SQUARE FOOTAGE DUE. | | | ? PROVIDE THE MITIGATION SQUARE FOOTAGE PROVIDED BASED | | | ON THE PLANT LIST. | | | | | | 3. PROVIDE A DIAGRAM OF THE REQUIRED AND PROVIDED | | | PUBLIC, SEMI-PUBLIC, PRIVATE OPEN AREAS AND URBAN | | | GREENWAYS SYSTEM FOR EACH PARCEL IN THE NMUD ZONING | | | DISTRICT. IDENTIFY THE TYPE OF OPEN SPACE. 10% COMMON | | | PRIVATE OPEN SPACE IS REQUIRED. | | | THE REQUIRED OPEN SPACE NEEDS TO BE QUANTIFIED, | | | IDENTIFIED AS TO THE TYPE, AND ALL REQUIREMENTS NEED TO | | | BE SHOWN FOR THAT OPEN SPACE TYPE. | | | SURFACE PARKING AREAS CANNOT BE COUNTED TOWARD REQUIRED | | | OPEN SPACE. | | | | | | 4. SHOW THE ROOFTOP TERRACES AND INCLUDE HOW THE | | | REQUIREMENTS OF SECTION 94-210 P. 5. ARE MET, INCLUDING | | | 15% LANDSCAPE REQUIREMENT AND PROVIDE A LANDSCAPE PLAN | | | FOR EACH AREA. | | | | | | 5. IDENTIFY RELOCATED TREES OR PALMS ON THE PLANT LIST | | | AND COUNT THEM TOWARD THE REQUIRED TREES. | | | | | | 6. IF ANY ARTIFICIAL TURF AREAS ARE PROPOSED, THEY MUST | | | MEET THE REQUIREMENTS OF SECTION 94-451, INCLUDING ALL | | | AREAS THAT ARE ALLOWED BY CODE MUST NOT BE VISIBLE FROM | | | A ROAD OR STREET. | | | | | | | | | | | | 7. BUFFER TREES AND HEDGES MUST BE PROVIDED ALONG ALL | | | BUFFERS. THERE IS A LARGE GAP IN THE TREES ADJACENT TO | | | THE WEST OF THE SURFACE PARKING LOT. THE WEST PROPERTY | | | LINE ADJACENT TO THE FEC RAILROAD RIGHT OF WAY REQUIRES | | | AT LEAST A 5 FOOT BUFFER STRIP PER SECTION 94-209 2. F. | | | 1. E. | | | | | | 8. PROVIDE CALCULATIONS FOR REQUIRED STREET TREES AT | | | MAXIMUM SPACING EVERY 30 FEET OR PORTION THEREOF AND | | | SHOW THE NUMBER PROVIDED FOR EACH STREETSCAPE LENGTH. | | | SHOW THE REQUIRED PLANTING STRIP. | | | | | | 9. CORRECT THE CODE REQUIREMENTS CHART ON SHEET L1.01TO | | | UPDATE THE SHADE AND FLOWERING TREE REQUIREMENTS OF | | | SECTION 94-442 C. 2. B. TO CURRENT CODE. | | | | | | | | | 10. CORRECT THE CODE REQUIREMENTS CHART ON SHEET | | | L1.01TO UPDATE THE SHADE AND FLOWERING TREE | | | REQUIREMENTS OF SECTION 94-443 C. 3. TO CURRENT CODE. | | | THE TREE PER 100 SQ FT REQUIREMENT WAS REMOVED. | | | | | | 11. AUSTRALIAN TREE FERN DOES NOT MEET THE DEFINITION | | | OF TREE. | | | | | | 12. SHOW ALL EXISTING AND PROPOSED WATER AND SEWER AND | | | DRAINAGE LINES ON THE LANDSCAPE PLAN. SHOW LOCATIONS OF | | | BACKFLOWS AND ADJUST LOCATIONS OF UTILITY LINES TO | | | RESOLVE CONFLICTS WITH EXISTING AND PROPOSED TREES AND | | | LANDSCAPING. | | | | | | 13. PLANT LIST NEEDS TO BE MODIFIED TO SEPARATE THE | | | REQUIRED OPEN SPACE PLANT LISTS. | | | | | | | | | 14. PROVIDE THE 50 REQUIRED FLORIDA FRIENDLY POINTS | | | BASED ON THE FINAL PLANT LIST PER SECTION 94-443(G). | | | AFTER MAKING THE FOLLOWING CORRECTIONS: | | | ? 2 INDICATE WHERE THE AREAS ARE DESIGNATED. | | | ? 3A AND 3C ARE NOT SUPPORTED BY THE PLANT LIST. | | | ? 5B AND 5D ADD UP TO MORE THAN 100%, MUST REDUCE ONE | | | CATEGORY | | | ? 6B IS NOT SUPPORTED BY THE PLAN SUBMITTED | | | | | | | | | 15. SHOW COMPLIANCE WITH SECTION 94-445 L. PLANT | | | SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL | | | ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT | | | SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF | | | SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA | | | WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA | | | LANDSCAPES. PROVIDE THE ACTUAL PERCENTAGE BASED ON THE | | | PLANT LIST. | | | | | | | | | 16. ALL SURFACE PARKING MUST MEET THE REQUIREMENTS OF | | | SECTION 94-443(C)(3) A. INCLUDING TERMINAL LANDSCAPE | | | ISLANDS, INTERIOR ISLANDS AND SHADE TREES. | | | 17. PROVIDE AN EXHIBIT SHOWING THE PARKING AREA SURFACE | | | CALCULATIONS, PARKING SPACE AREAS AND LANDSCAPE AREAS | | | PROVIDED TO DEMONSTRATE COMPLIANCE WITH SECTIONS 94-443 | | | (C)(3) AND (4). PROVIDE THE CALCULATIONS IN THE | | | LANDSCAPE REQUIREMENT CHART. REFER TO FIGURE XIV-1. | | | SHOW THE ACTUAL PROVIDED LANDSCAPE SQUARE FOOTAGE. | | | | | | 18. PROVIDE SCREENING HEDGES AND SHOW LOCATIONS FOR ALL | | | GROUND MOUNTED VALVES AND EQUIPMENT AND ADD A NOTE THAT | | | ALL EQUIPMENT WILL BE SCREENED. | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE | | | STREET TREES AND RIGHT OF WAY LANDSCAPING AND | | | IRRIGATION APPROVED WITH THIS PETITION. | | | 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF | | | WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A | | | SEPARATE MAINTENANCE AGREEMENT WITH THE CITY. | | | | | | | | | | | | PROJECT: NORTHWOOD ANCHOR SITE ROW ABANDONMENT | | | Z21100023 | | | NO COMMENTS AT THIS TIME. | | | | | | | | | PROJECT: NORTHWOOD ANCHOR SITE VARIANCES Z21080018 | | | NO COMMENTS AT THIS TIME. | | | | | | |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
4 |
Status |
P |
Date |
10-13-2022 |
|
|
Cont ID |
|
| Sent By |
mtechnow |
Date |
10-13-2022 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
mtechnow |
Date |
10-13-2022 |
Time |
16:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
3 |
Status |
F |
Date |
08-31-2022 |
|
|
Cont ID |
|
| Sent By |
mtechnow |
Date |
08-31-2022 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
mtechnow |
Date |
10-13-2022 |
Time |
16:10 |
Sent To |
|
|
| Notes |
| 2022-08-31 15:39:00 | | | | -ON 24TH ST. EXTEND THE PROPOSED SANITARY SYSTEM TO THE | | | WITHIN THE LIMITS OF THE PROPOSED DEVELOPMENT (THE | | | SPRUCE AKA THE PROPER). | | | -EXTEND THE FORCE MAIN ON BROADWAY TO THE CONNECTION | | | POINT ON 26TH ST. AND TO UPSIZE THE PROPOSED FROM 14? | | | TO 20?. THE CITY EXPECTS TO CONTRIBUTE TOWARDS THIS | | | WORK. | | | -EXTEND THE SANITARY SEWER ON 23RD STREET WESTWARD 100 | | | LINEAR FEET TOWARD PINEWOOD AVE. | | | -IN THE ALLEY NORTH OF NORTHWOOD RD., REMOVE THE | | | SANITARY SEWER FROM UNDER BUILDING OVERHANG AND INSTALL | | | A TERMINAL MANHOLE. | | | -DRAINAGE SYSTEMS ON 23RD STREET BETWEEN BROADWAY AVE | | | AND PINEWOOD AVE AND ON BROADWAY AVE SOUTH OF NORTHWOOD | | | ROAD ARE TO BE MAINTAINED BY THE DEVELOPER. | | | | | | CONTACT MIKE TECHNOW [email protected] WITH ANY | | | QUESTIONS |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
2 |
Status |
F |
Date |
06-27-2022 |
|
|
Cont ID |
|
| Sent By |
mtechnow |
Date |
06-27-2022 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
mtechnow |
Date |
06-27-2022 |
Time |
14:05 |
Sent To |
|
|
| Notes |
| 2022-06-27 14:06:54 | -SHOW PINEWOOD ROW AS PRIVATE AND THE PROPOSED GRAVITY | | | SEWER POINT OF CONNECTION ON 24TH ST. | | | -CALL FOR THE GRAVITY MAIN ON 23RD ST TO BE | | | BACK-PITCHED AND REVERSE FLOW DIRECTION INTO THE | | | EXISTING SYSTEM. | | | -THERE IS NO NEED TO EXTEND THE GRAVITY MAIN ON | | | BROADWAY/CANNOT CONNECT INTO ALLEY OFF BROADWAY. | | | -REMOVE BACKFLOWS FROM THE ROW. | | | -NO 3? SERVICES. UPSIZE OR DOWNSIZE. | | | -THE EXISTING FPL DUCT BANK NEEDS TO BE RELOCATED TO | | | PROVIDE SPACING FOR PROPOSED UTILITIES WITHIN THE ROAD | | | ROW. PROPOSED UTILITIES SHOULD NOT BE RUNNING UNDER THE | | | CURB. | | | -THE CITY IS EVALUATING REQUIRED UPSIZING FOR PROPOSED | | | UTILITIES AND WILL NEED TO LOOK AT FLOWS FOR PIPE | | | SIZING/LIFT STATION. | | | -SHOW ALL EXISTING UTILITIES. | | | | | | | | | CONTACT MIKE TECHNOW [email protected] 561-494-1047 |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
1 |
Status |
F |
Date |
04-13-2022 |
|
|
Cont ID |
|
| Sent By |
mtechnow |
Date |
04-13-2022 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
mtechnow |
Date |
04-13-2022 |
Time |
15:15 |
Sent To |
|
|
| Notes |
| 2022-04-13 15:15:38 | -CORRECT PIPE DIMENSIONS ON PINEWOOD. THERE IS AN | | | EXISTING 8? WM. | | | -UPSIZE THE 6? WM ON 25TH ST. (SMALL STRETCH OF PIPE) | | | -THE EXISTING BUSINESSES ON 23RD ST ARE SENDING FLOW TO | | | THE SANITARY SYSTEM. THE ONLY WAY THE SANITARY SYSTEM | | | CAN BE PRIVATE IS IF FLOW FROM THESE PROPERTIES IS | | | DIVERTED. | | | -WILL NEED TO UPSIZE THE SANITARY SYSTEM DOWNSTREAM DUE | | | TO ADDITIONAL IMPACTS ON THE SYSTEM. THE EXISTING | | | SYSTEM HAS THE GRAVITY SEWER BEHIND THE PROPERTIES ON | | | 25TH, THE PROPOSED IMPROVEMENTS SHOULD BE WITHIN THE | | | 25TH ST ROW. | | | -WILL NEED TO SEE ALL THE EXISTING DRY UTILITIES TO | | | FINALIZE THE PROPOSED CITY OWNED UTILITIES. | | | -SHOW THE EXISTING 14? CAS FM ON PINEWOOD AND PROVIDE A | | | PLAN TO ALLOW ACCESS FOR O&M OR PROPOSE THE MAIN BE | | | RELOCATED. IT CANNOT HAVE A BUILDING ON TOP OF IT. | | | -IS THE WATER MAIN PRIVATE AND ARE YOU PROPOSING A | | | MASTER METER? | | | |
|
|
| Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
| Rev No |
4 |
Status |
P |
Date |
09-26-2022 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
09-26-2022 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
| Rev No |
3 |
Status |
F |
Date |
07-29-2022 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
07-29-2022 |
Time |
08:26 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-07-29 08:26:38 | PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING: | | | | | | -SEE IF CAN ADJUST NORTHWEST PROPOSED SEWER LATERAL | | | SLIGHTLY TO THE EAST TO ELIMINATE EXTRA ROOT BARRIER AT | | | TREE TRUNK. | | | -AT BOTTOM OF L1.00 THERE IS A LEADER LINE WITH NO | | | LABEL. ADD LABEL AND VERIFY OBJECT DOES NOT CONFLICT | | | WITH PROPOSED METERED WATER SERVICE THERE. | | | -IN PRIOR REVISIONS OF CIVIL PLANS THERE WAS A SEPARATE | | | 8 INCH FIRELINE WITH DCDA FOR THE NORTHWEST BUILDING, | | | BUT CURRENT REVISION DOES NOT SHOW IT ANYMORE. PLEASE | | | PROVIDE MORE INFORMATION ON WHY IT IS NOT THERE | | | ANYMORE. | | | -METERS 2 INCHES AND SMALLER ARE INSTALLED UNDERGROUND | | | IN A METER BOX. CAN UPDATE CIVIL PLANS AT ENGINEERING | | | DEVELOPMENT SUBMITTAL. | | | -AT ENGINEERING DEVELOPMENT SUBMITTAL: PROVIDE PROFILES | | | FOR FIRELINES; UPDATE VALVE AND REDUCER ON C3.04 SO NOT | | | IN CROSSWALK AND PROPERLY LABELED. | | | -LANDSCAPE PLAN SHOWS PLANTS OVER NORTHEAST FPL VAULT. | | | -L2.00 SHOWS AT LEAST A COUPLE PROPOSED BIKE RACKS ON | | | TOP OF FPL VAULTS. RECOMMEND SHOWING FPL VAULTS IN | | | BACKGROUND OF L2.00. | | | | | | RESPECTFULLY, | | | MARK HURLEY | | | [email protected] |
|
|
| Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
| Rev No |
2 |
Status |
F |
Date |
07-27-2022 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
07-27-2022 |
Time |
07:40 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-07-27 07:39:00 | CIVIL PLANS DID NOT APPEAR TO BE UPDATED REVISION. | | | PLEASE SUBMIT MOST UPDATED REVISION OF CIVIL PLANS WITH | | | ANY CHANGES THAT WERE NOTED IN RESPONSE LETTER, SO CAN | | | PROPERLY REVIEW. |
|
|
| Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
5 |
Status |
F |
Date |
10-05-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
10-05-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
10-05-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-10-05 15:44:46 | 1- PLEASE PROVIDE CONTAINER SIZE/TYPE FOR THE SOLID | | | WASTE. | | | 2- PLEASE PROVIDE HEIGHT CLEARANCE OVER AT THE LOADING | | | ZONE, WHERE THE SOLID WASTE CONTAINER(S) GET SERVICED | | | AND THE BULK WASTE GET PICKED UP. | | | | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] | | | 561-822-2045 |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
4 |
Status |
F |
Date |
07-29-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
07-29-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
07-29-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-07-29 10:03:21 | 1- PLEASE PROVIDE CONTAINER SIZE/TYPE FOR THE SOLID | | | WASTE. | | | 2- PLEASE PROVIDE HEIGHT CLEARANCE OVER AT THE LOADING | | | ZONE, WHERE THE SOLID WASTE CONTAINER(S) GET SERVICED | | | AND THE BULK WASTE GET PICKED UP. | | | 3- IN CASE OF PROPOSING ADDITION OF ANY NEW CAN(S) IN | | | THE CITY`S RIGHT-OF-WAY , THE LOCATION AND QUANTITY OF | | | THE CAN(S) SHALL BE REVIEWED AND APPROVED BY PUBLIC | | | WORKS DEPARTMENT AND THE CAN(S) SHALL BE TYPE, SIZE AND | | | COLOR APPROVED BY PUBLIC WORKS DEPARTMENT. THE BUILDING | | | MAINTENANCE IS RESPONSIBLE TO MAINTAIN AND SERVICE THE | | | CAN(S). | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] | | | 561-822-2045 |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
3 |
Status |
F |
Date |
06-29-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
06-29-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
06-29-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-06-29 13:56:13 | | | | 1- PLEASE PROVIDE CONTAINER SIZE/TYPE FOR THE SOLID | | | WASTE | | | 2- PLEASE PROVIDE HEIGHT CLEARANCE OVER AT THE LOADING | | | ZONE, WHERE THE SOLID WASTE CONTAINER(S) GET SERVICED | | | AND THE BULK WASTE GET PICKED UP. | | | 3- IN CASE OF PROPOSING ADDITION OF ANY NEW CAN(S) IN | | | THE CITY`S RIGHT-OF-WAY , THE LOCATION AND QUANTITY OF | | | THE CAN(S) SHALL BE REVIEWED AND APPROVED BY PUBLIC | | | WORKS DEPARTMENT AND THE CAN(S) SHALL BE TYPE, SIZE AND | | | COLOR APPROVED BY PUBLIC WORKS DEPARTMENT. THE BUILDING | | | MAINTENANCE IS RESPONSIBLE TO MAINTAIN AND SERVICE THE | | | CAN(S). | | | 4- ALL THE PARKING STALL PAINTING SHALL COMPLY WITH THE | | | CITY`S MUNICIPAL CODE SECTION 94-485 AND FLORIDA | | | STATUES [553.5041 F.S.]. | | | 5- ALL STRIPING AND SIGNAGE SHALL MEET THE M.U.T.C.D. | | | LATEST EDITION. | | | 6- ALL PAVEMENT MARKING AND SIGNING DAMAGED DURING | | | CONSTRUCTION SHALL BE RESTORED. | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] | | | 561-822-2045 |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
2 |
Status |
F |
Date |
04-14-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
04-14-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
04-14-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-04-14 11:16:49 | | | | PLEASE PROVIDE THE FOLLOWINGS: | | | 1- DUMPSTER ENCLOSURE DETAIL. DETAILS FOR SANITATION | | | SERVICE (I.E. SOLID WASTE CONTAINER(S) TYPE, COLLECTION | | | LOCATION, ETC.). FOR A FREESTANDING SITE DUMPSTER | | | ENCLOSURE, THE ENCLOSURE SHALL COMPLY WITH THE LATEST | | | REVISION OF CITY OF WEST PALM BEACH GENERAL | | | CONSTRUCTION-GARBAGE ENCLOSURE STANDARD, GC-7. (LINK TO | | | THE LATEST REVISION OF THE GC-7 DOCUMENT: HTTPS://WWW.W | | | PB.ORG/HOME/SHOWPUBLISHEDDOCUMENT/3690/6376290604221000 | | | 00) | | | 2- OWNERS AND/OR OCCUPANTS OF PROPERTY THAT REQUIRE | | | GREASE HAULING SERVICES SHALL ENSURE THAT THEIR GREASE | | | TANKS OR CONTAINERS REMAIN CLEAN, AND ARE ENCLOSED AND | | | NOT IN PUBLIC VIEW. | | | | | | 3- IN CASE OF PROPOSING ADDITION OF ANY NEW CAN(S) IN | | | THE CITY`S RIGHT-OF-WAY , THE LOCATION AND QUANTITY OF | | | THE CAN(S) SHALL BE REVIEWED AND APPROVED BY PUBLIC | | | WORKS DEPARTMENT AND THE CAN(S) SHALL BE TYPE, SIZE AND | | | COLOR APPROVED BY PUBLIC WORKS DEPARTMENT. THE BUILDING | | | MAINTENANCE IS RESPONSIBLE TO MAINTAIN AND SERVICE THE | | | CAN(S). | | | | | | 4- PLEASE ALSO RELOCATE THE LOCATION/ORIENTATION OF THE | | | ENCLOSURES TO ALLOW OUR SANITATION FRONT LOAD | | | COLLECTION VEHICLE SAFELY ACCESS AND SERVICE THE | | | CONTAINER(S) WHILE MINIMIZING/AVOIDING ANY BACK UP | | | MOVEMENTS AND SHORT RADIUS TURNS. | | | | | | 5- BULK ITEMS WILL BE COLLECTED BY A CLAM TRUCK, FOR | | | WHICH THE ENCLOSURE SHOULD NOT HAVE A STOP BAR AND | | | GATES SHOULD BE COMPLETELY OPEN TO MITIGATE ANY CHANCES | | | OF DAMAGE WHILE BEING SERVICED. | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] | | | 561-822-2045 |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
F |
Date |
11-18-2021 |
|
|
Cont ID |
|
| Sent By |
|
Date |
11-18-2021 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
11-18-2021 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-11-18 06:58:52 | | | | PLEASE PROVIDE THE FOLLOWINGS: | | | 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID | | | WASTE VOLUME PRODUCED ALONG WITH THE SIZE, TYPE AND | | | QUANTITY OF THE CONTAINER (I.E. DUMPSTER/COMPACTOR) | | | THAT WILL BE UTILIZED THAT WILL BE UTILIZED FOR THE | | | SANITATION SERVICE. | | | 2- DETAILS FOR SANITATION SERVICE (I.E. SOLID WASTE | | | CONTAINER(S) TYPE, COLLECTION LOCATION, ETC.). | | | 3- AUTOTURN EXHIBIT (DYNAMIC ENVELOPE AND THE VEHICLE?S | | | WHEEL PATH) FOR THE SANITATION SERVICE, FRONT LOADER | | | TRUCK WITH THE FOLLOWING SPECS: | | | - DUAL AXLES | | | - TRUCK LENGTH: 35 FT | | | - TRUCK WIDTH: 11 FT | | | - TURNING RADIUS: | | | - SAE TURNING RADIUS: 32.5 FT | | | - CURB-TO-CURB DIAMETER: 74 FT | | | - WALL-TO-WALL DIAMETER: 86.3 FT | | | 4- DESIGNATED LOCATION FOR THE BULK ITEM PICK UP AND | | | RECYCLING CONTAINERS | | | | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] | | | 561-822-2045 | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
4 |
Status |
P |
Date |
10-11-2022 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
10-04-2022 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
10-11-2022 |
Time |
09:06 |
Sent To |
|
|
| Notes |
| 2022-10-04 10:55:49 | STORM #4 WAS GIVEN A PASS WITH SITE PLAN CONDITIONS | | | LISTED AT THE BOTTOM OF THESE NOTES. | | | | | | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE | | | 9/22/22 SUBMITTAL. PREVIOUSLY SATISFIED COMMENTS ARE | | | NOT INCLUDED. | | | | | | 1. [PARTIALLY SATISFIED] LABEL ALL THE STREETS ON ALL | | | OF THE SHEETS. FOR EXAMPLE, SHEET C1.01 ONLY LABELS | | | PINEWOOD AVE. NONE OF THE EAST-WEST STREETS ARE | | | LABELED. NEW COMMENT - ON SHEET C3.01 LABEL PINEWOOD | | | AVE NORTH AND SOUTH OF 25TH ST. | | | | | | 13. [SATISFIED] REVISE THE PARKING SPACE STRIPING | | | DETAIL TO MATCH CITY CODE. | | | | | | 16. [SATISFIED ??? SEE NEW COMMENTS ON THE 9/22/2022 | | | SUBMITTAL] RCP PIPE (MINIMUM 15 INCHES IN DIAMETER) TO | | | BE INSTALLED WITHIN THE RIGHT OF WAY. NEW COMMENT: NOT | | | ALL PIPES ARE LABELED. PROPOSED STORM PIPES ON 25TH ST | | | AT BROADWAY, ON BROADWAY AVE AT 24TH ST., BROADWAY AT | | | NORTHWOOD RD LABELED AS 18" HDPE. | | | | | | NEW COMMENTS (5/27/2022 SUBMITTAL): | | | | | | 17. [SATISFIED] INDICATE HOW THE EXISTING CATCH BASIN | | | ON THE SOUTH SIDE OF 23RD ST EAST OF PINEWOOD DRIVE | | | WILL CONNECT TO THE MS4. | | | | | | 18. [NOT SATISFIED ??? TO BE PROVIDED AND REVIEWED WITH | | | ENGINEERING PERMIT SUBMITTAL] PROVIDE PRE- AND | | | POST-DEVELOPMENT HGL CALCULATIONS FOR THE DRAINAGE | | | SYSTEM ON BROADWAY AND 23RD STREET WITH THE ENGINEERING | | | PERMIT SUBMITTAL. | | | | | | 19. [NOT SATISFIED] REVIEW DESIGN PLANS IN SFWMD | | | PERMITS FOR 24TH ST AND 25TH ST AND OTHER PROJECTS IN | | | THE VICINITY FOR STORM PIPE CONNECTIVITY. THE INLET ON | | | THE SOUTH SIDE OF 24TH ST EAST OF BROADWAY MAY BE | | | CONNECTED TO A MANHOLE SOUTH OF THE STRUCTURE INSTEAD | | | OF THE MANHOLE ON BROADWAY AVE. ADDITIONAL COMMENTS: | | | THE AS-BUILT PICTURE PROVIDED IN THE 7/15/22 RESPONSE | | | LETTER SHOWS THE DRAINAGE SYSTEM BEFORE CORNER BULBOUTS | | | WERE CONSTRUCTED ON 24TH STREET ABOUT 12 YEARS AGO. THE | | | AFOREMENTIONED MH IS VISIBLE IN THE APRIL 2011 AND | | | APRIL 2015 GOOGLE MAP STREETVIEWS. | | | | | | 20. [TO BE SATISFIED AT ENGINEERING PERMIT SUBMITTAL] | | | ADDITIONAL GRADES WILL BE NEEDED FOR THE ENGINEERING | | | PERMIT SUBMITTAL. NOTE PROPOSED SPOT GRADES WERE | | | REMOVED ON THE 9/22/22 SET. | | | | | | 21. [NOT SATISFIED ??? PROPOSED SPOT GRADES WERE | | | REMOVED FROM THE PGD PLANS BUT THE CROSS SECTIONS | | | APPEAR TO SHOW SIDEWALK AND PARKING SPACE CROSS SLOPES | | | OF 4% OR STEEPER, WHICH EXCEEDS THE 2% MAX SHOWN ON THE | | | CROSS SECTIONS.] THE FINISHED FLOOR ELEVATIONS AND SPOT | | | GRADES ON THE PGD PLANS PROVIDED WHERE THE CROSS | | | SECTION SYMBOLS ARE WILL RESULT IN CROSS SLOPES STEEPER | | | THAN THE MAX. 2% SHOWN ON THE CROSS SECTIONS FOR THE | | | PARKING AREA AND ALLOWED FOR THE SIDEWALK AREA. | | | | | | 22. [PARTIALLY SATISFIED] WILL THERE BE PEDESTRIAN | | | ACCESS TO THE SOUTH SIDE OF 23RD STREET AT THE PINEWOOD | | | AND BROADWAY INTERSECTIONS? SHOW CROSS WALKS AND CURB | | | RAMPS. ADDITIONAL COMMENTS - SHOW CURB RAMP AND | | | PEDESTRIAN CROSSWALK SIGN ON THE SOUTH SIDE OF 23RD ST | | | EAST OF PINEWOOD AVE SHOW NEW CURB RAMP ON SOUTH SIDE | | | OF 23RD STREET AT THE BROADWAY AVE. CROSSWALK. MAKE | | | SURE THE CRUB RAMP DOES NOT FALL WITHIN THE EXISTING | | | DRIVEWAY APRON OR FLARES. | | | | | | 23. [SATISFIED ??? WILL BE CONFIRMED WITH THE | | | ENGINEERING PERMIT SUBMITTAL] ALL CURB RAMPS WILL NEED | | | TO BE BROUGHT UP TO CURRENT ADA STANDARDS IF THE | | | PAVEMENT ADJACENT TO THE CURB RAMP IS DISTURBED OR | | | OVERLAID. | | | | | | 24. [SATISFIED] ADA MATS MAY BE NEEDED WHERE THE | | | SIDEWALKS MEET DRIVEWAYS FOR THE GARAGES OR ALLEYS. | | | | | | 25. SHEET C3.05: | | | A. [SATISFIED] BUILDING A (NORTHWEST) SERVICE - | | | 1. CONFIRM PROPOSED 3" WATER SERVICE WILL CROSS AN 8" | | | PVC SANITARY SEWER MAIN. | | | 2. CONFIRM TAP IS TO A 24" WM. | | | | | | B. [SATISFIED ??? NOTE SHEET C2.02 CALLS OUT STORM PIPE | | | AS HDPE] BUILDING A (NORTHEAST) SERVICE - SHOW THE | | | EXFILTRATION TRENCH. | | | | | | C. [SATISFIED] BUILDING A (SOUTHWEST) SERVICE - CONFIRM | | | THE WATER SERVICE WILL CROSS 15" RCP STORM AND 8" PVC | | | SEWER. | | | | | | D. [PARTIALLY SATISFIED ??? SHOW 14??? FM. CONFIRM 8??? | | | SSWR] BUILDING B SERVICE - SHOW PROPOSED STORM PIPE | | | BETWEEN EXISTING INLETS. | | | | | | E. [NOT SATISFIED ??? SHEET C2.02 LABELS PIPE AS 18 | | | INCH HDPE] BUILDING A (SOUTHEAST) SERVICE - | | | 2. CONFIRM RCP STORM VS. HDPE STORM. | | | | | | 26. [SATISFIED] SHOW BREAKS IN THE EXFILTRATION TRENCH | | | IF WATER OR SEWER SERVICE LINES WILL CROSS IN THE | | | ENVELOPE OF THE EXFILTRATION TRENCH. | | | | | | 27. [NOT SATISFIED ??? WILL PROVIDE WITH THE | | | ENGINEERING PERMIT SUBMITTAL] PROVIDE DETAILS OF THE | | | CONTROL STRUCTURES WITH THE ENGINEERING PERMIT | | | SUBMITTAL. | | | | | | 28. [SATISFIED] SECTION B-B - LEFT SIDE OF SECTION IS | | | LABELED AS 18.4 FEET LANDSCAPING. WILL THERE BE A | | | CONTINUOUS SIDEWALK ON THE WEST SIDE OF THE STREET? | | | | | | 29. [SATISFIED] SECTION E-E - CONFIRM 2.5 FEET | | | DIMENSION FOR THE TYPE 'F' CURB. SUM OF DIMENSIONS | | | ACROSS RIGHT OF WAY IS LESS THAN 75 FEET. | | | | | | 30. [SATISFIED] SECTION H-H - CONFIRM 2.5 FEET | | | DIMENSION FOR THE TYPE 'F' CURB. SUM OF DIMENSIONS | | | ACROSS RIGHT OF WAY IS MORE THAN 55 FEET. | | | | | | NEW COMMENTS (9/22/2022 SUBMITTAL) | | | | | | 31. MOVE THE CONSTRUCTION ENTRANCE OUT OF THE 25TH ST. | | | R/W ON THE EROSION CONTROL PLAN. | | | | | | 32. CALLOUT AND NUMBER THE NEW DRAINAGE STRUCTURE ON | | | THE SW CORNER OF 25TH ST AND PINEWOOD AVE AND THE PIPE | | | CONNECTION TO STRUCTURE EX-1. | | | | | | 33. NUMBER THE MANHOLE STORM STRUCTURE LOCATED BETWEEN | | | ST-15 AND ST-14 AND NUMBER THE EXISTING DRAINAGE | | | STRUCTURE EAST OF THIS MANHOLE AND LABEL THE STORM PIPE | | | BETWEEN THESE UNNUMBERED STRUCTURES ON THE WEST SIDE OF | | | BROADWAY AVE NORTH OF 24TH ST. | | | | | | 34. NUMBER THE PROPOSED DRAINAGE STRUCTURE TO THE | | | SOUTHWEST OF MH EX-3 AND LABEL THE STORM PIPE BETWEEN | | | THESE TWO STRUCTURES NEAR THE INTERSECTION OF 24TH ST | | | AND BROADWAY AVE. | | | | | | 35. NUMBER THE PROPOSED DRAINAGE STRUCTURE TO THE | | | NORTHWEST OF MANHOLE EX-4 AND LABEL THE STORM PIPE | | | BETWEEN THESE STRUCTURES IN THE INTERSECTION OF | | | NORTHWOOD ROAD AND BROADWAY AVE. | | | | | | 36. NUMBER THE EXISTING MANHOLE TO THE EAST OF MANHOLE | | | EX-4 ON NORTHWOOD ROAD. | | | | | | 37. THE PRELIMINARY STORMWATER MANAGEMENT CALCULATIONS | | | WERE REVIEWED TO SEE THE ASSUME WIDTH OF 5 FEET FOR THE | | | PROPOSED EXFILTRATION TRENCH. THE EXFILTRATION TRENCHES | | | ALONG BROADWAY AVE BETWEEN ST-34 AND ST-35 AND BETWEEN | | | ST-36 AND ST-37 ONLY MEASURE 3 FEET IN WIDTH. | | | | | | 38. STRUCTURE EX-3 ON BROADWAY AT 24TH ST MAY NEED TO | | | BE REPLACED WITH A LARGER STRUCTURE IN ORDER TO CONNECT | | | NEW STORM PIPES TO THE STRUCTURE. | | | | | | 39. STORM PIPE SOUTH OF STRUCTURE ST-14 LABELED (TWICE) | | | AS 14 LF 18??? HDPE 1 LF EXFILTRATION TRENCH. THIS | | | COMMENT CAN BE ADDRESSED WITH THE ENGINEERING PERMIT | | | SUBMITTAL. | | | | | | 40. ON THE PGD PLANS, SHOW EXISTING DRIVEWAY FOR 940 | | | NORTHWOOD ROAD AND THE DRIVEWAYS ON THE SOUTH SIDE OF | | | 23RD STREET SO THAT THE PROPOSED BULBOUT FOR THE | | | ONE-WAY PORTION OF THE STREET WILL NOT CONFLICT WITH | | | THE DRIVEWAYS. | | | | | | 41. PROVIDE A DETAIL FOR A VALLEY GUTTER INLET AND HOW | | | THE DROP CURB WILL TRANSITION TO THE VALLEY GUTTER TOP. | | | | | | ******************************************************* | | | ***************************** | | | ******************************************************* | | | ***************************** | | | CONDITIONS FOR SITE PLAN APPROVAL (THESE CAN BE | | | ADDRESSED WITH THE ENGINEERING PERMIT SUBMITTAL): | | | | | | - LABEL ALL THE STREETS ON ALL OF THE PLANS (COMMENT | | | #1) | | | | | | - PROVIDE PRE- AND POST-DEVELOPMENT HGL CALCULATIONS | | | FOR THE DRAINAGE SYSTEM FROM BROADWAY AVE/26TH ST OR | | | BROADWAY AVE/25TH ST TO PINEWOOD AVE/23RD ST. (COMMENT | | | #18) | | | | | | - REVISE STORM PIPE CONNECTION BETWEEN THE INLET ON THE | | | SOUTH SIDE OF 24TH ST EAST OF BROADWAY AVE TO THE | | | MANHOLE IN THE INTERSECTION OF BROADWAY AVE AND 24TH | | | ST. (COMMENT #19) | | | | | | - PROVIDE PROPOSED SPOT GRADES ON THE PGD PLANS. | | | SIDEWALK AND PARKING SPACE CROSS SLOPES ARE NOT TO | | | EXCEED 2%. (COMMENTS #20 AND #21) | | | | | | - SHOW EXISTING DRIVEWAYS ON THE SOUTH SIDE OF 23RD | | | STREET. SHOW CURB RAMPS THAT DO NOT INTERFERE WITH THE | | | DRIVEWAY APRONS OR DRIVEWAY FLARES. SHOW THAT THE | | | PROPOSED BULBOUT EAST OF THE BROADWAY AVE EXTENSION | | | WILL NOT CONFLICT WITH THE DRIVEWAYS.(COMMENTS #22 AND | | | #40) | | | | | | - ALL CURB RAMPS WHERE THE ADJACENT PAVEMENT IS | | | DISTURBED OR OVERLAID WILL NEED TO BE BROUGHT UP TO | | | CURRENT ADA STANDARDS. (COMMENT #23) | | | | | | - UTILITY PROFILES (SHEET C3.05) TO SHOW AND LABEL ALL | | | EXISTING (THAT WILL REMAIN) AND PROPOSED UTILITIES THAT | | | THE WATER SERVICES WILL BE CROSSING. COORDINATE PIPE | | | CALLOUTS WITH THE PGD AND UTILITY PLANS. (COMMENT #25) | | | | | | - PROVIDE DETAILS OF THE STORMWATER CONTROL STRUCTURES. | | | (COMMENT #27) | | | | | | - MOVE THE CONSTRUCTION ENTRANCE OUT OF THE R/W. | | | (COMMENTS #31) | | | | | | - CALLOUT AND NUMBER ALL OF THE EXISTING AND PROPOSED | | | DRAINAGE STRUCTURES AND STORM PIPES WITHIN THE | | | CONSTRUCTION LIMITS. (COMMENTS #32 TO #36) | | | | | | - LABEL THE WIDTH OF THE EXFILTRATION TRENCHES ON THE | | | PDG PLANS (COMMENTS #37 AND #39) | | | | | | - CONFIRM EXISTING DRAINAGE STRUCTURES DO NOT NEED TO | | | BE REPLACED FOR THE PROPOSED MODIFICATIONS TO THE | | | STRUCTURES (COMMENT #38) | | | | | | - PROVIDE A DETAIL FOR A VALLEY GUTTER INLET AND HOW | | | THE DROP CURB WILL TRANSITION TO THE VALLEY GUTTER TOP. | | | (COMMENT #41) | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | [email protected] | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
