Plan Review Details - Project Z21050015
Plan Review Stops For Project Z21050015
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 3 Status P Date 09-20-2021 Cont ID  
Sent By scwelter Date 09-20-2021 Time 15:28 Rev Time 0.00
Received By scwelter Date 09-20-2021 Time 15:32 Sent To  
Notes
2021-09-20 15:32:06PUBLIC ART - POSSIBLE SITES IDENTIFIED ON SITE PLAN -
 FINAL PLACEMENT TO BE DETERMINED.
  
 A COMPLETED ART ASSESSMENT APPLICATION AND EVIDENCE OF
 ESCROW ARE DUE AT TIME OF BUILDING PERMIT.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 2 Status F Date 06-10-2021 Cont ID  
Sent By scwelter Date 06-10-2021 Time 10:03 Rev Time 0.00
Received By scwelter Date 06-10-2021 Time 11:38 Sent To  
Notes
2021-06-10 10:04:39PUBLIC ART REQUIREMENT:
 IF TOTAL CONSTRUCTION COSTS OF THIS DEVELOPMENT ARE
 OVER $500,000 IT WILL BE SUBJECT TO THE PUBLIC ART
 REQUIREMENT AS PER CITY ORDINANCE.
 SECTION 78-129: ALL PRIVATE DEVELOPMENT PROJECTS,
 INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR
 IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL
 CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000 ARE SUBJECT TO THE PUBLIC ART REQUIREMENT.
 OPTION 1: INSTALL ARTWORK ON THE DEVELOPMENT SITE
 VALUED IN AN AMOUNT NOT LESS THAN ONE PERCENT OF THE
 TOTAL CONSTRUCTION COSTS; OR
 OPTION 2: CONTRIBUTE AN AMOUNT EQUAL TO 75 PERCENT OF
 ONE PERCENT OF THE TOTAL CONSTRUCTION COSTS FOR DEPOSIT
 TO THE PUBLIC ART ACCOUNT.
 A COMPLETED PUBLIC ART ASSESSMENT APPLICATION IS
 REQUIRED AT TIME OF BUILDING PERMIT SUBMITTAL.
  
 PLEASE CONTACT SYBILLE WELTER AT [email protected] OR
 561.822.1521 TO OBTAIN AN APPLICATION AND REVIEW THE
 REQUIREMENTS.
  

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 09-28-2021 Cont ID  
Sent By rbrown Date 09-28-2021 Time 18:57 Rev Time 0.00
Received By rbrown Date 09-28-2021 Time 18:57 Sent To  
Notes
2021-09-28 19:10:43DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS
 SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT
 REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH
 COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963,
 OR BY EMAIL: [email protected]
  
 3. FLOOD ZONE. PROVISO/CONDITION: AS STATED IN THEIR
 PPRC RESPONSE LETTER DATED 9/13/2021 THE DESIGN TEAM
 HAS ADVISED THAT IT WILL SEEK ISSUANCE OF A LETTER OF
 MAP REVISION BASED ON FILL LOMR-F BY FEMA IN ORDER TO
 ADDRESS THE COMMENT REGARDING THE PROPOSED FINISHED
 FLOOR LEVEL BEING EL 9.0 FT NAVD INSTEAD OF THE EL 10.0
 FT NAVD THAT WOULD BE REQUIRED TO MEET THE BASE FLOOD
 ELEVATION PLUS 2.0 FT FREEBOARD. CONDITION: EITHER THE
 LOMR-F MUST BE SUBMITTED TO THE BUILDING DIVISION PRIOR
 TO BUILDING PERMIT ISSUANCE, OR THE FINISHED FLOOR
 LEVEL BEING RAISED TO EL 10.0 FT NAVD.
  
 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 5. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES
 NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO
 MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL
 BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE
 EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED
 TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR
 OTHER APPROVED METHODS.
  
 6. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE
 REQUIRED. FOR INFORMATION ON THE REQUIRED TYPE, SIZE
 AND LOCATION, PLEASE CONTACT TIM LARGE, CHIEF PLUMBING
 INSPECTOR, DEVELOPMENT SERVICES DEPARTMENT, AT (561)
 805-6692, OR BY EMAIL: [email protected]
  
 7. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 8. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND
 CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF
 CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL
 NEIGHBORING PROPERTIES.
  
 9. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 10. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION
 OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING,
 CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT
 (561) 805 6659, OR BY EMAIL: [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 09-02-2021 Cont ID  
Sent By rbrown Date 09-02-2021 Time 20:24 Rev Time 0.00
Received By rbrown Date 09-02-2021 Time 20:24 Sent To  
Notes
2021-09-02 20:56:47DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS
 SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT
 REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH
 COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963,
 OR BY EMAIL: [email protected]
  
 3. FLOOD ZONE. SHEET C-500, PAVING, GRADING AND
 DRAINAGE PLAN SHOWS THE TOWNHOME FINISHED FLOOR
 ELEVATION (INCLUDING TOWNHOUSE -1 L1) TO BE AT EL 9.00
 NAVD. THE CITY HAS SUBMITTED AN APPEAL TO FEMA AGAINST
 THE METHODOLOGY USED BY FEMA TO ARRIVE AT THE FLOOD
 ELEVATIONS IN THE LATEST FLOOD INSURANCE RATE MAPS
 (FIRMS), BUT THE DISPOSITION OF THE APPEAL IS UNKNOWN
 AT THIS TIME. THEREFORE ACCORDING TO THE FLOOD
 INSURANCE RATE MAPS, THE PROPOSED BUILDING IS IN FLOOD
 ZONE AE WITH A BASE FLOOD ELEVATION OF 8 FT NAVD. THE
 FIRST FLOOR OF THE BUILDING AND ALL ASSOCIATED
 MECHANICAL EQUIPMENT (CHILLERS, GENERATORS ETC.) SHALL
 BE 24 INCHES (FREEBOARD) ABOVE THE BASE FLOOD
 ELEVATION, AND THAT IS EL 10.00 FT NAVD SO THE FINISHED
 FLOOR ELEVATION MUST BE RAISED TO THAT ELEVATION. ALSO
 THE ENTRANCE DOOR THRESHOLD TO TOWNHOUSE -1 L1 IS
 CURRENTLY SHOWN TO BE LOWER THAN THE ADJACENT SIDEWALK
 LEVEL WHICH IS APPROXIMATELY EL 11 FT NAVD. THERE IS A
 RELATIVELY SMALL AREA OF EXTERIOR GRADES AT
 APPROXIMATELY EL 8.8 FT NAVD (SWALE) BETWEEN THAT
 SIDEWALK AND THE DOOR THRESHOLD SO THE TOWNHOME COULD
 POTENTIALLY BE FLOODED DURING A STORM.
  
 4. LOCATION OF ACCESSIBLE PARKING SPACES. THE PARKING
 DATA TABLE ON SHEET A-100, BASEMENT LEVEL 00 FLOOR PLAN
 SHOWS THAT 41 PARKING SPACES ARE DEDICATED TO THE CAFE.
 THEREFORE 2 ACCESSIBLE PARKING SPACES MUST BE PROVIDED
 AND THEY MUST BE THE CLOSEST PARKING SPACES TO THE CAFE
 ENTRANCE. SHEET A-101, LEVEL 01 FLOOR PLAN, SHOWS 3
 ACCESSIBLE PARKING SPACES ON THAT LEVEL BUT ONLY 1 OF
 THEM IS NEAR THE ENTRANCE TO THE CAFE AND IT IS NOT THE
 CLOSEST PARKING SPACE TO THE ENTRANCE. PLEASE MAKE THE
 2 PARKING SPACES CLOSEST TO THE ENTRANCE OF THE CAFE,
 ACCESSIBLE PARKING SPACES . PER SECTION 208.3 OF
 FLORIDA ACCESSIBILITY CODE, ACCESSIBLE PARKING SPACES
 ARE TO BE LOCATED ON THE SHORTEST POSSIBLE ROUTE OF
 TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE ENTRANCE.
 THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL COMPLY
 WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE
  
 5. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 6. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES
 NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO
 MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL
 BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE
 EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED
 TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR
 OTHER APPROVED METHODS.
  
 7. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE
 REQUIRED. FOR INFORMATION ON THE REQUIRED TYPE, SIZE
 AND LOCATION, PLEASE CONTACT TIM LARGE, CHIEF PLUMBING
 INSPECTOR, DEVELOPMENT SERVICES DEPARTMENT, AT (561)
 805-6692, OR BY EMAIL: [email protected]
  
 8. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 9. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND
 CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF
 CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL
 NEIGHBORING PROPERTIES.
  
 10. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 11. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION
 OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING,
 CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT
 (561) 805 6659, OR BY EMAIL: [email protected]
  
 12. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT
 TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE
 ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP
 ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 07-16-2021 Cont ID  
Sent By rbrown Date 07-16-2021 Time 22:18 Rev Time 0.00
Received By rbrown Date 07-16-2021 Time 22:18 Sent To  
Notes
2021-07-16 22:20:46DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS
 SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT
 REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH
 COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963,
 OR BY EMAIL: [email protected]
  
 3. FLOOD ZONE. ACCORDING TO THE ADOPTED FLOOD INSURANCE
 RATE MAPS (FIRMS), THE PROPOSED BUILDING IS IN FLOOD
 ZONE AE WITH A BASE FLOOD ELEVATION OF 6 FT NAVD. THE
 FIRST FLOOR OF THE BUILDING AND ALL ASSOCIATED
 MECHANICAL EQUIPMENT (CHILLERS, GENERATORS ETC.) SHALL
 BE 24 INCHES (FREEBOARD) ABOVE THE BASE FLOOD
 ELEVATION.
  
 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 5. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES
 NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO
 MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL
 BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE
 EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED
 TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR
 OTHER APPROVED METHODS.
  
 6. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE
 REQUIRED. FOR INFORMATION ON THE REQUIRED TYPE, SIZE
 AND LOCATION, PLEASE CONTACT TIM LARGE, CHIEF PLUMBING
 INSPECTOR, DEVELOPMENT SERVICES DEPARTMENT, AT (561)
 805-6692, OR BY EMAIL: [email protected]
  
 7. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 8. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND
 CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF
 CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL
 NEIGHBORING PROPERTIES.
  
 9. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 10. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION
 OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING,
 CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT
 (561) 805 6659, OR BY EMAIL: [email protected]
  
 11. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT
 TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE
 ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP
 ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 06-09-2021 Cont ID  
Sent By rbrown Date 06-09-2021 Time 20:56 Rev Time 0.00
Received By rbrown Date 06-09-2021 Time 20:56 Sent To  
Notes
2021-06-09 21:04:58DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS
 SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT
 REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH
 COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963,
 OR BY EMAIL: [email protected]
  
 3. FLOOD ZONE. ACCORDING TO THE ADOPTED FLOOD INSURANCE
 RATE MAPS (FIRMS), THE PROPOSED BUILDING IS IN FLOOD
 ZONE AE WITH A BASE FLOOD ELEVATION OF 6 FT NAVD. THE
 FIRST FLOOR OF THE BUILDING AND ALL ASSOCIATED
 MECHANICAL EQUIPMENT (CHILLERS, GENERATORS ETC.) SHALL
 BE 24 INCHES (FREEBOARD) ABOVE THE BASE FLOOD
 ELEVATION.
  
 4. NUMBER OF ACCESSIBLE PARKING SPACES. ONLY 4
 ACCESSIBLE PARKING SPACES ARE SHOWN (2 ON SHEET A-101
 AND 2 ON SHEET A-102). WITH 311 PARKING SPACES BEING
 PROVIDED, 8 ACCESSIBLE PARKING SPACES ARE REQUIRED. THE
 MINIMUM NUMBER OF ACCESSIBLE PARKING SPACES PROVIDED
 SHALL BE IN ACCORDANCE WITH SECTION 208.2 OF FLORIDA
 ACCESSIBILITY CODE.
  
 5. VAN ACCESSIBLE PARKING SPACES. NONE OF THE
 ACCESSIBLE PARKING SPACES ARE MARKED AS VAN ACCESSIBLE.
 PER SECTION 208.2.4 OF FLORIDA ACCESSIBILITY CODE, ONE
 IN EVERY SIX REQUIRED ACCESSIBLE SPACES (AT LEAST ONE)
 IN A PARKING STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND
 DESIGNED IN ACCORDANCE WITH SECTION OF 502 OF FLORIDA
 ACCESSIBILITY CODE (VERTICAL CLEARANCE NOT LESS THAN 98
 INCHES AT SPACE AND VEHICULAR ACCESS ROUTE)
  
 6. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 7. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES
 NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO
 MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL
 BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE
 EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED
 TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR
 OTHER APPROVED METHODS.
  
 8. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE
 REQUIRED. FOR INFORMATION ON THE REQUIRED TYPE, SIZE
 AND LOCATION, PLEASE CONTACT TIM LARGE, CHIEF PLUMBING
 INSPECTOR, DEVELOPMENT SERVICES DEPARTMENT, AT (561)
 805-6692, OR BY EMAIL: [email protected]
  
 9. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 10. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND
 CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF
 CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL
 NEIGHBORING PROPERTIES.
  
 11. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 12. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION
 OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING,
 CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT
 (561) 805 6659, OR BY EMAIL: [email protected]
  
 13. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT
 TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE
 ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP
 ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 4 Status P Date 08-27-2021 Cont ID  
Sent By rrossano Date 08-27-2021 Time   Rev Time 0.00
Received By rrossano Date 08-27-2021 Time   Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 3 Status F Date 08-11-2021 Cont ID  
Sent By rrossano Date 08-11-2021 Time   Rev Time 0.00
Received By rrossano Date 08-11-2021 Time   Sent To  
Notes
2021-08-11 07:21:33THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
 -PLEASE RELOCATE IRRIGATION METER OUT OF HARDSCAPE AND
 INTO GRASS LANDSCAPE. METER BOX CANNOT BE IN SIDEWALK.
  
 -LABELS FOR 6 INCH METERS TALK ABOUT VAULTS, BUT
 ABOVE-GROUND METERS DON?T HAVE VAULTS. THEY WILL JUST
 HAVE CONCRETE SLAB WITH SMALLER BOXES.
  
 -WHICH METERS WILL FEED THE COOLING TOWER?
  
 -VERIFY NO CONFLICT WITH FIRELINES AND FPL UTILITIES OR
 FPL EASEMENT INSIDE PROPERTY.
  
 -GUY WIRE SHOWS IN MIDDLE OF SIDEWALK NEAR NORTH
 PROPERTY LINE ON LANDSCAPE PLAN. WILL IT REMAIN THERE
 BY END OF PROJECT?
  
 -ADD VISUAL SCALE ICONS TO LANDSCAPE PLAN SHEETS
 INCLUDING GROUND PLANTING PLAN LG-3.1.
  
 -GROUND PLANTING PLAN SHOWS MANY TREES IN CLOSE
 PROXIMITY TO UTILITY INFRASTRUCTURE. CONCERNED ABOUT
 ROOTS. THERE WERE ALSO A COUPLE TREES THAT LOOKED TO BE
 PROPOSED ON TOP OF WATER SERVICES AND WATER MAINS.
 PLEASE LOOK AGAIN AT THE LENGTH OF OLIVE, AND ALSO THE
 AREAS AROUND THE 6 INCH METERS AND BACKFLOW ASSEMBLIES,
 AND MAKE SURE NO CONFLICTS WITH TREES AND UTILITIES.
 MAY NEED TO INCREASE CLEARANCE DISTANCE AND ADD MORE
 ROOT BARRIERS. IF ADDING ROOT BARRIERS, MAKE SURE THEY
 ARE DRAWN AND LABELED CLEARLY ON GROUND PLANTING PLAN.
  
 -ADD RP TO LABEL FOR IRRIGATION BACKFLOW ASSEMBLY ON
 UTILITY PLAN.
  
 -LG3.2 SHOWS TREES PLANTED ON TOP OF STORMWATER
 UTILITY. ARE THE TREES EXISTING OR PROPOSED?
  
 -FOR THE PARKING SPACES ON THE NORTH SIDE OF DIANA PL,
 TREES ARE PLANTED CLOSE TO CURB. WILL VEHICLE
 PASSENGERS BE ABLE TO OPEN THEIR DOORS AND EXIT
 VEHICLES WITHOUT HITTING THE TREES?
  
 -IRRIGATION PLAN DOES NOT SHOW UPDATED LOCATION OF
 IRRIGATION METER AND BACKFLOW ASSEMBLY. PLEASE UPDATE
 IRRIGATION PLAN WITH THE UPDATED LOCATIONS SO THEY
 MATCH CIVIL PLANS.
  
 -LANDSCAPING PLAN SHEET D-2 HAS EMPTY BOXES. IS IT
 SUPPOSED TO BE EMPTY OR IS INFORMATION MISSING?
  
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status F Date 07-06-2021 Cont ID  
Sent By rrossano Date 07-06-2021 Time   Rev Time 0.00
Received By rrossano Date 07-06-2021 Time   Sent To  
Notes
2021-07-06 19:05:15FOLLOWUP COMMENTS:
  
 36. HOW WIDE IS SIDEWALK NEAR PROPOSED FIRE HYDRANT AND
 FDC? RESPONSE: SIDEWALK DIMENSIONS HAVE BEEN ADDED TO
 SHEET C5.00
 CANNOT FIND ON SHEET C5.00 PAVING PLAN OR ANY OTHER
 SHEET. PLEASE ADD DIMENSION TO UTILITY PLAN. SIDEWALK
 INQUIRING ABOUT IS THE ONE NORTH OF THE WATER METERS.
  
  
 COMMENTS AS FOLLOWS:
  
 -6 INCH AND 3 INCH METERS WITH THEIR ASSOCIATED
 BACKFLOW ASSEMBLIES NEED TO BE LOCATED OUTSIDE OF THE
 BUILDING. LOCATION OF 6 INCH METER SHOULD BE CLOSE
 ENOUGH TO CURB/STREET TO ACCESS WITH CRANE TRUCK
 (APPROX. 15 FOOT REACH)
  
 -6 INCH AND 3 INCH METERS NEED TO BE INSTALLED ABOVE
 GROUND VIA WATER SERVICE STANDARD DETAIL WS-3 REVISION
 SEP2019.
  
 -WATER SERVICE FOR 3 INCH METER WILL HAVE A SIMILAR
 FOOTPRINT AREA TO 6 INCH METER?S .
  
 -VERTICAL BACKFLOW ASSEMBLIES ARE NONSTANDARD DESIGN.
 APPLICANT ENGINEER WOULD NEED TO DESIGN AND VERIFY
 SETUP.
  
 -RP BACKFLOW ASSEMBLIES GENERALLY CANNOT BE INSTALLED
 ENTIRELY VERTICALLY. SOME SPECIALTY MAKE/MODELS MAY
 HAVE AN OFFSET VERTICAL SHAPE. PROPOSED BACKFLOW
 ASSEMBLY WOULD NEED TO BE USC APPROVED FOR THE
 MAKE/MODEL, SIZE, AND ORIENTATION.
  
 -LANDSCAPING MAY BE BLOCKING SIGHT AND ACCESSIBILITY TO
 BOTH FDCS.
  
 -VERIFY NORTHERN FIRE HYDRANT HAS ADEQUATE CLEARANCE TO
 TREES PER STANDARD DETAIL P-8.
  
 -SHOW AND LABEL THE RP BACKFLOW ASSEMBLY FOR IRRIGATION
 WATER SERVICE ON PLANS.
  
 -VERIFY THERE WILL ONLY BE ONE FIRELINE WATER SERVICE
 TO THE PROPERTY.
  
 -TREES ON LANDSCAPING PLAN STILL LOOK TO BE IN CONFLICT
 WITH THE WATER MAIN ON S. OLIVE AVE. INCREASE DISTANCE
 AND ADD ROOT BARRIERS.
  
 -GREASE TRAP CLEANOUT APPEARS TO CONFLICT WITH AT&T
 UTILITY.
  
 -IRRIGATION WATER SERVICE IS CLOSE TO A TREE.
 IRRIGATION METER BOX SHOULD ALSO BE LOCATED CLOSER TO
 WATER MAIN.
  
  
 RESPECTFULLY,
  
 MARK HURLEY
 FIELD CUSTOMER SERVICE SUPERVISOR
 CITY OF WEST PALM BEACH PUBLIC UTILITIES
 561-822-2262
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 06-08-2021 Cont ID  
Sent By vnoel Date 06-08-2021 Time 09:31 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2021-06-08 09:31:45Z21050015 - FLAGLER TOWER REZONING 1315 S FLAGLER
 INITIAL REVIEW
  
 1. THE CITY OF WEST PALM BEACH HAS A NUMBER OF
 REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY
 AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND
 WASTEWATER UTILITIES WITHIN THE CITY. TO VIEW
 DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AND OTHER
 ENGINEERING RELATED DOCUMENTS, GO HERE:
 HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING
 2. CODE OF ORDINANCES, CITY OF WEST PALM BEACH,
 FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED
 SEPT. 22, 2008. (SUPPLEMENT NO. 18) CHAPTER 90
 UTILITIES, ARTICLE I. SEC. 90-7.
 POLICY REGARDING EXTENSION OF WATER OR SEWER SERVICE
 FACILITIES OF THE CITY:
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
 3. AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, GO TO:
 HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING
 4. PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1040 FOR FURTHER
 ASSISTANCE.
 5. PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS
 OF ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES,
 INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND
 SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES,
 METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE
 SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 PLEASE SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL. ADDITIONALLY, PLAN VIEW SHALL SHOW ALL
 EXISTING AND PROPOSED UNDERGROUND UTILITY LAYOUT,
 INCLUDING FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED ON THE
 RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL
 UTILITY CROSSINGS.
 6. CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 ROW.
 7. PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE
 DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB
 DEVELOPMENT APPLICATION).
 8. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM
 AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE
 PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER.
 9. SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION
 (NAVD 88 AND NGVD 29).
 10. PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND
 STORMWATER ALONG ENTIRE PROJECT FRONTAGE.
 11. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
 12. PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR
 PROPOSED SANITARY LATERALS.
 13. PLEASE LABEL WATER LINES AS PRIVATE WHERE
 APPLICABLE.
 14. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED
 LOCATION OF WATER METER AND BACKFLOW PREVENTION.
 15. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING
 PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT
 HIM AT 561-494-2262 OR [email protected]
 16. PROVIDE DEDICATED UTILITY EASEMENTS TO ALLOW ACCESS
 FOR CITY PERSONNEL TO PROPOSED UTILITY WATER METERS.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT, (561) 494-1098 [email protected]
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
 COMMENTS AS FOLLOWS:
  
  
 -WILL THERE BE ANY WELLS ON SITE?
 -WHICH METER WILL THE COOLING TOWER BE FED FROM?
 -ON DIANA PL, SITE PLANS SHOWED GATES/DOORS OPENING
 INTO ADJACENT PROPERTY. VERIFY THAT IS ALLOWABLE.
 -ON SITE PLANS, SEEMED THAT SOME TOWNHOMES AND AMENITY
 ROOM DID NOT HAVE DOORS OPENING TO OUTSIDE AT GROUND
 LEVEL. IS THAT CORRECT?
 -LABEL SOUTHWEST RETAINING WALL ON SITE PLAN.
 -PAVEMENT RESTORATION PER STANDARDS WOULD BE NEEDED ON
 CURRIE CRESCENT, DIANA PL, AND FLAGLER DR. PLEASE ADD
 TO CIVIL PLANS.
 -DOES THE AT&T UTILITY ON SITE HAVE AN EASEMENT?
 -ON DEMO PLAN THERE IS A LABEL THAT SAYS REMOVE EXIST
 SEWER SERVICE BUT POINTS TO NOTHING.
 -CANNOT SEE AN EXISTING SEWER LATERAL FOR THE EXISTING
 SOUTHERN BUILDING ON CIVIL PLANS. PLEASE SHOW AND LABEL
 IF THERE IS ONE.
 -ON DEMO PLAN ON THE NORTH SIDE THERE IS NOTATION FOR
 GAS REMOVAL. PLEASE SHOW WHERE THE LINE ORIGINATES.
 -ON THE UTILITY PLAN, LABEL THE STORMWATER UTILITIES
 ADJACENT THE PROPERTY LINE AND IN THE ROW PRIVATE OR
 CITY.
 -THERE IS A CLEANOUT ON EAST SIDE THAT IS NOT LABELED
 ON UTILITY PLAN.
 -IS AN ADDITIONAL CLEANOUT NEEDED AT THE FLAGLER SEWER
 LATERAL TO MATCH THE OTHER LATERAL?
 -LABEL MANHOLES WITH ELEVATION INFORMATION.
 -POSSIBLE CONFLICT WITH MANHOLE AND CURB AT FLAGLER DR.
 -SHOW AND LABEL ALL EXISTING AND PROPOSED GATE VALVES
 ON WATER MAINS NEAR THE PROPERTY
 -FOR FORMAL ENGINEERING SUBMITTAL LABEL THE FIRELINE
 POINT OF SERVICE GATE VALVE.
 -SHOW AND LABEL ALL EXISTING AND PROPOSED FIRE
 HYDRANTS.
 -LABEL WHAT EACH WATER METER WILL BE USED FOR OR
 FEEDING.
 -DDCV CANNOT BE DOWNSTREAM OF 6 INCH METER. MUST BE ON
 SEPARATE TAP/LINE.
 -ADD SIZE OF DDCV TO LABEL.
 -LARGE METERS OVER 3 INCHES NEED TO BE INSTALLED
 ABOVE-GROUND.
 -SHOW ALL BACKFLOW ASSEMBLIES FOR DOMESTIC/GENERAL
 WATER USE AND LABEL WITH RP TYPE.
 -CONSIDER DUAL/PARALLEL BACKFLOW ASSEMBLIES FOR LARGE
 DOMESTIC METERS TO MINIMIZE WATER OUTAGES DURING
 BACKFLOW MAINTENANCE.
 -ONE GREASE TRAP HAS A CLEANOUTS ON BOTH SIDES, BUT THE
 OTHER DOES NOT. IS THAT ALRIGHT?
 -LOTS OF TREES ARE PLANTED OVER PRIVATE UTILITY PIPING
 NEAR DRIVEWAYS AND COULD CREATE MAINTENANCE PROBLEM IN
 FUTURE.
 -APPEAR TO BE TREE CONFLICTS AT WEST SIDE OF PROPERTY ?
 ESPECIALLY WITH OAK TREE THAT IS PROPOSED TO BE
 RELOCATED CLOSE TO SANITARY SEWER PIPE.
 -UTILITY EASEMENT NEEDED FOR PROPOSED FIRE HYDRANT.
 -PLEASE LABEL 6 INCH WATER SERVICE LINE AND TAP IN THE
 DRIVEWAY.
 -IRRIGATION PLAN SHOWS 1.5 INCH METER. IS IT PRIVATE
 SUB METER OR CITY? ALSO SHOW IT ON UTILITY PLAN.
 -ON SHEET C500 THE RETAINING WALL LINE IS NOT POINTED
 CORRECTLY IN THE DETAIL.
 -ADD ELEVATION DATUM STATEMENT TO UTILITY PLAN.
 -SHOW SEPARATE ENLARGED DETAIL AREA FOR WATER METERS
 AND BACKFLOW ASSEMBLIES.
 -APPEARS TO BE TREE CONFLICTS WITH UTILITIES NEAR WATER
 METERS AND BACKFLOW ASSEMBLIES.
 -FPL EASEMENT WOULD NEED TO BE VACATED TO ALLOW
 BUILDING OF STRUCTURES.
 -HOW WIDE IS SIDEWALK NEAR PROPOSED FIRE HYDRANT AND
 FDC?
 -WATER MAIN TAP DOES NOT APPEAR LARGE ENOUGH FOR THE
 METERS.
 -ADD WATER SERVICE STANDARD DETAIL FOR LARGE
 ABOVE-GROUND DOMESTIC METER.
 -THERE ARE UTILITY MAINTENANCE CONFLICTS WITH RETAINING
 WALLS AND STORMWATER AND WATER UTILITIES.
 -WOULD BACKHOE BE ABLE TO ACCESS METER AREA FOR
 MAINTENANCE WITHOUT DAMAGING MOTOR POOL AREA?
 -WILL THE NE SURVEY BENCHMARK REMAIN AFTER
 CONSTRUCTION?
 -SOME SUBMITTAL DOCUMENTS SAY 109 UNITS OR 108 DWELLING
 UNITS, BUT ANOTHER LISTING SAID 100 UNITS, PLUS 10
 GUESTHOUSES AND 9 TOWNHOMES. PLEASE CLARIFY AND MAKE
 SURE WATER DEMAND CALCULATIONS AGREE.
 -SHOW EXISTING METERED WATER SERVICE FOR THE NORTH
 BUILDING AND LABEL WITH WHAT IS HAPPENING TO IT.
  
  
 RESPECTFULLY,
  
 MARK HURLEY
 FIELD CUSTOMER SERVICE SUPERVISOR
 CITY OF WEST PALM BEACH PUBLIC UTILITIES
 561-822-2262
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 07-26-2021 Cont ID  
Sent By pleduc Date 07-26-2021 Time   Rev Time 0.00
Received By pleduc Date 07-26-2021 Time 09:08 Sent To  
Notes
2021-07-26 09:10:04FIRE HAS NO OBJECTIONS TO THE PROPOSED AND APPROVES.
  
 FIRE'S APPROVAL OF THIS SUBMITTED PROJECT DOES NOT
 CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 FIRE SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT THE
 APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 06-09-2021 Cont ID  
Sent By pleduc Date 06-09-2021 Time   Rev Time 0.00
Received By pleduc Date 06-09-2021 Time 14:26 Sent To  
Notes
2021-06-09 14:36:27THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT; HOWEVER, THE FOLLOWING COMMENTS ARE
 PROVIDED AND MAY NEED FURTHER CLARIFICATIONS WHERE
 APPLICABLE.
  
 UNFORTUNATELY I COULD NOT VIEW MOST OF THE SUBMITTALS
 AS I WAS EXPERIENCING IT PROBLEMS.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. ALL PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A,
 PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE,
 INCLUDING MORE SPECIFICALLY, CHAPTER 42 STORAGE
 OCCUPANCIES (PARKING STRUCTURES)
  
 7. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA
 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THIS
 STRUCTURE. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE
 BUILDING REACHES THREE LEVELS OR THIRTY FEET WHILE
 BEING CONSTRUCTED. SEPARATE SHOP DRAWINGS, ARE REQUIRED
 TO BE SUBMITTED, REVIEWED AND APPROVED BY THE FIRE
 PREVENTION BUREAU PRIOR TO ANY INSTALLATION.
 IT IS RECOMMENDED FOR HIGH RISES HAVE TWO SEPARATE FDC
 LOCATIONS REMOTELY LOCATED.
  
 7A. PER NFPA 14
 6.4.5.4* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED
 NOT MORE THAN 100 FT (30.5 M) FROM THE NEAREST FIRE
 HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY.
  
 7B. I WAS ABLE TO VIEW THE PROPOSED HYDRANT AND FDC ON
 THE WEST SIDE. DUE THE SIZE OF THE PROPOSED A 2ND FDC
 IS REQUEST ALONGFLAGLER FOR FIRE GROUND OPERATIONS. I
 WAS UNABLE TO LOCATE A 2ND HYDRANT FOR THAT FDC.
  
 7C. PER NFPA 1
 18.3 WATER SUPPLIES.
 18.3.1* AN APPROVED WATER SUPPLY CAPABLE OF SUPPLYING
 THE REQUIRED FIRE FLOW FOR FIRE PROTECTION SHALL BE
 PROVIDED TO ALL PREMISES UPON WHICH FACILITIES,
 BUILDINGS, OR PORTIONS OF BUILDINGS ARE HEREAFTER
 CONSTRUCTED OR MOVED INTO THE JURISDICTION. THE
 APPROVED WATER SUPPLY SHALL BE IN ACCORDANCE WITH
 SECTION 18.4.
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
 FOR THE PROPOSED FIRE PUMP(S) , WHAT IS(ARE) THE
 PRIMARY AND SECONDARY POWER SOURCES?
  
 7D. THE LOCATION OF THE DDCV FIRE LINE LOCATION SHALL
 MEET THE REQUIREMENTS OF NFPA 24 AND SHALL BE
 COORDINATED WITH THE OFFICE OF FIRE MARSHAL, THE CITY'S
 ENGINEERS OFFICE, THE LANDSCAPE PLANNER, AND THE CITY'S
 PLANNING AND ZONING OFFICE.
  
 8. A CLASS ?A? NFPA 72 COMPLIANT MONITORED FIRE ALARM
 SYSTEM IS REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP
 DRAWINGS, ARE REQUIRED TO BE SUBMITTED, REVIEWED AND
 APPROVED BY THE FIRE PREVENTION BUREAU PRIOR TO ANY
 INSTALLATION.
  
 9. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7
 KEYWAY SYSTEM.
 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTER?S
 EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA
 B44, SAFETY CODE FOR ELEVATORS.
 ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET
 MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN
 AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE
 IN THE HORIZONTAL POSITION.
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 11. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE
 BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND
 FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET
 OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER
 ARRIVING EMERGENCY VEHICLES.
  
 12. COMMAND ROOM - THE COMMAND ROOM SHOULD BE
 ACCESSIBLE FROM THE EXTERIOR.
  
 THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1,
 CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN
 THE FOLLOWING FEATURES:
 11.9.1 THE LOCATION, DESIGN, CONTENT, AND FIRE
 DEPARTMENT ACCESS OF THE EMERGENCY COMMAND CENTER SHALL
 BE APPROVED BY THE FIRE DEPARTMENT.
  
 11.9.2 THE EMERGENCY COMMAND CENTER SHALL BE SEPARATED
 FROM THE REMAINDER OF THE BUILDING BY A FIRE BARRIER
 HAVING A FIRE RESISTANCE RATING OF NOT LESS THAN 1
 HOUR.
  
 11.9.3 THE EMERGENCY COMMAND CENTER ROOM SHALL BE A
 MINIMUM OF 96 FT2 (8.9 M2) WITH A MINIMUM DIMENSION OF
 8 FT (2.4 M).
  
 A. PER FL BLDG CODE;(MORE STRICT) IT SHALL BE A MINIMUM
 OF 200 FT SQUARED WITH A MINIMUM DIMENSION OF 10 FT.
 B. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM.
 C. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM
 D. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION
 OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS
 E. A WORK TABLE.
 F. IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN
 FOR THE BUILDING.
 G. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 CONTROL UNIT.
 H. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF
 THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL
 I. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION
 SYSTEMS.
 J. CONTROLS FOR UNLOCKING STAIRWAY DOORS SIMULTANEOUSLY
 K. SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY
 PANELS
 L. EMERGENCY AND STANDBY POWER STATUS INDICATORS
 M. FIRE PUMP STATUS INDICATORS
 N. GENERATOR SUPERVISION DEVICES AND MANUAL START AND
 TRANSFER FEATURES.
 O. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE
 P. CONTROLS REQUIRED FOR SMOKE CONTROL
 Q. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1.
 R. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR
 SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS
 PROVIDED
 11.8.6* EMERGENCY COMMAND CENTER.
 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED
 IN A
 LOCATION APPROVED BY THE FIRE DEPARTMENT.
 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE
 FOLLOWING:
 (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS
 (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION
 SERVICE
 PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER SECTION
 OF THIS
 CODE
 (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION
 PANELS
 (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS
 (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS
 (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE
 PROVIDED
 IN ACCORDANCE WITH ASME A17.1/CSA B44
 (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS
 (8) EMERGENCY GENERATOR STATUS INDICATORS
 (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING
 SYSTEM
 (10) FIRE PUMP STATUS INDICATORS
 (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE
 PUBLIC TELEPHONE SYSTEM
 (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY
 11.8.8
  
 13. TWO-WAY RADIO ENHANCEMENT
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
 NFPA 72, 24.5.2* TWO-WAY RADIO COMMUNICATIONS
 ENHANCEMENT SYSTEMS.
 24.5.2.2 RADIO COVERAGE. RADIO COVERAGE SHALL BE
 PROVIDED THROUGHOUT THE BUILDING AS A PERCENTAGE OF
 FLOOR AREA AS SPECIFIED IN 24.5.2.2.1 THROUGH
 24.5.2.2.3.
 24.5.2.2.1 CRITICAL AREAS. CRITICAL AREAS, SUCH AS THE
 EMERGENCY COMMAND CENTER(S), THE FIRE PUMP ROOM(S),
 EXIT STAIRS, EXIT PASSAGEWAYS, ELEVATOR LOBBIES,
 STANDPIPE CABINETS, SPRINKLER SECTIONAL VALVE
 LOCATIONS, AND OTHER AREAS DEEMED CRITICAL BY THE
 AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED WITH
 99 PERCENT FLOOR AREA RADIO COVERAGE.
 24.5.2.2.2 GENERAL BUILDING AREAS. GENERAL BUILDING
 AREAS SHALL BE PROVIDED WITH 90 PERCENT FLOOR AREA
 RADIO COVERAGE.
 24.5.2.3 SIGNAL STRENGTH.
 24.5.2.3.1 INBOUND. A MINIMUM INBOUND SIGNAL STRENGTH
 OF -95 DBM, OR OTHER SIGNAL STRENGTH AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED
 THROUGHOUT THE COVERAGE AREA.
 24.5.2.3.2 OUTBOUND. A MINIMUM OUTBOUND SIGNAL STRENGTH
 OF -95 DBM AT THE DONOR SITE, OR OTHER SIGNAL STRENGTH
 AS REQUIRED BY THE AUTHORITY HAVING JURISDICTION, SHALL
 BE PROVIDED FROM THE COVERAGE AREA.
  
 THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL
 STRENGTH FOR THE RADIO SYSTEM USED BY WEST PALM BEACH
 FIRE RESCUE. TESTING SHALL BE BY AN ACCEPTABLE NATIONAL
 STANDARD DOCUMENTING PERCENTAGES NOTED ABOVE AND BY
 ACTUAL RADIO TESTING BY FIRE PERSONNEL. IF THE MINIMUM
 CANNOT BE MAINTAINED, A BI-DIRECTIONAL AMPLIFIED SYSTEM
 SHALL BE INSTALLED WITH A MINIMUM 2-HOUR RUN TIME
 BATTERY BACK-UP.
  
 PLEASE CONTACT MARK FILLA, PALM BEACH COUNTY PUBLIC
 SAFETY RADIO SYSTEMS MANAGER, [email protected],
 561-233-0837; AS OUR RADIOS OPERATE ON THEIR SYSTEM FOR
 DETAILED RADIO FREQUENCY AND INSTALLATION INSTRUCTIONS.
  
  
 14. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING.
 ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS,
 PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS.
  
 15. THE SMOKE CONTROL SYSTEM SHALL COMPLY WITH NFPA
 101, CHAPTER 9, BUILDING SERVICE AND FIRE PROTECTION
 EQUIPMENT, INCLUDING:
 THE SMOKE CONTROL SYSTEMS SHALL BE INSTALLED,
 INSPECTED, TESTED, AND MAINTAINED IN ACCORDANCE WITH
 NFPA 92, STANDARD FOR SMOKE CONTROL SYSTEMS; NFPA 204,
 STANDARD FOR SMOKE AND HEAT VENTING; OR NATIONALLY
 RECOGNIZED STANDARDS, ENGINEERING GUIDES, OR
 RECOMMENDED PRACTICES, AS APPROVED BY THE AUTHORITY
 HAVING JURISDICTION.
 THE ENGINEER OF RECORD SHALL CLEARLY IDENTIFY THE
 INTENT OF THE SYSTEM, THE DESIGN METHOD USED, THE
 APPROPRIATENESS OF THE METHOD USED, AND THE REQUIRED
 MEANS OF INSPECTING, TESTING, AND MAINTAINING THE
 SYSTEM.
 ACCEPTANCE TESTING SHALL BE PERFORMED BY A SPECIAL
 INSPECTOR IN ACCORDANCE WITH SECTION 9.9.
  
 16. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 17. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 8 Status P Date 11-08-2021 Cont ID  
Sent By rcaranci Date 11-08-2021 Time 12:05 Rev Time 0.00
Received By rcaranci Date 11-08-2021 Time 12:04 Sent To  
Notes
2021-11-08 12:05:15FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: FLAGLER TOWER Z21050015
 NOVEMBER 8, 2021
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 REVIEW: FLAGLER TOWERS 7/20/21
 1. PREVIOUSLY SATISFIED
 2. PREVIOUSLY SATISFIED
 3. PREVIOUSLY SATISFIED
 4. SATISFIED. DUE TO THE CONSTRUCTION IMPACT ON THE
 EXISTING MATURE TREES ON CITY PROPERTY ALONG DIANA PL.
 REMOVE FICUS TREES AND REPLACE WITH 1 TO 1 CATEGORY
 SHADE TREE. (SEE #5)
 7/27/21 RC: PLAN IS ALREADY IN PLACE BETWEEN PLANNING
 AND PARKS AND REC. TO REPLACE FICUS WITH GREEN BUTTON
 WOOD IN AGREEMENT WITH THE NORTON PARK PLACE CONDO.
 APPLICANTS MAINTENANCE RESPONSIBILITY FOR TREES ON
 NORTH SIDE OF DIANA PLACE.
 7/20/2021
 6. 7/27/21 RC. MAKE THE FOLLOWING CORRECTIONS TO THE
 TREE DISPOSITION LIST:
 ? SATISFIED. SHOW THE DISPOSITION OF TREES #1479 ?
 #1530.
 ? SATISFIED. IDENTIFY TREE #1504
 ? SATISFIED. PROVIDE MITIGATION SQUARE FOOTAGE DUE FOR
 TREES AND PALMS LISTED TO BE REMOVED. ON EXISTING TREES
 ON SITE LIST AND EXISTING TREES ON ADJACENT SITE LIST.
 7. SATISFIED. SEE COMMENT #6 TREE #1479 ON TREE LIST
 WILL NEED TO BE LISTED AS REMOVE TO REFLECT DEPICTION
 ON THE MAP. PAGE D-1
 8. SATISFIED. APPLICANT NEEDS PROVIDE LANDSCAPE PLANS
 FOR POOL TERRACE PAGE LA 3-1. THE LANDSCAPING ON THE
 AMENITIES LEVEL WILL BE APPROVED WITH PROJECT AND NEEDS
 TO BE SUBMITTED.
 9. SATISFIED. LIVE OAK TREES ON FLAGLER APPEAR TO BE IN
 CONFLICT WITH MAN HOLE COVERS AND STORM WATER LINE.
 ADJUST LINE OR TREE LOCATIONS TO BE RESOLVE.
 10. SATISFIED. LIVE OAK ON SOUTH SIDE BUFFER APPEARS TO
 BE TOO CLOSE TO BUILDING AND ENTRY CANOPY AND WILL
 OUTGROW ITS SPACE CREATING A CONFLICT WITH THE BUILDING
 AND SHADE CANOPY.
 THE TREES DO NOT APPEAR ON THE LANDSCAPE PLAN SHEET
 LG-3.1. IF THIS IS IN ERROR, PROVIDE A MANAGEMENT PLAN
 FOR THE MAINTENANCE OF THE TREES.
 11. SATISFIED. IN EAST SIDE COURTYARD THERE IS A STRAY
 UNMARKED DIAGONAL LINE GOING ACROSS. IDENTIFY LINE OR
 REMOVE IF IT?S NOT INTENTIONAL.
 SENIOR LANDSCAPE PLANNER WILL RETURN ON 7/22 PLAN IS
 SUBJECT TO HIS REVIEW
 7/27/21 RC.
 13. SATISFIED. ALL LANDSCAPE PLANS NEED TO BE ON AT
 LEAST 1-20 SCALE PLAN AS THE CURRENT SCALE IS NOT
 READABLE
 14. SATISFIED. SHOW OPEN SPACE SQUARE FOOTAGE FOR THE
 NON-BUILDING AREA OF THE LOT. ADJUST OPEN SPACE DIAGRAM
 ON SHEET LR-2. LANDSCAPING OVER BUILDING STRUCTURE IS
 NOT COUNTED FOR OPEN SPACE. PROVIDE A DIAGRAM SHOWING
 LANDSCAPED AREAS.
 15. SATISFIED. USING THE OPEN SPACE SQUARE FOOTAGE
 CALCULATE THE NUMBER OF REQUIRED SHADE TREES, FLOWERING
 TREES AND SHRUBS PER SECTION 94-442 (C) (2) B. ADD THE
 TOTAL TREES REQUIRED FOR OPEN SPACE AND FOR MULTIFAMILY
 REQUIREMENT AND SHOW THE TOTAL REQUIRED TREES.
 16. SATISFIED. SHOW THE PROVIDED LINEAR FEET OF
 LANDSCAPING FOR THE BUILDING PERIMETER.
 ABOVE GROUND POTS AND PLANTERS MAY NOT BE COUNTED AS
 PERIMETER LANDSCAPE. THERE ARE AREAS ADJACENT TO THE
 BUILDING ON THE OLIVE SIDE AND SHOWN AS PLANTINGS THAT
 DO NOT APPEAR AS OPENINGS IN THE PAVED AREAS. CLEARLY
 IDENTIFY THESE AREAS AND RECALCULATE THE PERIMETER
 LANDSCAPE.
 17. SATISFIED. ADD A NATIVE COLUMN TO THE PLANT
 SCHEDULE SO STAFF CAN VERIFY REQUIREMENTS.
 18. SATISFIED. MAGNOLIA MAY BE COUNTED AS NATIVE.
 19. SATISFIED. FLORIDA FRIENDLY REQUIREMENTS. PROVIDE
 AN AREA PLAN SHOWING THE SOD AREAS AS PART OF THE TOTAL
 LANDSCAPE AREA AND PROVIDE THE TOTAL PERCENTAGE. ITEM
 6B DOES NOT APPLY.
 ITEM 6B STILL DOES NOT APPLY.
 20. SATISFIED. PROVIDE ADDITIONAL INFORMATION ON SEA
 PLUM TREE IN ORDER TO IDENTIFY IF IT IS A CULTIVAR OF
 SEA GRAPE.
 21. SATISFIED. TOTAL NUMBER OF TREES PROVIDED NEEDS TO
 BE SHOWN FROM THE PLANT LIST. CURRENT COUNT IS 92 TREES
 PLUS 11 CABBAGE PALMS AT 3:1 FOR A TOTAL OF 95. SHOW
 RELOCATED TREES ON THE PLANT LIST. SHOW OFFSITE TREES
 ON THE PLANT LIST. IF REQUIRED TREES ARE NOT TO BE
 PROVIDED ON SITE A WAVER MUST BE REQUESTED.
 22. SATISFIED. THE TREES PROVIDED ON THE AMENITY AREA
 ON FLAGLER NEED TO BE SPREAD OUT TO PROVIDE SHADE FOR
 PEDESTRIANS.
 THE INTENT FOR THE OVERALL PEDESTRIAN PLAN FOR THE CITY
 IS TO PROVIDE TREE CANOPY SHADE OVER PUBLIC AREAS AND
 PEDESTRIAN SIDEWALKS. THE LARGE GAP ADJACENT TO THE
 PLAZA DOES NOT MEET THIS INTENT. STAFF DOES NOT
 RECOGNIZE HAVING THE TREES IN FRONT OF THE PLAZA AS A
 SAFETY ISSUE, AS THE TREES WOULD MEET CPTED (CRIME
 PREVENTION THROUGH ENVIRONMENTAL DESIGN)
 RECOMMENDATIONS FOR THE TREE BRANCHING TO BE ABOVE 7
 FEET. PEDESTRIAN ENJOYMENT OF THE PUBLIC WALKWAY ALSO
 OUTWEIGHS THE NEEDS OF THE PROPERTY OWNER TO EXPOSE THE
 ARCHITECTURE OF THE BUILDING.
 23. CONDITIONALLY SATISFIED. TRANSPLANTED OAK TREE
 #1538 APPEARS TO BE PROBLEMATIC IN THE SPECIFIED
 LOCATION THAT IT WILL CONFLICT WITH THE BUILDING
 CONSTRUCTION. TRANSPLANTED TREES MAY BE RELOCATED OFF
 SITE. THIS APPEARS THIS COULD ALSO BE AN ISSUE WITH THE
 OTHER RELOCATED TREES AND PALMS.
 THE APPLICANT HAS A NOTE PLACED ON THE PLANS FOR
 TEMPORARY STORAGE OF THE RELOCATED TREES. PROVIDE A
 MORE DETAILED PLAN ON HOW THIS WILL BE IMPLEMENTED. THE
 RELOCATED LIVE OAK IS SHOWN WITH PAVING PROPOSED OVER
 THE ROOT SYSTEM AT ITS NEW LOCATION THAT WILL NOT BE
 PRACTICAL OR HEALTHY FOR THE TREE. THE RENDERINGS SHOW
 GRASS AREA. A SUSPENDED PAVING SYSTEM OR SOIL CELLS
 MUST BE PROVIDED IF THE TREE IS TO BE SUSTAINABLE.
 PROVIDE THE RELOCATION AND MANAGEMENT PLAN FOR THE
 TREES BEFORE, DURING AND AFTER RELOCATION AND INCLUDE
 IT ON THE TREE DISPOSITION PLAN.
 THE APPLICANT HAS PROVIDED INFORMATION IN THE COMMENT
 RESPONSES, BUT THAT INFORMATION NEEDS TO BE IN A
 MANAGEMENT PLAN SUBMITTED FOR REVIEW.
 ADDITIONAL COMMENTS 8/18/21:
 24. SATISFIED. TREE COUNT ON THE PLANT LIST OF 29 LIVE
 OAK TREES DOES NOT MATCH THE PLAN SHOWING 30 TREES.
 25. SATISFIED. THE SIDEWALK PROPOSED ALONG OLIVE AVE.
 APPEARS TO BE TOO CLOSE TO EXISTING TREES AND PALMS.
 PROVIDE MORE DETAIL ON HOW THIS WILL BE ADDRESSED.
 SITE PLAN DOES NOT MATCH ADJUSTED SIDEWALK ON THE
 LANDSCAPE PLAN.
 26. SATISFIED. PROVIDE SCREENING HEDGES FOR ALL GROUND
 MOUNTED EQUIPMENT INCLUDING WATER AND FIRE BACKFLOWS ON
 THE CURRIE CRESCENT SIDE OF THE BUILDING.
 27. SATISFIED. VINES ARE SHOWN ON THE RENDERINGS ON THE
 WALL OF THE EAST SIDE OF THE BUILDING, BUT NO PLANTS
 ARE SHOWN ON THE LANDSCAPE PLAN. CORRECT TO SHOW THE
 PLANTINGS.
 28. SATISFIED. PROVIDE THE TOTAL MITIGATION DUE FOR THE
 ON SITE TREES AND PALMS TO BE REMOVED. ADONIDIA PALMS
 ARE CATEGORY 4 AND REQUIRE 50 SQ FT CANOPY MITIGATION
 PER TRUNK, SPANISH CHERRY IS LISTED UNDER CATEGORY 1
 AND REQUIRES 300 SQ FT CANOPY MITIGATION. PROVIDE THE
 LIST OF TREES ADDED TO THE SITE AND ASSIGN THE CANOPY
 CREDITS BASED ON THE CATEGORY AND PROVIDE THE TOTAL.
 THERE ARE CORRECTIONS REQUIRED FOR THE ONSITE AND
 OFFSITE MITIGATION CALCULATIONS.
 CALCULATIONS FOR THE MITIGATION PROVIDED ON SITE BASED
 ON THE PLANT LIST SHOULD BE REMOVED FROM SHEET L-3.4
 AND PLACED IN A CHART ON SHEET D-2. SABAL PALMS ARE
 CATEGORY 3 AND ARE 100 SQ FT CREDIT. TOTAL EXCESS OF
 TREE CANOPY NEEDS TO BE SHOWN.
 29. THE PLANTING PLANS FOR THE OFF SITE TREES NEED TO
 BE REVISED TO SHOW THE FOLLOWING:
 ? SATISFIED. THE ROYAL PALMS BETWEEN THE GREEN
 BUTTONWOOD TREES ARE NOT APPROPRIATE TO DUPLICATE THE
 CURRENT LOOK OF THE TREE CANOPY AND THEY WOULD PRESENT
 A SAFETY AND MAINTENANCE ISSUE OVER THE PAVEMENT AND
 PARKING SPACES. REMOVE THE ROW OF PALMS ADJACENT TO THE
 CURB.
 THERE IS A GAP IN THE TREE CANOPY ON THE SOUTH SIDE OF
 ACTION PL. ADJACENT TO THE ANGLED PARKING SPACES. GREEN
 BUTTONWOOD TREES MUST BE PLACED ALONG THIS AREA
 REPLACING THE ROYAL PALMS.
  
 ? SATISFIED. THERE IS NOT ENOUGH ROOM PROVIDED FOR THE
 ROOT ZONE OF THE TREES. THE SIDEWALK NEEDS TO BE PUSHED
 FARTHER AWAY FROM THE CURB (10 TO 12 FEET) ALLOWING
 ENOUGH ROOT SPACE FOR THE TREES AND THE NARROWER
 LANDSCAPE AREA ON THE BACK OF SIDEWALK. ROYAL PALMS
 COULD BE PLACED IN THIS STRIP, BUT THEY WOULD HAVE TO
 BE FAR ENOUGH AWAY FROM THE SIDEWALK TO AVOID FRONDS
 DROPPING ON THE SIDEWALK.
 ? SATISFIED. PROVIDE THE TOTAL TREE CANOPY MITIGATION
 DUE FOR THE REMOVED TREES AND PROVIDE THE MITIGATION
 SQUARE FOOTAGE PROVIDED FOR THE NEW TREES AND PALMS
 PROPOSED. IF THERE IS MITIGATION DUE, STAFF WILL
 DISCUSS OPTIONS TO ADDRESS IT.
 THERE ARE CORRECTIONS REQUIRED FOR THE ONSITE AND
 OFFSITE MITIGATION CALCULATIONS.
  
 SHOW THE TOTAL MITIGATION DUE AFTER CREDITS ON SHEET
 D-2.
  
 ? SATISFIED. INCREASING THE NUMBER OF GREEN BUTTONWOOD
 TREES AND ROYAL PALMS WOULD INCREASE THE PUBLIC
 BENEFITS AND THE AESTHETICS.
 ? SATISFIED. EXPLAIN WHY THERE IS A GAP ON THE CORNER
 OF OLIVE AND DIANA WITH NO TREE CANOPY PROVIDED. THIS
 WAS A LOCATION SUGGESTED BY STAFF FOR THE RELOCATED
 LIVE OAK TREE.
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
 2. THE APPLICANT, SUCCESSORS SHALL BE RESPONSIBLE FOR
 THE PERMITTING AND INSTALLATION OF THE STREET TREES,
 LANDSCAPING AND IRRIGATION IN THE RIGHT OF WAY AND ON
 THE CITY PARCEL ADJACENT TO THE SITE APPROVED WITH THIS
 PETITION.
 3. SEE CONDITION #5. THE APPLICANT, SUCCESSORS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE STREET TREES,
 LANDSCAPING AND IRRIGATION IN THE RIGHT OF WAY AND ON
 THE CITY PARCEL ADJACENT TO THE SITE APPROVED WITH THIS
 PETITION. THIS WILL BE THROUGH A SEPARATE MAINTENANCE
 AGREEMENT WITH THE CITY THAT MUST BE COMPLETED PRIOR TO
 THE FINAL CO FOR THE BUILDING.
 4. SATISFIED. PRIOR TO SCHEDULING FOR CITY COMMISSION,
 THE APPLICANT SHALL REVISE THE LANDSCAPE PLANS TO SHOW
 THE ROYAL PALMS AS 1:1 CREDIT TOWARD TREES PER SECTION
 94-442 (D) AND CORRECT THE TREE COUNTS FOR OFF SITE
 PALMS ON SHEET L-3.4 TO 44.
 5. PRIOR TO SCHEDULING FOR CITY COMMISSION, THE
 APPLICANT SHALL MAKE THE FOLLOWING REVISIONS TO THE
 TREE RELOCATION MANAGEMENT PLAN:
 A) LIVE OAK TREE #1536:
  IF OPTION #1 TO KEEP THE TREE IN ITS CURRENT LOCATION
 IS TO BE FINAL,
 1) THE TREE RELOCATION MANAGEMENT PLAN WILL BE REVISED
 TO REFLECT THIS CHOICE AND ADJUSTED TO ITEMIZE ALL
 ACTIONS TO BE COMPLETED AT EACH STAGE OF CONSTRUCTION.
 2) ALL PLANS MUST BE AMENDED TO SHOW THE PERMANENT
 LOCATION.
 3) THE TREE WILL BE MONITORED DAILY AND A WEEKLY REPORT
 SUBMITTED TO THE CITY ON THE CONDITION UNTIL THE FINAL
 LANDSCAPE INSPECTION.
 IF OPTION #2 TO RELOCATE THE TREE TO A LOCATION NEAR
 THE SITE IS TO BE FINAL,
 1) THE TREE RELOCATION MANAGEMENT PLAN WILL BE REVISED
 TO REFLECT THIS CHOICE AND ADJUSTED TO ITEMIZE ALL
 ACTIONS TO BE COMPLETED AT EACH STAGE OF CONSTRUCTION.
 2) ALL PLANS MUST BE AMENDED TO SHOW THE PERMANENT
 LOCATION.
 3) THE TREE SHALL BE MONITORED DAILY AND A WEEKLY
 REPORT SUBMITTED TO THE CITY ON THE CONDITION UNTIL THE
 FINAL LANDSCAPE INSPECTION AND MAINTAINED THEREAFTER IN
 ACCORDANCE WITH THE REQUIREMENTS OF SECTION 94-448 (E)3
 FOR ONE YEAR FROM THE DATE OF PLANTING IN THE FINAL
 LOCATION.
 SINCE OPTION #3 IS NOT SUPPORTED BY THE ARBORIST OR THE
 CITY AS PREFERABLE, THIS SHALL NOT BE AN OPTION AND
 SHALL BE REMOVED FROM THE REPORT.
 B) MAHOGANY TREES #1502, 1503, 1507, 1520, 1539, AND
 1540:
  
 1) IF THE TREES ARE TO BE MOVED TO A TEMPORARY HOLDING
 AREA, THE LOCATION OF THE TEMPORARY HOLDING AREA SHALL
 BE ESTABLISHED AND AGREEMENTS FOR STORAGE OF THE TREES
 ACCEPTABLE TO THE CITY SHALL BE ESTABLISHED WITH THE
 OWNER OF THE PROPERTY.
 2) THE TREE RELOCATION MANAGEMENT PLAN WILL BE REVISED
 TO REFLECT THIS CHOICE AND ADJUSTED TO ITEMIZE ALL
 ACTIONS TO BE COMPLETED AT EACH STAGE OF CONSTRUCTION.
  
 3) THE TREES SHALL BE MONITORED DAILY AND A WEEKLY
 REPORT SUBMITTED TO THE CITY ON THEIR CONDITION UNTIL
 THE FINAL LANDSCAPE INSPECTION AND MONITORED THEREAFTER
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION 94-448
 (E)3 FOR ONE YEAR FROM THE DATE OF PLANTING IN THE
 FINAL LOCATION.
  
 C) SABAL PALMS (34):
  
 1) IF THE PALMS ARE TO BE MOVED TO A TEMPORARY HOLDING
 AREA, THE LOCATION OF THE TEMPORARY HOLDING AREA SHALL
 BE ESTABLISHED AND AGREEMENTS FOR STORAGE OF THE TREES
 ACCEPTABLE TO THE CITY SHALL BE ESTABLISHED WITH THE
 OWNER OF THE PROPERTY.
 2) IF THE PALMS ARE TO BE TRANSPORTED TO A COMMERCIAL
 NURSERY OFF SITE, THE CONTRACTOR AND NURSERY SHALL BE
 IDENTIFIED.
 3) THE TREE RELOCATION MANAGEMENT PLAN WILL BE REVISED
 TO REFLECT THIS CHOICE AND ADJUSTED TO ITEMIZE ALL
 ACTIONS TO BE COMPLETED AT EACH STAGE OF CONSTRUCTION.
 4) THE PALMS SHALL BE MONITORED DAILY AND A WEEKLY
 REPORT SUBMITTED TO THE CITY ON THEIR CONDITION UNTIL
 THE FINAL LANDSCAPE INSPECTION AND MONITORED THEREAFTER
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION 94-448
 (E)3 FOR ONE YEAR FROM THE DATE OF PLANTING IN THE
 FINAL LOCATION.
  
 1. SATISFIED. A LETTER SIGNED BY THE PROPERTY OWNER OF
 1531 S OLIVE AVENUE INDICATING THAT THEY WILL ACCEPT
 THE LIVE OAK TREE FOR RELOCATION TO THEIR PROPERTY AND
 WILL ACCEPT OWNERSHIP AND MAINTAIN IT FOLLOWING THE
 REQUIREMENTS OF THE CITY.
 2. SATISFIED. 2.5 IRRIGATION C. WILL BE AMENDED TO
 INDICATE THAT RELOCATED TREES SHALL HAVE THE ENTIRE
 ROOTBALL IRRIGATED ADEQUATELY UNTIL ESTABLISHMENT.
 3. SATISFIED. A SITE VISIT REVEALED THAT TREES #1539
 AND #1540 ARE CALLOPHYLLUM TREES, NOT MAHOGANY.
 CORRECTIONS MUST BE MADE TO ALL PLANS.
  

Review Stop L LANDSCAPING
Rev No 7 Status P Date 09-29-2021 Cont ID  
Sent By rcaranci Date 09-29-2021 Time 14:19 Rev Time 0.00
Received By rcaranci Date 09-29-2021 Time 14:19 Sent To  
Notes
2021-09-29 14:21:02FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: FLAGLER TOWER Z21050015
 SEPTEMBER 29, 2021
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 REVIEW: FLAGLER TOWERS 7/20/21
 1. PREVIOUSLY SATISFIED
 2. PREVIOUSLY SATISFIED
 3. PREVIOUSLY SATISFIED
 4. SATISFIED. DUE TO THE CONSTRUCTION IMPACT ON THE
 EXISTING MATURE TREES ON CITY PROPERTY ALONG DIANA PL.
 REMOVE FICUS TREES AND REPLACE WITH 1 TO 1 CATEGORY
 SHADE TREE. (SEE #5)
 7/27/21 RC: PLAN IS ALREADY IN PLACE BETWEEN PLANNING
 AND PARKS AND REC. TO REPLACE FICUS WITH GREEN BUTTON
 WOOD IN AGREEMENT WITH THE NORTON PARK PLACE CONDO.
 APPLICANTS MAINTENANCE RESPONSIBILITY FOR TREES ON
 NORTH SIDE OF DIANA PLACE.
 7/20/2021
 6. 7/27/21 RC. MAKE THE FOLLOWING CORRECTIONS TO THE
 TREE DISPOSITION LIST:
 ? SATISFIED. SHOW THE DISPOSITION OF TREES #1479 ?
 #1530.
 ? SATISFIED. IDENTIFY TREE #1504
 ? SATISFIED. PROVIDE MITIGATION SQUARE FOOTAGE DUE FOR
 TREES AND PALMS LISTED TO BE REMOVED. ON EXISTING TREES
 ON SITE LIST AND EXISTING TREES ON ADJACENT SITE LIST.
 7. SATISFIED. SEE COMMENT #6 TREE #1479 ON TREE LIST
 WILL NEED TO BE LISTED AS REMOVE TO REFLECT DEPICTION
 ON THE MAP. PAGE D-1
 8. SATISFIED. APPLICANT NEEDS PROVIDE LANDSCAPE PLANS
 FOR POOL TERRACE PAGE LA 3-1. THE LANDSCAPING ON THE
 AMENITIES LEVEL WILL BE APPROVED WITH PROJECT AND NEEDS
 TO BE SUBMITTED.
 9. SATISFIED. LIVE OAK TREES ON FLAGLER APPEAR TO BE IN
 CONFLICT WITH MAN HOLE COVERS AND STORM WATER LINE.
 ADJUST LINE OR TREE LOCATIONS TO BE RESOLVE.
 10. SATISFIED. LIVE OAK ON SOUTH SIDE BUFFER APPEARS TO
 BE TOO CLOSE TO BUILDING AND ENTRY CANOPY AND WILL
 OUTGROW ITS SPACE CREATING A CONFLICT WITH THE BUILDING
 AND SHADE CANOPY.
 THE TREES DO NOT APPEAR ON THE LANDSCAPE PLAN SHEET
 LG-3.1. IF THIS IS IN ERROR, PROVIDE A MANAGEMENT PLAN
 FOR THE MAINTENANCE OF THE TREES.
 11. SATISFIED. IN EAST SIDE COURTYARD THERE IS A STRAY
 UNMARKED DIAGONAL LINE GOING ACROSS. IDENTIFY LINE OR
 REMOVE IF IT?S NOT INTENTIONAL.
 SENIOR LANDSCAPE PLANNER WILL RETURN ON 7/22 PLAN IS
 SUBJECT TO HIS REVIEW
 7/27/21 RC.
 13. SATISFIED. ALL LANDSCAPE PLANS NEED TO BE ON AT
 LEAST 1-20 SCALE PLAN AS THE CURRENT SCALE IS NOT
 READABLE
 14. SATISFIED. SHOW OPEN SPACE SQUARE FOOTAGE FOR THE
 NON-BUILDING AREA OF THE LOT. ADJUST OPEN SPACE DIAGRAM
 ON SHEET LR-2. LANDSCAPING OVER BUILDING STRUCTURE IS
 NOT COUNTED FOR OPEN SPACE. PROVIDE A DIAGRAM SHOWING
 LANDSCAPED AREAS.
 15. SATISFIED. USING THE OPEN SPACE SQUARE FOOTAGE
 CALCULATE THE NUMBER OF REQUIRED SHADE TREES, FLOWERING
 TREES AND SHRUBS PER SECTION 94-442 (C) (2) B. ADD THE
 TOTAL TREES REQUIRED FOR OPEN SPACE AND FOR MULTIFAMILY
 REQUIREMENT AND SHOW THE TOTAL REQUIRED TREES.
 16. SATISFIED. SHOW THE PROVIDED LINEAR FEET OF
 LANDSCAPING FOR THE BUILDING PERIMETER.
 ABOVE GROUND POTS AND PLANTERS MAY NOT BE COUNTED AS
 PERIMETER LANDSCAPE. THERE ARE AREAS ADJACENT TO THE
 BUILDING ON THE OLIVE SIDE AND SHOWN AS PLANTINGS THAT
 DO NOT APPEAR AS OPENINGS IN THE PAVED AREAS. CLEARLY
 IDENTIFY THESE AREAS AND RECALCULATE THE PERIMETER
 LANDSCAPE.
 17. SATISFIED. ADD A NATIVE COLUMN TO THE PLANT
 SCHEDULE SO STAFF CAN VERIFY REQUIREMENTS.
 18. SATISFIED. MAGNOLIA MAY BE COUNTED AS NATIVE.
 19. SATISFIED. FLORIDA FRIENDLY REQUIREMENTS. PROVIDE
 AN AREA PLAN SHOWING THE SOD AREAS AS PART OF THE TOTAL
 LANDSCAPE AREA AND PROVIDE THE TOTAL PERCENTAGE. ITEM
 6B DOES NOT APPLY.
 ITEM 6B STILL DOES NOT APPLY.
 20. SATISFIED. PROVIDE ADDITIONAL INFORMATION ON SEA
 PLUM TREE IN ORDER TO IDENTIFY IF IT IS A CULTIVAR OF
 SEA GRAPE.
 21. SATISFIED. TOTAL NUMBER OF TREES PROVIDED NEEDS TO
 BE SHOWN FROM THE PLANT LIST. CURRENT COUNT IS 92 TREES
 PLUS 11 CABBAGE PALMS AT 3:1 FOR A TOTAL OF 95. SHOW
 RELOCATED TREES ON THE PLANT LIST. SHOW OFFSITE TREES
 ON THE PLANT LIST. IF REQUIRED TREES ARE NOT TO BE
 PROVIDED ON SITE A WAVER MUST BE REQUESTED.
 22. SATISFIED. THE TREES PROVIDED ON THE AMENITY AREA
 ON FLAGLER NEED TO BE SPREAD OUT TO PROVIDE SHADE FOR
 PEDESTRIANS.
 THE INTENT FOR THE OVERALL PEDESTRIAN PLAN FOR THE CITY
 IS TO PROVIDE TREE CANOPY SHADE OVER PUBLIC AREAS AND
 PEDESTRIAN SIDEWALKS. THE LARGE GAP ADJACENT TO THE
 PLAZA DOES NOT MEET THIS INTENT. STAFF DOES NOT
 RECOGNIZE HAVING THE TREES IN FRONT OF THE PLAZA AS A
 SAFETY ISSUE, AS THE TREES WOULD MEET CPTED (CRIME
 PREVENTION THROUGH ENVIRONMENTAL DESIGN)
 RECOMMENDATIONS FOR THE TREE BRANCHING TO BE ABOVE 7
 FEET. PEDESTRIAN ENJOYMENT OF THE PUBLIC WALKWAY ALSO
 OUTWEIGHS THE NEEDS OF THE PROPERTY OWNER TO EXPOSE THE
 ARCHITECTURE OF THE BUILDING.
 23. CONDITIONALLY SATISFIED. TRANSPLANTED OAK TREE
 #1538 APPEARS TO BE PROBLEMATIC IN THE SPECIFIED
 LOCATION THAT IT WILL CONFLICT WITH THE BUILDING
 CONSTRUCTION. TRANSPLANTED TREES MAY BE RELOCATED OFF
 SITE. THIS APPEARS THIS COULD ALSO BE AN ISSUE WITH THE
 OTHER RELOCATED TREES AND PALMS.
 THE APPLICANT HAS A NOTE PLACED ON THE PLANS FOR
 TEMPORARY STORAGE OF THE RELOCATED TREES. PROVIDE A
 MORE DETAILED PLAN ON HOW THIS WILL BE IMPLEMENTED. THE
 RELOCATED LIVE OAK IS SHOWN WITH PAVING PROPOSED OVER
 THE ROOT SYSTEM AT ITS NEW LOCATION THAT WILL NOT BE
 PRACTICAL OR HEALTHY FOR THE TREE. THE RENDERINGS SHOW
 GRASS AREA. A SUSPENDED PAVING SYSTEM OR SOIL CELLS
 MUST BE PROVIDED IF THE TREE IS TO BE SUSTAINABLE.
 PROVIDE THE RELOCATION AND MANAGEMENT PLAN FOR THE
 TREES BEFORE, DURING AND AFTER RELOCATION AND INCLUDE
 IT ON THE TREE DISPOSITION PLAN.
 THE APPLICANT HAS PROVIDED INFORMATION IN THE COMMENT
 RESPONSES, BUT THAT INFORMATION NEEDS TO BE IN A
 MANAGEMENT PLAN SUBMITTED FOR REVIEW.
 ADDITIONAL COMMENTS 8/18/21:
 24. SATISFIED. TREE COUNT ON THE PLANT LIST OF 29 LIVE
 OAK TREES DOES NOT MATCH THE PLAN SHOWING 30 TREES.
 25. SATISFIED. THE SIDEWALK PROPOSED ALONG OLIVE AVE.
 APPEARS TO BE TOO CLOSE TO EXISTING TREES AND PALMS.
 PROVIDE MORE DETAIL ON HOW THIS WILL BE ADDRESSED.
 SITE PLAN DOES NOT MATCH ADJUSTED SIDEWALK ON THE
 LANDSCAPE PLAN.
 26. SATISFIED. PROVIDE SCREENING HEDGES FOR ALL GROUND
 MOUNTED EQUIPMENT INCLUDING WATER AND FIRE BACKFLOWS ON
 THE CURRIE CRESCENT SIDE OF THE BUILDING.
 27. SATISFIED. VINES ARE SHOWN ON THE RENDERINGS ON THE
 WALL OF THE EAST SIDE OF THE BUILDING, BUT NO PLANTS
 ARE SHOWN ON THE LANDSCAPE PLAN. CORRECT TO SHOW THE
 PLANTINGS.
 28. SATISFIED. PROVIDE THE TOTAL MITIGATION DUE FOR THE
 ON SITE TREES AND PALMS TO BE REMOVED. ADONIDIA PALMS
 ARE CATEGORY 4 AND REQUIRE 50 SQ FT CANOPY MITIGATION
 PER TRUNK, SPANISH CHERRY IS LISTED UNDER CATEGORY 1
 AND REQUIRES 300 SQ FT CANOPY MITIGATION. PROVIDE THE
 LIST OF TREES ADDED TO THE SITE AND ASSIGN THE CANOPY
 CREDITS BASED ON THE CATEGORY AND PROVIDE THE TOTAL.
 THERE ARE CORRECTIONS REQUIRED FOR THE ONSITE AND
 OFFSITE MITIGATION CALCULATIONS.
 CALCULATIONS FOR THE MITIGATION PROVIDED ON SITE BASED
 ON THE PLANT LIST SHOULD BE REMOVED FROM SHEET L-3.4
 AND PLACED IN A CHART ON SHEET D-2. SABAL PALMS ARE
 CATEGORY 3 AND ARE 100 SQ FT CREDIT. TOTAL EXCESS OF
 TREE CANOPY NEEDS TO BE SHOWN.
 29. THE PLANTING PLANS FOR THE OFF SITE TREES NEED TO
 BE REVISED TO SHOW THE FOLLOWING:
 ? SATISFIED. THE ROYAL PALMS BETWEEN THE GREEN
 BUTTONWOOD TREES ARE NOT APPROPRIATE TO DUPLICATE THE
 CURRENT LOOK OF THE TREE CANOPY AND THEY WOULD PRESENT
 A SAFETY AND MAINTENANCE ISSUE OVER THE PAVEMENT AND
 PARKING SPACES. REMOVE THE ROW OF PALMS ADJACENT TO THE
 CURB.
 THERE IS A GAP IN THE TREE CANOPY ON THE SOUTH SIDE OF
 ACTION PL. ADJACENT TO THE ANGLED PARKING SPACES. GREEN
 BUTTONWOOD TREES MUST BE PLACED ALONG THIS AREA
 REPLACING THE ROYAL PALMS.
  
 ? SATISFIED. THERE IS NOT ENOUGH ROOM PROVIDED FOR THE
 ROOT ZONE OF THE TREES. THE SIDEWALK NEEDS TO BE PUSHED
 FARTHER AWAY FROM THE CURB (10 TO 12 FEET) ALLOWING
 ENOUGH ROOT SPACE FOR THE TREES AND THE NARROWER
 LANDSCAPE AREA ON THE BACK OF SIDEWALK. ROYAL PALMS
 COULD BE PLACED IN THIS STRIP, BUT THEY WOULD HAVE TO
 BE FAR ENOUGH AWAY FROM THE SIDEWALK TO AVOID FRONDS
 DROPPING ON THE SIDEWALK.
 ? SATISFIED. PROVIDE THE TOTAL TREE CANOPY MITIGATION
 DUE FOR THE REMOVED TREES AND PROVIDE THE MITIGATION
 SQUARE FOOTAGE PROVIDED FOR THE NEW TREES AND PALMS
 PROPOSED. IF THERE IS MITIGATION DUE, STAFF WILL
 DISCUSS OPTIONS TO ADDRESS IT.
 THERE ARE CORRECTIONS REQUIRED FOR THE ONSITE AND
 OFFSITE MITIGATION CALCULATIONS.
  
 SHOW THE TOTAL MITIGATION DUE AFTER CREDITS ON SHEET
 D-2.
  
