Plan Review Details - Project Z21050011
Plan Review Stops For Project Z21050011
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 06-09-2021 Cont ID  
Sent By rbrown Date 06-09-2021 Time 21:09 Rev Time 0.00
Received By rbrown Date 06-09-2021 Time 21:09 Sent To  
Notes
2021-06-09 21:14:02DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 3. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND
 OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT,
 COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF
 OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED.
  
 4. GREASE INTERCEPTOR. A GREASE INTERCEPTOR MAY BE
 REQUIRED. FOR INFORMATION ON THE REQUIRED TYPE, SIZE
 AND LOCATION, PLEASE CONTACT TIM LARGE, CHIEF PLUMBING
 INSPECTOR, DEVELOPMENT SERVICES DEPARTMENT, AT (561)
 805-6692, OR BY EMAIL: [email protected]
  
 5. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 6. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND
 CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF
 CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL
 NEIGHBORING PROPERTIES.
  
 7. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 8. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION
 OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING,
 CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT
 (561) 805 6659, OR BY EMAIL: [email protected]
  
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  
2021-05-29 10:07:35 
  
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 5 Status P Date 03-02-2022 Cont ID  
Sent By ldeloren Date 03-02-2022 Time   Rev Time 0.00
Received By ldeloren Date 03-02-2022 Time   Sent To  
Notes
2022-03-02 07:52:14Z21050011 ? AUTOZONE 1236 PB LAKES ? 02-25-22 RESUB
 COMMENTS PER RICK ROSSANO, ENG. SERVICES SR. PROJECT
 COORDINATOR:
  
 SANITARY CCTV ALONG ENTIRE SOUTHERN LENGTH OF PROJECT
 SHALL BE PROVIDED TO ENGINEERING / PUBLIC UTILITIES FOR
 REVIEW AS A CONDITION OF SITE PLAN APPROVAL. ENGINEER
 OF RECORD/AGENT/DEVELOPER ACKNOWLEDGES THAT IN THE
 EVENT CITY SANITARY INFRASTRUCTURE NEEDS TO BE
 REPLACED, AT THE CITY?S DISCRETION, IT SHALL BE DONE AT
 THE DEVELOPERS? EXPENSE.
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
 NO FURTHER COMMENT.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 LYNN DELORENZO
 PROJECT COORDINATOR
 CITY OF WEST PALM BEACH ENGINEERING SERVICES
 OFFICE: (561)494-1085
 FAX: (561)9494-1116
 E-MAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 4 Status F Date 01-13-2022 Cont ID  
Sent By rrossano Date 01-13-2022 Time   Rev Time 0.00
Received By rrossano Date 01-13-2022 Time   Sent To  
Notes
2022-01-13 08:41:08COMMENTS PER RICK ROSSANO, ENG. SERVICES SR. PROJECT
 COORDINATOR, [email protected], 561-494-1098:
  
 1. PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND
 STORMWATER ALONG ENTIRE PROJECT FRONTAGE (PREVIOUS
 COMMENT - PROVISION OF REQUESTED CCTV IS A CONDITION OF
 SITE PLAN APPROVAL).
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
  
 -UTILITY SERVICE NOTES ON UTILITY PLAN LIST MANNY
 GONZALEZ AS CONTACT. HE NO LONGER WORKS FOR CITY WPB.
 PLEASE UPDATE AT FORMAL ENGINEERING SUBMITTAL.
  
 -SEWER MAIN HAS FLOW ARROWS GOING EAST, BUT WPB
 SANITARY COLLECTIONS ADVISES IT FLOWS WEST FROM THE
 APARTMENT COMPLEX TO AUSTRALIAN. AT FORMAL ENGINEERING
 SUBMITTAL PLEASE VERIFY AND UPDATE PLANS AS NEEDED.
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 3 Status F Date 09-15-2021 Cont ID  
Sent By rrossano Date 09-15-2021 Time   Rev Time 0.00
Received By rrossano Date 09-15-2021 Time   Sent To  
Notes
2021-09-15 14:40:18COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR, ENG.
 SERVICES DEPT., 561-494-1098 [email protected] :
  
 PLEASE ADDRESS COMMENTS FROM FIRST SUBMITTAL ?
 Z21050011 ? AUTOZONE 1236 PB LAKES ? INITIAL REVIEW
 1. THE CITY OF WEST PALM BEACH HAS A NUMBER OF
 REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY
 AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND
 WASTEWATER UTILITIES WITHIN THE CITY. TO VIEW
 DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AND OTHER
 ENGINEERING RELATED DOCUMENTS, GO HERE:
 HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING
 2. CODE OF ORDINANCES, CITY OF WEST PALM BEACH,
 FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED
 SEPT. 22, 2008. (SUPPLEMENT NO. 18) CHAPTER 90
 UTILITIES, ARTICLE I. SEC. 90-7.
 POLICY REGARDING EXTENSION OF WATER OR SEWER SERVICE
 FACILITIES OF THE CITY:
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
 3. AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, GO TO:
 HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING
 4. PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1040 FOR FURTHER
 ASSISTANCE.
 5. PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS
 OF ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES,
 INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND
 SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES,
 METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE
 SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 PLEASE SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL. ADDITIONALLY, PLAN VIEW SHALL SHOW ALL
 EXISTING AND PROPOSED UNDERGROUND UTILITY LAYOUT,
 INCLUDING FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED ON THE
 RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL
 UTILITY CROSSINGS.
 6. CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 ROW.
 7. PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE
 DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB
 DEVELOPMENT APPLICATION).
 8. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM
 AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE
 PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER.
 9. SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION
 (NAVD 88 AND NGVD 29).
 10. PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND
 STORMWATER ALONG ENTIRE PROJECT FRONTAGE.
 11. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
 12. PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR
 PROPOSED SANITARY LATERALS.
 13. PLEASE LABEL WATER LINES AS PRIVATE WHERE
 APPLICABLE.
 14. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED
 LOCATION OF WATER METER AND BACKFLOW PREVENTION.
 15. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING
 PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT
 HIM AT 561-494-2262 OR [email protected]
 16. PROVIDE DEDICATED UTILITY EASEMENTS TO ALLOW ACCESS
 FOR CITY PERSONNEL TO PROPOSED UTILITY WATER METERS.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT, (561) 494-1098 [email protected]
  
  
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
 THE PLANS DID NOT SEEM TO CHANGE MUCH OR ADDRESS
 COMMENTS PROVIDED EITHER THROUGH THE COMPUTER SYSTEM OR
 VERBALLY DURING PPRC MEETING.
 -SEWER LATERAL CROSSES ADJACENT PROPERTY. WILL THERE BE
 A LEGAL AGREEMENT TO ALLOW THAT AND CLARIFY OTHER
 FACTORS SUCH AS MAINTENANCE RESPONSIBILITY?
  
 -PLEASE VERIFY IF THERE IS AN EXISTING FENCE OVER THE
 WATER MAIN ON EAST SIDE OF PROPERTY.
  
