Plan Review Details - Project Z21060014
Plan Review Stops For Project Z21060014
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 07-09-2021 Cont ID  
Sent By scwelter Date 07-09-2021 Time 14:00 Rev Time 0.00
Received By ajones Date 07-09-2021 Time 14:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 07-07-2021 Cont ID  
Sent By rbrown Date 07-07-2021 Time 20:39 Rev Time 0.00
Received By rbrown Date 07-07-2021 Time 20:39 Sent To  
Notes
2021-07-07 20:41:05DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status P Date 07-01-2021 Cont ID  
Sent By rrossano Date 07-01-2021 Time   Rev Time  
Received By rrossano Date 07-01-2021 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 07-06-2021 Cont ID  
Sent By pleduc Date 07-06-2021 Time   Rev Time 0.00
Received By pleduc Date 07-06-2021 Time 11:22 Sent To  
Notes
2021-07-06 11:23:08FIRE HAS NO OBJECTIONS TO THE PROPOSED AND APPROVES.
  
 FIRE'S APPROVAL OF THIS SUBMITTED PROJECT DOES NOT
 CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 FIRE SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT THE
 APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 3 Status P Date 02-16-2022 Cont ID  
Sent By rcaranci Date 02-16-2022 Time 14:16 Rev Time 0.00
Received By rcaranci Date 02-16-2022 Time 14:16 Sent To  
Notes
2022-02-16 14:18:49FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT : PROPOSED DRIVE-THRU POD D GOLDEN SHOPPES
 Z21060014 RESUBMITTAL
  
 FEBRUARY 16, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. SATISFIED. THE GREEN BUTTON WOOD ON THE FAR SOUTH
 POINT OF THE DIVIDER MEDIAN COULD CAUSE A VISIBILITY
 ISSUE FOR DRIVERS AS IT MATURES. ADJUST TREE LOCATION
 TO MINIMIZE VISIBILITY ISSUES.
  
 2. SATISFIED. PROVIDE SCREENING FOR ALL GROUND MOUNTED
 VALVES AND EQUIPMENT. LOCATIONS IF ANY NEED TO BE
 SHOWN.
  
 3. PARTIALLY SATISFIED. SHOW PROPOSED LOCATIONS OF
 WATER SEWER AND DRAINAGE LINES, LIGHTING ON LANDSCAPE
 PLAN.
 LIGHTING LOCATIONS NEED TO BE SHOWN CLEARLY. PROVIDE A
 PHOTOMETRIC PLAN.
  
 4. SATISFIED. PLANTING ON EDGE OF PARKING SPACE SHALL
 BE NO HIGHER THAN 6 INCHES ABOVE CURB AND 24IN WIDE TO
 PREVENT DAMAGE TO LANDSCAPE FROM VEHICULAR
 ENCROACHMENT. PLEASE VERIFY SUNSHINE MIMOSA PLANTING
 AREA TO ACCOMMODATE THIS AND MINIMIZE DAMAGE TO SHRUBS
 .
 94-441 C 5 LANDSCAPE AREAS AND PLANT MATERIALS MUST BE
 PROTECTED FROM VEHICULAR ENCROACHMENT BY CURBS OR WHEEL
 STOPS. PARKED VEHICLES SHALL NOT EXTEND INTO A
 LANDSCAPED BUFFER AREA THAT IS FIVE OR LESS FEET WIDE
 UNLESS TWO ADDITIONAL FEET ARE ADDED TO THE BUFFER. THE
 TWO ADDITIONAL FEET OF LANDSCAPING SHALL CONTAIN NO
 PLANT, IRRIGATION DEVICE, OR OTHER OBJECT HIGHER THAN
 SIX INCHES ABOVE THE TOP OF THE CURB OF SUBSECTION (A)
 OF THIS SECTION. LANDSCAPE AREAS AND SIDEWALKS IN THE
 VEHICULAR USE AREA SHALL BE DESIGNED IN ACCORDANCE WITH
 THE MINIMUM REQUIREMENTS SET FORTH IN FIGURE XIV-2. THE
 USAGE OF CURBS IS MORE PREFERABLE TO WHEEL STOPS.
 HOWEVER, WHEEL STOPS SHOULD BE UTILIZED WHEN ON-SITE
 DRAINAGE IS A CONCERN. CURBING AND USAGE OF WHEEL STOPS
 ARE SUBJECT TO THE FOLLOWING REQUIREMENTS:
  