 ? SATISFIED. INCREASING THE NUMBER OF GREEN BUTTONWOOD
 TREES AND ROYAL PALMS WOULD INCREASE THE PUBLIC
 BENEFITS AND THE AESTHETICS.
 ? SATISFIED. EXPLAIN WHY THERE IS A GAP ON THE CORNER
 OF OLIVE AND DIANA WITH NO TREE CANOPY PROVIDED. THIS
 WAS A LOCATION SUGGESTED BY STAFF FOR THE RELOCATED
 LIVE OAK TREE.
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
 2. THE APPLICANT, SUCCESSORS SHALL BE RESPONSIBLE FOR
 THE PERMITTING AND INSTALLATION OF THE STREET TREES,
 LANDSCAPING AND IRRIGATION IN THE RIGHT OF WAY AND ON
 THE CITY PARCEL ADJACENT TO THE SITE APPROVED WITH THIS
 PETITION.
 3. THE APPLICANT, SUCCESSORS SHALL BE RESPONSIBLE FOR
 THE MAINTENANCE OF THE STREET TREES, LANDSCAPING AND
 IRRIGATION IN THE RIGHT OF WAY AND ON THE CITY PARCEL
 ADJACENT TO THE SITE APPROVED WITH THIS PETITION. THIS
 WILL BE THROUGH A SEPARATE MAINTENANCE AGREEMENT WITH
 THE CITY THAT MUST BE COMPLETED PRIOR TO THE FINAL CO
 FOR THE BUILDING.
 4. PRIOR TO SCHEDULING FOR CITY COMMISSION, THE
 APPLICANT SHALL REVISE THE LANDSCAPE PLANS TO SHOW THE
 ROYAL PALMS AS 1:1 CREDIT TOWARD TREES PER SECTION
 94-442 (D) AND CORRECT THE TREE COUNTS FOR OFF SITE
 PALMS ON SHEET L-3.4 TO 44.
 5. PRIOR TO SCHEDULING FOR CITY COMMISSION, THE
 APPLICANT SHALL MAKE THE FOLLOWING REVISIONS TO THE
 TREE RELOCATION MANAGEMENT PLAN:
 A) LIVE OAK TREE #1536:
  IF OPTION #1 TO KEEP THE TREE IN ITS CURRENT LOCATION
 IS TO BE FINAL,
 1) THE TREE RELOCATION MANAGEMENT PLAN WILL BE REVISED
 TO REFLECT THIS CHOICE AND ADJUSTED TO ITEMIZE ALL
 ACTIONS TO BE COMPLETED AT EACH STAGE OF CONSTRUCTION.
 2) ALL PLANS MUST BE AMENDED TO SHOW THE PERMANENT
 LOCATION.
 3) THE TREE WILL BE MONITORED DAILY AND A WEEKLY REPORT
 SUBMITTED TO THE CITY ON THE CONDITION UNTIL THE FINAL
 LANDSCAPE INSPECTION.
 IF OPTION #2 TO RELOCATE THE TREE TO A LOCATION NEAR
 THE SITE IS TO BE FINAL,
 1) THE TREE RELOCATION MANAGEMENT PLAN WILL BE REVISED
 TO REFLECT THIS CHOICE AND ADJUSTED TO ITEMIZE ALL
 ACTIONS TO BE COMPLETED AT EACH STAGE OF CONSTRUCTION.
 2) ALL PLANS MUST BE AMENDED TO SHOW THE PERMANENT
 LOCATION.
 3) THE TREE SHALL BE MONITORED DAILY AND A WEEKLY
 REPORT SUBMITTED TO THE CITY ON THE CONDITION UNTIL THE
 FINAL LANDSCAPE INSPECTION AND MAINTAINED THEREAFTER IN
 ACCORDANCE WITH THE REQUIREMENTS OF SECTION 94-448 (E)3
 FOR ONE YEAR FROM THE DATE OF PLANTING IN THE FINAL
 LOCATION.
 SINCE OPTION #3 IS NOT SUPPORTED BY THE ARBORIST OR THE
 CITY AS PREFERABLE, THIS SHALL NOT BE AN OPTION AND
 SHALL BE REMOVED FROM THE REPORT.
 B) MAHOGANY TREES #1502, 1503, 1507, 1520, 1539, AND
 1540:
  
 1) IF THE TREES ARE TO BE MOVED TO A TEMPORARY HOLDING
 AREA, THE LOCATION OF THE TEMPORARY HOLDING AREA SHALL
 BE ESTABLISHED AND AGREEMENTS FOR STORAGE OF THE TREES
 ACCEPTABLE TO THE CITY SHALL BE ESTABLISHED WITH THE
 OWNER OF THE PROPERTY.
 2) THE TREE RELOCATION MANAGEMENT PLAN WILL BE REVISED
 TO REFLECT THIS CHOICE AND ADJUSTED TO ITEMIZE ALL
 ACTIONS TO BE COMPLETED AT EACH STAGE OF CONSTRUCTION.
  
 3) THE TREES SHALL BE MONITORED DAILY AND A WEEKLY
 REPORT SUBMITTED TO THE CITY ON THEIR CONDITION UNTIL
 THE FINAL LANDSCAPE INSPECTION AND MONITORED THEREAFTER
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION 94-448
 (E)3 FOR ONE YEAR FROM THE DATE OF PLANTING IN THE
 FINAL LOCATION.
  
 C) SABAL PALMS (34):
  
 1) IF THE PALMS ARE TO BE MOVED TO A TEMPORARY HOLDING
 AREA, THE LOCATION OF THE TEMPORARY HOLDING AREA SHALL
 BE ESTABLISHED AND AGREEMENTS FOR STORAGE OF THE TREES
 ACCEPTABLE TO THE CITY SHALL BE ESTABLISHED WITH THE
 OWNER OF THE PROPERTY.
 2) IF THE PALMS ARE TO BE TRANSPORTED TO A COMMERCIAL
 NURSERY OFF SITE, THE CONTRACTOR AND NURSERY SHALL BE
 IDENTIFIED.
 3) THE TREE RELOCATION MANAGEMENT PLAN WILL BE REVISED
 TO REFLECT THIS CHOICE AND ADJUSTED TO ITEMIZE ALL
 ACTIONS TO BE COMPLETED AT EACH STAGE OF CONSTRUCTION.
 4) THE PALMS SHALL BE MONITORED DAILY AND A WEEKLY
 REPORT SUBMITTED TO THE CITY ON THEIR CONDITION UNTIL
 THE FINAL LANDSCAPE INSPECTION AND MONITORED THEREAFTER
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION 94-448
 (E)3 FOR ONE YEAR FROM THE DATE OF PLANTING IN THE
 FINAL LOCATION.
  

Review Stop L LANDSCAPING
Rev No 6 Status F Date 09-24-2021 Cont ID  
Sent By rcaranci Date 09-24-2021 Time 16:32 Rev Time 0.00
Received By rcaranci Date 09-24-2021 Time 16:32 Sent To  
Notes
2021-09-24 16:33:13FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: FLAGLER TOWER Z21050015
 SEPTEMBER 22, 2021
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 REVIEW: FLAGLER TOWERS 7/20/21
 1. PREVIOUSLY SATISFIED
 2. PREVIOUSLY SATISFIED
 3. PREVIOUSLY SATISFIED
 4. SATISFIED. DUE TO THE CONSTRUCTION IMPACT ON THE
 EXISTING MATURE TREES ON CITY PROPERTY ALONG DIANA PL.
 REMOVE FICUS TREES AND REPLACE WITH 1 TO 1 CATEGORY
 SHADE TREE. (SEE #5)
 7/27/21 RC: PLAN IS ALREADY IN PLACE BETWEEN PLANNING
 AND PARKS AND REC. TO REPLACE FICUS WITH GREEN BUTTON
 WOOD IN AGREEMENT WITH THE NORTON PARK PLACE CONDO.
 APPLICANTS MAINTENANCE RESPONSIBILITY FOR TREES ON
 NORTH SIDE OF DIANA PLACE.
 7/20/2021
 6. 7/27/21 RC. MAKE THE FOLLOWING CORRECTIONS TO THE
 TREE DISPOSITION LIST:
 ? SATISFIED. SHOW THE DISPOSITION OF TREES #1479 ?
 #1530.
 ? SATISFIED. IDENTIFY TREE #1504
 ? SATISFIED. PROVIDE MITIGATION SQUARE FOOTAGE DUE FOR
 TREES AND PALMS LISTED TO BE REMOVED. ON EXISTING TREES
 ON SITE LIST AND EXISTING TREES ON ADJACENT SITE LIST.
 7. SATISFIED. SEE COMMENT #6 TREE #1479 ON TREE LIST
 WILL NEED TO BE LISTED AS REMOVE TO REFLECT DEPICTION
 ON THE MAP. PAGE D-1
 8. SATISFIED. APPLICANT NEEDS PROVIDE LANDSCAPE PLANS
 FOR POOL TERRACE PAGE LA 3-1. THE LANDSCAPING ON THE
 AMENITIES LEVEL WILL BE APPROVED WITH PROJECT AND NEEDS
 TO BE SUBMITTED.
 9. SATISFIED. LIVE OAK TREES ON FLAGLER APPEAR TO BE IN
 CONFLICT WITH MAN HOLE COVERS AND STORM WATER LINE.
 ADJUST LINE OR TREE LOCATIONS TO BE RESOLVE.
 10. SATISFIED. LIVE OAK ON SOUTH SIDE BUFFER APPEARS TO
 BE TOO CLOSE TO BUILDING AND ENTRY CANOPY AND WILL
 OUTGROW ITS SPACE CREATING A CONFLICT WITH THE BUILDING
 AND SHADE CANOPY.
 THE TREES DO NOT APPEAR ON THE LANDSCAPE PLAN SHEET
 LG-3.1. IF THIS IS IN ERROR, PROVIDE A MANAGEMENT PLAN
 FOR THE MAINTENANCE OF THE TREES.
 11. SATISFIED. IN EAST SIDE COURTYARD THERE IS A STRAY
 UNMARKED DIAGONAL LINE GOING ACROSS. IDENTIFY LINE OR
 REMOVE IF IT?S NOT INTENTIONAL.
 SENIOR LANDSCAPE PLANNER WILL RETURN ON 7/22 PLAN IS
 SUBJECT TO HIS REVIEW
 7/27/21 RC.
 13. SATISFIED. ALL LANDSCAPE PLANS NEED TO BE ON AT
 LEAST 1-20 SCALE PLAN AS THE CURRENT SCALE IS NOT
 READABLE
 14. SATISFIED. SHOW OPEN SPACE SQUARE FOOTAGE FOR THE
 NON-BUILDING AREA OF THE LOT. ADJUST OPEN SPACE DIAGRAM
 ON SHEET LR-2. LANDSCAPING OVER BUILDING STRUCTURE IS
 NOT COUNTED FOR OPEN SPACE. PROVIDE A DIAGRAM SHOWING
 LANDSCAPED AREAS.
 15. SATISFIED. USING THE OPEN SPACE SQUARE FOOTAGE
 CALCULATE THE NUMBER OF REQUIRED SHADE TREES, FLOWERING
 TREES AND SHRUBS PER SECTION 94-442 (C) (2) B. ADD THE
 TOTAL TREES REQUIRED FOR OPEN SPACE AND FOR MULTIFAMILY
 REQUIREMENT AND SHOW THE TOTAL REQUIRED TREES.
 16. SATISFIED. SHOW THE PROVIDED LINEAR FEET OF
 LANDSCAPING FOR THE BUILDING PERIMETER.
 ABOVE GROUND POTS AND PLANTERS MAY NOT BE COUNTED AS
 PERIMETER LANDSCAPE. THERE ARE AREAS ADJACENT TO THE
 BUILDING ON THE OLIVE SIDE AND SHOWN AS PLANTINGS THAT
 DO NOT APPEAR AS OPENINGS IN THE PAVED AREAS. CLEARLY
 IDENTIFY THESE AREAS AND RECALCULATE THE PERIMETER
 LANDSCAPE.
 17. SATISFIED. ADD A NATIVE COLUMN TO THE PLANT
 SCHEDULE SO STAFF CAN VERIFY REQUIREMENTS.
 18. SATISFIED. MAGNOLIA MAY BE COUNTED AS NATIVE.
 19. SATISFIED. FLORIDA FRIENDLY REQUIREMENTS. PROVIDE
 AN AREA PLAN SHOWING THE SOD AREAS AS PART OF THE TOTAL
 LANDSCAPE AREA AND PROVIDE THE TOTAL PERCENTAGE. ITEM
 6B DOES NOT APPLY.
 ITEM 6B STILL DOES NOT APPLY.
 20. SATISFIED. PROVIDE ADDITIONAL INFORMATION ON SEA
 PLUM TREE IN ORDER TO IDENTIFY IF IT IS A CULTIVAR OF
 SEA GRAPE.
 21. SATISFIED. TOTAL NUMBER OF TREES PROVIDED NEEDS TO
 BE SHOWN FROM THE PLANT LIST. CURRENT COUNT IS 92 TREES
 PLUS 11 CABBAGE PALMS AT 3:1 FOR A TOTAL OF 95. SHOW
 RELOCATED TREES ON THE PLANT LIST. SHOW OFFSITE TREES
 ON THE PLANT LIST. IF REQUIRED TREES ARE NOT TO BE
 PROVIDED ON SITE A WAVER MUST BE REQUESTED.
 22. SATISFIED. THE TREES PROVIDED ON THE AMENITY AREA
 ON FLAGLER NEED TO BE SPREAD OUT TO PROVIDE SHADE FOR
 PEDESTRIANS.
 THE INTENT FOR THE OVERALL PEDESTRIAN PLAN FOR THE CITY
 IS TO PROVIDE TREE CANOPY SHADE OVER PUBLIC AREAS AND
 PEDESTRIAN SIDEWALKS. THE LARGE GAP ADJACENT TO THE
 PLAZA DOES NOT MEET THIS INTENT. STAFF DOES NOT
 RECOGNIZE HAVING THE TREES IN FRONT OF THE PLAZA AS A
 SAFETY ISSUE, AS THE TREES WOULD MEET CPTED (CRIME
 PREVENTION THROUGH ENVIRONMENTAL DESIGN)
 RECOMMENDATIONS FOR THE TREE BRANCHING TO BE ABOVE 7
 FEET. PEDESTRIAN ENJOYMENT OF THE PUBLIC WALKWAY ALSO
 OUTWEIGHS THE NEEDS OF THE PROPERTY OWNER TO EXPOSE THE
 ARCHITECTURE OF THE BUILDING.
 23. PARTIALLY SATISFIED. TRANSPLANTED OAK TREE #1538
 APPEARS TO BE PROBLEMATIC IN THE SPECIFIED LOCATION
 THAT IT WILL CONFLICT WITH THE BUILDING CONSTRUCTION.
 TRANSPLANTED TREES MAY BE RELOCATED OFF SITE. THIS
 APPEARS THIS COULD ALSO BE AN ISSUE WITH THE OTHER
 RELOCATED TREES AND PALMS.
 THE APPLICANT HAS A NOTE PLACED ON THE PLANS FOR
 TEMPORARY STORAGE OF THE RELOCATED TREES. PROVIDE A
 MORE DETAILED PLAN ON HOW THIS WILL BE IMPLEMENTED. THE
 RELOCATED LIVE OAK IS SHOWN WITH PAVING PROPOSED OVER
 THE ROOT SYSTEM AT ITS NEW LOCATION THAT WILL NOT BE
 PRACTICAL OR HEALTHY FOR THE TREE. THE RENDERINGS SHOW
 GRASS AREA. A SUSPENDED PAVING SYSTEM OR SOIL CELLS
 MUST BE PROVIDED IF THE TREE IS TO BE SUSTAINABLE.
 PROVIDE THE RELOCATION AND MANAGEMENT PLAN FOR THE
 TREES BEFORE, DURING AND AFTER RELOCATION AND INCLUDE
 IT ON THE TREE DISPOSITION PLAN.
 THE APPLICANT HAS PROVIDED INFORMATION IN THE COMMENT
 RESPONSES, BUT THAT INFORMATION NEEDS TO BE IN A
 MANAGEMENT PLAN SUBMITTED FOR REVIEW.
 ADDITIONAL COMMENTS 8/18/21:
 24. SATISFIED. TREE COUNT ON THE PLANT LIST OF 29 LIVE
 OAK TREES DOES NOT MATCH THE PLAN SHOWING 30 TREES.
 25. SATISFIED. THE SIDEWALK PROPOSED ALONG OLIVE AVE.
 APPEARS TO BE TOO CLOSE TO EXISTING TREES AND PALMS.
 PROVIDE MORE DETAIL ON HOW THIS WILL BE ADDRESSED.
 SITE PLAN DOES NOT MATCH ADJUSTED SIDEWALK ON THE
 LANDSCAPE PLAN.
 26. SATISFIED. PROVIDE SCREENING HEDGES FOR ALL GROUND
 MOUNTED EQUIPMENT INCLUDING WATER AND FIRE BACKFLOWS ON
 THE CURRIE CRESCENT SIDE OF THE BUILDING.
 27. SATISFIED. VINES ARE SHOWN ON THE RENDERINGS ON THE
 WALL OF THE EAST SIDE OF THE BUILDING, BUT NO PLANTS
 ARE SHOWN ON THE LANDSCAPE PLAN. CORRECT TO SHOW THE
 PLANTINGS.
 28. PARTIALLY SATISFIED. PROVIDE THE TOTAL MITIGATION
 DUE FOR THE ON SITE TREES AND PALMS TO BE REMOVED.
 ADONIDIA PALMS ARE CATEGORY 4 AND REQUIRE 50 SQ FT
 CANOPY MITIGATION PER TRUNK, SPANISH CHERRY IS LISTED
 UNDER CATEGORY 1 AND REQUIRES 300 SQ FT CANOPY
 MITIGATION. PROVIDE THE LIST OF TREES ADDED TO THE SITE
 AND ASSIGN THE CANOPY CREDITS BASED ON THE CATEGORY AND
 PROVIDE THE TOTAL.
 THERE ARE CORRECTIONS REQUIRED FOR THE ONSITE AND
 OFFSITE MITIGATION CALCULATIONS.
 CALCULATIONS FOR THE MITIGATION PROVIDED ON SITE BASED
 ON THE PLANT LIST SHOULD BE REMOVED FROM SHEET L-3.4
 AND PLACED IN A CHART ON SHEET D-2. SABAL PALMS ARE
 CATEGORY 3 AND ARE 100 SQ FT CREDIT. TOTAL EXCESS OF
 TREE CANOPY NEEDS TO BE SHOWN.
 29. THE PLANTING PLANS FOR THE OFF SITE TREES NEED TO
 BE REVISED TO SHOW THE FOLLOWING:
 ? SATISFIED. THE ROYAL PALMS BETWEEN THE GREEN
 BUTTONWOOD TREES ARE NOT APPROPRIATE TO DUPLICATE THE
 CURRENT LOOK OF THE TREE CANOPY AND THEY WOULD PRESENT
 A SAFETY AND MAINTENANCE ISSUE OVER THE PAVEMENT AND
 PARKING SPACES. REMOVE THE ROW OF PALMS ADJACENT TO THE
 CURB.
 THERE IS A GAP IN THE TREE CANOPY ON THE SOUTH SIDE OF
 ACTION PL. ADJACENT TO THE ANGLED PARKING SPACES. GREEN
 BUTTONWOOD TREES MUST BE PLACED ALONG THIS AREA
 REPLACING THE ROYAL PALMS.
  
 ? SATISFIED. THERE IS NOT ENOUGH ROOM PROVIDED FOR THE
 ROOT ZONE OF THE TREES. THE SIDEWALK NEEDS TO BE PUSHED
 FARTHER AWAY FROM THE CURB (10 TO 12 FEET) ALLOWING
 ENOUGH ROOT SPACE FOR THE TREES AND THE NARROWER
 LANDSCAPE AREA ON THE BACK OF SIDEWALK. ROYAL PALMS
 COULD BE PLACED IN THIS STRIP, BUT THEY WOULD HAVE TO
 BE FAR ENOUGH AWAY FROM THE SIDEWALK TO AVOID FRONDS
 DROPPING ON THE SIDEWALK.
 ? PARTIALLY SATISFIED. PROVIDE THE TOTAL TREE CANOPY
 MITIGATION DUE FOR THE REMOVED TREES AND PROVIDE THE
 MITIGATION SQUARE FOOTAGE PROVIDED FOR THE NEW TREES
 AND PALMS PROPOSED. IF THERE IS MITIGATION DUE, STAFF
 WILL DISCUSS OPTIONS TO ADDRESS IT.
 THERE ARE CORRECTIONS REQUIRED FOR THE ONSITE AND
 OFFSITE MITIGATION CALCULATIONS.
  
 SHOW THE TOTAL MITIGATION DUE AFTER CREDITS ON SHEET
 D-2.
  
 ? SATISFIED. INCREASING THE NUMBER OF GREEN BUTTONWOOD
 TREES AND ROYAL PALMS WOULD INCREASE THE PUBLIC
 BENEFITS AND THE AESTHETICS.
 ? SATISFIED. EXPLAIN WHY THERE IS A GAP ON THE CORNER
 OF OLIVE AND DIANA WITH NO TREE CANOPY PROVIDED. THIS
 WAS A LOCATION SUGGESTED BY STAFF FOR THE RELOCATED
 LIVE OAK TREE.
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
 2. THE APPLICANT, SUCCESSORS SHALL BE RESPONSIBLE FOR
 THE PERMITTING AND INSTALLATION OF THE STREET TREES AND
 RIGHT OF WAY LANDSCAPING AND IRRIGATION APPROVED WITH
 THIS PETITION.
  
 3. THE APPLICANT, SUCCESSORS SHALL BE RESPONSIBLE FOR
 THE MAINTENANCE OF THE, ROAD RIGHT OF WAY
 LANDSCAPING/TREES AND IRRIGATION. THIS WILL BE THROUGH
 A SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 5 Status F Date 09-01-2021 Cont ID  
Sent By rcaranci Date 09-01-2021 Time 16:49 Rev Time 0.00
Received By rcaranci Date 09-01-2021 Time 16:49 Sent To  
Notes
2021-09-01 16:49:51FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: FLAGLER TOWER Z21050015
 AUGUST 31, 2021
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 REVIEW: FLAGLER TOWERS 7/20/21
 1. PREVIOUSLY SATISFIED
 2. PREVIOUSLY SATISFIED
 3. PREVIOUSLY SATISFIED
 4. SATISFIED. DUE TO THE CONSTRUCTION IMPACT ON THE
 EXISTING MATURE TREES ON CITY PROPERTY ALONG DIANA PL.
 REMOVE FICUS TREES AND REPLACE WITH 1 TO 1 CATEGORY
 SHADE TREE. (SEE #5)
 7/27/21 RC: PLAN IS ALREADY IN PLACE BETWEEN PLANNING
 AND PARKS AND REC. TO REPLACE FICUS WITH GREEN BUTTON
 WOOD IN AGREEMENT WITH THE NORTON PARK PLACE CONDO.
 APPLICANTS MAINTENANCE RESPONSIBILITY FOR TREES ON
 NORTH SIDE OF DIANA PLACE.
 7/20/2021
 6. 7/27/21 RC. MAKE THE FOLLOWING CORRECTIONS TO THE
 TREE DISPOSITION LIST:
 ? SATISFIED. SHOW THE DISPOSITION OF TREES #1479 ?
 #1530.
 ? SATISFIED. IDENTIFY TREE #1504
 ? SATISFIED. PROVIDE MITIGATION SQUARE FOOTAGE DUE FOR
 TREES AND PALMS LISTED TO BE REMOVED. ON EXISTING TREES
 ON SITE LIST AND EXISTING TREES ON ADJACENT SITE LIST.
 7. SATISFIED. SEE COMMENT #6 TREE #1479 ON TREE LIST
 WILL NEED TO BE LISTED AS REMOVE TO REFLECT DEPICTION
 ON THE MAP. PAGE D-1
 8. SATISFIED. APPLICANT NEEDS PROVIDE LANDSCAPE PLANS
 FOR POOL TERRACE PAGE LA 3-1. THE LANDSCAPING ON THE
 AMENITIES LEVEL WILL BE APPROVED WITH PROJECT AND NEEDS
 TO BE SUBMITTED.
 9. SATISFIED. LIVE OAK TREES ON FLAGLER APPEAR TO BE IN
 CONFLICT WITH MAN HOLE COVERS AND STORM WATER LINE.
 ADJUST LINE OR TREE LOCATIONS TO BE RESOLVE.
 10. SATISFIED. LIVE OAK ON SOUTH SIDE BUFFER APPEARS TO
 BE TOO CLOSE TO BUILDING AND ENTRY CANOPY AND WILL
 OUTGROW ITS SPACE CREATING A CONFLICT WITH THE BUILDING
 AND SHADE CANOPY.
 THE TREES DO NOT APPEAR ON THE LANDSCAPE PLAN SHEET
 LG-3.1. IF THIS IS IN ERROR, PROVIDE A MANAGEMENT PLAN
 FOR THE MAINTENANCE OF THE TREES.
 11. SATISFIED. IN EAST SIDE COURTYARD THERE IS A STRAY
 UNMARKED DIAGONAL LINE GOING ACROSS. IDENTIFY LINE OR
 REMOVE IF IT?S NOT INTENTIONAL.
 SENIOR LANDSCAPE PLANNER WILL RETURN ON 7/22 PLAN IS
 SUBJECT TO HIS REVIEW
 7/27/21 RC.
 13. SATISFIED. ALL LANDSCAPE PLANS NEED TO BE ON AT
 LEAST 1-20 SCALE PLAN AS THE CURRENT SCALE IS NOT
 READABLE
 14. SATISFIED. SHOW OPEN SPACE SQUARE FOOTAGE FOR THE
 NON-BUILDING AREA OF THE LOT. ADJUST OPEN SPACE DIAGRAM
 ON SHEET LR-2. LANDSCAPING OVER BUILDING STRUCTURE IS
 NOT COUNTED FOR OPEN SPACE. PROVIDE A DIAGRAM SHOWING
 LANDSCAPED AREAS.
 15. SATISFIED. USING THE OPEN SPACE SQUARE FOOTAGE
 CALCULATE THE NUMBER OF REQUIRED SHADE TREES, FLOWERING
 TREES AND SHRUBS PER SECTION 94-442 (C) (2) B. ADD THE
 TOTAL TREES REQUIRED FOR OPEN SPACE AND FOR MULTIFAMILY
 REQUIREMENT AND SHOW THE TOTAL REQUIRED TREES.
 16. SATISFIED. SHOW THE PROVIDED LINEAR FEET OF
 LANDSCAPING FOR THE BUILDING PERIMETER.
 ABOVE GROUND POTS AND PLANTERS MAY NOT BE COUNTED AS
 PERIMETER LANDSCAPE. THERE ARE AREAS ADJACENT TO THE
 BUILDING ON THE OLIVE SIDE AND SHOWN AS PLANTINGS THAT
 DO NOT APPEAR AS OPENINGS IN THE PAVED AREAS. CLEARLY
 IDENTIFY THESE AREAS AND RECALCULATE THE PERIMETER
 LANDSCAPE.
 17. SATISFIED. ADD A NATIVE COLUMN TO THE PLANT
 SCHEDULE SO STAFF CAN VERIFY REQUIREMENTS.
 18. SATISFIED. MAGNOLIA MAY BE COUNTED AS NATIVE.
 19. SATISFIED. FLORIDA FRIENDLY REQUIREMENTS. PROVIDE
 AN AREA PLAN SHOWING THE SOD AREAS AS PART OF THE TOTAL
 LANDSCAPE AREA AND PROVIDE THE TOTAL PERCENTAGE. ITEM
 6B DOES NOT APPLY.
 ITEM 6B STILL DOES NOT APPLY.
 20. SATISFIED. PROVIDE ADDITIONAL INFORMATION ON SEA
 PLUM TREE IN ORDER TO IDENTIFY IF IT IS A CULTIVAR OF
 SEA GRAPE.
 21. SATISFIED. TOTAL NUMBER OF TREES PROVIDED NEEDS TO
 BE SHOWN FROM THE PLANT LIST. CURRENT COUNT IS 92 TREES
 PLUS 11 CABBAGE PALMS AT 3:1 FOR A TOTAL OF 95. SHOW
 RELOCATED TREES ON THE PLANT LIST. SHOW OFFSITE TREES
 ON THE PLANT LIST. IF REQUIRED TREES ARE NOT TO BE
 PROVIDED ON SITE A WAVER MUST BE REQUESTED.
 22. SATISFIED. THE TREES PROVIDED ON THE AMENITY AREA
 ON FLAGLER NEED TO BE SPREAD OUT TO PROVIDE SHADE FOR
 PEDESTRIANS.
 THE INTENT FOR THE OVERALL PEDESTRIAN PLAN FOR THE CITY
 IS TO PROVIDE TREE CANOPY SHADE OVER PUBLIC AREAS AND
 PEDESTRIAN SIDEWALKS. THE LARGE GAP ADJACENT TO THE
 PLAZA DOES NOT MEET THIS INTENT. STAFF DOES NOT
 RECOGNIZE HAVING THE TREES IN FRONT OF THE PLAZA AS A
 SAFETY ISSUE, AS THE TREES WOULD MEET CPTED (CRIME
 PREVENTION THROUGH ENVIRONMENTAL DESIGN)
 RECOMMENDATIONS FOR THE TREE BRANCHING TO BE ABOVE 7
 FEET. PEDESTRIAN ENJOYMENT OF THE PUBLIC WALKWAY ALSO
 OUTWEIGHS THE NEEDS OF THE PROPERTY OWNER TO EXPOSE THE
 ARCHITECTURE OF THE BUILDING.
 23. PARTIALLY SATISFIED. TRANSPLANTED OAK TREE #1538
 APPEARS TO BE PROBLEMATIC IN THE SPECIFIED LOCATION
 THAT IT WILL CONFLICT WITH THE BUILDING CONSTRUCTION.
 TRANSPLANTED TREES MAY BE RELOCATED OFF SITE. THIS
 APPEARS THIS COULD ALSO BE AN ISSUE WITH THE OTHER
 RELOCATED TREES AND PALMS.
 THE APPLICANT HAS A NOTE PLACED ON THE PLANS FOR
 TEMPORARY STORAGE OF THE RELOCATED TREES. PROVIDE A
 MORE DETAILED PLAN ON HOW THIS WILL BE IMPLEMENTED. THE
 RELOCATED LIVE OAK IS SHOWN WITH PAVING PROPOSED OVER
 THE ROOT SYSTEM AT ITS NEW LOCATION THAT WILL NOT BE
 PRACTICAL OR HEALTHY FOR THE TREE. THE RENDERINGS SHOW
 GRASS AREA. A SUSPENDED PAVING SYSTEM OR SOIL CELLS
 MUST BE PROVIDED IF THE TREE IS TO BE SUSTAINABLE.
 PROVIDE THE RELOCATION AND MANAGEMENT PLAN FOR THE
 TREES BEFORE, DURING AND AFTER RELOCATION AND INCLUDE
 IT ON THE TREE DISPOSITION PLAN.
 ADDITIONAL COMMENTS 8/18/21:
 24. SATISFIED. TREE COUNT ON THE PLANT LIST OF 29 LIVE
 OAK TREES DOES NOT MATCH THE PLAN SHOWING 30 TREES.
 25. PARTIALLY SATISFIED. THE SIDEWALK PROPOSED ALONG
 OLIVE AVE. APPEARS TO BE TOO CLOSE TO EXISTING TREES
 AND PALMS. PROVIDE MORE DETAIL ON HOW THIS WILL BE
 ADDRESSED.
 SITE PLAN DOES NOT MATCH ADJUSTED SIDEWALK ON THE
 LANDSCAPE PLAN.
 26. SATISFIED. PROVIDE SCREENING HEDGES FOR ALL GROUND
 MOUNTED EQUIPMENT INCLUDING WATER AND FIRE BACKFLOWS ON
 THE CURRIE CRESCENT SIDE OF THE BUILDING.
 27. SATISFIED. VINES ARE SHOWN ON THE RENDERINGS ON THE
 WALL OF THE EAST SIDE OF THE BUILDING, BUT NO PLANTS
 ARE SHOWN ON THE LANDSCAPE PLAN. CORRECT TO SHOW THE
 PLANTINGS.
 28. PARTIALLY SATISFIED. PROVIDE THE TOTAL MITIGATION
 DUE FOR THE ON SITE TREES AND PALMS TO BE REMOVED.
 ADONIDIA PALMS ARE CATEGORY 4 AND REQUIRE 50 SQ FT
 CANOPY MITIGATION PER TRUNK, SPANISH CHERRY IS LISTED
 UNDER CATEGORY 1 AND REQUIRES 300 SQ FT CANOPY
 MITIGATION. PROVIDE THE LIST OF TREES ADDED TO THE SITE
 AND ASSIGN THE CANOPY CREDITS BASED ON THE CATEGORY AND
 PROVIDE THE TOTAL.
 THERE ARE CORRECTIONS REQUIRED FOR THE ONSITE AND
 OFFSITE MITIGATION CALCULATIONS.
 29. THE PLANTING PLANS FOR THE OFF SITE TREES NEED TO
 BE REVISED TO SHOW THE FOLLOWING:
 ? PARTIALLY SATISFIED. THE ROYAL PALMS BETWEEN THE
 GREEN BUTTONWOOD TREES ARE NOT APPROPRIATE TO DUPLICATE
 THE CURRENT LOOK OF THE TREE CANOPY AND THEY WOULD
 PRESENT A SAFETY AND MAINTENANCE ISSUE OVER THE
 PAVEMENT AND PARKING SPACES. REMOVE THE ROW OF PALMS
 ADJACENT TO THE CURB.
 THERE IS A GAP IN THE TREE CANOPY ON THE SOUTH SIDE OF
 ACTION PL. ADJACENT TO THE ANGLED PARKING SPACES. GREEN
 BUTTONWOOD TREES MUST BE PLACED ALONG THIS AREA
 REPLACING THE ROYAL PALMS.
  
 ? SATISFIED. THERE IS NOT ENOUGH ROOM PROVIDED FOR THE
 ROOT ZONE OF THE TREES. THE SIDEWALK NEEDS TO BE PUSHED
 FARTHER AWAY FROM THE CURB (10 TO 12 FEET) ALLOWING
 ENOUGH ROOT SPACE FOR THE TREES AND THE NARROWER
 LANDSCAPE AREA ON THE BACK OF SIDEWALK. ROYAL PALMS
 COULD BE PLACED IN THIS STRIP, BUT THEY WOULD HAVE TO
 BE FAR ENOUGH AWAY FROM THE SIDEWALK TO AVOID FRONDS
 DROPPING ON THE SIDEWALK.
 ? PARTIALLY SATISFIED. PROVIDE THE TOTAL TREE CANOPY
 MITIGATION DUE FOR THE REMOVED TREES AND PROVIDE THE
 MITIGATION SQUARE FOOTAGE PROVIDED FOR THE NEW TREES
 AND PALMS PROPOSED. IF THERE IS MITIGATION DUE, STAFF
 WILL DISCUSS OPTIONS TO ADDRESS IT.
 THERE ARE CORRECTIONS REQUIRED FOR THE ONSITE AND
 OFFSITE MITIGATION CALCULATIONS.
  
 ? SATISFIED. INCREASING THE NUMBER OF GREEN BUTTONWOOD
 TREES AND ROYAL PALMS WOULD INCREASE THE PUBLIC
 BENEFITS AND THE AESTHETICS.
 ? SATISFIED. EXPLAIN WHY THERE IS A GAP ON THE CORNER
 OF OLIVE AND DIANA WITH NO TREE CANOPY PROVIDED. THIS
 WAS A LOCATION SUGGESTED BY STAFF FOR THE RELOCATED
 LIVE OAK TREE.
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
 2. THE APPLICANT, SUCCESSORS SHALL BE RESPONSIBLE FOR
 THE PERMITTING AND INSTALLATION OF THE STREET TREES AND
 RIGHT OF WAY LANDSCAPING AND IRRIGATION APPROVED WITH
 THIS PETITION.
  