 -HOW FAR IS THE EAST SIDE OF THE BUILDING TO THE WATER
 MAIN? PLEASE SHOW THAT ON UTILITY PLAN.
  
 -WILL A SEPARATE METERED IRRIGATION WATER SERVICE BE
 NEEDED?
  
 -WILL THE BUILDING HAVE FIRE SPRINKLERS?
  
 -SHOW AND LABEL ALL EXISTING FIRE HYDRANTS ON UTILITY
 PLAN. (THERE IS AT LEAST ONE TO THE SOUTHWEST AND ONE
 TO THE NORTHEAST)
  
 -ON THE UTILITY PLAN, PLEASE LABEL THE UNMARKED SQUARE
 OBJECT BETWEEN THE BATHROOMS AND DUMPSTER.
  
 -ON THE UTILITY PLAN, PLEASE LABEL THE OBJECT NEAR THE
 SOUTHEAST CORNER OF THE BUILDING IN THE UTILITY
 EASEMENT.
  
 -THERE APPEAR TO BE SOME TREE CONFLICTS WITH WATER
 UTILITIES. PLEASE ENSURE ROOTS WILL NOT GROW INTO WATER
 PIPING. INCREASE CLEARANCE DISTANCE AND ADD ROOT
 BARRIERS AS NEEDED.
  
 -IT APPEARS THERE IS A PROPOSED TREE IN DRAINAGE
 EASEMENT. IS THAT ALLOWED?
  
 -A COUPLE OF MANHOLES APPEAR TO CONFLICT WITH A PARKING
 BLOCK AND WITH AN ADA RAMP.
  
 -WILL THE MARQUEE AND MONUMENT SIGNS BE VISIBLE WITH
 THE ADJACENT TREES?
  
 -THERE ARE A LOT OF WATER SERVICES AND WATER METER
 BOXES ALONG THE EAST SIDE OF PROPERTY JUST WEST OF THE
 EXISTING FENCE. PLEASE SHOW AND LABEL ALL OF THEM ON
 THE UTILITY PLAN.
  
 -THERE IS A METER BOX AND BACKFLOW ASSEMBLY EAST OF THE
 SOUTHWEST FIRE HYDRANT. SHOW AND LABEL THAT ON UTILITY
 PLAN. IT SHOULD BE THE WATER SERVICE FOR THE ICE
 MACHINE BUSINESS 1256 PALM BEACH LAKES. ALSO SHOW THE
 PLUMBING PIPE IF IT CROSSES INTO THE PROPERTY; AND
 VERIFY R1-1 SIGN WILL NOT HIT IT.
  
 -ON THE UTILITY PLAN, THERE ARE A COUPLE OF UNLABELED
 LINES RUNNING FROM THE SOUTHEAST CORNER OF THE BUILDING
 TO THE PROPERTY LINE. PLEASE LABEL THOSE.
  
 -SURVEY SHOWS MULTIPLE 6 INCH WATER MAINS RUNNING
 EAST-WEST THROUGH PROPERTY. IT ALSO SHOWS SOME
 DIFFERENT LOCATIONS FOR THE NORTH-SOUTH WATER MAINS.
 PLEASE VERIFY LOCATIONS AND UPDATE UTILITY PLAN AS
 NEEDED.
  
 -PLEASE VERIFY THERE IS A 6 INCH WATER MAIN RUNNING
 NEAR THE NORTH PROPERTY LINE.
  
 -SURVEY SHOWS INGRESS/EGRESS EASEMENT NEAR NORTH
 DRIVEWAY. IS AN INGRESS/EGRESS EASEMENT NEEDED FOR
 SOUTHERN DRIVEWAY?
  
 -THERE IS AN EXISTING WATER METER AND BACKFLOW ASSEMBLY
 NEAR EAST SIDE OF PROPOSED BUILDING THAT LIKELY FEEDS
 1258 PALM BEACH LAKES RESTAURANT. PLEASE SHOW AND LABEL
 THE WATER METER, BACKFLOW ASSEMBLY, AND PLUMBING PIPE
 RUNNING TO RESTAURANT.
  
 -SHOW WATER METERS AND BACKFLOW ASSEMBLIES ON THE
 LANDSCAPING PLAN.
  
 -VERIFY PROPOSED METER BOX WOULD BE IN LANDSCAPING AREA
 AND NOT HARDSCAPE.
  
 -EXISTING DRAINAGE INFRASTRUCTURE IN EASEMENT THAT
 CROSSES MULTIPLE PROPERTIES APPEARS TO BE
 PRIVATELY-OWNED. HOW WILL OWNERSHIP AND MAINTENANCE BE
 HANDLED?
  
 -WHAT WILL YARD HYDRANT BE USED FOR?
  
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status F Date 07-28-2021 Cont ID  
Sent By rrossano Date 07-28-2021 Time   Rev Time 0.00
Received By rrossano Date 07-28-2021 Time   Sent To  
Notes
2021-07-28 13:33:351. FAILED, NO CIVIL PLANS OR RESPONSES PROVIDED.

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 05-29-2021 Cont ID  
Sent By rrossano Date 05-29-2021 Time   Rev Time  
Received By rrossano Date 05-29-2021 Time   Sent To  
Notes
2021-05-29 10:08:481. THE CITY OF WEST PALM BEACH HAS A NUMBER OF
 REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY
 AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND
 WASTEWATER UTILITIES WITHIN THE CITY. TO VIEW
 DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AND OTHER
 ENGINEERING RELATED DOCUMENTS, GO HERE:
 HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING
 2. CODE OF ORDINANCES, CITY OF WEST PALM BEACH,
 FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED
 SEPT. 22, 2008. (SUPPLEMENT NO. 18) CHAPTER 90
 UTILITIES, ARTICLE I. SEC. 90-7.
 POLICY REGARDING EXTENSION OF WATER OR SEWER SERVICE
 FACILITIES OF THE CITY:
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
 3. AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, GO TO:
 HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING
 4. PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1040 FOR FURTHER
 ASSISTANCE.
 5. PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS
 OF ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES,
 INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND
 SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES,
 METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE
 SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 PLEASE SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL. ADDITIONALLY, PLAN VIEW SHALL SHOW ALL
 EXISTING AND PROPOSED UNDERGROUND UTILITY LAYOUT,
 INCLUDING FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED ON THE
 RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL
 UTILITY CROSSINGS.
 6. CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 ROW.
 7. PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE
 DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB
 DEVELOPMENT APPLICATION).
 8. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM
 AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE
 PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER.
 9. SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION
 (NAVD 88 AND NGVD 29).
 10. PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND
 STORMWATER ALONG ENTIRE PROJECT FRONTAGE.
 11. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
 12. PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR
 PROPOSED SANITARY LATERALS.
 13. PLEASE LABEL WATER LINES AS PRIVATE WHERE
 APPLICABLE.
 14. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED
 LOCATION OF WATER METER AND BACKFLOW PREVENTION.
 15. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING
 PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT
 HIM AT 561-494-2262 OR [email protected]
 16. PROVIDE DEDICATED UTILITY EASEMENTS TO ALLOW ACCESS
 FOR CITY PERSONNEL TO PROPOSED UTILITY WATER METERS.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT, (561) 494-1098 [email protected]
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
 -SEWER LATERAL CROSSES ADJACENT PROPERTY. WILL THERE BE
 A LEGAL AGREEMENT TO ALLOW THAT AND CLARIFY OTHER
 FACTORS SUCH AS MAINTENANCE RESPONSIBILITY?
  