3 |
Status |
F |
Date |
07-01-2022 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
07-01-2022 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
07-01-2022 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2022-07-01 14:13:24 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE | | | 5/27/2022 SUBMITTAL. | | | | | | 1. [PARTIALLY SATISFIED] LABEL ALL THE STREETS ON ALL | | | OF THE SHEETS. FOR EXAMPLE, SHEET C1.01 ONLY LABELS | | | PINEWOOD AVE. NONE OF THE EAST-WEST STREETS ARE | | | LABELED. NEW COMMENT ? ON SHEET C3.01 LABEL PINEWOOD | | | AVE NORTH AND SOUTH OF 25TH ST. | | | | | | 2. [SATISFIED] COMPLETE THE PAVING, GRADING AND | | | DRAINAGE NOTES ON THE PGD PLAN SHEETS. SOME OF THE | | | NOTES DO NOT AGREE WITH THE VERTICAL DATUM LABEL AT THE | | | BOTTOM OF THE SHEETS. | | | | | | 3. [SATISFIED - EXFILTRATION TRENCH ON THE EAST SIDE OF | | | BROADWAY AVE SHOULD BE SET BACK FROM THE RIGHT OF WAY | | | TO ENSURE THE TRENCH DOES NOT ENCROACH INTO THE RIGHT | | | OF WAY DURING CONSTRUCTION.] EXFILTRATION TRENCH FOR | | | TREATING RUNOFF FROM ONSITE AREAS SHALL NOT BE LOCATED | | | WITHIN THE RIGHT OF WAY. | | | | | | 4. [SATISFIED] ON SHEET C2.03 THERE IS A NEW DRAINAGE | | | STRUCTURE ON THE EAST SIDE OF PINEWOOD AVE ABOUT 40 | | | FEET NORTH OF THE CENTERLINE OF NORTHWOOD ROAD. THIS | | | INLET IS SHOWN NEXT TO AN EXISTING INLET THAT IS BEING | | | CONVERTED TO A VALLEY GUTTER INLET. IS THE NEW INLET | | | NEEDED? | | | | | | 5. [SATISFIED] WHAT WILL BE THE MAXIMUM CROSS SLOPE OF | | | THE ON-STREET PARKING SPACES? | | | | | | 6. [SATISFIED - REVIEW SECTION F-F] LABEL THE PARKING | | | AREAS ON THE CROSS SECTIONS. | | | | | | 7. [SATISFIED] ADVISE IF THE WEST DROP CURB ON PINEWOOD | | | AVE WILL BE PARALLEL TO THE WEST RIGHT OF WAY. THE 9.0 | | | FT DIMENSION ON SECTION B-B DOES NOT APPEAR TO REACH | | | THE 2 FEET DROP CURB. | | | | | | 8. [SATISFIED] SIDEWALK CROSS SLOPES SHALL NOT EXCEED 2 | | | PERCENT. | | | | | | 9. [SATISFIED] THE DIMENSIONS FOR THE PARKING AREAS ON | | | SECTION D-D AND SECTION E-E (FOR BROADWAY AVE) APPEAR | | | TO INCLUDE THE TYPE 'D' CURB. | | | | | | 10. [SATISFIED] EXTEND SECTION F-F TO THE PARKING LOT | | | ON THE WEST SIDE OF PINEWOOD AVE. DIMENSION THE | | | SIDEWALKS, CURB AND GUTTER, TRAVEL LANES AND PARKING | | | AREA. | | | | | | 11. [SATISFIED] DIMENSION MINIMUM BUILDING SETBACKS ON | | | THE CROSS SECTIONS. | | | | | | 12. [SATISFIED - SHOW CROSS SECTION SYMBOL ON SHEET | | | C2.04] PROVIDE CROSS SECTION OF BROADWAY AVE SOUTH OF | | | NORTHWOOD ROAD. EXTEND SECTION FROM FACE OF BUILDING TO | | | FACE OF BUILDING. DIMENSION SIDEWALKS, CURB AND GUTTER, | | | PARKING AREAS, TRAVEL LANES, SETBACKS FROM R/W, ETC. | | | | | | 13. [NOT SATISFIED - INCLUDE PARKING STRIPING DETAIL | | | WITH THE ENGINEERING PERMIT SUBMITTAL] REVISE THE | | | PARKING SPACE STRIPING DETAIL TO MATCH CITY CODE. | | | | | | 14. [SATISFIED] THE CITY DOES NOT ALLOW THE USE OF | | | BLEEDERS WITH EXFILTRATION TRENCHES. | | | | | | 15. [SATISFIED - CAN HATCHING OR BOLD BORDER BE ADDED | | | ON SHEET C1.00 SHOWING THE ROWS TO BE ABANDONED?] LABEL | | | RIGHT OF WAYS PROPOSED TO BE ABANDONED ON THE PLAN | | | SHEETS. | | | | | | 16. [NOT SATISFIED] RCP PIPE (MINIMUM 15 INCHES IN | | | DIAMETER) TO BE INSTALLED WITHIN THE RIGHT OF WAY. NEW | | | COMMENT ? NOT ALL PIPES ARE LABELED. PROPOSED STORM | | | PIPES ON 25TH ST AT BROADWAY, ON BROADWAY AVE AT 24TH | | | ST., BROADWAY AT NORTHWOOD RD LABELED AS 18" HDPE. | | | | | | NEW COMMENTS: | | | | | | 17. INDICATE HOW THE EXISTING CATCH BASIN ON THE SOUTH | | | SIDE OF 23RD ST EAST OF PINEWOOD DRIVE WILL CONNECT TO | | | THE MS4. | | | | | | 18. PROVIDE PRE- AND POST-DEVELOPMENT HGL CALCULATIONS | | | FOR THE DRAINAGE SYSTEM ON BROADWAY AND 23RD STREET | | | WITH THE ENGINEERING PERMIT SUBMITTAL. | | | | | | 19. REVIEW DESIGN PLANS IN SFWMD PERMITS FOR 24TH ST | | | AND 25TH ST AND OTHER PROJECTS IN THE VICINITY FOR | | | STORM PIPE CONNECTIVITY. THE INLET ON THE SOUTH SIDE OF | | | 24TH ST EAST OF BROADWAY MAY BE CONNECTED TO A MANHOLE | | | SOUTH OF THE STRUCTURE INSTEAD OF THE MANHOLE ON | | | BROADWAY AVE. | | | | | | 20. ADDITIONAL GRADES WILL BE NEEDED FOR THE | | | ENGINEERING PERMIT SUBMITTAL. | | | | | | 21. THE FINISHED FLOOR ELEVATIONS AND SPOT GRADES ON | | | THE PGD PLANS PROVIDED WHERE THE CROSS SECTION SYMBOLS | | | ARE WILL RESULT IN CROSS SLOPES STEEPER THAN THE MAX. | | | 2% SHOWN ON THE CROSS SECTIONS FOR THE PARKING AREA AND | | | ALLOWED FOR THE SIDEWALK AREA. | | | | | | 22. WILL THERE BE PEDESTRIAN ACCESS TO THE SOUTH SIDE | | | OF 23RD STREET AT THE PINEWOOD AND BROADWAY | | | INTERSECTIONS? SHOW CROSS WALKS AND CURB RAMPS. | | | | | | 23. ALL CURB RAMPS WILL NEED TO BE BROUGHT UP TO | | | CURRENT ADA STANDARDS IF THE PAVEMENT ADJACENT TO THE | | | CURB RAMP IS DISTURBED OR OVERLAID. | | | | | | 24. ADA MATS MAY BE NEEDED WHERE THE SIDEWALKS MEET | | | DRIVEWAYS FOR THE GARAGES OR ALLEYS. | | | | | | 25. SHEET C3.05: | | | A. BUILDING A (NORTHWEST) SERVICE - | | | 1. CONFIRM PROPOSED 3" WATER SERVICE WILL CROSS AN 8" | | | PVC SANITARY SEWER MAIN. | | | 2. CONFIRM TAP IS TO A 24" WM. | | | | | | B. BUILDING A (NORTHEAST) SERVICE - SHOW THE | | | EXFILTRATION TRENCH. | | | | | | C. BUILDING A (SOUTHWEST) SERVICE - CONFIRM THE WATER | | | SERVICE WILL CROSS 15" RCP STORM AND 8" PVC SEWER. | | | | | | D. BUILDING B SERVICE - SHOW PROPOSED STORM PIPE | | | BETWEEN EXISTING INLETS. | | | | | | E. BUILDING A (SOUTHWEST) SERVICE - | | | 1. SHOULD BE LABELED SOUTHEAST? | | | 2. CONFIRM RCP STORM VS. HDPE STORM. | | | | | | 26. SHOW BREAKS IN THE EXFILTRATION TRENCH IF WATER OR | | | SEWER SERVICE LINES WILL CROSS IN THE ENVELOPE OF THE | | | EXFILTRATION TRENCH. | | | | | | 27. PROVIDE DETAILS OF THE CONTROL STRUCTURES WITH THE | | | ENGINEERING PERMIT SUBMITTAL. | | | | | | 28. SECTION B-B - LEFT SIDE OF SECTION IS LABELED AS | | | 18.4 FEET LANDSCAPING. WILL THERE BE A CONTINUOUS | | | SIDEWALK ON THE WEST SIDE OF THE STREET? | | | | | | 29. SECTION E-E - CONFIRM 2.5 FEET DIMENSION FOR THE | | | TYPE 'F' CURB. SUM OF DIMENSIONS ACROSS RIGHT OF WAY IS | | | LESS THAN 75 FEET. | | | | | | 30. SECTION H-H - CONFIRM 2.5 FEET DIMENSION FOR THE | | | TYPE 'F' CURB. SUM OF DIMENSIONS ACROSS RIGHT OF WAY IS | | | MORE THAN 55 FEET. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | [email protected] | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
F |
Date |
04-14-2022 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
04-14-2022 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
04-14-2022 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2022-04-14 12:02:10 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | | | | 1. LABEL ALL THE STREETS ON ALL OF THE SHEETS. FOR | | | EXAMPLE, SHEET C1.01 ONLY LABELS PINEWOOD AVE. NONE OF | | | THE EAST-WEST STREETS ARE LABELED. | | | | | | 2. COMPLETE THE PAVING, GRADING AND DRAINAGE NOTES ON | | | THE PGD PLAN SHEETS. SOME OF THE NOTES DO NOT AGREE | | | WITH THE VERTICAL DATUM LABEL AT THE BOTTOM OF THE | | | SHEETS. | | | | | | 3. EXFILTRATION TRENCH FOR TREATING RUNOFF FROM ONSITE | | | AREAS SHALL NOT BE LOCATED WITHIN THE RIGHT OF WAY. | | | | | | 4. ON SHEET C2.03 THERE IS A NEW DRAINAGE STRUCTURE ON | | | THE EAST SIDE OF PINEWOOD AVE ABOUT 40 FEET NORTH OF | | | THE CENTERLINE OF NORTHWOOD ROAD. THIS INLET IS SHOWN | | | NEXT TO AN EXISTING INLET THAT IS BEING CONVERTED TO A | | | VALLEY GUTTER INLET. IS THE NEW INLET NEEDED? | | | | | | 5. WHAT WILL BE THE MAXIMUM CROSS SLOPE OF THE | | | ON-STREET PARKING SPACES? | | | | | | 6. LABEL THE PARKING AREAS ON THE CROSS SECTIONS. | | | | | | 7. ADVISE IF THE WEST DROP CURB ON PINEWOOD AVE WILL BE | | | PARALLEL TO THE WEST RIGHT OF WAY. THE 9.0 FT DIMENSION | | | ON SECTION B-B DOES NOT APPEAR TO REACH THE 2 FEET DROP | | | CURB. | | | | | | 8. SIDEWALK CROSS SLOPES SHALL NOT EXCEED 2 PERCENT. | | | | | | 9. THE DIMENSIONS FOR THE PARKING AREAS ON SECTION D-D | | | AND SECTION E-E (FOR BROADWAY AVE) APPEAR TO INCLUDE | | | THE TYPE 'D' CURB. | | | | | | 10. EXTEND SECTION F-F TO THE PARKING LOT ON THE WEST | | | SIDE OF PINEWOOD AVE. DIMENSION THE SIDEWALKS, CURB AND | | | GUTTER, TRAVEL LANES AND PARKING AREA. | | | | | | 11. DIMENSION MINIMUM BUILDING SETBACKS ON THE CROSS | | | SECTIONS. | | | | | | 12. PROVIDE CROSS SECTION OF BROADWAY AVE SOUTH OF | | | NORTHWOOD ROAD. EXTEND SECTION FROM FACE OF BUILDING TO | | | FACE OF BUILDING. DIMENSION SIDEWALKS, CURB AND GUTTER, | | | PARKING AREAS, TRAVEL LANES, SETBACKS FROM R/W, ETC. | | | | | | 13. REVISE THE PARKING SPACE STRIPING DETAIL TO MATCH | | | CITY CODE. | | | | | | 14. THE CITY DOES NOT ALLOW THE USE OF BLEEDERS WITH | | | EXFILTRATION TRENCHES. | | | | | | 15. LABEL RIGHT OF WAYS PROPOSED TO BE ABANDONED ON THE | | | PLAN SHEETS. | | | | | | 16. RCP PIPE (MINIMUM 15 INCHES IN DIAMETER) TO BE | | | INSTALLED WITHIN THE RIGHT OF WAY. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP | | | CRITERIA. STORMWATER CALCULATIONS WILL BE REVIEWED WITH | | | THE ENGINEERING PERMIT SUBMITTAL. | | | | | | 2. PROVIDE COPY OF SFWMD ERP PERMIT BEFORE START OF | | | CONSTRUCTION, IF REQUIRED. | | | | | | 3. PROVIDE AN EROSION CONTROL PLAN WITH DETAILS. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | [email protected] | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
11-18-2021 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
11-18-2021 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
11-18-2021 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2021-11-18 13:40:31 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | 1. THE CITY?S OFFICIAL VERTICAL DATUM PER CITY CODE IS | | | NGVD1929. THE CITY IS ALLOWING SURVEYS AND PLANS TO USE | | | NAVD1988 PROVIDED THE CONVERSION EQUATION BETWEEN | | | NAVD1988 AND NGVD1929 IS ALSO PROVIDED. LIST THE | | | CONVERSION EQUATION TO NGVD1929 ON THE SURVEY AND ON | | | THE ENGINEERING PLANS. | | | | | | 2. LABEL THE STREET NAMES ON THE CIVIL PLAN SHEETS. | | | | | | 3. CONFIRM MATERIAL AND LAYOUT OF EXISTING STORMWATER | | | SYSTEM ON 25TH ST. | | | | | | 4. BROADWAY AVE NORTH OF 24TH STREET AND 24TH STREET | | | EAST OF BROADWAY ARE MAINTAINED BY FDOT. | | | | | | 5. MINIMUM 15? RCP TO BE INSTALLED WITHIN CITY R/W. | | | | | | 6. CONFIRM EXISTING DRAINAGE STRUCTURES ARE LARGE | | | ENOUGH TO ACCEPT NEW STORM PIPE CONNECTIONS. | | | | | | 7. PROVIDE CROSS SECTIONS FROM CENTERLINE OF ROAD TO | | | FACE OF BUILDING FOR EACH SIDE AND INTERIOR OF | | | DEVELOPMENT. | | | | | | | | | 8. SHOW MILL AND PAVEMENT OVERLAY LIMITS ON THE PGD | | | PLAN SHEETS. | | | | | | 9. PROVIDE SUFFICIENT OVERHEAD CLEARANCE TO MAINTAIN | | | UTILITIES WITHIN THE RIGHT OF WAY INCLUDING THE MAKING | | | OF REPAIRS OR REPLACING PIPE AND/OR STRUCTURES WITH | | | HEAVY EQUIPMENT. | | | | | | 10. ACCESS EASEMENT FOR THE SIDEWALK ON 23RD ST MAY BE | | | REQUIRED. | | | | | | 11. SHOW ADA MATS FOR SIDEWALK RAMPS. | | | | | | 12. EXFILTRATION TRENCHES NEXT TO BUILDINGS MAY MAKE | | | REPLACEMENT OF THE SYSTEM IN THE FUTURE PROBLEMATIC. | | | SUGGEST MOVING THE EXFILTRATION TRENCHES AWAY FROM THE | | | BUILDINGS. | | | | | | 13. IDENTIFY STORMWATER CONTROL STRUCTURES. | | | | | | 14. THE CITY DOES NOT ALLOW THE USE OF BLEEDERS WITH | | | EXFILTRATION TRENCHES. | | | | | | 15. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP | | | CRITERIA. | | | | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. PROVIDE COPY OF SFWMD ERP PERMIT BEFORE START OF | | | CONSTRUCTION. | | | | | | 2. PROVIDE A COPY OF THE DRAINAGE CALCULATIONS WITH THE | | | ENGINEERING PERMIT APPLICATION. | | | | | | 3. ACCESS EASEMENT FOR THE SIDEWALK ON 23RD ST MAY BE | | | REQUIRED. | | | | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | 561-351-0510 (M) | | | [email protected] | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
3 |
Status |
P |
Date |
10-14-2022 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
10-14-2022 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-10-14 09:33:40 | PASSED WITH CONDITION THAT PREVIOUS COMMENTS CONCERNING | | | REVISIONS TO FORCE MAIN, GRAVITY SEWER, ETC. THAT WAS | | | DISCUSSED IN MEETING WITH DEVELOPER/ENGINEER WILL BE | | | ADDRESSED IN ENGINEERING DEVELOPMENT PERMIT SUBMITTAL. |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
2 |
Status |
F |
Date |
04-11-2022 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
04-11-2022 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-04-11 11:02:36 | 1. NO RESPONSE TO SURVEY COMMENTS FROM 11/17/2021. | | | 2. HEIGHT OF BUILDING C OVER ALLEY ALSO NEEDS TO BE 25 | | | FEET AS OVER PINEWOOD. |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
11-17-2021 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
11-17-2021 |
Time |
08:34 |
Rev Time |
|
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2021-11-17 09:33:12 | 1. PROPERTY WILL REQUIRE A RE-PLAT. | | | 2. UTILITIES IS LOOKING INTO ABANDONMENT/RELOCATION OF | | | SOME OF ITS FACILITIES. | | | 3. ADD CONVERSION TO NGVD-29 ON SURVEY AND CIVIL PLANS. | | | 4. AS BUILDING WILL BE SPANNING THE ENTIRE WIDTH OF THE | | | RIGHT-OF-WAY(S), WILL THERE BE ANY SUPPORTS WITHIN THE | | | R/W? | | | 5. NO METERS OR BACKFLOWS ALLOWED IN SIDEWALKS. NEED | | | BLOWUP WITH DIMENSIONS FOR THOSE AREAS. | | | 6. RELOCATE STORM MANHOLE FROM CURBING IN ROUNDABOUT. | | | 7. AERIAL ENCROACHMENT AGREEMENT WILL BE REQUIRED FOR | | | SPANNED RIGHT-OF-WAYS ALONG WITH MAINTENANCE AGREEMENTS | | | FOR IMPROVEMENTS IN R/W. | | | 8. NEED FDOT APPROVAL/ACCEPTANCE OF IMPROVEMENTS ALONG | | | BROADWAY. | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
5 |
Status |
P |
Date |
10-19-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
10-19-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
10-19-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-10-19 17:17:01 | APPROVED WITH THE FOLLOWING CONDITIONS: | | | | | | 1) PROVIDE A CLEAN, DEDICATED TRANSPORTATION SITE PLAN | | | DEPICTING ALL RELATED ROADWAY AND TRANSPORTATION | | | FEATURES, FULLY DIMENSIONED AND SHOWCASING CURB DETAILS | | | ON THE OPPOSITE SIDE OF THE ROAD FRONTING THE PROPOSED | | | DEVELOPMENT. PLEASE KEEP IN MIND THAT THIS COMMENT WAS | | | PROVIDED AT THE VERY FIRST PPRC REVIEW AND WAS NEVER | | | COMPLETELY FULFILLED | | | 2) PROVIDE A REVISED AUTOTURN ANALYSIS SHOWCASING | | | SERVICE VEHICLES ACCESSING/EXITING THE FACILITY, | | | MANEUVERING AT EACH POSSIBLE LOADING OR SANITATION | | | ZONE(S), WITH BOTH DYNAMIC AND WHEEL PATHS HIGHLIGHTED | | | IN SEPARATE COLORS | | | 3) PROVIDE A LIST OF ON-GOING ITEMS UNDER DISCUSSION OR | | | REVIEW WITH COUNTY AND FDOT. OBTAIN COUNTY AND/OR FDOT | | | APPROVAL PERTAINING THE PORTION OF THE PROPOSED | | | DEVELOPMENT IMPACTING THEIR RIGHT OF WAY | | | 4) INSTALL AND SHOW SHARROW MARKINGS ALONG 23RD ST AND | | | PINEWOOD AVE | | | 5) 25TH ST ROADWAY DESIGN SHOULD ACCOMMODATE THE | | | PLANNED SEPARATED AND ELEVATED BICYCLE LANES FROM | | | AUSTRALIAN TO BROADWAY. PLEASE REFER TO THE CITY | | | BICYCLE MASTERPLAN FOR TYPICAL SECTION(S) AND UPDATE | | | THE SITE PLANS ACCORDINGLY. NOTE: CITY MAY NOT REQUIRE | | | THE DEVELOPER TO IMPLEMENT SUCH FEATURE ALONG SITE | | | FRONTAGE; HOWEVER, ROW MUST BE PRESERVED AND PROVIDED | | | TO ACCOMMODATE ITS FUTURE IMPLEMENTATION | | | 6) THE PROPOSED PINEWOOD AVENUE RE-ALIGNMENT IS NOT | | | CONDUCIVE TO A SAFE VEHICULAR STRAIGHT-THROUGH MOVEMENT | | | ACROSS THE 25TH AND 23RD INTERSECTIONS. SUCH MOVEMENT | | | SHOULD BE EITHER FORBIDDEN OR FACILITATED BY SIGNAGE, | | | STRIPING AND ROADWAY FEATURES SUCH AS FLEXIBLE POLES, | | | MIDDLE RAISED ISLANDS AND CHANNELIZATION. PLEASE REVISE | | | THE SITE PLANS ACCORDINGLY | | | 7) INSTALL AND SHOWCASE STOP BARS AND SIGNS ON EACH | | | GARAGE LEVEL. IT IS RECOMMENDED TO TREAT THE NORTHERN | | | AND SOUTHERN EAST-WEST DRIVE AISLES AS THE MAIN ONES, | | | WHILE THE NORTH-SOUTH AS MINOR | | | 8) DIRECTIONAL ARROW PAVEMENT MARKINGS ARE MISSING. | | | PLEASE INSERT THEM IN THE TRANSPORTATION SITE PLAN | | | THROUGHOUT WERE NEEDED (E.G. RIGHT ARROW FOR THE | | | SOUTHBOUND MOVEMENT, LEFT ARROW FOR THE EASTBOUND | | | MOVEMENT AT THE 23RD AND PINEWOOD INTERSECTION) | | | | | | PAST AND LATEST COMMENTS, FOR REFERENCE PURPOSES | | | | | | TRAFFIC COMMENTS | | | 1) SATISFIED. PROVIDE UPDATED COUNTY TPS LETTER ONCE | | | AVAILABLE | | | 2) SATISFIED. SUBMITTED TRAFFIC STUDY NEEDS REVISION AS | | | THE TRIP GENERATION RATES DO NOT REPRESENT THE LATEST | | | SITE PLAN | | | 3) SATISFIED. SCHEDULE A METHODOLOGY MEETING WITH THE | | | TRANSPORTATION ENGINEERING GROUP. PRIOR TO ANY REVISION | | | OR RESUBMISSION | | | 4) SATISFIED. REVISE THE TRAFFIC STUDY TO ALSO INCLUDE | | | RESIDENTIAL TRIPS IN THE SIGNIFICANCE ANALYSIS. CRCEA | | | EXEMPTION ONLY APPLIES TO COUNTY CONCURRENCY. TEST 2 | | | MAY BE NEEDED | | | 5) SATISFIED. PLEASE ELABORATE ON THE IMPROVEMENTS | | | NEEDED TO ACCOMMODATE FUTURE BACKGROUND TRAFFIC AND | | | THEIR CAPACITY FOR THE PROPOSED PROJECT TRAFFIC | | | 6) SATISFIED. KEEP THE INTERSECTION OF 25TH AND | | | PINEWOOD UNDER EXISTING TWO-WAY STOP CONTROL | | | CONFIGURATION | | | 7) SATISFIED. IMPLEMENT A LEFT-TURN LANE, NOT A TWLT | | | ONE, ON THE EAST AND WEST APPROACH OF THE 25TH AND | | | PINEWOOD INTERSECTION | | | SITE COMMENTS | | | 8) PARTIALLY SATISFIED. PROVIDE A CLEAN SITE PLAN, | | | SHOWCASING ONLY TRANSPORTATION FEATURES (I.E. ROAD, | | | CURB, GUTTER, SIDEWALK, DRIVEWAY, PAVEMENT MARKING, | | | SIGNAGE, PATHWAY, WALKWAY, PEDESTRIAN CROSSING, LOADING | | | ZONE, PICK-UP/DROP-OFF AREA) AND CORRESPONDING | | | DIMENSIONS. SHEET C2.01-C3.04 ARE UNACCEPTABLE, AS THEY | | | ARE OVERCROWDED WITH UNRELATED ITEMS AND MISSING | | | SEVERAL TRANSPORTATION FEATURES. ALSO, DIMENSIONS FOR | | | ALL LISTED TRANSPORTATION FEATURES ARE MISSING. A | | | DEDICATED SITE PLAN IS A CRITICAL ITEM FOR A PROPER | | | TRANSPORTATION REVIEW CONSIDERING THE SIGNIFICANT | | | IMPACT OF THE PROPOSED DEVELOPMENT TO THE EXISTING | | | NETWORK. SEVERAL DIMENSIONS ARE STILL MISSING IN THE | | | LATEST RESUBMISSION (SEPTEMBER 2022) | | | 9) PARTIALLY SATISFIED. ON THE SITE PLAN, PLEASE | | | SHOWCASE BASIC CURB DETAILS (I.E. DRIVEWAY AND PARKING | | | STALLS) ON THE OPPOSITE SIDE OF THE ROADS SURROUNDING | | | THE PROPOSED DEVELOPMENT. PLEASE PROVIDE DOCUMENT NAME | | | AND SHEET NUMBER SHOWCASING SUCH FEATURES. DETAILS | | | MISSING FOR THE FOLLOWING LOCATION: SOUTH SIDE OF 23RD | | | ST, EAST SIDE OF BROADWAY, NORTH SIDE OF 25TH ST. | | | SEVERAL PAVEMENT MARKINGS ARE STILL MISSING IN THE | | | LATEST RESUBMISSION (SEPTEMBER 2022) | | | 10) PARTIALLY SATISFIED. PROVIDE AUTOTURN ANALYSIS FOR | | | GARBAGE TRUCK AND/OR SERVICE VEHICLES DRIVING IN AND | | | OUT OF THE PROPOSED DEVELOPMENT WITH VEHICLE DYNAMIC | | | ENVELOPES CLEARLY DEFINED. ANALYSIS SHOULD BE PROVIDED | | | IN A SEPARATE FILE/DRAWING. PLEASE PROVIDE DOCUMENT | | | NAME AND SHEET NUMBER SHOWCASING THE ANALYSIS. SHEET | | | C4.01 IS INCOMPLETE, GARBAGE VEHICLES SHOULD BE SHOWN | | | TURNING-IN/ENTERING AND TURNING-OUT/EXITING THE | | | PREMISES OF THE PROPOSED DEVELOPMENT. PLEASE COORDINATE | | | WITH SANITATION SERVICES REGARDING TYPICAL FUTURE | | | ROUTE(S) | | | 11) SATISFIED. IDENTIFY AND DESIGNATE TWO OR MORE | | | ACCESSIBLE MICRO-MOBILITY STATION AREAS (MINIMUM 8 X 20 | | | FEET) AND PROVIDE BASIC ELECTRIFICATION READINESS. FOR | | | THE LATTER ITEM, MORE SPECIFICALLY: A CONDUIT (2??? | | | SCHEDULE 40 PVC) TO THE POWER SOURCE WITH AN ELECTRICAL | | | PULL BOX (240V ??? 10,000W CIRCUIT). PLEASE PROVIDE | | | DOCUMENT NAME AND SHEET NUMBER SHOWCASING SUCH FEATURE | | | 12) PARTIALLY SATISFIED. OBTAIN COUNTY AND/OR FDOT | | | APPROVAL PERTAINING THE PORTION OF THE PROPOSED | | | DEVELOPMENT IMPACTING THEIR RIGHT OF WAY. COMMENT WILL | | | BE SATISFIED ONCE APPROVAL DOCUMENTATION IS PROVIDED. | | | IN THE MEANTIME, PROVIDE A LIST OF ON-GOING ITEMS UNDER | | | DISCUSSION OR REVIEW WITH COUNTY AND FDOT | | | 13) SATISFIED. GARAGE RAMP ON 25TH ST NEEDS TO BE | | | RELOCATED. FRA REGULATIONS REQUIRE A MINIMUM DISTANCE | | | OF 60 FEET FROM RAILROAD CROSSING???S GATE ARM | | | 14) PARTIALLY SATISFIED. PROPER TURNAROUND SPACE NEEDS | | | TO BE PROVIDED AT EACH DEAD END WITHIN THE GARAGE. | | | PLEASE PROVIDE DOCUMENT NAME AND SHEET NUMBER. PROVIDE | | | A TURNAROUND SPACE ON THE NORTH-WEST CORNER OF THE | | | GARAGE LEVEL 2 | | | 15) INSTALL AND SHOW SHARROW MARKINGS ALONG 23RD ST | | | 16) INSTALL AND SHOW SHARROW MARKINGS ALONG PINEWOOD | | | AVE | | | 17) 25TH ST ROADWAY DESIGN SHOULD ACCOMMODATE THE | | | PLANNED SEPARATED AND ELEVATED BICYCLE LANES FROM | | | AUSTRALIAN TO BROADWAY. PLEASE REFER TO THE CITY | | | BICYCLE MASTERPLAN FOR TYPICAL SECTION(S) | | | 18) DIRECTIONAL ARROW PAVEMENT MARKINGS ARE MISSING. | | | PLEASE INSERT THEM THROUGHOUT WERE NEEDED (E.G. RIGHT | | | ARROW FOR THE SOUTHBOUND MOVEMENT, LEFT ARROW FOR THE | | | EASTBOUND MOVEMENT AT THE 23RD AND PINEWOOD | | | INTERSECTION) | | | 19) PROVIDE A MINIMUM OF 8-FEET WIDE UN-OBSTRUCTED | | | PEDESTRIAN WALKABLE AREA ALONG EACH OF THE ROADS | | | TRAVERSING OR FRONTING THE PROPOSED DEVELOPMENT. | | | SIDEWALK WIDTH IS INSUFFICIENT ALONG 25TH, OTHER | | | STREETS CANNOT BE VERIFIED AS DIMENSIONS ARE MISSING | | | 20) INSTALL AND SHOWCASE STOP BARS AND SIGNS ON EACH | | | GARAGE LEVEL. IT IS RECOMMENDED TO TREAT THE NORTHERN | | | AND SOUTHERN EAST-WEST DRIVE AISLES AS THE MAIN ONES, | | | WHILE THE NORTH-SOUTH AS MINOR | | | 21) PER CITY CODE 94-111(Q)(2) RAMP WITH SLOPES GREATER | | | THAN 14% MUST PROVIDE A BREAK-OVER TRANSITION | | | 22) THE PROPOSED PINEWOOD AVENUE RE-ALIGNMENT IS NOT | | | CONDUCIVE TO A SAFE VEHICULAR STRAIGHT-THROUGH MOVEMENT | | | ACROSS THE 25TH AND 23RD INTERSECTIONS. SUCH MOVEMENT | | | SHOULD BE EITHER FORBIDDEN OR FACILITATED BY SIGNAGE, | | | STRIPING AND ROADWAY FEATURES SUCH AS FLEXIBLE POLES, | | | MIDDLE RAISED ISLANDS AND CHANNELIZATION. PLEASE REVISE | | | THE SITE PLAN ACCORDINGLY | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
4 |
Status |
F |
Date |
07-28-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
07-28-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-07-28 12:50:15 | NONE OF THE TRANSPORTATION COMMENTS HAVE BEEN ADDRESSED | | | IN THE RESPONSE LETTER. | | | | | | TRAFFIC COMMENTS | | | 1) PARTIALLY SATISFIED. PROVIDE UPDATED COUNTY TPS | | | LETTER ONCE AVAILABLE | | | 2) SATISFIED. SUBMITTED TRAFFIC STUDY NEEDS REVISION AS | | | THE TRIP GENERATION RATES DO NOT REPRESENT THE LATEST | | | SITE PLAN | | | 3) NOT SATISFIED. SCHEDULE A METHODOLOGY MEETING WITH | | | THE TRANSPORTATION ENGINEERING GROUP. PRIOR TO ANY | | | REVISION OR RESUBMISSION | | | 4) NOT SATISFIED. REVISE THE TRAFFIC STUDY TO ALSO | | | INCLUDE RESIDENTIAL TRIPS IN THE SIGNIFICANCE ANALYSIS. | | | CRCEA EXEMPTION ONLY APPLIES TO COUNTY CONCURRENCY. | | | TEST 2 MAY BE NEEDED | | | 5) NOT SATISFIED. PLEASE ELABORATE ON THE IMPROVEMENTS | | | NEEDED TO ACCOMMODATE FUTURE BACKGROUND TRAFFIC AND | | | THEIR CAPACITY FOR THE PROPOSED PROJECT TRAFFIC | | | 6) NOT SATISFIED. KEEP THE INTERSECTION OF 25TH AND | | | PINEWOOD UNDER EXISTING TWO-WAY STOP CONTROL | | | CONFIGURATION | | | 7) NOT SATISFIED. IMPLEMENT A LEFT-TURN LANE, NOT A | | | TWLT ONE, ON THE EAST AND WEST APPROACH OF THE 25TH AND | | | PINEWOOD INTERSECTION | | | | | | SITE COMMENTS | | | 8) NOT SATISFIED. PROVIDE A CLEAN SITE PLAN, SHOWCASING | | | ONLY TRANSPORTATION FEATURES (I.E. ROAD, CURB, GUTTER, | | | SIDEWALK, DRIVEWAY, PAVEMENT MARKING, SIGNAGE, PATHWAY, | | | WALKWAY, PEDESTRIAN CROSSING, LOADING ZONE, | | | PICK-UP/DROP-OFF AREA) AND CORRESPONDING DIMENSIONS. | | | SHEET C2.01-C3.04 ARE UNACCEPTABLE, AS THEY ARE | | | OVERCROWDED WITH UNRELATED ITEMS AND MISSING SEVERAL | | | TRANSPORTATION FEATURES. ALSO, DIMENSIONS FOR ALL | | | LISTED TRANSPORTATION FEATURES ARE MISSING. A DEDICATED | | | SITE PLAN IS A CRITICAL ITEM FOR A PROPER | | | TRANSPORTATION REVIEW CONSIDERING THE SIGNIFICANT | | | IMPACT OF THE PROPOSED DEVELOPMENT TO THE EXISTING | | | NETWORK. | | | 9) NOT SATISFIED. ON THE SITE PLAN, PLEASE SHOWCASE | | | BASIC CURB DETAILS (I.E. DRIVEWAY AND PARKING STALLS) | | | ON THE OPPOSITE SIDE OF THE ROADS SURROUNDING THE | | | PROPOSED DEVELOPMENT. PLEASE PROVIDE DOCUMENT NAME AND | | | SHEET NUMBER SHOWCASING SUCH FEATURES. DETAILS MISSING | | | FOR THE FOLLOWING LOCATION: SOUTH SIDE OF 23RD ST, EAST | | | SIDE OF BROADWAY, NORTH SIDE OF 25TH ST, | | | 10) PARTIALLY SATISFIED. PROVIDE AUTOTURN ANALYSIS FOR | | | GARBAGE TRUCK AND/OR SERVICE VEHICLES DRIVING IN AND | | | OUT OF THE PROPOSED DEVELOPMENT WITH VEHICLE DYNAMIC | | | ENVELOPES CLEARLY DEFINED. ANALYSIS SHOULD BE PROVIDED | | | IN A SEPARATE FILE/DRAWING. PLEASE PROVIDE DOCUMENT | | | NAME AND SHEET NUMBER SHOWCASING THE ANALYSIS. SHEET | | | C4.01 SHOWS VEHICLE DYNAMIC ENCLOSURE ENCROACHMENTS | | | 11) PARTIALLY SATISFIED. IDENTIFY AND DESIGNATE TWO OR | | | MORE ACCESSIBLE MICRO-MOBILITY STATION AREAS (MINIMUM 8 | | | X 20 FEET) AND PROVIDE BASIC ELECTRIFICATION READINESS. | | | FOR THE LATTER ITEM, MORE SPECIFICALLY: A CONDUIT (2? | | | SCHEDULE 40 PVC) TO THE POWER SOURCE WITH AN ELECTRICAL | | | PULL BOX (240V 10,000W CIRCUIT). PLEASE PROVIDE | | | DOCUMENT NAME AND SHEET NUMBER SHOWCASING SUCH FEATURE | | | 12) PARTIALLY SATISFIED. OBTAIN COUNTY AND/OR FDOT | | | APPROVAL PERTAINING THE PORTION OF THE PROPOSED | | | DEVELOPMENT IMPACTING THEIR RIGHT OF WAY. COMMENT WILL | | | BE SATISFIED ONCE APPROVAL DOCUMENTATION IS PROVIDED. | | | IN THE MEANTIME, PROVIDE A LIST OF ON-GOING ITEMS UNDER | | | DISCUSSION OR REVIEW WITH COUNTY AND FDOT | | | 13) SATISFIED. GARAGE RAMP ON 25TH ST NEEDS TO BE | | | RELOCATED. FRA REGULATIONS REQUIRE A MINIMUM DISTANCE | | | OF 60 FEET FROM RAILROAD CROSSING'S GATE ARM | | | 14) PARTIALLY SATISFIED. PROPER TURNAROUND SPACE NEEDS | | | TO BE PROVIDED AT EACH DEAD END WITHIN THE GARAGE. | | | PLEASE PROVIDE DOCUMENT NAME AND SHEET NUMBER. | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