 3. THE APPLICANT, SUCCESSORS SHALL BE RESPONSIBLE FOR
 THE MAINTENANCE OF THE, ROAD RIGHT OF WAY
 LANDSCAPING/TREES AND IRRIGATION. THIS WILL BE THROUGH
 A SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 4 Status F Date 08-19-2021 Cont ID  
Sent By rcaranci Date 08-19-2021 Time 10:17 Rev Time 0.00
Received By rcaranci Date 08-19-2021 Time 10:17 Sent To  
Notes
2021-08-19 10:17:40FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: FLAGLER TOWER Z21050015
 AUGUST 18, 2021
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 REVIEW: FLAGLER TOWERS 7/20/21
 1. PREVIOUSLY SATISFIED
 2. PREVIOUSLY SATISFIED
 3. PREVIOUSLY SATISFIED
 4. SATISFIED. DUE TO THE CONSTRUCTION IMPACT ON THE
 EXISTING MATURE TREES ON CITY PROPERTY ALONG DIANA PL.
 REMOVE FICUS TREES AND REPLACE WITH 1 TO 1 CATEGORY
 SHADE TREE. (SEE #5)
 7/27/21 RC: PLAN IS ALREADY IN PLACE BETWEEN PLANNING
 AND PARKS AND REC. TO REPLACE FICUS WITH GREEN BUTTON
 WOOD IN AGREEMENT WITH THE NORTON PARK PLACE CONDO.
 APPLICANTS MAINTENANCE RESPONSIBILITY FOR TREES ON
 NORTH SIDE OF DIANA PLACE.
 7/20/2021
 6. 7/27/21 RC. MAKE THE FOLLOWING CORRECTIONS TO THE
 TREE DISPOSITION LIST:
 ? SATISFIED. SHOW THE DISPOSITION OF TREES #1479 ?
 #1530.
 ? SATISFIED. IDENTIFY TREE #1504
 ? SATISFIED. PROVIDE MITIGATION SQUARE FOOTAGE DUE FOR
 TREES AND PALMS LISTED TO BE REMOVED. ON EXISTING TREES
 ON SITE LIST AND EXISTING TREES ON ADJACENT SITE LIST.
 7. SATISFIED. SEE COMMENT #6 TREE #1479 ON TREE LIST
 WILL NEED TO BE LISTED AS REMOVE TO REFLECT DEPICTION
 ON THE MAP. PAGE D-1
 8. SATISFIED. APPLICANT NEEDS PROVIDE LANDSCAPE PLANS
 FOR POOL TERRACE PAGE LA 3-1. THE LANDSCAPING ON THE
 AMENITIES LEVEL WILL BE APPROVED WITH PROJECT AND NEEDS
 TO BE SUBMITTED.
 9. SATISFIED. LIVE OAK TREES ON FLAGLER APPEAR TO BE IN
 CONFLICT WITH MAN HOLE COVERS AND STORM WATER LINE.
 ADJUST LINE OR TREE LOCATIONS TO BE RESOLVE.
 10. PARTIALLY SATISFIED. LIVE OAK ON SOUTH SIDE BUFFER
 APPEARS TO BE TOO CLOSE TO BUILDING AND ENTRY CANOPY
 AND WILL OUTGROW ITS SPACE CREATING A CONFLICT WITH THE
 BUILDING AND SHADE CANOPY.
 THE TREES DO NOT APPEAR ON THE LANDSCAPE PLAN SHEET
 LG-3.1. IF THIS IS IN ERROR, PROVIDE A MANAGEMENT PLAN
 FOR THE MAINTENANCE OF THE TREES.
 11. SATISFIED. IN EAST SIDE COURTYARD THERE IS A STRAY
 UNMARKED DIAGONAL LINE GOING ACROSS. IDENTIFY LINE OR
 REMOVE IF IT?S NOT INTENTIONAL.
 SENIOR LANDSCAPE PLANNER WILL RETURN ON 7/22 PLAN IS
 SUBJECT TO HIS REVIEW
 7/27/21 RC.
 13. SATISFIED. ALL LANDSCAPE PLANS NEED TO BE ON AT
 LEAST 1-20 SCALE PLAN AS THE CURRENT SCALE IS NOT
 READABLE
 14. SATISFIED. SHOW OPEN SPACE SQUARE FOOTAGE FOR THE
 NON-BUILDING AREA OF THE LOT. ADJUST OPEN SPACE DIAGRAM
 ON SHEET LR-2. LANDSCAPING OVER BUILDING STRUCTURE IS
 NOT COUNTED FOR OPEN SPACE. PROVIDE A DIAGRAM SHOWING
 LANDSCAPED AREAS.
 15. SATISFIED. USING THE OPEN SPACE SQUARE FOOTAGE
 CALCULATE THE NUMBER OF REQUIRED SHADE TREES, FLOWERING
 TREES AND SHRUBS PER SECTION 94-442 (C) (2) B. ADD THE
 TOTAL TREES REQUIRED FOR OPEN SPACE AND FOR MULTIFAMILY
 REQUIREMENT AND SHOW THE TOTAL REQUIRED TREES.
 16. PARTIALLY SATISFIED. SHOW THE PROVIDED LINEAR FEET
 OF LANDSCAPING FOR THE BUILDING PERIMETER.
 ABOVE GROUND POTS AND PLANTERS MAY NOT BE COUNTED AS
 PERIMETER LANDSCAPE. THERE ARE AREAS ADJACENT TO THE
 BUILDING ON THE OLIVE SIDE AND SHOWN AS PLANTINGS THAT
 DO NOT APPEAR AS OPENINGS IN THE PAVED AREAS. CLEARLY
 IDENTIFY THESE AREAS AND RECALCULATE THE PERIMETER
 LANDSCAPE.
 17. SATISFIED. ADD A NATIVE COLUMN TO THE PLANT
 SCHEDULE SO STAFF CAN VERIFY REQUIREMENTS.
 18. SATISFIED. MAGNOLIA MAY BE COUNTED AS NATIVE.
 19. PARTIALLY SATISFIED. FLORIDA FRIENDLY REQUIREMENTS.
 PROVIDE AN AREA PLAN SHOWING THE SOD AREAS AS PART OF
 THE TOTAL LANDSCAPE AREA AND PROVIDE THE TOTAL
 PERCENTAGE. ITEM 6B DOES NOT APPLY.
 ITEM 6B STILL DOES NOT APPLY.
 20. SATISFIED. PROVIDE ADDITIONAL INFORMATION ON SEA
 PLUM TREE IN ORDER TO IDENTIFY IF IT IS A CULTIVAR OF
 SEA GRAPE.
 21. SATISFIED. TOTAL NUMBER OF TREES PROVIDED NEEDS TO
 BE SHOWN FROM THE PLANT LIST. CURRENT COUNT IS 92 TREES
 PLUS 11 CABBAGE PALMS AT 3:1 FOR A TOTAL OF 95. SHOW
 RELOCATED TREES ON THE PLANT LIST. SHOW OFFSITE TREES
 ON THE PLANT LIST. IF REQUIRED TREES ARE NOT TO BE
 PROVIDED ON SITE A WAVER MUST BE REQUESTED.
 22. NOT SATISFIED. THE TREES PROVIDED ON THE AMENITY
 AREA ON FLAGLER NEED TO BE SPREAD OUT TO PROVIDE SHADE
 FOR PEDESTRIANS.
 THE INTENT FOR THE OVERALL PEDESTRIAN PLAN FOR THE CITY
 IS TO PROVIDE TREE CANOPY SHADE OVER PUBLIC AREAS AND
 PEDESTRIAN SIDEWALKS. THE LARGE GAP ADJACENT TO THE
 PLAZA DOES NOT MEET THIS INTENT. STAFF DOES NOT
 RECOGNIZE HAVING THE TREES IN FRONT OF THE PLAZA AS A
 SAFETY ISSUE, AS THE TREES WOULD MEET CPTED (CRIME
 PREVENTION THROUGH ENVIRONMENTAL DESIGN)
 RECOMMENDATIONS FOR THE TREE BRANCHING TO BE ABOVE 7
 FEET. PEDESTRIAN ENJOYMENT OF THE PUBLIC WALKWAY ALSO
 OUTWEIGHS THE NEEDS OF THE PROPERTY OWNER TO EXPOSE THE
 ARCHITECTURE OF THE BUILDING.
 23. PARTIALLY SATISFIED. TRANSPLANTED OAK TREE #1538
 APPEARS TO BE PROBLEMATIC IN THE SPECIFIED LOCATION
 THAT IT WILL CONFLICT WITH THE BUILDING CONSTRUCTION.
 TRANSPLANTED TREES MAY BE RELOCATED OFF SITE. THIS
 APPEARS THIS COULD ALSO BE AN ISSUE WITH THE OTHER
 RELOCATED TREES AND PALMS.
 THE APPLICANT HAS A NOTE PLACED ON THE PLANS FOR
 TEMPORARY STORAGE OF THE RELOCATED TREES. PROVIDE A
 MORE DETAILED PLAN ON HOW THIS WILL BE IMPLEMENTED. THE
 RELOCATED LIVE OAK IS SHOWN WITH PAVING PROPOSED OVER
 THE ROOT SYSTEM AT ITS NEW LOCATION THAT WILL NOT BE
 PRACTICAL OR HEALTHY FOR THE TREE. THE RENDERINGS SHOW
 GRASS AREA. A SUSPENDED PAVING SYSTEM OR SOIL CELLS
 MUST BE PROVIDED IF THE TREE IS TO BE SUSTAINABLE.
 ADDITIONAL COMMENTS 8/18/21:
 24. TREE COUNT ON THE PLANT LIST OF 29 LIVE OAK TREES
 DOES NOT MATCH THE PLAN SHOWING 30 TREES.
 25. THE SIDEWALK PROPOSED ALONG OLIVE AVE. APPEARS TO
 BE TOO CLOSE TO EXISTING TREES AND PALMS. PROVIDE MORE
 DETAIL ON HOW THIS WILL BE ADDRESSED.
 26. PROVIDE SCREENING HEDGES FOR ALL GROUND MOUNTED
 EQUIPMENT INCLUDING WATER AND FIRE BACKFLOWS ON THE
 CURRIE CRESCENT SIDE OF THE BUILDING.
 27. VINES ARE SHOWN ON THE RENDERINGS ON THE WALL OF
 THE EAST SIDE OF THE BUILDING, BUT NO PLANTS ARE SHOWN
 ON THE LANDSCAPE PLAN. CORRECT TO SHOW THE PLANTINGS.
 28. PROVIDE THE TOTAL MITIGATION DUE FOR THE ON SITE
 TREES AND PALMS TO BE REMOVED. ADONIDIA PALMS ARE
 CATEGORY 4 AND REQUIRE 50 SQ FT CANOPY MITIGATION PER
 TRUNK, SPANISH CHERRY IS LISTED UNDER CATEGORY 1 AND
 REQUIRES 300 SQ FT CANOPY MITIGATION. PROVIDE THE LIST
 OF TREES ADDED TO THE SITE AND ASSIGN THE CANOPY
 CREDITS BASED ON THE CATEGORY AND PROVIDE THE TOTAL.
 29. THE PLANTING PLANS FOR THE OFF SITE TREES NEED TO
 BE REVISED TO SHOW THE FOLLOWING:
 ? THE ROYAL PALMS BETWEEN THE GREEN BUTTONWOOD TREES
 ARE NOT APPROPRIATE TO DUPLICATE THE CURRENT LOOK OF
 THE TREE CANOPY AND THEY WOULD PRESENT A SAFETY AND
 MAINTENANCE ISSUE OVER THE PAVEMENT AND PARKING SPACES.
 REMOVE THE ROW OF PALMS ADJACENT TO THE CURB.
 ? THERE IS NOT ENOUGH ROOM PROVIDED FOR THE ROOT ZONE
 OF THE TREES. THE SIDEWALK NEEDS TO BE PUSHED FARTHER
 AWAY FROM THE CURB (10 TO 12 FEET) ALLOWING ENOUGH ROOT
 SPACE FOR THE TREES AND THE NARROWER LANDSCAPE AREA ON
 THE BACK OF SIDEWALK. ROYAL PALMS COULD BE PLACED IN
 THIS STRIP, BUT THEY WOULD HAVE TO BE FAR ENOUGH AWAY
 FROM THE SIDEWALK TO AVOID FRONDS DROPPING ON THE
 SIDEWALK.
 ? PROVIDE THE TOTAL TREE CANOPY MITIGATION DUE FOR THE
 REMOVED TREES AND PROVIDE THE MITIGATION SQUARE FOOTAGE
 PROVIDED FOR THE NEW TREES AND PALMS PROPOSED. IF THERE
 IS MITIGATION DUE, STAFF WILL DISCUSS OPTIONS TO
 ADDRESS IT.
 ? INCREASING THE NUMBER OF GREEN BUTTONWOOD TREES AND
 ROYAL PALMS WOULD INCREASE THE PUBLIC BENEFITS AND THE
 AESTHETICS.
 ? EXPLAIN WHY THERE IS A GAP ON THE CORNER OF OLIVE AND
 DIANA WITH NO TREE CANOPY PROVIDED. THIS WAS A LOCATION
 SUGGESTED BY STAFF FOR THE RELOCATED LIVE OAK TREE.
  
  
 CONDITION OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
 2. THE APPLICANT, SUCCESSORS SHALL BE RESPONSIBLE FOR
 THE PERMITTING AND INSTALLATION OF THE STREET TREES AND
 RIGHT OF WAY LANDSCAPING AND IRRIGATION APPROVED WITH
 THIS PETITION.
  
 3. THE APPLICANT, SUCCESSORS SHALL BE RESPONSIBLE FOR
 THE MAINTENANCE OF THE, ROAD RIGHT OF WAY
 LANDSCAPING/TREES AND IRRIGATION. THIS WILL BE THROUGH
 A SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 3 Status F Date 07-27-2021 Cont ID  
Sent By rcaranci Date 07-27-2021 Time 11:37 Rev Time 0.00
Received By rcaranci Date 07-27-2021 Time 11:37 Sent To  
Notes
2021-07-27 11:41:16MEMO TO FILE
 FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: FLAGLER TOWER Z21050015
 JULY 27, 2021
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 REVIEW: FLAGLER TOWERS 7/20/21
 1. SATISFIED THE PLEACHING OR SHAPING OF TREES IS
 PROHIBITED BY THE CITY OF WEST PALM BEACH AND IS
 CONSIDERED TREE ABUSE. STANDARDS FOR TRIMMING SHALL BE
 PERFORMED IN ACCORDANCE WITH THE LATEST PRUNING
 STANDARDS FOR SHADE TREES RECOMMENDED BY THE NATIONAL
 ARBORIST ASSOCIATION. 94-446 B 1-5
  
 2. SATISFIED MULTIPLE TREES ALONG CURRIE CRESCENT ARE
 SHOWN TO BE PLANTED ON THE WATER AND STORMWATER LINES.
 ADJUST PLANTINGS IN CONFLICT WITH UTILITIES.
  
 3. SATISFIED PROVIDE THE CALCULATION FOR THE
 INTERRUPTIONS IN THE LANDSCAPE BUFFER ON THE PROPERTY
 LINES. UPDATE/ADJUST TREE COUNT CALCULATIONS BUFFER
 1/30 FEET.
  
 A. FLAGLER ? 9? UNABLE TO TELL TREE COUNT.
 B. SOUTH DIANA PL ? UPDATE TO REFLECT THAT 19 TREES ARE
 REQUIRED (NEED TO ROUND UP FOR ANY FRACTION OF A TREE).
 INCLUDING THE PALMS ON THE CORNER THE SOUTH SIDE BUFFER
 REQUIREMENT APPEARS TO BE MET .
 C. OLIVE ? 7? THE LANDSCAPE BUFFER TREES ARE TO BE
 INSTALLED ON- SITE, THEY CAN?T BE PLANTING ON THE RIGHT
 - OF ? WAY AND COUNT TOWARD MEETING CODE.
 D. CURRIE CRESCENT- 9? UNABLE TO TELL. AT LEAST ONE
 SHADE TREE SHALL BE PLANTED EVERY LINEAR FEET OR
 PORTION THEREOF. RELOCATED PALMS CANNOT ALL BE PLANTED
 IN THE SAME AREA DUE TO CODE SHADE TREE REQUIREMENTS.
 SEC. 94-443 A. ? F.
 E. NORTH PROPERTY LINE ? APPEARS TO HAVE 12 SEA GRAPE.
 REQUIREMENT MET.
  
  
  
 4. PARTIALLY SATISFIED DUE TO THE CONSTRUCTION IMPACT
 ON THE EXISTING MATURE TREES ON CITY PROPERTY ALONG
 DIANA PL. REMOVE FICUS TREES AND REPLACE WITH 1 TO 1
 CATEGORY SHADE TREE. (SEE #5)
 7/27/21 RC: PLAN IS ALREADY IN PLACE BETWEEN PLANNING
 AND PARKS AND REC. TO REPLACE FICUS WITH GREEN BUTTON
 WOOD IN AGREEMENT WITH THE NORTON PARK PLACE CONDO.
 APPLICANTS MAINTENANCE RESPONSIBILITY FOR TREES ON
 NORTH SIDE OF DIANA PLACE.
  
  
 7/20/2021
 6. 7/27/21 RC. MAKE THE FALLOWING CORRECTIONS TO THE
 TREE DISPOSITION LIST:
 ? SHOW THE DISPOSITION OF TREES #1479 ? #1530.
 ? IDENTIFY TREE #1504
 ? PROVIDE MITIGATION SQUARE FOOTAGE DUE FOR TREES AND
 PALMS LISTED TO BE REMOVED. ON EXISTING TREES ON SITE
 LIST AND EXISTING TREES ON ADJACENT SITE LIST .
  
  
 7. SEE COMMENT #6 TREE #1479 ON TREE LIST WILL NEED TO
 BE LISTED AS REMOVE TO REFLECT DEPICTION ON THE MAP.
 PAGE D-1
  
 8. APPLICANT NEEDS PROVIDE LANDSCAPE PLANS FOR POOL
 TERRACE PAGE LA 3-1. THE LANDSCAPING ON THE AMENITIES
 LEVEL WILL BE APPROVED WITH PROJECT AND NEEDS TO BE
 SUBMITTED.
  
 9. LIVE OAK TREES ON FLAGLER APPEAR TO BE IN CONFLICT
 WITH MAN HOLE COVERS AND STORM WATER LINE. ADJUST LINE
 OR TREE LOCATIONS TO BE RESOLVE.
  
 10. LIVE OAK ON SOUTH SIDE BUFFER APPEARS TO BE TO
 CLOSE TO BUILDING AND ENTRY CANOPY AND WILL OUTGROW ITS
 SPACE CREATING A CONFLICT WITH THE BUILDING AND SHADE
 CANOPY.
  
 11. IN EAST SIDE COURTYARD THERE IS A STRAY UNMARKED
 DIAGONAL LINE GOING ACROSS. IDENTIFY LINE OR REMOVE IF
 IT?S NOT INTENTIONAL.
  
 SENIOR LANDSCAPE PLANNER WILL RETURN ON 7/22 PLAN IS
 SUBJECT TO HIS REVIEW
 7/27/21 RC.
 13. ALL LANDSCAPE PLANS NEED TO BE ON AT LEAST 1-20
 SCALE PLAN AS THE CURRENT SCALE IS NOT READABLE
 14. SHOW OPEN SPACE SQUARE FOOTAGE FOR THE NON-BUILDING
 AREA OF THE LOT. ADJUST OPEN SPACE DIAGRAM ON SHEET
 LR-2. LANDSCAPING OVER BUILDING STRUCTURE IS NOT
 COUNTED FOR OPEN SPACE. PROVIDE A DIAGRAM SHOWING
 LANDSCAPED AREAS.
 15. USING THE OPEN SPACE SQUARE FOOTAGE CALCULATE THE
 NUMBER OF REQUIRED SHADE TREES, FLOWERING TREES AND
 SHRUBS PER SECTION 94-442 (C) (2) B. ADD THE TOTAL
 TREES REQUIRED FOR OPEN SPACE AND FOR MULTIFAMILY
 REQUIREMENT AND SHOW THE TOTAL REQUIRED TREES.
 16. SHOW THE PROVIDED LINIER FEET OF LANDSCAPING FOR
 THE BUILDING PERIMETER.
 17. ADD A NATIVE COLUMN TO THE PLANT SCHEDULE SO STAFF
 CAN VERIFY REQUIREMENTS.
 18. MAGNOLIA MAY BE COUNTED AS NATIVE.
 19. FLORIDA FRIENDLY REQUIREMENTS. PROVIDE AN AREA PLAN
 SHOWING THE SOD AREAS AS PART OF THE TOTAL LANDSCAPE
 AREA AND PROVIDE THE TOTAL PERCENTAGE. ITEM 6B DOES NOT
 APPLY.
 20. PROVIDE ADDITIONAL INFORMATION ON SEA PLUM TREE IN
 ORDER TO IDENTIFY IF IT IS A CULTIVAR OF SEA GRAPE.
 21. TOTAL NUMBER OF TREES PROVIDED NEEDS TO BE SHOWN
 FROM THE PLANT LIST. CURRENT COUNT IS 92 TREES PLUS 11
 CABBAGE PALMS AT 3:1 FOR A TOTAL OF 95. SHOW RELOCATED
 TREES ON THE PLANT LIST. SHOW OFFSITE TREES ON THE
 PLANT LIST. IF REQUIRED TREES ARE NOT TO BE PROVIDED ON
 SITE A WAVER MUST BE REQUESTED.
 22. THE TREES PROVIDED ON THE AMENITY AREA ON FLAGLER
 NEED TO BE SPREAD OUT TO PROVIDE SHADE FOR PEDESTRIANS.
 23. TRANSPLANTED OAK TREE #1538 APPEARS TO BE
 PROBLEMATIC IN THE SPECIFIED LOCATION THAT IT WILL
 CONFLICT WITH THE BUILDING CONSTRUCTION. TRANSPLANTED
 TREES MAYBE RELOCATED OFF SITE. THIS APPEARS THIS COULD
 ALSO BE AN ISSUE WITH THE OTHER RELOCATED TREES AND
 PALMS.
  
 CONDITION OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
 2. THE APPLICANT, SUCCESSORS SHALL BE RESPONSIBLE FOR
 THE PERMITTING AND INSTALLATION OF THE STREET TREES AND
 RIGHT OF WAY LANDSCAPING AND IRRIGATION APPROVED WITH
 THIS PETITION.
  
 3. THE APPLICANT, SUCCESSORS SHALL BE RESPONSIBLE FOR
 THE MAINTENANCE OF THE, ROAD RIGHT OF WAY
 LANDSCAPING/TREES AND IRRIGATION. THIS WILL BE THROUGH
 A SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 07-19-2021 Cont ID  
Sent By aburnett Date 07-19-2021 Time 11:53 Rev Time 0.00
Received By aburnett Date 07-19-2021 Time 11:53 Sent To  
Notes
2021-07-19 11:54:58ANDREW BURNETT, LANDSCAPE PLANNER 561-822-1562
 REVIEW: FLAGLER TOWERS 7/20/21
 1. SATISFIED THE PLEACHING OR SHAPING OF TREES IS
 PROHIBITED BY THE CITY OF WEST PALM BEACH AND IS
 CONSIDERED TREE ABUSE. STANDARDS FOR TRIMMING SHALL BE
 PERFORMED IN ACCORDANCE WITH THE LATEST PRUNING
 STANDARDS FOR SHADE TREES RECOMMENDED BY THE NATIONAL
 ARBORIST ASSOCIATION. 94-446 B 1-5
  
 2. SATISFIED MULTIPLE TREES ALONG CURRIE CRESCENT ARE
 SHOWN TO BE PLANTED ON THE WATER AND STORMWATER LINES.
 ADJUST PLANTINGS IN CONFLICT WITH UTILITIES.
  
 3. SATISFIED PROVIDE THE CALCULATION FOR THE
 INTERRUPTIONS IN THE LANDSCAPE BUFFER ON THE PROPERTY
 LINES. UPDATE/ADJUST TREE COUNT CALCULATIONS BUFFER
 1/30 FEET.
  
 A. FLAGLER ? 9? UNABLE TO TELL TREE COUNT.
 B. SOUTH DIANA PL ? UPDATE TO REFLECT THAT 19 TREES ARE
 REQUIRED (NEED TO ROUND UP FOR ANY FRACTION OF A TREE).
 INCLUDING THE PALMS ON THE CORNER THE SOUTH SIDE BUFFER
 REQUIREMENT APPEARS TO BE MET .
 C. OLIVE ? 7? THE LANDSCAPE BUFFER TREES ARE TO BE
 INSTALLED ON- SITE, THEY CAN?T BE PLANTING ON THE RIGHT
 - OF ? WAY AND COUNT TOWARD MEETING CODE.
 D. CURRIE CRESCENT- 9? UNABLE TO TELL. AT LEAST ONE
 SHADE TREE SHALL BE PLANTED EVERY LINEAR FEET OR
 PORTION THEREOF. RELOCATED PALMS CANNOT ALL BE PLANTED
 IN THE SAME AREA DUE TO CODE SHADE TREE REQUIREMENTS.
 SEC. 94-443 A. ? F.
 E. NORTH PROPERTY LINE ? APPEARS TO HAVE 12 SEA GRAPE.
 REQUIREMENT MET.
  
  
  
 4. PARTIALLY SATISFIED DUE TO THE CONSTRUCTION IMPACT
 ON THE EXISTING MATURE TREES ON CITY PROPERTY ALONG
 DIANA PL. REMOVE FICUS TREES AND REPLACE WITH 1 TO 1
 CATEGORY SHADE TREE. (SEE #5)
  
 7/20/2021
 5. THE USE OF LIVE OAK OR MAHOGANY WOULD BE PREFERRED
 FOR SUGGESTED REMOVAL AND REPLACEMENT OF FICUS. ZONING
 WILL CONDUCT ADDITIONAL INVESTIGATION ON FEASIBILITY OF
 REMOVAL, REPLACEMENT AND MAINTENANCE RESPONSIBILITIES
 OF TREES ON ACTAEON PL.
  
 6. UPDATE TREE DISPOSITION PLAN TO REFLECT PROPOSED
 TREE TO BE REMOVED ON ACTAEON.
  
 7. TREE #1479 ON TREE LIST WILL NEED TO BE LISTED AS
 REMOVE TO REFLECT DEPICTION ON THE MAP. PAGE D-1
  
 8. APPLICANT NEEDS PROVIDE LANDSCAPE PLANS FOR POOL
 TERRACE PAGE LA 3-1
  
 9. LIVE OAK TREES ON FLAGLER APPEAR TO BE IN CONFLICT
 WITH MAN HOLE COVERS AND STORM WATER LINE. ADJUST LINE
 OR TREE LOCATIONS TO RESOLVE
  
 10. LIVE OAK ON SOUTH SIDE BUFFER APPEARS TO BE TO
 CLOSE TO BUILDING AND ENTRY CANOPY AND WILL OUT GROW
 ITS SPACE CREATING A CONFLICT WITH THE BUILDING AND
 SHADE CANOPY. THIS COULD BE A BETTER LOCATION FOR LARGE
 SCALE PALM ..... ROYAL, BISMARK, MEDJOOL.
  
 11. UNABLE TO FIND INFORMATION ON PLAN REGARDING
 PLANTING SOIL
  
 12. IN EAST SIDE COURTYARD THERE IS A STRAY UNMARKED
 DIAGONAL LINE GOING ACROSS . IDENTIFY LINE OR REMOVE IF
 ITS NOT INTENTIONAL.
  
 SEINOR LANDSCAPE PLANNER WILL RETURN ON 7/22 PLAN IS
 SUBJECT TO HIS REVIEW
  
 CONDITION OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
 2. THE APPLICANT, SUCCESSORS SHALL BE RESPONSIBLE FOR
 THE PERMITTING AND INSTALLATION OF THE STREET TREES AND
 RIGHT OF WAY LANDSCAPING AND IRRIGATION APPROVED WITH
 THIS PETITION.
  
 3. THE APPLICANT, SUCCESSORS SHALL BE RESPONSIBLE FOR
 THE MAINTENANCE OF THE, ROAD RIGHT OF WAY
 LANDSCAPING/TREES AND IRRIGATION. THIS WILL BE THROUGH
 A SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 06-07-2021 Time   Rev Time  
Received By   Date 06-07-2021 Time   Sent To  
Notes
2021-06-07 11:49:111. THE PLEACHING OR SHAPING OF TREES IS PROHIBITED BY
 THE CITY OF WEST PALM BEACH AND IS CONSIDERED TREE
 ABUSE. STANDARDS FOR TRIMMING SHALL BE PERFORMED IN
 ACCORDANCE WITH THE LATEST PRUNING STANDARDS FOR SHADE
 TREES RECOMMENDED BY THE NATIONAL ARBORIST ASSOCIATION.
 94-446 B 1-5
  
 2. MULTIPLE TREES ALONG CURRIE CRESCENT ARE SHOWN TO BE
 PLANTED ON THE WATER AND STORMWATER LINES. ADJUST
 PLANTINGS IN CONFLICT WITH UTILITIES.
  
 3. PROVIDE THE CALCULATION FOR THE INTERRUPTIONS IN THE
 LANDSCAPE BUFFER ON THE PROPERTY LINES. UPDATE/ADJUST
 TREE COUNT CALCULATIONS BUFFER 1/30 FEET.
  
 A. FLAGLER ? 9? UNABLE TO TELL TREE COUNT.
 B. SOUTH DIANA PL ? UPDATE TO REFLECT THAT 19 TREES ARE
 REQUIRED (NEED TO ROUND UP FOR ANY FRACTION OF A TREE).
 INCLUDING THE PALMS ON THE CORNER THE SOUTH SIDE BUFFER
 REQUIREMENT APPEARS TO BE MET .
 C. OLIVE ? 7? THE LANDSCAPE BUFFER TREES ARE TO BE
 INSTALLED ON- SITE, THEY CAN?T BE PLANTING ON THE RIGHT
 - OF ? WAY AND COUNT TOWARD MEETING CODE.
 D. CURRIE CRESCENT- 9? UNABLE TO TELL. AT LEAST ONE
 SHADE TREE SHALL BE PLANTED EVERY LINEAR FEET OR
 PORTION THEREOF. RELOCATED PALMS CANNOT ALL BE PLANTED
 IN THE SAME AREA DUE TO CODE SHADE TREE REQUIREMENTS.
 SEC. 94-443 A. ? F.
 E. NORTH PROPERTY LINE ? APPEARS TO HAVE 12 SEA GRAPE.
 REQUIREMENT MET.
  
  
  
 4. DUE TO THE CONSTRUCTION IMPACT ON THE EXISTING
 MATURE TREES ON CITY PROPERTY ALONG DIANA PL. REMOVE
 FICUS TREES AND REPLACE WITH 1 TO 1 CATEGORY SHADE
 TREE.
  
  
 ANDREW BURNETT
 561-822-1562

Review Stop PW PUBLIC WORKS
Rev No 2 Status P Date 07-01-2021 Cont ID  
Sent By   Date 07-01-2021 Time   Rev Time 0.00
Received By   Date 07-01-2021 Time   Sent To  
Notes
2021-07-01 12:38:29PASSED WITH A PRIVISO FOR THE ROLL-OUT CONTAINERS TO BE
 FRONT LOAD TYPE.
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045
  

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 06-07-2021 Cont ID  
Sent By   Date 06-07-2021 Time   Rev Time  
Received By   Date 06-07-2021 Time   Sent To  
Notes
2021-06-07 14:31:15PLEASE PROVIDE THE FOLLOWINGS:
 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID
 WASTE VOLUME PRODUCED ALONG WITH THE SIZE, TYPE AND
 QUANTITY OF THE CONTAINER (I.E. DUMPSTER/COMPACTOR)
 THAT WILL BE UTILIZED THAT WILL BE UTILIZED FOR THE
 SANITATION SERVICE.
 2- DUMPSTER ENCLOSURE DETAIL. FOR A FREESTANDING SITE
 DUMPSTER ENCLOSURE, THE ENCLOSURE SHALL COMPLY WITH THE
 LATEST REVISION OF CITY OF WEST PALM BEACH GENERAL
 CONSTRUCTION-GARBAGE ENCLOSURE STANDARD, GC-7.
 3- AUTOTURN EXHIBIT (DYNAMIC ENVELOPE AND THE VEHICLES
 WHEEL PATH) FOR THE SANITATION SERVICE, FRONT LOADER
 TRUCK WITH THE FOLLOWING SPECS:
 - DUAL AXLES
 - TRUCK LENGTH: 35 FT
 - TRUCK WIDTH: 11 FT
 - TURNING RADIUS:
 - SAE TURNING RADIUS: 32.5 FT
 - CURB-TO-CURB DIAMETER: 74 FT
 - WALL-TO-WALL DIAMETER: 86.3 FT
 4- DESIGNATED LOCATION FOR THE BULK ITEM PICK UP AND
 RECYCLING CONTAINERS
  
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045

Review Stop STORM STORMWATER
Rev No 6 Status P Date 11-05-2021 Cont ID  
Sent By tward Date 11-05-2021 Time 13:47 Rev Time 0.00
Received By tward Date 11-05-2021 Time 13:50 Sent To  
Notes
2021-11-05 13:50:10THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 OCTOBER 29, 2021 PLAN SUBMITTAL.
  
 1. [CONDITION OF SITE PLAN APPROVAL - COORDINATE THE
 GRADING OF CURRIE CRESCENT WITH THE FORTE RESIDENCES
 DEVELOPMENT.] PROPOSED GRADES AT EAST CURB OF CURRIE
 CRESCENT AT THE INTERFACE BETWEEN THE 9/8/21 FORTE
 RESIDENCES GRADING PLAN AND THE 9/13/21 FLAGLER TOWERS
 GRADING PLAN APPEAR TO MATCH. [SEE NEW COMMENT 31
 BELOW]
  
 2. [SATISFIED] FLAGLER TOWERS GRADING PLAN SHOWS A SPOT
 GRADE OF 11.07 AT THE PROPOSED SANITARY SEWER MANHOLE.
 THIS GRADE WILL CAUSE WATER TO POND IN THE DRIVEWAY
 GUTTER TO THE NORTH (WHICH HAS SPOT GRADES OF 10.93 ON
 THE SOUTH SIDE AND 11.18 ME ON THE NORTH SIDE OF THE
 DRIVEWAY APRON.
  
 3. [SATISFIED] MAINTAIN CROWN CROSS SECTION OF CURRIE
 CRESCENT.
  
 4. [SATISFIED] REQUESTED DIMENSIONS WERE ONLY PROVIDE
 FOR SECTIONS B-B, C-C, D-D, H-H, AND J-J. PREVIOUS
 COMMENT: FOR THE CROSS SECTIONS ON SHEET C-501, PROVIDE
 DIMENSIONS FROM PROPERTY LINE/RIGHT OF WAY LINE TO
 VALLEY GUTTER OR BACK OF SIDEWALK.
  
 5. [SATISFIED] SIDEWALK ACROSS WEST DRIVEWAY TO CURRIE
 CRESCENT SHALL SLOPE TOWARD THE STREET. THE HIGH POINT
 OF THE DRIVEWAY SHALL BE SUFFICIENT TO PREVENT
 STORMWATER RUNOFF FROM THE RIGHT OF WAY FROM FLOWING
 DOWN THE DRIVEWAY TOWARD THE BUILDING AND AT THE SAME
 TIME MINIMIZE THE AREA OF THE DRIVEWAY SLOPING TOWARD
 THE ROAD (I.E. MAXIMIZE THE DRIVEWAY SLOPE BETWEEN THE
 HIGH POINT AND THE BACK OF THE SIDEWALK.)] SUGGEST
 SLOPING THE SIDEWALK PORTION OF THE DRIVEWAY SHOWN IN
 SECTION B-B TOWARD THE VALLEY GUTTER. THE GRADES SHOWN
 ON SHEET C-500 FOR THE DRIVEWAY WITH SECTION B-B (10.72
 AT EP AND 10.70/10.84 AT BOW ACROSS DRIVEWAY) DO NOT
 MATCH THE GRADES SHOWN ON SECTION B-B ON SHEET C-501
 (11.00 AT EP AND 11.04 AT BACK OF CROSSWALK [HIGH POINT
 OF DRIVEWAY]). SECTION B-B SHOWS LESS THAN 1/2 INCH
 DROP (0.04 FT) BETWEEN BACK OF WALK AND EP. THIS SHORT
 RISE WILL NOT STOP MUCH ROADWAY STORMWATER RUNOFF FROM
 FLOWING DOWN THE DRIVEWAY. THE GRADING PLAN DOESN?T
 APPEAR TO SUPPORT ALL OF THE CROSSWALK/SIDEWALK SLOPING
 TOWARD THE ROAD.
  
 6. [SATISFIED - SLOPES REMOVED FROM SHEET G-203.]
 PREVIOUS COMMENT: SECTION D-D SHOWS 13.5% SLOPE EAST OF
 THE PROPERTY LINE. SHEET G-203 SHOWS 7.5% RAMP UP.
 PREVIOUS COMMENT: COORDINATE THE SLOPES SHOWN FOR THE
 DRIVEWAYS WITH THE ARCHITECTURAL PLANS. FOR EXAMPLE,
 SECTION C-C SHOWS 3.4% SLOPE BETWEEN THE BUILDING AND
 VALLEY GUTTER. SHEET A-101 SHOWS THE DRIVEWAY AT 7.5%
 SLOPE.
  
 7. [SATISFIED] SECTION D-D: PROVIDE SIDEWALK AREA WITH
 SLOPE NO STEEPER THAN 2%.
  
 8. [SATISFIED] SECTION E-E: CORRECT LABELS FOR ROAD
 CENTERLINE AND PROPERTY LINE.
  
 9. [SATISFIED] [CONDITION OF SITE PLAN APPROVAL -
 PARALLEL PARKING SPACES ON DIANA PLACE SHALL SLOPE TO
 THE PROPOSED NORTH TYPE 'D' CURB AT MINIMUM 2% CROSS
 SLOPE. LANDSCAPE AREA BETWEEN BACK CURB AND 10 FT
 SIDEWALK SHALL HAVE 4:1 OR FLATTER SLOPE. THE 6.8 FT
 LONG SIDEWALK CONNECTORS BETWEEN 10 FT WIDE SIDEWALK
 AND THE PROPERTY LINE CAN SLOPE UP TO 7.2% (EQUATES TO
 LESS THAN 0.5 FT DROP) WITHOUT NEEDING HANDRAILS.
 DRAINAGE STRUCTURE AND STORM PIPE WILL BE NEEDED AT
 EAST END OF PARALLEL PARKING SPACES TO COLLECT
 STORMWATER RUNOFF AND CONVEY TO EXISTING DRAINAGE
 STRUCTURE.] (PREVIOUS COMMENT- GRADING OF THE AREA
 BETWEEN THE SOUTH PROPERTY LINE AND THE CENTER LINE OF
 DIANA PLACE CAN BE A CONDITION OF SITE PLAN APPROVAL TO
 BE WORKED OUT DURING ENGINEERING PERMIT SUBMITTAL.]
 REVISED COMMENT: THE GRADING BETWEEN THE ROAD
 CENTERLINE AND R/W, AS SHOWN ON SECTIONS H-H THROUGH
 J-J NEEDS FURTHER REFINEMENT. SINCE STEPS ARE BEING
 PROPOSED TO MAKE UP THE VERTICAL DISTANCE BETWEEN THE
 FINISHED FLOORS OF THE HOUSING UNITS AND THE DIANA
 PLACE PARCEL, MAINTAIN NORMAL CROWN FOR DIANA PLACE AND
 SLOPE THE PARKING TOWARD THE PROPOSED CURB LINE. FOR
 SECTION J-J, THE LANDSCAPE AREA SHOULD MEET THE TOP OF
 CURB. FOR SECTION J-J, SLOPE THE SIDEWALK TOWARD THE
 ROAD AND INSTALL A CATCH BASIN IN THE SMALL LANDSCAPE
 AREA AND CONNECT INTO THE CURB INLET ON THE STREET.
 PROVIDE SECTION(S) ON EITHER SIDE OF THE STEPS TO SHOW
 HOW THE AREA BETWEEN THE STEPS WILL SLOPE.
  