 -PLEASE VERIFY IF THERE IS AN EXISTING FENCE OVER THE
 WATER MAIN ON EAST SIDE OF PROPERTY.
  
 -HOW FAR IS THE EAST SIDE OF THE BUILDING TO THE WATER
 MAIN? PLEASE SHOW THAT ON UTILITY PLAN.
  
 -WILL A SEPARATE METERED IRRIGATION WATER SERVICE BE
 NEEDED?
  
 -WILL THE BUILDING HAVE FIRE SPRINKLERS?
  
 -SHOW AND LABEL ALL EXISTING FIRE HYDRANTS ON UTILITY
 PLAN. (THERE IS AT LEAST ONE TO THE SOUTHWEST AND ONE
 TO THE NORTHEAST)
  
 -ON THE UTILITY PLAN, PLEASE LABEL THE UNMARKED SQUARE
 OBJECT BETWEEN THE BATHROOMS AND DUMPSTER.
  
 -ON THE UTILITY PLAN, PLEASE LABEL THE OBJECT NEAR THE
 SOUTHEAST CORNER OF THE BUILDING IN THE UTILITY
 EASEMENT.
  
 -THERE APPEAR TO BE SOME TREE CONFLICTS WITH WATER
 UTILITIES. PLEASE ENSURE ROOTS WILL NOT GROW INTO WATER
 PIPING. INCREASE CLEARANCE DISTANCE AND ADD ROOT
 BARRIERS AS NEEDED.
  
 -IT APPEARS THERE IS A PROPOSED TREE IN DRAINAGE
 EASEMENT. IS THAT ALLOWED?
  
 -A COUPLE OF MANHOLES APPEAR TO CONFLICT WITH A PARKING
 BLOCK AND WITH AN ADA RAMP.
  
 -WILL THE MARQUEE AND MONUMENT SIGNS BE VISIBLE WITH
 THE ADJACENT TREES?
  
 -THERE ARE A LOT OF WATER SERVICES AND WATER METER
 BOXES ALONG THE EAST SIDE OF PROPERTY JUST WEST OF THE
 EXISTING FENCE. PLEASE SHOW AND LABEL ALL OF THEM ON
 THE UTILITY PLAN.
  
 -THERE IS A METER BOX AND BACKFLOW ASSEMBLY EAST OF THE
 SOUTHWEST FIRE HYDRANT. SHOW AND LABEL THAT ON UTILITY
 PLAN. IT SHOULD BE THE WATER SERVICE FOR THE ICE
 MACHINE BUSINESS 1256 PALM BEACH LAKES. ALSO SHOW THE
 PLUMBING PIPE IF IT CROSSES INTO THE PROPERTY; AND
 VERIFY R1-1 SIGN WILL NOT HIT IT.
  
 -ON THE UTILITY PLAN, THERE ARE A COUPLE OF UNLABELED
 LINES RUNNING FROM THE SOUTHEAST CORNER OF THE BUILDING
 TO THE PROPERTY LINE. PLEASE LABEL THOSE.
  
 -SURVEY SHOWS MULTIPLE 6 INCH WATER MAINS RUNNING
 EAST-WEST THROUGH PROPERTY. IT ALSO SHOWS SOME
 DIFFERENT LOCATIONS FOR THE NORTH-SOUTH WATER MAINS.
 PLEASE VERIFY LOCATIONS AND UPDATE UTILITY PLAN AS
 NEEDED.
  
 -PLEASE VERIFY THERE IS A 6 INCH WATER MAIN RUNNING
 NEAR THE NORTH PROPERTY LINE.
  
 -SURVEY SHOWS INGRESS/EGRESS EASEMENT NEAR NORTH
 DRIVEWAY. IS AN INGRESS/EGRESS EASEMENT NEEDED FOR
 SOUTHERN DRIVEWAY?
  
 -THERE IS AN EXISTING WATER METER AND BACKFLOW ASSEMBLY
 NEAR EAST SIDE OF PROPOSED BUILDING THAT LIKELY FEEDS
 1258 PALM BEACH LAKES RESTAURANT. PLEASE SHOW AND LABEL
 THE WATER METER, BACKFLOW ASSEMBLY, AND PLUMBING PIPE
 RUNNING TO RESTAURANT.
  
 -SHOW WATER METERS AND BACKFLOW ASSEMBLIES ON THE
 LANDSCAPING PLAN.
  
 -VERIFY PROPOSED METER BOX WOULD BE IN LANDSCAPING AREA
 AND NOT HARDSCAPE.
  
 -EXISTING DRAINAGE INFRASTRUCTURE IN EASEMENT THAT
 CROSSES MULTIPLE PROPERTIES APPEARS TO BE
 PRIVATELY-OWNED. HOW WILL OWNERSHIP AND MAINTENANCE BE
 HANDLED?
  
 -WHAT WILL YARD HYDRANT BE USED FOR?
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 06-09-2021 Cont ID  
Sent By pleduc Date 06-09-2021 Time   Rev Time 0.00
Received By pleduc Date 06-09-2021 Time 14:46 Sent To  
Notes
2021-06-09 14:55:47THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE DEPARTMENT.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT. THE FOLLOWING COMMENTS ARE INTENDED
 TO PROVIDE GUIDANCE FOR BUILDING PLAN SUBMITTAL.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE.
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT AN
 ADEQUATE WATER SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
 ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 8. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM,
 ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND
 SUBMITTED WITH THE MASTER PERMIT.
  
 8A) THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE
 LOCATIONS SHALL MEET THE REQUIREMENTS OF NFPA 24 AND
 SHALL BE COORDINATED WITH THE OFFICE OF FIRE MARSHAL,
 THE CITY'S ENGINEERS OFFICE, THE LANDSCAPE PLANNER, AND
 THE CITY'S PLANNING AND ZONING OFFICE.
  
 9. A COMPLETE LIFE SAFETY PLAN FOR THE OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 10. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE
 SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY
 DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS.
  