3 |
Status |
F |
Date |
06-22-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
06-22-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
06-22-2022 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-06-22 23:00:45 | TRAFFIC COMMENTS | | | 1) PARTIALLY SATISFIED. PROVIDE UPDATED COUNTY TPS | | | LETTER ONCE AVAILABLE | | | 2) SATISFIED. SUBMITTED TRAFFIC STUDY NEEDS REVISION AS | | | THE TRIP GENERATION RATES DO NOT REPRESENT THE LATEST | | | SITE PLAN | | | 3) NOT SATISFIED. SCHEDULE A METHODOLOGY MEETING WITH | | | THE TRANSPORTATION ENGINEERING GROUP. PRIOR TO ANY | | | REVISION OR RESUBMISSION | | | 4) NOT SATISFIED. REVISE THE TRAFFIC STUDY TO ALSO | | | INCLUDE RESIDENTIAL TRIPS IN THE SIGNIFICANCE ANALYSIS. | | | CRCEA EXEMPTION ONLY APPLIES TO COUNTY CONCURRENCY. | | | TEST 2 MAY BE NEEDED | | | 5) NOT SATISFIED. PLEASE ELABORATE ON THE IMPROVEMENTS | | | NEEDED TO ACCOMMODATE FUTURE BACKGROUND TRAFFIC AND | | | THEIR CAPACITY FOR THE PROPOSED PROJECT TRAFFIC | | | 6) NOT SATISFIED. KEEP THE INTERSECTION OF 25TH AND | | | PINEWOOD UNDER EXISTING TWO-WAY STOP CONTROL | | | CONFIGURATION | | | 7) NOT SATISFIED. IMPLEMENT A LEFT-TURN LANE, NOT A | | | TWLT ONE, ON THE EAST AND WEST APPROACH OF THE 25TH AND | | | PINEWOOD INTERSECTION | | | | | | SITE COMMENTS | | | 8) NOT SATISFIED. PROVIDE A CLEAN SITE PLAN, SHOWCASING | | | ONLY TRANSPORTATION FEATURES (I.E. ROAD, CURB, GUTTER, | | | SIDEWALK, DRIVEWAY, PAVEMENT MARKING, SIGNAGE, PATHWAY, | | | WALKWAY, PEDESTRIAN CROSSING, LOADING ZONE, | | | PICK-UP/DROP-OFF AREA) AND CORRESPONDING DIMENSIONS. | | | SHEET C2.01-C3.04 ARE UNACCEPTABLE, AS THEY ARE | | | OVERCROWDED WITH UNRELATED ITEMS AND MISSING SEVERAL | | | TRANSPORTATION FEATURES. ALSO, DIMENSIONS FOR ALL | | | LISTED TRANSPORTATION FEATURES ARE MISSING. A DEDICATED | | | SITE PLAN IS A CRITICAL ITEM FOR A PROPER | | | TRANSPORTATION REVIEW CONSIDERING THE SIGNIFICANT | | | IMPACT OF THE PROPOSED DEVELOPMENT TO THE EXISTING | | | NETWORK. | | | 9) NOT SATISFIED. ON THE SITE PLAN, PLEASE SHOWCASE | | | BASIC CURB DETAILS (I.E. DRIVEWAY AND PARKING STALLS) | | | ON THE OPPOSITE SIDE OF THE ROADS SURROUNDING THE | | | PROPOSED DEVELOPMENT. PLEASE PROVIDE DOCUMENT NAME AND | | | SHEET NUMBER SHOWCASING SUCH FEATURES. DETAILS MISSING | | | FOR THE FOLLOWING LOCATION: SOUTH SIDE OF 23RD ST, EAST | | | SIDE OF BROADWAY, NORTH SIDE OF 25TH ST, | | | 10) PARTIALLY SATISFIED. PROVIDE AUTOTURN ANALYSIS FOR | | | GARBAGE TRUCK AND/OR SERVICE VEHICLES DRIVING IN AND | | | OUT OF THE PROPOSED DEVELOPMENT WITH VEHICLE DYNAMIC | | | ENVELOPES CLEARLY DEFINED. ANALYSIS SHOULD BE PROVIDED | | | IN A SEPARATE FILE/DRAWING. PLEASE PROVIDE DOCUMENT | | | NAME AND SHEET NUMBER SHOWCASING THE ANALYSIS. SHEET | | | C4.01 SHOWS VEHICLE DYNAMIC ENCLOSURE ENCROACHMENTS | | | 11) PARTIALLY SATISFIED. IDENTIFY AND DESIGNATE TWO OR | | | MORE ACCESSIBLE MICRO-MOBILITY STATION AREAS (MINIMUM 8 | | | X 20 FEET) AND PROVIDE BASIC ELECTRIFICATION READINESS. | | | FOR THE LATTER ITEM, MORE SPECIFICALLY: A CONDUIT (2" | | | SCHEDULE 40 PVC) TO THE POWER SOURCE WITH AN ELECTRICAL | | | PULL BOX (240V - 10,000W CIRCUIT). PLEASE PROVIDE | | | DOCUMENT NAME AND SHEET NUMBER SHOWCASING SUCH FEATURE | | | 12) PARTIALLY SATISFIED. OBTAIN COUNTY AND/OR FDOT | | | APPROVAL PERTAINING THE PORTION OF THE PROPOSED | | | DEVELOPMENT IMPACTING THEIR RIGHT OF WAY. COMMENT WILL | | | BE SATISFIED ONCE APPROVAL DOCUMENTATION IS PROVIDED. | | | IN THE MEANTIME, PROVIDE A LIST OF ON-GOING ITEMS UNDER | | | DISCUSSION OR REVIEW WITH COUNTY AND FDOT | | | 13) SATISFIED. GARAGE RAMP ON 25TH ST NEEDS TO BE | | | RELOCATED. FRA REGULATIONS REQUIRE A MINIMUM DISTANCE | | | OF 60 FEET FROM RAILROAD CROSSING?S GATE ARM | | | 14) PARTIALLY SATISFIED. PROPER TURNAROUND SPACE NEEDS | | | TO BE PROVIDED AT EACH DEAD END WITHIN THE GARAGE. | | | PLEASE PROVIDE DOCUMENT NAME AND SHEET NUMBER. | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
2 |
Status |
F |
Date |
04-14-2022 |
|
|
Cont ID |
|
| Sent By |
|
Date |
04-14-2022 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-04-14 12:22:25 | TRAFFIC COMMENTS | | | 1) PROVIDE COUNTY TPS LETTER | | | 2) SUBMITTED TRAFFIC STUDY NEEDS REVISION AS THE TRIP | | | GENERATION RATES DO NOT REPRESENT THE LATEST SITE PLAN | | | 3) SCHEDULE A METHODOLOGY MEETING WITH THE | | | TRANSPORTATION ENGINEERING GROUP. PRIOR TO ANY REVISION | | | OR RESUBMISSION. | | | | | | SITE COMMENTS | | | 4) PROVIDE A CLEAN SITE PLAN, SHOWCASING ONLY | | | TRANSPORTATION FEATURES (I.E. ROAD, CURB, GUTTER, | | | SIDEWALK, DRIVEWAY, PAVEMENT MARKING, SIGNAGE, PATHWAY, | | | WALKWAY, PEDESTRIAN CROSSING, LOADING ZONE, | | | PICK-UP/DROP-OFF AREA) AND CORRESPONDING DIMENSIONS | | | 5) ON THE SITE PLAN, PLEASE SHOWCASE BASIC CURB DETAILS | | | (I.E. DRIVEWAY AND PARKING STALLS) ON THE OPPOSITE SIDE | | | OF THE ROADS SURROUNDING THE PROPOSED DEVELOPMENT. | | | PLEASE PROVIDE DOCUMENT NAME AND SHEET NUMBER | | | SHOWCASING SUCH FEATURES. | | | 6) PROVIDE AUTOTURN ANALYSIS FOR GARBAGE TRUCK AND/OR | | | SERVICE VEHICLES DRIVING IN AND OUT OF THE PROPOSED | | | DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES CLEARLY | | | DEFINED. ANALYSIS SHOULD BE PROVIDED IN A SEPARATE | | | FILE/DRAWING. PLEASE PROVIDE DOCUMENT NAME AND SHEET | | | NUMBER SHOWCASING THE ANALYSIS. | | | 7) IDENTIFY AND DESIGNATE TWO OR MORE ACCESSIBLE | | | MICRO-MOBILITY STATION AREAS (MINIMUM 8 X 20 FEET) AND | | | PROVIDE BASIC ELECTRIFICATION READINESS. FOR THE LATTER | | | ITEM, MORE SPECIFICALLY: A CONDUIT (2? SCHEDULE 40 PVC) | | | TO THE POWER SOURCE WITH AN ELECTRICAL PULL BOX (240V ? | | | 10,000W CIRCUIT). PLEASE PROVIDE DOCUMENT NAME AND | | | SHEET NUMBER SHOWCASING SUCH FEATURE | | | 8) OBTAIN COUNTY AND/OR FDOT APPROVAL PERTAINING THE | | | PORTION OF THE PROPOSED DEVELOPMENT IMPACTING THEIR | | | RIGHT OF WAY | | | 9) GARAGE RAMP ON 25TH ST NEEDS TO BE RELOCATED. FRA | | | REGULATIONS REQUIRE A MINIMUM DISTANCE OF 60 FEET FROM | | | RAILROAD CROSSING?S GATE ARM | | | 10) PROPER TURNAROUND SPACE NEEDS TO BE PROVIDED AT | | | EACH DEAD END WITHIN THE GARAGE | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
11-18-2021 |
|
|
Cont ID |
|
| Sent By |
|
Date |
11-18-2021 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2021-11-18 12:30:13 | TRAFFIC COMMENTS | | | 1) PROVIDE COUNTY TPS LETTER | | | 2) SUBMITTED TRAFFIC STUDY NEEDS REVISION AS THE TRIP | | | GENERATION RATES DO NOT REPRESENT THE LATEST SITE PLAN | | | 3) SCHEDULE A METHODOLOGY MEETING WITH THE | | | TRANSPORTATION ENGINEERING GROUP. PRIOR TO ANY REVISION | | | OR RESUBMISSION. | | | | | | SITE COMMENTS | | | 4) PROVIDE A CLEAN SITE PLAN, SHOWCASING ONLY | | | TRANSPORTATION FEATURES (I.E. ROAD, CURB, GUTTER, | | | SIDEWALK, DRIVEWAY, PAVEMENT MARKING, SIGNAGE, PATHWAY, | | | WALKWAY, PEDESTRIAN CROSSING, LOADING ZONE, | | | PICK-UP/DROP-OFF AREA) AND CORRESPONDING DIMENSIONS | | | 5) ON THE SITE PLAN, PLEASE SHOWCASE BASIC CURB DETAILS | | | (I.E. DRIVEWAY AND PARKING STALLS) ON THE OPPOSITE SIDE | | | OF THE ROADS SURROUNDING THE PROPOSED DEVELOPMENT. | | | PLEASE PROVIDE DOCUMENT NAME AND SHEET NUMBER | | | SHOWCASING SUCH FEATURES. | | | 6) PROVIDE AUTOTURN ANALYSIS FOR GARBAGE TRUCK AND/OR | | | SERVICE VEHICLES DRIVING IN AND OUT OF THE PROPOSED | | | DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES CLEARLY | | | DEFINED. ANALYSIS SHOULD BE PROVIDED IN A SEPARATE | | | FILE/DRAWING. PLEASE PROVIDE DOCUMENT NAME AND SHEET | | | NUMBER SHOWCASING THE ANALYSIS. | | | 7) IDENTIFY AND DESIGNATE TWO EASILY ACCESSIBLE | | | MICRO-MOBILITY STATION AREAS (MINIMUM 8 X 30 FEET) AND | | | PROVIDE BASIC ELECTRIFICATION READINESS. FOR THE LATTER | | | ITEM, MORE SPECIFICALLY: A CONDUIT (2" SCHEDULE 40 PVC) | | | TO THE POWER SOURCE WITH AN ELECTRICAL PULL BOX (240V | | | CIRCUIT). PLEASE PROVIDE DOCUMENT NAME AND SHEET NUMBER | | | SHOWCASING SUCH FEATURE. | | | 8) PROVIDE PARKING TABLE SHOWCASING THE NUMBER OF | | | REQUIRED AND PROVIDED PARKING SPACES, INCLUSIVE OF ADA | | | AND BICYCLE ONES | | | 9) OBTAIN COUNTY AND/OR FDOT APPROVAL PERTAINING THE | | | PORTION OF THE PROPOSED DEVELOPMENT IMPACTING THEIR | | | RIGHT OF WAY | | | 10) PROPER TURNAROUND SPACE NEEDS TO BE PROVIDED AT | | | EACH DEAD END WITHIN THE GARAGE | | | 11) NONE OF THE PROPOSED LOADING ZONES ARE CURRENTLY | | | FEASIBLE. AS CITY CODE FORBIDS MANEUVERING ON PUBLIC | | | ROW | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
10 |
Status |
F |
Date |
06-13-2023 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
06-13-2023 |
Time |
13:29 |
Rev Time |
1.00 |
| Received By |
eschneid |
Date |
05-08-2023 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2023-06-13 13:25:42 | FAILED | | | | | | REPEAT COMMENT: THE LATEST RESUBMITTED PLANS ARE NOT | | | INTERNALLY CONSISTENT (CIVIL, LANDSCAPE, ARCHITECTURAL) | | | NOR DO THEY MATCH THE PLANS SUBMITTED AS PART OF THE | | | FOUNDATION/SHELL PERMIT FOR BUILDING A (NOR DO THEY | | | APPEAR TO FULLY MATCH BUILDINGS B AND C). STAFF HAS | | | BEEN TOLD THAT THE FOUNDATION SET IS THE TRUE BUILDING | | | LAYOUT. | | | | | | ALL PLANS MUST MATCH WHAT IS SHOWN WHEN THE COMMENTS ON | | | FOUNDATION PERMIT 22110628 ARE ADDRESSED AND MEET THE | | | NMUD REGULATIONS OR THE APPROVED WAIVERS/VARIANCES | | | APPROVED AS PART OF THE LEVEL 3 SPECIAL REVIEW. | | | | | | PLEASE REVIEW THE COMMENTS WITH PERMIT NUMBER 22110628. | | | | | | PLEASE NOTE THAT SINCE PREVIOUSLY ISSUED COMMENTS | | | CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($600). | | | | | | CONTACT ERIC SCHNEIDER @ 561-822-1446 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
9 |
Status |
F |
Date |
04-20-2023 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
04-20-2023 |
Time |
11:46 |
Rev Time |
2.00 |
| Received By |
eschneid |
Date |
04-20-2023 |
Time |
11:46 |
Sent To |
|
|
| Notes |
| 2023-04-20 11:51:40 | CASE NO. PB 1895 FORMAL SITE PLAN - APRIL 6, 2023 | | | RESUBMITTAL | | | NORTHWOOD COMMONS | | | 2501 BROADWAY | | | | | | - CONTACT ERIC SCHNEIDER @ (561) 822-1446, | | | [email protected] | | | | | | - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | - WHEN RESUBMITTING, PLEASE PROVIDE TWO (2) PAPER | | | COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT OF ALL | | | PLANS. PLEASE NOTE THAT CHANGES ON THE RESUBMITTED | | | PLANS OR THE SUBMITTAL OF INFORMATION/PLANS TO ADDRESS | | | THE COMMENTS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | THE LEVEL III SPECIAL REVIEW, INCLUDING THE VARIANCES, | | | WAS APPROVED BY THE PLANNING BOARD ON NOVEMBER 15, | | | 2022. THE ARCHITECTURAL, LANDSCAPE AND CIVIL PLANS, | | | COLLECTIVELY, THE FORMAL SITE PLAN, IS NOT APPROVED. | | | THE PLANS REVIEWED BY STAFF FOR THE NOVEMBER 15, 2022 | | | PLANNING BOARD MEETING WERE USED TO DETERMINE THE | | | REQUESTED VARIANCES AND WAIVERS REQUIRED BY THE PROJECT | | | AND TO VERIFY GENERALLY THAT THE PROJECT MET NMUD CODE | | | REQUIREMENTS. TWO CONDITIONS OF THE LEVEL III SPECIAL | | | REVIEW APPROVAL WERE, "FINAL SITE DEVELOPMENT PLANS | | | MUST BE SUBMITTED TO THE PLANNING DIVISION AND PASS THE | | | FORMAL SITE PLAN REVIEW PROCESS." AND "THE FINAL | | | ELEVATIONS MUST BE APPROVED BY THE HISTORIC | | | PRESERVATION DIVISION PRIOR TO THE APPROVAL OF THE | | | FORMAL SITE PLAN." | | | | | | THE PLANS SUBMITTED FOR THE HISTORIC REVIEW ON DECEMBER | | | 5, 2022, INCLUDED CHANGES TO BUILDING C. PLANNING STAFF | | | REQUESTED ADDITIONAL INFORMATION TO VERIFY THAT THE | | | CHANGES STILL MET BOTH THE NMUD REGULATIONS AND THE | | | VARIANCES THAT WERE GRANTED BY THE PLANNING BOARD. ON | | | JANUARY 3, 2023, PLANNING STAFF WAS PROVIDED WITH | | | REVISED PLANS FOR BOTH BUILDINGS A AND C AND INFORMED | | | THAT THE ARCHITECT HAD MADE SOME CHANGES. STAFF ISSUED | | | COMMENTS AND REVIEWED ADDITIONAL PARTIAL SUBMITTALS | | | MADE ON JANUARY 19, 2023 AND FEBRUARY 28, 2023. EACH | | | SET OF PLANS INCLUDED SOME CORRECTIONS, BUT ALSO | | | INCLUDED NEW CHANGES. NONE OF THE NEW CHANGES WERE | | | HIGHLIGHTED AND THE PLANS THAT WERE INCLUDED WERE | | | INTERNALLY INCONSISTENT. | | | | | | THE APRIL 6, 2023 SUBMITTAL WAS TO INCLUDE ALL THE PLAN | | | REVISIONS MADE TO DATE IN ONE SET OF INTERNALLY | | | CONSISTENT PLANS SO THAT THE FORMAL SITE PLAN COULD BE | | | ISSUED. STAFF BEGAN TO REVIEW THE ARCHITECTURAL PLAN | | | SET AND NOTED THAT THE MAJORITY OF THE PLANS REVERTED | | | TO THE OUTDATED NOVEMBER 15, 2022 PLANS. THE SUBMITTAL | | | DID INCLUDE A FEW UPDATED PLANS TO ADDRESS THE LATEST | | | ROUND OF COMMENTS; HOWEVER, SINCE NOT ALL THE PLANS ARE | | | THE MOST RECENT PLANS, THE PLANS REMAIN INTERNALLY | | | INCONSISTENT. ADDITIONALLY, THE ARCHITECTURAL PLANS | | | SUBMITTED ON APRIL 6, 2023, DO NOT MATCH THE LANDSCAPE | | | AND CIVIL PLANS SUBMITTED ON APRIL 6, 2023. | | | | | | THE KIMLEY-HORN CIVIL AND LANDSCAPE PLANS APPEAR TO | | | MATCH THE ARCHITECTURAL PLANS SUBMITTED TO STAFF ON | | | FEBRUARY 28, 2023. STAFF IDENTIFIED ONE COMMENT ON | | | THESE PLANS THAT NEEDS TO BE ADDRESSED. | | | | | | HARDSCAPE | | | | | | 1) UPDATED COMMENT: THANK YOU FOR PROVIDING THE SEATING | | | CALCULATIONS FOR THE PUBLIC OPEN SPACE AREA ON SHEET | | | L2.00. THERE IS A 21-FOOT 1-INCH LENGTH OF PLANTER | | | SEATING IN THE WESTERN SECTION OF THE PUBLIC OPEN SPACE | | | THAT DIRECTLY CONFLICTS WITH THE MICRO MOBILITY STATION | | | LOCATION. THIS SEATING AREA MAY NOT BE COUNTED TOWARD | | | MEETING THE SEATING REQUIREMENT AS IT WILL BE BLOCKED | | | BY THE MICRO MOBILITY STATION. THE SEAT WALL MAY | | | REMAIN, BUT IT MAY NOT COUNT TOWARD MEETING THE PUBLIC | | | OPEN SPACE SEATING REQUIREMENT. | | | | | | LIGHTING | | | | | | 2) THANK YOU FOR PROVIDING THE LIGHTING PLANS. ANA | | | MARIA APONTE, DEPUTY DIRECTOR, COMMUNITY REDEVELOPMENT | | | AGENCY IS VERIFYING THAT THE FIXTURES BEING USED COMPLY | | | WITH THE DISCUSSIONS SHE HAD WITH YOUR TEAM. PLANNING | | | HAS VERIFIED THAT THE LOCATIONS FOR THE NEW POLES DO | | | NOT CONFLICT WITH THE PROPOSED TREES. | | | | | | THE NEXT SUBMITTAL SHALL INCLUDE THE CURRENT VERSIONS | | | OF ALL OF THE ARCHITECTURAL PLANS. ALL OF THE | | | ARCHITECTURAL PLANS SHALL BE INTERNALLY CONSISTENT AND | | | COMPLY WITH CODE REQUIREMENTS AND THE APPROVED WAIVERS | | | AND VARIANCES. PLEASE NOTE THAT ANY CHANGES THAT STAFF | | | HAS NOT PREVIOUSLY REVIEWED TO THE PLANS SHALL BE | | | CLOUDED AND PROVIDED IN A NARRATIVE. PLEASE NOTE THAT | | | NEW CHANGES WILL DELAY THE REVIEW. ALL PLANS SUBMITTED | | | FOR THE FORMAL SITE PLAN SHALL BE INTERNALLY | | | CONSISTENT, TO INCLUDE ADDRESSING THE OUTSTANDING | | | SEATING COMMENT. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
8 |
Status |
F |
Date |
03-28-2023 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
03-28-2023 |
Time |
09:49 |
Rev Time |
2.00 |
| Received By |
eschneid |
Date |
03-24-2023 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2023-03-28 10:05:30 | CASE NO. PB 1895 FORMAL SITE PLAN | | | NORTHWOOD COMMONS | | | 2501 BROADWAY | | | | | | - CONTACT ERIC SCHNEIDER @ (561) 822-1446, | | | [email protected] | | | | | | - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | - WHEN RESUBMITTING, PLEASE PROVIDE TWO (2) PAPER | | | COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT OF ALL | | | PLANS. PLEASE NOTE THAT CHANGES ON THE RESUBMITTED | | | PLANS OR THE SUBMITTAL OF INFORMATION/PLANS TO ADDRESS | | | THE COMMENTS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | THE LEVEL III SPECIAL REVIEW WAS APPROVED, INCLUDING | | | THE VARIANCES. THE ARCHITECTURAL, LANDSCAPE AND CIVIL | | | PLANS, COLLECTIVELY, THE FORMAL SITE PLAN, HAS THE | | | FOLLOWING ITEMS THAT NEED TO BE CORRECTED. PLEASE NOTE | | | THAT THERE ARE CONDITIONS THAT WILL BE INCLUDED WITH | | | THE FINAL APPROVAL LETTER. | | | | | | THE NEXT SUBMITTAL SHALL BE A FULL RESUBMITTAL WITH ALL | | | THE CURRENT PLAN VERSIONS. ALL PLANS SHALL BE | | | INTERNALLY CONSISTENT AND SUFFICIENTLY ADDRESS THE | | | REMAINING COMMENTS SO THAT STAFF CAN APPROVE THE FORMAL | | | SITE PLAN. PLEASE NOTE THAT ANY CHANGES TO THE PLANS | | | THAT STAFF HAS NOT PREVIOUSLY REVIEWED MAY DELAY THE | | | REVIEW. | | | | | | 1) UPDATED COMMENT: SINCE THE APPROVAL OF THE LEVEL III | | | SPECIAL REVIEW, STAFF WAS PROVIDED UPDATES TO THE | | | ELEVATION DRAWINGS FOR BUILDINGS A THERE ARE CHANGES TO | | | THE FENESTRATION: | | | | | | A. BUILDING A NEW PINEWOOD - THE ACTIVE USE AREA THAT | | | IS PROVIDED ON THE FENESTRATION AREA CALCULATIONS TABLE | | | ON SHEET A101.1B IS INCORRECT FOR BOTH SIDES OF NEW | | | PINEWOOD. THE NEW VALUE OF 6,019 SQUARE FEET OF ACTIVE | | | USE AREA SEEMS TO BE THE TOTAL FACADE AREA, NOT THE | | | ACTIVE USE AREA. WHEN COMPARING THE SITE PLAN AND | | | ELEVATIONS, THE ACTIVE USE AREA HAS MINIMALLY REDUCED | | | FROM THE NOVEMBER 14, 2022 LEVEL III SET OF DRAWINGS. | | | THE TABLE NEEDS TO REFLECT THE CORRECT ACTIVE USE ARE, | | | SINCE THIS IS WHAT THE BASIS FOR THE AMOUNT OF | | | FENESTRATION THAT IS REQUIRED. THE ELEVATION DRAWING | | | FOR THE WEST SIDE OF NEW PINEWOOD SHOWS FENESTRATION | | | ADDED FOR NON-ACTIVE USE AREAS, WHICH MAY NOT COUNT | | | TOWARD MEETING THE MINIMUM FENESTRATION FOR REQUIREMENT | | | ACTIVE-USE AREAS. NOTE: THE NOVEMBER 14, 2022 PLANS | | | EXCEEDED THE MINIMUM FENESTRATION REQUIREMENT BY A | | | SIGNIFICANT AMOUNT. INCORRECTLY SHOWING AN INCREASE IN | | | THE PROVIDED ACTIVE USE AREA ERRONEOUSLY REQUIRES MORE | | | FENESTRATION. | | | | | | B. BUILDING A PASEO (NORTH ELEVATION) - THE MINIMUM | | | FENESTRATION IS 70% OF THE ACTIVE USE AREA. THE NEW | | | PLANS PROVIDE 69% FENESTRATION, WHICH DOES NOT MEET THE | | | MINIMUM AMOUNT OF FENESTRATION. ROUNDING UP IS NOT | | | PERMITTED. BASED ON THE 4,297 SQUARE FEET OF ACTIVE USE | | | AREA, AT LEAST 3,008 SQUARE FEET OF FENESTRATION IS | | | REQUIRED. THIS COULD BE ACHIEVED BY ADDING FENESTRATION | | | TO THE SOUTH SIDE OF LINER UNIT 13. | | | | | | 2) UPDATED REPEAT COMMENT: THE DIMENSION LINES WERE NOT | | | UPDATED TO REFLECT THE SETBACK DIMENSIONS FROM THE | | | NORTHERN PROPERTY LINE TO THE WALL ON SHEET C1.50. | | | SHEETS C1.51, C1.52 AND DETAIL C-C ON SHEET C2.09 WERE | | | UPDATED. ALL PLANS MUST SHOW CONSISTENT INFORMATION. | | | | | | 3) UPDATED COMMENT: THANK YOU FOR PROVIDING THE PLANS | | | FOR THE PRESERVATION OF THE DOORWAY. THE CITY HISTORIC | | | PRESERVATION PLANNER HAS REVIEWED THE SUBMITTED PLANS | | | AND HAS APPROVED THE DESIGN WITH THE CONDITION THAT THE | | | ACTUAL DOOR BE REMOVED. THE DOORWAY NEEDS TO REMAIN | | | OPEN FOR PASS THROUGH. SHEET HP S-1.0B SHALL BE UPDATED | | | TO REFLECT THE DOOR REMOVAL AS PART OF THE SITE PLAN | | | PACKAGE RESUBMITTAL. | | | | | | HARDSCAPE | | | | | | 4) UPDATED COMMENT: THE MOST RECENT CIVIL PLANS SHOW 13 | | | BICYCLE RACKS THROUGHOUT THE DEVELOPMENT SITE. SHEETS | | | L.2.00 AND L2.11 THAT WERE SUBMITTED ON JANUARY 19, | | | 2023 LIST THAT THERE WILL BE 14 BICYCLE RACKS. THE | | | CORRECT NUMBER OF INSTALLED RACKS MUST BE PROVIDED ON | | | THESE SHEETS. | | | | | | 5) REPEAT UPDATED COMMENT: BASED ON THE AMOUNT OF | | | PROVIDED PUBLIC OPEN SPACE, 430 LINEAR FEET OF SEATING | | | IS REQUIRED (TABLE ON SHEET L1.02). IT WAS STAFF'S | | | UNDERSTANDING THAT THIS WAS BEING PROVIDED AS SEAT | | | WALLS AROUND THE LANDSCAPE PLANTERS. THE UPDATED CIVIL | | | SHEETS (C1.53 AND C1.54) SHOW WHAT APPEAR TO BE SEATING | | | AREAS AROUND THE PLANTERS THAT ARE LOCATED WITHIN THE | | | PUBLIC OPEN SPACE. NO LINEAR DIMENSIONS WERE PROVIDED | | | ON THESE SHEETS SO THAT STAFF COULD VERIFY COMPLIANCE | | | WITH THE MINIMUM 430 LINEAR FEET OF SEATING THAT IS | | | REQUIRED. NO HARDSCAPE PLAN WAS SUBMITTED WITH THE MOST | | | RECENT RESUBMITTAL, SO STAFF WAS UNABLE TO USE THE | | | HARDSCAPE PLAN TO VERIFY COMPLIANCE AS STATED IN THE | | | RESPONSE. | | | | | | 6) IN ADDITION TO NO NEW HARDSCAPE PLAN BEING | | | SUBMITTED, AN UPDATED LANDSCAPE PLAN REFLECTING THE | | | CHANGES TO THE PARKING AREAS AND THE SEATING WAS ALSO | | | NOT SUBMITTED. | | | | | | LIGHTING | | | | | | 7) PROVIDE THE LIGHTING PLANS THAT COMPLY WITH THE | | | DISCUSSIONS THAT HAVE BEEN HAD WITH ANA MARIA APONTE, | | | DEPUTY DIRECTOR, COMMUNITY REDEVELOPMENT AGENCY. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
7 |
Status |
F |
Date |
02-13-2023 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
02-13-2023 |
Time |
16:08 |
Rev Time |
2.00 |
| Received By |
eschneid |
Date |
02-07-2023 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2023-02-13 16:08:56 | CASE NO. PB 1895 FORMAL SITE PLAN | | | NORTHWOOD COMMONS | | | 2501 BROADWAY | | | | | | - CONTACT ERIC SCHNEIDER @ (561) 822-1446, | | | [email protected] | | | | | | - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF TWO | | | (2) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT | | | OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE | | | RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS | | | TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | THE LEVEL III SPECIAL REVIEW WAS APPROVED, INCLUDING | | | THE VARIANCES. THE ARCHITECTURAL, LANDSCAPE AND CIVIL | | | PLANS, COLLECTIVELY, THE FORMAL SITE PLAN, HAS THE | | | FOLLOWING ITEMS THAT NEED TO BE CORRECTED. PLEASE NOTE | | | THAT INCLUDED ARE THE CONDITIONS THAT WILL BE INCLUDED | | | WITH THE FINAL APPROVAL LETTER. IF ANY OF THOSE ITEMS | | | CAN BE ADDRESSED WITH THIS RESUBMITTAL (EXAMPLE | | | TRANSPORTATION PLANNER CONDITIONS) STAFF WOULD PREFER | | | TO SEE IT AT THIS TIME. | | | | | | 1) UPDATED COMMENT: SINCE THE APPROVAL OF THE LEVEL III | | | SITE PLAN REVIEW, STAFF WAS PROVIDED UPDATES TO THE | | | ELEVATION DRAWINGS FOR BUILDINGS A AND C. STAFF HAS | | | REVIEWED THE DRAWINGS AND NOTED THAT THERE ARE NO | | | CHANGES TO THE PLANAR BREAKS; HOWEVER, THERE ARE | | | CHANGES TO THE FENESTRATION: | | | | | | A. BUILDING A - FENESTRATION ALONG BROADWAY, 25TH AND | | | THE PUBLIC OPEN SPACE COMPLY. | | | B. BUILDING A - PROVIDE THE FENESTRATION DRAWINGS AND | | | PERCENTAGES FOR NEW PINEWOOD (EAST AND WEST - 50% | | | REQUIRED) AND THE PUBLIC PASEO (NORTH AND SOUTH - 70% | | | REQUIRED). ***** NEW DRAWINGS WERE NOT PROVIDED. THE | | | TABLE FOR THE PINEWOOD FENESTRATION WAS UPDATED, BUT | | | SINCE THE PLANS ARE THE SAME, STAFF IS NOT SURE HOW | | | THIS IS POSSIBLE. | | | C. BUILDING C - FENESTRATION ALONG 24TH STREET COMPLIES | | | | | | *** PLEASE ENSURE THAT ALL DATA TABLES SHOW THE SAME | | | ACCURATE VALUES ACROSS ALL PLAN SHEETS. | | | | | | 2) UPDATED COMMENT: THANK YOU FOR UPDATING THE KIMLEY | | | HORN BASE PLAN TO CORRECTLY SHOW THE BUILDING A | | | NORTHERN BUILDING WALL TO MATCH WHAT IS SHOWN ON THE | | | LATEST ARCHITECTURAL DRAWINGS. HOWEVER, THE DIMENSION | | | LINES WERE NOT UPDATED TO REFLECT THE SETBACK | | | DIMENSIONS TO THE WALL (SHEETS C1.50, C1.51 AND C1.52). | | | THE DIMENSION LINES MUST SHOW THE SETBACK, NOT A RANDOM | | | SPOT IN THE SIDEWALK. SECTION DETAIL C-C ON SHEET C2.09 | | | WAS NOT UPDATED TO REFLECT THE CORRECT SETBACK. PLEASE | | | NOTE THAT THERE IS AN FDC AND BACKFLOW THAT WILL NEED | | | TO BE ADJUSTED SO THEY ARE NOT LOCATED IN THE MIDDLE OF | | | THE NEW, WIDER SIDEWALK. | | | | | | 3) UPDATED COMMENT: THE HISTORIC PRESERVATION FINAL | | | ORDER REQUIRES THAT THE DOORWAY SECTION OF THE BUILDING | | | LOCATED AT 550 NORTHWOOD ROAD BE PRESERVED IN PLACE. | | | ***** THE ARCHITECTURAL PLANS MUST INCLUDE DETAILS NOT | | | ONLY OF HOW THE DOORWAY IS TO BE PRESERVED DURING THE | | | DEMOLITION OF THE REMAINDER OF THE BUILDING, BUT ALSO | | | THE DETAILS OF THE PRESERVED DOORWAY. THE DETAILS SHALL | | | INCLUDE DIMENSIONS FOR THE HEIGHT, WIDTH AND DEPTH OF | | | THE DOORWAY PORTION OF BE PRESERVED. THE HISTORIC | | | PRESERVATION PLANNER IS REQUIRING THIS TO BE SHOWN IN | | | PLAN AND IN ELEVATION ON THE ARCHITECTURAL PLANS AS | | | PART OF THE SITE PLAN APPROVAL. | | | | | | HARDSCAPE | | | | | | 4) UPDATED REPEAT COMMENT: THE BOLLARDS MAY NOT BE | | | LOCATED AT THE MIDDLE OF THE PARKING SPACE AS THEY WILL | | | OBSTRUCT DOOR OPENINGS, REGARDLESS OF THE FACT THAT | | | THEY HAVE BEEN MOVED 2.5 FEET FROM THE EDGE OF THE | | | SPACE. THE BOLLARDS SHALL BE PLACES SIMILAR TO HOW THE | | | CITY HAS INSTALLED BOLLARDS ALONG CLEMATIS STREET, | | | CLOSER TO THE ENDS OF THE PARKING SPACES. | | | | | | 5) THANK YOU FOR PROVIDING THE DIMENSION BOXES AROUND | | | THE BICYCLE PARKING. THE TWO BICYCLE PARKING SPACES AT | | | THE NORTH END OF PINEWOOD DO NOW SHOW THAT THE REQUIRED | | | 60-INCH CLEAR PATH REQUIRED BY THE NMUD REGULATIONS | | | WILL BE MAINTAINED WHILE THE BICYCLE RACK IS IN USE AND | | | SHALL BE RELOCATED. THE ONE ON THE EAST SIDE OF | | | PINEWOOD COULD BE SHIFTED TO THE SOUTH END OF THE | | | LANDSCAPE BED AND BE INSTALLED PERPENDICULAR TO THE | | | STREET. THE BICYCLE PARKING SPACE THAT HAS THE | | | DIMENSIONED BOX, SOUTH OF THE PASEO, ALSO DOES NOT HAVE | | | THE 60-INCH CLEAR AREA. THIS COULD ALSO BE SHIFTED | | | ADJACENT TO THE PLANTER. | | | | | | 6) BASED ON THE AMOUNT OF PROVIDED PUBLIC OPEN SPACE, | | | 430 LINEAR FEET OF SEATING IS REQUIRED (TABLE ON SHEET | | | L1.02). IT WAS STAFF'S UNDERSTANDING THAT THIS WAS | | | BEING PROVIDED AS SEAT WALLS AROUND THE LANDSCAPE | | | PLANTERS. STAFF HAD MEASURED THESE AREAS AND THE 430 | | | FEET WAS EXCEEDED, HOWEVER, WHEN COMPARING DIFFERENT | | | PLANS SOME OF THESE AREAS NO LONGER LOOK TO HAVE | | | SEATING AREAS. THE PROVISION OF THE BENCHES AS SEATING | | | ONLY PROVIDES 144 LINEAR FEET OF SEATING, WHICH DOES | | | NOT MEET THE MINIMUM REQUIREMENTS. PLEASE CLARIFY AND | | | INCLUDE DIMENSIONS FOR THE SEATING AREA THAT ARE BEING | | | CLAIMED TO COMPLY WITH THE SEATING REQUIREMENT. NOTE: | | | THE LEG ROOM FOR ONE BENCH SEEMS TO BE OBSTRUCTED BY A | | | BICYCLE RACK AND ANOTHER BY A BOLLARD. PLEASE REVIEW. | | | | | | PARKING | | | | | | 7) WHILE REVIEWING THE HARDSCAPE DIMENSIONS, STAFF | | | NOTED THAT THERE ARE TWO PARKING SPACES ON THE WEST | | | SIDE OF PINEWOOD THAT DO NOT MEET THE MINIMUM 22-FOOT | | | CURB LENGTH FOR PARALLEL PARKING SPACES. THESE SPACES | | | ARE APPROXIMATELY 16.5 FEET IN LENGTH AND THUS DO NOT | | | MEET THE CODE