Plan Review Details - Project Z21040002
Plan Review Stops For Project Z21040002
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 4 Status P Date 07-01-2022 Cont ID  
Sent By scwelter Date 07-01-2022 Time 11:57 Rev Time 0.00
Received By scwelter Date 07-01-2022 Time 11:59 Sent To  
Notes
2022-07-01 11:59:50ART ASSESSMENT APPLICATION COMPLETED. OPTION 2
 INVOICE PREPARED AND SENT TO DEVELOPER WHICH MUST BE
 PAID PRIOR TO OR AT THE TIME OF BUILDING PERMIT FEES.
  
 ANY QUESTIONS CONTACT [email protected]

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 3 Status F Date 05-16-2022 Cont ID  
Sent By scwelter Date 05-16-2022 Time 14:34 Rev Time 0.00
Received By scwelter Date 05-16-2022 Time 14:37 Sent To  
Notes
2022-05-16 14:36:49NEED TO COMPLETE AN ART ASSESSMENT APPLICATION ASAP -
 EMAIL [email protected]

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 2 Status F Date 02-07-2022 Cont ID  
Sent By scwelter Date 02-07-2022 Time 12:48 Rev Time 0.00
Received By scwelter Date 02-07-2022 Time 12:55 Sent To  
Notes
2022-02-07 12:55:35DEVELOPER MUST COMPLETE AN ART ASSESSMENT APPLICATION
 AT THE TIME OF BUILDING PERMIT SUBMITTAL.
  
 TWO OPTIONS:
 1. ART ON SITE AT 1% OF TOTAL CONSTRUCTION COSTS
 OR
 2. .75% (-25% OF 1%) INTO THE PUBLIC ART ACCOUNT.
  
 EMAIL [email protected] TO OBTAIN AN ART ASSESSMENT
 APPLICATION.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status F Date 04-27-2021 Cont ID  
Sent By scwelter Date 04-27-2021 Time 15:10 Rev Time 0.00
Received By scwelter Date   Time   Sent To  
Notes
2021-04-27 15:11:33PUBLIC ART REQUIREMENT:
 IF TOTAL CONSTRUCTION COSTS OF THIS DEVELOPMENT ARE
 OVER $500,000 IT WILL BE SUBJECT TO THE PUBLIC ART
 REQUIREMENT AS PER CITY ORDINANCE.
 SECTION 78-129: ALL PRIVATE DEVELOPMENT PROJECTS,
 INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR
 IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL
 CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000 ARE SUBJECT TO THE PUBLIC ART REQUIREMENT.
 OPTION 1: INSTALL ARTWORK ON THE DEVELOPMENT SITE
 VALUED IN AN AMOUNT NOT LESS THAN ONE PERCENT OF THE
 TOTAL CONSTRUCTION COSTS; OR
 OPTION 2: CONTRIBUTE AN AMOUNT EQUAL TO 75 PERCENT OF
 ONE PERCENT OF THE TOTAL CONSTRUCTION COSTS FOR DEPOSIT
 TO THE PUBLIC ART ACCOUNT.
 A COMPLETED PUBLIC ART ASSESSMENT APPLICATION IS
 REQUIRED AT TIME OF BUILDING PERMIT SUBMITTAL.
  
 PLEASE CONTACT SYBILLE WELTER AT [email protected] OR
 561.822.1521 TO OBTAIN AN APPLICATION AND REVIEW THE
 REQUIREMENTS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 05-13-2021 Cont ID  
Sent By rbrown Date 05-13-2021 Time 09:56 Rev Time 0.00
Received By rbrown Date 05-13-2021 Time 09:56 Sent To  
Notes
2021-05-13 10:00:59DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS
 SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT
 REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH
 COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963,
 OR BY EMAIL: [email protected]
  
 3. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 4. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE
 REQUIRED. FOR INFORMATION ON THE REQUIRED TYPE, SIZE
 AND LOCATION, PLEASE CONTACT TIM LARGE, CHIEF PLUMBING
 INSPECTOR, DEVELOPMENT SERVICES DEPARTMENT, AT (561)
 805-6692, OR BY EMAIL: [email protected]
  
 5. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 6. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 7. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT
 TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE
 ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP
 ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 8. BUILDING ADDRESS. THE ENTRANCES FOR THE NEW
 BUILDINGS AND TENANTS WILL BE IN DIFFERENT LOCATIONS
 FROM THE EXISTING. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION
 OF THE BUILDING ENTRANCE ALONG SOUTHERN BLVD. FOR
 STREET ADDRESSING, CONTACT CAROLINE PUELL, ADDRESSING
 COORDINATOR, AT (561) 805 6659, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 4 Status P Date 05-06-2022 Cont ID  
Sent By rrossano Date 05-06-2022 Time   Rev Time 0.00
Received By rrossano Date 05-06-2022 Time   Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 3 Status F Date 01-19-2022 Cont ID  
Sent By LDeLoren Date 01-19-2022 Time   Rev Time 0.00
Received By rrossano Date 01-19-2022 Time   Sent To  
Notes
2022-01-26 07:04:59COMMENTS FROM MICHAEL TECHNOW, PROJECT ENGINEER, WPB
 PUBLIC UTILITIES, 561-494-1047, [email protected] :
  
 SHEET C-501
 - ADD NOTE TO CUT AND CAP EXISTING 8? CAS PIPE AT THE
 MAIN DURING REMOVAL.
 - PROVIDE PROFILE FROM TAP TO POINT OF SERVICE SHOWING
 EXISTING UTILITIES AND CONFLICTS FOR WATER SERVICES AND
 FIRE LINE ON NOTTINGHAM BLVD.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status F Date 08-05-2021 Cont ID  
Sent By rrossano Date 08-05-2021 Time   Rev Time 0.00
Received By rrossano Date 08-05-2021 Time   Sent To  
Notes
2021-08-05 07:21:02COMMENT PER RICK ROSSANO, PROJECT COORDINATOR, ENG.
 SERVICES DEPT., DIRECT: (561) 494-1098 [email protected]
  
 PLEASE SHOW PARAMETERS OF UTILITY EASEMENTS FOR
 PROPOSED UTILITY WATER METERS IN BLOW UP 1 ON PAGE
 C-501.
  
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
 -THERE IS CROSS WALK AT NORTH SIDE OF BUILDING WITH
 MARKINGS THAT RUN INTO ISLAND CURB. PLEASE CORRECT.
  
 -THE ACCESSIBILITY PLAN DOES NOT SHOW ROUTE FROM ROW
 SIDEWALK TO BANK. IS THERE ONE?
  
 -ADD A SMALL UTILITY EASEMENT ALL THE WAY AROUND THE
 PROPOSED FIRE HYDRANT WITH ITS PIPING.
  
 -ONE OF THE WATER SERVICES NEAR THE DUMPSTER DOES NOT
 HAVE PLUMBING PIPE SHOWN. IS IT FOR IRRIGATION?
  
 -WILL THE IRRIGATION WATER SERVICE AT NORTH SIDE OF THE
 PROPERTY IRRIGATE THE SOUTH SIDE OF PROPERTY?
  
 -FOR FORMAL ENGINEERING SUBMITTAL: ADD ADDITIONAL GATE
 VALVES IN THE GRASS AFTER THE SIDEWALK FOR THE
 FIRELINES NEAR THE DUMPSTER AND LABEL THEM POINT OF
 SERVICE; LABEL ALL PROPOSED WATER SERVICE PIPE WITH
 PIPE SIZE AND MATERIAL TYPE.
  
 -IS THE SEWER LATERAL FOR THE WESTERN BUILDING SHOWN ON
 THE UTILITY PLAN?
  
 -VERIFY THE EXISTING WATER SERVICE SHOWN IN THE AREA OF
 BLOW UP 1 IS BEING REMOVED, AND ONE OF THE PROPOSED NEW
 METERED WATER SERVICES WILL CONTINUE PROVIDING WATER
 SERVICE AFTER PROJECT IS COMPLETED.
  
 -THE SEWER LATERALS FOR THE EAST BUILDING AND BANK ARE
 NOT SHOWN ON UTILITY PLAN. IF THEY ARE CONNECTED TO THE
 EXISTING 8 INCH CLAY SEWER PIPE AT THE REAR OF THE
 STORES, WILL THE EXISTING AND PROPOSED SEWER SYSTEMS
 FUNCTION PROPERLY?
  
 -THERE APPEAR TO BE BOLLARDS AROUND THE PROPOSED FIRE
 HYDRANT. CHECK TO SEE IF THEY COMPLY WITH STANDARD
 DETAIL P-8.
  
 -1.5 INCH METERS REQUIRE 2 INCH SERVICE PIPE BETWEEN
 THE METER AND WATER MAIN.
  
 -PAVEMENT RESTORATION BOUNDARIES ON NOTTINGHAM LOOK
 SMALLER THAN REQUIRED. CHECK DIMENSIONS NEEDED ON THE
 TRENCHING OR PAVEMENT RESTORATION STANDARD DETAILS AND
 ADJUST.
  
 -IS THERE AN FDC FOR THE EASTERN PROPOSED 8 INCH DCDA?
 IF NOT, IS ONE NEEDED?
  
 -ARE ANY OF THE PROPOSED RETAIL SHOPS PLANNING TO BE
 RESTAURANTS?
  
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 DIRECT: (561) 494-1098 [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 05-13-2021 Cont ID  
Sent By rrossano Date 05-13-2021 Time   Rev Time  
Received By rrossano Date 05-13-2021 Time   Sent To  
Notes
2021-05-13 08:29:231. THE CITY OF WEST PALM BEACH HAS A NUMBER OF
 REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY
 AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND
 WASTEWATER UTILITIES WITHIN THE CITY. TO VIEW
 DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AND OTHER
 ENGINEERING RELATED DOCUMENTS, CLICK HERE OR GO TO: HTT
 PS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING/ENGINEERING-FOR
 MS-PERMITS-AND-APPLICATIONS .
 2. CODE OF ORDINANCES, CITY OF WEST PALM BEACH,
 FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED
 SEPT. 22, 2008. (SUPPLEMENT NO. 18) CHAPTER 90
 UTILITIES, ARTICLE I. SEC. 90-7.
 POLICY REGARDING EXTENSION OF WATER OR SEWER SERVICE
 FACILITIES OF THE CITY:
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
 3. AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, CLICK HERE OR GO TO: HTTPS://WWW.WPB.
 ORG/GOVERNMENT/ENGINEERING/ENGINEERING-FORMS-PERMITS-AN
 D-APPLICATIONS .
 4. PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1040 FOR FURTHER
 ASSISTANCE.
 5. PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS
 OF ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES,
 INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND
 SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES,
 METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE
 SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 PLEASE SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL. ADDITIONALLY, PLAN VIEW SHALL SHOW ALL
 EXISTING AND PROPOSED UNDERGROUND UTILITY LAYOUT,
 INCLUDING FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED ON THE
 RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL
 UTILITY CROSSINGS.
 6. CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 ROW.
 7. PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE
 DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB
 DEVELOPMENT APPLICATION).
 8. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM
 AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE
 PER FAC 64E-8 FOR WATER AND PER FAC 64-E.008 FOR SEWER.
 9. SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION
 (NAVD 88 AND NGVD 29).
 10. PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND
 STORMWATER ALONG ENTIRE PROJECT FRONTAGE.
 11. PLEASE ADD NOTE TO PLANS SPECIFYING CITY?S
 DOWNSTREAM LIFT STATION NUMBER.
 12. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
 13. PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR
 PROPOSED SANITARY LATERALS.
 14. PLEASE LABEL WATER LINES AS PRIVATE WHERE
 APPLICABLE.
 15. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED
 LOCATION OF WATER METER AND BACKFLOW PREVENTION.
 16. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING
 PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT
 HIM AT 561-494-2262 OR [email protected]
 17. PROVIDE DEDICATED UTILITY EASEMENTS TO ALLOW ACCESS
 FOR CITY PERSONNEL TO PROPOSED UTILITY WATER METERS.
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
 -PROPOSED WATER METERS AND ASSOCIATED BACKFLOW
 ASSEMBLIES NEED TO BE LOCATED ADJACENT TO THE PROPERTY
 LINE.
  
 -SHOW AND LABEL ALL EXISTING AND PROPOSED FIRELINES
 WATER SERVICES ON THE UTILITY PLAN. THERE MAY BE SOME
 MISSING.
  
 -SINGLE METERED SERVICES ARE STANDARD ? NOT MULTIPLE OR
 BRANCHED.
  
 -SHOW AND LABEL ALL EXISTING AND PROPOSED WATER
 SERVICES, METERS, AND BACKFLOW ASSEMBLIES ON THE CIVIL
 PLANS (DEMO & UTILITY). MAKE SURE LABELS TELL WHAT IS
 HAPPENING TO THEM.
  
 -ADD RP TO LABELS OF DOMESTIC AND IRRIGATION BACKFLOW
 ASSEMBLIES.
  
 -LABEL EXISTING AND PROPOSED WATER MAINS WITH PIPE SIZE
 AND MATERIAL TYPE.
  
 -SHOW AND LABEL EXISTING AND PROPOSED WATER GATE VALVES
 THAT ARE 3 INCHES OR LARGER.
  
 -ATTEMPT TO NOT LOCATE WATER MAINS UNDER STRUCTURES OR
 CONCRETE SLABS.
  
 -SHOW AND LABEL ALL EXISTING AND PROPOSED UTILITY
 EASEMENTS. FOR EXAMPLE BELLSOUTH EASEMENT IS LABELED ON
 SURVEY, BUT NOT LABELED ON UTILITY PLAN.
  
 -THERE ARE SEVERAL MONITORING WELL LIDS/CAPS AROUND THE
 SOUTHEAST AREA OF PROPERTY. PLEASE SHOW AND LABEL
 THOSE, AND PROVIDE MORE DETAIL ABOUT THEM.
  
 -FOR FORMAL ENGINEERING SUBMITTAL: ADD SIZES TO LABELS
 FOR BACKFLOW ASSEMBLIES, ADD ELEVATION INFORMATION TO
 LABELS FOR SEWER MANHOLES.
  
 -PLEASE ADD WATER DEMAND CALCULATIONS TO UTILITY PLAN.
  
 -WILL FPU AND BELLSOUTH ALLOW OTHER UTILITIES TO CROSS
 THEIR EASEMENTS?
  
 -SEVERAL LANDSCAPE ISLANDS ENCROACH INTO FPU EASEMENT.
 IS THAT ACCEPTABLE?
  
 -PLEASE SHOW PROPOSED UTILITIES ON LANDSCAPING PLAN SO
 ANY CONFLICTS CAN BE IDENTIFIED.
  
 -SHOW AND LABEL EXISTING AND PROPOSED UTILITIES FOR THE
 BANK NEAR NORTHEAST CORNER OF PROPERTY.
  
 -ENSURE THAT ALL FIRELINES WILL HAVE ADEQUATE WATER IF
 USED AT THE SAME TIME.
  
 -THERE APPEARS TO BE WATER METER AT THE NORTH PROPERTY
 LINE ADJACENT SOUTHERN BLVD. WILL IT REMAIN AND WHAT
 WILL IT BE USED FOR?
  
 -ROOT BARRIERS MAY NEED TO BE INSTALLED WHERE TREES ARE
 CLOSE TO UTILITY LINES. (SUCH AS THE TREES NEAR THE GAS
 PIPING)
  
 -ANY PROPOSED DOMESTIC WATER METERS 3 INCHES AND LARGER
 MUST BE CONSTRUCTED ABOVE-GROUND.
  
 -WILL THE STORES THAT ARE NOT BEING DEMOLISHED BE OPEN
 DURING DEMOLITION AND CONSTRUCTION?
  
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 DIRECT: (561) 494-1098 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 01-12-2022 Cont ID  
Sent By pleduc Date 01-12-2022 Time   Rev Time 0.00
Received By pleduc Date 01-12-2022 Time 14:35 Sent To  
Notes
2022-01-12 14:38:21AFTER A REVIEW OF THE PPRC RESUBMITTAL PACKET THE
 PREVIOUSLY SUBMITTED FIRE PREVENTION BUREAU COMMENTS
 APPEAR TO HAVE BEEN ADDRESSED.
  
 HOWEVER, THE BUREAU'S APPROVAL OF THIS SUBMITTED
 PROJECT DOES NOT CONSTITUTE ITS FINAL REVIEW OR
 APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE DEPARTMENT
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 05-06-2021 Cont ID  
Sent By pleduc Date 05-06-2021 Time   Rev Time 0.00
Received By pleduc Date 04-29-2021 Time 16:17 Sent To  
Notes
2021-05-06 12:56:48THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE DEPARTMENT.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT. THE FOLLOWING COMMENTS ARE INTENDED
 TO PROVIDE GUIDANCE FOR BUILDING PLAN SUBMITTAL.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE,
 AND WHETHER IT IS MIXED OR SEPARATED OCCUPANCY.
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 THE PROPOSED LOCATIONS OF THE FIRE HYDRANT AND FDC ARE
 ACCEPTABLE WITH ANY CHANGES CLOSELY COORDINATED WITH
 THE BUREAU OF FIRE PREVENTION.
  
 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM,
 ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND
 SUBMITTED WITH THE MASTER PERMIT.
  
 9A) THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE
 LOCATIONS SHALL MEET THE REQUIREMENTS OF NFPA 24 AND
 SHALL BE COORDINATED WITH THE OFFICE OF FIRE MARSHAL,
 THE CITY'S ENGINEERS OFFICE, THE LANDSCAPE PLANNER, AND
 THE CITY'S PLANNING AND ZONING OFFICE.
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 11. MINIMUM TWO-WAY RADIO COMMUNICATIONS RADIO STRENGTH
 IS REQUIRED PER NFPA 1 & 72
  
 ANY REQUIRED SYSTEM SHALL MAINTAIN A MINIMUM RADIO
 SIGNAL STRENGTH OF -95 DBM FOR THE RADIO SYSTEM USED BY
 WEST PALM BEACH FIRE RESCUE. TESTING SHALL BE BY AN
 ACCEPTABLE NATIONAL STANDARD DOCUMENTING PERCENTAGES
 NOTED ABOVE AND BY ACTUAL RADIO TESTING BY FIRE
 PERSONNEL. IF THE MINIMUM CANNOT BE MAINTAINED, A
 BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH
 A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP.
  