 11. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
 12. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop L LANDSCAPING
Rev No 4 Status P Date 03-10-2022 Cont ID  
Sent By rcaranci Date 03-10-2022 Time 11:50 Rev Time 0.00
Received By rcaranci Date 03-10-2022 Time 11:49 Sent To  
Notes
2022-03-10 11:50:34FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 1225 PALM BEACH LAKES AUTO ZONE Z21050011
 MARCH 10, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
 THESE COMMENTS WERE NOT INCLUDED IN THE RESPONSE
 LETTER.
 1. SATISFIED. EAST SIDE OF PROPERTY HAS WATER AND POWER
 EASEMENT. TREES SHOULD NOT BE PLANTED ON EASEMENT
 EXISTING TREES SHOULD BE MOVED TO OTHER LOCATIONS ON
 PROJECT SITE. NO CLOSER THAN 5FT OF WATER MAIN.
 PER SECTION 94-443(A)(2)C. , REQUIRED BUFFER TREES MAY
 BE CLUSTERED AND IF THERE IS ADDITIONAL LANDSCAPE AREA
 ADJACENT TO THE BUFFER STRIP, REQUIRED TREES MAY BE
 PLACED ADJACENT TO THE BUFFER STRIP TO ALLOW A GREATER
 AREA FOR TREE DEVELOPMENT.
 IF THE REQUIRED EAST BUFFER TREES ARE TO BE PLACED IN
 THE LANDSCAPE AREAS ADJACENT TO THE EAST BUFFER, MARK
 THEM ON THE PLAN TO IDENTIFY THE COUNT MEETS THE
 REQUIREMENTS. PALMS MAY ALSO BE USED ADJACENT TO THE
 EASEMENT TO PROVIDE THE INTENDED BUFFERING. SHOW THE
 EXISTING TREES ON THE ADJACENT PROPERTY TO COORDINATE
 PLANTING LOCATIONS SO THERE IS NO CONFLICT.
  
 2. SATISFIED. LANDSCAPE BUFFER ON THE NORTH SIDE HAS
 ONLY ROYAL PALMS. THE BUFFER MUST CONTAIN FLOWERING OR
 SHADE TREES, IT CANNOT BE ENTIRELY PALMS AT LEAST ONE
 SHADE TREE PLANTED FOR EACH 30 LINEAR FEET. 94-443 B.
 1.-5.
 UNLESS THERE ARE UTILITY CONFLICTS THAT CAN BE SHOWN ON
 THE PLANS, SHADE TREES MUST BE PROVIDED. SEE DEFINITION
 OF SHADE TREE. THIS WOULD BE A CATEGORY 1 TREE WITH A
 MATURE SPREAD OF AT LEAST 25 FEET.
  
 3. SATISFIED. SUBSTITUTION OF PALM TREES.
 PALM TREES MAY BE SUBSTITUTED FOR NOT MORE THAN 35
 PERCENT OF THE SHADE OR FLOWERING TREES REQUIRED BY
 THIS ARTICLE. HOWEVER, WHEN PALM TREES ARE SUBSTITUTED
 FOR SHADE TREES, THREE PALM TREES SHALL BE PROVIDED FOR
 EACH REQUIRED SHADE TREE. THIS 3:1 SUBSTITUTION SHALL
 NOT BE REQUIRED FOR ROYAL PALM TREES (ROYSTONEA SPP.),
 SENEGAL DATE PALM (PHOENIX RECLINATA), MEDJOOL DATE
 PALM (PHOENIX DACTYLIFERA), BISMARCK PALM (BISMARCKIA
 NOBILIS), AND SILVER DATE PALM (PHOENIX SYLVESTRIS).
 94-442 (D)
 PROVIDE THE PERCENTAGE OF PALM TREE SUBSTITUTIONS.
  
  
 4. SATISFIED. EGG ROCK IS NOT AN EXCEPTED GROUND COVER
 FOR LANDSCAPE BEDS. NON CYPRESS HARDWOOD MUCH IS ONLY
 PERMITTED. 94-446 2. A.
  
 5. CONDITIONALLY SATISFIED. CONTINUE ROYAL PALM
 PLANTING & MAINTENANCE AGREEMENT FOR COUNTY RIGHT OF
 WAY PLANTING. PB COUNTY WOULD HAVE TO APPROVE PLANTING
 IN THE RIGHT OF WAY, AND THIS WILL NEED TO BE EXPLORED
 IF IT IS POSSIBLE. SECTION 94-452 ROADWAY
 BEAUTIFICATION APPLIES.
  
  
 ANDREW BURNETT UPDATE 6/9/2021
 561-822-1562
  
 ADDITIONAL COMMENTS 8/16/2021:
 6. CORRECT THE LANDSCAPE AREA EXHIBIT ON SHEET FOR THE
 FOLLOWING:
 ? SATISFIED. PROVIDED LANDSCAPE AREA SHADED SHOULD ONLY
 INCLUDE TERMINAL LANDSCAPE ISLANDS AND VEHICLE
 OVERHANG.
 ? SATISFIED. BUFFERS ARE NOT PART OF PARKING LANDSCAPE
 AREAS, REMOVE SHADING OF THESE. RECALCULATE PROVIDED
 PARKING LANDSCAPE AREA SQUARE FOOTAGE.
  
 6. SATISFIED. THE NEW PAVED AREA SOUTH OF THE PARCEL
 FOR CROSS ACCESS MUST SHOW SOD FOR SOIL STABILIZATION
 AND CURBS ALONG THE PAVED AREA.
  
 7. SATISFIED. CHANGE NOTE ON MULCH TO SPECIFY CYPRESS
 MULCH IS PROHIBITED AND REQUIRED DEPTH IS 3 INCHES.
  
 8. SATISFIED. LANDSCAPE TERMINAL ISLANDS WITH THE
 REQUIRED TREE MUST BE PROVIDED AT THE EAST ENDS OF THE
 NORTH PARKING AREA. THIS WOULD MAKE 8 REQUIRED TREES
 FOR PARKING TERMINAL ISLANDS.
  
 THE ISLAND WITH THE SIGN IS NOT A REQUIRED INTERIOR
 LANDSCAPE ISLAND, SO A TREE IS NOT REQUIRED. TREES MUST
 BE PROVIDED IN TERMINAL ISLANDS AND THE 75% SHADE TREE
 REQUIREMENT MET.
  
 LANDSCAPE COMMENT RESPONSES WERE NOT FOUND WITH THE
 LATEST SUBMITTAL.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF
 RIGHT OF WAY LANDSCAPING AND IRRIGATION APPROVED WITH
 THIS PETITION.
  
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 3 Status F Date 01-25-2022 Cont ID  
Sent By rcaranci Date 01-25-2022 Time 12:06 Rev Time 0.00
Received By rcaranci Date 01-25-2022 Time 12:06 Sent To  
Notes
2022-01-25 12:06:55FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 1225 PALM BEACH LAKES AUTO ZONE Z21050011
 JANUARY 24, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
 THESE COMMENTS WERE NOT INCLUDED IN THE RESPONSE
 LETTER.
 1. SATISFIED. EAST SIDE OF PROPERTY HAS WATER AND POWER
 EASEMENT. TREES SHOULD NOT BE PLANTED ON EASEMENT
 EXISTING TREES SHOULD BE MOVED TO OTHER LOCATIONS ON
 PROJECT SITE. NO CLOSER THAN 5FT OF WATER MAIN.
 PER SECTION 94-443(A)(2)C. , REQUIRED BUFFER TREES MAY
 BE CLUSTERED AND IF THERE IS ADDITIONAL LANDSCAPE AREA
 ADJACENT TO THE BUFFER STRIP, REQUIRED TREES MAY BE
 PLACED ADJACENT TO THE BUFFER STRIP TO ALLOW A GREATER
 AREA FOR TREE DEVELOPMENT.
 IF THE REQUIRED EAST BUFFER TREES ARE TO BE PLACED IN
 THE LANDSCAPE AREAS ADJACENT TO THE EAST BUFFER, MARK
 THEM ON THE PLAN TO IDENTIFY THE COUNT MEETS THE
 REQUIREMENTS. PALMS MAY ALSO BE USED ADJACENT TO THE
 EASEMENT TO PROVIDE THE INTENDED BUFFERING. SHOW THE
 EXISTING TREES ON THE ADJACENT PROPERTY TO COORDINATE
 PLANTING LOCATIONS SO THERE IS NO CONFLICT.
  