MINIMUM. THIS WAS NOT PREVIOUSLY NOTED | | | SINCE THE ONE SAMPLE SPACE DIMENSION ON SHEET A103.0 IS | | | SHOWN FOR A CONFORMING 22-FOOT LONG SPACE. THIS IS A | | | PROBLEM SINCE THE SITE IS NOW TWO PARKING SPACES SHORT | | | OF MEETING CODE. | | | | | | PUBLIC WORKS - SANITATION. | | | | | | 8) UPDATED COMMENT: THANK YOU FOR PROVIDING THE | | | NOTATIONS REGARDING THE SOLID WASTE CONTAINER SIZE/TYPE | | | AND THE HEIGHT CLEARANCE OVER THE LOADING ZONE WHERE | | | THE SOLID WASTE CONTAINER(S) GET SERVICED AND THE BULK | | | WASTE GETS PICKED UP. ***** THE PLANS SHOW THAT THE | | | SOLID WASTE FACILITY WILL OVERLAP WITH THE REQUIRED | | | LOADING ZONE, WHICH IS NOT PERMITTED. | | | | | | CONDITION: COMPLIANCE WITH THE WASTE MANAGEMENT LETTER | | | DATED OCTOBER 25, 2022, WILL BE INCLUDED AS A CONDITION | | | OF APPROVAL. | | | | | | POTENTIAL DRAFT CONDITIONS | | | | | | 1) PRIOR TO THE ISSUANCE OF BUILDING PERMITS FOR | | | VERTICAL CONSTRUCTION OF BUILDINGS A OR B, THE | | | SUBMITTED PLAT NEEDS TO BE RECORDED AND THE | | | RIGHTS-OF-WAY WITHIN THE SITE NEED TO BE ABANDONED. | | | | | | 2) ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES | | | NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO | | | MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL | | | BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE | | | EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED | | | TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR | | | OTHER APPROVED METHODS. | | | | | | 3) IF AT TIME OF CONSTRUCTION/PARKING SPACE STRIPING | | | ADDITIONAL SPACES ARE IDENTIFIED AS LESS THAN ONE FOOT | | | FROM A WALL, THE SPACES WILL ALSO NEED TO BE MARKED AS | | | COMPACT WITH AN AMENDMENT TO THE SITE PLAN AT THAT | | | TIME. | | | | | | 4) CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND | | | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF | | | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL | | | NEIGHBORING PROPERTIES. | | | | | | 5) PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER | | | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, | | | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE | | | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF | | | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION | | | THAT MAY AFFECT THE USE OF THEIR PROPERTY. | | | | | | 6) PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | | | | 7) THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE | | | STREET TREES AND RIGHT OF WAY LANDSCAPING AND | | | IRRIGATION APPROVED WITH THIS PETITION. | | | | | | 8)THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF | | | WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A | | | SEPARATE MAINTENANCE AGREEMENT WITH THE CITY. | | | | | | 9) THERE ARE UTILITY EASEMENTS SHOWN IN LOCATIONS IN | | | CONFLICT WITH REQUIRED TREES. THIS OCCURS AT THE | | | NORTHWEST CORNER OF THE SITE ALONG THE FEC RR, ALONG | | | 23RD STREET, AND THE WEST SIDE OF BROADWAY EXTENSION. | | | ANY UTILITIES INSTALLED IN THIS AREA MUST BE AT LEAST | | | 36 INCHES BELOW GRADE OR OTHERWISE LOCATED TO AVOID THE | | | REQUIRED TREE ROOT SYSTEMS. | | | | | | 10) PRIOR TO THE FIRST CERTIFICATE OF OCCUPANCY FOR THE | | | SITE: | | | | | | A. ACCESS AND MAINTENANCE EASEMENTS, APPROVED BY THE | | | CITY ATTORNEY'S OFFICE, ARE REQUIRED TO BE RECORDED FOR | | | ANY PORTIONS OF SIDEWALKS, ROADWAYS, PARKING SPACES AND | | | STREET LIGHTING LOCATED WITHIN THE DEVELOPMENT SITE. | | | B. AN AERIAL EASEMENT, APPROVED BY THE CITY ATTORNEY'S | | | OFFICE, IS REQUIRED TO BE RECORDED. | | | | | | 11) IN THE EVENT THAT THE FLORIDA DEPARTMENT OF | | | TRANSPORTATION (FDOT) DOES NOT ISSUE A PERMIT FOR THE | | | IMPROVEMENTS, TO INCLUDE THE LANDSCAPE, SHOWN WITHIN | | | THE BROADWAY ROW, THEN CODE COMPLIANT IMPROVEMENTS MUST | | | BE INSTALLED ON THE SITE AFTER THE APPROVAL OF A SITE | | | PLAN AMENDMENT. | | | | | | 12) THE HARDSCAPE ITEMS WITHIN THE FDOT ROW REQUIRE | | | PERMIT APPROVAL BY FDOT. THIS NEEDS TO BE PROVIDED. | | | | | | STORMWATER | | | | | | CONDITION: REVIEW THE COMMENTS MADE BY THE CITY | | | STORMWATER ENGINEER AS THERE ARE A NUMBER OF ITEMS THAT | | | NEED TO BE REFLECTED ON THE ENGINEERING PERMIT | | | SUBMITTAL. PLEASE ENSURE THAT ANY CHANGES MADE TO THE | | | ENGINEERING PLANS THAT AFFECT ABOVE GROUND CONDITIONS | | | ARE PROVIDED TO PLANNING AS WELL. | | | | | | TRANSPORTATION PLANNER CONDITIONS | | | | | | 1) PROVIDE A CLEAN, DEDICATED TRANSPORTATION SITE PLAN | | | DEPICTING ALL RELATED ROADWAY AND TRANSPORTATION | | | FEATURES, FULLY DIMENSIONED AND SHOWCASING CURB DETAILS | | | ON THE OPPOSITE SIDE OF THE ROAD FRONTING THE PROPOSED | | | DEVELOPMENT. PLEASE KEEP IN MIND THAT THIS COMMENT WAS | | | PROVIDED AT THE VERY FIRST PPRC REVIEW AND WAS NEVER | | | COMPLETELY FULFILLED | | | 2) PROVIDE A REVISED AUTOTURN ANALYSIS SHOWCASING | | | SERVICE VEHICLES ACCESSING/EXITING THE FACILITY, | | | MANEUVERING AT EACH POSSIBLE LOADING OR SANITATION | | | ZONE(S), WITH BOTH DYNAMIC AND WHEEL PATHS HIGHLIGHTED | | | IN SEPARATE COLORS | | | 3) PROVIDE A LIST OF ON-GOING ITEMS UNDER DISCUSSION OR | | | REVIEW WITH COUNTY AND FDOT. OBTAIN COUNTY AND/OR FDOT | | | APPROVAL PERTAINING THE PORTION OF THE PROPOSED | | | DEVELOPMENT IMPACTING THEIR RIGHT OF WAY | | | 4) INSTALL AND SHOW SHARROW MARKINGS ALONG 23RD ST AND | | | PINEWOOD AVE | | | 5) 25TH ST ROADWAY DESIGN SHOULD ACCOMMODATE THE | | | PLANNED SEPARATED AND ELEVATED BICYCLE LANES FROM | | | AUSTRALIAN TO BROADWAY. PLEASE REFER TO THE CITY | | | BICYCLE MASTERPLAN FOR TYPICAL SECTION(S) AND UPDATE | | | THE SITE PLANS ACCORDINGLY. NOTE: CITY MAY NOT REQUIRE | | | THE DEVELOPER TO IMPLEMENT SUCH FEATURE ALONG SITE | | | FRONTAGE; HOWEVER, ROW MUST BE PRESERVED AND PROVIDED | | | TO ACCOMMODATE ITS FUTURE IMPLEMENTATION | | | 6) THE PROPOSED PINEWOOD AVENUE RE-ALIGNMENT IS NOT | | | CONDUCIVE TO A SAFE VEHICULAR STRAIGHT-THROUGH MOVEMENT | | | ACROSS THE 25TH AND 23RD INTERSECTIONS. SUCH MOVEMENT | | | SHOULD BE EITHER FORBIDDEN OR FACILITATED BY SIGNAGE, | | | STRIPING AND ROADWAY FEATURES SUCH AS FLEXIBLE POLES, | | | MIDDLE RAISED ISLANDS AND CHANNELIZATION. PLEASE REVISE | | | THE SITE PLANS ACCORDINGLY | | | 7) INSTALL AND SHOWCASE STOP BARS AND SIGNS ON EACH | | | GARAGE LEVEL. IT IS RECOMMENDED TO TREAT THE NORTHERN | | | AND SOUTHERN EAST-WEST DRIVE AISLES AS THE MAIN ONES, | | | WHILE THE NORTH-SOUTH AS MINOR | | | 8) DIRECTIONAL ARROW PAVEMENT MARKINGS ARE MISSING. | | | PLEASE INSERT THEM IN THE TRANSPORTATION SITE PLAN | | | THROUGHOUT WERE NEEDED (E.G. RIGHT ARROW FOR THE | | | SOUTHBOUND MOVEMENT, LEFT ARROW FOR THE EASTBOUND | | | MOVEMENT AT THE 23RD AND PINEWOOD INTERSECTION) | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
6 |
Status |
F |
Date |
01-09-2023 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
01-06-2023 |
Time |
16:59 |
Rev Time |
2.00 |
| Received By |
eschneid |
Date |
10-25-2022 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2023-01-06 17:00:12 | CASE NO. PB 1895 FORMAL SITE PLAN | | | NORTHWOOD COMMONS | | | 2501 BROADWAY | | | | | | - CONTACT ERIC SCHNEIDER @ (561) 822-1446, | | | [email protected] | | | | | | - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF TWO | | | (2) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT | | | OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE | | | RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS | | | TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | THE LEVEL III SPECIAL REVIEW WAS APPROVED, INCLUDING | | | THE VARIANCES. THE ARCHITECTURAL, LANDSCAPE AND CIVIL | | | PLANS, COLLECTIVELY, THE FORMAL SITE PLAN, HAS THE | | | FOLLOWING ITEMS THAT NEED TO BE CORRECTED. PLEASE NOTE | | | THAT INCLUDED ARE THE CONDITIONS THAT WILL BE INCLUDED | | | WITH THE FINAL APPROVAL LETTER. IF ANY OF THOSE ITEMS | | | CAN BE ADDRESSED WITH THIS RESUBMITTAL (EXAMPLE | | | TRANSPORTATION PLANNER CONDITIONS) STAFF WOULD PREFER | | | TO SEE IT AT THIS TIME. | | | | | | 1) THERE IS AN OUTSTANDING FEE BALANCE OF $2,568. THIS | | | NEEDS TO BE PAID PRIOR TO THE ISSUANCE OF THE FORMAL | | | SITE PLAN APPROVAL. IT IS STAFF'S UNDERSTANDING THAT | | | THIS SOON TO BE PAID. | | | | | | 2) SINCE THE APPROVAL OF THE LEVEL III SITE PLAN | | | REVIEW, STAFF WAS PROVIDED UPDATES TO THE ELEVATION | | | DRAWINGS FOR BUILDINGS A AND C. STAFF HAS REVIEWED THE | | | DRAWINGS AND NOTED THAT THERE ARE NO CHANGES TO THE | | | PLANAR BREAKS; HOWEVER, THERE ARE CHANGES TO THE | | | FENESTRATION: | | | | | | A. BUILDING A - FENESTRATION ALONG BROADWAY, 25TH AND | | | THE PUBLIC OPEN SPACE COMPLY. | | | B. BUILDING A - PROVIDE THE FENESTRATION DRAWINGS AND | | | PERCENTAGES FOR NEW PINEWOOD (EAST AND WEST - 50% | | | REQUIRED) AND THE PUBLIC PASEO (NORTH AND SOUTH - 70% | | | REQUIRED). | | | C. BUILDING C - FENESTRATION ALONG 24TH STREET COMPLIES | | | | | | *** PLEASE ENSURE THAT ALL DATA TABLES SHOW THE SAME | | | ACCURATE VALUES ACROSS ALL PLAN SHEETS. | | | | | | 3) THE BASE PLANS USED BY KIMLEY HORN WERE NOT UPDATED | | | TO SHOW THE NEW NORTHERN BUILDING WALL OF BUILDING A | | | THAT IS SHOWN ON THE LATEST ARCHITECTURAL DRAWINGS. THE | | | NEW WALL IS LOCATED 1.3 FEET FURTHER SOUTH THAN THE | | | CURRENT KIMLEY HORN PLANS SHOW. THIS OCCURS ON THE | | | PLANS SUBMITTED FOR THE ENGINEERING REVIEW AS WELL AS | | | THE LATEST PLANNING FORMAL SITE PLAN. THESE PLANS MUST | | | BE CORRECTED TO MATCH THE ARCHITECTURAL PLANS. PLEASE | | | NOTE THAT THERE IS AN FDC AND BACKFLOW THAT WILL NEED | | | TO BE ADJUSTED SO THEY ARE NOT LOCATED IN THE MIDDLE OF | | | THE NEW, WIDER SIDEWALK. | | | | | | 4) THE HISTORIC PRESERVATION FINAL ORDER REQUIRES THAT | | | THE DOORWAY SECTION OF THE BUILDING LOCATED AT 550 | | | NORTHWOOD ROAD BE PRESERVED IN PLACE. THE DEMOLITION | | | PLAN SHOWS THE DOORWAY BEING REMOVED, WHICH IS NOT | | | PERMITTED. THE DEMOLITION PLANS MUST CLEARLY CALL OUT | | | THE PRESERVATION OF THE DOORWAY AND INCLUDE DETAILS NOT | | | ONLY OF HOW THE DOORWAY IS TO BE PRESERVED DURING THE | | | DEMOLITION OF THE REMAINDER OF THE BUILDING, BUT ALSO | | | THE DETAILS OF THE PRESERVED DOORWAY. THE DETAILS SHALL | | | INCLUDE DIMENSIONS FOR THE HEIGHT, WIDTH AND DEPTH OF | | | THE DOORWAY PORTION OF BE PRESERVED. THIS SHALL BE | | | SHOWN IN PLAN AND IN ELEVATION ON THE ARCHITECTURAL AND | | | CIVIL PLANS. | | | LANDSCAPE | | | | | | 5) REVIEW AND ADDRESS THE COMMENTS THAT WERE ENTERED BY | | | THE CITY LANDSCAPE PLANNER ON JANUARY 6, 2023. | | | | | | 6) A BACKFLOW METER ALONG 23RD STREET (AT MATCH LINE | | | BETWEEN SHEETS C2.03 AND C2.04) CONFLICTS WITH A | | | REQUIRED TREE AND NEEDS TO BE SHIFTED. THIS SHALL BE | | | CORRECTLY SHOWN ON ALL PLANS. | | | | | | 7) ROOT BARRIERS NEED TO BE SHOWN ON THE LANDSCAPE | | | PLANS WHERE TREES AND PALMS ARE IN CLOSE PROXIMITY TO | | | STORM, SEWER AND WATER LINES, BOTH PUBLIC AND PRIVATE. | | | THIS ONLY OCCURS IN A FEW LOCATIONS. | | | | | | HARDSCAPE | | | | | | 8) THE FINAL LOCATION OF THE NEW CROSSWALK ACROSS 23RD | | | STREET AT THE BROADWAY EXTENSION MAY NOT ANGLE ACROSS | | | 23RD STREET AS SHOWN. IT NEEDS TO BE RELOCATED TO THE | | | WEST SIDE OF THE BROADWAY EXTENSION AND BE | | | PERPENDICULAR TO THE SIDEWALK. THE OBSOLETE CURB CUT ON | | | THE SOUTH SIDE OF 23RD STREET (IN FRONT OF THE CRA | | | OWNED PARCEL) WILL NEED TO BE REMOVED TO FACILITATE A | | | SAFE CROSSING LOCATION. | | | | | | 9) THE HARDSCAPE AND CONTROL PLANS NEED TO SHOW THE | | | BOX, WITH DIMENSIONS, FOR THE BICYCLE RACK OFFSETS ON | | | THE PLANS, NOT JUST ON THE DETAIL PAGE. SCALING THE | | | PLANS SHOWS THE OFFSETS NOT MET IN SOME INSTANCES. | | | | | | 10) BOLLARDS MAY NOT BE LOCATED AT THE MIDDLE OF THE | | | PARKING SPACE AS THEY WILL OBSTRUCT DOOR OPENINGS. | | | | | | 11) BICYCLE RACKS MAY NOT BE ADJACENT TO PARKING SPACES | | | (ONE AT NORTH END OF NEW PINEWOOD). | | | | | | 12) ALL ABOVEGROUND HARDSCAPE FEATURES NEED TO BE SHOWN | | | ON THE CONTROL PLAN, WITH DIMENSIONS. | | | | | | STORMWATER | | | | | | 13) REVIEW THE COMMENTS MADE BY THE CITY STORMWATER | | | ENGINEER AS THERE ARE A NUMBER OF ITEMS THAT NEED TO BE | | | REFLECTED ON THE ENGINEERING PERMIT SUBMITTAL. PLEASE | | | ENSURE THAT ANY CHANGES MADE TO THE ENGINEERING PLANS | | | THAT AFFECT ABOVE GROUND CONDITIONS ARE PROVIDED TO | | | PLANNING AS WELL. | | | | | | PUBLIC WORKS - SANITATION. | | | | | | 14) PROVIDE A NOTE ON THE PLAN THAT INCLUDES THE | | | CONTAINER SIZE/TYPE FOR THE SOLID WASTE. | | | | | | 15) PROVIDE THE HEIGHT CLEARANCE OVER THE LOADING ZONE | | | WHERE THE SOLID WASTE CONTAINER(S) GET SERVICED AND THE | | | BULK WASTE GETS PICKED UP. | | | | | | THE INFORMATION PROVIDED IN COMMENT #S 14 AND 15 ABOVE | | | SHALL COMPLY WITH THE INFORMATION PROVIDED IN THE WASTE | | | MANAGEMENT LETTER DATED OCTOBER 25, 2022. THE LETTER | | | WILL BE INCLUDED AS A CONDITION OF APPROVAL. | | | | | | POTENTIAL DRAFT CONDITIONS | | | | | | 1) PRIOR TO THE ISSUANCE OF BUILDING PERMITS FOR | | | VERTICAL CONSTRUCTION OF BUILDINGS A OR B, THE | | | SUBMITTED PLAT NEEDS TO BE RECORDED AND THE | | | RIGHTS-OF-WAY WITHIN THE SITE NEED TO BE ABANDONED. | | | | | | 2) ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES | | | NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO | | | MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL | | | BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE | | | EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED | | | TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR | | | OTHER APPROVED METHODS. | | | | | | 3) IF AT TIME OF CONSTRUCTION/PARKING SPACE STRIPING | | | ADDITIONAL SPACES ARE IDENTIFIED AS LESS THAN ONE FOOT | | | FROM A WALL, THE SPACES WILL ALSO NEED TO BE MARKED AS | | | COMPACT WITH AN AMENDMENT TO THE SITE PLAN AT THAT | | | TIME. | | | | | | 4) CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND | | | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF | | | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL | | | NEIGHBORING PROPERTIES. | | | | | | 5) PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER | | | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, | | | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE | | | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF | | | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION | | | THAT MAY AFFECT THE USE OF THEIR PROPERTY. | | | | | | 6) PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | | | | 7) THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE | | | STREET TREES AND RIGHT OF WAY LANDSCAPING AND | | | IRRIGATION APPROVED WITH THIS PETITION. | | | | | | 8)THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF | | | WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A | | | SEPARATE MAINTENANCE AGREEMENT WITH THE CITY. | | | | | | 9) THERE ARE UTILITY EASEMENTS SHOWN IN LOCATIONS IN | | | CONFLICT WITH REQUIRED TREES. THIS OCCURS AT THE | | | NORTHWEST CORNER OF THE SITE ALONG THE FEC RR, ALONG | | | 23RD STREET, AND THE WEST SIDE OF BROADWAY EXTENSION. | | | ANY UTILITIES INSTALLED IN THIS AREA MUST BE AT LEAST | | | 36 INCHES BELOW GRADE OR OTHERWISE LOCATED TO AVOID THE | | | REQUIRED TREE ROOT SYSTEMS. | | | | | | 10) PRIOR TO THE FIRST CERTIFICATE OF OCCUPANCY FOR THE | | | SITE: | | | | | | A. ACCESS AND MAINTENANCE EASEMENTS, APPROVED BY THE | | | CITY ATTORNEY'S OFFICE, ARE REQUIRED TO BE RECORDED FOR | | | ANY PORTIONS OF SIDEWALKS, ROADWAYS, PARKING SPACES AND | | | STREET LIGHTING LOCATED WITHIN THE DEVELOPMENT SITE. | | | B. AN AERIAL EASEMENT, APPROVED BY THE CITY ATTORNEY'S | | | OFFICE, IS REQUIRED TO BE RECORDED. | | | | | | 11) IN THE EVENT THAT THE FLORIDA DEPARTMENT OF | | | TRANSPORTATION (FDOT) DOES NOT ISSUE A PERMIT FOR THE | | | IMPROVEMENTS, TO INCLUDE THE LANDSCAPE, SHOWN WITHIN | | | THE BROADWAY ROW, THEN CODE COMPLIANT IMPROVEMENTS MUST | | | BE INSTALLED ON THE SITE AFTER THE APPROVAL OF A SITE | | | PLAN AMENDMENT. | | | | | | 12) THE HARDSCAPE ITEMS WITHIN THE FDOT ROW REQUIRE | | | PERMIT APPROVAL BY FDOT. THIS NEEDS TO BE PROVIDED. | | | | | | TRANSPORTATION PLANNER CONDITIONS | | | | | | 1) PROVIDE A CLEAN, DEDICATED TRANSPORTATION SITE PLAN | | | DEPICTING ALL RELATED ROADWAY AND TRANSPORTATION | | | FEATURES, FULLY DIMENSIONED AND SHOWCASING CURB DETAILS | | | ON THE OPPOSITE SIDE OF THE ROAD FRONTING THE PROPOSED | | | DEVELOPMENT. PLEASE KEEP IN MIND THAT THIS COMMENT WAS | | | PROVIDED AT THE VERY FIRST PPRC REVIEW AND WAS NEVER | | | COMPLETELY FULFILLED | | | 2) PROVIDE A REVISED AUTOTURN ANALYSIS SHOWCASING | | | SERVICE VEHICLES ACCESSING/EXITING THE FACILITY, | | | MANEUVERING AT EACH POSSIBLE LOADING OR SANITATION | | | ZONE(S), WITH BOTH DYNAMIC AND WHEEL PATHS HIGHLIGHTED | | | IN SEPARATE COLORS | | | 3) PROVIDE A LIST OF ON-GOING ITEMS UNDER DISCUSSION OR | | | REVIEW WITH COUNTY AND FDOT. OBTAIN COUNTY AND/OR FDOT | | | APPROVAL PERTAINING THE PORTION OF THE PROPOSED | | | DEVELOPMENT IMPACTING THEIR RIGHT OF WAY | | | 4) INSTALL AND SHOW SHARROW MARKINGS ALONG 23RD ST AND | | | PINEWOOD AVE | | | 5) 25TH ST ROADWAY DESIGN SHOULD ACCOMMODATE THE | | | PLANNED SEPARATED AND ELEVATED BICYCLE LANES FROM | | | AUSTRALIAN TO BROADWAY. PLEASE REFER TO THE CITY | | | BICYCLE MASTERPLAN FOR TYPICAL SECTION(S) AND UPDATE | | | THE SITE PLANS ACCORDINGLY. NOTE: CITY MAY NOT REQUIRE | | | THE DEVELOPER TO IMPLEMENT SUCH FEATURE ALONG SITE | | | FRONTAGE; HOWEVER, ROW MUST BE PRESERVED AND PROVIDED | | | TO ACCOMMODATE ITS FUTURE IMPLEMENTATION | | | 6) THE PROPOSED PINEWOOD AVENUE RE-ALIGNMENT IS NOT | | | CONDUCIVE TO A SAFE VEHICULAR STRAIGHT-THROUGH MOVEMENT | | | ACROSS THE 25TH AND 23RD INTERSECTIONS. SUCH MOVEMENT | | | SHOULD BE EITHER FORBIDDEN OR FACILITATED BY SIGNAGE, | | | STRIPING AND ROADWAY FEATURES SUCH AS FLEXIBLE POLES, | | | MIDDLE RAISED ISLANDS AND CHANNELIZATION. PLEASE REVISE | | | THE SITE PLANS ACCORDINGLY | | | 7) INSTALL AND SHOWCASE STOP BARS AND SIGNS ON EACH | | | GARAGE LEVEL. IT IS RECOMMENDED TO TREAT THE NORTHERN | | | AND SOUTHERN EAST-WEST DRIVE AISLES AS THE MAIN ONES, | | | WHILE THE NORTH-SOUTH AS MINOR | | | 8) DIRECTIONAL ARROW PAVEMENT MARKINGS ARE MISSING. | | | PLEASE INSERT THEM IN THE TRANSPORTATION SITE PLAN | | | THROUGHOUT WERE NEEDED (E.G. RIGHT ARROW FOR THE | | | SOUTHBOUND MOVEMENT, LEFT ARROW FOR THE EASTBOUND | | | MOVEMENT AT THE 23RD AND PINEWOOD INTERSECTION) | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
F |
Date |
10-13-2022 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
10-13-2022 |
Time |
17:05 |
Rev Time |
16.00 |
| Received By |
eschneid |
Date |
10-04-2022 |
Time |
12:17 |
Sent To |
|
|
| Notes |
| 2022-10-13 17:06:05 | CASE NO. 1895 - SEPTEMBER 21, 2022 RESUBMITTAL | | | NORTHWOOD COMMONS - NMUD ANCHOR SITE | | | BROADWAY & 24TH STREET | | | | | | - CONTACT ERIC SCHNEIDER @ (561) 822-1446, | | | [email protected] | | | | | | - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | - WHEN RESUBMITTING, PLEASE PROVIDE THREE (3) PAPER | | | COPIES AND AN ELECTRONIC COPY IN .PDF AND .PNG FORMAT | | | OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE | | | RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS | | | TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | - ONCE THE COMMENTS ARE RESUBMITTED AND DEEMED | | | SUFFICIENTLY ADDRESSED, THE CASE WILL BE SCHEDULED FOR | | | THE NEXT AVAILABLE PLANNING BOARD MEETING. | | | | | | - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT | | | RECEIVED A RESPONSE TO THE COMMENTS WITHIN 60 DAYS FROM | | | THE DATE OF THESE COMMENTS (BY DECEMBER 12, 2022), THE | | | PLANNING DIVISION MAY NOTIFY THE APPLICANT THAT THE | | | CASE IS CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL | | | REQUIRE A NEW DEVELOPMENT APPLICATION. | | | | | | - PLEASE NOTE THAT PREVIOUSLY ISSUED COMMENTS CONTINUE | | | WERE NOT ADDRESSED, SO THE APPLICANT IS ASSESSED A | | | RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF THE ORIGINAL | | | APPLICATION FEE ($600). | | | | | | - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED | | | IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION | | | 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS. | | | | | | THIS APPLICATION WILL BE REVIEWED BY THE PLANNING BOARD | | | AS A SPECIAL REVIEW, WHICH INCLUDES THEIR ABILITY TO | | | GRANT WAIVERS AND VARIANCES. PRIOR TO SCHEDULING A | | | HEARING BEFORE THE PLANNING BOARD AN UPDATED | | | JUSTIFICATION STATEMENT MUST BE PROVIDE FOR EACH WAIVER | | | AND VARIANCE REQUESTED/REQUIRED. ONCE THE FINAL NUMBER | | | OF VARIANCES/WAIVERS IS DETERMINED, THE FEES WILL BE | | | ADJUSTED BASED ON WHAT HAS BEEN PAID TO DATE VS WHAT IS | | | STILL OWED. STAFF ANTICIPATES THAT BASED ON THE NUMBER | | | OF VARIANCES/WAIVERS IDENTIFIED THERE WILL BE | | | ADDITIONAL MONEY OWED TO THE CITY. | | | | | | 1) UPDATED COMMENT: PROVIDE A COPY OF THE TRAFFIC | | | IMPACT STUDY, DATED AUGUST 24, 2022, THAT IS REFERENCED | | | IN THE TPS LETTER ISSUED BY PBC ENGINEERING ON | | | SEPTEMBER 12, 2022. THE LETTER HAS SCALED BACK THE | | | RECOMMENDED CONDITIONS, SPECIFICALLY THE LEFT TURN ON | | | 25TH STREET, THAT WERE IN THE PREVIOUS LETTER AND THE | | | PRIOR TRAFFIC IMPACT ANALYSIS. PLEASE EXPLAIN WHAT | | | CHANGED. STAFF HAS ALSO NOTED THAT THE PROJECT HAS | | | SCALED BACK FROM WHAT IS APPROVED ON THE TPS LETTER - | | | TRAFFIC PERFORMANCE STANDARDS APPROVAL LETTER FROM THE | | | PALM BEACH COUNTY TRAFFIC DIVISION 66,200 SF RETAIL AND | | | 382 DU VS ACTUAL 64,200 SF & 381 DU. | | | | | | 2) UPDATED COMMENT: THANK YOU FOR SHOWING THE | | | RECONFIGURATION OF 23RD STREET TO TWO-WAY WEST OF THE | | | BROADWAY EXTENSION. PLEASE CHECK THE LOCATION OF THE | | | NEW CROSSWALK OF 23RD STREET ON THE EAST END OF THE | | | PROJECT. WHEN COMPARING THE PLANS TO THE AERIAL, THE | | | CROSSWALK IS DIRECTLY INTO THE MIDDLE OF THE DRIVEWAY | | | APRON FOR THE SINGLE-FAMILY HOUSE ON THE SOUTH SIDE OF | | | 23RD STREET, WHICH IS NOT PERMITTED. | | | | | | 3) REPEAT COMMENT: PROVIDE A PREDETERMINATION LETTER | | | FROM FDOT FOR THE IMPROVEMENTS WITHIN THE FDOT | | | RIGHTS-OF-WAY OF BROADWAY AND 24TH AND 25TH STREETS | | | ADJACENT TO THE PROJECT. *** THIS IS REQUIRED PRIOR TO | | | SCHEDULING A PLANNING BOARD HEARING. | | | | | | 4) REPEAT COMMENT: THE UNIT COUNT HAS INCREASED, SO AN | | | UPDATED SCAD IS REQUIRED. | | | | | | 5) BUILDING C: THE CIVIL PLANS INDICATE THAT THERE WILL | | | BE AN ACCESS AND UTILITY EASEMENT WHERE THE CURRENT | | | ALLEY EXISTS. THIS HAS NEVER BEEN DISCUSSED AS BEING | | | ABANDONED. THIS IS ALSO NOT REFLECTED ON THE OTHER | | | DISCIPLINE'S PLANS. | | | | | | 6) UPDATED COMMENT: ELEMENTS OF THE NORTHEAST CORNER OF | | | BUILDING B ENCROACHES INTO THE REQUIRED 10-FOOT PRIMARY | | | A SETBACK FROM BROADWAY. THIS NEEDS TO BE CORRECTED OR | | | A VARIANCE REQUESTED. SHEET A301 STILL SHOWS THE CORNER | | | OF THE BUILDING ON THE 1ST FLOOR ENCROACHING. PLEASE | | | CLARIFY. | | | | | | 7) THE SOUTHEAST CORNER OF BUILDING B IS SHOWN | | | DIFFERENTLY WITH DIFFERING WALL LOCATION AND COLORS | | | HIGHLIGHTING ON THE VARIOUS GROUND FLOOR SHEETS. PLEASE | | | PROVIDE CONSISTENT PLANS AND UPDATED ANY TABLES | | | ACCORDINGLY. | | | | | | 8) UPDATED COMMENT: ZONING INFORMATION TABLE ON SHEET | | | A0.02 BASES THE AVERAGE TOWER FLOOR PLATE ON THE TOTAL | | | SELLABLE SQUARE FOOTAGE, INSTEAD OF ON THE GROSS SQUARE | | | FOOTAGE AS REQUIRED. PLEASE UPDATE THE NUMBERS | | | ACCORDINGLY. SECTION 94-210.I.2.C OF THE NMUD | | | REGULATIONS LIMIT THE TOWER FLOOR PLATE TO 30,000 | | | SQUARE FEET FOR ANY SINGLE FLOORPLATE WITH AND AVERAGE | | | FLOORPLATE OF UP TO 20,000 SQUARE FEET. THE MAXIMUM | | | TOWER FLOORPLATES ARE SHOWN AT 48,335 SQUARE FEET. THE | | | NMUD FLOOR PLATE AVERAGE ONLY APPLIES TO THE TOWER | | | LEVELS OF BUILDING A. PLEASE PROVIDE THE GROSS SQUARE | | | FOOTAGE FOR EACH LEVEL INDIVIDUALLY FOR LEVELS 3-9. THE | | | TABLE ON SHEET A0.03 COMBINES THE INFORMATION FOR | | | LEVELS 3 AND 3.5, WHICH DOES NOT PERMIT STAFF TO | | | CALCULATE THE AVERAGE TOWER FLOOR PLATE SQUARE FOOTAGE. | | | THE INFORMATION ON THE TABLE ON SHEET A0.02 IS | | | INCORRECT. | | | | | | TOWER FLOOR PLATE: 48,335 SQUARE FEET = VARIANCE | | | REQUIRED | | | AVERAGE TOWER FLOOR PLATE: UNABLE TO DETERMINE EXACT | | | AVERAGE; HOWEVER, WILL EXCEED 20,000 SQUARE FEET = | | | VARIANCE REQUIRED | | | | | | 9) THE FLOOR PLAN SHEETS THAT SHOW LEVEL 1.5 FOR | | | BUILDING B ARE NOT ACCURATE (SHEETS A103.1, A104.1, | | | A305.1) WHEN COMPARED TO THE ELEVATION DRAWINGS. | | | BUILDING B HAS NO LEVEL 1.5. THE LEVEL 1.5 PLANS | | | INACCURATELY SHOW THE FLOOR PLAN LAYOUTS FROM LEVEL 2, | | | INCLUDING THE LANDING POINT OF THE PEDESTRIAN BRIDGE. | | | THE AREA FOR LEVEL 1.5 IS THE DOUBLE HIGH CEILING OF | | | LEVEL 1 FOR THE NON-RESIDENTIAL AND THE 2ND FLOOR OF | | | THE TOWNHOUSES. THE INCORRECT LOCATION OF THE | | | PEDESTRIAN BRIDGE RESULTS IN THE LEVEL 2 FLOOR PLAN | | | BEING SHOWN INCORRECTLY. | | | | | | 10) THE FLOOR PLAN SHEETS THAT SHOW LEVEL 1.5 FOR | | | BUILDING C ARE NOT ACCURATE (SHEETS A103.1, A104.1, | | | A305.1) WHEN COMPARED TO THE ELEVATION DRAWINGS. | | | BUILDING B IS NOT PERMITTED TO HAVE A LEVEL 1.5 AS THIS | | | WOULD EXCEED THE ALLOWED NUMBER OF STORIES. THE AREA | | | FOR LEVEL 1.5 IS THE DOUBLE HIGH CEILING OF LEVEL 1 FOR | | | THE NON-RESIDENTIAL PORTION OF THE BUILDING. AS | | | DISCUSSED IN THE LAST MEETING WITH STAFF, THIS ARE IS | | | PERMITTED TO BE A MEZZANINE FOR THE RESIDENTIAL UNITS | | | BUT MAY NOT BE A 2ND FLOOR FOR A TOWNHOUSE PRODUCT. THE | | | INFORMATION TO VERIFY THAT IT COMPLIES WITH THE | | | MEZZANINE REQUIREMENTS MUST BE PROVIDED. | | | | | | 11) THE BUILDING INFORMATION TABLE ON SHEET A0.02 | | | INCORRECTLY LISTS THE STUDIO UNITS AS 500 SQUARE FEET, | | | WHICH WOULD NOT COMPLY WITH NMUD MINIMUM UNIT SIZE. | | | | | | 12) SHEET A200 IS MISSING THE TITLE BLOCK INFORMATION. | | | | | | 13) UPDATED COMMENT: THE ARCHITECTURAL PLANS SHOW A | | | SUPPORT COLUMN ALONG THE EAST SIDE OF NEW PINEWOOD THAT | | | IS NOT SHOWN ON THE LANDSCAPE AND CIVIL PLANS. PLEASE | | | REVIEW AND CORRECT AS NECESSARY. | | | | | | DESIGN STANDARDS | | | | | | 14) UPDATED COMMENT: ACTIVE USE STANDARDS, INCLUDING | | | TRANSPARENCY. THE PROPOSED NMUD CORE CODE AMENDMENT HAS | | | UPDATED THE REQUIREMENTS. STAFF