 10. [SATISFIED] IT APPEARS THE TOWNHOME AT THE WEST END
 OF THE PROJECT WILL HOLD WATER BEHIND THE DIANA PLACE
 SIDEWALK.
  
 11. [SATISFIED] PROVIDE A CROSS SECTION FROM THE NORTH
 PROPERTY LINE TO THE FACE OF THE BUILDING INCLUDING
 DIMENSIONS TO THE OUTSIDE OF THE UNDERGROUND PARKING
 GARAGE.
  
 12. [SATISFIED - CONDITION OF ENGINEERING PERMIT
 APPROVAL - FOR THE EXFILTRATION TRENCH ALONG THE NORTH
 PROPERTY LINE, THE SFWMD TRENCH EQUATION WILL HAVE TO
 BE MODIFIED TO ACCOUNT FOR THE RETAINING WALL ON ONE
 SIDE AND POSSIBLE GARAGE WALL ON THE OTHER THAT WILL
 LIMIT THE FLOW OUT OF THE TRENCH.]
  
 13. [SATISFIED] EXPLAIN HOW THE EXFILTRATION TRENCH
 ALONG THE NORTH PROPERTY LINE WILL BE MAINTAINED,
 INCLUDING POSSIBLE REPLACEMENT, WHEN IT HAS LOST ITS
 DISPOSAL CAPACITY IN A FEW YEARS.
  
 14. [NOT SATISFIED. CONDITION OF ENGINEERING PERMIT
 APPROVAL - PROVIDE AN EXFILTRATION TRENCH DETAIL,
 LABELING THE TRENCH WIDTH AND THE ELEVATIONS FOR THE
 TOP OF TRENCH, THE BOTTOM OF THE TRENCH, AND THE PIPE
 INVERT.]
  
 15. [NOT SATISFIED. CONDITION OF ENGINEERING PERMIT
 APPROVAL - PROVIDE DETAIL OF CONTROL STRUCTURE(S). NOTE
 BLEEDERS CANNOT BE USED AS PART OF THE CONTROL TO
 SURCHARGE THE EXFILTRATION TRENCH.]
  
 16. [SATISFIED] SHOW MILL AND RESURFACING LIMITS ON
 CURRIE CRESCENT (BECAUSE OF THE TRENCH CUTS AND THE
 CHANGE IN PAVEMENT MARKINGS FOR THE PARKING SPACES).
 PREVIOUS COMMENT: SHOW MILL AND RESURFACING LIMITS FOR
 TRENCH CUTS IN THE ROADWAY PER CITY'S STANDARD DETAIL
 GC-8.
  
 17. [SATISFIED] CONVERT EXISTING DRAINAGE STRUCTURE IN
 THE EXISTING SOUTH DRIVEWAY TO S. FLAGLER DRIVE TO A
 CATCH BASIN WITH A HOODED FRAME AND GRATE. THE
 STRUCTURE MAY NEED TO BE ENLARGED IN ORDER TO CONNECT
 THE PROPOSED 15-INCH RCP FROM THE DEVELOPMENT.
  
 18. [SATISFIED - CONDITION OF ENGINEERING PERMIT
 APPROVAL - DRAINAGE SYSTEM DESIGN TO CONSIDER SEA LEVEL
 RISE.]
  
 19. [SATISFIED - PIPE WAS REMOVED] WHAT IS THE PURPOSE
 OF THE 6-INCH HDPE PIPE BETWEEN THE SIDEWALK AND EAST
 PROPERTY LINE?
  
 20. [SATISFIED. CONDITION OF ENGINEERING PERMIT
 APPROVAL - THE ROOF DRAIN SYSTEM WILL NEED TO BE
 DESIGNED SO THAT MANHOLE LIDS ARE NOT DISPLACED BY THE
 PRESSURE OF THE WATER OR TRAPPED AIR IN THE ROOF
 DOWNSPOUTS.]
  
 21. [SATISFIED] IT APPEARS THE TOWNHOME AT THE WEST END
 OF THE PROJECT WILL HOLD WATER BEHIND THE DIANA PLACE
 SIDEWALK.
  
 22. [SATISFIED - WATER QUALITY TREATMENT PER SFWMD ERP
 SHALL BE DESIGNED AND PROVIDED FOR THE ADDITIONAL
 IMPERVIOUS AREA IN THE DIANA PLACE PARCEL.] NEW COMMENT
 ? FINAL LAYOUT AND DESIGN OF DRAINAGE SYSTEMS ON DIANA
 PLACE TO BE WORKED OUT DURING ENGINEERING PERMIT
 SUBMITTAL.
  
 23. [SATISFIED - DRAINAGE SYSTEM SHOWN ON THE RECENTLY
 SUBMITTED FORTE RESIDENCES PLANS.] SHEET C-500 SHOWS
 PROPOSED STORM PIPE ALONG THE NORTH CURB OF CURRIE
 CRESCENT AND CATCH BASINS NEAR THE EAST END OF THE
 STREET BUT NO INFORMATION IS PROVIDED FOR THESE. THE
 SIDEWALK AND CURB SHOULD BE SHOWN TO BE REPLACED AND
 PROPOSED ASPHALT PAVEMENT IN THE WESTBOUND LANE OF
 CURRIE CRESCENT FOR THE STORM PIPE AND ON S. OLIVE AVE
 FOR THE DRAINAGE MANHOLE. THE CURB RAMP ON THE NE
 CORNER OF S. OLIVE AND CURRIE CRESCENT WILL NEED TO BE
 CONSTRUCTED TO CURRENT ADA CRITERIA.
  
 24. SATISFIED - GRADES MODIFIED] FOR THE NORTH DRIVEWAY
 TO CURRIE CRESCENT, SHEET C-500 SHOWS SPOT GRADES OF
 10.92 AND 10.60+/-ME FOR THE EDGE OF PAVEMENT NEXT TO
 THE DROP CURB/VALLEY GUTTER. CROSS SECTION D-D PROVIDES
 A SPOT GRADE OF 11.07 FOR THE EP NEXT TO THE DROP
 CURB/VALLEY GUTTER.
  
 25. [SATISFIED - SPOT GRADES REMOVED FROM ARCHITECTURAL
 PLANS] SECTION D-D ON SHEET C-500 SHOWS A SPOT GRADE OF
 11.86 AT THE PROPERTY LINE. SHEETS G-201 AND G-203 SHOW
 A SPOT GRADE OF 11FT 3IN AT THE PROPERTY LINE.
  
 26. [SATISFIED - SPOT GRADES REMOVED FROM ARCHITECTURAL
 PLANS] AT THE NORTH DRIVEWAY TO S. FLAGLER DRIVE, SHEET
 C-500 SHOWS THE PROPERTY LINE AT AN ELEVATION LESS THAN
 3.98 FT NAVD. SHEET G-203 SHOWS AN ELEVATION OF 4FT 3IN
 AT THE PROPERTY LINE CROSSING THE DRIVEWAY.
  
 27. [SATISFIED] - GRADES FOR CROSS SECTIONS SHOWN ON
 SHEET C-501 SHALL AGREE WITH THE GRADING PLAN ON SHEET
 C-500.
 A. SECTION B-B SHOWS EP GRADE OF 11.00; GRADING PLAN
 SHOWS SPOT GRADE OF 10.72.
 B. SECTION C-C SHOWS BACK OF GUTTER ELEVATION OF 11.18;
 GRADING PLAN SHOWS EP SPOT GRADE OF 10.72.
 C. SECTION D-D SHOWS SPOT GRADE OF 11.83 AT THE
 PROPERTY LINE/FRONT OF TRENCH DRAIN; GRADING PLAN CALLS
 OUT TRENCH DRAIN RIM ELEVATION OF 12.90.
 D. SECTIONS H-H, I-I AND J-J TO BE MODIFIED PER COMMENT
 NO. 9.
  
 28. CONSIDER MOVING THE CONTROL STRUCTURE OUT OF THE
 SIDEWALK BETWEEN S. OLIVE AVE AND THE RESTAURANT/CAFE.
  
 29. FORTE RESIDENCES DEVELOPMENT WAS INSTRUCTED TO MOVE
 THE 5 FT WIDE SIDEWALK ON THE NORTH SIDE OF CURRIE
 CRESCENT TO THE NORTH R/W LINE. THIS WILL REDUCE THE
 WIDTH OF THE ROAD AND MAY IMPACT THE AUTOTURN ANALYSES
 FOR FLAGLER TOWERS.
  
 30. [SATISFIED] THE FRAME AND COVER OF THE PROPOSED
 SANITARY SEWER MANHOLE WHERE CURRIE CRESCENT TURNS
 NORTH SHALL NOT BE WITHIN THE CURB AND GUTTER. THE RIM
 ELEVATION FOR THIS STRUCTURE (10.43) DOES NOT MATCH THE
 GRADING PLAN (11.07).
  
 NEW COMMENTS:
 31. FORTE RESIDENCES? EOR TO JUSTIFY THE PROPOSED CROSS
 SLOPES OF CURRIE CRESCENT OR FLATTEN THEM TO MEET THE
 FLORIDA GREEN BOOK.
  
 32. TYPE 'C' DETAIL HAS NOTE THAT WEIRS OR PRBS ARE NOT
 TO BE USED IN THIS TYPE OF STRUCTURE. THERE IS A
 PROPOSED TYPE 'C' INLET WITH PRB CALLED OUT IN THE
 NORTH FRONTAGE ALONG S. OLIVE AVE. [CAN BE ADDRESSED
 WITH ENGINEERING PERMIT SUBMITTAL]
  
 33. SHOW SWALE WHERE THE TOP OF CURB ELEVATION IS
 HIGHER THAN THE FRONT OF WALK ELEVATION ALONG DIANA
 PLACE (NEAR WEST END OF THE PARALLEL PARKING SPACES).
 [CAN BE ADDRESSED WITH ENGINEERING PERMIT SUBMITTAL]
  
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  

Review Stop STORM STORMWATER
Rev No 5 Status P Date 09-28-2021 Cont ID  
Sent By tward Date 09-28-2021 Time 17:23 Rev Time 0.00
Received By tward Date 09-28-2021 Time 17:23 Sent To  
Notes
2021-09-28 17:23:40THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 SEPTEMBER 13, 2021 PLAN SUBMITTAL.
  
 1. [CONDITION OF SITE PLAN APPROVAL - COORDINATE THE
 GRADING OF CURRIE CRESCENT WITH THE FORTE RESIDENCES
 DEVELOPMENT.] PROPOSED GRADES AT EAST CURB OF CURRIE
 CRESCENT AT THE INTERFACE BETWEEN THE 9/8/21 FORTE
 RESIDENCES GRADING PLAN AND THE 9/13/21 FLAGLER TOWERS
 GRADING PLAN APPEAR TO MATCH. NOTE COMMENTS ON THE
 9/8/21 FORTE RESIDENCES GRADING PLAN FOR CURRIE
 CRESCENT MAY CHANGE THE PROPOSED GRADES OF CURRIE
 CRESCENT. (PREVIOUS COMMENT: COORDINATE THE GRADING OF
 CURRIE CRESCENT WITH THE FLAGLER FORTE DEVELOPMENT).
  
 2. [CONDITION OF SITE PLAN APPROVAL - CURRIE CRESCENT
 CURB AND GUTTER TO HAVE POSITIVE DRAINAGE TO THE STREET
 DRAINAGE SYSTEM.] FLAGLER TOWERS GRADING PLAN SHOWS A
 SPOT GRADE OF 11.07 AT THE PROPOSED SANITARY SEWER
 MANHOLE. THIS GRADE WILL CAUSE WATER TO POND IN THE
 DRIVEWAY GUTTER TO THE NORTH (WHICH HAS SPOT GRADES OF
 10.93 ON THE SOUTH SIDE AND 11.18 ME ON THE NORTH SIDE
 OF THE DRIVEWAY APRON.
  
 3. [CONDITION OF SITE PLAN APPROVAL - MAINTAIN CROWN
 CROSS SECTION OF CURRIE CRESCENT.]
  
 4. [SATISFIED] REQUESTED DIMENSIONS WERE ONLY PROVIDE
 FOR SECTIONS B-B, C-C, D-D, H-H, AND J-J. PREVIOUS
 COMMENT: FOR THE CROSS SECTIONS ON SHEET C-501, PROVIDE
 DIMENSIONS FROM PROPERTY LINE/RIGHT OF WAY LINE TO
 VALLEY GUTTER OR BACK OF SIDEWALK.
  
 5. [NOT SATISFIED] [CONDITION OF SITE PLAN APPROVAL -
 SIDEWALK ACROSS WEST DRIVEWAY TO CURRIE CRESCENT SHALL
 SLOPE TOWARD THE STREET. THE HIGH POINT OF THE DRIVEWAY
 SHALL BE SUFFICIENT TO PREVENT STORMWATER RUNOFF FROM
 THE RIGHT OF WAY FROM FLOWING DOWN THE DRIVEWAY TOWARD
 THE BUILDING AND AT THE SAME TIME MINIMIZE THE AREA OF
 THE DRIVEWAY SLOPING TOWARD THE ROAD (I.E. MAXIMIZE THE
 DRIVEWAY SLOPE BETWEEN THE HIGH POINT AND THE BACK OF
 THE SIDEWALK.)] SUGGEST SLOPING THE SIDEWALK PORTION OF
 THE DRIVEWAY SHOWN IN SECTION B-B TOWARD THE VALLEY
 GUTTER. THE GRADES SHOWN ON SHEET C-500 FOR THE
 DRIVEWAY WITH SECTION B-B (10.72 AT EP AND 10.70/10.84
 AT BOW ACROSS DRIVEWAY) DO NOT MATCH THE GRADES SHOWN
 ON SECTION B-B ON SHEET C-501 (11.00 AT EP AND 11.04 AT
 BACK OF CROSSWALK [HIGH POINT OF DRIVEWAY]). SECTION
 B-B SHOWS LESS THAN 1/2 INCH DROP (0.04 FT) BETWEEN
 BACK OF WALK AND EP. THIS SHORT RISE WILL NOT STOP MUCH
 ROADWAY STORMWATER RUNOFF FROM FLOWING DOWN THE
 DRIVEWAY. THE GRADING PLAN DOESN?T APPEAR TO SUPPORT
 ALL OF THE CROSSWALK/SIDEWALK SLOPING TOWARD THE ROAD.
  
 6. [SATISFIED - SLOPES REMOVED FROM SHEET G-203.]
 PREVIOUS COMMENT: SECTION D-D SHOWS 13.5% SLOPE EAST OF
 THE PROPERTY LINE. SHEET G-203 SHOWS 7.5% RAMP UP.
 PREVIOUS COMMENT: COORDINATE THE SLOPES SHOWN FOR THE
 DRIVEWAYS WITH THE ARCHITECTURAL PLANS. FOR EXAMPLE,
 SECTION C-C SHOWS 3.4% SLOPE BETWEEN THE BUILDING AND
 VALLEY GUTTER. SHEET A-101 SHOWS THE DRIVEWAY AT 7.5%
 SLOPE.
  
 7. {SATISFIED] SECTION D-D: PROVIDE SIDEWALK AREA WITH
 SLOPE NO STEEPER THAN 2%.
  
 8. [SATISFIED] SECTION E-E: CORRECT LABELS FOR ROAD
 CENTERLINE AND PROPERTY LINE.
  
 9. [PARTIALLY SATISFIED] [CONDITION OF SITE PLAN
 APPROVAL - PARALLEL PARKING SPACES ON DIANA PLACE SHALL
 SLOPE TO THE PROPOSED NORTH TYPE 'D' CURB AT MINIMUM 2%
 CROSS SLOPE. LANDSCAPE AREA BETWEEN BACK CURB AND 10 FT
 SIDEWALK SHALL HAVE 4:1 OR FLATTER SLOPE. THE 6.8 FT
 LONG SIDEWALK CONNECTORS BETWEEN 10 FT WIDE SIDEWALK
 AND THE PROPERTY LINE CAN SLOPE UP TO 7.2% (EQUATES TO
 LESS THAN 0.5 FT DROP) WITHOUT NEEDING HANDRAILS.
 DRAINAGE STRUCTURE AND STORM PIPE WILL BE NEEDED AT
 EAST END OF PARALLEL PARKING SPACES TO COLLECT
 STORMWATER RUNOFF AND CONVEY TO EXISTING DRAINAGE
 STRUCTURE.] (PREVIOUS COMMENT- GRADING OF THE AREA
 BETWEEN THE SOUTH PROPERTY LINE AND THE CENTER LINE OF
 DIANA PLACE CAN BE A CONDITION OF SITE PLAN APPROVAL TO
 BE WORKED OUT DURING ENGINEERING PERMIT SUBMITTAL.]
 REVISED COMMENT: THE GRADING BETWEEN THE ROAD
 CENTERLINE AND R/W, AS SHOWN ON SECTIONS H-H THROUGH
 J-J NEEDS FURTHER REFINEMENT. SINCE STEPS ARE BEING
 PROPOSED TO MAKE UP THE VERTICAL DISTANCE BETWEEN THE
 FINISHED FLOORS OF THE HOUSING UNITS AND THE DIANA
 PLACE PARCEL, MAINTAIN NORMAL CROWN FOR DIANA PLACE AND
 SLOPE THE PARKING TOWARD THE PROPOSED CURB LINE. FOR
 SECTION J-J, THE LANDSCAPE AREA SHOULD MEET THE TOP OF
 CURB. FOR SECTION J-J, SLOPE THE SIDEWALK TOWARD THE
 ROAD AND INSTALL A CATCH BASIN IN THE SMALL LANDSCAPE
 AREA AND CONNECT INTO THE CURB INLET ON THE STREET.
 PROVIDE SECTION(S) ON EITHER SIDE OF THE STEPS TO SHOW
 HOW THE AREA BETWEEN THE STEPS WILL SLOPE.
  
 10. [SATISFIED] IT APPEARS THE TOWNHOME AT THE WEST END
 OF THE PROJECT WILL HOLD WATER BEHIND THE DIANA PLACE
 SIDEWALK.
  
 11. [SATISFIED] PROVIDE A CROSS SECTION FROM THE NORTH
 PROPERTY LINE TO THE FACE OF THE BUILDING INCLUDING
 DIMENSIONS TO THE OUTSIDE OF THE UNDERGROUND PARKING
 GARAGE.
  
 12. [SATISFIED - CONDITION OF ENGINEERING PERMIT
 APPROVAL - FOR THE EXFILTRATION TRENCH ALONG THE NORTH
 PROPERTY LINE, THE SFWMD TRENCH EQUATION WILL HAVE TO
 BE MODIFIED TO ACCOUNT FOR THE RETAINING WALL ON ONE
 SIDE AND POSSIBLE GARAGE WALL ON THE OTHER THAT WILL
 LIMIT THE FLOW OUT OF THE TRENCH.]
  
 13. [SATISFIED] EXPLAIN HOW THE EXFILTRATION TRENCH
 ALONG THE NORTH PROPERTY LINE WILL BE MAINTAINED,
 INCLUDING POSSIBLE REPLACEMENT, WHEN IT HAS LOST ITS
 DISPOSAL CAPACITY IN A FEW YEARS.
  
 14. [NOT SATISFIED. CONDITION OF ENGINEERING PERMIT
 APPROVAL - PROVIDE AN EXFILTRATION TRENCH DETAIL,
 LABELING THE TRENCH WIDTH AND THE ELEVATIONS FOR THE
 TOP OF TRENCH, THE BOTTOM OF THE TRENCH, AND THE PIPE
 INVERT.]
  
 15. [NOT SATISFIED. CONDITION OF ENGINEERING PERMIT
 APPROVAL - PROVIDE DETAIL OF CONTROL STRUCTURE(S). NOTE
 BLEEDERS CANNOT BE USED AS PART OF THE CONTROL TO
 SURCHARGE THE EXFILTRATION TRENCH.]
  
 16. [SATISFIED] SHOW MILL AND RESURFACING LIMITS ON
 CURRIE CRESCENT (BECAUSE OF THE TRENCH CUTS AND THE
 CHANGE IN PAVEMENT MARKINGS FOR THE PARKING SPACES).
 PREVIOUS COMMENT: SHOW MILL AND RESURFACING LIMITS FOR
 TRENCH CUTS IN THE ROADWAY PER CITY'S STANDARD DETAIL
 GC-8.
  
 17. [SATISFIED] CONVERT EXISTING DRAINAGE STRUCTURE IN
 THE EXISTING SOUTH DRIVEWAY TO S. FLAGLER DRIVE TO A
 CATCH BASIN WITH A HOODED FRAME AND GRATE. THE
 STRUCTURE MAY NEED TO BE ENLARGED IN ORDER TO CONNECT
 THE PROPOSED 15-INCH RCP FROM THE DEVELOPMENT.
  
 18. [SATISFIED - CONDITION OF ENGINEERING PERMIT
 APPROVAL - DRAINAGE SYSTEM DESIGN TO CONSIDER SEA LEVEL
 RISE.]
  
 19. [SATISFIED - PIPE WAS REMOVED] WHAT IS THE PURPOSE
 OF THE 6-INCH HDPE PIPE BETWEEN THE SIDEWALK AND EAST
 PROPERTY LINE?
  
 20. [SATISFIED. CONDITION OF ENGINEERING PERMIT
 APPROVAL - THE ROOF DRAIN SYSTEM WILL NEED TO BE
 DESIGNED SO THAT MANHOLE LIDS ARE NOT DISPLACED BY THE
 PRESSURE OF THE WATER OR TRAPPED AIR IN THE ROOF
 DOWNSPOUTS.]
  
 21. [SATISFIED] IT APPEARS THE TOWNHOME AT THE WEST END
 OF THE PROJECT WILL HOLD WATER BEHIND THE DIANA PLACE
 SIDEWALK.
  
 22. [CONDITION OF SITE PLAN APPROVAL - WATER QUALITY
 TREATMENT PER SFWMD ERP SHALL BE DESIGNED AND PROVIDED
 FOR THE ADDITIONAL IMPERVIOUS AREA IN THE DIANA PLACE
 PARCEL.] WHAT DRAINAGE MITIGATION (WATER QUALITY AND
 PEAK FLOW ATTENUATION) IS PROPOSED FOR THE ADDITIONAL
 IMPERVIOUS AREA IN THE DIANA PLACE PARCEL.
  
 23. [SATISFIED - DRAINAGE SYSTEM SHOWN ON THE RECENTLY
 SUBMITTED FORTE RESIDENCES PLANS.] SHEET C-500 SHOWS
 PROPOSED STORM PIPE ALONG THE NORTH CURB OF CURRIE
 CRESCENT AND CATCH BASINS NEAR THE EAST END OF THE
 STREET BUT NO INFORMATION IS PROVIDED FOR THESE. THE
 SIDEWALK AND CURB SHOULD BE SHOWN TO BE REPLACED AND
 PROPOSED ASPHALT PAVEMENT IN THE WESTBOUND LANE OF
 CURRIE CRESCENT FOR THE STORM PIPE AND ON S. OLIVE AVE
 FOR THE DRAINAGE MANHOLE. THE CURB RAMP ON THE NE
 CORNER OF S. OLIVE AND CURRIE CRESCENT WILL NEED TO BE
 CONSTRUCTED TO CURRENT ADA CRITERIA.
  
 24. SATISFIED - GRADES MODIFIED] FOR THE NORTH DRIVEWAY
 TO CURRIE CRESCENT, SHEET C-500 SHOWS SPOT GRADES OF
 10.92 AND 10.60+/-ME FOR THE EDGE OF PAVEMENT NEXT TO
 THE DROP CURB/VALLEY GUTTER. CROSS SECTION D-D PROVIDES
 A SPOT GRADE OF 11.07 FOR THE EP NEXT TO THE DROP
 CURB/VALLEY GUTTER.
  
 25. [SATISFIED - SPOT GRADES REMOVED FROM ARCHITECTURAL
 PLANS] SECTION D-D ON SHEET C-500 SHOWS A SPOT GRADE OF
 11.86 AT THE PROPERTY LINE. SHEETS G-201 AND G-203 SHOW
 A SPOT GRADE OF 11FT 3IN AT THE PROPERTY LINE.
  
 26. [SATISFIED - SPOT GRADES REMOVED FROM ARCHITECTURAL
 PLANS] AT THE NORTH DRIVEWAY TO S. FLAGLER DRIVE, SHEET
 C-500 SHOWS THE PROPERTY LINE AT AN ELEVATION LESS THAN
 3.98 FT NAVD. SHEET G-203 SHOWS AN ELEVATION OF 4FT 3IN
 AT THE PROPERTY LINE CROSSING THE DRIVEWAY.
  
 NEW COMMENTS:
 27. [CONDITION OF SITE PLAN APPROVAL - GRADES FOR CROSS
 SECTIONS SHOWN ON SHEET C-501 SHALL AGREE WITH THE
 GRADING PLAN ON SHEET C-500.]
 A. SECTION B-B SHOWS EP GRADE OF 11.00; GRADING PLAN
 SHOWS SPOT GRADE OF 10.72.
 B. SECTION C-C SHOWS BACK OF GUTTER ELEVATION OF 11.18;
 GRADING PLAN SHOWS EP SPOT GRADE OF 10.72.
 C. SECTION D-D SHOWS SPOT GRADE OF 11.83 AT THE
 PROPERTY LINE/FRONT OF TRENCH DRAIN; GRADING PLAN CALLS
 OUT TRENCH DRAIN RIM ELEVATION OF 12.90.
 D. SECTIONS H-H, I-I AND J-J TO BE MODIFIED PER COMMENT
 NO. 9.
  
 28. CONSIDER MOVING THE CONTROL STRUCTURE OUT OF THE
 SIDEWALK BETWEEN S. OLIVE AVE AND THE RESTAURANT/CAFE.
  
 29. FORTE RESIDENCES DEVELOPMENT WAS INSTRUCTED TO MOVE
 THE 5 FT WIDE SIDEWALK ON THE NORTH SIDE OF CURRIE
 CRESCENT TO THE NORTH R/W LINE. THIS WILL REDUCE THE
 WIDTH OF THE ROAD AND MAY IMPACT THE AUTOTURN ANALYSES
 FOR FLAGLER TOWERS.
  
 30. THE FRAME AND COVER OF THE PROPOSED SANITARY SEWER
 MANHOLE WHERE CURRIE CRESCENT TURNS NORTH SHALL NOT BE
 WITHIN THE CURB AND GUTTER. THE RIM ELEVATION FOR THIS
 STRUCTURE (10.43) DOES NOT MATCH THE GRADING PLAN
 (11.07).
  
  
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  

Review Stop STORM STORMWATER
Rev No 4 Status F Date 09-01-2021 Cont ID  
Sent By tward Date 09-01-2021 Time 15:14 Rev Time 0.00
Received By tward Date 09-01-2021 Time 15:15 Sent To  
Notes
2021-09-01 15:15:04THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 AUGUST 25, 2021 PLAN SUBMITTAL.
  
 1. [CONDITION OF SITE PLAN APPROVAL] THERE IS 0.42 FT
 DIFFERENCE IN GRADES OF EP SHOWN ON THE FLAGLER FORTE
 (11.02' NAVD) AND ON THE FLAGLER TOWER (10.60' NAVD +/-
 ME) PLANS. (PREVIOUS COMMENT: COORDINATE THE GRADING OF
 CURRIE CRESCENT WITH THE FLAGLER FORTE DEVELOPMENT.
  
 2. [CONDITION OF SITE PLAN APPROVAL] CURRIE CRESCENT
 CURB AND GUTTER TO HAVE POSITIVE DRAINAGE TO THE STREET
 DRAINAGE SYSTEM.
  
 3. [CONDITION OF SITE PLAN APPROVAL] MAINTAIN CROWN
 CROSS SECTION OF CURRIE CRESCENT.
  
 4. [SATISFIED] REQUESTED DIMENSIONS WERE ONLY PROVIDE
 FOR SECTIONS B-B, C-C, D-D, H-H, AND J-J. PREVIOUS
 COMMENT: FOR THE CROSS SECTIONS ON SHEET C-501, PROVIDE
 DIMENSIONS FROM PROPERTY LINE/RIGHT OF WAY LINE TO
 VALLEY GUTTER OR BACK OF SIDEWALK.
  
 5. [SATISFIED] SUGGEST SLOPING THE SIDEWALK PORTION OF
 THE DRIVEWAY SHOWN IN SECTION B-B TOWARD THE VALLEY
 GUTTER.
  
 6. [NOT SATISFIED] PREVIOUS COMMENT: SECTION D-D SHOWS
 13.5% SLOPE EAST OF THE PROPERTY LINE. SHEET G-203
 SHOWS 7.5% RAMP UP. PREVIOUS COMMENT: COORDINATE THE
 SLOPES SHOWN FOR THE DRIVEWAYS WITH THE ARCHITECTURAL
 PLANS. FOR EXAMPLE, SECTION C-C SHOWS 3.4% SLOPE
 BETWEEN THE BUILDING AND VALLEY GUTTER. SHEET A-101
 SHOWS THE DRIVEWAY AT 7.5% SLOPE.
  
 7. {SATISFIED] SECTION D-D: PROVIDE SIDEWALK AREA WITH
 SLOPE NO STEEPER THAN 2%.
  
 8. [SATISFIED] SECTION E-E: CORRECT LABELS FOR ROAD
 CENTERLINE AND PROPERTY LINE.
  
 9. [PARTIALLY SATISFIED - GRADING OF THE AREA BETWEEN
 THE SOUTH PROPERTY LINE AND THE CENTER LINE OF DIANA
 PLACE CAN BE A CONDITION OF SITE PLAN APPROVAL TO BE
 WORKED OUT DURING ENGINEERING PERMIT SUBMITTAL.]
 REVISED COMMENT: THE GRADING BETWEEN THE ROAD
 CENTERLINE AND R/W, AS SHOWN ON SECTIONS H-H THROUGH
 J-J NEEDS FURTHER REFINEMENT. SINCE STEPS ARE BEING
 PROPOSED TO MAKE UP THE VERTICAL DISTANCE BETWEEN THE
 FINISHED FLOORS OF THE HOUSING UNITS AND THE DIANA
 PLACE PARCEL, MAINTAIN NORMAL CROWN FOR DIANA PLACE AND
 SLOPE THE PARKING TOWARD THE PROPOSED CURB LINE. FOR
 SECTION J-J, THE LANDSCAPE AREA SHOULD MEET THE TOP OF
 CURB. FOR SECTION J-J, SLOPE THE SIDEWALK TOWARD THE
 ROAD AND INSTALL A CATCH BASIN IN THE SMALL LANDSCAPE
 AREA AND CONNECT INTO THE CURB INLET ON THE STREET.
 PROVIDE SECTION(S) ON EITHER SIDE OF THE STEPS TO SHOW
 HOW THE AREA BETWEEN THE STEPS WILL SLOPE.
  
 10. [SATISFIED] IT APPEARS THE TOWNHOME AT THE WEST END
 OF THE PROJECT WILL HOLD WATER BEHIND THE DIANA PLACE
 SIDEWALK.
  
 11. [SATISFIED] PROVIDE A CROSS SECTION FROM THE NORTH
 PROPERTY LINE TO THE FACE OF THE BUILDING INCLUDING
 DIMENSIONS TO THE OUTSIDE OF THE UNDERGROUND PARKING
 GARAGE.
  
 12. [SATISFIED - TO BE WORKED OUT AT ENGINEERING PERMIT
 SUBMITTAL] FOR THE EXFILTRATION TRENCH ALONG THE NORTH
 PROPERTY LINE, THE SFWMD TRENCH EQUATION WILL HAVE TO
 BE MODIFIED TO ACCOUNT FOR THE RETAINING WALL ON ONE
 SIDE AND POSSIBLE GARAGE WALL ON THE OTHER THAT WILL
 LIMIT THE FLOW OUT OF THE TRENCH.
  
 13. [SATISFIED] EXPLAIN HOW THE EXFILTRATION TRENCH
 ALONG THE NORTH PROPERTY LINE WILL BE MAINTAINED,
 INCLUDING POSSIBLE REPLACEMENT, WHEN IT HAS LOST ITS
 DISPOSAL CAPACITY IN A FEW YEARS.
  
 14. [NOT SATISFIED. INFORMATION CAN BE PROVIDED WITH
 ENGINEERING PERMIT SUBMITTAL] PROVIDE AN EXFILTRATION
 TRENCH DETAIL, LABELING THE TRENCH WIDTH AND THE
 ELEVATIONS FOR THE TOP OF TRENCH, THE BOTTOM OF THE
 TRENCH, AND THE PIPE INVERT.
  
 15. [NOT SATISFIED. INFORMATION CAN BE PROVIDED WITH
 ENGINEERING PERMIT SUBMITTAL] PROVIDE DETAIL OF CONTROL
 STRUCTURE(S). NOTE BLEEDERS CANNOT BE USED AS PART OF
 THE CONTROL TO SURCHARGE THE EXFILTRATION TRENCH.
  
 16. [PARTIALLY SATISFIED] SHOW MILL AND RESURFACING
 LIMITS ON CURRIE CRESCENT (BECAUSE OF THE TRENCH CUTS
 AND THE CHANGE IN PAVEMENT MARKINGS FOR THE PARKING
 SPACES). PREVIOUS COMMENT: SHOW MILL AND RESURFACING
 LIMITS FOR TRENCH CUTS IN THE ROADWAY PER CITY'S
 STANDARD DETAIL GC-8.
  
 17. [SATISFIED] CONVERT EXISTING DRAINAGE STRUCTURE IN
 THE EXISTING SOUTH DRIVEWAY TO S. FLAGLER DRIVE TO A
 CATCH BASIN WITH A HOODED FRAME AND GRATE. THE
 STRUCTURE MAY NEED TO BE ENLARGED IN ORDER TO CONNECT
 THE PROPOSED 15-INCH RCP FROM THE DEVELOPMENT.
  
 18. [SATISFIED - TO BE WORKED OUT AT ENGINEERING PERMIT
 SUBMITTAL] DRAINAGE SYSTEM DESIGN TO CONSIDER SEA LEVEL
 RISE.
  
 19. [SATISFIED - PIPE WAS REMOVED] WHAT IS THE PURPOSE
 OF THE 6-INCH HDPE PIPE BETWEEN THE SIDEWALK AND EAST
 PROPERTY LINE?
  
 20. [SATISFIED - TO BE ADDRESSED DURING FINAL
 ENGINEERING DESIGN] THE ROOF DRAIN SYSTEM WILL NEED TO
 BE DESIGNED SO THAT MANHOLE LIDS ARE NOT DISPLACED BY
 THE PRESSURE OF THE WATER OR TRAPPED AIR IN THE ROOF
 DOWNSPOUTS.
  
 21. [SATISFIED] IT APPEARS THE TOWNHOME AT THE WEST END
 OF THE PROJECT WILL HOLD WATER BEHIND THE DIANA PLACE
 SIDEWALK.
  
 22. [CONDITION OF SITE PLAN APPROVAL] WHAT DRAINAGE
 MITIGATION (WATER QUALITY AND PEAK FLOW ATTENUATION) IS
 PROPOSED FOR THE ADDITIONAL IMPERVIOUS AREA IN THE
 DIANA PLACE PARCEL.
  
 NEW COMMENTS:
 23. SHEET C-500 SHOWS PROPOSED STORM PIPE ALONG THE
 NORTH CURB OF CURRIE CRESCENT AND CATCH BASINS NEAR THE
 EAST END OF THE STREET BUT NO INFORMATION IS PROVIDED
 FOR THESE. THE SIDEWALK AND CURB SHOULD BE SHOWN TO BE
 REPLACED AND PROPOSED ASPHALT PAVEMENT IN THE WESTBOUND
 LANE OF CURRIE CRESCENT FOR THE STORM PIPE AND ON S.
 OLIVE AVE FOR THE DRAINAGE MANHOLE. THE CURB RAMP ON
 THE NE CORNER OF S. OLIVE AND CURRIE CRESCENT WILL NEED
 TO BE CONSTRUCTED TO CURRENT ADA CRITERIA.
  
 24. FOR THE NORTH DRIVEWAY TO CURRIE CRESCENT, SHEET
 C-500 SHOWS SPOT GRADES OF 10.92 AND 10.60+/-ME FOR THE
 EDGE OF PAVEMENT NEXT TO THE DROP CURB/VALLEY GUTTER.
 CROSS SECTION D-D PROVIDES A SPOT GRADE OF 11.07 FOR
 THE EP NEXT TO THE DROP CURB/VALLEY GUTTER.
  
 25. SECTION D-D ON SHEET C-500 SHOWS A SPOT GRADE OF
 11.86 AT THE PROPERTY LINE. SHEETS G-201 AND G-203 SHOW
 A SPOT GRADE OF 11FT 3IN AT THE PROPERTY LINE.
  
 26. AT THE NORTH DRIVEWAY TO S. FLAGLER DRIVE, SHEET
 C-500 SHOWS THE PROPERTY LINE AT AN ELEVATION LESS THAN
 3.98 FT NAVD. SHEET G-203 SHOWS AN ELEVATION OF 4FT 3IN
 AT THE PROPERTY LINE CROSSING THE DRIVEWAY.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  

Review Stop STORM STORMWATER
Rev No 3 Status F Date 08-19-2021 Cont ID  
Sent By tward Date 08-19-2021 Time 13:36 Rev Time 0.00
Received By tward Date 08-19-2021 Time 13:37 Sent To  
Notes
2021-08-19 13:37:20THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 AUGUST 5, 2021 PLAN SUBMITTAL.
  