 2. SATISFIED. LANDSCAPE BUFFER ON THE NORTH SIDE HAS
 ONLY ROYAL PALMS. THE BUFFER MUST CONTAIN FLOWERING OR
 SHADE TREES, IT CANNOT BE ENTIRELY PALMS AT LEAST ONE
 SHADE TREE PLANTED FOR EACH 30 LINEAR FEET. 94-443 B.
 1.-5.
 UNLESS THERE ARE UTILITY CONFLICTS THAT CAN BE SHOWN ON
 THE PLANS, SHADE TREES MUST BE PROVIDED. SEE DEFINITION
 OF SHADE TREE. THIS WOULD BE A CATEGORY 1 TREE WITH A
 MATURE SPREAD OF AT LEAST 25 FEET.
  
 3. NOT SATISFIED. SUBSTITUTION OF PALM TREES.
 PALM TREES MAY BE SUBSTITUTED FOR NOT MORE THAN 35
 PERCENT OF THE SHADE OR FLOWERING TREES REQUIRED BY
 THIS ARTICLE. HOWEVER, WHEN PALM TREES ARE SUBSTITUTED
 FOR SHADE TREES, THREE PALM TREES SHALL BE PROVIDED FOR
 EACH REQUIRED SHADE TREE. THIS 3:1 SUBSTITUTION SHALL
 NOT BE REQUIRED FOR ROYAL PALM TREES (ROYSTONEA SPP.),
 SENEGAL DATE PALM (PHOENIX RECLINATA), MEDJOOL DATE
 PALM (PHOENIX DACTYLIFERA), BISMARCK PALM (BISMARCKIA
 NOBILIS), AND SILVER DATE PALM (PHOENIX SYLVESTRIS).
 94-442 (D)
 PROVIDE THE PERCENTAGE OF PALM TREE SUBSTITUTIONS.
  
  
 4. SATISFIED. EGG ROCK IS NOT AN EXCEPTED GROUND COVER
 FOR LANDSCAPE BEDS. NON CYPRESS HARDWOOD MUCH IS ONLY
 PERMITTED. 94-446 2. A.
  
 5. CONDITIONALLY SATISFIED. CONTINUE ROYAL PALM
 PLANTING & MAINTENANCE AGREEMENT FOR COUNTY RIGHT OF
 WAY PLANTING. PB COUNTY WOULD HAVE TO APPROVE PLANTING
 IN THE RIGHT OF WAY, AND THIS WILL NEED TO BE EXPLORED
 IF IT IS POSSIBLE. SECTION 94-452 ROADWAY
 BEAUTIFICATION APPLIES.
  
  
 ANDREW BURNETT UPDATE 6/9/2021
 561-822-1562
  
 ADDITIONAL COMMENTS 8/16/2021:
 6. CORRECT THE LANDSCAPE AREA EXHIBIT ON SHEET FOR THE
 FOLLOWING:
 ? SATISFIED. PROVIDED LANDSCAPE AREA SHADED SHOULD ONLY
 INCLUDE TERMINAL LANDSCAPE ISLANDS AND VEHICLE
 OVERHANG.
 ? SATISFIED. BUFFERS ARE NOT PART OF PARKING LANDSCAPE
 AREAS, REMOVE SHADING OF THESE. RECALCULATE PROVIDED
 PARKING LANDSCAPE AREA SQUARE FOOTAGE.
  
 6. SATISFIED. THE NEW PAVED AREA SOUTH OF THE PARCEL
 FOR CROSS ACCESS MUST SHOW SOD FOR SOIL STABILIZATION
 AND CURBS ALONG THE PAVED AREA.
  
 7. SATISFIED. CHANGE NOTE ON MULCH TO SPECIFY CYPRESS
 MULCH IS PROHIBITED AND REQUIRED DEPTH IS 3 INCHES.
  
 8. NOT SATISFIED. LANDSCAPE TERMINAL ISLANDS WITH THE
 REQUIRED TREE MUST BE PROVIDED AT THE EAST ENDS OF THE
 NORTH PARKING AREA. THIS WOULD MAKE 8 REQUIRED TREES
 FOR PARKING TERMINAL ISLANDS.
  
 THE ISLAND WITH THE SIGN IS NOT A REQUIRED INTERIOR
 LANDSCAPE ISLAND, SO A TREE IS NOT REQUIRED. TREES MUST
 BE PROVIDED IN TERMINAL ISLANDS AND THE 75% SHADE TREE
 REQUIREMENT MET.
  
 LANDSCAPE COMMENT RESPONSES WERE NOT FOUND WITH THE
 LATEST SUBMITTAL.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF
 RIGHT OF WAY LANDSCAPING AND IRRIGATION APPROVED WITH
 THIS PETITION.
  
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 08-16-2021 Cont ID  
Sent By rcaranci Date 08-16-2021 Time 11:44 Rev Time 0.00
Received By rcaranci Date 08-16-2021 Time 11:44 Sent To  
Notes
2021-08-16 11:45:05FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 1225 PALM BEACH LAKES AUTO ZONE Z21050011
 AUGUST 16, 2021
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
 THESE COMMENTS WERE NOT INCLUDED IN THE RESPONSE
 LETTER.
 1. PARTIALLY SATISFIED. EAST SIDE OF PROPERTY HAS WATER
 AND POWER EASEMENT. TREES SHOULD NOT BE PLANTED ON
 EASEMENT EXISTING TREES SHOULD BE MOVED TO OTHER
 LOCATIONS ON PROJECT SITE. NO CLOSER THAN 5FT OF WATER
 MAIN.
 PER SECTION 94-443(A)(2)C. , REQUIRED BUFFER TREES MAY
 BE CLUSTERED AND IF THERE IS ADDITIONAL LANDSCAPE AREA
 ADJACENT TO THE BUFFER STRIP, REQUIRED TREES MAY BE
 PLACED ADJACENT TO THE BUFFER STRIP TO ALLOW A GREATER
 AREA FOR TREE DEVELOPMENT.
 IF THE REQUIRED EAST BUFFER TREES ARE TO BE PLACED IN
 THE LANDSCAPE AREAS ADJACENT TO THE EAST BUFFER, MARK
 THEM ON THE PLAN TO IDENTIFY THE COUNT MEETS THE
 REQUIREMENTS. PALMS MAY ALSO BE USED ADJACENT TO THE
 EASEMENT TO PROVIDE THE INTENDED BUFFERING. SHOW THE
 EXISTING TREES ON THE ADJACENT PROPERTY TO COORDINATE
 PLANTING LOCATIONS SO THERE IS NO CONFLICT.
  