HAS REVIEWED THE | | | BUILDINGS IN LIGHT OF THE NEW REQUIREMENTS AND | | | COMMENTED BELOW. THE STAFF CALCULATIONS ARE BASED ON | | | WHAT COULD BE DETERMINED FROM THE PLAN SHEETS. ACCURATE | | | TABLES MUST BE INCLUDED ON THE PLANS. *** PLEASE NOTE | | | THAT THE TRANSPARENCY/FENESTRATION IS BASED ON THE | | | ACTIVE USES PROVIDED, NOT THE FACADE AREA. THIS WILL | | | NOT HAVE AREAS SUCH AS THE TRASH ROOMS/BOH COUNT | | | AGAINST YOUR TRANSPARENCY REQUIREMENT. HOWEVER, THE | | | FULL HEIGHT OF THE GROUND FLOOR IS COUNTED INTO BOTH | | | CALCULATIONS, SO THE DOUBLE HEIGHT PORTIONS OF | | | BUILDINGS B AND C WHERE THERE IS ACTIVE USE, BUT NO | | | FENESTRATION WILL COUNT AGAINST THE PERCENTAGE | | | PROVIDED. RECOMMENDATION: YOU SHOULD ELABORATE IN YOUR | | | VARIANCE JUSTIFICATION ON THIS AS IT RELATES TO THE | | | ARCHITECTURAL DESIGN OF THESE BUILDINGS. | | | | | | ACTIVE USE: REQUIRED ALONG 23RD STREET, BROADWAY | | | (CORE), 25TH STREET - GROUND FLOOR - 80%, UPPER FLOORS | | | 100% | | | REQUIRED ALONG NEW PINEWOOD - GROUND FLOOR - 30%, | | | UPPER FLOORS - N/A | | | REQUIRED ALONG BROADWAY EXTENSION - GROUND FLOOR - | | | 80%, UPPER FLOORS - N/A | | | REQUIRED ALONG PUBLIC OPEN SPACE - GROUND FLOOR - | | | 75%, UPPER FLOORS - 75% | | | REQUIRED ALONG PUBLIC PASEO - GROUND FLOOR - 80%, | | | UPPER FLOORS - N/A | | | REQUIRED ALONG 24TH STREET, BROADWAY (TRANSITION), | | | NORTHWOOD ROAD - ALL FLOORS 100% | | | | | | BUILDING A ACTIVE USE | | | | | | BROADWAY GROUND FLOOR: 90% COMPLIES | | | BROADWAY UPPER FLOORS: ALL LEVELS 100% COMPLIES | | | 25TH STREET GROUND FLOOR: 94% COMPLIES | | | 25TH STREET LEVELS 1.5 & 2: 11% PROVIDED = VARIANCE | | | REQUIRED SECTION 94-209.2.E.2.B.I. | | | 25TH STREET LEVEL 3 & ABOVE: 100% COMPLIES | | | NEW PINEWOOD EAST: 64% COMPLIES | | | NEW PINEWOOD WEST: 37% COMPLIES | | | PUBLIC OPEN SPACE GROUND FLOOR: 92% COMPLIES | | | PUBLIC OPEN SPACE UPPER FLOORS: 100% COMPLIES | | | PUBLIC PASEO: 100% COMPLIES | | | | | | BUILDING B ACTIVE USE | | | | | | BROADWAY EXTENSION: 100% COMPLIES | | | 23RD STREET GROUND FLOOR: 85% COMPLIES | | | 23RD STREET UPPER FLOORS: 100% COMPLIES | | | NEW PINEWOOD: 100% COMPLIES | | | PUBLIC OPEN SPACE GROUND FLOOR: 97% COMPLIES | | | PUBLIC OPEN SPACE UPPER FLOORS: 100% COMPLIES | | | | | | BUILDING C ACTIVE USE | | | | | | BROADWAY ALL FLOORS: 100% COMPLIES | | | 24TH STREET ALL FLOORS: 100% COMPLIES | | | NORTHWOOD GROUND FLOOR: 92% PROVIDED = VARIANCE | | | REQUIRED SECTION 94-209.2.J.H.I.1 | | | NORTHWOOD UPPER FLOOR: 100% COMPLIES | | | | | | TRANSPARENCY: REQUIRED ALONG 23RD STREET, BROADWAY | | | (CORE), 25TH STREET - GROUND FLOOR NON-RESIDENTIAL - | | | 70%, GROUND FLOOR RESIDENTIAL - 30%, UPPER FLOORS - N/A | | | FOR ALL ACTIVE USE AREAS | | | REQUIRED ALONG NEW PINEWOOD - 50% OF GROUND FLOOR | | | ACTIVE USE AREAS | | | REQUIRED ALONG BROADWAY EXTENSION - 70% OF GROUND | | | FLOOR ACTIVE USE AREAS | | | REQUIRED ALONG PUBLIC OPEN SPACE - 70% OF ALL ACTIVE | | | USE AREAS | | | REQUIRED ALONG PUBLIC PASEO - 70% OF ALL ACTIVE USE | | | AREAS | | | REQUIRED ALONG 24TH STREET, BROADWAY (TRANSITION), | | | NORTHWOOD ROAD - GROUND FLOOR NON-RESIDENTIAL - 70%, | | | UPPER FLOORS - N/A FOR ALL ACTIVE USE AREAS | | | | | | BUILDING A TRANSPARENCY | | | | | | BROADWAY GROUND FLOOR: 100% COMPLIES | | | 25TH STREET GROUND FLOOR: 100% COMPLIES | | | NEW PINEWOOD EAST: APPEARS TO EXCEED 50%, BUT NO | | | TABULAR/GRAPHIC INFORMATION PROVIDED | | | NEW PINEWOOD WEST: APPEARS TO EXCEED 50%, BUT NO | | | TABULAR/GRAPHIC INFORMATION PROVIDED | | | PUBLIC OPEN SPACE GROUND FLOOR: 100% COMPLIES | | | PUBLIC OPEN SPACE UPPER FLOORS: TABULAR/GRAPHIC | | | INFORMATION REQUIRED FOR LEVELS 1.5 AND 2 ONLY | | | PUBLIC PASEO: APPEARS TO EXCEED 70%, BUT NO | | | TABULAR/GRAPHIC INFORMATION PROVIDED | | | | | | THE NON-ACTIVE USE AREAS ON THE BUILDING A FENESTRATION | | | DRAWINGS NEED TO BE SHOWN EXCLUDED FROM THE TABLE AND | | | DRAWINGS. | | | | | | THE FENESTRATION TABLE INCORRECTLY LISTS THE NORTH | | | ELEVATION OF BUILDING A AS HAVING NO FENESTRATION. THE | | | 100% IS SHOWN UNDER THE SOLID COLUMN. | | | | | | BUILDING B TRANSPARENCY | | | | | | BROADWAY EXTENSION GROUND FLOOR: SEE COMMENTS BELOW | | | VARIANCE REQUIRED SECTION 94-210.M.5 | | | 23RD STREET GROUND FLOOR: SEE COMMENTS BELOW VARIANCE | | | REQUIRED SECTIONS 94-210.P.1.II & III | | | NEW PINEWOOD GROUND FLOOR: 46% PROVIDED = VARIANCE | | | REQUIRED SECTION 94-210.M.4 | | | PUBLIC OPEN SPACE GROUND FLOOR: 47% PROVIDED = VARIANCE | | | REQUIRED SECTION 94-210.K.1.N | | | PUBLIC OPEN SPACE UPPER FLOORS: 28% PROVIDED = VARIANCE | | | REQUIRED SECTION 94-210.K.1.N | | | | | | BUILDING B COMMENTS | | | I. BROADWAY EXTENSION (EAST ELEVATION). THE EAST | | | ELEVATION FRONTS ON BROADWAY EXTENSION, WHICH REQUIRES | | | A MINIMUM OF 70% OF THE ACTIVE USE TO BE HAVE | | | TRANSPARENCY. THE TABLE LISTS 48% GROUND FLOOR | | | TRANSPARENCY, YET THE ELEVATION DRAWING DOES NOT MATCH | | | THE SITE PLAN AND DOES NOT SHOW THE FULL EXTENT OF THE | | | OF THE SOUTHEAST CORNER OF THE BUILDING. *** VARIANCE | | | REQUIRED | | | II. 23RD STREET GROUND FLOOR (SOUTH ELEVATION). THE NEW | | | REGULATIONS SEPARATE THE REQUIREMENTS FOR | | | NON-RESIDENTIAL (MIN 70%) AND RESIDENTIAL (30%). SINCE | | | THIS FACADE HAS BOTH, PLEASE PROVIDE THE TABLE | | | ACCORDINGLY. IT APPEARS THAT THE RESIDENTIAL PORTION OF | | | THE BUILDING WILL MEET CODE; HOWEVER, THE | | | NON-RESIDENTIAL LOOKS LOW (DUE TO THE DOUBLE HEIGHT | | | FLOOR) AND WOULD REQUIRE A VARIANCE. STAFF NEEDS THE | | | FINAL NUMBER TO PROCEED TO THE PLANNING BOARD. PLEASE | | | REMEMBER THAT THE TRANSPARENCY IS A PERCENTAGE OF THE | | | ACTIVE USE, SO THE BOH AND TRASH ROOMS WOULD NOT BE | | | INCLUDED AS THE BASE ACTIVE USE AREA. *** VARIANCE | | | REQUIRED | | | | | | BUILDING C TRANSPARENCY | | | | | | BROADWAY GROUND FLOOR: 49% PROVIDED = VARIANCE REQUIRED | | | SECTION-209.2.J.1.H.I.4 | | | 24TH STREET GROUND FLOOR: 52% PROVIDED = VARIANCE | | | REQUIRED SECTION-209.2.J.1.H.I.4 | | | NORTHWOOD GROUND FLOOR: 43% PROVIDED = VARIANCE | | | REQUIRED SECTION-209.2.J.1.H.I.4 | | | | | | 15) UPDATED COMMENT: STAFF HAS REVIEWED THE INFORMATION | | | PROVIDED FOR THE PLANAR BREAKS AND HAD THE FOLLOWING | | | COMMENTS. | | | | | | BUILDING A PLANAR BREAKS | | | | | | BROADWAY GROUND FLOOR: 21% COMPLIES | | | BROADWAY LEVEL 1.5: 13% THAT IS A MINIMUM OF 3 FEET IN | | | DEPTH (PASEO) *** ADDITIONAL 35% OF THE FRONTAGE HAS A | | | PLANAR BREAK THAT DOES NOT COMPLY WITH THE MINIMUM | | | 3-FOOT DEPTH = VARIANCE REQUIRED SECTION 94-209.2.J.1.A | | | BROADWAY LEVEL 2: 42% COMPLIES *** DOES NOT COMPLY WITH | | | THE MINIMUM 3-FOOT DEPTH = VARIANCE REQUIRED SECTION | | | 94-209.2.J.1.A | | | BROADWAY LEVELS 3 & ABOVE: ALL LEVELS 43% COMPLIES | | | 25TH STREET GROUND FLOOR: 21% COMPLIES | | | 25TH STREET LEVELS 1.5 & 2: 52% COMPLIES *** DOES NOT | | | COMPLY WITH THE MINIMUM 3-FOOT DEPTH = VARIANCE | | | REQUIRED SECTION 94-209.2.J.1.A | | | 25TH STREET LEVEL 3 & ABOVE: 50% COMPLIES | | | | | | BUILDING B PLANAR BREAKS | | | | | | 23RD STREET GROUND FLOOR: 24% COMPLIES | | | 23RD STREET UPPER FLOORS: 43% COMPLIES | | | | | | BUILDING C PLANAR BREAKS | | | | | | BROADWAY GROUND FLOOR: ** THIS IS INCORRECTLY | | | CALCULATED; HOWEVER, SINCE THE ALLEY GAP IS 28% OF THE | | | FRONTAGE, THE PLANAR BREAK COMPLIES. | | | BROADWAY LEVELS 2 & 3: ** THIS IS INCORRECTLY | | | CALCULATED, BOTH THE LENGTH OF THE BUILDING AND WHAT IS | | | A PLANAR BREAK. THE ONLY PLANAR BREAK IS AT THE SOUTH | | | END AT THE ANGLE AND RESULTS IN AN APPROXIMATELY 3% | | | PLANAR BREAK. SECTION 94-209.2.J.1.A | | | | | | 16) UPDATED COMMENT: PLANAR BREAKS ARE REQUIRED TO BE A | | | MINIMUM OF THREE FEET IN DEPTH. THE DEPTH SHOWN FOR THE | | | PLANAR BREAKS ON LEVELS 1.5 AND 2 OF BUILDING A ALONG | | | 25TH STREET AND BROADWAY ARE ONLY 1.6 FEET IN DEPTH, | | | WHICH REQUIRES THE APPROVAL OF A VARIANCE. STAFF IS NOT | | | PREPARED TO SUPPORT THE NEEDED VARIANCE REQUEST ALONG | | | 25TH STREET. THE SUGGESTIONS MADE BY ANA MARIA APONTE, | | | CRA DEPUTY DIRECTOR, TO LESSEN THE VARIANCES THAT WOULD | | | BE NEEDED WERE NOT IMPLEMENTED, SO THE STANDARD THAT | | | THE, "VARIANCE GRANTED IS THE MINIMUM VARIANCE THAT | | | WILL MAKE POSSIBLE THE REASONABLE USE OF THE LAND, | | | BUILDING, OR STRUCTURE", HAS NOT BEEN MET. | | | | | | STREETSCAPE | | | | | | 17) REPEAT COMMENT: THANK YOU FOR PROVIDING THE LIGHT | | | POLE LOCATIONS ON THE SITE PLAN; HOWEVER, THERE IS ONE | | | THAT IS IN DIRECT CONFLICT WITH A TREE AND MULTIPLE | | | THAT ARE SHOWN IN PARKING SPACES AND THE TRAVEL LANE | | | (ON ALL PLANS). THE POLES NEED TO BE SHOWN IN THE | | | CORRECT LOCATION. | | | | | | 18) THE POLE TYPE ALONG 25TH STREET NEEDS TO BE THE "S" | | | TYPE TO MATCH THE POLES ON 25TH STREET EAST OF | | | BROADWAY. | | | | | | 19) THE CRA MUST APPROVE THE USE OF TWO DIFFERENT POLE | | | STYLES ALONG BROADWAY BETWEEN 25TH STREET AND 23RD | | | STREET. THEY ARE CURRENTLY "T" TYPE. | | | | | | PARKING/LOADING | | | | | | 20) REPEAT COMMENT: PROVIDE VEHICLE TURNING RADIUS | | | DRAWING FOR MOVING TRUCKS INTO/OUT OF THE LOADING | | | AREAS. **** SHEET C4.02 ONLY SHOWS A MOVING TRUCK | | | ACCESSING PINEWOOD, BUT NOT THE ACTUAL LOADING AREAS. | | | | | | 21) THE PARKING REQUIRED AND PROVIDED TABLES AND THE | | | TOTAL PARKING SPACES LINE BOTH CONTAIN ERRORS. | | | | | | A. SHEETS A103.1 AND SHEET A301.5 - THERE ARE ONLY 233 | | | PARKING SPACES, NOT 235 ON THIS LEVEL. ALSO ON SHEET | | | A301.5 THE PARKING SPACE TYPE BREAKDOWN IS INCORRECT. | | | B. THE L1.5 CRA LINE STATES THAT THERE ARE SPACES, BUT | | | ONE OF THEM IS A DOUBLE COUNTED ADA SPACE THAT IS SHOWN | | | IN THE ADA LINE. | | | C. THE L1.5 PUBLIC PARKING LINE STATES THAT THERE ARE | | | 108 PARKING SPACES, WHEN THERE ARE 109 LABELED. | | | D. SHEET A302 LISTS AN INCORRECT NUMBER OF PARKING | | | SPACES. | | | E. THE PARKING REQUIRED TABLE INCORRECTLY LISTS 384 | | | SPACES PROVIDED FOR THE RESIDENTIAL, WHEN 403 ARE | | | PROVIDED AND 181 SPACES PROVIDED FOR THE COMMERCIAL, | | | WHEN ONLY 128 ARE PROVIDED. | | | F. ENSURE ALL TABLES AND INFORMATION ON ALL SHEETS | | | SHOWS CONSISTENT, ACCURATE INFORMATION. | | | | | | 22) THERE ARE SEVEN PARKING SPACES ON LEVEL 2 THAT SHOW | | | COLUMN ENCROACHMENTS, WHICH ARE NOT PERMITTED. | | | | | | 23) THANK YOU FOR PROVIDING THE DIMENSIONS FOR THE | | | PARKING SPACES ALONG WALLS. THERE IS ONE PP SPACE AT | | | THE NORTHWEST CORNER OF LEVEL 1.5 THAT DOES NOT HAVE | | | THE EXTRA ROOM. THIS SPACE NEEDS TO BE MARKED AS | | | COMPACT AND THE PARKING TABLE UPDATED WITH IT AS A LINE | | | ITEM. NOTE: IF AT TIME OF CONSTRUCTION/PARKING SPACE | | | STRIPING ADDITIONAL SPACES ARE IDENTIFIED AS LESS THAN | | | A FOOT FROM THE WALL, THEY WILL ALSO NEED TO BE MARKED | | | AS COMPACT WITH AN AMENDMENT TO THE SITE PLAN AT THAT | | | TIME. | | | | | | 24) THERE ARE 19 PARKING SPACES (18 PP & 1 ADA) LOCATED | | | OUTSIDE OF THE GATES ON LEVEL 1.5 THAT APPEAR TO BE THE | | | GUEST PARKING SPACES. PLEASE LABEL THESE AS THE GUEST | | | SPACES ON THE PLANS. NOTE: THE NON-ADA SPACES WILL NEED | | | TO BE MARKED AS GUEST WHEN CONSTRUCTED. | | | | | | 25) SHEETS A103.1 AND A301.5 SHOW DIFFERING LOCATIONS | | | FOR THE ADA VAN SPACES. ALL SHEETS NEED TO SHOW THE | | | SAME CONDITION. PLEASE MAKE SURE THAT THE ADA GUEST | | | SPACE IS AN ADA VAN SPACE SO THAT THERE IS ONE ADA VAN | | | SPACE AVAILABLE OUTSIDE THE GATED AREA. | | | | | | 26) THE PARKING SPACES TYP DETAIL SHOWS COLUMNS IN THE | | | PARKING SPACES, WHICH IS NOT PERMITTED. THE DETAIL | | | NEEDS TO BE CORRECTLY SHOWN. | | | | | | 27) THE ADA PARKING SPACE DETAIL CONTAINS A BLOW UP OF | | | THE SPACE BETWEEN THE STRIPING THAT DOES NOT CONFORM TO | | | CITY CODE. THE CITY REQUIRES 12 INCHES BETWEEN THE | | | STRIPES. A DETAIL CAN BE PROVIDED IF NEEDED. | | | | | | 28) REPEAT COMMENT: THANK YOU FOR PROVIDING THE BICYCLE | | | RACK MODEL DETAIL AND DIMENSIONS THAT WILL BE USED IN | | | THE BICYCLE STORAGE ROOMS. THIS MODEL NEEDS TO BE SHOWN | | | IN THE BICYCLE STORAGE ROOMS TO INCLUDE THE DIMENSIONS | | | OF THE ROOM AND THE RACKS IN THE ROOM. **** THE BICYCLE | | | ROOM DETAILS DO NOT SHOW THE SAME RACK OR THE | | | DIMENSIONS THAT ARE ON THE DETAIL. ADDITIONALLY, STAFF | | | ATTEMPTED TO CALCULATE THE NUMBER OF BICYCLES THAT | | | COULD BE STORED, AND THEY DO NOT MATCH THE NUMBER OF | | | RACKS IN EITHER THE RESIDENTIAL OR THE COMMERCIAL | | | ROOMS. | | | | | | 29) UPDATED COMMENT: THANK YOU FOR SHOWING BICYCLE | | | FACILITIES AT 13 LOCATIONS (MOSTLY IN GROUPS OF THREE | | | RACKS FOR SIX BICYCLES AT EACH LOCATION) THROUGHOUT THE | | | SITE AS WELL AS THE POST AND HITCH MODEL. PLEASE | | | PROVIDE THE PAD DETAIL SHOWING THE DIMENSIONS BASED ON | | | THE NUMBER OF POSTS THAT WILL BE INSTALLED. THE PAD | | | DETAIL MUST INCLUDE THE RACK(S) AND THE DIMENSIONS FROM | | | THE RACKS TO THE EDGE OF THE PAD. ADDITIONALLY, | | | DIMENSIONED PAD BOX NEEDS TO BE INCLUDED ON THE PLAN SO | | | THAT STAFF CAN VERIFY THAT PARKED BICYCLES WILL NOT | | | IMPEDE THE PEDESTRIAN TRAVEL PATHS OR BE WITHIN A | | | LANDSCAPE ISLAND OR OTHERWISE HAVE NONFUNCTIONING | | | BICYCLE PARKING. FOR CLARITY THIS DETAIL SHALL BE | | | PROVIDED AT A BIGGER SCALE. STAFF HAS NOTED THAT THE | | | HARDSCAPE DETAIL PLAN CALLS OUT A QUANTITY OF 10 POSTS, | | | WHICH WOULD NOT PERMIT THE INSTALLATION OF BICYCLE | | | PARKING AT ALL THE LOCATION SHOWN NOR AT THE QUANTITY | | | OF BICYCLE PARKING SHOWN. | | | | | | LANDSCAPE | | | | | | 30) THE PUBLIC OPEN SPACE DIAGRAMS ARE NOT CORRECTLY | | | DEPICTED AND DO NOT CLEARLY SHOW COMPLIANCE WITH THE | | | PUBLIC OPEN SPACE REQUIREMENTS. STAFF WILL PROVIDE A | | | MARK-UP UNDER SEPARATE COVER HIGHLIGHTING WHAT NEEDS TO | | | BE SHOWN. | | | | | | 31) THE MINIMUM 10% PERVIOUS REQUIREMENT IS NOT SHOWN | | | AS BEING MET ON THE LANDSCAPE PLAN FOR BOTH THE | | | BUILDING A & B PARCEL AND THE BUILDING C PARCEL. WHILE | | | BUILDING C IS A CONSTRAINED SITE, THE PROVISION OF THE | | | PUBLIC OPEN SPACE, THE BUFFER ALONG THE RAILROAD TRACK | | | AND THE AREA ON THE EAST SIDE OF THE BROADWAY EXTENSION | | | SEEM TO OFFER SUFFICIENT AREA TO MEET THE 10% MINIMUM. | | | IF THERE IS INSUFFICIENT DIRECT PERVIOUS AREA DUE TO | | | LANDSCAPE, YOU WILL NEED TO INSTALL A PERVIOUS PAVER | | | SYSTEM TO GET TO THE MINIMUM 10%. BUILDING C = VARIANCE | | | REQUIRED SECTION 94-210.I.3. PLANNING STAFF DOES NOT | | | SUPPORT WAIVING THE MINIMUM PERVIOUS SURFACE | | | REQUIREMENT FOR BUILDING A & C. | | | | | | WAIVERS/VARIANCES | | | | | | 32) SECTION 94-209.2.J.1.A - THE MAXIMUM HORIZONTAL | | | DIMENSION OF A BUILDING WITHIN THE MIXED-USE DISTRICTS | | | IS 250 FEET. BUILDING A EXCEEDS THIS ON ALL FRONTAGES. | | | STAFF IS UNABLE TO LOCATE THE FULL NORTH/SOUTH | | | DIMENSION FOR LEVEL 2 AS THIS IS THE LARGEST | | | FLOORPLATE. PLEASE CLEARLY PROVIDE ON ONE OF THE LEVEL | | | 2 SITE PLANS. **** VARIANCE REQUIRED. | | | | | | 33) SECTION 94-210.I.3.A - THE MAXIMUM LOT WIDTH FOR | | | FLEX BUILDINGS IS 200 FEET AND TOWER BUILDINGS IS 250 | | | FEET. | | | | | | BROADWAY LOT WIDTH: 554.75 FEET = VARIANCE REQUIRED. | | | | | | 34) SECTION 94-209.2.K.1 - THE MAXIMUM BLOCK LENGTH IS | | | 600 FEET. THE CURRENT BLOCK LENGTH IS 810 FEET (SPRUCE | | | TO PINEWOOD) WITH THE ABANDONMENT OF PINEWOOD EXTENDING | | | THIS TO 965 FEET AT ITS FURTHEST POINT WEST AT 25TH | | | STREET AND THE FEC RR. | | | | | | EAST/WEST BLOCK LENGTH: 965 FEET = VARIANCE REQUIRED. | | | | | | 35) SECTION 94-209.2.K.2 - THE MAXIMUM BLOCK PERIMETER | | | LENGTH IS 1,900 FEET. THE ABANDONMENT OF THE | | | RIGHTS-OF-WAY RESULT IN A BLOCK WITH A PERIMETER OF | | | SPRUCE, 23RD, FEC RR, 25TH, BROADWAY AND NORTHWOOD THAT | | | IS 2,192 FEET IN LENGTH. | | | | | | 36) SECTION 94-210.I.2.B - A SETBACK OF 15 FEET FROM | | | THE ALLEY IS REQUIRED FOR BUILDING C. THIS IS MET ON | | | THE GROUND FLOOR BUT NOT ON THE UPPER FLOORS WHERE THE | | | PLANS SHOW THE BUILDING STRADDLING THE ALLEY. | | | | | | 37) CONDITION: ACCESS EASEMENT REQUIRED FOR ANY | | | PORTIONS OF SIDEWALKS ON PRIVATE PROPERTY AND THE | | | ROADWAYS TRAVERSING THE SITE AND THE PARKING SPACES ON | | | PRIVATE PROPERTY. | | | | | | 38) CONDITION: AREAL EASEMENT REQUIRED WHERE BUILDING C | | | STRADDLES THE ALLEY. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
08-17-2022 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
08-17-2022 |
Time |
15:33 |
Rev Time |
16.00 |
| Received By |
eschneid |
Date |
08-08-2022 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2022-08-17 15:33:49 | CASE NO. 1895 ? JULY 19, 2022 RESUBMITTAL | | | NORTHWOOD COMMONS - NMUD ANCHOR SITE | | | BROADWAY & 24TH STREET | | | | | | - CONTACT ERIC SCHNEIDER @ (561) 822-1446, | | | [email protected] | | | | | | - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | - WHEN RESUBMITTING, PLEASE PROVIDE THREE (3) PAPER | | | COPIES AND AN ELECTRONIC COPY IN .PDF AND .PNG FORMAT | | | OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE | | | RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS | | | TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | - ONCE THE COMMENTS ARE RESUBMITTED AND DEEMED | | | SUFFICIENTLY ADDRESSED, THE CASE WILL BE SCHEDULED FOR | | | THE NEXT AVAILABLE PLANNING BOARD MEETING. | | | | | | - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT | | | RECEIVED A RESPONSE TO THE COMMENTS WITHIN 60 DAYS FROM | | | THE DATE OF THESE COMMENTS (BY OCTOBER 17, 2022), THE | | | PLANNING DIVISION MAY NOTIFY THE APPLICANT THAT THE | | | CASE IS CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL | | | REQUIRE A NEW DEVELOPMENT APPLICATION. | | | | | | - PLEASE NOTE THAT PREVIOUSLY ISSUED COMMENTS CONTINUE | | | WERE NOT ADDRESSED, SO THE APPLICANT IS ASSESSED A | | | RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF THE ORIGINAL | | | APPLICATION FEE ($600). | | | | | | - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED | | | IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION | | | 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS. | | | | | | THE PROPOSED DEVELOPMENT REQUIRES AMENDMENTS TO THE | | | ZONING AND LAND DEVELOPMENT REGULATIONS, WHICH MUST BE | | | ADOPTED PRIOR TO THE FINAL SITE PLAN APPROVAL. THE | | | RECENTLY ADOPTED CHANGE TO THE NMUD APPROVAL PROCESS | | | WILL SEE THIS APPLICATION BE REVIEWED BY THE PLANNING | | | BOARD AS A SPECIAL REVIEW, WHICH INCLUDES THEIR ABILITY | | | TO GRANT WAIVERS AND VARIANCES. STAFF HAS IDENTIFIED | | | MORE THAN THE THREE LISTED ON SHEET A0.02. NO | | | JUSTIFICATION WAS PROVIDED FOR EACH WAIVER AND VARIANCE | | | REQUESTED/REQUIRED. UNTIL ALL INFORMATION IS PROVIDED, | | | STAFF IS WITHHOLDING DETERMINATION ON SUPPORT/NOT | | | SUPPORT OF EACH INDIVIDUAL WAIVER AND VARIANCE. | | | | | | 1) UPDATED COMMENT: PROVIDE A REVISED TRAFFIC | | | PERFORMANCE STANDARDS APPROVAL LETTER FROM THE PALM | | | BEACH COUNTY TRAFFIC DIVISION FOR THE SCOPE OF THE | | | PROPOSED DEVELOPMENT BASED ON THE UPDATED PLANS AND | | | TRAFFIC IMPACT ANALYSIS (66,200 SF RETAIL AND 381 DU). | | | THE TRAFFIC LETTER NEEDS TO REFLECT THAT THE ANCHOR | | | SITE PROJECT BOUNDARIES ARE NOT VACANT, BUT THAT THE | | | CONTAIN BUILDINGS (3) AS SHOWN ON THE SURVEY. *** THE | | | LATEST TIA SHOWS THE NEW USE MIX HAVING LESS IMPACT | | | THAN WHAT THE CURRENT TPS LETTER, DATED MAY 13, 2022, | | | SHOWS; HOWEVER, THAT UNDER THE NEW SPECIAL REVIEW | | | PROCESS, THE PLANNING BOARD IS THE APPROVING AUTHORITY, | | | SO THE TPS LETTER IS REQUIRED PRIOR TO SCHEDULING THE | | | CASE BEFORE THE PLANNING BOARD. | | | | | | 2) THE PLANS DO NOT SHOW THE FOLLOWING ITEMS THAT ARE | | | LISTED IN THE TRAFFIC IMPACT ANALYSIS: | | | | | | A. ADDITION OF 80-FOOT EASTBOUND AND WESTBOUND LEFT | | | TURN LANES ON 25TH STREET, AT THE INTERSECTION OF 25TH | | | STREET AND PINEWOOD AVENUE. | | | B. CONVERSION OF 23RD STREET FROM ONE-WAY FLOW TO | | | TWO-WAY FLOW BETWEEN PINEWOOD AVENUE AND THE PROPOSED | | | BROADWAY EXTENSION. | | | | | | 3) REPEAT COMMENT: PROVIDE A PREDETERMINATION LETTER | | | FROM FDOT FOR THE IMPROVEMENTS WITHIN THE FDOT | | | RIGHTS-OF-WAY OF BROADWAY AND 24TH AND 25TH STREETS | | | ADJACENT TO THE PROJECT. *** THIS IS REQUIRED PRIOR TO | | | SCHEDULING A PLANNING BOARD HEARING. | | | | | | 4) THE UNIT COUNT HAS INCREASED, SO AN UPDATED SCAD IS | | | REQUIRED. | | | | | | 5) BUILDING C: PLANNING STAFF HAS NOTED THAT THE | | | COMMENT BY THE CITY SURVEYOR REQUIRING 25-FOOT | | | CLEARANCE OVER THE ALLEY HAS NOT BEEN MET. THIS | | | CLEARANCE IS REQUIRED SO THAT THERE IS ADEQUATE | | | CLEARANCE FOR ANY UTILITY MAINTENANCE WITHIN THE ALLEY. | | | PLEASE REMEMBER THAT THE MAXIMUM FIRST STORY HEIGHT IS | | | 20 FEET. | | | | | | 6) ELEMENTS OF THE NORTHEAST CORNER OF BUILDING B | | | ENCROACHES INTO THE REQUIRED 10-FOOT PRIMARY A SETBACK | | | FROM BROADWAY. THIS NEEDS TO BE CORRECTED OR A VARIANCE | | | REQUESTED. | | | | | | 7) THE WAIVER/VARIANCE TABLE ON SHEET A0.02 NEEDS TO | | | CORRECTLY SHOW THAT THE MAXIMUM AVERAGE FLOORPLATE IS | | | DEPENDENT ON THE TOWER'S PRIMARY USE, WHICH IS | | | RESIDENTIAL - 30,000 SQUARE FEET FOR ANY SINGLE | | | FLOORPLATE WITH AND AVERAGE FLOORPLATE OF UP TO 20,000 | | | SQUARE FEET. | | | | | | 8) THE BUILDING B ELEVATION DRAWINGS SHOW THE | | | PEDESTRIAN BRIDGE WITH A BASE ELEVATION OF 20 FEET IN | | | LINE WITH LEVEL 2; HOWEVER, THE BUILDING A ELEVATION | | | DRAWINGS SHOW THE PEDESTRIAN BRIDGE WITH A BASE | | | ELEVATION OF 27 FEET. PLEASE PROVIDE THE CROSS SLOPES | | | SO THAT ADA COMPLIANCE CAN BE VERIFIED. | | | | | | DESIGN STANDARDS | | | | | | 9) UPDATED COMMENT: ACTIVE USE STANDARDS - | | | | | | A. BUILDING B - THE ELEVATION LABELS AND THE SCALE ARE | | | INCORRECT ON SHEET A101.2. BY DEFINITION, THE ENTIRE | | | GROUND FLOOR IS DEFINED AS STOREFRONT, REGARDLESS OF | | | THE USE; THEREFORE, THE RESIDENTIAL PORTION OF THE | | | BUILDING MUST BE INCLUDED IN THE STOREFRONT GLAZING | | | CALCULATIONS. | | | B. BUILDING C - THE RESIDENTIAL PORTION OF THE BUILDING | | | MUST BE INCLUDED IN THE STOREFRONT GLAZING | | | CALCULATIONS. THE NORTHWEST CORNER NEEDS TO BE | | | INCLUDED. THE EAST ELEVATION TABLE INFORMATION IS | | | BACKWARDS (NOT 100% FENESTRATION). | | | C. CODE TEXT WILL INCLUDE CLARIFICATION THAT ACTIVE | | | USES ARE NOT REQUIRED ALONG THE RR. | | | | | | 10) UPDATED COMMENT: SECTION 94-209.J.A. REQUIRES THE | | | PROVISION OF PLANAR BREAKS FOR FRONTAGES EXCEEDING 150 | | | FEET IN LENGTH. THE PLANAR BREAK CALCULATIONS FOR THE | | | FRONTAGES OF BUILDINGS B AND C THAT EXCEED 150 FEET | | | WERE NOT PROVIDED. THE PLANAR BREAK CALCULATIONS WERE | | | NOT PROVIDED FOR THE GROUND FLOOR OF BUILDING A. PLANAR | | | BREAKS ARE REQUIRED, REGARDLESS OF THIS BEING | | | STOREFRONT. | | | | | | 11) PLANAR BREAKS ARE REQUIRED TO BE A MINIMUM OF THREE | | | FEET IN DEPTH. THE DEPTH SHOWN FOR THE PLANAR BREAKS ON | | | LEVELS 1.5 AND 2 OF BUILDING A ALONG 25TH STREET AND | | | BROADWAY ARE ONLY 1.6 FEET IN DEPTH, WHICH REQUIRES THE | | | APPROVAL OF A VARIANCE. STAFF IS NOT PREPARED TO | | | SUPPORT THIS VARIANCE REQUEST AS NO JUSTIFICATION HAS | | | BEEN PROVIDED FOR WHY THESE CANNOT MEET THE MINIMUM | | | REQUIREMENT. IF THE PLAN IS TO PROCEED WITH A VARIANCE | | | REQUEST, THEN YOU MUST PROVIDE NOT ONLY THE | | | JUSTIFICATION FOR THE VARIANCE, BUT ALSO BETTER DETAILS | | | AS TO WHAT THE ELEVATIONS WILL LOOK LIKE IF THE | | | VARIANCE IS APPROVED, TO INCLUDE THE SPECIFIC | | | ARCHITECTURAL TREATMENT THAT WILL OFFSET THE REDUCED | | | DEPTH DIMENSION. | | | | | | 12) REPEAT COMMENT: PROVIDE THE DIMENSIONS OF THE | | | PROJECTIONS AND ENCROACHMENTS (EX. BALCONIES AND OTHER | | | ARCHITECTURAL FEATURES) ON THE PLANS AND ELEVATIONS SO | | | THAT STAFF CAN VERIFY COMPLIANCE WITH THE NMUD | | | REGULATIONS. THIS HAS NOT BEEN PROVIDED FOR ALL THE | | | FACADES ON ALL THE BUILDINGS. **** THE FOLLOWING ARE | | | FEATURES THAT DID NOT HAVE DIMENSIONS PROVIDED. ANY | | | FEATURES THAT DO NOT MEET MINIMUM OR MAXIMUM | | | ENCROACHMENT ALLOWANCE WILL REQUIRE A VARIANCE. | | | | | | A. THE NORTH AND EAST ELEVATION DRAWINGS FOR BUILDING A | | | CALL OUT AN ALUMINUM CANOPY ON THE UPPER PORTION OF THE | | | GROUND LEVEL; HOWEVER, NO DETAILS OF THIS CANOPY, TO | | | INCLUDE DIMENSIONS, ARE PROVIDED SO THAT STAFF CAN | | | VERIFY CODE COMPLIANCE. ADDITIONALLY, THE CANOPY IS NOT | | | SHOWN ON THE SIDES OF THESE ELEVATION DRAWINGS | | | EXTENDING FROM THE BUILDING. | | | B. THE BALCONY THAT WRAPS BUILDING B. | | | C. THE CANOPY ON BUILDING C. NOTE: THE CANOPY IS SHOWN | | | ON THE ELEVATION DRAWINGS, BUT NOT THE SITE/FLOOR | | | PLANS. ADDITIONALLY, IT IS SHOWN ENCROACHING INTO THE | | | RIGHT-OF-WAY. | | | | | | 13) THE AREA WITH THE UNITS SUPPORTED OVER THE | | | ABANDONED PORTION OF NORTHWOOD ROAD IS LABELED AS A | | | COLONNADE. PLEASE REMOVE THIS NOMENCLATURE AS BY THE | | | NMUD REGULATIONS THIS DOES NOT MEET THE COLONNADE | | | ALLOWANCES, SPECIFICALLY, THE DEPTH EXCEEDS THE HEIGHT | | | AND COLONNADES ARE NOT PERMITTED TO HAVE ENCLOSED USED | | | ABOVE. | | | | | | 14) SECTION 94-209.2.J.1.H REQUIRES ARCHITECTURAL | | | FEATURES OR ARCHITECTURAL TREATMENT ON ALL FACADE | | | ELEVATIONS. THE BLANK WALL SHOWN ON THE EAST ELEVATION | | | OF BUILDING C IS NOT PERMITTED. | | | | | | 15) AS PART OF THE REALIGNMENT OF PINEWOOD AS A PRIVATE | | | DRIVE, STAFF WILL BE ADDING THE FOLLOWING PROVISION TO | | | THE NMUD REGULATIONS TO ENSURE THAT ACTIVE USES AND | | | TRANSPARENCY ARE MAINTAINED ALONG THE DRIVE. PLEASE | | | PROVIDE THE DIMENSIONS ALONG THE WEST SIDE OF NEW | | | PINEWOOD TO VERIFY THAT THE LANGUAGE MATCHES THE | | | PROPOSED BUILDING DESIGN. | | | | | | "THE REALIGNED PORTION OF PINEWOOD AVENUE SHALL HAVE A | | | MINIMUM OF 60 FEET BETWEEN BUILDING FACADES AND THE | | | TRAVEL LANES SHALL NOT TOTAL MORE THAN 20 FEET IN | | | WIDTH. SIDEWALKS AND ON-STREET PARKING SHALL BE | | | PROVIDED. A MINIMUM OF 50 PERCENT OF THE BUILDING | | | FRONTAGES ALONG EACH SIDE THE REALIGNED PORTION OF | | | PINEWOOD AVENUE SHALL CONFORM TO THE GROUND FLOOR | | | ACTIVE USE REQUIREMENTS." | | | | | | 16) ACCESS EASEMENT REQUIRED FOR ANY PORTIONS OF | | | SIDEWALKS ON PRIVATE PROPERTY AND THE ROADWAYS | | | TRAVERSING THE SITE AND THE PARKING SPACES ON PRIVATE | | | PROPERTY. | | | | | | 17) SHEET