 PLEASE CONTACT MARK FILLA, PALM BEACH COUNTY PUBLIC
 SAFETY RADIO SYSTEMS MANAGER, [email protected],
 561-233-0837; AS OUR RADIOS OPERATE ON THEIR SYSTEM FOR
 DETAILED RADIO FREQUENCY AND INSTALLATION INSTRUCTIONS.
  
 12. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE
 SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY
 DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS.
  
 13. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
 14. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 5 Status P Date 07-18-2022 Cont ID  
Sent By rcaranci Date 07-18-2022 Time 11:50 Rev Time 0.00
Received By rcaranci Date 07-18-2022 Time 11:50 Sent To  
Notes
2022-07-18 11:51:25FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: SOUTHDALE PLAZA PUBLIX Z21040002
 JULY 18, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PER SECTION 94-441(C)(2), THE VALUE OF
 THE PERMIT WILL EXCEED 50% OF THE VALUE OF THE
 STRUCTURE, SO THE SITE MUST BE BROUGHT INTO COMPLIANCE
 WITH THE CURRENT LANDSCAPE CODE REQUIREMENTS.
 THE APPLICANT WAS GIVEN THE LANDSCAPE CODE REQUIREMENTS
 AT A PRE APPLICATION MEETING, AND THE EXISTING SITE
 CONDITIONS WERE REVIEWED. IT IS POSSIBLE TO MEET THE
 REQUIREMENTS FOR THE SITE AND STAFF IS AVAILABLE TO
 REVIEW ANY POSSIBILITIES.
  
 2. SATISFIED. REQUIRED OPEN SPACE FOR THIS ZONING
 CATEGORY TO CALCULATE REQUIRED TREES, FLOWERING TREES
 AND SHRUBS PER SECTION 94-442(C)(2)B. AND (3) IS 40% OF
 THE ENTIRE SITE. REFLECT THIS SQUARE FOOTAGE ON THE
 SITE DATA AND LANDSCAPE CALCULATIONS.
 8/16/21 TOTAL SITE AREA IS 380,133 SQ FT. 40% IS
 152,053.2 SQ FT. THESE FIGURES ARE TO BE SHOWN ON THE
 LANDSCAPE CALCULATIONS. REQUIRED TREES (102), FLOWERING
 TREES (26) AND SHRUBS (305) ARE CALCULATED ON 152,053.2
 SQ FT. CORRECT ALL ITEMS ON CHART.
  
 FIGURES NEED TO BE CORRECTED TO REFLECT THE ABOVE
 CALCULATIONS.
  
  
 3. SATISFIED. SECTION 94-443 (C)(3)A. REQUIRES A
 TERMINAL LANDSCAPE ISLAND AND REQUIRED TREE FOR EACH
 ROW OF PARKING. (3)B. REQUIRES AN INTERIOR LANDSCAPE
 ISLAND WITH A REQUIRED TREE SO THERE ARE NO MORE THAN
 10 SPACES IN A ROW. ALL THESE LANDSCAPE AREAS MUST MEET
 THE MINIMUM WIDTH OF 8 FEET OF LANDSCAPE AREA AND BE
 THE FULL LENGTH OF THE ADJACENT SPACE. (3) C. REQUIRES
 DIVIDER MEDIANS WHERE THERE ARE MORE THAN 3 CONSECUTIVE
 ROWS OF PARKING. ALL AREAS OF PARKING MUST MEET THESE
 REQUIREMENTS.
 THERE ARE ISLANDS THAT DO NOT RUN THE LENGTH OF THE
 PARKING SPACE, AND THAT ARE MINIMIZED BY HAVING
 SIDEWALKS THROUGH THEM. THE INTENT OF THE CODE IS TO
 PROVIDE SHADE FOR AS MANY PARKING SPACES AS POSSIBLE
 AND MINIMIZE THE HEAT ISLAND EFFECT CREATED BY THE
 ASPHALT. ONLY ONE PARTIAL DIVIDER MEDIAN IS PROVIDED
 THAT IS ONLY ADJACENT TO 5 PARKING SPACES.
  
 THE LENGTH OF THE ISLANDS HAS BEEN ADDRESSED PER
 DISCUSSIONS WITH THE ENGINEER. CONFIGURATION OF ADA
 WALKWAYS NEEDS TO BE ADJUSTED TO ELIMINATE UNNECESSARY
 PAVED AREAS REDUCING THE PERVIOUS LANDSCAPE AREA.
  
 4. SATISFIED. SECTION 94-443(C)(3) REQUIRES THAT A
 MINIMUM OF 75 PERCENT OF ALL TREES THAT ARE REQUIRED TO
 BE PLANTED WITHIN THE INTERIOR OF AN OFF STREET PARKING
 AREA SHALL BE CATEGORY 1 SHADE TREES. SHOW THE
 PERCENTAGE OF CATEGORY 1 TREES PROVIDED FOR THE
 REQUIRED LANDSCAPE AREAS AS REQUIRED BY SECTION
 94-443(C)(3) FOR DIVIDER ISLANDS, TERMINAL, AND
 INTERIOR ISLANDS. THE ONLY TREE SPECIES LISTED ON THE
 PLANT LIST THAT ARE CATEGORY 1 ARE THE LIVE OAK TREES.
  
 79 LANDSCAPE ISLANDS REQUIRE 60 BE CATEGORY 1 SHADE
 TREES. LIVE OAK AND GUMBO LIMBO QUALIFY. ONLY 42 ARE
 PROVIDED, SO STAFF SUGGESTS RELOCATING OR REMOVING
 EXISTING PALMS AND REPLACING WITH 18 SHADE TREES.
  
 THERE ARE NOW 82 LANDSCAPE INTERIOR AND TERMINAL
 ISLANDS SHOWN. 62 CATEGORY 1 SHADE TREES ARE REQUIRED.
 COCONUT PALMS NEED TO BE REPLACED WITH SHADE TREES.
 GREEN BUTTONWOOD IS A CATEGORY 1 SHADE TREE.
  
  
 5. SATISFIED. PROVIDE A PLAN SHOWING THE PARKING
 LANDSCAPE AREAS COUNTED TOWARD COMPLIANCE WITH SECTION
 94-443(C)(3) AND (4) AND PROVIDE CALCULATIONS. PROVIDE
 THE TOTAL REQUIRED AND PROVIDED AS ONE TOTAL FOR BOTH
 SECTIONS. A SEPARATE EXHIBIT PLAN MUST BE PROVIDED TO
 SHOW THE AREAS COUNTED FOLLOWING THE DESCRIPTION OF
 AREAS AS SHOWN IN FIGURE XIV-1.
 AN EXHIBIT WAS PROVIDED ON SHEET L1.01 BUT IS
 INCOMPLETE. THE AREA OF PARKING SPACES NEEDS TO BE
 INDICATED AND ALL OTHER AREAS OF PAVEMENT NEED TO BE
 SHADED AND SQUARE FOOTAGE PROVIDED. CALCULATIONS ARE TO
 BE DONE AND ADD THE REQUIRED LANDSCAPE AREAS TOGETHER
 AND SHOW THE SQUARE FOOTAGE OF THE AREA PROVIDED.
 REMOVE THE CALCULATIONS FOR REQUIRED TREES PER 100
 SQUARE FEET, AS THIS IS NO LONGER IN THE LANDSCAPE
 CODE.
  
 STILL NEEDS TO BE REVISED.
  
 IF OTHER VUA IS 124,093 SQ FT, DIVIDED BY 100 TIMES 4
 EQUALS 4964 SQ FT
 380 PARKING SPACES TIMES 10 SQ FT EQUALS 3800 SQ FT
 TOTAL IS 8764 REQUIRED, 22,555 PROVIDED
  
 6. SATISFIED. THE TREE DISPOSITION CHART IS TO BE
 CORRECTED TO SHOW COCONUT PALMS AS CATEGORY 3 WITH 100
 SQ FT CANOPY MITIGATION DUE.
  
 7. SATISFIED. PER SECTION 94-443(B), BUFFER LENGTHS
 REQUIRE ONE TREE PER 30 FEET OR PORTION THEREOF FOR
 EACH BUFFER LENGTH AND A CONTINUOUS HEDGE. PROVIDE THE
 REQUIRED AND PROVIDED BUFFER TREES IN A CHART WITH THE
 INDIVIDUAL BUFFER SECTIONS IDENTIFIED AND THE BUFFER
 LENGTH EQUAL TO THE SURVEY LENGTH.
 8/16/21 REPEAT COMMENT -PROVIDE THE REQUIRED AND
 PROVIDED BUFFER TREES IN A CHART WITH THE INDIVIDUAL
 BUFFER SECTIONS IDENTIFIED AND THE BUFFER LENGTH EQUAL
 TO THE SURVEY LENGTH.
  
 STILL NEEDS TO BE REVISED.
  
  
  
 8. SATISFIED. BUFFERS NEED TO BE CONVERTED TO LANDSCAPE
 AREA FOR REQUIRED TREES AND HEDGES ON THE EAST AND WEST
 SIDES OF THE PROPERTY. THE CRAPE MYRTLE TREES ALONG
 SOUTHERN BOULEVARD WERE PLANTED BY THE PROPERTY OWNER
 AND ARE PART OF THE LANDSCAPING FOR THE SITE. THE NORTH
 5 FOOT LANDSCAPE BUFFER SHOULD BE CREATED INSIDE THE
 PROPERTY LINE AND MEET THE REQUIREMENTS. THE RIGHT OF
 WAY PLANTINGS WILL BE ACCEPTED TO MEET THE REQUIREMENTS
 OF SECTION 94-452 ROADWAY BEAUTIFICATION.
  
  
 9. SATISFIED. PER SECTION 94-443 (E)1., PROVIDE THE
 FOUNDATION PLANTING CALCULATION REQUIRED AND PROVIDED
 FOR THE ENTIRE BUILDING.
  
 MEASUREMENT AND PERCENTAGE WERE ONLY PROVIDED FOR THE
 FA?ADE. PROVIDE THE REQUIRED AND PROVIDED FOR THE
 BUILDING PERIMETER.
  
  
 10. SATISFIED. PROVIDE THE NUMBER AND PERCENTAGE OF
 SUBSTITUTION OF PALMS FOR REQUIRED TREES. SECTION
 94-442(D) REQUIRES A 3:1 RATIO FOR SUBSTITUTION FOR
 PALMS EXCEPT THE LISTED 1:1 SPECIES.
 PROVIDE THE PERCENTAGE OF PALMS SUBSTITUTED FOR THE 128
 REQUIRED SHADE AND FLOWERING TREES.
  
 11. SATISFIED. RECALCULATE THE SECTION IN THE LANDSCAPE
 DATA CHART TO COMPLY WITH SECTION 94-445 L. PLANT
 SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL
 ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT
 SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF
 SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA
 WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA
 LANDSCAPES. PROVIDE THE TOTAL PERCENTAGE OF NATIVE AND
 DROUGHT TOLERANT PLANTS BASED ON FINAL PLANT LIST.
 PERCENTAGE IS BASED ON TOTAL PLANTS, NOT SPECIES.
 REVISE PERCENTAGES.
  
  
 12. SATISFIED. SHOW THE LOCATIONS OF ALL SITE LIGHTING
 ON THE LANDSCAPE PLAN AND REDESIGN THE LOCATIONS OF THE
 LIGHTING ON SHORTER POLES TO RESOLVE ANY CONFLICTS WITH
 TREES IN THE PARKING AREA LANDSCAPE ISLANDS.
 STAFF COULD LOCATE ONLY ONE LIGHT POLE ON THE PLAN.
 LOCATIONS HAVE BEEN SHOWN, BUT AFTER THE REQUIRED SHADE
 TREES ARE ADDED IN THE LANDSCAPE ISLANDS, ALL CONFLICTS
 MUST BE RESOLVED, WHICH MAY INVOLVE ADJUSTING LOCATIONS
 OF THE LIGHT POLES.
  
  
 13. SATISFIED. SHOW THE LOCATIONS OF ALL UTILITIES ON
 THE LANDSCAPE PLAN, THERE ARE MULTIPLE CONFLICTS WITH
 TREES PER THE CIVIL DRAWINGS.
  
 14. SATISFIED. PROVIDE SCREENING FOR ALL GROUND MOUNTED
 VALVES AND EQUIPMENT.
 ALL DUMPSTERS AND TRASH COMPACTORS ARE REQUIRED TO HAVE
 A HEDGE AROUND THE NON-ACCESS SIDES OF THE ENCLOSURES.
 ADD THE REQUIRED LANDSCAPING TO ALL EXISTING AND
 PROPOSED ENCLOSURES.
  
 15. SATISFIED. SHOW LOCATIONS OF FPL TRANSFORMERS ON
 THE LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH
 LANDSCAPING.
 ONLY 2 TRANSFORMER LOCATIONS ARE INDICATED. EXPLAIN IF
 THERE ARE NOT MORE.
  
 ADDITIONAL COMMENTS 8/16/21:
  
 16. SATISFIED. PROVIDE THE LANDSCAPE PLAN IN A 1:20
 SCALE FOR CLARITY.
  
  
 17. SATISFIED. SUPPLY CROSS SECTION DRAWINGS OF THE
 LANDSCAPE BUFFERS TO DEMONSTRATE HOW THE ELEVATION
 CHANGES AND ENGINEERING WILL BE PROPOSED TO ACHIEVE THE
 REQUIRED LANDSCAPE BUFFER AREA.
 CROSS SECTIONS NEED TO BE SHOWN THAT REPRESENT ALL
 DIFFERENT CONDITIONS. IF THE WIDTH OF THE LANDSCAPE
 BUFFER AREA OR SLOPE VARIES, A CROSS SECTION MUST BE
 SHOWN FOR EACH TYPICAL CONDITION.
  
 18. SATISFIED. SEA GRAPE TREES ARE PROPOSED TO BE
 REMOVED. AN ARBORIST REPORT MUST BE SUPPLIED SHOWING
 WHY THE NATIVE TREES CANNOT BE PRESERVED OR
 TRANSPLANTED PER SECTION 94-448(D)(3).
 APPLICANT HAS INDICATED THIS WILL BE SUPPLIED WITH A
 LATER SUBMITTAL.
  
 19. SATISFIED. THE BANK IS INDICATED AS NOT BEING A
 SEPARATE PARCEL SO IT MUST BE COUNTED IN THE OVERALL
 LANDSCAPE CALCULATIONS AND THE REQUIRED LANDSCAPE
 PROVIDED.
  
 20. SATISFIED. BUFFER CHART INDICATES ALL LANDSCAPE
 BUFFERS ARE 7 FEET WIDE. THIS NEEDS TO BE SHOWN ON THE
 PLAN FOR THE WIDTHS OF ALL BUFFERS, AS SOME DO NOT MEET
 THE 5 FOOT MINIMUM.
  
 DIMENSIONS MUST BE PROVIDED ON THE SITE PLAN AND
 LANDSCAPE PLAN.
  
 ADDITIONAL COMMENTS 2/3/22:
  
 21. SATISFIED. EXFILTRATION TRENCH SOUTHWEST OF THE
 BANK BUILDING CONFLICTS WITH THE LANDSCAPE AREA AND
 TREES. MOVE INTO THE PAVED AREA AWAY FROM THE LANDSCAPE
 AREA.
  
 22. SATISFIED. SHOW CALCULATIONS BY LINEAR FEET AND
 PERCENTAGE FOR THE ADA ACCESS AND DRIVEWAY OPENINGS
 THAT INTERRUPT THE LANDSCAPE BUFFER FOR EACH SIDE OF
 THE PROPERTY. PER SECTION 94-443(B)(2) CANNOT EXCEED
 25% OF THE REQUIRED LENGTH.
  
 23. SATISFIED. IDENTIFY EXISTING TREES, PALMS AND
 SHRUBS TO REMAIN AS PART OF THE PLAN APPROVED WITH THIS
 PETITION.
  
 24. SATISFIED. PROVIDE CALCULATIONS FOR THE LANDSCAPE
 AREAS AND THE PROPOSED GRAVEL AREAS TO SHOW THE MINIMUM
 15% LANDSCAPE AREA IS MET.
  
 REQUIRED 15% OF THE SITE IS 57,020 SQ FT. 40,334 IS
 PROVIDED OR 10.6% IS PROVIDED. THIS IS INCREASED FROM
 34,692 OR 9.1% PROVIDING A REDUCTION IN THE
 NONCONFORMITY.
  
 25. SATISFIED. DIMENSION THE LANDSCAPE WIDTH IN THE
 INTERIOR ISLANDS THAT HAVE CART CORRALS. THEY DO NOT
 APPEAR TO MEET THE MINIMUM 8 FEET OF WIDTH.
  
 REMAINING COMMENTS CONSOLIDATED 5/19/22:
  
 26. SATISFIED. ON SHEET L-1.00, REVISE THE TREE CANOPY
 MITIGATION DUE FOR TREES #56, #57, AND #12 TO 300 SQ FT
 EACH FOR CATEGORY 1 TREES. REVISE THE TOTAL CANOPY
 MITIGATION DUE TO 5245 SQ FT. AND SHOW TOTAL AT THE
 BOTTOM OF THE COLUMN. REVISE THE CANOPY MITIGATION
 PROVIDED TO SHOW THE CANOPY MITIGATION CREDITS FOR ALL
 NEW TREES ADDED ON THE PLANT LIST AND PROVIDE THE
 TOTAL.
  
 27. SATISFIED. IN THE FRONT OF THE BUILDING, RELOCATE
 THE MOBILITY STATION CONCRETE PAD 8 FEET TO THE WEST TO
 PROVIDE THE REQUIRED LANDSCAPE AREA ADJACENT TO THE
 PARKING SPACE.
  