 ADDITIONAL COMMENTS 12/15/21:
 5. SATISFIED. BIKE RACK IS SHOWN IN EXISTING LANDSCAPE
 ISLAND WHERE THERE SHOULD BE A REQUIRED TREE. SHOW
 REQUIRED APPROVED TREES IN THE TWO LANDSCAPE ISLANDS ON
 EITHER SIDE OF THE TWO PARKING SPACES WEST OF THE DRIVE
 THROUGH LANE.
  
 CONDITION OF APPROVAL
  
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREE ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 12-15-2021 Cont ID  
Sent By rcaranci Date 12-15-2021 Time 15:29 Rev Time 0.00
Received By rcaranci Date 12-15-2021 Time 15:29 Sent To  
Notes
2021-12-15 15:30:13FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT : PROPOSED DRIVE-THRU POD D GOLDEN SHOPPES
 Z21060014 RESUBMITTAL
  
 DECEMBER 15, 2021
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. SATISFIED. THE GREEN BUTTON WOOD ON THE FAR SOUTH
 POINT OF THE DIVIDER MEDIAN COULD CAUSE A VISIBILITY
 ISSUE FOR DRIVERS AS IT MATURES. ADJUST TREE LOCATION
 TO MINIMIZE VISIBILITY ISSUES.
  
 2. SATISFIED. PROVIDE SCREENING FOR ALL GROUND MOUNTED
 VALVES AND EQUIPMENT. LOCATIONS IF ANY NEED TO BE
 SHOWN.
  
 3. PARTIALLY SATISFIED. SHOW PROPOSED LOCATIONS OF
 WATER SEWER AND DRAINAGE LINES, LIGHTING ON LANDSCAPE
 PLAN.
 LIGHTING LOCATIONS NEED TO BE SHOWN CLEARLY. PROVIDE A
 PHOTOMETRIC PLAN.
  
 4. SATISFIED. PLANTING ON EDGE OF PARKING SPACE SHALL
 BE NO HIGHER THAN 6 INCHES ABOVE CURB AND 24IN WIDE TO
 PREVENT DAMAGE TO LANDSCAPE FROM VEHICULAR
 ENCROACHMENT. PLEASE VERIFY SUNSHINE MIMOSA PLANTING
 AREA TO ACCOMMODATE THIS AND MINIMIZE DAMAGE TO SHRUBS
 .
 94-441 C 5 LANDSCAPE AREAS AND PLANT MATERIALS MUST BE
 PROTECTED FROM VEHICULAR ENCROACHMENT BY CURBS OR WHEEL
 STOPS. PARKED VEHICLES SHALL NOT EXTEND INTO A
 LANDSCAPED BUFFER AREA THAT IS FIVE OR LESS FEET WIDE
 UNLESS TWO ADDITIONAL FEET ARE ADDED TO THE BUFFER. THE
 TWO ADDITIONAL FEET OF LANDSCAPING SHALL CONTAIN NO
 PLANT, IRRIGATION DEVICE, OR OTHER OBJECT HIGHER THAN
 SIX INCHES ABOVE THE TOP OF THE CURB OF SUBSECTION (A)
 OF THIS SECTION. LANDSCAPE AREAS AND SIDEWALKS IN THE
 VEHICULAR USE AREA SHALL BE DESIGNED IN ACCORDANCE WITH
 THE MINIMUM REQUIREMENTS SET FORTH IN FIGURE XIV-2. THE
 USAGE OF CURBS IS MORE PREFERABLE TO WHEEL STOPS.
 HOWEVER, WHEEL STOPS SHOULD BE UTILIZED WHEN ON-SITE
 DRAINAGE IS A CONCERN. CURBING AND USAGE OF WHEEL STOPS
 ARE SUBJECT TO THE FOLLOWING REQUIREMENTS:
  
 ADDITIONAL COMMENTS 12/15/21:
  
 5. BIKE RACK IS SHOWN IN EXISTING LANDSCAPE ISLAND
 WHERE THERE SHOULD BE A REQUIRED TREE. SHOW REQUIRED
 APPROVED TREES IN THE TWO LANDSCAPE ISLANDS ON EITHER
 SIDE OF THE TWO PARKING SPACES WEST OF THE DRIVE
 THROUGH LANE.
  