 2. PARTIALLY SATISFIED. LANDSCAPE BUFFER ON THE NORTH
 SIDE HAS ONLY ROYAL PALMS. THE BUFFER MUST CONTAIN
 FLOWERING OR SHADE TREES, IT CANNOT BE ENTIRELY PALMS
 AT LEAST ONE SHADE TREE PLANTED FOR EACH 30 LINEAR
 FEET. 94-443 B. 1.-5.
 UNLESS THERE ARE UTILITY CONFLICTS THAT CAN BE SHOWN ON
 THE PLANS, SHADE TREES MUST BE PROVIDED. SEE DEFINITION
 OF SHADE TREE. THIS WOULD BE A CATEGORY 1 TREE WITH A
 MATURE SPREAD OF AT LEAST 25 FEET.
  
 3. NOT SATISFIED. SUBSTITUTION OF PALM TREES.
 PALM TREES MAY BE SUBSTITUTED FOR NOT MORE THAN 35
 PERCENT OF THE SHADE OR FLOWERING TREES REQUIRED BY
 THIS ARTICLE. HOWEVER, WHEN PALM TREES ARE SUBSTITUTED
 FOR SHADE TREES, THREE PALM TREES SHALL BE PROVIDED FOR
 EACH REQUIRED SHADE TREE. THIS 3:1 SUBSTITUTION SHALL
 NOT BE REQUIRED FOR ROYAL PALM TREES (ROYSTONEA SPP.),
 SENEGAL DATE PALM (PHOENIX RECLINATA), MEDJOOL DATE
 PALM (PHOENIX DACTYLIFERA), BISMARCK PALM (BISMARCKIA
 NOBILIS), AND SILVER DATE PALM (PHOENIX SYLVESTRIS).
 94-442 (D)
 PROVIDE THE PERCENTAGE OF PALM TREE SUBSTITUTIONS.
  
  
 4. SATISFIED. EGG ROCK IS NOT AN EXCEPTED GROUND COVER
 FOR LANDSCAPE BEDS. NON CYPRESS HARDWOOD MUCH IS ONLY
 PERMITTED. 94-446 2. A.
  
 5. PARTIALLY SATISFIED. CONTINUE ROYAL PALM PLANTING &
 MAINTENANCE AGREEMENT FOR COUNTY RIGHT OF WAY PLANTING.
 PB COUNTY WOULD HAVE TO APPROVE PLANTING IN THE RIGHT
 OF WAY, AND THIS WILL NEED TO BE EXPLORED IF IT IS
 POSSIBLE. SECTION 94-452 ROADWAY BEAUTIFICATION
 APPLIES.
  
  
 ANDREW BURNETT UPDATE 6/9/2021
 561-822-1562
  
 ADDITIONAL COMMENTS 8/0/2021:
 6. CORRECT THE LANDSCAPE AREA EXHIBIT ON SHEET FOR THE
 FOLLOWING:
 ? PROVIDED LANDSCAPE AREA SHADED SHOULD ONLY INCLUDE
 TERMINAL LANDSCAPE ISLANDS AND VEHICLE OVERHANG.
 ? BUFFERS ARE NOT PART OF PARKING LANDSCAPE AREAS,
 REMOVE SHADING OF THESE. RECALCULATE PROVIDED PARKING
 LANDSCAPE AREA SQUARE FOOTAGE.
  
 6. THE NEW PAVED AREA SOUTH OF THE PARCEL FOR CROSS
 ACCESS MUST SHOW SOD FOR SOIL STABILIZATION AND CURBS
 ALONG THE PAVED AREA.
  
 7. CHANGE NOTE ON MULCH TO SPECIFY CYPRESS MULCH IS
 PROHIBITED AND REQUIRED DEPTH IS 3 INCHES.
  
 8. LANDSCAPE TERMINAL ISLANDS WITH THE REQUIRED TREE
 MUST BE PROVIDED AT THE EAST ENDS OF THE NORTH PARKING
 AREA. THIS WOULD MAKE 8 REQUIRED TREES FOR PARKING
 TERMINAL ISLANDS.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 06-07-2021 Cont ID  
Sent By aburnett Date 06-07-2021 Time 14:59 Rev Time 0.00
Received By aburnett Date 06-07-2021 Time 14:59 Sent To  
Notes
2021-06-07 15:00:221. EAST SIDE OF PROPERTY HAS WATER AND POWER EASEMENT.
 TREES SHOULD NOT BE PLANTED ON EASEMENT EXISTING TREES
 SHOULD BE MOVED TO OTHER LOCATIONS ON PROJECT SITE. NO
 CLOSER THAN 5FT OF WATER MAIN.
  
 2. LANDSCAPE BUFFER ON THE NORTH SIDE HAS ONLY ROYAL
 PALMS. THE BUFFER MUST CONTAIN FLOWERING OR SHADE
 TREES, IT CANNOT BE ENTIRELY PALMS AT LEAST ONE SHADE
 TREE PLANTED FOR EACH 30 LINEAR FEET. 94-443 B. 1.-5.
  
 3. SUBSTITUTION OF PALM TREES.
 PALM TREES MAY BE SUBSTITUTED FOR NOT MORE THAN 35
 PERCENT OF THE SHADE OR FLOWERING TREES REQUIRED BY
 THIS ARTICLE. HOWEVER, WHEN PALM TREES ARE SUBSTITUTED
 FOR SHADE TREES, THREE PALM TREES SHALL BE PROVIDED FOR
 EACH REQUIRED SHADE TREE. THIS 3:1 SUBSTITUTION SHALL
 NOT BE REQUIRED FOR ROYAL PALM TREES (ROYSTONEA SPP.),
 SENEGAL DATE PALM (PHOENIX RECLINATA), MEDJOOL DATE
 PALM (PHOENIX DACTYLIFERA), BISMARCK PALM (BISMARCKIA
 NOBILIS), AND SILVER DATE PALM (PHOENIX SYLVESTRIS).
 94-442 (D)
  
  
 4 EGG ROCK IS NOT AN EXCEPTED GROUND COVER FOR
 LANDSCAPE BEDS. NON CYPRESS HARDWOOD MUCH IS ONLY
 PERMITTED. 94-446 2. A.
  