 28. SATISFIED. HEDGE NEEDS TO BE EXTENDED ALONG THE
 SIDE OF THE DUMPSTER ENCLOSURE LOCATED AT THE SOUTH
 SIDE OF THE SITE. CURB MAY NEED TO BE MODIFIED TO ALLOW
 PLANTING OF THE REQUIRED HEDGE.
  
 29. SATISFIED. QUALIFYING TERMINAL ISLAND TREE IS
 MISSING FROM THE LANDSCAPE AREA WITH THE FLAGPOLE.
 SMALL TREE OR PALM NEEDS TO BE INCLUDED THAT WILL NOT
 CONFLICT WITH THE POLE.
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 4 Status F Date 05-19-2022 Cont ID  
Sent By rcaranci Date 05-19-2022 Time 16:40 Rev Time 0.00
Received By rcaranci Date 05-19-2022 Time 16:40 Sent To  
Notes
2022-05-19 16:40:55FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: SOUTHDALE PLAZA PUBLIX Z21040002
 MAY 13, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PER SECTION 94-441(C)(2), THE VALUE OF
 THE PERMIT WILL EXCEED 50% OF THE VALUE OF THE
 STRUCTURE, SO THE SITE MUST BE BROUGHT INTO COMPLIANCE
 WITH THE CURRENT LANDSCAPE CODE REQUIREMENTS.
 THE APPLICANT WAS GIVEN THE LANDSCAPE CODE REQUIREMENTS
 AT A PRE APPLICATION MEETING, AND THE EXISTING SITE
 CONDITIONS WERE REVIEWED. IT IS POSSIBLE TO MEET THE
 REQUIREMENTS FOR THE SITE AND STAFF IS AVAILABLE TO
 REVIEW ANY POSSIBILITIES.
  
 2. SATISFIED. REQUIRED OPEN SPACE FOR THIS ZONING
 CATEGORY TO CALCULATE REQUIRED TREES, FLOWERING TREES
 AND SHRUBS PER SECTION 94-442(C)(2)B. AND (3) IS 40% OF
 THE ENTIRE SITE. REFLECT THIS SQUARE FOOTAGE ON THE
 SITE DATA AND LANDSCAPE CALCULATIONS.
 8/16/21 TOTAL SITE AREA IS 380,133 SQ FT. 40% IS
 152,053.2 SQ FT. THESE FIGURES ARE TO BE SHOWN ON THE
 LANDSCAPE CALCULATIONS. REQUIRED TREES (102), FLOWERING
 TREES (26) AND SHRUBS (305) ARE CALCULATED ON 152,053.2
 SQ FT. CORRECT ALL ITEMS ON CHART.
  
 FIGURES NEED TO BE CORRECTED TO REFLECT THE ABOVE
 CALCULATIONS.
  
  
 3. SATISFIED. SECTION 94-443 (C)(3)A. REQUIRES A
 TERMINAL LANDSCAPE ISLAND AND REQUIRED TREE FOR EACH
 ROW OF PARKING. (3)B. REQUIRES AN INTERIOR LANDSCAPE
 ISLAND WITH A REQUIRED TREE SO THERE ARE NO MORE THAN
 10 SPACES IN A ROW. ALL THESE LANDSCAPE AREAS MUST MEET
 THE MINIMUM WIDTH OF 8 FEET OF LANDSCAPE AREA AND BE
 THE FULL LENGTH OF THE ADJACENT SPACE. (3) C. REQUIRES
 DIVIDER MEDIANS WHERE THERE ARE MORE THAN 3 CONSECUTIVE
 ROWS OF PARKING. ALL AREAS OF PARKING MUST MEET THESE
 REQUIREMENTS.
 THERE ARE ISLANDS THAT DO NOT RUN THE LENGTH OF THE
 PARKING SPACE, AND THAT ARE MINIMIZED BY HAVING
 SIDEWALKS THROUGH THEM. THE INTENT OF THE CODE IS TO
 PROVIDE SHADE FOR AS MANY PARKING SPACES AS POSSIBLE
 AND MINIMIZE THE HEAT ISLAND EFFECT CREATED BY THE
 ASPHALT. ONLY ONE PARTIAL DIVIDER MEDIAN IS PROVIDED
 THAT IS ONLY ADJACENT TO 5 PARKING SPACES.
  
 THE LENGTH OF THE ISLANDS HAS BEEN ADDRESSED PER
 DISCUSSIONS WITH THE ENGINEER. CONFIGURATION OF ADA
 WALKWAYS NEEDS TO BE ADJUSTED TO ELIMINATE UNNECESSARY
 PAVED AREAS REDUCING THE PERVIOUS LANDSCAPE AREA.
  
 4. SATISFIED. SECTION 94-443(C)(3) REQUIRES THAT A
 MINIMUM OF 75 PERCENT OF ALL TREES THAT ARE REQUIRED TO
 BE PLANTED WITHIN THE INTERIOR OF AN OFF STREET PARKING
 AREA SHALL BE CATEGORY 1 SHADE TREES. SHOW THE
 PERCENTAGE OF CATEGORY 1 TREES PROVIDED FOR THE
 REQUIRED LANDSCAPE AREAS AS REQUIRED BY SECTION
 94-443(C)(3) FOR DIVIDER ISLANDS, TERMINAL, AND
 INTERIOR ISLANDS. THE ONLY TREE SPECIES LISTED ON THE
 PLANT LIST THAT ARE CATEGORY 1 ARE THE LIVE OAK TREES.
  
 79 LANDSCAPE ISLANDS REQUIRE 60 BE CATEGORY 1 SHADE
 TREES. LIVE OAK AND GUMBO LIMBO QUALIFY. ONLY 42 ARE
 PROVIDED, SO STAFF SUGGESTS RELOCATING OR REMOVING
 EXISTING PALMS AND REPLACING WITH 18 SHADE TREES.
  
 THERE ARE NOW 82 LANDSCAPE INTERIOR AND TERMINAL
 ISLANDS SHOWN. 62 CATEGORY 1 SHADE TREES ARE REQUIRED.
 COCONUT PALMS NEED TO BE REPLACED WITH SHADE TREES.
 GREEN BUTTONWOOD IS A CATEGORY 1 SHADE TREE.
  
  
 5. SATISFIED. PROVIDE A PLAN SHOWING THE PARKING
 LANDSCAPE AREAS COUNTED TOWARD COMPLIANCE WITH SECTION
 94-443(C)(3) AND (4) AND PROVIDE CALCULATIONS. PROVIDE
 THE TOTAL REQUIRED AND PROVIDED AS ONE TOTAL FOR BOTH
 SECTIONS. A SEPARATE EXHIBIT PLAN MUST BE PROVIDED TO
 SHOW THE AREAS COUNTED FOLLOWING THE DESCRIPTION OF
 AREAS AS SHOWN IN FIGURE XIV-1.
 AN EXHIBIT WAS PROVIDED ON SHEET L1.01 BUT IS
 INCOMPLETE. THE AREA OF PARKING SPACES NEEDS TO BE
 INDICATED AND ALL OTHER AREAS OF PAVEMENT NEED TO BE
 SHADED AND SQUARE FOOTAGE PROVIDED. CALCULATIONS ARE TO
 BE DONE AND ADD THE REQUIRED LANDSCAPE AREAS TOGETHER
 AND SHOW THE SQUARE FOOTAGE OF THE AREA PROVIDED.
 REMOVE THE CALCULATIONS FOR REQUIRED TREES PER 100
 SQUARE FEET, AS THIS IS NO LONGER IN THE LANDSCAPE
 CODE.
  
 STILL NEEDS TO BE REVISED.
  
 IF OTHER VUA IS 124,093 SQ FT, DIVIDED BY 100 TIMES 4
 EQUALS 4964 SQ FT
 380 PARKING SPACES TIMES 10 SQ FT EQUALS 3800 SQ FT
 TOTAL IS 8764 REQUIRED, 22,555 PROVIDED
  
 6. SATISFIED. THE TREE DISPOSITION CHART IS TO BE
 CORRECTED TO SHOW COCONUT PALMS AS CATEGORY 3 WITH 100
 SQ FT CANOPY MITIGATION DUE.
  
 7. SATISFIED. PER SECTION 94-443(B), BUFFER LENGTHS
 REQUIRE ONE TREE PER 30 FEET OR PORTION THEREOF FOR
 EACH BUFFER LENGTH AND A CONTINUOUS HEDGE. PROVIDE THE
 REQUIRED AND PROVIDED BUFFER TREES IN A CHART WITH THE
 INDIVIDUAL BUFFER SECTIONS IDENTIFIED AND THE BUFFER
 LENGTH EQUAL TO THE SURVEY LENGTH.
 8/16/21 REPEAT COMMENT -PROVIDE THE REQUIRED AND
 PROVIDED BUFFER TREES IN A CHART WITH THE INDIVIDUAL
 BUFFER SECTIONS IDENTIFIED AND THE BUFFER LENGTH EQUAL
 TO THE SURVEY LENGTH.
  
 STILL NEEDS TO BE REVISED.
  
  
  
 8. SATISFIED. BUFFERS NEED TO BE CONVERTED TO LANDSCAPE
 AREA FOR REQUIRED TREES AND HEDGES ON THE EAST AND WEST
 SIDES OF THE PROPERTY. THE CRAPE MYRTLE TREES ALONG
 SOUTHERN BOULEVARD WERE PLANTED BY THE PROPERTY OWNER
 AND ARE PART OF THE LANDSCAPING FOR THE SITE. THE NORTH
 5 FOOT LANDSCAPE BUFFER SHOULD BE CREATED INSIDE THE
 PROPERTY LINE AND MEET THE REQUIREMENTS. THE RIGHT OF
 WAY PLANTINGS WILL BE ACCEPTED TO MEET THE REQUIREMENTS
 OF SECTION 94-452 ROADWAY BEAUTIFICATION.
  
  
 9. SATISFIED. PER SECTION 94-443 (E)1., PROVIDE THE
 FOUNDATION PLANTING CALCULATION REQUIRED AND PROVIDED
 FOR THE ENTIRE BUILDING.
  
 MEASUREMENT AND PERCENTAGE WERE ONLY PROVIDED FOR THE
 FA?ADE. PROVIDE THE REQUIRED AND PROVIDED FOR THE
 BUILDING PERIMETER.
  
  
 10. SATISFIED. PROVIDE THE NUMBER AND PERCENTAGE OF
 SUBSTITUTION OF PALMS FOR REQUIRED TREES. SECTION
 94-442(D) REQUIRES A 3:1 RATIO FOR SUBSTITUTION FOR
 PALMS EXCEPT THE LISTED 1:1 SPECIES.
 PROVIDE THE PERCENTAGE OF PALMS SUBSTITUTED FOR THE 128
 REQUIRED SHADE AND FLOWERING TREES.
  
 11. SATISFIED. RECALCULATE THE SECTION IN THE LANDSCAPE
 DATA CHART TO COMPLY WITH SECTION 94-445 L. PLANT
 SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL
 ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT
 SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF
 SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA
 WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA
 LANDSCAPES. PROVIDE THE TOTAL PERCENTAGE OF NATIVE AND
 DROUGHT TOLERANT PLANTS BASED ON FINAL PLANT LIST.
 PERCENTAGE IS BASED ON TOTAL PLANTS, NOT SPECIES.
 REVISE PERCENTAGES.
  
  
 12. SATISFIED. SHOW THE LOCATIONS OF ALL SITE LIGHTING
 ON THE LANDSCAPE PLAN AND REDESIGN THE LOCATIONS OF THE
 LIGHTING ON SHORTER POLES TO RESOLVE ANY CONFLICTS WITH
 TREES IN THE PARKING AREA LANDSCAPE ISLANDS.
 STAFF COULD LOCATE ONLY ONE LIGHT POLE ON THE PLAN.
 LOCATIONS HAVE BEEN SHOWN, BUT AFTER THE REQUIRED SHADE
 TREES ARE ADDED IN THE LANDSCAPE ISLANDS, ALL CONFLICTS
 MUST BE RESOLVED, WHICH MAY INVOLVE ADJUSTING LOCATIONS
 OF THE LIGHT POLES.
  
  
 13. SATISFIED. SHOW THE LOCATIONS OF ALL UTILITIES ON
 THE LANDSCAPE PLAN, THERE ARE MULTIPLE CONFLICTS WITH
 TREES PER THE CIVIL DRAWINGS.
  
 14. SATISFIED. PROVIDE SCREENING FOR ALL GROUND MOUNTED
 VALVES AND EQUIPMENT.
 ALL DUMPSTERS AND TRASH COMPACTORS ARE REQUIRED TO HAVE
 A HEDGE AROUND THE NON-ACCESS SIDES OF THE ENCLOSURES.
 ADD THE REQUIRED LANDSCAPING TO ALL EXISTING AND
 PROPOSED ENCLOSURES.
  
 15. SATISFIED. SHOW LOCATIONS OF FPL TRANSFORMERS ON
 THE LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH
 LANDSCAPING.
 ONLY 2 TRANSFORMER LOCATIONS ARE INDICATED. EXPLAIN IF
 THERE ARE NOT MORE.
  
 ADDITIONAL COMMENTS 8/16/21:
  
 16. SATISFIED. PROVIDE THE LANDSCAPE PLAN IN A 1:20
 SCALE FOR CLARITY.
  
  
 17. SATISFIED. SUPPLY CROSS SECTION DRAWINGS OF THE
 LANDSCAPE BUFFERS TO DEMONSTRATE HOW THE ELEVATION
 CHANGES AND ENGINEERING WILL BE PROPOSED TO ACHIEVE THE
 REQUIRED LANDSCAPE BUFFER AREA.
 CROSS SECTIONS NEED TO BE SHOWN THAT REPRESENT ALL
 DIFFERENT CONDITIONS. IF THE WIDTH OF THE LANDSCAPE
 BUFFER AREA OR SLOPE VARIES, A CROSS SECTION MUST BE
 SHOWN FOR EACH TYPICAL CONDITION.
  
 18. SATISFIED. SEA GRAPE TREES ARE PROPOSED TO BE
 REMOVED. AN ARBORIST REPORT MUST BE SUPPLIED SHOWING
 WHY THE NATIVE TREES CANNOT BE PRESERVED OR
 TRANSPLANTED PER SECTION 94-448(D)(3).
 APPLICANT HAS INDICATED THIS WILL BE SUPPLIED WITH A
 LATER SUBMITTAL.
  
 19. SATISFIED. THE BANK IS INDICATED AS NOT BEING A
 SEPARATE PARCEL SO IT MUST BE COUNTED IN THE OVERALL
 LANDSCAPE CALCULATIONS AND THE REQUIRED LANDSCAPE
 PROVIDED.
  
 20. SATISFIED. BUFFER CHART INDICATES ALL LANDSCAPE
 BUFFERS ARE 7 FEET WIDE. THIS NEEDS TO BE SHOWN ON THE
 PLAN FOR THE WIDTHS OF ALL BUFFERS, AS SOME DO NOT MEET
 THE 5 FOOT MINIMUM.
  
 DIMENSIONS MUST BE PROVIDED ON THE SITE PLAN AND
 LANDSCAPE PLAN.
  
 ADDITIONAL COMMENTS 2/3/22:
  
 21. SATISFIED. EXFILTRATION TRENCH SOUTHWEST OF THE
 BANK BUILDING CONFLICTS WITH THE LANDSCAPE AREA AND
 TREES. MOVE INTO THE PAVED AREA AWAY FROM THE LANDSCAPE
 AREA.
  
 22. SATISFIED. SHOW CALCULATIONS BY LINEAR FEET AND
 PERCENTAGE FOR THE ADA ACCESS AND DRIVEWAY OPENINGS
 THAT INTERRUPT THE LANDSCAPE BUFFER FOR EACH SIDE OF
 THE PROPERTY. PER SECTION 94-443(B)(2) CANNOT EXCEED
 25% OF THE REQUIRED LENGTH.
  
 23. SATISFIED. IDENTIFY EXISTING TREES, PALMS AND
 SHRUBS TO REMAIN AS PART OF THE PLAN APPROVED WITH THIS
 PETITION.
  
 24. SATISFIED. PROVIDE CALCULATIONS FOR THE LANDSCAPE
 AREAS AND THE PROPOSED GRAVEL AREAS TO SHOW THE MINIMUM
 15% LANDSCAPE AREA IS MET.
  
 REQUIRED 15% OF THE SITE IS 57,020 SQ FT. 40,334 IS
 PROVIDED OR 10.6% IS PROVIDED. THIS IS INCREASED FROM
 34,692 OR 9.1% PROVIDING A REDUCTION IN THE
 NONCONFORMITY.
  
 25. SATISFIED. DIMENSION THE LANDSCAPE WIDTH IN THE
 INTERIOR ISLANDS THAT HAVE CART CORRALS. THEY DO NOT
 APPEAR TO MEET THE MINIMUM 8 FEET OF WIDTH.
  
 REMAINING COMMENTS CONSOLIDATED 5/19/22:
  
 26. ON SHEET L-1.00, REVISE THE TREE CANOPY MITIGATION
 DUE FOR TREES #56, #57, AND #12 TO 300 SQ FT EACH FOR
 CATEGORY 1 TREES. REVISE THE TOTAL CANOPY MITIGATION
 DUE TO 5245 SQ FT. AND SHOW TOTAL AT THE BOTTOM OF THE
 COLUMN. REVISE THE CANOPY MITIGATION PROVIDED TO SHOW
 THE CANOPY MITIGATION CREDITS FOR ALL NEW TREES ADDED
 ON THE PLANT LIST AND PROVIDE THE TOTAL.
  
 27. IN THE FRONT OF THE BUILDING, RELOCATE THE MOBILITY
 STATION CONCRETE PAD 8 FEET TO THE WEST TO PROVIDE THE
 REQUIRED LANDSCAPE AREA ADJACENT TO THE PARKING SPACE.
  
 28. HEDGE NEEDS TO BE EXTENDED ALONG THE SIDE OF THE
 DUMPSTER ENCLOSURE LOCATED AT THE SOUTH SIDE OF THE
 SITE. CURB MAY NEED TO BE MODIFIED TO ALLOW PLANTING OF
 THE REQUIRED HEDGE.
  