 CONDITION OF APPROVAL
  
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREE ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 07-06-2021 Cont ID  
Sent By aburnett Date 07-06-2021 Time 16:21 Rev Time 0.00
Received By aburnett Date 07-06-2021 Time 16:20 Sent To  
Notes
2021-07-06 16:21:40FROM: ANDREW BURNETT, LANDSCAPE PLANNER 561-822-1562
 PROJECT: PROPOSED DRIVE-THRU POD D GOLDEN SHOPPS
 Z21060014
  
 1. THE GREEN BUTTON WOOD ON THE FAR SOUTH POINT OF THE
 DIVIDER MEDIAN COULD CAUSE A VISIBILITY ISSUE FOR
 DRIVERS AS IT MATURES. ADJUST TREE LOCATION TO MINIMIZE
 VISIBILITY ISSUES.
  
 2. PROVIDE SCREENING FOR ALL GROUND MOUNTED VALVES AND
 EQUIPMENT. LOCATIONS IF ANY NEED TO BE SHOWN.
  
 3. SHOW PROPOSED LOCATIONS OF WATER SEWER AND DRAINAGE
 LINES, LIGHTING ON LANDSCAPE PLAN.
  
 4. PLANTING ON EDGE OF PARKING SPACE SHALL BE NO
 HIGHER THAN 6 INCHES ABOVE CURB AND 24IN WIDE TO
 PREVENT DAMAGE TO LANDSCAPE FROM VEHICULAR
 ENCROACHMENT. PLEASE VERIFY SUNSHINE MIMOSA PLANTING
 AREA TO ACCOMMODATE THIS AND MINIMIZE DAMAGE TO SHRUBS
 .
 94-441 C 5 LANDSCAPE AREAS AND PLANT MATERIALS MUST BE
 PROTECTED FROM VEHICULAR ENCROACHMENT BY CURBS OR WHEEL
 STOPS. PARKED VEHICLES SHALL NOT EXTEND INTO A
 LANDSCAPED BUFFER AREA THAT IS FIVE OR LESS FEET WIDE
 UNLESS TWO ADDITIONAL FEET ARE ADDED TO THE BUFFER. THE
 TWO ADDITIONAL FEET OF LANDSCAPING SHALL CONTAIN NO
 PLANT, IRRIGATION DEVICE, OR OTHER OBJECT HIGHER THAN
 SIX INCHES ABOVE THE TOP OF THE CURB OF SUBSECTION (A)
 OF THIS SECTION. LANDSCAPE AREAS AND SIDEWALKS IN THE
 VEHICULAR USE AREA SHALL BE DESIGNED IN ACCORDANCE WITH
 THE MINIMUM REQUIREMENTS SET FORTH IN FIGURE XIV-2. THE
 USAGE OF CURBS IS MORE PREFERABLE TO WHEEL STOPS.
 HOWEVER, WHEEL STOPS SHOULD BE UTILIZED WHEN ON-SITE
 DRAINAGE IS A CONCERN. CURBING AND USAGE OF WHEEL STOPS
 ARE SUBJECT TO THE FOLLOWING REQUIREMENTS:
  
 CONDITION OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREE ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT.
  