 1. [CONDITION OF SITE PLAN APPROVAL] COORDINATE THE
 GRADING OF CURRIE CRESCENT WITH THE FLAGLER FORTE
 DEVELOPMENT.
  
 2. [CONDITION OF SITE PLAN APPROVAL] CURRIE CRESCENT
 CURB AND GUTTER TO HAVE POSITIVE DRAINAGE TO THE STREET
 DRAINAGE SYSTEM.
  
 3. [CONDITION OF SITE PLAN APPROVAL] MAINTAIN CROWN
 CROSS SECTION OF CURRIE CRESCENT.
  
 4. [PARTIALLY SATISFIED] REQUESTED DIMENSIONS WERE ONLY
 PROVIDE FOR SECTIONS B-B, C-C, D-D, H-H, AND J-J.
 PREVIOUS COMMENT: FOR THE CROSS SECTIONS ON SHEET
 C-501, PROVIDE DIMENSIONS FROM PROPERTY LINE/RIGHT OF
 WAY LINE TO VALLEY GUTTER OR BACK OF SIDEWALK.
  
 5. [SATISFIED] SUGGEST SLOPING THE SIDEWALK PORTION OF
 THE DRIVEWAY SHOWN IN SECTION B-B TOWARD THE VALLEY
 GUTTER.
  
 6. [NOT SATISFIED] SECTION D-D SHOWS 10% SLOPE EAST OF
 THE PROPERTY LINE. SHEET A-101 SHOWS 7.5% RAMP UP.
 PREVIOUS COMMENT: COORDINATE THE SLOPES SHOWN FOR THE
 DRIVEWAYS WITH THE ARCHITECTURAL PLANS. FOR EXAMPLE,
 SECTION C-C SHOWS 3.4% SLOPE BETWEEN THE BUILDING AND
 VALLEY GUTTER. SHEET A-101 SHOWS THE DRIVEWAY AT 7.5%
 SLOPE.
  
 7. {SATISFIED] SECTION D-D: PROVIDE SIDEWALK AREA WITH
 SLOPE NO STEEPER THAN 2%.
  
 8. [SATISFIED] SECTION E-E: CORRECT LABELS FOR ROAD
 CENTERLINE AND PROPERTY LINE.
  
 9. [PARTIALLY SATISFIED ? GRADING OF THE AREA BETWEEN
 THE SOUTH PROPERTY LINE AND THE CENTER LINE OF DIANA
 PLACE CAN BE A CONDITION OF SITE PLAN APPROVAL TO BE
 WORKED OUT DURING ENGINEERING PERMIT SUBMITTAL.] THE
 GRADING BETWEEN THE ROAD CENTERLINE AND R/W, AS SHOWN
 ON SECTIONS H-H THROUGH K-K NEEDS FURTHER REFINEMENT.
 THE ROAD AND PARKING CROSS SLOPES NEED TO MEET THE
 CITY?S DESIGN CRITERIA AND BE ACCEPTABLE TO THE CITY
 TRANSPORTATION ENGINEER. THE LANDSCAPE SLOPES STEEPER
 THAN 4:1 ARE DIFFICULT TO MAINTAIN. FOR SECTION J-J,
 THE LANDSCAPE AREA SHOULD MEET THE TOP OF CURB. FOR
 SECTION K-K, THE ARROW FOR THE 0.1% LANDSCAPE SLOPE IS
 POINTING IN THE WRONG DIRECTION. PREVIOUS COMMENT:
 SECTION G-G, CONSIDER LOWERING THE COURTYARD AREA
 WITHIN THE PROPERTY IN ORDER TO FLATTEN THE SLOPE
 BETWEEN THE 10 FT WIDE SIDEWALK AND THE BACK OF CURB OF
 DIANA PLACE.
  
 10. [SATISFIED] IT APPEARS THE TOWNHOME AT THE WEST END
 OF THE PROJECT WILL HOLD WATER BEHIND THE DIANA PLACE
 SIDEWALK.
  
 11. [SATISFIED] PROVIDE A CROSS SECTION FROM THE NORTH
 PROPERTY LINE TO THE FACE OF THE BUILDING INCLUDING
 DIMENSIONS TO THE OUTSIDE OF THE UNDERGROUND PARKING
 GARAGE.
  
 12. [SATISFIED - TO BE WORKED OUT AT ENGINEERING PERMIT
 SUBMITTAL] FOR THE EXFILTRATION TRENCH ALONG THE NORTH
 PROPERTY LINE, THE SFWMD TRENCH EQUATION WILL HAVE TO
 BE MODIFIED TO ACCOUNT FOR THE RETAINING WALL ON ONE
 SIDE AND POSSIBLE GARAGE WALL ON THE OTHER THAT WILL
 LIMIT THE FLOW OUT OF THE TRENCH.
  
 13. [SATISFIED] EXPLAIN HOW THE EXFILTRATION TRENCH
 ALONG THE NORTH PROPERTY LINE WILL BE MAINTAINED,
 INCLUDING POSSIBLE REPLACEMENT, WHEN IT HAS LOST ITS
 DISPOSAL CAPACITY IN A FEW YEARS.
  
 14. [NOT SATISFIED. INFORMATION CAN BE PROVIDED WITH
 ENGINEERING PERMIT SUBMITTAL] PROVIDE AN EXFILTRATION
 TRENCH DETAIL, LABELING THE TRENCH WIDTH AND THE
 ELEVATIONS FOR THE TOP OF TRENCH, THE BOTTOM OF THE
 TRENCH, AND THE PIPE INVERT.
  
 15. [NOT SATISFIED. INFORMATION CAN BE PROVIDED WITH
 ENGINEERING PERMIT SUBMITTAL] PROVIDE DETAIL OF CONTROL
 STRUCTURE(S). NOTE BLEEDERS CANNOT BE USED AS PART OF
 THE CONTROL TO SURCHARGE THE EXFILTRATION TRENCH.
  
 16. [PARTIALLY SATISFIED] SHOW MILL AND RESURFACING
 LIMITS ON CURRIE CRESCENT (BECAUSE OF THE TRENCH CUTS
 AND THE CHANGE IN PAVEMENT MARKINGS FOR THE PARKING
 SPACES). PREVIOUS COMMENT: SHOW MILL AND RESURFACING
 LIMITS FOR TRENCH CUTS IN THE ROADWAY PER CITY'S
 STANDARD DETAIL GC-8.
  
 17. [SATISFIED] CONVERT EXISTING DRAINAGE STRUCTURE IN
 THE EXISTING SOUTH DRIVEWAY TO S. FLAGLER DRIVE TO A
 CATCH BASIN WITH A HOODED FRAME AND GRATE. THE
 STRUCTURE MAY NEED TO BE ENLARGED IN ORDER TO CONNECT
 THE PROPOSED 15-INCH RCP FROM THE DEVELOPMENT.
  
 18. [SATISFIED ? TO BE WORKED OUT AT ENGINEERING PERMIT
 SUBMITTAL] DRAINAGE SYSTEM DESIGN TO CONSIDER SEA LEVEL
 RISE.
  
 19. [SATISFIED ? PIPE WAS REMOVED] WHAT IS THE PURPOSE
 OF THE 6-INCH HDPE PIPE BETWEEN THE SIDEWALK AND EAST
 PROPERTY LINE?
  
 20. [SATISFIED ? TO BE ADDRESSED DURING FINAL
 ENGINEERING DESIGN] THE ROOF DRAIN SYSTEM WILL NEED TO
 BE DESIGNED SO THAT MANHOLE LIDS ARE NOT DISPLACED BY
 THE PRESSURE OF THE WATER OR TRAPPED AIR IN THE ROOF
 DOWNSPOUTS.
  
 21. [SATISFIED] IT APPEARS THE TOWNHOME AT THE WEST END
 OF THE PROJECT WILL HOLD WATER BEHIND THE DIANA PLACE
 SIDEWALK.
  
 22. [CONDITION OF SITE PLAN APPROVAL] WHAT DRAINAGE
 MITIGATION (WATER QUALITY AND PEAK FLOW ATTENUATION) IS
 PROPOSED FOR THE ADDITIONAL IMPERVIOUS AREA IN THE
 DIANA PLACE PARCEL.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  

Review Stop STORM STORMWATER
Rev No 2 Status F Date 07-27-2021 Cont ID  
Sent By tward Date 07-27-2021 Time 16:44 Rev Time 0.00
Received By tward Date 07-27-2021 Time 16:49 Sent To  
Notes
2021-07-27 16:45:52THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE JUNE
 30 SUBMITTAL.
  
 1. COORDINATE THE GRADING OF CURRIE CRESCENT WITH THE
 FLAGLER FORTE DEVELOPMENT.
  
 2. CURRIE CRESCENT CURB AND GUTTER TO HAVE POSITIVE
 DRAINAGE TO THE STREET DRAINAGE SYSTEM.
  
 3. MAINTAIN CROWN CROSS SECTION OF CURRIE CRESCENT.
  
 4. FOR THE CROSS SECTIONS ON SHEET C-501, PROVIDE
 DIMENSIONS FROM PROPERTY LINE/RIGHT OF WAY LINE TO
 VALLEY GUTTER OR BACK OF SIDEWALK.
  
 5. SUGGEST SLOPING THE SIDEWALK PORTION OF THE DRIVEWAY
 SHOWN IN SECTION B-B TOWARD THE VALLEY GUTTER.
  
 6. COORDINATE THE SLOPES SHOWN FOR THE DRIVEWAYS WITH
 THE ARCHITECTURAL PLANS. FOR EXAMPLE, SECTION C-C SHOWS
 3.4% SLOPE BETWEEN THE BUILDING AND VALLEY GUTTER.
 SHEET A-101 SHOWS THE DRIVEWAY AT 7.5% SLOPE.
  
 7. SECTION D-D: PROVIDE SIDEWALK AREA WITH SLOPE NO
 STEEPER THAN 2%.
  
 8. SECTION E-E: CORRECT LABELS FOR ROAD CENTERLINE AND
 PROPERTY LINE.
  
 9. SECTION G-G, CONSIDER LOWERING THE COURTYARD AREA
 WITHIN THE PROPERTY IN ORDER TO FLATTEN THE SLOPE
 BETWEEN THE 10 FT WIDE SIDEWALK AND THE BACK OF CURB OF
 DIANA PLACE.
  
 10. IT APPEARS THE TOWNHOME AT THE WEST END OF THE
 PROJECT WILL HOLD WATER BEHIND THE DIANA PLACE
 SIDEWALK.
  
 11. PROVIDE A CROSS SECTION FROM THE NORTH PROPERTY
 LINE TO THE FACE OF THE BUILDING INCLUDING DIMENSIONS
 TO THE OUTSIDE OF THE UNDERGROUND PARKING GARAGE.
  
 12. FOR THE EXFILTRATION TRENCH ALONG THE NORTH
 PROPERTY LINE, THE SFWMD TRENCH EQUATION WILL HAVE TO
 BE MODIFIED TO ACCOUNT FOR THE RETAINING WALL ON ONE
 SIDE AND POSSIBLE GARAGE WALL ON THE OTHER THAT WILL
 LIMIT THE FLOW OUT OF THE TRENCH.
  
 13. EXPLAIN HOW THE EXFILTRATION TRENCH ALONG THE NORTH
 PROPERTY LINE WILL BE MAINTAINED, INCLUDING POSSIBLE
 REPLACEMENT, WHEN IT HAS LOST ITS DISPOSAL CAPACITY IN
 A FEW YEARS.
  
 14. PROVIDE AN EXFILTRATION TRENCH DETAIL, LABELING THE
 TRENCH WIDTH AND THE ELEVATIONS FOR THE TOP OF TRENCH,
 THE BOTTOM OF THE TRENCH, AND THE PIPE INVERT.
  
 15. PROVIDE DETAIL OF CONTROL STRUCTURE(S). NOTE
 BLEEDERS CANNOT BE USED AS PART OF THE CONTROL TO
 SURCHARGE THE EXFILTRATION TRENCH.
  
 16. SHOW MILL AND RESURFACING LIMITS FOR TRENCH CUTS IN
 THE ROADWAY PER CITY'S STANDARD DETAIL GC-8.
  
 17. CONVERT EXISTING DRAINAGE STRUCTURE IN THE EXISTING
 SOUTH DRIVEWAY TO S. FLAGLER DRIVE TO A CATCH BASIN
 WITH A HOODED FRAME AND GRATE. THE STRUCTURE MAY NEED
 TO BE ENLARGED IN ORDER TO CONNECT THE PROPOSED 15-INCH
 RCP FROM THE DEVELOPMENT.
  
 18. DRAINAGE SYSTEM DESIGN TO CONSIDER SEA LEVEL RISE.
  
 19. WHAT IS THE PURPOSE OF THE 6-INCH HDPE PIPE BETWEEN
 THE SIDEWALK AND EAST PROPERTY LINE?
  
 20. THE ROOF DRAIN SYSTEM WILL NEED TO BE DESIGNED SO
 THAT MANHOLE LIDS ARE NOT DISPLACED BY THE PRESSURE OF
 THE WATER OR TRAPPED AIR IN THE ROOF DOWNSPOUTS.
  
 21. IT APPEARS THE TOWNHOME AT THE WEST END OF THE
 PROJECT WILL HOLD WATER BEHIND THE DIANA PLACE
 SIDEWALK.
  
 22. WHAT DRAINAGE MITIGATION (WATER QUALITY AND PEAK
 FLOW ATTENUATION) IS PROPOSED FOR THE ADDITIONAL
 IMPERVIOUS AREA IN THE DIANA PLACE PARCEL.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  
  

Review Stop STORM STORMWATER
Rev No 1 Status F Date 06-10-2021 Cont ID  
Sent By tward Date 06-10-2021 Time 11:28 Rev Time 0.00
Received By tward Date 06-10-2021 Time 11:29 Sent To  
Notes
2021-06-10 11:29:08THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. PROJECT SITE IS WITHIN A SPECIAL FLOOD HAZARD AREA.
 DRAFT COASTAL FLOOD ZONE MAPS HAVE BEEN ISSUED BY FEMA
 THAT MAY SHOW A HIGHER BASE FLOOD ELEVATION THAN WHAT
 IS SHOWN ON THE CURRENT FLOOD INSURANCE RATE MAPS. TWO
 FEET OF FREEBOARD ABOVE THE BFE WILL BE REQUIRED FOR
 THE FINISHED FLOOR ELEVATION AND ANY
 MECHANICAL/ELECTRICAL EQUIPMENT.
  
 2. LABEL THE VERTICAL DATUM AND CONVERSION EQUATION TO
 NGVD1929 ON ALL CIVIL ENGINEERING SHEETS WITH ELEVATION
 INFORMATION.
  
 3. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP
 CRITERIA AND CONSIDER SEA LEVEL RISE.
  
 4. MINIMUM 15 INCH DIAMETER RCP PIPE WITHIN THE RIGHT
 OF WAY.
  
 5. CURB RAMP AT CORNER OF CURRIE CRESCENT AND S. OLIVE
 AVE TO MEET CURRENT ADA CRITERIA.
  
 6. UPDATE FDOT STANDARD INDEX REFERENCES TO FDOT
 STANDARD PLAN REFERENCES.
  
 7. PROVIDE CROSS SECTIONS AT ALL DRIVEWAYS FROM THE
 CENTERLINE OF THE ROAD TO 10 FEET WITHIN THE PROPERTY.
 PROVIDE CROSS SLOPE INFORMATION FOR EACH CHANGE IN
 SLOPE. SHOW THE LOCATION OF THE RIGHT OF WAY LINE.
  
 8. PROVIDE TYPICAL CROSS SECTIONS FOR EACH SIDE OF THE
 BUILDING FROM THE ROAD CENTERLINE TO THE FACE OF THE
 BUILDING. SHOW THE LOCATION OF THE PROPERTY LINE.
  
 9. THE ELEVATION OF THE TRENCH GRATES ACROSS THE
 DRIVEWAYS SHOULD NOT BE LOWER THAN THE PERIMETER BERM
 ELEVATION.
  
 10. PRBS SHOULD BE USED IN STRUCTURES CONNECTED TO
 EXFILTRATION TRENCHES AND ON THE OUTFALL PIPE.
  
 11. SHOW SIDEWALK REPLACEMENT WHERE UTILITIES WILL BE
 CONSTRUCTED.
  
 12. IT APPEARS THERE WILL BE PARKING LOCATED BELOW THE
 GROUNDWATER TABLE ELEVATION. DESCRIBE HOW THE
 GROUNDWATER WILL BE PREVENTED FROM ENTERING THE BELOW
 GRADE PARKING AREA.
  
 13. SHOW UTILITIES ON THE LANDSCAPE PLANS.
  
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3. PROVIDE A COPY OF THE SFWMD ERP BEFORE THE START OF
 CONSTRUCTION.
  
 4. DRAINAGE CALCULATIONS WILL BE REVIEWED WITH THE
 ENGINEERING PERMIT APPLICATION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 07-26-2021 Cont ID  
Sent By vnoel Date 07-26-2021 Time 07:59 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2021-07-26 08:03:03CONDITIONS OF APPROVAL:
  
 1. REPLAT PRIOR TO C.O.
 2. AGREEMENT/LEASE FOR SIDEWALK ALONG SOUTH LINE WITHIN
 CITY PROPERTY.
 3. MAINTENANCE AGREEMENT FOR ANY IMPROVEMENTS WITHIN
 CITY RIGHT-OF-WAY.
 4. ANY REQUIRED UTILITY EASEMENTS.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 06-07-2021 Cont ID  
Sent By vnoel Date 06-07-2021 Time 08:43 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2021-06-07 09:12:191. REPLAT WILL BE REQUIRED. APPLICATION FOR MINOR
 SUBDIVISION IS MADE THROUGH PLANNING.
 2. NEED BLOW UP OF METER AREA WITH ELEVATIONS.
 3. SIDEWALK ALONG DIANA PLACE AND FLAGLER WILL REQUIRE
 MAINTENANCE AGREEMENT.
 4. UTILITY EASEMENTS WILL BE REQUIRED FOR METERS AND
 POSSIBLY WATER MAIN ALONG OLIVE AVE.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 5 Status P Date 09-27-2021 Cont ID  
Sent By   Date 09-27-2021 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2021-09-27 21:37:42NO FURTHER COMMENTS
  
 SATISFIED. APPROVED WITH THE CONDITION OF REVISING
 FREIGHT MANAGEMENT PLAN.
  
 TRAFFIC COMMENTS
 1) SATISFIED. PROVIDE COUNTY TPS LETTER ONCE RECEIVED.
 2) SATISFIED. SECOND PARAGRAPH OF THE TRAFFIC STUDY
 SEEMS INCOMPLETE OR MISSING TEXT AT THE END
 3) SATISFIED. DRIVEWAY DIAGRAM SHOWCASES AN ACCESS
 POINT ON DIANA, DUE TO THAT, THE TRAFFIC STUDY IS
 INVALID IN ITS ASSUMPTIONS AND FINDINGS. PLEASE CORRECT
 AND REVISE ACCORDING TO THE LATEST SITE PLAN.
 4) SATISFIED. PROPERLY DEPICT INBOUND/OUTBOUND VOLUMES
 THROUGH EACH OF THE PROPOSED DRIVEWAYS OR ENTRY POINTS.
 AGGREGATE AND SHOWCASE VOLUMES ENTERING/EXITING THE S
 FLAGLER AND CURRIE CRESCENT MAIN DRIVEWAYS IN FIGURE 4.
 5) SATISFIED. SPECIFY THE FUNCTIONALITY OF EACH
 DRIVEWAY (I.E. SERVICE, PUBLIC AND RESIDENTIAL)
 6) SATISFIED. PROVIDE A SEPARATE TRAFFIC STUDY FROM THE
 ONE SUBMITTED TO THE COUNTY, WHERE ALL VEHICULAR
 VOLUMES (I.E. RESIDENTIAL) ARE CONSIDERED
  
 SITE COMMENTS
 7) SATISFIED. ON THE SITE PLAN, PLEASE SHOWCASE BASIC
 CURB DETAILS (I.E. DRIVEWAY, PAVEMENT MARKINGS AND
 PARKING STALLS) OF THE PROPERTIES ON THE OPPOSITE SIDE
 OF THE ROADS SURROUNDING THE PROPOSED DEVELOPMENT
 8) SATISFIED. PROVIDE AUTOTURN ANALYSIS FOR GARBAGE
 TRUCK AND SERVICE VEHICLES DRIVING IN AND OUT OF THE
 PROPOSED DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES
 CLEARLY DEFINED. VEHICULAR MOVEMENTS SHALL BE DEPICTED
 FROM OLIVE AVENUE AND THROUGH ALL POTENTIALLY
 SERVICEABLE AREAS
 9) SATISFIED. PROVIDE SITE PLAN, OR INDICATE THE
 SPECIFIC SHEET SHOWCASING: ROAD, SIDEWALK, AND DRIVEWAY
 DIMENSIONS. SIDEWALK DIMENSIONS ARE MISSING.
 10) SATISFIED. PROVIDE A MINIMUM OF 8 FEET WIDE
 SIDEWALK ALONG PROPERTY FRONTAGE ON OLIVE AVE AND
 CURRIE CRESCENT.
 11) SATISFIED. PROVIDE A MINIMUM OF 10 FEET SIDEWALK
 ALONG FLAGLER DR
 12) SATISFIED. IDENTIFY AND DESIGNATE BY WAY OF
 PAVEMENT MARKINGS AN EASILY ACCESSIBLE MICRO-MOBILITY
 STATION AREA (MINIMUM 8 X 20 FEET) AND PROVIDE BASIC
 ELECTRIFICATION READINESS (CIRCUIT BOX AND ELECTRIC
 CONDUIT)
 13) SATISFIED. MAXIMUM ALLOWED DRIVEWAY WIDTH IS 25
 FEET. THE RESIDENTIAL DRIVEWAY ON CURRIE CRESCENT DOES
 NOT MEET SUCH CRITERIA.
 14) SATISFIED. MISSING DETAILS FOR THE SIDEWALK ON THE
 SOUTH-WEST CORNER OF THE PROPOSED DEVELOPMENT
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 4 Status P Date 09-01-2021 Cont ID  
Sent By   Date 09-01-2021 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2021-09-01 13:38:58PASSED WITH THE FOLLOWING CONDITION:
  
 PROVIDE THE REVISED FREIGHT/SERVICE VEHICLES MANAGEMENT
 PLAN.
  
 TRAFFIC COMMENTS
 1) SATISFIED. PROVIDE COUNTY TPS LETTER ONCE RECEIVED.
 2) SATISFIED. SECOND PARAGRAPH OF THE TRAFFIC STUDY
 SEEMS INCOMPLETE OR MISSING TEXT AT THE END
 3) SATISFIED. DRIVEWAY DIAGRAM SHOWCASES AN ACCESS
 POINT ON DIANA, DUE TO THAT, THE TRAFFIC STUDY IS
 INVALID IN ITS ASSUMPTIONS AND FINDINGS. PLEASE CORRECT
 AND REVISE ACCORDING TO THE LATEST SITE PLAN.
 4) SATISFIED. PROPERLY DEPICT INBOUND/OUTBOUND VOLUMES
 THROUGH EACH OF THE PROPOSED DRIVEWAYS OR ENTRY POINTS.
 AGGREGATE AND SHOWCASE VOLUMES ENTERING/EXITING THE S
 FLAGLER AND CURRIE CRESCENT MAIN DRIVEWAYS IN FIGURE 4.
 5) SATISFIED. SPECIFY THE FUNCTIONALITY OF EACH
 DRIVEWAY (I.E. SERVICE, PUBLIC AND RESIDENTIAL)
 6) SATISFIED. PROVIDE A SEPARATE TRAFFIC STUDY FROM THE
 ONE SUBMITTED TO THE COUNTY, WHERE ALL VEHICULAR
 VOLUMES (I.E. RESIDENTIAL) ARE CONSIDERED
 SITE COMMENTS
 7) SATISFIED. ON THE SITE PLAN, PLEASE SHOWCASE BASIC
 CURB DETAILS (I.E. DRIVEWAY, PAVEMENT MARKINGS AND
 PARKING STALLS) OF THE PROPERTIES ON THE OPPOSITE SIDE
 OF THE ROADS SURROUNDING THE PROPOSED DEVELOPMENT
 8) SATISFIED. PROVIDE AUTOTURN ANALYSIS FOR GARBAGE
 TRUCK AND SERVICE VEHICLES DRIVING IN AND OUT OF THE
 PROPOSED DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES
 CLEARLY DEFINED. VEHICULAR MOVEMENTS SHALL BE DEPICTED
 FROM OLIVE AVENUE AND THROUGH ALL POTENTIALLY
 SERVICEABLE AREAS
 9) SATISFIED. PROVIDE SITE PLAN, OR INDICATE THE
 SPECIFIC SHEET SHOWCASING: ROAD, SIDEWALK, AND DRIVEWAY
 DIMENSIONS. SIDEWALK DIMENSIONS ARE MISSING.
 10) SATISFIED. PROVIDE A MINIMUM OF 8 FEET WIDE
 SIDEWALK ALONG PROPERTY FRONTAGE ON OLIVE AVE AND
 CURRIE CRESCENT.
 11) SATISFIED. PROVIDE A MINIMUM OF 10 FEET SIDEWALK
 ALONG FLAGLER DR
 12) SATISFIED. IDENTIFY AND DESIGNATE BY WAY OF
 PAVEMENT MARKINGS AN EASILY ACCESSIBLE MICRO-MOBILITY
 STATION AREA (MINIMUM 8 X 20 FEET) AND PROVIDE BASIC
 ELECTRIFICATION READINESS (CIRCUIT BOX AND ELECTRIC
 CONDUIT)
 13) SATISFIED. MAXIMUM ALLOWED DRIVEWAY WIDTH IS 25
 FEET. THE RESIDENTIAL DRIVEWAY ON CURRIE CRESCENT DOES
 NOT MEET SUCH CRITERIA.
 14) SATISFIED. MISSING DETAILS FOR THE SIDEWALK ON THE
 SOUTH-WEST CORNER OF THE PROPOSED DEVELOPMENT
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 3 Status F Date 08-19-2021 Cont ID  
Sent By   Date 08-19-2021 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2021-08-19 11:12:33TRAFFIC COMMENTS
 1) SATISFIED. PROVIDE COUNTY TPS LETTER ONCE RECEIVED.
 2) SATISFIED. SECOND PARAGRAPH OF THE TRAFFIC STUDY
 SEEMS INCOMPLETE OR MISSING TEXT AT THE END
 3) SATISFIED. DRIVEWAY DIAGRAM SHOWCASES AN ACCESS
 POINT ON DIANA, DUE TO THAT, THE TRAFFIC STUDY IS
 INVALID IN ITS ASSUMPTIONS AND FINDINGS. PLEASE CORRECT
 AND REVISE ACCORDING TO THE LATEST SITE PLAN.
 4) SATISFIED. PROPERLY DEPICT INBOUND/OUTBOUND VOLUMES
 THROUGH EACH OF THE PROPOSED DRIVEWAYS OR ENTRY POINTS.
 AGGREGATE AND SHOWCASE VOLUMES ENTERING/EXITING THE S
 FLAGLER AND CURRIE CRESCENT MAIN DRIVEWAYS IN FIGURE 4.
 5) SATISFIED. SPECIFY THE FUNCTIONALITY OF EACH
 DRIVEWAY (I.E. SERVICE, PUBLIC AND RESIDENTIAL)
 6) SATISFIED. PROVIDE A SEPARATE TRAFFIC STUDY FROM THE
 ONE SUBMITTED TO THE COUNTY, WHERE ALL VEHICULAR
 VOLUMES (I.E. RESIDENTIAL) ARE CONSIDERED
 SITE COMMENTS
 7) SATISFIED. ON THE SITE PLAN, PLEASE SHOWCASE BASIC
 CURB DETAILS (I.E. DRIVEWAY, PAVEMENT MARKINGS AND
 PARKING STALLS) OF THE PROPERTIES ON THE OPPOSITE SIDE
 OF THE ROADS SURROUNDING THE PROPOSED DEVELOPMENT
 8) SATISFIED. PROVIDE AUTOTURN ANALYSIS FOR GARBAGE
 TRUCK AND SERVICE VEHICLES DRIVING IN AND OUT OF THE
 PROPOSED DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES
 CLEARLY DEFINED. VEHICULAR MOVEMENTS SHALL BE DEPICTED
 FROM OLIVE AVENUE AND THROUGH ALL POTENTIALLY
 SERVICEABLE AREAS
 9) SATISFIED. PROVIDE SITE PLAN, OR INDICATE THE
 SPECIFIC SHEET SHOWCASING: ROAD, SIDEWALK, AND DRIVEWAY
 DIMENSIONS. SIDEWALK DIMENSIONS ARE MISSING.
 10) PARTIALLY SATISFIED. PROVIDE A MINIMUM OF 8 FEET
 WIDE SIDEWALK ALONG PROPERTY FRONTAGE ON OLIVE AVE AND
 CURRIE CRESCENT.
 11) NOT SATISFIED. PROVIDE A MINIMUM OF 10 FEET
 SIDEWALK ALONG FLAGLER DR
 12) NOT SATISFIED. IDENTIFY AND DESIGNATE BY WAY OF
 PAVEMENT MARKINGS AN EASILY ACCESSIBLE MICRO-MOBILITY
 STATION AREA (MINIMUM 8 X 20 FEET) AND PROVIDE BASIC
 ELECTRIFICATION READINESS (CIRCUIT BOX AND ELECTRIC
 CONDUIT)
 13) NOT SATISFIED. MAXIMUM ALLOWED DRIVEWAY WIDTH IS 25
 FEET. THE RESIDENTIAL DRIVEWAY ON CURRIE CRESCENT DOES
 NOT MEET SUCH CRITERIA.
 14) NOT SATISFIED. MISSING DETAILS FOR THE SIDEWALK ON
 THE SOUTH-WEST CORNER OF THE PROPOSED DEVELOPMENT
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status F Date 07-16-2021 Cont ID  
Sent By   Date 07-16-2021 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2021-07-16 21:32:33TRAFFIC COMMENTS
 1) PARTIALLY SATISFIED. PROVIDE COUNTY TPS LETTER ONCE
 RECEIVED.
 2) SATISFIED. SECOND PARAGRAPH OF THE TRAFFIC STUDY
 SEEMS INCOMPLETE OR MISSING TEXT AT THE END
 3) SATISFIED. DRIVEWAY DIAGRAM SHOWCASES AN ACCESS
 POINT ON DIANA, DUE TO THAT, THE TRAFFIC STUDY IS
 INVALID IN ITS ASSUMPTIONS AND FINDINGS. PLEASE CORRECT
 AND REVISE ACCORDING TO THE LATEST SITE PLAN.
 4) PARTIALLY SATISFIED. PROPERLY DEPICT
 INBOUND/OUTBOUND VOLUMES THROUGH EACH OF THE PROPOSED
 DRIVEWAYS OR ENTRY POINTS. AGGREGATE AND SHOWCASE
 VOLUMES ENTERING/EXITING THE S FLAGLER AND CURRIE
 CRESCENT MAIN DRIVEWAYS IN FIGURE 4.
 5) SATISFIED. SPECIFY THE FUNCTIONALITY OF EACH
 DRIVEWAY (I.E. SERVICE, PUBLIC AND RESIDENTIAL)
 6) SATISFIED. PROVIDE A SEPARATE TRAFFIC STUDY FROM THE
 ONE SUBMITTED TO THE COUNTY, WHERE ALL VEHICULAR
 VOLUMES (I.E. RESIDENTIAL) ARE CONSIDERED
  
 SITE COMMENTS
 7) SATISFIED. ON THE SITE PLAN, PLEASE SHOWCASE BASIC
 CURB DETAILS (I.E. DRIVEWAY, PAVEMENT MARKINGS AND
 PARKING STALLS) OF THE PROPERTIES ON THE OPPOSITE SIDE
 OF THE ROADS SURROUNDING THE PROPOSED DEVELOPMENT
 8) SATISFIED. PROVIDE AUTOTURN ANALYSIS FOR GARBAGE
 TRUCK AND SERVICE VEHICLES DRIVING IN AND OUT OF THE
 PROPOSED DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES
 CLEARLY DEFINED. VEHICULAR MOVEMENTS SHALL BE DEPICTED
 FROM OLIVE AVENUE AND THROUGH ALL POTENTIALLY
 SERVICEABLE AREAS
 9) PARTIALLY SATISFIED. PROVIDE SITE PLAN, OR INDICATE
 THE SPECIFIC SHEET SHOWCASING: ROAD, SIDEWALK, AND
 DRIVEWAY DIMENSIONS. SIDEWALK DIMENSIONS ARE MISSING.
 10) NOT SATISFIED. PROVIDE A MINIMUM OF 8 FEET WIDE
 SIDEWALK ALONG PROPERTY FRONTAGE ON OLIVE AVE AND
 CURRIE CRESCENT
  
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 06-10-2021 Cont ID  
Sent By   Date 06-10-2021 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2021-06-10 12:06:35TRAFFIC COMMENTS
 1) PROVIDE COUNTY TPS LETTER
 2) SECOND PARAGRAPH OF THE TRAFFIC STUDY SEEMS
 INCOMPLETE OR MISSING TEXT AT THE END
 3) DRIVEWAY DIAGRAM SHOWCASES AN ACCESS POINT ON DIANA,
 DUE TO THAT, THE TRAFFIC STUDY IS INVALID IN ITS
 ASSUMPTIONS AND FINDINGS. PLEASE CORRECT AND REVISE
 ACCORDING TO THE LATEST SITE PLAN
 4) PROPERLY DEPICT INBOUND/OUTBOUND VOLUMES THROUGH
 EACH OF THE PROPOSED DRIVEWAYS OR ENTRY POINTS
 5) SPECIFY THE FUNCTIONALITY OF EACH DRIVEWAY (I.E.
 SERVICE, PUBLIC AND RESIDENTIAL)
 6) PROVIDE A SEPARATE TRAFFIC STUDY FROM THE ONE
 SUBMITTED TO THE COUNTY, WHERE ALL VEHICULAR VOLUMES
 (I.E. RESIDENTIAL) ARE CONSIDERED
  
 SITE COMMENTS
 7) ON THE SITE PLAN, PLEASE SHOWCASE BASIC CURB DETAILS
 (I.E. DRIVEWAY, PAVEMENT MARKINGS AND PARKING STALLS)
 OF THE PROPERTIES ON THE OPPOSITE SIDE OF THE ROADS
 SURROUNDING THE PROPOSED DEVELOPMENT
 8) PROVIDE AUTOTURN ANALYSIS FOR GARBAGE TRUCK AND
 SERVICE VEHICLES DRIVING IN AND OUT OF THE PROPOSED
 DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES CLEARLY
 DEFINED. VEHICULAR MOVEMENTS SHALL BE DEPICTED FROM
 OLIVE AVENUE AND THROUGH ALL POTENTIALLY SERVICEABLE
 AREAS
 9) PROVIDE SITE PLAN, OR INDICATE THE SPECIFIC SHEET
 SHOWCASING: ROAD, SIDEWALK AND DRIVEWAY DIMENSIONS
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop Z ZONING
Rev No 5 Status P Date 09-28-2021 Cont ID  
Sent By eschneid Date 09-28-2021 Time 08:34 Rev Time 2.00
Received By eschneid Date 09-27-2021 Time 09:48 Sent To  
Notes
2021-09-28 08:37:04CASE NO. PB 1857B 9/13/21 RESUBMITTAL
 FLAGLER TOWERS
 1315 SOUTH FLAGLER DRIVE
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446,
 [email protected]
  
 - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 1) IN ACCORDANCE WITH SECTION 166.033 OF THE FLORIDA
 STATUTES, YOU ARE NOT REQUIRED TO PROVIDE THE FAA
 APPROVAL LETTER PRIOR TO PROCEEDING TO THE PLANNING
 BOARD AND CITY COMMISSION UNLESS THE FAA ISSUES A FINAL
 AGENCY ACTION OF DENIAL. PLEASE BE AWARE THAT THE
 DEVELOPMENT ORDER WILL INCLUDE A PROVISION THAT THE FAA
 APPROVAL WILL BE REQUIRED PRIOR TO ISSUING A BUILDING
 PERMIT FOR WHATEVER HEIGHT THE FINAL BUILDING IS
 APPROVED AT.
  
 2) STAFF WILL NOT SUPPORT THE BUILDING IN EXCESS OF 300
 FEET IN HEIGHT.
  
 3) ROBERT BROWN, CHIEF BUILDING OFFICIAL, MUST APPROVE
 THE FFE OF 9. PLEASE REVIEW HIS COMMENTS WHEN THEY ARE
 POSTED.
  
 4) ROBERT BROWN, CHIEF BUILDING OFFICIAL, MUST APPROVE
 THAT THE NEW CONNECTION TO THE DIANA PLACE CROSSWALK
 PROVIDES AN ADA COMPLIANT ROUTE TO AVOID THE STEPS.
 PLEASE REVIEW HIS COMMENTS WHEN THEY ARE POSTED.
  
 PARKING
  
 5) CONDITION: TWO BICYCLE PARKING SPACES WERE REMOVED
 FROM THE CAFE AREA (8 TO 6). THIS REQUIRES AN UPDATE TO
 THE "PROPOSED" LINE OF THE BICYCLE PARKING TABLE. THE
 SITE MEETS THE MINIMUM REQUIRED; HOWEVER, THE TABLE
 WILL NEED TO BE CORRECTED PRIOR TO SCHEDULING THE CASE
 BEFORE THE CITY COMMISSION.
  
 DEVELOPMENT REGULATION: FPL EASEMENT WHICH BISECTS THE
 PROPOSED BUILDING LOCATION WILL NEED TO BE RELEASED BY
 FPL AND ALL OVERHEAD LINES MUST BE REMOVED. ANY NEW
 UTILITY LINES MUST BE RELOCATED UNDERGROUND.
  