A400 CUTS OFF THE ELEVATION HEIGHT DIMENSIONS | | | UNDER THE TITLE BLOCK. PLEASE REVISE. | | | | | | 18) THE BUILDING A ELEVATION DRAWINGS FAIL TO SHOW THE | | | COLUMNS/BALCONY SEPARATORS THAT ARE SHOWN ON THE FLOOR | | | PLANS RUNNING THE FULL HEIGHT OF THE BUILDING. NOTE: | | | THE RENDERINGS AND THE ELEVATION DRAWINGS FOR BUILDING | | | A SHOW A NUMBER OF DIFFERENCES. | | | | | | STREETSCAPE | | | | | | 19) UPDATED COMMENT: THE SITE PLAN NEEDS TO SHOW THE | | | ABOVE GROUND UTILITIES AND SITE FEATURES SUCH AS THE | | | FIRE HYDRANTS, LIGHT POLES, VERIZON POLE, BOLLARDS, | | | ETC. TO ACCURATELY REFLECT THE SITE CONDITIONS. | | | | | | 20) REPEAT COMMENT: NO DETAILS WERE PROVIDED ON THE | | | SITE LIGHTING TO VERIFY COMPLIANCE WITH THE NMUD | | | REGULATIONS. *** THIS IS REQUIRED PRIOR TO SCHEDULING A | | | PLANNING BOARD HEARING SO THAT STAFF CAN VERIFY THAT | | | THERE IS NO INCONSISTENCY WITH THE CODE REQUIREMENTS. | | | THE MIXED-USE DEVELOPMENT REGULATIONS REQUIRE THAT | | | STREETLIGHTS BE PROVIDED ALONG PUBLIC RIGHTS-OF-WAY | | | ADJACENT TO THE SITE. CLEARLY SHOW THE PEDESTRIAN | | | ORIENTED LIGHTING FOR THE SIDEWALKS ALONG THE SITE AND | | | WITHIN THE PASEO ON THE PLANS. THE LANDSCAPE AND CIVIL | | | PLANS INDICATE THAT SOME EXISTING LIGHTS WILL REMAIN, | | | BUT NOT ALL OF THE SITE IS COVERED. | | | | | | 21) REPEAT COMMENT: THANK YOU FOR INCLUDING A NOTE | | | STATING WHERE THE SIDEWALKS OR WALKWAYS CROSS THE | | | DRIVEWAY ENTRANCES TO THE PARKING FACILITIES, LOADING | | | AREAS, OR STREETS (BOTH PRIVATE AND PUBLIC), THE | | | SIDEWALK OR WALKWAY IS CONTINUOUS AND REMAINS AT A | | | CONSTANT LEVEL; HOWEVER, THIS NEEDS TO BE SHOWN IN | | | CROSS-SECTION (OR OTHER GRAPHIC METHOD) ON THE PLANS, | | | PREFERABLY THE CIVIL PLANS. **** STAFF IS UNABLE TO | | | LOCATE THE CROSS-SECTION DEMONSTRATING THE CONTINUOUS | | | SIDEWALK AT A CONSTANT LEVEL ON SHEET C2.05 AS STATED | | | IN THE KIMLEY HORN RESPONSE LETTER. | | | | | | 22) UPDATED COMMENT: THE LANE WIDTH DIMENSIONS ON | | | EITHER SIDE OF THE MEDIANS IN BROADWAY NEED TO BE | | | PROVIDED. NEITHER THE CIVIL PLANS NOR THE ARCHITECTURAL | | | PLANS INCLUDE THIS DIMENSION. NOTE: THE LINE WEIGHT ON | | | SOME OF THE LAYERS ON THE ARCHITECTURAL PLANS ARE SO | | | FAINT THAT THEY ARE UNREADABLE ? AN EXAMPLE IS THE | | | CURBS ALONG BROADWAY. | | | | | | 23) UPDATED COMMENT: ROADWAY CROSS-SECTIONS. | | | | | | A. SECTION A-A ON SHEET C2.05 SHOWS 9.5-FOOT WIDE | | | SIDEWALKS, WHILE THE SAME LOCATION ON SHEET A-301 SHOWS | | | 10-FOOT WIDE SIDEWALKS. ALL PLANS MUST SHOW THE SAME, | | | ACCURATE CONDITIONS. | | | B. SECTION E-E ON SHEET A2.05 SHOWS A 16.5-FOOT SETBACK | | | FOR BUILDING A, WHILE SHEET A301 SHOWS A 16-FOOT | | | SETBACK. A 5.2-FOOT SETBACK IS SHOWN TO BUILDING B IN | | | SECTION E-E, WHILE SHEET A200 SHOWS THE BUILDING AT THE | | | 5-FOOT SETBACK LINE. ALL PLANS MUST SHOW THE SAME, | | | ACCURATE CONDITIONS. | | | C. PROVIDE THE DIMENSION FROM THE EDGE OF THE PARKING | | | SPACES TO BUILDING B THAT IS SHOWN ON SECTION F-F ON | | | SHEET A2.05 ON A301. NOTE: SOME OF THE DIMENSION LINES | | | THAT WERE PREVIOUSLY SHOWN ON SHEET A301 ARE NO LONGER | | | INCLUDED. | | | D. SECTION E-E ON SHEET A2.05 SHOWS A 16.6-FOOT SETBACK | | | FOR BUILDING A, WHILE SHEET A301 SHOWS A 16-FOOT | | | SETBACK. ALL PLANS MUST SHOW THE SAME, ACCURATE | | | CONDITIONS. | | | | | | 24) REPEAT COMMENT: THE EXTENSION OF BROADWAY AND | | | CONCURRENT CLOSING OF THE VEHICULAR CONNECTIONS BETWEEN | | | BROADWAY AND PINEWOOD RESULTS IN MORE TRAFFIC BEING | | | ROUTED TO 23RD STREET SOUTH OF THE PROJECT. CURRENTLY | | | 23RD STREET WEST OF THE BROADWAY EXTENSION IS ONE-WAY | | | WEST WITH A BULB OUT TO RESTRICT THE EASTWARD FLOW OF | | | TRAFFIC. THIS WILL NEED TO BE REMOVED AND THIS SECTION | | | OF 23RD STREET REOPENED TO TWO-WAY TRAFFIC, WITH | | | APPROPRIATE TRAFFIC MARKINGS. **** THE COMMENT RESPONSE | | | STATES THAT THIS IS SHOWN ON THE CIVIL PLANS, YET IT IS | | | NOT DEFINED IN THIS AREA. THE TRAFFIC IMPACT STATEMENT | | | LISTS THIS A REQUIREMENT. | | | | | | 25) CHECK THE CLEARANCES BETWEEN THE BOLLARDS AND PASEO | | | COLUMNS WHERE THE PASEO CROSSES PINEWOOD. YOU MAY WANT | | | TO ADJUST THE SPACING TO ALLOW A MORE COMFORTABLE | | | PEDESTRIAN EXPERIENCE WALKING NORTH/SOUTH. | | | | | | PARKING/LOADING | | | | | | 26) REPEAT COMMENT: PROVIDE VEHICLE TURNING RADIUS | | | DRAWING FOR MOVING TRUCKS INTO/OUT OF THE LOADING | | | AREAS. **** SHEET C4.01 IS THE GARBAGE TRUCK PLAN, NOT | | | THE MOVING TRUCK PLAN. | | | | | | 27) THERE ARE A FEW PARKING SPACES THAT ARE ADJACENT TO | | | WALLS THAT DO NOT APPEAR TO HAVE AN ADDITIONAL ONE FOOT | | | TO ALLOW FOR THE OPENING OF DOORS. EITHER PROVIDE THAT | | | THESE SPACES HAVE ADEQUATE CLEARANCE, OR THEY WILL NEED | | | TO BE DESIGNATED AS COMPACT PARKING SPACES. THE PARKING | | | TABLE WILL NEED TO BE UPDATED ACCORDINGLY. | | | | | | 28) UPDATED COMMENT: THERE ARE TWO SPACE LABELS IN THE | | | NORTHEAST CORNER OF LEVEL 2 THAT ARE SHOWN IN CONFLICT | | | WITH THE ELEVATOR/STAIRS. THIS NEEDS TO BE CORRECTLY | | | SHOWN. | | | | | | 29) UPDATED COMMENT: DEAD END PARKING ROWS FOR CRA | | | PARKING IS NOT PERMITTED WITHOUT A TURNAROUND SPACE. | | | THE DEAD-END PARKING ROW ON LEVEL 1.5 THAT IS LABELED | | | AS CRA MUST CONTAIN A TURNAROUND SPACE, DUE TO THE | | | GATE. IT DOES NOT APPEAR THAT THE OPEN AREA ADJACENT TO | | | THE GATE OPPOSITE THE LAST PARKING SPACE HAS SUFFICIENT | | | AREA TO ACT AS A TURN AROUND. | | | | | | 30) THE NEWLY SHOWN CRA PARKING AREA ON LEVEL 1.5 IS | | | GATED AND DOES NOT HAVE AN ADA COMPLIANT PARKING SPACE | | | AND ACCESSIBLE ACCESS TO THE GROUND LEVEL. PROVIDE AN | | | ADA SPACE AND ACCESSIBLE ROUTE TO THE ELEVATOR THAT | | | DOES NOT REQUIRE THE USER TO TRAVEL BEHIND PARKED CARS. | | | THIS WILL REQUIRE THE REMOVAL OF TWO PARKING SPACES | | | (ONE CRA AND ONE DP). NOTE: THE ADA PARKING SPACE AND | | | AISLE BETWEEN THE CRA AND PP ON THE NORTH HALF OF THE | | | GARAGE MAY BE REPLACED WITH THE OTHER REMOVED CRA | | | SPACES. | | | | | | 31) THE RETAIL REQUIRES 132 PARKING SPACES. THE PLAN | | | DOES NOT SHOW SUFFICIENT PP SPACES (CRA SPACES MAY NOT | | | BE USED) TO ACCOMMODATE THE MINIMUM REQUIREMENT. NOTE: | | | THIS WOULD BE FURTHER REDUCED IF FDOT DOES NOT APPROVE | | | THE DESIGN FOR BROADWAY. | | | | | | REGULAR PP SPACES LEVEL 1.5: 89 | | | ADA PP SPACES LEVEL 1.5: 5 | | | ON-STREET PP SPACES: 34 | | | TOTAL PP SPACES: 128 | | | | | | 32) WHERE ARE THE 19 GUEST SPACES LOCATED WITHIN THE | | | GARAGE AND HOW ARE THEY ACCESSED BY GUESTS? THERE IS NO | | | CALL BOX SHOWN ON THE PLANS THAT WOULD ALLOW THE GUESTS | | | TO CONTACT A UNIT OWNER TO BE GRANTED ACCESS TO THE | | | GATE-CONTROLLED AREA. ANY CALL BOX NEEDS TO BE LOCATED | | | SUCH THAT TRAFFIC FLOW AND PARKING IS NOT INHIBITED | | | WHILE GUESTS ARE AWAITING ENTRANCE. | | | | | | 33) THE PARKING TABLE ON SHEET A103.3 DOES NOT MATCH | | | THE PARKING TABLE ON SHEET A103.1, WHICH SEEMS TO | | | CORRECTLY DEPICT WHAT IS SHOWN ON THE PLANS. ALL PAGES | | | MUST SHOW CONSISTENT, ACCURATE, CODE COMPLIANT | | | INFORMATION. | | | | | | 34) UPDATED COMMENT: THE PARKING REQUIREMENT MULTIPLIER | | | FOR THE RESIDENTIAL PORTION OF THE PROJECT IS | | | INCORRECTLY SHOWN AS 1 PER 20 INSTEAD OF 1 PER 10 ON | | | THE PARKING REQUIRED TABLE. THE PROJECT REQUIRES 14 | | | BICYCLE SPACES FOR THE COMMERCIAL PORTION (ROUND UP | | | PARTIAL SPACES). | | | | | | 35) UPDATED COMMENT: THANK YOU FOR PROVIDING THE | | | BICYCLE RACK MODEL DETAIL AND DIMENSIONS THAT WILL BE | | | USED IN THE BICYCLE STORAGE ROOMS. THIS MODEL NEEDS TO | | | BE SHOWN IN THE BICYCLE STORAGE ROOMS TO INCLUDE THE | | | DIMENSIONS OF THE ROOM AND THE RACKS IN THE ROOM. | | | | | | 36) UPDATED COMMENT: ON-STREET BICYCLE FACILITIES ARE | | | REQUIRED. THE DEVELOPMENT COVERS A LARGE AREA AND WHILE | | | EMPLOYEES AND RESIDENTIAL VISITORS CAN BE EXPECTED TO | | | USE THE BICYCLE PARKING ROOM AT THE NORTHWEST PORTION | | | OF THE SIDE, STORE CUSTOMERS ARRIVING VIA BICYCLE WILL | | | LOOK FOR BICYCLE PARKING CLOSE TO THE ENTRANCE OF THE | | | STORE THEY ARE VISITING. IF NOT BICYCLE FACILITY IS | | | IMMEDIATELY AVAILABLE, THE USER WILL CHAIN THEIR | | | BICYCLE TO LIGHT POLES, TREES, ETC., AND OFTEN BLOCK | | | THE PEDESTRIAN NETWORK. ON-STREET BICYCLE PAD | | | DIMENSIONS MUST BE CLEARLY SHOWN ON THE PLANS SO THAT | | | STAFF CAN VERIFY THAT THERE IS SUFFICIENT ROOM AND THAT | | | SIDEWALKS ARE NOT BLOCKED. THE PADS MUST INCLUDE THE | | | RACK(S) AND THE DIMENSIONS FROM THE RACKS TO THE EDGE | | | OF THE PAD. FOR CLARITY THIS DETAIL SHALL BE PROVIDED | | | AT A BIGGER SCALE. NOTE: THE HARDSCAPE PLAN SHOWS | | | ON-STREET BICYCLE RACKS; HOWEVER, NO DIMENSIONS ARE | | | PROVIDED TO VERIFY THE COMMENTS ABOVE. | | | | | | 37) REPEAT COMMENT: PROVIDE THE DIMENSIONS FROM THE | | | MICRO MOBILITY STATIONS TO THE PROPOSED PLAZA LANDSCAPE | | | AREAS SO STAFF CAN VERIFY THE PEDESTRIAN CLEARANCES. | | | **** THE DIMENSIONS WERE NOT PROVIDED SO STAFF IS | | | UNABLE TO VERIFY THE PEDESTRIAN CLEARANCE. | | | | | | LANDSCAPE | | | | | | 38) UPDATED COMMENT: THE ARCHITECTURAL, LANDSCAPE AND | | | CIVIL PLANS DO NOT SHOW THE SAME BASE PLANTING | | | CONDITIONS FOR THE COLUMNS ALONG PINEWOOD. ALL OF THE | | | COLUMNS NEED TO HAVE THE BASE PLANTINGS. | | | | | | 39) PUBLIC OPEN SPACE CALCULATION ON SHEET A102.0 | | | COUNTS MORE AREA THAN IS DEFINED AS PUBLIC OPEN SPACE. | | | THE BREAKDOWN ON SHEET L1.02 NEEDS TO BE PROVIDED ON | | | SHEET A102.0 SO THAT IT IS CLEAR THAT THERE IS 10,000+ | | | SF OF COMPLIANT PUBLIC OPEN SPACE. | | | | | | WAIVERS/VARIANCES | | | | | | 40) THE MAXIMUM HORIZONTAL DIMENSION OF A BUILDING | | | WITHIN THE MIXED USE DISTRICTS IS 250 FEET. BUILDING A | | | EXCEEDS THIS ON ALL FRONTAGES. PLEASE PROVIDE THE FULL | | | DIMENSION OF LEVEL 2 ON ALL ELEVATIONS AS THIS IS THE | | | LARGEST FLOORPLATE. **** VARIANCE REQUIRED. | | | | | | 41) THE MAXIMUM LOT WIDTH FOR FLEX BUILDINGS IS 200 | | | FEET AND TOWER BUILDINGS IS 250 FEET. THE LOT | | | CONTAINING BUILDINGS A AND B EXCEEDS THIS BASED ON THE | | | ABANDONMENT OF PINEWOOD AND NORTHWOOD ROAD AND THE | | | BLOCK NO LONGER BOUNDED ON ALL SIDES BY STREETS OR RR. | | | **** VARIANCE REQUIRED. | | | | | | 42) THE ADDITIONAL ABANDONMENT OF PINEWOOD AND | | | NORTHWOOD ROAD RESULTS IN EXCEEDING THE MAXIMUM BLOCK | | | LENGTH AND PERIMETER DIMENSION. PROVIDE THE PERIMETER | | | DIMENSION OF THE PARCEL THAT CONTAINS BUILDINGS A AND | | | B. **** VARIANCE REQUIRED. | | | | | | 43) THE NMUD REGULATIONS LIMIT THE TOWER FLOOR PLATE TO | | | 30,000 SQUARE FEET FOR ANY SINGLE FLOORPLATE WITH AND | | | AVERAGE FLOORPLATE OF UP TO 20,000 SQUARE FEET. THE | | | MAXIMUM TOWER FLOORPLATES ARE SHOWN AT 45,450 SQUARE | | | FEET. THE NMUD FLOOR PLATE AVERAGE ONLY APPLIES TO THE | | | TOWER PORTION OF BUILDINGS WITHIN THE CORE SUBDISTRICT. | | | **** VARIANCE REQUIRED. | | | | | | 44)THE ACTIVE USE LINER REQUIRED BY SECTION | | | 94-209.J.1.G.II. REQUIRED FOR THE FULL LENGTH OF THE | | | GROUND FLOOR IS NOT ACHIEVED FOR THE AREAS LISTED | | | BELOW. **** VARIANCES REQUIRED. | | | | | | A. BUILDING A ALONG 25TH STREET AT THE FIRE COMMAND | | | ROOM. PROVIDE THE DIMENSION OF THIS AREA ALONG 25TH | | | STREET. | | | B. BUILDING A ALONG THE GARDEN PLAZA AT THE STAIRS. | | | PROVIDE THE DIMENSION OF THIS AREA ALONG THE SOUTH SIDE | | | OF THE STAIRS AS WELL AS THE SOUTH SIDE OF THE ADJACENT | | | RETAIL AREA. | | | C. BUILDING B ALONG 23RD STREET AT THE BOH AND TRASH | | | ROOM. PROVIDE THE DIMENSION OF THIS AREA ALONG 23RD | | | STREET. | | | | | | 45) UPDATED COMMENT: SECTION 94-209.E.2.B.I. REQUIRES | | | THAT ALL LEVELS OF THE PARKING GARAGE MUST BE SCREENED | | | BY A LINER BUILDING CONTAINING A MINIMUM DEPTH OF 20 | | | FEET OF HABITABLE SPACE. THIS IS NOT MET ALONG THE FULL | | | LENGTH OF 25TH STREET. **** A VARIANCE FROM THIS CODE | | | REQUIREMENT IS NEEDED. PLEASE PROVIDE THE DIMENSION FOR | | | PARKING LEVELS 1.5 AND 2, MEASURED FROM THE WEST SIDE | | | OF THE CORRIDOR TO THE WESTERN BUILDING WALL. ALSO | | | PROVIDE THE DIMENSION FORM THE WEST SIDE OF THE | | | CORRIDOR TO THE WEST WALL OF UNIT 18. THE REMAINDER IS | | | THE UNSCREENED PORTION OF THE GARAGE AND WILL BE THE | | | WAIVER THAT YOU ARE REQUESTING FROM THE 100% SCREENING | | | REQUIREMENT. PLEASE ALSO PROVIDE THE DEPTH OF UNIT 18 | | | FROM 25TH STREET SO THAT STAFF CAN VERIFY THAT YOU ARE | | | MEETING THE 20 FOOT OF HABITABLE SPACE AND THAT ANOTHER | | | WAIVER IS NOT REQUIRED. | | | | | | 46) UPDATED COMMENT: SECTION 94-209.2.A.IV. REQUIRES | | | THAT ALL PARKING GARAGES MUST HAVE DIRECT PEDESTRIAN | | | ACCESS TO A PUBLIC WALKWAY. NONE OF THE PARKING SPACES | | | APPEAR TO HAVE DIRECT ACCESS TO A PUBLIC WALKWAY. THE | | | PP AND CRA SPACES ON THE NORTH SIDE OF THE GARAGE LEVEL | | | 1.5 USE AN ELEVATOR THAT THE FUTURE PUBLIC ACCESS | | | EASEMENT ALONG THE NEW PINEWOOD. THE CRA SPACE ON THE | | | SOUTH SIDE OF THE GARAGE LEVEL 1.5 HAVE EMERGENCY | | | ACCESS TO THE RAILROAD, WHICH IS NOT A PUBLIC WALKWAY. | | | EVEN UPON MODIFICATION TO ACCOMMODATE ADA, THESE USERS | | | WILL GO THROUGH THE LOBBY PRIOR TO GETTING TO A PUBLIC | | | ACCESS EASEMENT AREA (PASEO OR PINEWOOD). WHILE THE | | | RESIDENTS THAT HAVE ACCESS TO THE LINER UNIT CORRIDOR | | | WILL HAVE ACCESS TO THE JUMP LOBBIES, WHICH ARE | | | DIRECTLY ON A PUBLIC WALKWAY, IT IS UNCLEAR IF THE | | | RESIDENTS OF THE TOWER WILL HAVE ACCESS TO THESE AREAS | | | AS WELL. THE RESIDENT ONLY, LIMITED ACCESS TO THE JUMP | | | LOBBIES DOES NOT QUALIFY AS THE GARAGES HAVING DIRECT | | | ACCESS. **** A WAIVER OF THIS CODE PROVISION IS | | | REQUIRED. AS PART OF THE WAIVER, ALL UNIT OWNERS WOULD | | | NEED TO BE ABLE TO UTILIZE THE ELEVATORS AND STAIRS | | | THAT ACCESS THE JUMP LOBBIES. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
06-28-2022 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
06-28-2022 |
Time |
16:38 |
Rev Time |
20.00 |
| Received By |
eschneid |
Date |
06-23-2022 |
Time |
08:27 |
Sent To |
|
|
| Notes |
| 2022-06-28 16:39:13 | CASE NO. 1895 - MAY 27, 2022 RESUBMITTAL | | | NORTHWOOD COMMONS - NMUD ANCHOR SITE | | | BROADWAY & 24TH STREET | | | | | | - CONTACT ERIC SCHNEIDER @ (561) 822-1446, | | | [email protected] | | | | | | - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF THREE | | | (3) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT | | | OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE | | | RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS | | | TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | - ONCE THE COMMENTS ARE RESUBMITTED AND DEEMED | | | SUFFICIENTLY ADDRESSED, THE CASE WILL BE SCHEDULED FOR | | | THE NEXT AVAILABLE PLANNING BOARD MEETING. | | | | | | - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT | | | RECEIVED A RESPONSE TO THE COMMENTS WITHIN 60 DAYS FROM | | | THE DATE OF THESE COMMENTS (BY SEPTEMBER 28, 2022), THE | | | PLANNING DIVISION MAY NOTIFY THE APPLICANT THAT THE | | | CASE IS CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL | | | REQUIRE A NEW DEVELOPMENT APPLICATION. | | | | | | - PLEASE NOTE THAT PREVIOUSLY ISSUED COMMENTS CONTINUE | | | WERE NOT ADDRESSED, SO THE APPLICANT IS ASSESSED A | | | RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF THE ORIGINAL | | | APPLICATION FEE ($600). | | | | | | - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED | | | IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION | | | 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS. | | | | | | THE DSI RESUBMITTAL ORIGINALLY COINCIDED WITH A CODE | | | TEXT CHANGE TO THE NMUD DEVELOPMENT REGULATIONS. IT IS | | | ANTICIPATED THAT A CODE AMENDMENT FOR THE | | | VARIANCE/WAIVER PROCESS WILL BE ADOPTED BY THE CITY | | | COMMISSION IN JULY. STAFF HAS NOTED AREAS WHERE THE NEW | | | VARIANCE/WAIVER PROCESS IS PREFERABLE TO AN NMUD TEXT | | | CHANGE. THERE ARE SOME AREAS WHERE THE NMUD TEXT WILL | | | NEED TO BE AMENDED REGARDLESS SUCH AS TO THE REGULATING | | | MAPS. | | | | | | 1) THE PLANS SHOW DISCREPANCIES FOR THE ULTIMATE | | | OWNERSHIP AND BOUNDARY STATUS OF THE BROADWAY | | | EXTENSION. THE CIVIL AND LANDSCAPE PLANS SHOW A | | | DEDICATED RIGHT-OF-WAY, WHILE THE SITE PLAN SHOWS IT AS | | | PRIVATE PROPERTY. THERE ARE CONFLICTING CODE | | | IMPLICATIONS FOR HOW THE BROADWAY EXTENSION IS | | | CLASSIFIED. THE PLANNING COMMENTS ARE BASED ON THE | | | BROADWAY EXTENSION BEING PRIVATE PROPERTY WITH AN | | | ACCESS EASEMENT. THE ENGINEERING DEPARTMENT IS STILL | | | DETERMINING THE MOST APPROPRIATE OPTION. | | | | | | 2) THE DEMOLITION PLAN SHOWS THAT THE "LOT 23" BUILDING | | | AT THE SOUTHEAST CORNER OF THE SITE WILL STILL BE | | | REMOVED AS PART OF THE PROJECT. THE PLANS SHOW A NEW | | | BUILDING IN THIS LOCATION; HOWEVER, THE DETAILS OF THIS | | | BUILDING, TO INCLUDE DIMENSIONS, SETBACKS, HEIGHT, FULL | | | ELEVATIONS, ETC. HAVE NOT BEEN PROVIDED. THIS WOULD BE | | | BUILDING D ON THE PLANS. SINCE IT IS IN THE NORTHWOOD | | | ROAD HISTORIC DISTRICT, IT NEEDS TO BE APPROVED BY THE | | | HISTORIC PRESERVATION BOARD. | | | | | | 3) UPDATED COMMENT: PROVIDE A REVISED TRAFFIC | | | PERFORMANCE STANDARDS APPROVAL LETTER FROM THE PALM | | | BEACH COUNTY TRAFFIC DIVISION FOR THE SCOPE OF THE | | | PROPOSED DEVELOPMENT BASED ON THE UPDATED PLANS AND | | | TRAFFIC IMPACT ANALYSIS (73,990 SF RETAIL AND 364 DU). | | | THE TRAFFIC LETTER NEEDS TO REFLECT THAT THE ANCHOR | | | SITE PROJECT BOUNDARIES ARE NOT VACANT, BUT THAT THE | | | CONTAIN BUILDINGS (3) AS SHOWN ON THE SURVEY. *** THE | | | LATEST TIA SHOWS THE NEW USE MIX HAVING LESS IMPACT | | | THAN WHAT THE CURRENT TPS LETTER SHOWS; THEREFORE, THE | | | UPDATED TPS LETTER IS PRIOR TO THE SCHEDULING OF THE | | | CITY COMMISSION HEARING. | | | | | | 4) REPEAT COMMENT: PROVIDE A PREDETERMINATION LETTER | | | FROM FDOT FOR THE IMPROVEMENTS WITHIN THE FDOT | | | RIGHTS-OF-WAY OF BROADWAY AND 24TH AND 25TH STREETS | | | ADJACENT TO THE PROJECT. *** THIS IS REQUIRED PRIOR TO | | | SCHEDULING A PLANNING BOARD HEARING. | | | | | | 5) REPEAT COMMENT: SECTION 94-209.J.1.C REQUIRES THAT | | | PROJECTS WITH THREE OR MORE DISTINCTLY SEPARATE | | | BUILDINGS HAVE SUBSTANTIALLY DIFFERENT FRONT | | | ELEVATIONS. SUBSTANTIALLY DIFFERENT FRONT ELEVATIONS | | | SHALL INCLUDE BUT NOT BE LIMITED TO VARIATIONS IN | | | FENESTRATION, MATERIAL, MASSING AND COLOR. BUILDINGS B | | | AND C DO NOT HAVE SUBSTANTIALLY DIFFERENT FRONT | | | ELEVATIONS FROM EACH OTHER IN ACCORDANCE WITH THE CODE | | | REQUIREMENTS. BUILDING D WILL NEED TO COMPLY WITH THIS | | | REQUIREMENT AS WELL. PLEASE NOTE THAT THE BUILDING C | | | ELEVATIONS HAVE CHANGED FROM THOSE PRESENTED TO THE | | | HISTORIC PRESERVATION BOARD AND WILL REQUIRE APPROVAL | | | FROM THE HISTORIC PRESERVATION DIVISION. | | | | | | 6) BUILDING B: SHEET A0.03 PROJECT DATA AND SHEET A405 | | | SHOW DIFFERING HEIGHTS FOR THE BUILDING LEVELS. ALL | | | PLANS MUST SHOW CONSISTENT, ACCURATE INFORMATION. WHAT | | | IS LEVEL 1.5 LISTED ON THE DATA TABLE? | | | | | | 7) BUILDING C: SHEET A0.03 PROJECT DATA AND SHEET A406 | | | SHOW DIFFERING HEIGHTS FOR THE BUILDING LEVELS. ALL | | | PLANS MUST SHOW CONSISTENT, ACCURATE INFORMATION. | | | | | | 8) THE MINIMUM UNIT SIZE IN NMUD IS 550 SF. BUILDING A | | | LEVEL 3 UNITS 5 AND 19, LEVEL 4 UNITS 9 AND 23, AND | | | LEVELS 5 THROUGH 9 UNITS 10 AND 24 DO NOT MEET THIS | | | MINIMUM. | | | | | | 9) REPEAT COMMENT: PROVIDE THE HEIGHTS OF THE ROOFTOP | | | MECHANICAL EQUIPMENT AND THE MECHANICAL EQUIPMENT | | | SCREENING HEIGHTS FOR ALL BUILDINGS SO THAT STAFF CAN | | | VERIFY THAT THE EQUIPMENT IS SCREENED IN ACCORDANCE | | | WITH THE NMUD REQUIREMENTS. THE PARAPET HEIGHTS SHOWN | | | (STAFF HAD TO SCALE THE DRAWINGS) FOR BUILDINGS B AND C | | | WILL NOT SCREEN THE FULL HEIGHT OF THE A/C UNITS WHERE | | | THEY ARE LOCATED ON THE ROOF PLANS. | | | | | | 10) UPDATED COMMENT: THE VISIBILITY TRIANGLE | | | INFORMATION WAS NOT PROVIDED FOR THE INTERSECTION OF | | | THE BROADWAY EXTENSION AND NORTHWOOD ROAD. IT APPEARS | | | THAT THERE MAY BE A CONFLICT HERE WITH PROPOSED | | | BUILDING D. NOTE: THE CITY?S TRAFFIC ENGINEER IS | | | PERMITTED TO REVIEW THE SPECIFIC INTERSECTION | | | CONFIGURATION, SPECIFICALLY THE EXISTING BULB OUTS AND | | | DETERMINE IF THE PROPOSED BUILDING D PLACEMENT DOES NOT | | | PRESENT A VISIBILITY HAZARD. | | | | | | 11) UPDATED COMMENT: THE MAXIMUM LOT WIDTH FOR FLEX | | | BUILDINGS IS 200 FEET AND TOWER BUILDINGS IS 250 FEET. | | | THE LOT CONTAINING BUILDINGS A AND B EXCEEDS THIS BASED | | | ON THE ABANDONMENT OF PINEWOOD AND NORTHWOOD ROAD AND | | | THE BLOCK NO LONGER BOUNDED ON ALL SIDES BY STREETS OR | | | RR. **** POSSIBLE NEW VARIANCE/WAIVER PROCESS INSTEAD | | | OF CODE CHANGE. | | | 12) THE ADDITIONAL ABANDONMENT OF PINEWOOD AND | | | NORTHWOOD ROAD RESULTS IN EXCEEDING THE MAXIMUM BLOCK | | | LENGTH AND PERIMETER DIMENSION. **** POSSIBLE NEW | | | VARIANCE/WAIVER PROCESS INSTEAD OF CODE CHANGE. | | | | | | 13) THE PROPOSAL IS NOW TO ABANDON THE REMAINDER OF | | | PINEWOOD AND NORTHWOOD ROAD, WEST OF BROADWAY. THE | | | PROPERTY AND SETBACK LINES SHOWN ON THE PLANS NEED TO | | | BE ADJUSTED TO REFLECT THE NEW PROPERTY BOUNDARIES. | | | | | | 14) UPDATED COMMENT: STAFF IS HAVING DIFFICULTY | | | VERIFYING THAT THE TOWER AND THE ARCHITECTURAL FEATURES | | | ARE NOT ENCROACHING ON THE BROADWAY SETBACK. THE PLAN, | | | SECTION AND ELEVATION DRAWINGS SHOW DIFFERENCES | | | INCLUDING THAT THE TOWER BOTH IS AND IS NOT SET BACK 15 | | | FEET FROM THE EDGE OF THE PODIUM. BETTER, DIMENSIONED | | | GRAPHICS AT A LARGER SCALE NEED TO BE PROVIDED TO | | | VERIFY THAT THERE IS NO SETBACK ENCROACHMENT. | | | | | | 15) UPDATED COMMENT: SHEET A0.02 CONTINUES TO LIST THE | | | GROSS LAND AREA AS 144,250 SQUARE FEET. SHEET L1.01 NOW | | | LISTS THE SITE AS HAVING 128,027. | | | | | | A. THE SITE NOW HAS TWO DEVELOPMENT PARCELS (ONE | | | INCLUDING BUILDINGS A, B AND D AND ONE WITH BUILDING | | | C), EACH MUST INDEPENDENTLY MEET THE LANDSCAPE, OPEN | | | SPACE, STREETSCAPE, PERVIOUS, ETC. REQUIREMENTS OF | | | NMUD. | | | B. THE LAND AREA FOR EACH PARCEL NEEDS TO INCLUDE THE | | | ABANDONED RIGHTS-OF-WAY. NOTE THAT THE BROADWAY | | | EXTENSION AND NEW PINEWOOD WILL NOT BE SEPARATE | | | PARCELS, BUT RATHER ACCESS EASEMENTS. | | | | | | 16) BUILDING FRONTAGE (NOTE: THE COMMENTS BELOW ARE | | | BASED ON ALL OF THE STREETS WITHIN THE PARCEL | | | CONTAINING BUILDINGS A, B AND D REMAINING PRIVATE | | | EASEMENTS): | | | | | | A.THE NMUD REGULATIONS REQUIRE THAT A MINIMUM OF 50% | | | BUILDING FRONTAGE IS PROVIDED ALONG 23RD STREET WITHIN | | | THE MINIMUM AND MAXIMUM SETBACK. THE LINEAR DIMENSION | | | ALONG 23RD STREET IS 360 FEET, SO A MINIMUM BUILDING | | | FRONTAGE OF 180 FEET IS REQUIRED. A SIGNIFICANT PORTION | | | OF BUILDING B EXCEEDS THE 20-FOOT MAXIMUM SETBACK, | | | WHICH IS NOT PERMITTED TO COUNT TOWARD THE BUILDING | | | FRONTAGE. STAFF CALCULATES THE TOTAL BUILDING FRONTAGE | | | ALONG 23RD STREET AS ONLY 117 FEET, WHICH CONSISTS OF | | | THE PORTION OF BUILDING A FRONTING PLAZA 4, THE | | | PORTIONS OF BUILDING B THAT MEET THE MAXIMUM SETBACK | | | AND BUILDING D. THIS COULD BE SOLVED BY MOVING THE | | | BUILDING B TO THE SOUTH. | | | B. BUILDING A FRONTAGE COMPLIES ON 25TH STREET AND | | | BROADWAY. | | | C. THE NMUD REGULATIONS REQUIRE THAT A MINIMUM OF 90% | | | BUILDING FRONTAGE IS PROVIDED ALONG NORTHWOOD ROAD | | | WITHIN THE MINIMUM AND MAXIMUM SETBACK. THE EXISTING | | | BUILDING D DOES NOT PROVIDE ENOUGH FRONTAGE. SINCE THIS | | | AREA IS NOT WITHIN THE CORE SUBDISTRICT, A VARIANCE | | | WOULD BE REQUIRED. | | | D. BUILDING C FRONTAGE COMPLIES ON NORTHWOOD ROAD, 24TH | | | STREET AND BROADWAY. | | | | | | 17) UPDATED COMMENT: THE NMUD REGULATIONS REQUIRE THAT | | | THE PRIMARY ENTRANCE TO THE UPPER LEVELS OF A MIXED-USE | | | BUILDING SHALL BE FROM A PUBLIC RIGHT-OF-WAY. THE | | | PRIMARY ENTRANCE TO THE UPPER LEVELS OF BUILDING B IS | | | SHOWN FROM NEW PINEWOOD, WHICH IS NOT A PUBLIC | | | RIGHT-OF-WAY, BUT RATHER AN EASEMENT. THIS CAN BE | | | SOLVED BY HAVING A DOORWAY TO THE LOBBY FACING 23RD | | | STREET. | | | | | | 18) UPDATED COMMENT: THE NMUD REGULATIONS CURRENTLY | | | LIMIT THE TOWER FLOOR PLATE TO 30,000 SQUARE FEET FOR | | | ANY SINGLE FLOORPLATE WITH AND AVERAGE FLOORPLATE OF UP | | | TO 20,000 SQUARE FEET. THE MAXIMUM TOWER FLOORPLATES | | | ARE SHOWN AT 36,475 SQUARE FEET, THE MAXIMUM FLOORPLATE | | | WILL BE NO GREATER THAN 40,000 SQUARE FEET. THE NMUD | | | FLOOR PLATE AVERAGE ONLY APPLIES TO THE TOWER PORTION | | | OF BUILDINGS WITHIN THE CORE SUBDISTRICT. PROVIDE THE | | | AVERAGE FLOORPLATE OF FLOORS L-4 THROUGH L-9 AS THESE | | | ARE THE ONLY ONES THAT APPLY. **** POSSIBLE NEW | | | VARIANCE/WAIVER PROCESS INSTEAD OF CODE CHANGE. | | | | | | DESIGN STANDARDS | | | | | | 19) UPDATED COMMENT: ACTIVE USE STANDARDS | | | | | | A. THE STOREFRONT GLAZING CALCULATIONS WERE NOT | | | ACCURATELY PROVIDED. SECTION 94-209.J.1.G.I.4. REQUIRES | | | THAT STOREFRONTS HAVE A TRANSPARENT GLAZED AREA OF NOT | | | LESS THAN 70 PERCENT OF THE GROUND LEVEL FACADE AREA. | | | THE TABLE AND DRAWINGS PROVIDED FOR BUILDING A DO NOT | | | PROVIDE THE FACADE AREA FOR ONLY THE GROUND FLOOR THAT | | | CAN THEN BE USED TO DETERMINE IF THE PROVIDED GROUND | | | GLAZING LEVEL SQUARE FOOTAGE COMPLIES WITH THE 70% | | | MINIMUM. | | | B. THE REQUIRED STOREFRONT GLAZING CALCULATIONS FOR | | | BUILDINGS B, C AND D WAS NOT PROVIDED. | | | C. THE ACTIVE USE LINER REQUIRED BY SECTION | | | 94-209.J.1.G.II. IS REQUIRED TO BE ON EACH LEVEL OF | | | EACH BUILDING FRONTAGE ABOVE THE GROUND FLOOR. | | | ADDITIONALLY, SECTION 94-209.E.2.B.I. REQUIRES A 20 | | | FOOT DEEP LINER ALONG 24TH STREET. **** POSSIBLE NEW | | | VARIANCE/WAIVER PROCESS INSTEAD OF CODE CHANGE. | | | | | | 20) UPDATED COMMENT: NO FENESTRATION WAS PROVIDED ALONG | | | THE GROUND FLOOR OF THE BUILDING ALONG THE RR AS | | | REQUIRED BY SECTION 94-209.J.I. **** POSSIBLE NEW | | | VARIANCE/WAIVER PROCESS INSTEAD OF CODE CHANGE. | | | | | | 21) UPDATED COMMENT: SECTION 94-209.J.A. REQUIRES THE | | | PROVISION OF PLANAR BREAKS. WHILE THE PLANS APPEAR TO | | | SHOW ARTICULATION ON THE FACADES THAT REFLECT PLANAR | | | BREAKS, THE PLANS DO NOT INCLUDE DEPTH DIMENSIONS FOR | | | THE VARIOUS FEATURES, NOR IS A TABLE