Review Stop PARK PARKING
Rev No 1 Status N Date 02-01-2022 Cont ID  
Sent By ajones Date 02-01-2022 Time 13:28 Rev Time 0.00
Received By ajones Date 02-01-2022 Time 13:28 Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status N Date 02-01-2022 Cont ID  
Sent By ajones Date 02-01-2022 Time 13:29 Rev Time 0.00
Received By ajones Date 02-01-2022 Time 13:28 Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status P Date 06-24-2021 Cont ID  
Sent By   Date 06-24-2021 Time   Rev Time  
Received By   Date 06-24-2021 Time   Sent To  
Notes
2021-06-24 15:39:43NO OBJECTION FROM PUBLIC WORKS FOR THE PROPOSED
 DRIVE-THRU.
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045

Review Stop STORM STORMWATER
Rev No 3 Status P Date 02-17-2022 Cont ID  
Sent By tward Date 02-17-2022 Time 11:43 Rev Time 0.00
Received By tward Date 02-17-2022 Time 12:04 Sent To  
Notes
2022-02-17 12:03:24THE FOLLOWIONG COMMENTS ARE FROM THE REVIEW OF THE
 2/9/2022 SUBMITTAL:
  
 4. [PARTIALLY SATISFIED - PROVIDE VERTICAL DATUM AND
 CONVERSION EQUATION TO SHEET C600 ON ENGINEERING PERMIT
 SUBMITTAL.] LIST THE VERTICAL DATUM ON EVERY SHEET WITH
 ELEVATION INFORMATION. PROVIDE THE CONVERSION EQUATION
 TO NGVD1929 IF DATUM IS DIFFERENT.
  
 5. [SATISFIED] PROVIDE A CROSS SECTION FROM THE EAST
 PARCEL LINE TO THE FACE OF THE BUILDING SHOWING SURFACE
 FEATURES AND TYPICAL PAVEMENT SLOPES.
  
 7. [SATISFIED] CD100 SITE DEMOLITION PLAN
 A. ADD NOTES FOR ALL STORM PIPES AND STRUCTURES WITHIN
 THE DEMOLITION AREA THAT IS TO REMAIN.
 B. ADD VERTICAL DATUM REFERENCE AND CONVERSION EQUATION
 TO NGVD1929.
  
 8. [SATISFIED] CG100 PGD PLAN
 A. PROVIDE CONVERSION EQUATION TO NGVD1929.
 B. PROPOSED GRADING FOR DRIVE-THROUGH LANE TO THE EAST
 OF THE BUILDING SHOWS A LONG FLAT AREA.
 C. PROPOSED GRADING FOR THE TRAVEL LANE EAST OF THE
 ANGLED PARKING SHOWS LONG FLAT AREA.
 D. PROVIDE SPOT GRADES FOR THE FLOW LINE DOWN THE
 CENTER OF THE TRAVEL LANE EAST OF THE ANGLED PARKING.
 E. NO CURBING SHOWN FOR THE GREEN SPACE BETWEEN
 SIDEWALKS ON THE EAST SIDE OF THE BEGINNING OF THE
 TRAVEL LANE FOR THE ANGLED PARKING.
 F. NO CURBING SHOWN AROUND THE GREEN SPACE ON THE WEST
 SIDE OF THE END OF THE DRIVE THROUGH LANE.
  
 9. [ALL BUT 'E' SATISFIED. CAN BE ADDRESSED AT
 ENGINEERING PERMIT SUBMITTAL. PROVIDE AND/OR MODIFY THE
 DETAIL FOR PARKING SPACE STRIPING.] CR300 SIGNAGE AND
 STRIPING PLAN
 A. CROSSWALK STRIPING SHOULD MATCH EXISTING CROSS WALK
 STRIPING IN OTHER AREAS OF THE DEVELOPMENT TO BE
 CONSISTENT.
 B. IS A DO NOT ENTER SIGN NEEDED AT NORTH END OF DRIVE
 THROUGH LANE?
 C. ARE ONE WAY SIGNS NEEDED AT THE NORTH END OF THE
 ANGLED PARKING AREA?
 D. STOP BARS FOR DRIVE THROUGH LANE AND FOR ANGLED
 PARKING AREA.
 E. STRIPING BETWEEN PARKING SPACES (PARALLEL LINES
 CLOSED AT ONE END) SHALL CONFORM TO CITY'S CODE OF
 ORDINANCES (STALL PAINTING DETAIL SECTION 94-485)..
  