 DEVELOPMENT REGULATION: THE IMPROVEMENTS TO THE CITY
 OWNED PARCEL SOUTH OF THE PROPERTY, INCLUDING THE
 SIDEWALK, WALKWAYS AND LANDSCAPE, WILL BE THE
 MAINTENANCE RESPONSIBILITY OF THE FLAGLER TOWERS
 PROJECT. MAINTENANCE AGREEMENTS AND EASEMENTS WILL BE
 REQUIRED.
  
 DEVELOPMENT REGULATION: EVERY UNIT OWNER SHALL HAVE AT
 LEAST ONE EV EQUIPPED PARKING SPACE.
  
 DEVELOPMENT REGULATION: THERE WILL BE A DEVELOPMENT
 REGULATION REFERENCING THE TRAFFIC MANAGEMENT PLAN THAT
 WAS APPROVED BY THE CITY'S TRAFFIC ENGINEER.
  
  

Review Stop Z ZONING
Rev No 4 Status F Date 09-01-2021 Cont ID  
Sent By eschneid Date 09-01-2021 Time 17:07 Rev Time 6.00
Received By eschneid Date 09-01-2021 Time 17:04 Sent To  
Notes
2021-09-01 17:06:05CASE NO. PB 1857B - 3RD RESUBMITTAL REVIEW 9/1/21
 FLAGLER TOWERS
 1315 SOUTH FLAGLER DRIVE
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446,
 [email protected]
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF THREE
 (3) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE COMMENTS WITHIN 60 DAYS FROM
 THE DATE OF ISSUANCE (BY NOVEMBER 1, 2021), THE
 PLANNING DIVISION MAY NOTIFY THE APPLICANT THAT THE
 CASE IS CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL
 REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ON ADDITIONAL
 SUBMITTAL. IF COMMENTS ARE NOT ADDRESSED YOU WILL BE
 ASSESSED A RESUBMITTAL FEE. SUCH FEE IS 20% OF THE
 ORIGINAL APPLICATION FEE ($600).
  
 - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 1) REPEAT COMMENT: THANK YOU FOR PROVIDING THE FAA
 APPLICATION NUMBERS. YOU ARE REQUIRED TO SUBMIT THE FAA
 APPROVAL FOR THE PROPOSED TOWER PRIOR TO SCHEDULING
 THIS CASE FOR PLANNING BOARD.
  
 2) REPEAT COMMENT: STAFF WILL NOT SUPPORT THE BUILDING
 IN EXCESS OF 300 FEET IN HEIGHT. PLEASE NOTE THAT YOU
 ARE WELCOME TO PROCEED THROUGH THE PUBLIC HEARING
 PROCESS TO CITY COMMISSION; HOWEVER, STAFF WILL BE
 RECOMMENDING DENIAL OF THE REQUEST AS CURRENTLY
 PROPOSED. THE LATEST ROUND OF RESPONSES INCLUDES ITEMS
 WHICH MUST BE PROVIDED AND CORRECTED PRIOR TO BEING
 SCHEDULED FOR PLANNING BOARD, REGARDLESS OF THE
 BUILDING DESIGN (EXAMPLE: PARKING LOT CORRECTIONS).
  
 BUILDING PLACEMENT
  
 3) UPDATED COMMENT: SHEET G-201 WAS UPDATED TO SHOW THE
 BUILDING 15 FEET FROM THE SOUTH PROPERTY LINE. THE
 CIVIL PLAN CROSS SECTIONS H (14.6 FEET) AND I (14.8)
 SHOW THE BUILDING CLOSER THAN 15 FEET FROM THE PROPERTY
 LINE. ALL PLANS NEED TO SHOW THE SAME CONDITION WITH A
 MINIMUM 15-FOOT SETBACK.
  
 4) CITY STAFF HAS REVIEWED THE LATEST SIDEWALK AND
 LANDSCAPE CONFIGURATION ALONG DIANA PLACE.
  
 A. UPDATED COMMENT: THE WESTERNMOST TOWNHOUSES, WITH AN
 FFE OF 9 FEET ARE BELOW THE ROADWAY ELEVATION, WHICH IS
 A PROBLEM. THANK YOU FOR PROVIDING INFORMATION ON HOW
 YOU PLAN TO ACCOMPLISH THE DRAINAGE FOR THESE UNITS.
 THIS NEEDS TO BE APPROVED BY ROBERT BROWN, CHIEF
 BUILDING OFFICIAL. PLEASE NOTE THAT IT HAS COME TO THE
 PLANNING STAFF'S ATTENTION THAT THE FIMA FLOOD ZONE
 MAPS SHOW THAT YOUR FFE NEEDS TO BE SET AT 10, NOT 9
 FEET. WHILE THE CITY IS CURRENTLY APPEALING THIS
 DESIGNATION; IF THE APPEAL IS NOT GRANTED, YOU WILL
 NEED TO REVISE YOUR FINISHED FLOOR LEVEL.
  
 B. UPDATED COMMENT: THANK YOU FOR RELOCATING THE
 SIDEWALK CLOSER TO THE TOWNHOUSES AND FLATTENING OUT
 THE EXTREME GRADE ISSUES THAT PREVIOUSLY OCCURRED. THE
 STAIRS THAT YOU HAVE USED TO OFFSET THIS GRADE
 DIFFERENTIAL FOR THE WALKWAYS FROM THE SIDEWALK TO THE
 UNITS MAY NOT OCCUR ON THE CITY PROPERTY BUT MUST
 RATHER OCCUR ON YOUR PRIVATE PROPERTY. AS DISCUSSED ON
 THE CALL, FOR WALK-UP UNITS, THIS TYPICALLY OCCURS AT
 THE ENTRY TO THE BUILDING. PLEASE NOTE THAT PRELIMINARY
 DISCUSSIONS THAT PLANNING STAFF HAD WITH BUILDING STAFF
 VERIFIED THAT SHOULD THESE STAIRS BE WITHIN THE CITY
 PROPERTY THEY WOULD BE REQUIRED TO HAVE HANDRAILS,
 WHICH IS NOT AN ACCEPTABLE SITUATION.
  
 C. THE PROPOSED EAST/WEST SIDEWALK NOW SHOWS STEPS AT
 THE WESTERN END TO OFFSET THE GRADE DIFFERENTIAL, WHICH
 IS NOT ADA COMPLIANT. NO INFORMATION WAS PROVIDED TO
 VERIFY THAT THE NEW CONNECTION TO THE DIANA PLACE
 CROSSWALK PROVIDES AN ADA COMPLIANT ROUTE TO AVOID THE
 STEPS. THIS NEW CONFIGURATION REQUIRES APPROVAL BY
 ROBERT BROWN, CHIEF BUILDING OFFICIAL.
  
 PARKING
  
 5) UPDATED COMMENT: THANK YOU FOR PROVIDING THE BICYCLE
 PARKING CLOSER TO A GUEST ACCESSIBLE ENTRANCE TO THE
 BUILDING. THE LOCATION APPEARS TO REQUIRE THAT USERS
 WOULD NEED TO WALK THEIR BICYCLES THROUGH THE CAFE
 SEATING AREA, WHICH IS NOT IDEAL FOR EITHER THE CAFE
 OPERATION OR THE BICYCLE PARKER. PROVIDE A DIRECT PAVED
 CONNECTION FROM THE FRONT OF THE RACKS TO THE PUBLIC
 SIDEWALK SO THAT THE CONFLICT IS MINIMIZE (SEE E-MAILED
 ADDENDUM). THIS WILL ALSO ALLOW GUESTS A ROUTE TO THE
 BUILDING ENTRANCE THAT DOES NOT REQUIRE THEM TO WALK
 THROUGH THE CAFE SEATING AREA.
  
 LANDSCAPE
  
 6) THE ZONING AND LAND DEVELOPMENT REGULATIONS ONLY
 PERMIT HEDGES WITHIN A SETBACK TO BE A MAXIMUM HEIGHT
 OF 10 FEET. THE RESUBMITTED PLANS CALL OUT THE
 PODOCARPUS ALONG THE SOUTH PROPERTY LINE TO BE GROWN TO
 A HEIGHT OF 12 FEET TO ARCH OVER THE GATES. IS THIS
 PROPOSED TO BE THE OVERALL HEIGHT OF THE ARCH OR THE
 UNDERSIDE OF THE ARCH? YOU HAVE STATED THAT THERE WILL
 BE COLUMNS FOR THE GATES. THIS WOULD FORCE THE HEDGES
 WIDER FROM THE ENTRYWAY AND THUS CREATE A LARGE VISUAL
 OBSTRUCTION FOR PEDESTRIANS ALONG THE NEW DIANA PLACE
 WALKWAY. IF YOU CHOOSE TO MOVE FORWARD WITH THIS
 CONFIGURATION, AN ADDITIONAL WAIVER MUST BE REQUESTED,
 BUT STAFF WILL NOT SUPPORT IT.
  
 7) UPDATED COMMENT: THE TWO NEW TREES PROVIDED ADJACENT
 TO THE CANOPY AT THE SOUTH ENTRANCE ARE SHOWN PLANTED
 IN PAVEMENT, WHICH IS NOT PERMITTED. THE PLANTING AREA
 NEEDS TO BE SHOWN AS APPROPRIATE FOR A 200-GALLON ROOT
 BALL. WHILE ALL SHOWING THAT THE TREES WILL BE PLANTED
 IN PAVEMENT, THE CIVIL, SITE AND LANDSCAPE PLANS DO NOT
 SHOW THE SAME PAVEMENT CONDITIONS IN THIS AREA.
  
 8) SOME OF THE TREES ALONG THE SOUTH SIDE OF THE
 BUILDING ARE SHOWN PLANTED IN PAVEMENT, WHICH IS NOT
 PERMITTED. THE CIVIL, LANDSCAPE AND SITE PLANS ALL SHOW
 THE CONSISTENT PAVEMENT CONDITION.
  
 DEVELOPMENT REGULATION: FPL EASEMENT WHICH BISECTS THE
 PROPOSED BUILDING LOCATION WILL NEED TO BE RELEASED BY
 FPL AND ALL OVERHEAD LINES MUST BE REMOVED. ANY NEW
 UTILITY LINES MUST BE RELOCATED UNDERGROUND.
  
 DEVELOPMENT REGULATION: THE IMPROVEMENTS TO THE CITY
 OWNED PARCEL SOUTH OF THE PROPERTY, INCLUDING THE
 SIDEWALK, WALKWAYS AND LANDSCAPE, WILL BE THE
 MAINTENANCE RESPONSIBILITY OF THE FLAGLER TOWERS
 PROJECT. MAINTENANCE AGREEMENTS AND EASEMENTS WILL BE
 REQUIRED.
  
 DEVELOPMENT REGULATION: EVERY UNIT OWNER SHALL HAVE AT
 LEAST ONE EV EQUIPPED PARKING SPACE.
  
  

Review Stop Z ZONING
Rev No 3 Status F Date 08-19-2021 Cont ID  
Sent By eschneid Date 08-19-2021 Time 12:19 Rev Time 8.00
Received By eschneid Date 08-18-2021 Time 09:46 Sent To  
Notes
2021-08-19 12:16:46CASE NO. PB 1857B - 2ND RESUBMITTAL REVIEW 8/19/21
 FLAGLER TOWERS
 1315 SOUTH FLAGLER DRIVE
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446,
 [email protected]
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF THREE
 (3) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE COMMENTS WITHIN 60 DAYS FROM
 THE DATE OF ISSUANCE (BY OCTOBER 19, 2021), THE
 PLANNING DIVISION MAY NOTIFY THE APPLICANT THAT THE
 CASE IS CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL
 REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ON ADDITIONAL
 SUBMITTAL. IF COMMENTS ARE NOT ADDRESSED YOU WILL BE
 ASSESSED A RESUBMITTAL FEE. SUCH FEE IS 20% OF THE
 ORIGINAL APPLICATION FEE ($600).
  
 - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 1) UPDATED COMMENT: THE CITY OWNED PARCEL SOUTH OF THE
 PROJECT IS SUBJECT TO A DEED RESTRICTION. IN ORDER TO
 ENSURE THAT THE PROPOSED CHANGES DO NOT IMPACT THE DEED
 RESTRICTION, PRIOR TO SCHEDULING THE APPLICATION FOR
 THE PLANNING BOARD MEETING, YOU MUST PROVIDE WRITTEN
 CONSENT/NO OBJECTION FROM THE LAKE WORTH PIONEERS
 ASSOCIATION TO THE CITY.
  
 2) REPEAT COMMENT: THANK YOU FOR PROVIDING THE FAA
 APPLICATION NUMBERS. YOU ARE REQUIRED TO SUBMIT THE FAA
 APPROVAL FOR THE PROPOSED TOWER PRIOR TO SCHEDULING
 THIS CASE FOR PLANNING BOARD.
  
 3) REPEAT COMMENT: STAFF WILL NOT SUPPORT THE BUILDING
 IN EXCESS OF 300 FEET IN HEIGHT. PLEASE NOTE THAT YOU
 ARE WELCOME TO PROCEED THROUGH THE PUBLIC HEARING
 PROCESS TO CITY COMMISSION; HOWEVER, STAFF WILL BE
 RECOMMENDING DENIAL OF THE REQUEST AS CURRENTLY
 PROPOSED. THE LATEST ROUND OF RESPONSES INCLUDES ITEMS
 WHICH MUST BE PROVIDED AND CORRECTED PRIOR TO BEING
 SCHEDULED FOR PLANNING BOARD, REGARDLESS OF THE
 BUILDING DESIGN (EXAMPLE: PARKING LOT CORRECTIONS).
  
 BUILDING PLACEMENT
  
 4) THERE IS A DIMENSION TAG ON SHEET G-201 THAT NOW
 SHOWS A 14-FOOT 8-INCH SETBACK ALONG DIANA PLACE. THE
 BUILDING MAY NOT BE CLOSER THAN 15 FEET TO THE PROPERTY
 LINE.
  
 5) CITY STAFF HAS REVIEWED THE LATEST SIDEWALK AND
 LANDSCAPE CONFIGURATION ALONG DIANA PLACE. THANK YOU
 FOR SHOWING THE PARALLEL PARKING CONFIGURATION.
 A. THE SIDEWALK NEEDS TO BE MOVED CLOSER TO THE
 TOWNHOUSES TO PROVIDE FOR A LARGER LANDSCAPE AREA ALONG
 THE CURB TO PROVIDE A LARGER AREA FOR ROOT GROWTH AS
 WELL AS TO MOVE THE TREES FURTHER AWAY FROM THE DOOR
 SWING.
 B. THE WESTERNMOST TOWNHOUSES, WITH A FFE OF 9 FEET ARE
 BELOW THE ROADWAY ELEVATION, WHICH IS A PROBLEM.
 C. SOME OF THE GRADE CHANGE BETWEEN THE TOWNHOUSE
 COURTYARDS BEING SET AT CLOSE TO THE 9-FOOT FFE AND THE
 ROADWAY ARE VERY STEEP. IT MAY BE BEST TO HAVE STEPS
 DOWN FROM THE TOWNHOUSES TO A LOWER COURTYARD IN ORDER
 TO MAKE UP THE GRADE CHANGE, SIMILAR TO HOW THE FLAGLER
 TERRACE AND DOG PARK ARE HANDLED.
  
 6) AT THE SOUTHWEST CORNER OF THE SITE, IS IT POSSIBLE
 TO CONNECT THE EXISTING CROSSWALK DIRECTLY TO THE NEW
 EAST/WEST SIDEWALK? IS THE STEEP SWALE NECESSARY?
  
 7) UPDATED COMMENT: THE TWO NEW TREES PROVIDED ADJACENT
 TO THE CANOPY AT THE SOUTH ENTRANCE, INCLUDING SPECIES
 AND SIZE, ARE NOT SHOWN ON SHEET LG-3.1. SINCE THESE
 TREES ARE SHOWN ON THE SITE, THEY ARE NOT TO BE
 INCLUDED ON SHEET LG-3.2, THE DIANA ROAD IMPROVEMENTS.
 STAFF IS UNABLE TO VERIFY THAT THE 10-FOOT DEPTH WILL
 NOT INTERFERE THE TREES, NOR IF THE SPECIES IS
 APPROPRIATE FOR THE AREA IN WHICH THEY ARE INSTALLED.
  
 8) REPEAT COMMENT: PROVIDE THE HEIGHTS OF THE CAFE
 AWNINGS FROM GRADE.
  
 ELEVATIONS
  
 9) REPEAT COMMENT: THE EAST ELEVATION AT THE PARK IS
 NOT ACCURATE. THE GREEN WALL SHOWN ON THE ELEVATION
 DOES NOT HAVE THE STEPS UP TO THE TERRACE ACCURATELY
 SHOWN. ADDITIONALLY, STAFF IS UNABLE TO MATCH UP HOW IT
 ALIGNS WITH THE SITE PLAN. THE ELEVATION MAKES THIS
 WALL APPEAR TO BE CURVING, YET THIS IS NOT REFLECTED ON
 THE PLANS.
  
 PARKING
  
 10) REPEAT COMMENT: THE ADA PARKING SPACE DETAIL
 (ACCESSIBLE AND VAN ACCESSIBLE) ON SHEET A-054 DO NOT
 CONFORM TO CITY STRIPING STANDARDS. THE CITY STANDARD
 DETAIL HAS BEEN SENT TO TYLER WOOLSEY. THE CITY
 REQUIRES 16 INCHES BETWEEN STALL DEMARCATION LINES FOR
 ALL SPACES.
  
 11) REPEAT COMMENT: PROVIDE THE DIMENSIONS FOR THE
 BICYCLE RACK PAD ALONG SOUTH OLIVE. THE DEPTH MUST BE
 AT LEAST SIX FEET AND THE WIDTH IS BASED ON THE NUMBER
 OF RACK ELEMENTS. THE DIMENSIONS NEED TO BE SHOWN ON A
 PLAN (SITE, CIVIL, OR HARDSCAPE) AND THE DETAIL FOR THE
 SPECIFIC ALIGNMENT NEEDS TO BE ON A DETAIL SHEET. THE
 GENERIC DETAIL IS NOT SUFFICIENT. NOTE: THE BICYCLE
 PARKING AT THE CAFE IS NOT SHOWN ON THE HARDSCAPE PLAN.
  
 12) REPEAT COMMENT: PROVIDE THE DETAILS OF THE BICYCLE
 RACKS THAT WILL BE USED WITHIN THE BICYCLE STORAGE
 ROOMS. THE BICYCLE STORAGE ROOMS MUST SHOW THE ACCURATE
 RACKS AND THE DIMENSIONS REQUIRED BASED ON THE TYPE OF
 RACKS.
  
 13) REPEAT COMMENT: YOU MUST HAVE BICYCLE PARKING FOR
 GUESTS (VISITORS) NEAR ONE OF THE GUEST ACCESSIBLE
 ENTRANCES TO THE BUILDING. THE BICYCLE RACK BY THE CAFE
 IS NOT NEAR AN ENTRANCE TO THE RESIDENTIAL PORTION OF
 THE BUILDING THAT A GUEST CAN USE. IDENTIFY THE
 ENTRANCE(S) THAT ARE GUEST ACCESSIBLE AND PROVIDE AT
 LEAST ONE BICYCLE RACK, WITH PAD DIMENSIONS, ADJACENT
 TO THAT ENTRANCE. THE PLANS DO NOT INDICATE WHICH
 ENTRANCES ARE GUEST ACCESSIBLE.
  
 14) THERE ARE ONLY 108, NOT 109 RESIDENTIAL EV SPACES
 SHOWN. THERE IS TO BE ONE PER DWELLING UNIT.
  
 15) THE GOAL IS TO ENSURE THAT EVERY UNIT OWNER HAS EV
 CAPABILITY. WHILE YOU HAVE SHOWN 108 (SHORT 1)
 RESIDENTIAL EV STATIONS, HOW WILL YOU ENSURE THAT
 PARKING IS ASSIGNED SO THAT EACH UNIT GETS AN EV
 RECEPTACLE? IT WOULD SEEM STRANGE THAT IF A UNIT OWNER
 HAS TWO SPACES, THEY WOULD BE ON DIFFERENT FLOORS,
 WHICH WOULD NEED TO BE THE CASE SINCE SHEET A-100 SHOWS
 NO SPACES FOR RESIDENTIAL EV.
  
 LOADING/ACCESS
  
 16) REPEAT COMMENT: THE CITY'S ENGINEERING SERVICES
 DEPARTMENT NEEDS TO APPROVE THE USE OF CURRIE CRESCENT
 FOR MANEUVERING PRIOR TO THE CASE PROCEEDING THROUGH
 THE PUBLIC HEARING PROCESS. CALL TO DISCUSS IS
 SCHEDULED.
  
 17) REPEAT COMMENT: THE CITY'S ENGINEERING SERVICES
 DEPARTMENT NEEDS TO APPROVE THE NUMBER OF ACCESS POINTS
 TO CURRIE CRESCENT AND THE SEPARATION OF ACCESS POINTS
 TO THE CASE PROCEEDING THROUGH THE PUBLIC HEARING
 PROCESS. CALL TO DISCUSS IS SCHEDULED.
  
 WALLS
  
 18) UPDATED COMMENT: THE PLANS SHOW A FENCE ALONG DIANA
 PLACE AT THE TOWNHOUSE COURTYARDS.
 A. NO DETAILS ON THE MATERIAL OF THE CONCEALED FENCE
 WERE PROVIDED.
 B. THE MAXIMUM 5-FOOT HEIGHT OF THE DECORATIVE METAL,
 PICKET GATE IS NOT STATED ON THE PLANS.
  
 19) REPEAT COMMENT: THE PLANS DO NOT CALL OUT WHAT
 HEDGE MATERIAL WILL SCREEN THE 4-FOOT-TALL FENCE. THE
 RESPONSE STATES THAT THE MATERIAL WILL BE A PODOCARPUS
 HEDGE; HOWEVER, NO TAGS ON SHEET LG-3.1 DO NOT POINT TO
 THE HEDGE OR ANY FEATURE WITH HE SAME HATCHING PATTERN
 AS THE HEDGE. SHEET G-201 NEEDS TO BE CORRECTED TO
 STATE MAXIMUM 5-FOOT HEDGE ALONG THE SOUTH COURTYARDS.
  
 LANDSCAPE
  
 20) REPEAT COMMENT: SHEET LG-3.1 SHOWS PLANTING BEDS
 AGAINST THE WEST SIDE OF THE BUILDING WHICH ARE NOT
 REFLECTED ON THE CIVIL SHEETS OR SITE PLAN. ALL PLANS
 MUST SHOW THE SAME, ACCURATE CONDITIONS.
  
 DEVELOPMENT REGULATION: FPL EASEMENT WHICH BISECTS THE
 PROPOSED BUILDING LOCATION WILL NEED TO BE RELEASED BY
 FPL AND ALL OVERHEAD LINES MUST BE REMOVED. ANY NEW
 UTILITY LINES MUST BE RELOCATED UNDERGROUND.
  
 DEVELOPMENT REGULATION: THE IMPROVEMENTS TO THE CITY
 OWNED PARCEL SOUTH OF THE PROPERTY, INCLUDING THE
 SIDEWALK, WALKWAYS AND LANDSCAPE, WILL BE THE
 MAINTENANCE RESPONSIBILITY OF THE FLAGLER TOWERS
 PROJECT. MAINTENANCE AGREEMENTS AND EASEMENTS WILL BE
 REQUIRED.
  

Review Stop Z ZONING
Rev No 2 Status F Date 07-26-2021 Cont ID  
Sent By eschneid Date 07-26-2021 Time 17:13 Rev Time 8.00
Received By eschneid Date 07-20-2021 Time 08:45 Sent To  
Notes
2021-07-26 17:14:29CASE NO. PB 1857B -1ST RESUBMITTAL REVIEW
 FLAGLER TOWERS
 1315 SOUTH FLAGLER DRIVE
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446,
 [email protected]
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF THREE
 (3) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - THE PPRC COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND
 SUBMITTED TO THE PLANNING DIVISION BY 5 PM ON FRIDAY,
 JULY 30, 2021, TO BE ELIGIBLE TO BE SCHEDULED FOR THE
 SEPTEMBER 21, 2021 PLANNING BOARD MEETING.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE COMMENTS WITHIN 60 DAYS FROM
 THE DATE OF ISSUANCE (BY AUGUST 10, 2021), THE PLANNING
 DIVISION MAY NOTIFY THE APPLICANT THAT THE CASE IS
 CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL REQUIRE
 A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE ASSESSED A RESUBMITTAL
 FEE. SUCH FEE IS 20% OF THE ORIGINAL APPLICATION FEE
 ($600).
  
 - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 1) REPEAT COMMENT: THANK YOU FOR PROVIDING THE TRAFFIC
 STUDY THAT STATES THAT THE PROJECT DOES NOT GENERATE A
 SIGNIFICANT IMPACT. HOWEVER, YOU ARE STILL REQUIRED TO
 PROVIDE A PALM BEACH COUNTY TPS APPROVAL LETTER.
  
 2) UPDATED COMMENT: STAFF DOES NOT OBJECT TO THE
 PROPOSED SIDEWALK AND WALKWAYS TO THE TOWNHOUSE UNITS
 BEING INSTALLED AND THE TREES BEING REPLACED ON THE
 CITY OWNED PARCEL SOUTH OF THE PROJECT. THE PARCEL IS
 SUBJECT TO A DEED RESTRICTION. IN ORDER TO ENSURE THAT
 THE PROPOSED CHANGES DO NOT IMPACT THE DEED
 RESTRICTION, PRIOR TO SCHEDULING THE APPLICATION FOR
 THE PLANNING BOARD MEETING, YOU MUST PROVIDE WRITTEN
 CONSENT/NO OBJECTION FROM THE LAKE WORTH PIONEERS
 ASSOCIATION AND THE NORTON GALLERY AND SCHOOL OF ART,
 INC., TO THE CITY.
  
 3) REPEAT COMMENT: THANK YOU FOR PROVIDING THE FAA
 APPLICATION NUMBERS. YOU ARE REQUIRED TO SUBMIT THE FAA
 APPROVAL FOR THE PROPOSED TOWER PRIOR TO SCHEDULING
 THIS CASE FOR PLANNING BOARD.
  
 4) REPEAT COMMENT: STAFF WILL NOT SUPPORT THE BUILDING
 IN EXCESS OF 300 FEET IN HEIGHT. PLEASE NOTE THAT YOU
 ARE WELCOME TO PROCEED THROUGH THE PUBLIC HEARING
 PROCESS TO CITY COMMISSION; HOWEVER, STAFF WILL BE
 RECOMMENDING DENIAL OF THE REQUEST AS CURRENTLY
 PROPOSED. THE LATEST ROUND OF RESPONSES INCLUDES ITEMS
 WHICH MUST BE PROVIDED AND CORRECTED PRIOR TO BEING
 SCHEDULED FOR PLANNING BOARD, REGARDLESS OF THE
 BUILDING DESIGN (EXAMPLE: PARKING LOT CORRECTIONS).
  
 BUILDING PLACEMENT
  
 5) STAFF HAS REASSESSED THE MEASURE POINTS TO DETERMINE
 BASIS FOR THE NORTHERN SETBACK WAIVERS. LEVEL WILL BE
 15 FEET, LEVELS 2 THROUGH 4 (PODIUM) WILL BE 41 FEET
 AND THE NORTHERN TOWER WILL BE 41 FEET.
  
 6) THANK YOU FOR PROVIDING THE TWO CROSS SECTIONS EAST
 OF THE RESIDENT ENTRANCE ALONG DIANA PLACE. PLEASE
 PROVIDE ONE THAT INCLUDES THE ANGLED PARKING SPACES AND
 ONE THAT INCLUDES THE EASTERNMOST TOWNHOUSE SO THAT
 STAFF CAN SEE WHAT THE IMPACT OF CHANGING THE GRADE HAS
 AT THESE TWO LOCATIONS.
  
 7) STAFF HAS REVIEWED THE RESPONSE TO THE COMMENT
 REGARDING PUSHING THE SOUTHERN TOWER BACK FROM THE
 FACADE OF THE PODIUM. PROVIDE A CONTEXT ELEVATION FROM
 SOUTH FLAGLER DRIVE FACING EAST WHICH SHOWS HOW THE
 PROPOSED BUILDING INTERACTS WITH THE PARK AND THE
 NORTON MUSEUM. STAFF HAS INCLUDED THE VIEWPOINT IN THE
 COMMENT ADDENDUM SENT AS A SEPARATE FILE.
  
 8) UPDATED COMMENT: THANK YOU FOR CLARIFYING THAT THE
 FIVE (5) FOOT BALCONY ENCROACHMENT IS ONLY ON LEVEL 26
 AND 27. THIS WILL BE THE SPECIFIC WAIVER. STAFF WILL
 NOT SUPPORT A BLANKET WAIVER FOR ALL THE BALCONIES ON
 THE SOUTH FA?ADE TO EXTEND FIVE (5) FEET FROM THE
 BUILDING SINCE THIS IS NOT HOW THE DRAWINGS ARE BEING
 PRESENTED. THE WEST COLOR ELEVATION FAILS TO SHOW THE
 BALCONY. THE ELEVATION DRAWINGS MUST MATCH THE FLOOR
 PLANS.
  
 9) PROVIDE THE DEPTH OF THE TERRACE ON THE SOUTH SIDE
 OF THE TOWER ON LEVEL 10. THIS TERRACE ENCROACHES
 FURTHER INTO THE SOUTHERN SETBACK THAN THE OTHER
 TERRACES FOR WHICH DIMENSIONS WERE PROVIDED.
  
 10) PROVIDE THE DEPTH OF THE TRELLIS FEATURES THAT
 OVERHANG THE BUILDING EDGES.
  
 11) UPDATED COMMENT: EVEN THOUGH THE CANOPY AT THE
 SOUTH ENTRANCE WAS REDUCED IN SIZE, IT STILL INTERFERES
 WITH THE SPECIMEN OAK TREE THAT IS BEING PROPOSED AT
 THIS LOCATION. THE 10-FOOT DEPTH WILL INTERFERE WITH
 ANY TREE INSTALLED AS SHOWN.
  
 12) PROVIDE THE HEIGHTS OF THE CANOPIES AND AWNINGS
 FROM GRADE.
  
 13) REPEAT COMMENT: THE SITE OPEN SPACE IS INCORRECTLY
 CALCULATED. THE AREAS SUCH AS THE MOTOR COURT AND THE
 DRIVE WHERE IT IS ABOVE THE FIRST LEVEL OF THE BUILDING
 IS NOT OPEN SPACE IT IS THE BUILDING ROOF OF THE
 FIRST-FLOOR PARKING.
  
 14) WHAT DOES THE 3-FOOT SETBACK ENCROACHMENT NOTE AT
 THE FLAGLER DRIVE DRIVEWAY ENTRANCE REFER TOO?
  
 15) WHAT OCCURS IN THE ROOM BEHIND THE TERRACE TO THE
 WEST OF THE FLAGLER DRIVE RESIDENT PARK? IS THERE AN
 OPPORTUNITY TO HAVE THIS AS A ROOM THAT RESIDENTS CAN
 USE TO ENTERTAIN AS IT OVERLOOKS THE TERRACE AND THE
 PARK? IS THERE AN OPPORTUNITY TO HAVE WINDOWS? SEE
 ADDENDUM FOR LOCATION.
  
 16) THE SIDEWALK ALONG FLAGLER DRIVE WHERE IT MEETS
 FORTE MUST BE THE SAME WIDTH AS THE SIDEWALK THAT FORTE
 IS INSTALLING, NOT FIVE FEET AS PROPOSED. THIS NEEDS TO
 BE CLEARLY SHOWN ON THE PLANS.
  
 17) EXPLAIN THE ENTRANCES TO THE TOWNHOUSES. ONE UNIT
 APPEARS TO HAVE TWO MAIN ENTRANCES AND OTHERS SEEM TO
 HAVE THE INTERNAL WALKWAYS THAT CROSS BETWEEN UNIT
 COURTYARDS. PROVIDE ACCURATE CONFIGURATIONS. SEE
 ADDENDUM FOR LOCATION.
  
 ELEVATIONS
  
 18) PROVIDE THE ELEVATION DIMENSION LINES ON THE ACTUAL
 ELEVATION DRAWINGS. THE STACKING DIAGRAM DOES NOT
 PROVIDE THE DETAILS THAT ARE SHOWN ON THE ELEVATIONS.
  
 19) THE EAST ELEVATION AT THE PARK IS NOT ACCURATE. THE
 PARKING RAMP NOT SHOWN, AND THE DOORS AND WALLS DO NOT
 SEEM ACCURATE WHEN COMPARED TO THE SITE AND LANDSCAPE
 PLANS.
  
 PARKING
  
 20) THE PROJECT NOW CONTAINS EXCESS PARKING SPACES;
 HOWEVER, STAFF REQUIRES A BETTER DESCRIPTION OF HOW THE
 SPACES IN EACH GARAGE WILL BE ACCESSED AND WHO HAS
 ACCESS TO THE SPACES (VALET VS. SELF-PARK). UNTIL STAFF
 HAS A FULL UNDERSTANDING OF HOW THE PARKING WILL
 FUNCTION, WE ARE UNABLE TO GIVE AN ANSWER TO YOUR
 QUESTION, "CAN WE COUNT THE TANDEM SPACES ON THE SECOND
 GARAGE LEVEL TOWARDS MEETING OUR CODE REQUIREMENT IF WE
 PROVIDE A VALET PARKING PLAN AND THE SPACES ARE USED
 FOR VALETING THE STAFF, VISITORS, AND CAFE PARKING?"
 PLEASE PROVIDE A BREAKDOWN LIKE THE TABLE PROVIDED IN
 THE ADDENDUM. NOTE: IT DOES NOT NEED TO REPLACE ANY
 TABLES YOU CURRENTLY PROVIDE.
  
 21) REPEAT COMMENT: WHERE ARE THE GUEST PARKING SPACES
 AND HOW ARE THEY ACCESSED (ARE THEY REQUIRED TO BE
 VALET OR MAY THEY SELF-PARK)? THE 11 REQUIRED GUEST
 PARKING SPACES MUST BE LABELED ON THE ON THE PLANS.
  
 22) ADDITIONAL ADA COMMENTS FROM ROBERT BROWN REGARDING
 THE SECOND LEVEL PARKING (ONLY AS CAFE CUSTOMERS) AND
 GUEST PARKING:
  
 A. SINCE A TOTAL OF 67 PARKING SPACES ARE BEING
 PROVIDED EXCLUSIVELY FOR CAFE CUSTOMERS, NO MATTER
 WHETHER THOSE ARE SELF-PARKING OR VALET, 3 ACCESSIBLE
 PARKING SPACES MUST BE PROVIDED FOR CAF? CUSTOMERS AND
 THE USERS MUST BE ABLE TO SELF-PARK IF THEY WANT TO.
 THEIR VEHICLE MAY HAVE BEEN MODIFIED TO THE POINT WHERE
 A VALET CANNOT OPERATE IT.
 B. SINCE THE SPACES ARE EXCLUSIVELY FOR CAFE CUSTOMERS,
 ONE OF THE ACCESSIBLE SPACES MUST BE VAN ACCESSIBLE.
 C. THE USERS OF THE ACCESSIBLE PARKING SPACES MUST BE
 ABLE TO SELF-PARK IF THEY WANT TO. THEIR VEHICLE MAY
 HAVE BEEN MODIFIED TO THE POINT WHERE A VALET CANNOT
 OPERATE IT.
 D. WHEN THE GUEST PARKING SPACES ARE DESIGNATED ON THE
 PLANS, IF THEY ARE EXCLUSIVELY FOR GUESTS, THEY MUST
 INCLUDE ACCESSIBLE AND VAN ACCESSIBLE PARKING IN
 NUMBERS ACCORDING TO HOW MANY PARKING SPACES ARE
 DESIGNATED EXCLUSIVELY FOR GUEST PARKING.
  
 23) THE COMMENT RESPONSE STATES THAT THE LEVEL 3
 PARKING AREA IS ONLY FOR RESIDENTS. DOES THIS MEAN THAT
 THIS IS A SELF-PARK ONLY PARKING AREA?
  
 24) TANDEM PARKING SPACES ARE SHOWN ON LEVEL 3. WHO
 USES THESE TANDEM SPACES?
  
 25) ON THE RESIDENT PARKING LEVELS, DO UNIT OWNERS OWN
 DESIGNATED PARKING SPACES?
  
 26) REPEAT COMMENT: THE ADA PARKING SPACE DETAIL
 (ACCESSIBLE AND VAN ACCESSIBLE) ON SHEET A-054 DO NOT
 CONFORM TO CITY STRIPING STANDARDS. IF YOU REQUIRE THE
 CITY STANDARD DETAIL, PLEASE LET STAFF KNOW AND IT WILL
 BE PROVIDED.
  
 PARKING COUNTS:
  
 27) SHEET A-100 BASEMENT LEVEL - CORRECT THE ERRORS
 IDENTIFIED BELOW:
  
 A. THE TABLE LISTS 168 TOTAL PARKING SPACES, YET THE
 PARKING TAGS SHOW 169 PARKING SPACES, WHICH VERIFIES
 STAFF'S COUNT OF THE NUMBER OF PARKING SPACES.
 THERE ARE ONLY 14 COMPACT SPACES PROVIDED, NOT 15 AS
 STATED IN THE TABLE.
 THERE ARE 147 STANDARD PARKING SPACES PROVIDED, NOT 145
 AS STATED IN THE TABLE.
  
 B. THE PARKING BY TYPE TABLE LISTS 277 STANDARD PARKING
 SPACES, YET STAFF HAS COUNTED 325 STANDARD PARKING
 SPACES.
  
 28) SHEET A-102 LOBBY LEVEL - CORRECT THE ERRORS
 IDENTIFIED BELOW:
  
 A. THE TABLE LISTS 43 TOTAL PARKING SPACES, YET STAFF
 HAS COUNTED 68 PARKING SPACES.
 THERE ARE 42 STANDARD PARKING SPACES PROVIDED, NOT 17
 AS STATED IN THE TABLE.
  