 5. CONTINUE ROYAL PALM PLANTING & MAINTENANCE AGREEMENT
 FOR COUNTY RIGHT OF WAY PLANTING
  
  
 ANDREW BURNETT UPDATE 6/9/2021
 561-822-1562
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 3 Status P Date 01-10-2022 Cont ID  
Sent By   Date 01-10-2022 Time   Rev Time 0.00
Received By   Date 01-10-2022 Time   Sent To  
Notes
2022-01-10 13:47:35NO FURTHER COMMENTS.
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]

Review Stop PW PUBLIC WORKS
Rev No 2 Status F Date 07-28-2021 Cont ID  
Sent By   Date 07-28-2021 Time   Rev Time 0.00
Received By   Date 07-28-2021 Time   Sent To  
Notes
2021-07-28 13:25:11 
  
 PLEASE PROVIDE THE FOLLOWINGS:
 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID
 WASTE VOLUME PRODUCED ALONG WITH THE SIZE, TYPE AND
 QUANTITY OF THE CONTAINER (I.E. DUMPSTER/COMPACTOR)
 THAT WILL BE UTILIZED THAT WILL BE UTILIZED FOR THE
 SANITATION SERVICE.
 2- REVISED SSHEET C-05 TO REFLECT THE LATEST REVISON OF
 CITY`S DUMPSTER ENCLOSURE SPEC.L. FOR A FREESTANDING
 SITE DUMPSTER ENCLOSURE, THE ENCLOSURE SHALL COMPLY
 WITH THE LATEST REVISION OF CITY OF WEST PALM BEACH
 GENERAL CONSTRUCTION-GARBAGE ENCLOSURE STANDARD, GC-7.
 3- AUTOTURN EXHIBIT (DYNAMIC ENVELOPE AND THE VEHICLE?S
 WHEEL PATH) FOR THE SANITATION SERVICE, FRONT LOADER
 TRUCK WITH THE FOLLOWING SPECS:
 - DUAL AXLES
 - TRUCK LENGTH: 35 FT
 - TRUCK WIDTH: 11 FT
 - TURNING RADIUS:
 - SAE TURNING RADIUS: 32.5 FT
 - CURB-TO-CURB DIAMETER: 74 FT
 - WALL-TO-WALL DIAMETER: 86.3 FT
  
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045
  

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 06-07-2020 Cont ID  
Sent By   Date 06-07-2021 Time   Rev Time  
Received By   Date 06-07-2021 Time   Sent To  
Notes
2021-06-07 14:46:52PLEASE PROVIDE THE FOLLOWINGS:
 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID
 WASTE VOLUME PRODUCED ALONG WITH THE SIZE, TYPE AND
 QUANTITY OF THE CONTAINER (I.E. DUMPSTER/COMPACTOR)
 THAT WILL BE UTILIZED THAT WILL BE UTILIZED FOR THE
 SANITATION SERVICE.
 2- DUMPSTER ENCLOSURE DETAIL. FOR A FREESTANDING SITE
 DUMPSTER ENCLOSURE, THE ENCLOSURE SHALL COMPLY WITH THE
 LATEST REVISION OF CITY OF WEST PALM BEACH GENERAL
 CONSTRUCTION-GARBAGE ENCLOSURE STANDARD, GC-7.
 3- AUTOTURN EXHIBIT (DYNAMIC ENVELOPE AND THE VEHICLE?S
 WHEEL PATH) FOR THE SANITATION SERVICE, FRONT LOADER
 TRUCK WITH THE FOLLOWING SPECS:
 - DUAL AXLES
 - TRUCK LENGTH: 35 FT
 - TRUCK WIDTH: 11 FT
 - TURNING RADIUS:
 - SAE TURNING RADIUS: 32.5 FT
 - CURB-TO-CURB DIAMETER: 74 FT
 - WALL-TO-WALL DIAMETER: 86.3 FT
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045
  

Review Stop STORM STORMWATER
Rev No 2 Status P Date 03-01-2022 Cont ID  
Sent By tward Date 03-01-2022 Time 10:37 Rev Time 0.00
Received By tward Date 03-01-2022 Time 10:37 Sent To  
Notes
2022-03-01 10:37:17THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 2-17-2022 SUBMITTAL. THEY CAN BE ADDRESSED DURING
 ENGINEERING PERMIT SUBMITTAL.
  
 1. SHOW THE 2-FT PARKING OVERHANG LIMITS (DASHED LINE)
 ON THE PAVEMENT MARKING AND SIGNANGE PLAN, THE UTILITY
 PLAN AND THE LANDSCAPE PLAN.
  
 2. SHEET C-06 PAVEMENT MARKLING AND SIGNANGE PLAN
 A. SHOULD THE DIAGONAL LINES FOR THE LOADING AREA SOUTH
 OF THE BUILDING BE TURNED 90 DEGREES?
 B. ANY SIGNAGE OR PAVEMENT MARKINGS TO INDICATE AREA IS
 A LOADING AREA?
 C. SHOULD LOADING AREA PAVEMENT MARKINGS BE EXCLUDED
 FROM THE PEDESTRIAN CROSSWALK?
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  

Review Stop STORM STORMWATER
Rev No 1 Status F Date 06-10-2021 Cont ID  
Sent By tward Date 06-10-2021 Time 12:16 Rev Time 0.00
Received By tward Date 06-10-2021 Time 12:18 Sent To  
Notes
2021-06-10 12:18:29THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. THE CITY'S OFFICIAL VERTICAL DATUM PER CITY CODE IS
 NGVD1929. THE CITY IS ALLOWING SURVEYS AND PLANS TO USE
 NAVD1988 PROVIDED THE CONVERSION EQUATION BETWEEN
 NAVD1988 AND NGVD1929 IS ALSO PROVIDED. PROVIDE THE
 CONVERSION EQUATION ON THE SURVEY.
  
 2. FLOATING TURBIDITY CURTAIN MAY BE NEEDED AROUND THE
 END OF THE STORM OUTFALL PIPES IN THE CARVER CANAL.
  
 3. CONSIDER REDUCING PARKING SPACES BY TWO FEET AND
 PROVIDE TWO FEET LANDSCAPED OVERHANG.
  
 4. PROVIDE AGREEMENT TO ALLOW CONNECTION TO THE
 DRAINAGE SYSTEM IN THE 12 FT DRAINAGE EASEMENT.
  
 5. THE CITY DOES NOT ALLOW THE USE OF BLEEDERS WITH
 EXFILTRATION TRENCHES.
  
 6. LABEL THE PROPOSED CURBS. CURB TRANSITIONS MAY BE
 NEEDED AT THE DRIVEWAY ENTRANCES.
  
 7. PROVIDE CROSS SECTIONS FROM EACH LOT LINE TO THE
 FACE OF BUILDING. SHOW GRADE BREAKS AND FLOW DIRECTION.
 PROVIDE CROSS SLOPE IF GREATER THAN 2 PERCENT.
  
 8. SHOW UTILITIES ON THE LANDSCAPE PLAN.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3. PROVIDE A COPY OF THE SFWMD ERP OR ERP MODIFICATION
 IF THERE IS AN EXISTING PERMIT.
  