PROVIDED TO SHOW | | | THAT THE CUMULATIVE HORIZONTAL LENGTH OF ALL PLANAR | | | BREAKS SHALL BE GREATER THAN OR EQUAL TO 20% OF EACH | | | BUILDING FRONTAGE EXCEEDING 150 FEET FOR BUILDINGS A, B | | | AND C HAVE BEEN MET. | | | | | | 22) UPDATED COMMENT: PROVIDE THE DIMENSIONS OF THE | | | PROJECTIONS AND ENCROACHMENTS (EX. BALCONIES AND OTHER | | | ARCHITECTURAL FEATURES) ON THE PLANS AND ELEVATIONS SO | | | THAT STAFF CAN VERIFY COMPLIANCE WITH THE NMUD | | | REGULATIONS. THIS HAS NOT BEEN PROVIDED FOR ALL OF THE | | | FACADES ON ALL THE BUILDINGS. | | | | | | 23) THE SITE PLANS DO NOT SHOW ALL THE UTILITIES - EX. | | | FIRE HYDRANT MISSING AT SOUTHWEST CORNER OF BUILDING C. | | | ALL PLANS MUST SHOW ACCURATE CONDITIONS. | | | | | | STREETSCAPE | | | | | | 24) REPEAT COMMENT: NO DETAILS WERE PROVIDED ON THE | | | SITE LIGHTING TO VERIFY COMPLIANCE WITH THE NMUD | | | REGULATIONS. *** THIS IS REQUIRED PRIOR TO SCHEDULING A | | | PLANNING BOARD HEARING SO THAT STAFF CAN VERIFY THAT | | | THERE IS NO INCONSISTENCY WITH THE CODE REQUIREMENTS. | | | THE MIXED-USE DEVELOPMENT REGULATIONS REQUIRE THAT | | | STREETLIGHTS BE PROVIDED ALONG PUBLIC RIGHTS-OF-WAY | | | ADJACENT TO THE SITE. CLEARLY SHOW THE PEDESTRIAN | | | ORIENTED LIGHTING FOR THE SIDEWALKS ALONG THE SITE ON | | | THE PLANS. THE LANDSCAPE AND CIVIL PLANS INDICATE THAT | | | SOME EXISTING LIGHTS WILL REMAIN, BUT NOT ALL OF THE | | | SITE IS COVERED. | | | | | | 25) UPDATED COMMENT: THANK YOU FOR INCLUDING A NOTE | | | STATING WHERE THE SIDEWALKS OR WALKWAYS CROSS THE | | | DRIVEWAY ENTRANCES TO THE PARKING FACILITIES, LOADING | | | AREAS, OR STREETS (BOTH PRIVATE AND PUBLIC), THE | | | SIDEWALK OR WALKWAY IS CONTINUOUS AND REMAINS AT A | | | CONSTANT LEVEL; HOWEVER, THIS NEEDS TO BE SHOWN IN | | | CROSS-SECTION (OR OTHER GRAPHIC METHOD) ON THE PLANS, | | | PREFERABLY THE CIVIL PLANS. | | | | | | 26) REPEAT COMMENT: THE ARCHITECTURAL PLANS MUST SHOW | | | THE MEDIANS IN BROADWAY THAT ARE SHOWN ON THE CIVIL AND | | | LANDSCAPE PLANS. THE LANE WIDTH DIMENSIONS NEED TO BE | | | PROVIDED AT THESE LOCATIONS. | | | | | | 27) UPDATED COMMENT: ROADWAY CROSS-SECTIONS. | | | | | | A. THERE ARE DISCREPANCIES BETWEEN SECTION A-A ON SHEET | | | C2.05 AND THE SAME LOCATION ON SHEET A-301. SHEET A-301 | | | SHOWS THE 10-FOOT SIDEWALK DIMENSION EXTENDING INTO THE | | | PARKING SPACE. THE SECTION A-A DOES NOT MATCH AND | | | EXCEEDS THE 60 FEET BETWEEN BUILDINGS. | | | B. SECTION B-B ON SHEET C2.05 EXCEEDS THE 60 FEET | | | BETWEEN BUILDINGS AND CALLS OUT LANDSCAPING WHERE IT IS | | | ACTUALLY PAVED AREA. | | | C. THE DIMENSIONS PROVIDED ON SECTION C-C ON SHEET | | | A2.05 DO NOT MATCH THE DIMENSIONS PROVIDED ON SHEET | | | A-301. THERE IS ONE FOOT LESS WIDTH SHOWN ON SECTION | | | C-C. ALL PLANS NEED TO SHOW THE SAME, ACCURATE | | | CONDITIONS. ADDITIONALLY, SECTION C-C DOES NOT DEPICT | | | WHAT IS OCCURRING IN THE ROW BETWEEN THE CURB AND | | | PROPERTY LINE TO VERIFY THAT THE MINIMUM 5-FOOT WIDE | | | UNOBSTRUCTED SIDEWALK HAS BEEN PROVIDED. | | | D. THE DIMENSIONS PROVIDED ON SECTION D-D ON SHEET | | | A2.05 DO NOT MATCH THE DIMENSIONS PROVIDED ON SHEET | | | A-301. THERE IS ONE FOOT LESS WIDTH SHOWN ON SECTION | | | D-D. ALL PLANS NEED TO SHOW THE SAME, ACCURATE | | | CONDITIONS. | | | E. SECTION E-E ON SHEET A2.05 DOES NOT ACCURATELY | | | DEPICT WHAT IS OCCURRING AT THIS LOCATION. EX. TREE | | | GRATE NOT SHOWN. | | | F. THE DIMENSIONS PROVIDED ON SECTION F-F ON SHEET | | | A2.05 DO NOT MATCH THE DIMENSIONS PROVIDED ON SHEET | | | A-301. THERE IS ONE FOOT MORE WIDTH SHOWN ON SECTION | | | F-F. | | | G. SECTION G-G ON SHEET A2.05 DOES NOT ACCURATELY | | | DEPICT WHAT IS OCCURRING AT THIS LOCATION. EX. | | | LANDSCAPE STRIP NOT SHOWN. | | | H. SECTION H-H ON SHEET A2.05 DOES NOT ACCURATELY | | | REFLECT THE SITE PLAN OR OTHER CIVIL PLANS. | | | ADDITIONALLY, THE STATUS OF THE BROADWAY EXTENSION HAS | | | NOT BEEN DETERMINED BY THE CITY, SO THE PROPERTY LINES | | | WILL BE INCORRECT. BUILDING D DOES NOT COMPLY WITH ANY | | | STREETSCAPE REQUIREMENTS, TO INCLUDE THE ROADWAY | | | CROSS-SECTION REQUIREMENTS. | | | | | | 28) THE EXTENSION OF BROADWAY AND CONCURRENT CLOSING OF | | | THE VEHICULAR CONNECTIONS BETWEEN BROADWAY AND PINEWOOD | | | RESULTS IN MORE TRAFFIC BEING ROUTED TO 23RD STREET | | | SOUTH OF THE PROJECT. CURRENTLY 23RD STREET WEST OF THE | | | BROADWAY EXTENSION IS ONE-WAY WEST WITH A BULB OUT TO | | | RESTRICT THE EASTWARD FLOW OF TRAFFIC. THIS WILL NEED | | | TO BE REMOVED AND THIS SECTION OF 23RD STREET REOPENED | | | TO TWO-WAY TRAFFIC, WITH APPROPRIATE TRAFFIC MARKINGS. | | | | | | PARKING/LOADING | | | | | | 29) PROVIDE VEHICLE TURNING RADIUS DRAWING FOR MOVING | | | TRUCKS INTO/OUT OF THE LOADING AREAS. | | | | | | 30) UPDATED COMMENT: ALL LEVELS OF THE PARKING GARAGE | | | MUST BE SCREENED BY A LINER BUILDING CONTAINING A | | | MINIMUM DEPTH OF 20 FEET OF HABITABLE SPACE. THIS IS | | | NOT MET ALONG THE FULL LENGTH OF 25TH STREET. **** | | | POSSIBLE NEW VARIANCE/WAIVER PROCESS INSTEAD OF CODE | | | CHANGE. IF DONE AS A CODE TEXT CHANGE, THE SPECIFIC | | | CODE LANGUAGE MUST INCLUDE THE PROVISION OF | | | ARCHITECTURAL TREATMENT AND PLANAR BREAKS TO VARY THE | | | FACADE IN ORDER TO CONCEAL THE NON-HABITABLE PARKING. | | | | | | 31) THERE ARE FOUR PARKING SPACES IN THE NORTHEAST | | | CORNER OF LEVEL 1.5 THAT DO NOT CONTAIN A COLOR OR | | | LABELS AND ONE SPACE IN THE SOUTH PORTION THAT DOES NOT | | | CONTAIN A LABEL. | | | | | | 32) UPDATED COMMENT: DEAD END PARKING ROWS FOR | | | UNASSIGNED, TO INCLUDE PUBLIC, PARKING ARE NOT | | | PERMITTED WITHOUT A TURNAROUND SPACE. THE DEAD-END | | | PARKING ROW ON LEVEL 1.5 MUST CONTAIN A TURNAROUND | | | SPACE. THIS REMOVED SPACE MUST BE REFLECTED ON ALL THE | | | PARKING TABLES. | | | | | | 33) UPDATED COMMENT: SECTION 94-209.2.A.IV. REQUIRES | | | THAT ALL PARKING GARAGES MUST HAVE DIRECT PEDESTRIAN | | | ACCESS TO A PUBLIC WALKWAY. THE PUBLIC ELEVATORS THAT | | | ARE NOW DESIGNATED ON THE PLAN DO NOT PROVIDE ACCESS TO | | | A PUBLIC WALKWAY, BUT RATHER THE INTERNAL PRIVATE | | | ROADWAY NETWORK. **** POSSIBLE NEW VARIANCE/WAIVER | | | PROCESS INSTEAD OF CODE CHANGE. | | | | | | 34) UPDATED COMMENT: THANK YOU FOR PROVIDING THE COLUMN | | | LOCATIONS ON THE GARAGE LEVELS: | | | | | | A. PLEASE PROVIDE A DIAGRAM SHOWING HOW THE ?FINS? | | | SHOWN ON EACH SIDE OF EACH COLUMN INTERACT WITH THE | | | PARKING SPACES THAT THEY ARE LOCATED ADJACENT TO. IN | | | MANY INSTANCES THESE FINS EXTEND INTO THE PARKING | | | SPACES AND DRIVE AISLES MAKING THEM NO LONGER COMPLIANT | | | WITH CODE MINIMUMS. | | | B. THE COLUMNS ARE SHOWN EXTENDING ON LEVELS 3 AND | | | ABOVE. SOME OF THE COLUMNS ARE NO LONGER WITHIN THE | | | BUILDING AND VIOLATE THE TOWER SETBACK, WHICH IS NOT | | | PERMITTED. ADDITIONALLY, THE EXTERIOR COLUMNS, EVEN | | | WHERE THE SETBACK IS NOT VIOLATED, ARE NOT SHOWN ON THE | | | ELEVATION DRAWINGS AND RENDERINGS. | | | | | | 35) UPDATED COMMENT: THE PARKING STALL DETAIL WAS | | | REMOVED FROM THE PLANS AND NOT REPLACED. PROVIDED A | | | CITY CODE COMPLIANT PARKING DETAIL FOR ALL CONDITIONS. | | | | | | 36) REPEAT COMMENT: THE PARKING PROVIDED TABLES SHALL | | | CLEARLY SEPARATE THE PROVIDE ADA SPACES FROM THE TOTAL | | | PROVIDED SPACES FOR EACH CATEGORY. THE CURRENT LINE | | | ITEM FOR L2 PARKING GARAGE MAKE IT LOOK LIKE THERE ARE | | | ADA SPACES IN ADDITION TO THE REGULAR SPACES, WHICH | | | OVERSTATES THE NUMBER OF PROVIDED PARKING SPACES. | | | | | | 37) THERE ARE 26 PARKING ON-STREET PARKING SPACES, NOT | | | 25 AS LISTED. | | | | | | 38) UPDATED COMMENT: THE PLANS AND DATA TABLES DO NOT | | | CLEARLY SHOW THE PUBLIC PARKING SPACES REQUIRED IN | | | ACCORDANCE WITH THE AGREEMENT WITH CRA. THESE NEED TO | | | BE A SEPARATE LINE ITEM ON THE TABLES AND A SHOWN WITH | | | A SEPARATE MARKING FROM THE REQUIRED RETAIL SPACES. | | | STAFF HAS COUNTED THE NUMBER OF SPACES MARKED AS PUBLIC | | | PARKING AND IT IS DEFICIENT FOR RETAIL PLUS PUBLIC | | | PARKING SINCE ONLY 2 PARKING SPACES IN EXCESS OF THE | | | RETAIL REQUIREMENT ARE PROVIDED. | | | | | | 39) REPEAT COMMENT: THE CRA AGREEMENT REQUIRES THAT THE | | | DEVELOPER CONSTRUCT PUBLIC PARKING SPACES IN AN AMOUNT | | | TO EQUAL 10% OF THE PARKING REQUIRED FOR THE PROJECT. | | | WHILE THE PLANS DO NOT CLEARLY DEMONSTRATE WHERE THE | | | CRA REQUIRED PARKING SPACES ARE LOCATED, IT APPEARS | | | THAT SOME OF THEM ARE INTENDED TO BE LOCATED WITHIN THE | | | ON-STREET PARKING SHOWN ON THE PLANS. SINCE THE | | | LANGUAGE REQUIRES THAT NEW PARKING SPACES BE | | | CONSTRUCTED TO MEET THE CRA REQUIREMENT, PROVIDE AN | | | EXISTING PARKING INVENTORY OF THE ON-STREET PARKING | | | SPACES. EXISTING PARKING SPACES MAY NOT BE COUNTED AS | | | NEWLY CONSTRUCTED SPACES, AND ANY SPACES BEING REMOVED, | | | WILL NEED TO BE REPLACED AND MAY NOT BE COUNTED AS | | | NEWLY CREATED PARKING SPACES. | | | | | | 40) REPEAT COMMENT: THE PROJECT REQUIRES 15 BICYCLE | | | SPACES FOR THE COMMERCIAL PORTION AND 38 BICYCLE SPACES | | | FOR THE RESIDENTIAL PORTION. THERE ARE 53 TOTAL | | | REQUIRED BICYCLE PARKING SPACES. THIS SHALL BE | | | CORRECTLY REFLECTED ON THE PARKING TABLES AND SHOWN ON | | | THE PLANS. THE CURRENT PLAN ONLY LISTS 44 REQUIRED | | | BICYCLE PARKING SPACES. | | | | | | 41) REPEAT COMMENT: PROVIDE THE DIMENSIONS AND DETAIL | | | FOR THE BICYCLE RACKS, INCLUDING THE NUMBER OF SPACES, | | | LOCATED IN THE BICYCLE STORAGE ROOM AS WELL AS THE | | | DIMENSIONS OF THE ROOM AND THE RACKS IN THE ROOM. THIS | | | SHALL BE PROVIDED ON ITS OWN BICYCLE ROOM DETAIL SHEET | | | THAT THIS AT A LEGIBLE SCALE. | | | | | | 42) UPDATED COMMENT: ON-STREET BICYCLE FACILITIES ARE | | | REQUIRED. THE HARDSCAPE PLAN SHOWS ON-STREET BICYCLE | | | RACKS, YET THE ARCHITECTURAL, LANDSCAPE AND CIVIL PLANS | | | DO NOT. ALL PLANS MUST SHOW THE SAME CODE COMPLIANT | | | CONDITIONS. ON-STREET BICYCLE PAD DIMENSIONS MUST BE | | | CLEARLY SHOWN ON THE PLANS SO THAT STAFF CAN VERIFY | | | THAT THERE IS SUFFICIENT ROOM AND THAT SIDEWALKS ARE | | | NOT BLOCKED. THE PADS MUST INCLUDE THE RACKS AND THE | | | DIMENSIONS FROM THE RACKS TO THE EDGE OF THE PAD. FOR | | | CLARITY THIS DETAIL SHALL BE PROVIDED AT A BIGGER | | | SCALE. | | | | | | 43) UPDATED COMMENT: PROVIDE THE DIMENSIONS FROM THE | | | MICRO MOBILITY STATIONS TO THE PROPOSED PLAZA LANDSCAPE | | | AREAS SO STAFF CAN VERIFY THE PEDESTRIAN CLEARANCES. | | | | | | LANDSCAPE | | | | | | 44) THE REQUIRED LANDSCAPE AROUND BUILDING D HAS NOT | | | BEEN PROVIDED. THERE DOES NOT APPEAR TO BE ADEQUATE | | | ROOM TO INSTALL THIS ALONG THE BROADWAY EXTENSION. | | | | | | 45) THE LANDSCAPE PLANS DO NOT SHOW ALL OF THE PINEWOOD | | | AND PASEO SUPPORT COLUMNS. ALL OF THE COLUMNS ALONG | | | PINEWOOD NEED TO HAVE THE BASE PLANTINGS. | | | | | | 46) ALL BACK FLOW PREVENTORS MUST BE LOCATED ON PRIVATE | | | PROPERTY AND NOT WITHIN THE RIGHT-OF-WAY LANDSCAPE | | | STRIP. THE REQUIRED LANDSCAPE NEEDS TO BE PROVIDED | | | WHERE THESE WILL NO LONGER EXIST IN THE RIGHT-OF-WAY. | | | | | | 47) THE WATER AND FIRE LINES IN PLAZA IV ARE SHOWN IN | | | DIRECT CONFLICT WITH PROPOSED TREES. | | | | | | 48) THE COLUMNS FOR THE SOUTH SIDE OF BUILDING A ARE | | | NOT SHOWN ON THE LANDSCAPE PLAN WITHIN PLAZA III AND | | | DIRECTLY CONFLICT WITH SOME OF THE PROPOSED TREES. | | | ADDITIONALLY, PLEASE REVIEW THE COLUMN ORIENTATION | | | DETAILS AS THEY PROGRESS UP THE LEVELS AT THIS LOCATION | | | AS THEY CHANGE. | | | | | | PUBLIC OPEN SPACE | | | | | | 49) THE PROPOSAL TO REDEFINE THE REQUIRED OPEN SPACE AS | | | THE PASEO WAS BASED ON THE DESIGNS WITH NO PUBLIC OPEN | | | SPACE THAT MET THE CODE DEFINITION OF OPEN TO THE SKY. | | | THE NEW DESIGN THAT INCORPORATES CLOSURE OF NORTHWOOD | | | ROAD AND THE SOUTHWEST CORNER OF THE SITE AS PUBLIC | | | OPEN SPACE SEEMS TO MEET THE 10,000 SQUARE FOOT | | | REQUIREMENT. STAFF DID SOME ROUGH CALCULATIONS AND IT | | | SEEMS TO BE CLOSE. PROVIDE CALCULATIONS OF THIS AREA | | | (PLAZA III AND IV) THAT MEET THE DEFINITION OF OPEN | | | SPACE - OPEN TO THE SKY AND NOT WITHIN THE RIGHT-OF-WAY | | | OR REQUIRED MINIMUM SETBACK. THE AMOUNT OF AREA FOR | | | PLAZA III WILL BE REDUCED ON THE NORTH, EAST AND SOUTH | | | AS WELL AS WHERE THE OVERHEAD PASSAGE IS. PLAZA IV WILL | | | BE REDUCED ON THE NORTH SIDE DUE TO THE OVERHANG PLUS | | | THE REQUIRED 10-FOOT SETBACK. IF THIS AREA IS LESS THAN | | | 10,000 SQUARE FEET STAFF CAN REVIEW THE MERITS OF THE | | | PASEO TEXT CHANGE VS. A VARIANCE TO THE AMOUNT OF | | | REQUIRED PUBLIC OPEN SPACE VS. OPEN SPACE CODE CHANGE | | | SIMILAR TO THE DMP TO PERMIT CERTAIN COVERED AREAS TO | | | APPLY AS OPEN SPACE. IT MAY STILL BE NECESSARY TO ADD | | | PUBLIC PASEO AS A FEATURE, BUT STAFF PREFERS THAT THIS | | | NOT SUBSTITUTE FOR TRUE OPEN SPACE. | | | | | | PRIVATE OPEN SPACE | | | | | | 50) UPDATED COMMENT: THANK YOU FOR PROVIDING A TABLE | | | AND PLAN THAT DESCRIBE THE PRIVATE OPEN SPACE | | | REQUIREMENTS. | | | | | | A. THE TABLE DOES NOT CONTAIN THE SAME SITE AREA THAT | | | IS LISTED ON THE DATA COVER SHEET. NOTE: THIS WILL | | | CHANGE WHEN COMMENT NUMBER 15 IS ADDRESSED. | | | B. PRIVATE OPEN SPACE IS BASED ON THE SITE AREA WHERE | | | THE BUILDING(S) IS LOCATED. BUILDINGS A, B AND D ARE | | | ALL LOCATED ON ONE SITE, SO 10% OF THIS SITE AREA SHALL | | | BE PROVIDED AS PRIVATE OPEN SPACE. THIS MAY ALL BE | | | CONTAINED ON THE BUILDING A AMENITY DECK. PLEASE NOTE | | | THAT THE PRIVATE OPEN SPACE TABLE LISTS PRIVATE OPEN | | | SPACE ON LEVEL 2 OF BUILDING B, WHICH HAS NOT OPEN | | | SPACE AT THIS LOCATION. | | | C. PROVIDE INFORMATION ON HOW THE BUILDING C PRIVATE | | | OPEN SPACE MEETS THE REQUIREMENTS OF SECTION | | | 94-210.K.3.C. PRIVATE OPEN SPACES SHALL PROVIDE SHADED | | | AREAS, AND THEIR GROUND SURFACE SHALL BE A COMBINATION | | | OF PAVING MATERIALS, LAWN, OR GROUND COVER. NOTE: | | | ROOFTOP STRUCTURES MUST CLEARLY SHOW THAT THEY ARE NOT | | | EXCEEDING THE HEIGHT ALLOWANCE. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
04-14-2022 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
04-14-2022 |
Time |
11:05 |
Rev Time |
12.00 |
| Received By |
eschneid |
Date |
04-14-2022 |
Time |
11:05 |
Sent To |
|
|
| Notes |
| 2022-04-14 11:06:18 | CASE NO. 1895 - FEBRUARY 2022 RESUBMITTAL | | | NORTHWOOD COMMONS - NMUD ANCHOR SITE | | | BROADWAY & 24TH STREET | | | | | | - CONTACT ERIC SCHNEIDER @ (561) 822-1446, | | | [email protected] | | | | | | - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FOUR | | | (4) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT | | | OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE | | | RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS | | | TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | - THE PPRC COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND | | | SUBMITTED TO THE PLANNING DIVISION BY 5 PM ON FRIDAY, | | | APRIL 29, 2022, TO BE ELIGIBLE TO BE SCHEDULED FOR THE | | | JUNE 21, 2022 PLANNING BOARD MEETING. | | | | | | - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT | | | RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS | | | FROM THE DATE OF THE PPRC MEETING (BY JUNE 14, 2022), | | | THE PLANNING DIVISION MAY NOTIFY THE APPLICANT THAT THE | | | CASE IS CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL | | | REQUIRE A NEW DEVELOPMENT APPLICATION. | | | | | | - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($600). | | | | | | - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED | | | IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION | | | 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS. | | | | | | THE DSI RESUBMITTAL COINCIDES WITH A CODE TEXT CHANGE | | | TO THE NMUD DEVELOPMENT REGULATIONS. STAFF HAS REVIEWED | | | THE SUBMITTED PLANS FOR COMPLIANCE WITH BOTH THE | | | EXISTING REGULATIONS AND THE PROPOSED TEXT CHANGES, | | | WHERE APPLICABLE. THE APPLICANT?S STATED GOAL WAS TO | | | AMEND THE DEVELOPMENT REGULATIONS TO REFLECT THE DESIGN | | | OF THE PLAN WHERE IT COULD NOT COMPLY WITH THE | | | REGULATIONS AND THUS AVOID VARIANCES/WAIVERS AT THE | | | ZONING BOARD OF APPEALS. THE SUBMITTED CODE REVISIONS | | | DO NOT COVER ALL OF THE AREAS WHERE THE PLAN DOES NOT | | | COMPLY WITH THE CODE. STAFF HAS IDENTIFIED THESE | | | DISCREPANCIES. FOR BOTH THE APPLICANT PROPOSED AND THE | | | STAFF IDENTIFIED DISCREPANCIES, STAFF HAS INCLUDED IF | | | STAFF WILL SUPPORT A CODE CHANGE OR NOT. NOTE: THE CODE | | | REVISION CASE INCLUDES COMMENTS RELATED TO THE PROPOSED | | | CODE CHANGES THAT DO NOT DIRECTLY IMPACT THE SITE PLAN. | | | | | | 1) REPEAT COMMENT: PROVIDE A TRAFFIC PERFORMANCE | | | STANDARDS APPROVAL LETTER FROM THE PALM BEACH COUNTY | | | TRAFFIC DIVISION FOR THE FULL SCOPE OF THE PROPOSED | | | DEVELOPMENT. *** THIS IS REQUIRED PRIOR TO SCHEDULING A | | | PLANNING BOARD HEARING. | | | | | | 2) UPDATED COMMENT: THE NON-RESIDENTIAL SQUARE FOOTAGE | | | LISTED IN THE TRAFFIC IMPACT ANALYSIS DOES NOT MATCH | | | THE SITE DATA ON THE PLANS. THE TRAFFIC IMPACT ANALYSIS | | | MUST REFLECT THE FULL SCOPE OF THE DEVELOPMENT. | | | | | | 3) REPEAT COMMENT: PROVIDE A PREDETERMINATION LETTER | | | FROM FDOT FOR THE IMPROVEMENTS WITHIN THE FDOT | | | RIGHTS-OF-WAY OF BROADWAY AND 24TH AND 25TH STREETS | | | ADJACENT TO THE PROJECT. *** THIS IS REQUIRED PRIOR TO | | | SCHEDULING A PLANNING BOARD HEARING. | | | | | | 4) REPEAT COMMENT: SECTION 94-209.J.1.C REQUIRES THAT | | | PROJECTS WITH THREE OR MORE DISTINCTLY SEPARATE | | | BUILDINGS HAVE SUBSTANTIALLY DIFFERENT FRONT | | | ELEVATIONS. SUBSTANTIALLY DIFFERENT FRONT ELEVATIONS | | | SHALL INCLUDE BUT NOT BE LIMITED TO VARIATIONS IN | | | FENESTRATION, MATERIAL, MASSING AND COLOR. BUILDINGS B | | | AND C DO NOT HAVE SUBSTANTIALLY DIFFERENT FRONT | | | ELEVATIONS FROM EACH OTHER IN ACCORDANCE WITH THE CODE | | | REQUIREMENTS. | | | | | | 5) THE MAXIMUM GROUND FLOOR STORY HEIGHT IN NMUD IS 20 | | | FEET. THE RETAIL AREAS ON THE NORTHEAST PORTION OF | | | BUILDING A ARE SHOWN AT 26 FEET, WHICH DOES NOT COMPLY. | | | THE STORY HEIGHT LIMITATION WILL NEED TO BE REMOVED AS | | | AN NMUD CORE SUBAREA REQUIREMENT. STAFF DOES NOT OBJECT | | | TO THIS ADDED CHANGE. | | | | | | 6) THE MAXIMUM STORY HEIGHT ABOVE THE GROUND FLOOR IN | | | NMUD IS 12 FEET. PLEASE EXPLAIN THE 13-FOOT 4-INCH | | | LEVEL SHOWN ON THE ELEVATIONS (LEVEL 3.5) FOR BUILDING | | | A. IF IT IS IN EXCESS OF 12 FEET, IT DOES NOT COMPLY. | | | THE STORY HEIGHT LIMITATION WILL NEED TO BE REMOVED AS | | | AN NMUD CORE SUBAREA REQUIREMENT. STAFF DOES NOT OBJECT | | | TO THIS ADDED CHANGE. | | | | | | 7) BUILDING A: THE BUILDING HEIGHT PERMITTED WITHIN THE | | | AREA SOUTH OF CORE PARCEL B IS 56 FEET. THE UNITS ON | | | THE SOUTH END OF THE BUILDING, EAST OF PINEWOOD, | | | STARTING AT RESIDENCE LEVEL 4 EXCEED THE PERMITTED. | | | STAFF HAS NOTED THAT THE APPLICANT HAS SUBMITTED A CODE | | | CHANGE TO MOVE THIS LINE; HOWEVER, STAFF DOES NOT | | | SUPPORT THIS PROPOSED CHANGE. A SOLUTION IS TO MOVE | | | THIS LEG OF THE TOWER NORTH, PREFERABLY TO ALIGN WITH | | | 24TH STREET TO PROVIDE A TERMINAL VISTA. THE SOUTH | | | BOUNDARY OF CORE PARCEL B WAS SPECIFICALLY SET AT THIS | | | LOCATION TO PROVIDE A TRANSITION TO THE NORTHWOOD ROAD | | | HISTORIC DISTRICT. NOTE: SINCE PINEWOOD IS BEING | | | ABANDONED, THE AREA OF THE ABANDONED ROADWAY NEEDS TO | | | BE ASSIGNED A BUILDING HEIGHT DESIGNATION. STAFF DOES | | | NOT OBJECT TO THE PARCEL A HEIGHT LINE MOVING EAST TO | | | COVER THE ABANDONED PORTION OF PINEWOOD. | | | | | | 8) BUILDING B: THE PORTION OF THE BUILDING WITHIN THE | | | NORTHWOOD ROAD HISTORIC DISTRICT CONTINUES TO BE SHOWN | | | IN PLAN AND ELEVATION (SHEET A404) EXCEEDING THE | | | PERMITTED NUMBER OF STORIES AND BUILDING HEIGHT (3 | | | STORIES/44 FEET). NOTE: THE BUILDING IS CORRECTLY SHOWN | | | ON SHEET A113. ALL DRAWINGS MUST SHOW CONSISTENT, CODE | | | COMPLIANT CONDITIONS. | | | | | | 9) BUILDING C: THERE IS A DISCREPANCY WITH BUILDING C | | | IN PLAN AND IN ELEVATION. THE PLAN VIEW SHOWS THAT THE | | | 4TH STORY IS LOCATED ON THE NORTH SIDE OF THE ALLEY AND | | | THUS OUTSIDE OF THE NORTHWOOD ROAD HISTORIC DISTRICT | | | BOUNDARY. HOWEVER, THE ELEVATION VIEW ON SHEET A405 | | | SHOWS THE 4TH STORY EXTENDING INTO THE NORTHWOOD ROAD | | | HISTORIC DISTRICT, WHERE ONLY A 3-STORY BUILDING IS | | | PERMITTED. ALL DRAWINGS MUST SHOW CONSISTENT, CODE | | | COMPLIANT CONDITIONS. | | | | | | 10) PROVIDE THE SQUARE FOOTAGE FOR THE UNITS IN | | | BUILDING B SO THAT STAFF CAN VERIFY THAT THE MINIMUM | | | UNIT SIZE IS ACHIEVED. | | | | | | 11) BUILDING B SHOWS FOUR 1,200 SF TOWNHOUSES. THIS | | | UNIT'S SIZE/TYPE IS NOT LISTED ON THE UNIT MATRIX | | | BREAKDOWN. | | | | | | 12) BUILDING B IS NOT SHOWN IN THE SAME LOCATION IN | | | RELATIONSHIP TO THE WEST PROPERTY LINE ON SHEETS A113 | | | (ZERO FEET), A404 (5 FEET) AND A301 (10 FEET). ALL | | | DRAWINGS MUST SHOW CONSISTENT, CODE COMPLIANT | | | CONDITIONS. | | | | | | 13) THE WEST PROPERTY LINES DO NOT OVERLY THE SAME ON | | | SHEET A301. THIS LEADS TO INCORRECT SETBACK DIMENSIONS. | | | ADDITIONALLY, THE DIMENSION MUST BE FROM THE FURTHEST | | | PROJECTION. THE SUPPORT COLUMNS ARE SHOWN ENCROACHING | | | INTO THE REQUIRED 5-FOOT LANDSCAPE BUFFER. | | | | | | 14) PROVIDE THE ROOF PLAN FOR THE TOWER PORTION OF | | | BUILDING A. | | | | | | 15) PROVIDE THE HEIGHTS OF THE ROOFTOP MECHANICAL | | | EQUIPMENT AND THE MECHANICAL EQUIPMENT SCREENING | | | HEIGHTS FOR ALL THREE BUILDINGS SO THAT STAFF CAN | | | VERIFY THAT THE EQUIPMENT IS SCREENED IN ACCORDANCE | | | WITH THE NMUD REQUIREMENTS. | | | | | | 16) PROVIDE THE VISIBILITY TRIANGLE INFORMATION SO | | | STAFF CAN VERIFY COMPLIANCE WITH CODE FOR ALL CORNERS, | | | INCLUDING THE BROADWAY EXTENSION, THE ALLEY BETWEEN | | | BUILDING C, THE GARAGE RAMP AT 25TH STREET, AND THE NW | | | CORNER OF PINEWOOD AND NORTHWOOD ROAD. | | | | | | 17) THE MAXIMUM LOT WIDTH FOR FLEX BUILDINGS IS 200 | | | FEET. THE LOT CONTAINING BUILDING B IS 231 FEET LONG. | | | | | | 18) THE TOWER IS SHOWN ENCROACHING THE BROADWAY TOWER | | | SETBACK FROM THE PODIUM. THE 15-FOOT SETBACK LINE | | | DIMENSION TAG DOES NOT MATCH BLUE SETBACK LINE NOR DOES | | | IT SCALE TO 15 FEET. THE LINE SCALES TO 15 FEET. | | | | | | 19) SHEET A0.02 LISTS THE GROSS LAND AREA AS 144,250 | | | SQUARE FEET. SHEET L1.01 LISTS THE SITE AS HAVING | | | 88,595 SQUARE FEET, WHICH IS NOT THE AREA COVERED BY | | | BUILDING A. ALL PLANS MUST INCLUDE THE CORRECT AMOUNT | | | OF AREA. EACH DEVELOPMENT PARCEL, BUILDING A, B AND C, | | | MUST BE BROKEN DOWN SEPARATELY (INCLUDING THE ABANDONED | | | RIGHTS-OF-WAY) AND SHOW COMPLIANCE WITH THE PERVIOUS | | | AND IMPERVIOUS REQUIREMENTS. NOTE: THE LISTED 12,630 | | | SQUARE FEET OF PERVIOUS AREA WOULD NOT MEET THE MINIMUM | | | PERVIOUS AREA REQUIRED BY THE NMUD REGULATIONS, EITHER | | | INDIVIDUALLY OR COLLECTIVELY. | | | | | | 20) THE SETBACKS AND BUILDING FRONTAGE ALONG 23RD | | | STREET AND THE REMAINING SECTION OF PINEWOOD FOR | | | BUILDING A ARE NOT MET. | | | | | | 21) THE NMUD REGULATIONS REQUIRE THAT THE PRIMARY | | | ENTRANCE TO THE UPPER LEVELS OF A MIXED-USE BUILDING | | | SHALL BE FROM A PUBLIC RIGHT-OF-WAY. WHERE IS THE | | | PRIMARY ENTRANCE TO THE UPPER LEVELS OF BUILDING A? IT | | | APPEARS THAT IT IS EITHER THE NORTH OR SOUTH LOBBY, | | | NEITHER OF WHICH ACCESS A PUBLIC RIGHT-OF-WAY. PUTTING | | | THESE LOBBY ENTRANCES ADJACENT TO THE LOADING DOCKS AND | | | INTERNAL TO THE BUILDING DOES NOT PROVIDE AN | | | ATTRACTIVE, ACTIVE STREET PRESENCE FOR THE RESIDENTIAL | | | TOWER. THE MAIN ENTRANCE SHOULD BE PROMINENTLY ON | | | BROADWAY OR NORTHWOOD ROAD. | | | | | | 22) THE NMUD REGULATIONS REQUIRE THAT THE PRIMARY | | | ENTRANCE TO THE UPPER LEVELS OF A MIXED-USE BUILDING | | | SHALL BE FROM A PUBLIC RIGHT-OF-WAY. THE PRIMARY | | | ENTRANCE TO THE UPPER LEVELS OF BUILDING B IS SHOWN | | | FROM THE PRIVATE RIGHT-OF-WAY EXTENSION OF BROADWAY. | | | | | | 23) BUILDING C IS A FLEX BUILDING. TABLE VII-7 REQUIRES | | | THAT FLEX BUILDING THAT ABUTS A 15-FOOT WIDE ALLEY HAVE | | | A 15-FOOT SETBACK FROM THE EDGE OF THE ALLEY. BUILDING | | | C DOES NOT MEET THIS REQUIREMENT. STAFF IS NOT PREPARED | | | TO SUPPORT CHANGES TO THE SETBACK REQUIREMENTS OUTSIDE | | | OF THE CORE SUB-DISTRICT SINCE THIS WILL AFFECT | | | PROPERTIES THROUGHOUT NMUD. | | | | | | 24) THE NMUD REGULATIONS CURRENTLY LIMIT THE TOWER | | | FLOOR PLATE TO 30,000 SQUARE FEET FOR ANY SINGLE | | | FLOORPLATE WITH AND AVERAGE FLOORPLATE OF UP TO 20,000 | | | SQUARE FEET. THE TEXT AMENDMENT IS REQUESTING THAT THE | | | MAXIMUM FLOORPLATE CAN BE UP TO 50,000 SQUARE FEET. | | | PLEASE PROVIDE VERIFICATION THAT THE AVERAGE TOWER | | | FLOORPLATE IS 20,000 SQUARE FEET OR LESS. | | | | | | DESIGN STANDARDS | | | | | | 25) REPEAT COMMENT: NO INFORMATION WAS PROVIDED TO | | | VERIFY THE ACTIVE USE STANDARDS, THE FACADE | | | ARTICULATION REQUIREMENTS, THE ARCHITECTURAL TREATMENT | | | STANDARDS OR THE FENESTRATION STANDARDS THAT ARE | | | REQUIRED BY THE NMUD REGULATIONS. THIS SHALL BE | | | PROVIDED IN TABULAR FORM AND SHOWN ON THE ELEVATION | | | DRAWINGS. | | | | | | 26) STAFF WILL NOT SUPPORT THE AMENDMENT THAT WILL | | | PERMIT THE BUILDING THAT IS ALMOST 400 FEET IN LENGTH | | | ALONG BROADWAY AND 350 FEET IN LENGTH ALONG 25TH STREET | | | WITHOUT THE INCLUSION OF PLANAR BREAKS. | | | | | | 27) PROVIDE THE DIMENSIONS OF THE PROJECTIONS AND | | | ENCROACHMENTS (EX. BALCONIES AND OTHER ARCHITECTURAL | | | FEATURES) ON THE PLANS AND ELEVATIONS SO THAT STAFF CAN | | | VERIFY COMPLIANCE WITH THE NMUD REGULATIONS. | | | | | | 28) THE ROOF OF THE PASEO IS NOT RENDERED CORRECTLY. | | | THE SITE AND LANDSCAPE PLANS DO NOT SHOW HOLES IN THE | | | PARKING DECK THAT ARE ACCENTUATED WITH LANDSCAPE. | | | ADDITIONALLY, THE GRADE LEVEL LANDSCAPE THAT HAS BEEN | | | ADDED DOES NOT MATCH THE LANDSCAPE PLAN. YOU MAY NOT | | | PROVIDE INACCURATE RENDERINGS THAT MAKE THE FINAL | | | PRODUCT LOOK DIFFERENT THAN WHAT YOU ARE SHOWING IN THE | | | PLANS. | | | | | | STREETSCAPE | | | | | | 29) REPEAT COMMENT: NO DETAILS WERE PROVIDED ON THE | | | SITE LIGHTING TO VERIFY COMPLIANCE WITH THE NMUD | | | REGULATIONS. *** THIS IS REQUIRED PRIOR TO SCHEDULING A | | | PLANNING BOARD HEARING SO THAT STAFF CAN VERIFY THAT | | | THERE IS NO INCONSISTENCY WITH THE CODE REQUIREMENTS. | | | THE