 29. QUALIFYING TERMINAL ISLAND TREE IS MISSING FROM THE
 LANDSCAPE AREA WITH THE FLAGPOLE. SMALL TREE OR PALM
 NEEDS TO BE INCLUDED THAT WILL NOT CONFLICT WITH THE
 POLE.
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 3 Status F Date 02-04-2022 Cont ID  
Sent By rcaranci Date 02-04-2022 Time 10:00 Rev Time 0.00
Received By rcaranci Date 02-04-2022 Time 10:00 Sent To  
Notes
2022-02-04 10:00:38FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: SOUTHDALE PLAZA PUBLIX Z21040002
 FEBRUARY 3, 2022
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PARTIALLY SATISFIED. PER SECTION 94-441(C)(2), THE
 VALUE OF THE PERMIT WILL EXCEED 50% OF THE VALUE OF THE
 STRUCTURE, SO THE SITE MUST BE BROUGHT INTO COMPLIANCE
 WITH THE CURRENT LANDSCAPE CODE REQUIREMENTS.
 THE APPLICANT WAS GIVEN THE LANDSCAPE CODE REQUIREMENTS
 AT A PRE APPLICATION MEETING, AND THE EXISTING SITE
 CONDITIONS WERE REVIEWED. IT IS POSSIBLE TO MEET THE
 REQUIREMENTS FOR THE SITE AND STAFF IS AVAILABLE TO
 REVIEW ANY POSSIBILITIES.
  
 2. PARTIALLY SATISFIED. REQUIRED OPEN SPACE FOR THIS
 ZONING CATEGORY TO CALCULATE REQUIRED TREES, FLOWERING
 TREES AND SHRUBS PER SECTION 94-442(C)(2)B. AND (3) IS
 40% OF THE ENTIRE SITE. REFLECT THIS SQUARE FOOTAGE ON
 THE SITE DATA AND LANDSCAPE CALCULATIONS.
 8/16/21 TOTAL SITE AREA IS 380,133 SQ FT. 40% IS
 152,053.2 SQ FT. THESE FIGURES ARE TO BE SHOWN ON THE
 LANDSCAPE CALCULATIONS. REQUIRED TREES (102), FLOWERING
 TREES (26) AND SHRUBS (305) ARE CALCULATED ON 152,053.2
 SQ FT. CORRECT ALL ITEMS ON CHART.
  
 FIGURES NEED TO BE CORRECTED TO REFLECT THE ABOVE
 CALCULATIONS.
  
  
 3. PARTIALLY SATISFIED. SECTION 94-443 (C)(3)A.
 REQUIRES A TERMINAL LANDSCAPE ISLAND AND REQUIRED TREE
 FOR EACH ROW OF PARKING. (3)B. REQUIRES AN INTERIOR
 LANDSCAPE ISLAND WITH A REQUIRED TREE SO THERE ARE NO
 MORE THAN 10 SPACES IN A ROW. ALL THESE LANDSCAPE AREAS
 MUST MEET THE MINIMUM WIDTH OF 8 FEET OF LANDSCAPE AREA
 AND BE THE FULL LENGTH OF THE ADJACENT SPACE. (3) C.
 REQUIRES DIVIDER MEDIANS WHERE THERE ARE MORE THAN 3
 CONSECUTIVE ROWS OF PARKING. ALL AREAS OF PARKING MUST
 MEET THESE REQUIREMENTS.
 THERE ARE ISLANDS THAT DO NOT RUN THE LENGTH OF THE
 PARKING SPACE, AND THAT ARE MINIMIZED BY HAVING
 SIDEWALKS THROUGH THEM. THE INTENT OF THE CODE IS TO
 PROVIDE SHADE FOR AS MANY PARKING SPACES AS POSSIBLE
 AND MINIMIZE THE HEAT ISLAND EFFECT CREATED BY THE
 ASPHALT. ONLY ONE PARTIAL DIVIDER MEDIAN IS PROVIDED
 THAT IS ONLY ADJACENT TO 5 PARKING SPACES.
  
 THE LENGTH OF THE ISLANDS HAS BEEN ADDRESSED PER
 DISCUSSIONS WITH THE ENGINEER. CONFIGURATION OF ADA
 WALKWAYS NEEDS TO BE ADJUSTED TO ELIMINATE UNNECESSARY
 PAVED AREAS REDUCING THE PERVIOUS LANDSCAPE AREA.
  
 4. PARTIALLY SATISFIED. SECTION 94-443(C)(3) REQUIRES
 THAT A MINIMUM OF 75 PERCENT OF ALL TREES THAT ARE
 REQUIRED TO BE PLANTED WITHIN THE INTERIOR OF AN OFF
 STREET PARKING AREA SHALL BE CATEGORY 1 SHADE TREES.
 SHOW THE PERCENTAGE OF CATEGORY 1 TREES PROVIDED FOR
 THE REQUIRED LANDSCAPE AREAS AS REQUIRED BY SECTION
 94-443(C)(3) FOR DIVIDER ISLANDS, TERMINAL, AND
 INTERIOR ISLANDS. THE ONLY TREE SPECIES LISTED ON THE
 PLANT LIST THAT ARE CATEGORY 1 ARE THE LIVE OAK TREES.
  
 79 LANDSCAPE ISLANDS REQUIRE 60 BE CATEGORY 1 SHADE
 TREES. LIVE OAK AND GUMBO LIMBO QUALIFY. ONLY 42 ARE
 PROVIDED, SO STAFF SUGGESTS RELOCATING OR REMOVING
 EXISTING PALMS AND REPLACING WITH 18 SHADE TREES.
  
 THERE ARE NOW 82 LANDSCAPE INTERIOR AND TERMINAL
 ISLANDS SHOWN. 62 CATEGORY 1 SHADE TREES ARE REQUIRED.
 COCONUT PALMS NEED TO BE REPLACED WITH SHADE TREES.
 GREEN BUTTONWOOD IS A CATEGORY 1 SHADE TREE.
  
  
 5. PARTIALLY SATISFIED. PROVIDE A PLAN SHOWING THE
 PARKING LANDSCAPE AREAS COUNTED TOWARD COMPLIANCE WITH
 SECTION 94-443(C)(3) AND (4) AND PROVIDE CALCULATIONS.
 PROVIDE THE TOTAL REQUIRED AND PROVIDED AS ONE TOTAL
 FOR BOTH SECTIONS. A SEPARATE EXHIBIT PLAN MUST BE
 PROVIDED TO SHOW THE AREAS COUNTED FOLLOWING THE
 DESCRIPTION OF AREAS AS SHOWN IN FIGURE XIV-1.
 AN EXHIBIT WAS PROVIDED ON SHEET L1.01 BUT IS
 INCOMPLETE. THE AREA OF PARKING SPACES NEEDS TO BE
 INDICATED AND ALL OTHER AREAS OF PAVEMENT NEED TO BE
 SHADED AND SQUARE FOOTAGE PROVIDED. CALCULATIONS ARE TO
 BE DONE AND ADD THE REQUIRED LANDSCAPE AREAS TOGETHER
 AND SHOW THE SQUARE FOOTAGE OF THE AREA PROVIDED.
 REMOVE THE CALCULATIONS FOR REQUIRED TREES PER 100
 SQUARE FEET, AS THIS IS NO LONGER IN THE LANDSCAPE
 CODE.
  
 STILL NEEDS TO BE REVISED.
  
 6. SATISFIED. THE TREE DISPOSITION CHART IS TO BE
 CORRECTED TO SHOW COCONUT PALMS AS CATEGORY 3 WITH 100
 SQ FT CANOPY MITIGATION DUE.
  
 7. NOT SATISFIED. PER SECTION 94-443(B), BUFFER LENGTHS
 REQUIRE ONE TREE PER 30 FEET OR PORTION THEREOF FOR
 EACH BUFFER LENGTH AND A CONTINUOUS HEDGE. PROVIDE THE
 REQUIRED AND PROVIDED BUFFER TREES IN A CHART WITH THE
 INDIVIDUAL BUFFER SECTIONS IDENTIFIED AND THE BUFFER
 LENGTH EQUAL TO THE SURVEY LENGTH.
 8/16/21 REPEAT COMMENT -PROVIDE THE REQUIRED AND
 PROVIDED BUFFER TREES IN A CHART WITH THE INDIVIDUAL
 BUFFER SECTIONS IDENTIFIED AND THE BUFFER LENGTH EQUAL
 TO THE SURVEY LENGTH.
  
 STILL NEEDS TO BE REVISED.
  
  
  
 8. SATISFIED. BUFFERS NEED TO BE CONVERTED TO LANDSCAPE
 AREA FOR REQUIRED TREES AND HEDGES ON THE EAST AND WEST
 SIDES OF THE PROPERTY. THE CRAPE MYRTLE TREES ALONG
 SOUTHERN BOULEVARD WERE PLANTED BY THE PROPERTY OWNER
 AND ARE PART OF THE LANDSCAPING FOR THE SITE. THE NORTH
 5 FOOT LANDSCAPE BUFFER SHOULD BE CREATED INSIDE THE
 PROPERTY LINE AND MEET THE REQUIREMENTS. THE RIGHT OF
 WAY PLANTINGS WILL BE ACCEPTED TO MEET THE REQUIREMENTS
 OF SECTION 94-452 ROADWAY BEAUTIFICATION.
  
  
 9. NOT SATISFIED. PER SECTION 94-443 (E)1., PROVIDE THE
 FOUNDATION PLANTING CALCULATION REQUIRED AND PROVIDED
 FOR THE ENTIRE BUILDING.
  
 MEASUREMENT AND PERCENTAGE WERE ONLY PROVIDED FOR THE
 FA?ADE. PROVIDE THE REQUIRED AND PROVIDED FOR THE
 BUILDING PERIMETER.
  
  
 10. PARTIALLY SATISFIED. PROVIDE THE NUMBER AND
 PERCENTAGE OF SUBSTITUTION OF PALMS FOR REQUIRED TREES.
 SECTION 94-442(D) REQUIRES A 3:1 RATIO FOR SUBSTITUTION
 FOR PALMS EXCEPT THE LISTED 1:1 SPECIES.
 PROVIDE THE PERCENTAGE OF PALMS SUBSTITUTED FOR THE 128
 REQUIRED SHADE AND FLOWERING TREES.
  
 11. SATISFIED. RECALCULATE THE SECTION IN THE LANDSCAPE
 DATA CHART TO COMPLY WITH SECTION 94-445 L. PLANT
 SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL
 ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT
 SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF
 SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA
 WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA
 LANDSCAPES. PROVIDE THE TOTAL PERCENTAGE OF NATIVE AND
 DROUGHT TOLERANT PLANTS BASED ON FINAL PLANT LIST.
 PERCENTAGE IS BASED ON TOTAL PLANTS, NOT SPECIES.
 REVISE PERCENTAGES.
  
  
 12. PARTIALLY SATISFIED. SHOW THE LOCATIONS OF ALL SITE
 LIGHTING ON THE LANDSCAPE PLAN AND REDESIGN THE
 LOCATIONS OF THE LIGHTING ON SHORTER POLES TO RESOLVE
 ANY CONFLICTS WITH TREES IN THE PARKING AREA LANDSCAPE
 ISLANDS.
 STAFF COULD LOCATE ONLY ONE LIGHT POLE ON THE PLAN.
 LOCATIONS HAVE BEEN SHOWN, BUT AFTER THE REQUIRED SHADE
 TREES ARE ADDED IN THE LANDSCAPE ISLANDS, ALL CONFLICTS
 MUST BE RESOLVED, WHICH MAY INVOLVE ADJUSTING LOCATIONS
 OF THE LIGHT POLES.
  
  
 13. SATISFIED. SHOW THE LOCATIONS OF ALL UTILITIES ON
 THE LANDSCAPE PLAN, THERE ARE MULTIPLE CONFLICTS WITH
 TREES PER THE CIVIL DRAWINGS.
  
 14. SATISFIED. PROVIDE SCREENING FOR ALL GROUND MOUNTED
 VALVES AND EQUIPMENT.
 ALL DUMPSTERS AND TRASH COMPACTORS ARE REQUIRED TO HAVE
 A HEDGE AROUND THE NON-ACCESS SIDES OF THE ENCLOSURES.
 ADD THE REQUIRED LANDSCAPING TO ALL EXISTING AND
 PROPOSED ENCLOSURES.
  
 15. SATISFIED. SHOW LOCATIONS OF FPL TRANSFORMERS ON
 THE LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH
 LANDSCAPING.
 ONLY 2 TRANSFORMER LOCATIONS ARE INDICATED. EXPLAIN IF
 THERE ARE NOT MORE.
  
 ADDITIONAL COMMENTS 8/16/21:
  
 16. NOT SATISFIED. PROVIDE THE LANDSCAPE PLAN IN A 1:20
 SCALE FOR CLARITY.
  
  
 17. PARTIALLY SATISFIED. SUPPLY CROSS SECTION DRAWINGS
 OF THE LANDSCAPE BUFFERS TO DEMONSTRATE HOW THE
 ELEVATION CHANGES AND ENGINEERING WILL BE PROPOSED TO
 ACHIEVE THE REQUIRED LANDSCAPE BUFFER AREA.
 CROSS SECTIONS NEED TO BE SHOWN THAT REPRESENT ALL
 DIFFERENT CONDITIONS. IF THE WIDTH OF THE LANDSCAPE
 BUFFER AREA OR SLOPE VARIES, A CROSS SECTION MUST BE
 SHOWN FOR EACH TYPICAL CONDITION.
  
 18. NOT SATISFIED. SEA GRAPE TREES ARE PROPOSED TO BE
 REMOVED. AN ARBORIST REPORT MUST BE SUPPLIED SHOWING
 WHY THE NATIVE TREES CANNOT BE PRESERVED OR
 TRANSPLANTED PER SECTION 94-448(D)(3).
 APPLICANT HAS INDICATED THIS WILL BE SUPPLIED WITH A
 LATER SUBMITTAL.
  
 19. SATISFIED. THE BANK IS INDICATED AS NOT BEING A
 SEPARATE PARCEL SO IT MUST BE COUNTED IN THE OVERALL
 LANDSCAPE CALCULATIONS AND THE REQUIRED LANDSCAPE
 PROVIDED.
  
 20. NOT SATISFIED. BUFFER CHART INDICATES ALL LANDSCAPE
 BUFFERS ARE 7 FEET WIDE. THIS NEEDS TO BE SHOWN ON THE
 PLAN FOR THE WIDTHS OF ALL BUFFERS, AS SOME DO NOT MEET
 THE 5 FOOT MINIMUM.
  
 DIMENSIONS MUST BE PROVIDED ON THE SITE PLAN AND
 LANDSCAPE PLAN.
  
 ADDITIONAL COMMENTS 2/3/22:
  
  
 21. EXFILTRATION TRENCH SOUTHWEST OF THE BANK BUILDING
 CONFLICTS WITH THE LANDSCAPE AREA AND TREES. MOVE INTO
 THE PAVED AREA AWAY FROM THE LANDSCAPE AREA.
  
 22. SHOW CALCULATIONS BY LINEAR FEET AND PERCENTAGE FOR
 THE ADA ACCESS AND DRIVEWAY OPENINGS THAT INTERRUPT THE
 LANDSCAPE BUFFER FOR EACH SIDE OF THE PROPERTY. PER
 SECTION 94-443(B)(2) CANNOT EXCEED 25% OF THE REQUIRED
 LENGTH.
  
 23. IDENTIFY EXISTING TREES, PALMS AND SHRUBS TO REMAIN
 AS PART OF THE PLAN APPROVED WITH THIS PETITION.
  
 24. PROVIDE CALCULATIONS FOR THE LANDSCAPE AREAS AND
 THE PROPOSED GRAVEL AREAS TO SHOW THE MINIMUM 15%
 LANDSCAPE AREA IS MET.
  
 25. DIMENSION THE LANDSCAPE WIDTH IN THE INTERIOR
 ISLANDS THAT HAVE CART CORRALS. THEY DO NOT APPEAR TO
 MEET THE MINIMUM 8 FEET OF WIDTH.
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 08-16-2021 Cont ID  
Sent By rcaranci Date 08-16-2021 Time 16:45 Rev Time 0.00
Received By rcaranci Date 08-16-2021 Time 16:45 Sent To  
Notes
2021-08-16 16:46:20FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: SOUTHDALE PLAZA PUBLIX Z21040002
 AUGUST 16, 2021
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PARTIALLY SATISFIED. PER SECTION 94-441(C)(2), THE
 VALUE OF THE PERMIT WILL EXCEED 50% OF THE VALUE OF THE
 STRUCTURE, SO THE SITE MUST BE BROUGHT INTO COMPLIANCE
 WITH THE CURRENT LANDSCAPE CODE REQUIREMENTS.
 THE APPLICANT WAS GIVEN THE LANDSCAPE CODE REQUIREMENTS
 AT A PRE APPLICATION MEETING, AND THE EXISTING SITE
 CONDITIONS WERE REVIEWED. IT IS POSSIBLE TO MEET THE
 REQUIREMENTS FOR THE SITE AND STAFF IS AVAILABLE TO
 REVIEW ANY POSSIBILITIES.
  
 2. NOT SATISFIED. REQUIRED OPEN SPACE FOR THIS ZONING
 CATEGORY TO CALCULATE REQUIRED TREES, FLOWERING TREES
 AND SHRUBS PER SECTION 94-442(C)(2)B. AND (3) IS 40% OF
 THE ENTIRE SITE. REFLECT THIS SQUARE FOOTAGE ON THE
 SITE DATA AND LANDSCAPE CALCULATIONS.
 8/16/21 TOTAL SITE AREA IS 380,133 SQ FT. 40% IS
 152,053.2 SQ FT. THESE FIGURES ARE TO BE SHOWN ON THE
 LANDSCAPE CALCULATIONS. REQUIRED TREES (102), FLOWERING
 TREES (26) AND SHRUBS (305) ARE CALCULATED ON 152,053.2
 SQ FT. CORRECT ALL ITEMS ON CHART.
  