 B. THE BACK-UP DISTANCE BETWEEN SPACES 325 AND 344 ON
 LEVEL 2 PARKING DOES NOT CONTAIN THE CODE MINIMUM 24
 FEET AISLE, SO ONE OF THE SPACES MUST BE REMOVED (OR
 CONVERTED TO A COMPACT SPADE).
  
 29) SHEET A-103 LEVEL 3 - CORRECT THE ERRORS IDENTIFIED
 BELOW:
  
 A. THE TABLE LISTS 62 TOTAL PARKING SPACES, YET STAFF
 HAS COUNTED 84 PARKING SPACES.
 THERE ARE 61 STANDARD PARKING SPACES PROVIDED, NOT 40
 AS STATED IN THE TABLE.
 THERE IS 1 COMPACT PARKING SPACE PROVIDED THAT IS NOT
 ACCOUNTED FOR IN THE TABLE.
  
 B. THE PARKING SPACE NUMBERING ON SHEET A-103 STARTS AT
 351 INSTEAD OF 347 (NEXT NUMBER IN SEQUENCE FROM SHEET
 A-102) AND THUS THE BUILDING IS SHOWN TO HAVE 434
 PARKING SPACES, WHICH IS NOT ACCURATE.
  
 30) THERE ARE 430 TOTAL PARKING SPACES SHOWN ON THE
 PLANS (INCLUDES 49 TANDEM SPACES). NOTE: THE VARIOUS
 TABLES ALTERNATE BETWEEN COUNTING AND NOT COUNTING THE
 TANDEM SPACES IN THE TOTAL. IT MAY BE BEST TO HAVE A
 TOTAL OF THE SPACES THAT COUNT TOWARD THE PARKING
 REQUIREMENT AND THEN LIST THE TANDEM SPACES ON EACH
 FLOOR BELOW THE TOTAL AS ADDITIONAL AVAILABLE PARKING.
  
 31) THANK YOU FOR PROVIDING BICYCLE PARKING; HOWEVER:
  
 A. PROVIDE THE DIMENSIONS FOR THE BICYCLE RACK PAD
 ALONG SOUTH OLIVE. THE DEPTH MUST BE AT LEAST SIX FEET
 AND THE WIDTH IS BASED ON THE NUMBER OF RACK ELEMENTS.
 B. PROVIDE THE DETAILS OF THE BICYCLE RACKS THAT WILL
 BE USED WITHIN THE BICYCLE STORAGE ROOMS. THE BICYCLE
 STORAGE ROOMS MUST SHOW THE ACCURATE RACKS AND THE
 DIMENSIONS REQUIRED BASED ON THE TYPE OF RACKS.
 C. REPEAT COMMENT: YOU MUST HAVE BICYCLE PARKING FOR
 GUESTS (VISITORS) NEAR ONE OF THE GUEST ACCESSIBLE
 ENTRANCES TO THE BUILDING. THE BICYCLE RACK BY THE CAFE
 IS NOT NEAR AN ENTRANCE TO THE RESIDENTIAL PORTION OF
 THE BUILDING THAT A GUEST CAN USE. IDENTIFY THE
 ENTRANCE(S) THAT ARE GUEST ACCESSIBLE AND PROVIDE AT
 LEAST ONE BICYCLE RACK, WITH PAD DIMENSIONS, ADJACENT
 TO THAT ENTRANCE.
  
 32) UPDATED COMMENT: PROVIDE MORE DETAIL ON THE
 PROPOSED PRE-WIRING OF THE BUILDING FOR EV CHARGER
 INSTALLATION. WHILE STAFF APPRECIATES THAT YOU HAVE
 SHOWN 4 EV SPACES, NO DETAILS ON HOW THESE ACTUALLY
 FUNCTION WERE PROVIDED, TO INCLUDE WHERE THE CHARGING
 UNITS WOULD BE PLACED. PLEASE BE AWARE THAT AT LEAST
 ONE ADA PARKING SPACE WILL NEED TO BE EV COMPATIBLE.
 BELOW ARE THE REQUIREMENTS FOR EV FACILITIES BASED ON
 THE FORTE PROJECT REQUIREMENTS AND ARE THE EXPECTATIONS
 FOR THIS PROJECT. PLEASE NOTE THAT IT MAKES AVAILABLE
 LEVEL I CHARGING FOR EVERY UNIT OWNER WITH THE
 FACILITIES IN PLACE TO UPGRADE TO A LEVEL 2 CHARGER.
  
 CHARGING STATIONS: ELECTRONIC VEHICLE INFRASTRUCTURE
 MUST BE INSTALLED IN ACCORDANCE WITH PERMITS ISSUED BY
 THE CITY?S BUILDING DIVISION AS FOLLOWS:
  
 A. ONE LEVEL 1 FULL CIRCUIT INSTALLATION IS REQUIRED
 FOR EACH UNIT'S REQUIRED PARKING SPACES (109 TOTAL).
 EACH CIRCUIT IS REQUIRED TO BE A 20 AMP, 120 VOLT
 CIRCUIT, WITH RACEWAY/CONDUIT, WIRING, RECEPTACLE AND
 OVERCURRENT PROTECTION TO CODE. THE DEVELOPER SHALL
 INSTALL OVERSIZED RACEWAY/CONDUIT OR ADDITIONAL
 RACEWAY/CONDUIT, AS APPROVED BY THE CITY'S BUILDING
 DIVISION, THAT WILL PROVIDE THE ABILITY OF INDIVIDUAL
 UNIT OWNERS OR THE HOMEOWNERS? ASSOCIATION TO INSTALL
 THE WIRING, RECEPTACLE AND OVERCURRENT PROTECTION TO
 CODE TO ALLOW PARKING SPACES TO BE UPGRADED TO A LEVEL
 2, 40 AMP, 208/240 VOLT CIRCUIT. THE DEVELOPER SHALL
 PROVIDE SPACE TO INSTALL AN ADDITIONAL ELECTRICAL PANEL
 TO ACCOMMODATE LEVEL 2 FULL CIRCUIT UPGRADES.
  
 B. TWO LEVEL 2 FULL CIRCUIT INSTALLATIONS ARE REQUIRED
 FOR THE GUEST PARKING SPACES. EACH CIRCUIT IS REQUIRED
 TO BE A 40 AMP, 208/240 VOLT CIRCUIT, WITH
 RACEWAY/CONDUIT, WIRING, RECEPTACLE AND OVERCURRENT
 PROTECTION TO CODE. ONE DUAL PORT ELECTRIC VEHICLE
 CHARGER MUST BE INSTALLED FOR THE GUEST PARKING SPACES
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY
 FOR THE BUILDING.
  
 C. ONE LEVEL 1 FULL CIRCUIT INSTALLATION IS REQUIRED
 FOR FOUR (4) OF THE EMPLOYEE PARKING SPACES. EACH
 CIRCUIT IS REQUIRED TO BE A 20 AMP, 120 VOLT CIRCUIT,
 WITH RACEWAY/CONDUIT, WIRING, RECEPTACLE AND
 OVERCURRENT PROTECTION TO CODE.
  
 D. FOUR LEVEL 2 FULL CIRCUIT INSTALLATIONS ARE REQUIRED
 FOR THE VALET PARKING SPACES. EACH CIRCUIT IS REQUIRED
 TO BE A 40 AMP, 208/240 VOLT CIRCUIT, WITH
 RACEWAY/CONDUIT, WIRING, RECEPTACLE AND OVERCURRENT
 PROTECTION TO CODE. TWO DUAL PORT ELECTRIC VEHICLE
 CHARGERS MUST BE INSTALLED FOR THE VALET PARKING SPACES
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY
 FOR THE BUILDING. THE VALET SPACES CONTAINING THE
 ELECTRIC VEHICLE CHARGERS MAY NOT BE SOLD OR LEASED TO
 RESIDENTS AND MUST REMAIN AVAILABLE FOR CHARGING
 VEHICLES.
  
 LOADING/ACCESS
  
 33) UPDATED COMMENT: THE NORTH SIDE OF CURRIE CRESCENT
 HAS ON-STREET PARALLEL PARKING SPACES. THE TRUCK
 TURNING DIAGRAM SHOWS THE TRUCK USING THE FULL WIDTH OF
 CURRIE CRESCENT, WHICH IS IMPOSSIBLE IF A CAR IS PARKED
 IN THE PARALLEL SPACES. THE CITY'S PARKING DEPARTMENT
 DOES NOT SUPPORT THE REMOVAL OF PARKING SPACES IN THIS
 AREA AS THE PARKING SPACES SEE SIGNIFICANT USAGE. THE
 PARKING DIVISION WILL SUPPORT THE RELOCATION OF THE
 FIVE EXISTING PARKING SPACES TO THE NORTH SIDE OF DIANA
 PLACE. YOU NEED TO SHOW THE RELOCATED PARKING SPACES
 ALONG DIANA PLACE. SUGGESTION: RECONFIGURE THE PARKING
 ALONG THE NORTH SIDE OF DIANA PLACE TO BE A PARALLEL
 CONFIGURATION. THIS WOULD ALLOW MORE ROOM FOR TREES AT
 THE WEST END OF ROAD (WHERE THE ANGLE PARKING CURRENTLY
 EXISTS), PUSH CARS (AND THEIR HEADLIGHTS AT NIGHT)
 FURTHER AWAY FROM THE TOWNHOUSE UNITS ON THE WEST END
 OF THE DEVELOPMENT, AND WOULD PROVIDE PARKING SPACES IN
 FRONT OF ALL OF THE TOWNHOUSE UNITS THAT COULD BE
 UTILIZED BY UNIT OWNER GUESTS WHO DO NOT WANT TO PARK
 IN THE GARAGE.
  
 34) REPEAT COMMENT: THE CITY'S ENGINEERING SERVICES
 DEPARTMENT NEEDS TO APPROVE THE USE OF CURRIE CRESCENT
 FOR MANEUVERING PRIOR TO THE CASE PROCEEDING THROUGH
 THE PUBLIC HEARING PROCESS. CALL TO DISCUSS IS
 SCHEDULED.
  
 35) REPEAT COMMENT: THE CITY'S ENGINEERING SERVICES
 DEPARTMENT NEEDS TO APPROVE THE NUMBER OF ACCESS POINTS
 TO CURRIE CRESCENT AND THE SEPARATION OF ACCESS POINTS
 TO THE CASE PROCEEDING THROUGH THE PUBLIC HEARING
 PROCESS. CALL TO DISCUSS IS SCHEDULED.
  
 WALLS
  
 36) PROVIDE THE DETAILS OF THE DECORATIVE THREE-FOOT
 WALL ALONG THE VEHICULAR USE AREA ON THE NORTH PROPERTY
 LINE AND THE RETAINING WALLS.
  
 37) THE PLANS SHOW A FENCE ALONG DIANA PLACE AT THE
 TOWNHOUSE COURTYARDS. PLEASE PROVIDE DETAILS OF THE
 TYPE OF FENCE AND THE COLUMNS AND GATES. SHEET LG-1.1
 CALLS OUT THE COLUMNS AND GATES AS MAXIMUM 6 FEET. THE
 PLANS DO NOT CALL OUT WHAT HEDGE MATERIAL WILL SCREEN
 THE 4-FOOT-TALL FENCE. IN ORDER TO PROVIDE A
 COMFORTABLE PEDESTRIAN EXPERIENCE ALONG THE NEW DIANA
 PLACE WALKWAY, THE GATES NEED TO BE A PICKET STYLE AND
 THE HEDGE AND GATES SHALL NOT EXCEED 5 FEET IN HEIGHT.
  
 38) PROVIDE THE DETAILS OF THE STONE PLINTH WITH
 DECORATIVE FENCE LISTED ON THE HARDSCAPE PLAN.
  
 SIGNAGE
  
 39) ONE OF THE COMMENT RESPONSES STATED THAT THERE
 WOULD BE DIRECTIONAL SIGNAGE TO GUIDE DRIVING CUSTOMERS
 TO THE CAFE PARKING. PLEASE REVIEW THE SIGNAGE
 ALLOWANCE FOR PARKING AREA IDENTIFICATION SIGNS TO
 VERIFY WHAT SIZE AND SETBACKS ARE PERMITTED. PLEASE
 NOTE THAT A BUSINESS NAME/LOGO IS NOT PERMITTED ON
 PARKING AREA DIRECTIONAL SIGNS BY RIGHT. IF A SIGN THAT
 DOES NOT CONFORM THE BY RIGHT ALLOWANCE IS BEING
 CONTEMPLATED, THEN A SIGN PROGRAM THAT WAIVES THE CODE
 PROVISIONS MUST BE APPROVED BY THE CITY COMMISSION
 EITHER AS PART OF THIS APPLICATION OR A SEPARATE FUTURE
 MAJOR PLANNED DEVELOPMENT AMENDMENT. IF IT WILL BE
 REVIEWED NOW, THE DETAILS MUST BE SUBMITTED FOR STAFF
 REVIEW.
  
 40) WHILE REVIEWING THE RESPONSE THAT GENERATED THE
 PREVIOUS COMMENT, STAFF NOTED THAT NO SIGNAGE HAS BEEN
 PROPOSED FOR THE PROPERTY. IT IS NOT REQUIRED THAT YOU
 PROVIDE SIGN PLANS WITH THE APPLICATION; HOWEVER, THE
 FUTURE SIGN PLANS MUST THEN COMPLY WITH ALL CODE
 PROVISIONS. ANY WAIVERS OR DEVIATIONS FROM THE CODE
 PROVISIONS WOULD NEED TO BE APPROVED BY THE CITY
 COMMISSION AS A FUTURE MAJOR PLANNED DEVELOPMENT
 AMENDMENT. ADDITIONALLY, EVEN CODE COMPLIANT
 FREE-STANDING SIGNS ARE CHANGES TO THE SITE PLAN, SO
 THEIR LOCATION WILL REQUIRE A FUTURE MINOR PLANNED
 DEVELOPMENT AMENDMENT.
  
 LANDSCAPE
  
 41) THE LANDSCAPE PLANS NEED TO BE CLEANED UP TO SHOW
 THE FINAL CONDITIONS ONLY. THE CURRENT PLANS INCLUDE
 TREES THAT WILL NO LONGER REMAIN WHEN THE PROJECT IS
 COMPLETED AND STRAY LINEWORK FROM THE EXISTING SITE
 FEATURES (EX. CURBING IN THE NORTHEAST CORNER OF THE
 PLAN WHICH MAKES IT APPEAR THAT THERE IS A WALL ACROSS
 THE ENTRY DRIVE FROM FLAGLER).
  
 42) SHEET LG-3.1 SHOWS THE STORMWATER LINE ALONG THE
 LENGTH OF THE WEST SIDE OF THE BUILDING WHILE SHEET
 C-500 DOES NOT SHOW THE STORMWATER LINE IN THE SAME
 CONFIGURATION. ALL PLANS MUST SHOW THE SAME, ACCURATE
 CONDITIONS.
  
 43) THE CIVIL AND LANDSCAPE PLANS SHOW AN FPL LINE
 ALONG THE FLAGLER DRIVE FRONTAGE. PROVIDE A CROSS
 SECTION SHOWING THE DUCT BANK AND ITS RELATIONSHIP TO
 THE ROOT ZONES FOR THE OAK TREES PROPOSED ALONG FLAGLER
 DRIVE.
  
 44) SHEET LG-3.1 SHOWS PLANTING BEDS AGAINST THE WEST
 SIDE OF THE BUILDING WHICH ARE NOT REFLECTED ON THE
 CIVIL SHEETS OR SITE PLAN. ALL PLANS MUST SHOW THE
 SAME, ACCURATE CONDITIONS.
  
 DEVELOPMENT REGULATION: FPL EASEMENT WHICH BISECTS THE
 PROPOSED BUILDING LOCATION WILL NEED TO BE RELEASED BY
 FPL AND ALL OVERHEAD LINES MUST BE REMOVED. ANY NEW
 UTILITY LINES MUST BE RELOCATED UNDERGROUND.
  
 DEVELOPMENT REGULATION: THE IMPROVEMENTS TO THE CITY
 OWNED PARCEL SOUTH OF THE PROPERTY, INCLUDING THE
 SIDEWALK, WALKWAYS AND LANDSCAPE, WILL BE THE
 MAINTENANCE RESPONSIBILITY OF THE FLAGLER TOWERS
 PROJECT. MAINTENANCE AGREEMENTS AND EASEMENTS WILL BE
 REQUIRED.
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 06-03-2021 Cont ID  
Sent By eschneid Date 06-03-2021 Time 11:50 Rev Time 12.00
Received By eschneid Date 06-01-2021 Time 15:36 Sent To  
Notes
2021-06-03 11:51:56CASE NO. PB 1857B
 FLAGLER TOWERS
 1315 SOUTH FLAGLER DRIVE
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446,
 [email protected]
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF THREE
 (3) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - THE PPRC COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND
 SUBMITTED TO THE PLANNING DIVISION BY 5 PM ON FRIDAY,
 JUNE 25, 2021, TO BE ELIGIBLE TO BE SCHEDULED FOR THE
 AUGUST 17, 2021 PLANNING BOARD MEETING.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THE PPRC MEETING (BY AUGUST 10, 2021),
 THE PLANNING DIVISION MAY NOTIFY THE APPLICANT THAT THE
 CASE IS CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL
 REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($600).
  
 - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 1) THANK YOU FOR PROVIDING THE TRAFFIC STUDY THAT
 STATES THAT THE PROJECT DOES NOT GENERATE A SIGNIFICANT
 IMPACT. HOWEVER, YOU ARE STILL REQUIRED TO PROVIDE A
 PALM BEACH COUNTY TPS APPROVAL LETTER.
  
 2) THE SITE PLAN SHOWS A SIDEWALK AND WALKWAYS TO THE
 TOWNHOUSE UNITS BEING INSTALLED ON THE CITY OWNED
 PARCEL SOUTH OF THE PROJECT. THE PARCEL IS SUBJECT TO A
 DEED RESTRICTION THAT REQUIRES THE NORTON GALLERY AND
 SCHOOL OF ART, INC., TO BE NOTIFIED OF PROPOSED CHANGES
 TO THE PARCEL AND NOT OBJECT TO THE CHANGES. ONCE THE
 FULL SCOPE OF CHANGES TO THE PARCEL ARE FINALIZED
 BETWEEN THE APPLICANT AND STAFF, IT IS YOUR
 RESPONSIBILITY TO PROVIDE WRITTEN CONSENT FROM THE
 NORTON GALLERY AND SCHOOL OF ART, INC., TO THE CITY.
 THE SIDEWALK MUST BE A MINIMUM OF 10 FEET IN WIDTH AND
 IT WILL BE THE FLAGLER TOWERS MAINTENANCE
 RESPONSIBILITY. THERE WILL BE EASEMENTS AND OTHER
 AGREEMENTS REQUIRED FOR THE INSTALLATION OF ANY
 IMPROVEMENTS ON CITY PROPERTY.
  
 3) FPL EASEMENT WHICH BISECTS THE PROPOSED BUILDING
 LOCATION WILL NEED TO BE RELEASED BY FPL AND ALL
 OVERHEAD LINES MUST BE REMOVED. ANY NEW UTILITY LINES
 MUST BE RELOCATED UNDERGROUND.
  
 4) YOU ARE REQUIRED TO SUBMIT THE FFA APPROVAL FOR THE
 PROPOSED TOWER PRIOR TO SCHEDULING THIS CASE FOR
 PLANNING BOARD.
  
 5) PROVIDE THE LEGAL DESCRIPTION IN WORD FORMAT.
  
 6) STAFF WILL NOT SUPPORT A BUILDING IN EXCESS OF 300
 FEET IN HEIGHT. THE PROPOSED 356-FOOT TALL TOWERS DO
 NOT CONTINUE THE PATTERN OF BUILDINGS TRANSITIONING
 DOWN IN HEIGHT AS THEY MOVE SOUTH ALONG SOUTH FLAGLER
 DRIVE AND SOUTH OLIVE AVENUE TOWARD THE EXISTING LOWER
 SCALE RESIDENTIAL NEIGHBORHOODS.
  
 7) SHEET C-300 SHOWS THE SAME AT&T LINE AS REMAINING
 AND BEING REMOVED. ALL PLANS MUST SHOW THE SAME
 ACCURATE CONDITIONS.
  
 BUILDING PLACEMENT
  
 8) BASED ON THE BUILDING DESIGN, YOU ARE SHOWING A
 ZERO-FOOT NORTH SETBACK FOR THE GROUND LEVEL. PLACING
 DIRT AND A RETAINING WALL BETWEEN THE ABOVE GRADE LEVEL
 OF PARKING AND THE PROPERTY LINE TO THE NORTH DOES NOT
 MAKE THAT LEVEL OF BUILDING DISAPPEAR FOR THE PURPOSES
 OF SETBACKS. STAFF DOES NOT CURRENTLY SUPPORT THIS
 DESIGN BASED ON THE WAIVERS THAT IT REQUIRES.
  
 9) THE BUILDING SETBACK ALONG SOUTH FLAGLER DRIVE DOES
 NOT COMPLY WITH THE THEME THAT HAS BEEN ESTABLISHED BY
 PRIOR PROJECTS TO SET THE BUILDINGS BACK AND CREATE AN
 ENHANCED VISUAL OPEN SPACE ALONG SOUTH FLAGLER DRIVE.
 NOT ONLY IS THE BUILDING NOT SET BACK APPROPRIATELY,
 BUT THE OUTSIDE STAIRWAYS FROM THE TERRACES ENCROACH
 INTO THE MINIMUM 25-FOOT FRONT SETBACK REQUIRED IF THIS
 WAS AN MF32 ZONING BASED PROJECT NOT LOCATED ALONG
 SOUTH FLAGLER DRIVE.
  
 10) THE TERRACE, WHILE NOT SHOWING AN EXACT SETBACK
 DIMENSION ON THE PLANS, APPEARS TO BE APPROXIMATELY 25
 FEET FROM SOUTH FLAGLER DRIVE. THE TERRACE WALL EXTENDS
 OVER EIGHT (8) FEET ABOVE THE SIDEWALK GRADE AND THUS
 DOES NOT CREATE AN ENHANCEMENT FOR SOUTH FLAGLER DRIVE.
 THE FIRST LEVEL OF THE TOWNHOUSE UNITS WILL NOT BE
 VISIBLE TO A PEDESTRIAN.
  
 11) THE SOUTH PORTION OF THE BUILDING (BEHIND THE
 FOUNTAIN) IS A STAIRCASE TO UP TO THE AMENITY DECK,
 WHICH, UNLESS OPEN TO THE PUBLIC, IS ANOTHER SECTION OF
 THE BUILDING BROUGHT CLOSE TO SOUTH FLAGLER DRIVE WHICH
 PROVIDES NO ACTIVE USE INTERACTION.
  
 12) STAFF DOES NOT OPPOSE THE PODIUM SETBACK OF 15 FEET
 ALONG THE SOUTH PROPERTY LINE; HOWEVER, MORE DETAIL ON
 THE INTERACTION BETWEEN THE TOWNHOUSES AND THE PROPOSED
 SIDEWALK IS REQUIRED. THE RENDERINGS SEEM TO INDICATE
 THAT THE SOUTHEAST CORNER OF THE SITE WILL HAVE A HIGH
 RETAINING WALL AT THE CORNER, WHICH DOES NOT FOSTER ANY
 PERCEIVED INTERACTION WITH THE SITE. THE ADDITIONAL
 DETAILING NEEDS TO SHOW THE ELEVATIONS BETWEEN THE
 PROPOSED SIDEWALK AND THE ENTRY GARDENS.
  
 13) STAFF DOES NOT SUPPORT THE WESTERN TOWER BUILT TO
 THE 15-FOOT PODIUM LINE. THE JUSTIFICATION STATEMENT
 GOES TO GREAT LENGTHS TO STATE HOW THE DESIGN OF THE
 PODIUM AND THE TOWER POSITIONING LESSONS THE IMPACT OF
 THE MASS OF THE BUILDING. STAFF HAS ACCEPTED THIS IN
 THE PAST ONLY WHEN THE TOWER IS SETBACK FROM THE EDGE
 OF THE PODIUM. BUILDING A 20 PLUS STORY TOWER 15 FEET
 FROM A PROPERTY LINE ACCENTUATES THE SIZE OF THE
 BUILDING.
  
 14) THE NORTH/SOUTH PORTION OF CURRIE CRESCENT IS A
 FRONT PROPERTY LINE, WHICH REQUIRES A 25-FOOT, NOT
 10-FOOT SETBACK. NOTE: THIS IS NOT A FENCE HEIGHT
 WAIVER FOR THE WALL, SINCE THE WALL IS THE BUILDING
 WALL THAT ENCROACHES INTO THE SETBACK.
  
 15) THE EAST/WEST PORTION OF CURRIE CRESCENT IS A SIDE
 PROPERTY LINE SO IT MUST MEET THE ONE-FOOT SETBACK FOR
 EACH TWO FEET IN HEIGHT REQUIREMENT. THIS SECTION IS
 NOT COVERED IN YOUR WAIVER REQUEST.
  
 16) SHEET G-201 SHOWS THE BAY WINDOWS BEING 18 INCHES
 DEEP. PLEASE EXPLAIN WHY THE WAIVER REQUEST IS FOR 36
 INCHES.
  
 17) SHEET G-201 SHOWS THE BALCONY BEING 3 FEET 8 INCHES
 DEEP. PLEASE EXPLAIN WHY THE WAIVER REQUEST IS FOR 5
 FEET.
  
 18) STAFF DOES NOT OBJECT TO THE CAFE AWNINGS
 ENCROACHING 7 FEET INTO THE WESTERN SETBACK OVER THE
 ENTRANCES TO THE CAFE FROM THE OUTDOOR SEATING.
  
 19) STAFF IS NOT PREPARED TO SUPPORT A 12-FOOT CANOPY
 ENCROACHMENT INTO THE WEST SETBACK. THERE HAS BEEN
 INADEQUATE JUSTIFICATION PROVIDED AS TO WHY SUCH A DEEP
 CANOPY IS REQUIRED AT THIS ENTRANCE.
  
 20) STAFF DOES NOT SUPPORT THE 12-FOOT CANOPY
 ENCROACHMENT INTO THE SOUTH SETBACK. THE BUILDING
 SETBACK IS ALREADY BEING REQUESTED TO BE REDUCED HAS
 ALREADY BEEN REDUCED BY OVER 150 FEET. ENCROACHING
 FURTHER INTO THE SETBACK IS NOT JUSTIFIED FOR THE
 CANOPY. ADDITIONALLY, A 12-FOOT AWNING ENCROACHES INTO
 THE REQUIRED LANDSCAPE BUFFER WHERE THE PROPOSED OAK
 TREE IS LOCATED.
  
 21) PROVIDE THE SETBACK DIMENSIONS OF THE PODIUM
 (INCLUDING THE AMENITIES LEVEL) AND THE TWO TOWERS.
 THIS IS THE METHODOLOGY USED ON THE NEARBY TOWERS TO
 ESTABLISH THE BUILDING SETBACKS.
  
 22) THE SITE OPEN SPACE IS INCORRECTLY CALCULATED. THE
 AREAS SUCH AS THE MOTOR COURT AND THE DRIVE WHERE IT IS
 ABOVE THE FIRST LEVEL OF THE BUILDING IS NOT OPEN SPACE
 IT IS A BUILDING ROOF.
  
 ELEVATIONS
  
 23) PROVIDE THE ELEVATION HEIGHTS OF ALL THE FEATURES
 ON THE AMENITY DECK AND THE LEVEL 5 PLANS FOR THE ROOF.
  
 24) PROVIDE THE ELEVATION HEIGHT OF THE ROOF TOP
 MECHANICAL EQUIPMENT AND COOLING TOWER.
  
 25) PROVIDE ELEVATION HEIGHTS FOR THE VARIOUS FEATURES
 ALONG THE SOUTH FLAGLER DRIVE FRONTAGE.
  
 PARKING
  
 26) PLEASE PROVIDE HOW THE PARKING SPACES WILL BE
 ASSIGNED IN THE BUILDING. THERE ARE SEVERAL PRIVATE
 GARAGES WHICH INCLUDE THREE CAR SPACES. GIVEN THAT THE
 PARKING TABLE (PRIOR TO ANY OF THE FOLLOWING COMMENTS
 BEING ADDRESSED) SHOWS THAT THERE IS ONLY ONE EXTRA
 PARKING SPACE, ASSIGNING MULTIPLE UNITS MORE THAN TWO
 PARKING SPACES DOES NOT PERMIT THE OTHER UNITS TO HAVE
 THE REQUIRED TWO PARKING SPACES.
  
 27) IS THERE A VALET? PROVIDE THE VALET PLAN. PLEASE
 NOTE THAT VALETS ARE NOT PERMITTED TO USE THE PUBLIC
 RIGHTS-OF-WAY FOR MANEUVERING.
  
 28) HOW DOES A RESTAURANT/CAFE PARKING CUSTOMER OR A
 GUEST KNOW WHICH PARKING ENTRANCE TO USE?
  
 29) WHERE ARE THE RESTAURANT/CAFE PARKING AND GUEST
 PARKING SPACES. THESE NEED TO BE DESIGNATED ON THE
 PLAN.
  
 30) PROVIDE A DRAWING SHOWING HOW A RESTAURANT OR CAFE
 CUSTOMER GETS FROM THE PUBLIC PARKING TO THE RESTAURANT
 OR CAFE.
  
 31) WHO HAS ACCESS TO THE PARKING FIELD ON SHEET A-102?
 DEPENDING ON WHO HAS ACCESS, STAFF MAY HAVE COMMENTS
 REGARDING PARKING SPACE ACCESS AND TURN AROUND
 DEFICIENCIES.
  
 32) WHO HAS ACCESS TO THE PARKING FIELD ON SHEET A-103?
 DEPENDING ON WHO HAS ACCESS, STAFF MAY HAVE COMMENTS
 REGARDING PARKING SPACE ACCESS AND TURN AROUND
 DEFICIENCIES.
  
 33) ARE THE PARKING AREAS GATED? IF NOT HOW IS ACCESS
 CONTROLLED? IF SO, PROVIDE INFORMATION ON STACKING AND
 CALL BOXES.
  
 34) THE ADA PARKING SPACE DETAILS ON SHEET A-054 DO NOT
 CONFORM TO CITY STRIPING STANDARDS.
  
 35) THE ADA PARKING SPACES DO NOT APPEAR TO THE BE
 CLOSEST PARKING SPACES TO THE ELEVATORS LEADING TO THE
 UPPER FLOOR RESTAURANT OR TO THE CORRIDOR LEADING TO
 THE CAFE. PLEASE EXPLAIN.
  
 36) SHOW THE DEPTH DIMENSIONS FOR THE PARKING ROWS.
  
 37) THE DEAD-END PARKING ROW CONTAINING SPACES 112 AND
 162 MUST EITHER HAVE A MARKED TURN AROUND SPACE OR BE
 ALL ASSIGNED PARKING SPACES IN AN AREA WHERE A
 RESTAURANT/CAFE OR GUEST PARKER CANNOT ACCESS.
  
 38) DESCRIBE HOW THE MOTOR COURT WILL FUNCTION. WILL
 CARS BE PARKED HERE FOR ANY REASON?
  
 39) THE BUILDING IS DEFICIENT IN PARKING:
  
 A. YOU ARE PROPOSING A LUXURY HIGH RISE BUILDING THAT
 WILL REQUIRE ON-SITE STAFF. PLANNING STAFF REQUIRES
 THAT YOU PROVIDE PARKING SPACES WITHIN THE PARKING LOT
 FOR THE ON-SITE STAFF SO THAT THESE EMPLOYEES ARE NOT
 REQUIRED TO PARK IN THE SURROUNDING NEIGHBORHOODS.
 PLEASE PROVIDE HOW MANY RESIDENTIAL STAFF WILL ON-SITE
 AT PEAK TIME SO THE PROPER NUMBER OF SPACES CAN BE
 DETERMINED.
 B. ONLY THE OUTSIDE TANDEM PARKING SPACE MAY COUNT
 TOWARD MEETING THE PARKING REQUIREMENT.
 C. SPACES 1 AND 2 ON THE BASEMENT LEVEL DO NOT HAVE
 ADEQUATE BACK OUT MANEUVERING ROOM AND THUS DO NOT
 FUNCTION.
 D. PARKING SPACE 82 DOES NOT PROVIDE SAFE
 INGRESS/EGRESS TO THE SPACE GIVEN THE PROXIMITY TO THE
 GARAGE ENTRANCE AND THE WALLS.
  
 40) HOW DOES THE PERSON PARKING IN SPACE 110 LEAVE THE
 GARAGE?
  
 41) PROVIDE THE ANGLE OF PARKING SPACES 131 AND 132 AND
 PROVIDE DIMENSION LINES TO VERIFY THAT THEY MEET THE
 CODE REQUIRED BACK UP DISTANCE.
  
 42) NO BICYCLE PARKING WAS PROVIDED.
  
 A. YOU MUST HAVE BICYCLE PARKING FOR THE
 CAFE/RESTAURANT USERS LOCATED ON THE SOUTH OLIVE AVENUE
 SIDE OF THE SITE.
 B. YOU MUST HAVE A BICYCLE STORAGE ROOM FOR RESIDENTS.
 C. YOU MUST HAVE BICYCLE PARKING FOR GUESTS NEAR ONE OF
 THE GUEST ACCESSIBLE ENTRANCES TO THE BUILDING.
  
 43) PROVIDE MORE DETAIL ON THE PROPOSED PRE-WIRING OF
 THE BUILDING FOR EV CHARGER INSTALLATION. THERE ARE A
 NUMBER OF SPACES THAT ARE HEAD TO HEAD AS WELL AS THE
 TANDEM SPACES THAT DO NOT SEEM TO HAVE SPACE FOR
 CHANGING UNITS. PLEASE REMEMBER THAT THE ELECTRICAL
 ROOM NEEDS TO INCLUDE EXTRA SPACE FOR THE ADDITIONAL
 PANELS.
  
 LOADING/ACCESS
  
 44) THE NORTH SIDE OF CURRIE CRESCENT HAS ON-STREET
 PARALLEL PARKING SPACES. THE TRUCK TURNING DIAGRAM
 SHOWS THE TRUCK USING THE FULL WIDTH OF CURRIE
 CRESCENT, WHICH IS IMPOSSIBLE IF A CAR IS PARKED IN THE
 PARALLEL SPACES, AND THUS IS NOT PERMITTED.
  
 45) WHERE WILL A FULL-SIZED MOVING TRUCK PARK FOR THE
 RESIDENTIAL PORTION OF THE PROJECT?
  
 46) WHAT IS THE PLAN FOR GARBAGE PICK-UP?
  
 47) THE CITY'S ENGINEERING SERVICES DEPARTMENT NEEDS TO
 APPROVE THE USE OF CURRIE CRESCENT FOR MANEUVERING
 PRIOR TO THE CASE PROCEEDING THROUGH THE PUBLIC HEARING
 PROCESS.
  
 48) THE CITY'S ENGINEERING SERVICES DEPARTMENT NEEDS TO
 APPROVE THE NUMBER OF ACCESS POINTS TO CURRIE CRESCENT
 AND THE SEPARATION OF ACCESS POINTS TO THE CASE
 PROCEEDING THROUGH THE PUBLIC HEARING PROCESS.
  
 TOWNHOUSE UNITS
  
 49) PLEASE PROVIDE A SAMPLE FLOOR PLAN ON HOW THE
 TOWNHOUSE UNITS WILL WORK. THE LINEWORK ON LEVEL ONE
 SEEMS TO SHOW WHAT APPEAR TO BE 16 TOWNHOUSES.
  
 WALLS
  
 50) THE PROPOSED USE INCLUDES NON-RESIDENTIAL USES SO A
 SCREEN WALL IS REQUIRED ALONG THE NORTH AND SOUTH
 PROPERTY LINES. THE CITY COMMISSION, ON BEHALF OF THE
 CITY, WHO OWNS THE PROPERTY TO THE SOUTH MAY WAIVER THE
 REQUIREMENT AS PART OF THE RPD, BUT YOU HAVE NOT
 REQUESTED THIS WAIVER. PROVIDE VERIFICATION THAT THE
 WALL ALONG THE ENTIRE NORTH PROPERTY LINE COMPLIES WITH
 THE SECTION 94-443A.1 REQUIREMENTS OR THAT THE PROPERTY
 OWNER TO THE NORTH HAS GRANTED A WAIVER FOR THE
 REQUIRED WALL. NOTE: AN EARLIER COMMENT RELATES TO THE
 NORTH PROPERTY LINE AND ITS DESIGN.
  
 51) WALL HEIGHTS ARE MEASURED FROM THE ACTUAL GRADE ON
 THE EXTERIOR OF THE WALL, NOT THE MEAN GRADE OF THE
 PROPERTY USED FOR BUILDING HEIGHT. UPDATE YOUR WALL
 HEIGHT PLANS, CROSS SECTIONS AND REQUIRED WAIVERS TO
 COMPLY.
  
 52) NO INFORMATION IS PROVIDED ABOUT WHAT APPEARS TO BE
 A WALL WITH STEPS AT THE SOUTHWEST CORNER OF THE SITE.
  
 CAFE/RESTAURANT
  
 53) PROVIDE A DIAGRAM SHOWING HOW A PUBLIC CUSTOMER
 ACCESSES THE RESTAURANT.
  
 54) SHEET LG-3.1 CALLS OUT THE SURFACE AS SOD AT THE
 AREA SHOWN AS OUTDOOR SEATING FOR THE CAFE ALONG SOUTH
 OLIVE AVENUE. THERE ARE DISCREPANCIES ON THE VARIOUS
 PLANS AS TO WHAT THE AREA IN FRONT OF THE CAFE LOOKS
 LIKE ON THE VARIOUS PLANS. ALL PLANS MUST SHOW THE
 SAME, ACCURATE CONDITIONS.
  
  

  Print


Account Summary | Usage Policy | Privacy Policy