MIXED-USE DEVELOPMENT REGULATIONS REQUIRE THAT | | | STREETLIGHTS BE PROVIDED ALONG PUBLIC RIGHTS-OF-WAY | | | ADJACENT TO THE SITE. CLEARLY SHOW THE PEDESTRIAN | | | ORIENTED LIGHTING FOR THE SIDEWALKS ALONG THE SITE ON | | | THE PLANS. THE LANDSCAPE AND CIVIL PLANS INDICATE THAT | | | SOME EXISTING LIGHTS WILL REMAIN, BUT NOT ALL OF THE | | | SITE IS COVERED. ADDITIONALLY, IT DOES NOT APPEAR THAT | | | ALL OF THE EXISTING STREETLIGHT ORIENTATIONS ARE | | | ACCURATELY DEPICTED. STAFF MUST BE ABLE TO VERIFY THAT | | | THE LIGHTS DO NOT INTERFERE WITH PROPOSED TREE | | | CANOPIES. | | | | | | 30) PROVIDE VERIFICATION THAT WHERE THE SIDEWALKS OR | | | WALKWAYS CROSS THE DRIVEWAY ENTRANCES TO THE PARKING | | | FACILITIES, LOADING AREAS, OR STREETS (BOTH PRIVATE AND | | | PUBLIC), THE SIDEWALK OR WALKWAY IS CONTINUOUS AND | | | REMAINS AT A CONSTANT LEVEL. | | | | | | 31) VERIZON HAS APPROVAL TO INSTALL A WIRELESS | | | COMMUNICATION FACILITY POLE WITHIN THE BROADWAY | | | RIGHT-OF-WAY ADJACENT TO THE SITE. SHOW THE POLE ON THE | | | PLANS SO THAT STAFF CAN VERIFY THAT YOUR PLANS ARE | | | DESIGNED TO NOT HAVE CONFLICTS (EX. PROPOSED PARKING | | | SPACES, TREES, ETC.). | | | | | | 32) THE ARCHITECTURAL PLANS MUST SHOW THE MEDIANS IN | | | BROADWAY THAT ARE SHOWN ON THE CIVIL AND LANDSCAPE | | | PLANS. THE LANE WIDTH DIMENSIONS NEED TO BE PROVIDED AT | | | THESE LOCATIONS. | | | | | | 33) PLEASE EXPLAIN WHY THE PROPOSED ROADWAY CROSS | | | SECTIONS DO NOT COMPLY WITH THE FIGURES VII-16 AND | | | VII-18 STREET SECTIONS. THE STREET SECTIONS, COMBINED | | | WITH THE BUILDING SETBACKS ARE DESIGNED TO PROVIDE FOR | | | WIDE, PEDESTRIAN FRIENDLY SIDEWALKS. THIS DOES NOT | | | OCCUR ALONG PINEWOOD AND 25TH STREET. NO CROSS SECTION | | | WAS PROVIDED FOR NORTHWOOD ROAD, 23RD STREET, THE | | | BROADWAY EXTENSION AND THE PORTION OF PINEWOOD THAT IS | | | REMAINING. ADDITIONALLY, PINEWOOD EXCEEDS THE NMUD | | | MAXIMUM LANE WIDTH OF 10 FEET, WHICH UNLESS THE WIDER | | | WIDTH IS REQUIRED BY THE TRAFFIC ENGINEER, REQUIRES A | | | WAIVER. | | | | | | 34) BENCHES NEED TO BE DESIGNED TO PREVENT SLEEPING. | | | | | | 35) THERE ARE MULTIPLE LOCATIONS WHERE SHEET 301 SHOWS | | | THE LANDSCAPE PATTERN OVERLAID ON PAVEMENT. THE SITE | | | PLAN NEEDS TO ACCURATELY DEPICT WHAT IS SHOWN ON THE | | | LANDSCAPE PLAN. | | | | | | 36) THE DESIGN OF THE PASEO NEEDS TO BE REEXAMINED: | | | | | | A. THE 4.33-FOOT DIMENSION BETWEEN THE PLANTERS AND THE | | | STOREFRONTS IS NOT ADEQUATE FOR PEDESTRIANS TO | | | COMFORTABLY WINDOW SHOP. | | | B. THE PROPOSED TEXT HAD CONTEMPLATED RESTAURANT | | | OUTDOOR SEATING IN THE PASEO, YET BASED ON THE PLANTER | | | LOCATIONS, THERE IS NO ROOM FOR ANY OUTDOOR SEATING. | | | C. THE MICRO MOBILITY STATION IS LOCATED DIRECTLY IN | | | FRONT OF A DOORWAY. WHILE STAFF AGREES THAT A MICRO | | | MOBILITY STATION NEEDS TO BE LOCATED IN CLOSE PROXIMITY | | | TO THE PASEO, THE SPECIFIC LOCATION IS NOT AN | | | APPROPRIATE LOCATION. PROVIDE THE MICRO MOBILITY | | | STATION DIMENSIONS ON THE PLANS. | | | | | | PARKING/LOADING | | | | | | 38) NMUD ONLY PERMITS SURFACE PARKING LOTS TO THE SIDE | | | OR THE REAR OF A PROPERTY. THE PROPOSED PARKING LOT | | | FRONTING ON 23RD STREET DOES NOT MEET THIS STANDARD. | | | PLANNING STAFF DOES NOT SUPPORT A CODE AMENDMENT TO | | | PERMIT PARKING LOTS WITHIN THE BUILDING?S FRONT SETBACK | | | AREA. | | | | | | 39) THE SURFACE LOT, WHICH WHILE NOT PERMITTED BY THE | | | REGULATIONS, ALSO FAILS TO PROVIDE THE REQUIRED DIRECT | | | PEDESTRIAN ACCESS TO A PUBLIC WALKWAY, NOR DOES IT | | | PROVIDE THE REQUIRED LANDSCAPE BUFFER. | | | | | | 40) THE ENTRANCE TO THE SURFACE AND GARAGE PARKING AREA | | | FROM PINEWOOD EXCEEDS THE MAXIMUM PERMITTED 24 FEET IN | | | WIDTH DUE TO THE RADIUS STARTING INSIDE THE PROPERTY | | | LINE. THE RADIUS/FLAIR MAY NOT WIDEN UNTIL IT IS WITHIN | | | THE RIGHT-OF-WAY. | | | | | | 41) PROVIDE THE DIMENSIONS FOR THE LOADING ZONES ON THE | | | PLANS SO THAT STAFF CAN VERIFY CODE COMPLIANCE. 70K SF | | | OF COMMERCIAL USE REQUIRES TWO 10 X 50 FOOT SPACES. THE | | | SPACES PROVIDED ON THE PLANS DO NOT APPEAR TO BE 50 | | | FEET IN LENGTH. | | | | | | 42) ALL LEVELS OF THE PARKING GARAGE MUST BE SCREENED | | | BY A LINER BUILDING CONTAINING A MINIMUM DEPTH OF 20 | | | FEET IF HABITABLE SPACE. THIS IS NOT MET ALONG THE FULL | | | LENGTH OF 25TH STREET, NORTHWOOD ROAD AND 23RD STREET | | | AND PARTIALLY ALONG BROADWAY. THE PROPOSED CODE CHANGE | | | DID NOT ADDRESS THE FAILURE TO PROVIDE SCREENING. STAFF | | | WILL NOT SUPPORT BROADWAY NOT HAVING THE 20-FOOT DEPTH | | | OF HABITABLE SPACE. IF THE CODE IS AMENDED ON THE OTHER | | | FRONTAGES, THEN THERE NEEDS TO BE SPECIFIC LANGUAGE | | | DEALING WITH ARCHITECTURAL TREATMENT AND THE PROVISION | | | OF PLANAR BREAKS TO VARY THE FA?ADE IN ORDER TO CONCEAL | | | THE NON-HABITABLE PARKING. | | | | | | 43) REPEAT COMMENT: DEAD END PARKING ROWS FOR | | | UNASSIGNED PARKING ARE NOT PERMITTED WITHOUT A | | | TURNAROUND SPACE. THE PUBLIC PARKING SPACES ON THE | | | LOWER PARKING LEVEL MAY NOT BE LOCATED ON A DEAD-END | | | AISLE WITHOUT A TURNAROUND SPACE. FIVE PARKING SPACES | | | ON THE NORTHERN PORTION OF THE GARAGE WILL NEED TO BE | | | CONVERTED INTO TURN AROUND SPACES. | | | | | | 44) UPDATED COMMENT: ALL PARKING GARAGES MUST HAVE | | | DIRECT PEDESTRIAN ACCESS TO A PUBLIC WALKWAY. PROVIDE | | | WHICH ELEVATORS ARE FOR USE BY THE PUBLIC TO ACCESS THE | | | GROUND FLOOR. ADDITIONALLY, SINCE ALL OF THE ELEVATOR | | | ACCESS IS THROUGH SOME SORT OF LOBBY ON THE GROUND | | | FLOOR, PROVIDE INFORMATION ON HOW THE PUBLIC WILL BE | | | ABLE TO ACCESS THE LOBBY. THE SOUTH LOBBY, WHICH | | | PROVIDES ACCESS TO THE SOUTHERN, LOWER PARKING LEVEL | | | SEEMS TO BE A RESIDENT LOBBY. | | | | | | 45) COLUMNS ARE SHOWN IN DRIVE AISLES ON NORTH PORTION | | | OF THE LOWER LEVEL GARAGE. | | | | | | 46) MOST OF THE ADA ACCESS AISLES ON THE BOTH PARKING | | | LEVELS APPEAR TO HAVE A PORTION OF THE COLUMN | | | ENCROACHING. IF THIS IS NOT THE CASE, YOU NEED TO CLEAN | | | UP THE DRAWINGS TO SHOW NO ENCROACHMENTS. | | | | | | 47) ADA SPACE NEXT TO STAIRS ON THE EASTERN WALL OF | | | UPPER PARKING LEVEL HAS A COLUMN BLOCKING THE 5-FOOT | | | WIDE ACCESS AISLE AND NEEDS TO HAVE AN EXTRA FOOT ALONG | | | THE STAIRWELL WALL TO PERMIT ADEQUATE DOOR OPENING. | | | | | | 48) ALL PARKING SPACES NEXT TO A WALL NEED TO PROVIDE | | | AN EXTRA FOOT TO PERMIT ADEQUATE DOOR OPENING. | | | | | | 49) THE PARKING SPACES THAT HEAD AGAINST WALLS NEED | | | MORE CLARITY THAT THEY MEET THE REQUIRED 18-FOOT DEPTH. | | | THE SPACES WITH DIMENSION TAGS SHOW THE END OF THE | | | SPACE IN THE MIDDLE OF THE LINE SHOWING THE WALL, WHICH | | | MAKES THEM TOO SHORT. IF THIS IS A LINE WEIGHT ISSUE ON | | | THE PLAN VERSION, PROVIDE A CROSS SECTION THAT CLEARLY | | | DEMONSTRATES THAT THE PARKING STALLS AND DRIVE AISLES | | | HAVE SUFFICIENT DEPTH. THERE ARE SOME SPACES THAT THE | | | PARKING SPACE BOX IS SHOWN IN THE WALL (EX OVERLOOKING | | | THE RAMP ON THE LOWER PARKING LEVEL. | | | | | | 50) 20 SPACES ALONG THE NORTH WALL AND 10 SPACES ALONG | | | THE SOUTH WALL OF THE UPPER PARKING LEVEL AND 15 SPACES | | | ALONG THE NORTH WALL AND 8 SPACES ALONG THE SOUTH WALL | | | ON THE LOWER PARKING LEVEL DO NOT MEET THE MINIMUM | | | 18-FOOT STALL DEPTH. THIS IS 53 NON-COMPLIANT PARKING | | | SPACES. | | | | | | 51) THE PARKING RAMPS MAY NOT BE SHOWN ENCROACHING THE | | | COLUMNS AND WALLS ALONG THE WEST SIDE OF THE BUILDING. | | | | | | 52) THE STAIRWELLS ON THE EAST SIDE OF THE BUILDING | | | ENCROACH INTO THE DRIVE AISLES RESULTING IN THE CODE | | | REQUIRED 24-FOOT WIDTH NOT IN COMPLIANCE. | | | | | | 53) PROVIDE THE DETAILS ON HOW PEOPLE ARE PROTECTED | | | FROM THE EDGES OF THE PARKING RAMPS. THIS MAY AFFECT | | | THE PARKING STALLS ADJACENT TO THE RAMPS. | | | | | | 54) THE PARKING STALL DETAIL PROVIDED ON THE CIVIL PLAN | | | DOES NOT MEET CITY STANDARDS. PROVIDE THE ACCURATE | | | DETAIL. | | | | | | 55) THE RESPONSE STATES THAT THE TANDEM SPACES ARE FOR | | | RESIDENTS, WHICH DOES NOT PERMIT THE INSIDE SPACE TO BE | | | COUNTED TOWARD MEETING THE MINIMUM PARKING REQUIREMENTS | | | SINCE THE NMUD REQUIRES ONE PARKING SPACE PER UNIT. THE | | | INSIDE SPACE CANNOT BE ASSIGNED TO A UNIT THAT IS | | | DIFFERENT FROM THE OUTSIDE SPACE, SO IT MAY NOT COUNT. | | | | | | 56) THE PARKING PROVIDED TABLES SHALL CLEARLY SEPARATE | | | THE PROVIDE ADA SPACES FROM THE TOTAL PROVIDED SPACES | | | FOR EACH CATEGORY. THE CURRENT LINE ITEMS MAKE IT LOOK | | | LIKE THERE ARE ADA SPACES IN ADDITION TO THE REGULAR | | | SPACES. | | | | | | 57) 77,820 SQUARE FEET OF COMMERCIAL REQUIRES 156 | | | PARKING SPACES, NOT 152 OR 153 AS SHOWN ON DIFFERING | | | PARKING TABLES. THE TOTAL REQUIRED PARKING IS 534 | | | SPACES. | | | | | | 58) 53 PUBLIC PARKING SPACES ARE REQUIRED IN ACCORDANCE | | | WITH THE AGREEMENT WITH CRA AND NEED TO BE REFLECTED ON | | | THE PARKING TABLE AND THE PLANS. | | | | | | 59) EVEN WHEN NOT REMOVING THE PARKING SPACES THAT DO | | | NOT COMPLY WITH CODE DEPTH, WALL ADJACENCY OR DEAD-END | | | ROWS, THE PROJECT DOES NOT PROVIDE CODE MINIMUM | | | PARKING. THERE ARE 592 SPACES LISTED AS PROVIDED. | | | REMOVING THE 18 TANDEM AND 53 REQUIRED PUBLIC CRA | | | SPACES, RESULTS IN ONLY 521 PARKING SPACES PROVIDED, | | | WHICH IS LESS THAN THE REQUIRED 534 SPACES. | | | | | | 60) THE CRA AGREEMENT REQUIRES THAT THE DEVELOPER | | | CONSTRUCT PUBLIC PARKING SPACES IN AN AMOUNT TO EQUAL | | | 10% OF THE PARKING REQUIRED FOR THE PROJECT (53 PARKING | | | SPACES). WHILE THE PLANS DO NOT CLEARLY DEMONSTRATE | | | WHERE THE 53 CRA REQUIRED PARKING SPACES ARE LOCATED, | | | IT APPEARS THAT SOME OF THEM ARE INTENDED TO BE LOCATED | | | WITHIN THE ON-STREET PARKING SHOWN ON THE PLANS. SINCE | | | THE LANGUAGE REQUIRES THAT NEW PARKING SPACES BE | | | CONSTRUCTED TO MEET THE CRA REQUIREMENT, PROVIDE AN | | | EXISTING PARKING INVENTORY OF THE ON-STREET PARKING | | | SPACES. EXISTING PARKING SPACES MAY NOT BE COUNTED AS | | | NEWLY CONSTRUCTED SPACES, AND ANY SPACES BEING REMOVED, | | | WILL NEED TO BE REPLACED AND MAY NOT BE COUNTED AS | | | NEWLY CREATED PARKING SPACES. | | | | | | 61) THE PROJECT REQUIRES 16 BICYCLE SPACES FOR THE | | | COMMERCIAL PORTION AND 38 BICYCLE SPACES FOR THE | | | RESIDENTIAL PORTION. THERE ARE 54 TOTAL REQUIRED | | | BICYCLE PARKING SPACES. THIS SHALL BE CORRECTLY | | | REFLECTED ON THE PARKING TABLE. | | | | | | 62) WHO HAS ACCESS TO THE BICYCLE STORAGE AREA ON THE | | | UPPER PARKING LEVEL OF BUILDING A? | | | | | | 63) PROVIDE THE DIMENSIONS AND DETAIL FOR THE RACKS, | | | INCLUDING THE NUMBER OF SPACES, LOCATED IN THE BICYCLE | | | STORAGE ROOM AS WELL AS THE DIMENSIONS OF THE ROOM AND | | | THE RACKS IN THE ROOM. THIS SHALL BE PROVIDED ON ITS | | | OWN BICYCLE ROOM DETAIL SHEET THAT THIS AT A LEGIBLE | | | SCALE. | | | | | | 64) WHERE IS THE REQUIRED SHOWER AND CHANGING FACILITY | | | FOR THE COMMERCIAL TENANTS OF BUILDING A? | | | | | | 65) ALL ON-STREET BICYCLE PAD DIMENSIONS MUST BE | | | CLEARLY SHOWN ON THE PLANS SO THAT STAFF CAN VERIFY | | | THAT THERE IS SUFFICIENT ROOM AND THAT SIDEWALKS ARE | | | NOT BLOCKED. NUMEROUS BICYCLES RACKS ARE CURRENTLY | | | SHOWN BLOCKING SIDEWALKS. THE BICYCLE RACK DETAILS FOR | | | THESE SPACES NEED TO BE PROVIDED. | | | | | | 66) THE MICRO MOBILITY STATION NORTH OF BUILDING B MUST | | | BE RELOCATED. IT INTERFERES WITH A PROPOSED BICYCLE | | | RACK. | | | | | | LANDSCAPE | | | | | | 67) UPDATED COMMENT: THANK YOU FOR PROVIDING THE | | | REQUIRED LANDSCAPE BUFFER STRIP ALONG THE RAILROAD | | | RIGHT-OF-WAY. THE SITE PLAN SEEMS TO SHOW COLUMNS | | | ENCROACHING INTO THE LANDSCAPE BUFFER, WHICH IS NOT | | | PERMITTED. PLEASE REVIEW THE DRAWINGS FOR CLARITY SINCE | | | THE CIVIL AND LANDSCAPE PLANS DO NOT SHOW AN | | | ENCROACHMENT. | | | | | | 68) PROVIDE THE DIMENSIONS ON THE PLANS TO VERIFY THAT | | | A LANDSCAPE STRIP, A MINIMUM OF FIVE FEET IN WIDTH, IS | | | PROVIDED ALONG THE CURBSIDE ALONG THE STREET EDGE. IF | | | TREE GRATES ARE USED INSTEAD OF A LANDSCAPE STRIP, THEN | | | THE REQUIRED DIMENSION SHALL BE PROVIDED ON THE SITE | | | PLAN. NOTE: THE SOUTHWEST PORTION OF THE SITE FAILS TO | | | MEET THIS REQUIREMENT. THE LANDSCAPE AREA ADJACENT TO | | | THE PASEO ON BROADWAY ALSO FAILS TO MEET THIS | | | REQUIREMENT. | | | | | | 69) THE CODE STATES THAT A LANDSCAPE STRIP, NOT TREE | | | GRATES IS THE PREFERRED OPTION WHEN NO ON-STREET | | | PARKING IS PROVIDED. 23RD STREET AND 25TH STREET HAVE | | | NOT ON-STREET PARKING, SO A LANDSCAPE STRIP IS | | | REQUIRED. | | | | | | 70) THE CODE REQUIRES A MINIMUM UNOBSTRUCTED 60-INCH | | | AREA FOR THE SIDEWALK. THE SITE PLAN FAILS TO SHOW THE | | | EXISTING UTILITY POLES THAT ARE TO REMAIN ALONG 23RD | | | STREET ADJACENT TO BUILDING B. THEY ARE SHOWN ON THE | | | LANDSCAPE PLAN ? ENCROACHING INTO THE REQUIRED SIDEWALK | | | WIDTH, OVERLAPPING THE TREE PITS AND IN CONFLICT WITH | | | PROPOSED STREET TREE CANOPIES. | | | | | | 71) THERE IS A TREE SHOWN WHERE THE EXISTING FIRE | | | HYDRANT TO REMAIN IS SHOWN ON THE CIVIL PLAN IN FRONT | | | OF BUILDING C. | | | | | | 72) THERE ARE OAK TREES BEING SHOWN PLANTED ON TOP OF A | | | GAS LINE ALONG NORTHWOOD ROAD. PLEASE PROVIDE THE DEPTH | | | OF THE GAS LINE SO THAT STAFF CAN VERIFY THAT THERE IS | | | NO CONFLICT. | | | | | | HISTORIC PRESERVATION FUND | | | | | | 73) THIS PROJECT IS UTILIZING THE CORE SUBDISTRICT | | | HISTORIC PRESERVATION HEIGHT BONUS. PLEASE PROVIDE THE | | | AMOUNT OF SQUARE FOOTAGE BEING PROVIDED ABOVE THE | | | 80-FOOT BASE ZONING HEIGHT. | | | | | | PRIVATE OPEN SPACE | | | | | | 74) PRIVATE OPEN SPACE REQUIREMENTS ? NO CALCULATIONS | | | WERE PROVIDED. PRIVATE OPEN SPACES SHALL PROVIDE SHADED | | | AREAS, AND THEIR GROUND SURFACE SHALL BE A COMBINATION | | | OF PAVING MATERIALS, LAWN, OR GROUND COVER. | | | | | | 75) BUILDING A IS A MIXED-USE TOWER BUILDING, SO IT IS | | | REQUIRED TO PROVIDE A MINIMUM OF 10% COMMON, PRIVATE | | | OPEN SPACE ON SITE. IT APPEARS THAT THE INTENT IS TO | | | PROVIDE THE COMMON, PRIVATE OPEN SPACE ON THE ROOF OF | | | THE PARKING DECK. PROVIDE VERIFICATION THAT THE MINIMUM | | | AREA IS PROVIDED. | | | | | | 76) BUILDING B IS A MIXED-USE FLEX BUILDING, SO IT IS | | | REQUIRED TO PROVIDE A MINIMUM OF 10% COMMON, PRIVATE | | | OPEN SPACE ON SITE. THE PLANS SHOW NO COMMON, PRIVATE | | | OPEN SPACE PROVIDED FOR THIS BUILDING. | | | | | | 77) BUILDING C IS A MIXED-USE FLEX BUILDING, SO IT IS | | | REQUIRED TO PROVIDE A MINIMUM OF 10% COMMON, PRIVATE | | | OPEN SPACE ON SITE. THE PLANS SHOW NO COMMON, PRIVATE | | | OPEN SPACE PROVIDED FOR THIS BUILDING. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
11-18-2021 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
11-18-2021 |
Time |
09:24 |
Rev Time |
12.00 |
| Received By |
eschneid |
Date |
11-17-2021 |
Time |
20:33 |
Sent To |
|
|
| Notes |
| 2021-11-17 20:39:37 | CASE NO. 1895 | | | NORTHWOOD COMMONS - NMUD ANCHOR SITE | | | BROADWAY & 24TH STREET | | | | | | - CONTACT ERIC SCHNEIDER @ (561) 822-1446, | | | [email protected] | | | | | | - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FOUR | | | (4) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT | | | OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE | | | RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS | | | TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | - THE PPRC COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND | | | SUBMITTED TO THE PLANNING DIVISION BY 5 PM ON FRIDAY, | | | DECEMBER 3, 2021, TO BE ELIGIBLE TO BE SCHEDULED FOR | | | THE JANUARY 18, 2022 PLANNING BOARD MEETING. | | | | | | - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT | | | RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS | | | FROM THE DATE OF THE PPRC MEETING (BY JANUARY 18, | | | 2022), THE PLANNING DIVISION MAY NOTIFY THE APPLICANT | | | THAT THE CASE IS CONSIDERED WITHDRAWN. ANY FURTHER | | | ACTION SHALL REQUIRE A NEW DEVELOPMENT APPLICATION. | | | | | | - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($600). | | | | | | - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED | | | IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION | | | 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS. | | | | | | PLANNING STAFF BEGAN A REVIEW OF THE PLANS AND BEGAN TO | | | LIST DISCREPANCIES WITH THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS AND GENERAL ISSUES WITH THE QUALITY OF THE | | | INFORMATION PRESENTED ON THE PLANS. AFTER IDENTIFYING | | | OVER 30 COMMENTS, MANY WHICH WILL REQUIRE A REDESIGN OF | | | THE PLANS, PLANNING STOPPED THE REVIEW. THE PLANS NEED | | | TO BE CORRECTED TO COMPLY WITH THE CODE AND THE | | | INTERNAL INCONSISTENCIES AMONG THE PLAN SHEETS. STAFF | | | DID NOT FULLY VET OPEN SPACE, SETBACKS, STREETSCAPE, | | | MECHANICAL SCREENING AND LANDSCAPE COMPLIANCE TO NAME A | | | FEW, SO JUST BECAUSE COMMENTS WERE NOT ISSUED ABOUT A | | | PARTICULAR ASPECT OF THE PLAN, DO NOT ASSUME IT | | | COMPLIES. BASED ON WHAT STAFF HAS LISTED BELOW, STAFF | | | IS CONFIDENT THAT THERE ARE ADDITIONAL CODE | | | REQUIREMENTS THAT ARE NOT MET. | | | | | | 1) THE BUILDING HEIGHT IS NOT BEING MEASURED CORRECTLY. | | | IT DOES NOT START AT THE FINISHED FLOOR ELEVATION. | | | | | | 2) BUILDING A DOES NOT COMPLY WITH THE MAXIMUM NUMBER | | | OF STORIES AND BUILDING HEIGHT PERMITTED. | | | | | | A. THE MAXIMUM NUMBER OF STORIES PERMITTED WITHIN CORE | | | PARCELS A & B IS 8 STORIES (WITH THE HEIGHT BONUS). THE | | | BUILDING HAS 9 STORIES. IN ACCORDANCE WITH SECTION | | | 94-209.B.5., EACH PARKING GARAGE LEVEL AT THE FRONTAGE | | | LINE(S) SHALL EQUAL ONE STORY FOR THE PURPOSES OF | | | MEASURING BUILDING HEIGHT. THE PARKING GARAGE LEVEL | | | THAT YOU ARE DESIGNATING AS A MEZZANINE IS NOT A | | | MEZZANINE, IT IS A STORY SINCE IT IS ALONG MULTIPLE | | | FRONTAGE LINES. | | | B. THE MAXIMUM NUMBER OF STORIES/BUILDING HEIGHT | | | PERMITTED WITHIN THE AREA SOUTH OF CORE PARCEL B IS 4 | | | STORIES/56 FEET. THE ENTIRE ROW OF UNITS ON THE SOUTH | | | END OF THE BUILDING STARTING AT RESIDENCE LEVEL 4 | | | EXCEED THE PERMITTED NUMBER OF STORIES AND HEIGHT | | | PERMITTED. | | | | | | 3) BUILDING B DOES NOT COMPLY WITH THE NUMBER OF | | | STORIES AND BUILDING HEIGHT PERMITTED. | | | | | | A. THE MAXIMUM NUMBER OF STORIES/BUILDING HEIGHT | | | PERMITTED WITHIN THE HISTORICALLY DESIGNATED PORTION OF | | | THE TRANSITION SUBDISTRICT IS 3 STORIES/44 FEET. THE | | | BUILDING IN THIS AREA EXCEEDS THE PERMITTED NUMBER OF | | | STORIES AND HEIGHT. IF THE GROUND LEVEL IS INTENDED TO | | | CONTAIN A MEZZANINE THAT WOULD NOT COUNT AS A STORY, | | | THEN COMPLETE FLOOR PLANS SHOWING HOW THIS IS IN | | | REALITY A MEZZANINE MUST BE PROVIDED. THE CURRENT PLANS | | | SHOW THIS AS A FULL FLOOR. | | | B. THE MAXIMUM NUMBER OF STORIES PERMITTED WITHIN THE | | | AREA SOUTH OF CORE PARCEL B IS 4 STORIES FEET. THE | | | BUILDING IN THIS AREA EXCEEDS THE PERMITTED NUMBER OF | | | STORIES. IF THE GROUND LEVEL IS INTENDED TO CONTAIN A | | | MEZZANINE THAT WOULD NOT COUNT AS A STORY, THEN | | | COMPLETE FLOOR PLANS SHOWING HOW THIS IS IN REALITY A | | | MEZZANINE MUST BE PROVIDED. THE CURRENT PLANS SHOW THIS | | | AS A FULL FLOOR. | | | | | | 4) BUILDING C DOES NOT COMPLY WITH THE NUMBER OF | | | STORIES AND BUILDING HEIGHT PERMITTED. | | | | | | A. THE MAXIMUM NUMBER OF STORIES/BUILDING HEIGHT | | | PERMITTED WITHIN THE HISTORICALLY DESIGNATED PORTION OF | | | THE TRANSITION SUBDISTRICT IS 3 STORIES/44 FEET. THE | | | BUILDING IN THIS AREA EXCEEDS THE PERMITTED NUMBER OF | | | STORIES AND HEIGHT. THE PLANS CLEARLY CALL OUT A | | | 2-STORY GROUND LEVEL. | | | B. THE MAXIMUM NUMBER OF STORIES PERMITTED WITHIN THE | | | AREA SOUTH OF CORE PARCEL B IS 4 STORIES FEET. THE | | | BUILDING IN THIS AREA EXCEEDS THE PERMITTED NUMBER OF | | | STORIES. THE PLANS CLEARLY CALL OUT A 2-STORY GROUND | | | LEVEL. | | | | | | 5) THERE ARE PLAN SHEETS THAT CONTINUE TO SHOW BUILDING | | | C ENCROACHING INTO THE BROADWAY RIGHT-OF-WAY, WHICH IS | | | NOT PERMITTED. | | | | | | 6) THE GROUND FLOOR UNIT THAT WAS "CUT" TO AVOID | | | ENCROACHING INTO THE BROADWAY RIGHT-OF-WAY WAS NOT | | | UPDATED TO SHOW THE SQUARE FOOTAGE OR THAT IT EVEN | | | FUNCTIONS. | | | | | | 7) THE BUILDING A UNIT PLANS ARE INCOMPLETE. THERE ARE | | | UNITS THAT HAVE NOT INFORMATION PROVIDED. | | | | | | 8) THE ELEVATIONS FOR BUILDINGS B AND C DO NOT MATCH | | | THE FLOOR PLANS. | | | | | | 9) FULL FLOOR PLANS FOR BUILDINGS B AND C ARE REQUIRED | | | FOR STAFF TO SEE HOW THE BUILDINGS FUNCTION AS SHOWN. | | | | | | 10) PROVIDE A TRAFFIC PERFORMANCE STANDARDS APPROVAL | | | LETTER FROM THE PALM BEACH COUNTY TRAFFIC DIVISION FOR | | | THE FULL SCOPE OF THE PROPOSED DEVELOPMENT. | | | | | | 11) THE NUMBER OF UNITS AND THE NON-RESIDENTIAL SQUARE | | | FOOTAGE LISTED IN THE TRAFFIC IMPACT ANALYSIS DO NOT | | | MATCH THE SITE DATA ON THE PLANS. THE TRAFFIC IMPACT | | | ANALYSIS MUST REFLECT THE FULL SCOPE OF THE | | | DEVELOPMENT. | | | | | | 12) PROVIDE A PREDETERMINATION LETTER FROM FDOT FOR THE | | | IMPROVEMENTS WITHIN THE FDOT RIGHTS-OF-WAY OF BROADWAY | | | AND 25TH STREET ADJACENT TO THE PROJECT. | | | | | | 13) PROVIDE THE LETTER FROM COMCAST CONFIRMING THAT THE | | | PROPOSED PROJECT DOES NOT ENCROACH INTO THEIR EASEMENTS | | | OR OTHERWISE INTERFERE WITH THE PROVISIONS OF THEIR | | | SERVICES. | | | | | | 14) SECTION 94-209.J.1.C REQUIRES THAT PROJECTS WITH | | | THREE OR MORE DISTINCTLY SEPARATE BUILDINGS HAVE | | | SUBSTANTIALLY DIFFERENT FRONT ELEVATIONS. SUBSTANTIALLY | | | DIFFERENT FRONT ELEVATIONS SHALL INCLUDE BUT NOT BE | | | LIMITED TO VARIATIONS IN FENESTRATION, MATERIAL, | | | MASSING AND COLOR. THE PLANS AND NARRATIVE MUST VERIFY | | | THAT THE BUILDINGS COMPLY WITH THIS REQUIREMENT. | | | | | | 15) SHEET A404 SHOWS BUILDING C AS HAVING 4 EAST | | | ELEVATIONS. WHAT SHOULD BE LABELED AS THE NORTH AND | | | SOUTH ELEVATIONS DO NOT ALIGN WITH THE KEY PLAN. | | | | | | 16) SHEET A405 SHOWS BUILDING B AS HAVING 4 SOUTH | | | ELEVATIONS. | | | | | | 17) THE CITY'S MIXED USE DISTRICT DEFINES OPEN SPACE AS | | | AN IMPROVED OUTDOOR AREA OPEN TO THE SKY. FIGURE VII-3 | | | DESIGNATED PUBLIC OPEN SPACES AND GREENWAY REGULATING | | | PLAN REQUIRES PUBLIC OPEN SPACE WHERE 24TH STREET IS | | | PROPOSED FOR ABANDONMENT. THE DESIGN OF THE PROJECT | | | DOES NOT HAVE THIS AREA COMPLY WITH THE OPEN SPACE | | | DEFINITION; THEREFORE, THIS AREA DOES NOT COMPLY WITH | | | THE CODE REQUIREMENT. | | | | | | 18) THE ENTRANCES TO THE SURFACE AND GARAGE PARKING | | | AREAS EXCEED THE MAXIMUM PERMITTED 24 FEET IN WIDTH. | | | | | | 19) ALL LEVELS OF THE PARKING GARAGE MUST BE SCREENED | | | BY A LINER BUILDING CONTAINING A MINIMUM DEPTH OF | | | HABITABLE SPACE. STAFF RECOGNIZES THAT A VARIANCE TO | | | THIS PROVISION HAS BEEN PROVIDED, BUT STAFF DOES NOT | | | SUPPORT THE WAIVER REQUEST. | | | | | | 20) PROVIDE VERIFICATION THAT THE PARKING GARAGE HAS | | | DIRECT PEDESTRIAN ACCESS TO A PUBLIC WALKWAY. | | | | | | 21) SECTION 94-209.F.1.E REQUIRES A LANDSCAPE BUFFER | | | STRIP OF AT LEAST FIVE FEET WIDE SHALL BE PROVIDED | | | ALONG THE ENTIRE EDGE OF A PROPERTY ABUTTING A RAILROAD | | | RIGHT-OF-WAY. THE REQUIRED BUFFER HAS NOT BEEN | | | PROVIDED. PLANNING STAFF WILL NOT SUPPORT A WAIVER OF | | | THIS REQUIREMENT. | | | | | | 22) NO DETAILS WERE PROVIDED ON THE SITE LIGHTING TO | | | VERIFY COMPLIANCE WITH THE NMUD REGULATIONS. | | | | | | 23) PROVIDE HOW THE STOREFRONTS AT THE ABANDONED | | | PORTION OF 24TH STREET ARE BE DIRECTLY ACCESSIBLE FROM | | | A STREET FRONTAGE, URBAN GREENWAY OR PUBLIC, | | | SEMI-PUBLIC OR PRIVATE OPEN SPACE, GIVEN THAT THE | | | ABANDONED PORTION OF 24TH STREET DOES NOT MEET ANY OF | | | THESE DEFINITIONS. | | | | | | 24) NO INFORMATION WAS PROVIDED TO VERIFY THE ACTIVE | | | USE STANDARDS, THE FACADE ARTICULATION REQUIREMENTS, | | | THE ARCHITECTURAL TREATMENT STANDARDS OR THE | | | FENESTRATION STANDARDS. | | | | | | 25) NMUD DOES NOT PERMIT DWELLING UNITS CONTAINING LESS | | | THAN 550 SQUARE FEET, YET THE UNIT MATRIX SHOWS AT | | | LEAST 36 UNITS FAILING TO MEET THIS STANDARD. | | | | | | 26) DEAD END PARKING ROWS ARE NOT PERMITTED WITHOUT A | | | TURNAROUND SPACE. THERE ARE NUMEROUS THROUGHOUT THE | | | GARAGE. | | | | | | 27) THE PARKING SPACES AT THE TOP OF THE RAMPS ARE | | | UNSAFE GIVEN THE SLOPE OF THE RAMPS. | | | | | | 28) DESCRIBE WHO WILL USE THE TANDEM SPACES. | | | | | | 29) THERE ARE MISLABELED DIMENSION TAGS IN THE GARAGE. | | | | | | 30) THERE ARE STAIRS THAT DIRECTLY ENCROACH PARKING | | | SPACES AND DOORWAYS THAT CANNOT BE ACCESSED IF A CAR IS | | | PARKED IN THE SPACE IN FRONT OF THE DOOR. | | | | | | 31) NO DETAILS ON THE BICYCLE PARKING WAS PROVIDED, | | | BOTH FOR THE BICYCLE STORAGE ROOM AND THE STREET | | | BICYCLE PARKING. | | | | | | 32) THE VEHICLE LOADING/SERVICE AREAS MAY NOT USE CITY | | | RIGHTS-OF-WAY FOR MANEUVERING. | | | | | | 33) THE ARCHITECTURAL PLANS SHOW SUPPORT COLUMNS | | | LOCATED WITHIN PINEWOOD AVENUE, WHICH IS NOT PERMITTED. | | | PROVIDE PLANS THAT SHOW THE LOCATIONS OF THE STRUCTURAL | | | COLUMNS THAT ARE REQUIRED TO SUPPORT THE SPANS ACROSS | | | PINEWOOD AVENUE AND THE ABANDONED PORTION OF 25TH | | | STREET SO THAT STAFF CAN EVALUATE THE IMPACTS ON THE AT | | | GRADE LAYOUT. | | | | | | 34) THE INVITATION TO NEGOTIATE FOR THIS PROJECT | | | INCLUDED THE FOLLOWING LANGUAGE, "TRIRAIL COASTAL LINK | | | THE SOUTH FLORIDA REGIONAL TRANSIT AUTHORITY (SFRTA), | | | ALONG WITH STATE, REGIONAL AND LOCAL PARTNERS, IS | | | PLANNING THE CREATION OF A TRIRAIL COASTAL LINK RAIL | | | CONNECTION ALONG THE FEC RAILWAY FROM MIAMI TO JUPITER. | | | IN PREVIOUS PLANS THE ANCHOR SITE WAS CONSIDERED AS ONE | | | OF THE POTENTIAL LOCATIONS FOR A FUTURE TRI-RAIL STOP. | | | CURRENT PLANS DO NOT INCLUDE THE ANCHOR SITE IN "PHASE | | | 1"? OF THE RAIL CONNECTION; HOWEVER, DEVELOPMENT ON | | | THIS SITE SHOULD CONSIDER THE POSSIBILITY OF A FUTURE | | | STOP AND DEVELOPERS WOULD BE ENCOURAGED TO SUPPORT THE | | | RAIL CONNECTION AT THIS LOCATION. THE CRA'S NORTH END | | | VISION CONSIDERS THE ANCHOR SITE AS A PRIME RAIL STOP | | | LOCATION. CURRENT LOCATIONS AND STUDIES CAN BE LOCATED | | | AT HTTP://TRI-RAILCOASTALLINK.COM/." EXPLAIN HOW THE | | | PLANS PROVIDE A CONNECTION AT THIS LOCATION. | | | |
|
|
| |