 10. [SATISFIED] C600 CONSTRUCTION DETAILS
 A. ANGLED PARKING DETAIL - PARKING SPACE WIDTH IS SHOWN
 AS 9 FT IN THE DETAIL DRAWING AND CALLED OUT AS 8 FT 6
 IN ON SHEET CR300.
 B. SECTION A-A: SHOW SIDEWALK/CURB TO THE RIGHT OF THE
 ANGLED PARKING AS MONOLITHIC SIDEWALK.
 C. DIMENSION THE MONOLITHIC SIDEWALK.
 D. SHOW WHICH WAY THE MONOLITHIC SIDEWALK IS SLOPED.
 E. HOW WILL THE DRIVE-THROUGH TRANSACTIONS OCCUR ACROSS
 THE 5 FEET WIDE MONOLITHIC SIDEWALK NEXT TO THE
 BUILDING?
 F. WILL THE 5 FEET WIDE MONOLITHIC SIDEWALK NEXT TO THE
 BUILDING HAVE A THICKENED EDGE?
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  

Review Stop STORM STORMWATER
Rev No 2 Status F Date 01-20-2022 Cont ID  
Sent By tward Date 01-20-2022 Time 08:22 Rev Time 0.00
Received By tward Date 01-20-2022 Time 08:35 Sent To  
Notes
2022-01-20 08:35:33THE FOLLOWIONG COMMENTS ARE FROM THE REVIEW OF THE
 12/7/2021 SUBMITTAL:
  
 1. [SATISFIED] NO ENGINEERING PLANS (PAVING, GRADING,
 DRAINAGE) WERE PROVIDED.
  
 2. [SATISFIED] CONSIDER REDUCING LENGTH OF THE ANGLED
 PARKING SPACES BY PROVIDING 2 FEET OF LANDSCAPED
 OVERHANG, IF NOT INCLUDED IN THE CURRENT DESIGN.
  
 3. [SATISFIED] PROVIDE THE ANGLE FOR THE ANGLED PARKING
 SPACES.
  
 4. [PARTIALLY SATISFIED - SEE COMMENTS BELOW] LIST THE
 VERTICAL DATUM ON EVERY SHEET WITH ELEVATION
 INFORMATION. PROVIDE THE CONVERSION EQUATION TO
 NGVD1929 IF DATUM IS DIFFERENT.
  
 5. [PARTIALLY SATISFIED - SEE COMMENTS BELOW] PROVIDE A
 CROSS SECTION FROM THE EAST PARCEL LINE TO THE FACE OF
 THE BUILDING SHOWING SURFACE FEATURES AND TYPICAL
 PAVEMENT SLOPES.
  
 6. [SATISFIED] SHOW UTILITIES ON THE LANDSCAPE PLANS.
  
 ADDITONAL COMMENTS:
 7. CD100 SITE DEMOLITION PLAN
 A. ADD NOTES FOR ALL STORM PIPES AND STRUCTURES WITHIN
 THE DEMOLITION AREA THAT IS TO REMAIN.
 B. ADD VERTICAL DATUM REFERENCE AND CONVERSION EQUATION
 TO NGVD1929.
  
 8. CG100 PGD PLAN
 A. PROVIDE CONVERSION EQUATION TO NGVD1929.
 B. PROPOSED GRADING FOR DRIVE-THROUGH LANE TO THE EAST
 OF THE BUILDING SHOWS A LONG FLAT AREA.
 C. PROPOSED GRADING FOR THE TRAVEL LANE EAST OF THE
 ANGLED PARKING SHOWS LONG FLAT AREA.
 D. PROVIDE SPOT GRADES FOR THE FLOW LINE DOWN THE
 CENTER OF THE TRAVEL LANE EAST OF THE ANGLED PARKING.
 E. NO CURBING SHOWN FOR THE GREEN SPACE BETWEEN
 SIDEWALKS ON THE EAST SIDE OF THE BEGINNING OF THE
 TRAVEL LANE FOR THE ANGLED PARKING.
 F. NO CURBING SHOWN AROUND THE GREEN SPACE ON THE WEST
 SIDE OF THE END OF THE DRIVE THROUGH LANE.
  