 3. PARTIALLY SATISFIED. SECTION 94-443 (C)(3)A.
 REQUIRES A TERMINAL LANDSCAPE ISLAND AND REQUIRED TREE
 FOR EACH ROW OF PARKING. (3)B. REQUIRES AN INTERIOR
 LANDSCAPE ISLAND WITH A REQUIRED TREE SO THERE ARE NO
 MORE THAN 10 SPACES IN A ROW. ALL THESE LANDSCAPE AREAS
 MUST MEET THE MINIMUM WIDTH OF 8 FEET OF LANDSCAPE AREA
 AND BE THE FULL LENGTH OF THE ADJACENT SPACE. (3) C.
 REQUIRES DIVIDER MEDIANS WHERE THERE ARE MORE THAN 3
 CONSECUTIVE ROWS OF PARKING. ALL AREAS OF PARKING MUST
 MEET THESE REQUIREMENTS.
 THERE ARE ISLANDS THAT DO NOT RUN THE LENGTH OF THE
 PARKING SPACE, AND THAT ARE MINIMIZED BY HAVING
 SIDEWALKS THROUGH THEM. THE INTENT OF THE CODE IS TO
 PROVIDE SHADE FOR AS MANY PARKING SPACES AS POSSIBLE
 AND MINIMIZE THE HEAT ISLAND EFFECT CREATED BY THE
 ASPHALT. ONLY ONE PARTIAL DIVIDER MEDIAN IS PROVIDED
 THAT IS ONLY ADJACENT TO 5 PARKING SPACES.
  
 4. PARTIALLY SATISFIED. SECTION 94-443(C)(3) REQUIRES
 THAT A MINIMUM OF 75 PERCENT OF ALL TREES THAT ARE
 REQUIRED TO BE PLANTED WITHIN THE INTERIOR OF AN OFF
 STREET PARKING AREA SHALL BE CATEGORY 1 SHADE TREES.
 SHOW THE PERCENTAGE OF CATEGORY 1 TREES PROVIDED FOR
 THE REQUIRED LANDSCAPE AREAS AS REQUIRED BY SECTION
 94-443(C)(3) FOR DIVIDER ISLANDS, TERMINAL, AND
 INTERIOR ISLANDS. THE ONLY TREE SPECIES LISTED ON THE
 PLANT LIST THAT ARE CATEGORY 1 ARE THE LIVE OAK TREES.
  
 79 LANDSCAPE ISLANDS REQUIRE 60 BE CATEGORY 1 SHADE
 TREES. LIVE OAK AND GUMBO LIMBO QUALIFY. ONLY 42 ARE
 PROVIDED, SO STAFF SUGGESTS RELOCATING OR REMOVING
 EXISTING PALMS AND REPLACING WITH 18 SHADE TREES.
  
  
 5. PARTIALLY SATISFIED. PROVIDE A PLAN SHOWING THE
 PARKING LANDSCAPE AREAS COUNTED TOWARD COMPLIANCE WITH
 SECTION 94-443(C)(3) AND (4) AND PROVIDE CALCULATIONS.
 PROVIDE THE TOTAL REQUIRED AND PROVIDED AS ONE TOTAL
 FOR BOTH SECTIONS. A SEPARATE EXHIBIT PLAN MUST BE
 PROVIDED TO SHOW THE AREAS COUNTED FOLLOWING THE
 DESCRIPTION OF AREAS AS SHOWN IN FIGURE XIV-1.
 AN EXHIBIT WAS PROVIDED ON SHEET L1.01 BUT IS
 INCOMPLETE. THE AREA OF PARKING SPACES NEEDS TO BE
 INDICATED AND ALL OTHER AREAS OF PAVEMENT NEED TO BE
 SHADED AND SQUARE FOOTAGE PROVIDED. CALCULATIONS ARE TO
 BE DONE AND ADD THE REQUIRED LANDSCAPE AREAS TOGETHER
 AND SHOW THE SQUARE FOOTAGE OF THE AREA PROVIDED.
 REMOVE THE CALCULATIONS FOR REQUIRED TREES PER 100
 SQUARE FEET, AS THIS IS NO LONGER IN THE LANDSCAPE
 CODE.
  
 6. SATISFIED. THE TREE DISPOSITION CHART IS TO BE
 CORRECTED TO SHOW COCONUT PALMS AS CATEGORY 3 WITH 100
 SQ FT CANOPY MITIGATION DUE.
  
 7. NOT SATISFIED. PER SECTION 94-443(B), BUFFER LENGTHS
 REQUIRE ONE TREE PER 30 FEET OR PORTION THEREOF FOR
 EACH BUFFER LENGTH AND A CONTINUOUS HEDGE. PROVIDE THE
 REQUIRED AND PROVIDED BUFFER TREES IN A CHART WITH THE
 INDIVIDUAL BUFFER SECTIONS IDENTIFIED AND THE BUFFER
 LENGTH EQUAL TO THE SURVEY LENGTH.
 8/16/21 REPEAT COMMENT -PROVIDE THE REQUIRED AND
 PROVIDED BUFFER TREES IN A CHART WITH THE INDIVIDUAL
 BUFFER SECTIONS IDENTIFIED AND THE BUFFER LENGTH EQUAL
 TO THE SURVEY LENGTH.
  
  
 8. SATISFIED. BUFFERS NEED TO BE CONVERTED TO LANDSCAPE
 AREA FOR REQUIRED TREES AND HEDGES ON THE EAST AND WEST
 SIDES OF THE PROPERTY. THE CRAPE MYRTLE TREES ALONG
 SOUTHERN BOULEVARD WERE PLANTED BY THE PROPERTY OWNER
 AND ARE PART OF THE LANDSCAPING FOR THE SITE. THE NORTH
 5 FOOT LANDSCAPE BUFFER SHOULD BE CREATED INSIDE THE
 PROPERTY LINE AND MEET THE REQUIREMENTS. THE RIGHT OF
 WAY PLANTINGS WILL BE ACCEPTED TO MEET THE REQUIREMENTS
 OF SECTION 94-452 ROADWAY BEAUTIFICATION.
  
  
 9. PARTIALLY SATISFIED. PER SECTION 94-443 (E)1.,
 PROVIDE THE FOUNDATION PLANTING CALCULATION REQUIRED
 AND PROVIDED FOR THE ENTIRE BUILDING.
  
 MEASUREMENT AND PERCENTAGE WERE ONLY PROVIDED FOR THE
 FA?ADE. PROVIDE THE REQUIRED AND PROVIDED FOR THE
 BUILDING PERIMETER.
  
  
 10. PARTIALLY SATISFIED. PROVIDE THE NUMBER AND
 PERCENTAGE OF SUBSTITUTION OF PALMS FOR REQUIRED TREES.
 SECTION 94-442(D) REQUIRES A 3:1 RATIO FOR SUBSTITUTION
 FOR PALMS EXCEPT THE LISTED 1:1 SPECIES.
 PROVIDE THE PERCENTAGE OF PALMS SUBSTITUTED FOR THE 128
 REQUIRED SHADE AND FLOWERING TREES.
  
 11. PARTIALLY SATISFIED. RECALCULATE THE SECTION IN THE
 LANDSCAPE DATA CHART TO COMPLY WITH SECTION 94-445 L.
 PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES. PROVIDE THE TOTAL PERCENTAGE OF
 NATIVE AND DROUGHT TOLERANT PLANTS BASED ON FINAL PLANT
 LIST.
 PERCENTAGE IS BASED ON TOTAL PLANTS, NOT SPECIES.
 REVISE PERCENTAGES.
  
  
 12. PARTIALLY SATISFIED. SHOW THE LOCATIONS OF ALL SITE
 LIGHTING ON THE LANDSCAPE PLAN AND REDESIGN THE
 LOCATIONS OF THE LIGHTING ON SHORTER POLES TO RESOLVE
 ANY CONFLICTS WITH TREES IN THE PARKING AREA LANDSCAPE
 ISLANDS.
 STAFF COULD LOCATE ONLY ONE LIGHT POLE ON THE PLAN.
  
 13. SATISFIED. SHOW THE LOCATIONS OF ALL UTILITIES ON
 THE LANDSCAPE PLAN, THERE ARE MULTIPLE CONFLICTS WITH
 TREES PER THE CIVIL DRAWINGS.
  
 14. PARTIALLY SATISFIED. PROVIDE SCREENING FOR ALL
 GROUND MOUNTED VALVES AND EQUIPMENT.
 ALL DUMPSTERS AND TRASH COMPACTORS ARE REQUIRED TO HAVE
 A HEDGE AROUND THE NON-ACCESS SIDES OF THE ENCLOSURES.
 ADD THE REQUIRED LANDSCAPING TO ALL EXISTING AND
 PROPOSED ENCLOSURES.
  
 15. PARTIALLY SATISFIED. SHOW LOCATIONS OF FPL
 TRANSFORMERS ON THE LANDSCAPE PLAN AND RESOLVE
 CONFLICTS WITH LANDSCAPING.
 ONLY 2 TRANSFORMER LOCATIONS ARE INDICATED. EXPLAIN IF
 THERE ARE NOT MORE.
  
 ADDITIONAL COMMENTS 8/16/21:
  
 16. PROVIDE THE LANDSCAPE PLAN IN A 1:20 SCALE FOR
 CLARITY.
  
  
 17. SUPPLY CROSS SECTION DRAWINGS OF THE LANDSCAPE
 BUFFERS TO DEMONSTRATE HOW THE ELEVATION CHANGES AND
 ENGINEERING WILL BE PROPOSED TO ACHIEVE THE REQUIRED
 LANDSCAPE BUFFER AREA.
  
 18. SEA GRAPE TREES ARE PROPOSED TO BE REMOVED. AN
 ARBORIST REPORT MUST BE SUPPLIED SHOWING WHY THE NATIVE
 TREES CANNOT BE PRESERVED OR TRANSPLANTED PER SECTION
 94-448(D)(3).
  
 19. THE BANK IS INDICATED AS NOT BEING A SEPARATE
 PARCEL SO IT MUST BE COUNTED IN THE OVERALL LANDSCAPE
 CALCULATIONS AND THE REQUIRED LANDSCAPE PROVIDED.
  
 20. BUFFER CHART INDICATES ALL LANDSCAPE BUFFERS ARE 7
 FEET WIDE. THIS NEEDS TO BE SHOWN ON THE PLAN FOR THE
 WIDTHS OF ALL BUFFERS, AS SOME DO NOT MEET THE 5 FOOT
 MINIMUM.
 21.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 05-07-2021 Cont ID  
Sent By rcaranci Date 05-07-2021 Time 16:18 Rev Time 0.00
Received By rcaranci Date 05-07-2021 Time 16:18 Sent To  
Notes
2021-05-07 16:18:58FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: SOUTHDALE PLAZA PUBLIX Z21040002
 MAY 7, 2021
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PER SECTION 94-441(C)(2), THE VALUE OF THE PERMIT
 WILL EXCEED 50% OF THE VALUE OF THE STRUCTURE, SO THE
 SITE MUST BE BROUGHT INTO COMPLIANCE WITH THE CURRENT
 LANDSCAPE CODE REQUIREMENTS.
  
 2. REQUIRED OPEN SPACE FOR THIS ZONING CATEGORY TO
 CALCULATE REQUIRED TREES, FLOWERING TREES AND SHRUBS
 PER SECTION 94-442(C)(2)B. AND (3) IS 40% OF THE ENTIRE
 SITE. REFLECT THIS SQUARE FOOTAGE ON THE SITE DATA AND
 LANDSCAPE CALCULATIONS.
  
 3. SECTION 94-443 (C)(3)A. REQUIRES A TERMINAL
 LANDSCAPE ISLAND AND REQUIRED TREE FOR EACH ROW OF
 PARKING. (3)B. REQUIRES AN INTERIOR LANDSCAPE ISLAND
 WITH A REQUIRED TREE SO THERE ARE NO MORE THAN 10
 SPACES IN A ROW. ALL THESE LANDSCAPE AREAS MUST MEET
 THE MINIMUM WIDTH OF 8 FEET OF LANDSCAPE AREA AND BE
 THE FULL LENGTH OF THE ADJACENT SPACE. (3) C. REQUIRES
 DIVIDER MEDIANS WHERE THERE ARE MORE THAN 3 CONSECUTIVE
 ROWS OF PARKING. ALL AREAS OF PARKING MUST MEET THESE
 REQUIREMENTS.
  
 4. SECTION 94-443(C)(3) REQUIRES THAT A MINIMUM OF 75
 PERCENT OF ALL TREES THAT ARE REQUIRED TO BE PLANTED
 WITHIN THE INTERIOR OF AN OFF STREET PARKING AREA SHALL
 BE CATEGORY 1 SHADE TREES. SHOW THE PERCENTAGE OF
 CATEGORY 1 TREES PROVIDED FOR THE REQUIRED LANDSCAPE
 AREAS AS REQUIRED BY SECTION 94-443(C)(3) FOR DIVIDER
 ISLANDS, TERMINAL, AND INTERIOR ISLANDS. THE ONLY TREE
 SPECIES LISTED ON THE PLANT LIST THAT ARE CATEGORY 1
 ARE THE LIVE OAK TREES.
  
 5. PROVIDE A PLAN SHOWING THE PARKING LANDSCAPE AREAS
 COUNTED TOWARD COMPLIANCE WITH SECTION 94-443(C)(3) AND
 (4) AND PROVIDE CALCULATIONS. PROVIDE THE TOTAL
 REQUIRED AND PROVIDED AS ONE TOTAL FOR BOTH SECTIONS. A
 SEPARATE EXHIBIT PLAN MUST BE PROVIDED TO SHOW THE
 AREAS COUNTED FOLLOWING THE DESCRIPTION OF AREAS AS
 SHOWN IN FIGURE XIV-1.
  
 6. THE TREE DISPOSITION CHART IS TO BE CORRECTED TO
 SHOW COCONUT PALMS AS CATEGORY 3 WITH 100 SQ FT CANOPY
 MITIGATION DUE.
  
 7. PER SECTION 94-443(B), BUFFER LENGTHS REQUIRE ONE
 TREE PER 30 FEET OR PORTION THEREOF FOR EACH BUFFER
 LENGTH AND A CONTINUOUS HEDGE. PROVIDE THE REQUIRED AND
 PROVIDED BUFFER TREES IN A CHART WITH THE INDIVIDUAL
 BUFFER SECTIONS IDENTIFIED AND THE BUFFER LENGTH EQUAL
 TO THE SURVEY LENGTH.
  
 8. BUFFERS NEED TO BE CONVERTED TO LANDSCAPE AREA FOR
 REQUIRED TREES AND HEDGES ON THE EAST AND WEST SIDES OF
 THE PROPERTY. THE CRAPE MYRTLE TREES ALONG SOUTHERN
 BOULEVARD WERE PLANTED BY THE PROPERTY OWNER AND ARE
 PART OF THE LANDSCAPING FOR THE SITE. THE NORTH 5 FOOT
 LANDSCAPE BUFFER SHOULD BE CREATED INSIDE THE PROPERTY
 LINE AND MEET THE REQUIREMENTS. THE RIGHT OF WAY
 PLANTINGS WILL BE ACCEPTED TO MEET THE REQUIREMENTS OF
 SECTION 94-452 ROADWAY BEAUTIFICATION.
  
 9. PER SECTION 94-443 (E)1., PROVIDE THE FOUNDATION
 PLANTING CALCULATION REQUIRED AND PROVIDED FOR THE
 ENTIRE BUILDING.
  
  
 10. PROVIDE THE NUMBER AND PERCENTAGE OF SUBSTITUTION
 OF PALMS FOR REQUIRED TREES. SECTION 94-442(D) REQUIRES
 A 3:1 RATIO FOR SUBSTITUTION FOR PALMS EXCEPT THE
 LISTED 1:1 SPECIES.
  
 11. RECALCULATE THE SECTION IN THE LANDSCAPE DATA CHART
 TO COMPLY WITH SECTION 94-445 L. PLANT SPECIES. A
 MINIMUM OF 60 PERCENT OF PLANT MATERIAL ADDED SHALL BE
 FLORIDA NATIVE OR DROUGHT TOLERANT SPECIES SELECTED
 FROM THE CITY LIST OR THE LIST OF SPECIES IN THE MOST
 RECENT EDITION OF SOUTH FLORIDA WATER MANAGEMENT
 DISTRICT WATERWISE SOUTH FLORIDA LANDSCAPES. PROVIDE
 THE TOTAL PERCENTAGE OF NATIVE AND DROUGHT TOLERANT
 PLANTS BASED ON FINAL PLANT LIST.
  
  
 12. SHOW THE LOCATIONS OF ALL SITE LIGHTING ON THE
 LANDSCAPE PLAN AND REDESIGN THE LOCATIONS OF THE
 LIGHTING ON SHORTER POLES TO RESOLVE ANY CONFLICTS WITH
 TREES IN THE PARKING AREA LANDSCAPE ISLANDS.
  
 13. SHOW THE LOCATIONS OF ALL UTILITIES ON THE
 LANDSCAPE PLAN, THERE ARE MULTIPLE CONFLICTS WITH TREES
 PER THE CIVIL DRAWINGS.
  
 14. PROVIDE SCREENING FOR ALL GROUND MOUNTED VALVES AND
 EQUIPMENT.
  
 15. SHOW LOCATIONS OF FPL TRANSFORMERS ON THE LANDSCAPE
 PLAN AND RESOLVE CONFLICTS WITH LANDSCAPING.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  
  

Review Stop PW PUBLIC WORKS
Rev No 3 Status P Date 02-08-2022 Cont ID  
Sent By   Date 02-08-2022 Time   Rev Time 0.00
Received By   Date 02-08-2022 Time   Sent To  
Notes
2022-02-08 08:40:15NO FURTHER COMMENTS.
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
  

Review Stop PW PUBLIC WORKS
Rev No 2 Status F Date 07-29-2021 Cont ID  
Sent By   Date 07-29-2021 Time   Rev Time 0.00
Received By   Date 07-29-2021 Time   Sent To  
Notes
2021-07-29 08:13:56PLEASE PROVIDE THE FOLLOWINGS:
 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID
 WASTE VOLUME PRODUCED ALONG WITH THE SIZE AND TYPE OF
 THE CONTAINER (I.E. DUMPSTER/COMPACTOR) THAT WILL BE
 UTILIZED THAT WILL BE UTILIZED FOR THE SANITATION
 SERVICE.
 2- REVISED DUMPSTER ENCLOSURE DETAIL, SHEET C-912 TO
 REFLECT THE LATEST REVISION (RELEASED OCTOBER 2020) OF
 THE CITY ENCLOSURE. FOR A FREESTANDING SITE DUMPSTER
 ENCLOSURE, THE ENCLOSURE SHALL COMPLY WITH THE LATEST
 REVISION OF CITY OF WEST PALM BEACH GENERAL
 CONSTRUCTION-GARBAGE ENCLOSURE STANDARD, GC-7.
  