 4. DRAINAGE CALCULATIONS WILL BE REVIEWED WITH THE
 ENGINEERING PERMIT APPLICATION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 3 Status P Date 03-03-2022 Cont ID  
Sent By vnoel Date 03-03-2022 Time 08:05 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2022-03-03 08:07:03CONDITIONS OF APPROVAL PRIOR TO BUILDING PERMIT:
  
 1. SIGNED AND SEALED COPY OF SURVEY.
 2. CROSS ACCESS/UTILITY AGREEMENT.

Review Stop SURVEY SURVEYING
Rev No 2 Status F Date 01-13-2022 Cont ID  
Sent By vnoel Date 01-13-2022 Time 07:19 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2022-01-13 07:24:271. SURVEY NEEDS TO BE SIGNED AND SEALED.
 2. SURVEY NEEDS TO REFLECT PLAT RECORDED IN PLAT BOOK
 132 P. 148.
 3. CROSS ACCESS/UTILITY AGREEMENT WILL BE REQUIRED
 PRIOR TO FINAL APPROVAL.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 06-07-2021 Cont ID  
Sent By vnoel Date 06-07-2021 Time 10:41 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2021-06-07 11:18:301. PROPERTY IS CURRENTLY BEING REPLATTED.
 2. EXISTING UTILITIES NEED TO BE LOCATED AND SURVEYED,
 NOT PER ATLAS.
 3. CROSS ACCESS/UTILITY AGREEMENT WILL BE REQUIRED.
 4. TREES MAY NOT BE ALLOWED IN RETENTION AREAS. CHECK
 WITH TRACY WARD.
 5. PALM BEACH LAKES IS CURRENTLY UNDER CONSTRUCTION.
 SHOW PROPOSED IMPROVEMENTS PER PB COUNTY PLANS.
 6. NO TREES ALLOWED WITHIN 5 FEET OF EXISTING WATER
 MAIN ALONG EAST PROPERTY LINE.
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status P Date 09-22-2021 Cont ID  
Sent By   Date 09-22-2021 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2021-09-22 16:14:39NO FURTHER COMMENTS.
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 06-10-2021 Cont ID  
Sent By   Date 06-10-2021 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2021-06-10 02:05:10TRAFFIC COMMENTS
 1) PROVIDE AUTOTURN ANALYSIS FOR GARBAGE TRUCK AND
 SERVICE VEHICLES DRIVING IN AND OUT OF THE PROPOSED
 DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES CLEARLY
 DEFINED. ANALYSIS SHOULD BE PROVIDED IN A SEPARATE
 FILE/DRAWING
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 09-16-2021 Cont ID  
Sent By rthermid Date 09-16-2021 Time   Rev Time 0.00
Received By rthermid Date 09-16-2021 Time   Sent To  
Notes
2021-09-16 10:07:33PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW
 (RESUBMITTAL)
 ________________________________________
  
 DATE OF REVIEW: 9/16/2021
 PROJECT NO.: Z21050011
 CASE NO.: 21-07
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS WHICH WERE ISSUED PREVIOUSLY, AND HAVE
 NOT BEEN FULLY SATISFIED:
  
 1. [CONDITIONS OF APPROVAL] - PER THE LANDSCAPING
 COMMENTS, PRIOR TO THE REMOVAL OR RELOCATION OF ANY
 TREES ON SITE, A TREE ALTERATION PERMIT WILL HAVE TO BE
 OBTAINED AND APPROVED BY THE DEVELOPMENT SERVICES,
 PLANNING DIVISION.
  
 2. PRIOR TO FINAL APPROVAL, UPDATE THE PLANS TO SHOW
 THE 2' OVERHANG AND WHEEL STOPS AT ALL PARKING SPACES.
 ________________________________________
  
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
  
 B) 6 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE
 PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X
 17IN), AND AN ELECTRONIC COPY OF ALL PLANS.
  
 C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
  
 D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561-822-1443
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 06-10-2021 Cont ID  
Sent By rthermid Date 06-10-2021 Time   Rev Time  
Received By rthermid Date   Time   Sent To  
Notes
2021-06-10 11:15:27PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW
 (RESUBMITTAL)
 DATE OF REVIEW: 6/9/2021
 PROJECT NO.: Z21050011
 CASE NO.: ISPR 21-07
 ________________________________________
 GENERAL COMMENTS
  
 1. THE PROPERTY IS CURRENTLY BEING REPLATTED.
 2. ALL PROJECTS TOTALING OVER $750,000 WILL BE SUBJECT
 TO THE CITY OF WPB ART IN PUBLIC PLACES ORDINANCE.
 PLEASE CONTACT SYBILLE WELTER AT [email protected] FOR
 MORE INFORMATION.
 3. CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR AT
 [email protected] TO ESTABLISH ADDRESSES FOR THE
 STRUCTURES.
 4. PLEASE PROVIDE THE FOLLOWING ITEMS WHICH WERE
 MISSING FROM THE APPLICATION: PUBLIC UTILITY LETTER
 FROM COMCAST, CITY SERVICE LETTER.
  
 SITE PLAN COMMENTS
  
 CONNECTION/ACCESS
 5. A CROSS-ACCESS/UTILITY AGREEMENT WILL BE REQUIRED.
 6. PALM BEACH LAKES IS CURRENTLY UNDER CONSTRUCTION,
 SHOW PROPOSED IMPROVEMENTS PER PALM BEACH COUNTY PLANS.
 PARKING
 7. PROVIDE WHEEL STOPS AT ALL THE 18 FOOT PARKING SPOTS
 ADJACENT TO THE NORTHERN SIDE OF THE PROPERTY ADJACENT
 TO THE SIDEWALK ALONG PALM BEACH LAKES BOULEVARD; AND
 THE SOUTHEASTERN UTILITY EASEMENT.
  
 LANDSCAPE
 8. EAST SIDE OF THE PROPERTY HAS WATER/POWER EASEMENTS,
 TREES SHALL NOT BE PLANTED ON EASEMENT. EXISTING TREES
 SHALL BE MOVED TO OTHER LOCATIONS ON PROJECT SITE, NO
 CLOSER THAN 5 FEET.
 9. THE LANDSCAPE BUFFER ON THE NORTH SIDE OF THE
 PROPERTY MUST CONTAIN FLOWERING OR SHADE TREES, IT
 SHALL NOT BE ENTIRELY PALMS. PER SECTION 94-443.B.1-5:
 THERE SHALL BE ONE (1) SHADE TREE PER THIRTY (30)
 LINEAR FEET.
  
 OTHER SITE PLAN COMMENTS
 10. THE PROPOSED BICYCLE RACK (WIDE U BIKE RACK) IS NOT
 ALLOWED IN THE CITY OF WEST PALM BEACH. PROVIDE THE
 REQUIRED BICYCLE PARKING CONSISTENT WITH ALLOWED BIKE
 RACKS IN THE CITY AND A STANDARD CITY DETAIL.
 11. PROVIDE SPACING DIMENSIONS BETWEEN BIKE RACKS.
 12. INCLUDE THE DIMENSIONS OF MECHANICAL EQUIPMENT FROM
 THE SOUTHERN SIDE OF THE BUILDING TO PROPERTY LINES.
  
 DATA TABLE/LEGEND
 13. PLEASE ENCLOSE THE SITE DATA TABLE ELEMENTS WITHIN
 A TABLE.
  
  
 INSTRUCTIONS FOR RESUBMITTAL:
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
 WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FOUR (4)
 COPIES, ONE (1) REDUCED COPY IN 8.5 INCHES X 11 INCHES
 AND ONE (1) SET IN 11 INCHES X 17 INCHES, AND AN
 ELECTRONIC COPY OF ALL PLANS. NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS MAY RESULT IN ADDITIONAL COMMENTS.
 PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE.
  
 RAFAELA THERMIDOR,
 ASSOCIATE PLANNER
  

  Print