 9. CR300 SIGNAGE AND STRIPING PLAN
 A. CROSSWALK STRIPING SHOULD MATCH EXISTING CROSS WALK
 STRIPING IN OTHER AREAS OF THE DEVELOPMENT TO BE
 CONSISTENT.
 B. IS A DO NOT ENTER SIGN NEEDED AT NORTH END OF DRIVE
 THROUGH LANE?
 C. ARE ONE WAY SIGNS NEEDED AT THE NORTH END OF THE
 ANGLED PARKING AREA?
 D. STOP BARS FOR DRIVE THROUGH LANE AND FOR ANGLED
 PARKING AREA.
 E. STRIPING BETWEEN PARKING SPACES (PARALLEL LINES
 CLOSED AT ONE END) SHALL CONFORM TO CITY?S CODE OF
 ORDINANCES (STALL PAINTING DETAIL SECTION 94-485)..
  
 10. C600 CONSTRUCTION DETAILS
 A. ANGLED PARKING DETAIL - PARKING SPACE WIDTH IS SHOWN
 AS 9 FT IN THE DETAIL DRAWING AND CALLED OUT AS 8 FT 6
 IN ON SHEET CR300.
 B. SECTION A-A: SHOW SIDEWALK/CURB TO THE RIGHT OF THE
 ANGLED PARKING AS MONOLITHIC SIDEWALK.
 C. DIMENSION THE MONOLITHIC SIDEWALK.
 D. SHOW WHICH WAY THE MONOLITHIC SIDEWALK IS SLOPED.
 E. HOW WILL THE DRIVE-THROUGH TRANSACTIONS OCCUR ACROSS
 THE 5 FEET WIDE MONOLITHIC SIDEWALK NEXT TO THE
 BUILDING?
 F. WILL THE 5 FEET WIDE MONOLITHIC SIDEWALK NEXT TO THE
 BUILDING HAVE A THICKENED EDGE?
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  

Review Stop STORM STORMWATER
Rev No 1 Status F Date 07-08-2021 Cont ID  
Sent By tward Date 07-08-2021 Time 10:30 Rev Time 0.00
Received By tward Date 07-08-2021 Time 10:31 Sent To  
Notes
2021-07-08 10:31:39THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. NO ENGINEERING PLANS (PAVING, GRADING, DRAINAGE)
 WERE PROVIDED.
  
 2. CONSIDER REDUCING LENGTH OF THE ANGLED PARKING
 SPACES BY PROVIDING 2 FEET OF LANDSCAPED OVERHANG, IF
 NOT INCLUDED IN THE CURRENT DESIGN.
  
 3. PROVIDE THE ANGLE FOR THE ANGLED PARKING SPACES.
  
 4. LIST THE VERTICAL DATUM ON EVERY SHEET WITH
 ELEVATION INFORMATION. PROVIDE THE CONVERSION EQUATION
 TO NGVD1929 IF DATUM IS DIFFERENT.
  
 5. PROVIDE A CROSS SECTION FROM THE EAST PARCEL LINE TO
 THE FACE OF THE BUILDING SHOWING SURFACE FEATURES AND
 TYPICAL PAVEMENT SLOPES.
  
 6. SHOW UTILITIES ON THE LANDSCAPE PLANS.
  
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3. PROVIDE A COPY OF THE SFWMD ERP MODIFICATION BEFORE
 THE START OF CONSTRUCTION.
  
 4. DRAINAGE CALCULATIONS WILL BE REVIEWED WITH THE
 ENGINEERING PERMIT APPLICATION.
  
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 01-13-2022 Cont ID  
Sent By vnoel Date 01-13-2022 Time 07:32 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
***NONE***