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045
  

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 05-07-2021 Cont ID  
Sent By   Date 05-07-2021 Time   Rev Time  
Received By   Date 05-07-2021 Time   Sent To  
Notes
2021-05-07 15:11:22 
 PLEASE PROVIDE THE FOLLOWINGS:
 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID
 WASTE VOLUME PRODUCED ALONG WITH THE SIZE AND TYPE OF
 THE CONTAINER (I.E. DUMPSTER/COMPACTOR) THAT WILL BE
 UTILIZED THAT WILL BE UTILIZED FOR THE SANITATION
 SERVICE.
 2- REVISED DUMPSTER ENCLOSURE DETAIL, SHEET C-912 TO
 REFLECT THE LATEST REVISION OF THE CITY ENCLOSURE. FOR
 A FREESTANDING SITE DUMPSTER ENCLOSURE, THE ENCLOSURE
 SHALL COMPLY WITH THE LATEST REVISION OF CITY OF WEST
 PALM BEACH GENERAL CONSTRUCTION-GARBAGE ENCLOSURE
 STANDARD, GC-7.
 3- AUTOTURN EXHIBIT (DYNAMIC ENVELOPE AND THE TIRES
 PATH) FOR THE SANITATION SERVICE, FRONT LOADER TRUCK
 WITH THE FOLLOWING SPECS:
 - DUAL AXLES
 - TRUCK LENGTH: 35 FT
 - TRUCK WIDTH: 11 FT
 - TURNING RADIUS:
 - SAE TURNING RADIUS: 32.5 FT
 - CURB-TO-CURB DIAMETER: 74 FT
 - WALL-TO-WALL DIAMETER: 86.3 FT
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045
  

Review Stop STORM STORMWATER
Rev No 2 Status P Date 08-18-2021 Cont ID  
Sent By tward Date 08-18-2021 Time 09:16 Rev Time 0.00
Received By tward Date 08-18-2021 Time 09:16 Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status F Date 05-08-2021 Cont ID  
Sent By tward Date 05-08-2021 Time 23:33 Rev Time 0.00
Received By tward Date 05-08-2021 Time 23:33 Sent To  
Notes
2021-05-08 23:33:44THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. PROVIDE STORMWATER QUALITY TREATMENT FOR THE
 REDEVELOPED AREA OF THE SITE PER SFWMD ERP CRITERIA.
  
 2. LABEL THE VERTICAL DATUM AND ADD CONVERSION EQUATION
 TO NGVD1929 ON ALL SHEETS WITH ELEVATION INFORMATION.
  
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3. PROVIDE A COPY OF THE SFWMD ERP PERMIT BEFORE THE
 START OF CONSTRUCTION.
  
 4. DRAINAGE CALCULATIONS WILL BE REVIEWED WITH THE
 ENGINEERING PERMIT APPLICATION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 08-17-2021 Cont ID  
Sent By vnoel Date 08-17-2021 Time 08:49 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2021-08-17 08:52:401. UNITY OF TITLE NOT REQUIRED AS UNITY OF CONTROL
 EXISTS.
 2. UTILITY EASEMENTS WERE GRANTED UNDER THE UNITY OF
 CONTROL.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 05-07-2021 Cont ID  
Sent By vnoel Date 05-07-2021 Time 10:30 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2021-05-07 10:38:221. SURVEY NEEDS SIGNED AND SEALED.
 2. LABEL PROPERTY CORNERS.
 3. SURVEY NEEDS TO BE BASED ON A TITLE SEARCH.
 4. ADD CONVERSION TO NGVD.
 5. UNITY OF TITLE REQUIRED FOR THE 2 PARCELS.
 6. CUSTOMER SERVICE WILL INVESTIGATE EXISTING WATER
 MAIN IN REAR. UTILITY EASEMENT MAY BE REQUIRED OR
 POSSIBLY A MASTER METER.
 7. THERE ARE GRADE DIFFERENTIALS ALONG ADJACENT
 ROADWAYS THAT WILL NEED TO BE ADDRESSED.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 5 Status P Date 06-27-2022 Cont ID  
Sent By   Date 06-27-2022 Time   Rev Time 0.00
Received By   Date 06-27-2022 Time   Sent To  
Notes
2022-06-27 16:23:511) NOT APPLICABLE. PROVIDE TRAFFIC STUDY. THIS ITEM IS
 NECESSARY TO OBTAIN THE TPS LETTER. PLEASE EXPAND THE
 STUDY BY PROVIDING AN INTERSECTION ANALYSIS OF THE
 SOUTHERN/PARKER AND SOUTHERN/LAKE INTERSECTIONS,
 PROVIDE FUTURE CONDITION SCENARIO ASSUMING ROAD
 CONFIGURATION ACCORDING TO FDOT I-95/SOUTHERN BLVD
 INTERCHANGE AND FDOT SOUTHERN BLVD INTERCOASTAL BRIDGE
 PROJECTS, AS THEY MAY IMPACT VEHICULAR MOVEMENTS AT THE
 PROPOSED DEVELOPMENT DRIVEWAYS; ALSO INCLUDE REFERENCES
 TO THE CITY OF WEST PALM BEACH BICYCLE MASTERPLAN.
 PROVIDE AN ANALYSIS OF THE SOUTHERN BLVD DRIVEWAY,
 INCLUSIVE OF A DIAGRAM SHOWCASING EXISTING/FUTURE
 DAILY/PEAK HOUR TURNING VOLUMES. INDEPENDENTLY FROM
 PALM BEACH COUNTY REQUIREMENTS, THE CITY CAN REQUEST
 FURTHER ANALYSIS TO PROPERLY VALIDATE TRAFFIC
 OPERATIONS AND INTERSECTIONS LEVEL OF SERVICE.
 2) SATISFIED. PROVIDE COUNTY TPS LETTER. INDEPENDENTLY
 FROM THE PROPOSED DEVELOPMENT INCREASE/DECREASE OF
 SQUARE FOOTAGE. A TRAFFIC ANALYSIS NEEDS TO BE
 SUBMITTED TO THE COUNTY IN ORDER TO UPDATE THE TRAFFIC
 GENERATORS' DATABASE AND IDENTIFY POTENTIAL IMPACT TO
 THE ROAD SYSTEM.
 3) SATISFIED. EXPLAIN THE CHANGE IN DRIVEWAY
 DIRECTIONALITY ON THE NORTHERN SIDE OF THE PARKING LOT.
 OTHERWISE REVERT TO ORIGINAL CONFIGURATION
 4) SATISFIED. ALIGN PARKING AISLES' CENTERLINES WITH
 THE NORTHERN DRIVEWAY LANE ONES
 5) SATISFIED. ON THE SITE PLAN, PLEASE SHOWCASE BASIC
 CURB DETAILS (I.E. DRIVEWAY AND PARKING STALLS) ON THE
 OPPOSITE SIDE OF THE ROADS SURROUNDING THE PROPOSED
 DEVELOPMENT
 6) SATISFIED. PROVIDE AUTOTURN ANALYSIS FOR GARBAGE
 TRUCK AND SERVICE VEHICLES DRIVING IN AND OUT OF THE
 PROPOSED DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES
 CLEARLY DEFINED. ANALYSIS SHOULD BE PROVIDED IN A
 SEPARATE FILE/DRAWING
 7) SATISFIED. IDENTIFY AND DESIGNATE AN EASILY
 ACCESSIBLE MICRO-MOBILITY STATION AREA (MINIMUM 8 X 20
 FEET) AND PROVIDE BASIC ELECTRIFICATION READINESS
 (CIRCUIT BOX AND ELECTRIC CONDUIT)
 8) SATISFIED. PROVIDE PARKING TABLE SHOWCASING THE
 NUMBER OF REQUIRED AND PROVIDED PARKING SPACES,
 INCLUSIVE OF ADA AND BICYCLE ONES
 9) SATISFIED. CROSSWALK BY ADA STALLS IS MIS-ALIGNED
 WITH THE PARKING ISLE PATHWAY. SHEET C-302 DEPICTS A
 SLANTED CROSSWALK
 10) SATISFIED. PROVIDE OR INDICATE DOCUMENT SHEET
 DEPICTING ROAD, DRIVING ISLE, SIDEWALK AND DRIVEWAY
 DIMENSIONS. SHEET C-302 DOES NOT SHOW ROADWAYS NOR
 DRIVEWAYS DIMENSION
 11) SATISFIED. PROVIDE PARKING STALL DIMENSIONS FOR
 EACH MISSING ELEMENT DEPICTED IN CITY CODE CHAPTER 94
 ARTICLE XV FIGURE XV-2. SPECIFICALLY: (C) STALL DEPTH,
 (E) CURB LENGTH, (F) HALF-BAY, (G) FULL BAY. IF ALREADY
 PROVIDED, PLEASE INDICATE SHEET NUMBER.
 12) SATISFIED. VERIFY THAT SIDEWALK WIDTH ALONG
 NOTTINGHAM BLVD FULFILLS MINIMUM ADA STANDARDS
 REQUIREMENT OF 36 INCHES UN-OBSTRUCTED (I.E. NO LIGHT
 POLES WITHIN SUCH WIDTH
 13) SATISFIED. THE ADOPTED CITY BICYCLE MASTERPLAN
 REQUIRES PROTECTED SEPARATED BICYCLE LANES ALONG
 NOTTINGHAM BLVD. PLEASE REVISE PROPOSED ROADWAY DESIGN
 ALONG SITE FRONTAGE ACCORDINGLY
 14) SATISFIED. PER CITY CODE SEC 94-111(O)3: CURB CUTS,
 PARKING ENTRANCES, EXITS, AND DRIVEWAYS SHALL NOT BE
 WIDER THAN 25 FEET AS MEASURED PARALLEL TO THE STREET
 AT THE CURB. TWO-WAY DRIVEWAY GREATER THAN 25 FEET
 COULD BE PROVIDED ONLY WHEN ABSOLUTELY NECESSARY AND
 JUSTIFIED WITH AUTOTURN, IN WHICH CASE CHANNELIZING
 DIAGONAL HATCHING/CHEVRON MARKINGS SHOULD BE USED TO
 DELINEATE DRIVEWAY LANES FOR PASSENGER CARS.
 15) SATISFIED. AT THE DRIVEWAYS INTERFACE THE SIDEWALK
 OR WALKWAY SHALL BE CONTINUOUS AND REMAIN AT A CONSTANT
 LEVEL AT ALL INSTANCES
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 4 Status F Date 05-16-2022 Cont ID  
Sent By   Date 05-16-2022 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2022-05-16 17:01:041) PARTIALLY SATISFIED. PROVIDE TRAFFIC STUDY. THIS
 ITEM IS NECESSARY TO OBTAIN THE TPS LETTER. PLEASE
 EXPAND THE STUDY BY PROVIDING AN INTERSECTION ANALYSIS
 OF THE SOUTHERN/PARKER AND SOUTHERN/LAKE INTERSECTIONS,
 PROVIDE FUTURE CONDITION SCENARIO ASSUMING ROAD
 CONFIGURATION ACCORDING TO FDOT I-95/SOUTHERN BLVD
 INTERCHANGE AND FDOT SOUTHERN BLVD INTERCOASTAL BRIDGE
 PROJECTS, AS THEY MAY IMPACT VEHICULAR MOVEMENTS AT THE
 PROPOSED DEVELOPMENT DRIVEWAYS; ALSO INCLUDE REFERENCES
 TO THE CITY OF WEST PALM BEACH BICYCLE MASTERPLAN.
 PROVIDE AN ANALYSIS OF THE SOUTHERN BLVD DRIVEWAY,
 INCLUSIVE OF A DIAGRAM SHOWCASING EXISTING/FUTURE
 DAILY/PEAK HOUR TURNING VOLUMES. INDEPENDENTLY FROM
 PALM BEACH COUNTY REQUIREMENTS, THE CITY CAN REQUEST
 FURTHER ANALYSIS TO PROPERLY VALIDATE TRAFFIC
 OPERATIONS AND INTERSECTIONS LEVEL OF SERVICE.
 2) SATISFIED. PROVIDE COUNTY TPS LETTER. INDEPENDENTLY
 FROM THE PROPOSED DEVELOPMENT INCREASE/DECREASE OF
 SQUARE FOOTAGE. A TRAFFIC ANALYSIS NEEDS TO BE
 SUBMITTED TO THE COUNTY IN ORDER TO UPDATE THE TRAFFIC
 GENERATORS' DATABASE AND IDENTIFY POTENTIAL IMPACT TO
 THE ROAD SYSTEM.
 3) SATISFIED. EXPLAIN THE CHANGE IN DRIVEWAY
 DIRECTIONALITY ON THE NORTHERN SIDE OF THE PARKING LOT.
 OTHERWISE REVERT TO ORIGINAL CONFIGURATION
 4) SATISFIED. ALIGN PARKING AISLES' CENTERLINES WITH
 THE NORTHERN DRIVEWAY LANE ONES
 5) SATISFIED. ON THE SITE PLAN, PLEASE SHOWCASE BASIC
 CURB DETAILS (I.E. DRIVEWAY AND PARKING STALLS) ON THE
 OPPOSITE SIDE OF THE ROADS SURROUNDING THE PROPOSED
 DEVELOPMENT
 6) SATISFIED. PROVIDE AUTOTURN ANALYSIS FOR GARBAGE
 TRUCK AND SERVICE VEHICLES DRIVING IN AND OUT OF THE
 PROPOSED DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES
 CLEARLY DEFINED. ANALYSIS SHOULD BE PROVIDED IN A
 SEPARATE FILE/DRAWING
 7) SATISFIED. IDENTIFY AND DESIGNATE AN EASILY
 ACCESSIBLE MICRO-MOBILITY STATION AREA (MINIMUM 8 X 20
 FEET) AND PROVIDE BASIC ELECTRIFICATION READINESS
 (CIRCUIT BOX AND ELECTRIC CONDUIT)
 8) SATISFIED. PROVIDE PARKING TABLE SHOWCASING THE
 NUMBER OF REQUIRED AND PROVIDED PARKING SPACES,
 INCLUSIVE OF ADA AND BICYCLE ONES
 9) SATISFIED. CROSSWALK BY ADA STALLS IS MIS-ALIGNED
 WITH THE PARKING ISLE PATHWAY. SHEET C-302 DEPICTS A
 SLANTED CROSSWALK
 10) SATISFIED. PROVIDE OR INDICATE DOCUMENT SHEET
 DEPICTING ROAD, DRIVING ISLE, SIDEWALK AND DRIVEWAY
 DIMENSIONS. SHEET C-302 DOES NOT SHOW ROADWAYS NOR
 DRIVEWAYS DIMENSION
 11) SATISFIED. PROVIDE PARKING STALL DIMENSIONS FOR
 EACH MISSING ELEMENT DEPICTED IN CITY CODE CHAPTER 94
 ARTICLE XV FIGURE XV-2. SPECIFICALLY: (C) STALL DEPTH,
 (E) CURB LENGTH, (F) HALF-BAY, (G) FULL BAY. IF ALREADY
 PROVIDED, PLEASE INDICATE SHEET NUMBER.
 12) SATISFIED. VERIFY THAT SIDEWALK WIDTH ALONG
 NOTTINGHAM BLVD FULFILLS MINIMUM ADA STANDARDS
 REQUIREMENT OF 36 INCHES UN-OBSTRUCTED (I.E. NO LIGHT
 POLES WITHIN SUCH WIDTH). UNTIL FULL VERIFICATION, THIS
 ITEM WILL BE A KEPT AS A CONDITIONAL APPROVAL
 13) SATISFIED. THE ADOPTED CITY BICYCLE MASTERPLAN
 REQUIRES PROTECTED SEPARATED BICYCLE LANES ALONG
 NOTTINGHAM BLVD. PLEASE REVISE PROPOSED ROADWAY DESIGN
 ALONG SITE FRONTAGE ACCORDINGLY
 14) PER CITY CODE SEC 94-111(O)3: CURB CUTS, PARKING
 ENTRANCES, EXITS, AND DRIVEWAYS SHALL NOT BE WIDER THAN
 25 FEET AS MEASURED PARALLEL TO THE STREET AT THE CURB.
 TWO-WAY DRIVEWAY GREATER THAN 25 FEET COULD BE PROVIDED
 ONLY WHEN ABSOLUTELY NECESSARY AND JUSTIFIED WITH
 AUTOTURN, IN WHICH CASE CHANNELIZING DIAGONAL
 HATCHING/CHEVRON MARKINGS SHOULD BE USED TO DELINEATE
 DRIVEWAY LANES FOR PASSENGER CARS.
 15) AT THE DRIVEWAYS INTERFACE THE SIDEWALK OR WALKWAY
 SHALL BE CONTINUOUS AND REMAIN AT A CONSTANT LEVEL AT
 ALL INSTANCES
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 3 Status F Date 01-28-2022 Cont ID  
Sent By   Date 01-28-2022 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2022-01-28 19:56:52TRAFFIC COMMENTS
 1) PARTIALLY SATISFIED. PROVIDE TRAFFIC STUDY. THIS
 ITEM IS NECESSARY TO OBTAIN THE TPS LETTER. PLEASE
 EXPAND THE STUDY BY PROVIDING AN INTERSECTION ANALYSIS
 OF THE SOUTHERN/PARKER AND SOUTHERN/LAKE INTERSECTIONS,
 PROVIDE FUTURE CONDITION SCENARIO ASSUMING ROAD
 CONFIGURATION ACCORDING TO FDOT I-95/SOUTHERN BLVD
 INTERCHANGE AND FDOT SOUTHERN BLVD INTERCOASTAL BRIDGE
 PROJECTS, AS THEY MAY IMPACT VEHICULAR MOVEMENTS AT THE
 PROPOSED DEVELOPMENT DRIVEWAYS; ALSO INCLUDE REFERENCES
 TO THE CITY OF WEST PALM BEACH BICYCLE MASTERPLAN.
 PROVIDE AN ANALYSIS OF THE SOUTHERN BLVD DRIVEWAY,
 INCLUSIVE OF A DIAGRAM SHOWCASING EXISTING/FUTURE
 DAILY/PEAK HOUR TURNING VOLUMES
 2) SATISFIED. PROVIDE COUNTY TPS LETTER. INDEPENDENTLY
 FROM THE PROPOSED DEVELOPMENT INCREASE/DECREASE OF
 SQUARE FOOTAGE. A TRAFFIC ANALYSIS NEEDS TO BE
 SUBMITTED TO THE COUNTY IN ORDER TO UPDATE THE TRAFFIC
 GENERATORS? DATABASE AND IDENTIFY POTENTIAL IMPACT TO
 THE ROAD SYSTEM.
 3) SATISFIED. EXPLAIN THE CHANGE IN DRIVEWAY
 DIRECTIONALITY ON THE NORTHERN SIDE OF THE PARKING LOT.
 OTHERWISE REVERT TO ORIGINAL CONFIGURATION
 4) SATISFIED. ALIGN PARKING AISLES? CENTERLINES WITH
 THE NORTHERN DRIVEWAY LANE ONES
 5) SATISFIED. ON THE SITE PLAN, PLEASE SHOWCASE BASIC
 CURB DETAILS (I.E. DRIVEWAY AND PARKING STALLS) ON THE
 OPPOSITE SIDE OF THE ROADS SURROUNDING THE PROPOSED
 DEVELOPMENT
 6) SATISFIED. PROVIDE AUTOTURN ANALYSIS FOR GARBAGE
 TRUCK AND SERVICE VEHICLES DRIVING IN AND OUT OF THE
 PROPOSED DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES
 CLEARLY DEFINED. ANALYSIS SHOULD BE PROVIDED IN A
 SEPARATE FILE/DRAWING
 7) SATISFIED. IDENTIFY AND DESIGNATE AN EASILY
 ACCESSIBLE MICRO-MOBILITY STATION AREA (MINIMUM 8 X 20
 FEET) AND PROVIDE BASIC ELECTRIFICATION READINESS
 (CIRCUIT BOX AND ELECTRIC CONDUIT)
 8) SATISFIED. PROVIDE PARKING TABLE SHOWCASING THE
 NUMBER OF REQUIRED AND PROVIDED PARKING SPACES,
 INCLUSIVE OF ADA AND BICYCLE ONES
 9) PARTIALLY SATISFIED. CROSSWALK BY ADA STALLS IS
 MIS-ALIGNED WITH THE PARKING ISLE PATHWAY. SHEET C-302
 DEPICTS A SLANTED CROSSWALK
 10) PARTIALLY SATISFIED. PROVIDE OR INDICATE DOCUMENT
 SHEET DEPICTING ROAD, DRIVING ISLE, SIDEWALK AND
 DRIVEWAY DIMENSIONS. SHEET C-302 DOES NOT SHOW ROADWAYS
 NOR DRIVEWAYS DIMENSION
 11) NOT SATISFIED. PROVIDE PARKING STALL DIMENSIONS FOR
 EACH MISSING ELEMENT DEPICTED IN CITY CODE CHAPTER 94
 ARTICLE XV FIGURE XV-2. SPECIFICALLY: (C) STALL DEPTH,
 (E) CURB LENGTH, (F) HALF-BAY, (G) FULL BAY. IF ALREADY
 PROVIDED, PLEASE INDICATE SHEET NUMBER
 12) NOT SATISFIED. VERIFY THAT SIDEWALK WIDTH ALONG
 NOTTINGHAM BLVD FULFILLS MINIMUM ADA STANDARDS
 REQUIREMENT OF 36 INCHES UN-OBSTRUCTED (I.E. NO LIGHT
 POLES WITHIN SUCH WIDTH)
 13) NOT SATISFIED. THE ADOPTED CITY BICYCLE MASTERPLAN
 REQUIRES PROTECTED SEPARATED BICYCLE LANES ALONG
 NOTTINGHAM BLVD. PLEASE REVISE PROPOSED ROADWAY DESIGN
 ALONG SITE FRONTAGE ACCORDINGLY
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status F Date 08-25-2021 Cont ID  
Sent By   Date 08-25-2021 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2021-08-25 15:43:16TRAFFIC COMMENTS
 1) NOT SATISFIED. PROVIDE TRAFFIC STUDY. THIS ITEM IS
 NECESSARY TO OBTAIN THE TPS LETTER.
 2) NOT SATISFIED. PROVIDE COUNTY TPS LETTER.
 INDEPENDENTLY FROM THE PROPOSED DEVELOPMENT
 INCREASE/DECREASE OF SQUARE FOOTAGE. A TRAFFIC ANALYSIS
 NEEDS TO BE SUBMITTED TO THE COUNTY IN ORDER TO UPDATE
 THE TRAFFIC GENERATORS DATABASE AND IDENTIFY POTENTIAL
 IMPACT TO THE ROAD SYSTEM.
  
 SITE COMMENTS
 3) SATISFIED. EXPLAIN THE CHANGE IN DRIVEWAY
 DIRECTIONALITY ON THE NORTHERN SIDE OF THE PARKING LOT.
 OTHERWISE REVERT TO ORIGINAL CONFIGURATION.
 4) SATISFIED. ALIGN PARKING AISLES? CENTERLINES WITH
 THE NORTHERN DRIVEWAY LANE ONES
 5) SATISFIED. ON THE SITE PLAN, PLEASE SHOWCASE BASIC
 CURB DETAILS (I.E. DRIVEWAY AND PARKING STALLS) ON THE
 OPPOSITE SIDE OF THE ROADS SURROUNDING THE PROPOSED
 DEVELOPMENT
 6) SATISFIED. PROVIDE AUTOTURN ANALYSIS FOR GARBAGE
 TRUCK AND SERVICE VEHICLES DRIVING IN AND OUT OF THE
 PROPOSED DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES
 CLEARLY DEFINED. ANALYSIS SHOULD BE PROVIDED IN A
 SEPARATE FILE/DRAWING
 7) SATISFIED. IDENTIFY AND DESIGNATE AN EASILY
 ACCESSIBLE MICRO-MOBILITY STATION AREA (MINIMUM 8 X 20
 FEET) AND PROVIDE BASIC ELECTRIFICATION READINESS
 (CIRCUIT BOX AND ELECTRIC CONDUIT)
 8) SATISFIED. PROVIDE PARKING TABLE SHOWCASING THE
 NUMBER OF REQUIRED AND PROVIDED PARKING SPACES,
 INCLUSIVE OF ADA AND BICYCLE ONES
 9) NOT SATISFIED. CROSSWALK BY ADA STALLS IS
 MIS-ALIGNED WITH THE PARKING ISLE PATHWAY
 10) NOT SATISFIED. PROVIDE OR INDICATE DOCUMENT SHEET
 DEPICTING ROAD, DRIVING ISLE, SIDEWALK AND DRIVEWAY
 DIMENSIONS.
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 05-07-2021 Cont ID  
Sent By   Date 05-07-2021 Time   Rev Time  
Received By   Date 05-03-2021 Time   Sent To  
Notes
2021-05-07 11:54:55TRAFFIC COMMENTS
 1) PROVIDE TRAFFIC STUDY
 2) PROVIDE COUNTY TPS LETTER
  
 SITE COMMENTS
 1) EXPLAIN THE CHANGE IN DRIVEWAY DIRECTIONALITY ON THE
 NORTHERN SIDE OF THE PARKING LOT. OTHERWISE REVERT TO
 ORIGINAL CONFIGURATION.
 2) ALIGN PARKING AISLES' CENTERLINES WITH THE NORTHERN
 DRIVEWAY LANE ONES
 3) ON THE SITE PLAN, PLEASE SHOWCASE BASIC CURB DETAILS
 (I.E. DRIVEWAY AND PARKING STALLS) ON THE OPPOSITE SIDE
 OF THE ROADS SURROUNDING THE PROPOSED DEVELOPMENT
 4) PROVIDE AUTOTURN ANALYSIS FOR GARBAGE TRUCK AND
 SERVICE VEHICLES DRIVING IN AND OUT OF THE PROPOSED
 DEVELOPMENT WITH VEHICLE DYNAMIC ENVELOPES CLEARLY
 DEFINED. ANALYSIS SHOULD BE PROVIDED IN A SEPARATE
 FILE/DRAWING
 5) IDENTIFY AND DESIGNATE AN EASILY ACCESSIBLE
 MICRO-MOBILITY STATION AREA (MINIMUM 8 X 20 FEET) AND
 PROVIDE BASIC ELECTRIFICATION READINESS (CIRCUIT BOX
 AND ELECTRIC CONDUIT)
 6) PROVIDE PARKING TABLE SHOWCASING THE NUMBER OF
 REQUIRED AND PROVIDED PARKING SPACES, INCLUSIVE OF ADA
 AND BICYCLE ONES
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  
  

Review Stop Z ZONING
Rev No 5 Status P Date 08-17-2022 Cont ID  
Sent By eschneid Date 08-17-2022 Time 18:33 Rev Time 0.00
Received By eschneid Date 07-18-2022 Time 10:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 05-19-2022 Cont ID  
Sent By eschneid Date 05-19-2022 Time 16:25 Rev Time 1.50
Received By eschneid Date 05-19-2022 Time 11:13 Sent To  
Notes
2022-05-19 16:26:36INFORMAL SITE PLAN REVIEW 21-05 - APRIL 20, 2022
 RESUBMITTAL
 PUBLIX @ SOUTHDALE
 804 SOUTHERN BOULEVARD
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446,
 [email protected]
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF THREE
 (3) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THESE COMMENTS (BY JUNE 20, 2022), THE
 PLANNING DIVISION MAY NOTIFY THE APPLICANT THAT THE
 CASE IS CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL
 REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 ADDITIONAL RESUBMITTAL AT NO ADDITIONAL COST. IF
 PREVIOUSLY ISSUED COMMENTS CONTINUE TO NOT BE
 SUFFICIENTLY ADDRESSED, THE APPLICANT WILL BE ASSESSED
 A RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF THE ORIGINAL
 APPLICATION FEE ($200).
  
 1) UPDATED COMMENT: THANK YOU FOR PROVIDING THE GENERAL
 PARKING DIMENSION DETAIL TABLE; HOWEVER, THE STALL
 DEPTH THAT YOU HAVE LISTED FOR 45 ST AT 17.75 IS NOT
 ACTUALLY THE STALL DEPTH IN ACCORDANCE WITH THE MEASURE
 REQUIRED BY STALL PAINTING DETAIL "C", AND AS LISTED
 DOES NOT MEET THE MINIMUM CODE REQUIRED STALL DEPTH.
 WHEN SCALING THE PLAN, THE "C" DEPTH IS CLOSER TO 21
 FEET IN DEPTH (YOUR CAD MEASURE WILL BE ACCURATE). YOU
 DO NOT NEED TO UPDATE THE SITE PLAN DIMENSIONS, BUT YOU
 WILL NEED TO UPDATE THE TABLE TO SHOW THE CORRECT STALL
 DEPTH DIMENSION.
  
 2) UPDATED COMMENT: NOT ALL THE SCREEN WALL LOCATIONS
 ARE SHOWN ON THE LANDSCAPE PLANS - THE PUBLIX COMPACTOR
 SCREEN WALL IS MISSING.
  
 3) STAFF WILL BE ISSUING A REASONABLE ACCOMMODATION FOR
 THE WEST SIDE RAMP AND HANDRAIL. PLEASE PROVIDE REVISED
 ELEVATION DRAWINGS THAT SHOW THE RAMP AND HANDRAIL, TO
 INCLUDE THE HEIGHT OF EACH AT THE HIGHEST POINTS. THE
 REVISED ELEVATION DRAWINGS SHALL INCLUDE ALL UPDATED
 PLAN ELEMENTS BUT DOES NOT NEED TO BE IN COLOR.
  
 4) CONDITION (DRAFT): THE MICRO-MOBILITY STATION AREA
 MUST BE PROVIDED WITH BASIC ELECTRIFICATION READINESS
 CONSISTING OF AN ELECTRICAL PULL BOX (240V CIRCUIT) AND
 2-INCH SCHEDULE 40 PVC ELECTRIC CONDUIT TO THE POWER
 SOURCE. THE ELECTRICAL READINESS MUST BE APPROVED BY
 THE CITY'S TRAFFIC ENGINEER AND INSTALLED PRIOR TO THE
 CERTIFICATE OF OCCUPANCY FOR THE NEW PUBLIX.
  
  

Review Stop Z ZONING
Rev No 3 Status F Date 02-07-2022 Cont ID  
Sent By eschneid Date 02-07-2022 Time 09:57 Rev Time 2.00
Received By eschneid Date 02-04-2022 Time 14:54 Sent To  
Notes
2022-02-07 09:56:39INFORMAL SITE PLAN REVIEW 21-05 - DECEMBER 14, 2021
 RESUBMITTAL
 PUBLIX @ SOUTHDALE
 804 SOUTHERN BOULEVARD
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446,
 [email protected]
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF THREE
 (3) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THESE COMMENTS (BY APRIL 7, 2021), THE
 PLANNING DIVISION MAY NOTIFY THE APPLICANT THAT THE
 CASE IS CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL
 REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 ADDITIONAL RESUBMITTAL AT NO ADDITIONAL COST. IF
 PREVIOUSLY ISSUED COMMENTS CONTINUE TO NOT BE
 SUFFICIENTLY ADDRESSED, THE APPLICANT WILL BE ASSESSED
 A RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF THE ORIGINAL
 APPLICATION FEE ($200).
  
 1) UPDATED COMMENT: PROVIDE THE COMCAST, AND WEST PALM
 BEACH UTILITY LETTER APPROVALS.
  
 2) UPDATED COMMENT: PARKING DETAILS ARE REQUIRED FOR
 ALL CONDITIONS. NO PARKING DETAILS WERE PROVIDED.
 PLEASE NOTE THAT THE WHEEL STOPS SHOWN ADJACENT TO THE
 BUILDING DO NOT MEET THE CODE REQUIRED TWO FEET FROM
 THE END OF THE PARKING SPACE.
  
 3) REPEAT COMMENT: THE ZONING AND LAND DEVELOPMENT
 REQUIREMENTS REQUIRE THAT PARKING LOT LANDSCAPE ISLANDS
 BE THE FULL LENGTH OF THE PARKING SPACE. THE PLANS DO
 NOT COMPLY WITH THIS REQUIREMENT. YOU MUST EITHER
 LENGTHEN THE LANDSCAPE ISLANDS OR STRIPE THE SPACES TO
 NOT EXCEED THE ISLAND LENGTH. NOTE: THE ISLANDS SCALE
 TO THE MEET THE MINIMUM PARKING STALL LENGTH, SO THE
 ISLANDS CAN STAY THE LENGTH AS SHOWN IF THE STALL
 LENGTH IS REDUCED.
  
 4) UPDATED COMMENT: NOT ALL THE SCREEN WALL LOCATIONS
 ARE SHOWN ON THE CIVIL AND LANDSCAPE PLANS. THE CITY
 DOES NOT PERMIT CHAIN LINK FENCES TO SCREEN GENERATORS,
 WHICH IS WHAT IS CALLED OUT ON THE ELEVATION PLAN.
  
 5) THE BICYCLE RACK AT THE BANK NEEDS TO HAVE 24 INCHES
 ON EACH SIDE OF THE RACK, NOT 24 INCHES OF WIDTH.
  
 6) UPDATED COMMENT: THANK YOU FOR PROVIDING THE
 COMPACTOR SCREENING DETAILS ON THE ELEVATION PLANS;
 HOWEVER, THE ENCLOSURE IS NOT SHOWN ON THE SITE PLAN AS
 REQUIRED.
  
 7) UPDATED COMMENT: THANK YOU FOR PROVIDING THE
 LOCATION OF THE LIGHTING IN THE PARKING LOT. THERE ARE
 SEVERAL POLES LOCATED WITHIN THE PARKING FIELD BETWEEN
 PARKING SPACES. PROVIDE DETAILS THAT INCLUDE THE
 DIMENSION OF THE POLE AND ANY BOLLARDS OR OTHER
 PROTECTIVE DEVICES OVERLAID ON A TO SCALE PARKING STALL
 LAYOUT SO THAT STAFF CAN VERIFY THAT THE PROPOSED
 LAYOUT STILL PERMITS THE PARKING SPACES TO MEET CODE
 REQUIREMENTS.
  
 8) IN AN EMAIL TO LENS LUBIN, DATED SEPTEMBER 9, 2021,
 IN WHICH STAFF MADE AN IN-PROGRESS REVIEW OF THE PLANS,
 STAFF PROVIDED THE ADDITIONAL COMMENT BELOW, WHICH WAS
 NOT ADDRESSED AS PART OF THIS RESUBMITTAL:
  
 THE COLOR ELEVATIONS DO NOT SHOW THE PROPOSED RAMP
 ALONG THE WEST SIDE OF THE BUILDING. THE HEIGHT OF THE
 TOP OF THE RAIL MUST BE PROVIDED. PLEASE NOTE THAT THIS
 RAMP ENCROACHES INTO THE REQUIRED SETBACK AND LANDSCAPE
 BUFFER AND UNLESS IT IS SPECIFICALLY THERE TO MEET ADA
 REQUIREMENTS IT IS NOT PERMITTED. IF IT IS FOR ADA
 PURPOSES AND THE PURPOSED CANNOT BE ACHIEVED BY ANOTHER
 METHOD, YOU MUST SUBMIT A LETTER WITH YOUR RESUBMITTAL
 REQUESTING A REASONABLE ACCOMMODATION DETERMINATION
 BASED ON THE RAMP BEING INSTALLED TO MEET ADA
 PROVISIONS (PLEASE INCLUDE THE ADA CODE CITATION MET)
 AND THEN THE CITY WILL GRANT THE REASONABLE
 ACCOMMODATION TO WAIVE THE REQUIREMENT TO COMPLY WITH
 THE SETBACK AND LANDSCAPE BUFFER ENCROACHMENT. NOTE:
 THE TOP OF THE RAIL FROM GRADE MAY NOT EXCEED 6 FEET OR
 IT ALSO FALLS UNDER THE REASONABLE ACCOMMODATION
 WAIVER.
  