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 07-06-2021 Cont ID  
Sent By vnoel Date 07-06-2021 Time 09:26 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2021-07-06 09:32:491. SURVEY NEEDS TO BE SIGNED AND SEALED AND WITHIN 1
 YEAR OLD.
 2. SHOWS LIMITS OF DEMOLITION AND NEW PAVING/GRADING
 PLAN.
 3. SHOW EXISTING IMPROVEMENTS OF ADJOINING PROPERTY
 ALONG EAST PROPERTY LINE.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 3 Status P Date 01-13-2022 Cont ID  
Sent By   Date 01-13-2022 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2022-01-13 14:56:57TRAFFIC COMMENTS
 1) SATISFIED. PROVIDE COUNTY TPS LETTER. PLEASE CONFIRM
 WITH THE COUNTY THAT A BY-PASS LANE IS NOT REQUIRED
  
 SITE COMMENTS
 2) SATISFIED. VERIFY AND SHOW ON THE SITE PLAN THAT
 PARKING STALLS AND DRIVEWAY DIMENSIONS ARE COMPLIANT
 WITH THE ONES SHOWN IN FIGURE XV-2 OF CITY CODE SECTION
 94. ASSUMING A 30 DEGREE ANGLE STANDARD STALL, THE
 FOLLOWING DIMENSIONS ARE MISSING OR INCORRECT: B STALL
 WIDTH (8?6?), C STALL DEPTH (16?4?), E CURB LENGTH
 (17?), F HALF BAY (28?4?)
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status F Date 12-07-2021 Cont ID  
Sent By   Date 12-07-2021 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2021-12-07 20:13:00TRAFFIC COMMENTS
 1) SATISFIED. PROVIDE COUNTY TPS LETTER. PLEASE CONFIRM
 WITH THE COUNTY THAT A BY-PASS LANE IS NOT REQUIRED
  
 SITE COMMENTS
 1) NOT SATISFIED. VERIFY AND SHOW ON THE SITE PLAN THAT
 PARKING STALLS AND DRIVEWAY DIMENSIONS ARE COMPLIANT
 WITH THE ONES SHOWN IN FIGURE XV-2 OF CITY CODE SECTION
 94. ASSUMING A 30 DEGREE ANGLE STANDARD STALL, THE
 FOLLOWING DIMENSIONS ARE MISSING OR INCORRECT: B STALL
 WIDTH (8'6"), C STALL DEPTH (16'4"), E CURB LENGTH
 (17'), F HALF BAY (28'4"). PLEASE REFER TO THE "STALL
 PAINTING DETAIL" FIGURE RIGHT BELOW FIGURE XV-2 FOR
 CORRECT DIMENSIONING.
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 07-08-2021 Cont ID  
Sent By   Date 07-08-2021 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2021-07-08 11:46:18TRAFFIC COMMENTS
 1) PROVIDE COUNTY TPS LETTER. PLEASE CONFIRM WITH THE
 COUNTY THAT A BY-PASS LANE IS NOT REQUIRED
  
 SITE COMMENTS
 1) VERIFY AND SHOW ON THE SITE PLAN THAT PARKING STALLS
 AND DRIVEWAY DIMENSIONS ARE COMPLIANT WITH THE ONES
 SHOWN IN FIGURE XV-2 OF CITY CODE SECTION 94
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 02-17-2022 Cont ID  
Sent By kdefranc Date 02-17-2022 Time 14:43 Rev Time 0.00
Received By kdefranc Date 02-17-2022 Time 14:43 Sent To  
Notes
2022-02-17 14:46:282/17/22 - PASSED
  
 PROVIDE A SIGNED AND SEALED SURVEY. [SATISFIED]
  
 QUESTION: WHY HAVE THE DRIVE THRU START GOING SOUTH
 BOUND INSTEAD OF NORTH BOUND? [NO RESPONSE PROVIDED]
  
 WITH THE PROPOSED CHANGE IN THE FLOW OF TRAFFIC IN THE
 PARKING LOT, CONSIDER INSTALLING DIRECTIONAL SIGNS FOR
 SAFETY, ESPECIALLY WITH THE ONE-WAY TRAFFIC.
 [SATISFIED]
  
 INCLUDE SIDEWALK IN BASE PLAN. [SATISFIED]
  
 PROVIDE BICYCLE PARKING. (ONE PER TEN REQUIRED AUTO
 SPACES.) [PARTIALLY SATISFIED]
  
 THE PEDESTRIAN AREA/CONNECTION TO THE SOUTH MUST
 REMAIN. [SATISFIED]
  