 9) CONDITION (DRAFT): THE MICRO-MOBILITY STATION AREA
 MUST BE PROVIDED WITH BASIC ELECTRIFICATION READINESS
 CONSISTING OF AN ELECTRICAL PULL BOX (240V CIRCUIT) AND
 2-INCH SCHEDULE 40 PVC ELECTRIC CONDUIT TO THE POWER
 SOURCE. THE ELECTRICAL READINESS MUST BE APPROVED BY
 THE CITY'S TRAFFIC ENGINEER AND INSTALLED PRIOR TO THE
 CERTIFICATE OF OCCUPANCY FOR THE NEW PUBLIX.
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 08-16-2021 Cont ID  
Sent By eschneid Date 08-16-2021 Time 14:10 Rev Time 2.00
Received By eschneid Date 08-16-2021 Time 10:06 Sent To  
Notes
2021-08-16 14:11:01INFORMAL SITE PLAN REVIEW 21-05 - JULY 20, 2021
 RESUBMITTAL
 PUBLIX @ SOUTHDALE
 804 SOUTHERN BOULEVARD
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446,
 [email protected]
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF THREE
 (3) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THESE COMMENTS (BY OCTOBER 16, 2021),
 THE PLANNING DIVISION MAY NOTIFY THE APPLICANT THAT THE
 CASE IS CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL
 REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 ADDITIONAL RESUBMITTAL AT NO ADDITIONAL COST. IF
 PREVIOUSLY ISSUED COMMENTS CONTINUE TO NOT BE
 SUFFICIENTLY ADDRESSED, THE APPLICANT WILL BE ASSESSED
 A RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF THE ORIGINAL
 APPLICATION FEE ($200).
  
 1) REPEAT COMMENT: PROVIDE A TRAFFIC IMPACT STATEMENT
 VERIFYING THAT THE NEW DEVELOPMENT DOES NOT INCREASE
 VEHICLE TRIPS. IF THE TRAFFIC IMPACT STATEMENT SHOWS
 THAT THERE IS AN INCREASE IN TRAFFIC TRIPS, THEN YOU
 MUST PROVIDE A TPS APPROVAL LETTER FROM PALM BEACH
 COUNTY. **** THE COMMENT RESPONSE STATES THAT A
 CERTIFIED TRAFFIC ENGINEER STATED THAT A TRAFFIC STUDY
 WAS IS NOT NEEDED. YOU NEED TO SUBMIT
  
 2) UPDATED COMMENT: PROVIDE THE FPL, FPU, COMCAST, AND
 WEST PALM BEACH UTILITY LETTER APPROVALS.
  
 3) BASED ON THE ENTIRE SITE BEING ONE PARCEL, YOU MUST
 USE THE TOTAL SITE ACREAGE IN YOUR SITE DATA
 CALCULATIONS ON THE CIVIL AND LANDSCAPE PLANS - 380,133
 SF (8.727 ACRES). NOTE: THE LANDSCAPE PLANS MUST REMOVE
 THE ERRONEOUS REFERENCE TO THE PROPERTY LINE.
  
 4) THE PLANS SHOW THAT THE PARKING LOT IS BEING MILLED
 AND RESURFACED. IN ACCORDANCE WITH THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, THIS REQUIRES THE PARKING LOT,
 INCLUDING THE PERIMETER LANDSCAPE BUFFERS, TO BE
 BROUGHT INTO CONFORMANCE WITH THE CURRENT LANDSCAPE
 REQUIREMENTS. PROVIDE THE DIMENSIONS FOR THE PERIMETER
 LANDSCAPE BUFFERS AROUND THE ENTIRE SITE. THESE BUFFERS
 MUST BE AT LEAST FIVE (5) FEET IN WIDTH AND CONTAIN THE
 REQUIRED LANDSCAPE MATERIAL. **** THIS WAS NOT
 PROVIDED. SEE LANDSCAPE REVIEW COMMENTS FOR MORE
 INFORMATION.
  
 5) A ROUGH CALCULATION OF THE NEW CONSTRUCTION VALUE
 BASED ON THE INTERNATIONAL CODE COUNCIL (ICC), BUILDING
 VALUATION DATA (BVD) TABLE SHOWS THAT THE NEW
 CONSTRUCTION WILL EXCEED 50% OF THE VALUE OF THE
 EXISTING STRUCTURE. IN ACCORDANCE WITH THE ZONING AND
 LAND DEVELOPMENT REGULATIONS, THE ENTIRE SITE NEEDS BE
 BROUGHT INTO CONFORMANCE WITH THE LANDSCAPE
 REQUIREMENTS, INCLUDING FOUNDATION PLANTING AND,
 MINIMUM SITE LANDSCAPE PERCENTAGE. **** THIS WAS NOT
 PROVIDED. SEE LANDSCAPE REVIEW COMMENTS FOR MORE
 INFORMATION.
  
  
 6) UPDATED COMMENT: PLEASE VERIFY THAT ALL PARKING ROWS
 ARE PROVIDING A 45-DEGREE ANGLE. THIS IS NOT SHOWN ON
 EACH ROW AT THE MAIN PARKING FIELD NOR FOR THE PARKING
 ON THE EAST SIDE OF THE BUILDING. PARKING DETAILS ARE
 REQUIRED FOR ALL CONDITIONS.
  
 7) THE DIMENSION LINE ON THE PLAN FOR THE STALL DEPTHS
 IS NOT USING THE CORRECT MEASURE POINTS. STAFF IS
 UNABLE TO VERIFY THAT THE STALL DEPTHS COMPLY WITH THE
 ZONING AND LAND DEVELOPMENT REQUIREMENTS.
  
 8) THE ZONING AND LAND DEVELOPMENT REQUIREMENTS REQUIRE
 THAT PARKING LOT LANDSCAPE ISLANDS BE THE FULL LENGTH
 OF THE PARKING SPACE. THE PLANS DO NOT COMPLY WITH THIS
 REQUIREMENT.
  
 9) REPEAT COMMENT: THE SITE PLAN DOES NOT CLEARLY SHOW
 WHERE THE STOREFRONT BOLLARDS AND GUARD RAILS ARE
 LOCATED. **** THESE NEED TO BE LABELED ON THE SITE
 PLAN.
  
 10) THANK YOU FOR SHOWING THE SCREEN WALLS FOR THE
 COMPACTOR AND THE GENERATOR ON THE ELEVATION DRAWINGS.
 PLEASE PROVIDE THE HEIGHT DIMENSIONS ON THE ELEVATIONS
 AND THE SCREEN WALL LOCATIONS ON THE CIVIL AND
 LANDSCAPE PLANS.
  
 11) PROVIDE DIMENSIONS OF THE NEW DUMPSTER ENCLOSURES
 ON THE PLANS.
  
 12) ALL THE COLUMNS FOR THE BUILDING OVERHANG NEED TO
 BE REFLECTED ON THE CIVIL PLAN AS THE COLUMN LOCATIONS
 IMPACT BOTH CAR AND BICYCLE PARKING.
  
 13) THANK YOU FOR SHOWING BICYCLE RACKS ALONG THE FRONT
 OF THE BUILDING.
  
 A. THE PLANS MUST CLEARLY SHOW THE REQUIRED PAD DEPTH
 OF SIX (6) FEET AND 24 INCHES ON EITHER SIDE OF THE
 RACK (30 INCHES IS RACKS ARE IMMEDIATELY ADJACENT TO
 EACH OTHER INSTEAD OF SPREAD OUT).
  
 B. HOW WILL THE CARS PARKING IN FRONT OF THE BUILDING
 BE PREVENTED FROM OVERHANGING THE CURB (EX. WILL WHEEL
 STOPS BE PROVIDED)? THE CURRENT PLANS SHOW THAT AN
 OVERHANG IS POSSIBLE; HOWEVER, THIS OVERHANG DIRECTLY
 CONFLICTS WITH ANY BICYCLES THAT ARE PARKED IN THE
 BICYCLE RACKS AS SHOWN.
  
 C. IN ORDER TO PROVIDE WEATHER PROTECTION FOR PARKED
 BICYCLES, THE RACKS SHOULD BE MOVED UNDER THE ROOF
 OVERHANG.
  
 D. THE PUBLIX IS THE ANCHOR OF THIS SHOPPING PLAZA AND
 AS SUCH NEEDS TO HAVE A SOME OF THE BICYCLE RACKS
 CLOSER TO THE ENTRANCE, BOTH FOR CUSTOMERS AND
 EMPLOYEES.
  
 14) PLEASE DESCRIBE THE MICRO-MOBILITY STATION THAT IS
 NOW SHOWN ON THE PLANS.
  
 15) PROVIDE THE DETAILS OF THE COMPACTOR SCREENING. IT
 IS NOT PERMITTED TO SIT ON A PAD UNSCREENED AS SHOWN IN
 PERSPECTIVE #2.
  
 16) REPEAT COMMENT: THERE SEEMS TO BE A DISCREPANCY
 BETWEEN THE PERSPECTIVE DRAWINGS AND THE COLOR
 ELEVATIONS ON THE REAR PARAPET WALL. THE PERSPECTIVES
 CLEARLY SHOW A PARAPET THAT WILL HIDE THE ROOFTOP
 EQUIPMENT; HOWEVER, THE ELEVATIONS DO NOT SHOW A REAR
 PARAPET. **** THE PERSPECTIVE DRAWINGS CLEARLY SHOW THE
 SIDE AND REAR PARAPET WALLS AT THE SAME HEIGHT. THE
 REAR OF THE SIDE PARAPET WALLS IS VISIBLE AND EXTENDING
 HIGHER THAN WHAT IS SHOWN AS THE HIGH POINT OF THE REAR
 OF THE BUILDING. THE REAR PARAPET NEEDS TO BE
 ACCURATELY DEPICTED SO STAFF CAN BE CONFIDENT THAT THE
 ROOFTOP MECHANICAL EQUIPMENT WILL BE SCREENED (AS SHOWN
 ON THE PERSPECTIVE DRAWINGS). PROVIDE THE HEIGHT TO THE
 ROOF AND THE TOP OF THE REAR PARAPET ON THE ELEVATIONS
 (COLOR ELEVATIONS ARE NOT REQUIRED).
  
 17) IS NEW LIGHTING BEING PROPOSED ON THE SITE?
 LIGHTING NEEDS TO BE CLEARLY SHOWN ON THE CIVIL AND
 LANDSCAPE PLANS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 05-13-2021 Cont ID  
Sent By eschneid Date 05-13-2021 Time 11:53 Rev Time 2.00
Received By eschneid Date 05-13-2021 Time 11:53 Sent To  
Notes
2021-05-13 11:53:36INFORMAL SITE PLAN REVIEW 21-05
 PUBLIX @ SOUTHDALE
 804 SOUTHERN BOULEVARD
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446,
 [email protected]
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FOUR
 (4) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THESE COMMENTS/THE PPRC MEETING (BY
 JULY 13, 2021), THE PLANNING DIVISION MAY NOTIFY THE
 APPLICANT THAT THE CASE IS CONSIDERED WITHDRAWN. ANY
 FURTHER ACTION SHALL REQUIRE A NEW DEVELOPMENT
 APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($200).
  
 1) PROVIDE A TRAFFIC IMPACT STATEMENT VERIFYING THAT
 THE NEW DEVELOPMENT DOES NOT INCREASE VEHICLE TRIPS. IF
 THE TRAFFIC IMPACT STATEMENT SHOWS THAT THERE IS AN
 INCREASE IN TRAFFIC TRIPS, THEN YOU MUST PROVIDE A TPS
 APPROVAL LETTER FROM PALM BEACH COUNTY.
  
 2) PROVIDE A PREDETERMINATION LETTER FROM FDOT
 APPROVING THE MODIFICATION TO THE INGRESS/EGRESS
 (REVERSAL) FROM SOUTHERN BOULEVARD AND THAT ACCESS WILL
 CONTINUE TO MEET THEIR STANDARDS WITH THE
 REDEVELOPMENT. THIS LETTER IS FROM FDOT ACCESS
 MANAGEMENT.
  
 3) PROVIDE WRITTEN VERIFICATION FROM FDOT INTERCHANGE
 DIVISION (HUMBERTO ARRIETA) THAT YOUR PROPOSAL WILL NOT
 IMPACT OR BE IMPACTED BY (EX: RIGHT-OF-WAY WIDENING)
 THE SOUTHERN BOULEVARD I-95 INTERCHANGE PROJECT. THIS
 IS DIFFERENT FROM THE LETTER IN #2 ABOVE.
  
 4) PROVIDE AN ALTA SURVEY. A SKETCH OF BOUNDARY SURVEY
 DOES NOT MEET CITY APPLICATION REQUIREMENTS.
  
 5) PROVIDE THE FPL, FPU, COMCAST, AT&T AND WEST PALM
 BEACH UTILITY LETTER APPROVALS.
  
 6) THE CITY HAS NO RECORD OF APPROVING A LOT SPLIT OR
 MINOR SUBDIVISION TO CREATE THE PARCEL ON WHICH WELLS
 FARGO EXISTS. A UNITY OF TITLE IS REQUIRED TO REJOIN
 THIS NOT LEGALLY SUBDIVIDED PARCEL WITH THE PARENT
 PARCEL.
  
 7) THE PLANS SHOW THAT THE PARKING LOT IS BEING MILLED
 AND RESURFACED. IN ACCORDANCE WITH THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, THIS REQUIRES THE PARKING LOT,
 INCLUDING THE PERIMETER LANDSCAPE BUFFERS, TO BE
 BROUGHT INTO CONFORMANCE WITH THE CURRENT LANDSCAPE
 REQUIREMENTS. PROVIDE THE DIMENSIONS FOR THE PERIMETER
 LANDSCAPE BUFFERS AROUND THE ENTIRE SITE. THESE BUFFERS
 MUST BE AT LEAST FIVE (5) FEET IN WIDTH AND CONTAIN THE
 REQUIRED LANDSCAPE MATERIAL.
  
 8) A ROUGH CALCULATION OF THE NEW CONSTRUCTION VALUE
 BASED ON THE INTERNATIONAL CODE COUNCIL (ICC), BUILDING
 VALUATION DATA (BVD) TABLE SHOWS THAT THE NEW
 CONSTRUCTION WILL EXCEED 50% OF THE VALUE OF THE
 EXISTING STRUCTURE. IN ACCORDANCE WITH THE ZONING AND
 LAND DEVELOPMENT REGULATIONS, THE ENTIRE SITE NEEDS BE
 BROUGHT INTO CONFORMANCE WITH THE LANDSCAPE
 REQUIREMENTS, INCLUDING FOUNDATION PLANTING AND,
 MINIMUM SITE LANDSCAPE PERCENTAGE.
  
 9) THE SITE DATA TABLE LISTS THE PROVIDED FAR AS 25.38,
 WHICH IS NOT CORRECT.
  
 10) THE PARKING DETAIL ON SHEET C-901 SHOWS A 60-DEGREE
 PARKING ANGLE, WHICH REQUIRES AN 18-FOOT PARKING AISLE
 WIDTH AND A 19 FOOT 10 INCH STALL DEPTH, NEITHER OF
 WHICH ARE SHOWN MEETING CODE ON THE SITE LAYOUT PLAN.
 NOTE: THE GENERIC PARKING LOT DESIGN ON C-902 DOES NOT
 MATCH THE SITE PLAN AND NEEDS TO BE REMOVED OR SHOW
 CORRECT CONDITIONS. STAFF CANNOT VERIFY PARKING
 COMPLIANCE WITHOUT THE ACCURATE DATA.
  
 11) THE CITY DOES NOT PERMIT DEAD END PARKING ROWS.
 BOTH PARKING AREAS AT THE REAR OF THE BUILDING NEED TO
 HAVE A TURNAROUND SPACE.
  
 12) THE SITE PLAN DOES NOT CLEARLY SHOW WHERE THE
 STOREFRONT BOLLARDS AND GUARD RAILS ARE LOCATED.
  
 13) THERE ARE 20, NOT 18 ADA SPACES ON THE SITE. THE
 DATA TABLE NEEDS TO LIST THE CORRECT VALUE.
  
 14) THE PLANS NEED TO SHOW DIMENSIONAL COMPLIANCE WITH
 THE CITY'S LOADING SPACE REQUIREMENTS.
  
 15) PROVIDE DETAILS ON THE SCREENING OF THE STANDBY AND
 EMERGENCY GENERATORS THAT MEET CITY REQUIREMENTS.
  
 16) THE SITE REQUIRES 19 BICYCLE PARKING SPACES. THESE
 NEED TO BE SHOWN ON THE PLAN AND DISTRIBUTED THROUGHOUT
 THE SITE. PROVIDE THE DETAILS THAT COMPLY WITH CITY
 CODE.
  
 17) PROVIDE THE DETAILS OF THE COMPACTOR SCREENING. IT
 IS NOT PERMITTED TO SIT ON A PAD UNSCREENED AS SHOWN IN
 PERSPECTIVE #2.
  
 18) THERE SEEMS TO BE A DISCREPANCY BETWEEN THE
 PERSPECTIVE DRAWINGS AND THE COLOR ELEVATIONS ON THE
 REAR PARAPET WALL. THE PERSPECTIVES CLEARLY SHOW A
 PARAPET THAT WILL HIDE THE ROOFTOP EQUIPMENT; HOWEVER,
 THE ELEVATIONS DO NOT SHOW A REAR PARAPET.
  
  
  

  Print