 SHOW THE IMPROVEMENTS ON THE EAST SIDE OF DRIVEWAY ON
 THE HULETT PROPERTY. WE CAN PROVIDE YOU WITH THE RECENT
 SITE PLAN. [SATISFIED]
  
  
 ADDITIONAL COMMENT:
 THE PROPOSED BICYCLE PARKING FACILITY (?DOUBLE-SIDED
 GRID BIKE RACK? PROVIDED AS A RESPONSE TO THE BICYCLE
 PARKING RELATED QUESTION) IS NOT ALLOWED. PLEASE REFER
 TO THE BICYCLE PARKING GUIDELINE PDF DOCUMENT I
 PROVIDED VIA EMAIL FOR THE ALLOWED TYPES OF BICYCLE
 PARKING FACILITIES AND ASSOCIATED DIMENSIONAL DETAILS.
  
  
 CONDITIONS OF APPROVAL:
 1. THE PROPOSED BICYCLE PARKING FACILITY SHALL MEET THE
 BICYCLE PARKING DESIGN STANDARDS PER ZLDR SUBSECTION
 94-481(Q)(2)(C). FOR THE BUILDING PERMIT SUBMITTAL,
 PROVIDE THE ELEVATIONS AND DIMENSIONAL DETAILS OF THE
 PROPOSED BICYCLE PARKING FACILITY. THE PROPOSED BICYCLE
 PARKING FACILITY SHALL BE PROPERLY INSTALLED ACCORDING
 TO THE APPROVED PLANS AND BUILDING PERMIT PRIOR TO
 CERTIFICATE OF OCCUPANCY.
  
 2. FOR THE ENGINEERING PERMIT SUBMITTAL, PROVIDE THE
 VERTICAL DATUM AND CONVERSION EQUATION TO SHEET C600
 AND PROVIDE AND/OR MODIFY DETAIL FOR PARKING SPACE
 STRIPING IN COMPLIANCE WITH ZLDR SECTION 94-485.
  
 2. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED, AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT ? PLANNING DIVISION.
  
  
 KEVIE DEFRANC
 PLANNER - PLANNING DIVISION
 [email protected]
 561-822-1200
  

Review Stop Z ZONING
Rev No 1 Status F Date 07-07-2021 Cont ID  
Sent By awooten Date 07-07-2021 Time   Rev Time  
Received By awooten Date 07-07-2021 Time   Sent To  
Notes
2021-07-07 13:57:51PPRC 7/8/21
 ZONING REVIEW
 7800 OKEECHOBEE BOULEVARD
 ISPR 21-09 ? Z21060014
  
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
 B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND 2 SETS
 OF PHYSICAL PLANS, ALONG WITH ONE (1) REDUCED COPY (11
 IN X 17 IN).
 C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
 D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
 E. A RESUBMITTAL FEE OF 20% OF THE ORIGINAL APPLICATION
 FEE WILL BE ASSESSED AFTER THE FIRST
 RESUBMITTAL.
  
  
 PROVIDE A SIGNED AND SEALED SURVEY.
  
 QUESTION: WHY HAVE THE DRIVE THRU START GOING SOUTH
 BOUND INSTEAD OF NORTH BOUND?
  
 WITH THE PROPOSED CHANGE IN THE FLOW OF TRAFFIC IN THE
 PARKING LOT, CONSIDER INSTALLING DIRECTIONAL SIGNS FOR
 SAFETY, ESPECIALLY WITH THE ONE-WAY TRAFFIC.
  
 INCLUDE SIDEWALK IN BASE PLAN.
  
 PROVIDE BICYCLE PARKING. (ONE PER TEN REQUIRED AUTO
 SPACES.)
  
 THE PEDESTRIAN AREA/CONNECTION TO THE SOUTH MUST
 REMAIN.
  
 SHOW THE IMPROVEMENTS ON THE EAST SIDE OF DRIVEWAY ON
 THE HULETT PROPERTY. WE CAN PROVIDE YOU WITH THE RECENT
 SITE PLAN.
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  

  Print